D/A Converter Module
Thank you for buying the Mitsubishi general-purpose programmable logic controller MELSEC Q Series.
Prior to use, please read both this manual and detailed manual thoroughly and familiarize yourself with the product.
User's Manual
(Hardware)
MODEL Number
©2000 MITSUBISHI ELECTRIC CORPORATION
SAFETY PRECAUTIONS
(Read these precautions before using.)
When using Mitsubishi equipment, thoroughly read this manual and the associated manuals introduced in the manual. Also pay careful attention to safety and handle the module properly. These precautions apply only to Mitsubishi equipment. Refer to the user’s manual of the CPU module to use for a description of the PLC system safety precautions. These SAFETY PRECAUTIONS classify the safety precautions into two categories: "DANGER" and "CAUTION".
DANGER
CAUTION
Depending on circumstances, procedures indicated by CAUTION may also be linked to serious results. In any case, it is important to follow the directions for usage. Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward it to the end user.
[DESIGN PRECAUTIONS]
Do not bunch the control wires or communication cables with the main circuit or power wires, or install them close to each other. They should be installed 100 mm (3.94 inch) or more from each other. Not doing so could result in noise that may cause malfunction.
At power ON/OFF, voltage or current may instantaneously be output from the output terminal of this module. In such case, wait until the analog output becomes stable to start controlling the external device.
[INSTALLATION PRECAUTIONS]
Use the PLC in an environment that meets the general specifications given in the User's Manual of the CPU module being used. Using this PLC in an environment outside the range of the general specifications may cause electric shock, fire, malfunction, and damage to or deterioration of the product.
W hile pressing the installation lever located at the bottom of module, insert the module fixing tab into the fixing hole in the base unit until it stops. Improper installation may result in malfunction , breakdown or the module coming loose and dropping. Securely fix the module with screws if it is subject to vibration during use.
Tighten the screws within the range of specified torque. If the screws are loose, it may cause the module to fallout, short circuits, or malfunction. If the screws are tightened too much, it may cause damage to the screw and/or the module, resulting in fallout, short circuits or malfunction.
Be sure to shut off all phases of the external power supply used by the system before mounting or removing the module. Not doing so may cause damage to the module.
Do not directly touch the conductive area or electronic components of the module. Doing so may cause malfunction or failure in the module.
[WIRING PRECAUTIONS]
Always ground the FG terminal for the PLC. There is a risk of electric shock or malfunction.
When turning on the power and operating the module after wiring is completed, always attach the terminal cover that comes with the product. There is a risk of electric shock if the terminal cover is not attached.
Tighten the terminal screws within the range of specified torque. If the terminal screws are loose, it may result in short circuits or malfunction. If the terminal screws are tightened too much, it may cause damage to the screw and/or the module, resulting in short circuits or malfunction.
Be careful not to let foreign matters such as sawdust or wire chips get inside the module. These may cause fires, failure or malfunction.
The top surface of the module is covered with protective film to prevent foreign objects such as cable offcuts from entering the module when wiring. Do not remove this film until the wiring is complete. Before operating the system, be sure to remove the film to provide adequate heat ventilation.
About This Manual
The following manuals are also related to this product. Order them if necessary.
Related Manual
Procedures which may lead to a dangerous condition and cause death or serious injury if not carried out properly.
Procedures which may lead to a dangerous condition and cause superficial to medium injury, or physical damage only, if not carried out properly.
CAUTION
CAUTION
CAUTION
Manual Name Manual No. (Model code)
D/A Converter Module User's Manual
13JT24
IB-0800151-B (0509) MEE
SH-080054
(13JR02)
Conformance to the EMC Directive/Low Voltage Directive
When incorporating the Mitsubishi PLC into other machinery or equipment and keeping compliance with the EMC and low voltage directives, refer to Chapter 3, "EMC Directives and Low Voltage Directives" of the User's Manual (Hardware) included with the CPU module or base unit used. The CE logo is printed on the rating plate on the main body of the PLC that conforms to the EMC directive and low voltage instruction. By making this product conform to the EMC directive and low voltage instruction, it is not necessary to make those steps individually.
1. Overview
This manual explains specifications and the names of the components for the Q68DAV type D/A converter module (hereafter Q68DAV) and the Q68DAI type D/A converter module (hereafter Q68DAI) which are used in combination with the MELSEC-Q Series CPU module. In this manual, both the Q68DAV and Q68DAI are referred to as D/A converter modules. After unpacking, confirm that the following products are enclosed.
Q68DAV/Q68DAI Model Digital-Analog module 1 FG terminal L-shaped metal fitting 1
Part name Qty.
2. Specifications
The specifications for the D/A converter module are shown in the following table. For general specifications, refer to the operation manual for the CPU module being used.
Digital input value Maximu m resolution Digital input value Maximu m resolution Ambient
erature
tem 25 ± 5 °C Ambient
erature
tem 0 to 55 °C
Type
0 to 5
1.25 m
0.416mV0.333mV0.625 m
Type
Between output channels : Not insulated Between external supply power and analog output : Not insulated
Inrush current : 3.3A, within 70μs Inrush current : 3.1A, within 75μs
Item
Number of analog outputs 8 points (8 channels) Digital input 16-bit signed binary (normal resolution
Analog output – 10 to 10V DC (External load
maximum resolutio n
Normal resolution mode
High resolution mode
Accuracy
(Accuracy in respect to maximu m analog output value)
Conversion speed 80 μ s/ channel
Item
Absolute ma ximum output ± 12 V 21 mA Output short circuit protection Availab le Insulatio n method Between I/O terminal and PLC power supply : Photocoupler insulation
Number of occupied points 16 points Connecting terminals 18 points terminal block Applicable wire size 0.3 to 0.75 mm Applicable solderless terminals Other terminals than FG:R1.25 - 3
External supply power 24 V DC + 20 %, – 15 %
Internal current consumption (5 V DC) Weight 0.18 kg
Q68DAV Q68DAI
mode: –4096 to 4095,
high resolution mode:–12288 to
12287, –16384 to 16383)
resistance 1 k Ω to 1 M Ω)
Analog output range Analog output rangeI/O characteristics
1 to 5 V– 10 to
10 V
0 to 4000 – 4000 to 4000 0 to 4000 – 4000 to
1.0 mV2.5mV 0.75mV5 μ A4 μ A 1.5 μ A
0 to 12000 – 16000
– 12000
to 16000
to 12000
0.333 mV1.66 μ A 1.33 μ A 0.83
16-bit signed binary (normal
resolution mode: –4096 to 4095,
high resolution mode:–12288 to
0 to 20 mA DC (External load
resistance 0 Ω to 600 Ω)
Users
0 to 20 mA4 to 20 mAUsers
range
setting
0 to 12000 – 12000
12287)
range
setting
4000
to 12000
Within ± 0.1 % (Voltage : ± 10mV, Current : ± 20μA)
Within ± 0.3 % (Voltage : ± 30mV, Current : ± 60μA)
Q68DAV Q68DAI
2
(A solderless terminals with sleeves cannot be used)
FG terminal:R1.25-3, 1.25-YS3, RAV1.25-3, V1.25-YS3A
Ripple, spike within 500 mVP -P
0.19 A 0.28 A
0.39 A 0.38 A
3. Part Names
This section explains the names of the components for the D/A converter module.
Q68DA
IN 24VDC
RUN
ERROR
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
FG
1)
2)
3)
4)
Terminal Signal name
number
1V+I+
2
3V+I+
4
5V+I+
6
7V+I+
8
9V+I+
10
11 V+ I+
12
13 V+ I+
14
15 V+ I+
16
17 24 V
18 24 G
Q68DAV Q68DAI
CH.1
CH.2
CH.3
CH.4
CH.5
CH.6
CH.7
CH.8
COM
COM
COM
COM
COM
COM
COM
COM
CH.1
CH.2
CH.3
CH.4
CH.5
CH.6
CH.7
CH.8
COM
COM
COM
COM
COM
COM
COM
COM
Numbe
1) RUN LED Displays the operating status of the D/A converter module.
2) ERROR LED Displays the error status of the D/A converter module.
3) External power supply
4) FG terminal Terminal for frame ground
Name Description
On : Normal operation Flashing : During offset/gain setting mode Off : 5V power supply interrupted or watch dog timer error
On : Error Off : Normal operation Flashing : Error in switch settings
Switch No. 5 of th e intelli
set to a value other than "0".
terminal
This is the terminal for connecting the 24 V DC external power supply.
ent function module has been
4. Handling Precautions
(1) Do not drop the module or cause it to receive strong impact. (2) Tighten the terminal screws for the module to the specified torque shown below.
Insufficient tightening torque could result in shorts, failures or malfunction.
Module mounting screw (M3 screw) 0.36 to 0.48 N · m Terminal block terminal screw (M3 screw) 0.42 to 0.58 N · m Terminal block mounting screw (M3.5 screw) 0.66 to 0.89 N · m FG terminal screw (M3 screw) 0.42 to 0.58 N · m
Screw location Tightening torque
5. Wiring
5.1 Wiring precautions
(1) Use separate cables for the external output signal or external power supply
for the AC and D/A converter modules. Take steps to prevent the AC side from being affected by surge or inductance.
(2) Ground one point of the shield for shielded wires or shielded cables.
Point
If it is difficult to wire FG terminals due to the limited installation space, use FG terminal L-shaped metal fitting.
5.2 External wiring
(1) Q68DAV
D/A
conversion
A.G
+15 V
–15 V
DC/DC
converter
+24 V
Filter
A.G
(2) Q68DAI
D/A
conversion
A.G
+15V
–15V
DC/DC
converter
+24V
Filter
A.G
*1 Use a twisted two core shielded wire for the power wire. *2 If there is noise or ripples in the external wiring, connect a 0.1 to 0.47 m F25V
condenser between the V+/I+ terminal and COM.
5.3 Switch setting for intelligent functional module
The settings for the intelligent function module are performed using the I/O allocation settings for the GX Developer. It can be easy to set by inputting using hexadecimal-4 digits.
Switch 1
Switch 2
Switch 3 *2
Switch 4
Switch 5
Output range setting
(CH.1 to CH.4)
CH4 CH3 CH2 CH1
Output range setting
(CH.5 to CH.8)
CH8 CH7 CH6 CH5
b15
to
00
H
H
b8 b7 b6 b5 b4 b3 b2 b1 b0
CH8 CH7CH6 CH5 CH4CH3 CH2 CH1
H
:Normal resolution mode
0
H
1 to F
H
0H : Normal mode (D/A conversion processing) 1 to F
: Offset/gain setting mode
H
Analog output range Output range setting value
– 10 to 10 V 4 H
User range setting F H
00H : Normal mode (non-synchronized) 01 to FF
: High resolution mode
*1 *2
Motor drive module, etc.
V+
COM
24V 24G
FG
24 V DC
*1 *2
GND
Motor drive module, etc.
I+
COM
24 V DC
24V 24G
FG
Setting
4 to 20 mA 0 H *1 0 to 20 mA 1 H
1 to 5 V 2 H 0 to 5 V 3 H
: Synchronized output mode
H
GND
HOLD/CLEAR function settin 0 : CLEAR 1 : HOLD
0 : Fixed
1 kW
to
1 MW
0W
to
600W
Output range setting value can be set within the ranges described below depending on the D/A converter module's model name.
y Q68DAV..........0H, 2H to 4H, FH
*1: The module activates at the analog output range within 1
to 5V, when 0H is set.
y Q68DAI ...........0H, 1H, FH
*2: Switch 3 is set at decimal unit. Setting is comparatively easier when the input type is change to decimal.
6. External Dimensions
Q68DA
RUN
ERROR
98 (3.86)
IN 24VDC
FG
90 (3.54)
10.5
(0.41)
FG terminal L-shaped metal fitting
6.7 (0.26)
Warranty
Mitsubishi Electric shall not be liable for any loss caused by reasons for which Mitsubishi is not held accountable, lost business opportunities or unrealized gain on the customer's side resulting from failure of the product, or any other damage, secondary disaster, accident, damage to equipment other than the product or disruption of other business operations arising out of special circumstances which may or may not have been predicted at Mitsubishi.
For safe use of the product
z This product is manufactured as a general-purpose product intended for general industrial use only. It is
not designed nor manufactured for use in an equipment or system affecting human lives.
z If you are considering to use this product in equipment or systems for nuclear power generation, power
generation, aerospace, medical or passenger transport applications, consult our sales representatives.
z This product is manufactured under our strict quality control system. However, if the product is used in
the intended facility in such a way that a failure of the product may lead to serious accident or loss, incorporate backup or fail-saf e functions into the system design.
Country/Region Sales office/Tel
U.S.A Mi tsubishi Electric Automation Inc. 500 Corporate Woods Parkway Vernon Hills, IL 60061 Tel : +1-847-478-2100 Brazil MELCO-TEC Rep. Com.e Assessoria Tecnica Ltda. Rua Correia Dias, 184, Edificio Paraiso Trade Center-8 andar Paraiso, Sao Paulo, SP Brazil Tel : +55-11-5908-8331 Germany Mitsubishi Electric Europe B.V. German Branch Gothaer Strasse 8 D-40880 Ratingen, GERMANY Tel : +49-2102-486-0 U.K Mitsubishi Electric Europe B.V. UK Branch Travellers Lane, Hatfield, Herts., AL10 8XB,UK Tel : +44-1707-276100 Italy Mitsubishi Electric Europe B.V. Italian Branch Centro Dir. Colleoni, Pal. Perseo-Ingr.2 Via P aracelso 12, 20041 Agrate B., Milano, Italy Tel : +39-039-6053344 Spain Mitsubishi Electric Europe B.V. Spanish Branch Carretera de Rubi 76-80 08190 Sant Cugat del Valles, Barcelona, Spain Tel : +34-93-565-3131 France Mitsubishi Electric Europe B.V. French Branch 25 Boulevard des Bouvets, F-92741 Nanterre Cedex, France TEL: +33-1-5568-5568 South Africa Circuit Breaker Industries LTD. Tripswitch Drive, Elandsfontein Gauteng, South Africa Tel : +27-11-928-2000
HEAD OFFICE : 1-8-12 , OFFICE TOWER Z 14F HARUMI CHUO-KU 104-6212, JAPA N
NAGOYA WORKS : 1-14, YADA -MINAMI 5-CHOME, HIGASHI-KU, NAGOYA, JAPAN
When exported from Jap an, this manual does not require application to the M inistry of Economy, Tra de and Indust ry for service tr ansaction permis sion.
Country/Region Sales office/Tel
Hong Kong Ryoden Automation Ltd. 10th Floor, Manulife Tower, 169 Electric Road, North Point, HongKong Tel : +852-2887-8870 China Ryoden Automation Shanghai Ltd. 3F Block5 Building Automation Instrumentation Plaza 103 Cao Bao Rd. Shanghai 200233 China Tel : +86-21-6120-0808 Taiwan Setsuyo Enterprise Co., Ltd. 6F., No.105 Wu-Kung 3rd.RD, Wu-Ku Hsiang, Taipei Hsine, Taiwan Tel : +886-2-2299-2499 Korea HAN NEUNG TECHNO CO.,LTD. 1F Dong Seo Game Channel Bldg., 660-11, Deungchon-dong Kangsec-ku, Seoul, Korea Tel : +82-2-3660-9552 Singapore Mitsubishi Electric Asia Pte, Ltd. 307 Alexandra Road #05-01/02, Mitsubishi Electric Building Singapore 159943 Tel : +65-6473-2308 Thailand F. A. Tech Co.,Ltd. 898/28,29,30 S.V.City Building,Office Tower 2,Floor 17-18 Rama 3 Road, Bangkpongpang, Yannawa, Bangkok 10120 Tel : +66-2-682-6522 Indonesia P.T. Autoteknindo SUMBER MAKMUR Jl. Muara Karang Selatan Block a Utara No.1 Kav. No.11 Kawasan Industri/ Pergudangan Jakarta - Utara 14440 Tel : +62-21-663-0833 India Messung Systems Put,Ltd. Electronic Sadan NO:111 Unit No15, M.I.D.C BHOSARI,PUNE-411026, India Tel : +91-20-712-2807 Australia Mitsubishi Electric Australia Pty. Ltd. 348 Victoria Road, PostalBag, No 2, Rydalmere, N.S.W 2116, Australia Tel : +61-2-9684-7777
3.7 (0.15)
27.4
(1.08)
2
8.5
(0.08)
(0.33)
FG terminal screw (M3 screw)
Specifications subject to change without notice.
Printed in Ja
an on recycled paper.
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18
7.4
(0.29)
unit (mm (in.
Loading...