Mitsubishi PUHZ-RP200YHA2, PUHZ-RP250YHA2 Service Manual

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SERVICE MANUAL
R410A
Outdoor unit [model names]
PUHZ-RP200YHA2
PUHZ-RP250YHA2
PUHZ-RP200YHA2 PUHZ-RP250YHA2
November 2007
No.OCH428
Note:
This manual describes only
service data of the outdoor units.
RoHS compliant products
have <G> mark on the spec name plate.
PUHZ-RP200YHA2 PUHZ-RP250YHA2
CONTENTS
1. REFERENCE MANUAL ································ 2
2. SAFETY PRECAUTION································3
3. FEATURES····················································7
4. SPECIFICATIONS ········································· 8
5. DATA······························································ 9
6. OUTLINES AND DIMENSIONS ·················· 12
7. WIRING DIAGRAM ····································· 13
8. WIRING SPECIFICATIONS························· 14 REFRIGERANT SYSTEM DIAGRAM
9.
10. TROUBLESHOOTING································· 21
11. FUNCTION SETTING ·································· 73
12.
MONITORING THE OPERATION DATA BY THE REMOTE CONTROLLER
13. EASY MAINTENANCE FUNCTION··············90
14. DISASSEMBLY PROCEDURE···················· 93
············ 19
········· 80
PARTS CATALOG (OCB428)
1
REFERENCE MANUAL
INDOOR UNIT’S SERVICE MANUAL
Model name Service Ref.
PLA-RP35/50/60/71/100/125/140BA PLA-RP35/50/60/71/100/125/140BA
PCA-RP50/60/71/100/125/140GA PCA-RP50/60/71/100/125/140GA PCA-RP50GA2 PCA-RP50GA2
PCA-RP71/125HA
PKA-RP35/50GAL PKA-RP35/50GAL
PKA-RP60/71/100FAL PKA-RP60/71/100FAL PKA-RP50FAL2 PKA-RP50FAL2
PEAD-RP50/60/71/125/140EA PEAD-RP35/100EA2
PEAD-RP60/71/100GA
PEA-RP200/250/400/500GA
PCA-RP71/125HA
PEAD-RP50/60/71/125/140EA.UK PEAD-RP35/100EA2.UK
PEAD-RP60/71/100GA.UK
PEA-RP200/250/400/500GA.TH-AF PEA-RP200/250GA.TH-AFMF
(1).UK
Service
Manual No.
OCH412 OCB412
OC328
OC329
OC330
OC331
HWE05210
HWE05060
HWE0708A
2
2 SAFETY PRECAUTION
2-1. ALWAYS OBSERVE FOR SAFETY
Before obtaining access to terminal, all supply circuits must be disconnected.
2-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R410A
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with the followings.
· Be sure to perform replacement operation before test run.
· Change flare nut to the one provided with this product. Use a newly flared pipe.
· Avoid using thin pipes.
Make sure that the inside and outside of refrige­rant piping is clean and it has no contamination such as sulfur hazardous for use, oxides, dirt, shaving particles, etc. In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterio­ration of refrigerant oil etc.
Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrige­rant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Tools for R410A Gauge manifold Charge hose
Gas leak detector
Torque wrench
Flare tool Size adjustment gauge Vacuum pump adaptor
Electronic refrigerant charging scale
Keep the tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigerant oil applied to flares and flange connections.
If large amount of mineral oil enters, that can cause deterio­ration of refrigerant oil etc.
Charge refrigerant from liquid phase of gas cylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera­nt will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
3
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously. Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Tool name Specifications
Gauge manifold ·Only for R410A
·Use the existing fitting
·Use high-tension side pressure of 5.3MPa·G or over.
Charge hose ·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
Electronic scale
Gas leak detector ·Use the detector for R134a, R407C or R410A.
Adaptor for reverse flow check ·Attach on vacuum pump.
Refrigerant charge base
Refrigerant cylinder ·Only for R410A ·Top of cylinder (Pink)
·Cylinder with syphon
Refrigerant recovery equipment
specifications
. (UNF1/2)
4
5
2-3. Precautions when reusing existing R22 refrigerant pipes
(1) Flowchart
Measure the existing pipe thickness and check for damage.
The existing pipe thickness meets specifi­cations and the pipes are not damaged.
Check if the existing air conditioner can operate.
The existing air conditioner can operate. The existing air conditioner cannot operate.
After operating the cooling system for about 30 minutes, do a pump down work.
Disconnect the existing air conditioner from the pipes.
The existing piping can be reused. After flaring the pipes again, connect the new air conditioner.
Use a refrigerant recovery device to recover the refrigerant.
Check the oil condition when recovering refrigerant.
Oil is clean. (Clear to brownish color)
In case that existing pipes were used for gas or oil heat pump system, be sure to clean the pipes.
Oil is dirty. (Black color)
The existing pipe thickness does not meet specifications or the pipes are damaged.
When the compressor bearings are seized, winding is damaged or the compressor breaks down, iron particles or oil deterioration will blacken the oil.
The existing pipes cannot be reused. Use new pipes.
Perform the following inspections: air tightness test, vacuum dryness (additional refrigerant charge), gas leakage check
Replacement operation
Test operation
·When performing replacement operation, make sure that DIP SW8-2 on outdoor unit controller board is set to ON.
+Chemical compounds containing chlorine left in existing pipes are recovered by replace filter. LThe air conditioner automatically performs cooling operation through replace filter for about 2 hours.
Connecting a new air conditioner to existing R22 refrigerant pipes
Flare the pipe for the use with R410A refrigerant.
Use the flare nut attached to indoor and outdoor unit of the new air conditioner only.
When reusing existing R22 refrigerant pipes of which gas pipe is :28.58mm and, when the outdoor unit is installed to lower
position than the indoor unit, be sure to change the setting of the DIP SW8-1 on the controller circuit board of the outdoor unit to ON.
=This is to increase the speed of refrigerant passing in the gas pipe so that refrigerant oil can smoothly flow in the system.
• Use a different-diameter joint or brazing for the connection.
When reusing standard-size existing R22 refrigerant pipes.
The pipes can be reused with pipe length restriction described on TECHNICAL DATA BOOK.
(2) Cautions for refrigerant piping work
1/4 3/8 1/2 5/8 3/4
6.35
9.52
12.70
15.88
19.05
17.0
22.0
26.0
29.0
36.0
17.0
22.0
24.0
27.0
36.0
Nominal
dimensions(inch)
Flare nut dimensions
Outside
diameter
Dimension B
(mm)
R410A R22
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working pressure of R410A is 1.6 time higher than that of R22, their sizes of flared sections and flare nuts are different.
Thickness of pipes
Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness shown below. (Never use pipes of 0.7mm or below.)
Diagram below: Piping diameter and thickness
Nominal
dimensions (inch)
1/4 3/8 1/2 5/8 3/4 7/8
1
1-1/8
Outside
diameter (mm)
6.35
9.52
12.70
15.88
19.05
22.20
25.40
28.58
Thickness (mm)
R410A R22
0.8
0.8
0.8
1.0 — — — —
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that, R410A is a refrigerant, which has higher risk of leakage because of its working pressure higher than that of other refriger ants. Therefore, to enhance airtightness and intensity, flare cutting dimension of copper pipe for R410A have been speci­fied separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also have partly been changed to increase intensity as shown below. Set copper pipe correctly referring to copper pipe flaring dimensions for R410A below. For 1/2 and 5/8 inch, the dimension B changes. Use torque wrench corresponding to each dimension.
-
Dimension A
Flare cutting dimensions
Nominal
dimensions(inch)
Outside
diameter 1/4 3/8 1/2 5/8 3/4
6.35
9.52
12.70
15.88
19.05
Dimension A
R410A R22
9.1
13.2
16.6
19.7
24.0
+0
( )
-0.4
9.0
13.0
16.2
19.4
23.3
(mm)
Tools for R410A (The following table shows whether conventional tools can be used or not.)
Tools and materials Use R410A tools Can R22 tools be used? Gauge manifold
Charge hose Gas leak detector
Refrigerant recovery equipment Refrigerant cylinder Applied oil
Safety charger
Charge valve
Vacuum pump
Flare tool
Bender Pipe cutter Welder and nitrogen gas cylinder Refrigerant charging scale
Vacuum gauge or thermis­tor vacuum gauge and vacuum valve Charging cylinder
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.) : Tools for other refrigerants can be used under certain conditions. : Tools for other refrigerants can be used.
Air purge, refrigerant charge and operation check Gas leak check
Refrigerant recovery Refrigerant charge
Apply to flared section
Prevent compressor malfunction when charging refrigerant by
spraying liquid refrigerant Prevent gas from blowing out
when detaching charge hose Vacuum drying and air purge
Flaring work of piping
Bend the pipes Cut the pipes Weld the pipes Refrigerant charge Check the degree of vacuum. (Vacuum
valve prevents back flow of oil and refri­gerant to thermistor vacuum gauge) Refrigerant charge
Tool exclusive for R410A Tool exclusive for R410A Tool for HFC refrigerant Tool exclusive for R410A Tool exclusive for R410A Ester oil, ether oil and
alkylbenzene oil (minimum amount) Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can be used if equipped with adop­ter for reverse flow check Tools for other refrigerants
can be used by adjusting flaring dimension
(Usable if equipped
with adopter for rever­ se flow)
(Usable by adjusting flaring dimension)
Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used
Tool exclusive for R410A
6
Dimension B
Can R407C tools be used?
Ester oil, ether oil: Alkylbenzene oil: minimum amount
(Usable if equipped
with adopter for rever­ se flow)
(Usable by adjusting
flaring dimension)
3 FEATURES
3-1. COMBINATION OF INDOOR AND OUT DOOR UNITS
3-1-1. 1:1 SYSTEM, 1:2 SYSTEM
Outdoor unit
Indoor unit
PEA-RP200, 250GA
3-1-2. SYNCHRONIZED TWIN, TRIPLE AND QUADRUPLE SYSTEM (1) Synchronized twin (50:50)
Indoor unit
PLA-RP100BA 2 PLA-RP125BA2 PEAD-RP100EA2 2
PEAD-RP125EA 2
PEAD-RP100GA 2
PKA-RP100FAL 2
PCA-RP100GA 2
PCA-RP125GA 2
PCA-RP125HA 2
PUHZ-RP·YHA2
200 250
Outdoor unit
PUHZ-RP·YHA2
200 250
Indoor unit
200 2 250 2
PEA-RP400, 500GA
(2) Synchronized triple (33:33:33)
Outdoor unit
Indoor unit
PLA-RP60BA 3 PLA-RP71BA 3
PEAD-RP60EA 3 PEAD-RP71EA 3 PEAD-RP60GA 3 PEAD-RP71GA 3 PKA-RP60FAL 3 PKA-RP71FAL 3 PCA-RP60GA 3 PCA-RP71GA 3 PCA-RP71HA 3
PUHZ-RP·YHA2
200 250
PUHZ-RP·YHA2
Outdoor unit
(3)
Synchronized quadruple (25:25:25:25)
PLA-RP50BA 4 PLA-RP60BA 4
PEAD-RP50EA 4 PEAD-RP60EA 4 PEAD-RP60GA 4 PKA-RP50GAL 4 PKA-RP50FAL2 4 PKA-RP60FAL 4 PCA-RP50GA(2) 4
PCA-RP60GA
Indoor unit
Outdoor unit
PUHZ-RP·YHA2
200 250
4
3-1-3. MULTI DISTRIBUTION PIPE (OPTION)
Ratio of distributing Part No.
Synchronized twin 50:50 MSDD-50WR-E
Synchronized triple 33:33:33 MSDT-111R-E
Synchronized quadruple 25:25:25:25 MSDF-1111R-E
3-2. FEATURES
PUHZ-RP200YHA2 PUHZ-RP250YHA2
CHARGELESS SYSTEM PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT. (Max.30m)
The refrigerant circuit with LEV(Linear Expansion Valve) and accumulator always control the optimal refrigerant level regardless of the length (30m max. and 5m min.) of piping. The additional refrigerant charging work during installation often causes problems. It is completely eliminated by chargeless system. This unique system improves the quality and reliability of the work done. It also helps to speed up the installation time.
7
4 SPECIFICATIONS
Service Ref.
Mode
Power supply (phase, cycle, voltage) Running current Max. current External finish Refrigerant control Compressor Model Motor output Starter type Protection devices
Crankcase heater Heat exchanger Fan Fan(drive) % No. Fan motor output Airflow
OUTDOOR UNIT
Defrost method Noise level
Dimensions
Weight Refrigerant Charge Oil (Model) Pipe size O.D.
Connection method
Between the indoor & outdoor unit
REFRIGERANT PIPING
*
Cooling Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
mm(in.) mm(in.) mm(in.)
kg(lbs)
kg(lbs)
mm(in.) mm(in.)
A A
kW
W
kW
/min(L/s
dB dB
L
PUHZ-RP250YHA2PUHZ-RP200YHA2
Cooling
7.70
HP switch
Comp. Shell thermo
)
135(297)
6.5(14.3)
2.30(FV50S)
9.52(3/8)
25.4(1)
19
4.7
58 59
Heating
3 phase 50Hz, 400V
8.90
Munsell 3Y 7.8/1.1
Linear Expansion Valve
Hermetic
ANB52FFJMT
Inverter
Plate fin coil
Propeller fan % 2
0.150 + 0.150 130(2170)
Reverse cycle
950(37-3/8)
330 + 30(13+1-3/16)
1,350(53-1/8)
R410A
Flared
Flared & Brazing
Max. 30m
Max. 120m
Cooling
9.50
HP switch, LP switch
21
5.5
Discharge thermo
58 59
136(299)
7.1(15.7)
1.60(FV50S)
12.7(1/2)
25.4(1)
Heating
11.1
8
9
5 DATA
Amount of additional refrigerant charge (kg)
30 m and less 31-40 m and less 41-50 m and less 51-60 m and less 61-70 m and less 71-120 m and less
0.9 kg 1.8 kg 2.7 kg 3.6 kg
1.2 kg 2.4 kg 3.6 kg 4.8 kg
Outdoor unit
Permitted pipe length
RP200
RP250
120m or less
Initial charge
(kg)
6.5
7.1
No additional
charge necessary
The additional charge amount is obtained by the following formula.
Main piping: Liquid line size :9.52 overall length [m]
%
0.09
[kg/m]
Branch piping: Liquid line size :9.52 overall length [m] % 0.06 [kg/m]
Branch piping: Liquid line size :6.35 overall length [m] % 0.02 [kg/m]
3.6 (kg)
Amount of additional charge [kg]
Main piping: Liquid line size :12.7 over all length [m] % 0.12 [kg/m]
=
Additional charge amount for 70 m
RP200 3.6 kg RP250 4.8 kg
+
+
+–
Calculate the additional charge amount based on the following procedure. If the calculation results in an amount that is smaller than the "Additional charge amount for 70m," perform the additional charge using the amount shown in "Additional charge amount for 70m."
5-1. ADJUSTING THE AMOUNT OF REFRIGERANT
5-2. COMPRESSOR TECHNICAL DATA
DWÛ&
Unit
Compressor model
PUHZ-RP200, 250YHA2
ANB52FFJMT
U-V
0.30
Winding
Resistance
U-W
0.30
( )
W-V
0.30
5-3. NOISE CRITERION CURVES
MICROPHONE
1.5m
1m
UNIT
GROUND
PUHZ-RP200YHA2 PUHZ-RP250YHA2
90
80
70
60
50
40
COOLING
HEATING
58 59
SPL(dB)
MODE
LINE
NC-70
NC-60
NC-50
NC-40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-30
NC-20
5-4. ELECTRICAL PARTS SPECIFICATIONS
Outdoor unit
PUHZ-RP200YHA2
Parts name
FUSE
(FUSE1,2)
PUHZ-RP250YHA2
250V 15A
FUSE
(F 3,4)
Valve
4-way Valve Coil
21S4
Linear Expansion
Valve
Linear Expansion
Valve Coil
(LEV-A)(LEV-B)
Bypass Valve
Bypass Valve Coil
(SV)
Reactor
(DCL)
High pressure switch
(63H1)
High Pressure
Switch
(63H, 63H2)
Low Pressure
Switch
(63L)
Fan Motor
(MF1)(MF2)
Thermistor
(Outdoor Pipe)
(TH3)
Thermistor
(Discharge)
(TH4)
Thermistor
(Outdoor2-PhasePipe)
(TH6)
Thermistor
(Outdoor)
(TH7)
7HUPLQDO%ORFN
(Power Supply)
(TB1)
7HUPLQDO%ORFN
(Indoor / Outdoor)
(TB2)
Main Smoothing Capacitor
(CB1, CB2)
Rush Current
Protect Resister
(RS)
Compressor
(MC)
250V 6.3A
STF0731Z
STF AC220~240V
(BG50T388)
UKV-32D
(0~480 Pulse)
DC12V
FDF6A-008-RK
FQ AC220~240V
2.7mH 25A
OFF 3.60 + 0.2MPa
ON 2.80 ± 0.15MPa
8P 150W % 2
SIC-81FW-D8187
Û&NÛ&NÛ&NÛ&NÛ&NÛ&N
Û&NÛ&NÛ&NÛ&NÛ&NÛ&NÛ&NÛ&NÛ&N
Û&NÛ&NÛ&NÛ&NÛ&NÛ&N
Û&NÛ&NÛ&NÛ&NÛ&NÛ&N
(L1, L2, L3, N, )
(S1, S2, S3)
2200 400V
:
ANB52FFJMT
Scroll type 6P
OFF 4.14±0.1MPa / ON 3.14±0.15MPa
5P
3P
HAM-BD35
(0~480 Pulse)
ACB-1UB24
OFF -0.03 ± 0.03MPa
ON 0.05 ± 0.04MPa
10
PUHZ-RP250YHA2PUHZ-RP200YHA2
PLA-RP125BA ×2PLA-RP100BA ×2
PLA-RP125BAPLA-RP100BA
3, 50
3, 50
1, 501, 50
230230
400
400
HeatingCooling
HeatingCooling
11.1
2.37
(24.2)
0.60
(6.12)
72.8
41.2
0.9
7.5
20
15
41.1
7
6
9.50
2.86
(29.2)
0.89
(9.08)
78.2
48.4
16.2
7.5
27
19
14.2
35
24
0.77
0.10
8.90
2.46
(25.1)
0.64
(6.53)
65.6
42.9
-0.1
7.5
20
15
38.1
7
6
7.70
2.71
(27.6)
0.95
(9.69)
66.1
46.3
11.5
7.5
27
19
15.3
35
24
0.78
0.13
0.13 ×20.14 ×2
0.94 ×2 0.87 ×2
0.14 ×20.15 ×2
1.00 ×2 0.94 ×2
19,000 22,400 22,000 27,000
5.19 6.10 6.83 7.48
Electrical circuitRefrigerant circuitIndoor side
Outdoor
side
Representative matching
SHF
BF
Mode
Capacty
Input
Total
(kgf/%)
(kgf/%)
Phase , Hz
Voltage
Input
Current
Outdoor unit
Phase , Hz
Voltage
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
V
kW
A
V
A
Mpa
Mpa
Û&
Û&
Û&
m
Û&
Û&
Û&
Û&
Û&
Indoor unit
D.B.
W.B.
D.B.
D.B.
W.B.
W
kW
5-5. STANDARD OPERATION DATA
The unit of pressure has been changed to MPa based on international SI system. The conversion factor is : 1(MPa)=10.2(kgf/cm2)
11
6 OUTLINES AND DIMENSIONS
PUHZ-RP200YHA2 PUHZ-RP250YHA2
175600175
2-U Shaped notched holes
(foundation Bolt M10)
Installation Feet
Rear Air Intake
53
40560
417
37028 19
33030
Terminal Connections
Left···Power supply wiring
60 37
70
2-12%36 oval holes
(Foundation Bolt M10)
Air Discharge
)
Right···Indoor/Outdoor wiring
(
Earth terminal
950
322
Handle for moving
Service Panel
635
1350
Unit : mm
999
995
Brazing
*1 439
*1 A
371
*2 339
Front piping cover
Rear piping cover
71
23
71
Bottom piping hole
(Knockout)
219
Drain hole
(5-:33)
14514514522030
81
Side Air Intake
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
4 PIPING-WIRING DIRECTIONS
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
3 FOUNDATION BOLTS2 SERVICE SPACE
purchased locally.)
150
Over
Dimensions of space needed
for service access are
shown in the below diagram.
FREE
FOUNDATION
30
<Foundation bolt height>
Less than
500
Over
500
Over
10
Over
Service space
Over 150mm
Over 10mm
Handle for moving
Side Air Intake
Side Air Intake
Rear Air Intake
Handle for moving
Handle for moving
Handle for moving
A
447
:9.52
(3/8 inch)
421
:12.7
(1/2 inch)
Air Intake
Power supply wiring hole
(2-:27Knockout)
Rear trunking hole
(Knockout)
4045
5527
Right trunking hole
(Knockout)
Power supply wiring hole
4075
(2-:27Knockout)
6373
Right piping hole
(Knockout)
5527
40 45
Power supply wiring hole
(2-:27Knockout)
Rear piping hole
92
:92
637323
:92
922723
6373
:92
(Knockout)
65
5519
92
23
65
92
The diagram below shows a basic
example.
Explantion of particular details is
given in the installation manuals etc.
1 FREE SPACE (Around the unit)
Over 10mm
Over 1000mm
· · · ·Refrigerant GAS pipe connction (FLARE):19.05(3/4 inch)
· · · ·Refrigerant LIQUID pipe connection (FLARE)
Example of Notes
*1· · · ·Indication of STOP VALVE connection location
*2· · · ·Refrigerant GAS PIPE connention(BRAZING) O.D:25.4
PUHZ-RP250YHA2
PUHZ-RP200YHA2
12
Front trunking hole
(Knockout)
Front piping hole
(Knockout)
Piping Knockout Hole Details
7 WIRING DIAGRAM
PUHZ-RP200YHA2 PUHZ-RP250YHA2
[LEGEND]
SYMBOL TB1 TB2 Terminal Block<Indoor/Outdoor> MC MF1,MF2 21S4 SV Solenoid Valve (Bypass Valve) 63H,63H1,63H2 63L Low Pressure Switch TH3 TH4 TH6 TH7 LEV-A,LEV-B ACL4 DCL CB1,CB2 RS FUSE1, FUSE2 CY1,CY2
Terminal Block<Power Supply>
Motor for Compressor Fan Motor
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Thermistor<Outdoor Pipe>
Thermistor<Discharge> Thermistor<Outdoor 2-Phase Pipe> Thermistor<Outdoor> Electronic Expansion Valve
Reactor Reactor Main Smoothing Capacitor Rush Current Protect Resistor
Fuse<T15AL250V> Capacitor
C. B.
1
MF1
MS 3~
1
MF2
MS 3~
TB2
S1
INDOOR UNIT
S2
S3
NAME SYMBOL NAME SYMBOL NAME
TH7TH6 TH3 TH4
WÛ WÛ WÛ WÛ
CNF1
CNS
(WHT)
31
CY2
CY1
BRN
ORN
7
(WHT)
CNF2
7
(WHT)
2
YLW
3
1
CNDC (PNK)
WHT
FUSE1
WHT
412121 TH7/6 (RED)
(WHT)
TRANS
CNAC (WHT)
REDRED
FUSE2
P.B.
SC-U/V/W TB-L1/L2/L3 TB-P1 TB-P2 TB-C1 TB-N1 X52A
N.F.
LI1/ LI2/LI3/NI LO1/ LO2/LO3 GD1,GD2
C.B.
SW1
SW4 SW5 SW6 SW7
+3. For RP200
63H
TH3
TH4
(WHT
)
CN2
(WHT)
1
F3
21
F4
43
7
2
2
RS
RED
Power Circuit Board Connection Terminal<U/V/W-Phase> Connection Terminal<L1/L2/L3-Power supply>
Connection Terminal Connection Terminal
Connection Terminal
Connection Terminal
52C Relay
Noise Filter Circuit Board Connection Terminal Connection Terminal Connection Terminal<Ground>
Controller Circuit Board Switch<Forced Defrost, Defect History Record Reset, Refrigerant Address> Switch<Test Operation> Switch<Function Switch> Switch<Model Select> Switch<Function Setup>
+3. For RP250
63H2
63H1
63H
(YLW)
7
7
P. B.
7
CN2
(WHT)
1
2
(WHT)
1 2
(RED)
1
BLK
BLK
TB-P1
31
CN4
CN5
X52A
DCL
+4. RP250 only
63L
31
63L
(RED)
TB-P2
+5. RP200 RP250
LED2
LEV-A
M
LEV-A (WHT)
21S4
RED
=
5 LINE
=
6 LINE
<L1/L2/L3/NI-Power supply <L1/L2/L3-Power supply>
+6.RP250 only
LEV-B
M
35
61
61
LED1
CN4
(WHT)
12
2
X52
21S4
(GRN)
CB1 CB2
CNVMNT
LEV-B
(WHT)
(RED)
(WHT)
X55
13
SV2
(BLU)
SV
TB-C1 TB-N1
WHT
CNM
SC-W
SC-V
SC-U
31
CNMNT
(WHT)
TB-L3
TB-L2
TB-L1
BLK
51
141
1313
>
X51
(WHT)
SW5SW8SW4
SWP
SS
SW8 SW9 SWP CN31 LED1,LED2 F3,F4 SS CNM CNMNT
CNVMNT
CNDM
CN3S CN51 X51,X52,X55
+1+
1
SW6SW1
CN31
CN3S
CNDM
CN51
BLK
WHT
RED
BLK
WHT
RED
Switch<Function Setup> Switch Switch<Pump Down> Connector<Emergency Operation> LED<Operation Inspection Indicators>
Fuse<T6.3AL250V
Connector<Connection for Option> Connector<A-Control Service Inspection Kit> Connector <Connected to Optional M-NET Adapter Board> Connector <Connected to Optional M-NET Adapter Board> Connector < Connected for Option (Contact Input)> Connector<Connection for Option> Connector<Connection for Option> Relay
SW7
SW9
1
3
(WHT)
1
3
(WHT)
1
(WHT)
5
>
When M-NET adapter is connected
5
SW1
CN5
ABS
(WHT)
1
LED2
LED3
LED4
M-NET SUBSTRATE
2
CND
1
CN2M
(WHT)
(WHT) 31
LED1
LED5
3
TB7
M-NET
5
SW11
SW12
M-NET ADAPTER
SYMBOL
TB7 CN5 CND CN2M SW1
MC
W
V
MS
3~
U
SW11 SW12 LED1 LED2 LED3 LED4 LED5
Terminal Block(M-NET connection)
Connector<Transmission> Connector<Power Supply> Connector<M-NET communication>
Switch<Status of communication> Switch<Address setting:1st digit> Switch<Address setting:2nd digit> LED<Power Supply:DC5V> LED<Connection to Outdoor Unit> LED<Transmission:Sending> LED<Transmission:Receiving> LED<Power Supply:DC12V>
NAME
POWER SUPPLY 3N~ 400V 50Hz
NO FUSE BREAKER
TB1
L1
L2
L3
N
RED
WHT
BLK
BLU
GRN/YLW
2
N. F.
CNAC1
(WHT)
31
LI 1
LI 2
UU
LI 3
U
NI
U
U
GD2GD1
BLK
CNDC (PNK)
BLK
CNCT (RED)
31
2
WHT
CNAC2
(RED)
3112
LO 1
RED
LO 2
WHT
LO3
BLK
+
1 MODEL SELECT
MODEL
200Y
U
13
CNL
(BLU)
WHT
ACL4
250Y
+
2. SW5 -1 to 5 : Function Switch
SW6
ON OFF
12345678
ON OFF
12345678
ON OFF
ON OFF
SW5-6+2
123456
123456
13
8 WIRING SPECIFICATIONS
8-1. FIELD ELECTRICAL WIRING (power wiring specifications)
P200, P250
Outdoor unit model RP200, 250 Outdoor unit Power supply Outdoor unit input capacity *1 Main switch (Breaker)
Wiring
Wire No. %
size(mm
Outdoor unit power supply 5 % Min. 4 Indoor unit-Outdoor unit *2 Cable length 50 m : 3 % 4 (Polar)/Cable length 80 m : 3 % 6 (Polar) Indoor unit-Outdoor unit earth 1 % Min. 2.5
2
)
Remote controller-Indoor unit *3 2 % 0.69 (Non-polar) Outdoor unit L1-N, L2-N, L3-N AC 220 - 230 - 240 V
Circuit rating
Indoor unit-Outdoor unit S1-S2 *4 AC 220 - 230 - 240 V Indoor unit-Outdoor unit S2-S3 *4 DC 24 V Remote controller-Indoor unit *4 DC 14 V
*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV). *2. Max. 80 m Total Max. including all indoor/indoor connection is 80 m.
• Use one cable for S1 and S2 and another for S3 as shown in the picture.
• Max. 50m Total Max. for PEA-200, 250, 400, 500 Wiring size 3%1.5(Polar) *3. The 10 m wire is attached in the remote controller accessory. *4. The figures are NOT against the ground. S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulated by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and Indoor unit/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
3. Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied.
Phase Frequency & Voltage
380/400/415V 50Hz 3 phase(4 wires)
3N~(3ph 4-wires), 50 Hz,
380 - 400 - 415 V
32 A
Isolator
A-Control
Outdoor Unit
S1
S2
S3
3 poles isolator
S1
S2
S3
A-Control
Indoor Unit
Warning: In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
Synchronized twin and triple system Electrical wiring
• Synchronized twin • Synchronized triple
Outdoor
Unit power supply
Earth leakage breaker Wiring circuit breaker or
isolating switch
Outdoor unit
unit
L1 L2
3
L
N
Indoor/outdoor unit connection cable
S1 S2 S3
Indoor unit
S1 S2 S3
1
Remote controller
2
Indoor unit
1 2
S1 S2 S3
Unit power supply
Earth leakage breaker Wiring circuit breaker or
isolating switch
Outdoor unit
L1 L2 L
3
N
Indoor/outdoor connection cable
S1 S2 S3
Indoor unit
S1 S2 S3
1 2
Remote controller
Indoor unit
1 2
S1 S2 S3
Indoor unit
1 2
S1 S2 S3
14
S1 S2 S3
Indoor/outdoor unit connection cable
Indoor unit
Unit power supply
Unit power supply
Outdoor unit No.1
L1 L2 L3
N
S1 S2 S3
L1 L2 L3
N
Earth leakage breaker Wiring circuit breaker or
isolating switch
S1 S2 S3
Indoor/outdoor unit connection cable
TB4-1
TB4-2
Unit power supply
Outdoor unit No.2
L
1
L2 L3
N
S1 S2 S3
1 2
Remote controller
1:1 System (Indoor : PEA-200, 250) 1:2 System (Indoor : PEA-400, 500)
Indoor unit
L1 L2 L3 N
S1 S2 S3
1
Remote controller
2
supply
Unit power
Unit power
supply
Earth leakage breaker Wiring circuit breaker or
isolating switch
Outdoor unit
1
L L2
L3
N
Indoor/outdoor unit connection
cable S1 S2 S3
8-2. SEPARATE INDOOR UNIT/ OUTDOOR UNIT POWER SUPPLIES
Simultaneous twin/triple/four system
<For models without heater>
The optional indoor power supply terminal kit is required.
*
L
1
L
2
L
3

N
S1 S2 S3

L
L
N
S1 S2 S3
1
2
L
N
N
S1
S1
S2
S2
S3
S3
1
1
2
2
L N
S1 S2 S3
1 2
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
If the indoor and outdoor units have separate power supplies, refer to the table below. If the optional indoor power supply terminal kit is used, change the indoor unit electrical box wiring referring to the figure in the right and the DIP switch settings of the outdoor unit control board.
Indoor unit specifications Indoor power supply terminal kit (option) Indoor unit electrical box connector con­nection change Label affixed near each wiring diagram for the indoor and outdoor units Outdoor unit DIP switch settings (when using separate indoor unit/outdoor unit power supplies only)
ON OFF
Required
Required
Required
3
1 2 (SW8)
Electric heater (For models with heater)
L
N
S1
S2
S3
Indoor unit power supplied from outdoor unit (when shipped from factory)
Connectors (connections when shipped from the factory are for indoor unit power supplied from outdoor unit.)
BLUE
BLUE
YELLOW
YELLOW
CND
Set the SW8-3 to ON.
* There are 3 types of labels (Labels A, B, and C). Affix the appropriate labels to
the units according to the wiring method.
Indoor unit model Indoor unit power supply Indoor unit input capacity Main switch (Breaker)
Indoor unit power supply Indoor unit power supply earth
)
2
Indoor unit-Outdoor unit
(mm
Wiring
Indoor unit-Outdoor unit earth
Wire No. % size
Remote controller-Indoor unit
Indoor unit L-N *4
Indoor unit-Outdoor unit S1-S2 Indoor unit-Outdoor unit S2-S3
rating
Circuit
Remote controller-Indoor unit
*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV). The breaker shall be provided to ensure disconnection of all active phase conductor of the supply. *2. Max. 120 m *3. The 10 m wire is attached in the remote controller accessory. Max. 500 m *4. The figures are NOT always against the ground.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cables and indoor unit/outdoor unit connecting cables shall not be lighter than polychloroprene sheathed flexible cable. (Design 60245 IEC 57)
3. Install an earth longer than other cables.
*1
*2
*3
*4 *4 *4
15
RP35~140
~/N (single), 50 Hz, 230 V
16 A
2 % Min. 1.5 1 % Min. 1.5 2 % Min. 0.3
2 % 0.3 (Non-polar)
AC 230 V
– DC24 V DC12 V
control board
Outdoor unit power supply
Earth leakage breaker
Wiring circuit breaker or isolating switch
Outdoor unit
Indoor unit/outdoor unit connecting cales
Remote controller
Indoor unit
Option
Indoor unit power supply
ORANGE CND
Indoor unit
Electric heater (For models with heater)
L
N
S1
S2
S3
Separate indoor unit/outdoor unit power supplies
If the indoor and outdoor units have separate power supplies, change the connections of the connectors as shown in the following figure.
BLUE
YELLOW
Connectors
CND
Indoor unit
control board
ORANGE CND
YELLOW
BLUE
8-3. INDOOR – OUTDOOR CONNECTING CABLE
WIRING SPECIFICATIONS FOR 220-240 V 50 Hz (INDOOR-OUTDOOR CONNECTING CABLE)
Cross section of cable Wire size (mm2) Number of wires Polarity L (m)*6
Round
Flat
Flat
Round
2.5 3
2.5 3
1.5 4
2.5 4
Clockwise : S1-S2-S3 * Pay attention to stripe of yellow and green.
Not applicable (Because center wire has no cover finish)
From left to right : S1-Open-S2-S3
Clockwise : S1-S2-S3-Open *Connect S1 and S3 to the opposite angle.
Not applicable
(30)
*2
*5
(18)
*3
(30)
*4
*1 : Power supply cords of appliances shall not be lighter than design 60245 IEC or
227 IEC. *2 : In case that cable with stripe of yellow and green is available. *3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5 mm. *4 : In case of regular polarity connection (S1-S2-S3). *5 : In the flat cables are connected as this picture, they can be used up to 30 m.
2
Indoor/Outdoor separate power supply
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
*6 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, humidity or materials, etc.
Wire No. % Size ($)
Max. 120m
2 % Min. 0.3
(3C Flat cable 2)
+ The optional indoor power supply terminal kit is necessary.
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections). Intermediate connections can lead to communication errors if water enters the cables and causes insufficient insulation to ground or a poor electrical contact at the intermediate connection point.
16
8-4. M-NET WIRING METHOD
(Points to notice) (1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from
making an influence on the signal communication. Place them at intervals of more than 5cm. Do not put them in the same conduit tube.
(2) Terminal block (TB7) for transmission wires should never be connected to 220~240V power supply. If it is connected,
electronic parts on M-NET P.C. board may burn out.
(3) Use 2-core x 1.25mm
received normally if different types of transmission wires are put together in the same multi-conductor cable. Never do this because this may cause a malfunction.
2
shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be sent or
Group remote controller
Power supply unit for transmission wire
Refrigerant address 00
M-NET address 01
A-control remote controller
A-control remote controller
Refrigerant address 00
M-NET address 02
Refrigerant address 00
M-NET address 03
A-control remote controller
It would be ok if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Ground only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise. “Ed” error will appear on the LED display of outdoor unit. “0403” error will appear on the central-control remote controller.
Bad example (Multi spot grounding of shield wire)
Central remote controller
Power supply appliance
M-NET type outdoor unit
M-NET type outdoor unit
M-NET type outdoor unit
M-NET transmission wire
Good example 1 (Single spot grounding of shield wire)
Central remote controller
Power supply appliance
M-NET type outdoor unit
M-NET type outdoor unit
M-NET type outdoor unit
M-NET transmission wire
Good example 2 (Single spot grounding of shield wire)
Central remote controller
Power supply appliance
M-NET type outdoor unit
M-NET type outdoor unit
M-NET type outdoor unit
M-NET transmission wire
If there are more than 2 grounding spots on the shield wire, noise may enter into the shield wire because the ground wire
and shield wire form 1 circuit and the electric potential difference occurs due to the impedance difference among grounding
spots. In case of single spot grounding, noise does not enter into the shield wire because the ground wire and shield wire
do not form 1 circuit.
To avoid communication errors caused by noise, make sure to observe the single spot grounding method described in the
installation manual.
17
ƔM-NET wiring
2
5
2
13
SW11 ones digit
SW12 tens digit
3
4
3
4
5
6
5
6
M-NET terminal block
M1 M2 S
Transmission
12
3
4
2
5
1
6
0
7
9
8
3
4
2
5
1
6
0
7
9
8
ON
OFF
1
3
4
5
2
6
6
ON
OFF
1
3
4
5
2
6
14
OFF
OFF
ON
ON
wire
3
2
1
0
9
8
3
2
1
0
9
8
1
1
Ground wire
Shield part
50
4
5
6
7
~
4
5
6
7
3
4
5
2
7
3
4
5
2
15
3
4
2
5
1
6
0
7
9
8
3
4
2
5
1
6
0
7
9
8
6
6
2
(1) Use 2-core x 1.25mm
shield wire for electric wires.
(Excluding the case connecting to system controller.)
(2) Connect the wire to the M-NET terminal block. Connect one core of the
transmission wire (non-polar) to M1 terminal and the other to M2. Peel the shield wire, twist the shield part to a string and connect it to S terminal.
(3) In the system which several outdoor units are being connected, the terminal
(M1, M2, S) on M-NET terminal block should be individually wired to the other outdoor unit’s terminal, i.e. M1 to M1, M2 to M2 and S to S. In this case, choose one of those outdoor units and drive a screw to fix an ground wire on the plate as shown on the right figure.
8-4-1. M-NET address setting
In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to CITY MULTI system, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as that of the indoor unit in CITY MULTI system), and the address number should be consecutively set in a same group.
Address number can be set by using rotary switches
<Setting example>
M-NET Address No.
(SW11 for ones digit and SW12 for tens digit), which is located on the M-NET board of outdoor unit. (Initial setting: all addresses are set to “0”.)
Switng setting
8-4-2. Refrigerant address setting
In case of multiple grouping system (multiple refrigerant circuits in one group), indoor units should be connected by remote controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to “00” if the group set­ting is not conducted. Set the refrigerant address by using DIP SW1-3 to -6 on the outdoor controller board. [Initial setting: all switches are OFF. (All refrigerant addresses are “00”.)]
Refrigerant address
ON
OFF
1
ON
OFF
1
ON
OFF
1
3
4
5
2
6
0
ON
OFF
1
3
4
5
2
6
8
ON
OFF
1
3
4
5
2
6
1
ON
OFF
1
3
4
5
2
6
9
ON
OFF
1
3
4
5
2
6
2
ON
OFF
1
3
4
5
2
6
10
ON
OFF
1
3
4
5
2
6
3
ON
OFF
1
3
4
5
2
6
11
ON
OFF
1
3
4
5
2
6
4
ON
OFF
1
3
4
5
2
6
12
8-4-3. Regulations in address settings
In case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above sec­tion. Set the lowest number in the group for the outdoor unit whose refrigerant address is “00” as its M-NET address.
Group A Group B Group C
System controller
Power supply unit for transmission wire
Refrigerant address 00
M-NET address 01
A-control remote controller
+ Refrigerant addresses can be overlapped if they are in the different group.
Group A Group B
System controller
Power supply unit for transmission wire
Refrigerant address 00
M-NET address 01
A-control remote controller
Refrigerant address 00
M-NET address 02
A-control remote controller
Refrigerant address 01
M-NET address 02
Refrigerant address 01
M-NET address 03
TB5
TB5
A-control remote controller
Refrigerant address 00
M-NET address 04
Refrigerant address 00
M-NET address 04
A-control remote controller
Refrigerant address 01
M-NET address 03
Refrigerant address 02
M-NET address 05
+ In group B, M-NET address of the outdoor unit whose refrigerant address is “00” is not set to the minimum in the group. As
“3” is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address in the group for the outdoor unit whose refrigerant address is “00”.
18
9 REFRIGERANT SYSTEM DIAGRAM
Unit : mm
PUHZ-RP200YHA2
Ball valve
Refrigerant GAS pipe :25.4(:1 inch)
Refrigerant LIQUID pipe :9.52(:3/8 inch)
Strainer
(#50)
Service port (check)
Accumulator
Stop valve (with service port)
Strainer (#40)
4-way valve
Strainer (#100)
Restrictor valve
Strainer (#100)
Muffler
Compressor
Linear expansion valve
Outdoor heat exchanger
High pressure switch(63H)
Service port (check)
Thermistor (TH4)
Refrigerant flow in cooling
Refrigerant flow in heating
Distributor
Strainer (#100)
Thermistor (TH7)
Thermistor (TH6)
Thermistor (TH3)
PUHZ-RP250YHA2
Ball valve
Refrigerant GAS pipe :25.4(:1 inch)
Stop valve (with service port)
Refrigerant LIQUID pipe :12.7(:1/2 inch)
High pressure switch(63H2)
Strainer (#50)
Service port (check)
Strainer (#100)
Linear expansion valve B
Strainer (#100)
Power receiver
Restrictor valve
Capillary tube
O.D.4.0I.D.3.0L500
4-way valve
Low pressure switch(63L)
Linear expansion valve A
Muffler
Compressor
Replace filter
High pressure switch (63H1)
Service port (check)
Bypass valve
Heat exchanger
Thermistor (TH4) (Discharge)
Strainer (#100)
Thermistor (TH7)
Thermistor (TH6)
Thermistor (TH3)
Distributor
Replace filter
19
Bypass valve
OFF
12
ON
<SW4>


Stop Operation Cooling Heating
9-1. Refrigerant recovering (pump down)
Perform the following procedures to recover the refrigerant when moving the indoor unit or the outdoor unit. Turn on the power supply (circuit breaker).
+When power is supplied, make sure that “CENTRALLY CONTROLLED” is not displayed on the remote controller. If
“CENTRALLY CONTROLLED” is displayed, the refrigerant recovering (pump down) cannot be completed normally. After the liquid stop valve is closed, set the SWP switch on the control board of the outdoor unit to ON. The compressor
(outdoor unit) and fans (indoor and outdoor units) start operating and refrigerant recovering operation begins. LED1 and LED2 on the control board of the outdoor unit are lit. +Set the SWP switch (push-button type) to ON in order to perform refrigerant recovering operation only when the unit is
stopped. However, refrigerant recovering operation cannot be performed until compressor stops even if the unit is stopped. Wait 3 minutes until compressor stops and set the SWP switch to ON again. Because the unit automatically stops in about 2 to 3 minutes after the refrigerant recovering operation (LED1 is not lit
and LED2 is lit), be sure to quickly close the gas stop valve. +In case the outdoor unit is stopped when LED1 is lit and LED2 is not lit, open the liquid stop valve completely, and then
repeat step
3 minutes later.
+If the refrigerant recovering operation has been completed normally (LED1 is not lit and LED2 is lit), the unit will remain
stopped until the power supply is turned off. Turn off the power supply (circuit breaker.)
9-2. Unit replacement operation
When reusing the existing pipes that carried R22 refrigerant for the RP200 and RP250 models, replacement operation must be performed before performing a test run.
If new pipes are used, these procedures are not necessary.During replacement operation, “C5” is displayed on “A-Control Service Tool(PAC-SK52ST)”.
Replacement operation procedures
Turn on the power supply.Set DIP switch SW8-2 on the control board of the outdoor unit to ON to start replacement operation.
The replacement operation is performed using the cooling system. Cool air will flow from the indoor unit during the replace-
ment operation.
TEST RUN
During the replacement operation,
control board of the outdoor unit blink together.
The duration of the replacement operation is determined by the length of the piping. Always perform the replacement
operation for longer than the stipulated time.
* Use one of he following methods to complete replacement operation. When the replacement operation ends, the unit will
automatically stop.
(1)Set SW8-2 from ON to OFF. (When ending a replacement operation of
less than 2 hours.)
Each time SW8-2 is set from OFF to ON, the replacement operation can
be started. Always perform the replacement operation for longer than the stipulated time.
(2) The replacement operation will automatically stop after 2 hours. (It will end with SW8-2 still in the ON position.)
When the replacement operation has ended automatically after 2 hours of operation, there is no need to set SW8-2 from
ON to OFF; normal air conditioning operations can be started with the SW8-2 being set to ON. However, to repeat the replacement operation, SW8-2 will have to be returned to OFF and then set to ON.
,IWKHLQGRRUWHPSHUDWXUHLVEHORZÛ&WKHFRPSUHVVRUZLOORSHUDWHLQWHUPLWWHQWO\EXWWKHXQLWLVQRWIDXOW\
is displayed on the remote controller and LED1 (green) and LED2 (red) on the
<Required replacement operation times>
Piping Length
0 to 20 meters 30 minutes or more 21 to 30 meters 45 minutes or more 31 to 70 meters 60 minutes or more
"Replacement
Operation Time"
9-3. Start and finish of test run
Operation from the indoor unit
Execute the test run using the installation manual for the indoor unit.
Operation from the outdoor unit
By using the DIP switch SW4 on the control board of outdoor unit, test run can be started and finished, and its operation mode (cooling/heating) can be set up.
Set the operation mode (cooling/heating) using SW4-2. Turn on SW4-1 to start test run with the operation mode set by SW4-2. Turn off SW4-1 to finish the test run.
There may be a faint knocking sound around the machine room after power is supplied, but this is
no problem with product because the linear expansion valve is just moving to adjust opening pulse.
There may be a knocking sound around the machine room for several seconds after compressor
starts operating, but this is no problem with product because the check valve, itself, generates the sound since pressure difference is small in the refrigerant circuit.
Note: The operation mode cannot be changed by SW4-2 during test run. (To change test run mode, stop the unit by SW4-1, change the operation mode and restart the test run by SW4-1.)
20
10 TROUBLESHOOTING
10-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring at service, are summarized in the table below. Check the contents below before investigating details.
Unit conditions at service
The trouble is reoccurring.
The trouble is not reoccurring.
Error code
Displayed
Not displayed
Logged
Not logged
Actions to be taken for service (summary)
Judge what is wrong and take a corrective action according to “10-4. Self-diagnosis action table”.
Conduct troubleshooting and ascertain the cause of the trouble according to “10-5. Troubleshooting by inferior phenomena”.
Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise and etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the trouble occurred, matters related to wiring and etc. Reset error code logs and restart the unit after finishing service. There is no abnormality in electrical component, controller board, remote controller and etc.
Re-check the abnormal symptom.Conduct trouble shooting and ascertain the cause of the
trouble phenomena”. Continue to operate unit for the time being if the cause is not ascertained. There is no abnormality concerning of parts such as electrical component, controller board, remote controller and etc.
according to “10-5. Troubleshooting
by inferior
10-2. CHECK POINT UNDER TEST RUN
(1) Before test run
After installation of indoor and outdoor units, piping work and electric wiring work, re-check that there is no refrigerant leak-
age, loosened connections and incorrect polarity.
Measure impedance between the ground and the power supply terminal block(L, N) on the outdoor unit by 500V Megger and
check that it is 1.0M or over.
+Don’t use 500V Megger to indoor/outdoor connecting wire terminal block(S1, S2, S3) and remote controller terminal block
(1, 2). This may cause malfunction.
Make sure that test run switch (SW4) is set to OFF before turning on power supply.
Turn on power supply 12 hours before test run in order to protect compressor.
For specific models which requires higher ceiling settings or auto-recovery feature from power failure, make proper changes
of settings referring to the description of “11. Function setting”.
Make sure to read operation manual before test run. (Especially items to secure safety.)
21
"TEST RUN" and the currently selected operation mode are displayed altemately.
Displays the remaining test run time.
[TEST] button
Pipe (liquid) temperature
Operating procedures
1. Turn on the main power supply.
2. Press TEST button twice.
3. Press OPERATION SWITCH button.
4. Press AIR DIRECTION button.
5. Check the outdoor unit fan for correct running.
6. Press the ON/OFF button to reset the test run in progress.
7. Register the contact number.
While the room temperature display on the remote controller is “PLEASE WAIT”, the remote controller is disabled. Wait until “PLEASE WAIT” disappears before using remote controller. “PLEASE WAIT” appears for about 2 minutes after power supply is turned on. +1
The TEST RUN appears on the screen.
Cooling mode: Heating mode: Check if warm air blows. (It takes a little while until warm air blows.)
Check for correct motion of auto-vanes.
The outdoor unit features automatic capacity control to provide optimum fan speeds. Therefore, the fan keeps running at a low speed to meet the current outside air condition unless it exceeds its available maximum power. Then, in actuality, the fan may stop or run in the reverse direction depending on the outside air, but this does not mean malfunction.
Check if cool air blows and water is drained.
• In case of test run, the OFF timer will be activated, and the test run will automatically stop after 2 hours.
• The room temperature display section shows the pipe temperature of indoor units during the test run.
• Check that all the indoor units are running properly in case of simultaneous twin, triple and quadruple operation. Malfunctions may not be displayed regardless of incorrect wiring. +1 After turning on the power supply, the system will go into startup mode, “PLEASE WAIT” will blink on the display section
of the room temperature, and lamp(green) of the remote controller will blink. As to INDOOR BOARD LED, LED1 will be lit up, LED2 will either be lit up in case the address is 0 or turned off in case the address is not 0. LED3 will blink. As to OUTDOOR BOARD LED, LED1(green) and LED2(red) will be lit up. (After the startup mode of the system finishes, LED2(red) will be turned off.) In case OUTDOOR BOARD LED is digital display, — and — will be displayed alternately every second.
• If one of the above operations doesn’t function correctly, the causes written below should be considered. Find causes from
the symptoms.
The below symptoms are under test run mode. “startup” in the table means the display status of +1 written above.
Symptoms in test run mode
Remote Controller Display
Remote controller displays “PLEASE WAIT”, and
After power is turned on, “PLEASE WAIT” is displayed for 3 minutes, then error code is displayed.
No display appears even when remote controller operation switch is turned on. (Operation lamp does not light up.)
Display appears but soon disappears even when remote controller is operated.
+Press the remote controller’s
LCD
P1 P2 P4 P5 P6 P8 P9 Fb
cannot be operated.
CHECK
Contents of trouble
Abnormality of room temperature thermistor Abnormality of pipe temperature thermistor/Liquid Abnormality of drain sensor/ Float switch connector open Drain overflow protection is working. Freezing/overheating protection is working. Abnormality of pipe temperature Abnormality of pipe temperature thermistor/Cond./Eva Abnormality of indoor controller board
OUTDOOR BOARD LED Display
< > indicates digital display.
After “startup” is displayed, only green lights up. <00> After “startup” is displayed, green(once) and red(once) blink alternately. <F1>
After “startup” is displayed, green(once) and red(twice) blink
alternately. <F3, F5, F9> After “startup” is displayed,
green(twice) and red(once) blink alternately. <EA. Eb>
After “startup” is displayed, only green lights up. <00>
After “startup” is displayed, only green lights up. <00>
• After power is turned on, “PLEASE WAIT” is displayed for 2 minutes during
• Incorrect connection of outdoor terminal block (L S1, S2, S3.)
• Outdoor unit’s protection device connector is open.
• Incorrect wiring between the indoor and outdoor unit (Polarity is wrong for S1, S2, S3.)
• Remote controller transmission wire is short.
• There is no outdoor unit of address 0. (Address is other than 0.)
• Remote controller transmission wire is open.
• After canceling function selection, operation is not possible for about 30 seconds. (Normal)
system startup. (Normal)
button twice to perform self-diagnosis. See the table below for the contents of LCD dis-
LCD
Malfunction outdoor unit
U1~UP
Malfunction
F3~F9 E0~E5
Remote controller transmitting error
E6~EF
Indoor/outdoor unit communication error No error history
---­No applied unit
FFFF
Forced compressor stop(due to water leakage abnormality)
PA
outdoor unit
Contents of trouble
See the table below for details of the LED display (LED 1, 2, 3) on the indoor controller board.
(microcomputer power supply)
LED1
(remote controller)
LED2
(indoor/outdoor communication)
LED3
Lits when power is supplied. Lits when power is supplied for wired remote controller. The indoor unit should be connected to the outdoor unit with address “0” setting.
Blinks when indoor and outdoor unit are communicating.
Cause
1, L2, L3 and
22
TEST RUN
TEST RUN
MODE
MODE
HEAT
FAN
VANE
,
ON/OFF
MODE
CHECK
TEST RUN
SET
TEST RUN
FAN
VANE
LOUVER
RESET
CLOCK
TEMP
AUTO STOP
AUTO START
h
min
Test run [for wireless remote controller]
Measure an impedance between the power supply terminal block on the outdoor unit and ground with a 500V Megger and check that it is equal to or greater than 1.0M.
Turn on the main power to the unit.
Press the
(Start this operation from the status of remote controller display turned off.)
and current operation mode are displayed.
A
Press the
check whether cool air is blown out from the unit.
Press the
check whether warm air is blown out from the unit.
Press the
from the unit.
Press the
properly.
Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver
while following steps to .
• It is not possible to run in FAN, DRY or AUTO mode.
button twice continuously.
( ) button to activate
( ) button to activate
COOL
mode, then
mode, then
button and check whether strong air is blown out
button and check whether the auto vane operates
23
10-3. HOW TO PROCEED "SELF-DIAGNOSIS"
10-3-1. When a Problem Occurs During Operation
If a problem occurs in the air conditioner, the indoor and outdoor units will stop, and the problem is shown in the remote controller display.
[CHECK] and the refrigerant address are displayed on the temperature display, and the error code and unit number are displayed alternately as shown below. (If the outdoor unit is malfunctioning, the unit number will be "00".)
In the case of group control, for which one remote controller controls multiple refrigerant systems, the refrigerant address and error code of the unit that first experienced trouble (i.e., the unit that transmitted the error code) will be displayed.
To clear the error code, press the button.
Error code (2 or 4 digits)
ON/OFF
(Alternating Display)
Address (3 digits) or unit number (2 digits)
When using remote-/local-controller combined operation, cancel the error code after turning off remote operation. During
central control by a MELANS controller, cancel the error code by pressing the
ON/OFF
button.
10-3-2. Self-Diagnosis During Maintenance or Service
Since each unit has a function that stores error codes, the latest check code can be recalled even if it is cancelled by the remote controller or power is turned off.
Check the error code history for each unit using the remote controller.
Switch to self-diagnosis mode.
Press the will change as shown below.
CHECK
button twice within 3 seconds. The display content
Unit number or refrigerant address to be diagnosed
Set the unit number or refrigerant address you want to diagnose.
Press the [TEMP] buttons ( and ) to select the desired number or address. The number (address) changes between [01] and [50] o r [00]
an d
[15].
The refrigerant address will begin to blink approximately 3 seconds after being selected and the self-diagnosis process will begin.
Display self-diagnosis results.
<When there is error code history>
(Alternating Display)
Error code (2 or 4 digits)
<When there is no error code history> <When there is no corresponding unit>
Address (3 digits) or unit number (2 digits)
Reset the error history.
Display the error history in the diagnosis result display screen (see step
).
24
CHECK
Press the
address or refrigerant address will blink.
Cancel self-diagnosis. Self-diagnosis can be cancelled by the following 2 methods.
Press the
Press the
ON/OFF
CHECK
ON/OFF
button twice within 3 seconds. The self-diagnosis
button twice within 3 seconds. Self-diagnosis will be cancelled and the screen will return to the previous state in effect before the
button. Self-diagnosis will be cancelled and the indoor unit will stop.
start of self-diagnosis.
When the error history is reset, the display will look like the one shown below. However, if you fail to reset the error history, the error content will be displayed again.
10-3-3. Remote Controller Diagnosis
If the air conditioner cannot be operated from the remote controller, diagnose the remote controller as explained below.
First, check that the power-on indicator is lit. If the correct voltage (DC12 V) is not supplied to the remote controller, the indicator will not light. If this occurs, check the remote controller's wiring and the indoor unit.
Power on indicator
Switch to the remote controller self-diagnosis mode.
Press the
will change as shown below.
CHECK
button for 5 seconds or more. The display content
Press the
FILTER
button to start self-diagnosis.
Remote controller self-diagnosis result
[When the remote controller is functioning correctly]
Check for other possible causes, as there is no problem with the remote controller.
[Where the remote controller is not defective, but cannot be operated.] (Error display 2) [E3], [6833] or [6832] blinks.
There might be noise or interference on the transmission path, or the indoor unit or other remote controllers are defective. Check the transmission path and other controllers.
© Transmission is not possible.
[When the remote controller malfunctions] (Error display 1) "NG" blinks. ©The remote controller's transmitting-receiv-
The remote controller must be replaced with a new one.
(Error display 3)
The number of data errors is the difference between the number of bits sent from the remote controller and the number actually transmitted through the transmission path. If such a problem is occurring, the transmitted data is affected by noise, etc. Check the transmission path.
ing circuit is defective.
"ERC" and the number of data errors are displayed. © Data error has occurred.
When the number of data errors is "02":
Transmission data from remote controller
Transmission data on transmission path
To cancel remote controller diagnosis
Press the approximately 30 seconds, the state in effect before the diagnosis will be restored.
button for 5 seconds or more. Remote controller diagnosis will be cancelled, "PLEASE WAIT" and operation lamp will blink. After
25
10-3-4. Malfunction-diagnosis method by wireless remote controller
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop.
<Malfunction-diagnosis method at maintenance service>
[Procedure]
CHECK display
ON/OFF button
CHECK button
ON/OFF
MODE
CHECK
TEST RUN
SET
CHECK
FAN
VANE
LOUVER
RESET
TEMP
AUTO STOP
AUTO START
CLOCK
h
min
Refrigerant address display
Temperature button
HOUR button
1. Press the CHECK button twice.
2. Press the temperature buttons.
3. Point the remote controller at the
sensor on the indoor unit and press the HOUR button.
• "CHECK" lights, and refrigerant address "00" blinks.
• Check that the remote controller's display has stopped before continuing.
• Select the refrigerant address of the indoor unit for the self-diagnosis. Note: Set refrigerant address using the outdoor unit’s DIP switch (SW1).
(For more information, see the outdoor unit installation manual.)
• If an air conditioner error occurs, the indoor unit's sensor emits an intermit­ tent buzzer sound, the operation lamp blinks, and the error code is output. (It takes 3 seconds at most for error code to appear.)
4. Point the remote controller at the
sensor on the indoor unit and press the ON/OFF button.
• The check mode is cancelled.
26
• Refer to the following tables for details on the check codes. [Output pattern A]
Beeper sounds
OPERATION INDICATOR lamp blink pattern
Beep
Self-check starts (Start signal received)
Beep Beep Beep Beep Beep Beep
1st2nd3
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “P5”)
rd
0.5 sec.
th
n
On
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
[Output pattern B]
Beeper sounds
OPERATION INDICATOR lamp blink pattern
Beep Beep Beep Beep Beep
1st2nd3
Off
Self-check starts (Start signal received)
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “U2”)
[Output pattern A] Errors detected by indoor unit
Wireless remote controller
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks Check code
(Number of times)
1P1
2
P2 Pipe (TH2) sensor error P9 Pipe (TH5) sensor error
3 E6,E7
Intake sensor error
Indoor/outdoor unit communication error
4 P4 Drain sensor error/Float switch connector open
5
P5 Drain pump error
PA Forced compressor stop(due to water leakage abnormality) 6 P6 Freezing/Overheating protection operation 7 EE Communication error between indoor and outdoor units 8 P8 Pipe temperature error 9 E4, E5 Remote controller signal receiving error
10 11
12 Fb Indoor unit control system error (memory error, etc.)
E0, E3
Remote controller transmission error
E1, E2 Remote controller control board error
nd
1st2
Off
Number of blinks/beeps in pattern indicates the check code in the following table
rd
th
n
On
0.5 sec.
· · · Repeated
Beep Beep
nd
1st2
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check code in the following table
· · · Repeated
Symptom Remark
As for indoor unit, refer to indoor unit's service manual.
[Output pattern B]
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks Check code
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote controller
Symptom Remark
(Number of times)
1
2 3 4
5
6
7 8 9
10
11
12 13 14
E9
UP U3,U4 UF U2
U1,Ud
U5 U8 U6 U7
U9,UH
– –
Others
*1 If the beeper does not sound again after the initial
the OPERATION INDICATOR lamp does not come on,
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
Compressor overcurrent interruption Open/short of outdoor unit thermistors Compressor overcurrent interruption (When compressor locked) Abnormal high discharging temperature/insufficient refrigerant Abnormal high pressure (63H worked)/Overheating
protection operation
Abnormal temperature of heatsink
Outdoor unit fan protection stop
Compressor overcurrent interruption/Abnormality of power module Abnormality of superheat due to low discharge temperature Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
– Other errors (Refer to the technical manual for the outdoor unit.)
2 beeps to confirm the self-check start signal was received and
there are no error records.
For details, check the LED display of the outdoor controller board.
*2 If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
27
10-4. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is turned on>
Error Code
Abnormal point and detection method
No voltage is supplied to terminal
block(TB1) of outdoor unit. a) Power supply breaker is
b) Contact failure or disconnec-
c) Open phase (L2 or N phase)
(Note 1) Refer to indoor unit section for code P and code E.
Case
Check following items.
a) Power supply breaker b), c) Connection of power supply terminal
turned off.
tion of power supply terminal
Judgment and action
block(TB1)
None
63L connector open
Abnormal if 63L connector circuit is open for 3 minutes continuously after power sup­ply.
F3
(5202)
63L: Low-pressure switch <RP250 only>
Electric power is not supplied to
outdoor controller circuit board. a) Disconnection of connector
(CNDC)
Disconnection of reactor
(ACL4)
Disconnection of outdoor noise
filter circuit board or parts fail­ure in outdoor noise filter circuit board
Defective outdoor controller
circuit board
Disconnection or contact failure
of 63L connector on outdoor controller circuit board.
Disconnection or contact failure
of 63L.
63L is working due to refriger-
ant leakage or defective parts.
Defective outdoor controller
circuit board.
Check connection of the connector (CNDC)
on the outdoor controller circuit board. Check connection of the connector CNDC on the outdoor noise filter circuit board. Refer to 10-9.
Check connection of reactor. (ACL4)
a) Check connection of outdoor noise filter
circuit board. b) Replace outdoor noise filter circuit board.
Refer to 10-9.
Replace controller board (When items above
are checked but the units cannot be repaired).
Check connection of 63L connector on
outdoor controller circuit board. Refer to 10-9.
Check the 63L side of connecting wire.
Check refrigerant pressure.
Charge additional refrigerant. Check continuity by tester. Replace the parts if the parts are defective.
Replace outdoor controller circuit board.
F5
(5201)
F9
(4119)
63H connector open
Abnormal if 63H connector circuit is open for 3 minutes continuously after power sup­ply. 63H: High-pressure switch
2 connector open
Abnormal if both 63H and 63L connector circuits are open for 3 minutes continuously after power supply.
63H: High-pressure switch 63L: Low-pressure switch <RP250 only>
Disconnection or contact failure
of 63H connector on outdoor controller circuit board
Disconnection or contact failure
of 63H
63H is working due to defective
parts.
Defective outdoor controller
circuit board
Disconnection or contact failure
of connector (63H,63L) on outdoor controller circuit board.
Disconnection or contact failure
of 63H, 63L.
63H and 63L are working due
to defective parts.
Defective outdoor controller
circuit board.
Check connection of 63H connector on
outdoor controller circuit board. Refer to 10-9.
Check the 63H side of connecting wire.
Check continuity by tester.
Replace the parts if the parts are defective.
Replace outdoor controller circuit board.
Check connection of connector(63H,63L) on
outdoor controller circuit board. Refer to 10-9.
Check the 63H and 63L side of connecting
wire.
Check continuity by tester.
Replace the parts if the parts are defective.
Replace outdoor controller circuit board.
28
Error Code
EA
(6844)
Eb
(6845)
Abnormal point and detection method
Indoor/outdoor unit connector miswiring, excessive number of units
1. Outdoor controller circuit board can automatically check the number of connected indoor units. Abnormal if the
number cannot be checked automati­cally due to miswiring of indoor/outdoor unit connecting wire and etc. after power is turned on for 4 minutes.
2. Abnormal if outdoor controller circuit
board recognizes excessive number of indoor units.
Miswiring of indoor/outdoor unit connecting wire (converse wiring or dis­connection)
Outdoor controller circuit board can automatically set the unit number of indoor units. Abnormal if the indoor unit number can­not be set within 4 minutes after power on because of miswiring (converse wiring or disconnection) of indoor/outdoor unit con­necting wire.
Case
Contact failure or miswiring of
indoor/outdoor unit connecting wire
Diameter or length of indoor/
outdoor unit connecting wire is out of specified capacity.
Excessive number of indoor
units are connected to 1 out­door unit.(5 units or more)
Defective transmitting receiving
circuit of outdoor controller circuit board
Defective transmitting receiving
circuit of indoor controller board
Defective indoor power board 2 or more outdoor units have
refrigerant address “0” . (In case of group control)
Noise has entered into power supply or indoor / outdoor unit connecting wire.
Contact failure or miswiring of
indoor/outdoor unit connecting wire
Diameter or length of indoor/
outdoor unit connecting wire is out of specified capacity.
Defective transmitting receiving
circuit of outdoor controller circuit board
Defective transmitting receiving
circuit of indoor controller board
Defective indoor power board 2 or more outdoor units have
refrigerant address “0”.
(In case of group control) Noise has entered into power
supply or indoor/outdoor unit connecting wire.
Judgment and action
Check disconnection or looseness or polar-
ity of indoor/outdoor unit connecting wire of indoor and outdoor units.
Check diameter and length of indoor/outdoor
unit connecting wire. Total wiring length: 80m (Including wiring connecting each indoor unit and between indoor and outdoor unit) Also check if the connection order of flat cable is S1, S2, S3.
Check the number of indoor units that are
connected to one outdoor unit. (If EA is detected.)
~ Turn the power off once, and on again to check. Replace outdoor controller circuit board, indoor controller board or indoor power board if abnormality occurs again.
Check if refrigerant addresses (SW1-3 to
SW1-6 on outdoor controller circuit board) are overlapping in case of group control system.
Check transmission path, and remove the
cause.
+ The descriptions above, -, are for EA, Eb
and EC.
EC
(6846)
Start-up time over
The unit cannot finish start-up process within 4 minutes after power on.
Contact failure of indoor/
outdoor unit connecting wire
Diameter or length of indoor/
outdoor unit connecting wire is out of specified capacity.
2 or more outdoor units have
refrigerant address “0” . (In case of group control)
Noise has entered into power
supply or indoor/outdoor unit connecting wire.
29
<Abnormalities detected while unit is operating>
Error Code
U1
(1302)
Abnormal point and detection method
High pressure (High-pressure switch 63H(RP200)/63H1 or 63H2(RP250) worked)
Abnormal if high-pressure switch 63H(RP200)/63H1 or 63H2(RP250) worked ( + ) during compressor operation. + 63H1: 4.15 MPa 63H, 63H2: 3.6 MPa
63H, 63H1, 63H2: High-pressure switch
Case
Short cycle of indoor unitClogged filter of indoor unitDecreased airflow caused by
dirt of indoor fan
Dirt of indoor heat exchangerLocked indoor fan motorMalfunction of indoor fan motorDefective operation of stop
valve (Not fully open)
Clogged or broken pipeLocked outdoor fan motor
Malfunction of outdoor fan
motor
Short cycle of outdoor unitDirt of outdoor heat exchangerDecreased airflow caused by
defective inspection of outside temperature thermistor (It detects lower temperature than actual temperature.)
Disconnection or contact failure
of connector (63H) on outdoor controller board
Disconnection or contact failure
of 63H connection
Defective outdoor controller
board
Defective action of linear
expansion valve
Malfunction of fan driving
circuit
Judgment and action
~Check indoor unit and repair defect.
Check if stop valve is fully open.
Check piping and repair defect.~ Check outdoor unit and repair defect.
Check the inspected temperature of outside
temperature thermistor on LED display. (SW2 on A-Control Service Tool : Refer to 10-10.)
~Turn the power off and check F5 is
displayed when the power is turned again. When F5 is displayed, refer to “Judgment and action” for F5.
Check linear expansion valve.
Refer to 10-7.
Replace outdoor controller board.
U2
(1102)
U3
(5104)
High discharging temperature
(1) Abnormal if discharge temperature ther-
mistor (TH4) exceeds 125or 110 continuously for 5 minutes. Abnormal if condenser/evaporator tem perature thermistor (TH5) exceeds 40 during defrosting and discharge temper­ature thermistor (TH4) exceeds 110
(2) Abnormal if discharge superheat
(Cooling: TH4 – TH5 / Heating: TH4 – TH6) exceeds 70 continuously for 10 minutes.
Open/short circuit of discharge temperature thermistor (TH4)
Abnormal if open (3 or less) or short (217 or more) is detected during compressor operation. (Detection is inoperative for 10 minutes of compressor starting process and for 10 minutes after and during defrosting.)
.
Overheated compressor opera-
tion caused by shortage of refrigerant
Defective operation of stop
-
valve
Defective thermistorDefective outdoor controller
board
Defective action of linear
expansion valve
Clogging with foreign objects in
refrigerant circuit
+Clogging occurs in the parts
which become below freez­ing point when water enters in refrigerant circuit.
Disconnection or contact
failure of connector (TH4) on the outdoor controller circuit board
Defective thermistor
Defective outdoor controller
circuit board
Check intake superheat.
Check leakage of refrigerant. Charge additional refrigerant.
Check if stop valve is fully open.
 Turn the power off and check if U3 is dis-
played when the power is turned on again. When U3 is displayed, refer to “Judgement and action” for U3.
Check linear expansion valve.
Refer to 10-7.
After recovering refrigerant, remove water
from entire refrigerant circuit under vacuum more than 1 hour.
Check connection of connector (TH4) on the
outdoor controller circuit board. Check breaking of the lead wire for thermistor (TH4). Refer to 10-9.
Check resistance value of thermistor (TH4) or
temperature by microcomputer. (Thermistor/TH4: Refer to 10-7.) (SW2 on A-Control Service Tool: Refer to 10-10.)
Replace outdoor controller board.
30
Loading...
+ 68 hidden pages