Mitsubishi SRK10CRV-S1, SRK10CRS-S1, SRK13CRV-S, SRK10CRS-S, SRK10CRS-S2 Technical Manual & Parts List

...
Page 1
RESIDENTIAL AIR-CONDITIONING
TECHNICAL MANUAL & PARTS LIST
WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS (Split system, air cooled cooling only type)
SRK10CRV-S, S1 SRK13CRV-S, S1 SRK10CRS-S, S1, S2, S3, S4, S5, S6 SRK13CRS-S, S1, S2, S3, S4, S5, S6
Page 2
Page 3
TECHNICAL MANUAL
Page 4
gs32+4
CONTENTS
1. SPECIFICATIONS .................................................................................... 4
(2) Outdoor units .................................................................................... 23
(3) Wireless remote control
.................................................................... 24
........................................................................ 22
(1) Indoor units ......................................................................................... 22
2. EXTERIOR DIMENSIONS
3. ELECTRICAL WIRING ............................................................................. 25
(1) Indoor units ......................................................................................... 25
(2) Outdoor units ...................................................................................... 27
....................................................... 31
6. RANGE OF USAGE & LIMITATIONS
5. PIPING SYSTEM ..................................................................................... 30
4. NOISE LEVEL .......................................................................................... 28
............................................................................... 35
8. APPLICATION DATA
............................................................................... 33
7. CAPACITY TABLES
9. OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ........... 45
(6) 3D auto operation

4IMEROPERATION
................................................................................. 50
(5) Flap and louver control ..................................................................... 48
...................................................... 47(4) Custom cord switching procedure
........................................................................ 47(3) Auto restart function
(2) Unit ON/OFF button
.......................................................................... 47
(1) Operation control function by remote control ..................................... 45
(8) Installation location setting ................................................................. 50
(10) Outline of automatic operation .......................................................... 51
/UTLINEOFCOOLINGOPERATION .............................................................. 51
(11) Protective control function
.................................................................. 52
.............................................................................. 53
.................... 54
4ROUBLESHOOTINGPROCEDURE)FTHEAIRCONDITIONERRUNS
4ROUBLESHOOTINGPROCEDURE
)FTHEAIRCONDITIONERDOESNOTRUNATALL
....... 53
(1) Cautions
............................................................................................ 53
(2) Items to check before troubleshooting ................................................ 53
3ELFDIAGNOSISTABLE ............................................................................ 54
(6) Inspection procedures corresponding to detail of trouble ................... 55
10. MAINTENANCE DATA
Page 5
gs32+4
(OWTOMAKESUREOFWIRELESSREMOTECONTROL ..................................... 57

0HENOMENONOBSERVEDAFTERSHORTCIRCUITWIREBREAKAGEONSENSOR
........ 56
#HECKINGTHEINDOORELECTRICALEQUIPMENT
.......................................... 56
How to read the model name
Example: SRK 10 C
Series code
Cooling only type
Product capacity
Model name SRK : Wall mounted type
SRC : Outdoor unit
RV-S
Page 6
Page 7
Page 8
Page 9
Page 10
Page 11
Page 12
Page 13
Page 14
Page 15
Page 16
Page 17
Page 18
Page 19
Page 20
Page 21
Page 22
Page 23
Page 24
Unit:mm
Wireless remote control
Note(1)The model name label is attached
    on the underside of the panel.
60
150
17.3
788
2760
45
60
45
790
268
17.5
Outlet for down piping
Refer to the above view
200 39.3
43.244.5
102.5 585 102.5
206.5 450 133.5
138 450 202
44.5
7.5252.28.3
Service space
65
Service space
15
50
Service space
100
Service space
53.5
380.6
448.6 520
Space for installation and service when viewing from the front
D A
B
E
C
53.5
Installation plate
Unit
Hole on wall for right rear piping
Hole on wall for left rear piping
Gas piping
Outlet for wiring
Drain hose
Liquid piping
F
ECD
B
Symbol
A
φ65
VP16
φ6.35(14")(Flare
Content
φ65
φ9.5238")(Flare
Outlet for piping(on both side)
G
φ12.7(12")(Flare
Model 10
Model 13
3224
45
609
G
Terminal block
F
Page 25
φ9.52(38")(Flare
Content
C Pipecable draw-out hole D E Anchor bolt hole
Drain discharge hole
Symbol
B
A Service valve connection(gas side)
M10×4places
φ20×2places
Service valve connection(liquid side)
φ6.35(14")(Flare
63.4
390.6
390.6
69.4
111.6 510 158.4
780 61.9
17.9
14.8 312.5 24.3
351.6
50.6
12
Terminal block
97.7 42.5
40°
40°
138.4 33.5
15.8
290
A
C
B
D
E
540
2-16x12
Unit:mm
φ12.7(12")(Flare
Content
C Pipecable draw-out hole
E Anchor bolt hole
Drain discharge hole
Symbol
B
A Service valve connection(gas side)
M10×4places
φ20×2places
Service valve connection(liquid side)
φ6.35(14")(Flare
63.4
390.6
390.6
69.4
111.6 510 158.4
780 61.9
17.9
14.8 312.5 24.3
351.6
50.6
12
Terminal block
97.7 42.5
40°
40°
138.4 33.5
15.8
290
A
C
B
E
595
D
D
2-16x12
Unit:mm
Page 26
Unit: mm
60
17.3
150
Unit: mm
60
17.3
150
Unit: mm
17.3
150
Unit: mm
17.3
150
Page 27
U
MFM
BK
Color symbol
BL
BR
LB
YE
RD
YG
WH
Red
YellowGreen
White
Black
Blue
Brown
Light blue
Yellow
Symbol
Meaning of Marks
Parts name Symbol Parts name
Capacitor forCF
I
FMIFM
ZNR
FM
I
Fuse
Fan motor
Flap motor
Varistor
Th2
T
Room temp. thermistor
Heat exchanger thermistor
Terminal block
F
Th1
Power source
220230240V 50Hz
YG
LB
BR
Printed circuit board
T
YG
BL
BR
WH
BK
TO
OUTDOOR
UNIT
Th1
Th2
Wireless
R-Amp
Display
CNE
CNG
YEWHRD
M
CNW
IC15
ZNR
153
CNU
CF
I
52C-4 52C-3
52C
F
250V 3.15A
CONTROL BOX
1
2
Back up Sw
CNM
N
t°
1
FM
I
t°
Page 28
U
M
M
M
LM
LM
FM
BK
Color symbol
BL
BR
LB
YE
RD
YG
WH
Red
YellowGreen
White
Black
Blue
Brown
Light blue
Yellow
Symbol
Meaning of Marks
Parts name Symbol Parts name
Capacitor forCF
I
FMIFM
ZNR
FM
I
Fuse
Fan motor
Flap motor
Varistor
Louver motorRIGHTLM
Th2
T
Room temp. thermistor
Heat exchanger thermistor
Terminal block
F Th1
Power source
220230240V 50Hz
YG
LB
BR
Printed circuit board
T
YG
BL
BR
WH
BK
TO
OUTDOOR
UNIT
Th1
Th2
Wireless
R-Amp
Display
CNE
CNG
YEWHRD
M
CNW
CNY
IC15
ZNR
153
CNU
CF
I
52C-4 52C-3
52C
F
250V 3.15A
CONTROL BOX
1
2
Back up Sw
CNX
CNM
N
R
Louver motorLEFTLM
L
t°
1
R
L
FM
I
t°
Page 29
RUNNINGCAPACITORFORCOMPRESSOR RUNNINGCAPACITORFORFANMOTOR
CFo
Cc
FANMOTOR
COMPRESSORMOTOR
FMo
CM
DESCRIPTION
ITEM
TERMINALBLOCKINDOORUNITT1 TERMINALBLOCKOUTDOORUNITT2
MOTORPROTECTOR51C
R
C
CM
S
51C
3
1
2
BLACK
BLACK
RED
BLACK
WHITE
2/N
1
T1
Powersource 220-240V50Hz
RUNNINGCAPACITORFORCOMPRESSOR RUNNINGCAPACITORFORFANMOTOR
CFo
Cc
FANMOTOR
COMPRESSORMOTOR
FMo
CM
DESCRIPTION
ITEM
TERMINALBLOCKINDOORUNITT1 TERMINALBLOCKOUTDOORUNITT2
2/N
1
T1
Powersource 220-240V50Hz
R
C
S
WHITE
CM
BLACK
RED
Page 30
Mike position as below
0.8m
1m
Unit
Mike position (Center & Low points)
10
20
30
40
50
60
70
Sound Pressure Level (dB)
(Standard 2×10
-5
P a )
Mid Octave Band Frequency (Hz)
63 125 250 500 1000 2000 4000 8000
10
20
30
40
50
60
70
N70
N60
N50
N40
N30
N20
Mike position: at highest noise level in position as mentined below
Distance from front side 1m
Mike position as below
0.8m
1m
Unit
Mike position (Center & Low points)
10
20
30
40
50
60
70
Sound Pressure Level (dB)
(Standard 2×10
-5
P a )
Mid Octave Band Frequency (Hz)
63 125 250 500 1000 2000 4000 8000
10
20
30
40
50
60
70
N70
N60
N50
N40
N30
N20
Page 31
Mike position as below
0.8m
1m
Unit
Mike position (Center & Low points)
10
20
30
40
50
60
70
Sound Pressure Level (dB)
(Standard 2×10
-5
P a )
Mid Octave Band Frequency (Hz)
63 125 250 500 1000 2000 4000 8000
10
20
30
40
50
60
70
N70
N60
N50
N40
N30
N20
10
20
30
40
50
60
70
Sound Pressure Level (dB)
(Standard 2×10
-5
P a )
Mid Octave Band Frequency (Hz)
63 125 250 500 1000 2000 4000 8000
10
20
30
40
50
60
70
N70
N60
N50
N40
N30
N20
Mike position: at highest noise level in position as mentined below
Distance from front side 1m
Mike position as below
0.8m
1m
Unit
Mike position (Center & Low points)
Page 32
Outdoor unitIndoor unit
Room temp. sensor
Heat exchanger
Flare connecting
Heat exchanger sensor
Liquid pipe ø6.35
Check joint
Service valve (Liquid)
Flare connecting
Heat exchanger
Compressor
Capillary tube
Accumulator
Service valve
Cooling cycle
(Gas)
Capillary tube
10 : ø9.52
Gas pipe
13 : ø12.7
( )
Page 33
Net capacity = Capacity shown on specification Correction factors as follows.
(1) Coefficient of cooling capacity in relation to temperatures
All models
Models
Item
Indoor return air temperature (
Upper, lower limits
)
Outdoor air temperature (
Upper, lower limits
)
Refer to the selection chart
Refrigerant line (one way) length
Max. 15m
Max. 10m (Outdoor unit is higher
)
Max. 10m (Outdoor unit is lower
)
Min. 3 minutes
Max. 10 times/h
Min. 85% of rating
Vertical height difference between outdoor unit and indoor unit
Power source voltage
Voltage at starting
Frequency of ON−OFF cycle
ON and OFF interval
Rating 10%
14 16 18 20 22
15
20
25
30
35
40
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
43
24
ISO-T1 Standard ConditionIndoor air W.B. temperature °C W.B.
Cooling
Applicable range
Coefficient of cooling
capacity in relation
to temperature
Cooling operation
Outdoor air D.B.
temperature
°C D.B.
Page 34
(2) Correction of cooling capacity in relation to one way length of refrigerant piping
How to obtain the cooling capacity
=
Piping length [m]
Cooling
7
1.0
10
0.99 0.975
15
3600
SRK13CRV-S
SRK13CRV-S
3510
Page 35
Cooling Mode
(220-240V)
Capacity 2.700 kW
Wind Hi
Air flow 10 (m
3
/min)
Cooling Mode
(220V)
Capacity 2.700 kW
Wind Hi
Air flow 10 (m
3
/min)
TC : Total cooling capacity (kW) SHC : Sensible heat capacity (kW)
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 3.04 2.71 3.18 2.64 3.30 2.67 3.36 2.61 3.42 2.55 3.52 2.52 3.61 2.37 12 2.99 2.69 3.13 2.62 3.25 2.65 3.31 2.59 3.37 2.53 3.48 2.50 3.58 2.36 14 2.93 2.66 3.08 2.59 3.21 2.62 3.27 2.57 3.33 2.52 3.44 2.49 3.54 2.34 16 2.87 2.63 3.02 2.56 3.16 2.60 3.22 2.55 3.28 2.49 3.40 2.47 3.50 2.33 18 2.81 2.59 2.96 2.53 3.11 2.57 3.17 2.53 3.23 2.47 3.36 2.45 3.46 2.31 20 2.75 2.56 2.90 2.50 3.05 2.55 3.12 2.50 3.19 2.45 3.31 2.43 3.42 2.29 22 2.69 2.53 2.84 2.47 3.00 2.52 3.07 2.48 3.13 2.43 3.27 2.41 3.38 2.28 24 2.62 2.50 2.77 2.44 2.94 2.50 3.02 2.46 3.08 2.41 3.22 2.39 3.33 2.26 26 2.56 2.46 2.7
1 2.41 2.88 2.47 2.96 2.43 3.03 2.38 3.17 2.37 3.29 2.24 28 2.49 2.43 2.64 2.38 2.82 2.44 2.91 2.41 2.97 2.36 3.12 2.35 3.24 2.22 30 2.42 2.39 2.57 2.34 2.76 2.41 2.85 2.38 2.91 2.33 3.07 2.33 3.19 2.20 32 2.35 2.35 2.50 2.31 2.70 2.38 2.79 2.35 2.86 2.31 3.01 2.31 3.14 2.18 34 2.28 2.28 2.43 2.27 2.63 2.36 2.73 2.33 2.79 2.28 2.96 2.28 3.08 2.16 35 2.24 2.24 2.39 2.26 2.60 2.34 2.70 2.31 2.76 2.27 2.93 2.27 3.06 2.15 36 2.20 2.20 2.35 2.24 2.57 2.32 2.67 2.30 2.73 2.25 2.90 2.26 3.03 2.14 38 2.13 2.13 2.27 2.20 2.50 2.29 2.61 2.27 2.67 2.23 2.84 2.24 2.97 2.12 39 2.09 2.09 2.24 2.19 2.47 2.28 2.57 2.26 2.64 2.21 2.81 2.22 2.94 2.10
Hi
indoor temperature
Outdoor DB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 3.04 2.52 3.18 2.48 3.30 2.59 3.36 2.56 3.42 2.53 3.52 2.62 3.61 2.55 12 2.99 2.50 3.13 2.46 3.25 2.57 3.31 2.54 3.37 2.51 3.48 2.61 3.58 2.52 14 2.93 2.47 3.08 2.43 3.21 2.55 3.27 2.52 3.33 2.49 3.44 2.59 3.54 2.51 16 2.87 2.44 3.02 2.41 3.16 2.53 3.22 2.50 3.28 2.48 3.40 2.58 3.50 2.50 18 2.81 2.41 2.96 2.38 3.11 2.51 3.17 2.48 3.23 2.46 3.36 2.55 3.46 2.49 20 2.75 2.38 2.90 2.35 3.05 2.49 3.12 2.46 3.19 2.44 3.31 2.54 3.42 2.48 22 2.69 2.35 2.84 2.33 3.00 2.46 3.07 2.44 3.13 2.42 3.27 2.52 3.38 2.47 24 2.62 2.31 2.77 2.30 2.94 2.44 3.02 2.42 3.08 2.40 3.22 2.51 3.33 2.45 26 2.56 2.29 2.7
1 2.26 2.88 2.42 2.96 2.40 3.03 2.38 3.17 2.49 3.29 2.44 28 2.49 2.26 2.64 2.23 2.82 2.39 2.91 2.38 2.97 2.36 3.12 2.48 3.24 2.43 30 2.42 2.23 2.57 2.20 2.76 2.37 2.85 2.36 2.91 2.34 3.07 2.46 3.19 2.41 32 2.35 2.20 2.50 2.18 2.70 2.34 2.79 2.33 2.86 2.31 3.01 2.45 3.14 2.40 34 2.28 2.16 2.43 2.14 2.63 2.32 2.73 2.31 2.79 2.29 2.96 2.42 3.08 2.38 35 2.24 2.14 2.39 2.13 2.60 2.30 2.70 2.30 2.76 2.28 2.93 2.41 3.06 2.37 36 2.20 2.13 2.35 2.11 2.57 2.29 2.67 2.28 2.73 2.26 2.90 2.41 3.03 2.36 38 2.13 2.09 2.27 2.08 2.50 2.26 2.61 2.26 2.67 2.24 2.84 2.39 2.97 2.35 39 2.09 2.08 2.24 2.06 2.47 2.25 2.57 2.25 2.64 2.23 2.81 2.38 2.94 2.33
Outdoor DB
indoor temperature
Hi
(kW)
(kW)
14WB 21WB
16WB 23WB
18WB 26WB
19WB 27WB
20WB 28WB
22WB 31WB
24WB 33WB
14WB 21WB
16WB 23WB
18WB 26WB
19WB 27WB
20WB 28WB
22WB 31WB
24WB 33WB
Page 36
Cooling Mode
(220-240V)
Capacity 3.600 kw
Wind Hi
Air flow 10 (m
3
/min)
Cooling Mode
(220V)
Capacity 3.600 kw
Wind Hi
Air flow 10 (m
3
/min)
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 4.06 3.27 4.25 3.19 4.40 3.21 4.48 3.15 4.55 3.08 4.69 3.04 4.81 2.87 12 3.98 3.22 4.17 3.15 4.34 3.18 4.42 3.12 4.50 3.06 4.64 3.02 4.77 2.85 14 3.91 3.18 4.10 3.11 4.28 3.15 4.36 3.09 4.44 3.03 4.58 2.99 4.72 2.83 16 3.83 3.14 4.02 3.07 4.21 3.11 4.29 3.06 4.38 3.00 4.53 2.97 4.67 2.81 18 3.75 3.10 3.95 3.03 4.14 3.08 4.23 3.03 4.31 2.97 4.47 2.94 4.61 2.79 20 3.67 3.05 3.87 2.99 4.07 3.04 4.16 2.99 4.25 2.94 4.41 2.92 4.56 2.76 22 3.59 3.00 3.78 2.95 4.00 3.00 4.10 2.96 4.18 2.90 4.35 2.89 4.50 2.74 24 3.50 2.96 3.70 2.90 3.92 2.97 4.02 2.92 4.11 2.87 4.29 2.86 4.44 2.71 26 3.41 2.91 3.6
1 2.85 3.84 2.93 3.95 2.89 4.04 2.84 4.23 2.83 4.38 2.69 28 3.32 2.86 3.52 2.81 3.76 2.89 3.88 2.85 3.96 2.80 4.16 2.80 4.32 2.66 30 3.23 2.81 3.43 2.76 3.68 2.85 3.80 2.82 3.89 2.77 4.09 2.77 4.25 2.63 32 3.14 2.76 3.33 2.71 3.60 2.81 3.72 2.78 3.81 2.73 4.02 2.74 4.18 2.60 34 3.04 2.71 3.23 2.67 3.51 2.77 3.64 2.74 3.73 2.69 3.94 2.70 4.11 2.57 35 2.99 2.68 3.18 2.64 3.47 2.74 3.60 2.72 3.68 2.67 3.91 2.69 4.07 2.56 36 2.94 2.66 3.13 2.62 3.42 2.72 3.56 2.70 3.64 2.65 3.87 2.67 4.04 2.54 38 2.84 2.60 3.03 2.56 3.33 2.68 3.47 2.66 3.56 2.61 3.79 2.64 3.96 2.51 39 2.79 2.58 2.98 2.54 3.29 2.66 3.43 2.64 3.51 2.59 3.75 2.62 3.92 2.49
Hi
indoor temperature
Outdoor DB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 4.06 3.26 4.25 3.18 4.40 3.20 4.48 3.14 4.55 3.07 4.69 3.03 4.81 2.85 12 3.98 3.22 4.17 3.14 4.34 3.17 4.42 3.11 4.50 3.04 4.64 3.00 4.77 2.83 14 3.91 3.17 4.10 3.10 4.28 3.13 4.36 3.08 4.44 3.01 4.58 2.98 4.72 2.81 16 3.83 3.13 4.02 3.06 4.21 3.10 4.29 3.04 4.38 2.98 4.53 2.95 4.67 2.79 18 3.75 3.09 3.95 3.02 4.14 3.06 4.23 3.01 4.31 2.95 4.47 2.93 4.61 2.77 20 3.67 3.04 3.87 2.98 4.07 3.03 4.16 2.98 4.25 2.92 4.41 2.90 4.56 2.74 22 3.59 3.00 3.78 2.93 4.00 2.99 4.10 2.95 4.18 2.89 4.35 2.87 4.50 2.72 2
4 3.50 2.95 3.70 2.89 3.92 2.95 4.02 2.91 4.11 2.86 4.29 2.84 4.44 2.69 26 3.41 2.90 3.61 2.85 3.84 2.92 3.95 2.88 4.04 2.82 4.23 2.81 4.38 2.66 28 3.32 2.85 3.52 2.80 3.76 2.88 3.88 2.84 3.96 2.79 4.16 2.78 4.32 2.64 30 3.23 2.80 3.43 2.75 3.68 2.84 3.80 2.80 3.89 2.75 4.09 2.75 4.25 2.61 32 3.14 2.75 3.33 2.70 3.60 2.79 3.72 2.76 3.81 2.71 4.02 2.72 4.18 2.58 34 3.04 2.70 3.23 2.65 3.51 2.75 3.64 2.73 3.73 2.68 3.94 2.69 4.11 2.55 35 2.99 2.67 3.18 2.63 3.47 2.73 3.60 2.71 3.68 2.66 3.91 2.67 4.07 2.53 36 2.94 2.65 3.13 2.60 3.42 2.71 3.56 2.69 3.64 2.6
4 3.87 2.65 4.04 2.52 38 2.84 2.59 3.03 2.55 3.33 2.66 3.47 2.65 3.56 2.60 3.79 2.62 3.96 2.49 39 2.79 2.57 2.98 2.53 3.29 2.64 3.43 2.63 3.51 2.58 3.75 2.60 3.92 2.47
Hi
indoor temperature
Outdoor DB
14WB 21WB
16WB 23WB
18WB 26WB
19WB 27WB
20WB 28WB
22WB 31WB
24WB 33WB
14WB 21WB
16WB 23WB
18WB 26WB
19WB 27WB
20WB 28WB
22WB 31WB
24WB 33WB
(kW)
(kW)
TC : Total cooling capacity (kW) SHC : Sensible heat capacity (kW)
Page 37
Safety precautions
Before installation, read the “Safety precautions” carefully and strictly follow it during the installation work in order to protect yourself.v The precautionary items mentioned below are distinguished into two levels,v
WARNING
and
CAUTION
.
WARNING
: Wrong installation would cause serious consequences such as injuries or death.
CAUTION
: Wrong installation might cause serious consequences depending on circumstances. Both mention the important items to protect your health and safety so strictly follow them by any means. Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the operating methods as v well as the maintenance methods of this equipment to the user according to the user’s manual. Keep the installation manual together with user’s manual at a place where any user can read at any time. Moreover if necessary, ask v to hand them to a new user. Before starting the installation work, proper precautions (using suitable protective clothing, groves etc.) should be taken by qualifiedv installer. Please pay attention not to fall down the tools, etc. when installing the unit at the high position.v If unusual noise can be heard during operation, consult the dealer.v The meanings of “Marks” used here are shown as follows:v
Never do it under any circumstances.
Always do it according to the instruction.
WARNING
Installation must be carried out by the qualified installer.v
If you install the system by yourself, it may cause serious trouble such as water leaks, electric shocks, fire and personal injury, as a result of a system malfunction. Do not carry out the installation and maintenance work except by the qualified installer.
Install the system in full accordance with the installation v manual.
Incorrect installation may cause bursts, personal injury, water leaks, electric shocks and fire.
Be sure to use only for household and residence.v
If this appliance is installed in inferior environment such as machine shop etc., it can cause malfunction.
Use the original accessories and the specified components forv installation.
If parts other than those prescribed by us are used, it may cause water leaks, electric shocks, fire and personal injury.
Install the unit in a location with good support.v
Unsuitable installation locations can cause the unit to fall resulting in material damage and personal injury.
Ensure the unit is stable when installed, so that it can withstand v earthquakes and strong winds.
Unsuitable installation locations can cause the unit to fall and cause material damage and personal injury.
Ventilate the working area well in the event of refrigerantv leakage during installation.
If the density of refrigerant exceeds the limit, please consult the dealer and install the ventilation system, otherwise lack of oxygen can occur, which can cause serious accident.
When installing in small rooms, take prevention measures not v to exceed the density limit of refrigerant in the event of leakage, referred by the formula (accordance with ISO5149).
If the density of refrigerant exceeds the limit, please consult the dealer and install the ventilation system, otherwise lack of oxygen can occur, which can cause serious accident.
After completing installation, check that no refrigerant leaks v from the system.
If refrigerant leaks into the room and comes into contact with an oven or other hot surface, poisonous gas is produced.
Use the prescribed pipes, flare nuts and tools for R410A.v
Using existing parts (for R22 or R407C) can cause the unit failure and serious accidents due to burst of the refrigerant circuit.
Tighten the flare nut by torque wrench with specified method.v
If the flare nuts were tightened with excess torque, this may cause burst and refrigerant leakage after a long period.
Do not open the operation valves for liquid line and gas line v until completed refrigerant piping work, air tightness test and evacuation.
If the compressor is operated in state of opening operation valves before completed connection of refrigerant piping w
ork, air can be sucked into refrigerant circuit, which can cause burst or personal injury due to anomalously high pressure in the refrigerant.
The electrical installation must be carried out by the qualifiedv electrician in accordance with “the norm for electrical work” and “national wiring regulation”, and the system must be connected to the dedicated circuit.
Power supply with insufficient capacity and incorrect function done by improper work can cause electric shocks and fire.
Be sure to shut off the power before starting electrical work.v
Failure to shut off the power can cause electric shocks, unit failure or incorrect function of equipment.
Be sure to use the cables conformed to safety standard and v cable ampacity for power distribution work.
Unconformable cables can cause electric leak, anomalous heat production or fire.
This appliance must be connected to main power supply by
v
means of a cir
cuit breaker or switch (fuse 20A) with a contact
separation of at least 3mm. When plugging this appliance, a plug conforming to the norm v
IEC60884-1 must be used. Use the prescribed cables for electrical connection, tighten v
the cables securely in terminal block and relieve the cables correctly to prevent overloading the terminal blocks.
Loose connections or cable mountings can cause anomalous heat production or fire.
Arrange the wiring in the control box so that it cannot be v pushed up further into the box. Install the service panel correctly.
Incorrect installation may result in overheating and fire.
Be sure to fix up the service panels.v
Incorrect fixing can cause electric shocks or fire due to intrusion of dust or water.
Be sure to switch off the power supply in the event of v installation, inspection or servicing.
If the power supply is not shut off, there is a risk of electric shocks, unit failure or personal injury due to the unexpected start of fan.
Stop the compressor before removing the pipe after shutting the v service valve on pump down work.
If the pipe is removed when the compressor is in operation with the service valve open, air would be mixed in the refrigeration circuit and it could cause explosion and injuries due to abnormal high pressure in the cooling cycle.
Only use prescribed option parts. The installation must be v carried out by the qualified installer.
If you install the system by yourself, it can cause serious trouble such as water leaks, electr
ic shocks, fire.
Be sure to wear protective goggles and gloves while at work.v Earth leakage breaker must be installed.v
If the earth leakage breaker is not installed, it can cause electric shocks.
Do not put the drainage pipe directly into drainage channelsv where poisonous gases such as sulphide gas can occur.
Poisonous gases will flow into the room through drainage pipe and seriously affect the user’s health and safety. This can also cause the corrosion of the indoor unit and a resultant unit failure or refrigerant leak.
Ensure that no air enters in the refrigerant circuit when the unit v is installed and removed.
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit becomes too high, which can cause burst and personal injury.
Do not bundle or wind or process the power cord. Do not deformv the power cord by treading it.
This may cause fire or heating.
Do not process or splice the power cord, or share the socketv with other power plugs.
This may cause fire or electric shock due to defecting contact, defecting insulation and over-current etc.
Do not vent R410A into the atmosphere : R410A is a fluorinatedv greenhouse gas, covered by the Kyoto Protocol with Global Warming Potential (GWP)=1975.
Do not run the unit with removed panels or protections.v
Touching rotating equipments, hot surfaces or high voltage parts can cause personal injury due to entrapment, burn or electric shocks.
Do not perform any change of protective device itself or its v setup condition.
The forced operation by short-circuiting protective device of pressure switch and temperature controller or the use of non specified component can cause fire or burst.
WALL TYPE AIR-CONDITIONER
R410A REFRIGERANT USED
While install the unit, be sure to checkthe selection of installation place, power supply specifications, usage limitation (piping length, height differences between indoor and outdoor units, power supply voltage and etc.) and installation spaces.
Page 38
Safety precautions
CAUTION
Carry out the electrical work for ground lead with care.v
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults such as electric shocks due to short-circuiting.
Use the circuit breaker of correct capacity. Circuit breaker v should be able to disconnect all poles under over current.
Using the incorrect one could cause the system failure and fire.
Install isolator or disconnect switch on the power supply wiring v in accordance with the local codes and regulations.
The isolator should be locked in OFF state in accordance with EN60204-1.
Be sure to install indoor unit properly according to instruction v manual so that drainage can run off smoothly.
Improper installation of indoor unit can cause dropping water into the room and damaging personal property.
Install the drainage pipe to run off drainage securely accordingv to the installation manual.
Incorrect installation of the drainage pipe can cause dropping water into the room and damaging personal property.
Be sure to install the drainage pipe with descending slope of v 1/100 or more, and not to make traps and air-bleedings.
Check if the drainage runs off securely during commissioning and ensure the space for inspection and maintenance.
After maintenance, all wiring, wiring ties and the like, should v be returned to their original state and wiring route, and the necessary clearance from all metal parts should be secured.
Secure a space for installation, inspection and maintenance v specified in the manual.
Insufficient space can result in accident such as personal injury due to falling from the installation place.
Take care when carrying the unit by hand.v
If the unit weights more than 20kg, it must be carried by two or more persons. Do not carry by the plastic straps, always use the carry handle when carrying the unit by hand. Use gloves to minimize the risk of cuts by the aluminum fins.
Dispose of any packing materials correctly.v
Any remaining packing materials can cause personal injury as it contains nails and wood. And to avoid danger of suffocation, be sure to keep the plastic wrapper away from children and to dispose after tear it up.
For installation work, be careful not to get injured with the heat v exchanger, piping flare portion or screws etc.
Be sure to insulate the refri
gerant pipes so as not to condense v
the ambient air moisture on them.
Insufficient insulation can cause condensation, which can lead to moisture damage on the ceiling, floor, furniture and any other valuables.
When perform the air-conditioner operation (cooling or dryingv operation) in which ventilator is installed in the room. In this case, using the air-conditioner in parallel with the ventilator, there is the possibility that drain water may backflow in accordance with the room lapse into the negative pressure status. Therefore, set up the opening port such as incorporate the air into the room that may appropriate to ventilation (For example; Open the door a little). In addition, just as above, so set up the opening port if the room lapse into negative pressure status due to register of the wind for the high rise apartment etc.
Be sure to perform air tightness test by pressurizing with v nitrogen gas after completed refrigerant piping work.
If the density of refrigerant exceeds the limit in the event of refrigerant leakage in the small room, lack of oxygen can occur, which can cause serious accidents.
Do not install the unit in the locations listed below.v
Locations where carbon fiber, metal powder or any powder is floating.
v
Locations where any substances that can affect the unit such as v sulphide gas, chloride gas, acid and alkaline can occur. Vehicles and ships.v Locations where cosmetic or special sprays are often used.v Locations with direct exposure of oil mist and steam such as v kitchen and machine plant. Locations where any machines which generate high frequency v harmonics are used. Locations with salty atmospheres such as coastlines.v Locations with heavy snow (If installed, be sure to provide base v flame and snow hood mentioned in the manual). Locations where the unit is exposed to chimney smoke.v Locations at high altitude (more than 1000m high).v Locations with ammonic atmospheres.v Locations where heat radiation from other heat source can affectv the unit. Locations without good air circulation.v Locations with any obstacles which can prevent inlet and outlet air v of the unit. Locations where short circuit of air can occur (in case of multiplev units installation). Locations where strong air blows against the air outlet of outdoor unit.
v
Locations where something located above the unit could fall.v It can cause remarkable decrease in performance, corrosion and damage of components, malfunction and fire.
Do not install the indoor unit in the locations listed below (Bev sure to install the indoor unit according to the installation manual for each model because each indoor unit has each limitation).
Locations with any obstacles which can prevent inlet and outlet air v
of the unit.
Locations where vibration can be amplified due to insufficientv
strength of structure.
Locations where the infrared receiver is exposed to the direct sunlight
v
or the strong light beam (in case of the infrared specification unit).
Locations where an equipment affected by high harmonics is placedv
(TV set or radio receiver is placed within 1m).
Locations where drainage cannot run off safely.v It can affect performance or function and etc.
Do not install the outdoor unit in the locations listed below.v
Locations where discharged hot air or operating sound of the v
outdoor unit can bother neighborhood.
Locations where outlet air of the outdoor unit blows directly to v
plants. The outlet air can affect adversely to the plant etc.
Locations where vibration can be amplified and transmitted due to v
insufficient strength of structure.
Locations where vibration and operation sound generated by the outdoor
v
unit can affect seriously (on the wall or at the place near bed room).
Locations where an equipment affected by high harmonics is placedv
(TV set or radio receiver is placed within 1m).
Locations where drainage cannot run off safely.v It can affect surrounding environment and cause a claim.
Do not install the unit where corrosive gas (such as sulfurousv acid gas etc.) or combustible gas (such as thinner and petroleum gases) can accumulate or collect, or where volatile combustible substances are handled.
Corrosive gas can cause corrosion of heat exchanger, breakage of plastic parts and etc. And combustible gas can cause fir
e.
Do not install the unit near the location where leakage of v combustible gases can occur.
If leaked gases accumulate around the unit, it can cause fire.
Do not use the indoor unit at the place where water splashes v may occur such as in laundries.
Since the indoor unit is not waterproof, it can cause electric shocks and fire.
Do not install nor use the system close to the equipment that v generates electromagnetic fields or high frequency harmonics.
Equipment such as inverters, standby generators, medical high frequency equipments and telecommunication equipments can affect the system, and cause malfunctions and breakdowns.The system can also affect medical equipment and telecommunication equipment, and obstruct its function or cause jamming.
Do not place any variables which will be damaged by getting wetv under the indoor unit.
When the relative humidity is higher than 80% or drainage pipe is clogged, condensation or drainage water can drop and it can cause the damage of valuables.
Do not install the remote control at the direct sunlight.v
It can cause malfunction or deformation of the remote control.
Do not use the unit for special purposes such as storing foods,v cooling precision instruments and preservation of animals, plants or art.
It can cause the damage of the items.
Do not install the outdoor unit in a location where insects and v small animals can inhabit.
Insects and small animals can enter the electric parts and cause damage or fire. Instruct the user to keep the surroundings clean.
Do not use the base flame for outdoor unit which is corroded or v damaged due to long periods of operation.
Using an old and damage base flame can cause the unit falling down and cause personal injury.
Do not use any materials other than a fuse with the correct v rating in the location where fuses are to be used.
Connecting the circuit with copper wire or other metal thread can cause unit failure and fire.
Do not touch any buttons with wet hands.v
It can cause electric shocks.
Do not touch any refrigerant pipes with your hands when the v system is in operation.
During operation the refrigerant pipes become extremely hot or extremely cold depending the operating condition, and it can cause burn injury or frost injury.
Do not touch the suction or aluminum fin on the outdoor unit.v
This may cause injury.
Do not put anything on the outdoor unit and operating unit.v
This may cause damage the objects or injury due to falling to the object.
Do not clean up the unit with water.v
Page 39
A place where good air circulation can be obtained and where rain,
snow or sunshine will not directly strike the unit.
A place where discharged hot air or unit’s operating sound will not
be a nuisance to the neighborhood.
A place where servicing space can be secured.A place where vibration will not be enlarged.
*Avoid installing in the following places.
s! place near the bedroom and the like, so that the operation noise
will cause no trouble.
s
A place where there is possibility of flammable gas leakage.
s!PLACEexposed to strong wind. s)N a salt-laden atmosphere or a place where the generation of oil
mist, vapor or fume is expected.
Blowing out port and suction port on the back side of the unit can be
installed at a distance of 10cm from walls.
)NCASETHEBARRIERISMORABove in height, or is overhead, the sufficient space between the unit and wall shall be secured.
When the unit is installed, the space of the following dimension and
above shall be secured.
OUTDOOR UNIT
Note (1) )F the wall ishigher than  m or aceiling
is present, distances larger than indicated in the above table must be provided.
Selection of installation location
Where there is no obstructions to the air flow and where the cooled
air can be evenly distributed.
A solid place where the unit or the wall will not vibrate.A place where there will be enough space for servicing. (Where
space mentioned right can be secured)
Where wiring and the piping work will be easy to conduct.The place where receiving part is not exposed to the direct rays of
the sun or the strong rays of the street lighting.
A place where it can be easily drained.
A place separated at least 1m away from the television or the radio. (To prevent interfence to images and sounds.)
A place that home appliance and household goods, etc. aren’t
below unit.
INDOOR UNIT
10 cm
5 cm
10 cm
Left side
CM-).
Air intake
CM-).
10 cm
-).
Air outlet
Air intake
No obstacles (Service space for electrical parts)
Right side
)(
Standard accessories
)NSTALLATIONKIT
Accessories for indoor unit
Q'ty
)NSTALLATIONBOARD
(Attached to the rear of the indoor unit)
1
Wireless remote control 1
Remote control holder
Tapping screws
FORINSTALLATIONBOARDDIABYMM
Wood screw
FORREMOTECONTOROLSWITCHHOLDERDIABYMM
"ATTERY;2!!!-ICRO6]
Air-cleaning fi sretl
Filter holders (Attached to the front panel of the indoor unit)
Option parts Q'ty
Sealing plate 1
Sleeve 1
)NCLINATIONPLATE 1
Putty 1
Drain hose (extention hose) 1
Piping cover (for insulation of connection piping)
1
Necessary tools for the installation work
1 Plus headed driver (Phillips screwdriver)
Knife
3 Saw
4 Tape measure
Hammer
6 Spanner wrench
7 Torque wrench
(
^.qM
^KGFqM
)
8 (OLECOREDRILLMMINDIAMETER
9 Wrench key (Hexagon) [4m/m]
10 6acuum pump
11
6acuum pump adapter (Anti-reverse flow type)
(
Designed specifically
for R410A
)
1Gauge manifold
(
Designed specifically
for R410A
)
13 Change hose
(
Designed specifically
for R410A
)
14 Flaring tool set
(
Designed specifically
for R410A
)
1Gas leak detector
(
Designed specifically
for R410A
)
16
Gauge for projection adjustment (Used when flare is made by using conventional flare tool)
17 Pipe bender
1
Page 40
Installation of indoor unit
Installation of installation board
Limitations for one way piping length and vertical height difference
One way piping length ( )
15 m
Vertical height difference (h)
Outdoor unit is lower
10 m
Outdoor unit is higher
10 m
Drilling of holes and fi xture sleeve (Option parts)
Page 41
Connecting power source by power cable.
connecting diagram
Terminal and power cable
on the indoor unit
Brown
Power source
Blue Yellow/Green
L N
1 2
Terminal on the outdoor unit
1 2
Page 42
Open/close and detachment/attachment of air inlet panel
1 To open, pull the panel at both ends of lower part and release
latches, then pull up the panel until you feel resistance. (The air inlet panel stops at approx. 60˚ open position.)
2 To close, hold the panel at both ends of lower part to lower
downward and push it slightly until the latch works, then push the center portion slightly.
3 To remove, pull up the panel to the position shown in right
illustration and pull it toward you.
4 To install, insert the air inlet panel arm into the slot on the
front panel from the position shown in right illustration, hold the panel at both ends of lower part, lower it downward slowly, then push it slightly until the latch works and further push the center portion slightly.
Page 43
Installation of outdoor unit
Make sure that the unit is stable in installation.
Fix the unit to stable base.
Perform wiring, making wire terminal numbers
conform to terminal numbers of indoor unit terminal block.
Connection of refrigerant pipings
Preparation
Keep the openings of the pipes covered with tapes etc. to prevent dust, sand, etc. from entering them.
v Remove the flared nuts.
(on both liquid and gas sides)
Flaring workv
v Remove the flared nuts.
(on both liquid and gas sides)
v Install the removed flared nuts to the
pipes to be connected, then flare the pipes.
CAUTION
Do not apply v
refrigerating machine oil to the flared surface.
A
90± 0.5°
roodtuOroodnI
(Do not turn)
Measur ement B
Copper pipe
Flaring block
Remove Remove
Press Press
Dimension A Liquid side : ø6.35: 9.1 Gas side ø9.52: 13.2
ø12.7: 16.6 ø15.88: 19.7
Copper pipe diameter
Measurement B (mm)
Use a flare tool designed for R410A or a conventional flare tool. Please note that measurement B (protrusion from the flaring block) will vary depending on the type of a flare tool in use. If a conventional flare tool is used, please use a copper pipe gauge or a similar instrument to check protrusion so that you can keep measurement B to a correct value.
Clutch type flare
tool for R410A
Conventional (R22) flare tool
Clutch type Wing nut type
F 6.35 0.0~0.5 1.0~1.5 1.5~2.0
F 9.52 0.0~0.5 1.0~1.5 1.5~2.0
F 12.7 0.0~0.5 1.0~1.5 2.0~2.5
F 15.88 0.0~0.5 1.0~1.5 2.0~2.5
(Unit : mm)
Connect the pipes on both liquid and gas sides. Tighten the nuts to the following torque.
N·m (kgf·m)
Liquid side (F 6.35) 14.0 ~ 18.0 (1.4~1.8)
Gas side (F 9.52) 34.0 ~ 42.0 (3.4~4.2)
(F 12.7) 49.0 ~ 61.0 (4.9~6.1)
F 15.88) 68.0 ~ 82.0 (6.8~8.2)
CAUTION
Do not apply excess torque to the flared nuts.v
Otherwise, the flared nuts may crack depending on the conditions and refrigerant leak may occur.
Indoor Outdoor
Liquid side Gas side
(Do not turn)
Liquid side Gas side
Connection of refrigerant
piping
1 2
Terminal block
Interconnecting wire
Terminal and power cable
on the indoor unit
Brown
Power source
Blue Yellow/Green
L N
1 2
Terminal on the outdoor unit
1 2
connecting diagram
Page 44
Insulation of connecting portion
Cover the connection portion of the refrigerant piping with the pipe
cover and seal them.
If neglecting to do so, moisture occurs on the piping and water will drip out.
Finishing and fixing
Tie up the piping with wrapping tape, and shape it so that it
conforms to which the pipe is attached.
Fix them with clamps as right figure.
Vinyl tape
To cover the connecting por tion with insulation materials, cut upper portion and then seal it with insulation
materials.
Co ve r th e ex te rio r po rt ion with covering tape and shape the piping so it will match the contours of the route that the pipin g t o t ake. Also fix the
wiring and pipings to the wall with clamps.
Insulation Refrigerant piping Electrical wiring Covering tape
Drain hose
Tapping screw
g Additional refrigerant charge
Models SRK10CRV-S
SRK13CRV-S SRK10CRS-S, S3, S4, S5, S6 SRK13CRS-S, S3, S4, S5, S6
Models SRK10CRV-S1
SRK13CRV-S1 SRK10CRS-S1, S2 SRK13CRS-S1, S2
Air purge
Securely tighten the operation valve cap and the check joint blind nut after adjustment.
Operation valve size
(mm)
Operation valve cap
tightening torque (N·m)
Check joint blind nut
tightening torque (N·m)
F
6.35 (1/4") 20 ~ 30
10 ~ 12
F
9.52 (3/8")
F
12.7 (1/2") 25 ~ 35
F
15.88 (5/8") 30 ~ 40
Compound pressure gauge
Operation valve cap
Operation valve (three-way valve)
Operation valve cap
-0.1MPa
(-76cmHg)
Handle Lo
Pressure gauge
Handle Hi
Charge hose (Designed specifically for R410A)
Vacuum pump adapter (Anti-reverse flow type) (Designed specifically for R410A)
Vacuum pump
Charge hose (Designed specifically for R410A)
Check joint
Operation valve (two-way valve)
Gauge manifold (Designed specifically for R410A)
Tighten all flare nuts in the pipings both indoor
and outside wall so as not to cause leak.
Connect operationvalve, charge hose, manifold
valve and vacuum pump as is illustrated right.
Open manifold valve handle Lo to its full
width, and perform vacuum or evacuation. Continue the vacuum or evacuation operation for 15 minutes or more and check to see that the vacuum gauge reads -0.1MPa.
After completing vacuum operation, close the
Lo handle and stop operation of the vacuum pump.
After completing vacu um operation, fully
open operation valve (Both gas and liquid sides) with hexagon headed wrench.
Check for possible leakage of gas in the
connection parts of both indoor and outdoor.
v Since the system uses check joints differing in diameter
from those found on the conventional models, a charge hose (for R22) presently in use is not applicable. Please use one designed specifi
cally for R410A.
v Please use an anti-reverse flow type vacuum pump adapter
so as to prevent vacuum pump oil from running back into the system. Oil running back into an air-conditioning system may cause the refrigerant cycle to break down.
When refrigerant piping exceeds 5m conduct additional refrigerant charge after refrigerant sweeping. 5m over 15m: Additional charge amount per meter = 10g/m
[Example]
How much amount of additional charge for 15m piping?
(15 - 5)m × 10g/m = 100g
100g for additional charge
g Additional refrigerant charge
When refrigerant piping exceeds 7.5m conduct additional refrigerant charge after refrigerant sweeping.
7.5m over 15m: Additional charge amount per meter = 10g/m
[Example]
How much amount of additional charge for 15m piping?
(15 - 7.5)m × 10g/m = 75g
75g for additional charge
Page 45
Installation of remote control switch
Mounting method of battery
Earthing work
+
+
-
-
v Uncover the remote control switch, and mount the
batteries [R03(AAA, Micro)s2 pieces] in the body regularly.
(Fit the poles with the indication marks, &⊖.
without fail)
v Earth work shall be carried out without fail in order to prevent electric shock and noise generation. v The connection of the earth cable to the following substances causes dangerous failures, therefore it shall never be done.
City water pipe, Town gas pipe, TV antenna, lightning conductor, telephone line, etc.
Trial run and operation
Conduct trial run after confirming that there is no gas leaks.When conducting trial run set the remote control thermostat to continuous operation position. However when the power source is
cut off or when the unit’s operation switch is turned off or was turned to fan operation position, the unit will not go into operation in order to protect the compressor.
Explain to the customer on the correct usage of the air-conditioner in simple layman’s terms.Make sure that drain flows properly.
Battery
Cover
Fixing to pillar or wall
v Conventionally, op erate the wireless remote
control by holding in your hand.
v Avoid installing it on a clay wall etc.
Screws
CAUTION
Do not use new and old batteries together.
How to relocate or dispose of the unit
v In order to protect the environment, be sure to pump down
(recovery of refrigerant).
v Pump down isthe method of recovering refrigerant fromthe
indoor unit to the outdoor unit when the pipes are removed from the unit.
<How to pump down>
Connect charge hose to check joint.Liquid side : Close the liquid valve with hexagon wrench
key. Gas side : Fully open the gas valve. Carry out cooling operation. (If indoor temperature is low,
operate forced cooling operation.)
After low pressure gauge become 0.01MPa, close the gas
valve then stop cooling operation.
v Forced cooling operation
Turnon a power supply again after awhile afterturn offa power supply. Then press continually the ON/OFF button 5 seconds
or more.
Page 46
Installations test check points
Check the following points again after completion of the installation, and before turning on the power. Conduct a test run again and ensure that the unit operates properly.
At the same time, explain to the customer how to use the unit and how to take care of the unit following the instruction manual.
After installation
The power source voltage is correct as the rating.
No gas leaks from the joints of the operation valve.
Operation valve is fully open.
The pipe joints for indoor and outdoor pipes have been insulated.
Test run
Air-conditioning operation is normal.
No abnormal noise.
Water drains smoothly.
Protective functions are not working.
The remote control is normal.
Operation of the unit has been explained to the customer.
(Three-minute restart preventive timer) When the air-conditioner is restarted or when changing the operation, the unit will not start operating for approximately 3 minutes.
This is to protect the unit and it is not a malfunction.
Page 47
ECONO light (orange)
Illuminate s during ECO NOMY operati on.
HI POWER light (green)
Illuminate s during H IGH POWER opera tion.
RUN light (green)
Illuminate s during o peration and CLEAN operation.
TIMER light (yellow)
Illuminate s during TIM ER operatio n.
FAN SPEED button
Each time the button i s pushed, th e indicator is switche d over in t urn.
HI POWER/ECONO button
This butt on changes the HIGH PO WER/ ECONOMY mo de.
TEMPERATURE Button
This butt on sets the room tempe rature. (This but ton changes the presen t time and
TIMER tim e.)
ON TIMER button
This butt on selects ON TIMER op eration.
SLEEP button
This butto n changes to SLEEP opera tion.
CLEAN switch
This swic h changes t he CLEAN mo de.
OPERATION MODE select button
Each time the button pushed, th e indicator is switche d over in t urn.
ON/OFF (luminous) button
Press for starting o peration, p ress agian for stoppi ng.
AIR FLOW (UP/DOWN) button
This butt on changes the air flo w (up/ down) mode .
The above illustration shows all controls, but in practi ce only the relevant parts a re shown.
OFF TIMER button
This butt on selects OFF TIMER o peration.
CANCEL button
This butt on cancels the ON time r, OFF timer, an d SLEEP ope ration.
ACL switch
Switch for resetting m icrocomputer and setting t ime.
Page 48
3D AUTO light (green)
Illuminate s during 3D AUTO operation.
HI POWER light (green)
Illuminate s during HI GH POWER opera tion.
RUN light (green)
Illuminate s during op eration and CLEAN operation.
TIMER light (yellow)
Illuminate s during TIM ER operatio n.
Operation and indication section for remote control
Operation section
SRK10YJV-S SRK13YJV-S
FAN SPEED button
Each time the but ton is push ed, the indicator is swit ched over i n turn.
v
The above illustr ation shows all contro ls, but in practice only the r elevant par ts are show n.
OPERATION MODE select button
Each time the but ton pushed, the indicator is switched over i n turn.
ON/OFF (luminous) button
Press for startin g operation , press aga in for stoppi ng.
HI POWER/ECONO button
This bu tton cha nges the HIGH PO WER/ ECONOMY mo de.
AIR FLOW (UP/DOWN) button
This butto n changes t he air flow (up/down) mode.
This butto n changes t he air flow (left/righ t) mode.
SLEEP button
This butto n changes t o SLEEP ope ration.
CLEAN switch
This switc h changes t he CLEAN mo de.
ON TIMER button
This butto n selects O N TIMER ope ration.
AIR FLOW (LEFT/RIGHT) button
3D AUTO button
Thi s b utto n set s 3D AUTO o pera tion.
Thi s b utto n can cels t he ON t imer , OFF timer, and SLEEP operati on.
CANCEL button
ACL switch
Switch for resetting microco mputer and setting ti me.
OFF TIMER button
This butto n selects O FF TIMER op eration.
TEMPERATURE button
This butto n sets the room temper ature. (This butt on changes the pre sent time a nd
TIMER time .)
Page 49
Cut
Jumper wire (J7)
Jumper wire (J6)
Unit ON/OFF button
In emergen cies, this button c an be used for turni ng on/off the unit when remote con trol is not availab le.
Page 15
RUN light (green)
Illuminate s during operation and CLEAN operation.
TIMER light (yellow)
Illuminate s during TIMER oper ation.
Unit ON/OFF button
Page 50
(5) Flap and louver control (Louver control function only CRS models)
(a) Flap
(b) Louver
(c) Swing
(i)
(d) Memory flap (Flap or Louver stopped)
(e) When not operating
COOL , DRY, FAN
Remote control display
Approx. 10° Approx. 20° Approx. 30°
(Swing)
(Flap stopped)
Approx. 45° Approx. 60°
Angle of Flap from Horizontal
Center installation
Remote control display
Right end installation
Left end installation
Angle of Louver
Left Approx. 45°
Left Approx. 45°
Left Approx. 20°
Left Approx. 30°
Center
Left Approx. 20°
Right Approx. 20°
Center
Right Approx. 45°
Right Approx. 20°
Left Approx. 20°
Center
Right Approx. 20° Right Approx. 30° Right Approx. 45°
(Louver stopped)
(Swing) (Spot) (Wide)
In COOL, DRY, FAN operation
Approx.
10°
Approx. 60°
(ii)
Page 51
(6) 3D auto operation (only CRS models)
Operation step
Flap
Louver
Conditions for jumping to next STEP
Fan speed Setting fan speed
_
20 cycle
60 cycle
60 cycle
Auto : HIGH POWER
Setting fan speed
STEP1 STEP2 STEP3 STEP4
Left louver
The left louver and right louver operate in the same direction left and right.
The left louver and right louver operate in opposite directions to each other on the left and right sides.
The left louver and right louver operate in opposite directions to each other on the left and right sides.
Right louver
Left louver Right louver
Left louver Right louver
1.4.6 3D auto operation
(only SRK10CJV-2, 13CJV-2)
Control the flap and louver by 3D AUTO button on the wireless remote control.
Fan speed and air flow direction are automatically controlled, allowing the entire room to efficiently conditioned.
(a) Detail of operation
(i) Perform STEP1 → STEP2 → STEP3 → STEP4 one time.
(ii) After performing STEP4 in (i) above, the next steps to be carried out are determined by the difference between
the room
temperature and the setting temperature.
1) Room temperature – Setting temperature > 5ºC: STEP2 STEP3 →→ STEP4 are performed.
2) Room temperature – Setting temperature
<
5ºC: STEP3
=
STEP4 are performed.
Other than Auto: Setting fan speed
Page 52
(b) Sleep timer operation
(7) Timer operation
(a) Comfortable timer setting (ON timer)
(c) OFF timer operation
(8) Installation location setting (only CRS models)
(a) Setting
(i)
If the air conditioning unit is running, press the ON/OFF button to stop.
(ii) Press the AIR FLOW (UP/DOWN) button and the
AIR FLOW (LEFT/RIGHT) button together for 5 seconds
or more.
(iii) Setting the air-conditioning installation location.
(iv) Press the ON/OFF button.
Airf low range Airf low rangeAirf low range
(Left End Installation) (Center Installation) (Right End Installation)
(Center Installation) (Right End Installation) (Left End Installation)
(i) , (iv)
(ii)
(iii)
Page 53
27.5
25.5
19.5
18
30
ON OFF OFF
ON
OFF OFF
ON ON ON
Thermostat ON Thermostat OFF Failure
Cooling
Compressor
Indoor fan motor
Outdoor fan motor
Auto fan control
Speed 5
Speed 3
Speed 2
Model
Fan speed
All model
Auto
MED
HI
LO
Page 54
(a) Frost prevention for indoor heat exchanger (During cooling or dehumidifying)
(i) Operating conditions
1) Indoor heat exchanger temperature (Th2) is lower than 2.5ºC.
2) 3 minutes elapsed after the start of operation.
(ii) Detail of frost prevention operation
Compressor OFF
Indoor fan Protects the fan tap just before frost prevention control.
Outdoor fan Depending on the stop mode
(iii) Reset condition: Indoor heat exchanger temperature (Th2) is higher than 8ºC.
(b) Indoor fan motor protection
When the airconditioner is operating and the indoor fan motor is turned ON, if the indoor fan motor has operated at 300
min
-1
or under for more than 30 seconds, the unit enters first in the stop mode and then stops the entire system.
TIMER light illuminates simultaneously and the RUN light flashing 6-time at each 8-second.
(c) 3 minutes forced operation
When the compressor begins operating the thermal operation is not effective for 3 minutes, so operation continues as
is in the operation mode. (After 3 minutes has passed the thermal operation is effective.)
However, stopping the compressor via a stop signal or protection control has priority.
(d) Abnormality of outdoor unit
When the indoor heat exchanger temperature does not fall to 25°C or below for 40 minutes after 5 minutes have elap-
sed since the compressor operation start, the abnormality stop occurs. (RUN light : ON, TIMER light : 2-time flash)
(e) Sensor disconnection (room temperature, indoor heat exchanger
)
(i) Room temperature sensor
If the temperature detected by the room temperature sensor is –20ºC or lower continuously for 15 seconds or longer
while operation is stopped, an error indication is displayed. (RUN light: 2-time flash, TIMER light: ON)
(ii) Indoor heat exchanger temperature sensor
If the temperature detected by the indoor heat exchanger temperature sensor is –20ºC or lower continuously for 15
seconds or longer while operation is stopped, an error indication is displayed.
(RUN light : 1-time flash, TIMER light : ON)
Page 55
YES
YES
YES
NO
NO
NO
NO
YES
Page 56
NO
NO
NO
NO
YES
YES
YES
YES
NO
YES
When a heat exchanger sensor wire disconnection is detected while operation is stopped. (If a temperature of –20ºC or lower is detected for 15 seconds, it is judged that the wire is disconnected.) (Not displayed during operation.)
When a room temperature sensor wire disconnection is detected while operation is stopped. (If a temperature of –20ºC or lower is detected for 15 seconds, it is judged that the wire is disconnected.) (Not displayed during operation.)
• Broken heat exchanger sensor
wire, poor connector connection
• Indoor PCB is faulty
• Broken room temperature
sensor wire, poor connector connection
• Indoor PCB is faulty
When conditions for turning the indoor unit’s fan motor on exist during air­conditioner operation, an indoor unit fan motor speed of 300 min
-1
or lower is
measured for 30 seconds or longer. (The air-conditioner stops.)
• Defective fan motor, poor connector connection
ON
1-time
flash
ON
2-time
flash
ON
6-time
flash
When there is an emergency stop caused by trouble in the outdoor unit, or the
input current value is found to be lower than the set value.
(The air-conditioner stops.)
• Broken compressor wire
• Compressor blockage
52C relay in indoor PCB is faulty
• Improper wire connection
between indoor and outdoor
2-time
flash
ON
Indoor unit display panel
Cause Display (flashing) condition
RUN
light
TIMER
light
Heat exchanger sensor error
Room temperature sensor error
Indoor fan motor error
Trouble of outdoor unit
Description
of trouble
Page 57
30
25
20
15
10
5
30
20
10
40 50 60
70
0
-
10
Page 58
Does compressor operation?
Is capacitor for compressor normal?
Replace compressor.
Insufficient gas
Is refrigerant amount normal?
Is connector for compressor connection good?
Does trouble persist after charging gas?
Clogged capillary tube or strainer, etc.
Replace capacitor for compressor.
Correct connection
Check if there are any places where gas is leaking
YES
YES
NO NO
NO
NO
NO
YES
YES
YES
Is there voltage at power source?
(AC 220/230/240V)
Replace PCB
Inspect power source.
If the packag e co mponents are not damaged, replace the fuse and perform an operation check again.
Is the fuse burnt out? (3.15 A)
NO
YES
NO
YES
Page 59
Page 60
Page 61
PARTS LIST
INDOOR UNI
T
SRK10CRV-S, S1 SRK13CRV-S, S1 SRK10CRS-S, S1, S2, S3, S4, S5, S
6
SRK13CRS-S, S1, S2, S3, S4, S5, S
6
OUTDOOR UNIT
SRC10CRV-S, S1 SRC13CRV-S, S1 SRC10CRS-S, S1, S2, S3, S4, S5, S
6
SRC13CRS-S, S1, S2, S3, S4, S5, S
6
Page 62
CRAE0215
2
5
6
12
12
9
8
12
10
10
10
10
14
16
13
17
11
11
4
24
21
23
28
28
3
4
15
18
7
20
19
25
27
22
26
1
PANEL & FAN ASSY
Page 63
SRK10CRV-S, S1
CRAE0215
END ITEM NO. : RMA002F060CA, 060CB
10 30 50 100 500 1000
1-6 RMA102A100 PANEL ASSY,FRONT 1 1 1 1 2
1 RKX122A300L PANEL,FRONT 1
2 RMA435A100 PANEL, AIR INLET 1 1 1 2 3
3 RKX437A300 FILTER,AIR 2 1 1 1 2
4 RKX129A013 CAP 2
5 RKX129A014 HOLDER,FILTER 2 1 1 1 2
6 RKX133A300 PLATE,ORNAMENT 1 1 1 1 2
7-20 RKX435A302G GRILLE ASSY,AIR OUT 1 1 1 2 3
7 RKX435A303A GRILLE,AIR OUTLET 1
8 RKX436A001 FLAP(A) 1 UPPER
9 RKX436A002 FLAP(B) 1 LOWER
10-11 RKX436A006A LOUVER ASSY 2
10 RKX436A005B LOUVER 6
11 RKX129A015A PLATE,CONNECTING 1
12 RKW935C200 COLLAR 6
13 RKX129A010 BRACKET,MOTOR (A) 1 1 1 1 2
14 RKX144A001A LINK 1 1 1 1 2
15 RKX144A002 CRANK(A) 1 1 1 1 2
16 RKX144A003 CRANK(B) 1 1 1 1 2
17 SSA512T096 MOTOR,STEPPING 1 1 1 1 2
18 RKS504A100G HARNESS ASSY 1 1 1 1 2
19 SSA423A102 HOSE,DRAIN 1
20 SSA326A047 PLUG 1
21 RKX111A001 BASE ASSY 1 1 1 1 2
22 SSA511J218A MOTOR,AC 1 1 1 1 2
23 SSA431G047 IMPELLER 1 1 1 2 4
24 SSA923C114 BEARING,PLANE 1 1 1 1 2
25 RKX129A005 COVER, MOTOR 1 1 1 1 2
26 RKX032A001 PLATE,INSTALLATION 1 1 1 1 2
27 RKX132A001A LID 1 1 1 2 4
28 SSA913A007A SCREW, TAP 4
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 64
%4#'
















*'#6':%*%10641.
Page 65
SRK10CRV-S, S1
CRAE0280
END ITEM NO. : RMA002F060CA, 060CB
10 30 50 100 500 1000
1-4 RKX301A007K HEAT EXCH ASSY (AIR) 1 1 1 1 2
2 RKX315D005 HEADER ASSY 1
3 RKX129A016 BRACKET ASSY (L) 1
4 RKX315A004 DISTRIBUTOR ASSY 1
5-7 RKX321A001 PIPE ASSY 1
6 SSA323F091 UNION (SLD) 1 FOR GAS
7 SSA323F091A UNION (SLD) 1 FOR LIQ.
8 RKX129A001G PLATE ASSY, BAFFLE 1 1 1 1 2
9 RKX142A001A BOX, CONTROL 1
10 RKX505A001T PWB ASSY 1 2 2 4 8
11 SSA555B050C VARISTOR 1 1 1 1 2 Z
12 SSA564A132 FUSE (CURRENT) 1 1 1 2 4 F 3.15A
13 SSA551A163L SENSOR ASSY 1 1 1 2 4
14 RKV504A500 HARNESS ASSY (POWER) 1 1 1 1 2
15 SSA561B713 TERMINAL, BLOCK 1 1 1 2 2
16 RMA011G003 LABEL, WIRING 1
17 RKX503A301A DISPLAY ASSY 1 1 1 2 3
18 RKX505A007A PWB ASSY (DISPLAY ASSY) 1 2 2 4 8
19 RKJ941F001A SPRING, LEAF 1
20 RMA008A018C PARTS, STANDARD 1 FOR SRK10CRV-S
20 RMA008A018D PARTS, STANDARD 1 FOR SRK10CRV-S1
21 RKT437A011 FILTER, CLEAN 1 2 2 4 8
22 RKT437A005 FILTER,LIGHT CLEAN 1 2 2 4 8
23 RMA012A086 MANUAL, INSTRUCTION 1 FOR SRK10CRV-S
23 RMA012A087 MANUAL, INSTRUCTION 1 FOR SRK10CRV-S1
24 RKX502A001B CONTROL ASSY, REMOTE 1 2 3 5 10
25 RKN032A002C HOLDER (REMO-CON) 1 1 1 1 2
(26) RMA011F026T
LABEL MODEL NAME 1
FOR SRK10CRV-S
(26) RMA011F026V
LABEL MODEL NAME 1
FOR SRK10CRV-S1
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 66
CRAE0215
2
5
6
12
12
9
8
12
10
10
10
10
14
16
13
17
11
11
4
24
21
23
28
28
3
4
15
18
7
20
19
25
27
22
26
1
PANEL & FAN ASSY
Page 67
SRK13CRV-S, -S1
CRAE0215
END ITEM NO. : RMA002F060DA, 060DB
10 30 50 100 500 1000
1-6 RMA102A100 PANEL ASSY,FRONT 1 1 1 1 2
1 RKX122A300L PANEL,FRONT 1
2 RMA435A100 PANEL, AIR INLET 1 1 1 2 3
3 RKX437A300 FILTER,AIR 2 1 1 1 2
4 RKX129A013 CAP 2
5 RKX129A014 HOLDER,FILTER 2 1 1 1 2
6 RKX133A300 PLATE,ORNAMENT 1 1 1 1 2
7-20 RKX435A302J GRILLE ASSY,AIR OUT 1 1 1 2 3
7 RKX435A303A GRILLE,AIR OUTLET 1
8 RKX436A001 FLAP(A) 1 UPPER
9 RKX436A002 FLAP(B) 1 LOWER
10-11 RKX436A006A LOUVER ASSY 2
10 RKX436A005B LOUVER 6
11 RKX129A015A PLATE,CONNECTING 1
12 RKW935C200 COLLAR 6
13 RKX129A010 BRACKET,MOTOR (A) 1 1 1 1 2
14 RKX144A001A LINK 1 1 1 1 2
15 RKX144A002 CRANK(A) 1 1 1 1 2
16 RKX144A003 CRANK(B) 1 1 1 1 2
17 SSA512T096 MOTOR,STEPPING 1 1 1 1 2
18 RKS504A100G HARNESS ASSY 1 1 1 1 2
19 SSA423A102 HOSE,DRAIN 1
20 SSA326A047 PLUG 1
21 RKX111A001 BASE ASSY 1 1 1 1 2
22 SSA511J218A MOTOR,AC 1 1 1 1 2
23 SSA431G047 IMPELLER 1 1 1 2 4
24 SSA923C114 BEARING,PLANE 1 1 1 1 2
25 RKX129A005 COVER, MOTOR 1 1 1 1 2
26 RKX032A001 PLATE,INSTALLATION 1 1 1 1 2
27 RKX132A001A LID 1 1 1 2 4
28 SSA913A007A SCREW, TAP 4
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 68
%4#'
















*'#6':%*%10641.
Page 69
SRK13CRV-S, -S1
CRAE0280
END ITEM NO. : RMA002F060DA, 060DB
10 30 50 100 500 1000
1-4 RMA301A022 HEAT EXCH ASSY (AIR) 1 1 1 1 2
2 RKX315D005 HEADER ASSY 1
3 RKX129A016 BRACKET ASSY (L) 1
4 RKX315A004 DISTRIBUTOR ASSY 1
5-7 RKX321A001B PIPE ASSY 1
6 SSA323F088B UNION (SLD) 1 FOR GAS
7 SSA323F091A UNION (SLD) 1 FOR LIQ.
8 RKX129A001G PLATE ASSY, BAFFLE 1 1 1 1 2
9 RKX142A001A BOX, CONTROL 1
10 RKX505A001V PWB ASSY 1 2 2 4 8
11 SSA555B050C VARISTOR 1 1 1 1 2 Z
12 SSA564A132 FUSE (CURRENT) 1 1 1 2 4 F 3.15A
13 SSA551A163L SENSOR ASSY 1 1 1 2 4
14 RKV504A500 HARNESS ASSY (POWER) 1 1 1 1 2
15 SSA561B713 TERMINAL, BLOCK 1 1 1 2 2
16 RMA011G003 LABEL, WIRING 1
17 RKX503A301A DISPLAY ASSY 1 1 1 2 3
18 RKX505A007A PWB ASSY (DISPLAY ASSY) 1 2 2 4 8
19 RKJ941F001A SPRING, LEAF 1
20 RMA008A018C PARTS, STANDARD 1 FOR SRK13CRV-S
20 RMA008A018D PARTS, STANDARD 1 FOR SRK13CRV-S1
21 RKT437A011 FILTER, CLEAN 1 2 2 4 8
22 RKT437A005 FILTER,LIGHT CLEAN 1 2 2 4 8
23 RMA012A086 MANUAL, INSTRUCTION 1 FOR SRK13CRV-S
23 RMA012A087 MANUAL, INSTRUCTION 1 FOR SRK13CRV-S1
24 RKX502A001B CONTROL ASSY, REMOTE 1 2 3 5 10
25 RKN032A002C HOLDER (REMO-CON) 1 1 1 1 2
(26) RMA011F026W
LABEL MODEL NAME 1
FOR SRK13CRV-S
(26) RMA011F026Y
LABEL MODEL NAME 1
FOR SRK13CRV-S1
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 70
CRAE0213
4
14
14
9
8
14
10
10
12
12
18
20
24
15
22
11
21
17
22
13
2
5
1
31
28
30
35
35
6
3
4
16
22
25
21
19
23
7
27
26
32
34
33
29
PANEL & FAN ASSY
Page 71
SRK10CRS-S, S1, S2, S3, S4, S5, S
6
CRAE0213
END ITEM NO. : RMA002F060AA, AB, AC, AD, AF, AG, AH
10 30 50 100 500 1000
1-6 RMA102A100B PANEL ASSY,FRONT 1 1 1 1 2 FOR S, S3, S4, S5, S6
1-6 RMA102A100H PANEL ASSY,FRONT 1 1 1 1 2 FOR S1, S2
1 RKX122A300M PANEL,FRONT 1
2 RMA435A100A PANEL, AIR INLET 1 1 1 2 3 FOR S, S3, S4, S5, S6
2 RKX435A300C PANEL, AIR INLET 1 1 1 2 3 FOR S1, S2
3 RKX437A300 FILTER,AIR 2 1 1 1 2
4 RKX129A013 CAP 2
5 RKX129A014 HOLDER,FILTER 2 1 1 1 2
6 RKX133A300 PLATE,ORNAMENT 1 1 1 1 2
7-27 RKX435A302F GRILLE ASSY,AIR OUT 1 1 1 2 3
7 RKX435A303A GRILLE,AIR OUTLET 1
8 RKX436A001 FLAP(A) 1 UPPER
9 RKX436A002 FLAP(B) 1 LOWER
10-11 RKX436A003B LOUVER ASSY .(R) 1 1 1 2 2
10 RKX436A005B LOUVER 6
11 RKX129A008A PLATE,CONNECTING(R) 1
12-13 RKX436A004B LOUVER ASSY .(L) 1
12 RKX436A005B LOUVER 6
13 RKX129A009A PLATE,CONNECTING(L) 1
14 RKW935C200 COLLAR 6
15 RKX129A010 BRACKET,MOTOR (A) 1 1 1 1 2
16 RKX129A011 BRACKET,MOTOR (B) 1
17 RKX129A012 BRACKET,MOTOR (C) 1
18 RKX144A001A LINK 1 1 1 1 2
19 RKX144A002 CRANK(A) 1 1 1 1 2
20 RKX144A003 CRANK(B) 1 1 1 1 2
21 RKW144A204 CRANK(C) 2 1 1 1 2
22 SSA512T096 MOTOR,STEPPING 3 1 1 1 2
23 RKS504A100G HARNESS ASSY 1 1 1 1 2 FOR FLAP
24 RKS504A100 HARNESS ASSY 1 1 1 1 2 FOR LOUVER(R)
25 RKS504A100L HARNESS ASSY 1 1 1 1 2 FOR LOUVER(L)
26 SSA423A102 HOSE,DRAIN 1
27 SSA326A047 PLUG 1
28 RKX111A001 BASE ASSY 1 1 1 1 2
29 SSA511J218A MOTOR,AC 1 1 1 1 2
30 SSA431G047 IMPELLER 1 1 1 2 4
31 SSA923C114 BEARING,PLANE 1 1 1 1 2
32 RKX129A005 COVER, MOTOR 1 1 1 1 2
33 RKX032A001 PLATE,INSTALLATION 1 1 1 1 2
34 RKX132A001A LID 1 1 1 2 4
35 SSA913A007A SCREW, TAP 4
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 72
%4#'
















*'#6':%*%10641.
Page 73
SRK10CRS-S, S1, S2, S3, S4, S5, S
6
CRAE0280
END ITEM NO. : RMA002F060AA, AB, AC, AD, AF, AG, AH
10 30 50 100 500 1000
1-4 RKX301A007K HEAT EXCH ASSY (AIR) 1 1 1 1 2
2 RKX315D005 HEADER ASSY 1
3 RKX129A016 BRACKET ASSY (L) 1
4 RKX315A004 DISTRIBUTOR ASSY 1
5-7 RKX321A001 PIPE ASSY 1
6 SSA323F091 UNION (SLD) 1 FOR GAS
7 SSA323F091A UNION (SLD) 1 FOR LIQ.
8 RKX129A001G PLATE ASSY, BAFFLE 1 1 1 1 2
9 RKX142A001A BOX, CONTROL 1
10-12 RKX505A001W PWB ASSY 1 2 2 4 8
11 SSA555B050C VARISTOR 1 1 1 1 2 Z
12 SSA564A132 FUSE (CURRENT) 1 1 1 2 4 F 3.15A
13 SSA551A163L SENSOR ASSY 1 1 1 2 4
14 RKV504A500 HARNESS ASSY (POWER) 1 1 1 1 2
15 SSA561B713 TERMINAL, BLOCK 1 1 1 2 2
16 RMA011G004 LABEL, WIRING 1
17 RKX503A301 DISPLAY ASSY 1 1 1 2 3
18 RKX505A007 PWB ASSY (DISPLAY ASSY) 1 2 2 4 8
19 RKJ941F001A SPRING, LEAF 1
20 RMA008A018 PARTS, STANDARD 1 FOR S
20 RMA008A018A PARTS, STANDARD 1 FOR S1, S2
20 RMA008A018F PARTS, STANDARD 1 FOR S3
20 RMA008A018G PARTS, STANDARD 1 FOR S4
20 RMA008A018H PARTS, STANDARD 1 FOR S5
20 RMA008A018B PARTS, STANDARD 1 FOR S6
21 RKT437A011 FILTER, CLEAN 1 2 2 4 8 FOR S, S3, S4, S5, S6
21 RMA437A003 FILTER, CLEAN 1 2 2 4 8 FOR S1, S2
22 RKT437A005 FILTER,LIGHT CLEAN 1 2 2 4 8 FOR S, S3, S4, S5, S6
22 RMA437A004 FILTER, CLEAN 1 2 2 4 8 FOR S1, S2
23 RMA012A082 MANUAL, INSTRUCTION 1 FOR S, S6
23 RMA012A083 MANUAL, INSTRUCTION 1 FOR S1, S2
23 RMA012A088 MANUAL, INSTRUCTION 1 FOR S3
23 RMA012A089 MANUAL, INSTRUCTION 1 FOR S4
23 RMA012A090 MANUAL, INSTRUCTION 1 FOR S5
24 RKX502A001 CONTROL ASSY, REMOTE 1 2 3 5 10
25 RKN032A002C HOLDER (REMO-CON) 1 1 1 1 2
(26) RMA011F026 LABEL MODEL NAME 1 FOR S
(26) RMA011F026A LABEL MODEL NAME 1 FOR S1
(26) RMA011F026B LABEL MODEL NAME 1 FOR S2
(26) RMA011F026C LABEL MODEL NAME 1 FOR S3
(26) RMA011F026F LABEL MODEL NAME 1 FOR S4
(26) RMA011F026G LABEL MODEL NAME 1 FOR S5
(26) RMA011F026H LABEL MODEL NAME 1 FOR S6
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 74
CRAE0213
4
14
14
9
8
14
10
10
12
12
18
20
24
15
22
11
21
17
22
13
2
5
1
31
28
30
35
35
6
3
4
16
22
25
21
19
23
7
27
26
32
34
33
29
PANEL & FAN ASSY
Page 75
SRK13CRS-S, S1, S2, S3, S4, S5, S
6
CRAE0213
END ITEM NO. : RMA002F060BA, BB, BC, BD, BF, BG, BH
10 30 50 100 500 1000
1-6 RMA102A100B PANEL ASSY,FRONT 1 1 1 1 2 FOR S, S3, S4, S5, S6
1-6 RMA102A100H PANEL ASSY,FRONT 1 1 1 1 2 FOR S1, S2
1 RKX122A300M PANEL,FRONT 1
2 RMA435A100A PANEL, AIR INLET 1 1 1 2 3 FOR S, S3, S4, S5, S6
2 RKX435A300C PANEL, AIR INLET 1 1 1 2 3 FOR S1, S2
3 RKX437A300 FILTER,AIR 2 1 1 1 2
4 RKX129A013 CAP 2
5 RKX129A014 HOLDER,FILTER 2 1 1 1 2
6 RKX133A300 PLATE,ORNAMENT 1 1 1 1 2
7-27 RKX435A302H GRILLE ASSY,AIR OUT 1 1 1 2 3
7 RKX435A303A GRILLE,AIR OUTLET 1
8 RKX436A001 FLAP(A) 1 UPPER
9 RKX436A002 FLAP(B) 1 LOWER
10-11 RKX436A003B LOUVER ASSY .(R) 1 1 1 2 2
10 RKX436A005B LOUVER 6
11 RKX129A008A PLATE,CONNECTING(R) 1
12-13 RKX436A004B LOUVER ASSY .(L) 1
12 RKX436A005B LOUVER 6
13 RKX129A009A PLATE,CONNECTING(L) 1
14 RKW935C200 COLLAR 6
15 RKX129A010 BRACKET,MOTOR (A) 1 1 1 1 2
16 RKX129A011 BRACKET,MOTOR (B) 1
17 RKX129A012 BRACKET,MOTOR (C) 1
18 RKX144A001A LINK 1 1 1 1 2
19 RKX144A002 CRANK(A) 1 1 1 1 2
20 RKX144A003 CRANK(B) 1 1 1 1 2
21 RKW144A204 CRANK(C) 2 1 1 1 2
22 SSA512T096 MOTOR,STEPPING 3 1 1 1 2
23 RKS504A100G HARNESS ASSY 1 1 1 1 2 FOR FLAP
24 RKS504A100 HARNESS ASSY 1 1 1 1 2 FOR LOUVER(R)
25 RKS504A100L HARNESS ASSY 1 1 1 1 2 FOR LOUVER(L)
26 SSA423A102 HOSE,DRAIN 1
27 SSA326A047 PLUG 1
28 RKX111A001 BASE ASSY 1 1 1 1 2
29 SSA511J218A MOTOR,AC 1 1 1 1 2
30 SSA431G047 IMPELLER 1 1 1 2 4
31 SSA923C114 BEARING,PLANE 1 1 1 1 2
32 RKX129A005 COVER, MOTOR 1 1 1 1 2
33 RKX032A001 PLATE,INSTALLATION 1 1 1 1 2
34 RKX132A001A LID 1 1 1 2 4
35 SSA913A007 SCREW, TAP 4
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 76
%4#'
















*'#6':%*%10641.
Page 77
SRK13CRS-S, S1, S2, S3, S4, S5, S
6
CRAE0280
END ITEM NO. : RMA002F060BA, BB, BC, BD, BF, BG, BH
10 30 50 100 500 1000
1-4 RMA301A022 HEAT EXCH ASSY (AIR) 1 1 1 1 2
2 RKX315D005 HEADER ASSY 1
3 RKX129A016 BRACKET ASSY (L) 1
4 RKX315A004 DISTRIBUTOR ASSY 1
5-7 RKX321A001B PIPE ASSY 1
6 SSA323F088B UNION (SLD) 1 FOR GAS
7 SSA323F091A UNION (SLD) 1 FOR LIQ.
8 RKX129A001G PLATE ASSY, BAFFLE 1 1 1 1 2
9 RKX142A001A BOX, CONTROL 1
10-12 RKX505A001Y PWB ASSY 1 2 2 4 8
11 SSA555B050C VARISTOR 1 1 1 1 2 Z
12 SSA564A132 FUSE (CURRENT) 1 1 1 2 4 F 3.15A
13 SSA551A163L SENSOR ASSY 1 1 1 2 4
14 RKV504A500 HARNESS ASSY (POWER) 1 1 1 1 2
15 SSA561B713 TERMINAL, BLOCK 1 1 1 2 2
16 RMA011G004 LABEL, WIRING 1
17 RKX503A301 DISPLAY ASSY 1 1 1 2 3
18 RKX505A007 PWB ASSY (DISPLAY ASSY) 1 2 2 4 8
19 RKJ941F001A SPRING, LEAF 1
20 RMA008A018 PARTS, STANDARD 1 FOR S
20 RMA008A018A PARTS, STANDARD 1 FOR S1, S2
20 RMA008A018F PARTS, STANDARD 1 FOR S3
20 RMA008A018G PARTS, STANDARD 1 FOR S4
20 RMA008A018H PARTS, STANDARD 1 FOR S5
20 RMA008A018B PARTS, STANDARD 1 FOR S6
21 RKT437A011 FILTER,CLEAN 1 2 2 4 8 FOR S, S3, S4, S5, S6
21 RMA437A003 FILTER,CLEAN 1 2 2 4 8 FOR S1, S2
22 RKT437A005 FILTER,LIGHT CLEAN 1 2 2 4 8 FOR S, S3, S4, S5, S6
22 RMA437A004 FILTER,CLEAN 1 2 2 4 8 FOR S1, S2
23 RMA012A082 MANUAL, INSTRUCTION 1 FOR S, S6
23 RMA012A083 MANUAL, INSTRUCTION 1 FOR S1, S2
23 RMA012A088 MANUAL, INSTRUCTION 1 FOR S3
23 RMA012A089 MANUAL, INSTRUCTION 1 FOR S4
23 RMA012A090 MANUAL, INSTRUCTION 1 FOR S5
24 RKX502A001 CONTROL ASSY, REMOTE 1 2 3 5 10
25 RKN032A002C HOLDER (REMO-CON) 1 1 1 1 2
(26) RMA011F026J LABEL MODEL NAME 1 FOR S
(26) RMA011F026K LABEL MODEL NAME 1 FOR S1
(26) RMA011F026L LABEL MODEL NAME 1 FOR S2
(26) RMA011F026N LABEL MODEL NAME 1 FOR S3
(26) RMA011F026P LABEL MODEL NAME 1 FOR S4
(26) RMA011F026R LABEL MODEL NAME 1 FOR S5
(26) RMA011F026S LABEL MODEL NAME 1 FOR S6
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 78
CRBE0290
6
11
9
10
13
14
3
15
12
2
4
8
7
5
1
7
7
PANEL & FAN ASSY
Page 79
SRC10CRV-S, -S1
CRBE0290
END ITEM NO. : RMC003F060CA, 060CB
10 30 50 100 500 1000
1 RCV122A006C PANEL ASSY, FRONT 1 1 1 1 2
2 RCV123A001 PANEL ASSY,SIDE(R) 1 1 1 1 2
3 RCV124A500A PANEL ASSY, TOP 1 1 1 1 2
4 RCV132A003 COVER ASSY SERVICE 1 1 1 2 4
5 RCV435A002 GRILLE ASSY,AIR OUT 1 1 1 2 3
6 SSA944B036B HANDLE 1
7 SSA913A034F SCREW, TAP 25
8 SSA913A034G SCREW, TAP 1
9 RCV116A005B BRACKET ASSY 1
10 SSA511B822 MOTOR,AC 1 2 2 4 8
11 RCV116A003 BRACKET MOTOR(U) 1
12 RCV141A500 PLATE,BAFFLE 1
13 SSA431B254 PROPELLER 1 1 1 2 4
14 SSA914B007AC NUT, TH 1
15 RCV111A001F BASE ASSY 1 1 1 1 2
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 80
CRBE0420
1
21
3
2
4
5
6
8
7
19
13
22
20
18
9
10
11
14
15
16
17
23
12
(GAS)
(LIQ.)
HEAT EXCH. & CONTROL
Page 81
SRC10CRV-S, -S1
CRBE0420
END ITEM NO. : RMC003F060CA, 060CB
10 30 50 100 500 1000
1-3 RMC301A082 HEAT EXCH ASSY (AIR) 1 1 1 1 2
2 RMC321A262 PIPE ASSY 1
3 RMC321A263 PIPE ASSY 1
4-5 RMC304A041 PIPING ASSY 1 1 1 1 2
4 RMC315B031 CAPILLARY 1
5 RMC315B032 CAPILLARY,SUB 1
6 RCS116A004 BRACKET(VALVE) 1
7 RCS381A004B VALVE,SERVICE(1/4" ) 1 1 1 1 2 LIQ.
8 RCV381A001A VALVE,SERVICE(3/8" ) 1 1 1 1 2 GAS
9 RMC201A064 COMPRESSOR ASSY 1 1 2 3 8
10 SSA914C013A NUT, FLANGE 3
11 RMC941C052 CUSHION, RUBBER 3
12 RMC154D016 INSULATION, COMP 1
13 RMC932C005 GASKET, COVER 1
14 RMC947K006 COVER, TERMINAL 1 1 1 2 4
15 RMC914C003 NUT, FLANGE 1
16 SSA552A842 CAPACITOR, RUNNING 1 1 1 1 2
17 SSA552A843G CAPACITOR, RUNNING 1 1 1 1 2
18 RMC533B011 PROTECTOR, MOTOR 1 1 1 1 2
19 SSA561B669 BLOCK, TERMINAL 1 1 1 2 2
20 RMC504A010C WIRING ASSY 1 1 1 1 2 FOR COMP.
21 RCS142A500 COVER (TB) 1
22 RCV116A500 BRACKET (TB) 1
23 SSA937A812 CLAMP 1
(24) RMC011F029R LABEL, MODEL NAME 1 FOR SRC10CRV-S
(24) RMC011F029S LABEL, MODEL NAME 1 FOR SRC10CRV-S1
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 82
CRBE0290
6
11
9
10
13
14
3
15
12
2
4
8
7
5
1
7
7
PANEL & FAN ASSY
Page 83
SRC13CRV-S, S1
CRBE0290
END ITEM NO. : RMC003F060DA, DB
10 30 50 100 500 1000
1 RCV122A005B PANEL ASSY, FRONT 1 1 1 1 2
2 RCV123A005B PANEL ASSY SIDE(R) 1 1 1 1 2
3 RCV124A500A PANEL ASSY,TOP 1 1 1 1 2
4 RCV132A004 COVER ASSY SERVICE 1 1 1 2 4
5 RCV435A002 GRILLE AIR OUTLET 1 1 1 2 3
6 SSA944B036B HANDLE 1
7 SSA913A034F SCREW, TAP 25
8 SSA913A034G SCREW, TAP 1
9 RCV116A006 BRACKET ASSY 1
10 SSA511B823 MOTOR,AC 1 2 2 4 8
11 RCV116A003 BRACKET,MOTOR(U) 1
12 RCV141A501 PLATE,BAFFLE 1
13 SSA431B254 PROPELLER 1 1 1 2 4
14 SSA914B007AC NUT, TH 1
15 RCV111A001D BASE ASSY 1 1 1 1 2
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 84
CRBE0288a
1
22
3
2
4
7
9
8
20
15
23
21
10
11
12
16
17
18
19
24
13
(GAS)
(LIQ.)
14
HEAT EXCH. & CONTROL
Page 85
SRC13CRV-S, S1
CRBE0288a
END ITEM NO. : RMC003F060DA, DB
10 30 50 100 500 1000
1-3 RMC301A087 HEAT EXCH ASSY (AIR) 1 1 1 1 2 FOR SPARE PART
2 RMC321A292 PIPE ASSY 1
3 RMC321A295 PIPE ASSY 1
4-5 RMC304A051 PIPING ASSY (EXPAN) 1 1 1 1 2
4 RMC315B046 CAPILLARY 1
(5) RMC321A299 PIPE (DISCH) 1
(6) RMC321A300 PIPE (SUNTION) 1
7 RCS116A004 BRACKET (VALVE) 1
8 RCS381A004B VALVE, SERVICE (1/4") 1 1 1 1 2 LIQ.
9 RCV381A002 VALVE, SERVICE (1/2") 1 1 1 1 2 GAS
10 RMC201A065 COMPRESSOR ASSY 1 1 2 3 8
11 SSA914C013A NUT, FLANGE 3
12 RMC941C003 CUSHION, RUBBER 3
13 RMC154D017 INSULATION, COMP 1 BODY
14 RMC154D018 INSULATION, COMP 1 TOP
15 RMC932C003 GASKET, COVER 1
16 RMC947K003 COVER, TERMINAL 1 1 1 2 4
17 SSA914C016 NUT, FLANGE 1
18 SSA552A842A CAPACITOR, RUNNING 1 1 1 1 2 FOR MOTOR
19 SSA552A843J CAPACITOR, RUNNING 1 1 1 1 2 FOR COMP.
20 SSA561B669 BLOCK, TERMINAL 1 1 1 2 2
21 RMC504A010D WIRING ASSY 1 1 1 1 2 FOR COMP.
22 RCS142A500 COVER (TB) 1
23 RCV116A500 BRACKET (TB) 1
24 SSA937B924 CLAMP 1
(25) RMC011F029T LABEL, MODEL NAME 1 FOR SRC13CRV-S
(25) RMC011F029V LABEL, MODEL NAME 1 FOR SRC13CRV-S1
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 86
CRBE0290
6
11
9
10
13
14
3
15
12
2
4
8
7
5
1
7
7
PANEL & FAN ASSY
Page 87
SRC10CRS-S, S1, S2, S3, S4, S5, S
6
CRBE0290
END ITEM NO. : RMC003F060AA, AB, AC, AD, AF, AG, AH
10 30 50 100 500 1000
1 RCV122A006C PANEL FRONT 1 1 1 1 2
2 RCV123A001 PANEL SIDE(R) 1 1 1 1 2
3 RCV124A500A PANEL ASSY, TOP 1 1 1 1 2
4 RCV132A003 COVER ASSY SERVICE 1 1 1 2 4
5 RCV435A002 GRILLE ASSY,AIR OUT 1 1 1 2 3
6 SSA944B036B HANDLE 1
7 SSA913A034F SCREW, TAP 25
8 SSA913A034G SCREW, TAP 1
9 RCV116A005B BRACKET ASSY 1
10 SSA511B822 MOTOR,AC 1 2 2 4 8
11 RCV116A003 BRACKET MOTOR(U) 1
12 RCV141A500 PLATE,BAFFLE 1
13 SSA431B254 PROPELLER 1 1 1 2 4
14 SSA914B007AC NUT, TH 1
15 RCV111A001F BASE ASSY 1 1 1 1 2
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 88
CRBE0420
1
21
3
2
4
5
6
8
7
19
13
22
20
18
9
10
11
14
15
16
17
23
12
(GAS)
(LIQ.)
HEAT EXCH. & CONTROL
Page 89
SRC10CRS-S, S1, S2, S3, S4, S5, S
6
CRBE0420
END ITEM NO. : RMC003F060AA, AB, AC, AD, AF, AG, AH
10 30 50 100 500 1000
1-3 RMC301A082 HEAT EXCH ASSY (AIR) 1 1 1 1 2
2 RMC321A262 PIPE ASSY 1
3 RMC321A263 PIPE ASSY 1
4-5 RMC304A041 PIPING ASSY 1 1 1 1 2
4 RMC315B031 CAPILLARY 1
5 RMC315B032 CAPILLARY,SUB 1
6 RCS116A004 BRACKET(VALVE) 1
7 RCS381A004B VALVE,SERVICE(1/4" ) 1 1 1 1 2 LIQ.
8 RCV381A001A VALVE,SERVICE(3/8" ) 1 1 1 1 2 GAS
9 RMC201A064 COMPRESSOR ASSY 1 1 2 3 8
10 SSA914C013A NUT, FLANGE 3
11 RMC941C052 CUSHION, RUBBER 3
12 RMC154D016 INSULATION, COMP 1
13 RMC932C005 GASKET, COVER 1
14 RMC947K006 COVER, TERMINAL 1 1 1 2 4
15 RMC914C003 NUT, FLANGE 1
16 SSA552A842 CAPACITOR, RUNNING 1 1 1 1 2 FOR MOTOR
17 SSA552A843G CAPACITOR, RUNNING 1 1 1 1 2 FOR COMP.
18 RMC533B011 PROTECTOR, MOTOR 1 1 1 1 2
19 SSA561B669 BLOCK, TERMINAL 1 1 1 2 2
20 RMC504A010C WIRING ASSY 1 1 1 1 2 FOR COMP.
21 RCS142A500 COVER (TB) 1
22 RCV116A500 BRACKET (TB) 1
23 SSA937A812 CLAMP 1
(24) RMC011F029 LABEL, MODEL NAME 1 FOR SRC10CRS-S
(24) RMC011F029A LABEL, MODEL NAME 1 FOR SRC10CRS-S1
(24) RMC011F029B LABEL, MODEL NAME 1 FOR SRC10CRS-S2
(24) RMC011F029C LABEL, MODEL NAME 1 FOR SRC10CRS-S3
(24) RMC011F029D LABEL, MODEL NAME 1 FOR SRC10CRS-S4
(24) RMC011F029F LABEL, MODEL NAME 1 FOR SRC10CRS-S5
(24) RMC011F029G LABEL, MODEL NAME 1 FOR SRC10CRS-S6
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 90
CRBE0290
6
11
9
10
13
14
3
15
12
2
4
8
7
5
1
7
7
PANEL & FAN ASSY
Page 91
SRC13CRS-S, S1, S2, S3, S4, S5, S
6
CRBE0290
END ITEM NO. : RMC003F060BA, BB, BC, BD, BF, BG, BH
10 30 50 100 500 1000
1 RCV122A005B PANEL ASSY, FRONT 1 1 1 1 2
2 RCV123A005B PANEL ASSY, SIDE(R) 1 1 1 1 2
3 RCV124A500A PANEL ASSY,TOP 1 1 1 1 2
4 RCV132A004 COVER ASSY SERVICE 1 1 1 2 4
5 RCV435A002 GRILLE AIR OUTLET 1 1 1 2 3
6 SSA944B036B HANDLE 1
7 SSA913A034F SCREW, TAP 25
8 SSA913A034G SCREW, TAP 1
9 RCV116A006 BRACKET ASSY 1
10 SSA511B823 MOTOR,AC 1 2 2 4 8
11 RCV116A003 BRACKET,MOTOR(U) 1
12 RCV141A501 PLATE,BAFFLE 1
13 SSA431B254 PROPELLER 1 1 1 2 4
14 SSA914B007AC NUT, TH 1
15 RCV111A001D BASE ASSY 1 1 1 1 2
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 92
CRBE0288a
1
22
3
2
4
7
9
8
20
15
23
21
10
11
12
16
17
18
19
24
13
(GAS)
(LIQ.)
14
HEAT EXCH. & CONTROL
Page 93
SRC13CRS-S, S1, S2, S3, S4, S5, S
6
CRBE0288a
END ITEM NO. : RMC003F060BA, BB, BC, BD, BF, BG, BH
10 30 50 100 500 1000
1-3 RMC301A087 HEAT EXCH ASSY (AIR) 1 1 1 1 2 FOR SPARE PART
2 RMC321A292 PIPE ASSY 1
3 RMC321A295 PIPE ASSY 1
4-5 RMC304A051 PIPING ASSY (EXPAN) 1 1 1 1 2
4 RMC315B046 CAPILLARY 1
(5) RMC321A299 PIPE (DISCH) 1
(6) RMC321A300 PIPE (SUNTION) 1
7 RCS116A004 BRACKET (VALVE) 1
8 RCS381A004B VALVE, SERVICE (1/4") 1 1 1 1 2 LIQ.
9 RCV381A002 VALVE, SERVICE (1/2") 1 1 1 1 2 GAS
10 RMC201A065 COMPRESSOR ASSY 1 1 2 3 8
11 SSA914C013A NUT, FLANGE 3
12 RMC941C003 CUSHION, RUBBER 3
13 RMC154D017 INSULATION, COMP 1 BODY
14 RMC154D018 INSULATION, COMP 1 TOP
15 RMC932C003 GASKET, COVER 1
16 RMC947K003 COVER, TERMINAL 1 1 1 2 4
17 SSA914C016 NUT, FLANGE 1
18 SSA552A842A CAPACITOR, RUNNING 1 1 1 1 2 FOR MOTOR
19 SSA552A843J CAPACITOR, RUNNING 1 1 1 1 2 FOR COMP.
20 SSA561B669 BLOCK, TERMINAL 1 1 1 2 2
21 RMC504A010D WIRING ASSY 1 1 1 1 2 FOR COMP.
22 RCS142A500 COVER (TB) 1
23 RCV116A500 BRACKET (TB) 1
24 SSA937B924 CLAMP 1
(25) RMC011F029H LABEL, MODEL NAME 1 FOR SRC13CRS-S
(25) RMC011F029J LABEL, MODEL NAME 1 FOR SRC13CRS-S1
(25) RMC011F029K LABEL, MODEL NAME 1 FOR SRC13CRS-S2
(25) RMC011F029L LABEL, MODEL NAME 1 FOR SRC13CRS-S3
(25) RMC011F029M LABEL, MODEL NAME 1 FOR SRC13CRS-S4
(25) RMC011F029N LABEL, MODEL NAME 1 FOR SRC13CRS-S5
(25) RMC011F029P LABEL, MODEL NAME 1 FOR SRC13CRS-S6
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 94
Loading...