1. Locate the area where the Remote Status Alarm Panel (RSAP) will be installed. The
monitor should be within 300 feet (91 meters) of the UPS.
2. Mount the monitor to the wall using the four pre-drilled holes in the back. Use
appropriate hardware for the installation.
3. Wiring requirements are: 7 twisted pair 16 AWG cable run in metal conduit. Use Belden
Catalog No. 1485B (8 twisted pair) or equivalent. All electrical and mechanical
connections to be made per local and/or national electric codes.
4. Connect the conduit to the RSAP by punching the appropriately sized hole in a
convenient location.. Caution! Care should be taken not to damage any internal
components when drilling hole for conduit.
5. Refering to Figure 2.0, 3.0, and the corresponding UPS wiring diagram, connect the
seven (7) pairs of twisted wire from the RSAP to the customer accessible alarm contact
terminal bar in the UPS module. (Refer to the UPS’ owner’s manual for location)
6. Refering to Figure 3.0, install (6) AA batteries (included). Batteries will provide about 8
hours of run time in the event of an AC power failure. Replace these batteries yearly for
optimum performance.
7. Refering to Figure 1.0, connect the power supply adapter into the corresponding jack
located on the bottom left-hand side of the RSAP enclosure. Plug the power supply into a
convenient 120V/60Hz wall receptacle. Failure to connect to a suitable wall outlet will
drain the RSAP’s internal batteries and/or result in damage to the monitor. (If supplied
with the hardwire version, please refer to Figure 3.1 for AC input terminal block layout.
Connect L1, Neutral, and Ground with minimum of 18awg wire.)
Caution!
The monitor must be installed by a qualified electrician. Installation to be inspected
by an Authorized UPS Service Engineer at the time of UPS startup.
10/13/04 2 93120-MAN07
Operating Instructions
ALARM SILENCE pushbutton is used to silence the alarm.
MONITOR RESET pushbutton is used to reset the RSAP’s UPS FAULT alarm. The monitor will alarm
again if the alarm condition is still present following the RESET.
Monitor TEST pushbutton is used to check the operation of all LED's and the audible alarm. All LED’s
that are illuminated will go off and all lights that are off will illuminate. Horn will also sound.
INTERNAL MONITOR BATTERY TEST button is used to test the condition of the monitor's battery
pack. If the yellow LED does not illuminate, replace the batteries.
Reset the RSAP as follows:
1. On the UPS, note the alarm and it’s fault code. If applicable, contact 24 hour UPS field service at
(800) 887-7830.
2. If no alarm code is present, press the monitor reset button.
3. If the monitor's audible alarm sounds again repeat steps 1and 2.
4. Contact Mitsubishi service if the alarm cannot be reset after a few attempts.
Refer to Figure 1.0 for the location of the LED's and pushbuttons described below:
1. Rectifier / Charger LED.
operating.
2. Battery LED.
This yellow LED is illuminated as long as the UPS is in the battery backup mode.
The audible alarm will beep intermittently.
3. Inverter On LED
4. Output LED
. The green LED is illuminated as long as the UPS’ inverter is operating.
. This green LED is illuminated as long as there is power to the critical load. (either
by the Inverter or Bypass)
5. Load On Bypass LED
by the Bypass.
6. AC Input LED.
This green LED is illuminated as long as there is AC power supplied to the
system.
7. UPS Fault.
This Red LED is illuminated and the audible alarm sounds when a UPS fault has
occurred. The RSAP must be reset after the alarm is cleared.
8. Overload LED.
This red LED is illuminated when a UPS overload has occurred. The audible
alarm will also sound.
9. Input Failure LED
present. The audible alarm will also sound.
10. Battery Low Voltage
cutoff voltage. The audible alarm will also sound.
11. Alarm Silence LED
been pressed and alarm condition is still present. If alarm condition clears, the ALARM
SILENCE LED will automatically reset.
12. Internal Monitor Battery OK LED.
push button is pressed and the batteries are OK. If this light is dim or does not light, replace all
internal batteries.
This green LED is illuminated as long as the UPS’ inverter is
. This yellow LED is illuminated as long as the critical load is powered
. This red LED is illuminated when an input power failure condition is
. This red LED is illuminated as soon as the DC bus voltage approaches its
. This LED will illuminate when the ALARM SILENCE pushbutton has
This yellow LED will illuminate when it's corresponding
10/13/04 3 93120-MAN07
4. OUTPUT TO CRITICAL LOAD (GREEN LED)
5. LOAD ON BYPASS (YELLOW LED)
3. INVERTER ON (GREEN LED)
AUDIBLE ALARM
2. BATTERIES ON (YELLOW LED)
MONITOR RESET PUSHBUTTON
MONITOR TEST PUSHBUTTON
ALARM SILENCE PUSHBUTTON
INTERNAL MONITOR BATTERY TEST PUSHBUTTON
OUTPUT
MONITOR RESET
ALARM SILENCE
MONITOR TEST
INTERNAL MONITOR
BATTERY TEST
FIGURE 1.0
VOLTAGE
INPUT FAILURE
BATTERY LOW
12. INTERNAL MONITOR BATTERY
ALARM SILENCE
OK (YELLOW LED)
INPUT TRANSFORMER
INTERNAL MONITOR
BATTERY OK
INPUT CONFIGURATION
OPTIONS: VARIOUS INPUT CONFIGURATIONS ARE AVAILABLE FOR THE
UPS REMOTE MONITOR. PLEASE CONSULT THE FACTORY ABOUT YOUR
PARTICULAR APPKICATION.
6' CORD
FEMALE MIC PLUG
(SEE OPTIONS)
OVERLOAD
UPS FAULT
INPUT
BYPASS
7. UPS FAULT (RED LED)
8. OVERLOAD (RED LED)
6. AC INPUT ON (GREEN LED)
1. RECTIFIER ON (GREEN LED)
9. INPUT FAILURE (RED LED)
11. ALARM SILENCE (RED LED)
10. BATTERY LOW VOLTAGE (RED LED)
10/13/04 4 93120-MAN07
4. OUTPUT TO CRITICAL LOAD (GREEN LED)
5. LOAD ON BYPASS (YELLOW LED)
3. INVERTER ON (GREEN LED)
AUDIBLE ALARM
2. BATTERIES ON (YELLOW LED)
MONITOR RESET PUSHBUTTON
MONITOR TEST PUSHBUTTON
ALARM SILENCE PUSHBUTTON
INTERNAL MONITOR BATTERY TEST PUSHBUTTON
OUTPUT
INPUT
BYPASS
MONITOR RESET
UPS FAULT
OVERLOAD
MONITOR TEST
INPUT FAILURE
ALARM SILENCE
INTERNAL MO NITOR
BATTERY TEST
FIGURE 1.1
VOLTAGE
ALARM SILENCE
BATTERY LOW
INTERNAL MONITOR
BATTERY OK
(INTERNAL POWER SUPPLY / HARDWIRE OPTION)
OK (YELLOW LED)
7. UPS FAULT (RED LED)
8. OVERLOAD (RED LED)
6. AC INPUT ON (GREEN LED)
1. RECTIFIER ON (GREEN LED)
9. INPUT FAILURE (RED LED)
11. ALARM SILENCE (RED LED)
12. INTERNAL MONITOR BATTERY
10. BATTERY LOW VOLTAGE (RED LED)
10/13/04 5 93120-MAN07
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.