• PANELhas been changed.
SLP-2AL➔SLP-2ALW
SLP-2AA➔SLP-2AAW
(White : 0.70Y 8.59/0.97)➔(Pure white : 6.4Y 8.9/0.4)
2
Page 3
2
Auto Air Swing Vane
Disperses airflow up and
down and adjusts the angle
of airflow direction.
Grille
Filter
Removes dust and pollutants
from inhaled air.
Horizontal Air Outlet
Sets horizontal airflow automatically
during cooling or dehumidifying.
Air Intake
Inhales air from room.
ON/OFF
RESET
TOO
WARM
TOO
COOL
MODE
AUTO COOL
DRY
HEAT
FAN
VANE
SELECT
TIME
h
ON / OFF button
To start and to stop operation.
VANE CONTROL button
To change the airflow
direction.
FAN SPEED button
To set fan speed to Low,
Medium or High.
TIMER SELECT button
To set time to start or stop
unit operation.
TEMPERATURE
SETTING button
To set any
desired room
temperature.
MODE SELECT button
To change the operation
mode; Auto, Cooling ,
Heating and Drying . (SLZ)
PART NAMES AND FUNCTIONS
Indoor Unit
SLZ-KA25VAL.THSLZ-KA25VA.THSLZ-KA25VAL1.THSLZ-KA25VA1.TH
SLZ-KA35VAL.THSLZ-KA35VA.THSLZ-KA35VAL1.THSLZ-KA35VA1.TH
SLZ-KA50VAL.THSLZ-KA50VA.THSLZ-KA50VAL1.THSLZ-KA50VA1.TH
“PLEASE WAIT” message
This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power failure.
“NOT AVAILABLE” message
This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have).
If a single remote controller is used to operate multiple indoor units simultaneously that are different types, this message will not be displayed as
far as any of the indoor units is equipped with the function.
Display Section
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc.
*Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the
remote controller has been prohibited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, the time to be
switched off is shown.
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
To be displayed on when it is time to
clean the filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Up/Down Air Direction indicator
Shows the direction of the
outcoming airflow.
“One Hour Only” indicator
Room Temperature display
Shows the room temperature. The room
temperature display range is 8~39:.
The display blinks if the temperature
is less than
8: or 39:
or more.
Louver display
Indicates the action of the swing louver.
Does not appear if the louver is not
running.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Displayed if the airflow is set to
low or downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off in one hour,
when the airflow direction also
changes.
● Wired remote controller
5
Page 6
3
SLZ-KA25VAL(1).TH
SLZ-KA25VA
(1).TH
SLZ-KA35VAL
(1).TH
SLZ-KA35VA
(1).TH
Indoor service ref.
Function
Power supply
Single phase
230V, 50Hz
600/540/480
10
0.35
75
0.014
0.19
PK6V15-LD
4
37/31/28
650/530/480
3
10
10
10
Cooling
90
Heating
93
Single phase
230V, 50Hz
660/540/480
10
0.40
85
0.014
0.26
PK6V20-LL
4
38/33/29
690/570/510
3
10
10
10
Cooling
94
Heating
94
Air flow
(High/Medium/Low)
Power outlet
Running current ✽1
Power input Rated frequency
Dew prevention heater
Power factor ✽1
Fan motor current ✽1
Model
Winding
resistance (at 26:)
Width
Height
Depth
Weight
Air direction
Sound level(High/Medium/Low)
Fan speed(High/Medium/Low)
Fan speed regulator
Thermistor TH1(at25:)
Thermistor TH2(at25:)
Thermistor TH5(at25:)
TO OUTDOOR UNIT : 3P TO WIRED REMOTE CONTROLLER : 2P (SLZ-KA25/35/50VA)
141:i3:
240V AC 15W
INDOOR UNIT
Item
Service ref.
Indoor fan capacitor
Fuse
Vane motor
Terminal block
Indoor fan motor thermal fuse
Cord Heater
SLZ-KA25VAL
(1).TH SLZ-KA35VAL(1).TH SLZ-KA50VAL(1).TH
(C1)
(FUSE)
(MV)
(TB)
(H2)
SLZ-KA25VA
(1).TH SLZ-KA35VA(1).TH SLZ-KA50VA(1).TH
SPECIFICATIONS
NOTE : Test conditions are based on ISO 5151.
Cooling : IndoorD.B. 27: W.B. 19:
Outdoor D.B. 35: W.B. 24:
Heating : IndoorD.B. 20: W.B. 15:
Specifications and rating conditions of main electric parts
Refrigerant piping length (one way): 5m
✽1 Measured under rated operating frequency
Outdoor D.B. 7: W.B. 6:
6
Page 7
90
80
70
60
50
40
30
20
10
631252505001000 2000 40008000
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SLZ-KA35VAL.TH
SLZ-KA35VA.TH
SLZ-KA35VAL
1.TH
SLZ-KA35VA
1.TH
High
Medium
38
SPL(dB)33LINE
<50Hz>
NOTCH
Low
29
90
80
70
60
50
40
30
20
10
631252505001000 2000 40008000
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SLZ-KA25VAL.TH
SLZ-KA25VA.TH
SLZ-KA25VAL
1.TH
SLZ-KA25VA
1.TH
High
Medium
37
SPL(dB)31LINE
<50Hz>
NOTCH
Low
28
NOISE CRITERION CURVES
UNIT
1.5m
MICROPHONE
CEILING
90
80
70
60
50
40
30
20
10
631252505001000 2000 40008000
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SLZ-KA50VAL.TH
SLZ-KA50VA.TH
SLZ-KA50VAL
1.TH
SLZ-KA50VA
1.TH
High
Medium
39
SPL(dB)34LINE
<50Hz>
NOTCH
Low
30
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation.
• Area in which the remote controller is not exposed to direct sunshine
• Area in which there is no heating source nearby
• Area in which the remote controller is not exposed to cold (or hot) winds
• Area in which the remote controller can be operated easily
• Area in which the remote controller is beyond the reach of children
Installation method
1 Attach the remote controller holder to the desired location using 2 tapping screws.
2 Insert the lower end of the controller into the holder.
A Wireless remote controller (Accessory)
B Wall
C Remote controller holder (Accessory)
D Fixing screw (Accessory)
• The signal can travel up to approximately 7 meters (in a straight line) within 45
degrees to both right and left of the center line of the receiver.
In addition, the signal may not be received if there is interference of light of fluorescent
lights or strong sunlight.
A
C
B
D
ON/OFF
RESET
TOO
WARM
TOO
COOL
MODE
AUTO COOL
DRY
HEAT
FAN
VANE
SELECT
TIME
h
5717.5
140
Unit : mm
9
Page 10
WIRED REMOTE CONTROLLER
130
120
19
43.5
Unit : mm
10
Page 11
5
SWE
GRILLE
OFF
ON
SW3
OFF
54321
ON
SW2
OFF
54321
ON
WHT
RED
RED
CNDK
(POWER
BOARD)
ZNR
X1
RED
ORN
YLW
YLW
BLU
BLU
BLU
BLU
LED3
CN2L
CN32 CN51 CN41
(REMOCON)
BLU
TO OUTDOOR UNIT
S3
ORN
MF
MV
MV
MV
MV
5
5
5
5
H2
5
21
P.B
3
TB4
S1
S2
TB15
1
2
TO MA-REMOTE
CONTROLLER
DC8.7-13V
}
REMOTE
CONTROLLER
W.R
9
5
CN6V
(VANE)
GRN
BLU
WHT
ORN
RED
YLW
YLW
X5
X5 X4
X4X7X6
X6X7
97531
C1
BLK
WHT
BLU
YLW
BRN
RED
I.B
CNB
BZ
LED2
LED1
SW1
SW2
RU
W.B
9
CN22
1
(2 PHASE)
CN29
BLK
WHT
RED
(INTAKE)
(LIQUID)
CN31
3
CN20
CN21
112
212
2
12
DS
TH5
TH1
TH2
X1
YLW
BLU
(D·U·M)
CNP
RED
(D·HEATER)
CNC
313131
CND
(POWER)
ORN
FUSE
(CONTROL)
CN3C
BLU
3131
LED1
12
12
TRANS
DC13.1V
CN2S(WHT)
AC220-240V
CNSK(RED)
WHT
BLK
2
1
(POWER
BOARD)
CN2D
WHT
LED2
* Case of wireress model
* Case of wired model
See fig:w1
MODELS
KA25
KA35
KA50
<fig:w1>
ON
OFF
12345
ON
OFF
12345
ON
OFF
12345
SW2
YLW
YLW
RED
ORN
YLW
WHT
BLU
17451089236
DP
GRY
VLT
BLU
YLW
ORN
RED
BRN
SKYBLU
PINK
WHT
(WIRELESS)
CN90
987654321
654321
(FAN)
FAN
WHT
BRN
RED
ORN
YLW
BLU
VLT
GRY
PINK
SKY BLU
123456789
(DRAIN)
WHT
NOTES : 1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires have polarities, make sure to match terminal numbers(S1,S2,S3) for correct wiring.
3. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
w For details on how to operate self-diagnosis, refer to the technical manuals etc.
1 Turn on the power.
2 Press the [CHECK] button twice.
3 Set address with [TEMP] button if system control is used.
4 Press the [ON/OFF] button to stop the self-check.
A CHECK button
B Address
C TEMP. button
D IC : Indoor unit
OC: Outdoor unit
E Check code
F Unit No.
G Timer ON/OFF button
A
F
C
BBEED
G
<To delete check code>
1 Display the error code on the self-check result display screen.
2 The address for self-check will blink when the
G ON/OFF
button is pressed twice within 3 seconds.
– – – – : No trouble generated in the past.
F F F F : No corresponding unit.
ON/OFF
RESET
TOO
WARM
TOO
COOL
MODE
AUTO COOL
DRY
HEAT
FAN
VANE
SELECT
TIME
h
24
23
56
24
[Procedure]
1 Turn ON the power.
2 While pressing both the MODE SELECT button and
TOO COOL button on the remote controller at the same
time, press the RESET button.
3 Firstly, release the RESET button.
4 And release the other 2 buttons since all LCD in
operation display section of the remote controller is
displayed after 3 seconds.
5 Transmit the signal of remote controller, pressing ON/ OFF
button on the remote controller.
(The above procedure allows OPERATION INDICATOR lamp
to indicate the failure-mode.)
6 Transmit the signal of remote controller, pressing ON/ OFF
button to stop the self-check.
OPERATION INDICATER
TROUBLESHOOTING
7-1. CAUTIONS ON TROUBLESHOOTING
(1) Before troubleshooting, check the followings:
1Check the power supply voltage.
2Check that the indoor/outdoor connecting wire is correct.
(2) Take care of the followings during servicing.
1 Before servicing the air conditioner, be sure to turn off the remote controller first to stop the main unit, and then turn
off the breaker.
2 When removing the indoor controller board, hold the edge of the board with care NOTto apply stress on the
components.
3 When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
7-2. SELF-CHECK
7-2-1. Wired remote controller
7-2-2. Wireless remote controller
13
Page 14
[Output pattern A] Errors detected by indoor unit
[Output pattern B]
E9
*1If the beeper does not sound again after the initial
2 beeps to confirm the self-check start signal was received and
the OPERATION INDICATOR lamp does not come on,
there are no error records.
*2If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
OPERATION
INDICATOR
lamp blink
pattern
BeepBeep Beep BeepBeepBeep Beep
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “U2”)
Number of blinks/beeps in pattern indicates
the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check
starts
(Start signal
received)
Beeper sounds
[Output pattern B]
OPERATION
INDICATOR
lamp blink
pattern
Beep
Beep Beep BeepBeepBeep Beep
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
On
0.5 sec.
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
Number of blinks/beeps in pattern indicates
the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check
starts
(Start signal
received)
Beeper sounds
• Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds/OPERATION
INDICATOR lamp blinks1 Check code
SymptomRemark
(Number of times)
Wireless remote controller
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks1 Check code
(Number of times)
Wireless remote controller
Wired remote controller
1P1
Intake sensor error
P9Pipe (TH5) sensor error
2
P2Pipe (TH2) sensor error
3E6,E7
Indoor/outdoor unit communication error
4P4Drain sensor error
5P5Drain pump error
6P6Freezing/Overheating protection operation
7EECommunication error between indoor and outdoor units
8P8Pipe temperature error
9E4, E5Remote controller signal receiving error
10
–
11
–
–
–
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Abnormal high discharging temperature/49C worked/
insufficient refrigerant
6
Abnormal high pressure (63H worked)/Overheating
protection operation
7
Abnormal temperature of heatsink
8
Outdoor unit fan protection stop
9
Compressor overcurrent interruption/Abnormal of power module
10
Abnormality of superheat due to low discharge temperature
11
Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
12
13
U2
U5
UP
U3,U4
UF
U1,Ud
U8
U6
U7
U9,UH
Others
–
–
–
–
14
Other errors (Refer to the technical manual for the outdoor unit.)
For details, check
the LED display
of the outdoor
controller board.
As for outdoor
unit, refer to
service manual
OC322 or
OC323.
12FbIndoor unit control system error (memory error, etc.)
–
E0, E3
–E1, E2Remote controller control board error
Remote controller transmission error
Compressor overcurrent interruption
14
continued to the next page.
Page 15
•
If the unit cannot be operated properly after the test run, refer to the following table to find out the cause.
Symptom
Cause
Wired remote controller
On the wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller can be received.
• Operation lamp is blinking.
• The buzzer makes a short ping sound.
PLEASE WAIT
PLEASE WAIT → Error code
No messages appear even
when operation switch is turned
ON (operation lamp does not
light up).
For about 2 minutes after power-on
Subsequent to about 2 minutes
after power-on
•
For about 2 minutes after power-on,operation
of the
remote controller is not possible due to system start-up.
(Correct operation)
•Connector for the outdoor unit’s protection device is not
connected.
•Reverse or open phase wiring for the outdoor unit’s
power terminal block
•Incorrect wiring between indoor and outdoor units.
(incorrect polarity of S1, S2, S3)
•Remote controller wire short
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer)
Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for remote controller)
Indicates whether power is supplied to the remote controller.
This LED lights only in the case of the indoor unit which is connected to the
outdoor unit refrigerant address “0”.
LED3 (communication between indoor and
outdoor units)
Indicates state of communication between the indoor and outdoor units.
Make sure that this LED is always blinking.
• On wireless remote controller
2The continuous buzzer sounds from receiving section of indoor unit.
3Blink of operation lamp
• On wired remote controller
1Check code displayed on the LCD.
15
Page 16
7-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
P2
Abnormal point and detection method
Room temperature thermistor (TH1)
1 The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 minutes. (The unit returns to normal operation, if it has been reset normally.)
2 Constantly detected during cooling,
drying and heating operation
Short: 90: or more
Open: -40: or less
Pipe temperature thermistor/Liquid
(TH2)
1 The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 minutes. (The unit returns to normal operation, if it has been reset normally.)
2 Constantly detected during cooling,
drying, and heating (except defrosting)
operation.
Short: 90: or more
Open: -40: or less
Note: Refer to the manual of outdoor unit for the details of display
such as F, U, and other E.
Cause
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN20) on the indoor controller
board (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective indoor controller
board
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN21) on the indoor controller
board (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective refrigerant circuit is
causing thermistor temperature
of 90: or more or -40: or
less.
If you put force on (draw or bend) the lead wire
with measuring resistance value of thermistor,
breaking of wire or contact failure can be
detected.
2 Check contact failure of connector (CN20) on
the indoor controller board. Refer to 7-5.
Turn the power back on and check restart
after inserting connector again.
4 Check room temperature display on remote
controller.
Replace indoor controller board if there is
abnormal difference with actual room
temperature.
Turn the power off, and on again to operate
after checking.
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN21) on
the indoor controller board. Refer to 7-5. Turn
the power on and check restart after inserting
connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid>
temperature is extremely low (in cooling
mode) or high (in heating mode), refrigerant
circuit may have defect.
5 Check pipe <liquid> temperature with remote
controller in test run mode. If there is extreme
difference with actual pipe <liquid> temperature,
replace indoor controller board.
P4
P5
Drain sensor (DS)
1 Suspensive abnormality, if short/open of
thermistor is detected for 30 seconds
continuously.
Turn off compressor and indoor fan.
2 Short/open is detected for 30 seconds
continuously during suspensive
abnormality.
(The unit returns to normal operation,
if it has been reset normally.)
3 Detect the following condition.
• During cooling and drying operation
• In case that pipe <liquid> temperature
- room temperature <-10deg
(Except defrosting)
• When pipe <liquid> temperature or
room temperature is short/open
temperature.
• During drain pump operation
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor heats itself and
temperature rises slightly. Turn off
compressor and indoor fan.
2 Drain pomp is abnormal if the condition
above is detected during suspensive
abnormality.
3 Constantly detected during drain pump
operation
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN31) on the indoor controller
board (Insert failure)
3 Breaking of wire or contact
failure of drain sensor wiring
4 Defective indoor controller board
1 Malfunction of drain pump
2 Defective drain
Clogged drain pump
Clogged drain pipe
3 Attached drop of water at the
drain sensor
• Drops of drain trickles from
lead wire
• Clogged filter is causing
wave of drain.
4 Defective indoor controller board
Turn the power off, and on again to operate
after checking.
the indoor controller board. Refer to 7-5. Turn
the power back on and check restart after
inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited,
and abnormality reappears.
Turn the power off, and on again to operate
after checking.
1 Check if drain pump works.
2 Check drain function.
3 Check the setting of lead wire of drain sensor
and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited
and abnormality reappears.
Refer to 7-5.
Turn the power off, and on again to operate
after checking.
16
Page 17
Error Code
P6
Abnormal point and detection method
Freezing/overheating protection is
working
1 Freezing protection (Cooling mode)
The unit is in 6-minute resume prevention
mode if pipe <liquid or condenser/evaporator> temperature stays under
-15: for 3 minutes after the compressor started. Abnormal if it stays under 15: for 3 minutes again within 16 min-
utes after 6-minute resume prevention
mode.
2 Overheating protection (Heating mode)
The units is in 6-minute resume
prevention mode if pipe <condenser /
evaporator> temperature is detected as
over 70: after the compressor started.
Abnormal if the temperature of over
70: is detected again within 10 minutes
after 6-minute resume prevention mode.
Cause
(Cooling or drying mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Low-load (low temperature)
operation out of the tolerance
range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
defective.
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
(clogging)
(Heating mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Overload (high temperature)
operation out of the tolerance
range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
defective.
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
(clogging)
8 Bypass circuit of outdoor unit
is defective.
Countermeasure
(Cooling or drying mode)
1 Check clogging of the filter.
2 Remove shields.
4 Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector
(FAN) on the indoor controller board.
WThe indoor controller board should be
normal when voltage of AC 220~240V is
detected while fan motor is connected.
Refer to 7-5.
5 Check outdoor fan motor.
67 Check operating condition of refrigerant
circuit.
(Heating mode)
1 Check clogs of the filter.
2 Remove shields.
4 Measure the resistance of fan motor's
winding.
Measure the output voltage of fan's connector
(FAN) on the indoor controller board.
WThe indoor controller board should be
normal when voltage of AC 220~240V is
detected while fan motor is connected.
Refer to 7-5.
5 Check outdoor fan motor.
6~8Check operating condition of refrigerant
circuit.
P8
Pipe temperature
<Cooling mode>
Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes after compressor start and 6 minutes
after the liquid or condenser/evaporator pipe
is out of cooling range.
Note 1) It takes at least 9 min. to detect.
Note 2) Abnormality P8 is not detected in
drying mode.
Cooling range : -3 deg ] (TH-TH1)
TH: Lower temperature between liquid pipe
temperature (TH2) and
condenser/evaporator temperature
(TH5)
TH1: Intake temperature
<Heating mode>
When 10 seconds have passed after the
compressor starts operation and the hot
adjustment mode has finished, the unit is
detected as abnormal when
condenser/evaporator pipe temperature is
not in heating range within 20 minutes.
Note 3) It takes at least 27 minutes to
detect abnormality.
Note 4) It excludes the period of defrosting
(Detection restarts when defrosting
mode is over)
Heating range : 3 deg [ (TH5-TH1)
1 Slight temperature difference
between indoor room
temperature and pipe <liquid
or condenser / evaporator>
temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
<liquid or condenser /
evaporator> thermistor
• Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units
connection)
3 Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
4 Defective detection of indoor
room temperature and pipe
<condenser / evaporator>
temperature thermistor
5 Stop valve is not opened
completely.
1~4Check pipe <liquid or condenser /
evaporator> temperature with room
temperature display on remote
controller and outdoor controller circuit
board.
Pipe <liquid or condenser / evaporator>
temperature display is indicated by
setting SW2 of outdoor controller circuit
board as follows.
Conduct temperature check with outdoor
controller circuit board after connecting
(
‘A-Control Service Tool(PAC-SK52ST)’.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
)
17
Page 18
Error Code
P9
E0
or
E4
E3
or
E5
Abnormal point and detection method
Pipe temperature thermistor /
Condenser / Evaporator (TH5)
1 The unit is in 3-minute resume protec-
tion mode if short/open of thermistor is
detected. Abnormal if the unit does not
get back to normal within 3 minutes.
(The unit returns to normal operation, if
it has been reset normally.)
2 Constantly detected during cooling, dry-
ing, and heating operation (except
defrosting)
Short: 90: or more
Open: -40: or less
find blank of transmission path for 6 seconds and could not transmit.
(Error code: E3)
2 Remote controller receives transmitted
data at the same time, compares the
data, and when detecting it, judges
different data to be abnormal 30
continuous times. (Error code: E3)
1 Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2 Indoor controller board receives trans-
mitted data at the same time, compares
the data,and when detecting it, judges
different data to be abnormal 30
continuous times. (Error code: E5)
Cause
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN29) on the indoor controller
board (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Temperature of thermistor is
90: or more or -40: or less
caused by defective refrigerant
circuit.
5 Defective indoor controller
board
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as “sub” remote controller. In
this case, E0 is displayed on
remote controller, and E4 is
displayed at LED (LED1, LED2)
on the outdoor controller circuit
board.
3 Miswiring of remote controller
4 Defective transmitting/receiving
circuit of remote controller
5 Defective transmitting/receiving
circuit of indoor controller board
of refrigerant address “0”
6 Noise has entered into the
transmission wire of remote
controller.
1 2 remote controllers are set as
“main.”
(In case of 2 remote con-
trollers)
2 Remote controller is connected
with 2 indoor units or more.
3 Repetition of refrigerant
address
4 Defective transmitting/receiving
circuit of remote controller
5 Defective transmitting/receiving
circuit of indoor controller
board
6 Noise has entered into trans-
mission wire of remote controller.
Countermeasure
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN29)
on the indoor controller board.
Refer to 7-5.
Turn the power on and check restart after
inserting connector again.
4 Operate in test run mode and check pipe
<condenser / evaporator> temperature with
outdoor controller circuit board. If pipe
<condenser / evaporator> temperature is
extremely low (in cooling mode) or high (in
heating mode), refrigerant circuit may have
defect.
5 Operate in test run mode and check pipe
<condenser / evaporator> temperature with
outdoor control circuit board. If there is
extreme difference with actual pipe
<condenser / evaporator> temperature
replace indoor controller board.
There is no abnormality if none of above
comes within the unit.
Turn the power off and on again to operate.
In case of checking pipe temperature
with outdoor controller circuit board,
be sure to connect A-control service
(
tool (PAC-SK52ST).
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main”,
if there is no problem with the action above.
3 Check wiring of remote controller.
• Total wiring length: max. 500m
(Do not use cablex 3 or more)
• The number of connecting indoor units:
max. 16 units
• The number of connecting remote controller: max. 2 units
When the above-mentioned problem of 1~3
are not seen.
4 Diagnose remote controllers.
a) When “RC OK” is displayed,
remote controllers have no problem.
Turn the power off, and on again to
check. If abnormality generates again,
replace indoor controller board.
b) When “RC NG” is displayed,
replace remote controller.
c) When “RC E3” is displayed,
d) When “ERC 00-06” is displayed,
[ c),d)→Noise may be causing abnormality. ]
∗ If the unit is not normal after replacing
indoor controller board in group control,
indoor controller board of address “0”
may be abnormal.
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting.
4~6 Diagnose remote controller.
a) When “RC OK”is displayed, remote con-
trollers have no problem.
Turn the power off, and on again to check.
When becoming abnormal again, replace
indoor controller board.
b)When “RC NG” is displayed, replace
remote controller.
c)When “RC E3”or “ERC 00-66” is dis-
played, noise may be causing abnormali-
ty.
)
18
Page 19
Error Code
E6
E7
Fb
E1
or
E2
Abnormal point and detection method
Indoor/outdoor unit communication
error (Signal receiving error)
1 Abnormal if indoor controller board
cannot receive any signal normally for 6
minutes after turning the power on.
2 Abnormal if indoor controller board
cannot receive any signal normally for 3
minutes.
3 Consider the unit abnormal under the
following condition: When 2 or more
indoor units are connected to one
outdoor unit, indoor controller board
cannot receive a signal for 3 minutes
from outdoor controller circuit board, a
signal which allows outdoor controller
circuit board to transmit signals.
Indoor/outdoor unit communication
error (Transmitting error)
Abnormal if “1” receiving is detected 30
times continuously though indoor controller
board has transmitted “0”.
Indoor controller board
Abnormal if data cannot be normally read
from the nonvolatile memory of the indoor
controller board.
Remote controller control board
1 Abnormal if data cannot be normally
read from the nonvolatile memory of the
remote controller control board.
(Error code: E1)
2 Abnormal if the clock function of remote
controller cannot be normally operated.
(Error code: E2)
Cause
1 Contact failure, short circuit or,
miswiring (converse wiring) of
indoor/outdoor unit connecting
wire
outdoor unit connecting wire of indoor unit or
outdoor unit.
Check all the units in case of twin indoor
unit system.
2-4 Turn the power off, and on again to
check. If abnormality generates again,
replace indoor controller board or outdoor
controller circuit board.
∗ Other indoor controller board may have
defect in case of twin indoor unit system.
1-3 Turn the power off, and on again to
check. If abnormality generates again,
replace indoor controller board.
1 Replace indoor controller board.
Countermeasure
PA
(2502)
(2500)
Forced compressor stop
(due to water leakage abnormality)
1 When the intake temperature subtracted
with liquid pipe temperature is less than
-10:, drain sensor detects whether
it is soaked in the water or not at the interval
of 90 seconds. (Drain pump will start operating
when the drain sensor detects to be
soaked in the water.)
2 The unit has a water leakage abnormali-
ty when the following conditions, a) and
b), are satisfied while the above-mentioned detection is performed.
a) The drain sensor detects to be
soaked in the water 10 times in a row.
b) The intake temperature subtracted with
liquid pipe temperature is detected to be
less than -10: for a total of 30 minutes.
(When the drain sensor detects to
be NOT soaked in the water, the detection
record of a) and b) will be cleared.)
3 The drain sensor detection is performed
in operations other than cooling. (When
the unit stops operating, during heating
or fan operation, when the unit stops
because of some abnormality)
*Once the water leakage abnormality is
detected, abnormality state will not be
released until the main power is reset.
1 Drain pump trouble
2 Drain defective
· Drain pump clogging
· Drain pipe clogging
3 Open circuit of drain sensor
side heater
4 Contact failure of drain sensor
connector
5 Dew condensation on drain
sensor
· Drain water trickles along
lead wire.
· Drain water waving due to filter
clogging
6 Extension piping connection
difference at twin, triple,
quadruple system
7 Miswiring of indoor/ outdoor
connecting at twin, triple,
quadruple system
8 Room temperature thermistor /
liquid pipe temperature thermistor detection is defective.
1Check the drain pump.
Performance
2Please check whether water can be
drained.
3Check the resistance of the drain sensor
side heater.
4Check the connector contact failure.
5 Check the drain sensor leadwire mounted.
Check the filter clogging.
6Check the piping connection.
7Check the indoor/ outdoor connecting wires.
8Check the room temperature display of
remote controller.
Check the indoor liquid pipe temperature
display of outdoor controller board.
19
Page 20
7-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Phenomena
(1)LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is also off.
1 Power supply of rated voltage is not supplied to out-
door unit.
2 Defective outdoor controller circuit board
3 Power supply of 220~240V is not supplied to indoor
unit.
4 Defective indoor power board
5 Defective indoor controller board
Cause
Countermeasure
1 Check the voltage of outdoor power
supply terminal block (L, N) or (L
• When AC 220~240V is not detected,
check the power wiring to outdoor unit
and the breaker.
• When AC 220~240V is detected,
check 2 (below).
2 Check the voltage between outdoor
terminal block S1 and S2.
• When AC 220~240V is not detected,
—check the fuse on outdoor controller
circuit board.
—check the wiring connection.
• When AC 220~240V is detected,
check 3 (below).
3 Check the voltage between indoor terminal
block S1 and S2.
• When AC 220~240V is not detected,
check indoor/outdoor unit connecting
wire for miswiring.
• When AC 220~240V is detected,
check 4 (below).
4 Check voltage output from CN2S on indoor
power board (DC13.1V). Refer to 7-5.
• When no voltage is output,
check the wiring connection.
• When output voltage is between
DC12.5V and DC13.7V,
check 5 (below).
5 Check the wiring connection between
indoor controller board and indoor power
board. Check the fuse on indoor controller
board. If no problems are found, indoor
controller board is defective.
3, N).
(2)LED2 on indoor controller board
is blinking.
• When LED1 on indoor controller board is lit.
1 Mis-setting of refrigerant address for outdoor unit
(There is no unit corresponding to refrigerant
address “0”.)
• When LED1 on indoor controller board is also blinking.
Connection failure of indoor/outdoor unit connecting
wire
• When LED1 is lit
1 Miswiring of remote controller wires
Under twin indoor unit system, 2 or more indoor
2 Refrigerant address for outdoor unit is wrong or not
set.
Under grouping control system, there are some units
whose refrigerant address is 0.
3 Short-cut of remote controller wires
4 Defective remote controller
units
1 Check the setting of refrigerant address
for outdoor unit.
Set the refrigerant address to “0”.
(For grouping control system under
which 2 or more outdoor units are
connected, set one of the units to “0”.)
Set refrigerant address using SW1 (3-6)
on outdoor controller circuit board.
Check indoor/outdoor unit connecting wire
for connection failure.
1 Check the connection of remote cotroller
wires in case of twin triple indoor unit
system. When 2 or more indoor units are
wired in one refrigerant system, connect
remote controller wires to one of those
units.
2 Check the setting of refrigerant address
in case of grouping control system. If
there are some units whose refrigerant
addresses are 0 in one group, set one of
the units to 0 using SW1 (3-6) on outdoor controller circuit board.
34 Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the
short-cut of remote controller wires.
• When LED2 is lit, connect remote
controller wires again and:
if LED2 is blinking, remote controller
is defective; if LED2 is lit, connection
failure of remote controller terminal
block etc. has returned to normal.
CNDK
Connect to the indoor
power board (CNSK)
(220~240V AC)
CNC
Dew prevention
heater (H2)
(220~240V AC)
CNP
Drain-pump output
(DP)
(220~240V AC)
CN2D
Connector to the indoor
power board (CN2S)
(12.5~13.7V DC)
}
+
–
LED1
Power supply
(I.B)
LED2
Power supply
(R.B)
LED3
Transmission
(Indoor/outdoor)
CN22
Remote controller
connecting wire
+
}
(10.4~14.6V DC)
–
CN20
Room temperature
thermistor (TH1)
CN21
Pipe temperature
thermistor/Liquid
(TH2)
CN29
Condenser/evaporator
temperature thermistor
(TH5)
CN31
Drain sensor (DS)
CN90
Connect to the
wireless remote
controller board
(CNB)
CN41
Connector
(HA terminal-A)
CN6V
Vane motor output
(MV)
CN51
Centrally control
FAN
Fan motor output
SW3
Mode selection
SWE
Emergency operation
22
CN2L
Connector
(LOSSNAY)
Jumper connector
J11~J15
Unit setting
SW2
Capacity setting
Page 23
7-6. TROUBLE CRITERION OF MAIN PARTS
Measure the resistance between the terminals with a tester.
Measure the resistance after 3 minutes have passed since the power supply was intercepted.
(At the ambient temperature 0:~60:)
(Refer to the next page for a detail.)
Abnormal
Open or short
Normal
0.6k"~6.0k"
BLKREDORNYLW
BLU
BRN
WHT
P
Room temperature
thermistor
(TH1)
Condenser/evaporator
temperature thermistor
(TH5)
Measure the resistance with a tester.
(Part temperature 10°C ~ 30°C)
Measure the resistance between the terminals with a tester.
(Coil wiring temperature 10°C ~ 30°C)
Pipe temperature
thermistor/liquid
(TH2)
Indoor fan motor
(MF)
Check method and criterion
Part name
Normal
KA25VA(L)
Normal
WHT-BLK
BLK-BLU
BLU-YLW
BRN-RED
386~428"
81~91"
28~32"
157~174"
KA35VA(L)
373~413"
155~172"
44~49"
302~335"
KA50VA(L)
308~341"
135~151"
44~49"
293~324"
4.3kΩ~9.6k"
Abnormal
Abnormal
Opened or
short-circuited
Opened or short-circuited
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20:~30:)
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20:~30:)
(1) Slide the knob of air intake grille to the direction of the
arrow 1 to open the air intake grille.
(2) Remove the string hook from the panel to prevent the grille
from dropping.
(3) Slide the hinge of the intake grille to the direction of the
arrow 2 and remove the air intake grille.
2. Removing the fan guard
(1) Open the air intake grille.
(2) Remove the 3 screws of fan guard.
3. Removing the panel
(1) Remove the air intake grille. (Refer to 1)
Corner panel (See figure 2)
(1) Remove the screw of the corner.
(2) Slide the corner panel to the direction of the arrow 3, and
remove the corner panel.
Panel (See photo 2)
(1) Disconnect the connector that connects with the unit.
(2) Remove the 2 screws from the panel and loose another 2
screws, which are fixed to the oval hole, have different
diameter.
(3) Rotate the panel a little to remove the screws.(Slide the
panel so that the screw comes to a larger diameter of the
oval hole, which has 2 different diameters.)
Figure 1
Air intake grille
Air intake grille knob
Photo 1
Fan guard
Figure 2
Corner
panel
Photo 2
Connectors
Screws
Grille
Screw
Corner
panel
Screws
Air intake grille
Panel
Screws
Panel
4. Removing the electrical parts
(1) Remove the 2 screws and the control box cover.
<Electrical parts in the control box>
• Indoor controller board (I.B)
• Terminal block (TB4)
• Indoor power board (P.B)
27
Photo 3
Indoor power board(P.B)
Indoor controller board
(I.B)
Terminal block
(TB4)
Page 28
OPERATING PROCEDURE
PHOTOS&ILLUSTRATIONS
5. Removing the room temperature thermistor (TH1)
(1) Remove the panel. (Refer to 3)
(2) Pull out the room temperature thermistor from the drain
pan.
(3) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(4) Remove the connector (CN20) from the indoor controller
board, and disconnect the room temperature thermistor.
6. Removing the drain pan
(1) Remove the panel. (Refer to 3)
(2) Remove the room temperature thermistor and the 2 lead
wires held with fastener; wireless controller board relay
connector (9P red) and panel relay connector (10P white).
(3) Remove the 4 screws fixed to the drain pan, and remove
the drain pan.
(4) Remove the fan guard. (Refer to 2)
7. Removing the pipe temperature thermistor/liquid (TH2)
and condenser/evaporator temperature thermistor (TH5)
(1) Remove the panel. (Refer to 3)
(2) Remove the drain pan. (Refer to 6)
(3) Disconnect the indoor coil thermistor from the holder.
(4) Remove the 3 screws fixed to the piping cover, and
remove the piping cover. (See photo 9)
(5) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
Photo 4
Screw
Room
temperature
thermistor
(TH1)
Screw
Photo 5
Control box
Fan guard
Control box
Connectors
Drain plug
Screw
Drain pan
Screw
Pipe temperature thermistor/liquid (TH2)
(6) Remove the connector (CN21) from the indoor controller
board, and disconnect the pipe temperature thermistor/liquid.
Condenser/evaporator temperature thermistor (TH5)
(6) Remove the connector (CN29) from the indoor controller
board, and disconnect the condenser/evaporator temperature
thermistor.
8. Removing the fan motor (MF)
(1) Remove the panel. (Refer to 3)
(2) Remove the drain pan. (Refer to 6)
(3) Remove the nut and the washer from the turbo fan, and
remove the turbo fan.
(4) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(5) Disconnect the connectors of the (fan 1) and the (fan 2)
from the indoor controller board.
(6) Remove the 3 screws fixed to the piping cover, and
remove the piping cover. (See photo 9)
(7) Remove the 6 screws fixed to the flat plate, and remove
the flat plate.
(8) Disconnect the lead wires to the direction of the fan motor,
and remove the 3 nuts of the fan motor.
Pipe temperature
thermistor/liquid
(TH2)
Photo 6
Screws
Lead
wires
Screw
Flat plate
Condenser/evaporator
temperature thermistor
(TH5)
Screw
Nut
Nut
Fan motor
(MF)
Nut
Screws
28
Page 29
OPERATING PROCEDUREPHOTOS&ILLUSTRATIONS
9. Removing the drain pump (DP) and drain sensor (DS)
(1) Remove the panel. (Refer to 3 )
(2) Remove the drain pan. (Refer to 6)
(3) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(4) Remove the connectors of the (CNP) and the (CN31)
from the indoor controller board.
(5) Remove the 1 screw fixed to the cover, and remove the
cover.
(6) Disconnect the lead wires to the direction of the drain
pump.(See photo 7)
(7) Remove the 3 screws of the drain pump.
(8) Cut the drain hose band, pull out the drain hose from the
drain pump.
(9) Pull out the drain pump.
(10) Remove the drain sensor and the holder.
10. Removing the heat exchanger
(1) Remove the panel. (Refer to 3 )
(2) Remove the drain pan. (Refer to 6)
(3) Remove the nut and the washer from the turbo fan, and
remove the turbo fan.
(4) Remove the 2 screws fixed to the control box cover, and
remove the control box cover.
(5) Disconnect the connector of the (fan) from the indoor con-
troller board.
(6) Remove the 3 screws fixed to the piping cover, and
remove the piping cover. (See photo 9)
(7) Remove the pipe temperature thermistor/liquid and
condenser/evaporator temperature thermistor. (Refer to 7)
(8) Disconnect the lead wires to the direction of the fan motor.
(9) Remove the 1 coil support screw, the 2 inside coil screws
(See photo 10), and the 4 outside coil screws (See photo 9)
from the heat exchanger, and remove the heat exchanger.
AIR OUTLET GRILLE
AIR OUTLET GRILLE
WIRELSS REMOTE CONTROL BOARD
AUTO VANE
CORNER PANEL
AIR FILTER
INTAKE GRILLE
VANE MOTOR
VANE BUSH
GEAR (V)
GEAR (M)
Parts name
SLP-2AL SLP-2AA
Q'ty/set
PANEL PARTS
SLP-2AL(FOR SLZ-KA25/35/50VAL.TH)
SLP-2AA(FOR SLZ-KA25/35/50VA.TH)
BASE
DRUM-1
LEG-1
DRUM-2
INDOOR HEAT EXCHANGER
INDOOR HEAT EXCHANGER
INDOOR HEAT EXCHANGER
MOTOR MOUNT
INDOOR FAN MOTOR
INDOOR FAN MOTOR
INDOOR FAN MOTOR
PK6V15-LD
PK6V20-LL
PK6V20-LM
FLAT PLATE
TURBO FAN
SPL WASHER
DRAIN PAN
ROOM TEMPERATURE THERMISTOR
FAN GUARD
DRAIN PLUG
COIL SUPPORT
AIR OUTLET GRILLE
AIR OUTLET GRILLE
AIR OUTLET GRILLE
AIR OUTLET GRILLE
WIRELSS REMOTE CONTROL BOARD
AUTO VANE
AUTO VANE
CORNER PANEL
CORNER PANEL
AIR FILTER
INTAKE GRILLE
INTAKE GRILLE
VANE MOTOR
VANE BUSH
GEAR (V)
GEAR (M)
BASE
DRUM-1
LEG-1
DRUM-2
INDOOR HEAT EXCHANGER
INDOOR HEAT EXCHANGER
INDOOR HEAT EXCHANGER
MOTOR MOUNT
INDOOR FAN MOTOR
INDOOR FAN MOTOR
INDOOR FAN MOTOR
PK6V15-LD
PK6V20-LL
PK6V20-LM
FLAT PLATE
TURBO FAN
SPL WASHER
DRAIN PAN
ROOM TEMPERATURE THERMISTOR
FAN GUARD
DRAIN PLUG
COIL SUPPORT
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Jul. 2007 No.OC320 REVISED EDITION-B PDF 7
Distributed in Sep. 2006 No.OC320 REVISED EDITION-A PDF 7
Distributed in Feb. 2005 No.OC320 PDF 8
Made in Japan
New publication, effective Jul. 2007
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.