Mitsubishi Q2ASCPU, Q2ASCPU-S1, Q2ASHCPU, Q2ASHCPU-S1 User Manual

Q2AS(H)CPU(S1)
Mitsubishi Programmable Controller
(Hardware)
Thank you for purchasing the Mitsubishi programmable logic controller
MELSEC-QnA series.
Prior to use, please read both this and relevant manual
thoroughly to fully understand the product.
MODEL
MODEL
CODE
IB(NA)-66677-H(0810)MEE
Q2ASCPU-U(H/W)-E
13J857
©1996 MITSUBISHI ELECTRIC CORPORATION

SAFETY PRECAUTIONS

(Be sure to read these instructions before use.)
Before using the product, read this and relevant manuals carefully and handle the product correctly with full attention to safety. In this manual, SAFETY PRECAUTIONS are classified into 2 levels: "DANGER" and "CAUTION".
Indicates that incorrect handling may cause hazardous
DANGER
conditions, resulting in death or severe injury.
CAUTION
Under some circumstances, failure to observe the instructions may also lead to serious results. Be sure to observe the instructions of both levels to ensure the safety. Please keep this manual in a safe place for future reference and also pass this manual on to the end user.
Indicates that incorrect handling may cause hazardous conditions, resulting in minor or moderate injury and/or property damage.
CAUTION level
[DESIGN PRECAUTIONS]
DANGER
Create a safety circuit outside the programmable controller to ensure the
whole system will operate safely even if an external power failure or a programmable controller failure occurs. Otherwise, incorrect output or malfunction may cause an accident. (1) For an emergency stop circuit, protection circuit and interlock circuit that
is designed for incompatible actions such as forward/reverse rotation or for damage prevention such as the upper/lower limit setting in positioning, any of them must be created outside the programmable controller. Install the emergency stop switch outsid the controlpanel so that workers can operate it easily.
A-1
[DESIGN PRECAUTIONS]
DANGER
(2) When the programmable controller detects the following error
conditions, it stops the operation and turn off all the outputs. The overcurrent protection device or overvoltage protection device of
the power supply module is activated.
The programmable controller CPU detects an error such as a
watchdog timer error by the self-diagnostics function.
In the case of an error of a part such as an I/O control part that cannot be detected by the programmable controller CPU, all the outputs may turn on. In order to make all machines operate safely in such a case, set up a fail-safe circuit or a specific mechanism outside the programmable controller.
Refer to "LOADING AND INSTALLATION" in this manual for example fail safe circuits.
(3) Depending on the failure of the output module’s relay or transistor, the
output status may remain ON or OFF incorrectly. For output signals that may lead to a serious accident, create an external monitoring circuit. If load current more than the rating or overcurrent due to a short circuit
in the load has flowed in the output module for a long time, it may cause a fire and smoke. Provide an external safety device such as a fuse.
Design a circuit so that the external power will be supplied after
power-up of the programmable controller. Activating the external power supply prior to the programmable controller may result in an accident due to incorrect output or malfunction.
For the operation status of each station at a communication error in
data link, refer to the respective data link manual. The communication error may result in an accident due to incorrect output or malfunction.
A-2
[DESIGN PRECAUTIONS]
DANGER
When controlling a running programmable controller (data modification) by
connecting a peripheral device to the CPU module or a PC to a special function module, create an interlock circuit on sequence programs so that the whole system functions safely all the time. Also, before performing any other controls (e.g. program modification, operating status change (status control)), read the manual carefully and ensure the safety. In these controls, especially the one from an external device to a programmable controller in a remote location, some programmable controller side problem may not be resolved immediately due to failure of data communications. To prevent this, create an interlock circuit on sequence programs and establish corrective procedures for communication failure between the external device and the programmable controller CPU.
When setting up the system, do not allow any empty slot on the base unit.
If any slot is left empty, be sure to use a blank cover (A1SG60) or a dummy module (A1SG62) for it. When using the extension base unit, A1S52B(S1), A1S55B(S1) or A1S58B(S1), attach the included dustproof cover to the module in slot 0. Otherwise, internal parts of the module may be flied in the short circuit test or when an overcurrent or overvoltage is accidentally applied to external I/O section.
CAUTION
Do not install the control lines or communication cables together with the
main circuit or power lines, or bring them close to each other. Keep a distance of 100mm (3.94inch) or more between them. Failure to do so may cause malfunctions due to noise.
If having read register R outside the allowable range with the MOV
instruction, the file register data will be FFFF
H. Using this as it is may cause
malfunctions. Pay attention not to use any out-of-range file register when designing sequence programs. For instruction details, refer to the programming manual.
When an output module is used to control the lamp load, heater, solenoid
valve, etc., a large current (ten times larger than the normal one) may flow at the time that the output status changes from OFF to ON. Take some preventive measures such as replacing the output module with the one of a suitable current rating.
A-3
[INSTALLATION PRECAUTIONS]
CAUTION
Use the programmable controller under the environment specified in the
user’s manual. Otherwise, it may cause electric shocks, fires, malfunctions, product deterioration or damage.
Insert the module fixing projection into the fixing hole in the base unit and
then tighten the module mounting screw within the specified torque. When no screw is tightened, even if the module is installed correctly, it may cause malfunctions, a failure or a drop of the module. Tightening the screw excessively may damage the screw and/or the module, resulting in a drop of the module, a short circuit or malfunctions.
Connect the extension cable to the connector of the base unit or module.
Check the cable for incomplete connection after connecting it. Poor electrical contact may cause incorrect inputs and/or outputs.
Insert the memory card and fully press it to the memory card connector.
Check for incomplete connection after installing it. Poor electrical contact may cause malfunctions.
Be sure to shut off all phases of the external power supply used by the
system before mounting or removing the module. Failure to do so may damage the module.
Do not directly touch the conductive part or electronic components of the
module. Doing so may cause malfunctions or a failure of the module.
A-4
[WIRING PRECAUTIONS]
DANGER
Be sure to shut off all phases of the external power supply used by the
system before wiring. Failure to do so may result in an electric shock or damage of the product.
Before energizing and operating the system after wiring, be sure to attach the
terminal cover supplied with the product. Failure to do so may cause an electric shock.
CAUTION
Always ground the FG and LG terminals to the protective ground conductor.
Failure to do so may cause an electric shock or malfunctions.
Wire the module correctly after confirming the rated voltage and terminal
layout. Connecting a power supply of a different voltage rating or incorrect wiring may cause a fire or failure.
Do not connect multiple power supply modules to one module in parallel.
The power supply modules may be heated, resulting in a fire or failure.
Press, crimp or properly solder the connector for external connection with the
specified tool. Incomplete connection may cause a short circuit, fire or malfunctions.
Tighten terminal screws within the specified torque range. If the screw is too
loose, it may cause a short circuit, fire or malfunctions. If too tight, it may damage the screw and/or the module, resulting in a short circuit or malfunctions.
Carefully prevent foreign matter such as dust or wire chips from entering the
module. Failure to do so may cause a fire, failure or malfunctions.
Install our programmable controller in a control panel for use.
Wire the main power supply to the power supply module installed in a control panel through a distribution terminal block. Furthermore, the wiring and replacement of a power supply module have to be performed by a maintenance worker who acquainted with shock protection. (For the wiring methods, refer to Type Q2AS(H)CPU(S1) User’s Manual.)
A-5
[STARTUP AND MAINTENANCE PRECAUTIONS]
DANGER
Do not touch any terminal during power distribution.
Doing so may cause an electric shock.
Properly connect batteries. Do not charge, disassemble, heat or throw them
into the fire and do not make them short-circuited and soldered. Incorrect battery handling may cause personal injuries or a fire due to exothermic heat, burst and/or ignition.
Be sure to shut off all phases of the external power supply used by the
system before cleaning or retightening the terminal screws or module mounting screws. Failure to do so may result in an electric shock. If they are too loose, it may cause a short circuit or malfunctions. If too tight, it may cause damage to the screws and/or module, resulting in an accidental drop of the module, short circuit or malfunctions.
CAUTION
When performing online operations (especially, program modification, forced
output or operating status change) by connecting a peripheral device to the running CPU module, read the manual carefully and ensure the safety. Incorrect operation will cause mechanical damage or accidents.
Do not disassemble or modify each of modules.
Doing so may cause failure, malfunctions, personal injuries and/or a fire.
When using a wireless communication device such as a mobile phone, keep
a distance of 25cm (9.84inch) or more from the programmable controller in all directions. Failure to do so may cause malfunctions.
Be sure to shut off all phases of the external power supply used by the
system before mounting or removing the module. Failure to do so may result in failure or malfunctions of the module.
Do not drop or apply any impact to the battery.
Doing so may damage the battery, resulting in electrolyte spillage inside the battery. If any impact has been applied, discard the battery and never use it.
Do not install/remove the terminal block more than 50 times after the first use
of the product. (IEC 61131-2 compliant)
Before handling modules, touch a grounded metal object to discharge the
static electricity from the human body. Failure to do so may cause failure or malfunctions of the module.
A-6
[DISPOSAL PRECAUTIONS]
CAUTION
When disposing of the product, treat it as an industrial waste.
When disposing of batteries, separate them from other wastes according to the local regulations. (For details of the battery directive in EU member states, refer to the Q2AS(H)CPU(S1) User's Manual.)
[TRANSPORTATION PRECAUTIONS]
CAUTION
When transporting lithium batteries, make sure to treat them based on the
transportation regulations. (Refer to Chapter 7 for details of the relevant models.)
A-7

REVISIONS

*The manual number is given on the bottom right of the front cover. Print Date *Manual Number Revision Jan., 1996 IB(NA) 66677-A First edition
Sep., 1998 IB(NA) 66677-B
Correction
SAFETY PRECAUTIONS, Section 4.5.2
Addition
Specifications, Performance specifications, EMC standards, Low-Voltage instruction
Deletion
I/O module specifications and connections
Dec., 2002 IB(NA) 66677-C Equivalent to Japanese version E
Correction
SAFETY PRECAUTIONS, 1.1, Chapter 3, Section 4.2, 4.3.1, 4.3.2, 4.5.2, Chapter 5, Chapter 6, Section 6.2
Dec., 2003 IB(NA) 66677-D
Addition of model
A1SY42P
Jul., 2005 IB(NA) 66677-E
Addition
Chapter 7, Section 7.1, 7.2
Correction
SAFETY PRECAUTIONS, Section 5.2.1,
5.2.2, 5.3.1, 5.3.2, 6.2
Correction
SAFETY PRECAUTIONS, Section 1.1, Chapter 3, Section 3.1, 3.1.1, 3.1.2, 3.1.3,
3.2, 3.2.4, 3.2.7, 4.1.1, 4.2, 4.3.1, 4.3.2,
4.3.3, 4.3.4, 4.4, 6.2, 6.3 Section change
Section 6.1, 6.2 are changed to Section 6.2,
6.3, respectively.
A-8
*The manual number is given on the bottom right of the front cover. Print Date *Manual Number Revision Oct., 2006 IB(NA) 66677-F
May, 2007 IB(NA) 66677-G
Oct., 2008 IB(NA) 66677-H
Addition of model
A1SY40P, A1SY41P
Addition
Section 6.5, 6.6, 6.7, 6.8, 6.9, 6.10
Correction
SAFETY PRECAUTIONS, Section 1.1,
3.1.3, 3.2.4, 3.2.6, 4.1.1, 4.1.3, 4.3.2, 4.3.3,
4.3.4, 5.2.1, 5.2.2, Chapter 6
Partial Correction
Section 3.1.1, 3.1.3, 3.1.4, 3.2.7, 4.3.3,
4.3.4, 5.2.1, 6.3
Partial Correction
SAFETY PRECAUTIONS, Section 1.1, 3.1,
3.1.1, 3.1.2, 3.1.3, 3.2, 3.2.1, 3.2.2, 3.2.3,
3.2.4, 3.2.5, 3.2.6, 3.2.7, 4.1.3, 4.2, 4.3.3,
4.3.4, 4.5.2, 5.1.1, 5.2.1, Chapter 6
Japanese Manual Version IB(NA)68653-J
This manual confers no industrial property rights or any rights of any other kind, nor dose it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
©1996 Mitsubishi Electric Corporation
A-9

CONTENTS

1. SPECIFICATIONS .....................................................................................................1
1.1 SPECIFICATIONS.................................................................................................1
2. PERFORMANCE SPECIFICATION..........................................................................2
2.1 QnASCPU Module Performance Specification .....................................................2
3. EMC DIRECTIVES AND LOW VOLTAGE DIRECTIVES ........................................3
3.1 Requirements for Compliance with EMC Directives .............................................3
3.1.1 EMC standard.................................................................................................4
3.1.2 Installation instructions for EMC Directive......................................................5
3.1.3 Cables.............................................................................................................6
3.1.4 Power supply module ...................................................................................11
3.1.5 Base unit .......................................................................................................11
3.1.6 Ferrite core....................................................................................................11
3.1.7 Noise filter (power supply line filter)..............................................................12
3.2 Requirements for Compliance with Low Voltage Directives................................13
3.2.1 Standard applied for MELSEC-QnA series programmable controller .........13
3.2.2 Precautions when using the MELSEC-QnA series programmable controller
...............................................................................................................................13
3.2.3 Power supply ................................................................................................14
3.2.4 Control panel.................................................................................................15
3.2.5 Module installation ........................................................................................16
3.2.6 Grounding .....................................................................................................16
3.2.7 External wiring ..............................................................................................16
4. LOADING AND INSTALLATION ............................................................................17
4.1 Installing the Module............................................................................................17
4.1.1 Notes on handling the module......................................................................17
4.1.2 Installation environment................................................................................18
4.1.3 Notes on installing the base unit...................................................................19
4.2 Fail-safe Circuit Concept .....................................................................................21
4.3 Wiring ...................................................................................................................27
4.3.1 Power supply module specifications ............................................................27
4.3.2 Part names and settings...............................................................................29
4.3.3 Wiring instructions ........................................................................................30
4.3.4 Wiring to module terminals ...........................................................................35
4.4 Precautions when Connecting the Uninterruptive Power Supply (UPS).............36
4.5 Part names and Settings .....................................................................................37
4.5.1 Part names and settings...............................................................................37
4.5.2 Relation between switch operation and the LED indication .........................39
5. SPECIFICATION AND CONNECTION OF I/O MODULES
5.1 Input modules ......................................................................................................41
5.1.1 Input module specifications ..........................................................................41
5.1.2 Input module connections.............................................................................43
5.2 Output modules....................................................................................................47
5.2.1 Output module specifications .......................................................................47
5.2.2 Output module connections..........................................................................49
5.3 Input/output combined modules ..........................................................................57
5.3.1 Input/output combined module specifications ..............................................57
5.3.2 Input/output composite module connections................................................59
.........................................41
A-10
6. ERROR CODE......................................................................................................... 61
6.1 Error Code Type ..................................................................................................62
6.2 Reading Error Code.............................................................................................62
6.3 Error Code List.....................................................................................................63
6.4 Canceling of Errors............................................................................................225
7. TRANSPORTATION PRECAUTIONS..................................................................226
7.1 Relevant Models................................................................................................226
7.2 Transportation Guidelines .................................................................................226
A-11
This manual explains safety precautions, I/O module wiring, and error codes regarding the Q2ASCPU, Q2ASCPU-S1, Q2ASHCPU, and Q2ASHCPU-S1 (hereinafter, these are all referred to as Q2ASCPU).

About this manual

The following tables show the manuals relevant to this product. Refer to these tables when you order a manual, if necessary.
Detailed Manual
Manual title
type Q2AS(H)CPU(S1) User's Manual
This manual explains performance, functions, and handling of the Q2ASCPU, Q2ASCPU-S1, Q2ASHCPU, and Q2ASHCPU-S1, power supply, memory
rd, specifications, and handling of the base unit.
ca
(sold separately)
Relavant Manuals
Manual title
QnACPU-GUIDEBOOK
This manual explains how to create a program, write the program using the CPU module, and debug the program. This manual is designed for first-time users of the QnACPU. It also explains some applications of the QnACPU.
(sold separately)
QnACPU PROGRAMMING MANUAL (Fundamentals)
This manual describes programming methods, device names, and parameters required to create a program. It also describes various types of programs.
(sold separately) QCPU(Q mode)/QnACPU PROGRAMMING MANUAL (Common Instructions)
This manual explains how to use sequence instructions, basic instructions, and application instructions.
(sold separately) QnACPU PROGRAMMING MANUAL (Special Function)
This manual describes specific instructions for a special function module for the QnACPU.
(sold separately) QnACPU PROGRAMMING MANUAL (AD57 Instructions)
This manual describes specific instructions for controlling the AD57(S1) type CRT controller module from the QnACPU.
(sold separately)
Manual number
(Type code)
SH-3599 (13J858)
Manual number
(Type code)
IB-66606 (13JF10)
IB-66614 (13JF46)
SH080039
(13JF58)
SH-4013 (13JF56)
IB-66617 (13JF49)
A-12
Manual title
QCPU(Q mode)/QnACPU PROGRAMMING MANUAL (PID Control Instructions)
This manual describes specific instructions for PID control for the QnACPU.
(sold separately)
QCPU(Q mode)/QnACPU PROGRAMMING MANUAL (SFC)
This manual describes the system configuration, performance specifications functions, programming, debugging procedures, and the error codes of the SW0SRX-SAP3 and SW0NX-SAP3.
(sold separately)
Ans Module type I/O User's Manual
This manual describes the specifications for the compact building block type I/O modules.
(sold separately)
Manual number
(Type code)
SH-080040
(13JF59)
SH-080041
(13JF60)
IB-66541 (13JF81)
A-13

1. SPECIFICATIONS

1.1 SPECIFICATIONS

Table 1.1 General specification
Item Specifications
Ambient operating temperature Ambient storage temperature Ambient operating humidity Ambient storage humidity
Frequency Acceleration Amplitude
Conforming
Vibration resistance
Shock resistance
Operating ambience No corrosive gases Operating elevation *3 2000m (6562ft.) max. Installation location Control panel Over voltage category *1 Pollution level *2 2 max. Equipment category Class I
to JIS B 3502, IEC 61131-2
Under intermitten t vibration
Under continuous vibration
(147 m/s
10 to 90 % RH, No-condensing
10 to 90 % RH, No-condensing
10 to 57Hz ⎯⎯
57 to 150Hz 9.8m/s
10 to 57Hz ⎯⎯
57 to 150Hz 4.9m/s
Conforming to JIS B 3502, IEC 61131-2
2
, 3 times in each of 3 directions X Y Z)
0 to 55 °C
20 to 75 °C
II max.
0.075mm (0.003in.)
2
⎯⎯
0.035mm (0.001in.)
2
⎯⎯
No. of
sweeps
10 times
each in
X, Y, Z
directions
(for 80min.)
*1: This indicates the section of the power supply to which the equipment is assumed to be
connected between the public electrical power distribution network and the machinery within premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.
*2: This index indicates the degree to which conductive material is generated in terms of the
environment in which the equipment is used. Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected occasionally.
*3: Do not use or store the programmable controller in the environment when the pressure is
higher than the atmospheric pressure at sea level. Otherwise, malfunction may result. To use the programmable controller in high-pressure environment, contact your nearest Mitsubishi representative.
1

2. PERFORMANCE SPECIFICATION

2.1 QnASCPU Module Performance Specification

Performance specification of Q2ASCPU module is as follows:
Item
Control method Repetitive operation of stored program
I/O control method Refresh mode
Programming language
Processing speed (sequence instructions)
Constant scan (Function that makes scan time constant)
Memory capacity Capacity of loading memory cards (2036 kbyte maximum)
Program capacity
I/O device points 8192 points (X/Y0 to 1FFF)
I/O points
Clock function
Allowable momentary power failure period 5 VDC Internal current consumption Mass 0.5 kg 0.5 kg 0.5 kg 0.5 kg External dimension 130(H) × 54.5(W) × 110(D) (5.12 × 2.15 × 4.33) mm (inch)
LD 0.2 s/step 0.075 s/step
MOV 0.6
Number of steps Number of files
Q2ASCPU Q2ASCPU-S1
Sequence control dedicated language
Relay symbol language, logic symbolic language, MELSAP3
s/step 0.225 s/step
5 to 2000 ms (configurable in multiple of 5 ms module)
28 k steps
maximum
28 files 60 files 28 files 60 files
512 points
(X/Y0 to 1FF)
Year, month, date, hour, minute, second, day of week
Accuracy : -1.7 to +4.9s (TYP. +1.7s) / d at 0 depress centigrade Accuracy : -1.0 to +5.2s (TYP. +2.2s) / d at 25 depress centigrade Accuracy : -7.3 to +2.5s (TYP. -1.9s) / d at 55 depress centigrade
0.3 A 0.3 A 0.7 A 0.7 A
60 k steps
maximum
1024 points
(X/Y0 to 3FF)
(auto-detects leap years)
By power supply module
Model
Q2ASHCPU Q2ASHCPU-S1
(SFC)
28 k steps
maximum
512 points
(X/Y0 to 1FF)
60 k steps
maximum
1024 points
(X/Y0 to 3FF)
Remark
I/O enabled by specifying direct I/O
, DY )
(DX
Set parameter values to specify
Number of usable points in program Number of points accessible to actual I/O modules
2

3. EMC DIRECTIVES AND LOW VOLTAGE DIRECTIVES

The products sold in the European countries have been required by law to comply with the EMC Directives and Low Voltage Directives of the EU Directives since 1996 and 1997, respectively. The manufacturers must confirm by self-declaration that their products meet the requirements of these directives, and put the CE mark on the products.

3.1 Requirements for Compliance with EMC Directives

The EMC Directives specifies emission and immunity criteria and requires the products to meet both of them, i.e., not to emit excessive electromagnetic interference (emission): to be immune to electromagnetic interference outside (immunity). Guidelines for complying the machinery including MELSEC-QnA series programmable controller with the EMC Directives are provided in Section 3.1.1 to
3.1.6 below. The guidelines are created based on the requirements of the regulations and relevant standards, however, they do not guarantee that the machinery constructed according to them will not comply with the Directives. Therefore, the manufacturer of the machinery must finally determine how to make it comply with the EMC Directives: if it is actually compliant with the EMC Directives.
3

3.1.1 EMC standards

When the programmable controller is installed following the directions given in this manual its EMC performance is compliant to the following standards and levels as required by the EMC directive.
Specifications Test Item Test Description Standard Values
30M-230 M Hz QP: 30dBμ V/m
EN61000-6-4 (2001)
EN61131-2/A12 (2000)
EN61000-6-2 (2001)
EN55011 *2 Radiated noise
EN55011 *2 Conduction noise
EN61000-4-2 *2 Static electricity immunity EN61000-4-4 *2 First transient burst noise
EN61000-4-12 *2 Damped oscillatory wave
EN61000-4-3 *2 Radiated electromagnetic field
EN61000-4-6 *2 Conduction noise
Measure the emission released by the product.
Measure the emission released by the product to the power line.
Immunity test by applying static electricity to the module enclosure. Immunity test by applying burst noise to the power line and signal line. Immunity test in which a damped oscillatory wave is superimposed on the power line. Immunity test by applying a radiated electric field to the product. Immunity test by inducting an electromagnetic field in the power line signal line.
(30m measurement) *1 230M-1000MHz QP: 37dBμ V/m (30m measurement) *1 150k-500kHz QP: 79dB, Mean: 66dB*1 500k-30MHz QP: 73dB, Mean: 60dB *1
4kV contact discharge 8kV air discharge
2kV Power line 1kv Signal line
1kv
10V/m, 26-1000MHz
10 V/ms, 0.15-80MHZ, 80% AM modulation@1kHz
1: QP: Quasi-peak value, Mean: Average value 2: The programmable controller is an open type device (device installed to
another device) and must be installed in a conductive control panel. The tests for the corresponding items were performed while the programmable controller was installed inside the control panel.
4

3.1.2 Installation instructions for EMC Directive

The programmable controller is open equipment and must be installed within a control cabinet for use.* This not only ensures safety but also ensues effective shielding of programmable controller-generated electromagnetic noise. * : Also, each network remote station needs to be installed inside the control
panel. However, the waterproof type remote station can be installed outside the control panel.
(1) Control cabinet
(a) Use a conductive control cabinet. (b) When attaching the control cabinet's top plate or base plate, mask
painting and weld so that good surface contact can be made between the cabinet and plate.
(c) To ensure good electrical contact with the control cabinet, mask the paint
on the installation bolts of the inner plate in the control cabinet so that contact between surfaces can be ensured over the widest possible area.
(d) Earth the control cabinet with a thick wire so that a low impedance
connection to ground can be ensured even at high frequencies.
(e) Holes made in the control cabinet must be 10 cm (3.94 in.) diameter or
less. If the holes are 10 cm (3.94 in.) or larger, radio frequency noise may be emitted.
(f) Lock the control panel so that only those who are trained and have
acquiredenough knowledge of electric facilities can open the control panel.
(2) Connection of power and earth wires
Earthing and power supply wires for the programmable controller system must be connected as described below. (a) Provide an earthing point near the power supply module. Earth the
power supply's LG and FG terminals (LG: Line Ground, FG: Frame Ground) with the thickest and shortest wire possible. (The wire length must be 30 cm (11.81 in.) or shorter.) The LG and FG terminals function is to pass the noise generated in the programmable controller system to the ground, so an impedance that is as low as possible must be ensured. In addition, make sure to wire the ground cable short as the wires are used to relieve the noise, the wire itself carries large noise content and thus short wiring means that the wire is prevented from acting as an antenna.
(b) The earth wire led from the earthing point must be twisted with the power
supply wires. By twisting with the earthing wire, noise flowing from the power supply wires can be relieved to the earthing. However, if a filter is installed on the power supply wires, the wires and the earthing wire may not need to be twisted.
5
n

3.1.3 Cables

The cables pulled out of the control panel contain a high frequency noise component. On the outside of the control panel, therefore, they serve as antennas to emit noise. Ensure to use shielded cables for the cables, which are connected to the I/O modules, special modules and those pulled out to outside of the control panel. Mounting ferrite core is not required except some types of CPU however, noise emanated via the cable can be restrained using it. The use of a shielded cable also increases noise resistance. The signal lines (including common line) connected to the programmable controller input/output modules and intelligent modules use shielded cables to assure noise resistance, as a condition, standardized on EN61131-2/A12 (2000). If a shielded cable is not used or not earthed correctly, the noise resistance will be less than the rated value
(1) Earthing of shielded of cables
(a) Earth the shield of the shielded cable as near the unit as possible taking
care so that the earthed cables are not induced electromagnetically by the cable to be earthed.
(b) Take appropriate measures so that the shield section of the shielded
cable from which the outer cover was partly removed for exposure is earthed to the control panel on an increased contact surface. A clamp may also be used as shown in the figure below. In this case, however, apply a cover to the painted inner wall surface of the control panel which comes in contact with the clamp.
Screw
Shield sectio
Clamp fitting
Paint mask
Shielded cable
Note) The method of earthing by soldering a wire onto the shield section of
the shielded cable as shown below is not recommended. The high frequency impedance will increase and the shield will be ineffective.
Shielded cable Wire
Crimp terminal
6
(2) MELSECNET (II) and MELSECNET/10 units
(a) Use a double-shielded coaxial cable for the MELSECNET unit which
uses coaxial cables. Noise in the range of 30 MHz or higher in radiation noise can be suppressed by the use of double-shielded coaxial cables (Mitsubishi Cable: 5C-2V-CCY). Earth the outer shield to the ground. The precautions on shielding to be followed are the same as those stated in item (1) above.
Earth this sectionShield
(b) Ensure to attach a ferrite core to the double-shielded coaxial cable
connected to the MELSECNET unit. In addition, position the ferrite core on each cable near the outlet of the control panel. TDK-make ZCAT3035 ferrite core is recommended.
(3) Ethernet module
Precautions to be followed when AUI cables and coaxial cables are used are described below. (a) Ensure to earth also the AUI cables connected to the 10BASE5
connectors of the A1SJ71QE71-B5. Because the AUI cable is of the shielded type, as shown in the figure below, partly remove the outer cover of it, and earth the exposed shield section to the ground on the widest contact surface.
AUI cable
Shield
(b) Use shielded twisted pair cables as the twisted pair cables*1 connected
to the 10BASE-T connectors. For the shielded twisted pair cables, strip part of the outer cover and earth the exposed shield section to the ground on the widest contact surface as shown below.
Shielded twisted pair cables
Shield
Refer to (1) for the earthing of the shield. *1: Make sure to install a ferrite core for the cable. As a ferrite core, ZCAT2035 manufactured by TDK is recommended.
7
(c) Always use double-shielded coaxial cables as the coaxial cables*2
connected to the 10BASE2 connectors. Earth the double-shielded coaxial cable by connecting its outer shield to the ground.
Earth hereShield
Refer to (1) for the earthing of the shield. *2: Make sure to install a ferrite core for the cable. As a ferrite core, ZCAT2035 manufactured by TDK is recommended.
Ethernet is the registered trademark of XEROX, Co.,LTD
(4) I/O and other communication cables
For the I/O signal lines (including common line) and other communication cables (RS-232, RS-422, etc), if extracted to the outside of the control panel, also ensure to earth the shield section of these lines and cables in the same manner as in item (1) above.
(5) Positioning Modules
Precautions to be followed when the machinery conforming to the EMC Directive is configured using the A1SD75P
-S3 are described below.
(a) When wiring with a 2 m (6.56 ft.) or less cable
• Ground the shield section of the external wiring cable with the cable clamp. (Ground the shield at the closest location to the A1SD75 external wiring connector.)
• Wire the external wiring cable to the drive unit and external device with the shortest practicable length of cable.
• Install the drive unit in the same panel.
y
l p
e
p
l
u
u
s
d
r
o
e
m
w o P
e
l
5
e
u
l
7
d
u
D
o
d
S
o
m
1
m
A
U P C
External wiring connector
Cable clamp
External wiring cable (within 2 m (6.56 ft.))
Drive unit
8
(b) When wiring with cable that exceeds 2 m (6.56 ft.), but is 10 m (32.81 ft.)
or less
• Ground the shield section of the external wiring cable with the cable clamp. (Ground the shield at the closest location to the A1SD75 external wiring connector.)
• Install a ferrite core.
• Wire the external wiring cable to the drive unit and external device with the shortest practicable length of cable.
y
l p
e
p
l
u
u
s
d
r
o
e
m
w o P
e
l
5
u
e
7
l
d
u
D
o
d
S
o
m
1
m
A
U P C
External wiring connector
Ferrite core Cable clamp
External wiring cable (2 m to 10 m (6.56 ft. to 32.81 ft.))
Drive unit
(c) Ferrite core and cable clamp types and required quantities
• Cable clamp Type: AD75CK (Mitsubishi Electric)
• Ferrite core Type: ZCAT3035-1330 (TDK ferrite core)
• Required quantity
Cable length Prepared part
Within 2 m (6.56 ft.) AD75CK 1 1 1
2 m (6.56 ft.) to 10m (32.81 ft.)
AD75CK 1 1 1 ZCAT3035-1330 1 2 3
1 axis 2 axes 3 axes
Inside control panel
A1SD75
Required Qty
20 30cm
AD75CK
(7.87 11.81inch)
9
(6) CC-Link Module
(a) Be sure to ground the cable shield that is connected to the CC-Link
module close to the exit of control panel or to any of the CC-Link stations within 30 cm (11.81 in.) from the module or stations. The CC-Link dedicated cable is a shielded cable. As shown in the illustration below, remove a portion of the outer covering and ground as large a surface area of the exposed shield part as possible.
CC-Link dedicated cable Shield
(b) Always use the specified CC-Link dedicated cable. (c) The CC-Link module, the CC-Link stations and the FG line inside the
control panel should be connected at the FG terminal as shown in the diagram below.
[Simplified diagram]
Local module
DA DB
Terminal
DG
SLD
resistor
FG
Terminal resistor
Master module
(Blue)
DA
(White)
DB
(Yellow)
DG
SLD
FG
CC-Link
dedicated
cable
Remote module
DA DB
DG
SLD
FG
CC-Link
dedicated
cable
(d) Power line connecting to the external power supply terminal (compliant
with I/O power port of CE standard) should be 30m (98.43 ft.) or less. Power line connecting to module power supply terminal (compliant with main power port of CE standard) should be 10m (32.81 ft.) or less.
(e) A power line connecting to the analog input of the following modules
should be 30cm or less.
AJ65BT-64RD3
AJ65BT-64RD4
AJ65BT-68TD
(7) Measures against static electricity
When using an insulation displacement connector without connector cover, a connected cable for the connector is thin in applicable wire size and coating. Therefore, note that the module may cause an electric discharge failure. As measures against the failure, using pressure-displacement type connector whose applicable wire size is thick or soldering type connector is recommended.
10

3.1.4 Power supply module

The precautions required for each power supply module are described below. Always observe the items noted as precautions.
Model Precautions
A1S61PN, A1S62PN
A1S63P 1
Make sure to short and ground the LG and FG terminals. Use the 24VDC panel power equipment conforming to the EU Directive.
2
1: If sufficient filter circuitry is built into the 24 VDC external power supply
module, the noise generated by A1S63P will be absorbed by that filter circuit, so a line filter may not be required. Filtering circuitry of version F or later of A1S63P is improved so that a external line filter is not required.
2: To ensure the compliance with CE (EN6111-21/A11), make sure to short
the LG and FG terminals using a wire of 6 to 7cm.

3.1.5 Base unit

The following table shows models of base units that are compatible with EMC instructions.
Type Model name Applicability
Main base unit
A1S38HBEU Applicable A1S3
B, A1S38HB Not applicable
Extension base unit A1S5 B(S1), A1S6 B(S1) Applicable

3.1.6 Ferrite core

Use of ferrite cores is effective in reducing the conduction noise in the band of about 10 MHz and radiated noise in 30 to 100 MHz band. It is recommended to attach ferrite cores when the shield of the shielded cable coming out of control panel does not work effectively, or when emission of the conduction noise from the power line has to be suppressed.*1 The ferrite cores used in our tests are TDK's ZCAT3035. It should be noted that the ferrite cores should be fitted to the cables in the position immediately before they are pulled out of the enclosure. If the fitting position is improper, the ferrite will not produce any effect.
1:To response with CE (EN61131-2/A12), make sure to mount 2 or more
ferrite cores onto the power supply line. The mounting position should be as near the power supply module as possible. Ferrite core Type: ZCAT2235-1030A (TDK ferrite core)
11

3.1.7 Noise filter (power supply line filter)

A noise filter is a component which has an effect on conducted noise. With the exception of some models, it is not required to fit the noise filter to the power supply line, but fitting it can further suppress noise. (The noise filter has the effect of reducing conducted noise of 10 M Hz or less.) Use any of the following noise filters (double
type filters) or equivalent.
Model name FN343-3/01 FN660-6/06 ZHC2203-11
Manufacturer SCHAFFNER SCHAFFNER TDK
Rated current 3 A 6 A 3 A
Rated voltage 250 V
The precautions required when installing a noise filter are described below.
(1) Do not bundle the wires on the input side and output side of the noise filter.
When bundled, the output side noise will be induced into the input side wires from which the noise was filtered.
Input side
(power supply side)
Induction
Filter
Input side
(power supply side)
Filter
Output side
(device side)
Output side
(device side)
(a) The noise will be
included when the input
(b) Separate and lay the
input and output wires. and output wires are bundled.
(2) Earth the noise filter earthing terminal to the control cabinet with the shortest
wire possible (approx. 10 cm (3.94 in.)).
12

3.2 Requirements for Compliance with Low Voltage Directives

The Low Voltage Directives apply to the electrical equipment operating from 50 to 1000VAC or 75 to 1500VDC; the manufacturer must ensure the adequate safety of the equipment. Guidelines for installation and wiring of MELSEC-QnA series programmable controller are provided in Section 3.2.1 to 3.2.7 for the purpose of compliance with the EMC Directives. The guidelines are created based on the requirements of the regulations and relevant standards, however, they do not guarantee that the machinery constructed according to them will comply with the Directives. Therefore, the manufacturer of the machinery must finally determine how to make it comply with the EMC Directives: if it is actually compliant with the EMC Directives.

3.2.1 Standard applied for MELSEC-QnA series programmable controller

The standard applied for MELSEC-QnA series programmable controller series is EN61010-1 safety of devices used in measurement rooms, control rooms, or laboratories.
For the modules which operate with the rated voltage of 50 VAC/75 VDC or above, we have developed new models that conform to the above standard. For the modules which operate with the rated voltage under 50 VAC/75 VDC, the conventional models can be used, because they are out of the low voltage directive application range.

3.2.2 Precautions when using the MELSEC-QnA series programmable controller

Module selection (1) Power module
For a power module with rated input voltage of 100/200 VAC, select a model in which the internal part between the first order and second order is intensively insulated, because it generates hazardous voltage (voltage of 42.4 V or more at the peak) area. For a power module with 24 VDC rated input, a conventional model can be used.
(2) I/O module
For I/O module with rated input voltage of 100/200 VAC, select a model in which the internal area between the first order and second order is intensively insulated, because it has hazardous voltage area. For I/O module with 24 VDC rated input, a conventional model can be used.
(3) CPU module, memory cassette, base unit
Conventional models can be used for these modules, because they only have a 5 VDC circuit inside.
(4) Special function module
Conventional models can be used for the special modules including analog module, network module, and positioning module, because the rated voltage is 24 VDC or smaller.
(5) Display device
Use the CE-marked product.
13

3.2.3 Power supply

The insulation specification of the power module was designed assuming installation category II. Be sure to use the installation category II power supply to the programmable controller. The installation category indicates the durability level against surge voltage generated by a thunderbolt. Category I has the lowest durability; category IV has the highest durability.
Category III Category II Category ICategory IV
Figure 1.: Installation Category
Category II indicates a power supply whose voltage has been reduced by two or more levels of isolating transformers from the public power distribution.
14

3.2.4 Control panel

Because the programmable controller is an open device (a device designed to be stored within another module), be sure to use it after storing in the control panel.
(1) Electrical shock prevention
In order to prevent persons who are not familiar with the electric facility such as the operators from electric shocks, the control panel must have the following functions:
(a) The control panel must be equipped with a lock so that only the personnel
who has studied about the electric facility and have enough knowledge can open it.
(b) The control panel must have a structure which automatically stops the
power supply when the box is opened.
(c) For electric shock protection, use IP20 or greater control panel.
(2) Dustproof and waterproof features
The control panel also has the dustproof and waterproof functions. Insufficient dustproof and waterproof features lower the insulation withstand voltage, resulting in insulation destruction. The insulation in our programmable controller is designed to cope with the pollution level 2, so use in an environment with pollution level 2 or below.
Pollution level 1: An environment where the air is dry and conductive dust
does not exist.
Pollution level 2: An environment where conductive dust
does not usually exist, but occasional temporary conductivity occurs due to the accumulated dust. Generally, this is the level for inside the control panel equivalent to IP54 in a control room or on the floor of a typical factory.
Pollution level 3: An environment where conductive dust exits and
conductivity may be generated due to the accumulated dust. An environment for a typical factory floor.
Pollution level 4: Continuous conductivity may occur due to rain, snow, etc.
An outdoor environment.
As shown above, the programmable controller can realize the pollution level 2
when stored in a control panel equivalent to IP54.
15
Loading...