Mitsubishi Q64TD, Q64TDV-GH, Q64TD-U-H-JE User Manual

Thermocouple Input Module Channel Isolated Thermocouple /Micro Voltage Input Module
MITSUBISHI General-Purpose PROGRAMMABLE LOGIC CONTROLLER
User’s Manual
(Hardware)
Q64TDV-GH
Thank you for purchasing the Mitsubishi general-purpose programmable logic controller MELSEC-Q series.
Prior to use, please read this manual thoroughly and familiarize yourself with the product
MODEL Q64TD-U-H-JE MODEL
CODE
13JT30
IB(NA)-0800155-B(0201)MEE
© 2000 MITSUBISHI ELECTRIC CORPORATION
A - 1
SAFETY PRECAUTIONS
(Read these precautions before using.)
When using Mitsubishi equipment, thoroughly read this manual and the associated manuals introduced in this manual. Also pay careful attention to safety and handle the module properly. These SAFETY PRECAUTIONS classify the safety precautions into two categories: “DANGER” and “CAUTION”.
DANGER
CAUTION
Procedures which may lead to a dangerous condition and cause death or serious injury, if not carried out properly.
Procedures which may lead to a dangerous condition and cause superficial to medium injury, or physical damage only, if not carried out properly.
Depending on circumstances, procedures indicated by CAUTION may also be linked to serious results. In any case, it is important to follow the directions for usage.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward it to the end user.
[DESIGN PRECAUTIONS]
DANGER
Do not write data into the "system area" of the buffer memory of intelligent
function modules. Also, do not use any "prohibited to use" signals as an output signal to an intelligent function module from the PLC CPU. Writing data into the "system area" or outputting a signal for "prohibited to use" may cause a PLC system malfunction.
CAUTION
Do not bunch the control wires or communication cables with the main
circuit or power wires, or install them close to each other. They should be installed 100 mm(3.94 inch) or more from each other. Not doing so could result in noise that may cause malfunction.
A - 2
[INSTALLATION PRECAUTIONS]
CAUTION
Use the PLC in an environment that meets the general specifications
contained in the CPU user's manual. Using this PLC in an environment outside the range of the general specifications may cause electric shock, fire, malfunction, and damage to or deterioration of the product.
When installing the module, securely insert the module fixing tabs into the
mounting holes of the base module while pressing the installation lever located at the bottom of the module downward. Improper installation may result in malfunction, breakdown or the module coming loose and dropping. Securely fix the module with screws if it is subject to vibration during use.
Tighten the screws within the range of specified torque.
If the screws are loose, it may cause the module to fallout, short circuits, or malfunction. If the screws are tightened too much, it may cause damage to the screw and/or the module, resulting in fallout, short circuits or malfunction.
Switch all phases of the external power supply off when mounting or
removing the module. Not ding so may cause electric shock or damage to the module.
Do not directly touch the conductive area or electronic components of the
module. Doing so may cause malfunction or failure in the module.
[WIRING PRECAUTIONS]
CAUTION
Always ground the FG terminal for the PLC.
There is a r isk of electr ic shock or malfunction.
When turning on the power and operating the module after wiring is
completed, always attach the terminal cover that comes with the product. There is a risk of electric shock if the terminal cover is not attached.
Tighten the terminal screws within the range of specified torque.
If the terminal screws are loose, it may result in short circuits or malfunction.If the terminal screws are tightened too much, it may cause damage to the screw and/or the module, resulting in short circuits or malfunction.
Be careful not to let foreign matter such as sawdust or wire chips get inside
the module.They may cause fires, failure or malfunction.
A - 3
[WIRING PRECAUTIONS]
CAUTION
The top surface of the module is covered with protective film to prevent
foreign objects such as cable offcuts from entering the module when wiring. Do not remove this film until the wiring is complete. Before operating the system, be sure to remove the film to provide adequate ventilation.
Always place the thermocouple at least 100mm (3.94inch) away from the
main circuit cables and AC control lines. Fully keep it away from high­voltage cables and circuits which include harmonics, such as an inverter's load circuit. Not doing so will make the module more susceptible to noises, surges and inductions.
REVISIONS
The manual number is given on the bottom right of the top cover.
Print Date
Manual Number Revision
Nov.,2000 IB (NA)-0800155-A First edition Jan.,2002 IB (NA)-0800155-B Model Q64TDV-GH was added.
Addition Section2.2 Correction About the Manuals, Chapter1, Section2.1,Chapter4,Section5.1 Section5.2
,
Section5.3,Chapter6
This manual confers no industrial property rights or any rights of any other kind, nor dose it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
© 2000 MITSUBISHI ELECTRIC CORPORATION
A - 4
CONTENTS
SAFETY PRECAUTIONS..............................................................................A-1
REVISIONS...................................................................................................A-3
CONTENTS...................................................................................................A-4
About the Manuals.........................................................................................A-5
Conformance to the EMC Directive/Low Voltage Directive............................A-5
1. OVERVIEW...................................................................................................1
2. SPECIFICATIONS.........................................................................................1
2.1 Specifications of Q64TD..........................................................................1
2.1.1 Performance specifications.............................................................1
2.1.2 Usable thermocouples and measured temperature range
accuracies.......................................................................................2
2.2 Specifications of Q64TD V -GH.................................................................3
2.2.1 Performance specifications.............................................................3
2.2.2 Usable thermocouples and measured temperature range
accuracies ......................................................................................5
2.2.3 Micro voltage input range and accuracies.......................................5
3. LOADING AND INSTALLATION....................................................................6
3.1 Handling Instructions...............................................................................6
3.2 Installation Envi ronment ..........................................................................6
4. NAMES AND SETTINGS OF THE PARTS....................................................7
5. WIRING.........................................................................................................8
5.1 Wiring Instruc tions...................................................................................8
5.2 External Wiring........................................................................................8
5.3 Intelligent Function Module Switch Setting.............................................10
6. OUTLINE DRAWINGS ................................................................................11
A - 5
About the Manuals
The following manuals are related to this product. Referring to this list, please request the necessary manuals.
Detailed manual
Manual Name
Manual Number
(Model Code)
Thermocouple Input Module , Channel Isolated Thermocouple/Micro Voltage Input Module User's Manual Q64TD/Q64TDV-GH/GX Configurator-TI (SW1D5C­QTIU-E)
SH-080141
(13JR30)
Conformance to the EMC Directive/Low Voltage Directive For details on making Mitsubishi PLC conform to the EMC directive and low
voltage instruction when installing it in your product, please see Chapter 3, "EMC Directive and Low Voltage Instruction" of the User's Manual (Hardware) of the PLC CPU to use. The CE logo is printed on the rating plate on the main body of the PLC that conforms to the EMC directive and low voltage instruction.
1
1. OVERVIEW
This user's manual provides the specifications, handling, part names and others of the Q64TD thermocouple temperature input module (abbreviated to the Q64TD) and Q64TDV-GH channel isolated thermocouple/micro voltage input module (abbreviated to the Q64TDV-GH) used with the MELSEC-Q series CPU module.
2. SPECIFICATIONS
The following are the specifications of the Q64TD/Q64TDV-GH.
2.1 Specifications of Q64TD
2.1.1 P erformance Specif ications
Item Specifications
Number of channels 4 channels
Temperature conversion value
16-bit, signed binary
(-2700 to 18200: Value to the first decimal place
10 times)
Out put
Scaling value 16-bit, signed binary Standard with which thermocouple conforms
JIS C1602-1995
Usable thermocouples and measured temperature range accuraci e s
Refer to Section 2.1.2
Cold junction temperature compensation accuracy
1.0
Accuracy As per calculation expression marked *1 Resolution B,R,S,N : 0.3 K,E,J,T : 0.1 Conversion speed 40ms/channel *2 Number of analog input points
4 channels + Pt100 connection channel/module
Insulation system
Across thermocouple input and earth Across thermocouple input channels Across cold junction temperature compensation input (Pt100) and earth
: Transformer insulation : Transformer insulation : No insulation
Dielectric withstand voltage 1780VrmsAC/3 cycles (altitude 2000m)
Insulation re sistance
Across thermocouple input and earth Across thermocouple input channels
: 500VDC 100M
or more using
insulation resistance tester
: 500VDC 10M
or more using
insulation resistance tester Wire break detection Yes (Each channel independent) *3 E2PROM write count Max. 100 thousand times Number of occupied points 16 points Connection terminals 18-point terminal block Applicable wire size 0.3 to 0.75mm
2
Applicable crimping terminals 1.25-3 R1.25-3(Sleeved crimping terminals are unusable) Internal current consumption (5VDC)
0.50A
Weight 0.25kg Outline dimensions 98(H) 27.4(W) 90(D)mm
*1: Calculate the accuracy in the following method.
(Accur acy) = ( co nvers ion acc urac y) + (t empe rat ure char acte rist ic)
(operating ambient temperature variation) + (cold junction temperature compensation accuracy) An operating ambient temperature variation indicates a deviation of the operating ambient tempera tur e f r om th e 25
5 range.
Example: W hen the t hermoc oupl e used is B , the op erati ng amb ient t emper ature is 35 , and the measure d temper atur e is 10 00
, the accura cy is:
( 2.5 ) + ( 0.4 ) (5 ) + ( 1 ) =
5.5
*2: The conversion speed is a period from when a temperature is input and converted into a
corresponding digital value until the value is stored into the buffer memory. When two or more channels are used, the conversion speed is "40ms
number of conversion enabled channels".
*3: At wire break detection, the temperature measurement value right before wire brea k occurrence is held.
2
2.1.2 Usable Thermocouples and Measured Temperature Range Accuracies
Usable
Thermo
couple
Type
Measured
Temperature
Range*1
Conversion Accuracy
(At operating ambient
temperature
25
5 )
Temperature Characteristic
(Per operating ambient
temperature variation of 1 )
Max. Temperature
Error at Ambient
Temperature 55
0 to 600 ——— *3 ——— *3 ——— *3
600 to 800
*2
3.0 13.0
800 to 1700
*2
2.5
0.4
12.5
B
1700 to 1820
——— *3 ——— *3 ——— *3
-50 to 0 ——— *3 ——— *3 ——— *3
0 to 300
*2
2.5 0.4 12.5
300 to 1600
*2
2.0 0.3 9.5
R
1600 to 1760
——— *3 ——— *3 ——— *3
-50 to 0 ——— *3 ——— *3 ——— *3
0 to 300
*2
2.5 0.4 12.5
300 to 1600
*2
2.0 0.3 9.5
S
1600 to 1760
——— *3 ——— *3 ——— *3
-270 to -200 ——— *3 ——— *3 ——— *3
-200 to 0
*2
Larger value of 0.5 and
0.5% of measured temperature
Larger value of 0.06 and
0.2% of measured temperature
11.0
0 to 1200
*2
Larger value of 0.5 and
0.25% of measured temperature
Larger value of 0.06 and
0.02% of measured temperature
9.0
K
1200 to 1370
——— *3 ——— *3 ——— *3
-270 to -200 ——— *3 ——— *3 ——— *3
-200 to 0
*2
Larger value of 0.5 and
0.5% of measured temperature
Larger value of 0.06 and
0.15% of measured temperature
8.5
0 to 900
*2
Larger value of 0.5 and
0.25% of measured temperature
Larger value of 0.06 and
0.02% of measured temperature
6.75
E
900 to 1000
——— *3 ——— *3 ——— *3
-210 to -40 ——— *3 ——— *3 ——— *3
-40 to 750
*2
Larger value of 0.5 and
0.25% of measured temperature
Larger value of 0.06 and
0.02% of measured temperature
5.625
J
750 to 1200
——— *3 ——— *3 ——— *3
-270 to -200 ——— *3 ——— *3 ——— *3
-200 to 0
*2
Larger value of 0.5 and
0.5% of measured temperature
Larger value of 0.06 and
0.1% of measured temperature
6.0
0 to 350
*2
Larger value of 0.5 and
0.25% of measured temperature
Larger value of 0.06 and
0.02% of measured temperature
2.625
T
350 to 400
——— *3 ——— *3 ——— *3
-270 to -200 ——— *3 ——— *3 ——— *3
-200 to 0
*2
Larger value of 0.5 and
0.5% of measured temperature
Larger value of 0.06 and
0.2% of measured temperature
11.0
0 to 1250
*2
Larger value of 0.5 and
0.25% of measured temperature
Larger value of 0.06 and
0.02% of measured temperature
9.375
N
1250 to 1300
——— *3 ——— *3 ——— *3
*1: If a value entered from the thermocouple is outside the measured temperature range given in the table, it is
handled as the maximum/minimum value of the measured temperature range. *2: The accuracies only in the temperature ranges of Class 1 to 3 (shaded areas) in JIS C1602-1995 apply. *3: Temperature measurement can be made, but accuracy is not guaranteed.
3
2.2 Specifications of Q64TDV-GH
2.2.1 P erformance Specif ications
Item Specifications
Number of channels 4 channels
Temperature conversion value
16-bit, signed binary
(-2700 to 18200: Value to the first decimal place
10 times) Micro voltage conversion value
16-bit signed binary (-25000 to 25000)
Out put
Scaling value 16-bit, signed binary
Standard with which thermocouple conforms
JIS C1602-1995
Usable thermocouples and measured temperature range accuraci e s
Refer to Section 2.2.2
Cold junction temperature compensation accuracy
1.0
Thermocouple input accuracy
As per calculation expression marked *1
Micro voltage input range
-100mV to +100mV (input resistance 2M
or more)
Micro voltage input accuracy Refer to Section 2.2.3.
Thermocouple input
B:0.7 R,S:0.8 K,T:0.3 E:0.2 J:0.1 N:0.4
Resolution
Micro voltage input
4 V
Sampling period 20ms/channel *2 Conversion speed Sampling period 3*3 Number of analog input points
4 channels + Pt100 connection channel/module
Absolute maximum input 5V
Insulation system
Across thermocouple input/micro voltage input and earth Across thermocouple input/micro voltage input channels Across cold junction temperature compensation input (Pt100) and earth
: Transformer insulation : Transformer insulation : No insulation
Dielectric withstand voltage 1780VrmsAC/3 cycles (altitude 2000m)
Insulation re sistance
Across thermocouple input/micro voltage input and earth Across thermocouple input/micro voltage input channels
: 500VDC 100M
or more using
insulation resistance tester
: 500VDC 10M
or more using
insulation resistance tester Wire break detection Yes (Each channel independent) *4 E2PROM write count Max. 100 thousand times Number of occupied points 16 points Connection terminals 18-point terminal block Applicable wire size 0.3 to 0.75mm
2
Applicable crimping terminals 1.25-3 R1.25-3(Sleeved crimping terminals are unusable) Internal current consumption (5VDC)
0.50A
Weight 0.25kg Outline dimensions 98(H) 27.4(W) 112(D)mm
*1: Calculate the accuracy in the following method.
(Accur acy) = ( co nvers ion acc urac y) + (t empe rat ure char acte rist ic)
(operating ambient temperature variation) + (cold junction temperature compensation accuracy) An operating ambient temperature variation indicates a deviation of the operating ambient tempera tur e f r om th e 25
5 range.
Example: W hen the t hermoc oupl e use d is B, the op erat ing am bient tem peratur e is 3 5 , and the measure d temper atur e is 10 00
, the accura cy is:
(
3.5
) + ( 0.4 ) (5 ) + ( 1 ) =
6.5
4
*2: A period until a thermocouple input value/micro voltage input value is converted
into a temperature
measurement value/micro voltage conversion value.
*3: A period until a thermocouple input value/micro voltage input value is converted into a
temperature measurement value/micro voltage conversion value and the resultant value is stored into the buffer memory. The conversion speed is a delay time that occurs during sampling processing. It is independent of averaging processing. Example: When two channels are enabled for conversion (Conversion speed) = (sampling period)
3
= (20ms
2 channels) 3
= 120ms
CH.1 CH.2
Input 1)
Conversion speed
Conversion processing
Buffer memory
Input 2)
CH.1 CH.2
CH.1 CH.2 CH.1 CH.2 CH.1 CH.2
Input 1)
Input 2)
Conversion speed
*4:At wire break detection, the temperature measurement value/micro voltage conversion value right
before wire break occurrence is held.
5
2.2.2 Usable Thermocouples and Measured Temperature Range Accuracies
Usable
Thermo
couple
Type
Measured
Temperature
Range*1
Conversion Accuracy
(At operating ambient
temperature
25
5 )
Temperature Characteristic
(Per operating ambient
temperature variation of 1 )
Max. Temperature
Error at Ambient
Temperature 55
0 to 600 ——— *3 ——— *3 ——— *3
600 to 800
*2
4.0 14.0
800 to 1700
*2
3.5
0.4
13.5
B
1700 to 1820
——— *3 ——— *3 ——— *3
-50 to 0 ——— *3 ——— *3 ——— *3
0 to 300
*2
4.0 14.0
300 to 1600
*2
3.5
0.4
13.5
R
1600 to 1760
——— *3 ——— *3 ——— *3
-50 to 0 ——— *3 ——— *3 ——— *3
0 to 300
*2
4.0 14.0
300 to 1600
*2
3.5
0.4
13.5
S
1600 to 1760
——— *3 ——— *3 ——— *3
-270 to -200 ——— *3 ——— *3 ——— *3
-200 to 0
*2
2.0 8.25
0 to 200
*2
1.5 7.75
0 to 1200
*2
2.0
0.25
8.25
K
1200 to 1370
——— *3 ——— *3 ——— *3
-270 to -200 ——— *3 ——— *3 ——— *3
-200 to 200
*2
1.5 5.25
200 to 900
*2
2.0
0.15
5.75
E
900 to 1000
——— *3 ——— *3 ——— *3
-210 to -40 ——— *3 ——— *3 ——— *3
-40 to 200
*2
1.5 5.25
200 to 750
*2
2.0
0.15
5.75
J
750 to 1200
——— *3 ——— *3 ——— *3
-270 to -200 ——— *3 ——— *3 ——— *3
-200 to 0
*2
2.0 4.5
0 to 350
*2
1.5
0.1
4.0
T
350 to 400 ——— *3 ——— *3 ——— *3
-270 to -200 ——— *3 ——— *3 ——— *3
-200 to 0
*2
2.5 8.75
0 to 200
*2
2.0 8.25
0 to 1250
*2
2.5
0.25
8.75
N
1250 to 1300
——— *3 ——— *3 ——— *3
*1: If a value entered from the thermocouple is outside the measured temperature range given in the table, it is
handled as the maximum/minimum value of the measured temperature range. *2: The accuracies only in the temperature ranges of Class 1 to 3 (shaded areas) in JIS C1602-1995 apply. *3: Temperature measurement can be made, but accuracy is not guaranteed.
2.2.3 Micro voltage input range and accuracies
Conversion Accuracy
Input Type
Measurable Voltage
Range
(At 25 5 operating ambient temperature)
(At 0 to 55 operating ambient temperature)
Micro voltage input -100 to 100mV 0.2mV 0.8mV
6
3. LOADING AND INSTALLATION
3.1 Handling Instructions (1) Do not drop the case and connectors of the module and subject them to
hard impact.
(2) Do not remove the printed circuit boards of the module from the case. Doing
so can cause a failure.
(3) Be careful to prevent wire-offcuts and other foreign matter from entering the
module. They can cause a fire, failure or malfunction.
(4) To prevent wire-offcuts and other foreign matter from entering the module
during wiring, the module carries a foreign matter ingress prevention label at its top. During wiring, do not remove this label. For system operation, always remove this label to ensure adequate heat dissipation.
(5) Tighten the mounting and terminal screws of the module within the following
ranges.
Screw Location Tightening Torque Range Module mounting screw (M3 screw) 36 to 48 N · cm Terminal block terminal screw (M3 screw) 42 to 58 N · cm Terminal block mounting screw (M3.5 screw) 66 to 89 N · cm
(6) To mount the module on the base, securely insert the module fastening
latch into the fastening hole on the base. Improper installation may result in a module malfunction, or may cause the module to fall off.
3.2 Installation Environment Refer to the user's manual of the CPU module used.
7
4. NAMES AND SETTINGS OF THE PARTS
Terminal Block Layout
Terminal number Signal name
1RTD + 2 3RTD ­4 5 6 CH1 SLD 7 CH2 SLD 8 CH1 +
9 CH2 + 10 CH1 ­11 CH2 ­12 CH3 + 13 CH4 + 14 CH3 ­15 CH4 ­16 CH3 SLD 17 CH4 SLD 18 FG
1)
2)
Q64TD
RUN
ERROR
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18
R T D
CH1+ CH2+
1­2-
SLD
SLD
CH3+ CH4+
3­4-
SLD
SLD
(FG)
Q64TD
3)
4)
1)
2)
Q64TDV-GH
RUN
ERROR
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18
R
T
D
CH1+ CH2+
1­2-
SLD
SLD
CH3+ CH4+
3­4-
SLD
SLD
(FG)
Q64TDV
-GH
3)
4)
Q64TD
Q64TDV-GH
Number Name and Appearance Description
1) RUN LED
Indicates the operating status of the Q64TD/Q64TDV-GH. On : Operating normally. Flicker : Offset/gain setting mode Off : 5V power-off , Watchdog timer error occurrence or
module change enabled status during online module change
2) ERR LED
Indicates the error status of the Q64TD/Q64TDV-GH. On : Error occurrence Flicker : Switch setting error
Switch 5 was set to other than 0 in intelligent function module switch setting of GX Developer.
Off : Operating normally.
3) Terminal block Used for wiring of the thermocouple, etc.
4)
Cold junction temperature compensation resistor
Used for cold junction temperature compensation using Pt100.
8
5. WIRING
5.1 Wiring Instructions (1) Use separate cables for the AC control circuit and Q64TD/Q64TDV-GH's
external input signals to avoid the influence of AC side surges and inductions.
(2) Always place the thermocouple/micro voltage signal cable at least 100mm
away from the main circuit cables and AC control circuit lines. Fully keep it away from high-voltage cables and circuits which include harmonics, such as an inverter's load circuit. Not doing so will make the module more susceptible to noises, surges and inductions.
(3) Insulation-sleeved crimping terminals cannot be used with the terminal
block. It is recommended to fit mark tubes or insulation tubes to the wire connection parts of the crimping terminals.
5.2 External Wiring (1) Thermocouple
RTD
Input
amplifier
CH1
Filter
Transformer
CH4
Pt100
*1
*2
*1:As cables, always use shielded compensation conductors. Also, wire the shielded cables as short as possible. *2:Always connect to the eart h ter mi na l of the control box.
+
-
SLD
SLD
FG
Input
amplifier
Input
amplifier
Filter
Transformer
+
-
+
-
9
(2) Micro voltage signal
RTD
Input
amplifier
CH1
Filter
Transformer
CH4
Pt100
*1
*2
*1:As cables, always use shield ed conductors. Also, wire the shielded cables as short as possible. *2:Always connect to the earth terminal of the control box.
+
-
SLD
SLD
FG
Input
amplifier
Input
amplifier
Filter
Transformer
+
-
+
-
Load cell or like
Load cell or like
10
5.3 Intelligent Function Module Switch Setting Make the intelligent function module switch se tting using the I/O assignment
setting of GX Developer. You can make setting easily by entering hexadecimal numbers into 4 digits.
Setting Item
Input type Set value Thermocouple K 0 Thermocouple E 1
Thermocouple J 2 Thermocouple T 3 Thermocouple B 4 Thermocouple R 5 Thermocouple S 6 Thermocouple N 7
Micro voltage input
*
8
Switch 1
Input type setting
CH4 CH3CH2 CH1
H
Offset/gain setting Set value
Factory setting 0
User setting 1
Switch 2
Offset/gain setting
CH4 CH3CH2 CH1
H
Switch 3 Empty Switch 4
H
0
H
: With cold junction temperature compensation
1 to F
H
: Without cold junction temperature compensation
0
H
: Normal mode
1 to F
H
: Offset/gain setting mode
Invalid when the setting of Switch 1 is 8 (micro voltage input)
Switch 5 Empty
* Micro voltage input can be set on the Q64TDV-GH only.
11
6. OUTLINE DRAWINGS
1) Q64TD
27.4(1.08)
Q64TD
RUN
ERROR
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18
R
T
D
CH1+ CH2+
1­2-
SLD SLD
CH3+ CH4+
3­4-
SLD SLD
(FG)
Q64TD
2(0.08
)
112(4.41)
98 (3.86)
105(4.14)
2(0.08)
5(0.20)
Unit: mm (in.)
2) Q64TDV-GH
27.4(1.08)
Q64TDV-GH
RUN
ERROR
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18
R T D
CH1+ CH2+
1­2-
SLD
SLD
CH3+ CH4+
3­4-
SLD
SLD
(FG)
Q64TDV
-GH
2(0.08)
112(4.41)
98 (3.86)
105(4.14)
2(0.08)
5(0.20)
Unit: mm (in.)
Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to other duties.
For safe use
! This product has been manufactured as a general-purpose part for general industries,
and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life.
! Before using the product for special purposes such as nuclear power, electric power,
aerospace, medicine or passenger movement vehicles, consult with Mitsubishi.
! This product has been manufactured under strict quality control. However, when
installing the product where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.
U.S.A Mitsubishi Electric Automation Inc. 500 Corporate Woods Parkway Vernon Hills, IL 60061 Tel : +1-847-478-2100 Brazil MELCO-TEC Rep. Com.e Assessoria Tecnica Ltda. Av. Rio Branco, 123-15 ,and S/1507, Rio de Janeiro, RJ CEP 20040-005, Brazil Tel : +55-21-221-8343 Germany Mitsubishi Electric Europe B.V. German Branch Gothaer Strasse 8 D-40880 Ratingen, GERMANY Tel : +49-2102-486-0 U.K Mitsubishi Electric Europe B.V. UK Branch Travellers Lane, Hatfield, Herts., AL10 8XB,UK Tel : +44-1707-276100
Italy Mitsubishi Electric Europe B.V. Italian Branch
Centro Dir. Colleoni, Pal. Perseo - Ingr.2 Via Paracelso 12, 20041 Agrate B., Milano, Italy Tel:+39-039-60531
Spain Mitsubishi Electric Europe B.V. Spanish Branch Carretera de Rubi 76-80 08190 - Sant Cugat del Valles, Barcelona, Spain Tel:+34-935-653135
South Africa Circuit Breaker Industries LTD. Private Bag 2016, Isando 1600, Johannesburg, South Africa Tel : +27-11-928-2000
Hong Kong Ryoden Automation Ltd. 10th Floor, Manulife Tower, 169 Electric Road, North Point, HongKong Tel : +852-2887-8870
China Ryoden International Shanghai Ltd. 3F Block5 Building Automation Instrumentation Plaza 103 Cao Bao Rd.
Shanghai 200233 China Tel : +86-21-6475-3228 Taiwan Setsuyo Enterprise C o. , Ltd. 6F., No.105 Wu-Kung 3rd.RD, Wu-Ku Hsiang, Taipei Hsine, Taiwan Tel : +886-2-2299-2499 Korea HAN NEUNG TECHNO CO.,LTD. 1F Dong Seo Game Channel Bldg., 660-11, Deungchon-dong Kangsec-ku, Seoul, Korea Tel : +82-2-3668-6567 Singapore Mitsubishi Electric Asia Pte, Ltd. 307 ALEXANDRA ROAD #05-01/02, MITSUBISHI ELECTRIC BUILDING SINGAPORE 159943 Tel : +65-473-2480 Thailand F. A. Tech Co.,Ltd. 898/28,29,30 S.V.City Building,Office Tower 2,Floor 17-18 Rama 3 Road, Bangkpongpang, Yannawa, Bangkok 10120 Tel : +66-2-682-6522 Indonesia P.T. Autoteknindo SUMBER MAKMUR Jl. Muara Karang Selatan Block A Utara No.1 Kav. No.11 Kawasan Industri/ Pergudangan Jakarta - Utara 14440 Tel : +62-21-663-0833 India Messung Systems Put,Ltd. Electronic Sadan NO:111 Unit No15, M.I.D.C BHOSARI,PUNE-411026 Tel : +91-20-7128927 Australia Mitsubishi Electric Australia Pty. Ltd. 348 Victoria Road, PostalBag, No 2, Rydalmere, N.S.W 2116, Australia Tel : +61-2-9684-7777
Country/Region Sales office/Tel Country/Region Sales office/Tel
When exported from Japan, this manual does not require application to the Ministry of Economy, Trade and Industry for service transaction permission.
Specifications subject to change without notice.
Printed in Japan on recycled paper.
HEAD OFFICE : 1-8-12, OFFICE TOWER Z 14F HARUMI CHUO-KU 104-6212, JAPAN
NAGOYA WORKS : 1-14, YADA-MINAMI5, HIGASHI-KU, NAGOYA, JAPAN
Loading...