(Read these precautions before using this product.)
Before using this product, please read this manual and the relevant manuals carefully and pay full
attention to safety to handle the product correctly.
The precautions given in this manual are concerned with this product only. For the safety precautions of
the programmable controller system, refer to the user’s manual for the CPU module used.
In this manual, the safety instructions are classified into two levels: "WARNING" and "CAUTION".
!!
Under some circumstances, failure to observe the precautions given under "CAUTION" may lead to
serious consequences.
Observe the precautions of both levels because they are important for personal and system safety.
Make sure that the end users read this manual and then keep the manual in a safe place for future
reference.
!
[DESIGN PRECAUTIONS]
!
WARNING
When a communication error occurs on PROFIBUS-DP, the status of the faulty station is as
follows. Configure an interlock circuit in the sequence program using the communication status
information (input X1) so that the system can operate safely.
Failure to do so may result in an accident due to an incorrect output or malfunction.
(1) The input data from the master station remains unchanged from the data prior to the
communication error.
(2) When the master station becomes faulty, the output status of the QJ71PB93D will be as in
the parameter settings of the master station.
(3) When any QJ71PB93D is down, the output state of other slave stations will be in
accordance with the parameter settings of the master station.
Do not output (turn on) the "Use prohibited" signal as the output signal to an intelligent function
module from the CPU module.
Writing data into the "system area" or outputting a signal for "Use prohibited" may cause system
malfunction in the programmable controller.
A - 1 A - 1
!
CAUTION
Do not install the PROFIBUS cables together with the main circuit lines or power cables.
Keep a distance of 100mm or more between them.
Failure to do so may result in malfunction due to noise.
[INSTALLATION PRECAUTIONS]
!
CAUTION
Use the programmable controller under the environment specified in the user's manual of the
CPU module used.
Failure to do so may result in electric shock, fire, malfunction, or damage to or deterioration of
the product.
To mount the module, while pressing the module mounting lever in the lower part of the module,
fully insert the module fixing projection(s) into the hole(s) in the base unit and press the module
until it snaps into place.
Incorrect mounting may cause malfunctions, a failure, or a drop of the module.
When using the programmable controller in an environment of frequent vibrations, fix the
module with a screw.
Tighten the screws within the range of specified torque.
If the screws are loose, it may cause the module to fallout, short circuits, or malfunction.
If the screws are tightened too much, it may cause damage to the screw and/or the module,
resulting in fallout, short circuits or malfunction.
Shut off the external power supply (all phases) used in the system before mounting or removing
the module.
Failure to do so may result in damage to the product.
Do not directly touch any conductive parts and electronic components of the module.
Doing so can cause malfunction or failure of the module.
[WIRING PRECAUTIONS]
!
WARNING
Shut off the external power supply (all phases) used in the system before wiring the PROFIBUS
cables.
Failure to do so may result in failure or malfunctions of the module.
Be sure to shut off all phases of the external power supply used by the system before wiring
PROFIBUS cables.
Failure to do so may result in failure or malfunctions of the module.
A - 2 A - 2
!
CAUTION
Prevent foreign matter such as dust or wire chips from entering the module. Such foreign matter
can cause a fire, failure, or malfunction.
Place the PROFIBUS cables in a duct or clamp them.
If not, dangling cables may swing or inadvertently be pulled, resulting in damages to the module
or cables or malfunctions due to poor contact.
When disconnecting the PROFIBUS cable from the module, do not pull by holding the cable
section. To disconnect the cable, make sure to hold the connector which is coupled with the
module. Do not attempt to pull the cable to disconnect it from the module. It could damage the
module or the cable, or cause malfunction due to a poor contact of the cable.
A protective film is attached to the top of the module to prevent foreign matter, such as wire
chips, from entering the module during wiring.
Do not remove the film during wiring.
Remove it for heat dissipation before system operation.
[STARTING AND MAINTENANCE PRECAUTIONS]
!
WARNING
Shut off the external power supply (all phases) used in the system before cleaning the module
or retightening the connector screws or module fixing screws.
Failure to do so may result in electric shock or cause the module to fail or malfunction.
Undertightening can cause drop of the screw, short circuit, or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit, or
malfunction.
!
CAUTION
Do not disassemble or modify the modules.
Doing so may cause failure, malfunction, injury, or a fire.
Use any radio communication device such as a cellular phone or PHS (Personal Handy-phone
System) more than 25cm (9.85 inches) away in all directions from the programmable controller.
Failure to do so may cause malfunction.
Shut off the external power supply (all phases) used in the system before mounting or removing
the module.
Failure to do so may cause the module to fail or malfunction.
After the first use of the product, do not mount/remove the module to/from the base unit more
than 50 times (IEC 61131-2 compliant).
Exceeding the limit of 50 times may cause malfunction.
Before handling the module, touch a grounded metal object to discharge the static electricity
from the human body.
Failure to do so may cause the module to fail or malfunction.
A - 3 A - 3
[DISPOSAL PRECAUTIONS]
!
CAUTION
When disposing of this product, treat it as industrial waste.
A - 4 A - 4
CONDITIONS OF USE FOR THE PRODUCT
(1) Mitsubishi programmable controller ("the PRODUCT") shall be used in conditions;
i) where any problem, fault or failure occurring in the PRODUCT, if any, shall not lead to any major or serious accident;
and
ii) where the backup and fail-safe function are systematically or automatically provided outside of the PRODUCT for the
case of any problem, fault or failure occurring in the PRODUCT.
(2) The PRODUCT has been designed and manufactured for the purpose of being used in general industries.
MITSUBISHI SHALL HAVE NO RESPONSIBILITY OR LIABILITY (INCLUDING, BUT NOT LIMITED TO ANY AND ALL
RESPONSIBILITY OR LIABILITY BASED ON CONTRACT, WARRANTY, TORT, PRODUCT LIABILITY) FOR ANY
INJURY OR DEATH TO PERSONS OR LOSS OR DAMAGE TO PROPERTY CAUSED BY the PRODUCT THAT ARE
OPERATED OR USED IN APPLICATION NOT INTENDED OR EXCLUDED BY INSTRUCTIONS, PRECAUTIONS, OR
WARNING CONTAINED IN MITSUBISHI'S USER, INSTRUCTION AND/OR SAFETY MANUALS, TECHNICAL
BULLETINS AND GUIDELINES FOR the PRODUCT.
("Prohibited Application")
Prohibited Applications include, but not limited to, the use of the PRODUCT in;
• Nuclear Power Plants and any other power plants operated by Power companies, and/or any other cases in which the
public could be affected if any problem or fault occurs in the PRODUCT.
• Railway companies or Public service purposes, and/or any other cases in which establishment of a special quality
assurance system is required by the Purchaser or End User.
• Aircraft or Aerospace, Medical applications, Train equipment, transport equipment such as Elevator and Escalator,
Incineration and Fuel devices, Vehicles, Manned transportation, Equipment for Recreation and Amusement, and
Safety devices, handling of Nuclear or Hazardous Materials or Chemicals, Mining and Drilling, and/or other
applications where there is a significant risk of injury to the public or property.
Notwithstanding the above restrictions, Mitsubishi may in its sole discretion, authorize use of the PRODUCT in one or
more of the Prohibited Applications, provided that the usage of the PRODUCT is limited only for the specific
applications agreed to by Mitsubishi and provided further that no special quality assurance or fail-safe, redundant or
other safety features which exceed the general specifications of the PRODUCTs are required. For details, please
contact the Mitsubishi representative in your region.
A - 5 A - 5
REVISIONS
* The manual number is given on the bottom left of the back cover.
Section 3.5 5.2, 3.5.1 to 3.5.3 5.2.1 to 5.2.3, 3.6 3.5, 5.1.1
5.2, 5.2 to 5.5 5.4 to 5.7
Jul., 2007 SH(NA)-080318E-E
Change of a term
"PLC" was changed to "programmable controller".
Correction
About the Generic Terms and Abbreviations, Section 2.1, 2.3, 3.1,
3.4.1, 5.5, 8.2 to 8.3, Appendix 1
Addition
Section 5.3.1, 5.4.1, 7.3.1, 7.3.2, 9.4
Section number change
Chapter 8(3) Section 8.1, Section 8.1 to 8.2 8.2 to 8.3
Nov., 2007 SH(NA)-080318E-F
Correction
Section 3.3.2, 3.4.1, 7.3.1
A - 6 A - 6
* The manual number is given on the bottom left of the back cover.
Print Date * Manual NumberRevision
Jun., 2015 SH(NA)-080318E-G
Correction
SAFETY PRECAUTIONS, COMPLIANCE WITH EMC AND LOW
VOLTAGE DIRECTIVES, ABOUT THE GENERIC TERMS AND
ABBREVIATIONS, MEANINGS AND DEFINITIONS OF THE TERMS,
Section 2.1, 2.4, Chapter 3, Section 4.1.2, 4.1.4, Chapter 5, Section
7.3.1, 7.3.2, 8.1, Chapter 9, Appendix 2
Addition
CONDITIONS OF USE FOR THE PRODUCT, Section 2.2
Section number change
Section 2.2 to 2.3 Section 2.3 to 2.4
Sep., 2018 SH(NA)-080318E-H
Correction
Related Manuals, Section 2.1, 2.4
Japanese Manual Version SH-080317-G
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
nses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
lice
rights which may occur as a result of using the contents noted in this manual.
2002 MITSUBISHI ELECTRIC CORPORATION
A - 7
A - 7
INTRODUCTION
Thank you for purchasing the Mitsubishi Electric Programmable Controller MELSEC-Q Series.
Before using the equipment, please read this manual carefully to develop full familiarity with the functions
and performance of the graphic operation terminal you have purchased, so as to ensure correct use.
Please forward a copy of this manual to the end user.
MANUALS ..................................................................................................................................................... A -11
COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES .............................................................. A -11
ABOUT THE GENERIC TERMS AND ABBREVIATIONS .......................................................................... A -12
MEANINGS AND DEFINITIONS OF THE TERMS ..................................................................................... A -13
PRODUCT CONFIGURATION .................................................................................................................... A -14
1 OVERVIEW 1- 1 to 1- 3
1 5 6 8 8
1.1 QJ71PB93D Features ............................................................................................................................. 1 -2
2 SYSTEM CONFIGURATION 2- 1 to 2- 7
2.1 Applicable Systems .................................................................................................................................. 2-1
2.2 When Used in a Redundant System ....................................................................................................... 2-
2.3 Precautions for Configuring a System ..................................................................................................... 2-
2.4 Checking Serial No. and Function Version ............................................................................................. 2-
3.3 I/O Signal .................................................................................................................................................. 3-3
3.3.1 I/O signal list ...................................................................................................................................... 3-
3.3.2 I/O signal detail description .............................................................................................................. 3-
3 4
3.4 Buffer Memory List ................................................................................................................................. 3-14
4.1 Functions for Communication with Class 1 Master ................................................................................ 4-1
4.1.1 I/O data communication function ...................................................................................................... 4-
1
4.1.2 I/O data separation prevention function ........................................................................................... 4-4
4.1.3 Global control function ...................................................................................................................... 4-
7
4.1.4 Word data swapping function .......................................................................................................... 4-10
A - 8 A - 8
5 SETTINGS AND PROCEDURES BEFORE SYSTEM OPERATION 5- 1 to 5-25
5.1 Procedures before Operation .................................................................................................................. 5-1
5.2 Parameter Setting to Master Station ....................................................................................................... 5-
5.2.1 Data module setting .......................................................................................................................... 5-
5.2.2 Data assignment mode setting ......................................................................................................... 5-
5.5 Part Names ............................................................................................................................................. 5-19
5.6 Execution Method for Self-diagnosis ...................................................................................................... 5-20
6.1 Transmission Delay Time of Output Receive (Master station QJ71PB93D) ..................................... 6-4
6.2 Transmission Delay Time of Input Send (QJ71PB93D Master station) ............................................ 6-
5
7 PROGRAMMING 7- 1 to 7-22
7.1 Communication Sequence ..................................................................................................................... 7 -1
7.2 Station Number Setting ........................................................................................................................... 7 -
7.3 Communication of I/O Data .................................................................................................................... 7 -
The following are manuals related to this product.
Request for the manuals as needed according to the chart below.
Related Manuals
Manual Name Manual Number
PROFIBUS-DP Master Module User's Manual
Describes the overview, system configuration, specifications, functions, procedures before system
operation, programming and dedicated instructions of the QJ71PB92V.
(Sold separately)
PROFIBUS-DP Interface Module User's Manual
Describes the overview, system configuration, specifications, functions, procedures before system
operation, programming and dedicated instructions of the QJ71PB92D.
(Sold separately)
SH-080572ENG
(13JR84)
SH-080127
(13JR22)
GX Configurator-DP Version7 Operating Manual
Explains the overview, installation method, screen operations, etc. of GX Configurator-DP Version 7.
(Sold separately)
COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES
(1) Method of ensuring compliance
To ensure that Mitsubishi Electric programmable controllers maintain EMC and
Low Voltage Directives when incorporated into other machinery or equipment,
certain measures may be necessary. Please refer to one of the following
manuals.
• QCPU User's Manual (Hardware Design, Maintenance and Inspection)
• Safety Guidelines
(This manual is included with the CPU module or base unit.)
The CE mark on the side of the programmable controller indicates compliance
with EMC and Low Voltage Directives.
(2) Additional measures
No additional measures are necessary for the compliance of this product with
EMC and Low Voltage Directives.
SH-080579ENG
(13JU54)
A - 11 A - 11
ABOUT THE GENERIC TERMS AND ABBREVIATIONS
Unless otherwise specified, this manual uses the following generic terms and
abbreviations to describe the Type QJ71PB93D PROFIBUS-DP slave module.
Generic Term/Abbreviation Description of the abbreviation/general terms
QJ71PB93D Abbreviation for the model QJ71PB93D PROFIBUS-DP slave module.
QJ71PB92V Abbreviation for the model QJ71PB92V PROFIBUS-DP master module.
Generic term for the Q00JCPU, Q00CPU, Q00UJCPU, Q00UCPU, Q01CPU,
Q01UCPU, Q02CPU, Q02HCPU, Q02PHCPU, Q02UCPU, Q03UDCPU, 03UDVCPU,
Q03UDECPU, Q04UDHCPU, Q04UDVCPU, Q04UDEHCPU, Q06HCPU,
CPU module
GX Works2 The product name of the software package for the MELSEC programmable controllers
GX Configurator-DP
PROFIBUS-DP Abbreviation of PROFIBUS-DP network.
BBLKRD Abbreviation for G.BBLKRD.
BBLKWR Abbreviation for G.BBLKWR.
The configurator for the QJ71PB93D
Generic term for the product name SWnD5C-PROFID-E ("n" means version 7 or
later.)
A - 12 A - 12
MEANINGS AND DEFINITIONS OF THE TERMS
The terms used in this manual have the following meanings and definitions.
Term Definition
A basic version of PROFIBUS-DP.
The following functions are executable:
PROFIBUS-DPV0
PROFIBUS-DPV1
PROFIBUS-DPV2
Class 1 master station A device exchanging I/O data with a slave stations. (QJ71PB92V, QJ71PB92D, etc.)
Class 2 master station
Slave station
Repeater A device used to connect different segments of PROFIBUS-DP.
Bus terminator
Configuration tool
GSD file
Station number
Slave parameter
I/O configuration information
(Data module)
Input data
Output data
Global control
Communication watchdog
timer
Extended diagnostic error
information
Bus cycle time
Module watchdog timer Watchdog timer in the QJ71PB93D.
I/O data exchange
Diagnostic information notification
etc.
A PROFIBUS-DP version for which the following functions have been added to the
basic functionality of PROFIBUS-DPV0.
Acyclic communication
Alarm function
etc.
A PROFIBUS-DP version for which the following functions have been added to the
PROFIBUS-DPV1 functionality.
Time stamping
etc.
A device that communicates with slave stations and checks their station number
settings and/or operation states.
The Class 2 master station is used as a master station for supervising the network,
which can start, maintain, and diagnose the system.
A device that exchanges I/O data with a Class 1 master station. (QJ71PB93D,
ST1H-PB, etc.)
A terminating resistor that is connected to either end of each segment on
PROFIBUS-DP.
Software used to set slave parameters, etc. and to write them to a master station.
(GX Configurator-DP, etc.)
An electronic file that contains parameters of a slave station.
The GSD file is used to set up the slave parameters on configuration tool.
The numbers assigned to a master station and slave stations.
The station number is set within the range from 0 to 125.
The parameter for a slave station, which is set on the master station.
The setting items are described on the GSD File.
Information on I/O configuration of a slave station.
Data sent by the QJ71PB93D and received by the master station. (data input by the
master station.)
Data sent by the master station and received by the QJ71PB93D. (data output by the
master station.)
This function enables synchronization command transmission for I/O data from a
Class 1 master station to slave stations.
Watchdog timer set in the slave parameter of the master station.
Diagnostic information specific to each slave station.
Each of slave stations notifies of it to the master station when an error is detected.
PROFIBUS-DP processing time for the master station to perform cyclic transfer with
each slave station.
A - 13 A - 13
PRODUCT CONFIGURATION
The product configuration of this product is given in the table below.
QJ71PB93D QJ71PB93D PROFIBUS-DP slave module. 1
Model Product name Quantity
A - 14 A - 14
r
1 OVERVIEW
MELSEC-Q
1 OVERVIEW
Class 1 master station
(QJ71PB92V)
Bus terminator
This is the user's manual for the QJ71PB93D PROFIBUS-DP slave module (hereafter
abbreviated as "QJ71PB93D"), which is used to connect a MELSEC-Q series
programmable controller to a PROFIBUS-DP network.
The QJ71PB93D operates as a slave station in the PROFIBUS-DP network.
Slave station (QJ71PB93D)Slave station (MELSEC-ST system)Slave station
The module conforms with EN50170 Volume 2 (Part 1, 2, 3, 4, 8) and can
communicate with the master station as a PROFIBUS-DP slave station.
(2) I/O data communication with class 1 master station
The module can communicate I/O data with the class 1 master station (master
station that makes data communication cyclically with a slave station) of
PROFIBUS-DP.
The QJ71PB93D supports the PROFIBUS-DPV0 function.
PROFIBUS-DPV1 and PROFIBUS-DPV2, which are extended versions of
PROFIBUS-DP, are not supported.
(a) Available data size
The QJ71PB93D can handle the following size of data. (Refer to Section
4.1.1)
Input data : Max. 122 words
Output data : Max. 122 words
Max. 192 words in total
Class 1 master station
Output
image
Input
image
Bus terminatorBus terminator
PROFIBUS-DP network
Buffer memory
Read 1
Write 2
CPU moduleQJ71PB93D (slave station)
Output
receive
area
Input
send
area
(3) Communication can be made by merely setting the master station
Output
image
Input
image
1: Reads with BBLKRD/MOV/FROM instruction
or automatic refresh
2: Writes with BBLKWR/MOV/TO instruction or
automatic refresh
parameters
After you have set the parameters at the master station, the QJ71PB93D can
make communication by merely setting the station number. (Refer to Section 5.1)
1 - 2 1 - 2
1 OVERVIEW
MELSEC-Q
(4) Swapping of I/O data
When I/O data is sent/received from/to the master station, their upper and lower
bytes can be swapped.
Though PROFIBUS-DP handles the upper and lower bytes of I/O data differently
depending on the master station type, the I/O data need not be swapped in a
sequence program. (Refer to Section 4.1.4)
(5) Start/stop of refreshing the input send area
Refreshing of send data from the QJ71PB93D to the master station is
controllable by an output signal (Y00).
Providing an interlock disables the buffer memory data from being sent to the
master station at error occurrence. (Refer to Section 4.1.1)
(6) Extended trouble notification function
Data stored in the extended trouble information area of the buffer memory can be
sent to the master station as extended trouble information
faulty, for example.
When the host is not faulty anymore, notify the master station that there is no
fault. (Refer to Section 3.4.2(9))
: Diagnostics Information (device-related trouble information set by the user as
desired)
when the host is
(7) Compatibility with global control function
Compatibility with the global control function allows the updating of I/O data at the
QJ71PB93D to be controlled from the class 1 master station using the command
(SYNC, UNSYNC, FREEZE, UNFREEZE) sent by the class 1 master. (Refer to
Section 4.1.3)
(8) Communication with class 2 master station
The following communications can be made with the class 2 master station
(master station designed for network management to perform booting,
maintenance and diagnostics) of PROFIBUS-DP.
Read from input send area/output receive area
Read of I/O configuration information
Station number change
For the way to use each function, refer to the manual of the class 2 master
station used.
(9) I/O data separation prevention
For data transmission between the CPU module and buffer memory of
QJ71PB93D, automatic refresh or dedicated instruction are used to prevent I/O
data from being separated
: The data of specified sizes are not matched with each other.
. (Refer to Section 4.1.2)
(10) Compatibility with multiple CPU system
Even when a plurality of CPU modules are installed through the multiple CPU
system, this model can be controlled by any CPU module.
1 - 3 1 - 3
2 SYSTEM CONFIGURATION
2 SYSTEM CONFIGURATION
2.1 Applicable Systems
MELSEC-Q
2
This section describes applicable systems.
(1) Mountable modules, No. of mountable modules, and mountable
base unit
(a) When mounting with a CPU module
REMARKS
When using the module with a C Controller module, refer to the user's manual for
the C Controller module.
For the CPU modules, the number of modules, and base units mountable
to the QJ71PB93D, refer to user's manual for the CPU module used.
• User's Manual for the CPU module used (Hardware Design, Maintenance
and Inspection)
2 - 1 2 - 1
2 SYSTEM CONFIGURATION
POINT
(1) There are restrictions on the number of automatic refresh parameters that can
be set for CPU modules.
For details, refer to Section 5.3.1(5).
(2) To utilize the data consistency function and dedicated instruction, use a CPU
module whose first 5 digits of the serial No. is "02092" or later.
If this function is used in any other models, I/O data may be identified as invalid
values.
(b) When mounting to remote I/O station of MELSECNET/H
The QJ71PB93D cannot be mounted to remote I/O station of the
MELSECNET/H.
Mount it next to the CPU module on the MELSECNET/H remote master
station.
(2) Compatibility with a multiple CPU system
When using the QJ71PB93D in a multiple CPU system, refer to the User's
Manual (Multiple CPU System) for CPU module used.
(a) Compatible QJ71PB93D
The function version of the QJ71PB93D has been "B" from the first release
and it supports the multiple CPU system.
(3) Compatibility with online module change
The QJ71PB93D cannot be changed online.
(4) Applicable software packages
Please configure the system by combining QJ71PB93D and software package
as follows:
GX Works2: For setting CPU module parameters and creating sequence
programs (Required)
GX Configurator-DP : For setting the QJ71PB93D station number and automatic
refresh parameter
1 GX Configurator-DP is required when using automatic refresh.
The station number can also be set on a sequence program. (Refer to Section 5.3)
MELSEC-Q
2
1
2 - 2 2 - 2
2 SYSTEM CONFIGURATION
MELSEC-Q
System
Q00J/Q00/Q01CPU
Q02/Q02H/Q06H/Q12H/
Q25HCPU
Q02PH/Q06PHCPU
Q12PH/Q25PHCPU
Q12PRH/Q25PRHCPU Redundant system Version 7.00A or later*3
Q00UJCPU Single CPU system
Q00U/Q01UCPU
Q02UCPU
Q03UD/Q04UDH/
Q06UDHCPU
Q10UDH/Q20UDHCPU
Q13UDH/Q26UDHCPU
Q03UDV/Q04UDV/
Q06UDV/Q13UDV/
Q26UDVCPU
Q03UDE/Q04UDEH/
Q06UDEH/Q13UDEH/
Q26UDEHCPU
Q10UDEH/Q20UDEHCPU
Q50UDEH/Q100UDEHCPU
Single CPU system
Multiple CPU system Version 1.14Q or later
Single CPU system Version 1.11M or later
Multiple CPU system Version 1.14Q or later
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU system Version 1.14Q or later
Single CPU system
Multiple CPU system Version 1.14Q or later
Single CPU system
Multiple CPU system Version 1.14Q or later
Single CPU system
Multiple CPU system Version 1.14Q or later
Single CPU system
Multiple CPU system Version 1.14Q or later
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU system Version 1.14Q or later
Single CPU system
Multiple CPU system Version 1.14Q or later
Single CPU system
Multiple CPU system
GX Configurator-DP1 GX Works22
Version 7.00A or later
Version 7.04E or later
Version 7.00A or later
Version 7.04E or later
Version 7.03D or later
Version 7.02C or later
Version 7.04E or later
Version 7.03D or later
Version 7.09K or later Version 1.95Z or later
Version 7.03D or later
Version 7.04E or later
Version 7.07H or later Version 1.25B or later
1 The operation mode of the QJ71PB93D cannot be changed using
GX Configurator-DP Version 7.03D or later.
Change the mode using operation mode change request area
(buffer memory address: 8CFH).
2 For how to use GX Configurator-DP and GX Works2 together,
refer to the GX Configurator-DP Operating Manual.
3 To mount the QJ71PB93D on an extension base unit, use GX
Configurator-DP Version 7.03D or later.
Software Version
Version 1.11M or later
Version 1.86Q or later
Version 1.11M or later
Version 1.11M or later
Version 1.11M or later
Version 1.11M or later
Version 1.11M or later
Version 1.11M or later
Version 1.11M or later
2 - 3 2 - 3
2 SYSTEM CONFIGURATION
2.2 When Used in a Redundant System
For the precautions on when using an extension base unit, refer to the User's Manual
(Redundant System) for the CPU module used.
2.3 Precautions for Configuring a System
(1) Precaution for station number setting
(a) If a station number different from the one of the currently operating station is
set during I/O data communication, the communication is suspended to
execute the setting.
It is restarted after completion of the station number setting.
(b) Do not change the operation mode during execution of the station number
setting.
Doing so may disable proper station number setting or mode change.
(2) Precaution for parameter writing
(a) If a parameter based on a station number setting different from the one of the
currently operating station is written to the QJ71PB93D that is exchanging I/O
data, the I/O data communication is suspended. It is restarted after
completion of parameter writing.
(b) Do not change the operation mode from the sequence program during
parameter writing.
Doing so may disable proper station number setting or mode change.
(c) Do not write parameters from multiple GX Configurator-DPs to a single
QJ71PB93D at the same time.
Doing so makes the parameter values of the QJ71PB93D incorrect.
(3) When switching the operation mode using Y11/X11 on the
sequence program
Be sure to switch the mode while the module READY signal (X1D) of the
QJ71PB93D is ON.
If data are read from or written to the buffer memory with the X1D status ignored,
the CPU module may detect an error to stop the sequence calculation.
MELSEC-Q
2 - 4 2 - 4
2 SYSTEM CONFIGURATION
2.4 Checking Serial No. and Function Version
The serial No. and function version of the QJ71PB93D can be checked on the rating
plate, on the front of the module, and on the System monitor of GX Works2.
(1) Checking on the rating plate
The rating plate is located on the side of the QJ71PB93D.
MELSEC-Q
(2) Checking on the front of the module
The serial No. and function version on the rating plate are printed on the front (at
the bottom) of the module.
2 - 5 2 - 5
2 SYSTEM CONFIGURATION
(3) Checking on the System monitor window (Product information list
window)
To display the System monitor, select [Diagnosis] [System monitor]
[Product information list] button of GX Works2.
MELSEC-Q
Product No.
"-" is displayed as QJ71PB93D does not support the product number
display.
POINT
The serial No. displayed on the Product Information List window of GX Works2 may
differ from that on the rating plate or on the front of the module.
The serial No. on the rated plate or on the front of the module indicates the
management information of the product.
The serial No. displayed on the Product Information List window of GX Works2
indicates the functional information of the product. The functional information of
the product will be updated when a function is added.
2 - 6 2 - 6
2 SYSTEM CONFIGURATION
MEMO
MELSEC-Q
2 - 7 2 - 7
3 SPECIFICATIONS
MELSEC-Q
3 SPECIFICATIONS
This chapter describes the performance specifications, network configuration, I/O
signals, buffer memory, and operation modes of the QJ71PB93D.
For the general specifications of the QJ71PB93D, refer to the User's Manual
3.1 Performance Specifications
Item Specifications
PROFIBUS-DP station type Slave station (Complies with EN50170 Volume2 (Part 1, 2, 3, 4, 8))
Station numbers that may be set 0 to 125 2
Max. number of data that may be
communicated
Electrical standard/characteristics Complies with EIA-RS485
Medium Shielded twisted pair cable (Type A) (Refer to Section 5.7.1)
Network topology Bus topology (Tree topology when repeaters are used)
Data link method Polling method
Encoding method NRZ
Transmission speed 1 9.6 kbps to 12 Mbps (Refer to (1) in this section)
Transmission distance Differs depending on the transmission speed (Refer to (1) in this section)
Maximum number of repeaters
Transmission specifications
Number of connectable modules
(Per segment)
Flash ROM write count Max. 10000 times
Number of occupied I/O points 32 points (I/O assignment : 32 intelligent points)
1 Transmission speed control within +/- 0.3% (EN50170 Volume 2 compliant)
2 Factory-set to "126" (EN50170 Volume 2 compliant)
Set a station number within 0 to 125 for I/O data communication.
3 - 1 3 - 1
(Hardware Design, Maintenance and Inspection) for the CPU module used.
Number of I/O data is 192 words in total. (Size of I/O data is up to 122 words.)
3 units (Refer to
32 units (including repeaters)
(1) in this section)
For the noise immunity, withstand voltage, insulation resistance, and others in the
programmable controller system using this module, refer to the power supply module
specifications given in the User's Manual (Hardware Design, Maintenance and
Inspection) for the CPU module used.
(1) Transmission distance
Transmission Speed Transmission Distance
9.6 kbps
19.2 kbps
93.75 kbps
187.5 kbps 1000 m (3281 ft.)/segment 4000 m (13123 ft.)/network
500 kbps 400 m (1312 ft.)/segment 1600 m (5249 ft.)/network
1.5 Mbps 200 m (656 ft.)/segment 800 m (2625 ft.)/network
3 Mbps
6 Mbps
12 Mbps
3 The max. transmission distance in the table above is based on the case where 3 repeaters are used.
The calculation formula for the transmission distance extended using a repeater(s) is:
Max. transmission distance [m/network] = (Number of repeaters + 1) x Transmission distance [m/segment]
1200 m (3937 ft.)/segment 4800 m (15748 ft.)/network
100 m (328 ft.)/segment 400 m (1312 ft.)/network
Max. Transmission Distance when
Repeater is Used
3
3
r
r
3 SPECIFICATIONS
3.2 Network Configuration
MELSEC-Q
3
This section explains the basic PROFIBUS-DP configuration for using the QJ71PB93D
as a slave station.
(1) System equipment
The following table shows the equipment required for the PROFIBUS-DP system.
System Equipment Description
Slave station QJ71PB93D
Class 1 master station QJ71PB92V, QJ71PB92D, etc.
Configuration tool Configurator applicable to the master station
Repeater Required when 32 or more slave stations are connected
PROFIBUS cable
Bus terminator
Refer to section 5.7.1
(2) Network configuration
In the PROFIBUS-DP system configuration, the following conditions must be
satisfied:
(a) Number of connectable modules in the whole network (when repeaters are
used)
Master station + Slave station
1: Including the QJ71PB93D
(b) Number of connectable modules per segment
Master station + Slave station
1: Including the QJ71PB93D
2: A repeater is counted for both segments.
(c) Maximum number of repeaters
Up to 3 repeaters can be used for communication between master station
and the QJ71PB93D.
(d) Number of slave stations that are connectable to master station
The maximum number of slave stations that may be connected to one
master station depends on the specifications of the master station.
Master station
Bus terminator
1 126
1 + repeaters 2 32
Class 1
Bus terminato
QJ71
CPU
module
PB93D
Slave
Station No. 1
Slave
Station No. 2
Slave
Station No. 30
Bus terminator
QJ71
CPU
PB93D
module
Slave
Station No. 31
Slave
Station No. 32
Slave
Station No. 60
3 - 2 3 - 2
Repeater
Bus terminato
3 SPECIFICATIONS
MELSEC-Q
3.3 I/O Signal
3.3.1 I/O signal list
The I/O signal configuration used in the QJ71PB93D and the data communications
with the CPU module are described below.
The following I/O signal assignment is based on the case where the start I/O No. of the
QJ71PB93D is "0000" (installed to slot 0 of the main base unit).
Device X represents an input signal from the QJ71PB93D to the CPU module.
Device Y shows an output signal from the CPU module to the QJ71PB93D.
Refer to the corresponding reference sections for details.
Signal direction: QJ71PB93D CPU module Signal direction: CPU module
Device No. Description Device No.Description
X00 Watchdog timer error Y00 Input send area refresh directive signal
X01 I/O communication signal Y01 Use prohibited
X02 Extension trouble notification completion signal Y02 Extension trouble notification request signal
X03 Module error signal Y03 Module error reset request signal
X11 Operation mode change completion signal Y11 Operation mode change request signal
X12 Use prohibited Y12 Use prohibited
X13 Station number change completion signal Y13 Station number change request signal
X14
X15 Y15
X16 Y16
X17 Y17
X18 Y18
X19 Y19
X1A Y1A
X1B Y1B
X1C Y1C
X1D Module READY signal Y1D
X1E
X1F Y1F
Use prohibited
Use prohibited
Use prohibited
Use prohibited
Y08
Y0C
Y14
Y1E
Use prohibited
Use prohibited
Use prohibited
POINT
Do not output (turn on) the "Use prohibited" signals.
Doing so may cause the programmable controller system malfunction.
QJ71PB93D
3 - 3 3 - 3
3 SPECIFICATIONS
3.3.2 I/O signal detail description
(1) Watchdog timer error (X00)
(a) This signal turns on when a watchdog timer error occurs on the
QJ71PB93D.
(b) The watchdog timer error (X00) does not turn off until the following
operation is performed.
Turning the programmable controller power off to on
Resetting the CPU module
If the signal turns on again, a hardware error may be the cause.
(2) I/O communication signal (X01)
(a) This signal turns on when the module is ready to communicate with the
Communication with
master station
master station properly.
(b) While the I/O communication signal (X01) is on, the output receive area is
updated to the output data sent from the master station.
(It is independent of the status of the input send area refresh directive
signal (Y00).)
(c) The I/O communication signal (X01) turns off when a communication time-
out error occurs due to a stop of communication with the master station.
However, if the communication watchdog timer setting in the master station
side parameters is "invalid", the I/O communication signal does not turn off
since a communication time-out error does not occur.
(The output data in the output receive area is held.)
Communication watchdog timer Setting
in Master Station Side Parameters
Invalid
Valid (2 to 65025)
The communication watchdog timer setting can be confirmed in the
"Current communication watchdog timer value (buffer memory address:
8D1
(d) Use this signal as a signal for interlocking output receive area read
performed with the MOV/FROM instruction.
H)" of the QJ71PB93D.
MELSEC-Q
Operation at Master Station Fault
No error
(I/O communication signal (X01) remains on)
Communication time-out error occurrence
(I/O communication signal (X01) turns off)
Communication in progressCommunication stop
Communication stop
I/O communication signal (X01)ONOFFOFF
Data update in output
receive area
Output receive area
(Buffer memory address :
to BFH)
0
H
Not updatedUpdatedNot updated
MOV/FROM instruction
Execution of read from
output receive area
3 - 4 3 - 4
Loading...
+ 100 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.