Outdoor Unit: 16-TON PURY-P192TSHMU-A-BS
(Consists of Two PURY-P96THMU-A-BS and One CMY-R100VBK Twinning Kit)
Job Name: Location:
Drawing Reference: Schedule No.
System No.: Date:
OutdOOr VrFZ HEAt rEcOVEry SyStEM FEAturES
• 3-phase, 208/230V systems
• Modular variable refrigerant ow zoning (VRFZ) systems; smaller capacity units can be piped together to form a single, large-capacity two-pipe system
• Compact size for each outdoor module; can be transported through standard-sized doorways for installation
• Required Twinning Kit allows for easy eld piping connection
• Selectable fan static, 0.12 or 0.24"WG external static pressure; factory set to 0"WG
• Max. Total Refrigerant Piping Length: 1,804' (P72,96); 1,969' (P120,144,168); 2,461' (P192); 2,625' (P216,240); Max. Line Length: 541'; Max. Control Wiring Length: 1,650'
• Connects to CITY MULTI indoor units; controlled via CITY MULTI Controls Network (CMCN)
• External finish: Pre-coated Galvanized-steel Sheets with thermoset polyester-resin
• Operating Temperature Range Cooling (Outdoor): 23° ~ 109°F (-5° ~ +43°C) DB Heating (Outdoor): -4° ~ +60°F (-20° ~ +16°C) WB
PURY-P96THMU-A-BS
OPtIONAL PArtS
□ Twinning Kit*.…………………………………...……...CMY-R100VBK □ Branch Joint (T-Branch: ≤ 72,000 Btu/h).………….CMY-Y102S-G2 □ Branch Joint (T-Branch: 73,000-144,000 Btu/h).……….CMY-Y102L-G2 □ Joint Adapter (Port Connector>54,000 Btu/h).………….CMY-R160J □ Main BC Controller.…………………..CMB-P108/1010/1013/1016NU-GA □ Sub BC Controller.…………………CMB-P104/108NU-GB/-1016NU-HB
* Twinning Kit is necessary to combine the refrigerant ows of the
modules and is included in the outdoor unit set.
PURY-P96THMU-A-BS
Specications System Module 1 Module 2
Unit Type
Nominal Cooling Capacity Btu/h 192,000 96,000 96,000 Nominal Heating Capacity Btu/h 200,000 108,000 108,000
External Dimensions (H x W x D) In. / mm Refer to Module Data
Net Weight Lbs. / kg 1,170 / 530 585 / 265 585 / 265
Electrical Power Requirements Voltage, Phase, Hertz Refer to Module Data** 208-230V, 3-phase, 60Hz
Cooling Power Input kW 17.04
Heating Power Input kW 15.85 Cooling Current (208/230V) A 52.5 / 47.5 Heating Current (208/230V) A 48.8 / 44.2 Minimum Circuit Ampacity
(MCA)**
Maximum Overcurrent Protection (MOCP)**
Piping Diameter
From Twinning Kit to Indoor Units (Brazed) (In. / mm)
From Modules to Twinning Kit (Brazed) (In. / mm)
Indoor Unit
Sound Pressure Levels dB(A) 62.0 58.0 58.0
Fan
Type x Quantity Propeller Fan x 1 Propeller Fan x 1
Airow Rate cFM 7,750 7,750 Direct-drive Inverter Motor Output kW 0.92 0.92 Compressor Operating Range 9% to 100% Refer to System Data
Compressor Type x Quantity Compressor Motor Output kW 7.0 7.0 Compressor Crankcase Heater kW 0.057 0.057 Refrigerant Lubricant MEL32 High-pressure Protection Device Compressor / Fan Protection Device Overheat Protection / Thermal Switch Overheat Protection / Thermal Switch Inverter Protection Device Overheat / Overcurrent Protection Overheat / Overcurrent Protection Blue Fin Anti-corrosion Protection: Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants;
≥1μm to 1.5μm thick; Salt Spray Test Method - no unusual rust development to 960 hours.
A Refer to Module Data** 35 / 32** 35 / 32**
A Refer to Module Data** 40 / 40** 40 / 40**
Liquid (High Pressure) 7/8 / 22.2
Gas (Low Pressure) 1-1/8 / 28.58
Liquid (High Pressure) Gas (Low Pressure) 7/8 / 22.2 7/8 / 22.2 Total Capacity 50 to 150% of ODUs
Model / Quantity P06 ~ P96 / 1 to 48
PURY-P192TSHMU-A-BS
Refer to Module Data
Refer to Module Data
Refer to Module Data
Refer to Module Data
Refer to Module Data
PURY-P96THMU-A-BS PURY-P96THMU-A-BS
65 x 48-1/16 x 29-15/16 /
1,650 x 1,220 x 760
Refer to System Data
Refer to System Data
Refer to System Data
3/4 / 19.05 3/4 / 19.05
Refer to System Data
Inverter-driven Scroll Hermetic x 1 Inverter-driven Scroll Hermetic x 1
601 psi / 4.15 MPa 601 psi / 4.15 MPa
65 x 48-1/16 x 29-15/16 /
1,650 x 1,220 x 760
R410A
** Each individual module requires a separate electrical connection. Reference electrical data for each individual module.
Page 2
SEACOAST PROTECTION
P96 P120
Unit model
Low pressure
High pressure
Twinning pipe ~ Outdoor unit
Outdoor unit 1Outdoor unit 2
Front view
Left view
1650 (64-31/32)
To BC controller
To BC controller
a
b
Twinning pipe (High pressure) <optional parts>
e
f
c
d
Twinning pipe(Low pressure) <optional parts>
Intake air
Intake air
760 (29-15/16)
Discharge air
Intake air
30 (1-3/16)1220 (48-1/16) 1220 (48-1/16)
ø22.2(7/8)
PURY-P120THMU-A(-BS)
PURY-P120THMU-A(-BS)
PURY-P240TSHMU-A(-BS)
c or e
ø19.05(3/4)
ø19.05(3/4)
PURY-P96THMU-A(-BS)
PURY-P120THMU-A(-BS)
PURY-P216TSHMU-A(-BS)
d or f
ø28.58(1-1/8)
ø22.2(7/8)
PURY-P96THMU-A(-BS)
PURY-P96THMU-A(-BS)
PURY-P192TSHMU-A(-BS)
Low pressure
Twinning pipe connection size
Outdoor unit 1
Component unit name
Package unit name
BC controller ~ Twinning pipe
a b
High pressure
Outdoor Twinning Kit(optional parts)
CMY- R100VBK
Outdoor unit 2
ø28.58(1-1/8)
ø28.58(1-1/8)
Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2.Twinning pipe (high pressure) should not have a side-to-side angle of more than 15 degrees.
3.Refer to the Installation Manual for details of the Twinning pipe installation.
4.The straight length of piping before the Twinning pipe (section "a" in the figure) must be at least 500mm(19-11 /16) (*including the straight pipe supplied with the Twinning pipe).
5.Use only the Twinning pipes manufactured by Mitsubishi (optional parts).
Unit : mm(in)
External Panel Base, External Front Panel, Pillar: Alloyed galvanized-steel sheets with thermoset
polyester-resin coating on internal and external surfaces
Compressor Cover: Galvanized-aluminum sheets with thermoset polyester-resin coating on internal and
external surfaces
Electrical Parts Box: Galvanized-aluminum sheets with thermoset polyester-resin coating on external
surface
Fan Motor Support: Galvanized-steel sheets with thermoset polyester-resin coating on internal and
external surfaces
Printed Circuit Board: Epoxy resin with polyurethane-coating on external surface
Outdoor Unit: PURY-P192TSHMU-A-BS – DIMENSIONS
Page 3
<Reducer pipe(Accessory)>
<Low-pressure pipe twinning kit (Accessory)>
High-pressure twinning pipe
Low-pressure pipe twinning kit
<Reducer pipe(Accessory)>
<Pipe for routing through the bottom (Accessory)>
<Pipe for routing through the front (Accessory)>
<Elbow pipe (Accessory)>
1"
3/4"
5/8"
5/8"
5/8" (Outside diameter)
5/8”
3/4"
(Outside diameter)
1"
(Outside diameter)
(Outside diameter)
(Outside diameter)
(Outside diameter)
(2Pcs.)
3/4"
3/4"
(Outside diameter)
(Outside diameter)
(Outside diameter)
3/4”
1"
1”
1”
1”
7/8"
7/8"
1-5/32"
3/4"
5/8”
3/4”
3/4"
7/8”
1-5/32”
3/4”
7/8"
7/8"
7/8"
1-5/32"
1-5/32"
3/4"
3/4"
1-3/32”
1”
2-3/8”
7-17/32"4-17/32"
21/32"
8-7/16”
7-9/16"
21/32"
4-17/32"
2-5/16"
7-17/32"
7-17/32"3-11/16"
2-5/16"
2-3/8”
3-5/32"
3-5/32"
2-3/8”
3-17/32”
1-1/4”
4-5/32”
2-15/32"
2-15/32"
3-5/32"
1-13/32”
5-1/4”
21/32”
6-15/16”
17-1/32”
2-15/32"
1-7/16”
1-7/16”
1-31/32"
1-31/32"
21/32"
8-7/16”
For instructions on piping the units together using the twinning kit, see the Installation Manual.
CMY-R100VBK
Twinning Kit: CMY-R100VBK
Page 4
Certificate Number FM33568
Certificate Number EC97J1227
Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired ISO 9001 certification under Series 9000 of the International Standard Organization (ISO) based on a review of quality warranties for the production of refrigeration and air conditioning equipment.
ISO Authorization System The ISO 9000 series is a plant authorization system relating to quality warranties as stipulated by the ISO. ISO 9001 certifies quality warranties based on the "design, development, production, installation and auxiliary services" for products built at an authorized plant.
Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired environmental management system standard ISO 14001 certification.
The ISO 14000 series is a set of standards applying to environmental protection set by the International Standard Organization (ISO).
(Mounting pitch)
ø45 Knockout hole
(Use when twinning kit (optional parts) is mounted.)
Front access hole
ø34 Knockout hole
NO.
For pipes
For transmission cables
Usage
Bottom access hole
Front access hole
Front access hole
Bottom access hole
Front access hole
140 X 77 Knockout hole
150 X 94 Knockout hole
ø65 Knockout hole
Front access hole
For wires
ø62.7 or ø34.5 Knockout hole
ø43.7 or ø22.2 Knockout hole
Specifications
(10-11/16)
(3-5/32) (3-5/32)
(41-3/4)
2 X 2-14(9/16) X 20(13/16) Oval hole
(23/32)(23/32)
724 (721 ~ 727)
(29-15/16)
(28-13/32 ~ 28-5/8)
(28-17/32)
(3-23/32)
(5-23/32)
(3-5/16)
(3-9/32)
(5-29/32)
(10-3/8)
(64-31/32)
(55-17/32)
(9-15/32)
(48-1/16)
(29-15/16)
(5-3/16)
(5-23/32)
(11-7/8)
(8-17/32)
(8-9/16)
(5-3/4)
(3-9/16)
(3-1/16)
(2-5/16)
(5-17/32)
(2-31/32)
(10-11/16)
(9-29/32)
(9-9/32)
(29-15/16)
(2-3/16)(1)
(1)(2-3/16)
(2-5/32)
ø28.58 Brazed
760
150
8494
271 140
(Mounting pitch)
235
146
2
4
5
7
1
Accessories Connecting pipe Low pressure · Pipe (IDø25.4 [1] X IDø22.2 [7/8])················P96 1 pc.
· Pipe (IDø25.4 [1] X IDø28.58 [1-1/8])···········P120 1 pc.
High pressure · Pipe (IDø25.4 [1] X ODø19.05 [3/4])·············P96, P120 1 pc.
·
Elbow (IDø19.05 [3/4] X ODø19.05 [3/4])········P96, P120 1 pc.
55
PURY-P120THMU (-BS)
*1. Use only the supplied connecting pipes (for bottom and front piping).
*1
3
6
Refrigerant service valve <High pressure>
217
7790
58
75
251
55
Refrigerant service valve <Low pressure>
Refrigerant service
valve <High pressure>
Refrigerant service
valve <Low pressure>
ø22.2 Brazed
Low pressure
Connection specifications for the refrigerant service valve
High pressure
ø19.05 Brazed
PURY-P96THMU (-BS)
Model
Connecting pipe specifications
1220
760
1650
240
1410
271
216
18
8080
1060
18
301
83
Intake air
Control box
Intake air
Service panel
131
(760)
Discharge air
Intake air
54
2525
145
263
145
(7/8)
(5-17/32)(3-1/16)
(1-25/32)
(3-23/32)(5-29/32)
(2-9/16)
(1-11/32)
(2-15/32) (1-3/8)
(1-3/4)
(1-1/8)
(7/8)
(3/4)
To p view
Left side view
Front view
Bottom view
Note 1. Refer to the Engineering or Installation manual for information regarding
necessary clearance around the unit, and installation site requirements.
2. When brazing the pipes, protect the refrigerant service valve by wrapping it with a wet cloth to keep its temperature under 120°C (248°F).
1
2
4
3
5
6
7
Unit : mm(in)
Modules 1 and 2: PURY-P96THMU-A-BS – DIMENSIONS
C SD - PURY-P192TSHMU-A-BS - 1 - 200809 © MITSUBISHI ELECTRIC / HVAC 2008
HVAC Advanced Products Division
Mitsubishi Electric & Electronics USA, Inc.
3400 Lawrenceville Suwanee Rd. Suwanee, GA 30024
Tele: 678-376-2900 • Fax: 800-889-9904 Toll Free: 800-433-4822 (#4)
www.mehvac.com
Specications are subject to change without notice.