Mitsubishi PUHY-RP_Y(S)JM-A, PURY-RP_YJM-A DATA BOOK

MODEL
DATA BOOK
REPLACE MULTI
1.OUTDOOR UNIT
Y SERIES ................................................................................................................. 1
R2 SERIES............................................................................................................. 57
3.SYSTEM DESIGN
Y SERIES ............................................................................................................. 177
R2 SERIES........................................................................................................... 229
4.CONTROLLER ................................................................................................. 273
Y SERIES
OUTDOOR UNITS
I.Y SERIES
1. SPECIFICATIONS........................................................................................................................................... 2
2. EXTERNAL DIMENSIONS .............................................................................................................................. 15
3. CENTER OF GRAVITY ................................................................................................................................... 19
4. ELECTRICAL WIRING DIAGRAMS................................................................................................................ 20
5. SOUND LEVELS ............................................................................................................................................. 21
6. CAPACITY TABLES........................................................................................................................................ 25
6-1. Correction by temperature....................................................................................................................... 25
6-2. Correction by total indoor......................................................................................................................... 35
6-3. Correction by refrigerant piping length..................................................................................................... 39
6-4. Correction at frost and defrost ................................................................................................................. 42
6-5. Operation temperature range .................................................................................................................. 43
7. OPTIONAL PARTS.......................................................................................................................................... 44
7-1. OUTDOOR TWINNING KIT..................................................................................................................... 44
8. UNIT SELECTION........................................................................................................................................... 45
8-1. Indoor and outdoor unit selection ............................................................................................................ 45
8-2. Calculation samples................................................................................................................................. 47
8-3. Pipe diameter correction factor ................................................................................................................ 50
OUTDOOR UNITS
1
1. SPECIFICATIONS
I.Y SERIES1. SPECIFICATIONS
Model PUHY-RP200YJM-A(-BS) PUHY-RP250YJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 22.4 28.0
(Nominal) *1 kcal / h 19,300 24,100
*1 BTU / h 76,400 95,500
Power input kW 5.68 8.28
Current input A 9.5-9.1-8.7 13.9-13.2-12.7
COP kW / kW 3.94 3.38
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F) 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F) -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 25.0 31.5
(Nominal) *2 kcal / h 21,500 27,100
Power input kW 5.69 7.83
Current input A 9.6-9.1-8.7 13.2-12.5-12.1
COP kW / kW 4.39 4.02
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F) 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F) -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~17 P15~P250 / 1~21
Sound pressure level (measured in anechoic room) dB <A> 56 57
Refrigerant Liquid pipe mm (in.) 12.7(1/2) Brazed 12.7(1/2) Brazed
piping diameter Gas pipe mm (in.) 28.58(1-1/8) Brazed 28.58(1-1/8) Brazed
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 4.8 6.8
Case heater kW 0.035(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 6.5kg (15lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit LEV and HIC circuit
Net weight kg (lbs) 230(508) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C666 KD94C666
Wiring KE94C427 KE94C427
Standard attachment Document Installation Manual Installation Manual
Accessory Refrigerant conn. pipe Refrigerant conn. pipe
Optional parts
*2 BTU / h 85,300 107,500
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5 Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
Header: CMY-Y104/108/1010-G Header: CMY-Y104/108/1010-G
type)
(601,479 psi)
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pressure switch at 4.15,3.3MPa
type)
(601,479 psi)
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS 2
1. SPECIFICATIONS
Model PUHY-RP300YJM-A(-BS) PUHY-RP350YJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 33.5 40.0
(Nominal) *1 kcal / h 28,800 34,400
*1 BTU / h 114,300 136,500
Power input kW 9.37 12.28
Current input A 15.8-15.0-14.4 20.7-19.6-18.9
COP kW / kW 3.57 3.25
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F) 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F) -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 37.5 45.0
(Nominal) *2 kcal / h 32,300 38,700
Power input kW 9.86 13.12
Current input A 16.6-15.8-15.2 22.1-21.0-20.2
COP kW / kW 3.80 3.42
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F) 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F) -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~26 P15~P250 / 1~30
Sound pressure level (measured in anechoic room) dB <A> 59 60
Refrigerant Liquid pipe mm (in.) 12.7(1/2) Brazed 15.88(5/8) Brazed
piping diameter Gas pipe mm (in.) 28.58(1-1/8) Brazed 34.93(1-3/8) Brazed
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 8.2 9.9
Case heater kW 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Control LEV and HIC circuit LEV and HIC circuit
Net weight kg (lbs) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C666 KD94C666
Wiring KE94C427 KE94C427
Standard attachment Document Installation Manual Installation Manual
Accessory Refrigerant conn. pipe Refrigerant conn. pipe
Optional parts
*2 BTU / h 128,000 153,500
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
Header: CMY-Y104/108/101 0-G Header: CMY-Y104/108/101 0-G
type)
(601,479 psi)
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pre ssure switch at 4.15,3.3MPa
type)
(601,479 psi)
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guar antee reliability of pre-existing pipes and pre-existing cables.
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS
3
1. SPECIFICATIONS
Model PUHY-RP400YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 45.0
(Nominal) *1 kcal / h 38,700
*1 BTU / h 153,500
Power input kW 11.87
Current input A 20.0-19.0-18.3
COP kW / kW 3.79
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 50.0
(Nominal) *2 kcal / h 43,000
Power input kW 11.38
Current input A 19.2-18.2-17.5
COP kW / kW 4.39
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 59
Refrigerant Liquid pipe mm (in.) 15.88(5/8) Brazed
piping diameter Gas pipe mm (in.) 34.93(1-3/8) Brazed
Set Model
Model PUHY-RP200YJM-A(-BS) PUHY-RP200YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Refrigerant Type x original charge R410A x 6.5kg (15lbs) R410A x 6.5kg (15lbs)
Net weight kg (lbs) 230(508) 230(508)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed
distributor Gas pipe mm (in.) 19.05(3/4) Brazed 19.05(3/4) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 4.8 4.8
Case heater kW 0.035(240 V) 0.035(240 V)
Lubricant MEL32 MEL32
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Control LEV and HIC circuit
Wiring KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 170,600
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5 Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
type)
(601,479 psi)
Header: CMY-Y104/108/1010-G
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pressure switch at 4.15,3.3MPa
type)
(601,479 psi)
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS 4
1. SPECIFICATIONS
Model PUHY-RP450YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-41 5V 50/60Hz
Cooling capacity *1 kW 50.0
(Nominal) *1 kcal / h 43,000
*1 BTU / h 170,600
Power input kW 14.40
Current input A 24.3-23.0-22.2
COP kW / kW 3.47
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 56.0
(Nominal) *2 kcal / h 48,200
Power input kW 13.42
Current input A 22.6-21.5-20.7
COP kW / kW 4.17
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 59.5
Refrigerant Liquid pipe mm (in.) 15.88(5/8) Brazed
piping diameter Gas pipe mm (in.) 34.93(1-3/8) Brazed
Set Model
Model PUHY-RP200YJM-A(-BS) PUHY-RP250YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Refrigerant Type x original charge R410A x 6.5kg (15lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 230(508) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed
distributor Gas pipe mm (in.) 19.05(3/4) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 4.8 6.8
Case heater kW 0.035(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Control LEV and HIC circuit
Wiring KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 191,100
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guar antee reliability of pre-existing pipes and pre-existing cables.
type)
(601,479 psi)
Header: CMY-Y104/108/101 0-G
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pre ssure switch at 4.15,3.3MPa
type)
(601,479 psi)
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS
5
1. SPECIFICATIONS
Model PUHY-RP500YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 56.0
(Nominal) *1 kcal / h 48,200
*1 BTU / h 191,100
Power input kW 16.96
Current input A 28.6-27.1-26.2
COP kW / kW 3.30
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 63.0
(Nominal) *2 kcal / h 54,200
Power input kW 15.67
Current input A 26.4-25.1-24.2
COP kW / kW 4.02
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 60
Refrigerant Liquid pipe mm (in.) 15.88(5/8) Brazed
piping diameter Gas pipe mm (in.) 34.93(1-3/8) Brazed
Set Model
Model PUHY-RP250YJM-A(-BS) PUHY-RP250YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 6.8 6.8
Case heater kW 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Control LEV and HIC circuit
Wiring KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 215,000
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5 Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
type)
(601,479 psi)
Header: CMY-Y104/108/1010-G
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pressure switch at 4.15,3.3MPa
type)
(601,479 psi)
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS 6
1. SPECIFICATIONS
Model PUHY-RP550YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-41 5V 50/60Hz
Cooling capacity *1 kW 63.0
(Nominal) *1 kcal / h 54,200
*1 BTU / h 215,000
Power input kW 18.58
Current input A 31.3-29.7-28.7
COP kW / kW 3.39
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 69.0
(Nominal) *2 kcal / h 59,300
Power input kW 17.69
Current input A 29.8-28.3-27.3
COP kW / kW 3.90
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 61
Refrigerant Liquid pipe mm (in.) 15.88(5/8) Brazed
piping diameter Gas pipe mm (in.) 34.93(1-3/8) Brazed
Set Model
Model PUHY-RP250YJM-A(-BS) PUHY-RP300YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) B razed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 6.8 8.2
Case heater kW 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Control LEV and HIC circuit
Wiring KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 235,400
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guar antee reliability of pre-existing pipes and pre-existing cables.
type)
(601,479 psi)
Header: CMY-Y104/108/101 0-G
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pre ssure switch at 4.15,3.3MPa
type)
(601,479 psi)
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS
7
1. SPECIFICATIONS
Model PUHY-RP600YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 69.0
(Nominal) *1 kcal / h 59,300
*1 BTU / h 235,400
Power input kW 19.94
Current input A 33.6-31.9-30.8
COP kW / kW 3.46
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 76.5
(Nominal) *2 kcal / h 65,800
Power input kW 20.13
Current input A 33.9-32.2-31.1
COP kW / kW 3.80
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 62
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 34.93(1-3/8) Brazed
Set Model
Model PUHY-RP300YJM-A(-BS) PUHY-RP300YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7(1/2) Brazed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 8.2 8.2
Case heater kW 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Control LEV and HIC circuit
Wiring KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 261,000
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5 Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
type)
(601,479 psi)
Header: CMY-Y104/108/1010-G
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pressure switch at 4.15,3.3MPa
type)
(601,479 psi)
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS 8
1. SPECIFICATIONS
Model PUHY-RP650YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-41 5V 50/60Hz
Cooling capacity *1 kW 73.0
(Nominal) *1 kcal / h 62,800
*1 BTU / h 249,100
Power input kW 22.00
Current input A 37.1-35.2-34.0
COP kW / kW 3.31
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 81.5
(Nominal) *2 kcal / h 70,100
Power input kW 22.70
Current input A 38.3-36.4-35.0
COP kW / kW 3.59
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 62.5
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP300YJM-A(-BS) PUHY-RP350YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7(1/2) B razed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 28.58(1-1/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP100VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 8.2 9.9
Case heater kW 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch
Control LEV and HIC circuit
Wiring KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 278,100
L/s 3,083 3,083
cfm 6,532 6,532
Pre-coated galvanized steel sheets (+powder coating for -BS
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in. 67-3/8(65 without legs) x 36-1/4 x 29-15/16 67-3/8(65 without legs) x 36-1/4 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.3MPa
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guar antee reliability of pre-existing pipes and pre-existing cables.
type)
(601,479 psi)
Header: CMY-Y104/108/101 0-G
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pre ssure switch at 4.15,3.3MPa
type)
(601,479 psi)
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS
9
1. SPECIFICATIONS
Model PUHY-RP700YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 80.0
(Nominal) *1 kcal / h 68,800
*1 BTU / h 273,000
Power input kW 23.59
Current input A 39.8-37.8-36.4
COP kW / kW 3.39
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 88.0
(Nominal) *2 kcal / h 75,700
Power input kW 21.35
Current input A 36.0-34.2-33.0
COP kW / kW 4.12
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 61.5
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP200YJM-A(-BS) PUHY-RP250YJM-A(-BS) PUHY-RP250YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture
Starting method Inverter Inverter Inverter
Motor output kW 4.8 6.8 6.8
Case heater kW 0.035(240 V) 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32 MEL32
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Inverter circuit (COMP. / FAN)
Compressor Over- heat protection Over-heat protection Over -heat protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 6.5kg (15lbs) R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 230(508) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed 9.52(3/8) Brazed
distributor Gas pipe mm (in.) 19.05(3/4) Brazed 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP200VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Control LEV and HIC circuit
Wiring KE94C427 KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 300,300
L/s 3,083 3,083 3,083
cfm 6,532 6,532 6,532
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in.
67-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
tection
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Ove r-current pro-
Header: CMY-Y104/108/1010-G
tection
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
kcal =kW x 860 BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg / 0.4536 *The specification data is subject to rounding variation.
16
tection
OUTDOOR UNITS 10
1. SPECIFICATIONS
Model PUHY-RP750YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 85.0
(Nominal) *1 kcal / h 73,100
*1 BTU / h 290,000
Power input kW 25.70
Current input A 43.3-41.2-39.7
COP kW / kW 3.30
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 95.0
(Nominal) *2 kcal / h 81,700
Power input kW 23.63
Current input A 39.8-37.8-36.5
COP kW / kW 4.02
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 62
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP250YJM-A(-BS) PUHY-RP250YJM-A(-BS) PUHY-RP250YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture
Starting method Inverter Inverter Invert er
Motor output kW 6.8 6.8 6.8
Case heater kW 0.045(240 V) 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32 MEL32
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Inverter circuit (COMP. / FAN)
Compressor Over-heat protection Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed 9.52(3/8) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP200VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Control LEV and HIC circuit
Wiring KE94C427 KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 324,100
L/s 3,083 3,083 3,083
cfm 6,532 6,532 6,532
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in.
67-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guar antee reliability of pre-existing pipes and pre-existing cables.
tection
AC&R Works, MITSUBISHI ELECTRIC
Over-heat protection, Over-current pro-
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
tection
Header: CMY-Y104/108/1010-G
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
kcal =kW x 860 BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg / 0.4536 *The specification data is subject to rounding variation.
16
tection
OUTDOOR UNITS
11
1. SPECIFICATIONS
Model PUHY-RP800YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 90.0
(Nominal) *1 kcal / h 77,400
*1 BTU / h 307,100
Power input kW 27.19
Current input A 45.9-43.6-42.0
COP kW / kW 3.31
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 100.0
(Nominal) *2 kcal / h 86,000
Power input kW 25.44
Current input A 42.9-40.7-39.3
COP kW / kW 3.93
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 62.5
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP250YJM-A(-BS) PUHY-RP250YJM-A(-BS) PUHY-RP300YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture
Starting method Inverter Inverter Inverter
Motor output kW 6.8 6.8 8.2
Case heater kW 0.045(240 V) 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32 MEL32
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Inverter circuit (COMP. / FAN)
Compressor Over- heat protection Over-heat protection Over -heat protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 9.52(3/8) Brazed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP200VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Control LEV and HIC circuit
Wiring KE94C427 KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 341,200
L/s 3,083 3,083 3,083
cfm 6,532 6,532 6,532
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in.
67-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
tection
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Ove r-current pro-
Header: CMY-Y104/108/1010-G
tection
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
kcal =kW x 860 BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg / 0.4536 *The specification data is subject to rounding variation.
16
tection
OUTDOOR UNITS 12
1. SPECIFICATIONS
Model PUHY-RP850YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 96.0
(Nominal) *1 kcal / h 82,600
*1 BTU / h 327,600
Power input kW 28.57
Current input A 48.2-45.8-44.1
COP kW / kW 3.36
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 108.0
(Nominal) *2 kcal / h 92,900
Power input kW 27.97
Current input A 47.2-44.8-43.2
COP kW / kW 3.86
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 63.5
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP250YJM-A(-BS) PUHY-RP300YJM-A(-BS) PUHY-RP300YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture
Starting method Inverter Inverter Invert er
Motor output kW 6.8 8.2 8.2
Case heater kW 0.045(240 V) 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32 MEL32
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Inverter circuit (COMP. / FAN)
Compressor Over-heat protection Over-heat protection Over-heat protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52(3/8) Brazed 12.7(1/2) Brazed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP200VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Control LEV and HIC circuit
Wiring KE94C427 KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 368,500
L/s 3,083 3,083 3,083
cfm 6,532 6,532 6,532
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in.
67-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guar antee reliability of pre-existing pipes and pre-existing cables.
tection
AC&R Works, MITSUBISHI ELECTRIC
Over-heat protection, Over-current pro-
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
tection
Header: CMY-Y104/108/1010-G
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
kcal =kW x 860 BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg / 0.4536 *The specification data is subject to rounding variation.
16
tection
OUTDOOR UNITS
13
1. SPECIFICATIONS
Model PUHY-RP900YSJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 101.0
(Nominal) *1 kcal / h 86,900
*1 BTU / h 344,600
Power input kW 29.61
Current input A 49.9-47.4-45.7
COP kW / kW 3.41
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 113.0
(Nominal) *2 kcal / h 97,200
Power input kW 29.73
Current input A 50.1-47.6-45.9
COP kW / kW 3.80
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~130 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~32
Sound pressure level (measured in anechoic room) dB <A> 64
Refrigerant Liquid pipe mm (in.) 19.05(3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28(1-5/8) Brazed
Set Model
Model PUHY-RP300YJM-A(-BS) PUHY-RP300YJM-A(-BS) PUHY-RP300YJM-A(-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3 / min 185 185 185
Control , Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture
Starting method Inverter Inverter Inverter
Motor output kW 8.2 8.2 8.2
Case heater kW 0.045(240 V) 0.045(240 V) 0.045(240 V)
Lubricant MEL32 MEL32 MEL32
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760 1,710(1,650 without legs) x 920 x 760
Protection devices High pressure protection
Inverter circuit (COMP. / FAN)
Compressor Over- heat protection Over-heat protection Over -heat protection
Fan motor Thermal switch Thermal switch Thermal switch
Refrigerant Type x original charge R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs) R410A x 9.0kg (20lbs)
Net weight kg (lbs) 255(563) 255(563) 255(563)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure Copper pipe,tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7(1/2) Brazed 12.7(1/2) Brazed 12.7(1/2) Brazed
distributor Gas pipe mm (in.) 22.2(7/8) Brazed 22.2(7/8) Brazed 22.2(7/8) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C667
Standard attachment Document Installation Manual
Optional parts Outdoor Twinning kit: CMY-RP200VBK
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes : Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Control LEV and HIC circuit
Wiring KE94C427 KE94C427 KE94C427
Accessory Refrigerant conn. pipe
*2 BTU / h 385,600
L/s 3,083 3,083 3,083
cfm 6,532 6,532 6,532
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar> <MUNSELL 5Y 8/1 or similar>
in.
67-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/1667-3/8(65 without legs) x 36-1/4 x 29-15/
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
tection
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Ove r-current pro-
Header: CMY-Y104/108/1010-G
tection
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
Pre-coated galvanized steel sheets
(+powder coating for -BS type)
High pressure sensor, High pressure
switch at 4.15,3.3MPa (601,479 psi)
Over-heat protection, Over-current pro-
kcal =kW x 860 BTU/h =kW x 3,412 cfm =m3/min x 35.31 lbs =kg / 0.4536 *The specification data is subject to rounding variation.
16
tection
OUTDOOR UNITS 14
2. EXTERNAL DIMENSIONS
172
143
142
ø15.88 Brazed
(
ø12.7 Brazed) (ø28.58 Brazed)
ø34.93 Brazed
ø12.7 Brazed
ø28.58 Brazed
(
ø22.2 Brazed)
ø28.58 Brazed
(
ø19.05 Brazed)
PUHY-RP350YJM-A(-BS)
PUHY-RP300YJM-A(-BS)
ø12.7 Brazed
(
ø9.52 Brazed)
BA
GasLiquid
GasLiquid
Connection specifications for
the refrigerant service valve
PUHY-RP250YJM-A(-BS)
PUHY-RP200YJM-A(-BS)
Position dimensions
for the refrigerant
service valve
(Mounting pitch)
(Mounting pitch)
Refrigerant service
valve <gas>
Refrigerant service
valve <liquid>
Model
Connecting pipe specifications
2×2-14×20 Oval hole
Refrigerant service
valve <gas>
Refrigerant service
valve <liquid>
ø34 Knockout hole
ø52 Knockout hole
ø52 or ø27 Knockout hole
ø65 or ø40 Knockout hole
150 × 92 Knockout hole
102 × 72 Knockout hole
Front through hole
Bottom through hole
Front through hole
Front through hole
Bottom through hole
Front through hole
For transmission cables
For wires
For pipes
SpecificationsUsage
NO.
Note1. Please refer to (2/2) for information
regarding necessary spacing around the
unit and foundation work.
2. The detachable leg can be removed at site.
3. At brazing of pipes, wrap the refrigerant service valve
with wet cloth and keep the temperature of
refrigerant service valve under 120°C.
<Accessories>
Connecting pipe
<Gas> · Elbow (IDø25.4 × ODø25.4)
· Pipe (IDø25.4 × ODø19.05)
· Pipe (IDø25.4 × ODø22.2)
· Pipe (IDø25.4 × ODø28.58)
· Pipe (IDø25.4 × ODø34.93)
<Liquid>
· Pipe (IDø9.52 × ODø9.52)
· Pipe (IDø9.52 × ODø12.7)
· Pipe (IDø12.7 × ODø12.7)
· Pipe (IDø12.7 × ODø15.88)
···RP200, RP250, RP300, RP350
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
···RP200
···RP250, RP300
···RP200, RP250, RP300, RP350
···RP350
···RP200, RP250, RP300
···RP200, RP250, RP300
···RP350
···RP350
*2 *2
*2
*2
*2
221 150
145
*1
*1 Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied.
*2 Indicates dimensions and connection specifications in the case the unit is
used in combination with other outdoor units.
83
(front and back, 2 points)
Note 2*
5555
60 60
760
A
B
(60)
Detachable leg
(60)
1710
72
(760)
Control box
80 760 80
18
724 (721~727)
18
92 86
131
251
186
132
6
5
4
3
2
1
25
Intake
air
90
204
102
251
240
Intake
air
Service
panel
1410
1650
760
920
88
25
54
Intake
air
Discharge air
145
98
Front view
Left side view
Top view
Bottom view
PUHY-RP200, 250, 300, 350YJM-A (-BS)
Unit : mm
2. EXTERNAL DIMENSIONS
OUTDOOR UNITS
15
2. EXTERNAL DIMENSIONS
Secure enough space around the unit as shown in the figure below.
When the height of the walls on the front, back or on the sides <H>
exceeds the wall height limit as defined below, add the height
that exceeds the height limit <h> to the figures that are marked
with an asterisk.
1. Required space around the unit
In case of single installation
2. Foundation work
<Wall height limit> Front: Up to the unit height
Back: Up to 500 mm from
the unit bottom
Side: Up to the unit height
<field supply required>
<field supply required>
Detachable leg
Detachable leg
Corner of the
installation leg
M10 anchor bolt
<field supply required>
30 mm max.
• With a space of at least
300 mm to the wall on
the back of the unit
With a space of at least
100 mm to the wall on
the back of the unit
30 mm max.
<Side view>
H
h
h
H
Front
<Top view> <Top view>
Front
Corner of the
installation leg
M10 anchor bolt
<field supply required>
Front
Unit height
<To be left open>
<To be left open>
<To be left open>
<To be left open>
<To be left open>
<To be left open>
<To be left open>
30 min.
450 min.
450 min.
15 min.*
15 min.*
50 min.*
50 min.*
300 min.*
450 min.*
100 min.*
450 min.*
300 min.*450 min.*
100 min.*450 min.*
100 min.
450 min.*
450 min.
450 min.
100 min.*
15 min.*
300 min.*900 min.300 min.*
300 min.*900 min.
1000 min.*
500
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
Refer to the Installation Manual when installing units on an installation base.
In case of collective installation
When multiple units are installed adjacent to each other, secure enough space to allow
for air circulation and walkway between groups of units as shown in the figures below.
At least two sides must be left open.
As with the single installation, add the height that exceeds the height limit <h>
to the figures that are marked with an asterisk.
If there is a wall at both the front and the rear of the unit, install up to six units
consecutively in the side direction and provide a space of 1000 mm or more as inlet space/
passage space for each six units.
Take into consideration the surface strength, water drainage route,
piping route, and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
Build the foundation in such way that the corner of the installation leg is
securely supported as shown in the right figure. (Fig.A, B)
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
The protrusion length of the anchor bolt must not exceed 30 mm. (Fig.A, B)
Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts. (Fig.C, D)
To prevent small animals and water and snow from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
<Unit: mm>
Front
Front
Wall <H>
Wall <H>
Wall <H>
Wall <H>
Wall <H>
Wall <H> Wall <H>
Wall <H>
<To be left open>
<To be left open>
Front
<To be left open>
<Unit: mm>
Front
Wall <H>
Wall <H>
Front
Front
Front
Front
Front
Front
Fixing plate
Fixing plate
Fig.D (with detachable legs)
Fig.C (without detachable legs)
Fig.B (with detachable legs)
Fig.A (without detachable legs)
PUHY-RP200, 250, 300, 350YJM-A (-BS)
Unit : mm
OUTDOOR UNITS 16
2. EXTERNAL DIMENSIONS
Detachable leg
Note 2*
Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. The detachable leg can be removed at site.
3. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
4. The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500 mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
5. Only use the Twinning pipe by Mitsubishi (optional parts).
ø19.05
ø41.28
a
Outdoor unit 2
760
920 30 920
ø9.52
RP350
ø28.58ø12.7
RP300
ø22.2ø12.7
RP250
PUHY-RP300YJM-A(-BS)
PUHY-RP350YJM-A(-BS)
PUHY-RP650YSJM-A(-BS)
PUHY-RP300YJM-A(-BS)
PUHY-RP300YJM-A(-BS)
PUHY-RP600YSJM-A(-BS)
PUHY-RP250YJM-A(-BS)
PUHY-RP300YJM-A(-BS)
PUHY-RP550YSJM-A(-BS)
PUHY-RP250YJM-A(-BS)
PUHY-RP250YJM-A(-BS)
PUHY-RP500YSJM-A(-BS)
PUHY-RP200YJM-A(-BS)
PUHY-RP250YJM-A(-BS)
PUHY-RP450YSJM-A(-BS)
Twinning pipe~Outdoor unit
d or f
Gas
Liquid
c or e
RP200
Unit model
b
Gas
Liquid
Outdoor unit 1
ø9.52 ø19.05
ø22.2
(60)
1650
1710
Intake
air
Outdoor unit 2Outdoor unit 1
Discharge air
Intake
air
Intake
air
Left side view
To indoor unit
Front view
c
d
b
a
f
e
Gas Twinning pipe <optional parts>
Liquid Twinning pipe <optional parts>
To indoor unit
Twinning pipe connection size
PUHY-RP400YSJM-A(-BS)
PUHY-RP200YJM-A(-BS)
PUHY-RP200YJM-A(-BS)
Package unit name
Component unit name
Outdoor Twinning Kit (optional parts)
Indoor unit~Twinning pipe
ø34.93
ø15.88
CMY-RP100VBK
PUHY-RP400, 450, 500, 550, 600, 650YSJM-A (-BS)
Unit : mm
OUTDOOR UNITS
17
2. EXTERNAL DIMENSIONS
Note 2*
Detachable leg
Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. The detachable leg can be removed at site.
3. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
4. The pipe section before the Twinning pipe (sections "a" , "b" , "c" and "d" in the figure) must have at least 500 mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
5. Only use the Twinning pipe by Mitsubishi (optional parts).
(60)
1710
30
920
1650
760
920
30
920
Liquid
PUHY-RP250YJM-A(-BS)
PUHY-RP700YSJM-A(-BS)
CMY-RP200VBK
ø19.05
ø41.28
ø19.05
ø34.93
d
c
a
Gas
b
Twinning pipe connection size
Gas
PUHY-RP250YJM-A(-BS)
Liquid
PUHY-RP250YJM-A(-BS)
Outdoor unit 3
PUHY-RP300YJM-A(-BS)
Outdoor unit 1
PUHY-RP800YSJM-A(-BS)
Outdoor unit 2
Component unit name
PUHY-RP250YJM-A(-BS)
PUHY-RP250YJM-A(-BS)
PUHY-RP250YJM-A(-BS)
Package unit name
Outdoor Twinning Kit (optional parts)
Indoor unit~Twinning pipe 2
PUHY-RP250YJM-A(-BS)
Twinning pipe 1~Twinning pipe 2
PUHY-RP750YSJM-A(-BS)
PUHY-RP200YJM-A(-BS) PUHY-RP300YJM-A(-BS)
PUHY-RP300YJM-A(-BS)
PUHY-RP300YJM-A(-BS)
PUHY-RP900YSJM-A(-BS)
PUHY-RP250YJM-A(-BS)
PUHY-RP300YJM-A(-BS)
PUHY-RP300YJM-A(-BS)
PUHY-RP850YSJM-A(-BS)
Twinning pipe~Outdoor unit
ø12.7
RP250
RP200
ø9.52
Liquid
Gas
e or g or i f or h or j
ø19.05
ø22.2ø9.52
RP300
ø22.2
Unit model
f
e
To indoor unit
To indoor unit
i
b
a
j
c
d
g
h
Front view
Liquid Twinning pipe 1
<optional parts>
Gas Twinning pipe 1
<optional parts>
Liquid Twinning pipe 2
<optional parts>
Gas Twinning pipe 2
<optional parts>
Outdoor unit 3
Left side view
Outdoor unit 2Outdoor unit 1
Intake
air
Intake
air
Intake
air
Discharge air
PUHY-RP700, 750, 800, 850, 900YSJM-A (-BS)
Unit : mm
OUTDOOR UNITS 18
3. CENTER OF GRAVITY
PUHY-RP200, RP250, RP300, RP350YJM-A (-BS)
760
80
Y
724
1410
Z
920
X
760
Model X Y Z
Unit: mm
330 337 550 325 342 550 325 352 550 325 352 550
PUHY-RP200YJM-A (-BS) PUHY-RP250YJM-A (-BS) PUHY-RP300YJM-A (-BS) PUHY-RP350YJM-A (-BS)
3. CENTER OF GRAVITY
OUTDOOR UNITS
19
4. ELECTRICAL WIRING DIAGRAMS
PUHY-RP200, 250, 300, 350YJM-A (-BS)
HIC bypass, Controls refrigerant
flow in HIC circuit
Oil flow control
SLEV
Refrigerant charging port for
auto-charge
SV8
SV5b
Outdoor unit heat exchanger
capacity control
SV3
Capacity control, Refrigerant
phase control in auto-cleaning
Middle pressure
63HS2
Pressure protection for pre-
existing pipes
63H2
For opening/closing the bypass
circuit
For opening/closing the bypass
circuit
Solenoid
valve
Pipe temperature
Z24, 25
Thermistor
Discharge pipe temperature
ACC inlet pipe temperature
Subcooled liquid refrigerant
temperature
OA temperature
IPM temperature
Function setting connector
THHS
TH7
TH6
TH5
TH4
TH3
Power supply
Explanation
Indoor/Outdoor transmission
cable
Central control transmission
cable
Terminal
block
TB7
TB3
TB1
Symbol
Pressure control, Refrigerant flow
rate control
DC reactor
DCL
SV1a
LEV2a, b
LEV1
Linear
expansion
valve
Solenoid
valve
CT12, 22, 3
CH11
Crankcase heater (for heating the compressor)
Current sensor (AC)
Magnetic relay (inverter main circuit)
72C
Low pressure
Discharge pressure
High pressure protection for the
outdoor unit
Pressure
switch
Pressure
sensor
63LS
63H1
Symbol
Explanation
4-way valve
21S4a, b
For opening/closing the bypass
circuit under the O/S
SV1b
SV9
63HS1
<Symbol explanation>
*1. Single-dotted lines indicate wiring
not supplied with the unit.
*2. Dot-dash lines indicate the control
box boundaries.
*3. Refer to the Data book for connecting
input/output signal connectors.
*4. Daisy-chain terminals (TB3) on the
outdoor units in the same refrigerant
system together.
*5. Faston terminals have a locking
function. Make sure the terminals
are securely locked in place after
insertion. Press the tab on the
terminals to remove them.
*6. Control box houses high-voltage parts.
Before inspecting the inside of the
control box, turn off the power, keep
the unit off for at least 10 minutes,
and confirm that the voltage between
FT-P and FT-N on INV Board has dropped
to DC20V or less.
SV8
X14
CN510
yellow
165
SV3
SV1b
63HS2
312
CN992
yellow
123
M
SLEV
65432
1
CNLVD
blue
2112
P
63H2
1
3
DCL
M1 M2
SV1a
Z3
21
M-NET power
supply circuit
C5
LED3: CPU in
operation
LED1: Normal
operation
SC-L1
SC-L2
1
2
W
U
SC-W
1
Z5
R1R2R3
C3
C2
F3F2F1
Z1 Z2
R4
D1
R5
R6
C11
DB1
C7C8C9
C10
C4
C1
C6
Power Source
3N~
50/60Hz
380/400/415V
N
L3L2L1
TB1
N
L3L2L1
L
F4
AC250V
6.3A T
black
white
red
3
1
CN3
green
TB24
N
TB23
L3
TB22
L2
TB21
L1
CN1B
4131
CN1A
UUU
F1,F2,F3
AC250V
6.3A T
U
Z4
DSA
CN2
653
1
Noise
Filter
U
ZNR01
U
31
CN5
red
3
CN4
blue
1
471
CNINV
CNVDC
4
1
FAN Board
F01
DC700V
4A T
C630
C631
R631
R630
IPM
CN18V
blue
CN4
red
CN5
21 1 3 12
234
1
CN21
blue
CN22
red
654
3
LED2: Error
Fan motor
(Heat exchanger)
M
3~
V
C100
R1 R5
*5
black
red
2
43
1
72C
black
red
SC-P1
SC-P2
4
CN1
1
LED1: Normal operation (lit)
/ Error(blink)
CN5V
yellow
CN6
21 3 1
CN4
1
2
CN2
152
7
1
CNTYP
black
C1
RSH1
THHS
*6
FT-P
FT-N
P
N
INV Board
+
+-
+
+++
+++
+
R34
C30
C32
C34
C36
R30
R32
C31
C33
C35
C37
R31
R33
black
white
red
R35
CT3
SC-L3
IPM
SC-U
SC-V
CT12 CT22
red white black
blackwhitered
U
V
W
MS
3~
Motor
(Compressor)
Central control
transmission
cable
Indoor/Outdoor
transmission
cable
Indoor/Outdoor
transmission
cable
*4
TP2TP1
TB7
SM2M1
TB3
M-NET Board
13
CN04
red
LED1: Power supply to
Indoor/Outdoor transmission line
CN102
4321
CNS2
yellow
21 5432
CNIT
red
1
63H1
P
LEV2b
M
LEV2a
M
M
LEV1
12345
6
CNLVA
CNLVB
red
12345
6
54321
6
CNLVC
red
3
1
CNTYP2
black
Z24
321
Z25
CNTYP5
green
CNTYP4
green
432
1
CN213
red
CN212
2
1
CN990
2
1
TH6
TH7
TH3
TH5
213
63LS
63HS1
213
TH4
321
CN202
red
CN201
231
CN211
2
1
red
CNIT
yellow
CNS2
51234
OFF
ON
14
14
CN41
CN40
CN102
4321
CN3D
123
red
CN3S
123
blue
CN3N
123
*3
CNAC
red
21
F01
AC250V
3.15A T
631
SV9
X09
CN508
black
X06
X07
135
6
CN507
red
6
3
SV5b
CN506
X05
3
1
21S4a
CN504
green
X04
X03
CH11
3
1
CN503
blue
2
1
CN502
X02
X01
21S4b
1
1
CN501
2
3
CNAC2
black
6
5
72C
1
2
CN72
red
31
CNDC
pink
12
CNT01
13 12 21 21
CN801
yellow
CNT02
CN332
blue
CN4
CN2
752
1
CPU power
supply circuit
Power failure
detection circuit
Control Board
LED1
SW1
ONOFF
1
10
SW2
ONOFF
1
10
SW3
ONOFF
1
10
SW4
ONOFF
1
10
ONOFF
1
10
SW5
543
12V
1
CN51
*3
SWU2 SWU1
10's
digit
1's
digit
Unit address
setting
LED1
Display
setting
Function
setting
Compressor ON/OFF output
Error detection output
TB7 Power
selecting
connector
LED3: Lit when powered
LED2: CPU in operation
4. ELECTRICAL WIRING DIAGRAMS
OUTDOOR UNITS 20
5. SOUND LEVELS
Measurement condition PUHY-RP200, 250, 300, 350YJM-A (-BS)
Measurement location
1m
1m
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 62.5 61.0 58.5 53.0 50.0 45.5 39.0 36.0 56.0
Low noise mode
50/60Hz 56.5 48.5 46.0 39.0 38.5 32.5 33.0 25.5 44.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP200YJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 59.0 62.0 60.0 54.0 50.5 46.0 41.0 35.0 57.0
Low noise mode
50/60Hz 58.0 53.5 44.0 39.0 36.5 32.5 31.0 24.5 44.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP250YJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
5. SOUND LEVELS
Sound level of PUHY-RP300YJM-A (-BS)
90
80
Standard Low
50/60Hz 50/60Hz
70
60
50
40
Octave band sound level (dB)
30
Approximate minimum
20
audible limit on continuous noise
10
63 125 250 500 1k 2k 4k 8k
Octave band central frequency (Hz)
Standard Low noise mode
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
50/60Hz 65.5 64.0 61.5 56.0 53.0 48.5 45.0 43.0 59.0 50/60Hz 61.5 60.0 49.5 45.0 42.0 39.0 40.0 38.0 50.0
63 125 250 500 1k 2k 4k 8k dB(A)
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
Sound level of PUHY-RP350YJM-A (-BS)
90
80
70
60
50
40
Octave band sound level (dB)
30
Approximate minimum
20
audible limit on continuous noise
10
63 125 250 500 1k 2k 4k 8k
Standard Low noise mode
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
50/60Hz 62.0 65.0 63.0 57.0 53.5 49.0 48.0 42.0 60.0 50/60Hz 62.0 54.0 48.5 46.0 41.5 40.0 41.5 39.5 50.0
Standard Low
Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A)
50/60Hz 50/60Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OUTDOOR UNITS
21
5. SOUND LEVELS
Measurement condition PUHY-RP400, 450, 500, 550, 600, 650YSJM-A (-BS)
Measurement location
1m
1m
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 62.0 65.0 63.0 57.0 53.5 49.0 44.0 38.0 60.0
Low noise mode
50/60Hz 61.0 56.5 47.0 42.0 39.5 35.5 34.0 27.5 47.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP500YSJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 65.5 64.0 61.5 56.0 53.0 48.5 42.0 39.0 59.0
Low noise mode
50/60Hz 59.5 51.5 49.0 42.0 41.5 35.5 36.0 28.5 47.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP400YSJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 66.0 66.0 63.5 58.0 55.0 50.5 46.5 43.5 61.0
Low noise mode
50/60Hz 63.5 61.0 50.5 46.0 43.0 40.0 40.5 38.0 51.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP550YSJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 64.0 64.5 62.5 56.5 53.0 48.5 43.0 38.5 59.5
Low noise mode
50/60Hz 60.5 54.5 48.0 42.0 40.5 35.5 35.0 28.0 47.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP450YSJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 68.5 67.0 64.5 59.0 56.0 51.5 48.0 46.0 62.0
Low noise mode
50/60Hz 64.5 63.0 52.5 48.0 45.0 42.0 43.0 41.0 53.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP600YSJM-A (-BS)
OUTDOOR UNITS 22
5. SOUND LEVELS
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 67.0 67.5 65.0 59.5 56.0 51.5 49.5 45.5 62.5
Low noise mode
50/60Hz 65.0 61.0 52.0 48.5 45.0 42.5 44.0 42.0 53.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP650YSJM-A (-BS)
OUTDOOR UNITS
23
5. SOUND LEVELS
Measurement condition PUHY-RP700, 750, 800, 850, 900YSJM-A (-BS)
Measurement location
1m
1m
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 67.0 67.5 65.5 59.5 56.0 51.5 47.5 44.0 62.5
Low noise mode
50/60Hz 65.0 62.0 52.0 47.0 44.0 41.0 41.0 38.5 52.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP800YSJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 65.5 66.5 64.5 58.5 55.0 50.5 45.5 40.0 61.5
Low noise mode
50/60Hz 63.0 57.5 50.0 44.0 42.5 37.5 37.0 30.0 49.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP700YSJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 69.0 68.5 66.0 60.5 57.5 53.0 49.0 46.5 63.5
Low noise mode
50/60Hz 65.5 63.5 53.0 48.5 45.5 42.5 43.0 41.0 53.5
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP850YSJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 64.0 67.0 65.0 59.0 55.5 51.0 46.0 40.0 62.0
Low noise mode
50/60Hz 63.5 59.0 49.5 44.5 41.5 37.5 36.0 29.5 49.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP750YSJM-A (-BS)
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 70.5 69.0 66.5 61.0 58.0 53.5 50.0 48.0 64.0
Low noise mode
50/60Hz 66.5 65.0 54.5 50.0 47.0 44.0 45.0 43.0 55.0
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PUHY-RP900YSJM-A (-BS)
OUTDOOR UNITS 24
6. CAPACITY TABLES
6. CAPACITY TABLES
6-1. Correction by temperature
CITY MULTI could have various capacities at different designing temperatures. Using the nominal cooling/heating capacity values and the ratios below, the capacity can be found for various temperatures.
PUHY-
Nominal Cooling Capacity
Input
RP200YJM-A RP250YJM-A
kW
BTU/h
kW
22.4
76,400
5.68
28.0
95,500
8.28
1.3
1.2
1.1
1.0
0.9
0.8
Ratio of cooling capacity
0.7
0.6
1.2
1.1
1.0
0.9
0.8
Ratio of power input
0.7
0.6
Indoor Temperature
PUHY-
Nominal Heating Capacity
Input
RP200YJM-A RP250YJM-A
kW
BTU/h
kW
25.0
85,300
5.69
31.5
107,500
7.83
0.5
-5 0 5 10 15 20 25 30 35 40 45
23 32 41 50 59 68 77 86 95 104 113
1.4
1.3
1.2
1.1
1.0
0.9
0.8
Ratio of heating capacity
0.7
0.6
1.1
1.0
0.9
Ratio of cooling capacity and power input Outdoor temperature
Indoor Temperature
0.8
Ratio of power input
0.7
0.6
0.5
-20
-4
-15 5
OUTDOOR UNITS
-10 14
Ratio of heating capacity and power input Outdoor temperature
-5
23
0
32
5
41
10 50
15 59
25
6. CAPACITY TABLES
Ratio of cooling capacity and power input Outdoor temperature
Ratio of heating capacity and power input Outdoor temperature
-5 0 5 10 15 20 25 30 35 40 45 23 32 41 50 59 68 77 86 95 104 113
1.1
1.2
1.0
0.9
0.8
0.7
0.6
0.5
Ratio of power input
-20
-4
-15 5
-10 14
-5
23
0
32
5
41
10 50
15 59
0.6
0.8
0.9
1.0
0.7
0.6
0.5
0.4
Ratio of power input
1.4
1.3
1.1
1.0
0.9
0.8
0.7
1.2
Ratio of cooling capacity
Indoor Temperature
1.3
1.2
1.0
0.9
0.8
0.7
1.1
Ratio of heating capacity
Indoor Temperature
Nominal Cooling Capacity
Input
kW
BTU/h
kW
Nominal Heating Capacity
Input
kW
BTU/h
kW
Nominal Cooling Capacity
Input
kW
BTU/h
kW
Nominal Heating Capacity
Input
kW
BTU/h
kW
PUHY-
RP300YJM-A RP350YJM-A
PUHY-
RP300YJM-A RP350YJM-A
PUHY-
RP400YSJM-A
PUHY-
RP400YSJM-A
33.5
114,300
9.37
40.0
136,500
12.28
37.5
128,000
9.86
45.0
153,500
13.12
45.0
153,500
11.87
50
170,600
11.38
OUTDOOR UNITS 26
6. CAPACITY TABLES
PUHY-
Nominal Cooling Capacity
Input
PUHY-
Nominal Cooling Capacity
Input
PUHY-
Nominal Cooling Capacity
Input
RP450YSJM-A
kW
BTU/h
kW
50.0
170,600
14.40
RP550YSJM-A P600YSJM-A
kW
BTU/h
kW
63.0
215,000
18.58
RP650YSJM-A
kW
BTU/h
kW
73.0
249,100
22.0
RP500YSJM-A
56.0
191,100
16.96
69.0
235,400
19.94
1.4
1.3
1.2
1.1
1.0
0.9
Ratio of cooling capacity
0.8
0.7
1.2
1.1
1.0
0.9
0.8
Ratio of power input
0.7
0.6
Indoor Temperature
PUHY-
Nominal Heating Capacity
Input
PUHY-
Nominal Heating Capacity
Input
PUHY-
Nominal Heating Capacity
Input
RP450YSJM-A
kW
BTU/h
kW
191,100
RP500YSJM-A
56.0
13.42
RP550YSJM-A RP600YSJM-A
kW
BTU/h
kW
69.0
235,400
17.69
RP650YSJM-A
kW
BTU/h
kW
81.5
278,100
22.70
63.0
215,000
15.67
76.5
261,000
20.13
0.5
-5 0 5 10 15 20 25 30 35 40 45
23 32 41 50 59 68 77 86 95 104 113
1.3
1.2
1.1
1.0
0.9
0.8
Ratio of heating capacity
0.7
0.6
1.1
1.0
0.9
Ratio of cooling capacity and power input Outdoor temperature
Indoor Temperature
0.8
Ratio of power input
0.7
0.6
0.5
-20
-4
-15 5
OUTDOOR UNITS
-10 14
Ratio of heating capacity and power input Outdoor temperature
-5
23
0
32
5
41
10 50
15 59
27
6. CAPACITY TABLES
Ratio of cooling capacity and power input Outdoor temperature
Ratio of heating capacity and power input Outdoor temperature
-5 0 5 10 15 20 25 30 35 40 45 23 32 41 50 59 68 77 86 95 104 113
1.1
1.2
1.0
0.9
0.8
0.7
0.6
0.5
Ratio of power input
-20
-4
-15 5
-10 14
-5
23
0
32
5
41
10 50
15 59
0.6
0.9
1.0
1.1
0.8
0.7
0.6
0.5
Ratio of power input
1.4
1.3
1.1
1.0
0.9
0.8
0.7
1.2
Ratio of cooling capacity
Indoor Temperature
1.3
1.2
1.0
0.9
0.8
0.7
1.1
Ratio of heating capacity
Indoor Temperature
Nominal Cooling Capacity
Input
kW
BTU/h
kW
Nominal Heating Capacity
Input
kW
BTU/h
kW
Nominal Cooling Capacity
Input
kW
BTU/h
kW
Nominal Heating Capacity
Input
kW
BTU/h
kW
PUHY-
RP700YSJM-A RP750YSJM-A
PUHY-
PUHY-
RP800YSJM-A
PUHY-
80.0
273,000
23.59
85.0
290,000
25.07
88.0
300,300
21.35
95.0
324,100
23.63
90.0
307,100
27.19
100.0
341,200
25.44
RP700YSJM-A PR750YSJM-A
RP800YSJM-A
OUTDOOR UNITS 28
6. CAPACITY TABLES
PUHY-
Nominal Cooling Capacity
Input
RP850YSJM-A RP900YSJM-A
kW
BTU/h
kW
96.0
327,600
28.57
101.0
344,600
29.61
1.3
1.2
1.1
1.0
0.9
Ratio of cooling capacity
0.8
0.7
1.1
1.0
0.9
0.8
0.7
Ratio of power input
0.6
0.5
Indoor Temperature
PUHY-
Nominal Heating Capacity
Input
RP850YSJM-A RP900YSJM-A
kW
BTU/h
kW
108.0
368,500
27.97
113.0
385,600
29.73
0.4
-5 0 5 10 15 20 25 30 35 40 45
23 32 41 50 59 68 77 86 95 104 113
1.2
1.1
1.0
0.9
0.8
Ratio of heating capacity
0.7
0.6
1.1
1.0
0.9
Ratio of cooling capacity and power input Outdoor temperature
Indoor Temperature
0.8
Ratio of power input
0.7
0.6
0.5
-20
-4
-15 5
OUTDOOR UNITS
-10 14
Ratio of heating capacity and power input Outdoor temperature
-5
23
0
32
5
41
10 50
15 59
29
6. CAPACITY TABLES
Ratio of cooling capacity and power input Outdoor temperature
Ratio of heating capacity and power input Outdoor temperature
-5 0 5 10 15 20 25 30 35 40 45 23 32 41 50 59 68 77 86 95 104 113
1.1
1.2
1.0
0.9
0.8
0.7
0.6
0.5
Ratio of power input
-20
-4
-15 5
-10 14
-5
23
0
32
5
41
10 50
15 59
0.6
1.0
1.2
1.4
1.6
0.8
0.6
0.4
0.2
Ratio of power input
1.3
1.2
1.0
0.9
0.8
0.7
0.6
1.1
Ratio of cooling capacity
Indoor Temperature
1.3
1.4
1.2
1.0
0.9
0.8
0.7
1.1
Ratio of heating capacity
Indoor Temperature
Nominal Cooling Capacity
Input
kW
BTU/h
kW
Nominal Heating Capacity
Input
kW
BTU/h
kW
RP200YJM-A RP250YJM-A
22.4
76,400
5.68
28.0
95,500
8.28
25.0
85,300
5.69
31.5
107,500
7.83
RP200YJM-A RP250YJM-A
Correction by temperature (High Heating Performance Mode)
CITY MULTI could have various capacities at different designing temperatures. Using the nominal cooling/heating capacity val­ues and the ratios below, the capacity can be found for various temperatures. To select high heating performance mode, DipSW 3-7 must be set to ON. (In the low ambient temperature, heating capacity and power input become higher than those under standard mode.)
OUTDOOR UNITS 30
6. CAPACITY TABLES
PUHY-
Nominal Cooling Capacity
Input
PUHY-
Nominal Cooling Capacity
Input
RP300YJM-A RP350YJM-A
kW
BTU/h
kW
33.5
114,300
9.37
RP400YSJM-A
kW
BTU/h
kW
45.0
153,500
11.87
40.0
136,500
12.28
1.4
1.3
1.2
1.1
1.0
0.9
Ratio of cooling capacity
0.8
0.7
1.2
1.1
1.0
0.9
0.8
Ratio of power input
0.7
0.6
Indoor Temperature
PUHY-
Nominal Heating Capacity
Input
PUHY-
Nominal Heating Capacity
Input
RP300YJM-A RP350YJM-A
kW
BTU/h
kW
37.5
128,000
9.86
RP400YSJM-A
kW
BTU/h
kW
50
170,600
11.38
45.0
153,500
13.12
0.5
-5 0 5 10 15 20 25 30 35 40 45
23 32 41 50 59 68 77 86 95 104 113
1.4
1.2
1.0
0.8
0.6
0.4
Ratio of heating capacity
0.2
0.0
1.4
1.2
1.0
Ratio of cooling capacity and power input Outdoor temperature
Indoor Temperature
0.8
Ratio of power input
0.6
0.4
0.2
-20
-4
-15 5
OUTDOOR UNITS
-10 14
Ratio of heating capacity and power input Outdoor temperature
-5
23
0
32
5
41
10 50
15 59
31
6. CAPACITY TABLES
Ratio of cooling capacity and power input Outdoor temperature
Ratio of heating capacity and power input Outdoor temperature
-5 0 5 10 15 20 25 30 35 40 45 23 32 41 50 59 68 77 86 95 104 113
1.1
1.2
1.0
0.9
0.8
0.7
0.6
0.5
Ratio of power input
-20
-4
-15 5
-10 14
-5
23
0
32
5
41
10 50
15 59
0.6
0.5
1.2
1.4
1.6
1.0
0.8
0.6
0.4
Ratio of power input
1.4
1.3
1.1
1.0
0.9
0.8
0.7
1.2
Ratio of cooling capacity
Indoor Temperature
1.3
1.2
1.0
0.9
0.8
0.7
1.1
Ratio of heating capacity
Indoor Temperature
Nominal Cooling Capacity
Input
kW
BTU/h
kW
Nominal Heating Capacity
Input
kW
BTU/h
kW
Nominal Cooling Capacity
Input
kW
BTU/h
kW
Nominal Heating Capacity
Input
kW
BTU/h
kW
Nominal Cooling Capacity
Input
kW
BTU/h
kW
Nominal Heating Capacity
Input
kW
BTU/h
kW
50.0
170,600
14.40
56.0
191,100
16.96
56.0
191,100
13.42
63.0
215,000
15.67
63.0
215,000
18.58
69.0
235,400
19.94
69.0
235,400
17.69
76.5
261,000
20.13
73.0
249,100
22.0
81.5
278,100
22.70
PUHY-
RP450YSJM-A
RP500YSJM-A
PUHY-
PUHY-
RP550YSJM-A P600YSJM-A
PUHY-
PUHY-
RP650YSJM-A
RP450YSJM-A
RP500YSJM-A
RP550YSJM-A RP600YSJM-A
RP650YSJM-A
PUHY-
OUTDOOR UNITS 32
6. CAPACITY TABLES
Nominal Cooling Capacity
Input
Nominal Cooling Capacity
Input
RP700YSJM-A PR750YSJM-A
kW
BTU/h
kW
80.0
273,000
23.59
RP800YSJM-A
kW
BTU/h
kW
90.0
307,100
27.19
85.0
290,000
25.07
1.4
1.3
1.2
1.1
1.0
0.9
Ratio of cooling capacity
0.8
0.7
1.2
1.1
1.0
0.9
0.8
Ratio of power input
0.7
0.6
Indoor Temperature
Nominal Heating Capacity
Input
Nominal Heating Capacity
Input
RP700YSJM-A PR750YSJM-A
kW
BTU/h
kW
88.0
300,300
21.35
RP800YSJM-A
kW
BTU/h
kW
100.0
341,200
25.44
95.0
324,100
23.63
0.5
-5 0 5 10 15 20 25 30 35 40 45
23 32 41 50 59 68 77 86 95 104 113
1.4
1.2
1.0
0.8
0.6
0.4
Ratio of heating capacity
0.2
0.0
1.4
1.2
1.0
Ratio of cooling capacity and power input Outdoor temperature
Indoor Temperature
0.8
Ratio of power input
0.6
0.4
0.2
-20
-4
-15 5
OUTDOOR UNITS
-10 14
Ratio of heating capacity and power input Outdoor temperature
-5
23
0
32
5
41
10 50
15 59
33
6. CAPACITY TABLES
Ratio of cooling capacity and power input Outdoor temperature
Ratio of heating capacity and power input Outdoor temperature
-5 0 5 10 15 20 25 30 35 40 45 23 32 41 50 59 68 77 86 95 104 113
1.0
1.1
0.9
0.8
0.7
0.6
0.5
0.4
Ratio of power input
-20
-4
-15 5
-10 14
-5
23
0
32
5
41
10 50
15 59
0.2
1.0
1.2
1.4
0.8
0.6
0.4
0.2
Ratio of power input
1.3
1.1
1.0
0.9
0.7
0.8
1.2
Ratio of cooling capacity
Indoor Temperature
1.4
1.0
0.8
0.6
0.4
1.2
Ratio of heating capacity
Indoor Temperature
Nominal Cooling Capacity
Input
kW
BTU/h
kW
Nominal Heating Capacity
Input
kW
BTU/h
kW
96.0
327,600
28.57
101.0
344,600
29.61
108.0
368,500
27.97
113.0
385,600
29.73
PUHY-
RP850YSJM-A RP900YSJM-A
PUHY-
RP850YSJM-A RP900YSJM-A
OUTDOOR UNITS 34
6. CAPACITY TABLES
Capacity(kW)
Input(kW)
Total capacity of indoor units
10.0
10.0
20.0
30.0
40.0
50.0
0.0
5.0
50 100 200 300150 250 350
100 200 300 400 500
Capacity(kW)
Input(kW)
Total capacity of indoor units
10.0
20.0
30.0
40.0
50.0
2.5
5.0
10.0
15.0
7.5
12.5
RP200 RP250
PUHY-RP200, 250YJM-A (-BS)
PUHY-RP300, 350YJM-A (-BS)
Cooling Heating
Cooling Heating
RP300 RP350
Cooling Heating
Cooling Heating
6-2. Correction by total indoor
CITY MULTI system have different capacities and inputs when many combinations of indoor units with different total capacities are connected. Using following tables, the maximum capacity can be found to ensure the system is installed with enough capacity for a particular application.
OUTDOOR UNITS
35
6. CAPACITY TABLES
Capacity(kW)
Input(kW)
Total capacity of indoor units
20.0
10.0
10.0
15.0
30.0
40.0
50.0
60.0
0.0
5.0
200 300 400 500 600 700 800
Capacity(kW)
Input(kW)
Total capacity of indoor units
30.0
40.0
50.0
60.0
70.0
0.0
5.0
15.0
20.0
10.0
Cooling Heating
Cooling Heating
Cooling Heating
Cooling Heating
RP500 RP550
RP400 RP450
PUHY-RP400, 450YSJM-A (-BS)
PUHY-RP500, 550YSJM-A (-BS)
200 300 400 500 600
OUTDOOR UNITS 36
6. CAPACITY TABLES
Capacity(kW)
Input(kW)
Total capacity of indoor units
50.0
40.0
30.0
20.0
60.0
70.0
80.0
90.0
0.0
10.0
200 300 400 500 600 700 800 900
300 400 500 600 700 800 900 1000
Capacity(kW)
Input(kW)
Total capacity of indoor units
40.0
20.0
60.0
80.0
100.0
120.0
0.0
10.0
30.0
20.0
RP600 RP650
PUHY-RP600,650YSJM-A (-BS)
PUHY-RP700,750YSJM-A (-BS)
Cooling Heating
Cooling Heating
Cooling Heating
Cooling Heating
RP700 RP750
OUTDOOR UNITS
37
6. CAPACITY TABLES
Capacity(kW)
Input(kW)
Total capacity of indoor units
40.0
20.0
60.0
80.0
100.0
120.0
0.0
10.0
40.0
30.0
400 600 800 1000 14001200
400 500 600 700 800 1200900 1000 1100
Capacity(kW)
Input(kW)
Total capacity of indoor units
60.0
40.0
80.0
100.0
120.0
140.0
0.0
10.0
30.0
20.0
Cooling Heating
Cooling Heating
Cooling Heating
RP900
RP800 RP850
PUHY-RP800, 850YSJM-A (-BS)
PUHY-RP900YSJM-A (-BS)
OUTDOOR UNITS 38
6. CAPACITY TABLES
PUHY-RP400YSJM-A (-BS)
Piping equivalent length (m)
Cooling capacity correction factor
200
300
400 520
0.70
0.75
0.80
0.85
0.90
0.95
1
0 20 40 60 80 100 120 140
PUHY-RP450YSJM-A (-BS)
Piping equivalent length (m)
Cooling capacity correction factor
225 338
450 585
0.75
0.80
0.85
0.90
0.95
1
0 20 40 60 80 100 120 140
PUHY-RP500YSJM-A (-BS)
Piping equivalent length (m)
Cooling capacity correction factor
250 375
500 650
0.70
0.75
0.80
0.85
0.90
0.95
1
0 20 40 60 80 100 120 140
PUHY-RP550YSJM-A (-BS)
Piping equivalent length (m)
Cooling capacity correction factor
275
413
550 715
0.70
0.75
0.80
0.85
0.90
0.95
1
0 20 40 60 80 100 120 140
6-3. Correction by refrigerant piping length
6-3-1. Cooling capacity correction
PUHY-RP200YJM-A (-BS)
1
100
0.95
0.90
0.85
0.80
0.75
Cooling capacity correction factor
0.70
0 20 40 60 80 100 120 140
PUHY-RP250YJM-A (-BS)
Piping equivalent length (m)
1
0.95
0.90
0.85
0.80
0.75
Cooling capacity correction factor
0.70
0 20 40 60 80 100 120 140
Piping equivalent length (m)
150
200 260
125 188
250 325
PUHY-RP300YJM-A (-BS)
1
0.95
0.90
0.85
0.80
0.75
Cooling capacity correction factor
0.70
0 20 40 60 80 100 120 140
PUHY-RP350YJM-A (-BS)
Piping equivalent length (m)
1
0.95
0.90
0.85
0.80
0.75
Cooling capacity correction factor
0.70
0 20 40 60 80 100 120 140
Piping equivalent length (m)
150
225
300 390
175 263
350 455
OUTDOOR UNITS
39
6. CAPACITY TABLES
PUHY-RP600YSJM-A (-BS)
Piping equivalent length (m)
Cooling capacity correction factor
300 450
600 780
0.70
0.75
0.80
0.85
0.90
0.95
1
0 20 40 60 80 100 120
PUHY-RP800YSJM-A (-BS)
Piping equivalent length (m)
Cooling capacity correction factor
400, 600
800 1040
0.70
0.75
0.80
0.85
0.90
0.95
1
0 20 40 60 80 100 120
PUHY-RP650YSJM-A (-BS)
Piping equivalent length (m)
Cooling capacity correction factor
325, 488
650 845
0.70
0.75
0.80
0.85
0.90
0.95
1
0 20 40 60 80 100 120
PUHY-RP850YSJM-A (-BS)
Piping equivalent length (m)
Cooling capacity correction factor
425 637
850 1105
0.70
0.75
0.80
0.85
0.90
0.95
1
0 20 40 60 80 100 120
PUHY-RP700YSJM-A (-BS)
Piping equivalent length (m)
Cooling capacity correction factor
350, 525
700 910
0.70
0.75
0.80
0.85
0.90
0.95
1
0 20 40 60 80 100 120
PUHY-RP900YSJM-A (-BS)
Piping equivalent length (m)
Cooling capacity correction factor
450 675
900 1170
0.70
0.75
0.80
0.85
0.90
0.95
1
0 20 40 60 80 100 120
PUHY-RP750YSJM-A (-BS)
Piping equivalent length (m)
Cooling capacity correction factor
375, 563
750 975
0.70
0.75
0.80
0.85
0.90
0.95
1
0 20 40 60 80 100 120
OUTDOOR UNITS 40
6. CAPACITY TABLES
PUHY-RP600, 650YSJM-A (-BS)
0 20 40 60 80 100 120
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
0.90
PUHY-RP700, 750, 800YSJM-A (-BS)
0 20 40 60 80 100 120
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
0.90
PUHY-RP850, 900YSJM-A (-BS)
0 20 40 60 80 100 120
Heating capacity correction factor
0.95
1.00
Piping equivalent length (m)
0.90
6-3-2. Heating capacity correction
PUHY-RP200, 250YJM-A (-BS)
1.00
0.95
Heating capacity correction factor
0.90 0 20 40 60 80 100 120 140
PUHY-RP300, 350YJM-A (-BS)
1.00
0.95
Piping equivalent length (m)
Heating capacity correction factor
0.90 0 20 40 60 80 100 120 140
PUHY-RP400, 450, 500, 550YSJM-A (-BS)
1.00
0.95
Heating capacity correction factor
0.90 0 20 40 60 80 100 120 140
6-3-3. How to obtain the equivalent piping length
1. PUHY-RP200YJM-A (-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.35 x number of bent on the piping) [m]
2. PUHY-RP250, 300YJM-A (-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.42 x number of bent on the piping) [m]
3. PUHY-RP350YJM-A (-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.47 x number of bent on the piping) [m]
4. PUHY-RP400, 450, 500, 550, 600, 650YSJM-A (-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.50 x number of bent on the piping) [m]
5. PUHY-RP700, 750, 800YSJM-A (-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.70 x number of bent on the piping) [m]
6. PUHY-RP850, 900YSJM-A (-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.80 x number of bent on the piping) [m]
Piping equivalent length (m)
Piping equivalent length (m)
OUTDOOR UNITS
41
6. CAPACITY TABLES
6-4. Correction at frost and defrost
Due to frost at the outdoor heat exchanger and the automatic defrost operation, the heating capacity of the outdoor unit can be calculated by multiplying the correction factor shown in the table below.
Table of correction factor at frost and defrost
Outdoor inlet air temp. °C 64210-2-4-6-8-10-20
Outdoor inlet air temp. °F 43 39 36 34 32 28 25 21 18 14 14
PUHY-RP200YJM-A(-BS) 1.00 0.93 0.85 0.83 0.84 0.86 0.90 0.90 0.95 0.95 0.95
PUHY-RP250YJM-A(-BS) 1.00 0.93 0.85 0.83 0.84 0.86 0.90 0.90 0.95 0.95 0.95
PUHY-RP300YJM-A(-BS) 1.00 0.93 0.82 0.80 0.82 0.86 0.90 0.90 0.95 0.95 0.95
PUHY-RP350YJM-A(-BS) 1.00 0.93 0.85 0.83 0.84 0.86 0.90 0.90 0.95 0.95 0.95
PUHY-RP400YSJM-A (-BS) 1.00 0.93 0.85 0.83 0.84 0.86 0.90 0.90 0.95 0.95 0.95
PUHY-RP450YSJM-A (-BS) 1.00 0.93 0.85 0.83 0.84 0.86 0.90 0.90 0.95 0.95 0.95
PUHY-RP500YSJM-A (-BS) 1.00 0.94 0.87 0.86 0.87 0.88 0.90 0.90 0.93 0.93 0.93
PUHY-RP550YSJM-A (-BS) 1.00 0.94 0.87 0.86 0.87 0.88 0.90 0.90 0.93 0.93 0.93
PUHY-RP600YSJM-A (-BS) 1.00 0.94 0.87 0.86 0.87 0.88 0.90 0.90 0.93 0.93 0.93
PUHY-RP650YSJM-A (-BS) 1.00 0.98 0.89 0.88 0.89 0.90 0.92 0.95 0.95 0.95 0.95
PUHY-RP700YSJM-A (-BS) 1.00 0.94 0.87 0.86 0.87 0.88 0.90 0.90 0.93 0.93 0.93
PUHY-RP750YSJM-A (-BS) 1.00 0.94 0.87 0.86 0.87 0.88 0.90 0.90 0.93 0.93 0.93
PUHY-RP800YSJM-A (-BS) 1.00 0.98 0.89 0.88 0.89 0.90 0.92 0.95 0.95 0.95 0.95
PUHY-RP850YSJM-A (-BS) 1.00 0.94 0.87 0.86 0.87 0.88 0.90 0.90 0.93 0.93 0.93
PUHY-RP900YSJM-A (-BS) 1.00 0.98 0.89 0.88 0.89 0.90 0.92 0.95 0.95 0.95 0.95
OUTDOOR UNITS 42
6. CAPACITY TABLES
30
25
20
15
10
5
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
-4 5 14 23 32 41 50 59 68 77 86 95 104 113 122
-4 5 14 23 32 41 50 59 68 77 86 95 104 113 122
Indoor temperature
Outdoor temperature
30
25
20
15
10
5
86
77
68
59
50
41
86
77
68
59
50
41
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
Indoor temperature
Outdoor temperature
Ref.: PUHY_YHM-A_TMPRNG_EUDB_ALL
6-5. Operation temperature range
OUTDOOR UNITS
43
7. OPTIONAL PARTS
For Gas pipe: For Liquid pipe:
ID:Inner Diameter OD:Outer Diameter
mm
CMY-RP100VBK
<Deformed pipe(Accessory)>
ID ø19.05
ID ø19.05OD ø15.88
OD ø28.58
OD ø28.58 ID ø25.4
OD ø28.58 ID ø22.2
(2 pcs.)
(2 pcs.)
85
62
62
62
69
OD ø34.93
ID ø41.28
ID ø9.52OD ø12.7
(2 pcs.)
49
Note 2
The straight part of pipe
Pipe cover
658
( 500 )
600
98
OD ø15.88
ID ø15.88
ID ø12.7
OD ø12.7
OD ø12.7
ID ø12.7
Distributer
(Dot-dashed part)
The straight part of pipe
748
( 500 )
666
162
Distributer
ID ø34.93
Note 2
Pipe cover
(Dot-dashed part)
OD ø31.75
OD ø28.58
ID ø28.58
OD ø28.58
ID ø28.58
For Gas pipe: For Liquid pipe:
ID:Inner Diameter OD:Outer Diameter
mm
CMY-RP200VBK
<Deformed pipe(Accessory)>
(Dot-dashed part)
(Dot-dashed part)
(Dot-dashed part)
(Dot-dashed part)
Note 2
The straight part of pipe
Note 2
The straight part of pipe
Note 2
The straight part of pipe
Note 2
The straight part of pipe
Distributer
Distributer
Distributer
Pipe cover
Pipe cover
663
OD ø25.4
ID ø22.2
ID ø22.2OD ø25.4
ID ø28.58
ID ø19.05
62
62
ID ø19.05OD ø22.2
62
(2 pcs.)
162
69
(2 pcs.)
Distributer
OD ø38.1
OD ø15.88
ID ø41.28
ID ø12.7
ID ø38.1
49
ID ø9.52
OD ø15.88
( 500 )
658
600
115
606
( 500 )
661
OD ø15.88
OD ø19.05
ID ø15.88
ID ø19.05
ID ø19.05
OD ø15.88
( 500 )
748
( 500 )
743
666
Pipe cover
OD ø25.4
ID ø28.58
OD ø25.4
OD ø28.58
62
49
98
162
OD ø12.7
OD ø28.58
ID ø9.52
ID ø28.58
OD ø28.58
ID ø34.93
OD ø28.58
OD ø31.75
Pipe cover
OD ø12.7
ID ø19.05
ID ø12.7
ID ø12.7
OD ø15.88
OD ø12.7
ID ø34.93
49
Distributer
15
The angle of the branch pipe is within against the horizontal plane.
2. The length of the straight part of pipe connected in front of the twinning pipe must be 500mm or longer. Removing, cutting and bending the twinning kit will cause damage the unit.
3. Pipe diameter is indicated by inside diameter.
Note 1. Reference the attitude angle of the branch pipe below the fig.
15
7. OPTIONAL PARTS
7-1. OUTDOOR TWINNING KIT
For PUHY-RP-YSJM, following optional Outdoor Twinning Kit is needed to use to combine to refrigerant flows of its PUHY-RP­YJM. Details of selecting the proper kit should be referred to the System Design Section.
OUTDOOR UNITS 44
8. UNIT SELECTION
8. UNIT SELECTION
8-1. Indoor and outdoor unit selection
(1) Selecting indoor units
1) Calculate the thermal road of each room.
2) Based on the thermal load corrected for indoor unit return air temperature, select appropriate indoor unit models. Refer to the correction factor diagram for the outdoor unit whose capacity is the closest to the total thermal load of the
system (Qi). Refer to “CAPACITY TABLES (Indoor unit)” and “6. CAPACITY TABLES.”
3) Calculate the total capacity of the indoor units in the system (N).
(2) Selecting outdoor units
1) Based on the total capacity of the indoor units (N), tentatively select the capacity of the outdoor unit (X). The total capacity of the indoor units to be connected to a given outdoor unit (N) should not exceed the maximum
connectable capacity of the outdoor unit.
2) The tentatively selected standard capacity of the outdoor unit (X) will be defined as Qs. * If the total capacity of the indoor units that are connected to a given outdoor unit exceeds 100% of the outdoor unit
capacity (X), refer to the outdoor unit partial load capacity table, find the capacity that corresponds to the total capacity N, and use it as the standard outdoor unit capacity (Qs).
3) Obtain the maximum outdoor unit capacity (Qm) by multiplying Qs (standard outdoor unit capacity) by the following correction factors: piping length, outside air temperature, and defrost (heating).
Find the piping length correction factor from the diagram that corresponds to the total indoor unit capacity (N).
Qm = Qs x Piping length correction factor x Outside air temperature correction factor x Defrost correction factor (heating only) x Pipe diameter correction factor
Outside air temperature correction factor Piping length correction factor Defrost correction factor (heating only) Pipe diameter correction factor (applicable only if non-standard size pipes are connected)
4) Make sure the maximum outdoor unit capacity Qm is equal to or greater than the total thermal load Qi.
If Qm is smaller than Qi, reconsider the outdoor unit capacity (X) so that Qm ≥ Qi will hold true.
5) After selecting indoor and outdoor units, calculate the apportioned indoor unit capacity, and make sure that the formula "Thermal load ≤ Indoor unit capacity" will hold true for each room.
If the thermal load exceeds the indoor unit capacity in one or more rooms, increase the indoor unit size as long as doing so
will not exceed the maximum connectable capacity of the outdoor unit. Then, start over from step 1) above. If the maximum connectable capacity is exceeded by increasing the indoor unit capacity, increase the outdoor capacity as well, then start over from step 1) above.
Refer to 6-1. Refer to 6-3. Refer to 6-4. Refer to 8-3.
Calculate the indoor/outdoor unit capacities and check for unit compatibility by considering both the heating and the cooling loads. If the formula Qm ≥ Qi does not hold true for either cooling or heating, reconsider the outdoor unit capacity (X).
OUTDOOR UNITS
45
8. UNIT SELECTION
(3) Obtaining the unit capacity
(4) Notes
A. If the apportioned indoor unit capacity obtained in step 5) on the previous page is equal to or greater than the rated
indoor unit capacity, the following formula will be used to calculate the indoor unit capacity: "Rated capacity x return air temperature correction factor x piping length correction factor (x pipe diameter correction factor)".
B. If the apportioned indoor unit capacity obtained in step 5) on the previous page is smaller than the rated indoor unit
capacity, the following formula will be used to calculate the indoor unit capacity: "Apportioned indoor unit capacity x return air temperature correction factor."
* The standard outside air temperatures used to obtain the return air temperature correction factor is 35ºCDB for cooling
and 6ºCWB for heating.
* If non-standard size pipes are connected, use the pipe diameter correction factors for the main pipes, merge pipes, and
branch pipes.
When deciding the outside air temperature to calculate unit capacity requirements, take into consideration the possible temperature rise around the outdoor unit due to short-cycling. (When installing outdoor units collectively on the rooftop or if outdoor units are surrounded by walls or other objects, it is recommended to set the outside temperature as 43ºC for calculation.)
If you want to take sensible heat load into consideration, refer to the relevant catalogs for information on sensible heat factor when selecting indoor units.
OUTDOOR UNITS 46
8. UNIT SELECTION
8-2. Calculation samples
(1) To connect indoor units using the standard pipes
Design conditions <Cooling>
<Heating>
<Miscellaneous information>
A. Calculating the cooling load
a) The thermal load (13.5 kW/room), indoor unit return air temperature correction factor, and piping length correction
factor are used to calculate the required indoor unit capacity, based on which a 125 model of indoor unit is tentatively selected. (Because the total thermal load is 27 kW, the air temperature correction diagram for the 250 model outdoor
unit will be used.) b) Because the total capacity of indoor units (N) is 250, the 250 model outdoor unit is tentatively selected. Based on the above, the standard capacity Qs will be 28 kW. c) The correction values obtained from the air temperature correction factor graph and the piping length correction factor
graph for the 250 model outdoor units are as follows:
If the standard capacity Qs is corrected for indoor/outside air temperatures and piping length, the maximum outdoor unit
capacity Qm can be obtained as follows: Qm = 28 x 0.99 x 0.97 = 26.8 kW.
The result shows that the thermal load Qi (27 kW) exceeds the unit capacity Qm, so a larger 300 model outdoor unit
needs to be selected.
d) For the 300 model units, the outside air temperature correction factor is 0.99. The piping length correction factor that
can be obtained from the diagram for the system whose total indoor unit capacity is 250 would be 0.96. Because the standard outdoor unit capacity Qs is 33.5 kW, the maximum outdoor unit capacity Qm can be obtained
using the following formula: Qm = 33.5 x 0.99 x 0.96 = 31.8 kW. The result 31.8 kW is greater than the Qi (27 kW), so
the maximum capacity Qm meets the capacity requirement. e) Compare the thermal loads on the indoor units, using the maximum outdoor unit capacity apportioned to each indoor
unit and taking the indoor unit return air temperature correction factors into consideration. The correction factor for the
return air temperature at 18.5ºCWB is 0.99 (at the standard outside dry-bulb temperature of 35ºC), and this value can
be plugged into the following formula to obtain the capacity.
32.1 kW x 125/250 x 0.99 = 15.8 kW The result shows that the capacity (15.8 kW) is greater than the thermal load (13.5 kW), and based on this result, two
125 model indoor units and one 300 model outdoor unit can be selected.
B. Calculating the heating load
Next, you will calculate the heating load and unit capacity requirements, using the models that were selected in the previous section.
a) The standard capacity (Qs) of the tentatively selected 300 model outdoor unit is 37.5 kW. b) Use this value in the following formula to obtain the maximum outdoor unit capacity Qm as shown below: Qm = 37.5 x 1.00 x 0.965 x 0.975 = 35.2 kW, (where the outside air temperature is 5ºCWB, capacity correction factor
is 1.00 (at the standard indoor dry-bulb temperature of 20ºC), defrost correction factor is 0.965, piping length is 50 m,
and capacity correction factor is 0.975). The result shows that the Maximum outdoor unit capacity Qm (35.2 kW) exceeds the heating load Qi (29 kW). c) You can now check to see if this value will meet the capacity requirement for each indoor unit by using the following
formula: 35.2 x 125/250 x 0.96 = 16.8 kW (where the indoor unit return air temperature correction factor at 21ºCDB is
0.96) (standard outside temperature at 6ºC). The result shows that the unit capacity (16.8 kW) exceeds the thermal
load for each room (14.5 kW). Based on the above calculation, the following indoor and outdoor units can be selected. Indoor units: 125 model x 2 units Outdoor unit: RP300 model
C. Calculating the capacity requirement
a) The cooling capacity of the tentatively selected outdoor unit apportioned to each indoor unit is 15.8 kW, which exceeds
the rated cooling capacity of the 125 model unit (14.0 kW). The actual cooling capacity under the specified conditions is
calculated as follows: 14.0 x 0.99 x 0.97 = 13.4 kW (where the return air temperature correction factor at the standard
outside temperature of 35ºCDB is 0.99 and the piping length correction factor is 0.97). b) The heating capacity of the tentatively selected outdoor unit apportioned to each indoor unit is 16.8 kW, which exceeds
the rated cooling capacity of the 125 model unit (16.0 kW). The actual heating capacity under the specified conditions is
calculated as follows: 16.0 x 0.95 x 0.975 = 14.8 kW (where the return air temperature correction factor at the standard
outside temperature of 6ºCWB is 0.95 and the piping length correction factor is 0.975).
Indoor design dry-bulb temperature: 26ºC/Indoor design wet-bulb temperature: 18.5ºC Outdoor design dry-bulb temperature: 36ºC Cooling load: 13.5 kW for each of the two rooms
Indoor design dry-bulb temperature: 21ºC Outdoor design wet-bulb temperature: 5ºC Heating load: 14.5 kW for each of the two rooms
Main piping: ø28.58 x 45 m, Branch piping: ø19.05 x 5 m (Equivalent indoor and outdoor piping length: 50 m)
Outside air temperature 36ºCDB Piping length: 50 m
Capacity correction factor 0.99 (at the standard indoor wet-bulb temperature of 19ºC) Capacity correction factor: 0.97
OUTDOOR UNITS
47
8. UNIT SELECTION
(2) To connect indoor units using non-standard pipes
A. Calculating the cooling load
B. Calculating the heating load
Next, we will calculate the heating load, using the models that are selected based on the cooling load calculation.
Design conditions <Cooling>
<Heating>
<Miscellaneous information>
a) The thermal load of 13 kW per room and the indoor unit return air temperature correction factor are used to calculate
the required indoor unit capacity, based on which a 125 model of indoor unit is tentatively selected. (Because the total thermal load is 26 kW, the air temperature correction diagram for the 250 model outdoor unit will be used.)
b) Because the total capacity of indoor units (N) is 250, the 250 model outdoor unit is tentatively selected. Based on the above, the standard capacity Qs will be 28 kW.
c) The correction values obtained from the air temperature correction factor graph and the piping length correction factor
graph for the 250 model outdoor units are as follows:
d) For the 300 model, the outside air temperature correction factor is 0.99, the pipe diameter correction factor for a 45 m
pipe with a diameter of ø25.4 is 0.98, and the piping length correction factor is 0.96 (read from the diagram for the unit whose total indoor unit capacity N is 250).
Where the standard outdoor unit capacity Qs is 33.5 kW, the maximum outdoor unit capacity Qm can be obtained as
follows: Qm = 33.5 x 0.99 x 0.98 x 0.96= 31.2 kW. This value is greater than the thermal load Qi (27 kW), and the maximum capacity Qm satisfies the capacity requirements.
e) Compare the thermal loads on the indoor unit side, using the maximum outdoor unit capacity apportioned to each
indoor unit and taking the indoor unit return air condition correction factors into consideration. The correction factor for the return air temperature at 18.5ºC is 0.99 (at the standard outside dry-bulb temperature of 35ºC), and the pipe diameter correction factor for a 5 m pipe with a diameter of ø15.88 connected to a 125-model unit is 0.99. These values can be plugged into the following formula to obtain the capacity.
31.8 kW x 125/250 x 0.99 x 0.99=15.5 kW. The result shows that the capacity (15.5 kW) is greater than the thermal load of 13.5 kW, and based on this result, two
125 model indoor units and one 300 model outdoor unit can be selected.
a) The standard capacity Qs of the tentatively selected (during cooling load calculation) 300 model outdoor unit is 37.5
kW.
The standard capacity Qs is corrected for indoor/outside air temperatures and piping length to obtain the maximum outdoor unit capacity Qm as follows: Qm = 37.5 x 1.00 x 0.975 x 0.975 = 35.6 kW. The result shows that the Maximum outdoor unit capacity Qm (35.6 kW) exceeds the heating load Qi (29 kW).
b) The correction values obtained from the air temperature correction factor graph and the piping length correction factor
graph for the 300 model outdoor units are as follows:
c) You can now check to see if this value will meet the capacity requirement for each indoor unit by using the following
formula: 35.6 x 125/250 x 0.96 x 0.99 = 16.9 kW (where the correction factor for the indoor unit return air temperature of 21ºCDB is 0.96 (standard outside temperature at 6ºC), and the pipe diameter correction factor for a 5 m branch pipe with a diameter of ø15.88 connected to a 125 models is 0.99. The result shows that the unit capacity 16.9 kW exceeds the thermal load for each room (14.5 kW).
Based on the above calculation, the following indoor and outdoor units can be selected. Indoor units: 125 model x 2 units Outdoor unit: RP300 model
The standard capacity Qs is corrected for indoor/outside air temperatures, piping length, and pipe diameter to obtain the maximum outdoor unit capacity Qm as follows: Qm = 28 x 0.99 x 0.97 x 0.98 = 26.3 kW. Because this value does not meet the thermal load Qi (27 kW), a larger 300 model outdoor unit needs to be selected.
Indoor design dry-bulb temperature: 26ºC/Indoor design wet-bulb temperature: 18.5ºC Outdoor design dry-bulb temperature: 36ºC Cooling load: 13.5 kW for each of the two rooms Indoor design dry-bulb temperature: 21ºC Outdoor design wet-bulb temperature: 5ºC Heating load: 14.5 kW for each of the two rooms
Main piping: ø25.4 x 45 m, Branch piping: ø15.88 x 5 m (Equivalent indoor and outdoor piping length: 50 m)
Outside air temperature 36ºCDB Piping length: 50 m Main piping: ø25.4 x 45 m
Capacity correction factor 0.99 (at the standard indoor wet-bulb temperature of 19ºC) Capacity correction factor: 0.97 Pipe diameter correction factor: 0.98
Outside air temperature 5ºCWB
Piping length: 50 m
Capacity correction factor 1.00 (at the standard indoor dry-bulb temperature of 20ºC) Defrost correction factor is 0.975 Capacity correction factor: 0.975
OUTDOOR UNITS 48
8. UNIT SELECTION
<Capacity requirement calculation flow chart>
Obtain the thermal load (Qi).
Correct for the indoor unit return air temperature.
Determine the capacity for each indoor unit.
Calculate the total indoor unit capacity (N).
Select the outdoor unit capacity (X).
Correct the standard outdoor unit capacity (Qs) for outside air temperature and piping length to obtain the corrected capacity (Qm).
Thermal load Qi > Corrected capacity Qm
NO
Apportion the corrected outdoor unit capacity (Qm) to each indoor unit.
Multiply the apportioned capacity by the indoor unit temperature correction factor, and make sure it is equal to or greater than the thermal load.
YES
Select the outdoor unit one rank higher in capacity.
Finish (calculations to be done for both cooling and heating)
OUTDOOR UNITS
49
8. UNIT SELECTION
8-3. Pipe diameter correction factor
8-3-1. Correction factors for the outdoor units and main pipe diameter
PUHY-RP200YJM-A
1
0.90
0.80
0.70
Pipe diameter correction factor
0.60 0 20 40 60 80 100
Equivalent main piping length (m)
PUHY-RP250YJM-A
1
0.90
0.80
0.70
Pipe diameter correction factor
Ø
25.4
Ø
22.2
Ø
19.05
Ø
25.4
Ø
22.2
PUHY-RP350YJM-A
1
0.90
0.80
0.70
Pipe diameter correction factor
0.60 0 20406080100
Equivalent main piping length (m)
PUHY-RP400YSJM-A
1
0.90
0.80
0.70
Pipe diameter correction factor
Ø
28.58
Ø
25.4
Ø
28.58
0.60 0 20406080100
Equivalent main piping length (m)
PUHY-RP300YJM-A
1
0.90
0.80
0.70
Pipe diameter correction factor
0.60 0 20 40 60 80 100
Equivalent main piping length (m)
Ø
Ø
25.4
22.2
0.60 0 20 40 60 80 100
Equivalent main piping length (m)
PUHY-RP450YSJM-A
1
0.90
0.80
0.70
Pipe diameter correction factor
0.60 0 20406080100
Equivalent main piping length (m)
Ø
28.58
OUTDOOR UNITS 50
8. UNIT SELECTION
Equivalent main piping length (m)
Ø
28.58
1
0.90
0.80
0.60
0.70
Pipe diameter correction factor
PUHY-RP500YSJM-A
0 20 40 60 80 100
Equivalent main piping length (m)
Ø
28.58
Ø
34.93
1
0.90
0.80
0.60
0.70
Pipe diameter correction factor
PUHY-RP650YSJM-A
0 20406080100
Equivalent main piping length (m)
Ø
28.58
1
0.90
0.80
0.60
0.70
Pipe diameter correction factor
PUHY-RP550YSJM-A
0 20406080100
Equivalent main piping length (m)
Ø
34.93
1
0.90
0.80
0.60
0.70
Pipe diameter correction factor
PUHY-RP700YSJM-A
0 20 40 60 80 100
Ø
28.58
Equivalent main piping length (m)
1
0.90
0.80
0.60
0.70
Pipe diameter correction factor
PUHY-RP600YSJM-A
0 20 40 60 80 100
Equivalent main piping length (m)
Ø
34.93
1
0.90
0.80
0.60
0.70
Pipe diameter correction factor
PUHY-RP750YSJM-A
0 20406080100
OUTDOOR UNITS
51
8. UNIT SELECTION
PUHY-RP800YSJM-A
1
0.90
0.80
0.70
Pipe diameter correction factor
0.60 0 20 40 60 80 100
Equivalent main piping length (m)
Ø
34.93
OUTDOOR UNITS 52
8. UNIT SELECTION
Branch piping length (m)
Ø
12.7
1
0.90
0.80
Pipe diameter correction factor
P50
010 40
20
30
Ø
25.4
Ø
22.2
Branch piping length (m)
1
0.90
0.80
Pipe diameter correction factor
P250
010 40
20
30
Ø
15.88
Branch piping length (m)
1
0.90
0.80
Pipe diameter correction factor
P100, P125, P140
010 40
20
30
Ø
22.2
Ø
19.05
Branch piping length (m)
1
0.90
0.80
Pipe diameter correction factor
P200
010 40
20
30
8-3-2. Correction factors for the indoor units and branch pipe diameter
OUTDOOR UNITS
53
8. UNIT SELECTION
8-3-3. Correction factors for the downstream indoor units and the pipes at the downstream of
the branch pipe
P81~P40
1
0.90
Pipe diameter correction factor
0.80 010 40
Equivalent main piping length (m)
20
30
P161~P200
1
0.90
Ø
15.88
Ø
Ø
22.2
19.05
P331~P400
1
0.90
Pipe diameter correction factor
0.80 010 40
Equivalent main piping length (m)
20
30
P401~P630
1
0.90
Ø
28.58
Ø
28.58
Pipe diameter correction factor
0.80 010 40
Equivalent main piping length (m)
20
30
P201~P300
1
0.90
Pipe diameter correction factor
0.80 010 40
Equivalent main piping length (m)
20
30
Ø
22.2
Pipe diameter correction factor
0.80 010 40
Equivalent main piping length (m)
20
30
P631~P650
1
0.90
Pipe diameter correction factor
0.80 010 40
Equivalent main piping length (m)
20
30
Ø
34.93
Ø
28.58
OUTDOOR UNITS 54
8. UNIT SELECTION
Equivalent main piping length (m)
Ø
34.93
1
0.90
0.80
Pipe diameter correction factor
P651~P800
010 40
20
30
OUTDOOR UNITS
55
I.Optional parts for the heat source units1. JOINT
56
R2 SERIES
OUTDOOR UNITS
I.R2 SERIES
1. SPECIFICATIONS........................................................................................................................................... 58
2. EXTERNAL DIMENSIONS .............................................................................................................................. 60
3. CENTER OF GRAVITY ................................................................................................................................... 62
4. ELECTRICAL WIRING DIAGRAMS................................................................................................................ 63
5. SOUND LEVELS ............................................................................................................................................. 64
6. CAPACITY TABLES........................................................................................................................................ 65
6-1. Correction by temperature....................................................................................................................... 65
6-2. Correction by total indoor......................................................................................................................... 67
6-3. Correction by refrigerant piping length..................................................................................................... 68
6-4. Correction by port counts of the BC controller......................................................................................... 70
6-5. Correction at frost and defrost ................................................................................................................. 70
6-6. Operation temperature range .................................................................................................................. 71
7. UNIT SELECTION........................................................................................................................................... 72
7-1. Indoor and outdoor unit selection ............................................................................................................ 72
7-2. Calculation samples................................................................................................................................. 74
7-3. Pipe diameter correction factor ................................................................................................................ 77
OUTDOOR UNITS
57
1. SPECIFICATIONS
I.R2 SERIES1. SPECIFICATIONS
Model PURY-RP200YJM-A(-BS) PURY-RP250YJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 22.4 28.0
(Nominal) *1 kcal / h 19,300 24,100
*1 BTU / h 76,400 95,500
Power input kW 5.23 7.28
Current input A 8.8-8.3-8.0 12.2-11.6-11.2
COP kW / kW 4.28 3.84
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F) 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F) -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 25.0 31.5
(Nominal) *2 kcal / h 21,500 27,100
Power input kW 5.81 7.72
Current input A 9.8-9.3-8.9 13.0-12.3-11.9
COP kW / kW 4.30 4.08
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F) 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F) -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~150 % of outdoor unit capacity 50~150 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~20 P15~P250 / 1~25
Sound pressure level (measured in anechoic room) dB <A> 56 57
Refrigerant High pressure mm (in.) 19.05(3/4) Brazed 19.05(3/4) Brazed
piping diameter Low pressure mm (in.) 28.58(1-1/8) Brazed 28.58(1-1/8) Brazed
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 1,220 x 760 1,710(1,650 without legs) x 1,220 x 760
Protection devices High pressure protection
Refrigerant Type x original charge R410A x 11.8kg (27lbs) R410A x 11.8kg (27lbs)
Net weight kg (lbs) 275(607) 290(640)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) - -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle) Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C669 KD94C669
Standard attachment Document Installation Manual Installation Manual
Optional parts Joint: CMY-R160-J1 Joint: CMY-R160-J1
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Air flow rate m3 / min 225 225
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 5.4 6.8
Case heater kW 0.035(240 V) 0.045(240 V)
Lubricant MEL32 MEL32
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor Discharge thermo protection, Over-current protection Discharge thermo protection, Over-current protection
Fan motor Thermal switch Thermal switch
Control Indoor LEV and BC controller Indoor LEV and BC controller
Wiring KE94C428 KE94C428
Accessory Refrigerant conn. pipe Refrigerant conn. pipe
*2 BTU / h 85,300 107,500
L/s 3,750 3,750
cfm 7,945 7,945
Pre-coated galvanized steel sheets (+powder coating for -BS
in. 67-3/8(65 without legs) x 48-1/16 x 29-15/16 67-3/8(65 without legs) x 48-1/16 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.6MPa
BC controller: CMB-P104,105,106,108,1010,1013,1016V-G1 BC controller: CMB-P104,105,106,108,1010,1013,1016V-G1
Main BC controller: CMB-P108,1010,1013,1016V-GA1 Main BC controller: CMB-P108,1010,1013,1016V-GA1
Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1 Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
type)
<MUNSELL 5Y 8/1> <MUNSELL 5Y 8/1>
(601,522 psi)
Pre-coated galvanized steel sheets (+powder coating for -BS
High pressure sensor, High pressure switch at 4.15,3.6MPa
type)
(601,522 psi)
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS 58
1. SPECIFICATIONS
Model PURY-RP300YJM-A(-BS)
Power source 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 33.5
(Nominal) *1 kcal / h 28,800
*1 BTU / h 114,300
Power input kW 8.83
Current input A 14.9-14.1-13.6
COP kW / kW 3.79
Temp. range of Indoor W.B. 15.0~24.0°C(59~75°F)
cooling Outdoor D.B. -5.0~43.0°C(23~109°F)
Heating capacity *2 kW 37.5
(Nominal) *2 kcal / h 32,300
Power input kW 9.48
Current input A 16.0-15.2-14.6
COP kW / kW 3.95
Temp. range of Indoor D.B. 15.0~27.0°C(59~81°F)
heating Outdoor W.B. -20.0~15.5°C(-4~60°F)
Indoor unit Total capacity 50~150 % of outdoor unit capacity
connectable Model / Quantity P15~P250 / 1~30
Sound pressure level (measured in anechoic room) dB <A> 59
Refrigerant High pressure mm (in.) 19.05(3/4) Brazed
piping diameter Low pressure mm (in.) 28.58(1-1/8) Brazed
FAN Type x Quantity Propeller fan x 1
Compressor Type x Quantity Inverter scroll hermetic compressor
External finish
External dimension HxWxD mm 1,710(1,650 without legs) x 1,220 x 760
Protection devices High pressure protection
Refrigerant Type x original charge R410A x 11.8kg (27lbs)
Net weight kg (lbs) 290(640)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) -
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KD94C669
Standard attachment Document Installation Manual
Optional parts Joint: CMY-R160-J1
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1) Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1) Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB) Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH2O, 6.1 mmH2O).
Air flow rate m3 / min 225
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1
*3 External static press. 0 Pa (0 mmH2O)
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 7.8
Case heater kW 0.045(240 V)
Lubricant MEL32
Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection
Compressor Discharge thermo protection, Over-current protection
Fan motor Thermal switch
Control Indoor LEV and BC controller
Wiring KE94C428
Accessory Refrigerant conn. pipe
*2 BTU / h 128,000
L/s 3,750
cfm 7,945
Pre-coated galvanized steel sheets (+powder coating for -BS
in. 67-3/8(65 without legs) x 48-1/16 x 29-15/16
High pressure sensor, High pressure switch at 4.15,3.6MPa
BC controller: CMB-P104,105,106,108,1010,1013,1016V-G1
Main BC controller: CMB-P108,1010,1013,1016V-GA1
Sub BC controller: CMB-P1 04,108V-GB1,CMB-P1016V-HB1
ferred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice.
.Our company is unable to guar antee reliability of pre-existing pipes and pre-existing cables.
type)
<MUNSELL 5Y 8/1>
(601,522 psi)
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg / 0.4536
*The specification data is
subject to rounding variation.
OUTDOOR UNITS
59
2. EXTERNAL DIMENSIONS
PURY-RP200, 250, 300YJM-A (-BS)
Unit : mm
ø19.05 Brazed263
Low
pressure
High
pressure
Low
pressure
High
pressure
AB
Position dimensions
for the refrigerant
service valve
Connecting pipe specifications
Model
Connection specifications for
the refrigerant service valve
ø28.58 Brazed261
PURY-RP300YJM-A(-BS)
PURY-RP250YJM-A(-BS)
PURY-RP200YJM-A(-BS)
A
B
145
145
271
83
301
150
8494
271
140
(Mounting pitch)
235
146
2
4
5
7
1
ø45 Knockout hole
ø34 Knockout hole
ø52 or ø27 Knockout hole
ø65 or ø40 Knockout hole
Specifications
140
×
77 Knockout hole
150
×
94 Knockout hole
ø65 Knockout hole
(Uses when twinning kit (optional
parts) is mounted.)
Front through hole
NO.
For pipes
For wires
For transmission cables
Usage
Front through hole
Bottom through hole
Front through hole
Front through hole
Bottom through hole
Front through hole
(front and back, 2 points)
Note 2*
<Accessories>
Connecting pipe
<Low pressure> • Pipe (IDø25.4 × IDø28.58) 1 pc.
Note 1. Please refer to (2/2) for information
regarding necessary spacing around the
unit and foundation work.
2. The detachable leg can be removed at site.
3. At brazing of pipes, wrap the refrigerant service
valve with wet cloth and keep the temperature of
refrigerant service valve under 120ºC.
55
*1. Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied.
*1
3
6
Refrigerant service
valve <High pressure>
217
77
90
58
75
251
Detachable leg
760
60
55
60
(60)
(Mounting pitch)
2×2-14×20 Oval hole
Refrigerant service
valve <Low pressure>
Refrigerant service
valve <High pressure>
Refrigerant service
valve <Low pressure>
(60)
1710
1220
760
1650
2401410
216
18
724 (721~727)
8080
1060
18
Intake
air
Control box
Intake
air
Service
panel
131
(760)
Discharge air
Intake
air
54
25
25
Front view
Bottom view
Top view
Left side view
2. EXTERNAL DIMENSIONS
OUTDOOR UNITS 60
2. EXTERNAL DIMENSIONS
PURY-RP200, 250, 300YJM-A (-BS)
Unit : mm
Secure enough space around the unit as shown in the figure below.
In case of single installation
1. Required space around the unit
2. Foundation work
When the height of the walls on the front, back or on the sides <H>
exceeds the wall height limit as defined below, add the height
that exceeds the height limit <h> to the figures that are marked
with an asterisk.
<Wall height limit> Front: Up to the unit height
Back: Up to 500 mm from
the unit bottom
Side: Up to the unit height
<Top view>
<Top view>
Front
Front
<To be left open>
Front
H
h
h
H
Unit height
30 min.
450 min. 450 min.
15 min.*
15 min.*
50 min.*
50 min.*
300 min.*
450 min.*
100 min.*
450 min.*
300 min.*450 min.*
15 min.*
500
<To be left open>
<To be left open>
<To be left open>
<To be left open>
<To be left open>
<To be left open>
<Side view>
100 min.*450 min.*
100 min.
450 min.* 450 min. 450 min. 100 min.*
300 min.*900 min.300 min.*
300 min.*900 min.
1000 min.*
Detachable leg
30 mm max.
M10 anchor bolt
<field supply required>
Corner of the
installation leg
Corner of the
installation leg
M10 anchor bolt
<field supply required>
30 mm max.
• With a space of at least
100 mm to the wall on
the back of the unit
• With a space of at least
300 mm to the wall on
the back of the unit
<field supply required>
<field supply required>
Detachable leg
Take into consideration the surface strength, water drainage route,
piping route, and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
Build the foundation in such way that the corner of the installation leg is
securely supported as shown in the right figure. (Fig.A, B)
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
The protrusion length of the anchor bolt must not exceed 30 mm. (Fig.A, B)
Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts. (Fig.C, D)
To prevent small animals and water and snow from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
Refer to the Installation Manual when installing units on an installation base.
<Unit: mm>
Wall <H>
Wall <H>
Front
Wall <H>
Front
Front
Front
Wall <H>
Wall <H>
Front
Front
Front
Front
<To be left open>
<To be left open>
Wall <H>
Wall <H>
Wall <H>
Front
<To be left open>
<Unit: mm>
Wall <H>
Wall <H>
Front
When multiple units are installed adjacent to each other, secure enough space to allow
for air circulation and walkway between groups of units as shown in the figures below.
At least two sides must be left open.
As with the single installation, add the height that exceeds the height limit <h>
to the figures that are marked with an asterisk.
If there is a wall at both the front and the rear of the unit, install up to six units
consecutively in the side direction and provide a space of 1000 mm or more as inlet space/
passage space for each six units.
In case of collective installation
Fig.A (without detachable legs)
Fig.B (with detachable legs)
Fixing plate
Fig.C (without detachable legs) Fig.D (with detachable legs)
Fixing plate
OUTDOOR UNITS
61
3. CENTER OF GRAVITY
PURY-RP200, RP250, RP300YJM-A (-BS)
1060
80
Y
724
1470
Z
60
1220
X
760
Model X Y Z
Unit: mm
445 342 642 443 333 633
PURY-RP200YJM-A (-BS) PURY-RP250, 300YJM-A (-BS)
3. CENTER OF GRAVITY
OUTDOOR UNITS 62
4. ELECTRICAL WIRING DIAGRAMS
PURY-RP200, 250, 300YJM-A (-BS)
Discharge suction bypass
SV2
Middle pressure control
Heat exchanger low pressure bypass
Heat exchanger capacity control
SV5c
SV6
4-way valve (Cooling/Heating switching)
Explanation
Symbol
63H1
Pressure
switch
High pressure protection for the
outdoor unit
Symbol
Explanation
Solenoid
valve
Discharge pressure
Pressure
sensor
63HS1
63H2
Low pressure
Magnetic relay (inverter main circuit)
Current sensor (AC)
Crankcase heater (for heating the compressor)
DC reactor
63LS
72C
CH11
CT12, 22, 3
DCL
63HS2
Pressure protection for pre-
existing pipes
Middle pressure
Solenoid
valve
SV1a
SV4a, b, c, d
SLEV
Oil flow control
21S4a
Terminal
block
Thermistor
Liquid pipe temperature
Discharge pipe temperature
For opening/closing the bypass
circuit
ACC inlet pipe temperature
Heat exchanger inlet pipe
temperature
OA temperature
IPM temperature
Function setting connector
Power supply
Indoor/Outdoor transmission
cable
Central control transmission
cable
For opening/closing the bypass
circuit
SV5b
Z24, 25
THHS
TH7
TH6
SV8
TH5
TH4
TH3
TB7
TB3
TB1
SV9
For opening/closing the bypass
circuit under the O/S
Refrigerant charging port for
auto-charge
*1. Single-dotted lines indicate wiring
not supplied with the unit.
*2. Dot-dash lines indicate the control
box boundaries.
*3. Refer to the Data book for connecting
input/output signal connectors.
*4. Faston terminals have a locking
function. Make sure the terminals
are securely locked in place after
insertion. Press the tab on the
terminals to remove them.
*5. Control box houses high-voltage parts.
Before inspecting the inside of the
control box, turn off the power, keep
the unit off for at least 10 minutes,
and confirm that the voltage between
FT-P and FT-N on INV Board has dropped
to DC20V or less.
<Symbol explanation>
3
5
1
SV8
X06
SV4d
X11
SV4c
3121
P
63H2
M
SLEV
65432
1
CNLVD
blue
63HS2
312
CN992
yellow
123
5
1
X12
SV6
3
1
CNTYP
black
C100
SW1
ONOFF
1
10
SW2
ONOFF
1
10
SW3
ONOFF
1
1's
digit
LED1
Display
setting
LED2: CPU in operation
C5
Z5
C3
C2
F2
R1
R2
3
3
Z241Z25
CNTYP5
green
CNTYP4
green
2
4
F1
CNTYP2
black
R3
Z1 Z2
R34
C30
C32
C34
C36
213
63LS
63HS1
213
321
CN202
red
CN201
2
10
OFF
1
TB1
black
F3
N
L3L2L1
F4
AC250V
6.3A T
black
white
L
F1,F2,F3
AC250V
6.3A T
DSA
R35
CT3
R4
white
R33
SC-L3
R30
U
red white
D1
1
R5
R32
red
CNIT
R6
CN2
3
1
2
C31
CN18V
blue
W
6
yellow
CNS2
5
U
TB7 Power
selecting
connector
Z4
Function
setting
CN5
red
4
51
C11
CN4
red
3
TB21
CN1B
L1
14
LED1: Power supply to
Indoor/Outdoor transmission line
1
ZNR01
CN1A
U
MS
3~
6235
red
Noise
Filter
ON
OFF
TB22
CN3
green
TB24
3
Fan motor
(Heat exchanger)
N
C33
TB23
1
CN211
TH4
4
IPM
FAN Board
F01
DC700V
4A T
1
LED3: Lit when powered
*4
M
3~
black
1
U
red
DB1
2
2
N
72C
1
Central control
transmission
cable
Motor
(Compressor)
black
V
Indoor/Outdoor
transmission
cable
SC-P2
4
1
CN41
CN40
4
CN3D
123
C7
C8
red
CN3S
12
3
TP2TP1
CT12
black
L2
L3L2
R5
U
LED1: Normal
operation
1
3
L1
3
SWU2
red
2
C35
3
M2
1
3
M-NET power
supply circuit
CN213
red
1
63H1
P
1
white
CNIT
red
SWU1
10
*3
CN51
5432
CN102
CN04
red
2
SC-L2
red
CN212
2
SC-P1
4
TH6
1
4
CNS2
yellow
TB3
32
TB7
SC-U
S
M-NET Board
CN1
black
C37
CN5V
yellow
C1
C9
10's
digit
C10
Unit address
setting
CN6
4
DCL
3
1
LED1: Normal operation (lit)
/ Error (blink)
1
CN990
3
blue
CN3N
1
*3
1
LED3: CPU in
operation
2
CNAC
red
21
R1
2
1
3
TH7
TH3
TH5
11
M1
F01
AC250V
3.15A T
3
M1
CN4
1
CN2
1
M2
SC-V
U
IPM
CT22
CNAC2
black
2
6
5
72C
1
CN4CN332
blue
5
Power failure
detection circuit
2
1
U
21
SW4
ONOFF
1
CNINV
CN2
CN102
432
1
1
CNDC
pink
123
CPU power
supply circuit
ON
2
CN72
red
10
SW5
LED1
Control Board
SC-W
5
SC-L1
4
1
7
2
3
CN801
yellow
CNT01
21
CNT02
13 1
W
2
234
1
CN21
blue
U
2
CNVDC
114
7
CN4
blue
Compressor ON/OFF output
Error detection output
1
C631
4
1
1
12V
Indoor/Outdoor
transmission
cable
LED2: Error
R63031R631
2
CN22
red
Z3
CN5
2
R31
1
C6
Power Source
3N~
50/60Hz
380/400/415V
2
5C17
RSH1
THHS
FT-P
*5
P
N
FT-N
C4
INV Board
1
C630
+++
+
+++
+
3
red
L3
1
2
1
1
+
+
-
V
2
1
CN502 X02
SV1a
CH11
3
1
CN503
blue
X03
21S4a
1
3
CN504
green
X04
6
3
CN506
X05
SV5b
SV4a
6
5
CN507
red
3
1
X07
X08
SV4b
653
1
CN508
black
X09
X10
SV2
6
5
1
CN509
blue
X14
SV5c
X13
CN510
yellow
3
6
SV9
4. ELECTRICAL WIRING DIAGRAMS
OUTDOOR UNITS
63
5. SOUND LEVELS
Measurement condition PURY-RP200, 250, 300YJM-A (-BS)
Measurement location
1m
1m
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 65.0 63.5 61.0 56.0 53.0 48.5 45.0 42.5 59.0
Low noise mode
50/60Hz 61.0 59.5 49.0 44.5 41.5 38.5 39.5 37.5 50.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
Sound level of PURY-RP300YJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 62.5 61.0 58.5 53.0 50.0 45.5 39.0 36.0 56.0
Low noise mode
50/60Hz 56.5 48.5 46.0 39.0 38.5 32.5 33.0 25.5 44.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PURY-RP200YJM-A (-BS)
When Low Noise Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low Noise Mode automatically in the case that the operation condition is severe.
63 125 250 500 1k 2k 4k 8k dB(A)
Standard
50/60Hz 59.0 62.0 60.0 54.0 50.5 46.0 41.0 35.0 57.0
Low noise mode
50/60Hz 58.0 53.5 44.0 39.0 36.5 32.5 31.0 24.5 44.0
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum audible limit on continuous noise
Standard Low
50/60Hz 50/60Hz
Sound level of PURY-RP250YJM-A (-BS)
5. SOUND LEVELS
OUTDOOR UNITS 64
6. CAPACITY TABLES
6. CAPACITY TABLES
6-1. Correction by temperature
CITY MULTI could have various capacities at different designing temperatures. Using the nominal cooling/heating capacity values and the ratios below, the capacity can be found for various temperatures.
PURY-
Nominal Cooling Capacity
Input
PURY-
Nominal Cooling Capacity
Input
RP200YJM-A RP250YJM-A
kW
BTU/h
kW
22.4
76,400
5.23
RP300YJM-A
kW
BTU/h
kW
33.5
114,300
8.83
28.0
95,500
7.28
1.4
1.3
1.2
1.1
1.0
0.9
Ratio of cooling capacity
0.8
0.7
1.2
1.1
1.0
0.9
0.8
Ratio of power input
0.7
0.6
Indoor Temperature
PURY-
Nominal Heating Capacity
Input
PURY-
Nominal Heating Capacity
Input
RP200YJM-A RP250YJM-A
kW
BTU/h
kW
25.0
85,300
5.81
RP300YJM-A
kW
BTU/h
kW
37.5
128,000
9.48
31.5
107,500
7.72
0.5
-5 0 5 10 15 20 25 30 35 40 45
23 32 41 50 59 68 77 86 95 104 113
1.3
1.2
1.1
1.0
0.9
0.8
Ratio of heating capacity
0.7
0.6
1.0
0.9
0.8
Ratio of cooling capacity and power input Outdoor temperature
Indoor Temperature
0.7
Ratio of power input
0.6
0.5
0.4
-20
-4
-15 5
OUTDOOR UNITS
-10 14
Ratio of heating capacity and power input Outdoor temperature
-5
23
0
32
5
41
10 50
15 59
65
6. CAPACITY TABLES
Ratio of cooling capacity and power input Outdoor temperature
Ratio of heating capacity and power input Outdoor temperature
-5 0 5 10 15 20 25 30 35 40 45
23 32 41 50 59 68 77 86 95 104 113
1.1
1.2
1.0
0.9
0.8
0.7
0.6
0.5
Ratio of power input
-20
-4
-15 5
-10 14
-5
23
0
32
5
41
10 50
15 59
0.6
0.5
1.2
1.4
1.6
1.0
0.8
0.6
0.4
Ratio of power input
1.4
1.3
1.1
1.0
0.9
0.8
0.7
1.2
Ratio of cooling capacity
Indoor Temperature
1.3
1.2
1.0
0.9
0.8
0.7
1.1
Ratio of heating capacity
Indoor Temperature
Nominal Cooling Capacity
Input
kW
BTU/h
kW
Nominal Heating Capacity
Input
kW
BTU/h
kW
PURY-
RP200YJM-A RP250YJM-A
PURY-
RP200YJM-A RP250YJM-A
22.4
76,400
5.23
28.0
95,500
7.28
25.0
85,300
5.81
31.5
107,500
7.72
Nominal Cooling Capacity
Input
kW
BTU/h
kW
PURY-
RP300YJM-A
33.5
114,300
8.83
Nominal Heating Capacity
Input
kW
BTU/h
kW
PURY-
RP300YJM-A
37.5
128,000
9.48
Correction by temperature (High Heating Performance Mode)
CITY MULTI could have various capacities at different designing temperatures. Using the nominal cooling/heating capacity val­ues and the ratios below, the capacity can be found for various temperatures. To select high heating performance mode, DipSW 3-7 must be set to ON. (In the low ambient temperature, heating capacity and power input become higher than those under standard mode.)
OUTDOOR UNITS 66
6. CAPACITY TABLES
Capacity(kW)
Input(kW)
Total capacity of indoor units
15.0
10.0
10.0
20.0
25.0
30.0
35.0
2.0
6.0
8.0
4.0
100 200 300 400
100 200 300 400 500
Capacity(kW)
Input(kW)
Total capacity of indoor units
10.0
20.0
30.0
40.0
50.0
2.0
6.0
4.0
10.0
12.0
8.0
Cooling Heating
Cooling Heating
Cooling Heating
RP300
RP200 RP250
PURY-RP200, 250YJM-A (-BS)
PURY-RP300YJM-A (-BS)
6-2. Correction by total indoor
CITY MULTI system has different capacity and input at different total capacity of indoor unit connected. Using following tables, the maximum capacity can be observed so as to ensure the system having enough capacity to meet the conditions.
OUTDOOR UNITS
67
6. CAPACITY TABLES
Piping equivalent length (m)
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Cooling capacity correction factor
PURY-RP200YJM-A (-BS)
Total capacity of indoor unit
100
150
200 300
0 20 40 60 80 100 120
Piping equivalent length (m)
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Cooling capacity correction factor
PURY-RP250YJM-A (-BS)
Total capacity of indoor unit
125
188
250 375
0 20 40 60 80 100 120
Piping equivalent length (m)
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Cooling capacity correction factor
PURY-RP300YJM-A (-BS)
Total capacity of indoor unit
150
225
300 450
0 20 40 60 80 100 120
6-3. Correction by refrigerant piping length
CITY MULTI system can extend the piping flexibly within its limitation for the actual situation. Yet, a decrease of cooling/heating capacity could happen correspondently. Using following correction factor according to the equivalent length of the piping shown at 6-3-1 and 6-3-2, the capacity can be observed. 6-3-3 shows how to obtain the equivalent length of piping.
6-3-1. Cooling capacity correction
OUTDOOR UNITS 68
6. CAPACITY TABLES
6-3-2. Heating capacity correction
PURY-RP200YJM-A (-BS)
1.00
0.95
0.90
Heating capacity correction factor
0.85 0 20 40 60 80 100 120
Piping equivalent length (m)
PURY-RP250YJM-A (-BS)
1.00
0.95
0.90
Heating capacity correction factor
0.85 0 20 40 60 80 100 120
Piping equivalent length (m)
PURY-RP300YJM-A (-BS)
1.00
0.95
0.90
Heating capacity correction factor
0.85 0 20 40 60 80 100 120
Piping equivalent length (m)
OUTDOOR UNITS
69
6. CAPACITY TABLES
6-3-3. How to obtain the equivalent piping length
1. PURY-RP200YJM-A (-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.35 x number of bent on the piping) [m]
2. PURY-RP250, 300YJM-A (-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.42 x number of bent on the piping) [m]
6-4. Correction by port counts of the BC controller
Indoor unit sizes P200 and P250 must be connected to 2 ports on the BC controller. Indoor unit sizes from P100 to P140 should normally be connected to 2 ports on the BC controller (set BC controller DIP-SW 4-6 to its ON position). In cases whereby indoor unit sizes from P100 to P140 are connected to only 1port on the BC controller (set BC controller DIP-SW 4-6 to its OFF position), the cooling capacity of the indoor unit should be multiplied by a correction factor of 0.97.
6-5. Correction at frost and defrost
Due to frost at the outdoor heat exchanger and the automatic defrost operation, the heating capacity of the outdoor unit can be calculated by multiplying the correction factor shown in the table below.
Table of correction factor at frost and defrost
Outdoor inlet air temp. °C 64210-2-4-6-8-10-20
Outdoor inlet air temp. °F 43 39 36 34 32 28 25 21 18 14 -4
PURY-RP200YJM -A ( -BS ) 1.00 0.95 0.84 0.83 0.83 0.87 0.90 0.95 0.95 0.95 0.95
PURY-RP250YJM -A ( -BS ) 1.00 0.95 0.84 0.83 0.83 0.87 0.90 0.95 0.95 0.95 0.95
PURY-RP300YJM -A ( -BS ) 1.00 0.93 0.82 0.80 0.82 0.86 0.90 0.90 0.95 0.95 0.95
OUTDOOR UNITS 70
6. CAPACITY TABLES
30
25
20
15
10
5
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
-4 5 14 23 32 41 50 59 68 77 86 95 104 113 122
-4 5 14 23 32 41 50 59 68 77 86 95 104 113 122
Indoor temperature
Outdoor temperature
30
25
20
15
10
5
86
77
68
59
50
41
86
77
68
59
50
41
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
Indoor temperature
Outdoor temperature
Outdoor temperature
-5 to 21 CDB (23 to 70 FDB)
-6 to 15.5 CWB (21 to 60 FWB) 15 to 24 CWB (59 to 75 FWB)
15 to 27 CDB (59 to 81 FDB)
Indoor temperature
Cooling Heating
Ref.: PURY_YHM-A_TMPRNG_EUDB_ALL
Combination of cooling/heating operation (Cooling main or Heating main)
6-6. Operation temperature range
OUTDOOR UNITS
71
7. UNIT SELECTION
(1) Selecting indoor units
(2) Selecting outdoor units
1) Calculate the thermal road of each room.
2) Based on the thermal load corrected for indoor unit return air temperature, select appropriate indoor unit models. Refer to the correction factor diagram for the outdoor unit whose capacity is the closest to the total thermal load of the
system (Qi). Refer to “CAPACITY TABLES (Indoor unit)” and “6. CAPACITY TABLES.”
3) Calculate the total capacity of the indoor units in the system (N).
1) Based on the total capacity of the indoor units (N), tentatively select the capacity of the outdoor unit (X). The total capacity of the indoor units to be connected to a given outdoor unit (N) should not exceed the maximum
connectable capacity of the outdoor unit.
2) The tentatively selected standard capacity of the outdoor unit (X) will be defined as Qs. * If the total capacity of the indoor units that are connected to a given outdoor unit exceeds 100% of the outdoor unit
capacity (X), refer to the outdoor unit partial load capacity table, find the capacity that corresponds to the total capacity N, and use it as the standard outdoor unit capacity (Qs).
3) Obtain the maximum outdoor unit capacity (Qm) by multiplying Qs (standard outdoor unit capacity) by the following correction factors: piping length, outside air temperature, and defrost (heating).
Find the piping length correction factor from the diagram that corresponds to the total indoor unit capacity (N).
4) Make sure the maximum outdoor unit capacity Qm is equal to or greater than the total thermal load Qi.
If Qm is smaller than Qi, reconsider the outdoor unit capacity (X) so that Qm ≥ Qi will hold true.
5) After selecting indoor and outdoor units, calculate the apportioned indoor unit capacity, and make sure that the formula "Thermal load ≤ Indoor unit capacity" will hold true for each room.
If the thermal load exceeds the indoor unit capacity in one or more rooms, increase the indoor unit size as long as doing so
will not exceed the maximum connectable capacity of the outdoor unit. Then, start over from step 1) above. If the maximum connectable capacity is exceeded by increasing the indoor unit capacity, increase the outdoor capacity as well, then start over from step 1) above.
Qm = Qs x Piping length correction factor x Outside air temperature correction factor x Defrost correction factor (heating only) x Pipe diameter correction factor
Outside air temperature correction factor Piping length correction factor Defrost correction factor (heating only) Pipe diameter correction factor (applicable only if non-standard size pipes are connected)
Refer to 6-1. Refer to 6-3. Refer to 6-4. Refer to 8-3.
Calculate the indoor/outdoor unit capacities and check for unit compatibility by considering both the heating and the cooling loads. If the formula Qm ≥ Qi does not hold true for either cooling or heating, reconsider the outdoor unit capacity (X).
7. UNIT SELECTION
7-1. Indoor and outdoor unit selection
OUTDOOR UNITS 72
7. UNIT SELECTION
(3) Obtaining the unit capacity
A. If the apportioned indoor unit capacity obtained in step 5) on the previous page is equal to or greater than the rated
indoor unit capacity, the following formula will be used to calculate the indoor unit capacity: "Rated capacity x return air temperature correction factor x piping length correction factor (x pipe diameter correction factor)".
B. If the apportioned indoor unit capacity obtained in step 5) on the previous page is smaller than the rated indoor unit
capacity, the following formula will be used to calculate the indoor unit capacity: "Apportioned indoor unit capacity x return air temperature correction factor."
* The standard outside air temperatures used to obtain the return air temperature correction factor is 35ºCDB for cooling
and 6ºCWB for heating.
* If non-standard size pipes are connected, use the pipe diameter correction factors for the main pipes, merge pipes, and
branch pipes.
(4) Notes
When deciding the outside air temperature to calculate unit capacity requirements, take into consideration the possible temperature rise around the outdoor unit due to short-cycling. (When installing outdoor units collectively on the rooftop or if outdoor units are surrounded by walls or other objects, it is recommended to set the outside temperature as 43ºC for calculation.)
If you want to take sensible heat load into consideration, refer to the relevant catalogs for information on sensible heat factor when selecting indoor units.
OUTDOOR UNITS
73
7. UNIT SELECTION
(1) To connect indoor units using the standard pipes
A. Calculating the cooling load
B. Calculating the heating load
C. Calculating the capacity requirement
Design conditions <Cooling>
<Heating>
<Miscellaneous information>
a) The thermal load (13.5 kW/room), indoor unit return air temperature correction factor, and piping length correction
factor are used to calculate the required indoor unit capacity, based on which a 125 model of indoor unit is tentatively selected. (Because the total thermal load is 27 kW, the air temperature correction diagram for the 250 model outdoor
unit will be used.) b) Because the total capacity of indoor units (N) is 250, the 250 model outdoor unit is tentatively selected. Based on the above, the standard capacity Qs will be 28 kW. c) The correction values obtained from the air temperature correction factor graph and the piping length correction factor
graph for the 250 model outdoor units are as follows:
d) For the 300 model units, the outside air temperature correction factor is 0.99. The piping length correction factor that
can be obtained from the diagram for the system whose total indoor unit capacity is 250 would be 0.96. Because the standard outdoor unit capacity Qs is 33.5 kW, the maximum outdoor unit capacity Qm can be obtained
using the following formula: Qm = 33.5 x 0.99 x 0.96 = 31.8 kW. The result 31.8 kW is greater than the Qi (27 kW), so
the maximum capacity Qm meets the capacity requirement. e) Compare the thermal loads on the indoor units, using the maximum outdoor unit capacity apportioned to each indoor
unit and taking the indoor unit return air temperature correction factors into consideration. The correction factor for the
return air temperature at 18.5ºCWB is 0.99 (at the standard outside dry-bulb temperature of 35ºC), and this value can
be plugged into the following formula to obtain the capacity.
32.1 kW x 125/250 x 0.99 = 15.8 kW The result shows that the capacity (15.8 kW) is greater than the thermal load (13.5 kW), and based on this result, two
125 model indoor units and one 300 model outdoor unit can be selected.
a) The standard capacity (Qs) of the tentatively selected 300 model outdoor unit is 37.5 kW. b) Use this value in the following formula to obtain the maximum outdoor unit capacity Qm as shown below: Qm = 37.5 x 1.00 x 0.965 x 0.975 = 35.2 kW, (where the outside air temperature is 5ºCWB, capacity correction factor
is 1.00 (at the standard indoor dry-bulb temperature of 20ºC), defrost correction factor is 0.965, piping length is 50 m,
and capacity correction factor is 0.975). The result shows that the Maximum outdoor unit capacity Qm (35.2 kW) exceeds the heating load Qi (29 kW). c) You can now check to see if this value will meet the capacity requirement for each indoor unit by using the following
formula: 35.2 x 125/250 x 0.96 = 16.8 kW (where the indoor unit return air temperature correction factor at 21ºCDB is
0.96) (standard outside temperature at 6ºC). The result shows that the unit capacity (16.8 kW) exceeds the thermal
load for each room (14.5 kW). Based on the above calculation, the following indoor and outdoor units can be selected. Indoor units: 125 model x 2 units Outdoor unit: RP300 model
a) The cooling capacity of the tentatively selected outdoor unit apportioned to each indoor unit is 15.8 kW, which exceeds
the rated cooling capacity of the 125 model unit (14.0 kW). The actual cooling capacity under the specified conditions is
calculated as follows: 14.0 x 0.99 x 0.97 = 13.4 kW (where the return air temperature correction factor at the standard
outside temperature of 35ºCDB is 0.99 and the piping length correction factor is 0.97). b) The heating capacity of the tentatively selected outdoor unit apportioned to each indoor unit is 16.8 kW, which exceeds
the rated cooling capacity of the 125 model unit (16.0 kW). The actual heating capacity under the specified conditions is
calculated as follows: 16.0 x 0.95 x 0.975 = 14.8 kW (where the return air temperature correction factor at the standard
outside temperature of 6ºCWB is 0.95 and the piping length correction factor is 0.975).
If the standard capacity Qs is corrected for indoor/outside air temperatures and piping length, the maximum outdoor unit
capacity Qm can be obtained as follows: Qm = 28 x 0.99 x 0.97 = 26.8 kW.
The result shows that the thermal load Qi (27 kW) exceeds the unit capacity Qm, so a larger 300 model outdoor unit
needs to be selected.
Main piping: ø28.58 x 45 m, Branch piping: ø19.05 x 5 m (Equivalent indoor and outdoor piping length: 50 m)
Indoor design dry-bulb temperature: 26ºC/Indoor design wet-bulb temperature: 18.5ºC Outdoor design dry-bulb temperature: 36ºC Cooling load: 13.5 kW for each of the two rooms
Indoor design dry-bulb temperature: 21ºC Outdoor design wet-bulb temperature: 5ºC Heating load: 14.5 kW for each of the two rooms
Outside air temperature 36ºCDB Piping length: 50 m
Capacity correction factor 0.99 (at the standard indoor wet-bulb temperature of 19ºC) Capacity correction factor: 0.97
Next, you will calculate the heating load and unit capacity requirements, using the models that were selected in the previous section.
7-2. Calculation samples
OUTDOOR UNITS 74
7. UNIT SELECTION
(2) To connect indoor units using non-standard pipes
Design conditions <Cooling>
<Heating>
<Miscellaneous information>
A. Calculating the cooling load
a) The thermal load of 13 kW per room and the indoor unit return air temperature correction factor are used to calculate
the required indoor unit capacity, based on which a 125 model of indoor unit is tentatively selected. (Because the total thermal load is 26 kW, the air temperature correction diagram for the 250 model outdoor unit will be used.)
b) Because the total capacity of indoor units (N) is 250, the 250 model outdoor unit is tentatively selected. Based on the above, the standard capacity Qs will be 28 kW.
c) The correction values obtained from the air temperature correction factor graph and the piping length correction factor
graph for the 250 model outdoor units are as follows:
Indoor design dry-bulb temperature: 26ºC/Indoor design wet-bulb temperature: 18.5ºC Outdoor design dry-bulb temperature: 36ºC Cooling load: 13.5 kW for each of the two rooms Indoor design dry-bulb temperature: 21ºC Outdoor design wet-bulb temperature: 5ºC Heating load: 14.5 kW for each of the two rooms
Main piping: ø25.4 x 45 m, Branch piping: ø15.88 x 5 m (Equivalent indoor and outdoor piping length: 50 m)
Outside air temperature 36ºCDB Piping length: 50 m Main piping: ø25.4 x 45 m
The standard capacity Qs is corrected for indoor/outside air temperatures, piping length, and pipe diameter to obtain the maximum outdoor unit capacity Qm as follows: Qm = 28 x 0.99 x 0.97 x 0.98 = 26.3 kW. Because this value does not meet the thermal load Qi (27 kW), a larger 300 model outdoor unit needs to be selected.
d) For the 300 model, the outside air temperature correction factor is 0.99, the pipe diameter correction factor for a 45 m
pipe with a diameter of ø25.4 is 0.98, and the piping length correction factor is 0.96 (read from the diagram for the unit whose total indoor unit capacity N is 250).
Where the standard outdoor unit capacity Qs is 33.5 kW, the maximum outdoor unit capacity Qm can be obtained as
follows: Qm = 33.5 x 0.99 x 0.98 x 0.96= 31.2 kW. This value is greater than the thermal load Qi (27 kW), and the maximum capacity Qm satisfies the capacity requirements.
e) Compare the thermal loads on the indoor unit side, using the maximum outdoor unit capacity apportioned to each
indoor unit and taking the indoor unit return air condition correction factors into consideration. The correction factor for the return air temperature at 18.5ºC is 0.99 (at the standard outside dry-bulb temperature of 35ºC), and the pipe diameter correction factor for a 5 m pipe with a diameter of ø15.88 connected to a 125-model unit is 0.99. These values can be plugged into the following formula to obtain the capacity.
31.8 kW x 125/250 x 0.99 x 0.99=15.5 kW. The result shows that the capacity (15.5 kW) is greater than the thermal load of 13.5 kW, and based on this result, two
125 model indoor units and one 300 model outdoor unit can be selected.
B. Calculating the heating load
Next, we will calculate the heating load, using the models that are selected based on the cooling load calculation.
a) The standard capacity Qs of the tentatively selected (during cooling load calculation) 300 model outdoor unit is 37.5
kW.
b) The correction values obtained from the air temperature correction factor graph and the piping length correction factor
graph for the 300 model outdoor units are as follows:
Capacity correction factor 0.99 (at the standard indoor wet-bulb temperature of 19ºC) Capacity correction factor: 0.97 Pipe diameter correction factor: 0.98
Outside air temperature 5ºCWB
Piping length: 50 m
The standard capacity Qs is corrected for indoor/outside air temperatures and piping length to obtain the maximum outdoor unit capacity Qm as follows: Qm = 37.5 x 1.00 x 0.975 x 0.975 = 35.6 kW. The result shows that the Maximum outdoor unit capacity Qm (35.6 kW) exceeds the heating load Qi (29 kW).
c) You can now check to see if this value will meet the capacity requirement for each indoor unit by using the following
formula: 35.6 x 125/250 x 0.96 x 0.99 = 16.9 kW (where the correction factor for the indoor unit return air temperature of 21ºCDB is 0.96 (standard outside temperature at 6ºC), and the pipe diameter correction factor for a 5 m branch pipe with a diameter of ø15.88 connected to a 125 models is 0.99. The result shows that the unit capacity 16.9 kW exceeds the thermal load for each room (14.5 kW).
Based on the above calculation, the following indoor and outdoor units can be selected. Indoor units: 125 model x 2 units Outdoor unit: RP300 model
Capacity correction factor 1.00 (at the standard indoor dry-bulb temperature of 20ºC) Defrost correction factor is 0.975 Capacity correction factor: 0.975
OUTDOOR UNITS
75
7. UNIT SELECTION
<Capacity requirement calculation flow chart>
Obtain the thermal load (Qi).
Correct for the indoor unit return air temperature.
Determine the capacity for each indoor unit.
Calculate the total indoor unit capacity (N).
Finish (calculations to be done for both cooling and heating)
Select the outdoor unit capacity (X).
Select the outdoor unit one rank higher in capacity.
Apportion the corrected outdoor unit capacity (Qm) to each indoor unit.
Multiply the apportioned capacity by the indoor unit temperature correction factor, and make sure it is equal to or greater than the thermal load.
Thermal load Qi > Corrected capacity Qm
YES
NO
Correct the standard outdoor unit capacity (Qs) for outside air temperature and piping length to obtain the corrected capacity (Qm).
OUTDOOR UNITS 76
7. UNIT SELECTION
Equivalent main piping length (m)
Ø
19.05
Ø
22.2
Ø
25.4
1
0.90
0.80
0.60
0.70
Pipe diameter correction factor
PURY-RP200YJM-A
0 20 40 60 80 100
Equivalent main piping length (m)
Ø
22.2
Ø
25.4
1
0.90
0.80
0.60
0.70
Pipe diameter correction factor
PURY-RP250YJM-A
0 20406080100
Equivalent main piping length (m)
Ø
22.2
Ø
25.4
1
0.90
0.80
0.60
0.70
Pipe diameter correction factor
PURY-RP300YJM-A
0 20 40 60 80 100
7-3. Pipe diameter correction factor
7-3-1. Correction factors for the outdoor units and main pipe diameter
OUTDOOR UNITS
77
7. UNIT SELECTION
7-3-2. Correction factors for the indoor units and branch pipe diameter
P50
1
0.90
Pipe diameter correction factor
0.80 010 40
Branch piping length (m)
20
30
P100, P125, P140
1
0.90
Ø
12.7
Ø
15.88
P250
1
0.90
Pipe diameter correction factor
0.80 010 40
Branch piping length (m)
20
30
Ø
Ø
25.4
22.2
Pipe diameter correction factor
0.80 010 40
Branch piping length (m)
20
30
P200
1
0.90
Pipe diameter correction factor
0.80
010 40
Branch piping length (m)
20
30
Ø
22.2
Ø
19.05
OUTDOOR UNITS 78
7. UNIT SELECTION
Equivalent main piping length (m)
Ø
15.88
1
0.90
0.80
Pipe diameter correction factor
P81~P40
010 40
20
30
Equivalent main piping length (m)
1
0.90
0.80
Pipe diameter correction factor
Ø
28.58
P331~P400
010 40
20
30
Equivalent main piping length (m)
Ø
22.2
Ø
19.05
1
0.90
0.80
Pipe diameter correction factor
P161~P200
010 40
20
30
Equivalent main piping length (m)
Ø
28.58
1
0.90
0.80
Pipe diameter correction factor
P401~P630
010 40
20
30
Equivalent main piping length (m)
Ø
22.2
1
0.90
0.80
Pipe diameter correction factor
P201~P300
010 40
20
30
Equivalent main piping length (m)
Ø
28.58
Ø
34.93
1
0.90
0.80
Pipe diameter correction factor
P631~P650
010 40
20
30
7-3-3. Correction factors for the downstream indoor units and the pipes at the downstream of
the branch pipe
OUTDOOR UNITS
79
7. UNIT SELECTION
P651~P800
1
0.90
Pipe diameter correction factor
Ø
34.93
0.80 010 40
Equivalent main piping length (m)
20
30
OUTDOOR UNITS 80
1. Cooling capacity with Outdoor units
PEFY-P-VMH-E PEFY-P-VMR-E-L/R PEFY-P-VMS1(L)-E
A1 A2 A3 A4
B1 B2 B3 B4
D1 D2 D3 D4
E1 E2 E3 E4
F1 F2 F3 F4
G1 G2 G3 G4
H1 H2 H3 H4
I1 I2 I3 I4
X1 X2 X3 X4
PUHY-RP200, 250YJM PURY-RP200, 250YJM
PUHY-RP200, 250YJM PURY-RP200, 250YJM
PUHY-RP300-400Y(S)JM PURY-RP300YJM
PUHY-RP450-650YSJM PUHY-RP700-800YSJM
PEFY-P-VMA(L)-E
PMFY-P-VBM-E
PLFY-P-VLMD-E
PLFY-P-VCM-E PLFY-P-VBM-E
PCFY-P-VKM-E
PKFY-P-VBM-E PKFY-P-VHM-E PKFY-P-VKM-E
PFFY-P-VKM-E PFFY-P-VLEM-E PFFY-P-VLRM-E PFFY-P-VLRMM-E
The databook reader is supposed to refer specified Indoor unit at the tables to check if the designed capacity in enough or not for your situation.
PEFY-P-VMH-E PEFY-P-VMR-E-L/R PEFY-P-VMS1(L)-E
A5
B5
D5
E5
F5
G5
H5
I5
PEFY-P-VMA(L)-E
PMFY-P-VBM-E
PLFY-P-VLMD-E PLFY-P-VCM-E
PLFY-P-VBM-E
PCFY-P-VKM-E
PKFY-P-VBM-E PKFY-P-VHM-E PKFY-P-VKM-E
PFFY-P-VKM-E PFFY-P-VLEM-E PFFY-P-VLRM-E PFFY-P-VLRMM-E
* For the cooling capacity of PEFY-P-VMH-E-F, please refer to its own section.
2. Heating capacity with Outdoor units
3. Capacity tables for PEFY-P-VMH-E-F
All Indoor units
PUHY-RP300-400Y(S)JM PURY-RP300YJM
PUHY-RP450-650YSJM PUHY-RP700-800YSJM
PUHY-RP850, 900YSJM
PUHY-RP850, 900YSJM
X5
* For the heating capacity of PEFY-P-VMH-E-F, please refer to its own section.
All Indoor units
CAPACITY TABLES (Indoor unit)
81
4.3 3.3 4.4 3.4 4.7 3.3 4.9 3.4 5.0 3.5 5.3 3.5 5.7 3.4
4.3 3.3 4.4 3.4 4.7 3.3 4.9 3.4 5.0 3.5 5.3 3.5 5.7 3.4
4.3 3.3 4.4 3.4 4.7 3.3 4.9 3.4 5.0 3.5 5.3 3.5 5.6 3.4
4.3 3.2 4.4 3.3 4.6 3.3 4.8 3.4 4.9 3.5 5.2 3.4 5.5 3.4
4.2 3.2 4.3 3.3 4.6 3.3 4.7 3.3 4.8 3.4 5.0 3.4 5.4 3.3
4.1 3.2 4.2 3.3 4.5 3.2 4.6 3.3 4.7 3.4 5.0 3.3 5.3 3.3
4.0 3.1 4.1 3.2 4.4 3.2 4.5 3.2 4.6 3.4 4.9 3.3 5.2 3.3
3.9 3.1 4.1 3.2 4.3 3.2 4.4 3.2 4.5 3.3 4.8 3.3 5.0 3.2
3.9 3.1 4.0 3.2 4.2 3.1 4.3 3.2 4.5 3.3 4.7 3.2 5.0 3.2
3.8 3.0 3.9 3.1 4.1 3.1 4.2 3.1 4.3 3.2 4.5 3.2 4.8 3.1
5.3 3.8 5.5 3.9 5.9 3.9 6.0 3.9 6.2 4.1 6.6 4.0 7.1 4.0
5.3 3.8 5.5 3.9 5.9 3.9 6.0 3.9 6.2 4.1 6.6 4.0 7.1 4.0
5.3 3.8 5.5 3.9 5.9 3.9 6.0 3.9 6.2 4.1 6.6 4.0 6.9 3.9
5.3 3.8 5.5 3.9 5.8 3.9 5.9 3.9 6.1 4.0 6.4 4.0 6.8 3.9
5.2 3.8 5.3 3.8 5.7 3.8 5.8 3.8 6.0 4.0 6.3 3.9 6.7 3.9
5.1 3.7 5.3 3.8 5.5 3.8 5.7 3.8 5.9 3.9 6.2 3.9 6.6 3.8
5.0 3.7 5.2 3.8 5.5 3.7 5.6 3.7 5.7 3.9 6.0 3.8 6.4 3.7
4.9 3.6 5.0 3.7 5.3 3.7 5.5 3.7 5.6 3.8 5.9 3.8 6.3 3.7
4.8 3.6 5.0 3.7 5.3 3.6 5.4 3.7 5.5 3.8 5.8 3.7 6.2 3.7
4.7 3.5 4.8 3.6 5.1 3.6 5.2 3.6 5.4 3.7 5.7 3.7 6.0 3.6
6.7 5.0 7.0 5.2 7.5 5.1 7.7 5.2 7.9 5.4 8.4 5.3 9.0 5.3
6.7 5.0 7.0 5.2 7.5 5.1 7.7 5.2 7.9 5.4 8.4 5.3 9.0 5.3
6.7 5.0 7.0 5.2 7.5 5.1 7.7 5.2 7.8 5.4 8.3 5.3 8.8 5.2
6.7 5.0 6.9 5.1 7.3 5.1 7.5 5.1 7.7 5.3 8.1 5.2 8.7 5.2
6.6 4.9 6.8 5.1 7.2 5.0 7.4 5.1 7.6 5.3 8.0 5.2 8.5 5.1
6.5 4.9 6.7 5.0 7.0 4.9 7.2 5.0 7.4 5.2 7.8 5.1 8.3 5.0
6.4 4.8 6.5 5.0 6.9 4.9 7.1 5.0 7.3 5.1 7.7 5.1 8.1 5.0
6.2 4.8 6.4 4.9 6.8 4.8 6.9 4.9 7.1 5.1 7.5 5.0 8.0 4.9
6.1 4.7 6.3 4.8 6.7 4.8 6.8 4.8 7.0 5.0 7.3 4.9 7.8 4.9
6.0 4.6 6.1 4.8 6.5 4.7 6.6 4.8 6.8 4.9 7.2 4.9 7.6 4.8
7.6 5.6 7.9 5.8 8.4 5.7 8.6 5.8 8.9 6.0 9.4 5.9 10.1 5.9
7.6 5.6 7.9 5.8 8.4 5.7 8.6 5.8 8.9 6.0 9.4 5.9 10.1 5.9
7.6 5.6 7.9 5.8 8.4 5.7 8.6 5.8 8.8 6.0 9.4 5.9 9.9 5.8
7.6 5.6 7.8 5.7 8.2 5.7 8.5 5.7 8.7 5.9 9.2 5.8 9.8 5.8
7.4 5.5 7.6 5.7 8.1 5.6 8.3 5.7 8.5 5.9 9.0 5.8 9.6 5.7
7.3 5.4 7.5 5.6 7.9 5.5 8.1 5.6 8.4 5.8 8.8 5.7 9.4 5.6
7.2 5.4 7.4 5.5 7.8 5.5 8.0 5.5 8.2 5.7 8.6 5.6 9.2 5.5
7.0 5.3 7.2 5.5 7.6 5.4 7.8 5.5 8.0 5.7 8.5 5.6 9.0 5.5
6.9 5.2 7.1 5.4 7.5 5.3 7.7 5.4 7.9 5.6 8.3 5.5 8.8 5.4
6.7 5.2 6.9 5.3 7.3 5.3 7.4 5.3 7.7 5.5 8.1 5.4 8.6 5.3
8.6 6.3 8.9 6.5 9.5 6.5 9.7 6.6 10.0 6.8 10.6 6.7 11.4 6.7
8.6 6.3 8.9 6.5 9.5 6.5 9.7 6.6 10.0 6.8 10.6 6.7 11.4 6.7
8.6 6.3 8.9 6.5 9.5 6.5 9.7 6.6 9.9 6.8 10.5 6.7 11.2 6.6
8.5 6.3 8.8 6.5 9.3 6.4 9.5 6.5 9.8 6.7 10.3 6.6 11.0 6.5
8.4 6.2 8.6 6.4 9.1 6.3 9.4 6.4 9.6 6.6 10.1 6.5 10.8 6.4
8.2 6.2 8.5 6.3 8.9 6.3 9.1 6.3 9.4 6.6 9.9 6.4 10.5 6.4
8.1 6.1 8.3 6.3 8.8 6.2 9.0 6.3 9.2 6.5 9.7 6.4 10.3 6.3
7.9 6.0 8.1 6.2 8.6 6.1 8.8 6.2 9.0 6.4 9.5 6.3 10.1 6.2
7.7 5.9 8.0 6.1 8.5 6.1 8.6 6.1 8.9 6.4 9.3 6.2 9.9 6.1
7.6 5.8 7.8 6.0 8.2 6.0 8.4 6.0 8.6 6.2 9.1 6.1 9.6 6.0
10.6 8.5 11.0 8.8 11.8 8.8 12.1 8.9 12.5 9.3 13.2 9.2 14.2 9.1
10.6 8.5 11.0 8.8 11.8 8.8 12.1 8.9 12.5 9.3 13.2 9.2 14.2 9.1
10.6 8.5 11.0 8.8 11.8 8.8 12.1 8.9 12.4 9.2 13.1 9.1 13.9 9.0
10.6 8.5 10.9 8.8 11.5 8.7 11.9 8.8 12.2 9.2 12.8 9.0 13.7 8.9
10.4 8.4 10.7 8.7 11.3 8.6 11.6 8.7 11.9 9.1 12.5 8.9 13.4 8.8
10.2 8.3 10.5 8.6 11.1 8.5 11.4 8.6 11.7 9.0 12.3 8.8 13.1 8.7
10.0 8.2 10.3 8.5 10.9 8.4 11.2 8.6 11.5 8.9 12.1 8.8 12.8 8.6
9.8 8.1 10.1 8.4 10.7 8.3 10.9 8.5 11.3 8.8 11.9 8.7 12.5 8.5
9.6 8.1 9.9 8.3 10.5 8.2 10.8 8.4 11.1 8.7 11.6 8.6 12.3 8.5
9.4 7.9 9.7 8.2 10.2 8.1 10.4 8.3 10.8 8.6 11.3 8.5 12.0 8.3
13.3 9.8 13.8 10.1 14.7 10.1 15.1 10.2 15.6 10.6 16.5 10.4 17.7 10.3
13.3 9.8 13.8 10.1 14.7 10.1 15.1 10.2 15.6 10.6 16.5 10.4 17.7 10.3
13.3 9.8 13.8 10.1 14.7 10.1 15.1 10.2 15.5 10.5 16.4 10.4 17.4 10.2
13.2 9.8 13.7 10.1 14.4 9.9 14.8 10.1 15.3 10.4 16.0 10.2 17.1 10.1
13.0 9.7 13.4 9.9 14.2 9.8 14.6 10.0 14.9 10.3 15.7 10.1 16.7 10.0
12.7 9.5 13.2 9.8 13.9 9.7 14.2 9.8 14.6 10.2 15.4 10.0 16.4 9.9
12.5 9.4 12.9 9.7 13.7 9.6 14.0 9.7 14.4 10.1 15.1 9.9 16.0 9.7
12.3 9.3 12.6 9.6 13.4 9.5 13.7 9.6 14.1 9.9 14.8 9.8 15.7 9.6
12.0 9.2 12.4 9.5 13.2 9.4 13.4 9.5 13.9 9.9 14.5 9.6 15.4 9.5
11.8 9.1 12.1 9.3 12.8 9.2 13.0 9.3 13.4 9.7 14.1 9.5 15.0 9.4
PEFY-P-VMH-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
kcal/h = kW x 860, Btu/h = kW x 3,412
Indoor air temp.
71 ˚FDB / 59˚FWB 73˚FDB / 61˚FWB 77˚FDB / 64˚FWB 81˚FDB / 66˚FWB 82˚FDB / 68˚FWB 86˚FDB / 72˚FWB 90˚FDB / 75˚FWB
21.5˚CDB / 15˚CWB 23˚CDB / 16˚CWB 25˚CDB / 18˚CWB 27˚CDB / 19˚CWB 28˚CDB / 20˚CWB 30˚CDB / 22˚CWB 32˚CDB / 24˚CWB
˚CDB˚FDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
40
(4.5)
50
(5.6)
63
(7.1)
71
(8.0)
Outdoor air temp.
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
68 73 77 82 86 91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
Model
size
(Rated kW)
80
(9.0)
100
(11.2)
125
(14.0)
CAPACITY TABLES
82
A1. Cooling capacity with PUHY-RP200, 250YJM/PURY-RP200, 250YJM
15.2 11.2 15.8 11.6 16.8 11.5 17.3 11.7 17.8 12.1 18.9 11.9 20.2 11.8
15.2 11.2 15.8 11.6 16.8 11.5 17.3 11.7 17.8 12.1 18.9 11.9 20.2 11.8
15.2 11.2 15.8 11.6 16.8 11.5 17.3 11.7 17.7 12.0 18.7 11.9 19.8 11.7
15.1 11.2 15.6 11.5 16.5 11.4 17.0 11.5 17.4 11.9 18.3 11.7 19.5 11.6
14.9 11.1 15.3 11.4 16.2 11.2 16.6 11.4 17.0 11.8 17.9 11.6 19.1 11.4
14.6 10.9 15.0 11.2 15.8 11.1 16.2 11.2 16.7 11.6 17.6 11.4 18.7 11.3
14.3 10.8 14.7 11.1 15.6 11.0 16.0 11.1 16.4 11.5 17.3 11.3 18.3 11.1
14.0 10.7 14.4 10.9 15.3 10.8 15.6 10.9 16.1 11.4 17.0 11.2 17.9 11.0
13.8 10.5 14.2 10.8 15.0 10.7 15.4 10.8 15.8 11.3 16.6 11.0 17.6 10.9
13.4 10.4 13.8 10.7 14.6 10.6 14.9 10.6 15.4 11.1 16.2 10.9 17.1 10.7
21.3 16.1 22.1 16.6 23.5 16.5 24.2 16.7 25.0 17.4 26.4 17.1 28.3 17.0
21.3 16.1 22.1 16.6 23.5 16.5 24.2 16.7 25.0 17.4 26.4 17.1 28.3 17.0
21.3 16.1 22.1 16.6 23.5 16.5 24.2 16.7 24.8 17.3 26.2 17.1 27.8 16.8
21.2 16.0 21.8 16.5 23.1 16.3 23.7 16.6 24.4 17.2 25.6 16.8 27.3 16.6
20.8 15.9 21.4 16.3 22.7 16.1 23.3 16.4 23.9 16.9 25.1 16.6 26.8 16.4
20.4 15.7 21.1 16.2 22.2 15.9 22.7 16.1 23.4 16.8 24.6 16.5 26.2 16.2
20.0 15.5 20.6 15.9 21.8 15.8 22.4 16.0 23.0 16.6 24.2 16.3 25.6 16.1
19.6 15.3 20.2 15.7 21.4 15.6 21.8 15.8 22.5 16.4 23.7 16.1 25.1 15.9
19.3 15.1 19.8 15.6 21.1 15.4 21.5 15.6 22.2 16.3 23.2 15.9 24.6 15.7
18.8 14.9 19.4 15.4 20.5 15.2 20.8 15.4 21.5 16.0 22.6 15.7 24.0 15.5
26.6 20.0 27.6 20.7 29.4 20.5 30.2 20.8 31.2 21.6 33.0 21.3 35.4 21.1
26.6 20.0 27.6 20.7 29.4 20.5 30.2 20.8 31.2 21.6 33.0 21.3 35.4 21.1
26.6 20.0 27.6 20.7 29.4 20.5 30.2 20.8 30.9 21.5 32.8 21.2 34.7 20.9
26.5 19.9 27.3 20.5 28.8 20.3 29.7 20.6 30.5 21.3 32.1 20.9 34.2 20.7
26.0 19.7 26.7 20.3 28.3 20.1 29.1 20.3 29.8 21.0 31.4 20.7 33.5 20.4
25.5 19.5 26.3 20.1 27.7 19.8 28.4 20.0 29.3 20.8 30.8 20.4 32.8 20.2
25.1 19.3 25.8 19.8 27.3 19.6 28.0 19.9 28.7 20.6 30.2 20.2 32.1 19.9
24.6 19.0 25.2 19.5 26.7 19.4 27.3 19.6 28.1 20.4 29.7 20.0 31.4 19.7
24.1 18.8 24.8 19.4 26.3 19.2 26.9 19.4 27.7 20.2 29.0 19.8 30.8 19.5
23.5 18.5 24.2 19.1 25.6 18.9 26.0 19.1 26.9 19.8 28.3 19.5 30.0 19.2
PEFY-P-VMH-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
kcal/h = kW x 860, Btu/h = kW x 3,412
Indoor air temp.
71 ˚FDB / 59˚FWB 73˚FDB / 61˚FWB 77˚FDB / 64˚FWB 81˚FDB / 66˚FWB 82˚FDB / 68˚FWB 86˚FDB / 72˚FWB 90˚FDB / 75˚FWB
21.5˚CDB / 15˚CWB 23˚CDB / 16˚CWB 25˚CDB / 18˚CWB 27˚CDB / 19˚CWB 28˚CDB / 20˚CWB 30˚CDB / 22˚CWB 32˚CDB / 24˚CWB
˚CDB˚FDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
140
(16.0)
200
(22.4)
250
(28.0)
Outdoor air temp.
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
68 73 77 82 86 91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
Model
size
(Rated kW)
A1. Cooling capacity with PUHY-RP200, 250YJM/PURY-RP200, 250YJM
CAPACITY TABLES
83
2.0 1.7 2.1 1.7 2.3 1.7 2.4 1.9 2.4 1.9 2.6 1.8 2.8 1.8
2.0 1.7 2.1 1.7 2.3 1.7 2.4 1.9 2.4 1.9 2.6 1.8 2.8 1.8
2.0 1.7 2.1 1.7 2.3 1.7 2.4 1.9 2.4 1.9 2.6 1.8 2.7 1.8
2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.9 2.4 1.8 2.5 1.8 2.7 1.8
1.9 1.6 2.0 1.7 2.2 1.7 2.3 1.8 2.3 1.8 2.5 1.8 2.6 1.8
1.9 1.6 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.6 1.8
1.9 1.6 2.0 1.7 2.1 1.7 2.2 1.8 2.2 1.8 2.4 1.8 2.5 1.7
1.8 1.6 1.9 1.7 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.5 1.7
1.8 1.6 1.9 1.7 2.0 1.6 2.1 1.8 2.1 1.8 2.3 1.7 2.4 1.7
1.8 1.6 1.8 1.6 2.0 1.6 2.0 1.7 2.0 1.7 2.2 1.7 2.4 1.7
2.5 1.9 2.7 2.0 2.9 2.0 3.0 2.2 3.1 2.1 3.3 2.1 3.5 2.1
2.5 1.9 2.7 2.0 2.9 2.0 3.0 2.2 3.1 2.1 3.3 2.1 3.5 2.1
2.5 1.9 2.7 2.0 2.9 2.0 3.0 2.2 3.1 2.1 3.3 2.1 3.5 2.1
2.5 1.9 2.6 2.0 2.8 2.0 3.0 2.1 3.0 2.1 3.2 2.1 3.4 2.1
2.5 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.1 2.0 3.3 2.0
2.4 1.9 2.5 2.0 2.7 1.9 2.8 2.1 2.9 2.1 3.1 2.0 3.3 2.0
2.4 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.8 2.0 3.0 2.0 3.2 2.0
2.4 1.8 2.5 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 2.0 3.1 2.0
2.3 1.8 2.4 1.9 2.6 1.9 2.7 2.0 2.7 2.0 2.9 2.0 3.1 1.9
2.3 1.8 2.4 1.9 2.5 1.8 2.6 2.0 2.6 1.9 2.8 1.9 3.0 1.9
3.2 2.3 3.4 2.5 3.7 2.5 3.9 2.6 4.0 2.6 4.2 2.6 4.6 2.6
3.2 2.3 3.4 2.5 3.7 2.5 3.9 2.6 4.0 2.6 4.2 2.6 4.6 2.6
3.2 2.3 3.4 2.5 3.7 2.5 3.9 2.6 4.0 2.6 4.2 2.6 4.5 2.5
3.2 2.3 3.4 2.4 3.6 2.4 3.8 2.6 3.9 2.5 4.1 2.5 4.4 2.5
3.2 2.3 3.3 2.4 3.6 2.4 3.7 2.6 3.8 2.5 4.0 2.5 4.3 2.5
3.1 2.3 3.3 2.4 3.5 2.4 3.7 2.5 3.7 2.5 4.0 2.5 4.2 2.4
3.1 2.3 3.2 2.4 3.4 2.3 3.6 2.5 3.7 2.5 3.9 2.4 4.1 2.4
3.0 2.2 3.2 2.3 3.3 2.3 3.5 2.5 3.6 2.4 3.8 2.4 4.0 2.4
3.0 2.2 3.1 2.3 3.3 2.3 3.5 2.4 3.5 2.4 3.7 2.4 4.0 2.3
2.9 2.2 3.0 2.3 3.2 2.2 3.3 2.4 3.3 2.3 3.6 2.3 3.9 2.3
PEFY-P-VMR-E-L/R
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
kcal/h = kW x 860, Btu/h = kW x 3,412
Indoor air temp.
71 ˚FDB / 59˚FWB 73˚FDB / 61˚FWB 77˚FDB / 64˚FWB 81˚FDB / 66˚FWB 82˚FDB / 68˚FWB 86˚FDB / 72˚FWB 90˚FDB / 75˚FWB
21.5˚CDB / 15˚CWB 23˚CDB / 16˚CWB 25˚CDB / 18˚CWB 27˚CDB / 19˚CWB 28˚CDB / 20˚CWB 30˚CDB / 22˚CWB 32˚CDB / 24˚CWB
˚CDB˚FDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20
(2.2)
25
(2.8)
32
(3.6)
Outdoor air temp.
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
68 73 77 82 86 91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
Model
size
(Rated kW)
CAPACITY TABLES
84
A1. Cooling capacity with PUHY-RP200, 250YJM/PURY-RP200, 250YJM
CAPACITY TABLES
85
A1. Cooling capacity with PUHY-RP200, 250YJM/PURY-RP200, 250YJM
1.5 1.4 1.6 1.5 1.8 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.2 1.6
1.5 1.4 1.6 1.5 1.8 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.2 1.6
1.5 1.4 1.6 1.5 1.8 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
1.5 1.4 1.6 1.5 1.7 1.5 1.8 1.6 1.8 1.6 1.9 1.6 2.1 1.6
1.5 1.4 1.6 1.5 1.7 1.5 1.8 1.6 1.8 1.6 1.9 1.6 2.0 1.6
1.5 1.4 1.5 1.5 1.6 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.5
1.4 1.4 1.5 1.5 1.6 1.5 1.7 1.6 1.7 1.6 1.8 1.5 1.9 1.5
1.4 1.4 1.5 1.5 1.6 1.4 1.7 1.6 1.7 1.5 1.8 1.5 1.9 1.5
1.4 1.4 1.5 1.4 1.6 1.4 1.6 1.6 1.7 1.5 1.8 1.5 1.9 1.5
1.4 1.4 1.4 1.4 1.5 1.4 1.6 1.5 1.6 1.5 1.7 1.5 1.8 1.5
2.0 1.7 2.1 1.8 2.3 1.8 2.4 2.0 2.4 1.9 2.6 1.9 2.8 1.9
2.0 1.7 2.1 1.8 2.3 1.8 2.4 2.0 2.4 1.9 2.6 1.9 2.8 1.9
2.0 1.7 2.1 1.8 2.3 1.8 2.4 2.0 2.4 1.9 2.6 1.9 2.7 1.9
2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
1.9 1.7 2.0 1.8 2.2 1.8 2.3 1.9 2.3 1.9 2.5 1.9 2.6 1.9
1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.8
1.9 1.7 2.0 1.8 2.1 1.7 2.2 1.9 2.2 1.9 2.4 1.9 2.5 1.8
1.8 1.7 1.9 1.7 2.0 1.7 2.1 1.9 2.2 1.9 2.3 1.8 2.5 1.8
1.8 1.7 1.9 1.7 2.0 1.7 2.1 1.9 2.1 1.8 2.3 1.8 2.4 1.8
1.8 1.6 1.8 1.7 2.0 1.7 2.0 1.8 2.0 1.8 2.2 1.8 2.4 1.8
2.5 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
2.5 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
2.5 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
2.5 2.1 2.6 2.2 2.8 2.2 3.0 2.3 3.0 2.3 3.2 2.3 3.4 2.2
2.5 2.0 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.1 2.2 3.3 2.2
2.4 2.0 2.5 2.1 2.7 2.1 2.8 2.3 2.9 2.2 3.1 2.2 3.3 2.2
2.4 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.8 2.2 3.0 2.2 3.2 2.2
2.4 2.0 2.5 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.1
2.3 2.0 2.4 2.1 2.6 2.0 2.7 2.2 2.7 2.2 2.9 2.2 3.1 2.1
2.3 2.0 2.4 2.0 2.5 2.0 2.6 2.2 2.6 2.1 2.8 2.1 3.0 2.1
3.2 2.5 3.4 2.6 3.7 2.6 3.9 2.8 4.0 2.8 4.2 2.8 4.6 2.7
3.2 2.5 3.4 2.6 3.7 2.6 3.9 2.8 4.0 2.8 4.2 2.8 4.6 2.7
3.2 2.5 3.4 2.6 3.7 2.6 3.9 2.8 4.0 2.8 4.2 2.7 4.5 2.7
3.2 2.5 3.4 2.6 3.6 2.6 3.8 2.8 3.9 2.7 4.1 2.7 4.4 2.7
3.2 2.5 3.3 2.6 3.6 2.6 3.7 2.7 3.8 2.7 4.0 2.7 4.3 2.6
3.1 2.4 3.3 2.5 3.5 2.5 3.7 2.7 3.7 2.7 4.0 2.6 4.2 2.6
3.1 2.4 3.2 2.5 3.4 2.5 3.6 2.7 3.7 2.6 3.9 2.6 4.1 2.6
3.0 2.4 3.2 2.5 3.3 2.5 3.5 2.6 3.6 2.6 3.8 2.6 4.0 2.5
3.0 2.4 3.1 2.5 3.3 2.4 3.5 2.6 3.5 2.6 3.7 2.6 4.0 2.5
2.9 2.3 3.0 2.4 3.2 2.4 3.3 2.6 3.3 2.5 3.6 2.5 3.9 2.5
4.0 3.0 4.3 3.2 4.6 3.2 4.9 3.4 5.0 3.4 5.3 3.3 5.7 3.3
4.0 3.0 4.3 3.2 4.6 3.2 4.9 3.4 5.0 3.4 5.3 3.3 5.7 3.3
4.0 3.0 4.3 3.2 4.6 3.2 4.9 3.4 5.0 3.4 5.3 3.3 5.6 3.3
4.0 3.0 4.3 3.2 4.5 3.1 4.8 3.4 4.8 3.3 5.2 3.3 5.5 3.2
4.0 3.0 4.2 3.1 4.5 3.1 4.7 3.3 4.8 3.3 5.0 3.2 5.4 3.2
3.9 2.9 4.1 3.1 4.4 3.1 4.6 3.3 4.7 3.2 5.0 3.2 5.3 3.2
3.8 2.9 4.0 3.1 4.3 3.0 4.5 3.2 4.6 3.2 4.9 3.2 5.2 3.1
3.8 2.9 4.0 3.0 4.2 3.0 4.4 3.2 4.5 3.2 4.8 3.1 5.0 3.1
3.7 2.9 3.9 3.0 4.1 3.0 4.3 3.2 4.4 3.1 4.7 3.1 5.0 3.0
3.6 2.8 3.8 2.9 4.0 2.9 4.2 3.1 4.2 3.0 4.5 3.0 4.8 3.0
5.0 3.7 5.3 3.9 5.8 3.9 6.0 4.2 6.2 4.1 6.6 4.1 7.1 4.0
5.0 3.7 5.3 3.9 5.8 3.9 6.0 4.2 6.2 4.1 6.6 4.1 7.1 4.0
5.0 3.7 5.3 3.9 5.8 3.9 6.0 4.2 6.2 4.1 6.6 4.1 6.9 4.0
5.0 3.7 5.3 3.9 5.7 3.8 5.9 4.1 6.0 4.0 6.4 4.0 6.8 4.0
4.9 3.7 5.2 3.8 5.5 3.8 5.8 4.1 5.9 4.0 6.3 3.9 6.7 3.9
4.8 3.6 5.1 3.8 5.4 3.7 5.7 4.0 5.8 4.0 6.2 3.9 6.6 3.9
4.8 3.6 5.0 3.7 5.3 3.7 5.6 4.0 5.7 3.9 6.0 3.9 6.4 3.8
4.7 3.5 4.9 3.7 5.2 3.6 5.5 3.9 5.5 3.8 5.9 3.8 6.3 3.7
4.6 3.5 4.8 3.6 5.1 3.6 5.4 3.9 5.5 3.8 5.8 3.8 6.2 3.7
4.5 3.5 4.7 3.6 5.0 3.5 5.2 3.8 5.2 3.7 5.7 3.7 6.0 3.7
6.4 4.7 6.8 4.9 7.3 4.9 7.7 5.3 7.8 5.2 8.4 5.2 9.0 5.1
6.4 4.7 6.8 4.9 7.3 4.9 7.7 5.3 7.8 5.2 8.4 5.2 9.0 5.1
6.4 4.7 6.8 4.9 7.3 4.9 7.7 5.3 7.8 5.2 8.3 5.1 8.8 5.0
6.3 4.7 6.7 4.9 7.2 4.9 7.5 5.2 7.6 5.1 8.1 5.1 8.7 5.0
6.2 4.6 6.6 4.8 7.0 4.8 7.4 5.1 7.5 5.1 8.0 5.0 8.5 4.9
6.1 4.6 6.5 4.8 6.9 4.7 7.2 5.1 7.3 5.0 7.8 4.9 8.3 4.9
6.0 4.5 6.4 4.7 6.7 4.7 7.1 5.0 7.2 4.9 7.7 4.9 8.1 4.8
6.0 4.5 6.2 4.7 6.6 4.6 6.9 4.9 7.0 4.9 7.5 4.8 8.0 4.7
5.9 4.4 6.1 4.6 6.5 4.6 6.8 4.9 6.9 4.8 7.3 4.7 7.8 4.7
5.8 4.4 6.0 4.5 6.3 4.5 6.6 4.8 6.6 4.7 7.2 4.7 7.6 4.6
PEFY-P-VMS1(L)-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
kcal/h = kW x 860, Btu/h = kW x 3,412
Indoor air temp.
71 ˚FDB / 59˚FWB 73˚FDB / 61˚FWB 77˚FDB / 64˚FWB 81˚FDB / 66˚FWB 82˚FDB / 68˚FWB 86˚FDB / 72˚FWB 90˚FDB / 75˚FWB
21.5˚CDB / 15˚CWB 23˚CDB / 16˚CWB 25˚CDB / 18˚CWB 27˚CDB / 19˚CWB 28˚CDB / 20˚CWB 30˚CDB / 22˚CWB 32˚CDB / 24˚CWB
˚CDB˚FDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20
(2.2)
15
(1.7)
25
(2.8)
32
(3.6)
40
(4.5)
50
(5.6)
63
(7.1)
Outdoor air temp.
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
68 73 77 82 86 91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
Model
size
(Rated kW)
CAPACITY TABLES
86
A2. Cooling capacity with PUHY-RP300-400Y(S)JM/PURY-RP300YJM
4.4 3.3 4.5 3.4 4.9 3.4 5.0 3.5 5.2 3.6 5.5 3.6 5.9 3.5
4.3 3.3 4.5 3.4 4.8 3.4 5.0 3.4 5.1 3.6 5.4 3.5 5.7 3.5
4.3 3.3 4.4 3.4 4.7 3.3 4.9 3.4 5.0 3.5 5.3 3.5 5.6 3.4
4.2 3.2 4.3 3.3 4.6 3.3 4.8 3.4 4.9 3.5 5.2 3.4 5.5 3.4
4.1 3.2 4.2 3.3 4.5 3.3 4.7 3.3 4.8 3.4 5.1 3.4 5.4 3.3
4.1 3.2 4.2 3.2 4.4 3.2 4.6 3.3 4.7 3.4 5.0 3.4 5.3 3.3
4.0 3.1 4.1 3.2 4.3 3.2 4.5 3.2 4.6 3.4 4.9 3.3 5.2 3.3
4.0 3.1 4.0 3.2 4.3 3.1 4.4 3.2 4.5 3.3 4.8 3.3 5.1 3.2
3.9 3.1 3.9 3.1 4.2 3.1 4.3 3.2 4.9 3.5 4.7 3.2 5.0 3.2
3.8 3.0 3.8 3.1 4.1 3.0 4.2 3.1 4.3 3.2 4.6 3.2 4.8 3.1
5.4 3.9 5.6 4.0 6.0 4.0 6.3 4.0 6.5 4.2 6.9 4.1 7.3 4.1
5.4 3.9 5.6 4.0 6.0 3.9 6.2 4.0 6.4 4.1 6.7 4.1 7.1 4.0
5.3 3.8 5.5 3.9 5.9 3.9 6.0 3.9 6.2 4.1 6.6 4.0 7.0 4.0
5.2 3.8 5.4 3.9 5.7 3.8 5.9 3.9 6.1 4.0 6.5 4.0 6.9 3.9
5.2 3.7 5.3 3.8 5.6 3.8 5.8 3.8 6.0 4.0 6.4 3.9 6.7 3.9
5.1 3.7 5.2 3.8 5.5 3.7 5.7 3.8 5.9 3.9 6.2 3.9 6.6 3.8
5.0 3.6 5.1 3.7 5.4 3.7 5.6 3.7 5.8 3.9 6.1 3.8 6.5 3.8
4.9 3.6 5.0 3.7 5.3 3.6 5.5 3.7 5.7 3.8 6.0 3.8 6.3 3.7
4.8 3.6 4.8 3.6 5.2 3.6 5.3 3.6 6.1 4.0 5.9 3.7 6.2 3.7
4.7 3.5 4.7 3.5 5.0 3.5 5.2 3.6 5.3 3.7 5.7 3.7 6.0 3.6
6.9 5.1 7.1 5.2 7.7 5.2 8.0 5.3 8.2 5.5 8.7 5.5 9.2 5.4
6.9 5.1 7.1 5.2 7.6 5.2 7.8 5.3 8.1 5.5 8.5 5.4 9.1 5.3
6.8 5.0 7.0 5.2 7.4 5.1 7.7 5.2 7.9 5.4 8.4 5.3 8.9 5.2
6.6 5.0 6.8 5.1 7.3 5.1 7.5 5.1 7.8 5.3 8.2 5.3 8.7 5.2
6.5 4.9 6.7 5.0 7.1 5.0 7.4 5.1 7.6 5.3 8.1 5.2 8.5 5.1
6.4 4.9 6.6 5.0 7.0 4.9 7.2 5.0 7.5 5.2 7.9 5.1 8.4 5.1
6.3 4.8 6.4 4.9 6.8 4.9 7.1 5.0 7.3 5.2 7.7 5.1 8.2 5.0
6.2 4.8 6.3 4.8 6.7 4.8 6.9 4.9 7.2 5.1 7.6 5.0 8.0 4.9
6.1 4.7 6.1 4.8 6.6 4.7 6.8 4.8 7.7 5.3 7.4 5.0 7.8 4.9
6.0 4.6 6.0 4.7 6.4 4.7 6.6 4.8 6.8 4.9 7.2 4.9 7.6 4.8
7.8 5.7 8.0 5.9 8.6 5.9 9.0 5.9 9.2 6.2 9.8 6.1 10.4 6.0
7.7 5.7 8.0 5.8 8.5 5.8 8.8 5.9 9.1 6.1 9.6 6.0 10.2 5.9
7.6 5.6 7.8 5.8 8.4 5.7 8.6 5.8 8.9 6.0 9.4 5.9 10.0 5.9
7.5 5.5 7.7 5.7 8.2 5.7 8.5 5.7 8.7 6.0 9.3 5.9 9.8 5.8
7.4 5.5 7.5 5.6 8.0 5.6 8.3 5.7 8.6 5.9 9.1 5.8 9.6 5.7
7.2 5.4 7.4 5.5 7.9 5.5 8.2 5.6 8.4 5.8 8.9 5.7 9.4 5.6
7.1 5.4 7.2 5.5 7.7 5.4 8.0 5.5 8.2 5.7 8.7 5.7 9.2 5.6
7.0 5.3 7.1 5.4 7.6 5.4 7.8 5.5 8.1 5.7 8.6 5.6 9.1 5.5
6.9 5.3 6.9 5.3 7.4 5.3 7.6 5.4 8.7 5.9 8.4 5.5 8.8 5.4
6.7 5.2 6.7 5.2 7.2 5.2 7.4 5.3 7.6 5.5 8.1 5.4 8.6 5.4
8.7 6.4 9.0 6.6 9.7 6.6 10.1 6.7 10.4 7.0 11.0 6.9 11.7 6.8
8.7 6.4 9.0 6.6 9.6 6.6 9.9 6.7 10.2 6.9 10.8 6.8 11.5 6.7
8.6 6.4 8.8 6.5 9.4 6.5 9.7 6.6 10.0 6.8 10.6 6.7 11.3 6.6
8.4 6.3 8.6 6.4 9.2 6.4 9.5 6.5 9.8 6.7 10.4 6.7 11.0 6.5
8.3 6.2 8.5 6.3 9.0 6.3 9.4 6.4 9.6 6.7 10.3 6.6 10.8 6.5
8.1 6.1 8.3 6.3 8.9 6.2 9.2 6.3 9.5 6.6 10.0 6.5 10.6 6.4
8.0 6.1 8.1 6.2 8.6 6.1 9.0 6.3 9.3 6.5 9.8 6.4 10.4 6.3
7.9 6.0 8.0 6.1 8.5 6.1 8.8 6.2 9.1 6.4 9.6 6.3 10.2 6.2
7.8 6.0 7.8 6.0 8.3 6.0 8.6 6.1 9.8 6.7 9.4 6.3 9.9 6.2
7.6 5.8 7.6 5.9 8.1 5.9 8.4 6.0 8.6 6.2 9.1 6.2 9.7 6.1
10.9 8.6 11.3 8.9 12.1 8.9 12.5 9.1 12.9 9.5 13.7 9.3 14.6 9.2
10.8 8.6 11.2 8.9 11.9 8.8 12.3 9.0 12.7 9.4 13.5 9.3 14.3 9.1
10.7 8.5 11.0 8.8 11.7 8.7 12.1 8.9 12.5 9.3 13.2 9.2 14.0 9.0
10.5 8.4 10.8 8.7 11.5 8.6 11.9 8.8 12.2 9.2 13.0 9.1 13.7 8.9
10.3 8.4 10.5 8.6 11.3 8.6 11.6 8.7 12.0 9.1 12.8 9.0 13.4 8.8
10.1 8.3 10.4 8.5 11.0 8.5 11.4 8.7 11.8 9.0 12.4 8.9 13.2 8.8
10.0 8.2 10.1 8.4 10.8 8.3 11.2 8.6 11.5 8.9 12.2 8.8 12.9 8.7
9.9 8.2 9.9 8.3 10.6 8.3 10.9 8.5 11.3 8.8 12.0 8.7 12.7 8.6
9.7 8.1 9.7 8.2 10.4 8.2 10.7 8.4 12.2 9.2 11.7 8.6 12.4 8.5
9.4 7.9 9.4 8.1 10.1 8.1 10.4 8.3 10.7 8.6 11.4 8.5 12.0 8.4
13.6 10.0 14.1 10.3 15.1 10.3 15.7 10.4 16.2 10.8 17.2 10.7 18.2 10.5
13.5 9.9 14.0 10.2 14.9 10.2 15.4 10.3 15.9 10.7 16.8 10.6 17.9 10.4
13.4 9.9 13.7 10.1 14.6 10.0 15.1 10.2 15.6 10.6 16.5 10.4 17.5 10.3
13.1 9.7 13.4 10.0 14.4 9.9 14.8 10.1 15.3 10.5 16.2 10.3 17.2 10.1
12.9 9.6 13.2 9.8 14.1 9.8 14.6 10.0 15.0 10.3 16.0 10.2 16.8 10.0
12.7 9.5 13.0 9.7 13.8 9.7 14.3 9.8 14.7 10.2 15.5 10.1 16.5 9.9
12.5 9.4 12.7 9.6 13.4 9.5 14.0 9.7 14.4 10.1 15.3 9.9 16.2 9.8
12.3 9.3 12.4 9.5 13.2 9.4 13.7 9.6 14.1 10.0 15.0 9.8 15.8 9.7
12.1 9.2 12.1 9.3 13.0 9.3 13.4 9.5 15.2 10.4 14.6 9.7 15.5 9.5
11.8 9.1 11.8 9.2 12.6 9.1 13.0 9.3 13.4 9.7 14.2 9.5 15.1 9.4
PEFY-P-VMH-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
kcal/h = kW x 860, Btu/h = kW x 3,412
Indoor air temp.
71 ˚FDB / 59˚FWB 73˚FDB / 61˚FWB 77˚FDB / 64˚FWB 81˚FDB / 66˚FWB 82˚FDB / 68˚FWB 86˚FDB / 72˚FWB 90˚FDB / 75˚FWB
21.5˚CDB / 15˚CWB 23˚CDB / 16˚CWB 25˚CDB / 18˚CWB 27˚CDB / 19˚CWB 28˚CDB / 20˚CWB 30˚CDB / 22˚CWB 32˚CDB / 24˚CWB
˚CDB˚FDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
40
(4.5)
50
(5.6)
63
(7.1)
71
(8.0)
Outdoor air temp.
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
68 73 77 82 86 91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
Model
size
(Rated kW)
80
(9.0)
100
(11.2)
125
(14.0)
CAPACITY TABLES
87
A2. Cooling capacity with PUHY-RP300-400Y(S)JM/PURY-RP300YJM
15.5 11.4 16.1 11.8 17.3 11.7 17.9 11.9 18.5 12.4 19.6 12.2 20.8 12.0
15.4 11.4 16.0 11.7 17.0 11.6 17.6 11.8 18.2 12.2 19.2 12.1 20.4 11.9
15.3 11.3 15.7 11.6 16.7 11.5 17.3 11.7 17.8 12.1 18.9 11.9 20.0 11.7
15.0 11.1 15.4 11.4 16.4 11.3 17.0 11.5 17.5 12.0 18.5 11.8 19.6 11.6
14.7 11.0 15.0 11.2 16.1 11.2 16.6 11.4 17.1 11.8 18.2 11.7 19.2 11.4
14.5 10.9 14.8 11.1 15.8 11.0 16.3 11.2 16.8 11.7 17.8 11.5 18.8 11.3
14.2 10.8 14.5 11.0 15.4 10.9 16.0 11.1 16.5 11.5 17.4 11.4 18.5 11.2
14.1 10.7 14.2 10.8 15.1 10.8 15.6 10.9 16.2 11.4 17.1 11.2 18.1 11.1
13.8 10.6 13.8 10.7 14.8 10.6 15.3 10.8 17.4 11.9 16.7 11.1 17.7 10.9
13.4 10.4 13.4 10.5 14.4 10.4 14.9 10.6 15.3 11.0 16.2 10.9 17.2 10.7
21.7 16.3 22.5 16.8 24.2 16.8 25.1 17.1 25.9 17.8 27.4 17.5 29.1 17.3
21.6 16.3 22.4 16.8 23.9 16.7 24.6 16.9 25.4 17.6 26.9 17.3 28.6 17.1
21.4 16.1 22.0 16.6 23.4 16.5 24.2 16.7 24.9 17.4 26.4 17.1 28.0 16.9
20.9 15.9 21.5 16.4 23.0 16.3 23.7 16.6 24.5 17.2 25.9 17.0 27.4 16.7
20.6 15.8 21.1 16.2 22.5 16.1 23.3 16.4 24.0 17.0 25.5 16.8 26.9 16.5
20.3 15.6 20.7 16.0 22.1 15.9 22.8 16.2 23.5 16.8 24.9 16.5 26.4 16.3
19.9 15.4 20.3 15.8 21.5 15.6 22.4 16.0 23.1 16.6 24.4 16.4 25.9 16.1
19.7 15.3 19.8 15.6 21.2 15.5 21.8 15.8 22.6 16.4 24.0 16.2 25.4 16.0
19.4 15.2 19.4 15.4 20.7 15.3 21.4 15.6 24.3 17.1 23.4 16.0 24.8 15.7
18.8 14.9 18.8 15.1 20.2 15.0 20.8 15.4 21.4 15.9 22.7 15.8 24.1 15.5
27.2 20.3 28.1 20.9 30.2 20.9 31.4 21.3 32.3 22.1 34.3 21.8 36.4 21.5
27.0 20.2 28.0 20.9 29.8 20.7 30.8 21.0 31.8 21.9 33.7 21.5 35.7 21.2
26.7 20.1 27.4 20.6 29.3 20.5 30.2 20.8 31.2 21.6 33.0 21.3 35.0 21.0
26.2 19.8 26.9 20.3 28.7 20.2 29.7 20.6 30.6 21.4 32.4 21.1 34.3 20.7
25.8 19.6 26.3 20.1 28.1 20.0 29.1 20.3 30.0 21.1 31.9 20.9 33.6 20.5
25.3 19.4 25.9 19.9 27.6 19.7 28.6 20.1 29.4 20.9 31.1 20.6 33.0 20.3
24.9 19.2 25.3 19.6 26.9 19.4 28.0 19.9 28.8 20.6 30.5 20.3 32.3 20.0
24.6 19.1 24.8 19.4 26.5 19.2 27.3 19.6 28.3 20.4 30.0 20.1 31.7 19.8
24.2 18.8 24.2 19.1 25.9 19.0 26.7 19.3 30.4 21.3 29.3 19.9 30.9 19.5
23.5 18.5 23.5 18.8 25.2 18.7 26.0 19.1 26.7 19.8 28.4 19.6 30.1 19.3
PEFY-P-VMH-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
kcal/h = kW x 860, Btu/h = kW x 3,412
Indoor air temp.
71 ˚FDB / 59˚FWB 73˚FDB / 61˚FWB 77˚FDB / 64˚FWB 81˚FDB / 66˚FWB 82˚FDB / 68˚FWB 86˚FDB / 72˚FWB 90˚FDB / 75˚FWB
21.5˚CDB / 15˚CWB 23˚CDB / 16˚CWB 25˚CDB / 18˚CWB 27˚CDB / 19˚CWB 28˚CDB / 20˚CWB 30˚CDB / 22˚CWB 32˚CDB / 24˚CWB
˚CDB˚FDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
140
(16.0)
200
(22.4)
250
(28.0)
Outdoor air temp.
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
68 73 77 82 86 91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
Model
size
(Rated kW)
2.1 1.7 2.2 1.8 2.4 1.8 2.5 1.9 2.5 1.9 2.7 1.9 2.9 1.9
2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.9 2.5 1.9 2.6 1.9 2.8 1.8
2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.9 2.4 1.9 2.6 1.8 2.8 1.8
2.1 1.7 2.1 1.8 2.3 1.7 2.3 1.9 2.4 1.9 2.5 1.8 2.7 1.8
2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.6 1.8
2.0 1.7 2.0 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.6 1.8
2.0 1.7 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.8
1.9 1.6 1.9 1.7 2.1 1.7 2.1 1.8 2.2 1.8 2.4 1.8 2.5 1.7
1.9 1.6 1.9 1.7 2.0 1.6 2.1 1.8 2.4 1.8 2.3 1.7 2.4 1.7
1.8 1.6 1.8 1.6 2.0 1.6 2.0 1.7 2.1 1.7 2.2 1.7 2.4 1.7
2.7 2.0 2.8 2.1 3.0 2.1 3.1 2.2 3.2 2.2 3.4 2.2 3.6 2.1
2.7 2.0 2.8 2.1 3.0 2.1 3.1 2.2 3.2 2.2 3.4 2.1 3.6 2.1
2.7 2.0 2.7 2.0 2.9 2.0 3.0 2.2 3.1 2.1 3.3 2.1 3.5 2.1
2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.2 2.1 3.4 2.1
2.6 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.0
2.5 1.9 2.6 2.0 2.8 2.0 2.9 2.1 2.9 2.1 3.1 2.0 3.3 2.0
2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.0 3.1 2.0 3.2 2.0
2.5 1.9 2.5 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 2.0 3.2 2.0
2.4 1.9 2.4 1.9 2.6 1.9 2.7 2.0 3.0 2.1 2.9 2.0 3.1 1.9
2.4 1.8 2.4 1.9 2.5 1.9 2.6 2.0 2.7 2.0 2.8 1.9 3.0 1.9
3.5 2.5 3.6 2.5 3.9 2.5 4.0 2.7 4.2 2.7 4.4 2.6 4.7 2.6
3.5 2.5 3.6 2.5 3.8 2.5 4.0 2.7 4.1 2.6 4.3 2.6 4.6 2.6
3.4 2.4 3.5 2.5 3.8 2.5 3.9 2.6 4.0 2.6 4.2 2.6 4.5 2.5
3.4 2.4 3.5 2.5 3.7 2.5 3.8 2.6 3.9 2.6 4.2 2.5 4.4 2.5
3.3 2.4 3.4 2.4 3.6 2.4 3.7 2.6 3.9 2.5 4.1 2.5 4.3 2.5
3.3 2.4 3.3 2.4 3.5 2.4 3.7 2.5 3.8 2.5 4.0 2.5 4.2 2.4
3.2 2.3 3.3 2.4 3.5 2.3 3.6 2.5 3.7 2.5 3.9 2.4 4.2 2.4
3.2 2.3 3.2 2.3 3.4 2.3 3.5 2.5 3.6 2.4 3.9 2.4 4.1 2.4
3.1 2.3 3.1 2.3 3.3 2.3 3.4 2.4 3.9 2.6 3.8 2.4 4.0 2.3
3.0 2.2 3.0 2.3 3.2 2.2 3.3 2.4 3.4 2.4 3.7 2.3 3.9 2.3
PEFY-P-VMR-E-L/R
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
kcal/h = kW x 860, Btu/h = kW x 3,412
Indoor air temp.
71 ˚FDB / 59˚FWB 73˚FDB / 61˚FWB 77˚FDB / 64˚FWB 81˚FDB / 66˚FWB 82˚FDB / 68˚FWB 86˚FDB / 72˚FWB 90˚FDB / 75˚FWB
21.5˚CDB / 15˚CWB 23˚CDB / 16˚CWB 25˚CDB / 18˚CWB 27˚CDB / 19˚CWB 28˚CDB / 20˚CWB 30˚CDB / 22˚CWB 32˚CDB / 24˚CWB
˚CDB˚FDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20
(2.2)
25
(2.8)
32
(3.6)
Outdoor air temp.
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
68 73 77 82 86 91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
Model
size
(Rated kW)
CAPACITY TABLES
88
A2. Cooling capacity with PUHY-RP300-400Y(S)JM/PURY-RP300YJM
1.6 1.5 1.7 1.5 1.8 1.5 1.9 1.7 2.0 1.7 2.1 1.6 2.2 1.6
1.6 1.5 1.7 1.5 1.8 1.5 1.9 1.6 1.9 1.6 2.0 1.6 2.2 1.6
1.6 1.5 1.7 1.5 1.8 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
1.6 1.5 1.6 1.5 1.7 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
1.6 1.4 1.6 1.5 1.7 1.5 1.8 1.6 1.8 1.6 1.9 1.6 2.0 1.6
1.5 1.4 1.6 1.5 1.7 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.5
1.5 1.4 1.5 1.5 1.6 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.5
1.5 1.4 1.5 1.5 1.6 1.4 1.7 1.6 1.7 1.6 1.8 1.5 1.9 1.5
1.5 1.4 1.5 1.4 1.6 1.4 1.6 1.6 1.8 1.6 1.8 1.5 1.9 1.5
1.4 1.4 1.4 1.4 1.5 1.4 1.6 1.5 1.6 1.5 1.7 1.5 1.8 1.5
2.1 1.8 2.2 1.9 2.4 1.9 2.5 2.0 2.5 2.0 2.7 2.0 2.9 1.9
2.1 1.8 2.2 1.9 2.3 1.9 2.4 2.0 2.5 2.0 2.6 1.9 2.8 1.9
2.1 1.8 2.2 1.8 2.3 1.8 2.4 2.0 2.4 2.0 2.6 1.9 2.8 1.9
2.1 1.8 2.1 1.8 2.3 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
2.0 1.8 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.6 1.9
2.0 1.7 2.0 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.9
2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.5 1.8
1.9 1.7 1.9 1.8 2.1 1.7 2.1 1.9 2.2 1.9 2.4 1.8 2.5 1.8
1.9 1.7 1.9 1.7 2.0 1.7 2.1 1.9 2.4 1.9 2.3 1.8 2.4 1.8
1.8 1.7 1.8 1.7 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.8 2.4 1.8
2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.4 3.2 2.4 3.4 2.3 3.6 2.3
2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.4 3.2 2.4 3.4 2.3 3.6 2.3
2.7 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.2 2.3 3.4 2.2
2.6 2.1 2.6 2.2 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 2.9 2.3 3.1 2.2 3.3 2.2
2.5 2.1 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.2
2.5 2.0 2.5 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.2 2.2
2.4 2.0 2.4 2.1 2.6 2.1 2.7 2.2 3.0 2.3 2.9 2.2 3.1 2.1
2.4 2.0 2.4 2.0 2.5 2.0 2.6 2.2 2.7 2.2 2.8 2.1 3.0 2.1
3.5 2.6 3.6 2.7 3.9 2.7 4.0 2.9 4.2 2.9 4.4 2.8 4.7 2.8
3.5 2.6 3.6 2.7 3.8 2.7 4.0 2.8 4.1 2.8 4.3 2.8 4.6 2.7
3.4 2.6 3.5 2.7 3.8 2.6 3.9 2.8 4.0 2.8 4.2 2.8 4.5 2.7
3.4 2.6 3.5 2.6 3.7 2.6 3.8 2.8 3.9 2.8 4.2 2.7 4.4 2.7
3.3 2.5 3.4 2.6 3.6 2.6 3.7 2.7 3.9 2.7 4.1 2.7 4.3 2.7
3.3 2.5 3.3 2.6 3.5 2.6 3.7 2.7 3.8 2.7 4.0 2.7 4.2 2.6
3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.7 3.7 2.7 3.9 2.6 4.2 2.6
3.2 2.5 3.2 2.5 3.4 2.5 3.5 2.6 3.6 2.6 3.9 2.6 4.1 2.6
3.1 2.4 3.1 2.5 3.3 2.5 3.4 2.6 3.9 2.8 3.8 2.6 4.0 2.5
3.0 2.4 3.0 2.4 3.2 2.4 3.3 2.6 3.4 2.6 3.7 2.5 3.9 2.5
4.4 3.2 4.5 3.3 4.9 3.3 5.0 3.5 5.2 3.5 5.5 3.4 5.9 3.4
4.3 3.2 4.5 3.3 4.8 3.3 5.0 3.4 5.1 3.4 5.4 3.4 5.7 3.3
4.3 3.2 4.4 3.2 4.7 3.2 4.9 3.4 5.0 3.4 5.3 3.3 5.6 3.3
4.2 3.1 4.3 3.2 4.6 3.2 4.8 3.4 4.9 3.3 5.2 3.3 5.5 3.2
4.1 3.1 4.2 3.2 4.5 3.1 4.7 3.3 4.8 3.3 5.1 3.3 5.4 3.2
4.1 3.0 4.2 3.1 4.4 3.1 4.6 3.3 4.7 3.3 5.0 3.2 5.3 3.2
4.0 3.0 4.1 3.1 4.3 3.0 4.5 3.2 4.6 3.2 4.9 3.2 5.2 3.1
4.0 3.0 4.0 3.0 4.3 3.0 4.4 3.2 4.5 3.2 4.8 3.1 5.1 3.1
3.9 3.0 3.9 3.0 4.2 3.0 4.3 3.2 4.9 3.3 4.7 3.1 5.0 3.1
3.8 2.9 3.8 2.9 4.1 2.9 4.2 3.1 4.3 3.1 4.6 3.1 4.8 3.0
5.4 3.9 5.6 4.0 6.0 4.0 6.3 4.3 6.5 4.2 6.9 4.2 7.3 4.1
5.4 3.9 5.6 4.0 6.0 4.0 6.2 4.2 6.4 4.2 6.7 4.1 7.1 4.1
5.3 3.9 5.5 4.0 5.9 3.9 6.0 4.2 6.2 4.1 6.6 4.1 7.0 4.0
5.2 3.8 5.4 3.9 5.7 3.9 5.9 4.1 6.1 4.1 6.5 4.0 6.9 4.0
5.2 3.8 5.3 3.9 5.6 3.8 5.8 4.1 6.0 4.0 6.4 4.0 6.7 3.9
5.1 3.7 5.2 3.8 5.5 3.8 5.7 4.0 5.9 4.0 6.2 3.9 6.6 3.9
5.0 3.7 5.1 3.8 5.4 3.7 5.6 4.0 5.8 3.9 6.1 3.9 6.5 3.8
4.9 3.7 5.0 3.7 5.3 3.7 5.5 3.9 5.7 3.9 6.0 3.8 6.3 3.8
4.8 3.6 4.8 3.7 5.2 3.6 5.3 3.9 6.1 4.1 5.9 3.8 6.2 3.7
4.7 3.5 4.7 3.6 5.0 3.6 5.2 3.8 5.3 3.8 5.7 3.7 6.0 3.7
6.9 4.9 7.1 5.1 7.7 5.1 8.0 5.4 8.2 5.4 8.7 5.3 9.2 5.2
6.9 4.9 7.1 5.1 7.6 5.0 7.8 5.3 8.1 5.3 8.5 5.2 9.1 5.1
6.8 4.9 7.0 5.0 7.4 5.0 7.7 5.3 7.9 5.2 8.4 5.2 8.9 5.1
6.6 4.8 6.8 4.9 7.3 4.9 7.5 5.2 7.8 5.2 8.2 5.1 8.7 5.0
6.5 4.8 6.7 4.9 7.1 4.8 7.4 5.1 7.6 5.1 8.1 5.0 8.5 4.9
6.4 4.7 6.6 4.8 7.0 4.8 7.2 5.1 7.5 5.0 7.9 5.0 8.4 4.9
6.3 4.7 6.4 4.7 6.8 4.7 7.1 5.0 7.3 5.0 7.7 4.9 8.2 4.8
6.2 4.6 6.3 4.7 6.7 4.7 6.9 4.9 7.2 4.9 7.6 4.8 8.0 4.8
6.1 4.6 6.1 4.6 6.6 4.6 6.8 4.9 7.7 5.1 7.4 4.8 7.8 4.7
6.0 4.5 6.0 4.5 6.4 4.5 6.6 4.8 6.8 4.8 7.2 4.7 7.6 4.6
PEFY-P-VMS1(L)-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
kcal/h = kW x 860, Btu/h = kW x 3,412
Indoor air temp.
71 ˚FDB / 59˚FWB 73˚FDB / 61˚FWB 77˚FDB / 64˚FWB 81˚FDB / 66˚FWB 82˚FDB / 68˚FWB 86˚FDB / 72˚FWB 90˚FDB / 75˚FWB
21.5˚CDB / 15˚CWB 23˚CDB / 16˚CWB 25˚CDB / 18˚CWB 27˚CDB / 19˚CWB 28˚CDB / 20˚CWB 30˚CDB / 22˚CWB 32˚CDB / 24˚CWB
˚CDB˚FDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20
(2.2)
15
(1.7)
25
(2.8)
32
(3.6)
40
(4.5)
50
(5.6)
63
(7.1)
Outdoor air temp.
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
68 73 77 82 86 91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
Model
size
(Rated kW)
CAPACITY TABLES
89
A2. Cooling capacity with PUHY-RP300-400Y(S)JM/PURY-RP300YJM
4.3 3.2 4.4 3.3 4.7 3.3 4.8 3.4 5.0 3.5 5.3 3.5 5.7 3.4
4.2 3.2 4.3 3.3 4.6 3.3 4.8 3.4 5.0 3.5 5.3 3.5 5.6 3.4
4.2 3.2 4.3 3.3 4.6 3.3 4.7 3.3 4.9 3.5 5.2 3.4 5.6 3.4
4.1 3.2 4.2 3.3 4.5 3.3 4.7 3.3 4.9 3.5 5.2 3.4 5.4 3.3
4.1 3.2 4.2 3.2 4.5 3.2 4.6 3.3 4.8 3.4 5.1 3.4 5.4 3.4
4.1 3.1 4.1 3.2 4.4 3.2 4.5 3.3 4.8 3.4 5.1 3.4 5.4 3.3
4.0 3.1 4.1 3.2 4.4 3.2 4.5 3.2 4.7 3.4 5.0 3.4 5.4 3.3
4.0 3.1 4.0 3.2 4.3 3.2 4.4 3.2 4.7 3.4 5.0 3.3 5.3 3.3
3.9 3.1 4.0 3.2 4.3 3.2 4.4 3.2 4.6 3.3 5.0 3.3 5.3 3.3
3.9 3.1 3.9 3.1 4.2 3.1 4.3 3.2 4.5 3.3 4.9 3.3 5.2 3.3
5.3 3.8 5.5 3.9 5.8 3.9 6.0 3.9 6.2 4.1 6.6 4.0 7.1 4.0
5.3 3.8 5.4 3.9 5.8 3.9 5.9 3.9 6.2 4.1 6.6 4.0 7.0 4.0
5.2 3.8 5.3 3.8 5.7 3.8 5.9 3.9 6.1 4.0 6.5 4.0 6.9 3.9
5.2 3.7 5.3 3.8 5.7 3.8 5.8 3.8 6.0 4.0 6.4 4.0 6.7 3.9
5.1 3.7 5.2 3.8 5.6 3.8 5.8 3.8 6.0 4.0 6.4 3.9 6.8 3.9
5.0 3.7 5.2 3.8 5.5 3.7 5.7 3.8 5.9 4.0 6.3 3.9 6.7 3.9
5.0 3.6 5.1 3.7 5.5 3.7 5.6 3.7 5.8 3.9 6.3 3.9 6.7 3.8
4.9 3.6 5.0 3.7 5.4 3.7 5.5 3.7 5.8 3.9 6.2 3.9 6.6 3.8
4.8 3.6 5.0 3.7 5.3 3.7 5.4 3.7 5.7 3.9 6.2 3.9 6.6 3.8
4.8 3.6 4.9 3.6 5.3 3.6 5.4 3.7 5.7 3.8 6.0 3.8 6.5 3.8
6.7 5.0 6.9 5.1 7.4 5.1 7.6 5.2 7.9 5.4 8.4 5.3 8.9 5.3
6.7 5.0 6.9 5.1 7.3 5.1 7.5 5.1 7.8 5.4 8.3 5.3 8.8 5.2
6.6 4.9 6.8 5.1 7.2 5.0 7.5 5.1 7.7 5.3 8.2 5.3 8.8 5.2
6.5 4.9 6.7 5.0 7.2 5.0 7.4 5.1 7.7 5.3 8.2 5.2 8.5 5.1
6.5 4.9 6.6 5.0 7.1 5.0 7.3 5.1 7.6 5.3 8.1 5.2 8.6 5.1
6.4 4.8 6.5 5.0 7.0 4.9 7.2 5.0 7.5 5.2 8.0 5.2 8.5 5.1
6.3 4.8 6.4 4.9 6.9 4.9 7.1 5.0 7.4 5.2 8.0 5.2 8.4 5.1
6.2 4.8 6.4 4.9 6.8 4.9 7.0 4.9 7.3 5.2 7.8 5.1 8.4 5.1
6.1 4.7 6.3 4.8 6.8 4.8 6.9 4.9 7.2 5.1 7.8 5.1 8.3 5.0
6.1 4.7 6.2 4.8 6.7 4.8 6.8 4.8 7.2 5.1 7.7 5.1 8.2 5.0
7.6 5.6 7.8 5.7 8.3 5.7 8.6 5.8 8.9 6.0 9.4 5.9 10.1 5.9
7.5 5.6 7.7 5.7 8.2 5.7 8.5 5.7 8.8 6.0 9.4 5.9 10.0 5.8
7.4 5.5 7.6 5.7 8.2 5.6 8.4 5.7 8.7 5.9 9.3 5.9 9.9 5.8
7.4 5.5 7.5 5.6 8.1 5.6 8.3 5.7 8.6 5.9 9.2 5.9 9.6 5.7
7.3 5.4 7.4 5.6 8.0 5.6 8.2 5.6 8.6 5.9 9.1 5.8 9.7 5.7
7.2 5.4 7.4 5.5 7.8 5.5 8.1 5.6 8.5 5.8 9.0 5.8 9.6 5.7
7.1 5.4 7.2 5.5 7.8 5.5 8.0 5.5 8.3 5.8 9.0 5.8 9.5 5.7
7.0 5.3 7.2 5.4 7.7 5.4 7.9 5.5 8.3 5.8 8.8 5.7 9.4 5.6
6.9 5.3 7.1 5.4 7.6 5.4 7.8 5.4 8.2 5.7 8.8 5.7 9.4 5.6
6.9 5.2 7.0 5.4 7.5 5.3 7.7 5.4 8.1 5.7 8.6 5.6 9.3 5.6
8.5 6.3 8.8 6.5 9.4 6.5 9.6 6.5 10.0 6.8 10.6 6.7 11.3 6.7
8.5 6.3 8.7 6.5 9.3 6.4 9.5 6.5 9.9 6.8 10.6 6.7 11.2 6.6
8.4 6.2 8.6 6.4 9.2 6.4 9.5 6.5 9.8 6.7 10.4 6.7 11.1 6.6
8.3 6.2 8.5 6.3 9.1 6.3 9.4 6.4 9.7 6.7 10.4 6.6 10.8 6.5
8.2 6.2 8.4 6.3 9.0 6.3 9.3 6.4 9.6 6.7 10.3 6.6 10.9 6.5
8.1 6.1 8.3 6.3 8.8 6.2 9.1 6.3 9.5 6.6 10.2 6.6 10.8 6.5
8.0 6.1 8.1 6.2 8.8 6.2 9.0 6.3 9.4 6.5 10.1 6.5 10.7 6.4
7.9 6.0 8.1 6.2 8.6 6.1 8.9 6.2 9.3 6.5 9.9 6.5 10.6 6.4
7.8 6.0 8.0 6.1 8.6 6.1 8.7 6.2 9.2 6.5 9.9 6.4 10.5 6.4
7.7 5.9 7.9 6.1 8.5 6.1 8.6 6.1 9.1 6.4 9.7 6.4 10.4 6.3
10.6 8.5 10.9 8.8 11.6 8.7 12.0 8.9 12.5 9.3 13.2 9.2 14.1 9.1
10.5 8.5 10.8 8.7 11.5 8.7 11.9 8.8 12.3 9.2 13.2 9.1 13.9 9.0
10.4 8.4 10.7 8.7 11.4 8.6 11.8 8.8 12.2 9.2 13.0 9.1 13.8 9.0
10.3 8.4 10.5 8.6 11.3 8.6 11.6 8.7 12.1 9.1 12.9 9.0 13.4 8.8
10.2 8.3 10.4 8.6 11.2 8.5 11.5 8.7 12.0 9.1 12.8 9.0 13.6 8.9
10.1 8.3 10.3 8.5 11.0 8.4 11.3 8.6 11.9 9.0 12.7 9.0 13.4 8.8
10.0 8.2 10.1 8.4 10.9 8.4 11.2 8.6 11.6 9.0 12.5 8.9 13.3 8.8
9.9 8.2 10.0 8.4 10.8 8.3 11.0 8.5 11.6 8.9 12.4 8.9 13.2 8.8
9.7 8.1 9.9 8.3 10.7 8.3 10.9 8.4 11.4 8.9 12.3 8.8 13.1 8.7
9.6 8.1 9.8 8.3 10.5 8.2 10.8 8.4 11.3 8.8 12.1 8.8 13.0 8.7
13.2 9.8 13.7 10.1 14.6 10.0 15.0 10.1 15.6 10.6 16.5 10.4 17.6 10.3
13.2 9.8 13.5 10.0 14.4 9.9 14.8 10.1 15.4 10.5 16.5 10.4 17.4 10.2
13.0 9.7 13.4 9.9 14.3 9.9 14.7 10.0 15.3 10.4 16.2 10.3 17.3 10.2
12.9 9.6 13.2 9.8 14.1 9.8 14.6 10.0 15.1 10.4 16.1 10.3 16.8 10.0
12.7 9.5 13.0 9.8 14.0 9.8 14.4 9.9 15.0 10.3 16.0 10.2 16.9 10.1
12.6 9.5 12.9 9.7 13.7 9.6 14.1 9.8 14.8 10.3 15.8 10.2 16.8 10.0
12.5 9.4 12.7 9.6 13.7 9.6 14.0 9.7 14.6 10.1 15.7 10.1 16.7 10.0
12.3 9.3 12.6 9.6 13.4 9.5 13.8 9.6 14.5 10.1 15.5 10.0 16.5 9.9
12.1 9.2 12.4 9.5 13.4 9.5 13.6 9.5 14.3 10.0 15.4 10.0 16.4 9.9
12.0 9.2 12.3 9.4 13.2 9.4 13.4 9.5 14.1 10.0 15.1 9.9 16.2 9.8
PEFY-P-VMH-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
kcal/h = kW x 860, Btu/h = kW x 3,412
Indoor air temp.
71 ˚FDB / 59˚FWB 73˚FDB / 61˚FWB 77˚FDB / 64˚FWB 81˚FDB / 66˚FWB 82˚FDB / 68˚FWB 86˚FDB / 72˚FWB 90˚FDB / 75˚FWB
21.5˚CDB / 15˚CWB 23˚CDB / 16˚CWB 25˚CDB / 18˚CWB 27˚CDB / 19˚CWB 28˚CDB / 20˚CWB 30˚CDB / 22˚CWB 32˚CDB / 24˚CWB
˚CDB˚FDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
40
(4.5)
50
(5.6)
63
(7.1)
71
(8.0)
Outdoor air temp.
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
68 73 77 82 86 91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
Model
size
(Rated kW)
80
(9.0)
100
(11.2)
125
(14.0)
CAPACITY TABLES
90
A3. Cooling capacity with PUHY-RP450-650YSJM
15.1 11.2 15.6 11.5 16.6 11.4 17.1 11.6 17.8 12.1 18.9 11.9 20.2 11.8
15.0 11.2 15.4 11.4 16.5 11.4 17.0 11.5 17.6 12.0 18.8 11.9 19.9 11.7
14.9 11.1 15.3 11.4 16.3 11.3 16.8 11.5 17.4 11.9 18.6 11.8 19.8 11.7
14.7 11.0 15.0 11.2 16.2 11.2 16.6 11.4 17.3 11.9 18.4 11.7 19.2 11.4
14.6 10.9 14.9 11.2 16.0 11.2 16.5 11.3 17.1 11.8 18.2 11.7 19.4 11.5
14.4 10.8 14.7 11.1 15.7 11.0 16.2 11.2 17.0 11.7 18.1 11.6 19.2 11.4
14.2 10.8 14.5 11.0 15.6 11.0 16.0 11.1 16.6 11.6 17.9 11.6 19.0 11.4
14.1 10.7 14.4 10.9 15.4 10.9 15.8 11.0 16.6 11.6 17.7 11.5 18.9 11.3
13.8 10.6 14.2 10.8 15.3 10.8 15.5 10.9 16.3 11.5 17.6 11.4 18.7 11.3
13.8 10.5 14.0 10.8 15.0 10.7 15.4 10.8 16.2 11.4 17.3 11.3 18.6 11.2
21.2 16.0 21.8 16.5 23.3 16.4 24.0 16.6 25.0 17.4 26.4 17.1 28.2 17.0
21.1 16.0 21.6 16.4 23.1 16.3 23.7 16.6 24.6 17.3 26.3 17.1 27.9 16.8
20.8 15.9 21.4 16.3 22.8 16.2 23.5 16.5 24.4 17.2 26.0 17.0 27.7 16.8
20.6 15.8 21.1 16.2 22.6 16.1 23.3 16.4 24.2 17.1 25.8 16.9 26.9 16.5
20.4 15.7 20.8 16.0 22.4 16.0 23.1 16.3 24.0 17.0 25.5 16.8 27.1 16.6
20.2 15.5 20.6 15.9 22.0 15.8 22.6 16.1 23.7 16.9 25.3 16.7 26.9 16.5
19.9 15.4 20.3 15.8 21.8 15.8 22.4 16.0 23.3 16.7 25.1 16.6 26.7 16.4
19.7 15.3 20.1 15.7 21.5 15.6 22.1 15.9 23.2 16.7 24.8 16.5 26.4 16.3
19.4 15.2 19.8 15.6 21.4 15.6 21.7 15.7 22.8 16.5 24.6 16.5 26.2 16.2
19.3 15.1 19.6 15.5 21.1 15.4 21.5 15.6 22.6 16.4 24.2 16.3 26.0 16.2
26.5 19.9 27.3 20.5 29.1 20.4 30.0 20.7 31.2 21.6 33.0 21.3 35.3 21.1
26.3 19.9 27.0 20.4 28.8 20.3 29.7 20.6 30.8 21.4 32.9 21.3 34.9 20.9
26.0 19.7 26.7 20.3 28.6 20.2 29.4 20.5 30.5 21.3 32.5 21.1 34.6 20.8
25.8 19.6 26.3 20.1 28.3 20.0 29.1 20.3 30.2 21.2 32.2 21.0 33.6 20.5
25.5 19.5 26.0 19.9 28.0 19.9 28.8 20.2 30.0 21.1 31.9 20.9 33.9 20.6
25.2 19.3 25.8 19.8 27.4 19.7 28.3 20.0 29.7 21.0 31.6 20.8 33.6 20.5
24.9 19.2 25.3 19.6 27.3 19.6 28.0 19.9 29.1 20.8 31.4 20.7 33.3 20.4
24.6 19.1 25.1 19.5 26.9 19.4 27.6 19.7 29.0 20.7 30.9 20.5 33.0 20.3
24.2 18.8 24.8 19.4 26.7 19.4 27.2 19.5 28.6 20.5 30.8 20.4 32.8 20.2
24.1 18.8 24.5 19.2 26.3 19.2 26.9 19.4 28.3 20.4 30.2 20.2 32.5 20.1
PEFY-P-VMH-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
kcal/h = kW x 860, Btu/h = kW x 3,412
Indoor air temp.
71 ˚FDB / 59˚FWB 73˚FDB / 61˚FWB 77˚FDB / 64˚FWB 81˚FDB / 66˚FWB 82˚FDB / 68˚FWB 86˚FDB / 72˚FWB 90˚FDB / 75˚FWB
21.5˚CDB / 15˚CWB 23˚CDB / 16˚CWB 25˚CDB / 18˚CWB 27˚CDB / 19˚CWB 28˚CDB / 20˚CWB 30˚CDB / 22˚CWB 32˚CDB / 24˚CWB
˚CDB˚FDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
140
(16.0)
200
(22.4)
250
(28.0)
Outdoor air temp.
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
68 73 77 82 86 91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
Model
size
(Rated kW)
CAPACITY TABLES
91
A3. Cooling capacity with PUHY-RP450-650YSJM
2.1 1.7 2.1 1.8 2.3 1.8 2.4 1.9 2.5 1.9 2.6 1.8 2.8 1.8
2.1 1.7 2.1 1.8 2.3 1.7 2.3 1.9 2.4 1.9 2.6 1.8 2.7 1.8
2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.9 2.4 1.9 2.6 1.8 2.7 1.8
2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.6 1.8
2.0 1.7 2.0 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.8
2.0 1.7 2.0 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.5 1.8 2.6 1.8
2.0 1.7 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.5 1.8 2.6 1.8
1.9 1.6 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.6 1.8
1.9 1.6 1.9 1.7 2.1 1.7 2.1 1.8 2.2 1.8 2.4 1.8 2.6 1.8
1.9 1.6 1.9 1.7 2.1 1.7 2.1 1.8 2.2 1.8 2.4 1.8 2.6 1.8
2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.1
2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.1
2.6 2.0 2.7 2.0 2.9 2.0 2.9 2.1 3.1 2.1 3.2 2.1 3.5 2.1
2.6 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.0
2.5 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.0
2.5 1.9 2.6 2.0 2.7 2.0 2.8 2.1 3.0 2.1 3.2 2.1 3.4 2.0
2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.1 3.1 2.0 3.3 2.0
2.5 1.9 2.5 1.9 2.7 1.9 2.8 2.0 2.9 2.1 3.1 2.0 3.3 2.0
2.4 1.9 2.5 1.9 2.7 1.9 2.7 2.0 2.9 2.0 3.1 2.0 3.3 2.0
2.4 1.9 2.5 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 2.0 3.2 2.0
3.4 2.4 3.5 2.5 3.7 2.5 3.9 2.6 4.0 2.6 4.2 2.6 4.5 2.5
3.4 2.4 3.5 2.5 3.7 2.5 3.8 2.6 4.0 2.6 4.2 2.6 4.5 2.5
3.3 2.4 3.4 2.5 3.7 2.4 3.8 2.6 3.9 2.6 4.2 2.5 4.4 2.5
3.3 2.4 3.4 2.4 3.6 2.4 3.7 2.6 3.9 2.6 4.1 2.5 4.3 2.5
3.3 2.4 3.3 2.4 3.6 2.4 3.7 2.5 3.9 2.5 4.1 2.5 4.4 2.5
3.2 2.3 3.3 2.4 3.5 2.4 3.6 2.5 3.8 2.5 4.1 2.5 4.3 2.5
3.2 2.3 3.3 2.4 3.5 2.4 3.6 2.5 3.7 2.5 4.0 2.5 4.3 2.5
3.2 2.3 3.2 2.4 3.5 2.3 3.5 2.5 3.7 2.5 4.0 2.5 4.2 2.4
3.1 2.3 3.2 2.3 3.4 2.3 3.5 2.4 3.7 2.5 4.0 2.5 4.2 2.4
3.1 2.3 3.2 2.3 3.4 2.3 3.5 2.4 3.6 2.4 3.9 2.4 4.2 2.4
PEFY-P-VMR-E-L/R
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
kcal/h = kW x 860, Btu/h = kW x 3,412
Indoor air temp.
71 ˚FDB / 59˚FWB 73˚FDB / 61˚FWB 77˚FDB / 64˚FWB 81˚FDB / 66˚FWB 82˚FDB / 68˚FWB 86˚FDB / 72˚FWB 90˚FDB / 75˚FWB
21.5˚CDB / 15˚CWB 23˚CDB / 16˚CWB 25˚CDB / 18˚CWB 27˚CDB / 19˚CWB 28˚CDB / 20˚CWB 30˚CDB / 22˚CWB 32˚CDB / 24˚CWB
˚CDB˚FDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20
(2.2)
25
(2.8)
32
(3.6)
Outdoor air temp.
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
68 73 77 82 86 91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
Model
size
(Rated kW)
CAPACITY TABLES
92
A3. Cooling capacity with PUHY-RP450-650YSJM
CAPACITY TABLES
93
A3. Cooling capacity with PUHY-RP450-650YSJM
1.6 1.5 1.7 1.5 1.8 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
1.6 1.5 1.6 1.5 1.8 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
1.6 1.5 1.6 1.5 1.7 1.5 1.8 1.6 1.9 1.6 2.0 1.6 2.1 1.6
1.6 1.4 1.6 1.5 1.7 1.5 1.8 1.6 1.8 1.6 2.0 1.6 2.0 1.6
1.5 1.4 1.6 1.5 1.7 1.5 1.8 1.6 1.8 1.6 1.9 1.6 2.1 1.6
1.5 1.4 1.6 1.5 1.7 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.6
1.5 1.4 1.5 1.5 1.7 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.6
1.5 1.4 1.5 1.5 1.6 1.5 1.7 1.6 1.8 1.6 1.9 1.6 2.0 1.5
1.5 1.4 1.5 1.5 1.6 1.5 1.6 1.6 1.7 1.6 1.9 1.6 2.0 1.5
1.5 1.4 1.5 1.5 1.6 1.4 1.6 1.6 1.7 1.6 1.8 1.5 2.0 1.5
2.1 1.8 2.1 1.8 2.3 1.8 2.4 2.0 2.5 2.0 2.6 1.9 2.8 1.9
2.1 1.8 2.1 1.8 2.3 1.8 2.3 1.9 2.4 1.9 2.6 1.9 2.7 1.9
2.0 1.8 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.6 1.9 2.7 1.9
2.0 1.8 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.6 1.9
2.0 1.7 2.0 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.7 1.9
2.0 1.7 2.0 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.5 1.9 2.6 1.9
1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.6 1.9
1.9 1.7 1.9 1.8 2.1 1.8 2.1 1.9 2.2 1.9 2.4 1.9 2.6 1.8
1.9 1.7 1.9 1.7 2.1 1.7 2.1 1.9 2.2 1.9 2.4 1.9 2.6 1.8
2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.1 2.3 3.3 2.3 3.5 2.3
2.6 2.1 2.7 2.2 2.9 2.2 2.9 2.3 3.1 2.3 3.2 2.3 3.5 2.2
2.6 2.1 2.6 2.2 2.8 2.2 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.0 2.3 3.2 2.3 3.4 2.2
2.5 2.1 2.6 2.1 2.7 2.1 2.8 2.3 3.0 2.3 3.2 2.2 3.4 2.2
2.5 2.1 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.1 2.2 3.3 2.2
2.4 2.0 2.5 2.1 2.7 2.1 2.7 2.2 2.9 2.2 3.1 2.2 3.3 2.2
2.4 2.0 2.5 2.1 2.6 2.1 2.7 2.2 2.8 2.2 3.0 2.2 3.2 2.2
3.4 2.6 3.5 2.7 3.7 2.6 3.9 2.8 4.0 2.8 4.2 2.8 4.5 2.7
3.4 2.6 3.5 2.6 3.7 2.6 3.8 2.8 4.0 2.8 4.2 2.8 4.5 2.7
3.3 2.6 3.4 2.6 3.7 2.6 3.8 2.8 3.9 2.8 4.2 2.7 4.4 2.7
3.3 2.5 3.4 2.6 3.6 2.6 3.7 2.7 3.9 2.7 4.1 2.7 4.3 2.6
3.3 2.5 3.3 2.6 3.6 2.6 3.7 2.7 3.9 2.7 4.1 2.7 4.4 2.7
3.2 2.5 3.3 2.6 3.5 2.5 3.6 2.7 3.8 2.7 4.1 2.7 4.3 2.6
3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.7 3.7 2.7 4.0 2.7 4.3 2.6
3.2 2.5 3.2 2.5 3.5 2.5 3.5 2.7 3.7 2.7 4.0 2.7 4.2 2.6
3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.6 3.7 2.7 4.0 2.6 4.2 2.6
3.1 2.4 3.2 2.5 3.4 2.5 3.5 2.6 3.6 2.6 3.9 2.6 4.2 2.6
4.3 3.1 4.4 3.2 4.7 3.2 4.8 3.4 5.0 3.4 5.3 3.3 5.7 3.3
4.2 3.1 4.3 3.2 4.6 3.2 4.8 3.4 5.0 3.4 5.3 3.3 5.6 3.3
4.2 3.1 4.3 3.2 4.6 3.2 4.7 3.3 4.9 3.3 5.2 3.3 5.6 3.3
4.1 3.1 4.2 3.2 4.5 3.1 4.7 3.3 4.9 3.3 5.2 3.3 5.4 3.2
4.1 3.1 4.2 3.1 4.5 3.1 4.6 3.3 4.8 3.3 5.1 3.3 5.4 3.2
4.1 3.0 4.1 3.1 4.4 3.1 4.5 3.3 4.8 3.3 5.1 3.3 5.4 3.2
4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.2 4.7 3.2 5.0 3.2 5.4 3.2
4.0 3.0 4.0 3.1 4.3 3.0 4.4 3.2 4.7 3.2 5.0 3.2 5.3 3.2
3.9 3.0 4.0 3.0 4.3 3.0 4.4 3.2 4.6 3.2 5.0 3.2 5.3 3.2
3.9 2.9 3.9 3.0 4.2 3.0 4.3 3.2 4.5 3.2 4.9 3.2 5.2 3.1
5.3 3.8 5.5 4.0 5.8 3.9 6.0 4.1 6.2 4.1 6.6 4.1 7.1 4.0
5.3 3.8 5.4 3.9 5.8 3.9 5.9 4.1 6.2 4.1 6.6 4.1 7.0 4.0
5.2 3.8 5.3 3.9 5.7 3.9 5.9 4.1 6.1 4.1 6.5 4.0 6.9 4.0
5.2 3.8 5.3 3.9 5.7 3.8 5.8 4.1 6.0 4.1 6.4 4.0 6.7 3.9
5.1 3.7 5.2 3.8 5.6 3.8 5.8 4.0 6.0 4.0 6.4 4.0 6.8 3.9
5.0 3.7 5.2 3.8 5.5 3.8 5.7 4.0 5.9 4.0 6.3 4.0 6.7 3.9
5.0 3.7 5.1 3.8 5.5 3.8 5.6 4.0 5.8 4.0 6.3 3.9 6.7 3.9
4.9 3.7 5.0 3.7 5.4 3.7 5.5 3.9 5.8 4.0 6.2 3.9 6.6 3.9
4.8 3.6 5.0 3.7 5.3 3.7 5.4 3.9 5.7 3.9 6.2 3.9 6.6 3.9
4.8 3.6 4.9 3.7 5.3 3.7 5.4 3.9 5.7 3.9 6.0 3.9 6.5 3.8
6.7 4.9 6.9 5.0 7.4 5.0 7.6 5.2 7.9 5.2 8.4 5.2 8.9 5.1
6.7 4.8 6.9 5.0 7.3 4.9 7.5 5.2 7.8 5.2 8.3 5.1 8.8 5.1
6.6 4.8 6.8 4.9 7.2 4.9 7.5 5.2 7.7 5.2 8.2 5.1 8.8 5.0
6.5 4.8 6.7 4.9 7.2 4.9 7.4 5.1 7.7 5.1 8.2 5.1 8.5 4.9
6.5 4.7 6.6 4.8 7.1 4.8 7.3 5.1 7.6 5.1 8.1 5.0 8.6 5.0
6.4 4.7 6.5 4.8 7.0 4.8 7.2 5.0 7.5 5.1 8.0 5.0 8.5 4.9
6.3 4.7 6.4 4.7 6.9 4.7 7.1 5.0 7.4 5.0 8.0 5.0 8.4 4.9
6.2 4.6 6.4 4.7 6.8 4.7 7.0 5.0 7.3 5.0 7.8 4.9 8.4 4.9
6.1 4.6 6.3 4.7 6.8 4.7 6.9 4.9 7.2 4.9 7.8 4.9 8.3 4.9
6.1 4.6 6.2 4.6 6.7 4.6 6.8 4.9 7.2 4.9 7.7 4.9 8.2 4.8
PEFY-P-VMS1(L)-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
kcal/h = kW x 860, Btu/h = kW x 3,412
Indoor air temp.
71 ˚FDB / 59˚FWB 73˚FDB / 61˚FWB 77˚FDB / 64˚FWB 81˚FDB / 66˚FWB 82˚FDB / 68˚FWB 86˚FDB / 72˚FWB 90˚FDB / 75˚FWB
21.5˚CDB / 15˚CWB 23˚CDB / 16˚CWB 25˚CDB / 18˚CWB 27˚CDB / 19˚CWB 28˚CDB / 20˚CWB 30˚CDB / 22˚CWB 32˚CDB / 24˚CWB
˚CDB˚FDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20
(2.2)
15
(1.7)
25
(2.8)
32
(3.6)
40
(4.5)
50
(5.6)
63
(7.1)
Outdoor air temp.
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
68 73 77 82 86 91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
Model
size
(Rated kW)
CAPACITY TABLES
94
A4. Cooling capacity with PUHY-RP700-800YSJM
4.3 3.3 4.5 3.4 4.8 3.4 5.0 3.5 5.2 3.6 5.5 3.6 5.9 3.5
4.3 3.3 4.4 3.4 4.7 3.4 4.9 3.4 5.1 3.6 5.4 3.5 5.8 3.5
4.2 3.2 4.4 3.3 4.7 3.3 4.8 3.4 5.0 3.5 5.3 3.5 5.7 3.4
4.1 3.2 4.3 3.3 4.6 3.3 4.7 3.3 4.9 3.5 5.2 3.4 5.6 3.4
4.1 3.1 4.2 3.3 4.5 3.2 4.7 3.3 4.8 3.4 5.1 3.4 5.5 3.4
4.0 3.1 4.1 3.2 4.4 3.2 4.6 3.3 4.7 3.4 5.0 3.4 5.4 3.3
3.9 3.1 4.1 3.2 4.3 3.2 4.5 3.2 4.6 3.4 5.0 3.3 5.3 3.3
3.8 3.0 4.0 3.2 4.3 3.1 4.4 3.2 4.6 3.3 4.9 3.3 5.2 3.3
3.8 3.0 3.9 3.1 4.2 3.1 4.3 3.2 4.5 3.3 4.8 3.3 5.1 3.2
3.7 3.0 3.8 3.1 4.1 3.0 4.2 3.1 4.4 3.3 4.7 3.2 5.0 3.2
5.4 3.9 5.6 4.0 6.0 4.0 6.2 4.0 6.4 4.2 6.9 4.1 7.3 4.1
5.3 3.8 5.5 3.9 5.9 3.9 6.1 4.0 6.3 4.1 6.8 4.1 7.2 4.0
5.3 3.8 5.4 3.9 5.8 3.9 6.0 3.9 6.2 4.1 6.6 4.0 7.1 4.0
5.2 3.7 5.3 3.8 5.7 3.8 5.9 3.9 6.1 4.0 6.5 4.0 6.9 3.9
5.0 3.7 5.2 3.8 5.6 3.8 5.8 3.8 6.0 4.0 6.4 3.9 6.8 3.9
5.0 3.6 5.1 3.7 5.5 3.7 5.7 3.8 5.9 3.9 6.3 3.9 6.7 3.9
4.9 3.6 5.0 3.7 5.4 3.7 5.6 3.7 5.8 3.9 6.2 3.9 6.6 3.8
4.8 3.5 5.0 3.7 5.3 3.6 5.5 3.7 5.7 3.9 6.0 3.8 6.4 3.8
4.7 3.5 4.8 3.6 5.2 3.6 5.4 3.7 5.6 3.8 5.9 3.8 6.3 3.7
4.6 3.4 4.7 3.5 5.0 3.5 5.2 3.6 5.4 3.7 5.8 3.7 6.2 3.7
6.9 5.1 7.1 5.2 7.6 5.2 7.9 5.3 8.2 5.5 8.7 5.5 9.3 5.4
6.7 5.0 7.0 5.2 7.5 5.2 7.8 5.2 8.0 5.5 8.6 5.4 9.1 5.3
6.7 5.0 6.9 5.1 7.4 5.1 7.6 5.2 7.9 5.4 8.4 5.3 8.9 5.3
6.5 4.9 6.7 5.1 7.2 5.0 7.5 5.1 7.7 5.3 8.3 5.3 8.8 5.2
6.4 4.8 6.6 5.0 7.1 5.0 7.3 5.1 7.6 5.3 8.1 5.2 8.7 5.2
6.3 4.8 6.5 4.9 7.0 4.9 7.2 5.0 7.5 5.2 8.0 5.2 8.5 5.1
6.2 4.7 6.4 4.9 6.8 4.9 7.1 5.0 7.3 5.2 7.8 5.1 8.3 5.0
6.1 4.7 6.3 4.9 6.7 4.8 7.0 4.9 7.2 5.1 7.7 5.1 8.2 5.0
6.0 4.6 6.1 4.8 6.6 4.7 6.8 4.8 7.1 5.1 7.5 5.0 8.0 4.9
5.8 4.6 6.0 4.7 6.4 4.7 6.6 4.8 6.9 5.0 7.3 4.9 7.8 4.9
7.7 5.7 8.0 5.8 8.6 5.8 8.9 5.9 9.2 6.2 9.8 6.1 10.4 6.0
7.6 5.6 7.9 5.8 8.4 5.8 8.7 5.9 9.0 6.1 9.7 6.0 10.2 5.9
7.5 5.6 7.8 5.7 8.3 5.7 8.6 5.8 8.9 6.0 9.4 5.9 10.1 5.9
7.4 5.5 7.6 5.6 8.2 5.6 8.4 5.7 8.7 5.9 9.3 5.9 9.9 5.8
7.2 5.4 7.5 5.6 8.0 5.6 8.3 5.7 8.6 5.9 9.1 5.8 9.8 5.8
7.1 5.3 7.3 5.5 7.8 5.5 8.1 5.6 8.4 5.8 9.0 5.8 9.6 5.7
7.0 5.3 7.2 5.5 7.7 5.4 8.0 5.5 8.2 5.7 8.8 5.7 9.4 5.6
6.8 5.2 7.1 5.4 7.6 5.4 7.8 5.5 8.1 5.7 8.6 5.6 9.2 5.6
6.7 5.2 6.9 5.3 7.4 5.3 7.7 5.4 8.0 5.6 8.5 5.6 9.0 5.5
6.6 5.1 6.7 5.2 7.2 5.2 7.5 5.3 7.8 5.5 8.3 5.5 8.8 5.4
8.7 6.4 9.0 6.6 9.7 6.6 10.0 6.7 10.4 7.0 11.1 6.9 11.7 6.8
8.6 6.3 8.9 6.5 9.5 6.5 9.8 6.6 10.2 6.9 10.9 6.8 11.5 6.7
8.5 6.3 8.7 6.5 9.4 6.5 9.7 6.6 10.0 6.8 10.6 6.7 11.3 6.7
8.3 6.2 8.6 6.4 9.2 6.4 9.5 6.5 9.8 6.7 10.5 6.7 11.2 6.6
8.1 6.1 8.4 6.3 9.0 6.3 9.3 6.4 9.6 6.7 10.3 6.6 11.0 6.5
8.0 6.0 8.2 6.2 8.8 6.2 9.1 6.3 9.5 6.6 10.1 6.5 10.8 6.4
7.8 6.0 8.1 6.2 8.6 6.1 9.0 6.3 9.3 6.5 9.9 6.4 10.5 6.4
7.7 5.9 8.0 6.1 8.5 6.1 8.8 6.2 9.1 6.5 9.7 6.4 10.4 6.3
7.6 5.8 7.7 6.0 8.3 6.0 8.6 6.1 9.0 6.4 9.5 6.3 10.1 6.2
7.4 5.8 7.6 5.9 8.1 5.9 8.4 6.0 8.7 6.3 9.3 6.2 9.9 6.1
10.8 8.6 11.2 8.9 12.0 8.9 12.5 9.1 12.9 9.4 13.8 9.4 14.6 9.2
10.6 8.5 11.0 8.8 11.8 8.8 12.2 9.0 12.7 9.4 13.6 9.3 14.3 9.1
10.5 8.5 10.9 8.8 11.6 8.7 12.0 8.9 12.4 9.3 13.2 9.2 14.1 9.1
10.3 8.4 10.6 8.7 11.4 8.6 11.8 8.8 12.2 9.2 13.0 9.1 13.9 9.0
10.1 8.3 10.5 8.6 11.2 8.5 11.6 8.7 12.0 9.1 12.8 9.0 13.7 8.9
9.9 8.2 10.2 8.5 11.0 8.4 11.4 8.6 11.8 9.0 12.5 8.9 13.4 8.8
9.7 8.1 10.1 8.4 10.8 8.3 11.2 8.6 11.5 8.9 12.3 8.8 13.1 8.7
9.6 8.0 10.0 8.3 10.6 8.3 11.0 8.5 11.4 8.8 12.1 8.8 12.9 8.6
9.4 7.9 9.6 8.2 10.4 8.2 10.8 8.4 11.1 8.8 11.9 8.7 12.6 8.6
9.2 7.8 9.4 8.1 10.1 8.1 10.5 8.3 10.9 8.7 11.6 8.6 12.3 8.5
13.5 9.9 14.0 10.2 15.1 10.2 15.6 10.4 16.1 10.8 17.2 10.7 18.3 10.6
13.3 9.8 13.8 10.1 14.8 10.1 15.3 10.3 15.8 10.7 16.9 10.6 17.9 10.4
13.2 9.8 13.6 10.0 14.6 10.0 15.1 10.2 15.5 10.6 16.5 10.4 17.6 10.3
12.9 9.6 13.3 9.9 14.3 9.9 14.8 10.0 15.3 10.4 16.3 10.4 17.4 10.2
12.6 9.5 13.1 9.8 14.0 9.8 14.5 9.9 15.0 10.3 16.0 10.2 17.1 10.1
12.4 9.4 12.8 9.7 13.7 9.6 14.2 9.8 14.7 10.2 15.7 10.1 16.7 10.0
12.2 9.3 12.6 9.6 13.4 9.5 14.0 9.7 14.4 10.1 15.4 10.0 16.4 9.9
12.0 9.2 12.5 9.5 13.2 9.4 13.7 9.6 14.2 10.0 15.1 9.9 16.1 9.8
11.8 9.1 12.0 9.3 13.0 9.3 13.4 9.5 13.9 9.9 14.8 9.8 15.8 9.6
11.5 8.9 11.8 9.2 12.6 9.1 13.1 9.3 13.6 9.7 14.5 9.6 15.4 9.5
PEFY-P-VMH-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
kcal/h = kW x 860, Btu/h = kW x 3,412
Indoor air temp.
71 ˚FDB / 59˚FWB 73˚FDB / 61˚FWB 77˚FDB / 64˚FWB 81˚FDB / 66˚FWB 82˚FDB / 68˚FWB 86˚FDB / 72˚FWB 90˚FDB / 75˚FWB
21.5˚CDB / 15˚CWB 23˚CDB / 16˚CWB 25˚CDB / 18˚CWB 27˚CDB / 19˚CWB 28˚CDB / 20˚CWB 30˚CDB / 22˚CWB 32˚CDB / 24˚CWB
˚CDB˚FDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
40
(4.5)
50
(5.6)
63
(7.1)
71
(8.0)
Outdoor air temp.
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
68 73 77 82 86 91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
Model
size
(Rated kW)
80
(9.0)
100
(11.2)
125
(14.0)
15.4 11.4 16.0 11.7 17.2 11.7 17.8 11.9 18.4 12.3 19.7 12.2 20.9 12.1
15.2 11.2 15.8 11.6 16.9 11.6 17.5 11.7 18.1 12.2 19.4 12.1 20.5 11.9
15.0 11.2 15.5 11.5 16.6 11.4 17.2 11.6 17.8 12.1 18.9 11.9 20.2 11.8
14.7 11.0 15.2 11.3 16.3 11.3 16.9 11.5 17.4 11.9 18.6 11.8 19.8 11.7
14.4 10.8 15.0 11.2 16.0 11.2 16.6 11.3 17.1 11.8 18.2 11.7 19.5 11.6
14.2 10.7 14.6 11.1 15.7 11.0 16.2 11.2 16.8 11.7 17.9 11.6 19.1 11.4
13.9 10.6 14.4 10.9 15.4 10.9 16.0 11.1 16.5 11.5 17.6 11.4 18.7 11.3
13.7 10.5 14.2 10.9 15.1 10.8 15.7 11.0 16.2 11.4 17.3 11.3 18.4 11.2
13.4 10.4 13.8 10.6 14.8 10.6 15.4 10.8 15.9 11.3 17.0 11.2 18.0 11.0
13.1 10.2 13.4 10.5 14.4 10.4 15.0 10.7 15.5 11.1 16.6 11.0 17.6 10.9
21.6 16.3 22.4 16.8 24.1 16.8 24.9 17.0 25.8 17.7 27.6 17.6 29.2 17.3
21.3 16.1 22.1 16.6 23.6 16.6 24.5 16.9 25.3 17.5 27.1 17.4 28.7 17.1
21.1 16.0 21.7 16.5 23.3 16.4 24.1 16.7 24.9 17.4 26.4 17.1 28.2 17.0
20.6 15.8 21.3 16.3 22.8 16.2 23.6 16.5 24.4 17.2 26.1 17.0 27.8 16.8
20.2 15.5 20.9 16.1 22.4 16.0 23.2 16.3 24.0 17.0 25.5 16.8 27.3 16.6
19.8 15.4 20.5 15.9 22.0 15.8 22.7 16.1 23.5 16.8 25.1 16.6 26.8 16.4
19.5 15.2 20.2 15.7 21.5 15.6 22.4 16.0 23.1 16.6 24.6 16.5 26.2 16.2
19.2 15.1 19.9 15.6 21.2 15.5 22.0 15.8 22.7 16.5 24.2 16.3 25.8 16.1
18.8 14.9 19.3 15.3 20.7 15.3 21.5 15.6 22.3 16.3 23.7 16.1 25.2 15.9
18.4 14.7 18.8 15.1 20.2 15.0 20.9 15.4 21.7 16.1 23.2 15.9 24.6 15.7
27.0 20.2 28.0 20.9 30.1 20.8 31.2 21.2 32.2 22.0 34.4 21.9 36.5 21.5
26.6 20.0 27.6 20.7 29.5 20.6 30.6 21.0 31.6 21.8 33.9 21.6 35.8 21.3
26.3 19.9 27.2 20.5 29.1 20.4 30.1 20.7 31.1 21.6 33.0 21.3 35.3 21.1
25.8 19.6 26.6 20.2 28.6 20.2 29.5 20.5 30.5 21.3 32.6 21.1 34.7 20.9
25.2 19.3 26.2 20.0 28.0 19.9 29.0 20.3 30.0 21.1 31.9 20.9 34.2 20.7
24.8 19.1 25.6 19.7 27.4 19.7 28.4 20.0 29.4 20.9 31.4 20.7 33.5 20.4
24.4 18.9 25.2 19.5 26.9 19.4 28.0 19.9 28.8 20.6 30.8 20.4 32.8 20.2
23.9 18.7 24.9 19.4 26.5 19.2 27.4 19.6 28.4 20.5 30.2 20.2 32.2 20.0
23.5 18.5 24.1 19.0 25.9 19.0 26.9 19.4 27.9 20.2 29.7 20.0 31.5 19.7
23.0 18.2 23.5 18.8 25.2 18.7 26.2 19.1 27.2 20.0 29.0 19.8 30.8 19.5
PEFY-P-VMH-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
kcal/h = kW x 860, Btu/h = kW x 3,412
Indoor air temp.
71 ˚FDB / 59˚FWB 73˚FDB / 61˚FWB 77˚FDB / 64˚FWB 81˚FDB / 66˚FWB 82˚FDB / 68˚FWB 86˚FDB / 72˚FWB 90˚FDB / 75˚FWB
21.5˚CDB / 15˚CWB 23˚CDB / 16˚CWB 25˚CDB / 18˚CWB 27˚CDB / 19˚CWB 28˚CDB / 20˚CWB 30˚CDB / 22˚CWB 32˚CDB / 24˚CWB
˚CDB˚FDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
140
(16.0)
200
(22.4)
250
(28.0)
Outdoor air temp.
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
68 73 77 82 86 91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
Model
size
(Rated kW)
CAPACITY TABLES
95
A4. Cooling capacity with PUHY-RP700-800YSJM
2.1 1.7 2.2 1.8 2.4 1.8 2.4 1.9 2.5 1.9 2.7 1.9 2.9 1.9
2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.9 2.5 1.9 2.7 1.9 2.8 1.8
2.1 1.7 2.1 1.8 2.3 1.8 2.4 1.9 2.4 1.9 2.6 1.8 2.8 1.8
2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.9 2.4 1.9 2.6 1.8 2.7 1.8
2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8 2.7 1.8
1.9 1.6 2.0 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.5 1.8 2.6 1.8
1.9 1.6 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.6 1.8
1.9 1.6 2.0 1.7 2.1 1.7 2.2 1.8 2.2 1.8 2.4 1.8 2.5 1.7
1.8 1.6 1.9 1.7 2.0 1.6 2.1 1.8 2.2 1.8 2.3 1.8 2.5 1.7
1.8 1.6 1.8 1.6 2.0 1.6 2.1 1.8 2.1 1.7 2.3 1.7 2.4 1.7
2.7 2.0 2.8 2.1 3.0 2.1 3.1 2.2 3.2 2.2 3.4 2.2 3.7 2.1
2.7 2.0 2.8 2.1 3.0 2.0 3.1 2.2 3.2 2.2 3.4 2.1 3.6 2.1
2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.1
2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.3 2.1 3.5 2.1
2.5 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.1 3.4 2.1
2.5 1.9 2.6 2.0 2.7 2.0 2.8 2.1 2.9 2.1 3.1 2.0 3.3 2.0
2.4 1.9 2.5 1.9 2.7 1.9 2.8 2.1 2.9 2.0 3.1 2.0 3.3 2.0
2.4 1.9 2.5 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 2.0 3.2 2.0
2.4 1.8 2.4 1.9 2.6 1.9 2.7 2.0 2.8 2.0 3.0 2.0 3.2 2.0
2.3 1.8 2.4 1.9 2.5 1.9 2.6 2.0 2.7 2.0 2.9 2.0 3.1 1.9
3.5 2.5 3.6 2.5 3.9 2.5 4.0 2.7 4.1 2.7 4.4 2.6 4.7 2.6
3.4 2.4 3.5 2.5 3.8 2.5 3.9 2.6 4.1 2.6 4.4 2.6 4.6 2.6
3.4 2.4 3.5 2.5 3.7 2.5 3.9 2.6 4.0 2.6 4.2 2.6 4.5 2.5
3.3 2.4 3.4 2.4 3.7 2.4 3.8 2.6 3.9 2.6 4.2 2.6 4.5 2.5
3.2 2.3 3.4 2.4 3.6 2.4 3.7 2.5 3.9 2.5 4.1 2.5 4.4 2.5
3.2 2.3 3.3 2.4 3.5 2.4 3.7 2.5 3.8 2.5 4.0 2.5 4.3 2.5
3.1 2.3 3.2 2.4 3.5 2.3 3.6 2.5 3.7 2.5 4.0 2.5 4.2 2.4
3.1 2.3 3.2 2.3 3.4 2.3 3.5 2.5 3.7 2.5 3.9 2.4 4.1 2.4
3.0 2.2 3.1 2.3 3.3 2.3 3.5 2.4 3.6 2.4 3.8 2.4 4.1 2.4
3.0 2.2 3.0 2.3 3.2 2.2 3.4 2.4 3.5 2.4 3.7 2.4 4.0 2.3
PEFY-P-VMR-E-L/R
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
kcal/h = kW x 860, Btu/h = kW x 3,412
Indoor air temp.
71 ˚FDB / 59˚FWB 73˚FDB / 61˚FWB 77˚FDB / 64˚FWB 81˚FDB / 66˚FWB 82˚FDB / 68˚FWB 86˚FDB / 72˚FWB 90˚FDB / 75˚FWB
21.5˚CDB / 15˚CWB 23˚CDB / 16˚CWB 25˚CDB / 18˚CWB 27˚CDB / 19˚CWB 28˚CDB / 20˚CWB 30˚CDB / 22˚CWB 32˚CDB / 24˚CWB
˚CDB˚FDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20
(2.2)
25
(2.8)
32
(3.6)
Outdoor air temp.
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
20.0
22.5
25.0
27.5
30.0
32.5
35.0
37.5
40.0
43.0
68 73 77 82 86 91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
68
73
77
82
86
91
95 100 104 110
Model
size
(Rated kW)
CAPACITY TABLES
96
A4. Cooling capacity with PUHY-RP700-800YSJM
Loading...