Mitsubishi PURY-RP200YJM-A (-BS), PURY-RP250YJM-A (-BS), PURY-RP300YJM-A (-BS) Installation Manual

Air Conditioners For Building Application Outdoor Unit
PURY-RP200YJM-A (-BS) PURY-RP250YJM-A (-BS) PURY-RP300YJM-A (-BS)
For use with R410A
MINERAL OIL COLLECTION (REFRIGERANT OIL RECOVERY) INSTRUCTIONS MANUAL
ANLEITUNGSHANDBUCH FÜR DIE MINERALÖLSAMMLUNG (KÄLTEMITTELÖLENTNAHME)
MANUAL DE INSTRUCCIONES PARA LA RECOGIDA DE ACEITE MINERAL (RECUPERACIÓN DE ACEITE REFRIGERANTE)
RACCOLTA DELL’OLIO MINERALE (RECUPERO DELL’OLIO REFRIGERANTE) MANUALE DI ISTRUZIONI
MANUAL DE INSTRUÇÕES DE RECOLHA DE ÓLEO MINERAL (RECUPERAÇÃO DO ÓLEO REFRIGERANTE)
GBDFEIP
1. Unit Components
Figure 1 Top view of the refrigerant pipes inside an outdoor unit
GB
H
I
CJ2 CJ1
CJ4
C
B
D
A
A: Refrigerant charge port (for automatic
B: Check joint on the low-pressure side
CJ5
F
G
CJ3
CJ4
C: Service port on the high-pressure valve
D: Service port on the low-pressure valve
E
E: A valve to be closed after the completion
Figure 2 Valve types allocations
F: High-pressure valve G: Low-pressure valve H:O/T I:ACC J:COMP
CJ3: Refrigerant charge port CJ4: Oil sampling port CJ5: Refrigerant oil discharge port
CJ5
charging only)
A port through which additional refrigerant is charged after the completion of refrigerant oil recovery operation
Connecting port to the refrigerant circuit
• Evacuation port (high-pressure side)
• A port through which refrigerant for the indoor units is charged
Connecting port to the refrigerant circuit
• Evacuation port (low-pressure side)
• A port through which refrigerant for the indoor units is charged
of refrigerant oil recovery operation (BV3) (Be sure to close this valve after the completion of refrigerant oil recovery operation.)
J
2
2. Refrigerant Oil Recovery Operation Flow
2.1 Refrigerant oil recovery operation monitor display
1. How to read the LED on the service monitor Units' operation status can be monitored on the LED display by setting the dipswitches SW1-1 through 1-10 on the MAIN board of the outdoor units. Four 7-segment LEDs are used to display numerical values, flags, and alphabets to display various information.
7SEG LED
The LEDs display such information as pressure and temperature in numerical values and operating conditions and the ON/OFF status of solenoid valve as flags.
GB
Display of numerical values
Example:When the pressure sensor reads 18.8 kg/cm
* The unit of pressure is in kg/cm
2
G.
* Use the following conversion formula to convert the displayed value into a value in SI unit (MPa).
SI unit (MPa) = Displayed value (kg/cm
2
G (Item No. 58)
2
G) u0.098
Flag display (Each set of two lines in vertical alignment indicates a flag.)
Example:Outdoor unit in the 3-minute restart delay mode. (Item No. 14)
LD1 LD2 LD3 LD4
LD6 LD7 LD8
LD5
2. Table of items that can be monitored on the LED on the outdoor unit circuit board
No
12345678910 580101110000High pressure (kgf/cm2G) -99.9 to 999.9 591101110000Low pressure (kgf/cm
600011110000
45 1 0 1 1 0 1 0 0 0 0 Discharge temperature (°C) -99.9 to 999.9
1311100000100
1220101111000
1200001111000
SW1
Display content
2
G) -99.9 to 999.9
Intermediate pressure
2
(kgf/cm
G)
Refrigerant oil recovery operation steps
Refrigerant oil recovery remaining time
Refrigerant oil recovery completion indicator flag Refrigerant charge adjustment completion indicator flag
(*1)
LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 LD9
LED display
-99.9 to 999.9
rEP
0 to 9999
S-1 (0)
r-1 (0)
steps
(*2)
(*1) The initial remaining time that indicates the refrigerant oil recovery is 80. A countdown will start on step 3 in the cooling mode.
The countdown does not include the time for checking the refrigerant charge amount.
(*2) S-1: Refrigerant oil recovery complete, S-0: Refrigerant oil recovery incomplete,
r-1: Refrigerant charge adjustment complete, r-0: Refrigerant charge adjustment incomplete.
3
LD10
Notes
Reversed
display
Reversed
display
2.2 Procedures for refrigerant oil recovery
1Evacuating the existing pipes, and ensuring air tightness
Procedure 1
4.15 MPa. After checking the air tightness, evacuate the air through the service port on both the high-pressure and low-pressure valves.
Charge airtight gas through the service port on both the high-pressure and low-pressure valves. The air tightness should be
GB
Low-pressure valve
High-pressure valve
2Refrigerant charging
Procedure 2
•If the length or diameter of the refrigerant pipe is unknown Charge the required amount of refrigerant (indoor units + BC controllers) through both high-pressure and low-pressure service port valves.
•When refrigerant pipe diameter and length are already known Charge the required amount of refrigerant (indoor units + BC controllers + pipes) through both the high-pressure and low-pressure service port valves. See the table below for the required amount of refrigerant for the indoor units and BC controllers. To calculate the required amount of refrigerant charged for the pipes, refer to 10.1. “Calculation of additional refrigerant charge” in the installation manual on the CD-ROM. If there is excess refrigerant that cannot be charged, use it during oil recovery operation at step 4 (cooling operation).
High-pressure valve
Low-pressure valve
Total capacity of
connected indoor units
- 80 2.0
81 - 160 2.5 161 - 330 3.0 331 - 390 3.5 391 - 480 4.5
Total outdoor unit Model
P200 2.0
P250
P300
Charged amount (kg)
Charged amount per
BC controller
(Standard / Main) (kg)
3.0
* After charging the required amount of refrigerant to the existing pipes, open the valve so that the pressure in the existing pipes and outdoor unit
are equal. (Refer to Procedure 3.) Do not open the valve on the outdoor unit when the existing pipes are under vacuum. Doing so may cause the refrigerant that is dissolved in the refrigerant oil in the compressor to form and cause some oil to migrate to the existing pipes, resulting in insufficient lubrication.
4
3Opening the valves
A
Procedure 3
Use a hexagonal wrench to open the valves. Refer to the table below for the proper wrench size.
Open both the high-pressure and low-pressure valves.
High-pressure valve
8, 10, 12 HP 8 mm 8 mm
Low-pressure valve
Hexagonal wrench size
A
High-
pressure
pressure
Low-
4Connecting the refrigerant cylinder(s)
Procedure 4 service port on high-pressure and low-pressure side, and connect the charging hose to the refrigerant charge port CJ3 (only for automatic charging). * Check that each cylinder has the correct amount of refrigerant. * If the amount of refrigerant is insufficient, the units may stop during refrigerant oil recovery or it may take longer than usual to complete a test
run.
If the required amount of refrigerant is not charged, disconnect the charging hose connected to the refrigerant cylinder from the
GB
Refrigerant charge port (CJ3)
5Setting the unit address and checking for proper system operation
Procedure 5 * If an attempt is made to operate the outdoor unit before the refrigerant oil recovery operation is complete, an error code 7116 will appear on the
remote controller. This does not indicate a malfunction. Wait for the oil recovery operation to be completed. The error code 7116 will go off upon completion of oil recovery operation.
Set the unit address, turn on the power, and check for proper operation of the system.
5
6Refrigerant oil recovery operation
Outdoor unit capacity and the maximum
amount of refrigerant charge
Outdoor unit
capacity
Maximum amount of refrigerant charge
(except for the indoor units and
BC controllers) (kg)
RP200, 250, 300 20.0
Procedure 6
Set the dipswitches 3-1 and 4-8 to ON in that order. The compressor turns on, and oil recovery operation starts.
Procedure 7
The refrigerant oil recovery operation is explained in the next page. Wait for the operation to be automatically completed.
* If there was excess refrigerant that had not been charged at “2Refrigerant charging”, charge it during oil recovery operation at step 4 (cooling
operation). After charging the refrigerant, close the valve on the refrigerant cylinder. (Even when the required amount of refrigerant is already
charged, refrigerant charge is automatically adjusted.) * If the cylinder runs out of refrigerant during the refrigerant oil recovery operation, continue the operation and replace the cylinder. * If the cumulative oil recovery operation hour is more than three and a half hours, turn the dipswitches 4-8 and 3-1 to OFF to stop the operation
and turn the dipswitches 4-7 on the units (OC) to OFF.
Wait for the operation to be automatically completed.
GB
* Refer to the table at right for the maximum amount of refrigerant charge.
Do not exceed the maximum amount.
If the refrigerant oil recovery operation does not finish after the maximum
amount of refrigerant is charged, close the valve on refrigerant cylinder, and wait
for the operation to be completed automatically. * If the cylinder runs out of refrigerant during the refrigerant oil recovery operation,
continue the operation and replace the cylinder.
I
LED monitor
Address switches
Close the panel at bottom front of the unit.
SW3-1
SW5
SW4 SW2
OFF ON
SW3
SW1SW3
1 2 3 4 5 6 7 8 9
10
Each dipswitch has 1 to 10 switches from the top. (OFF-left, ON-right) (e.g., SW3-1 is the top switch of SW3. The figure at left indicates that only SW3-1 is set to ON.)
Dipswitches
If the length or diameter of the refrigerant pipe is known, please make note of the following.
If more than the amount of refrigerant that you calculated is charged into the system in auto-charge mode, then there is no problem if you wish to close the cylinder valve while the unit is operating. The unit will stop operating of its own accord.
6
7Check for successful completion of the refrigerant oil recovery operation.
Procedure 8
the outdoor unit’s LED indicates a successful completion.
Turn the dipswitches 1-4, 1-5, 1-6, and 1-7 to ON to verify that the refrigerant oil recovery operation is completed. “S-1” or “r-1” on
LED
“S-1” “r-1”: The refrigerant oil recovery operation is successfully completed. Go to the next procedure. “S-1” “r-0”: The refrigerant charge adjustment is not completed, but regular air conditioning operation can be started. If there was excess
“S-0” “r-1”: The refrigerant oil recovery operation is not completed. To restart the refrigerant oil recovery operation, set the dipswitches 3-1 and
“S-0” “r-0”: The refrigerant oil recovery operation is not completed. To restart the refrigerant oil recovery operation, set the dipswitches 3-1 and
refrigerant that had not been charged, charge it through the low-pressure check joint (CJ2) during the air conditioning operation.
4-8 to ON in that order.
4-8 to ON in that order.
GB
8Disconnecting the cylinder
Procedure 9
After completing the oil recovery operation, close the valve on the cylinder, and disconnect the cylinder within five minutes.
9Recording the amount of refrigerant that was charged
Procedure 10
Write on the control box panel the amount of refrigerant charged.
0Closing the valve on the connecting port to the refrigerant circuit
Procedure 11
Close BV3 completely. The refrigerant oil recovered from the existing pipes is sealed in an oil recovery vessel.
Turn the valve clockwise by 90 degrees. * Use a tool if necessary.
Compressor side
A A
B
SO OS
Oil-recovery side
<Factory setting>
A Lever B (Cap tightening torque: 20-25N•m
(200-250 kg•cm))
C Rotation direction
C
<After the oil-recovery test run>
7
1. Gerätekomponenten
Bild 1: Kältemittelleitungen eines Außengeräts in der Draufsicht
D
H
I
CJ2 CJ1
CJ4
C
F
B
D
G
CJ3
Bild 2: Ventiltypzuordnungen
CJ4
E
A
CJ5
A: Kältemittelfüllanschluss (nur zum
automatischen Befüllen)
B: Prüfverbindung an der Niederdruckseite
Ein Anschluss zum Nachfüllen von Kältemittel nach erfolgter Kältemittelölentnahme
C: Wartungsanschluss am Hochdruckventil
Verbindungsanschluss zum Kältemittelkreis:
• Entlüftungsanschluss (Hochdruckseite)
• Ein Anschluss, über den Kältemittel für die Innengeräte aufgefüllt wird
D: Wartungsanschluss am Niederdruckventil
Verbindungsanschluss zum Kältemittelkreis:
• Entlüftungsanschluss (Niederdruckseite)
• Ein Anschluss, über den Kältemittel für die Innengeräte aufgefüllt wird
E: Ein Ventil, das nach erfolgter
Kältemittelölentnahme geschlossen werden muss (BV3) (Sicherstellen, dass dieses Ventil nach erfolgter Kältemittelölentnahme geschlossen wird.)
F: Hochdruckventil G: Niederdruckventil H:O/T I: Akkumulator J: Kompressor
CJ3: Kältemittelfüllanschluss CJ4: Ölprüfanschluss CJ5: Kältemittelölablassanschluss
CJ5
J
8
2. Arbeitsablauf bei der Kältemittelölentnahme
2.1 Monitoranzeige bei der Kältemittelölentnahme
1. Hinweise zum Lesen der LED am Wartungsmonitor Der Betriebsstatus der Geräte kann an der LED-Anzeige durch Einstellen der Dip-Schalter SW1-1 bis 1-10 auf der Hauptplatine der Außengeräte überwacht werden. Numerische Werte, Hinweissymbole und Buchstaben werden mit vier 7-Segment-LEDs angezeigt.
7-SEGMENT-LED
Die LEDs zeigen zum Beispiel Druck- und Temperaturdaten als numerische Werte sowie Betriebszustände und den EIN/AUS-Status von Spulenventilen als Hinweissymbole an.
Anzeige von numerischen Werten
Beispiel: Wenn der Drucksensor 18,8 kg/cm
* Der Druck wird in kg/cm * Der Anzeigewert kann anhand der folgenden Umrechnungsformel in SI-Einheiten (MPa) konvertiert werden.
SI-Einheit (MPa) = Anzeigewert (kg/cm
2
2
G anzeigt (Punkt Nr. 58)
G angezeigt.
2
G) u0,098
D
Hinweissymbolanzeige (Jedes Set von zwei vertikal ausgerichteten Linien zeigt ein Symbol an.)
Beispiel: Außengerät im Betriebszustand „Neustart 3 Minuten verzögert“. (Punkt Nr. 14)
LD1 LD2 LD3 LD4
LD6 LD7 LD8
LD5
2. Tabelle der Punkte, die mit der LED an der Leiterplatte des Außengeräts überwacht werden können.
Nr.
12345678910 580101110000Hoher Druck (kgf/cm2G) -99,9 bis 999,9 591101110000Niedriger Druck (kgf/cm
600011110000
45 1 0 1 1 0 1 0 0 0 0 Ablasstemperatur (°C) -99,9 bis 999,9
1311100000100
1220101111000
1200001111000
SW1
Anzeigeinhalt
2
G) -99,9 bis 999,9
Mittlerer Druck
2
(kgf/cm
G)
Arbeitsschritte bei der Kältemittelölentnahme
Verbleibende Zeit bei der Kältemittelölentnahme
Anzeigesymbol für abgeschlossene Kältemittelölentnahme Anzeigesymbol für abgeschlossene Anpassung der Kältemittelbefüllung
(*1)
LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 LD9
LED-Anzeige
-99,9 bis 999,9
Schritte
rEP
0 bis 9999
r-1 (0)
S-1 (0)
(*2)
LD10
Hinweise
Umgekehrte
Anzeige
Umgekehrte
Anzeige
(*1) Bei der Kältemittelölentnahme wird die verbleibende Zeit anfänglich als 80 angezeigt. Ein Countdown startet im Kühlbetrieb bei Schritt 3.
Die Zeit zum Prüfen der Kältemittelfüllmenge ist im Countdown nicht eingeschlossen.
(*2) S-1: Kältemittelölentnahme abgeschlossen, S-0: Kältemittelölentnahme nicht abgeschlossen,
r-1: Anpassen der Kältemittelbefüllung abgeschlossen, r-0: Anpassen der Kältemittelbefüllung nicht abgeschlossen.
9
2.2 Kältemittelölentnahmeverfahren
1Entlüften der vorhandenen Rohrleitungen und gewährleisten der Luftdichtigkeit
Verfahren 1 Die Luftdichtigkeit sollte 4,15 MPa betragen. Entlüften Sie das System nach der Prüfung der Luftdichtigkeit über den Wartungsanschluss am Hoch- und Niederdruckventil.
Befüllen Sie das System über den Wartungsanschluss am Hoch- und Niederdruckventil mit Luftdichtigkeitsprüfgas.
D
Niederdruckventil
Hochdruckventil
2Kältemittelbefüllung
Verfahren 2
•Wenn die Länge oder der Durchmesser der Kältemittelrohrleitung unbekannt ist Befüllen Sie das System mit der erforderlichen Menge von Kältemittel (Innengeräte + BC-Steuerungen) über die Hoch- und Niederdruckwartungsanschlussventile.
•Wenn der Durchmesser und die Länge der Kältemittelrohrleitung bekannt sind Befüllen Sie das System mit der erforderlichen Menge von Kältemittel (Innengeräte + BC-Steuerungen + Leitungen) über die Hoch- und Niederdruckwartungsanschlussventile. Entnehmen Sie die für die Innengeräte und BC-Steuerungen erforderliche Menge von Kältemittel der Tabelle unten. Angaben zur Berechnung der zum Befüllen der Rohrleitungen erforderlichen Kältemittelmenge finden Sie unter 10.1. „Berechnen der Kältemittelnachfüllmenge“ im Installationshandbuch auf der CD-ROM. Falls eine Restmenge von Kältemittel verbleibt, die nicht eingefüllt werden kann, kann diese bei der Ölentnahme in Schritt 4 (Kühlbetrieb) verwendet werden.
Gesamtkapazität
Hochdruckventil
Niederdruckventil
der angeschlossenen
Innengeräte
- 80 2,0
81 - 160 2,5 161 - 330 3,0 331 - 390 3,5 391 - 480 4,5
Außengerätemodell
(insgesamt)
P200 2,0
P250
P300
Füllmenge (kg)
Füllmenge je
BC-Steuerung
(Standard/Hauptgerät)
(kg)
3,0
* Nach dem Befüllen der vorhandenen Rohrleitungen mit der erforderlichen Kältemittelmenge muss das Ventil geöffnet werden, um den Druck in
den vorhandenen Rohrleitungen und dem Außengerät auszugleichen. (Siehe Verfahren 3.) Das Ventil am Außengerät darf nicht geöffnet werden, wenn die vorhandenen Rohrleitungen unter Unterdruck stehen. Andernfalls könnte das im Kältemittelöl gelöste Kältemittel im Kompressor ausschlagen, einen Teil des Öls in die vorhandenen Rohrleitungen verdrängen und in einer unzureichenden Schmierung resultieren.
10
3Öffnen der Ventile
A
Verfahren 3 Verwenden Sie zum Öffnen der Ventile einen Sechskantschlüssel. Die geeignete Schlüsselgröße kann der untenstehenden Tabelle entnommen werden.
Öffnen Sie das Hoch- und das Niederdruckventil.
Hochdruckventil
8, 10, 12 HP 8 mm 8 mm
Niederdruckventil
Sechskantschlüsselgröße
A
Hoher Druck
Niedriger
Druck
4Anschließen der/des Kältemittelzylinder/s
Verfahren 4 Füllschlauch vom Wartungsanschluss an der Hoch- oder Niederdruckseite abgetrennt und am Kältemittelfüllanschluss CJ3 angeschlossen werden (nur bei automatischer Befüllung). * Vergewissern Sie sich, dass jeder Zylinder die korrekte Kältemittelmenge enthält. * Bei einer unzureichenden Kältemittelmenge können die Geräte während der Kältemittelölentnahme stoppen oder das Durchführen des
Testbetriebs kann länger als gewöhnlich dauern.
Wenn das System nicht mit der erforderlichen Kältemittelmenge befüllt ist, muss der am Kältemittelzylinder angeschlossene
D
Kältemittelfüllanschluss (CJ3)
5Einstellen der Geräteadresse und prüfen des ordnungsgemäßen Systembetriebs
Verfahren 5 Betrieb. * Wenn versucht wird, das Außengerät in Betrieb zu nehmen, bevor die Kältemittelölentnahme abgeschlossen ist, erscheint an der
Fernbedienung der Fehlercode 7116. Dies weist nicht auf eine Funktionsstörung hin. Warten Sie, bis die Ölentnahme abgeschlossen ist.
Der Fehlercode 7116 erlischt, wenn die Ölentnahme abgeschlossen ist.
Stellen Sie die Geräteadresse ein, schalten Sie die Stromversorgung ein und prüfen Sie das System auf seinen ordnungsgemäßen
11
6Kältemittelölentnahme
Außengerätekapazität und maximale
Kältemittelfüllmenge
Außengerätekap
azität
Maximale Kältemittelfüllmenge (mit
Ausnahme von Innengeräten und
BC-Steuerungen) (kg)
RP200, 250, 300 20,0
Verfahren 6
Stellen Sie die Dip-Schalter 3-1 und 4-8 in dieser Reihenfolge auf EIN. Der Kompressor schaltet ein und die Ölentnahme beginnt.
Verfahren 7
Die Kältemittelölentnahme wird auf der folgenden Seite erläutert. Warten Sie bis zum automatischen Abschluss des
Entnahmevorgangs. * Falls eine Restmenge von Kältemittel verbleibt, die unter „2 Kältemittelbefüllung“ nicht eingefüllt wurde, muss diese bei der Ölentnahme in
Schritt 4 (Kühlbetrieb) nachgefüllt werden. Nach dem Befüllen des Systems mit Kältemittel muss das Ventil am Kältemittelzylinder geschlossen werden. (Die Kältemittelbefüllung wird auch dann automatisch angepasst, wenn das System bereits mit der erforderlichen Kältemittelmenge befüllt ist.)
* Falls der Kältemittelvorrat im Zylinder während der Kältemittelölentnahme erschöpft wird, setzen Sie den Vorgang fort und tauschen den
Zylinder aus.
* Falls die Ölentnahme insgesamt mehr als dreieinhalb Stunden dauert, müssen die Dip-Schalter 4-8 und 3-1 auf AUS gestellt werden, um den
Vorgang zu stoppen, und die Dip-Schalter 4-7 an den Geräten (OC) müssen ebenfalls auf AUS gestellt werden.
Warten Sie bis zum automatischen Abschluss des Entnahmevorgangs.
D
* Die maximale Kältemittelfüllmenge kann der Tabelle rechts entnommen
werden. Die maximale Menge darf nicht überschritten werden.
Falls die Kältemittelölentnahme nach der Befüllung mit der maximalen Kältemittelmenge nicht beendet wird, schließen Sie das Ventil am Kältemittelzylinder und warten Sie, bis der Vorgang automatisch abgeschlossen wird.
* Falls der Kältemittelvorrat im Zylinder während der Kältemittelölentnahme
erschöpft wird, setzen Sie den Vorgang fort und tauschen den Zylinder aus.
I
LED-Monitor
Adressschalter
Tafel unten an der Gerätefront schließen.
SW3-1
SW5
SW4 SW2
OFF ON
SW3
SW1SW3
An jedem Dip-Schalter sind, von oben beginnend,
1 2
die Schalter 1 bis 10 vorhanden. (OFF (AUS)-links,
3 4 5
ON (EIN)-rechts)
6 7
(SW3-1 ist z. B. der oberste Schalter von SW3.
8 9
10
Das Bild links zeigt, dass nur SW3-1 auf EIN gestellt ist.)
Dip-Schalter
Bitte beachten Sie Folgendes wenn die Länge oder der Durchmesser der Kältemittelrohrleitung bekannt ist.
Wenn im automatischen Befüllungsmodus mehr Kältemittel als berechnet in das System geladen wird, besteht kein Problem, wenn Sie das Ventil am Kältemittelzylinder während der Bedienung dieses Geräts schließen. Das Gerät stoppt daraufhin automatisch.
12
Loading...
+ 28 hidden pages