Mitsubishi SEH-1.6AR.TH, SEH-2.5AR.TH, SEH-2AR.TH, SUH-1.6VR.TH, SUH-2VR.TH Service Manual

...
Page 1
TECHNICAL & SERVICE MANUAL
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
CONTENTS
1. PART NAMES AND FUNCTIONS ········2
2. SPECIFICATIONS·································4
3. OUTLINES AND DIMENSIONS············6
4. WIRING DIAGRAM·······························9
REFRIGERANT SYSTEM DIAGRAM
······12
6. DATA ···················································16
7. MICROPROCESSOR CONTROL·······20
8. TROUBLESHOOTING························27
9. DISASSEMBLY PROCEDURE···········35
10. PARTS LIST········································42
11. OPTIONAL PARTS ·····························48
<Indoor unit>
SEH-1.6AR.TH SEH-2AR.TH SEH-2.5AR.TH
No. OC165
[Models]
INDOOR UNIT
The Slim Line. From Mitsubishi Electric.
REMOTE CONTROLLER
SUH-1.6VR.TH SUH-2VR.TH SUH-2.5VR.TH
<Outdoor unit>
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
MODE
SELECT
FAN
SPEED
TIMER
MODE
DRY HEAT
HIGH
LOW
AUTO STOP
START
g
OUTDOOR UNIT
Ceiling Concealed
Series SEH
Page 2
2
1
PART NAMES AND FUNCTIONS
Indoor Unit
SEH-1.6AR.TH SEH-2AR.TH SEH-2.5AR.TH
Air outlet duct flange
Air outlet
Air inlet (Selecting the either back side or bottom side)
SUH-1.6VR.TH SUH-2VR.TH
Air inlet
Air outlet
Drain outlet
Piping
Drain hose
SUH-2.5VR.TH
Air inlet
Air outlet
Outdoor Unit
Page 3
3
Remote controller SEH-1.6AR.TH
SEH-2AR.TH SEH-2.5AR.TH
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY HEAT
HIGH
LOW
AUTO STOP
START
g
TIMER / TEMP.
This button is used to change between display of room temperature and display of remaining timer during "AUTO STOP" operation. Green lamps light in selected display
Remaining timer time display
Lamps display remaining timer time or room temperature.
Lamps indicate time remaining until timer stops timed operation. Green lamps corresponding to remaining number of hours light.
Room Temperature display
Lamps display temperature settings and actual room temperatures.
Temperature settings; Green lamps light.
Temperature in room; Green lamps flash.
(Example display readings are for explanations only ; autual display readings will differ.)
This button is used to change between low and high fan speeds. One of two green lamps lights to indicate fan speed in effect.
MODE SELECT button
This button is used to change between cooling, heating and DRY operation modes. One of three green lamps lights to indicate mode in effect.
ON / OFF button
Pushing button starts operation. Pushing again stops operation. Green lamp remains lit during
UP and DOWN buttons
Temperature control (While "TEMP" green lamps is lit.) Use UP and DOWN buttons to set disired temperature between 18 and 29°C.
Timed operation (While green "TIMER" lamp is lit.) Use UP and DOWN buttons to set timed operation between one and twelve hours.
TIMER MODE button
Used for selecting timed starting or stopping. Green lamps lights to indicate timer mode selected.
Pushing UP and Down buttons together for more than two seconds will initiate "trial run" or "inspection" mode. Avoid pushing these buttons simultaneously during normal operation. Push ON / OFF button to cancel trial run or inspection mode if initiated by accident.
All green lamps turn off when air conditioner is stopped.
Avoid operation of buttons with fingernails or other sharp objects. Sharp objects may scratch operating panel.
Attention :
Settings remain in effect until changed. Air conditioner can be operated by simply pushing ON /OFF button once settings have been made.
FAN SPEED button
Display Panel Operating Panel
Page 4
4
Model
Function
Power supply Capacity Dehumidification Air flow Running current Power input Auxiliary heater Power factor Starting current Compressor motor current Fan motor current
kW
R/h
K/h
A
W
A(kW)
%
A A A
W
"
"
"
mm mm mm mm mm mm
kg
kg dB dB
rpm rpm
kg
R
k" k" k"
Capacity
Electrical data
Coefficient of performance(C.O.P)
Compressor
Indoor fan motor
Outdoor fan motor
Dimensions
Indoor unit
Indoor unit
Width Height Depth Width Height Depth
Indoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Outdoor unit
RT11(at 25:) RT12(at 25:) RT61(at 0:)
Sound level (Hi) Fan speed (Hi) Fan speed regulator
Outdoor unit
Outdoor unit
Refrigerant filling capacity(R-22)
Thermistor
Weight
Special remarks
Model Output Winding resistance (at 20:) Model
Winding resistance (at 20:)
Model
Winding resistance (at 20:)
SEH-1.6AR.TH
Single phase, 220-240V, 50Hz
Cooling
SEH-2AR.TH
3.9-3.9
1.7
7.0-7.3
1460-1590
95-90
6.41-6.72
2.67-2.45
Heating
4.1-4.2 —
6.4-6.8
1350-1460
95-90
5.81-6.22
3.04-2.88
43 35
50 720-770 780-820
1.65
MS-56 O 0.52
RH-247VHAT
1200
C-R:2.13 C-S:3.91
PK6V19-EC
WHT-BLK :251.4 BLK-BLU :19.9
BLU-YLW :26.5 YLW-BRN :13.2
BRN-RED :50.0
RA6V40-EE
WHT-BLK :130.4
BLK-RED :134.6
59 39
52 810-850 810-845
1.8
MS-32(N-1) O 1.2
1100
270 700 850 605 290
35
3 1
10 10
33.18
780
Cooling
5.3-5.4
2.1
10.4-9.9
2270-2330
99-97
9.72-9.27
2.33-2.32
Heating
5.7-5.8 —
9.4-9.1
2050-2110
99-97
8.72-8.47
2.78-2.75
NH-38VMDT
1700
C-R:1.07 C-S:2.26
PK6V32-EC
WHT-BLK :161.9 BLK-BLU : 50.3
BLU-YLW :18.7 YLW-BRN :8.0
BRN-RED :39.2
RA6V50-OF
WHT-BLK :116.4
BLK-RED :111
1020
35-38 52-58
0.59-0.58 0.68-0.63
Refrigerant oil
SPECIFICATIONS
2
NOTE:Test conditions
Cooling : Indoor DB27°C WB19°C
Outdoor DB35°C WB24°C
Heating : Indoor DB20°C WB
Outdoor DB 7°C WB 6°C
Page 5
5
Model
NOTE:Test conditions
Cooling : Indoor DB27°C WB19°C
Outdoor DB35°C WB24°C
Heating : Indoor DB20°C WB
Outdoor DB 7°C WB 6°C
Function
Power supply
Capacity
Capacity
Electrical data
Coefficient of performance(C.O.P)
Compressor
Indoor fan motor
Outdoor fan motor
Dimensions
Weight
Special remarks
Dehumidification Air flow Running current Power input Auxiliary heater Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance (at 20:) Model
Winding resistance (at 20:)
Model
Winding resistance (at 20:)
Width
Indoor unit
Outdoor unit
Indoor unit Outdoor unit Sound level (Hi) Fan speed (Hi) Fan speed regulator Refrigerant filling capacity(R-22)
Refrigerant oil
Thermistor
Height Depth Width Height Depth
Indoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Outdoor unit
RT11(at 25:) RT12(at 25:) RT61(at 0:)
kW
R/h
K/h
A
W
A(kW)
%
A A A
W
"
"
"
mm mm mm mm mm mm
kg
kg dB dB
rpm rpm
kg
R
k" k" k"
SEH-2.5AR.TH
Cooling
Single phase, 220-240V, 50Hz
6.6-6.7
3.0 1200
13.5-12.6
2950-2950
99-97
59
12.55-11.74
0.95-0.86
2.10-2.14 NH-47VMDT
2200
C-R :0.96 C-S :2.07
PK6V50-EC
WHT-BLK :101.1 BLK-BLU :56.1
BLU-YLW :14.7 YLW-BRN :6.7
BRN-RED :28.2
RA6V85-AA
WHT-BLK :62.7 BLK-YLW :30.2
YLW-RED :62.9
1100
270 700 870 850 295
35 72 43
53 860-890 720-750
3 2
2.4
MS-32(N-1) O 1.2
10
10
33.18
Heating
6.9-7.0 —
12.3-11.8
2680-2750
99-97
11.35-10.94
2.57-2.55
Page 6
6
OUTLINES AND DIMENSIONS
3
INDOOR UNIT
SEH-1.6AR.TH SEH-2AR.TH SEH-2.5AR.TH
SUH-1.6VR.TH SUH-2VR.TH
605
29220
50
183
500
161
850
74
30
100
157
35
30
Service panel
Liquid refrigerant
pipe joint
Refrigerant pipe
(flare)
Gas refrigerant
pipe joint
Refrigerant pipe
(flare)
6.35 (SUH-1.6/2VR.TH)
12.7 (SUH-1.6VR.TH)
15.88 (SUH-2VR.TH)
Air inlet
View A
A
Electrical parts box
Suspension
bolt
pitch
Air outlet
Access door
Service space(It is necessary to maintain a working service area from the ceiling.)
20 mm or more
Access door
Electrical parts box
Suspension bolt pitch
Suspension bolt pitch
Drain plug R1 male
Refrigerent pipe(liquid)
{6.35(SEH-1.6/2AR.TH) {9.52(SEH-2.5AR.TH)
Refrigerent pipe(gas)
{12.7(SEH-1.6AR.TH) {15.88(SEH-2/2.5AR.TH)
Unit : mm
OUTDOOR UNIT
35
248
Drainage 3holes 16.2
350
20
290
310
345
10cm or more
50cm
If the right/left sides or back side is vacant,the front has only to be 50cm unobstructed.
or m
ore
If the front or right/left sides
are vacant, the top has only
to be 10cm
10cm or more
unobstructed.
10cm or more
35cm
or m
ore
Page 7
7
SUH-2.5VR.TH
More than 350 mm
More than 10 mm
Open as a rule
More than 500 mm if the
front and both sides are open.
More than 100 mm
More than 200 mm if three
area obstacles to both sides.
Open as a rule
More than 500 mm if the
back both sides and top
are open.
OUTDOOR UNIT
Unit : mm
362 330
150
500
Service space
500
10
39.5 27.5
200
Note:Allow adequate
upper clearance
10
Front opening
10
Outdoor Unit-Necessary surrounding clearance
1715
Air intake
500
4553
Refrigerant-pipe flared
connection [15.88 5/8F
Refrigerant-pipe flared
850
Terminal block for power line
Terminal block for indoor and outdoor unit connection
870
Service panel
Handle for moving
connection [9.52 3/8F
553
352
337
403
Knock out holes for
power line 2-[27
120
60
Knock out hole
for front piping
Knock out hole
(refrigerant,drainage
and wiring)
33
104
R20
0
2
R
for right piping
(refrigerant,drainage
and wiring)
45 42
Bottom
piping hole
25 max.
Standard bolt length
80
65
Front right piping holes-
17
R6
2-U-shaped
notched
holes
detail figures
12
185 185
Air intake
200
The upper side must be open.
Air outlet
1000For 10 units or less
302
724295
Outlet guide
installation hole
Side air intake
Handle for moving
Rear fresh
air intake
441
Drain hole
2-12o23 Oval holes
(standard bolt M10)
179 524
40 60524
Drain hole
33
23
Outdoor Unit-Necessary surrounding clearance
(Concentrated installation)
100 10
Handle
for moving
95
138
Rear piping hole
Page 8
8
REMOTE CONTROLLER
Remote controller cable installation
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
MODE
SELECT
FAN
SPEED
TIMER
MODE
DRY HEAT
HIGH
LOW
AUTO STOP
START
75
69
108
117
108
96.5
12
90.5
11.6
3.6
33
117
33
g
Rear side wiring arrangememt opening
Upper side wiring arrangement opening
Fixing hole
83.5
12
86
4.6
46
9.2
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY HEAT
HIGH
LOW
AUTO STOP
START
Exposed remote controller cable
Cable can be connected only to the top of the remote controller. (Right side, left side, and buttom are not possible.)
g
For exposed remote controller cable installation
Note : The cable for the remote controller has 10m (39ft) length and 12-core with connectors O.D. 5.8.
For recessed remote controller cable installation
Unit : mm
Remote controller cable
Conduit tube (local arrangement)
Switch box (local arrangement)
Set screw (match with switch box), local arrangement.
Page 9
NOTE :1. Since the indoor fan motor (MF) is connected with 50 Hz power, if 60Hz power is used,change the wiring
connection showing fig:*1
Indoor Fan Motor(MF) for 60Hz
2. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
3. Use copper conductors only. (For field wiring)
4. Symbols below indicate. /:Terminal block, : Connector
How to remove the terminals shown at ”w” mark.
9
WIRING DIAGRAM
4
TB
CIRCUIT BREAKER
POWER SUPPLY ~/N 220-240V
TB
GRN/YLW
12VDC
3
RED
L
W
W
W
W
W
N
BRN
220-240V~
N
BLU
WHT
GRN/YLW
BLU
TO OUTDOOR UNIT CONNECTING
P.C
CONTROLLER
REMOTE
BOARD
CN
113104
CN CN
112
52
2
RT12
1212
CNR
120
CN
120
CN
104B
RT11
TRANS
HIC1
3
CN201
ELECTRONIC CONTROL P.C BOARD
NR11
52C
F11
4
3
2 1
BLU
YLW
YLW BLU
SR144
LDFH
BLK BLK
8
LDCOM
LDC11 LDC12
LDFL LDFM LDFVL
SR142
SR143
SR141
GRN/YLW
WHT ORN RED
BRN
BRN
WHT
7
5 6
1 2 3 4
C11
RED
BLU
ORN
MF
50Hz
2
W
SR141 SR144
RT11
TB
TERMINAL BLOCK
RT12 INDOOR COIL
THERMISTOR
HIC1
DC/DC CONVERTER
NR11
MF
52C
F11
SYMBOL
NAME NAME
C11
SYMBOL
FAN MOTOR CAPACITOR
SOLID STATE RELAY
FUSE(3.15A)
COMPRESSOR CONTACTOR
ROOM TEMPERATURE THERMISTOR
VARISTOR
FAN MOTOR
NAMESYMBOL
~
REMOTE CONTROLLER INTERFACE
P.C. BOARD
w” shows the terminals with a lock mechanism,so they cannot be removed when you pull the lead wire.
Be sure to pull the wire by pushing the locking lever (project part) of the terminal with a finger.
1Slide the sleeve. 2Pull the wire while pushing the locking lever.
BLUE
YELLOW
60
50
fig: *1
BLUE
INDOOR UNIT
SEH-1.6/2/2.5AR.TH
Page 10
10
OUTDOOR UNIT
SUH-1.6/2VR.TH
NOTE :1. Use copper conductors only. (For field wiring)
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers (N,2,3 and ;).
3. Symbols below indicate. /:Terminal block, : Connector
4. ”w” shows the terminals with a lock mechanism,so they cannot be removed when you pull the lead wire.
Be sure to pull the wire by pushing the locking lever (project part) of the terminal with a finger.
1Slide the sleeve. 2Pull the wire while pushing the locking lever.
12VDC
220-240V
TO INDOOR
CONNECTING
UNIT
TB
RT61
21S4
BLK
BLK
4
MF
3
W
2
W
WHT
N
W
GRN/YLW
RED
F
BLU
WHT
DSAR
WHT ORN RED
3 2 1
WHT
WHT
RED
BLU
A1
VLT YLW
WHT
BLU
52C1
CR
A2
L1/1 T1/2
CN730
3 2 1
W
TAB20
YLW
52C1
T3/6L3/5
52C
WW
4
3
BLU
W
C1
CN711
C65
WHT
W
RED
BLK
W
123
SR61
F61
C
MC
S
4
CN661
IC881
TRANS
R
BLK
BLK
CN721
X62
NR61
DEICER P.C. BOARD
WHTWHT
CZ
SYMBOL NAME NAME
C1
COMPRESSOR CAPACITOR C65 F61 FUSE (2A)
F
FUSE (2A)
MC
COMPRESSOR
<INNER THERMOSTAT>
FAN MOTOR MF
<INNER THERMOSTAT>
NR61 VARISTOR
SYMBOL
RT61
SR61
TB X62
21S4
52C
52C1
DEFROST THERMISTOR SOLID STATE RELAY TERMINAL BLOCK REVERSING VALVE RELAY SOLENOID COIL
CONTACTOR COMPRESSOR CONTACTOR
NAMESYMBOL
IC881 DC/DC CONVERTER DSAR
SURGE ABSORBER 1FAN MOTOR CAPACITOR CR SURGE ABSORBER 2 CZ SURGE ABSORBER 3
Page 11
11
SUH-2.5VR.TH
RED
ORN
WHT
BLK
YLW
12VDC
TB
YLW
2 1
BLK WHT ORN RED
3
4
5
6
MF
X1
BRN
SR61
X62
BLK
CN721
CN730
2 1
3
BLK
21S4
1
5
3
C2
CN711
CN661
123
RT61
4
A2
A1
ORN
WHT
YLWVLT
TB2
CR
WHT
4
52C1
F61
NR61
TRANS
IC881
220-240V~
DSAR
GRN/YLW
RED
W
W
W
W
WW
3
2
N
TO INDOOR
UNIT
CONNECTING
WHT
RED
7
RED
VLT
BLU
26F1
X1
WHT
TAB20
52C
3
YLW
DEICER P.C. BOARD
BLU
WHTWHT
CZ
T3/6L3/5
BLU
L1/1 T1/2
52C1
WHT
C1
RED
BLK
S
C
R
MC
BLU
8
F
CZ SURGE ABSORBER 3
CR SURGE ABSORBER 2
IC881 DC/DC CONVERTERF61 FUSE (2A)
CONTACTOR
SOLENOID COIL
21S4
X62
MF
FAN MOTOR <INNER THERMOSTAT>
MC
COMPRESSOR <INNER THERMOSTAT>
TB,TB2
SR61
RT61
NR61 VARISTOR
F
C2
SYMBOL NAME NAME
C1
DSAR
SYMBOL
COMPRESSOR CAPACITOR
SURGE ABSORBER 1
FAN MOTOR CAPACITOR
FUSE (2A)
TERMINAL BLOCK
52C1
THERMAL REED SWITCH
26F1
X1 FAN MOTOR RELAY
52C
COMPRESSOR CONTACTOR
REVERSING VALVE RELAY
SOLID STATE RELAY
DEFROST THERMISTOR
NAMESYMBOL
NOTE :1. Use copper conductors only. (For field wiring)
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers (N,2,3 and ;).
3. Symbols below indicate. /:Terminal block, : Connector
4. ”w” shows the terminals with a lock mechanism,so they cannot be removed when you pull the lead wire. Be sure to pull the wire by pushing the locking lever (project part) of the terminal with a finger.
1Slide the sleeve. 2Pull the wire while pushing the locking lever.
OUTDOOR UNIT
Page 12
12
5
REFRIGERANT SYSTEM DIAGRAM
Indoor heat exchanger
Outdoor heat exchanger
Distributor (With strainer)
Flared connection
Room temperature thermistor RT11
Indoor coil thermistor RT12
Defrost thermistor RT61
Flared connection
Stop valve
Stop valve (with service port)
Strainer
Strainer
Strainer
Capillary tube ({3.0x{1.8xR330)
Capillary
tube
({3.0x{1.6xR550)
Restrictor valve
Refrigerant flow in cooling
Compressor
Accumulator
Strainer 1
valve
Muffler
Refrigerant flow in heating
Refrigerant pipe [12.7 (Option) (with heat insulator)
Refrigerant pipe (Option) [6.35 (with heat insulator)
Dis Pressure Regulator
Reversing
INDOOR UNIT
SEH-1.6AR.TH
OUTDOOR UNIT
SUH-1.6VR.TH
Indoor heat exchanger
Outdoor heat exchanger
Distributor (With strainer)
Flared connection
Room temperature thermistor RT11
Indoor coil thermistor RT12
Defrost thermistor RT61
Flared connection
Stop valve
Stop valve (with service port)
Strainer
Capillary tube ({4.0X{2.4XR660)
Capillary
tube
({3.0X{1.6XR860)X2
Restrictor valve
Refrigerant flow in cooling
Compressor
Accumulator
Strainer 1
valve
Muffler
Refrigerant flow in heating
Refrigerant pipe [15.88 (Option) (with heat insulator)
Refrigerant pipe (Option) [6.35 (with heat insulator)
Dis Pressure Regulator
Strainer
Strainer
Reversing
INDOOR UNIT
SEH-2AR.TH
OUTDOOR UNIT
SUH-2VR.TH
Page 13
13
INDOOR UNIT OUTDOOR UNIT
SEH-2.5AR.TH
SUH-2.5VR.TH
Indoor heat exchanger
Indoor coil thermistor RT12
Room temperature thermistor RT11
Strainer
Distributor (With strainer)
Strainer
Refrigerant pipe [15.88 (Option) (with heat insulator)
Ball valve
Flared connection
Flared connection
Refrigerant pipe (Option) [9.52 (with heat insulator)
Muffler
Accumulator
Strainer 3
Ball valve (with service port)
Reversing valve
Compressor
Strainer 2
Dis Pressure Regulator
Distributor
Capillary tube ({4.0x{2.0xR410)
Refrigerant flow in cooling Refrigerant flow in heating
Outdoor heat exchanger
Defrost thermistor RT61
Page 14
14
Models
A: Refrigerant piping Max.length 15m(49ft)
Max. Height difference *
7m(23ft)
MAX. REFRIGERANT PIPING LENGTH & MAX. HEIGHT DIFFERENCE
SEH-1.6AR.TH SEH-2AR.TH SEH-2.5AR.TH
Length : m(ft)
A
15(49)
Piping size O.D. : mm (in.)
Gas
Liquid
{12.7(1/2)
{6.35(1/4)
{15.88(5/8)
wIt does not matter which unit is higher.
Models
SEH-1.6AR.TH SEH-2AR.TH SEH-2.5AR.TH
Outdoor unit:precharged
(up to 7m)
1,650 1,800
Refrigerant piping length (one way)
7m08m509m
100
10m
150
11m
200
12m
250
13m
300
14m
350
15m
400
Calculation : (SEH-1.6/2AR)og=50g/mo(Refrigerant piping length minus 7m)
(SEH-2.5AR)og=65g/mo(Refrigerant piping length minus 7m)
If pipe length exceeds 7m, additional refrigerant (Freon 22) charge is required
ADDITIONAL REFRIGERANT CHARGE (R-22 : g)
{9.52(3/8)
2,400
130
195 260
325
390 455 520
Page 15
15
EVACUATION PROCEDURES
Connect the refrigerant pipes (both the liquid and gas pipes) between the indoor and the outdoor units.
Remove the service port cap of the stop/ball valve on the gas pipe side of the outdoor unit gas pipe. (The stop/ball valve will not work in its initial state fresh out of the factory (totally closed with cap on).)
Connect the gauge manifold valve and the vacuum pump to the service port of the stop/ball valve of the outdoor unit. : For SUH-1.6/2VR.TH connect to gas pipe side.
For SUH-2.5VR.TH connect to liquid pipe side.
Run the vacuum pump for more than 15 minutes and at this time confirm that the pressure gauge indicates
-0.1 Mpa (-76 cmHg).
Check the vacuum with the gauge manifold valve, then close the gauge manifold valve, and stop the vacuum pump.
Leave as it is for one or two minutes. Make sure the pointer of the gauge manifold valve remains in the same position.
After refrigerant pipes are connected and evacuated, fully open all stop/ball valves on gas and liquid pipe sides. Operating without fully opening lowers the performance and causes trouble.
Pipe length : 7m maximum No gas charge is needed.
Pipe length exceeding 7m Charge the prescribed amount of gas.
Remove the gauge manifold valve quickly from the service port of the stop/ball valve.
Tighten the cap to the service port to obtain the initial status.
Tighten the cap to the stop/ball valve.
Leak test
Ball valve (liquid side)
Service port
Valve knob Lo
Valve knob Hi
Charge hose
Vacuum
pump
Manifold valve
Compound gauge Pressure gauge
-1.0110 Pa (-760mmHg)
Stop valve
Stop valve
Stop valve
Close
Caps
Gauge manifold valve
Gas pipe
Connection pipe
Open
Vacuum pump
Service port
Hexagonal wrench
Liquid pipe
Hexagonal wrench
<SUH-2.5VR.TH>
<SUH-1.6/2VR.TH>
Page 16
16
DATA
6
The standard data contained in these specifications apply only to the operation of the air conditioner under normal condition.
Operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
Rated voltage : ±10% (198~264V), 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
COOLING (1) Indoor intake air wet-bulb temperature :
˚CWB
(2) Indoor outlet air wet-bulb temperature :
˚CWB
(3) Outdoor intake air dry-bulb temperature :
˚CDB
(4) Total input : W
Indoor air wet/dry-bulb temperature difference on the side of the chart on page shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and-dry-bulb thermometers to the indoor air inlet as shown in the figure, and at least 2 sets of wet­and-dry-bulb termometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet-and-dry-bulb thermometers to the outdoor air inlet.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of the room.
5. Press the TEST RUN switch once to start the COOL(HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
Air outlet
Air inlet
Wet-and dry-bulb thermometers
Wet-and dry-bulb thermometers
BACK VIEW
INDOOR UNIT
OUTDOOR UNIT
HEATING (1) Indoor intake air dry-bulb temperature :
˚CDB
(2) Indoor outlet air dry-bulb temperature :
˚CDB
(3) Outdoor intake air wet-bulb temperature :
˚CWB
(4) Total input : W
20.6
19.0
17.5
15.9
14.3
12.7
11. 1
8.7
8.0
7.3
6.6
5.9
5.3
9.5
9.4
10.0
8.6
7.8
7.1
6.3
5.6
SEH-2AR.TH
SEH-1.6AR.TH
22.3
22.9
20.6
21.1
18.9
19.4
17.2
17.6
15.4
15.8
13.7
14.1
12.0
12.3
10.3
10.6
9.1
8.3
7.5
6.7
6.0
SEH-2.5AR.TH
SEH-2AR.TH
EH-1.6AR.TH
EH-2.5AR.TH
Page 17
17
Dry Bulb temperature (˚C)
Relative humidity (%)
(4) OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
COOL operation
1 Both indoor and outdoor units are under the same temperature/humidity condition.
2 Air flow should be set at MAX.
0.8
0.7
0.6
0.5
0.4
0.3 15 18 20 25 30 32 35(:)
50 60 70 (%)
Ambient temperature (:) / Ambient humidity (%)
Outdoor low pressure
8
7
6
5
4
3
15 18 20 25 30 32 35(:)
50 60 70 (%)
Ambient temperature (:) / Ambient humidity (%)
Outdoor unit current (A)
240V
220V
8
7
5
6
4
3
(MPa•G)
(kgf/F• G)
SEH-1.6AR.TH
3 The unit of pressure has been changed to MPa based on the international system of units(SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa • G) =10.2(kgf/
f
f
• G)
0.7
0.6
0.5
0.4
0.3
0.2 15 18 20 25 30 32 35(:)
50 60 70 (%)
Ambient temperature (:) / Ambient humidity (%)
Outdoor low pressure
10
9
8
7
6
5
15 18 20 25 30 32 35(:)
50 60 70 (%)
Ambient temperature (:) / Ambient humidity (%)
Outdoor unit current (A)
240V
220V
(MPa•G)
7
6
4
3
2
5
(kgf/F• G)
SEH-2AR.TH
SEH-2.5AR.TH
240V
220V
0.7
0.6
0.5
0.4
0.3
0.2 15 18 20 25 30 32 35(:)
50 60 70 (%)
Ambient temperature (:) / Ambient humidity (%)
Outdoor low pressure
13
12
11
10
9
8
7
15 18 20 25 30 32 35(:)
50 60 70 (%)
Ambient temperature (:) / Ambient humidity (%)
Outdoor unit current (A)
(MPa•G)
7
6
4
3
2
5
(kgf/F• G)
Page 18
18
10
9
8
7
0 2 5 10 15 20 25(:)
Ambient temperature (:)
Outdoor unit current (A)
240V
220V
240V
220V
13
11
9
7
0 2 5 10 15 20 25(:)
Ambient temperature (:)
Outdoor unit current (A)
SEH-2AR.TH
SEH-2.5AR.TH
8
7
6
5
4
3
0 2 5 10 15 20 25(:)
Ambient temperature (:)
Outdoor unit current (A)
HEAT operation
Condition Indoor : Dry bulb temerature 20.0:
Wet bulb temerature 14.5:
Outdoor : Dry bulb temerature 7,15,20:
Wet bulb temerature 6,12,14.5:
240V 220V
SEH-1.6AR.TH
Page 19
19
(5) INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW
SEH-1.6AR.TH
80
60
40
20
External static pressure(Pa)
(1Pa = 0.1mmAq)
0
Fan Performance
Recommended range
105 7 15 20 25
Air flow (K/X)
1.1
1.0
0.9
Correction factor
0.8
1.3
1.2
1.1
1.0
Correction factor
0.9
Corrected Air flow
Cooling
1051520
Air flow (K/X)
Heating
Capacity Input
25
SEH-2AR.TH
80
60
40
20
External static pressure(Pa)
(1Pa = 0.1mmAq)
0
SEH-2.5AR.TH
80
60
Fan Performance
Recommended range
15510 2025
Air flow (K/X)
Fan Performance
Recommended range
0.8
Corrected Airflow
1.1
1.0
0.9
Correction factor
0.8
1.2
1.1
1.0
0.9
Correction factor
0.8
Corrected Air flow
1.1
1.0
0.9
Correction factor
0.8
5101520
Air flow (K/X)
Cooling
510152025
Air flow (K/X)
Heating
510152025
Air flow (K/X)
Cooling
10 15 20 25 30
Air flow (K/X)
25
Capacity Input
Capacity Input
40
20
External static pressure(Pa)
(1Pa = 0.1mmAq)
0
15510 2025
Air flow (K/X)
1.3
1.2
1.1
1.0
Correction factor
0.9
Heating
10 15 20 25 30
Air flow (K/X)
Page 20
20
MICROPROCESSOR CONTROL
7
1. COOL operation
(1) Compressor control
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when the room temperature is higher than the set temperature.
The compressor stops when the room temperature is equal to or lower than the set temperature.
3 The compressor stops in check mode.
(2) Indoor fan control
Indoor fan speed LOW/HIGH depends on the remote controller setting.
(3) Outdoor fan control
POWER ON/OFF with the compressor.
(4) Coil frost prevention
1 Temperature control
When the indoor coil thermistor RT12 reads -1°C or below, the coil frost prevention mode starts immediately. However the coil frost prevention will not work for 5 minutes after the compressor starts. During the coil frost prevention compressor stops and the indoor fan operates at the set speed for 5 minutes. After that, if RT12 still reads or below -1°C, this mode prolonged untill theRT12 reads over -1°C. After the coil frost prevention stops, units will not enter this mode again at least 5 minutes even RT12 reads -1°C.
2 Time control
When the three conditions below have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes. a. Compressor has been continuously operating. b. Indoor fan speed is Low. c. Room temperature is below 26°C. When compressor stops ,the accumulated time is canceled and when compressor restarts, time counting starts from the beginning. Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds 26°C. However, when two of the above conditions (b.And c.) are satisfied again time accumulation is resumed.
<How to operate>
1 Press POWER ON / OFF button. 2 Press MODE SELECT button to set operation mode to COOL. 3 Check lamp is ON and set desired temperature with UP or DOWN but-
ton.
NOTES : 1. When lamp is ON, press TIMER/TEMP button to change the
display to temperature mode.
2. Set temperature changes by 1°C in the range 18 ~ 29°C each time UP or DOWN button is pressed.
3. The lighting lamp shows the set temperature, and the flashing lamp shows the room temperature. When the room temperature is equal to the set temperature, the lamp keeps lighting, 0.5 seconds brightly and 0.5 seconds faintly.
TIMER
<COOL operation time chart>
W1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this
period has ended.
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
MODE
SELECT
FAN
SPEED
TIMER
MODE
DRY HEAT
HIGH
LOW
AUTO
STOP
START
g
TEMP
Thermostat
Indoor fan
Operation starts by POWER button ON.
ON
OFF
ON
OFF
Room temperature becomes equal to set temperature.
Room temperature rises above set temperature.
LOW or HIGHLOW or HIGH
Operation stops by POWER button OFF.
Compressor Outdoor fan
ON
OFF
}
MIN. 3 minutes 1
Page 21
21
2. DRY operation
<How to operate>
1 Press POWER ON / OFF button. 2 Press MODE SELECT button to set operation mode to DRY. 3 Check lamp is ON and set desired temperature with UP or DOWN but-
ton.
NOTES : 1. When lamp is ON, press TIMER/TEMP button to change the
display to temperature mode.
2. Unable to set temperature. POWER ON/OFF are operated by microprocessor control automatically.
3. The flashing lamp shows the room temperature.
TIMER
<DRY operation time chart> In case of the room temperature of 23: and above.
Thermostat
Indoor fan
Outdoor fan compressor
1st ON
8min.
1min
.
4min.
3min.
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
(1) Setting temperature
Follow the right chart with according to the initial room temperature. When the room temperature is 13: or under, dry operation does not work.
(2) ON/OFF control
When the room temperature is 23°C or over:
Compressor operates by temperature control and time control.
1 Set temperature is controlled to fall 2°C above from initial set temperature. 2 When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON. Indoor fan and outdoor fan operate in the same cycle as the compressor.
When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
(3) Coil frost prevention
The operation is same as that of coil frost prevention during COOL mode. However the indoor fan speed becomes the set speed or Low.
TIMER TEMP
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER/TEMP.
UP
DOWN
POWER
ON/OFF
COOL
MODE
DRY
SELECT
HEAT
g
HIGH
FAN
SPEED
LOW
AUTO STOP
TIMER MODE
START
MITSUBISHI ELECTRIC
TEMP
Page 22
22
3. HEAT operation
<How to operate>
1 Press POWER ON / OFF button. 2 Press MODE SELECT button to set operation mode to HEAT. 3 Check lamp is ON and set desired temperature with UP or DOWN but-
ton.
NOTES : 1. When lamp is ON, press TIMER/TEMP button to change the
display to temperature mode.
2. Set temperature changes by 1°C in the range 18 ~ 29°C each time UP or DOWN button is pressed.
3. The lighting lamp shows the set temperature, and the flashing lamp shows the room temperature. When the room temperature is equal to the set temperature, the lamp keeps lighting, 0.5 seconds brightly and 0.5 seconds faintly.
TIMER
(1) Compressor control
1 3minute time delay
To prevent overload, the compressor will not start within 3minutes after stop.
2 The compressor runs when the room temperature is higher than the set temperature.
The compressor stops when the room temperature is equal to or higher than the set temperature.
w 4degrees up control
During heat operation, lower the room temperature for 4degrees more than thermistor value.
3 The compressor stops in check mode. 4 Follow the item (5) during defrosting.
<HEAT operation time chart>
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Compressor Outdoor fan
ON
LOW or HIGHLOW LOW LOW or HIGH VLo
OFF
OFF
ON OFF
Operation starts by POWER button ON.
Operation stops by POWER button OFF.
Room temperature becomes equal to set temperature.
Room temperature falls below set tem­perature.
}
w1 Even if the room temperature falls below the set temperature during this period, the compressor will not start until this period has ended.
TIMER TEMP
TIMER/TEMP.
29
12
28
11
27
10
26
9
25
8
24
7
23
6
DOWN
22
5
21
4
20
3
19
2
18
1
POWER
ON/OFF
COOL
MODE
DRY
SELECT
HEAT
UP
g
HIGH
FAN
SPEED
LOW
AUTO STOP
TIMER MODE
START
MITSUBISHI ELECTRIC
TEMP
Page 23
23
(2) Indoor fan control
1 Cold air prevention control
The fan runs at set speed when the indoor coil thermistor RT12 temperature exceeds 22°C. The fan operates at VLo when the temperature is below 18°C. But the fan stops when the indoor fan operates at VLo and the room temperature is 15°C or less. Released
Cold Air Prevention
NOTE : At initial in hysteresis this control works.
2 New warm air control.
When compressor starts in heating operation or after defrosting, the fan changes the speed with dependance on the indoor coil thermistor RT12 temperature to blow out warm air. After releasing of cold air prevention, when the indoor coil temperature is 37°C or above, the fan speed shifts to the set speed, and when the fan speed is changed by the remote controller, the fan speed is the set speed. When the indoor coil temperature is less than 37°C, the fan speed is controlled by time as below.
<Time condition> <Indoor fan speed> less than 2 minutes························Low 2 minutes or more··························High
The upper limit of the fan speed is the set speed.
If the thermostat turns off, this operation changes to flow soft control.
3 Flow soft control
After the thermostat turns off, the indoor fan operates at VLo.
NOTE : When the thermostat turns on, the fan operates at the set speed. Due to the cold air prevention control, the fan
does not start until the indoor coil thermistor RT12 reads 22°C or more.
4 Follow the item (5) during defrosting.
(3) Outdoor fan control
POWER ON/OFF with the compressor. However during defrosting, follow the item (5).
(4) Reversing valve
18°C
22°C
Heating · · · · · ON Cooling · · · · · OFF Dry · · · · · · · · OFF
NOTE: The Reversing valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
ON OFF
Compressor
Reversing valve
Outdoor fan
(COOL / DRY)
(HEAT)
5 sec.
5 sec.
Page 24
24
(5) Defrosting
Defrosting of outdoor heat exchanger is controlled by deicer P.C. board, with detection by the defrost thermistor RT61.
1Defrost starting conditions
When all conditions of a),b) are satisfied, the defrosting operation starts.
a) Under the heat operation, the compressor cumulative operation time exceeds 40 minutes without the detrosting
operation working.
b) The defrost thermistor RT61 reads - 3°C or less.
2Defrost terminating conditions
When the condition d) or e) is satisfied, the defrosting operation stops.
d) The defrost thermistor RT61 reads 3.1°C or more. e) The defrosting time exceeds 10 minutes.
NOTE w When the indoor coil thermistor reads above 18°C, indoor fan operates at VLo for 30 seconds.
w When the indoor coil thermistor reads 18°C or less, the indoor fan stops.
<Defrosting time chart>
Defrost thermistor
3.1: or more
-3: or less
Outdoor 52C relay (Compressor)
X62
(Reversing valve)
SR61 Outdoor fan
Defrost counter
Indoor fan
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Max 10 min.
30 sec.
15 sec.
30 sec.
15 sec.
VLo
w
RT61
Page 25
25
4. TIMER operation
<Timer function>
AUTO STOP ·········Air conditioner stops after the set time lapses. AUTO START ········Air conditioner starts after the set time lapses.
<How to operate
AUTO STOP timer>
1 While lamp is lighting, press TIMER MODE button.
and lamps turn ON.
2 Set the time for the AUTO STOP timer with the UP or DOWN button.
NOTE : The time setting is in 1 hour units up to 12 hours.
3 With the lapse of time, the timer lamps turn OFF one by one, showing the
remaining time.
4 To cancel the AUTO STOP timer and continue operation, press the TIMER MODE
button. To cancel the AUTO STOP timer and stop operation, press the POWER ON/OFF button.
<How to operate AUTO START timer>
1 While lamp is OFF, press TIMER MODE button.
and lamps turn ON.
2 Set the time for the AUTO START timer with the UP or DOWN button.
NOTE : The time setting is in 1 hour units up to 12 hours.
3 With the lapse of time, the timer lamps turn OFF one by one, showing the
remaining time.
4 To cancel the AUTO START timer and keep the unit OFF, press the TIMER MODE
button. To cancel the AUTO START timer and start operation, press the POWER ON / OFF button.
TIMER
POWER
POWER
5. TEST RUN
The unit starts the test run by pressing both the UP and DOWN buttons simultaneously for more than two seconds during
lamp ON or the unit OFF.
The test run automatically stops in 2 hours.
Set temperature is not displayed during test run.
During the test run, the thermo function are as below.
Room temperature is displayed by the flashing green lamp when TIME/TEMP button is pressed.
The test run can be released by pressing the POWER ON / OFF or the TIMER MODE button.
TIMER
Initial 30 minutes
Thermo ON at the all time
Since 30 minutes passed to terminating of the
test run
Thermo ON/OFF as 24: of setting
temperature
TIMER TEMP
TIMER/TEMP.
29
12
28
11
27
10
26
9
25
8
24
7
23
6
22
5
21
4
20
3
19
2
18
1
UP
DOWN
POWER
COOL DRY HEAT
HIGH
LOW
AUTO
STOP
START
MITSUBISHI ELECTRIC
ON/OFF
MODE
SELECT
g
FAN
SPEED
TIMER
TIMER MODE
Page 26
26
6. SERVICE FUNCTION
(1) AUTO RESTART FUNCTION
Operating the J2 Jumper line on the remote control Interface P.C.board of the indoor unit. The function can set the auto restart function.
J2 = Auto restart wAuto restart setting on the shipping. No J2 = No auto restart
(2) COMPULSORY DEFROSTING MODE FOR SERVICE
By short circuit of the connector JP607 and R853 on the outdoor deicer P.C. board, defrosting mode can be accomplished regardless of the defrost interval restriction. Defrost thermistor RT61 must be below -3:.
(3) DEFROST TERMINATION CHANGE
<JPC> when the JPC wire of the deicer P.C. board is cut, the defrost interval time will be changed.(See page 33.) <JPE> when the JPE wire of the deicer P.C. board is cut, the defrost temperature will be changed.(See page 33.)
(4) 4degrees up Function
Operating the J3 Jumper line on the remote control Interface P.C.board of the indoor unit. The function can set the 4degrees up function.(See page 32.) W 4degrees setting on the shipping.
J3 = 4degrees up NoJ3 = No 4degrees up
Model
Jumper wire Change point
JPC
JPE
Defrost interval time changes from 40 minutes to 15minutes.
Defrost start temperature changes from
-3: to 0:.
Defrost finish temperature changes from
3.1: to 10.1:.
SEH-1.6AR.TH SEH-2AR.TH SEH-2.5AR.TH
Page 27
27
TROUBLESHOOTING
8
1. Cautions on troubleshooting
(1) Before troubleshooting, check the followings:
1Check the power supply voltage. 2Check the indoor/outdoor connecting wire for mis-wiring.
(2) Take care the followings during servicing.
1 Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then turn
off the breaker.
2 When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
3 When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Page 28
28
2. Self diagnostic function
(1) When trouble occurs during operation, the unit stops and enters the self-diagnotic mode, and displays the trouble
location with the timer lamps on the remote controller. All the other lamps are OFF.
(2) To activate the self-diagnostic function for service, press the UP and DOWN buttons simultaneously for more than two
seconds during operation with lamp ON.
(3) The timer lamps show the latest trouble. Trouble data is memorised unit the next trouble occurs, even when the breaker
turns OFF. To clear the memory, press the UP and DOWN buttons simultaneously for more than two seconds during
the test run. (4) All buttons except the POWER ON/OFF button are unavailable during the self-diagnostic mode. (5) To release the self-diagnostic mode, press the POWER ON/OFF button.
TEMP.
12
11
10
9
8
7
6
5
1
2
3
4
(Indicates that the unit is in self-diagnostic mode)
TIMER TEMP.
29 Remote controller interface signal error
28 Mis-wiring or indoor-outdoor signal error
27 Indoor thermistor abnormally
26 Outdoor thermistor abnormally
25
24
23
22
18
19
20
21
Page 29
29
3. Trouble shooting
(1) In case of being indicated irregularity on the self diagnoses
No Phenomenon Cause Countermeasure
29 Remote controller interface
signal error
Mis-wiring of the Interface P.C.board.
Reinsert the wiring connector of the Interface P.C.board.
Trouble of the Interface P.C.board.
Exchange the Interface P.C.board.
Trouble of the Indoor P.C.board. Exchange the Indoor P.C.board.
28
Mis-wiring
Wiring between the indoor and outdoor is coming off.
Check the wiring out between the indoor and outdoor.
Difference of wiring polarity between the indoor and outdoor.
Indoor-outdoor signal error
Trouble of the outdoor deicer P.C.board.
Check the deicer P.C.board out.
Trouble of the Indoor P.C.board.
Exchange the Indoor P.C.board.
27
Indoor coil thermistor Mis-connecting of the Indoor coil
thermistor.
Reinsert the connector (CN112).
Trouble of the Indoor coil thermistor.
Room temperature thermistor
Trouble of the Indoor P.C.board.
Check the resistance value of the thermistor.
Mis-connecting of the room temperature thermistor.
Exchange the Indoor P.C.board.
Reinsert the connector (CN113).
Trouble of the room temperature thermistor.
Trouble of the Indoor P.C.board.
Exchange the Indoor P.C.board.
Check the resistance value of the thermistor.
26 Outdoor thermistor
Mis-connecting of the Outdoor thermistor.
Reinsert the connector (CN661).
Trouble of the Outdoor thermistor.
Trouble of the deicer P.C.board.
Check the resistance value of the thermistor.
Exchange the deicer P.C.board.
Page 30
30
(2) Other case
Phenomenon Cause Countermeasure
Not working of remote controller switch ON/OFF
Mis-connecting the remote control wiring. Reinsert the connector of remote control wiring.
Mis-connecting the Interface P.C.board.
Reinsert the wiring connector of Indoor P.C.board and Interface P.C.board.
Short circuit the protecting parts in the Indoor P.C.board.
Check the varistor(NR11) and fuse(F11) out in the Indoor P.C.board.
Trouble of the Interface P.C.board.
Check the Interface P.C.board out.
Trouble of the Indoor P.C.board.
Working the Indoor units and not working the outdoor units.
Trouble of the remote controller. Exchange the remote controller.
Wiring between the indoor and outdoor is coming off.
Check the wiring out between the indoor and outdoor.
Difference of wiring polarity between the indoor and outdoor.
Check the deicer P.C.board out.
Trouble of the deicer P.C.board.
Not rotating the fan in the indoor unit.
Trouble of the contactor(52C1).
Trouble of the compressor(MC) and outdoor fan motor(MF).
Exchange the contactor.
Check the compressor and fan motor out.
Frequency switching connector is coming off.
Fan motor connector is coming off.
Check the connector out.
Check the frequency (50Hz/60Hz) in the indoor unit.
Trouble of the Indoor P.C.board. Check the fan motor output of the Indoor
P.C.board.
Trouble of the fan motor.
Check the resistance value between the each tap of fan motor.
Check the Indoor P.C.board out.
Page 31
31
4. Test point of P.C.board
(1) Indoor electronic control P.C. board
Fan motor power supply 220 - 240V AC
75643218
60Hz
Hi
Fuse 250V AC 3.15A
Power supply input 220-240V AC
12V DC
5V DC
+ –
+ –
Time short point
Indoor coil thermistor (RT12)
VLo Lo
50Hz
Room temperature thermistor (RT11)
Indoor coil thermistor (RT12) Room temperature thermistor (RT11)
40
30
20
Resistance (K')
10
0
0
10 20 30 40 50 60
Temperature ( C)
Page 32
32
(2) Remote controller interface P.C. board
To Indoor electronic control P.C.board
To REMOTE CONTROLLER
– JP15= 0V + JP16= 12V DC + JP17= 5V DC
AUTO RESTART FUNCTION
4degrees up Function
Page 33
Outdoor fan motor
220-240V AC
Solenoid coil
220-240V AC
R601 5~10V DC
+
INPUT
220-240V AC
Defrost thermistor(RT61)
Fuse 2A/250V
Defrost interval time short pin
}
J9 J8
5V DC
Defrost interval Defrost termination temperature change Jumper wire JPC and JPE
}
52C
12V DC
+
}
12V DC
+
}
}
}
}
}
DEICER P.C. BOARD
+
33
(3) Deicer P.C. board
Page 34
34
Measure the resistance between the terminals with a tester. (Coil wiring temperature10°C ~ 30°C)
Compressor
Room temperature thermistor
5. Trouble criterion of main parts
Part name
Indoor coil thermistor
Indoor fan motor
Outdoor fan motor
Check method and criterion
Measure the resistance with a tester. (Part temperature 10°C ~ 30°C)
Measure the resistance between the terminals with a tester. (Coil wiring temperature -10°C ~ 40°C)
Measure the resistance between the terminals with a tester. (Coil wiring temperature -10°C ~ 40°C)
Figure
C
S
R
BLK
RED
WHT
BLK RED ORNYLW
BLU
BRN
WHT
GRN
YLW
P
Normal
8k~ 20k
Abnormal
Opened or short-circuited
Normal
1.6VR
1.87~2.30
3.44~4.22
2VR
0.94~1.16
1.99~2.44
C-R
C-S
Normal
Abnormal
Opened or
short-circuited
2AR
WHT-BLK
Normal
Abnormal
Opened or
short-circuited
102 ~ 126
97.9 ~ 120
2VR WHT-BLK BLK-RED
1.6VR
115 ~ 141 118 ~ 146
1.6AR
155.5~168.2241.4~261.2
BLK-BLU
48.3~52.319.0~20.6
BLU-YLW
17.8~19.425.4~27.5
YLW-BRN
7.6~8.312.6~13.7
BRN-RED
37.6~40.747.9~51.9
Abnormal
Opened or
short-circuited
1.6/2VR
BLK
RED ORN
WHT
MAIN
AUX
P
: Inner protector
p
2.5VR
0.84~1.04
1.82~2.24
55.3 ~ 67.7
2.5VR
BLK-YLW YLW-RED
26.6 ~ 32.6
55.4 ~ 67.9
2.5VR
BLK YLW
RED ORN
WHT
MAIN
AUX.2
AUX.1
P
Defrost thermistor (Outdoor)
Measure the resistance with a tester. (Part temperature - 10°C ~ 40°C)
Normal
5k~ 60k
Abnormal
Opened or short-circuited
Indoor Unit : SEH-1.6AR.TH SEH-2AR.TH SEH-2.5AR.TH Outdoor Unit : SUH-1.6VR.TH SUH-2VR.TH SUH-2.5VR.TH
2.5AR
97.0~105
53.8~58.3
14.0~15.3
6.3~6.9
27.0~29.3
Page 35
35
1. Removing the electrical parts
(1) Remove the 2 screws and the electrical parts cover.
(See Photo 1.)
Indoor controller board
Transformer
Run capacitor
Fuse (3.15A)
Terminal block
(See Photo 2.)
DISASSEMBLY PROCEDURE9
Indoor Unit : SEH-1.6AR.TH SEH-2AR.TH SEH-2.5AR.TH
OPERATING PROCEDURE PHOTOS
2. Removing the indoor coil thermistor(RT12)
(1) Remove the electrical parts cover.
(See Photo 1.)
(2) Remove the 2 screws and the service panel.
(See Photo 1.)
(3) Remove the thermister (RT12) from the holder.
(See Photo 3.)
(4) Disconnect the connector (CN112) from the indoor
controller board and pull the lead wire of thermistor (RT12) out.
Drain pan
Electrical parts cover
Service panel
Front panel
Set screws (for drin pan)
Fuse
Set screws
Terminal block
Transformer
Run capacitor
Thermistor
(RT12)
Photo 2.
Photo 3.
Photo 1.
Page 36
36
3. Removing the room temp. thermistor(RT11)
(1) Remove the electrical parts cover.
(See Photo 1.)
(2) Remove the front panel at fan side.(12 screws)
(See Photo 1.)
(3) Remove the thermister (RT11) from the fan casing.
(See Photo 4.)
(4) Disconnect the connector (CN113)from the indoor
controller board and pull the lead wire of thermistor (RT11) out.
PHOTOS
OPERATING PROCEDURE
4. Removing the sirocco fan and the fan moter.
(1) Remove the electrical parts cover.
(See Photo 1.)
(2) Remove the front panel at fan side.(12 screws)
(See Photo 1.)
(3) Disconnect the fan motor connector from the indoor
controller board
(See Photo 2.)
(4) Remove the thermistor (RT11) from the fan casing.
(See Photo 4.)
(5) Undo the 4 claws and remove the fan claws.(down side)
<Either left or right>
(See Photo 4.)
(6) Remove the motor bands. (A screw each on left and
right.)
(See Photo 4.)
(7) Disconnect the earth wire.(from the fan motor leg.)
(See Photo 5.)
(8) Remove the fan motor and the sirocco fan by assembly.
(See Photo 5.)
(9) Unscrew the setting screw and remove the sirocco fan.
<Either left or right>
(See Photo 5.)
Set screw
Earth wire
Motor bands
Thermistor
(RT11)
Claws
Screws
Fan casing
Fan motor
Claws
Photo 4.
Photo 5.
Page 37
37
5. Removing the drain pan
(1) Unscrew each set screw on the right and left, and
remove the drain pan pushing it toward the the back.
(See Photo 1.)
PHOTOS
OPERATING PROCEDURE
6. Removing the heat exchanger
(1) Remove the drain pan.
(See Photo 1.)
(2) Remove the Under flange at heat exchanger side.
(16 screws)
(See Photo 6.)
(3) Remove the 4 screws of heat exchanger.( 2 screws
each on left and right)
(See Photo 7.)
(4) Remove the service panel.( 3 screws )
(See Photo 7.)
(5) Put the heat exchanger down to the fan motor and
pull it toward you.
(See Photo 7.)
Screws
Under flange
Screws
(for heat exchanger)
Service panel
Screws (for service panel)
Heat exchanger
Photo 6.
Photo 7.
Page 38
38
OPERATING PROCEDURE PHOTOS
1. Removing the front panel
(1) Remove the screws of the front panel. (2) Hold the bottom of the front panel on the both side to
remove the cabinet.
2. Removing the deicer P.C. board
(1) Remove the service panel and the front panel. (2) Disconnect all the connectors and the terminals on the
deicer P.C. board.
(3) Remove the deicer P.C. board.
Ourtdoor Unit : SUH-1.6VR.TH SUH-2VR.TH
Photo 1
Photo 3
Photo 2
Black lead wire
White lead wire
Screws
Screws
Service panel
Terminal block
Screws
Red lead wire
Deicer P.C. board
Page 39
39
OPERATING PROCEDURE PHOTOS
3. Removing the outdoor fan motor
(1) Remove the front panel. (Refer to 1) (2) Unconnect the connector remove the clamp of fan motor
lead wire. (3) Remove the propeller nut and remove the propeller fan. (4) Remove screws fixing the fan motor.
4. Removing the compressor
(1) Remove the front panel. (Refer to 1) (2) Remove the soundproof felt. (3) Remove the terminal cover on the compressor (4) Remove the electrical assembly.
(Refer to 2) (5) Release gas from the refrigerant circuit. (6) Disconnect the welded part of the discharge pipe (7) Disconnect the welded part of the suction pipe. (8) Remove nuts fixing the compressor. (9) Remove the compressor.
Photo 5
Terminal cover
Compressor
Discharge pipe
Suction pipe
Compressor nuts
Photo 4
propeller fan
Set screws for outdoor fan motor
Lead clamps
Outdoor fan motor
Propeller fan nut
Set screws for outdoor fan motor
Page 40
40
OPERATING PROCEDURE PHOTOS
1. Removing the electrical parts
(1)
Remove the 5 screws and the top panel. (3 screws in front and 2 screws in rear
)
(2)
Remove the screw of the cover panel. To remove the cover panel, pull it toward you and unhook the catches from the side panel.
(3)
Remove the screw of the service panel. To remove the
service panel, pull it down toward you and unhook the catches on the both sides.
2. Removing the fan motor
(1)
Remove the 3 screws of the front panel. Open the front panel to a 45-degree angle. Then lift it and unhook the 3 catches to remove.
(2)
Remove the propeller fan nut and the propeller fan.
(3)
Remove the 3 screws and the fan motor. Disconnect the lead connectors.
Photo 1
Photo 2
Photo 3
Top panel
Service panel
Panel cover
Front panel
Capacitor
Contactor
Terminal blockScrews
Screws
Ourtdoor Unit : SUH-2.5VR.TH
Propeller fan nut
Valve bed
Lead connectors
Separator support plate
Motor support
Propeller
fan
Page 41
41
OPERATING PROCEDURE PHOTOS
3. Removing the heat exchanger and the compressor
(1)
Remove the rear panel (2 screws in front, 1 screw on the side, 3 screws in the rear). Remove the valve bed, and open the rear panel to the rear to remove.
NOTE :
All panels are fixed by catches, and must be removed by shifting up and down.
(2)
Remove the 4 screws of the right side panel and remove it.
(3)
Remove the 3 screws of the rear guard and remove it.
(4)
Remove the 4 screws of the separator support plate and remove it.
(5)
Remove the 2 screws of the motor support and remove it.
(6)
Remove the 5 screws of the valve bed. The valve bed is fixed by the catches on the right and left sides. Lift it to remove.
(7)
Remove the electrical parts box. Disconnect the connectors from the high pressure switch, crank case heater, shell thermo, and fan motor lead.
(8)
Remove the 2 screws of the separator and remove it.
(9)
Remove the 2 screws of the heat exchanger and remove it. Detach the welded point of pipe.
(
10
)
Remove the 3 nuts of the compressor and remove it. Detach the welded points of the compressor suction pipe and discharge pipe.
Photo 4
Photo 5
Photo 6
Compressor
Ball valve
Charge plug
Heat exchanger
Accumulator
Screws
Screws
Page 42
42
PARTS LIST10
No.
Parts No.
Parts name
Specification
Remarks
Unit
Amount
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Q'ty/set
Price
1 2 3 4
5
6 7
8
9 10 11 12 13 14
FRONT PANEL RIGHT SIDE PANEL LEFT SIDE PANEL BASE FAN MOTOR FAN MOTOR FAN MOTOR SIROCCO FAN RUBBER MOUNT INDOOR HEAT EXCHANGER INDOOR HEAT EXCHANGER INDOOR HEAT EXCHANGER DRAIN PAN RIGHT LEG LEFT LEG INDOOR COIL THERMISTOR ROOM TEMPERARURE THERMISTOR SEPARATOR ASSY
E07 039 000 E07 051 085 E07 039 086 E07 039 290 E07 039 300 E07 040 300 E07 041 300 E07 039 500 E02 179 505 E07 039 620 E07 040 620 E07 041 620 E07 039 700 E07 039 808 E07 039 809 E07 039 307 E07 039 308 E07 039 293
(Drawing No.)
MF MF MF
RT12 RT11
SEH-1.6
SEH-2 AR.TH
SEH-2.5
1 1 1 1 1
2 2 1
1 2 2 1 1 1
1 1 1 1
1
2 2
1
1 2 2 1 1 1
1 1 1 1
1 2 2
1 1 2 2 1 1 1
INDOOR UNIT STRUCTURAL PARTS SEH-1.6AR.TH SEH-2AR.TH SEH-2.5AR.TH
12
8
9
1
13
6
7
11
3
4
2
5
Part number that are circled is not shown in the illustration.
14
Page 43
43
INDOOR UNIT ELECTRICAL PARTS SEH-1.6AR.TH SEH-2AR.TH SEH-2.5AR.TH
SEH-1.6 SEH-2 SEH-2.5
AR.TH
No.
Parts No.
Parts name
Specification
3.15A
Remarks
(Drawing No.)
Unit
Amount
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty/set
Price
1 2 3 4 5 6 7 8 9
10
11 12
CABLE(FOR BOARD) REMOTE CONTROLLER CABLE COMPRESSOR CONTACTOR TERMINAL BLOCK TERMINAL BLOCK FUSE VARISTOR REMOTE CONTROLLER REMOTE CONTROLLER COVER ELECTRONIC CONTROL P.C. BOARD ELECTRONIC CONTROL P.C. BOARD ELECTRONIC CONTROL P.C. BOARD REMOTE CONTROLLER INTERFACE P.C. BOARD CONTROLLER COVER
1 1 1 1 1 1 1 1 1
1
1 1
E07 039 087 E07 027 089 E02 138 340 E02 367 377 E02 199 374 E02 127 382 E02 085 385 E07 039 426 E07 027 088 E07 039 450 E07 040 450 E07 041 450 E07 039 454 E07 039 449
52C
TB TB
F11
NR11
1 1 1 1 1 1 1 1 1 1
1 1
1 1 1 1 1 1 1 1 1
1 1 1
L,N, 3,2,N,
8921 11 10
4
5
3
6
Part number that are circled is not shown in the illustration.
Page 44
44
OUTDOOR UNIT STRUCTURAL PARTS SUH-1.6VR.TH SUH-2VR.TH
2
6
15
10
9
32517 19 18 26 4 24
3252120 1
8
Page 45
45
No.
Parts No.
Parts name
Specification
Remarks
Unit
Amount
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty/set
Price
1 2 3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
(Drawing No.)
S-N18EX S-N11EX
3.0MF-440VAC 50MF-440VAC 35MF-440VAC
3RUBBER 4RUBBER
RH-247VHAT NH-38VMDT
[3.0O[1.8OR330 [3.0O[1.6OR860 [4.0O[2.4OR660 [3.0O[1.6OR550
MF MF RT61 52C1 52C1 C65 C1 C1 TB F
DSAR NR61
21S4 21S4
1 1 1
1 1
1
1 1
1 1 1 1 1 1 1
1 1 3
1 1
1
1 1 1
1 1
1
1 1
1 1 1 1
1 1 1 1
1 1 1
1 1
1 1 1 1 1
1 1
1
4 1 1 1
1
1
1 1
1
1 1
2 1
1 1 1
FRONT PANEL BACK PANEL (OUT) SERVICE PANEL BASE BASE FAN MOTOR FAN MOTOR DEFROST THERMISTOR COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR FAN MOTOR CAPACITOR COMPRESSOR CAPACITOR COMPRESSOR CAPACITOR TERMINAL BLOCK FUSE (OUT) FUSE HOLDER SURGE ABSORBER 1 VARISTOR DEICER P.C. BOARD DEICER P.C. BOARD SOLENOID COIL SOLENOID COIL PROPELLER FAN COMPRESSOR RUBBER MOUNT COMPRESSOR RUBBER MOUNT MOTOR SUPPORT GRILLE (OUT) OUTDOOR HEAT EXCHANGER OUTDOOR HEAT EXCHANGER RESTRICTOR VALVE RESTRICTOR VALVE DIS PRESSURE REGULATOR STOP VALVE (GAS) STOP VALVE (GAS) STOP VALVE (LIQUID) COMPRESSOR COMPRESSOR ACCUMULATOR ACCUMULATOR STRAINER 1 CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE SURGE ABSORBER2 SURGE ABSORBER3 REVERSING VALVE
E02 141 232 E02 140 233 E02 141 245 E02 139 290 E02 201 290 E02 141 301 E02 144 301 E02 139 310 E07 012 340 E07 042 340 E02 214 351 E02 082 353 E02 089 353 E02 198 374 E02 095 382 E07 001 241 E02 128 383 E02 085 385 E07 042 451 E07 043 451 E02 139 490 E02 156 490 E02 141 501 E02 075 506 E02 138 506 E02 139 515 E02 141 521 E02 139 630 E07 042 630 E02 096 642 E02 154 642 E07 042 644 E02 140 661 E02 150 661 E02 139 662 E07 042 900 E07 043 900 E02 134 932 E02 258 932 E07 042 933 E07 042 936 E07 043 936 E07 049 936 E07 042 937 E07 042 384 E02 214 386 E02 077 961
MC MC
CR CZ
2A
SUH-1.6 SUH-2
VR.TH
Part number that are circled is not shown in the illustration.
Page 46
46
9
6
828 5
3
29
30
11
32
10
26
37 36 35
121315
24
27
1819 25
2
2
1
31
14 41
38 33
16
OUTDOOR UNIT STRUCTURAL PARTS
SUH-2.5VR.TH
7
20
Page 47
47
Part number that are circled is not shown in the illustration.
No.
Parts No.
1
E07 001 006
2
E07 001 009
3
E02 214 232
4
E07 001 241
5
E02 214 245
6
E02 214 249
7
E02 077 961
8
E02 214 290
9
E02 214 297
10
E02 214 301
11
E02 214 310
12
E07 012 340
13
E02 288 343
14
E02 138 351
15
E02 082 353
16
E02 198 374
17
E07 044 374
18
E02 214 381
19
E02 095 382
20
E02 128 383
21
E02 214 384
22
E02 085 385
23
E02 214 386
24
E07 044 451
25
E02 156 490
26
E02 214 501
27
E02 138 506
28
E02 214 515
29
E02 214 521
30
E02 214 522
31
E07 003 523
32
E02 214 630
33
E07 001 641
34
E07 042 644
35
E02 010 661
36
E02 010 662
37
E02 042 900
38
E02 214 932
39
E07 044 933
40
E07 050 933
41
E07 044 936
Parts name
PANEL COVER HANDEL FRONT PANEL FUSE HOLDER SERVICE PANEL LEFT SIDE PANEL REVERSING VALVE BASE TOP PANEL FAN MOTOR DEFROST THERMISTOR COMPRESSOR CONTACTOR FAN MOTOR RELAY FAN MOTOR CAPACITOR COMPRESSOR RUN CAPACITOR TERMINAL BLOCK TERMINAL BLOCK THERMAL REED SWITCH FUSE(OUT) SURGE ABSORBER 1 SURGE ABSORBER 2 VARISTOR SURGE ABSORBER 3 DEICER P.C. BOARD SOLENOID COIL PROPELLER FAN COMPRESSOR RUBBER MOUNT MOTOR SUPPORT FAN GUARD REAR PANEL REAR GUARD OUTDOOR HEAT EXCHANGER CHARGE PLUG DIS PRESSURE REGULATOR BALL VALVE(GAS) BALL VALVE(LIQUID) COMPRESSOR ACCUMULATOR STRAINER 2 STRAINER 3 CAPILLARY TUBE
Specification
2A
Q'ty/set
SUH-2.5VR.TH
1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Remarks
(Drawing No.)
S-N18EX
3.0MF-440VAC 50MF-440VAC
4RUBBER
5/8" 3/8" NH-47VMDT
{4.0X{2.0XR410
Wiring
Diagram
Symbol
MF RT61 52C1 X1 C2 C1 TB TB2 26F1 F DSAR CR NR61 CZ
21S4
MC
Recom­mended
Q'ty
Unit
Price
Amount
Page 48
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100 TELEX J24532 CABLE MELCO TOKYO
CCopyright 1998 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Issued in Aug.1998. No. OC165 96 Printed in Japan.
New publication, effective Aug. 1998. Specifications subject to change without notice.
OPTIONAL PARTS
11
1. REFRIGERANT PIPES
The air conditioner has flared connections its indoor and outdoor sides. Please use the optional extension pipe as follows.
3. AIR FILTER
Applied unit
SEH-1.6AR.TH
SEH-2AR.TH
SEH-2.5AR.TH
Models
PAC - 1000 FT
Applied unit
SEH-1.6AR.TH
SEH-2AR.TH
Models Pipe length
Pipe size O.D.mm (in.)
Cross-section A-Gas
{12.7
(1/2)
{15.88
(5/8)
{6.35
(1/4)
{27
{31
{21
{27
0
150 400
0
150 400
B-liquid
Insulation
CD
3m 5m
7m 10m 15m
3m
5m
7m 10m 15m
MAC-680PI MAC-681PI MAC-682PI MAC-683PI MAC-684PI
MAC-670PI MAC-671PI MAC-672PI MAC-673PI MAC-674PI
Additional
refrigerant
charge
R-22(g)
SEH-2.5AR.TH
0
195 520
3m
5m
7m
10m 15m
MAC-860PI MAC-861PI MAC-862PI MAC-863PI MAC-864PI
{9.52
(3/8)
2. REMOTE CONTROLLER EXTENSION CABLE
When installing the remote controller at a distance from the air conditioner, use the designated extension cable with connector.
Part No.
Length
PAC-905EC
12m
PAC-906EC
20m
PAC-918EC
30m
PAC-919EC
50m
Loading...