• This manual describes only
service data of the indoor units.
Model name
indication
ON/OFF
TOO
TOO
WARM
COOL
FAN
SELECT
AUTO COOL
TIME
VANE
DRY
HEAT
MODE
RESET
REMOTE CONTROLLER
INDOOR UNIT
WIRED REMOTE CONTROLLER
(Option)
CONTENTS
1. REFERENCE MANUAL
2. PARTS NAMES AND FUNCTIONS
3. SPECIFICATIONS
4. OUTLINES AND DIMENSIONS
5. WIRING DIAGRAM
6.
REFRIGERANT SYSTEM DIAGRAM
7. TROUBLESHOOTING
8. 4-WAY AIR FLOW SYSTEM
9. DISASSEMBLY PROCEDURE
......................
...............................
............................
.......................
..............
..........
PARTS CATALOG (OCB564)
.....
...........
.....
2
2
6
8
11
12
13
27
29
Page 2
Use the specied refrigerant only
OCH564
Never use any refrigerant other than that specied.
Doing so may cause a burst, an explosion, or re when the unit is being used, serviced, or disposed of.
Correct refrigerant is specied in the manuals and on the spec labels provided with our products.
We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused
by failure to follow the instructions.
1
REFERENCE MANUAL
1-1. OUTDOOR UNIT’S SERVICE MANUAL
Service Ref.Service Manual No.
SUZ-KA25/35/50VA4.TH
OCH545/OCB545
1-2. TECHNICAL DATA BOOK
Series (Outdoor unit)Data Book No.
SUZ-KA
•
VA4OCS26
2
PARTS NAMES AND FUNCTIONS
2-1. INDOOR UNIT
Horizontal Air Outlet
Sets horizontal airflow automatically
during cooling or dehumidifying.
Filter
Removes dust and pollutants
from drawn in air.
Grille
Auto Air Swing Vane
Disperses airflow up and
down and adjusts the angle
of airflow direction.
Air Intake
Draws in air from room.
Page 3
2-2. WIRELESS REMOTE CONTROLLER
OCH564
TEMPERATURE
SETTING button
To set any
h
temperature.
desired room
ON/OFF
TOO
WARM
TOO
COOL
ON / OFF button
To start and to stop operation.
MODE SELECT button
To change the operation
mode; Auto, Cooling ,
Heating and Drying . (SLZ)
AUTO COOL
DRY
HEAT
MODE
FAN
VANE
SELECT
TIME
RESET
TIMER SELECT button
To set time to start or stop
unit operation.
FAN SPEED button
To set fan speed to Low,
Medium or High.
VANE CONTROL button
To change the airflow
direction.
Attention:
• Avoid pushing buttons with fingernails and other sharp objects. Sharp objects may damage remote controller.
33
Page 4
2-3. Wired remote controller (Option) PAR-31MAA
OCH564
The functions which can be used are restricted according to each model.
Display
Full mode
6
7
8
9
10
1
11
The main display can be displayed in two different modes: "Full" and "Basic."
The initial setting is "Full."
15
13
14
12
Room
CoolAuto
ModeTemp.Fan
Set temp.
21
Basic mode
Cool
1
ModeTemp.Fan
Note: All icons are displayed for explanation.
1 Operation mode
Indoor unit operation mode appears here.
181716
3
Fri
19
20
2 Preset temperature
Preset temperature appears here.
3 Clock
(See the Installation Manual.)
Current time appears here.
4 Fan speed
4
Fan speed setting appears here.
5 Button function guide
Functions of the corresponding buttons appear
2
5
here.
6
Appears when the ON/OFF operation is centrally
controlled.
7
2
3
Fri
AutoSet temp.
4
Appears when the operation mode is centrally
controlled.
8
Appears when the preset temperature is centrally
controlled.
9
Appears when the filter reset function is centrally
controlled.
10
Indicates when filter needs maintenance.
11 Room temperature
5
(See the Installation Manual.)
Current room temperature appears here.
12
Appears when the buttons are locked.
13
Appears when the On/Off timer or Night setback
function is enabled.
14
Appears when the Weekly timer is enabled.
15
Appears while the units are operated in the
energy-save mode.
16
Appears while the outdoor units are operated in
the silent mode.
17
Appears when the built-in thermistor on the
remote controller is activated to monitor the
room temperature (a).
appears when the thermistor on the
indoor unit is activated to monitor the room
temperature.
18
Indicates the vane setting.
19
Indicates the louver setting.
20
Indicates the ventilation setting.
21
Appears when the preset temperature range is
restricted.
Controller interface
*
1234
Function buttons
10987
• When the backlight is off, pressing any button turns the backlight on and
does not perform its function. (except for the ON/OFF button)
• Most settings (except ON/OFF, mode, fan speed, temperature) can be
made from the Menu screen.
1 ON/OFF button
Press to turn ON/OFF the indoor unit.
2 SELECT button
Press to save the setting.
3 RETURN button
5
Press to return to the previous screen.
4 MENU button
Press to bring up the Main menu.
6
5 Backlit LCD
Operation settings will appear.
When the backlight is off, pressing any
button turns the backlight on and it
will stay lit for a certain period of time
depending on the screen.
6 ON/OFF lamp
This lamp lights up in green while the unit
is in operation. It blinks while the remote
controller is starting up or when there is
an error.
The functions of the function buttons
change depending on the screen. Refer
to the button function guide that appears
at the bottom of the LCD for the functions
they serve on a given screen.
When the system is centrally controlled,
the button function guide that
corresponds to the locked button will not
appear.
Main displayMain menu
Room
Set temp.
CoolAuto
Mode Temp.Fan
7 8 9 07 8 9 0
Function guide
Main
Fri
Main menu
Vane·Louver·Vent. (Lossnay)
High power
Timer
Weekly timer
OU silent mode
Main display:
CursorPage
7 Function button F1
Main display: Press to change the operation
mode.
Main menu: Press to move the cursor down.
8 Function button F2
Main
display
Main menu: Press to move the cursor up.
: Press to decrease temperature.
9 Function button F3
Main
display
Main menu: Press to go to the previous page.
: Press to increase temperature.
10 Function button F4
Main
display
Main menu: Press to go to the next page.
: Press to change the fan speed.
45
Page 5
Main menu list
OCH564
Setting and display itemsSetting details
Vane · Louver · Vent.
(Lossnay)
High powerUse to reach the comfortable room temperature quickly.
TimerOn/Off timer*Use to set the operation On/Off times.
Auto-Off timerUse to set the Auto-Off time.
Filter informationUse to check the lter status.
Error informationUse to check error information when an error occurs.
Weekly timer*Use to set the weekly operation On / Off times.
Energy saving Auto returnUse to get the units to operate at the preset temperature after performing energy-save operation for a specied
Schedule*Set the start/stop times to operate the units in the energy-save mode for each day of the week, and set the
Night setback*Use to make Night setback settings.
RestrictionTemp. rangeUse to restrict the preset temperature range.
Operation lockUse to lock selected functions.
MaintenanceAuto descending panel Auto descending panel (Optional parts) Up / Down you can do.
Manual vane angleUse to set the vane angle for each vane to a xed position.
Initial settingMain/SubWhen connecting two remote controllers, one of them needs to be designated as a sub controller.
ClockUse to set the current time.
Main displayUse to switch between "Full" and "Basic" modes for the Main display.
ContrastUse to adjust screen contrast.
Initial settingDisplay detailsMake the settings for the remote controller related items as necessary.
Auto modeWhether or not to use the AUTO mode can be selected by using the button.
Administrator
word
Language selectionUse to select the desired language.
ServiceTest runSelect "Test run" from the Service menu to bring up the Test run menu.
Input maintenanceSelect "Input maintenance Info." from the Service menu to bring up the Maintenance information screen.
Function settingMake the settings for the indoor unit functions via the remote controller as necessary.
LOSSNAY setting
(City Multi only)
CheckError history: Display the error history and execute "delete error history".
Self checkError history of each unit can be checked via the remote controller.
Maintenance password Take the following steps to change the maintenance password.
Remote controller
check
* Clock setting is required.
pass-
Use to set the vane angle.
• Select a desired vane setting from ve different settings.
Use to turn ON / OFF the louver.
• Select a desired setting from "ON" and "OFF."
Use to set the amount of ventilation.
• Select a desired setting from "Off," "Low," and "High."
• Units can be operated in the High-power mode for up to 30 minutes.
• Time can be set in 5-minute increments.
• Time can be set to a value from 30 to 240 in 10-minute increments.
• The lter sign can be reset.
• Check code, error source, refrigerant address, unit model, manufacturing number, contact information (dealer's phone
number) can be displayed.
(The unit model, manufacturing number, and contact information need to be registered in advance to be displayed.)
• Up to eight operation patterns can be set for each day.
(Not valid when the On/Off timer is enabled.)
time period.
• Time can be set to a value from 30 and 120 in 10-minute increments.
(This function will not be valid when the preset temperature ranges are restricted.)
energy-saving rate.
• Up to four energy-save operation patterns can be set for each day.
• Time can be set in 5-minute increments.
• Energy-saving rate can be set to a value from 0% and 50 to 90% in 10% increments.
Select "Yes" to enable the setting, and "No" to disable the setting. The temperature range and the start/stop times can be set.
•
• Different temperature ranges can be set for different operation modes.
• The locked functions cannot be operated.
• The initial setting is "Full."
Clock: The initial settings are "Yes" and "24h" format.
Temperature: Set either Celsius (°C) or Fahrenheit (°F).
Room temp. : Set Show or Hide.
Auto mode: Set the Auto mode display or Only Auto display.
This setting is valid only when indoor units with the AUTO mode function are connected.
The administrator password is required to make the settings for the following items.
• Restriction setting • Outdoor unit silent mode setting • Night set back
• Test run • Drain pump test run
The following settings can be made from the Maintenance Information screen.
• Model name input • Serial No. input • Dealer information input
This setting is required only when the operation of City Multi units is interlocked with LOSSNAY units.
Refrigerant leak check: Refrigerant leaks can be judged.
Smooth maintenance: The indoor and outdoor maintenance data can be displayed.
Request cord: Details of the operation data including each thermistor temperature and error history can be checked.
When the remote controller does not work properly, use the remote controller checking function to troubleshoot the problem.
5
Page 6
3
OCH564
SPECIFICATIONS
Indoor service ref.
Mode
Power supply (phase, cycle, voltage)
Input
Running current*
Dew prevention heater
Power factor*
Electrical
data
Fan motor output*
Airflow (Low/Midium/High)
K/h
Noise level (Low/Midium/High)
Width
snoisnemiD
Depth
Height
Weight
NOTE : Test conditions are based on ISO 5151.
Cooling : Indoor D.B. 27˚C W.B. 19˚C
Outdoor D.B. 35˚C W.B. 24˚C
Heating : Indoor D.B. 20˚C W.B. 15˚C
Outdoor D.B. 7˚C W.B. 6˚C
Refrigerant piping length (one way): 5m
*Measured under rated operating frequency
Specifications and rating conditions of main electric parts
INDOOR UNIT
Item
Fuse
Vane motor
Terminal block
Cord Heater
Service ref.
(FUSE)
(MV)
(TB)
(H2)
SLZ-KA25VAL3.TH(-ER)
TO OUTDOOR UNIT: 3P TO WIRED REMOTE CONTROLLER: 2P
SLZ-KA35VAL3.TH(-ER)
250V 6.3A
MSBPC20 12V 250"
240V AC 15W
SLZ-KA50VAL3.TH(-ER)
Page 7
NOISE CRITERION CURVES
OCH564
SLZ-KA25VAL3.TH(-ER)
SLZ-KA35VAL3.TH(-ER)
NOTCH
High
Medium
Low
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
HEARING FOR
CONTINUOUS
NOISE
10
631252505001000200040008000
BAND CENTER FREQUENCIES, Hz
<50Hz>
SPL(dB)33LINE
38
29
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
SLZ-KA50VAL3.TH(-ER)
NOTCH
High
Medium
Low
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
HEARING FOR
CONTINUOUS
NOISE
10
631252505001000200040008000
BAND CENTER FREQUENCIES, Hz
<50Hz>
SPL(dB)34LINE
39
30
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
UNIT
CEILING
1.5m
MICROPHONE
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher
by about 2 dB than the indicated level during cooling and heating operation.
• Area in which the remote controller is not exposed to direct sunlight
• Area in which there is no heating source nearby
• Area in which the remote controller is not exposed to cold (or hot) winds
• Area in which the remote controller can be operated easily
• Area in which the remote controller is beyond the reach of children
Installation method
1 Attach the remote controller holder to the desired location using 2 tapping screws.
2 Insert the lower end of the controller into the holder.A Wireless remote controller (Accessory) B WallC Remote controller holder (Accessory)
D Fixing screw (Accessory)
• The signal can travel up to approximately 7 meters (in a straight line) within 45
degrees to both right and left of the center line of the receiver.
In addition, the signal may not be received if there is interference of light of fluorescent
lights or strong sunlight.
Condenser/evaporator
temperature thermistor
(TH23)
Pipe temperature
thermistor/liquid
(TH22)
#50
Refrigerant GAS pipe connection
(Flare)
Refrigerant LIQUID pipe connection
(Flare)
Strainer
#50
Refrigerant flow in cooling
Refrigerant flow in heating
1213
Page 13
7
OCH564
TROUBLESHOOTING
7-1. CAUTIONS ON TROUBLESHOOTING
(1) Before troubleshooting, check the followings:
Check the power supply voltage.
Check that the indoor/outdoor connecting wire is correct.
(2) Take care of the followings during servicing.
Before servicing the air conditioner, be sure to turn off the remote controller first to stop the main unit, and then turn
off the breaker.
When removing the indoor controller board, hold the edge of the board with care NOT to apply stress on the
components.
When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wire
7-2. SELF-CHECK
Wireless remote controller
56
24
ON/OFF
AUTO COOL
DRY
HEAT
MODE
TOO
WARM
FAN
VANE
h
TOO
COOL
SELECT
TIME
RESET
24
23
7-2-1. WIRED REMOTE CONTROLLER
For details, refer to the installation manual that comes with each remote controller.
7-2-2. WIRELESS REMOTE CONTROLLER
1 Turn ON the power.
2 While pressing both the MODE SELECT button and
TOO COOL button on the remote controller at the same
time, press the RESET button.
3 Firstly, release the RESET button.
4 And release the other 2 buttons since all LCD in
operation display section of the remote controller is
displayed after 3 seconds.
5 Transmit the signal of remote controller, pressing ON/ OFF
button on the remote controller.
(The above procedure allows OPERATION INDICATOR lamp
to indicate the failure-mode.)
6 Transmit the signal of remote controller, pressing a button other
than ON/ OFF button or VANE button to stop the self-check.
OPERATION INDICATER
13
Page 14
[Output pattern A] Errors detected by indoor unit
[Output pattern B]
E9
1. If the beeper does not sound again after the initial
2 beeps to confirm the self-check start signal was received and
the OPERATION INDICATOR lamp does not come on,
there are no error records.
2. If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
OPERATION
INDICATOR
lamp blink
pattern
BeepBeep Beep BeepBeep
Beep Beep
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
··· Repeated
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “U2”)
Number of blinks/beeps in pattern indicates
the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check
starts
(Start signal
received)
Beeper sounds
[Output pattern B]
OPERATION
INDICATOR
lamp blink
pattern
Beep
Beep Beep BeepBeepBeep Beep
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
On
0.5 sec.
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
··· Repeated
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
Number of blinks/beeps in pattern indicates
the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check
starts
(Start signal
received)
Beeper sounds
• Refer to the following tables for details on the check codes.
[Output pattern A]
Notes:
Beeper sounds/OPERATION
INDICATOR lamp blinks1 Check code
SymptomRemarks
(Number of times)
Wireless remote controller
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks1 Check code
(Number of times)
Wireless remote controller
Wired remote controller
1P1
Intake sensor error
P9Pipe (TH23) sensor error
2
P2Pipe (TH22) sensor error
3E6,E7
Indoor/outdoor unit communication error
4P4Drain sensor error
5P5Drain pump error
6P6Freezing/Overheating protection operation
7EECommunication error between indoor and outdoor units
8P8Pipe temperature error
9E4, E5Remote controller signal receiving error
10
–
11
–
–
–
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Abnormal high discharging temperature/49C operated/
insufficient refrigerant
6
Abnormal high pressure (63H operated)/Overheating
protection operation
7
Abnormal temperature of heatsink
8
Outdoor unit fan protection stop
9
Compressor overcurrent interruption/Abnormal of power module
10
Abnormality of superheat due to low discharge temperature
11
Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
12
13
U2
U5
UP
U3,U4
UF
U1,Ud
U8
U6
U7
U9,UH
Others
–
–
–
–
14
Other errors (Refer to the technical manual for the outdoor unit.)
For details, check
the LED display
of the outdoor
controller board.
As for outdoor
unit, refer to
outdoor unit’s
service manual.
12FbIndoor unit control system error (memory error, etc.)
14PLRefrigerant circuit abnomal
–
E0, E3
–E1, E2Remote controller control board error
Remote controller transmission error
Compressor overcurrent interruption
OCH564
1415
continued to the next page.
Page 15
•
If the unit cannot be operated properly after the test run, refer to the following table to find out the cause.
Symptom
Cause
Wired remote controller
On the wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller can be received.
• Operation lamp is blinking.
• The buzzer makes a short ping sound.
PLEASE WAIT
PLEASE WAIT → check code
No messages appear even
when operation switch is turned
ON (operation lamp does not
light up).
For about 2 minutes after power-on
Subsequent to about 2 minutes
after power-on
•
For about 2 minutes after power-on,operation
of the
remote controller is not possible due to system start-up.
(Correct operation)
•Connector for the outdoor unit’s protection device is not
connected.
•Reverse or open phase wiring for the outdoor unit’s
power terminal block
•Incorrect wiring between indoor and outdoor units.
(incorrect polarity of S1, S2, S3)
•Remote controller wire short
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microprocessor)
Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for remote controller)
Indicates whether power is supplied to the remote controller.
This LED lights only in the case of the indoor unit which is connected to the
outdoor unit refrigerant address “0”.
LED3 (communication between indoor and
outdoor units)
Indicates state of communication between the indoor and outdoor units.
Make sure that this LED is always blinking.
• On wireless remote controller
1 The continuous buzzer sounds from receiving section of indoor unit.
2 Blink of operation lamp
• On wired remote controller
1 Check code displayed on the LCD.
OCH564
15
Page 16
7-3. SELF-DIAGNOSIS ACTION TABLE
OCH564
Check code
P1
P2
Abnormal point and detection method
Room temperature thermistor (TH21)
1The unit is in 3-minute resume prevention
mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3
minutes. (The unit returns to normal
operation, if it has been reset normally.)
2 Constantly detected during cooling,
drying and heating operation
Short: -90˚C or more
Open: -40˚C or less
Pipe temperature thermistor/Liquid
(TH22)
1 The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3
minutes. (The unit returns to normal
operation, if it has been reset normally.)
2 Constantly detected during cooling,
drying, and heating (except defrosting)
operation.
Short: 90˚C or more
Open: -40˚C or less
Note: Errors to be detected in outdoor unit, such as codes starting
with F, U or E (excluding E0 to E7), are not covered in this
document. Please refer to the outdoor unit's service manual
for the details.
Cause
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN20) on the indoor controller
board (Insert failure)
Breaking of wire or contact
failure of thermistor wiring
Defective indoor controller
board
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN21) on the indoor controller
board (Insert failure)
Breaking of wire or contact
failure of thermistor wiring
Defective refrigerant circuit is
causing thermistor temperature
of 90˚C or more or -40˚C or
less.
Defective indoor controller board
Countermeasure
1~
Check resistance value of thermistor.
.....
0˚C
15.0 kΩ
.......
10˚C
20˚C
30˚C
40˚C
If you put force on (draw or bend) the lead wire
with measuring resistance value of thermistor,
breaking of wire or contact failure can be detected.
2 Check contact failure of connector (CN20)
on the indoor controller board. Refer to "7-5.
TEST POINT DIAGRAM". Turn the power
back on and check restart after inserting
connector again.
Check room temperature display on remote
controller.
Replace indoor controller board if there
is abnormal difference with actual room
temperature.
Turn the power off, and on again to operate
after checking.
~ Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN21)
on the indoor controller board. Refer to "7-5.
TEST POINT DIAGRAM". Turn the power on
and check restart after inserting connector
again.
Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid>
temperature is extremely low (in cooling
mode) or high (in heating mode), refrigerant
circuit may have defect.
Check pipe <liquid> temperature with
remote controller in test run mode. If there is
extreme difference with actual pipe <liquid>
temperature, replace indoor controller board.
Turn the power off, and on again to operate
after checking.
.......
.......
.......
9.6 kΩ
6.3 kΩ
4.3 kΩ
3.0 kΩ
P4
P5
Drain sensor (DS)
1 Suspensive abnormality, if short/open
of thermistor is detected for 30 seconds
continuously.
Turn off compressor and indoor fan.
2 Short/open is detected for 30 seconds
continuously during suspensive
abnormality.
(The unit returns to normal operation,
if it has been reset normally.)
Detect the following condition.
• During cooling and drying operation
• In case that pipe <liquid> temperature room temperature <-10deg
(Except defrosting)
• When pipe <liquid> temperature
or room temperature is short/open
temperature.
• During drain pump operation
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor of
drain sensor heats itself and temperature
rises slightly. Turn off compressor and
indoor fan.
2Drain pump is abnormal if the condition
above is detected during suspensive
abnormality.
Constantly detected during drain pump
operation
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN31) on the indoor controller
board (Insert failure)
Breaking of wire or contact
failure of drain sensor wiring
Defective indoor controller board
1 Malfunction of drain pump
2 Defective drain
Clogged drain pump
Clogged drain pipe
Attached drop of water at the
drain sensor
• Drops of drain trickles from
lead wire
• Clogged filter is causing
wave of drain.
Defective indoor controller board
1~3 Check resistance value of thermistor.
2 Check contact failure of connector (CN31)
on the indoor controller board. Refer to "7-5.
TEST POINT DIAGRAM". Turn the power
back on and check restart after inserting
connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited,
and abnormality reappears.
Turn the power off, and on again to operate
after checking.
1 Check if drain pump operates.
2 Check drain function.
3 Check the setting of lead wire of drain
sensor and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited
and abnormality reappears.
Refer to "7-5. TEST POINT DIAGRAM".
Turn the power off, and on again to operate
after checking.
0˚C
10˚C
20˚C
30˚C
40˚C
.......
.......
.......
.......
.......
6.0 kΩ
3.9 kΩ
2.6 kΩ
1.8 kΩ
1.3 kΩ
1617
Page 17
Check code
OCH564
P6
Abnormal point and detection method
Freezing/overheating protection is
operating
Freezing protection (Cooling mode)
The unit is in 6-minute resume prevention
mode if pipe <liquid or condenser/
evaporator> temperature stays under
-15˚C for 3 minutes after the compressor
started. Abnormal if it stays under -15˚C
for 3 minutes again within 16 minutes
after 6-minute resume prevention mode.
Overheating protection (Heating mode)
The units is in 6-minute resume
prevention mode if pipe <condenser /
evaporator> temperature is detected as
over 70˚C after the compressor started.
Abnormal if the temperature of over
70˚C is detected again within 10 minutes
after 6-minute resume prevention mode.
Cause
(Cooling or drying mode)
1 Clogged filter (reduced airflow)
Short cycle of air path
Low-load (low temperature)
operation out of the tolerance
range
Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
defective.
Defective outdoor fan control
Overcharge of refrigerant
Defective refrigerant circuit
(clogging)
(Heating mode)
1 Clogged filter (reduced airflow)
Short cycle of air path
Overload (high temperature)
operation out of the tolerance
range
Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
defective.
Defective outdoor fan control
Overcharge of refrigerant
Defective refrigerant circuit
(clogging)
Bypass circuit of outdoor unit is
defective.
Countermeasure
(Cooling or drying mode)
1 Check clogging of the filter.
Remove blockage.
Refer to "7-7-2. DC FAN MOTOR (FAN
MOTOR/ INDOOR CONTROLLER BOARD)".
Check outdoor fan motor. Refer to "7-5.
TEST POINT DIAGRAM".
Check operating condition of refrigerant
circuit.
(Heating mode)
1 Check clogs of the filter.
Remove blockage.
Refer to "7-7-2. DC FAN MOTOR (FAN
4
MOTOR/ INDOOR CONTROLLER BOARD)".
Check outdoor fan motor.
~ Check operating condition of refrigerant
circuit.
P8
Pipe temperature
<Cooling mode>
Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes after compressor start and 6 minutes
after the liquid or condenser/evaporator pipe
is out of cooling range.
Note 1) It takes at least 9 minutes to
detect.
Note 2) Abnormality P8 is not detected in
drying mode.
Cooling range: -3 deg (TH-TH21)
TH: Lower temperature between liquid pipe
temperature (TH22) and condenser/
evaporator temperature (TH23)
TH21: Intake temperature
<Heating mode>
When 10 seconds have passed after the
compressor starts operation and the hot
adjustment mode has finished, the unit is
detected as abnormal when condenser/
evaporator pipe temperature is not in heating range within 20 minutes.
Note 3) It takes at least 27 minutes to
detect abnormality.
Note 4) It excludes the period of defrosting
(Detection restarts when defrosting
mode is over)
Heating range: 3 deg (TH23-TH21)
1 Slight temperature difference
between indoor room
temperature and pipe <liquid
or condenser / evaporator>
temperature thermistor
• Shortage of refrigerant
• Disconnected holder of
pipe <liquid or condenser /
evaporator> thermistor
• Defective refrigerant circuit
Converse connection of
extension pipe (on plural units
connection)
Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
Defective detection of indoor
room temperature and pipe
<condenser / evaporator>
temperature thermistor
Stop valve is not opened
completely.
Check pipe <liquid or condenser /
1~
evaporator> temperature with room
temperature display on remote controller
and outdoor controller circuit board.
Pipe <liquid or condenser / evaporator>
temperature display is indicated by setting
SW2 of outdoor controller circuit board as
follows.
Conduct temperature check with outdoor
controller circuit board after connecting
(
‘A-Control Service Tool (PAC-SK52ST)’.
Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
)
17
Page 18
Check code
OCH564
P9
PL
Abnormal point and detection method
Pipe temperature thermistor / Condenser
/ Evaporator (TH23)
1 The unit is in 3-minute resume protec-
tion mode if short/open of thermistor is
detected. Abnormal if the unit does not
get back to normal within 3 minutes. (The
unit returns to normal operation, if it has
been reset normally.)
2 Constantly detected during cooling,
drying, and heating operation (except
defrosting)
Short: 90°C or more
Open: -40°C or less
Abnormal refrigerant circuit
During Cooling, Dry, or Auto Cooling
operation, the following conditions are
regarded as failures when detected for
one second.
a) The compressor continues to run for 30
or more seconds.
b) The liquid pipe temperature or the
condense/evaporator temperature is
75°C or more.
These detected errors will not be
cancelled until the power source is
reset.
Cause
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN29) on the indoor controller
board (Insert failure)
Breaking of wire or contact
failure of thermistor wiring
Temperature of thermistor is
90°C or more or -40°C or less
caused by defective refrigerant
circuit.
Defective indoor controller
board
1 Abnormal operation of 4-way
valve
2 Disconnection of or leakage in
refrigerant pipes
Air into refrigerant piping
Abnormal operation (no
rotation) of indoor fan
· Defective fan motor.
· Defective indoor control board.
Defective refrigerant circuit
(clogging)
Countermeasure
Check resistance value of thermistor.
1~
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN29)
on the indoor controller board.
Refer "7-5. TEST POINT DIAGRAM".
Turn the power on and check restart after
inserting connector again.
Operate in test run mode and check pipe
<condenser/evaporator> temperature with
outdoor controller circuit board. If pipe
<condenser/evaporator> temperature is
extremely low (in cooling mode) or high (in
heating mode), refrigerant circuit may have
defect.
Operate in test run mode and check pipe
<condenser/evaporator> temperature
with outdoor control circuit board. If there
is extreme difference with actual pipe
<condenser/evaporator> temperature replace
indoor controller board.
There is no abnormality if none of the above
comes within the unit.
Turn the power off and on again to operate.
In case of checking pipe temperature
with outdoor controller circuit board,
be sure to connect A-control service
(
tool (PAC-SK52ST).
1 When this error occurs, be sure to
replace the 4-way valve.
2 Check refrigerant pipes for disconnection or
leakage.
3 After the recovery of refrigerant, vacuum
dry the whole refrigerant circuit.
4 Refer to section "7-7. TROUBLE
CRITERION OF MAIN PARTS".
5 Check refrigerant circuit for operation.
To avoid entry of moisture or air into
refrigerant circuit which could cause
abnormal high pressure, purge air in
refrigerant circuit or replace refrigerant.
)
E0
or
E4
Remote controller transmission
error(E0)/signal receiving error(E4)
1 Abnormal if main or sub remote con-
troller cannot receive any transmission
normally from indoor unit of refrigerant
address “0” for 3 minutes.
(Check code : E0)
2 Abnormal if sub-remote controller could
not receive for any signal for 2 minutes.
(Check code: E0)
1 Abnormal if indoor controller board
cannot receive normally any data from
remote controller board or from other
indoor controller board for 3 minutes.
(Check code: E4)
2 Indoor controller board cannot receive
any signal from remote controller for 2
minutes. (Check code: E4)
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as “sub” remote controller. In
this case, E0 is displayed on
remote controller, and E4 is
displayed at LED (LED1, LED2)
on the outdoor controller circuit
board.
Miswiring of remote controller
Defective transmitting/receiving
circuit of remote controller
Defective transmitting/receiving
circuit of indoor controller board
of refrigerant address “0”
Noise has entered into the
transmission wire of remote
controller.
1819
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main”, if
there is no problem with the action above.
3 Check wiring of remote controller.
• Total wiring length: max. 500 m
(Do not use cable × 3 or more)
• The number of connecting indoor units:
max. 16 units
• The number of connecting remote
controller: max. 2 units
When the above-mentioned problem of
1~3are not seen.
Diagnose remote controllers.
a) When “RC OK” is displayed, remote
controllers have no problem.
Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
b) When “RC NG” is displayed, replace
remote controller.
c)
When “RC E3” or “ERC 00-66” is displayed,
noise may be causing abnormality.
Page 19
Check code
OCH564
E3
or
E5
E6
Abnormal point and detection method
Remote controller transmission
error(E3)/signal receiving error(E5)
1 Abnormal if remote controller could not
find blank of transmission path for 6
seconds and could not transmit.
transmitted data at the same time,
compares the data, and when detecting
it, judges different data to be abnormal
30 continuous times. (Check code: E5)
Indoor/outdoor unit communication
error (Signal receiving error)
1 Abnormal if indoor controller board
cannot receive any signal normally for 6
minutes after turning the power on.
2 Abnormal if indoor controller board
cannot receive any signal normally for 3
minutes.
Consider the unit abnormal under the
following condition: When 2 or more
indoor units are connected to one
outdoor unit, indoor controller board
cannot receive a signal for 3 minutes
from outdoor controller circuit board, a
signal which allows outdoor controller
circuit board to transmit signals.
Cause
1 2 remote controllers are set as
“main.”
(In case of 2 remote controllers)
2 Remote controller is connected
with 2 indoor units or more.
Repetition of refrigerant
address
Defective transmitting/receiving
circuit of remote controller
Defective transmitting/receiving
circuit of indoor controller board
Noise has entered into transmission wire of remote controller.
1 Contact failure, short circuit or,
miswiring (converse wiring) of
indoor/outdoor unit connecting
wire
2 Defective transmitting/receiv-
ing circuit of indoor controller
board
Defective transmitting/receiving
circuit of indoor controller board
Noise has entered into indoor/
outdoor unit connecting wire.
Countermeasure
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting.
~ Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem.
Turn the power off, and on again to check.
When becoming abnormal again, replace
indoor controller board.
b) When “RC NG” is displayed, replace
remote controller.
c)
When “RC E3” or “ERC 00-66” is displayed,
noise may be causing abnormality.
1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or
outdoor unit.
Check all the units in case of twin indoor unit
system.
2~4Turn the power off, and on again to
check. If abnormality generates again,
replace indoor controller board or outdoor
controller circuit board.
* Other indoor controller board may have
defect in case of twin indoor unit system.
E7
Fb
(FB)*
E1
or
E2
Indoor/outdoor unit communication
error (Transmitting error)
Abnormal if “1” receiving is detected 30
times continuously though indoor controller
board has transmitted “0”.
Indoor controller board
Abnormal if data cannot be normally read
from the nonvolatile memory of the indoor
controller board.
Remote controller control board
1 Abnormal if data cannot be normally
read from the nonvolatile memory of the
remote controller control board.
-10°C, drain sensor detects whether it is
soaked in the water or not at the interval
of 90 seconds. (Drain pump will start
operating when the drain sensor detects
to be soaked in the water.)
2 The unit has a water leakage abnormality
when the following conditions, a) and b),
are satisfied while the above-mentioned
detection is performed.
a) The drain sensor detects to be
soaked in the water 10 times in a row.
b) The intake temperature subtracted
from liquid pipe temperature is
detected to be less than -10°C for a
total of 30 minutes.
(When the drain sensor detects to
be NOT soaked in the water, the
detection record of a) and b) will be
cleared.)
The drain sensor detection is performed
in operations other than cooling. (When
the unit stops operating, during heat
ing or fan operation, when the unit stops
because of some abnormalities)
* Once the water leakage abnormality is
detected, abnormality state will not be
released until the main power is reset.
Cause
1 Drain pump trouble
2 Drain defective
· Drain pump clogging
· Drain pipe clogging
Open circuit of drain sensor
side heater
Contact failure of drain sensor
connector
Dew condensation on drain
sensor
· Drain water trickles along lead
wire
· Drain water waving due to filter
clogging
Extension piping connection
difference at twin, triple,
quadruple system
Miswiring of indoor/outdoor connecting at twin, triple,
quadruple system
Room temperature thermistor/
liquid pipe temperature
themistor detection is defective.
Countermeasure
1 Check the drain pump.
2 Please check whether water can be drained.
Check the resistance of the drain sensor side
heater.
Check the connector contact failure.
Check the drain sensor lead wire mounted.
Check the filter clogging.
Check the piping connection.
Check the indoor/outdoor connecting wires.
Check the room temperature display of
remote controller.
Check the indoor liquid pipe temperature
display of outdoor controller board.
2021
Page 21
7-4. TROUBLESHOOTING OF PROBLEMS
OCH564
Phenomena
(1) LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is also off.
1 Power supply of rated voltage is not supplied to out-
door unit.
2 Defective outdoor controller circuit board
Power supply of 220~240V is not supplied to indoor
unit.
4 Defective indoor controller board
Cause
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Countermeasure
1 Check the voltage of outdoor power
supply terminal block (L, N) or (L
• When AC 220~240V is not detected,
check the power wiring to outdoor unit
and the breaker.
• When AC 220~240V is detected,
check 2 (below).
2 Check the voltage between outdoor
terminal block S1 and S2.
• When AC 220~240V is not detected,
—check the fuse on outdoor controller
circuit board.
—check the wiring connection.
• When AC 220~240V is detected,
check
Check the voltage between indoor terminal
block S1 and S2.
• When AC 220~240V is not detected,
check indoor/outdoor unit connecting
wire for miswiring.
• When AC 220~240V is detected,
check
4 Check the wiring connection between
TB4 and CN01. Check the fuse on indoor
controller board. If no problems are found,
indoor controller board is defective.
(below).
(below).
3, N).
(2) LED2 on indoor controller board
is blinking.
• When LED1 on indoor controller board is lit.
1 Mis-setting of refrigerant address for outdoor unit
(There is no unit corresponding to refrigerant
address “0”.)
• When LED1 on indoor controller board is also blinking.
Connection failure of indoor/outdoor unit connecting
wire
• When LED1 is lit
1 Miswiring of remote controller wires
Under twin indoor unit system, 2 or more indoor
2 Refrigerant address for outdoor unit is wrong or not
set.
Under grouping control system, there are some units
whose refrigerant address is 0.
Short-cut of remote controller wires
Defective remote controller
units
1 Check the setting of refrigerant address
for outdoor unit.
Set the refrigerant address to “0”.
(For grouping control system under
which 2 or more outdoor units are
connected, set one of the units to “0”.)
Set refrigerant address using SW1 (3-6)
on outdoor controller circuit board.
Check indoor/outdoor unit connecting wire
for connection failure.
1 Check the connection of remote
controller wires in case of twin triple
indoor unit system. When 2 or more
indoor units are wired in one refrigerant
system, connect remote controller wires
to one of those units.
2 Check the setting of refrigerant address
in case of grouping control system. If
there are some units whose refrigerant
addresses are 0 in one group, set one of
the units to 0 using SW1 (3-6) on outdoor
controller circuit board.
Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the
short-cut of remote controller wires.
• When LED2 is lit, connect remote
controller wires again and:
if LED2 is blinking, remote controller
is defective; if LED2 is lit, connection
failure of remote controller terminal
block etc. has returned to normal.
CN29
Condenser/evaporator
temperature thermistor
(TH23)
CN41
Connector
(HA terminal-A)
SWE
Emergency
operation
CN6V
Vane motor
output (MV)
SW2
Capacity
setting
SW3
Mode
selection
CN31
Drain sensor
(DS)
LED2
Power supply
(R.B)
CN105
Connector (IT)
CNMF
Fan motor output
F1
FUSE
(6.3A 250V)
CN22
Remote controller
–
connecting wire
}
(10.4~14.6V DC)
+
CN3C
Transmission
(Indoor/outdoor)
(0~24V DC)
CNP
Drain-pump
output (DP)
(208/230V AC)
CNC
Dew prevention
heater (H2)
(208/230V AC)
CN01
Power supply input
(208/230V AC)
CN90
Connect to the
wireless remote
controller board
(CNB)
LED1
Power supply
(I.B)
22
Page 23
7-6. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
OCH564
Each function is controlled by the dip switch on control P.C. board.
Model setting and capacity setting are memorised in the nonvolatile memory of the indoor controller board.
The black square (■) indicates a switch position.
Switch
SW2
SW3
• Function setting becomes effective when the Dip switch SW3-5 is ON.
* Switch off SW3-5 when the function setting is done by wired remote controller.
Functions
Capacity
setting
Function
setting
Model
SLZ-KA25VAL3
SLZ-KA35VAL3
SLZ-KA50VAL3
Dip switchFunction
SW3-1
SW3-2
SW3-3
SW3-4
SW3-5*
Setting by the DIP switch
Setting
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
Power failure
automatic recovery
Set temperature in
heating mode (4 deg up)
Fan speed when the
thermostat is OFF
(during heating mode)
Condenser/evaporator
temperature thermistor
(TH23)
Vane motor (MV)
White
4
Blue
M
35
Yellow
Orange
Red
2
1
Drain pump (DP)
Yellow
1
2
Yellow
Drain sensor (DS)
1
2
3
Check method and criterion
Measure the resistance with a tester.
(Parts temperature 10 to 30°C)
Normal
4.3 to 9.6 k"
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20 to 30°C)
Red — Yellow
Red — Blue
Red — Orange
Red — White
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20 to 30°C)
NormalAbnormal
290 "
Measure the resistance between the terminals with a tester.
Measure the resistance after 3 minutes have passed since the power supply was intercepted.
(At the ambient temperature 0 to 60°C)
Normal
0.6 to 6.0 k"
Opened or short-circuited
Open or short
Open or short
Abnormal
NormalConnectorAbnormal
300 "Open or short
Abnormal
(Refer to the next page for a detail.)
2425
Page 25
7-7-1. THERMIISTOR CHARACTERISTIC GRAPH
OCH564
<Thermistor Characteristic graph>
Thermistor for
lower temperature
•Room temperature thermistor (TH21)
•Pipe temperature thermistor/liquid (TH22)
•Condenser/evaporator temperature
thermistor (TH23)
Thermistor R0=15 kΩ ± 3%
Fixed number of B=3480 ± 2%
Rt=15exp { 3480( ) }
1
273+t
1
273
0˚C 15 kΩ
10˚C9.6 kΩ
20˚C6.3 kΩ
25˚C5.2 kΩ
30˚C4.3 kΩ
40˚C3.0 kΩ
Thermistor for
drain sensor
< Thermistor for lower temperature >
50
40
30
20
Resistance (k")
10
0
-20 -10 0 10 20 30 40 50
10
Temperature (:)
< Thermistor for drain sensor >
Thermistor R
0=6.0 kΩ ±5%
Fixed number of B=3390 ± 2%
Rt=6exp { 3390( ) }
1
273+t
˚C6.0 kΩ
0
˚C3.9 kΩ
10
1
273
20˚C2.6 kΩ
25˚C2.2 kΩ
˚C1.8 kΩ
30
40˚C1.3 kΩ
60˚C0.6 kΩ
9
8
7
6
5
4
Resistance (k")
3
2
1
0
-20020 406080
Temperature (:)
25
Page 26
7-7-2. DC FAN MOTOR (FAN MOTOR/ INDOOR CONTROLLER BOARD)
OCH564
Check method of DC fan motor (fan motor / indoor controller circuit board)
Notes
1
· High voltage is applied to the connector (CNMF) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNMF) for the motor with the power supply on.
(It causes trouble of the indoor controller circuit
Self check
2
Symptom : The indoor fan cannot turn around.
Indoor controller board fuse check
board and fan motor.)
Is the fuse normal?
Yes
Wiring contact check
Contact of fan motor connector (CNMF)
Is there contact failure?
No
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit
No
Yes
Is the resistance
between the terminals of
drain pump normal?
Replace the drain pump.
Wiring recovery
board.
No
Yes
TEST POINT1 : VDC (between 1 (+) and 4 (-) of the fan connector): VDC DC 310~340 V
TEST POINT2 : VCC (between 5 (+) and 4 (-) of the fan connector): VCC DC 15 V
Is the voltage normal?
No
Replace indoor
controller board
Yes
Replace the fan motor.
OK
Check the operation of fan.END
NG
Replace indoor controller board.
OK
Check the operation
NG
END
Replace the fan motor.
Replace the fan motor.
Replace the indoor controller board.
Page 27
84-WAY AIR FLOW SYSTEM
OCH564
8-1. FRESH AIR INTAKE (LOCATION FOR INSTALLATION)
At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when required.
(1) Slide the knob of air intake grille to the direction of the
arrow to open the air intake grille.
(2) Remove the string hook from the panel to prevent the grille
from dropping.
(3) Slide the hinge of the intake grille to the direction of the
arrow 2 and remove the air intake grille.
2. Removing the fan guard
(1) Open the air intake grille.
(2) Remove the 3 screws of fan guard.
3. Removing the panel
(1) Remove the air intake grille. (Refer to procedure 1)
Corner panel (See Figure 2)
(1) Remove the screw of the corner.
(2) Slide the corner panel to the direction of the arrow
remove the corner panel.
Panel (See Photo 2)
(1) Disconnect the connector that connects with the unit.
(2) Remove the 2 screws from the panel and loose another
2 screws, which are fixed to the oval hole, have different
diameter.
(3) Rotate the panel a little to remove the screws. (Slide the
panel so that the screw comes to a larger diameter of the
oval hole, which has 2 different diameters.)
, and
Figure 1
Air intake grille
Air intake grille knob
Photo 1
Fan guard
Figure 2
Corner
panel
Photo 2
Connectors
Screws
Grille
Screw
Corner
panel
Screws
Air intake grille
Panel
Screws
Panel
4. Removing the electrical parts
(1) Remove the 2 screws and the control box cover.
<Electrical parts in the control box>
• Indoor controller board (I.B)
• Terminal block (TB4)
2929
Photo 3
Indoor controller board
(I.B)
Terminal block
(TB4)
Page 30
OPERATING PROCEDURE
OCH564
PHOTOS & ILLUSTRATIONS
5. Removing the room temperature thermistor (TH21)
(1) Remove the panel. (Refer to procedure 3)
(2) Pull out the room temperature thermistor from the drain
pan.
(3) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(4) Remove the connector (CN20) from the indoor controller
board, and disconnect the room temperature thermistor.
6. Removing the drain pan
(1) Remove the panel. (Refer to procedure 3)
(2) Remove the room temperature thermistor and the 2 lead
wires held with fastener; wireless controller board relay
connector (9P red) and panel relay connector (10P white).
(3) Remove the 4 screws fixed to the drain pan, and remove
the drain pan.
(4) Remove the fan guard. (Refer to procedure 2)
7. Removing the pipe temperature thermistor/liquid (TH22)
and condenser/evaporator temperature thermistor (TH23)
(1) Remove the panel. (Refer to procedure 3)
(2) Remove the drain pan. (Refer to procedure 6)
(3) Disconnect the indoor coil thermistor from the holder.
(4) Remove the 3 screws fixed to the piping cover, and remove
the piping cover. (See Photo 9)
(5) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
Photo 4
Screw
Room
temperature
thermistor
(TH21)
Screw
Photo 5
Control box
Control box
Connectors
Drain plug
Screw
Drain pan
Screw
Fan guard
Pipe temperature thermistor/liquid (TH22)
(6) Remove the connector (CN21) from the indoor controller
board, and disconnect the pipe temperature thermistor/liquid.
Condenser/evaporator temperature thermistor (TH23)
(6) Remove the connector (CN29) from the indoor controller
board, and disconnect the condenser/evaporator temperature
thermistor.
8. Removing the fan motor (MF)
(1) Remove the panel. (Refer to procedure 3)
(2) Remove the drain pan. (Refer to procedure 6)
(3) Remove the nut and the washer from the turbo fan, and
remove the turbo fan.
(4) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(5) Disconnect the connectors of the (fan 1) and the (fan 2)
from the indoor controller board.
(6) Remove the 3 screws fixed to the piping cover, and remove
the piping cover. (See Photo 9)
(7) Remove the 6 screws fixed to the flat plate, and remove
the flat plate.
(8) Disconnect the lead wires to the direction of the fan motor,
and remove the 3 nuts of the fan motor.
Pipe temperature
thermistor/liquid
(TH22)
Photo 6
Screws
Lead
wires
Flat plate
Condenser/evaporator
temperature thermistor
(TH23)
Screw
Nut
Fan motor
(MF)
Nut
Screws
30
Screw
Nut
Page 31
OPERATING PROCEDUREPHOTOS & ILLUSTRATIONS
OCH564
9. Removing the drain pump (DP) and drain sensor (DS)
(1) Remove the panel. (Refer to procedure 3 )
(2) Remove the drain pan. (Refer to procedure 6)
(3) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(4) Remove the connectors of the (CNP) and the (CN31)
from the indoor controller board.
(5) Remove the 1 screw fixed to the cover, and remove the
cover.
(6) Disconnect the lead wires to the direction of the drain
pump. (See Photo 7)
(7) Remove the 3 screws of the drain pump.
(8) Cut the drain hose band, pull out the drain hose from the
drain pump.
(9) Pull out the drain pump.
(10) Remove the drain sensor and the holder.
10. Removing the heat exchanger
(1) Remove the panel. (Refer to procedure 3 )
(2) Remove the drain pan. (Refer to procedure 6)
(3) Remove the nut and the washer from the turbo fan, and
remove the turbo fan.
(4) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(5) Disconnect the connector of the (fan) from the indoor con-
troller board.
(6) Remove the 3 screws fixed to the piping cover, and remove
the piping cover. (See Photo 9)
(7) Remove the pipe temperature thermistor/liquid and
condenser/evaporator temperature thermistor. (Refer to
procedure 7)
(8) Disconnect the lead wires to the direction of the fan motor.
(9) Remove the 1 coil support screw, the 2 inside coil screws
(See Photo 10), and the 4 outside coil screws (See Photo 9)
from the heat exchanger, and remove the heat exchanger.
Photo 7
Control
box
Photo 8
Drain
hose
Screw
Photo 9
Coil
screws
Screws of
piping cover
Piping cover
Screw
Drain sensor (DS)Drain pump (DP)
Fixing band
Cover
Lead wires
Lead wires
Screws
Control box
Coil
screws
Control box
31
Photo 10
Coil
screws
Coil
support
Heat exchanger
Coil support screw
Page 32
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Copyright 2014 MITSUBISHI ELECTRIC CORPORATION
Distributed in Jun. 2014 No.OCH564
Made in Japan
New publication, effective Jun. 2014
Specifications are subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.