Mitsubishi SCM45ZA, SKM25ZA, SKM28ZA, SKM22ZA, SKM32ZA User Manual

...
Page 1
191191
6. INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER[2room]
(Air to air heat pump type)
(OUTDOOR UNIT) SCM45ZA
(INDOOR UNIT) SKM22ZA
SKM25ZA SKM28ZA SKM32ZA SKM40ZA
Page 2
192
CONTENTS
6.1 GENERAL INFORMATION ........................................................................193
6.1.1 Specific features ................................................................................. 193
6.1.2 How to read the model name .............................................................193
6.2 SELECTION DATA ..................................................................................... 194
6.2.1 Specifications...................................................................................... 194
6.2.2 Range of usage & limitations............................................................. 198
6.2.3 Exterior dimensions............................................................................199
6.2.4 Piping system...................................................................................... 201
6.2.5 Selection chart .................................................................................... 202
6.3 ELECTRICAL DATA ................................................................................... 203
6.3.1 Electrical wiring ..................................................................................203
6.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ............. 205
6.5 APPLICATION DATA .................................................................................215
6.5.1 Installation of indoor unit ................................................................... 216
6.5.2 Installation of remote controller ........................................................218
6.5.3 Installation of outdoor unit.................................................................219
6.5.4 Electrical wiring ..................................................................................220
6.5.5 Refrigerant piping ...............................................................................221
6.5.6 Test run and handling instruction .....................................................223
6.6 MAINTENANCE DATA ............................................................................... 224
6.6.1 Trouble shooting .................................................................................224
6.6.2 Servicing ..............................................................................................232
Page 3
193
6.1 GENERAL INFORMATION
6.1.1 Specific features
(1) Equipped with an inverter scroll compressor.
¡Low noise. Low vibration and compact.
(2) The long piping makes the location of the inside and units flexible.
¡No need for additional charge of refrigerant : 20 m ¡Maximum piping length : 30 m
(3) Connectable indoor capacity
Number of connectable units : 1 to 2 units Total of indoor units (class kW) : 6.5 kW
(4) Indoor units are available with 5 capacities.
5 capacities ········ 22, 25, 28, 32, 40
(5) Inverter (Frequency converter) for multi-steps power control
¡Heating / Cooling
The rotational speed of a compressor is changed in step in relation to varying load, to interlock with the indoor and outdoor unit fans controlled to changes in frequency, thus controlling the power.
¡Allowing quick heating/cooling operation during start-up period. Constant room temperature by fine-tuned control after the unit
has stabilized.
(6) Fuzzy control
Fuzzy control calculates the amount of variation in the difference between the suction air temperature and the setting temperature in compliance with the fuzzy rules in order to control the air capacity and the inverter frequency.
(7) Self diagnosis function
We are constantly trying to do better service to our customers by installing such judges that show abnormality of operation as follows. (See Page 225)
6.1.2 How to read the model name
Example : SK M 25 Z A
Series No.
Inverter and heat pump type.
Product capacity
Multiple system
Model name
SK : Wall mounted type SC : Outdoor unit
Page 4
194
Item
Models
SKM22ZA SKM25ZA SKM28ZA SKM32ZA SKM40ZA
Cooling capacity W 2200 2500 2800 3200 4000
Heating capacity W 3200 3400 4000 4500 5400
Noise level
Cooling
dB
Hi : 38 Lo : 29 Hi : 39 Lo : 31 Hi : 40 Lo : 30 Hi : 42 Lo : 31
Hi : 52 Lo : 43 Hi : 53 Lo : 45 Hi : 54 Lo : 44 Hi : 56 Lo : 45
Heating
Hi : 39 Lo : 30 Hi : 40 Lo : 32 Hi : 41 Lo : 32 Hi : 42 Lo : 32
Hi : 53 Lo : 44 Hi : 54 Lo : 46 Hi : 55 Lo : 46 Hi : 56 Lo : 46
Exterior dimensions Height × Width × Depth
mm 250 × 750 × 178 275 × 790 × 174
Color Ivory white
Net weight kg 7.5 8.0
Air handling equipment
Fan type & Q’ty
Tangential fan × 1
Motor W 17 18
Cooling 7.0 7.7 9.0 9.5
Air flow (at high)
Heating
CMM
7.5 9.1 10 10
Air filter, Q’ty
Polypropylene net × 2 (Washable)
Operation switch Wireless-Remote controller
Room temperature control M.C thermostat
Pilot lamp RUN (Green), TIMER (Yellow)
Safety equipment
O.D mm (in)
φ 6.35 (1/4″)
φ 9.52 (3/8″) φ 12.7 (1/2″)
Connecting method Flare connecting
Attached length of piping Liquid line : 0.4m Gas line : 0.35m
Insulation Necessary (Both Liquid & Gas lines)
Drain hose Connectable
Accessories (including) Mounting kit
Optional parts
Outdoor units to be combined SCM45ZA
6.2 SELECTION DATA
6.2.1 Specifications
(1) Indoor unit
Models SKM22ZA, 25ZA, 28ZA, 32ZA, 40ZA
(2) Capacity indicated is the rated capacity with one unit operating under ISO-T1 standards conditions.
Refrigerant piping
Liquid line
Gas line
Frost protection, Serial error protection Fan motor error protection
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27ºC 19ºC 35ºC 24ºC ISO-T1, JIS C9612 Heating 20ºC 7ºC 6ºC ISO-T1, JIS C9612
Sound level
Power level
Sound level
Power level
Page 5
195
Item
Model
SCM45ZA
Cooling capacity W 4500 (2000 ~ 5100)
Heating capacity W 5600 (2200 ~ 6000)
Power source 1 Phase 220/240V 50Hz
Power consumption
Cooling
W
1820 (680 ~ 2050)
Heating 1950 (650 ~ 2190)
Running current
Cooling 8.4/7.7
Heating
A
9.0/8.2
Sound level
Cooling : 46 Heating : 48
Noise level
Power level
dB
Cooling : 60 Heating : 62
Exterior dimensions
Height × Width × Depth
mm
595 × 720 × 290
Color Stucco white
Net weight kg 36 Refrigerant equipment
Compressor type & Q’ty
GR5490FD41 × 1
Motor kW 1.2
Starting method Direct start Refrigerant control Capillary tubes + Electric expansion valve
Refrigerant kg R22 1.3 (Pre-charged up to the piping length of 20m)
Refrigerant oil R 0.45 (BARREL FREEZE 32SAM)
Air handling equipment
Fan type & Q’ty
Propeller fan × 2
Motor W 24
Air flow (at high) CMM 30
Shock & vibration absorber Rubber (for compressor)
Safety equipment
Size × Core × Number mm (in)
Liquid line: φ 6.35 (1/4) × 2
Gas line: φ 9.52 (3/8) × 2
Connecting method Flare connecting
Attached length piping
Insulation Necessary (Both Liquid & Gas lines)
Power source supply Terminal block (Screw fixing type)
Size × Core number 1.5 mm2 × 4 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type)
Accessories (included)
Union : (φ 9.52 / φ 12.7) × 1
Installation sheet, Manual instruction
Indoor units to be combined
(2) Outdoor unit
Model SCM45ZA
Compressor overheat protection, Overcurrent protection High pressure protection, Serial signal error protection
Notes (1) The data are measured at the following conditions.
SKM22, 25, 28, 32, 40 type
Refrigerant piping
Connec­tion wiring
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27ºC 19ºC 35ºC 24ºC ISO-T1, JIS C9612 Heating 20ºC 7ºC 6ºC ISO-T1, JIS C9612
(2) The values for capacity and power consumption shown in a range ( ) indicate the minimum and maximum of the range. (3) If the piping length exceeds 20 m, additional charging is required. (20g/m)
Page 6
196
(3) Operation data
¡ The combinations of the indoor units is indicated by numbers. They are read as follows.
(Example) SKM22ZA / 22 SKM40ZA / 40
¡ The capacity of the indoor units is shown by rooms. If this exceeds the maximum capacity of the outdoor unit, the demand
capacity will be proportionally distributed.
¡ If units are to be combined, use the table below to make the proper selection.
(a) Heating
Indoor unit
combination
Heating capacity (kW) Power consumption (W)
Running
current (A)
Room heating capacity (kW) Total capacity (kW)
A room
3.2
3.4
4.0
4.5
5.4
2.8
2.6
2.5
2.3
2.0
2.8
2.6
2.5
2.2
2.8
3.0
3.1
3.3
3.6
2.8
3.0
3.1
3.4
B room Min.
Standard
Max.
Min.
Standard
StandardMax.
1.4
1.4
1.4
1.4
1.4
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
3.2
3.4
4.0
4.5
5.4
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
3.9
4.0
4.7
5.6
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
400
400
400
400
400
650
650
650
650
650
650
650
650
650
1030
1170
1350
1580
2030
1980
1950
1900
1850
1780
1950
1880
1830
1750
1330
1390
1680
2080
2300
2190
2160
2100
2050
1970
2160
2080
2030
1940
4.73/4.34
5.37/4.92
6.20/5.68
7.25/6.65
9.32/8.54
9.09/8.33
8.95/8.21
8.72/8.00
8.49/7.79
8.17/7.49
8.95/8.21
8.63/7.91
8.40/7.70
8.03/7.37
1
room
2
room
22
25
28
32
40
22+22
22+25
22+28
22+32
22+40
25+25
25+28
25+32
25+40
(220/240V)
Page 7
197
(b) Cooling
Indoor unit
combination
Cooling capacity (kW) Power consumption (W)
Running
current (A)
Room cooling capacity (kW) Total capacity (kW)
A room
2.2
2.5
2.8
3.2
4.0
2.2
2.1
2.0
1.9
1.7
2.25
2.2
2.1
1.8
2.2
2.4
2.6
2.8
3.1
2.25
2.4
2.6
3.0
B room Min.
Standard
Max.
Min.
Standard
StandardMax.
1.1
1.1
1.1
1.1
1.1
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.2
2.5
2.8
3.2
4.0
4.4
4.5
4.6
4.7
4.8
4.5
4.6
4.7
4.8
2.5
2.8
3.0
3.5
4.5
4.7
4.8
4.9
5.0
5.1
4.8
4.9
5.0
5.1
350
350
350
350
350
680
680
680
680
680
680
680
680
680
750
900
1040
1200
1580
1750
1820
1830
1840
1850
1820
1830
1840
1850
900
1040
1150
1360
1850
1950
2020
2030
2040
2050
2020
2030
2040
2050
3.44/3.16
4.13/3.79
4.78/4.38
5.51/5.05
7.25/6.65
8.03/7.37
8.36/7.66
8.40/7.70
8.45/7.74
8.49/7.79
8.36/7.66
8.40/7.70
8.45/7.74
8.49/7.79
1
room
2
room
22
25
28
32
40
22+22
22+25
22+28
22+32
22+40
25+25
25+28
25+32
25+40
(220/240V)
Page 8
198
6.2.2 Range of usage & limitations
Indoor intake air temperature (Upper, lower limits)
Indoor units that can be used in combination
Length for one indoor unit
Total length for all rooms
Max. 25m
Max. 30m
6.5kW
1 to 2 units
SCM45ZA
Refer to the selection chart.
Compressor stop/start frequency
Power source voltage
1 cycle time
Stop time
Voltage fluctuation
Voltage drop during start
Interval unbalance
Difference in height between indoor units (C)
Within ± 3% of rated voltage
Within ±15% of rated voltage
Within ±10% of rated voltage
3 min or more
6 min or more (from stop to stop or from start to start)
Max. 25m
Max. 15m
Max. 10m
Outdoor air temperature (Upper, lower limits)
Number of connected units
Total of indoor units (class kW)
Difference in height between indoor and outdoor units
When above outdoor unit (B)
When below outdoor unit (A)
Item
Model
A
B
C
Page 9
199
6.2.3 Exterior dimensions
(1) Indoor unit
Models SKM22ZA, 25ZA
A
750
75
92
40
60
746.9
7.5
62
62 7.5
16
VIEW A
65615
150
450 150
Room temp. thermistor
Terminal block
Piping for Gas (
Ø9.52) 370
Piping for Liquid (
Ø6.35) 420
Piping hole
(
Ø65)
Piping hole
(Ø65)
Piping hole right (left)
178 3
250
4615
19
9236.5
4.5
36
117
40
37
36
569
49
Unit: mm
Model SKM28ZA
A
790
15
67
51
60
62
18
16
780
VIEW A
15 760
170
450 170
Room temp. thermistor
Terminal block
Piping for Gas (Ø9.52) 390
Piping for Liquid (
Ø
6.35) 440
Drain hose 600 (
Ø
16)
Piping hole
(
Ø
65)
Piping hole
(Ø65)
Piping hole right (left)
Unit: mm
174 3
275
187.5 61
46
9260
117
37
6
36
56
9
49
Page 10
200
Models SKM32ZA, 40ZA
A
790
15
67
51
60
62
18
16
780
VIEW A
15 760
170
450 170
Room temp. thermistor
Terminal block
Piping for Gas (Ø12.7) 390
Piping for Liquid (Ø6.35) 440
Drain hose 600 (
Ø
16)
Piping hole
(
Ø
65)
Piping hole
(Ø65)
Piping hole right (left)
Unit: mm
174 3
275
187.5 61
46
9260
117
37
6
36
56
9
49
(2) Outdoor unit
Model SCM45ZA
Ground terminal
Liquid line service valve B Unit
Liquid line service valve A Unit
42.5
14 13.5
84.7
96.5 42.5
14.4
595
340
312.5
290
48.1 46.6
88.2
Elongated hole (2-16×12)
19
12
Drain hole
720 62
50
87 510
411.5
256
123
29.7
Terminal block
Gas line service valve B Unit
Gas line service valve A Unit
35°
35°
(ø6.35)
(ø6.35)
(ø9.52)
(ø9.52)
Page 11
201
6.2.4 Piping system
Model SCM45ZA
Outdoor unit
Indoor unit
Thermistor (Th
I
-R)
Thermistor (Th
I
-A)
Check joint
Thermistor (Th
O
-D)
Thermistor (Th
O
-A)
Thermistor (ThO-R)
Heat exchanger
Heat exchanger
Liquid line
Gas line
(ø6.35)
(ø6.35)
(ø9.52)
(ø9.52)
Strainer
Suction
Accumulator
Compressor
Discharge
Muffler
4 way valve
Service valve
(Liquid)
Capillary tube
Electric expansion valve
EEVA
EEVB
Cooling cycle Heating cycle
Service valve
(Gas)
Page 12
202
6.2.5 Selection chart
Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be obtained in the following way.
Net capacity = Capacity shown on specificationCorrection factors as follows. (1) Coefficient of cooling and heating capacity in relation to temperatures
(2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way piping length between the indoor and outdoor units.
(3) Correction relative to frosting on outdoor heat exchanger during heating
In additions to the foregoing corrections (1), (2) the heating capacity needs to be adjusted also with respect to the frosting on the outdoor heat exchanger.
15
ISO-T1 Standard ConditionOutdoor air W.B. temperature °C W.B.
010-10 -5 5
14 16 18 20 22
15
10
27 25
20 15
20
25
30
35
40
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
43
24
20
ISO-T1 Standard ConditionIndoor air W.B. temperature °C W.B.
Heating
Cooling
Applicable range
Coefficient of cooling &
Heating capacity in
relation to temperature
Cooling operation
Outdoor air D.B.
temperature
°C D.B.
Heating operation
Indoor air D.B.
temperature
°C D.B.
Air inlet temperature of
outdoor unit in ˚C WB
Adjustment coefficient
-10
0.95-90.94-70.93-50.91-30.88-10.8610.8730.9251.00
Piping length [m]
Cooling Heating
7
1.0
1.0
10
0.99
1.0
15
0.975
1.0
20
0.965
1.0
25
0.95
1.0
Page 13
203
RD
WH
BK
JR
F (250V · 3.15A)
Power line (Outdoor unit)
Black Blue Gray Yellow Red White Purple Yellow/Green
BK BL GR Y RD WH PP Y/GN
Color symbol
S
ZNR
CF
I
CNC CNB
TR
FMI
Q
CNM
CNE CND CNG
Display
Wireless R-Amp
Back up switch
Printed circuit board
ThI-AThI-R
FMI
SM
COM
CNU
CF
BL
RD RD BK BK
CNW
GR PP
Y WH RD
1
2
Y/GN
3
CM FM
0
L DS EEVA, B 20S
Parts name
Compressor motor Fan motor Reactor Diode stack Electric expansion valve 4 way valve (coil)
Symbol
Tho-A Tho-R Tho-D LED2 LED1, 3
Parts name
Thermistor (outdoor air temp.) Thermistor (outdoor H.X temp.) Thermistor (comp. dome temp.) Warning lamp (Red) Serial signal lamp (Green)
Symbol
Indoor Unit
FM
I
CF
I
SM TR ZNR
Parts name
Fan motor Capacitor (for FM
I
) Flap motor Transformer Varistor
Symbol
Q F Th
I
-A
Th
I
-R
Parts name
Fan motor control triac Fuse Thermistor (Room temp.) Thermistor (Indoor H. X temp.)
Symbol
6.3 ELECTRICAL DATA
Meaning of marks
Outdoor Unit
6.3.1 Electrical wiring
(1) Indoor unit
Models SKM22ZA, 25ZA, 28ZA, 32ZA, 40ZA
Page 14
204
(2) Outdoor unit
Model SCM45ZA
~+
++++
~
1 2 3 1 2 3
1 2
Y/GN
Y/GN
WH
BK
BL
WH
BK
RD
Serial A
Serial B
52X2-4
AC·R
AC·S
S. OUT
R. IN
S. IN
G
CNB CNB
LED1 LED3 LED2
(Red)
GY
DS
IC2
P
RDU WH BK
Tho-A Tho-R
CND
CNC
CNACNFCNECNA
Tho-D
V
W
N
BL
ORWH
L
WH
BK
UNIT A
UNIT B
Power source 1 Phase 220/240V 50Hz
Printed circuit board
Fuse
250V 25A
Printed circuit board
Power
transistor
CM
20S EEVA FMoEEVB
(Green)
Black Blue Gray Red White Orange Yellow/Green
BK BL GY RD WH OR Y/GN
Color symbol
Page 15
205
FAN SPEED ON/OFF
MODE
TEMP
AIR FLOW
SET TIMER TIMER
ACL
HI POWER
ECONO
CONT
HI POWER
ECONO
ON OFF
TIMER
AUTO
HI
MED
LO
FAN SPEED indicator
Indicators the ¡ for the fan speed which has been set.
ON-TIMER OFF-TIMER indicator
FAN SPEED button
Each time the button is pushed, the ¡ indicator is switched over in turn.
HI POWER button
This button changes the HI POWER operation.
SET TEMPERATURE button
This button sets the room temperature.
ECONOMY button
This button changes the ECONOMY operation.
SET TIMER button
This button sets the ON TIMER time or SLEEP time.
HI POWER operation indicator
Indicators during HI POWER operation.
ECONOMY operation indicator
Indicators during ECONOMY operation.
Operation switch over indicator
Indicators the ¡ for the operation which has been set.
AIR FLOW indicator
Indicator selected flap mode.
OPERATION MODE select button
Each time the button is pushed, the ¡ indicator is switched over in turn.
ON/OFF button
This button, when pressed, starts operation and stops when repressed.
AIR FLOW button
This button changes the flap mode.
TIMER button
The button selects ON TIMER operation, OFF-TIMER operation or normal operation.
Reset switch
Switch for resetting microcomputer.
RUN TIMER
INVERTER
TIMER RUN
RUN (HOT KEEP) lamp (green)
Illuminates during operation.
Flashs at stop blowing due to the hot keep.
Illuminates during TIMER operation.
TIMER lamp (yellow)
INVERTER
¡ Above figure shows all indications for the purpose of explanation,
but practically only the pertinent parts are indicated.
Heat pump model : [ (AUTO) · (Cool) · (Heat) · (Dry)] Cooling only model: [ (AUTO) · (Cool) · (Fan) · (Dry)]
6.4
OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
(1) Remote Controller
(2) Indoor unit indicator
Models SKM22, 25 models
Models SKM28, 32, 40 models
Page 16
206
(3) Back-up switch
When the remote controller become weak, or if the remote controller is lost or malfunctioning, this switch may be used to turn the unit on and off.
(a) Operation
Push the switch once to place the unit in the automatic mode. Push it once more to turn the unit off.
(b) Detail of operation
Operation starts in the same way as the previous operation.
¡ The flap operation as shown above will be repeated.
Stops at the level position for one minute.
s
In case of cooling
t
and dry operation
s
In case of heating
t
operation
Sway operation
Sway operation
(4) Flap control
Control the flap by AIRFLOW button on the wireless remote control.
(a) Natural flow (AUTO)
The flap will be automatically set to the angle of air flow best to operation.
1) Starting time of operation
ON/OFF
¡ The flap operation as shown above will be repeated.
Models SKM22, 25 models Models SKM28, 32, 40 models
ON/OFF button
(c) Swing flap
Flap moves in upward and downward directions continuously.
Horizontal blowing
2) When not operating
The flap returns to the position of air flow directly below, when operation has stopped.
(b) Memory flap (Only case of SKM28, 32, 40 models)
While the flap is operating if the AIRFLOW button is pushed once, it stops swinging at an angle. As this angle is memorized in the microcomputer, the flap will be automatically set to the angle when next operation is started.
Recommendable stopping angle of the flap
Slant forward blowing
COOLDRY
HEAT
ON/OFF button
Page 17
207
(5) Comfort timer setting
If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto mode operation is selected, the comfort timer starts and determines the starting time of next operation based on the initial value of 15 minutes and the relationship between the room temperature at the setting time (temperature of room temperature thermistor) and the setting temperature. (Max. 60 minutes)
Operation mode Operation start time correction value (Min.)
3 < Room temp. – Setting temp. 1 < Room temp. – Setting temp. 3 Room temp. – Setting temp. 1
At cooling
+5 No change –5
3 < Setting temp. – Room temp. 2 < Setting temp. – Room temp. 3 Setting temp. – Room temp. 2
At heating
+5 No change –5
Notes (1) At 5 minutes before the timer ON time, operation starts regardless of the temperature of the room temperature thermistor (Th
I-A).
(2) This function does not actuate when the operation select switch is set at the dehumidifying as well as the dehumidifying in the auto mode.
However, the operation of item (1) above is performed during the dehumidifying in the auto mode.
(3) During the pleasant reservation operation, both the operation lamp and timer lamp illuminate and the timer lamp goes off after expiration of the timer, ON setting
time.
Corrects the starting time of next operation by calculating the temperature difference.
(Example) Heating
Setting temperature
Room temperature
Operation starting time
Time
Setting time
15 min. 10 min. 5 min. earlier earlier earlier
¡ If the difference (= Setting temperature – Room
temperature) is 4ºC, the correction value is found to be +5 minutes from the table shown above so that the starting time of next operation is determined as follows:
15 min. earlier + 5 min. = 20 min. earlier
↑↑
Current operation Correction value start time
Capacity control is within the range shown above. If demand capacity of the indoor units exceeds the maximum capac­ity of the outdoor unit, the demand capacity will be proportionally distributed.
2) Outdoor unit speed control (28 ~ 120 rps)
(6) Cooling operation
(a) Summary
1) Capacity control
Model
Capacity
SCM45ZA
2.0 ~ 5.1 kW
SCM45YA
2.0 ~ 5.1 kW
28 rps or less More than 28 rps, but 120 rps or less More than 120 rps
Decision speed
28 rps
28 to 120 rps
120 rps
Indoor unit instruction total speed value
Note (1) The indoor unit instruction total speed value is the total of the values from each unit in item (b).
(b) Mode switching
Within the selected mode, the unit operates using the values shown below which were obtained by multiplying a conversion coefficient to the indoor unit instruction speed.
Model (Indoor)
Operation Mode
Automatic
High
Medium
Low
Hi power
Econo
28 ~ 58
28 ~ 58
28 ~ 44
28 ~ 30
58
28 ~ 34
28 ~ 68
28 ~ 68
28 ~ 50
28 ~ 32
68
28 ~ 36
28 ~ 88
28 ~ 88
28 ~ 60
28 ~ 30
86
28 ~ 50
28 ~ 96
28 ~ 96
28 ~ 70
28 ~ 34
96
28 ~ 40
28 ~ 110
28 ~ 118
28 ~ 100
28 ~ 40
108
28 ~ 50
22 25 28 32 40
(rps)
Page 18
208
(7) Heating Operation
(a) Summary
1) Capacity control
Model
Capacity
SCM45ZA
2.2 ~ 6.0 kW
28 rps or less More than 28 rps, but 120 rps or less More than 120 rps, but 134 rps or less More than 134 rps
Decision speed
28 rps
28 to 120 rps
120 to 134 rps
134 rps
Indoor unit instruction total speed value
Capacity control is within the range shown above. If demand capacity of the indoor units exceeds the maximum capac­ity of the outdoor unit, the demand capacity will be proportionally distributed.
2) Outdoor unit speed control (28 ~ 134 rps)
Note (1) The indoor unit instruction total speed value is the total of the values from each unit in item (b).
(c) Operation of Major Functional Components in Cooling Mode
Functional components
Operation
Instruction speed
Indoor unit fan
Compressor
Outdoor unit fan Electronic
expansion valve
See preceding table
ON
According to instruction speed
According to outdoor unit speed
According to decision speed
0
(All indoor units)
OFF
According to stop mode
According to mode switching
OFF
0
(Thermostat off units)
ON
All closed
(Thermostat off units)
According to outdoor unit speed
According to mode switching
All closed
(Fan, stop, abnormal stop units)
0
(Fan, stop, abnormal stop units)0 (All units)
ON
First speed or low
OFF
OFF
According to stop mode
Cooling
Thermostat OFF (All indoor units)
Thermostat OFF
(Some of indoor units)
Fan, stop, abnormal stop
(Some of indoor units)
Failure
(Outdoor Unit)
Fixed Automatic
(b) Mode switching
Within the selected mode, the unit operates using the values shown below which were obtained by multiplying a conversion coefficient to the indoor unit instruction speed.
(c) Operation of Major Functional Components in Heating Mode
Model (Indoor)
Operation Mode
Automatic
High
Medium
Low
Hi power
Econo
28 ~ 74
28 ~ 74
28 ~ 50
28 ~ 34
76
28 ~ 42
28 ~ 80
28 ~ 80
28 ~ 58
28 ~ 36
82
28 ~ 44
28 ~ 120
28 ~ 120
28 ~ 86
28 ~ 46
120
28 ~ 60
28 ~ 126
28 ~ 126
28 ~ 92
28 ~ 46
120
28 ~ 54
28 ~ 134
28 ~ 134
28 ~ 126
28 ~ 54
126
28 ~ 64
22 25 28 32 40
(rps)
Functional components
Operation
Instruction speed
Indoor unit fan
Compressor
Outdoor unit fan Electronic
expansion valve
See preceding table
ON
According to mode switching
According to instruction speed
According to outdoor unit speed
According to decision speed
0
(All indoor units)
OFF
According to stop mode
Hot Keep
Hot Keep
OFF
0
(Thermostat off units)
ON
After 4 minutes all closed: 58 pulse
(Thermostat off units)
According to mode switching
According to instruction speed
According to outdoor unit speed
58 Pulse
(Fan, stop, abnormal stop units)
0
(Fan, stop, abnormal stop units)0 (All units)
ON OFF
Hot Keep
Hot Keep
OFF
According to stop mode
Heating
Thermostat OFF (All indoor units)
Thermostat OFF
(Some of indoor units)
Fan, stop, abnormal stop
(Some of indoor units)
Failure
(Outdoor Unit)
Fixed Automatic
Page 19
209
(d) Hot keep operation
If the hot keep operation is selected during the heating operation, the indoor fan is controlled based on the temperature of the indoor unit heat exchanger (detected with ThI-R, indoor unit heat exchanger thermistor) to prevent blowing of cool wind.
¡ Normal mode (Normal heating operation, operation after HI POWER completion)
1st speed
¡ Values of a, b
AB
At 0 rps command 22 25 Other than 0 rps
17 19
command
Note (1) Refer to the table shown above right for the values A and B.
¡ Hot keep M mode [During HI POWER operation (for 15 min.)]
Indoor fan
Indoor heat exchanger temp. (˚C)
2nd speed
3rd speed
4th speed
5th speed
6th speed
7th speed
1st speed
Indoor heat exchanger temp. (˚C)
2nd speed
3rd speed
4th speed
5th speed
6th speed
7th speed
(e) Defrosting
(i) When the following conditions are met, the defrosting operation will start.
1) During normal operation
a) When 40 minutes has passed since the start of heating or 40 minutes after the last defrosting (based on cumu-
lative operation time of compressor).
b) When the outdoor heat exchanger thermistor (Tho-R) temperature is –2 °C or less for 3 continuous minutes
after 37 minutes have passed.
c) Outdoor temperature thermistor (Tho-A) – outdoor heat exchanger thermistor (Tho-R) temperature
0.44 ×
outdoor temperature thermistor (Tho-A) temperature + A °C or more.
A = Outdoor temperature – 2 °C: 4, outdoor temperature < – 2 °C: 6.
d)When the compressor is operating.
u Or, during heating, defrosting will start when the decision speed counts zero (0) rps for 10 times or more
and all conditions in a), b) and d) have been satisfied.
2) During defrosting acceleration
a) When 40 minutes has passed since the last defrosting (based on cumulative operation time of compressor). b) When the compressor is operating.
u Or, during heating, defrosting will start when the decision speed counts zero (0) rps for 10 times or more
and all conditions in a) and b) have been satisfied.
Note (1) Defrosting acceleration is when the finishing of the previous defrosting is according to the defrosting conditions of the 10 minutes
that have passed.
Indoor fan
Page 20
210
3) Operation of function component in defrosting
4) Conditions for finishing defrosting
When any of the following conditions is met, the defrosting finishing operation will start.
1 When the temperature of the outdoor heat exchanger thermistor (Tho-R) is 9 °C or more. 2 When 10 minutes has passed after the start of defrosting.
(8) Determining the operating mode
The cooling and heating operating modes are the remote control switch mode that have been previously determined.
If a mode differing from these is selected after this, the selected mode will appear in the display of the remote control, but only the fan will operate.
A unit
B unit
Cooling
Cooling
Fan Heating
HeatingFan
Cooling
switch
ON
Heating
switch
ON
Heating
switch
ON
Cooling
switch
ON
Heating
switch
ON
Operation Operation
Operation Operation
Operation
Example of operating pattern
Note (1) [ ] indicates currect operation.
1 2
Example
First operation Second operation
Notes
Different mode is only fan operation.
Selected Mode
Cooling Heating
Remote Control Display
Cooling Heating
Operation
Cooling Heating
Selected Mode
Heating Cooling
Remote Control Display
Heating
Cooling
Operation
Fan
(1)
Fan
Note (1) If the display shows
heating and the opera­tion is fan, Hot Keep will operate.
Notes (1) Indoor unit fan is
in response to Hot Keep.
(2) Outdoor unit fan
starts
6
seconds af­ter the start of the compressor.
80 sec.80 sec.
ON
OFF
OFF
0 rps
According to rps
EEV control
Calculated start
Opening in relation to conditions
Opening in relation to conditions
Defrost end conditions
Start of defrost operation Defrost operation
Fully closed
Defrost end operation
80 rps
Decision speed Decision speedOutdoor unit speed
Outdoor unit fan
Electronic expansion valve EEVA,B (Operating unit)
Electronic expansion valve EEVA,B (Stopped unit)
4-way valve
200 pulse
When 2 units are operating: 150 pulse When 1 unit is operating: 200 pulse
Page 21
211
(9) Control and protection functions
(a) Start of protection for compressor
When the decision speed becomes a speed other than 0 rps and when the compressor is starting operation, an inverter decision speed of 40 rps or less indicates four-way valve switching protection and a speed of 40 rps or more indicates that protection of the compressor has started.
1) Start of protection for compressor
a) After the compressor has started, the speed of the outdoor unit will reach a maximum value of 56 rps for 1 minute
and 45 seconds.
b) During this time, if the decision speed exceeds 56 rps, operation will be at 56 rps; if it is 56 rps or less, operation will
be at the decision speed or operation with 4-way valve switching protection. c) The outdoor unit fan speed operates according to outdoor unit speed. d) If restarting after a thermostat stop, the protection function for the outdoor unit operates and when restarting after
the inverter stop, compressor protection is not started. e) During the start of protection, current safe and compressor overheat have priority.
2) 4-way valve switching protection
Four-way valve switching protection is performed so that four-way valve switching will be performed smoothly. a) When the decision speed starts at less than 40 rps, it forces the decision speed to operate at 40 rps for 30 seconds. b) After 30 seconds, the speed of the outdoor unit is transferred to the decision speed. c) This function applies to all units starting from an outdoor unit speed of 0 rps. d) Current safe and compressor overheat protection are enabled even when this function is in operation.
(b) Heating overload protection control
During heating operation, if the outdoor unit is operating at a speed at 28 rps or more and the outdoor temperature is 12 °C or more for 30 continuous seconds, current safe control is performed. Operation is restored when the outdoor temperature is 10 °C or less.
(c) Cooling overload protection control
During cooling operation, if the outdoor unit is operating at a speed at 28 rps or more and the outdoor temperature is 39 °C or more for 3 continuous minutes, current safe control is performed by turning the outdoor fan dial up by 1 unit. Operation is restored when the outdoor temperature is 38 °C or less.
(d) Heating thermostat OFF control
When there is a heating operation being performed for one room while a heating thermostat OFF is being performed in another room, the following controls are performed to prevent overheating.
1) This control is performed when all of the following conditions have been satisfied.
a) Compressor: During operation (determined speed 28 rps or more) b) One room serial signal: Operating mode – heating, command speed: other than 0 rps. c) Other room serial signal: Operating mode – heating, command speed: 0 rps.
2) Description of control
Start of control
Release of control
58 pulse
4 min
Fully closed
EEV A, B Heating 0 rps compatible
EEV A, B Operating unit compatible
Outdoor unit fan
According to outdoor rps
Actual operating speed Decision rps
Outdoor unit speed Decision rps
Functional components Operation of each functional components Remarks
Page 22
212
(e) High pressure cut protection control
The high pressure cut protection operates during heating operations when a heating 0 rps serial signal is received from one of the two operating indoor units. 1 When only one of two operating units sends a “heating 0 rpssignal.
2 min.
0 rps
instruction
A room
B room
Indoor unit instruction speed
Functional components Operation of each functional components Remarks
Instruction speed from indoor unit that has heating 0 rps.
Instruction speed for indoor unit that has other than heating 0 rps.
Actual operating speed
Outdoor unit fan
4-way valve
EEVA
EEVB
Calculated rps
0 rps
Calculated rps
0 rps
Fully closed
Decision rps
58 pulse or EEV control
According to outdoor rps
OFF
ON
OFF
According to outdoor rps
According to outdoor rps
Corresponding expansion valve for unit with serial signal that has heating 0 rps.
Corresponding expansion valve for unit with serial signal that has other than heating 0 rps.
2 When decision speed becomes 0 rps during high pressure cut protection control
2 min.
200 pulse
200 pulse
0 rps instruction
Functional components Operation of each functional components Remarks
The sequence for o rps instruction
shows one example.
Actual operating speed
Outdoor unit fan
4-way valve
EEVA
EEVB
Calculated rps
Calculated rps
0 rps
0 rps
Decision rps
0 rps
According to
outdoor rps
OFF
ON
According to
outdoor rps
Fully closed
According to
outdoor rps
Fully closed
OFF
0 rps instruction
A room
B room
Indoor unit instruction speed
2 min. 25 sec.
Page 23
213
(f) Low Hz continuous operation protection control
The following controls are performed to return oil to the compressor when the outdoor unit speed of 28 rps or more to 40 rps or less is continuously operated for 20 minutes.
1) The decision speed is forced to operate at 40 rps for 2 minutes.
2) The outdoor fan and electronic expansion valve are operated according to the outdoor unit speed.
3) If there is an instruction exceeding 40 rps during this forced 40 rps operation, this control ends and the operation follows that instruction.
(g) Heating low temperature protection control
The following controls are performed when the outdoor unit is in heating operation at a speed other than 0 rps and the outdoor temperature is 2 °C or less for 1 continuous minute.
1) The outdoor unit fan speed is forced to 5th speed.
2) This control is ended when the outdoor temperature reaches 4 °C or more.
(h) Current safe control
1) When converter in port current is detected at the current sensor (CT) and it exceeds the set amperage, the speed is reduced 2 rps. This is rechecked after one second and if it still exceeds the set amperage, the speed is reduced another 2 rps.
2) If the actual speed operated at 28 rps or less, the inverter is stopped. It is restarted after a 3 minute delay. However, if it is restarted repeatedly within an interval of 1 hour, it will not start on the 5 times.
(i) Current cut
This detects converter output current at the shunt resistor and if it exceeds the set value, the inverter is stopped. It is restarted after a 3 minute delay. However, if the current cut operates again when the actual speed is less than 20 rps, it will not start on the 4 times.
(j) Compressor overheat protection
The detection temperature of the compressor dome thermistor (Tho-D) is used to prevent oil deterioration and damage to the motor wire due to overheating of the compressor.
1) If Tho-D becomes
125 °C, the inverter is stopped. After the stop mode has been activated, the inverter will be
restarted when Tho-D becomes < 95 °C. However, if it is restarted repeatedly within an interval of 1 hour, it will not start on the 3 times.
2) When 105 °C
Tho-D < 125 °C, the following outdoor unit speed controls are performed.
(k) Serial transmission abnormality protection
If the compressor is operating with an outdoor speed other than 0 rps and a serial signal cannot be received from all indoor controls with outdoor controls having serial signals other than stop - 0 rps continuously for 1 minute and 55 seconds, the inverter is stopped. After the inverter has been stopped, it will be restarted after the compressor start delay if a serial signal can be received again from the indoor control.
Compressor doom temperature (°C)
Notes (1) If the temperature of the compressor dome is 105 °C or more and less than 125 °C, the outdoor unit speed is reduced by 8 rps.
(2) After 20 seconds, if the temperature of the compressor dome has decreased, it is lowered 2 rps. If the temperature has risen or is
the same, it is lowered another 8 rps.
(3) If the temperature of the compressor dome is 95 °C or more and less than 105 °C, the speed of the outdoor unit is maintained. If
operation is maintained at the same speed for 6 minutes or more or if the temperature is 95 °C or less, control is returned to normal operation.
6 minutes of more has passed
(3)
6 minutes of more has passed
(3)
6 minutes of more has passed
(3)
Lower limit 28 rps
8 rps
12510595
8 rps or 2 rps
(2)
8 rps or 2 rps
(2)
0 rps
Decision speed
Inverter
Page 24
214
(l) Compressor lock
If the motor for the compressor does not turn a half a turn approximately 0.3 seconds after it has been started, it is determined that a compressor lock has occurred and the inverter is stopped.
(m) Compressor dome thermistor broken wire protection control
1) When the outdoor unit speed is other than 0 rps and after the compressor has started to operate, if after 10 minutes there is a compressor dome thermistor temperature10-second interrupt signal (less than 7 °C), it is immediately placed in stop mode and restarted. (This detection is only performed once when the compressor is on.)
2) If an error continues for 4 times continuously, a permanent stop is made. (Restoration requires resetting the power supply.)
(n) Outdoor unit failure
This is a function for determining when there is trouble with the outdoor unit during air conditioning. The inverter is stopped if any one of the following in item 1), 2) is satisfied. Once the unit is stopped by this function, it is not restarted.
1) When the input current is measured at 1 A or less for 3 continuous minutes or more.
2) If the outdoor unit sends a 0 rps signal to the indoor unit 3 times or more within 20 minutes of the power being turned on.
(o) Stop mode (Decision speed is 0 rps, when the protection function for the outdoor controller is operating,
when restarting due to operation change)
(10) Regulation of outdoor air flow
(a) The fan operates as follows according to the speed of the outdoor unit. (Except during defrost.)
(b) If the outdoor unit fan motor speed is 300 rpm or less for 30 seconds or more continuously, the compressor and outdoor unit
fan are stopped.
Functional
components
Operation
Outdoor unit
speed
Actual operating
speed
Outdoor unit fan
E EVA
4-way valve
E EVB
Cooling Heating
Operation of outdoor unit protection function, if restarting
when recovering from thermostat stop and switching operations.
If stopping due to an indoor unit instruction and if permanent stop.
Cooling Heating
Stop instructions
All stop Stop instructions All stop 0 rps instructions Restart Stop instructions Restart
Decision
rps
0
Outdoor
rps
0
According to
outdoor rps
0
ON
OFF
EEV
control
Fully
closed
EEV
control
Fully
closed
3 min.
3 min.
3 min.
2 min.
2 min. 25 sec.
200 pulse
200 pulse
55 sec.
3 min.
3 min.
3 min.
2 min.
2 min. 25 sec.
200 pulse
200 pulse
2 min.
55 sec.
2 min. 25 sec.
200 pulse
200 pulse
2 min.
2 min. 25 sec.
200 pulse
200 pulse
Outdoor unit speed
Outdoor fan speed
Fuzzy auto
when starting
1st speed
Less than 80
2nd speed
80 or more and
less than 100
3rd speed
100 or more
and less than 120
4th speed
120 or more
5th speed
Page 25
215
6.5 APPLICATION DATA SAFETY PRECAUTIONS
¡ Please read these “Safety Precautions” first then accurately execute the installation work. ¡ Though the precautionary points indicated herein are divided under two headings,
WARNING and CAUTION , those points
which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the
WARNING section. However, there is also a possibility of serious consequences in relationship to the points listed in the CAUTION section as well. In either case, important safety related information is indicated, so by all means, properly observe all
that is mentioned.
¡ After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please explain
operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner’s manual.
Moreover, ask the customer to keep this sheet together with the owner’s manual.
WARNING
¡ This system should be applied to places as households, residences and the like. Application to inferior environ-
ment such as engineering shop could cause equipment malfunction.
¡ Please entrust installation to either the company which sold you the equipment or to a professional contractor.
Defects from improper installations can be the cause of water leakage, electric shocks and fires.
¡ Execute the installation accurately, based on following the installation manual. Again, improper installations can
result in water leakage, electric shocks and fires.
¡ For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insuffi-
cient, injury can result from a falling of the unit.
¡ For electrical work, please see that a licensed electrician executes the work while following the safety standards
related to electrical equipment, and local regulations as well as the installation instructions, and that only exclu­sive use circuits are used. Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and fires.
¡ Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted
to the terminal connection part, through properly securing it improper connection or securing can result in heat generation or fire.
¡ Take care that wiring does not rise upward, and accurately install the lid/service panel. It’s improper installation
can also result in heat generation or fire.
¡ When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the
designated refrigerant (R22) within the refrigeration cycle. Rupture and injury caused by abnormal high pressure can result from such mixing.
¡ Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this
company can result in water leakage, electric shock, fire and refrigerant leakage.
¡ Ventilate the work area when refrigerant leaks during the operation.
Coming in contact with fire, refrigerant could generate toxic gas.
¡ Confirm after the foundation construction work that refrigerant does not leak.
If coming in contact with fire of a fan heater, a stove or movable cooking stove, etc., refrigerant leaking in the room could generate toxic gas.
CAUTION
¡ Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightning rod or a telephone
ground wire. Improper placement of ground wires can result in electric shock.
¡ The installation of an earth leakage breaker is necessary depending on the established location of the unit.
No installing an earth leakage breaker may result in electric shock.
¡ Do not install the unit where there is a concern about leakage of combustible gas.
The rare event of leaked gas collecting around the unit could result in an outbreak of fire.
¡ For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it
to prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
Page 26
216
6.5.1 Installation of indoor unit
(a) Caution for installation
1) The system should be applied to places as households, residences and the like.
2) The equipment shall be installed in accordance with national wiring regulations.
3) The connection to the fixed wiring of the mains supply must be made via a double pole isolating switch with a contact gap of at least 3mm in each pole.
4) When the outdoor unit has a possibility of being overturned or being displaced and fall from its original installation position, the outdoor unit should be fixed in its position by the use of anchor bolts or wires.
(b) Installation of indoor unit
1) Fixing of installation Board
Outdoor side
5°
ø65
Indoor side
Wall thickness × 1.5cm
Sleeve
Sleeve Inclined plate
Sealing plate
Putty
Pipe
Assembled state
¡ Drill a hole with a 65 whole
core drill.
¡ Find the inside wall structures (pillar, etc.) and secure
the board after checking the horizontal level.
Unit: mm
¡ When the pipe is connected at the rear, cut off the lower and the right
side portions of the sleeve collar (as shown by the broken line.)
Reference hole
450
Level surface matching mark
¡ Horizontal level adjustment of the board is conducted
with four temporarily tightened screws.
¡Adjust so that the board will be horizontal with the
reference hole in the center.
2) Drilling of holes and fixture of sleeve (Option ports)
¡The connecting wires may touch the metal inside the wall and cause danger so it is necessary to always use the sleeve.
Installation space (Indoor unit) Models SKM22, 25 models Models SKM28, 32, 40 models
Indoor unit
[Front View]
Installation board
50
Service space
100
15
Service space
15
760
450170 170
5
260
9
40 Service space
Service space
15
61187.5
36
67
51
Gas pipe 390
Liquid pipe 440
Drain hose 600
(Connection hole outside diameter ø16)
Position for the hole in the wall ø65
Position for the hole in the wall ø65
50
75 615
450
60
100
40
Gas pipe 370
Liquid pipe 420
92
ø65
ø65
9
40
236.54.5
36
36
15
19
15
46
Service space
Position for the hole in the wall
Position for the hole in the wall
Service space
Service space
Service space
Indoor unit
Installation board
150
150
Page 27
217
3) Mounting of interconnecting wires (Field wiring)
a) Remove the lid. b) Remove the terminal block cover. c) Connect the connection wire securely to the terminal block.
Cautions when piping from the left and the rear center of the unit
Earth terminal
Terminal block
Wiring clamp
Cover
Lid
Pipe
Drain hose
Left Side Piping
Left rear piping Right rear piping
Right
Rear
Under
Left rear
Left
Left side piping
[Procedure for exchanging the drain hose.]
Right side piping
1.Remove the drain hose.
2.Remove the drain cap.
3.Insert the drain cap.
4.Connect the drain hose.
Right Side Piping
The piping can be removed from the rear, left, left rear, right and from under the unit.
¡ Tape only the portion that runs through the wall.
Always tape the crossover wires with the pipe.
¡ Loosen and remove the
spring-type clamp.
¡ Remove with your
hand or a pair of pliers.
¡
Use a hexagonal wrench to correctly insert the drain cap which was removed in 2. Caution: Be careful because if the cap is not inserted property, water leak may occur.
¡ Loosen the spring-type
clamp and securely insert the drain hose. Caution: Be careful because if the cap is not inserted properly, water leak may occur.
¡ Hold the bottom of the pipe and change its direction
before stretching it and shaping it.
Wall
Gutter
Pipes storage area
¡ When conducting the central rear piping, use
a nipper to cut out knock-out holes in the installation board.
¡ Do not place the power supply cords
above the gutter, because the air conditioner is structured in a way where condensation on the back side is collected in to the drain pan before drainage.
Removed by pressing in the section with the broken lines and pulling it towards the arrow.
Use cables for interconnection wiring to avoid loosening of the wires. CENELEC code for cables Required field cables. H05 RNR4G1.5 (Example) H Harmonized cable type 05 300/500 volts R Natural-and/or synth. rubber wire insulation N Polychloroprene rubber conductors insulation R Stranded core 4 Number of conductors G One conductor of the cable is the earth conductor (yellow/green)
1.5 Section of copper wire (mm
2
)
[Top View]
1) Connect the connection wire securely to the terminal block. If the
wire is not affixed completely, contact will be poor, and it is danger­ous as the terminal block may heat up and catch fire.
2) Take care not to confuse the terminal numbers for indoor and out-
door connections.
3) Affix the connection wire using the wiring clamp.
d) Attach the terminal block cover. e) Attach the lid.
4) Shaping the pipe and drain hose
[Shaping the pipe] [Taping of the exterior]
Page 28
218
Drainage
Too high It curves like a wave.
under 5 cm
Smell from sewerage drains.
The end of the drain hose is touching the water.
The gap to the ground is less than 5 cm.
The end of the drain hose is touching the sewage drains.
Drain hose
Extension drain hose
when a part of the extension drain hose is indoors
Shielding pipe
Indoor unit
Hook (2 locations)
Installation
board
Instalation board
Indoor unit base lower hook
Wall
Installing steps
1. Hook the upper part of the indoor unit to the installation board.
2. The unit can be installed simply by gently pushing in the lower part.
¡ The drain hose must be fit with a downward slope. ¡ Do not set the drain hose like the following illustrations.
¡ Pour water in the drain pan below the heat exchanger and confirm that the water is drained outside. ¡ If the extension drain hose is indoors, make sure it is insulated using a shielding pipe (not supplied).
5) Securing the Indoor Unit to the Installation Board
6.5.2 Installation of remote controller
(1) Mounting method of battery
Uncover the remote control switch, and mount the batteries (UM-4 × 2 pieces) in the body regularly. (Fit the poles with the indication marks, , & . without fail)
(2) Fixing to pillar or wall
(a) Conventionally, operate the remote control switch by holding in your hand. (b) In the case of stationary operation service as by mounting on the holder for
the remote control switch, make sure that the locating place is satisfactory for access service before installing it.
(c) Avoid installing it on a clay wall etc.
Cover
Battery
Holder (remote control switch)
Adjust the installation to vertical attitude.
Avoid projecting the screw head.
Wood screw
ø3.5 × 16
Page 29
219
Air inlet
Service space
()
Air inlet
Air Outlet
Note (1) If the wall is higher than 1.2 m or a ceiling is
present, distances larger than indicated in the above table must be provided.
300
Air inlet Air inlet
Air inlet
Air Outlet
Air Outlet
Air Outlet
80 mm or more
180 mm or more
75 mm or more
80 mm or more
280 mm or more
80 mm or more
280 mm or more
250mm or more
Air inlet
(2) Installation of outdoor unit
(a) Make sure that sufficient space for installation and service is secured. (b) Fix the leg sections of the unit on a firm base which will not play.
Attach cushion pads, etc. between the unit and the mounting fixtures not to transmit vibration to the building.
(c) Attach a drain elbow, etc. under the drain port of the bottom plate to guide drain water.
(Drain elbow should not be used where days when temperature drops below 0°C continue for several days. Draining may be disturbed by frozen water.)
(d) When installing the unit at a higher place or where it could be toppled with strong winds, secure the unit firmly with
foundation bolts, wire, etc.
6.5.3 Installation of outdoor unit
(1) Selection of installation location
(Please install with the customers consent in a location that follows the conditions listed below.) (a) Where the following installation space is available, and where air does not gather. (b) Where rain and sunlight do not directly hit the unit, and where there is enough air circulation. (c) Also, where the unit cannot be buried by snow.
A location which can sustain the weight of the unit, and where noises and vibrations are not enhanced. (d) Where blasts of cold or hot air and noise do not bother the neighbors. (e) Where the unit does not receive heat radiation from other heat sources. (f) Where there are no obstructions (animals, plants, etc.) to the suction inlet and blowing outlet. (g) Where water may drain out. (h) Please avoid the following locations.
1) Where there is constant exposure to harsh winds such as the top floors of a building. Also, locations with exposure to salty air.
2) Where there are oil splashes, vapor, and smoke.
3) Where there are possibilities of flammable gas leaks.
(i) Installation space (on a flat surface)
If there are no open space to install the unit, and it must be installed in a location where there are obstructions such as a wall to the suction inlet and the blowing outlet, please ob­serve the following points. In such cases, please also be aware that the performance of the cooling/heating system may de­cline by approximately 10%.
Page 30
220
6.5.4 Electrical wiring
Power source
UNIT A
1212 3
123
UNIT B
UNIT A UNIT B
123
123
Out side
In side
Earth leakage breaker
Circuit breaker
Power source
12
Earth leakage breaker
Circuit breaker
[POWER SUPPLY CODE]
CENELEC code for cables required field cables. H05RNR3G 4.0
(e) After connecting the power supply wires, make sure to secure the wires with wiring clamps.
(2) Connecting the outside/inside crossover wires
(a) Ensure that crossover wiring is matched with crossover piping in A and B rooms. (b) The length of the crossover wires should be under 25 m. If it longer than 25 m, signal errors between the units may occur and
cause the operation to shut down. (c) Use the crossover wires specified below. Different wires may cause heat generation and fire. Do not to use unspecified wires. [INTERCONNECTING WIRING CODE]
CENELEC code for cables required field cables.
H05RNR4G 1.5 (d) Make sure the terminal numbers on the terminal board of the indoor and outdoor connections are correct. (e) After connecting the crossover wires to the terminal board, use wiring clamps to secure the wiring.
Use cables for interconnection wiring to avoid loosening of the wires. CENELEC code for cables Required field cables. H05 RNR3G4.0 (Example) H Harmonized cable type 05 300/500 volts R Natural-and/or synth. rubber wire insulation N Polychloroprene rubber conductors insulation R Stranded core 3 Number of conductors G One conductor of the cable is the earth conductor (yellow/green)
4.0 Section of copper wire (mm
2
)
SCM45ZA
SCM45YA
25A 25A
(1) Connection of the power lines
(a) This multi-type room air conditioner receives its power from outside. (b) It is necessary to use a single phase 200/240 V 50 Hz for the power supply. (c) An earth leakage breaker and a circuit breaker must be installed.
Their capacities are listed below. (d) Use the power supply wires specified below. Different wires may cause heat generation and fire. Do not to use unspecified
wires.
Never bundle, wind or treat the power wires. Otherwise, heat or fire may be generated.
Page 31
221
* If the total length for all the rooms exceeds the length of chargeless refrigerant pipe,
additionally charge with refrigerant according the item 4.
¡The diameter of the refrigerant pipe:
¡Outdoor unit and the total connectable indoor units (class kW):
Liquid side
Gas side
2.2 · 2.5 · 2.8kW
ø 9.52 · t 0.8
3.2 · 4.0kW
ø 12.7 · t 0.8
ø 6.35 · t 0.8
Class of indoor unit (kW)
Diameter of joint pipe
Model
SCM45ZA
SCM45YA
Total of indoor units (class kW)
6.5kW
6.5kW
(2) Connection of refrigerant piping
¡ The service valve corresponding to each indoor unit is as illustrated in the right figure. ¡ Changing the gas side piping size
If the piping connection for the gas side of the outdoor unit does not match the piping size
of the indoor unit, use the parts provided for variable connections to make the joint.
Variable diameter joint (provided): ø9.52 ø12.7 (1 piece) [Examples of use of variable diameter joints]
Connection of indoor unit of Class 4.0 to A unit.
¡ Securely fit the copper packing between the service valve and the variable diameter joint to prevent shifting. ¡ Cover the pipes with tape so that dust and sand do not enter the pipe until they are connected.
[Connection of pipes]
¡ When connecting the pipes to the outdoor unit, be careful about the discharge of fluorocarbon gas or oil. ¡ Make sure to match the pipes between the indoor unit and the outdoor unit with the correct service valves.
(1) Preparations
¡ Remove the flare nut (from both
liquid and gas sides).
¡ Remove the flare nut (from both
liquid and gas sides).
¡Fit the removed flare nut to the joint pipe, and then flare it.
A dimensions
Liquid side: ø 6.35: ø 9 ~ ø 9.5 Gas side:
ø 9.52: ø 13.2 ~ ø 14 ø 12.7: ø 16.2 ~ ø 17
Gas
Gas side service valve
Liquid
Liquid side service valve
Service valve for room B
Service valve for room A
ø9.52
ø9.52
ø6.35 pipe
ø12.7 pipe
Indoor unit
4.0 kW class
Liquid side service valve (ø6.35)
Gas side service valve (ø9.52)
Copper packing Variable diameter joint (ø9.52–ø12.7)
Service valve for room A
Indoor
Remove
Push
Outdoor
Remove
Push
90+0.5˚
A
A
B
C
Length for one indoor unit Total length for all rooms
Lower installation spot of the indoor unit A Upper installation spot of the indoor unit B Maximum height difference of the indoor units C
Length of chargeless refrigerant pipe
*
Height difference
Under 25m Under 30m Under 15m Under 10m Under 25m
20m
6.5.5 Refrigerant Piping
(1) Limit
The maximum permissible length of the refrigerant pipes for the outdoor units, and the maximum permissible height difference for the outdoor units are as shown below.
Page 32
222
(3) Air purging
(a) Remove the cap on both gas and liquid sides before starting operation. (b) After completing the operation, do not forget to tighten the cap (gas may leak). (c) Conduct air purging for all connected indoor units.
(2) Connection
Indoor Outdoor
¡ Secure the nut with a specified tightening
torque to avoid any gas leaks.
¡ Secure the nut with a specified tightening
torque to avoid any gas leaks.
¡ When air purging with a vacuum pump,
secure the nut with a specified tightening torque to avoid any gas leaks.
¡ When air purging with a refrigerant from
an outdoor unit, just temporarily secure the nut.
¡ Specified tightening torques are as follows:
Liquid side (ø 6.35): 17mm in width across flat of the flare nut: 15.7-19.6 N·m (1.6-2.0 kgf·m)
Gas side (ø 9.52): 22mm in width across flat of the flare nut: 29.4-39.2 N·m (3.0-4.0 kgf·m)
Gas side (ø 12.7): 24mm in width across flat of the flare nut: 39.2-49.0 N·m (4.0-5.0 kgf·m)
Note: Fully open the service valves (on both liquid and gas sides) after completing air purging
Liquid side Gas side
Liquid side
Gas side
(4) Additional refrigerant charge
(a) When the total refrigerant pipe length for all the rooms exceeds the length of the uncharged pipe (20m), additional refrigerant
is required.
(If 20m or less, additional charge is not required.)
(b) For this multi type room air conditioner, it is not necessary to charge the refrigerant for the total maximum length in all the
rooms.
*1: Charge amount at the time of shipment.
(c) Ensure that there are no gas leaks from the pipe joints by using a leak detector or soap water.
1 Secure all flare nuts on both indoor and outdoor sides to prevent leaks from
the pipes.
2 Connect the service valves, charge hose, manifold valve and vacuum pump
as shown in the right figure.
3 Fully open the handle Lo for the manifold valve, and pump a vacuum for 15
minutes. Ensure that the meter is indicating -0.1 MPa (-76cmHg).
4 After vacuuming, fully open the service valve (both liquid and gas sides)
with a hexagon wrench.
5 Ensure that there are no gas leaks from the joints in the indoor and outdoor
units.
6 Repeat the above steps 1 ~ 5 for all connected indoor units.
Open
Open
Vacuum pump
Charge hose
Charge hose
Handle Lo
Handle Hi
Manifold valve
Pressure gauge
Compound pressure gauge
-0.1 MPa (-76cmHg)
Model
SCM45ZA SCM45YA
Charged pipe length
(Amount of uncharged
refrigerant) *1
Maximum total pipe length for all rooms
(Maximum amount of refrigerant)
On site additional charge
20g/m1300g 1500g
Procedure
To protect the global environment, use a vacuum pump that do not release flourocarbon gas into the atmosphere. When a vacuum pump cannot be used due to certain conditions for installation, sufficient refrigerant is available for air purging with refrigerant for the outdoor unit.
Page 33
223
(5) Heat insulation for joint
Heat insulation for joints
Position so the slit comes on top.
Vinyl tape
Cover the joint with insulation material for the indoor unit and tape it.
Tapping screw
Drain hose
Exterior tape
Crossover wires
Pipes
Pipe clamp
Apply exterior tape and shape along the place where the pipes will be rout­ed. Secure to the wall with a pipe clamp. Be careful not to damage the pipes and the wires.
(2) Test run
(a) Carry out the test run for each unit individually. (If 2 units are tested at the same time, wrong wiring and wrong pipe
connections cannot be checked.) (b) After each individual test, run the units in all the rooms simultaneously and check the units. (c) Test both the cooling and the heating.
(Three-minute restart preventive timer)
When the air conditioner is restarted or when changing the operation, the unit will not start operating for approximately 3
minutes. This is to protect the unit and it is not a malfunction.
Beware of wrong connections in refrigerant piping and wiring
¡ Make sure to match the piping and wiring from each unit to the outdoor unit. ¡ Be careful because if connections are wrong, normal operation cannot be achieved and may damage the compressor.
[Correct connections] [Example of wrong connections]
A unit
A
B
B unit
Outdoor
unit
Indoor unit
Indoor unit
Piping Wiring
A unit
A
B
B unit
Outdoor
unit
Installation test check points
Check the following points again after completion of the installation, and before turning on the power. Conduct a test run again and ensure that the unit operates properly. At the same time, explain to the customer how to use the unit and how to take care of the unit following the instruction manual.
After installation Test run
The power supply voltage is correct as the rating. No gas leaks from the joints of the service valve. Power cables and crossover wires are securely inserted and fixed to the terminal board. Each indoor and outdoor unit is properly connected (no wrong wiring or piping). Service valve is fully open. Refrigerant has been additionally charged (when the total pipe length exceeds the refrigerant charged pipe length). The pipe joints for indoor and outdoor pipes have been insulated. Earthing work has been conducted properly.
Air conditioning and heating are normal. No abnormal noise. Water drains smoothly. Protective functions are not working. Operation of the unit has been explained to the customer.
6.5.6 Test run and handling instruction
(1) Inspection
Check according to the following check items.
Finish and fixing
Page 34
224
6.6 MAINTENANCE DATA
6.6.1 Trouble shooting
(1) Trouble shooting to be performed prior to exchanging PCB, (Printed circuit board) [Common to all models]
All the models described in this chapter are controlled by a microcomputer. When providing maintenance service to customers it is necessary to understand the function controlled by a micro computer thoroughly, so as not to mistakenly identify correct opera­tions as mis-operations. It is also necessary to perform the following simple checks before conducting detailed checks or exchang­ing printed circuit board.
Before exchanging Printed circuit board
Claim call from the user
Ascertain the nature of the claim.
Ascertain the operation status.
Does the trouble occur again?
Is this nonsense claim?
Operate the unit.
Does the trouble occur again?
Temporarily turn off the power source and turn it on again in about 1 min. and turn the unit on again.
YES
NO
YES
YES
Does the trouble occur again?
Disconnect connectors and connect them again.
Operate the unit again after confirming that the fuse and the varistor equipped on PCB does not burn out.
Carry out checks according to detailed check process (See later page)
Unit did not cool, etc.
¡ Is the power on? ¡ Is the thermostat setting correct?
(Not too high?)
¡ Is the unit in a time operation? ¡ Does user understand function?
etc.
¡ Explain the function of the unit to user.
No need for PCB change
Check further the status when the trouble Occurred (such as the timer of occurrence, power failures, thunder, use status of other electrical appliances, etc.). Clarify the reason for the problem and explain it thoroughly to the user.
No need for PCB change
Microcomputer runaway due to power source conditions is a possible cause.
No need for PCB change
The cause is defective connector contact.
YES
NO
NO
NO
Page 35
225
Indoor unit indicator
RUN lamp
1 time flash
2 time flash
6 time flash
Keeps flashing
Keeps flashing
Comes on
Comes on
Comes on
Comes on
Comes on
Comes on
Comes on
Comes on
Comes on
Comes on
Comes on
1 time flash
2 time flash
1 time flash
2 time flash
2 time flash
3 time flash
5 time flash
6 time flash
2 time flash
2 time flash
Stays off
Stays off
Stays off
Stays off
Stays off
1 time flash
2 time flash
3 time flash
5 time flash
6 time flash
7 time flash
Comes on
TIMER lamp
Outdoor unit
indicator
(LED 2)
Description of
trouble
Cause Conditions of flashing
On for 4 sec­onds and off for 4 seconds
Outdoor heat exchang­er thermistor error
Indoor heat exchanger thermistor error
Room temperature ther­mistor error
Outdoor temperature thermistor error
Current cut
Comp. dome thermis­tor error
Current safe stop
Over heat of compressor
Error of signal trans­mission
Compressor lock
Outdoor fan motor error
Indoor fan motor error
Broken comp. dome thermistor wire Connector poor connection
When heat exchanger thermistor temperature of –20 °C or under continued for more than 3 seconds while operation is stopped. (This is not displayed during operation.)
When room temperature thermistor temperature of –20 °C or under continued for more than 3 seconds while operation is stopped. (This is not displayed during operation.)
When air conditioner is operating and indoor fan motor is turned ON, indoor fan motor speed of 400 rpm or under continued for more than 30 seconds. (Air conditioner stops.)
When outdoor temperature thermistor temperature of –40 °C or under continued for more than 3 seconds while operation is stopped. (This is not displayed during operation.)
When heat exchanger entrance thermistor temper­ature of –50 °C or under continued for more than 3 seconds while operation is stopped. (This is not displayed during operation.)
When an error with the outdoor unit causes an error stop, or when the input current is measured at 1 A or less for 3 continuous minutes or more. (Compressor is stopped.)
When converter output current which exceeds setting value is detected. (Compressor stops.)
When the actual speed is 28 rps or less and the current save has operated. (Compressor stops)
After the outdoor unit speed has been 0 rps or more for 10 continuous minutes and the compressor dome thermistor has sent a 10 second or more broken wire signal (less than 7 °C). (Compressor is stopped.)
When comp. dome thermistor value exceeds setting value. (Compressor Stops.)
If serial signal cannot be sent or received for 1 minute and 55 seconds continuously.
Defective compressor Defective outdoor PCB
Overload operation Overcharge
Gas shortage Defective comp. dome thermistor
Defective power transistor. Broken compressor wire Compressor blockage
Defective power supply Broken signal wire Defective indoor/outdoor unit circuit boads.
Defective fan motor Connector poor connection
When the outdoor unit fan motor operates at 300 rpm or less for 30 seconds or more continuously.
When the motor for the compressor does not turn a half a turn approximately 0.3 seconds after it has been started.
Broken heat exchanger thermistor wire Connector poor connection
Broken room temperature thermistor wire Connector poor connection
Broken heat exchanger thermistor wire Poor connector connection
Broken outdoor thermistor wire Poor connector connection
Defective fan motor Connector poor connection
Compressor locking Open phase on compressor output Shortcircuit on power transformer
Trouble of outdoor unit
(2) Indication of self diagnosis
Page 36
226
(3) Inspection procedures corresponding to detail of trouble
Thermistor error
[Broken thermistor wire, connector poor connection]
Is connector connection good?
YES
YES
NO
NO
Replace PCB.
Is thermistor resistance value good?
Correct connection.
Replace thermistor.
30
25
20
15
10
5
30
20
10
40 50 60
7
0
0
–10
Temperature (˚C) Resistance (k) Temperature (˚C) Resistance (kΩ)
0 164 70 8.7
5 127 75 7.3 10 99 80 6.2 15 78 85 5.3 20 62 90 4.5 25 50 95 3.9 30 40 100 3.3 35 32 105 2.9 40 26 110 2.5 45 21 115 2.2 50 17 120 1.9 55 14 125 1.6 60 12 130 1.4 65 10 135 1.3
Thermistor temperature characteristics (Room temp., indoor and outdoor unit heat exchanger temp., outdoor temp.)
Comp. dome thermistor temperature characteristics
Temperature (˚C)
(Shortcircuit)
(Broken wire)
Resistance (kΩ)
Current cut
[Open phase on compressor output terminal, compressor lock]
YES
YES
NO
NO
YES
NO
¡ Check compressor wiring visually. ¡ Check insulation resistance. (1 M or over) ¡ Check coil wire resistance. (Few Ω)
Does current cut operate when operating inverter with compressor wire disconnected?
Is output voltage applied to all 3 phases of power transistor?
Is there any shortcircuit?
Inspect compressor.
Defective inverter
Defective inverter
Secure space for inlet and outlet.
If check results are normal, compressor is locked.
Page 37
227
Outdoor unit error
[Broken power transistor, broken compressor wire]
Is output voltage applied to all 3 phases of power transistor?
YES
YES
NO
NO
Inspect compressor. (Broken coil wire)
Is compressor wiring connected securely?
Connect securely.
Current safe stop
[Overload operation, compressor lock, overcharge]
Defective inverter
Secure space for inlet and outlet.
Discharge refrigerant.
Is refrigerant charge quantity adequate?
Is outdoor ventilation condition good?
Inspect compressor.
Defective inverter
YES
YES
NO
NO
YES
Compressor overheat
[Gas shortage, defective comp. dome thermistor]
Is comp. dome thermistor resistance value good?
Is sufficient quantity of refrigerant circulated?
Defective inverter
YES
YES
NO
NO
YES
NO
Gas shortage
Connector connection check, resistance value check, replacement of comp. dome thermistor
Does trouble persist after charging gas?
Clogged capillary tube, etc.
Indoor fan motor error
[Defective fan motor, defective indoor PCB]
YES
YES
NO
NO
Is connector connection good?
Is voltage applied to fan motor?
(Between White - Red)
Defective fan motor
Correct connector connection.
Defective indoor unit PCB
Page 38
228
Outdoor fan motor error
[Defective fan motor, defective outdoor PCB]
Compressor lock
[Defective compressor, defective outdoor PCB]
NO
YES
¡ Check compressor wiring visually. ¡ Check insulation resistance. (1 M or over) ¡ Check coil wire resistance. (Few Ω)
Is output voltage applied to all 3 phases of power transistor?
Inspect compressor.
Defective inverter
If check results are normal, compressor is locked.
Serial signal transmission abnormality
YES
YES
NO
NO
Is connector connection good?
Is voltage applied to fan motor?
(DC)
Defective fan motor
Correct connector connection.
Defective outdoor unit PCB
Is this a recurring error when reset­ting power supply?
Is the wiring connection between the indoor and outdoor unit improperly wired?
Is AC 220/240 V measured between ter­minals 1 and 2 on the outdoor unit?
Is the electrical system operating properly (fuse, reactor, etc.)?
Does the voltage between terminals 2 and 3 on the outdoor unit oscillate bet­ween approximately DC 0 and 12 volts?
Does the voltage between terminals 2 and 3 on the indoor unit oscillate bet­ween approximately DC 0 and 12 volts?
Correct indoor and out­door unit connections.
Defective indoor unit circuit board.
Defective outdoor cir­cuit board
This is due to a tempo­rary cause (interfer­ence, etc.) and is not a failure of the unit.
Defective indoor unit circuit board. Inspect interconnection wire.
Inspect interconnec­tion wire.
Replace fuse and reac­tor.
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
(1)
Possible causes include interference from the lighting, spontaneous load inter­ference, power supply interference and radial interference.
[Indoor/outdoor printed circuit board defect Outdoor power source abnormality]
Page 39
229
(4) Phenomenon observed after shortcircuit, wire breakage on thermistors.
(a) Indoor unit
Phenomenon
Thermistor
Shortcircuit Broken wire Cooling Release of continuous compressor operation command Heating Continuous compressor operation command is not released.
Cooling System can be operated normally.
Heating High pressure control mode (Inverter stop command)
(b) Outdoor unit
Phenomenon
Thermistor
Shortcircuit Broken wire Cooling System can be operated normally. Heating Defrosting is not performed. Cooling System can be operated normally. Heating Defrosting is not operated.
All modes
Defrosting is performed for 10 minutes at approx. 1 hour.
Defrosting is performed for 10 minutes at intervals of approx. 30 minutes.
Compressor stop (There is no inverter output.)
Operation mode
Room temperature thermistor
Continuous compressor operation command is not released. Release of continuous compressor operation command Continuous compressor operation command is not released.
(Anti-frosting)
Hot keep (Indoor fan stop)
Heat exchanger thermistor
Operation mode
Heat exchanger thermistor
Outdoor temperature thermistor
Comp. dome thermistor
Compressor overload protection is disabled. (Can be operated.)
(5) How to make sure of remote controller
Is remote controller
normal?
YES
Again pushing operating switch
Operating the unit?
NO
Does backup switch operates?
Operating the unit.
NO
NO
YES
YES
Remote controller defects
Abnormality is not found.
(a) Press the reset switch of the remote controller. (b) If all LCD are displayed after zero (0) display, it is ba-
sically normal.
Replace the display.
Control problem on main unit
Is the unit
operable with remote
controller?
Normal
Defective remote controller
NO
YES
(1)
Note (1) Check method of remote controller
Heat Pump model
Cooling only model
Page 40
230
(6) Indoor electrical components inspection flowchart
Is there voltage between terminal blocks 1 and 2 ? (AC 220/240 V)
Indoor electrical components are normal.
Is there voltage between CNC (1) and (2) on the secondary side of the transformer? (Approx. 12 V)
Is the voltage between terminal blocks 2 and 3 oscillating between DC 0 and 12V?
Inspect power source for outdoor unit.
Replace fuse.
Replace the transformer.
Replace printed circuit board.
Is the fuse burnt out? (3.15 A)
YES
YES
YES
YES
NO
NO
NO
NO
Page 41
231
(7) Outdoor unit inspection points
Inspection of resistance value of Comp. dome thermistor
Remove the connector and check the resistance value. See the section of thermistor characteristics on page 226.
Inspection of reactor conductivity
Remove the connector and check for conductivity.It must be conductive.
¡Inspection of electronic expansion valve
To test if there is voltage.
(Voltage is only applied to the electronic expansion valve when the valve angle is being changed.) Red to white Red to Orange Brown to yellow Brown to blue
If the expansion valve does not operate as shown above, it is defective.
Normal if there is approximately DC 5 V 10 seconds after the power supply is turned on.
}
¡Display lamp inspection
LED 2 (Abnormality display lamp - Red)
LED 1, 3 (Light display for each room -
Green)
ON or flashing: Protection function operating ON when there is a serial signal being received among each of the indoor units. OFF during ignition, stop abnormality.
¡Power source and serial
signal inspection
1 to 2: AC220/240V 2 to 3: Normal if the voltage oscil-
lates between DC 0 and approx. 12V
CAUTION – HIGH VOLTAGE
High voltage is produced in the control box. Don't touch electrical parts in the control box for 5 minutes after the unit is stopped.
~+
++++
~
1 2 3 1 2 3
1 2
Y/GN
Y/GN
WH
BK
BL
WH
BK
RD
Serial A
Serial B
G
CNB CNB
LED1 LED3 LED2
(Red)
GY
DS
IC2
P
RDU WH BK
Tho-A Tho-R
CND
CNC
CNACNFCNECNA
Tho-D
V
W
N
BL
ORWH
WH
BK
UNIT A
UNIT B
Power source 1 Phase 220/240V 50Hz
Printed circuit board
Fuse
250V 25A
Printed circuit board
Power
transistor
CM
20S EEVA FMoEEVB
(Green)
52X2-4
AC·R
AC·S
S. OUT
R. IN
S. IN
L
Output voltage
(ACV)
(Example) Self-diagnosis display : Flashes 2 times
Measure in this section
Operation SW ON
8 ~ 10 sec.
0
1
Power transistor inspection procedure [Use a tester with a needle indicator for the inspection. (Do not use a digital tester. Check in the AC 300 volt range.)] (1) If there is a self-diagnosis display, inspect the compressor system (burns, wiring mistakes, etc.). If no problems are found,
check the output of the power transistor.
(2) Output inspection procedure
Disconnect the terminals for the compres­sor. If an output such as the one shown in the figure on the right can be measured, the power transistor and the circuit board for the outdoor unit are normal.
For about 50 seconds. After being switched on, there will be a delay of approximately one minute depending on the conditions.
Page 42
232
Liquid side
Gas side
Check joint
Service hose
Charge hose
Vacuum pump
Refrigerant cylinder
Gauge manifold
6.6.2 Servicing
(1) Evacuation
The evacuation is an procedure to purge impurities ...... noncondensable gas, air, moisture from the refrigerant equipment by using
a vacuum pump. Since the refrigerant R22 is very insoluble in water, even a small amount of moisture left in the refrigerant equipment will freeze, causing what is called water clogging. ¡ Evacuation procedure (a) Check to ensure that there is no internal pressure in the unit. If there is an internal pressure, it
should be relieved through the check joint. (b) Connect the service hoses of the gauge manifold to the check joint of the gas & liquid piping. (c) Connect a vacuum pump to the charge hose
A
. Repeat evacuation in the following sequence.
Stop the vacuum pump.
(2) Refrigerant charge
(a) Discharge refrigerant entirely from the unit and evacuate the unit.
Note: Addition of refrigerant without evacuation is unreasonable, because it will result in low charge or overcharge. (b) Keep the gauge manifold and connect a refrigerant cylinder to the unit. (c) Record the weight of the refrigerant cylinder on the balance. This is necessary for making sure of the charged refrigerant
amount. (d) Purge air from the charge hose
A
Firstly loose the connecting portion of the charge hose A at the gauge manihold side and open the valve 3 for a few
seconds, and then immediately retighten it after observing that gas is blow out from the loosened portion. (e) Open the valve 1 and 3 after discharging air from the charge hose
A
, then the gas refrigerant begins flowing from the
cylinder into the unit. Be sure to erect the refrigerant cylinder upright to let gas refrigerant flow into the unit. (f) When refrigerant has been charged into the system to some extent, refrigerant flow becomes stagnant, when that happens,
start the compressor in cooling cycle until the unit is filled with gas to the specified weight. (g) Making sure of the refrigerant amount, close the valve 3. (h) Disconnect the charge hose from the unit. Cover the valve ports of the refrigerant piping with caps and tighten them securely. (i) Check for gas leakage applying a gas leak detector along the piping line.
(j) Start the air conditioner and make sure of its operating condition ...... high side and low side pressures and temperature
difference between suction air and outlet air.
Notes (1) Do not use the refrigerant pressure to expel air.
(2) Do not use the compressor for evacuation. (3) Do not operate the compressor in the vacuum condition.
Start the vacuum pump.
Compound pressure gauge indicates –0.1 MPa (–76 cmHg)
Operate the vacuum pump for more than 15 minutes after –0.1 MPa ( –76 cmHg) is indicated.
Close low pressure valve 1 of gauge manifold.
Loading...