Mitsubishi SEZ-KD25VA(L).TH, SEZ-KD35VA(L).TH, SEZ-KD50VA(L).TH, SEZ-KD60VA(L).TH, SEZ-KD71VA(L).TH Service Manual

TECHNICAL & SERVICE MANUAL
CONTENTS
1. PART NAMES AND FUNCTIONS········2
2. SPECIFICATIONS·································5
3. OUTLINES AND DIMENSIONS··········18
4.WIRING DIAGRAM ·····························19
5.
·······20
6.TROUBLESHOOTING·························21
7. DISASSEMBLY PROCEDURE···········33
INDOOR UNIT
Indoor unit [Model names] [Service Ref.]
SEZ-KD25VA(L) SEZ-KD25VA(L).TH SEZ-KD35VA(L) SEZ-KD35VA(L).TH SEZ-KD50VA(L) SEZ-KD50VA(L).TH SEZ-KD60VA(L) SEZ-KD60VA(L).TH SEZ-KD71VA(L) SEZ-KD71VA(L).TH
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
WIRED REMOTE
CONTROLLER
(For SEZ-KD·VA model )
ON/OFF
TEMP.
Model name indication
No.HWE07110
REVISED EDITION-B
September 2007
WIRELESS REMOTE
CONTROLLER
(For SEZ-KD·VAL model )
ON/OFF
TEMP
2
1
PART NAMES AND FUNCTIONS
Indoor Unit SEZ-KD25VA(L).TH SEZ-KD35VA(L).TH SEZ-KD50VA(L).TH SEZ-KD60VA(L).TH SEZ-KD71VA(L).TH
Air outlet duct flange
Air outlet
Air inlet
Operation buttons
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
Wired remote controller
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
Set Temperature buttons
Down
Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button (Set Day button)
Opening the door
Start/Stop button
Fan Speed button
Filter button (<return sign> button)
Test Run button
Service button (Clear button)
Airflow Up/Down button
Louver button (
Operation button)
To preceding operation number
Ventilation button (
Operation button)
To next operation number
3
Display
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON OFF
Hr AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Identifies the current operation
Shows the operating mode, etc. * Multilanguage display is sup-
ported.
Centrally Controlled indicator
Indicates that operation of the re­mote controller has been prohib­ited by a master controller.
Timer Is Off indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, shows the time remaining.
Sensor indication
Displayed when the remote controller sensor is used.
Locked indicator
Indicates that remote controller but­tons have been locked.
Clean The Filter indicator
Comes on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre­sponding timer is set.
Up/Down Air Direction indica­tor
The indicator shows the direc­tion of the outcoming airflow.
One Hour Only indicator
Displayed if the airflow is set to Low and downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off after one hour, at which time the airflow di­rection also changes.
Room Temperature display
Shows the room temperature.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is stationary.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
Caution
Only the Power on indicator lights when the unit is stopped and power supplied to the unit.
If you press a button for a feature that is not installed in the indoor unit, the remote controller will display the Not Available
message. If you are using the remote controller to operate multiple indoor units, this message will appear only if the feature is not present at the parent unit.
When power is turned ON for the first time, it is normal that “PLEASE WAITis displayed on the room temperature indication (For max. 2minutes). Please wait until this PLEASE W AITindication disappears then start the operation.
4
Wireless remote controller
When using the wireless remote controller, point it towards the receiver on the indoor unit.
If the remote controller is operated within approximately two minutes after power is supplied to the indoor unit, the indoor unit may beep twice as the unit is performing the initial automatic check.
The indoor unit beeps to confirm that the signal transmitted from the remote controller has been received. Signals can be received up to approximately 7 meters in a direct line from the indoor unit in an area 45° to the left and right of the unit. However, illumination such as fluorescent lights and strong light can affect the ability of the indoor unit to receive sig­nals.
If the operation lamp near the receiver on the indoor unit is flashing, the unit needs to be inspected. Consult your dealer for service.
Handle the remote controller carefully. Do not drop the remote controller or subject it to strong shocks.In addition, do not get the remote controller wet or leave it in a location with high humidity.
To avoid misplacing the remote controller, install the holder included with the remote controller on a wall and be sure to always place the remote controller in the holder after use.
CLOCK
CHECK
RESET
SET
TEST RUN
MODE
FAN
VANE
LOUVER
min
h
AUTO START
AUTO STOP
ON/OFF
TEMP
NOT AVAILABLE
MODEL SELECT
TEST RUN
CHECK
SET TEMPERATURE button
SET TEMPERATURE button sets and any desired room temperature.
AUTO STOP/AUTO START button
Used for selecting timed starting or st­opping.
VANE CONTROL button
Used to change the airflow direction.
LOUVER button
Used for adjusting the airflow direction.
min button
Used for setting the current time.
h button
Used for setting the current time.
FAN SPEED button
This button is used to set fan speed to low, medium or high.
MODE SELECT button
This button is used to change between auto, cooling, heating and drying oper­ation modes.
TEST RUN button
CHECK button
ON/OFF button
Pushing button starts operation. Pushing again stops operation.
Battery installation/replacement
1. Remove the top cover, insert two AAA batteries, and then install the top cover.
Top cover
2. Press the Reset button.
1
2
3
Press the Reset button with an object that has a narrow end.
Two AAA batteries Insert the negative (–) end of each battery first. Install the batter­ies in the correct direc­tions (+, –).
Operation buttons
5
2
SPECIFICATIONS
Model Name Capacity
Power source Power input Current Temperature set range Remote controller Airflow direction
Type x Quantity
Fan
External static press Motor type Motor output Driving mechanism
Airflow rate(Low-Mid-High) External finish External dimension H x W x D Net weight Wiring
Min.size of wire Amperage of wire breaker
Refrigerant piping diameter
Liquid Gas
R410A
R410A Drain piping diameter Noise level (Low-Mid-High) (measured in anechoic room)
Insulation material Air filter Refrigerant control device Connectable outdoor unit Protection devices Heat exchanger Varistor Terminal block Power outlet A Standard attachment
Document Accessory *3
Optional parts Remark
kW
kW A
˚C(˚F)
Pa
kW
m3/min
mm In. kg mm(in.) A
mm(in.) mm(in.) mm(in.)
dB<A>
SEZ-KD25VA(L)
Cooling
2.5 230V (50Hz)
0.04
0.39
19 to 30 (67 to 86)
-
Sirocco fan x 2
5-15-35-50
DC blushless motor
0.096
Direct-driven
5.5-7.0-9.0 Galvanized
200 x 700 x 700
7-7/8 x 27-9/16 x 27-9/16
18
1.6 (1/8) 15
ø6.35 (ø1/4) Flare ø9.52 (ø3/8) Flare
O.D. 32 (1-9/32)
23-26-30
Polystyrene foam, Polyethylene foam, Urethane foam
PP Honeycomb fabric (washable)
-
R410A SUZ-KA25VA(H)
Fuse (250V 6.3A)
Cross fin (Aluminum fin and copper tube)
ERZV10D471
To outdoor unit : 3P To wired remote controller : 2P
10
Installation Manual, Instruction Book
Drain hose (flexible joint), Remote Controller
Drain Iift-up mechanism (PAC-KE07DM-E)
Heating
3.0
0.04
0.39
17 to 28 (63 to 83)
SEZ-KD35VA(L)
Cooling
3.5
0.05
0.46
19 to 30 (67 to 86)
Polystyrene foam, Polyethylene foam, Urethane foam
Cross fin (Aluminum fin and copper tube)
To outdoor unit : 3P To wired remote controller : 2P
Installation Manual, Instruction Book
Drain hose (flexible joint), Remote Controller
Drain Iift-up mechanism (PAC-KE07DM-E)
230V (50Hz)
-
Sirocco fan x 2
5-15-35-50
DC blushless motor
0.096
Direct-driven
7.0-9.0-11.0 Galvanized
200 x 900 x 700
7-7/8 x 35-7/16 x 27-9/16
21
1.6 (1/8) 15
ø6.35 (ø1/4) Flare ø9.52 (ø3/8) Flare
O.D. 32 (1-9/32)
23-28-33
PP Honeycomb fabric (washable)
-
R410A SUZ-KA35VA(H)
Fuse (250V 6.3A)
ERZV10D471
10
Heating
4.0
0.05
0.46
17 to 28 (63 to 83)
Note
1.Cooling/Heating capacity indicates the maximum value at operation under the following condition. <Cooling> Indoor: 27˚CD.B./19˚CW.B. (81˚FD.B. / 66˚FW.B. Outdoor:35˚CD.B. (95˚FD.B. )
<Heating> Indoor:20
2.The external static pressure is set to 15 Pa at factory shipment.
3.Wired Remote Controller for VA model , Wireless Remote Controller for VAL model
˚CD.B. (68˚FD.B.) Outdoor:7˚CD.B. / 6˚CW.B. (45˚FD.B. / 43˚FW.B.)
Pipe length: 7.5m (24-9/16ft) Height difference: 0m (0ft)
6
Model Name Capacity
Power source Power input Current Temperature set range Remote controller Airflow direction
Type x Quantity
Fan
External static press Motor type Motor output Driving mechanism
Airflow rate(Low-Mid-High) External finish External dimension H x W x D Net weight Wiring
Min.size of wire Amperage of wire breaker
Refrigerant piping diameter
Liquid Gas
R410A
R410A Drain piping diameter Noise level (Low-Mid-High) (measured in anechoic room)
Insulation material Air filter Refrigerant control device Connectable outdoor unit Protection devices Heat exchanger Varistor Terminal block Power outlet A Standard attachment
Document Accessory *3
Optional parts Remark
kW
kW A
˚C(˚F)
Pa
kW
m3/min
mm In. kg mm(in.) A
mm(in.) mm(in.) mm(in.)
dB<A>
SEZ-KD50VA(L)
Cooling
5.0
0.07
0.63
19 to 30 (67 to 86)
Polystyrene foam, Polyethylene foam, Urethane foam
Cross fin (Aluminum fin and copper tube)
To outdoor unit : 3P To wired remote controller : 2P
Installation Manual, Instruction Book
Drain hose (flexible joint), Remote Controller
Drain Iift-up mechanism (PAC-KE07DM-E)
230V (50Hz)
-
Sirocco fan x 3
5-15-35-50
DC blushless motor
0.096
Direct-driven
10.0-12.5-15.0 Galvanized
200 x 900 x 700
7-7/8 x 35-7/16 x 27-9/16
23
1.6 (1/8) 15
ø6.35 (ø1/4) Flare ø12.7 (ø1/2) Flare
O.D. 32 (1-9/32)
30-34-37
PP Honeycomb fabric (washable)
-
R410A SUZ-KA50VA
Fuse (250V 6.3A)
ERZV10D471
20
Heating
6.0
0.07
0.63
17 to 28 (63 to 83)
SEZ-KD60VA(L)
Cooling
5.5
0.07
0.63
19 to 30 (67 to 86)
Polystyrene foam, Polyethylene foam, Urethane foam
Cross fin (Aluminum fin and copper tube)
To outdoor unit : 3P To wired remote controller : 2P
Installation Manual, Instruction Book
Drain hose (flexible joint), Remote Controller
Drain Iift-up mechanism (PAC-KE07DM-E)
230V (50Hz)
-
Sirocco fan x 4
5-15-35-50
DC blushless motor
0.096
Direct-driven
12.0-15.0-18.0 Galvanized
200 x 1100 x 700
7-7/8 x 43-5/16 x 27-9/16
27
1.6 (1/8) 15
ø6.35 (ø1/4) Flare
ø15.88 (ø5/8) Flare
O.D. 32 (1-9/32)
30-34-38
PP Honeycomb fabric (washable)
-
R410A SUZ-KA60VA
Fuse (250V 6.3A)
ERZV10D471
20
Heating
7.0
0.07
0.63
17 to 28 (63 to 83)
Note
1.Cooling/Heating capacity indicates the maximum value at operation under the following condition. <Cooling> Indoor: 27˚CD.B./19˚CW.B. (81˚FD.B. / 66˚FW.B. Outdoor:35˚CD.B. (95˚FD.B. )
<Heating> Indoor:20
2.The external static pressure is set to 15 Pa at factory shipment.
3.Wired Remote Controller for VA model , Wireless Remote Controller for VAL model
˚CD.B. (68˚FD.B.) Outdoor:7˚CD.B. / 6˚CW.B. (45˚FD.B. / 43˚FW.B.)
Pipe length: 7.5m (24-9/16ft) Height difference: 0m (0ft)
7
Model Name Capacity
Power source Power input Current Temperature set range Remote controller Airflow direction
Type x Quantity
Fan
External static press Motor type Motor output Driving mechanism
Airflow rate(Low-Mid-High) External finish External dimension H x W x D Net weight Wiring
Min.size of wire Amperage of wire breaker
Refrigerant piping diameter
Liquid Gas
R410A
R410A Drain piping diameter Noise level (Low-Mid-High) (measured in anechoic room)
Insulation material Air filter Refrigerant control device Connectable outdoor unit Protection devices Heat exchanger Varistor Terminal block Power outlet A Standard attachment
Document Accessory *3
Optional parts Remark
kW
kW A
˚C(˚F)
Pa
kW
m3/min
mm In. kg mm(in.) A
mm(in.) mm(in.) mm(in.)
dB<A>
Cooling
7.1
0.10
0.84
19 to 30 (67 to 86)
Polystyrene foam, Polyethylene foam, Urethane foam
To outdoor unit : 3P To wired remote controller : 2P
SEZ-KD71VA(L)
230V (50Hz)
-
Sirocco fan x 4
5-15-35-50
DC blushless motor
0.096
Direct-driven
12.0-16.0-20.0 Galvanized
200 x 1100 x 700
7-7/8 x 43-5/16 x 27-9/16
27
1.6 (1/8) 15
ø9.52 (ø3/8) Flare
ø15.88 (ø5/8) Flare
O.D. 32 (1-9/32)
30-35-40
PP Honeycomb fabric (washable)
-
R410A SUZ-KA71VA
Fuse (250V 6.3A)
Cross fin (Aluminum fin and copper tube)
ERZV10D471
20
Installation Manual, Instruction Book
Drain hose (flexible joint), Remote Controller
Drain Iift-up mechanism (PAC-KE07DM-E)
Heating
8.1
0.10
0.84
17 to 28 (63 to 83)
Note
1.Cooling/Heating capacity indicates the maximum value at operation under the following condition. <Cooling> Indoor: 27˚CD.B./19˚CW.B. (81˚FD.B. / 66˚FW.B. Outdoor:35˚CD.B. (95˚FD.B. )
<Heating> Indoor:20
2.The external static pressure is set to 15 Pa at factory shipment.
3.Wired Remote Controller for VA model , Wireless Remote Controller for VAL model
˚CD.B. (68˚FD.B.) Outdoor:7˚CD.B. / 6˚CW.B. (45˚FD.B. / 43˚FW.B.)
Pipe length: 7.5m (24-9/16ft) Height difference: 0m (0ft)
8
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SEZ-KD25VA(L).TH
External static pressure: 15Pa
High
Middle
30
SPL(dB)
26
Low
23
LINE
<50/60Hz>
NOTCH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SEZ-KD25VA(L).TH
External static pressure: 5Pa
High
Middle
29
SPL(dB)
25
Low
22
LINE
<50/60Hz>
NOTCH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SEZ-KD25VA(L).TH
External static pressure: 50Pa
High
Middle
33
SPL(dB)
29
Low
25
LINE
<50/60Hz>
NOTCH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SEZ-KD25VA(L).TH
External static pressure: 35Pa
High
Middle
31
SPL(dB)
28
Low
24
LINE
<50/60Hz>
NOTCH
NOISE CRITERION CURVES
NOTE:The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than displayed level under actual installation condition by surrounding echoes.The sound level can be higher by about 2 dB than the displayed level during cooling and heating operation.
9
SEZ-KD35VA(L).TH
NOTE:The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than displayed level under actual installation condition by surrounding echoes.The sound level can be higher by about 2 dB than the displayed level during cooling and heating operation.
External static pressure: 5Pa
90
NOTCH
High
Middle
Low
<50/60Hz>
SPL(dB)
33 28 23
LINE
SEZ-KD35VA(L).TH
External static pressure: 15Pa
90
NOTCH
High
Middle
Low
<50/60Hz>
SPL(dB)
33 28 23
LINE
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
SEZ-KD35VA(L).TH
External static pressure: 35Pa
90
NOTCH
High
Middle
Low
<50/60Hz>
SPL(dB)
34 29 24
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
LINE
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
SEZ-KD35VA(L).TH
External static pressure: 50Pa
90
NOTCH
High
Middle
Low
<50/60Hz>
SPL(dB)
35 31 25
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
10
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SEZ-KD50VA(L).TH
External static pressure: 15Pa
High
Middle
37
SPL(dB)
34
Low
30
LINE
<50/60Hz>
NOTCH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SEZ-KD50VA(L).TH
External static pressure: 5Pa
High
Middle
36
SPL(dB)
33
Low
29
LINE
<50/60Hz>
NOTCH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SEZ-KD50VA(L).TH
External static pressure: 50Pa
High
Middle
39
SPL(dB)
36
Low
32
LINE
<50/60Hz>
NOTCH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SEZ-KD50VA(L).TH
External static pressure: 35Pa
High
Middle
38
SPL(dB)
35
Low
31
LINE
<50/60Hz>
NOTCH
NOTE:The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than displayed level under actual installation condition by surrounding echoes.The sound level can be higher by about 2 dB than the displayed level during cooling and heating operation.
11
SEZ-KD60VA(L).TH
NOTE:The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than displayed level under actual installation condition by surrounding echoes.The sound level can be higher by about 2 dB than the displayed level during cooling and heating operation.
External static pressure: 5Pa
90
NOTCH
High
Middle
Low
<50/60Hz>
SPL(dB)
37 33 29
LINE
SEZ-KD60VA(L).TH
External static pressure: 15Pa
90
NOTCH
High
Middle
Low
<50/60Hz>
SPL(dB)
38 34 30
LINE
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
SEZ-KD60VA(L).TH
External static pressure: 35Pa
90
NOTCH
High
Middle
Low
<50/60Hz>
SPL(dB)
39 35 31
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
LINE
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
SEZ-KD60VA(L).TH
External static pressure: 50Pa
90
NOTCH
High
Middle
Low
<50/60Hz>
SPL(dB)
39 36 32
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
80
70
60
50
40
30
APPROXIMATE
20
TERESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
12
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SEZ-KD71VA(L).TH
External static pressure: 15Pa
High
Middle
40
SPL(dB)
35
Low
30
LINE
<50/60Hz>
NOTCH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SEZ-KD71VA(L).TH
External static pressure: 5Pa
High
Middle
39
SPL(dB)
34
Low
29
LINE
<50/60Hz>
NOTCH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SEZ-KD71VA(L).TH
External static pressure: 50Pa
High
Middle
42
SPL(dB)
37
Low
32
LINE
<50/60Hz>
NOTCH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
SEZ-KD71VA(L).TH
External static pressure: 35Pa
High
Middle
41
SPL(dB)
36
Low
31
LINE
<50/60Hz>
NOTCH
NOTE:The sound level is measured in an anechoic room where
echoes are few, when compressor stops.The sound may be bigger than displayed level under actual installation condi­tion by surrounding echoes.The sound level can be higher by about 2 dB than the displayed level during cooling and heating operation.
Measurement location
2m
1m
Aux. duct
1.5m
test unit
13
INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW
SEZ-KD25VA
(External static pressure 15Pa) 220-240V 50/60Hz
External static pressure (Pa)
0
10
20
30
40
50
Airflow rate(m
3
/min)
45678910
Middle
Low
High
Limit
Rated point
0
40
30
20
10
45678910
Airflow rate(m
3
/min)
External static pressure (Pa)
SEZ-KD25VA
(External static pressure 5Pa) 220-240V 50/60Hz
Middle
Low
High
Rated point
Limit
0
10
20
30
40
50
60
70
80
45678910
Airflow rate(m
3
/min)
External static pressure (Pa)
SEZ-KD25VA
(External static pressure 50Pa) 220-240V 50/60Hz
Middle
Low
High
Limit
Rated point
0
10
20
30
40
50
60
70
80
45678910
Airflow rate(m
3
/min)
External static pressure (Pa)
SEZ-KD25VA
(External static pressure 35Pa) 220-240V 50/60Hz
Middle
Low
High
Limit
Rated point
14
External static pressure (Pa)
SEZ-KD35VA
(External static pressure 15Pa) 220-240V 50/60Hz
Airflow rate(m
3
/min)
0
10
20
30
40
50
6 7 8 9 101112
Middle
Low
High
Limit
Rated point
0
40
30
20
10
External static pressure (Pa)
6789101112
Airflow rate(m
3
/min)
SEZ-KD35VA
(External static pressure 5Pa) 220-240V 50/60Hz
Middle
Low
High
Limit
Rated point
0
20
10
30
40
50
60
70
80
External static pressure (Pa)
Airflow rate(m
3
/min)
SEZ-KD35VA
(External static pressure 50Pa) 220-240V 50/60Hz
6 7 8 9 101112
Middle
Low
High
Limit
Rated point
0
20
10
30
40
50
60
70
80
External static pressure (Pa)
SEZ-KD35VA
(External static pressure 35Pa) 220-240V 50/60Hz
6789101112
Airflow rate(m
3
/min)
Middle
Low
High
Limit
Rated point
15
SEZ-KD50VA
(External static pressure 5Pa) 220-240V 50/60Hz
40
SEZ-KD50VA
(External static pressure 15Pa) 220-240V 50/60Hz
50
Limit
30
20
External static pressure (Pa)
10
Low
0
8 9 10 11 12 13 14 15 16
Middle
Airflow rate(m
3
/min)
Rated point
SEZ-KD50VA
(External static pressure 35Pa) 220-240V 50/60Hz
80
70
60
50
40
30
External static pressure (Pa)
20
10
Low
Middle
Rated point
High
Limit
High
Limit
40
30
20
External static pressure (Pa)
10
0
8 9 10 11 12 13 14 15 16
Low
Middle
Airflow rate(m
3
/min)
Rated point
SEZ-KD50VA
(External static pressure 50Pa) 220-240V 50/60Hz
80
Limit
70
60
50
40
30
External static pressure (Pa)
20
10
Middle
Low
Rated point
High
High
0
8 9 10 11 12 13 14 15 16
Airflow rate(m
3
/min)
0
8 9 10 11 12 13 14 15 16
Airflow rate(m
3
/min)
16
External static pressure (Pa)
SEZ-KD60VA
(External static pressure 15Pa) 220-240V 50/60Hz
Airflow rate(m
3
/min)
9 10111213141516171819
0
50
40
30
20
10
Middle
Low
High
Limit
Rated point
External static pressure (Pa)
SEZ-KD60VA
(External static pressure 5Pa) 220-240V 50/60Hz
Airflow rate(m
3
/min)
9 10111213141516171819
0
40
30
20
10
Middle
Low
High
Limit
Rated point
External static pressure (Pa)
SEZ-KD60VA
(External static pressure 50Pa) 220-240V 50/60Hz
Airflow rate(m
3
/min)
9 10111213141516171819
0
10
20
30
40
60
70
50
80
Middle
Limit
Rated point
Low
High
External static pressure (Pa)
SEZ-KD60VA
(External static pressure 35Pa) 220-240V 50/60Hz
Airflow rate(m
3
/min)
9 10111213141516171819
0
10
20
30
40
60
70
50
80
Middle
Limit
Rated point
Low
High
17
SEZ-KD71VA
(External static pressure 5Pa) 220-240V 50/60Hz
40
SEZ-KD71VA
(External static pressure 15Pa) 220-240V 50/60Hz
50
30
20
External static pressure (Pa)
10
Middle
0
Low
11 12 13 14 15 16 17 18 19 20 21
Airflow rate(m
3
Rated point
/min)
SEZ-KD71VA
(External static pressure 35Pa) 220-240V 50/60Hz
80
70
60
50
40
30
External static pressure (Pa)
20
10
Low
Middle
Rated point
Limit
High
Limit
High
40
30
20
External static pressure (Pa)
10
Low
0
11 12 13 14 15 16 17 18 19 20 21
Airflow rate(m
3
Rated point
Middle
/min)
SEZ-KD71VA
(External static pressure 50Pa) 220-240V 50/60Hz
80
70
60
50
40
30
External static pressure (Pa)
20
10
Low
Middle
Rated point
Limit
High
Limit
High
0
3
Airflow rate(m
/min)
2120191817161514131211
0
3
Airflow rate(m
/min)
2120191817161514131211
18
OUTLINES AND DIMENSIONS
3
Unit : mm
SEZ-KD25VA(L).TH SEZ-KD35VA(L).TH SEZ-KD50VA(L).TH SEZ-KD60VA(L).TH SEZ-KD71VA(L).TH
24
20
16
900
700
500
9
7
5
1060
860
660
LJHK
{12.7
SEZ-KD71VA(L)
SEZ-KD60VA(L)
SEZ-KD50VA(L)
SEZ-KD35VA(L)
700 752 798 660 7 600 800
{15.88
{9.52
{6.35
{9.52
1198
998
AModel
SEZ-KD25VA(L)
1152
952
B
1100
900
C
1060
860
D
11
9
E
1000
800
F
1200
1000
G
Air outlet
Air inlet
Terminal block (Remote controller transmission line)
Drain pipe(O.D.{32)(Spontaneous draining)
1
Gas pipe
1
Liquid pipe
2
Refrigerant piping flare connection (gas)
2
Refrigerant piping flare connection (liquid)
Terminal block (Indoor/outdoor connecting line)
Suspension bolt hole 4-14X30 Slot
Air filter
Control box
2XE-{2.9
2X2-{2.9
L-{2.9
Knockout hole {27 (Indoor/outdoor connecting line)
Knockout hole {27 (Remote controller transmission line)
10
170
57
More than 300
450
G
50
50~150
50
777
450
15
20
100
100X(E-1)=F
30
D (Duct)
625
(Suspension bolt pitch)
90
A
23
B (Suspension bolt pitch)
C
23 677
700
25100
23
150
(Duct)
116 70
270
102
More than 10mm
More than 20mm
25
49
10
88
100
100XJ=K 8812
12
37
100
20 157.5
20 H
200
37
Access door
Note2
Note1.Use M10 screw for the suspension bolt (field supply).
2.Keep the service space for the maintenance at the bottom.
3.This chart indicates for SEZ-KD50VA(L) model,which has 3 fans. SEZ-KD25,35VA(L) models have 2 fans. SEZ-KD60,71VA(L) models have 4 fans.
4.In case an inlet duct is used,remove the air filter(supply with the unit), then install the filter(field supply) at suction side.
Make the access door at the appointed position properly for service maintenance.
Ceiling surface
Access door
Required space for service and maintenance
19
4
WIRING DIAGRAM
SEZ-KD25VA(L).TH SEZ-KD35VA(L).TH SEZ-KD50VA(L).TH SEZ-KD60VA(L).TH SEZ-KD71VA(L).TH
1~
M
135
311456734
12
4231
4123 67895
54321678
1324
912
3
LED1
Optional Parts
L1:only SEZ-KD71VA(L)
INSIDE SECTION OF CONTROL BOX
CN22
(Red)
CN3C
CNMF
SW2SW1
CN90
CN32
CN20CN44
CN4F
CN41
SWE
ON
OFF
CN51
(Blue)
TO MA REMOTE CONTROLLER
FS
TH2 TH5 TH1
Fan motor
TB15
CN4F
Optional Parts
CN2L
(Blue)
LED3
LED2
I.B.
S1
TB4
S3
S2
TO OUTDOOR UNIT
Drainpump
FS
FLOAT SWITCH
L1
AC REACTOR(POWER FACTOR IMPROVEMENT)
SW2
SWITCH (COOLING ON/OFF)
SWITCH (HEATING ON/OFF)
SW1
LED (RUN INDICATOR)
LED1
BZ1
BUZZER
RU RECEIVING UNIT
W.B. WIRELESS REMOTE CONTROLLER BOARD
TB4
TB15
TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE)
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
LED2 LED3 TRANSMISSION(INDOOR-OUTDOOR)
POWER SUPPLY(I.B.)
LED1 POWER SUPPLY(I.B.)
ZNR01,02 VARISTOR
AUX. RELAYX1
FUSE FUSE AC250V 6.3A
DSA
CONNECTOR (CENTRALLY CONTROL)
CN41 CN51
CONNECTOR (HA TERMINAL-A)
CN2L
NAME
SYMBOL EXPLANATION
SW1 SW2
INDOOR CONTROLLER BOARD
CN32
I.B.
SYMBOL SYMBOL NAME
CONNECTOR (LOSSNAY) CONNECTOR (REMOTE SWITCH)
SWE
ARRESTER
SWITCH (FOR MODE SELECTION) SWITCH (FOR CAPACITY CODE) CONNECTOR (EMERGENCY OPERATION)
TH1
INTAKE AIR TEMP. THERMISTOR
TH2
PIPE TEMP. THERMISTOR/LIQUID
TH5
COND. /EVA. TEMP. THERMISTOR
X1
DC310~340V Rectify circuit
U
U
FUSE
ZNR01
(Black)
CN01
CNP
ZNR02
(Blue)
DSA
1
t
°
M
t
°
t
°
1 2
L1
RECEIVER
RU
CN1
LED1
SW1 SW2
W.B.
BZ1
For
SEZ-KD • VAL
For SEZ-KD • VA
NOTE)1. Since the outdoor side electric wiring may change be sure to
check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers(S1,S2,S3).
3. Symbols used in wiring diagram above are,
:Connector, :Terminal Block.
20
REFRIGERANT SYSTEM DIAGRAM
5
Pipe temperature thermistor/liquid (TH2)
Distributor
Condenser/evaporator temperature thermistor (TH5)
Room temperature thermistor (TH1)
Refrigerant flow in cooling Refrigerant flow in heating
Strainer #50
Strainer #50
Heat exchanger
Refrigerant GAS pipe connection (Flare)
Refrigerant LIQUID pipe connection (Flare)
SEZ-KD25VA(L).TH SEZ-KD35VA(L).TH SEZ-KD50VA(L).TH SEZ-KD60VA(L).TH SEZ-KD71VA(L).TH
21
6
TROUBLESHOOTING
6-1. CAUTIONS ON TROUBLESHOOTING
(1) Before troubleshooting, check the followings:
1 Check the power supply voltage. 2 Check the indoor/outdoor connecting wire for mis-wiring.
(2) Take care the followings during servicing.
1 Before servicing the air conditioner, be sure to turn off the remote controller first to stop the main unit, and then turn
off the breaker.
2 When removing the indoor controller board, hold the edge of the board with care NOT to apply stress on the
components.
3 When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wires
˚C
˚C
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
B
C
A
E D
6-2. SELF-CHECK FUNCTION
Wired remote controller
(1) Tur n on the power. (2) Press the [CHECK] button twice. (3) Set refrigerant address with [TEMP] button
if system control is used.
(4) Press the [ON/OFF] button to stop the
self-check.
AA
CHECK button
BB
Refrigerant address
CC
TEMP button
DD
IC : Indoor unit OC : Outdoor unit
EE
Check code
1 Check code Symptom Remark P1 Intake sensor error P2 Pipe (TH2) sensor error P9 Pipe (TH5) sensor error E6,E7 Indoor/outdoor unit communication error P4 Drain sensor error P5 Drain pump error P6 Freezing/Overheating protection operation EE Communication error between indoor and outdoor units P8 Pipe temperature error E0, E3~E5 Remote controller transmission error E1, E2 Remote controller control board error Fb Indoor unit control system error (memory error, etc.) E9 Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit) UP Compressor overcurrent interruption U3,U4 Open/short of outdoor unit thermistors UF Compressor overcurrent interruption (When compressor locked) U2 Abnormal high discharging temperature/49C worked/insufficient refrigerant U1,Ud Abnormal high pressure (63H worked)/Overheating protection operation U5 Abnormal temperature of heat sink U8 Outdoor unit fan safeguard stop U6 Compressor overcurrent interruption/Abnormal of power module U7 Abnormality of super heat due to low discharge temperature U9,UH Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit
/Current sensor error
Others Other errors (Refer to the technical manual for the outdoor unit.)
For details, check the LED display of the outdoor controller board. As for outdoor unit, refer to service manual OC322.
On wired remote controller. 1 Check code displayed in the LCD.
For description of each check code, refer to the following table.
22
If the unit cannot be operated properly after the test run has been performed, refer to the following table to remove the cause.
Symptom
Cause
Wired remote controller LED 1, 2 (PCB in outdoor unit)
On the wireless remote controller with condition above, following phenomena take place.
No signals from the remote controller are accepted.
Operation lamp is blinking.
The buzzer makes a short piping sound.
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).
For about 2 minutes after power-on
After about 2 minutes has expired after power-on
After LED 1, 2 are lighted, LED 2 is
turned off, then only LED 1 is
Only LED 1 is lighted.
LED 1, 2 blink.
Only LED 1 is lighted.
LED 1 blinks twice, LED 2 blinks once.
For about 2 minutes after power-on,op­eration of the remote controller is not possible due to system start-up. (Correct operation)
Connector for the outdoor units protection device is not connected.
Reverse or open phase wiring for the outdoor units power terminal block (L1, L2, L3)
Incorrect wiring between indoor and outdoor units (incorrect polarity of S1, S2, S3)
Remote controller wire short
Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for remote controller)
Indicates whether power is supplied to the remote controller. This LED lights only in the case of the indoor unit which is connected to the outdoor unit refrigerant address 0.
LED3 (communication between indoor and outdoor units)
Indicates state of communication between the indoor and outdoor units. Make sure that this LED is always blinking.
lighted.
(Correct operation)
Wireless remote controller
(1) Tur n on the power to the unit at least 12 hours before the test run. (2) Press the TEST RUN button
AA
twice continuously.
(Start this operation from the status of remote controller display turned off.)
and current operation mode are displayed.
(3) Press the MODE button
BB
to activate COOL mode, then check whether
cool air is blown out from the unit.
(4) Press the MODE button
BB
to activate HEAT mode, then check whether
warm air is blown out from the unit.
(5) Press the FAN button
CC
and check whether fan speed changes.
(6) Press the VANE button
DD
and check whether the auto vane operates prop-
erly.
(7) Press the ON/OFF button to stop the test run.
Note:
Point the remote controller towards the indoor unit receiver while fol­lowing steps (2) to (7).
It is not possible to run the in FAN, DRY or AUTO mode.
TEST RUN
23
[Output pattern A] Errors detected by indoor unit
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes
(Number of times)
1 2 3 4 5 6 7 8
9 10 11 12
No sound
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wireless remote controller
Beeper sounds/OPERATION INDICATOR
lamp flashes (Number of times)
1 2 3 4 5 6 7 8 9
10 11 12
13 14
*1 If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not
come on, there are no error records.
*2 If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm the self-check start signal was
received, the specified refrigerant address is incorrect.
On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit. Blink of operation lamp
On wired remote controller Check code displayed on the LCD.
Wired remote
controller
Check code
P1 P2, P9 E6, E7 P4 P5 P6 EE P8 E4
– –
Fb – –
Symptom
Intake sensor error Pipe (Liquid or 2-phase pipe) sensor error Indoor/outdoor unit communication error Drain sensor error Drain pump error Freezing/Overheating safeguard operation Communication error between indoor and outdoor units Pipe temperature error Remote controller signal receiving error
– –
Indoor unit control system error (memory error, etc.) No corresponding
Symptom
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit) Compressor overcurrent interruption Open/short of outdoor unit thermistors Compressor overcurrent interruption (When compressor locked) Abnormal high discharging temperature/49C worked/ insufficient refrigerant Abnormal high pressure (63H worked)/ Overheating safeguard operation Abnormal temperature of heat sink Outdoor unit fan protection stop Compressor overcurrent interruption/Abnormal of power module Abnormality of super heat due to low discharge temperature Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/Current sensor error
– –
Other errors (Refer to the technical manual for the outdoor unit.)
Remark
Remark
For details, check the LED display of the outdoor controller board.
If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
PLEASE WAIT
PLEASE WAIT →Error code
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).
On the wireless remote controller with conditions above, following phenomena takes place.
No signals from the remote controller are accepted.
OPE lamp is blinking.
The buzzer makes a short ping sound.
Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For about 2 minutes following power-on
After about 2 min­utes has expired following power-on
Symptom
LED 1, 2 (PCB in outdoor unit)Wired remote controller After LED 1, 2 are lighted, LED 2 is turned off, then only LED 1 is lighted. (Correct operation)
Only LED 1 is lighted. → LED 1, 2 blink.
Only LED 1 is lighted. → LED 1, 2 blinks twice, LED 2 blinks once.
For about 2 minutes after power-on, operation of the remote controller is not possible due to system start-up. (Correct operation)
Connector for the outdoor units protection device is not connected.
Reverse or open phase wiring for the outdoor units power terminal block (L1, L2, L3)
Incorrect wiring between indoor and outdoor units (incorrect polarity of S1, S2, S3)
Remote controller wire short
Cause
24
Indicates whether control power is supplied. Make sure that this LED is always lit. Indicates whether power is supplied to the remote controller. This LED lights only in the case of the indoor unit which is connected to the outdoor unit refrigerant address “0”. Indicates state of communication between the indoor and outdoor units. Make sure that this LED is always blinking.
LED 1 (power for microcomputer) LED 2 (power for remote controller)
LED 3 (communication between indoor and outdoor units)
AUTO RESTART FUNCTION
Indoor controller board
This model is equipped with the AUTO RESTART FUNCTION. When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are memorized by the indoor controller board. The auto restart function sets to work the moment the power has restored after power failure, then, the unit will restart automatically. Set the AUTO RESTART FUNCTION using the wireless remote controller. (Mode no.1).
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
25
6-3. SELF-DIAGNOSIS ACTION TABLE
Note: Refer to the manual of outdoor unit for the details of display
such as F, U, and other E.
Error Code
Abnormal point and detection method
Cause
Countermeasure
P1
Room temperature thermistor (TH1)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying and heating operation Short: 90
: or more
Open: -40
: or less
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN20) on the indoor controller board (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective indoor controller
board
13 Check resistance value of thermistor. 0
: ······15.0k" 10: ····9.6k" 20: ····6.3k" 30: ····4.3k" 40: ····3.0k" If you put force on (draw or bend) the lead wire with measuring resistance value of thermistor breaking of wire or contact failure can be detected. 2 Check contact failure of connector (CN20) on
the indoor controller board. Refer to 6-5. Turn the power on again and check restart after inserting connector again.
4 Check room temperature display on remote
controller. Replace indoor controller board if there is abnormal difference with actual room temperature.
Turn the power off, and on again to operate after check.
P2
Pipe temperature thermistor/Liquid (TH2)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating (except defrosting) operation. Short: 90
: or more
Open: -40
: or less
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN44) on the indoor controller board (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective refrigerant circuit is
causing thermistor temperature of 90
: or more or -40: or
less.
5 Defective indoor controller board
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above. 2 Check contact failure of connector (CN44) on
the indoor controller board. Refer to 6-5.Turn the power on again and check restart after inserting connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid> temperature is extremely low (in cooling mode) or high (in heating mode), refrigerant circuit may have defective.
5 Check pipe <liquid> temperature with remote
controller in test run mode. If there is extreme difference with actual pipe <liquid> temperature, replace indoor controller board.
Turn the power off, and on again to operate after check.
P4
(5701)
Contact failure of drain float switch (CN4F)
1 Extract when the connector of drain float
switch is disconnected. (3 and 4 of connector CN4F is not short-circuited.)
2 Constantly detected during operation.
1 Contact failure of connector
(Insert failure)
2 Defective indoor controller
board
1 Check contact failure of float switch connec-
tor. Turn the power on again and check after inserting connector again.
2 Operate with connector (CN4F) short-circuited.
Replace indoor controller board if abnormali­ty reappears.
P5
Drain overflow protection operation
1 Suspensive abnormality, if drain float
switch is detected to be underwater for 1 minute and 30 seconds continuously with drain pump on. Turn off compressor and indoor fan.
2 Drain pump is abnormal if the condition
above is detected during suspensive abnormality.
3 Constantly detected during drain pump
operation.
1 Malfunction of drain pump 2 Defective drain
Clogged drain pump Clogged drain pipe
3 Defective drain float switch
Catch of drain float switch or malfunction of moving parts cause drain float switch to be detected under water (Switch On)
4 Defective indoor-controller
board
1 Check if drain-up machine works. 2 Check drain function.
3 Remove drain float switch connector CN4F
and check if it is short (Switch On) with the moving part of float switch UP, or OPEN with the moving part of float switch down. Replace float switch if it is short with the moving part of float switch down.
4 Replace indoor controller board if it is short-
circuited between
3-4 of the drain float switch connector CN4F and abnormality reappears.
It is not abnormal if there is no problem about the above-mentioned
1~4 Turn the power off, and on again to operate after check.
26
Error Code
Abnormal point and detection method
Cause
Countermeasure
P6
Freezing/overheating protection is working
1 Freezing protection (Cooling mode)
The unit is in six-minute resume prevention mode if pipe <liquid or condenser/evap­orator> temperature stays under
-15
: for three minutes after the com­pressor started. Abnormal if it stays under -15: for three minutes again within 16 minutes after six-minute resume prevention mode.
2 Overheating protection (Heating mode)
The units is in six-minute resume prevention mode if pipe <Liquid or con­denser / evaporator> temperature is detected as over 70: after the com­pressor started. Abnormal if the temper­ature of over 70: is detected again within 10 minutes after six-minute resume prevention mode.
P8
1 Slight temperature difference
between indoor room temperature and pipe <liquid or condenser / evaporator> temperature thermistor
Shortage of refrigerant
Disconnected holder of pipe
<liquid or condenser /
evaporator> thermistor
Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units connection)
3 Converse wiring of indoor/
outdoor unit connecting wire (on plural units connection)
4 Defective detection of indoor
room temperature and pipe <condenser / evaporator> temperature thermistor
5 Stop valve is not opened
completely.
(Cooling or drying mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Low-load (low temperature)
operation beyond the tolerance range
4 Defective indoor fan motor
Fan motor is defective.
Indoor controller board is
defective.
5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit
(clogs)
(Heating mode)
1 Clogged filter (reduced airflow) 2 Shor t cycle of air path 3 Over-load (high temperature)
operation beyond the tolerance range
4 Defective indoor fan motor
Fan motor is defective.
Indoor controller board is
defective.
5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit
(clogs)
8 Bypass circuit of outdoor unit
is defective.
(Cooling or drying mode)
1 Check clogging of the filter. 2 Remove shields.
4 Refer to 6-7. DC Fan motor (FAN MOTOR/
INDOOR CONTROLLER BOARD)
5 Check outdoor fan motor. 67 Check operating condition of refrigerant
circuit.
(Heating mode)
1 Check clogs of the filter. 2 Remove shields.
4 Refer to 6-7. DC Fan motor (FAN MOTOR/
INDOOR CONTROLLER BOARD)
5 Check outdoor fan motor. 6~8Check operating condition of refrigerant
circuit.
Pipe temperature
<Cooling mode> Detected as abnormal when the pipe tem­perature is not in the cooling range 3 min­utes after compressor start and 6 minutes after the liquid or condenser/evaporator pipe is out of cooling range. Note 1) It takes at least 9 minutes.to
detect.
Note 2) Abnormality P8 is not detected in
drying mode. Cooling range : -3 deg ] (TH-TH1) TH: Lower temperature between: liquid
pipe temperature (TH2) and con­denser/evaporator temperature (TH5)
TH1: Intake temperature <Heating mode>
When 10 seconds have passed after the compressor starts operation and the hot adjustment mode has finished, the unit is detected as abnormal when condenser/evaporator pipe temperature is not in heating range within 20 minutes.
Note 3) It takes at least 27 minutes to
detect abnormality. Note 4) It excludes the period of defrosting
(Detection restarts when defrost-
ing mode is over) Heating range : 3 deg [ (TH5-TH1)
1~4 Check pipe <liquid or condenser /
evaporator> temperature with room temperature display on remote controller and outdoor controller circuit board. Pipe <liquid or condenser / evaporator> temperature display is indicated by setting SW2 of outdoor controller circuit board as follows.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor unit connecting wire.
Conduct temperature check with outdoor controller circuit board after connecting A-Control Service Tool(PAC-SK52ST)’.
(
)
27
Error Code
Abnormal point and detection method
Cause
Countermeasure
P9
Abnormality of pipe temperature ther­mistor / Condenser-Evaporator (TH5)
1 The unit is in three-minute resume pro-
tection mode if short/open of thermistor is detected. Abnormal if the unit does not get back to normal within three min­utes. (The unit returns to normal opera­tion, if it has normally reset.)
2 Constantly detected during cooling, dry-
ing, and heating operation (except defrosting) Short: 90: or more Open: -40: or less
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN44) on the indoor controller board (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Temperature of thermistor is
90: or more or -40: or less caused by defective refrigerant circuit.
5 Defective indoor controller
board
13 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN44)
on the indoor controller board. Refer to 6-5. Turn the power on and check restart after inserting connector again.
4 Operate in test run mode and check pipe
<condenser / evaporator> temperature. If pipe <condenser / evaporator> tempera­ture is extremely low (in cooling mode) or high (in heating mode), refrigerant circuit may have defect.
5 When no problems are found in 1-4 above,
replace the indoor unit control board.
E0
or
E4
Remote controller transmission error(E0)/signal receiving error(E4)
1 Abnor mal if main or sub remote con-
troller can not receive normally any transmission from indoor unit of refriger­ant address “0” for three minutes. (Error code : E0)
2 Abnor mal if sub remote controller could
not receive for any signal for two min­utes. (Error code: E0)
1 Abnor mal if indoor controller board can
not receive normally any data from remote controller board or from other indoor controller board for three minutes. (Error code: E4)
2 Indoor controller board cannot receive
any signal from remote controller for two minutes. (Error code: E4)
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main.
If there is no problem with the action above.
3 Check wiring of remote controller.
Total wiring length: max.500m (Do not use cable 3 or more)
The number of connecting indoor units: max.16units
The number of connecting remote con­troller: max.2units
When it is not the above-mentioned problem of
1~3 4 Diagnose remote controllers.
a) When RC OKis displayed,
Remote controllers have no problem. Turn the power off, and on again to check. If abnormality generates again, replace indoor controller board.
b) When RC NGis displayed,
Replace remote controller. c) When RC E3is displayed, d) When ERC 00-06is displayed, [ c),d)Noise may be causing abnormality. ]
If the unit is not nor mal after replacing
indoor controller board in group control, indoor controller board of address “0” may be abnormal.
E3
or
E5
Remote controller transmission error(E3)/signal receiving error(E5)
1 Abnormal if remote controller could not
find blank of transmission path for six seconds and could not transmit.
(Error code: E3)
2 Remote controller receives transmitted
data at the same time, compares the data, and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E3)
1 Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2 Indoor controller board receives trans-
mitted data at the same time, compares the data,and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E5)
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting. 4~6 Diagnose remote controller.
a) When RC OKis displayed, remote con-
trollers have no problem.
Turn the power off,and on again to check. When becoming abnormal again, replace
indoor controller board.
b)When RC NGis displayed, replace
remote controller.
c)When RC E3or ERC 00-66is displayed,
noise may be causing abnormality.
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as subremote controller. In this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED1, LED2) on the outdoor controller circuit board.
3 Mis-wiring of remote controller 4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board of refrigerant address “0”
6 Noise has entered into the
transmission wire of remote controller.
1 Two remote controller are set
as main.
(In case of 2 remote con-
trollers)
2 Remote controller is connected
with two indoor units or more.
3 Repetition of refrigerant
address
4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board
6 Noise has entered into trans-
mission wire of remote con­troller.
28
E6
1 Contact failure, short circuit or,
mis-wiring (converse wiring) of indoor/outdoor unit connecting wire
2 Defective transmitting receiving
circuit of indoor controller board
3 Defective transmitting receiving
circuit of indoor controller board
4 Noise has entered into indoor/
outdoor unit connecting wire.
Check LED display on the outdoor control cir-
cuit board. (Connect A-control service tool, PAC-SK52ST.) Refer to EA-EC item if LED displays EA-EC.
1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or outdoor unit.
Check all the units in case of twin triple indoor unit system.
2-4 Turn the power off, and on again to check.
If abnormality generates again, replace indoor controller board or outdoor controller circuit board.
Other indoor controller board may have
defect in case of twin triple indoor unit system.
E7
Indoor/outdoor unit communication error (Transmitting error)
Abnormal if “1” receiving is detected 30 times continuously though indoor controller board has transmitted “0”.
1 Defective transmitting receiving
circuit of indoor controller board
2 Noise has entered into power
supply.
3 Noise has entered into outdoor
control wire.
1-3 Turn the power off, and on again to check.
If abnormality generates again, replace indoor controller board.
Indoor/outdoor unit communication error (Signal receiving error)
1 Abnormal if indoor controller board
cannot receive any signal normally for six minutes after turning the power on.
2 Abnormal if indoor controller board
cannot receive any signal normally for three minutes.
3 Consider the unit as abnormal under the
following condition:When two or more indoor units are connected to an outdoor unit, indoor controller board cannot receive a signal for three minutes from outdoor controller circuit board, a signal which allows outdoor controller circuit board to transmit signals.
Error Code
Abnormal point and detection method
Cause
Countermeasure
Fb
Indoor controller board
Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board.
1 Defective indoor controller
board
1 Replace indoor controller board.
E1
or
E2
Remote controller control board
1 Abnormal if data cannot be read normal-
ly from the nonvolatile memory of the remote controller control board.
(Error code: E1)
2 Abnormal if the clock function of remote
controller cannot be operated normally. (Error code: E2)
1 Defective remote controller 1 Replace remote controller.
PA
(2500)
Water leakage
This detection is performed during the operation (stop, heating, fan, or error stop mode etc.) other than cooling and dry. 1 When a) and b) are found, water leakage
occurs. a) Pipe <liquid> temperature - inlet tem-
perature < -10˚C for 30 minutes
b) When drain float switch is detected to
be soaked in the water for 15 minutes or more.
* When drain float switch is detected to
be NOT soaked in the water, each counting of a) and b) is cleared.
*When this error is detected, the error will not be reset until the main power is reset.
1 Mis-piping of extension pipes
(When connected with multiple units)
2 Mis-wiring of indoor/outdoor
unit connecting wire (When connected with multiple units)
3 Detection failure of the indoor
unit inlet/ pipe <liquid> ther­mistor
4 Drain pump failure 5 Drainage failure
· Clogged drain pump
· Clogged drain pipe
6 Drain float switch failure
· Drain float switch is detected to be soaked in the water (ON status) due to the operation failure of the moving parts.
· Contact failure of drain float switch connector (Loose connector)
1Check the extension pipes for mis-piping.
2Check the Indoor/outdoor unit connecting
wire for mis-wiring.
3Check room temperature display on remote
controller and indoor pipe <liquid> tempera­ture. (Refer to the countermeasure on P2.)
4Check if drain-up machine works.
5 Check drain function.
6Check drain float switch.(Refer to the coun-
termeasure on P4 and P5.)
29
6-4.TROUBLESHOOTING BY INFERIOR PHENOMENA
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Phenomena
Cause
Countermeasure
(1)LED2 on indoor controller board
is off.
When LED1 on indoor controller board is also off.
1 Power supply of rated voltage is not supplied to out-
door unit.
2 Defective outdoor controller circuit board
3 Power supply of 220~240V is not supplied to indoor
unit.
4 Defective indoor controller board
1 Check the voltage of outdoor power
supply terminal block (L, N) or (L3, N).
When AC 220~240V is not detected. Check the power wiring to outdoor unit and the breaker.
When AC 220~240V is detected.
Check 2 (below).
2 Check the voltage between outdoor
terminal block S1 and S2.
When AC 220~240V is not detected.
Check the fuse on outdoor controller circuit board.
Check the wiring connection.
When AC 220~240V is detected.
Check 3 (below).
3 Check the voltage between indoor terminal
block S1 and S2.
When AC 220~240V is not detected. Check indoor/outdoor unit connecting wire for mis-wiring.
When AC 220~240V is detected.
Check 4 (below).
4 Check the fuse on indoor controller board.
Check the wiring connection. If no problem are found, indoor controller board is defective.
(2)LED2 on indoor controller board
is blinking.
When LED1 on indoor controller board is also blinking. Connection failure of indoor/outdoor unit connecting wire
When LED1 is lit.
1 Mis-wiring of remote controller wires
Under twin triple indoor unit system, 2 or more indoor units are wired together.
2 Refrigerant address for outdoor unit is wrong or not
set.
Under grouping control system, there are some units whose refrigerant address is 0.
3 Shor t-cut of remote controller wires 4 Defective remote controller
Check indoor/outdoor unit connecting wire for connection failure.
1 Check the connection of remote con-
troller wires in case of twin triple indoor unit system.When 2 or more indoor units are wired in one refrigerant system, connect remote controller wires to one of those units.
2 Check the setting of refrigerant address
in case of grouping control system.
If there are some units whose refrigerant addresses are 0 in one group, set one of the units to 0 using SW1 (3-6) on outdoor controller circuit board.
34 Remove remote controller wires and
check LED2 on indoor controller board.
When LED2 is blinking, check the short-cut of remote controller wires.
When LED2 is lit, connect remote controller wires again and:
if LED2 is blinking, remote controller is defective;if LED2 is lit, connection failure of remote controller terminal block etc.has retur ned to nor mal.
30
6-5. TEST POINT DIAGRAM
6-5-1. Indoor controller board
SEZ-KD25VA(L).TH SEZ-KD35VA(L).TH SEZ-KD50VA(L).TH SEZ-KD60VA(L).TH SEZ-KD71VA(L).TH
CN01 Power supply voltage (220 - 240VAC) SWE Emergency operation SW1 Model selection SW2 Capacity setting CN32 Remote start/stop adapter CN22 For MA remote controller cable con-
nection
(10 - 13 VDC (Between 1 and 3.)) CN51 Centralized control CN41 JAMA standard HA terminal A CN44 Thermistor
(liquid/condenser/evaporator
temperature) CN4F Float thermistor CN20 Thermistor (Inlet temperature) CN3C Indoor-outdoor transmission
(0 - 24VDC) CNMF Fan motor output
1 - 4: 310 - 340 VDC
5 - 4: 15 VDC
6 - 4: 0 - 6.5 VDC
7 - 4: Stop 0 or 15 VDC
Run 7.5 VDC (0 - 15 pulse)
CNP Drain-up mechanism output (200VAC) CN2L LOSSNAY CN90 Wireless remote controller (*1) V
FG
Voltage on the (-) side of PC672 and
C955
(Same with the voltage between 7 (+)
and 4 (-) of CNMF) V
CC
Voltage between the C955 pins 15
VDC
(Same with the voltage between 5 (+)
and 4 (-) of CNMF) V
sp Voltage between the C626 pins
0VDC (with the fan stopped)
1 - 6.5VDC (with the fan in operation)
(Same with the voltage between 6 (+)
and 4 (-) of CNMF)
CN3C
CNP
Fuse(6.3A 250V)
CNMF
CN20
CN44
CN90
CN4F
LED1
LED2
LED3
SWE
CN2L
C626
PC672
SW2
CN41
CN22
SW1
CN32
CN51
CN01
C955
31
6-6. TROUBLE CRITERION OF MAIN PARTS SEZ-KD25VA(L).TH
SEZ-KD35VA(L).TH SEZ-KD50VA(L).TH SEZ-KD60VA(L).TH SEZ-KD71VA(L).TH
Room temperature thermistor (TH1)
Condenser/evaporator temperature thermistor (TH5)
Measure the resistance with a tester. (Part temperature 10°C ~ 30°C)
Pipe temperature thermistor/liquid (TH2)
Wiring diagram
Check method and criterion
Part name
Normal
8k~20k
Abnormal
Opened or short-circuited
Motor
Board with build-in motor
Current detecting resistor
Regulator Hall IC
Motor winding
Power device
Pre
driver
Vm (Power supply for motor)
Vcc (Power supply for control)
Vsp (Speed command voltage)
PG (Pulse output for rotation)
GND
32
6-7. DC FAN MOTOR (FAN MOTOR/ INDOOR CONTROLLER BOARD)
Notes
· High voltage is applied to the connecter (CNMF) for the fan motor. Give attention to the service.
· Do not pull out the connector (CNMF) for the motor with the power supply on. (It causes trouble of the indoor controller circuit
board and fan motor.)
Self check Symptom : The indoor fan cannot turn around.
No
NG
NG
Wiring contact check
Contact of fan motor connector (CNMF)
Check the fuse (FUSE) on indoor controller board.
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit
board.
TEST POINT
1 :VDC (between 1 (+) and 4 (-) of the fan connector): VDC DC310~340V
TEST POINT 2 :VCC (between 5 (+) and 4 (-) of the fan connector): VCC DC15V
Wiring recovery
Replace drain pump (DP).
Replace indoor controller board.
Replace the fan motor.
Replace indoor controller board (I.B). Replace fan motor (MF).
Replace indoor controller board.
Replace the fan motor.
Is the voltage normal?
Is there no contact failure?
Yes
1
2
Yes
No
Did the fuse blow?
Check the drain pump (DP) Is the resistance between terminals normal?
No
Yes
Yes
No
Check the operation of fan. END
Yes
OK
Check the operation. END
OK
Check method of DC fan motor (fan motor / indoor controller circuit board)
33
SEZ-KD25VA(L).TH SEZ-KD35VA(L).TH SEZ-KD50VA(L).TH SEZ-KD60VA(L).TH SEZ-KD71VA(L).TH
1. Control box
1. Removing the control box cover (1) Remove the two fixing screws on the cover (A)
to remove it.
2.Thermistor (Intake air)
1. Remove the control box cover according to the procedure in section [1].
(1) Pull out the thermistor holder (B) and thermis-
tor (C) on the control box.
(A)
Fig. 1
Fig. 2
SEZ-KD·VA model only
KD71VA(L) model only
(B),(C)
Fig. 3
DISASSEMBLY PROCEDURE7
Exercise caution when removing heavy parts.
34
3. Drainpan
Exercise caution when removing heavy parts.
1. Removing the filter and the bottom plate (1) Push up the tab on the filter, and pull out the
filter in the direction of the arrow 1.
(2) Remove the fixing screws on the bottom plate
(D), (E) to remove it.
2. Removing the drainpan (1) Pull out the drain pan in the direction of the
arrow 1.
Note
Drain the water out of the drain pan before removing it.
To avoid dew condensation, use insulated screws in the places marked with circles in Figure 6.
(D) (E)
(a)
(a)
(a)
(a)
(a) T ab
Fig. 4
Fig. 5
Insulation material
(E)
Fig. 6
35
4.Thermistor (Condenser / evaporator) (Liquid pipe)
1. Remove the drain pan according to the proce-
dure in section [3].
2. Removing the Heat exchanger cover (1) Remove the four fixing screws on the heat
exchanger cover (F) to remove it.
3. Removing the thermistor (1) Remove the thermistor (G) from the thermistor
holder (H) on the copper tube.
Thermistor size Liquid pipe: ø8mm Condenser / evaporator: ø6mm
(F)
Fig. 7
(G),(H)
Fig. 8
Exercise caution when removing heavy parts.
36
3. Removing the motor cable (1) Remove the motor cable threw the rubber
bush.
4. Removing the fan motor and the Sirocco fan (1) Remove the two motor fixing screws to
remove the motor and the Sirocco fan in the direction of arrow 3.
Fig. 11
(2) Remove the four fan case fixing screws to
take the top half of the fan casing off.
Fig. 12
Exercise caution when removing heavy parts.
2. Removing the fan casing (bottom half) (1) Squeeze the tabs on the fan casing to remove
it in the direction of arrow 2.
(a)
(a) T ab
Fig. 10
5. Fan and fan motor
1. Removing the filter and the bottom plate (1) Push down the tab on the filter, and pull out
the filter in the direction of the arrow 1.
(2) Remove the fixing screws on the bottom plate
(J) to remove it.
(J)
(a)
(a) T ab
(a)
(a)
(a)
Fig. 9
37
Fig. 13
(2) Remove the two bearing retainer screws to
remove the bearing.
Fig. 14
6. Bearing [KD50·60·71VA(L) model only]
1. Removing the bearing (1) Remove the two fixing screws on the bearing
cover (K) to remove it.
7. Heat exchanger
1. Remove the drain pan according to the proce-
dure in section [3].
2. Remove the heat exchanger cover according to
the procedure in section [4] 2.
3. Removing the cover (1) Remove the two fixing screws on the cover (L)
to remove it.
4. Removing the Heat exchanger (1) Remove the fixing screws on the heat
exchanger (M) to remove it.
(L)
Fig. 15
(M)
Fig. 16
Exercise caution when removing heavy parts.
(K)
New publication, effective Sep. 2007.
Specifications subject to change without notice.
HWE07110 Printed in Japan
TM
Loading...