Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Store the piping to be used during installation
indoors and keep both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
In case of using the existing pipes for R22, be careful with
the followings.
· For RP4, 5 and 6, be sure to perform replacement opera tion before test run.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Keep the tools with care.
If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Flare tool
Electronic refrigerant
charging scale
Vacuum pump adaptor
Size adjustment gauge
Gauge manifold
Torque wrench
Gas leak detector
Charge hose
Tools for R410A
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
2-1. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R410A
[1] Cautions for service
(1) Perform service after collecting the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
3
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.Specifications
1Gauge manifold·Only for R410A
·Use the existing fitting
·Use high-tension side pressure of 5.3MPa·G or over.
2Charge hose·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
3Electronic scale
4Gas leak detector·Use the detector for R134a, R407C or R410A.
5Adaptor for reverse flow check·Attach on vacuum pump.
6Refrigerant charge base
7Refrigerant cylinder·Only for R410ATop of cylinder (Pink)
8Refrigerant recovery equipment
specifications
Cylinder with syphon
. (UNF1/2)
4
2-2. CHANGED POINT
Connecting a new air conditioner
1Flaring work should be done so that flare meets the dimension for R410A.
Use flare nut provided with indoor and outdoor unit.
2When using gas piping of [19.05mm for RP4, 5 or 6.
Make sure that DIP SW8-1 on outdoor unit controller board is set to ON.
WThis is to keep the pressure on pipes within permissible range.
●Use different diameter joint or adjust the piping size by brazing.
3When using pipes larger than specified size for RP1.6, 2, 2.5 or 3.
Make sure that DIP SW8-1 on outdoor unit controller board is set to ON.
W
This is to prevent oil flow ratio from lowering due to the decrease in flowing refrigerant.
●Use different diameter joint or adjust the piping size by brazing.
4When existing pipes are specified size.
The pipes can be reused referring to table 1 on page 18.
●Use different diameter joint or adjust the piping size by brazing.
★When using existing pipes for RP4, 5 and 6.
Make sure that DIP SW8-2 on outdoor unit controller board is set to ON and perform
replacement operation.
wChemical compounds containing chlorine left in existing pipes are collected by rep lace filter.
●The air conditioner automatically performs cooling operation through replace filter
for about 2 hours.
Measure the existing pipe thickness and check for damage.
Check if existing air conditioner can operate.
Existing air conditioner can
operate.
Disconnect existing air conditioner from piping.
Existing pipes can be reused.
In case the unit is RP1.6, 2,
2.5 ro 3 which utilizes AB oil.
In case the unit is RP4, 5
or 6 which utilize ester oil.
Perform cooling operation
for about 30 minutes and
then do a pump down work.
Use a refrigerant recovery
equipment to collect the refrigerant.
Check the oil condition
when collecting the refrigerant.
Disconnect existing air conditioner
from pipes and clean pipes using
cleaning device.
Existing air conditioner
cannot operate.
The existing pipe thickness meets specifications and the pipes are not damaged.
The existing pipe thickness does not meet
specifications or the pipes are damaged.
Oil is clean.
Connect a new air conditioner.Connect a new air conditioner.
Perform replacement operation.
Oil is dirty.
Attach a filter drier.
When the compressor bearings
are glazed, rotation scratches
are present, or the compressor
breaks down, iron particles or
oil deterioration will blacken the
oil.
·When performing replacement operation, make sure that DIP SW8-2 on outdoor unit controller board is
set to ON.
wChemical compounds containing chlorine left in existing pipes are collected by replace filter.
●The air conditioner automatically performs cooling operation through replace filter for about 2 hours.
Existing pipes cannot be
reused. Use new pipes.
• Precautions when reusing existing R22 refrigerant pipes
(1) Flowchart
Bender
Pipe cutter
Welder and nitrogen gas cylinder
Refrigerant charging scale
Vacuum gauge or thermistor vacuum gauge and
vacuum valve
Charging cylinder
Air purge and refrigerant charge
Operation check and the two above
Gas leak check
Collection of refrigerant
Refrigerant charge
Apply to flared section
Prevent compressor malfunction
when charging refrigerant by
spraying liquid refrigerant
Prevent gas from blowing out
when detaching charge hose
Vacuum drying and air
purge
Flaring work of piping
Bend the pipes
Cut the pipes
Weld the pipes
Charge refrigerant
Check the degree of vacuum. (Vacuum
valve prevents back flow of oil and refrigerant to thermistor vacuum gauge)
Charge refrigerant
Tool exclusive for R410A
Tool exclusive for R410A
Tool for HFC refrigerant
Tool exclusive for R410A
Tool exclusive for R410A
Ester oil and alkylbenzene
oil (minimum amount)
Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can
be used if equipped with adopter for reverse flow check
Tools for other refrigerants
can be used by adjusting
flaring dimension
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants
can be used
Tool exclusive for R410A
Tools and materialsUseR410A toolsCan R22 tools be used?
(Usable if equipped
with adopter for rever se flow)
(Usable by adjusting
flaring dimension)
Can R407C tools be used?
Ester oil:
Alkylbenzene oil: minimum amount
(Usable if equipped
with adopter for rever se flow)
(Usable by adjusting
flaring dimension)
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.)
: Tools for other refrigerants can be used under certain conditions.
: Tools for other refrigerants can be used.
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410Ais same
as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working
pressure of R410A is 1.6 time higher than that of R22, their sizes of flared sections and flare nuts are different.
1Thickness of pipes
Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness
shown below. (Never use pipes of 0.7mm or below.)
2Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that,
R410A is a refrigerant, which has higher risk of leakage because of its working pressure higher than that of other refrigerants. Therefore, to enhance airtightness and intensity, flare cutting dimension of copper pipe for R410A have been specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also
have partly been changed to increase intensity as shown below. Set copper pipe correctly referring to copper pipe flaring
dimensions for R410A below. For 1/2” and 5/8”, the dimension B changes.
Use torque wrench corresponding to each dimension.
Dimension A
3Tools for R410A (The following table shows whether conventional tools can be used or not.)
6
Dimension B
3COMBINATION OF INDOOR AND OUTDOOR UNITS
Heat pump type
Outdoor unit
PUHZ-RP
PEAD-RP·EA.UK
PEAD-RP·EA1.UK
PLA-RP·AA.UK
PLA-RP·AA1.UK
PEAD-RP·GA.UK
PLA-RP·AA
PLA-RP·AA1
—
—
OC293
REVISED EDITION-B
OC297
REVISED EDITION-D
PKA-RP·GAL
OC301
REVISED EDITION-A
PKA-RP·FAL
OC305
PCA-RP·GA
OC311
Indoor unit
Service
Manual No.
Service Ref.
45
Heat pump
without
electric heater
VHA
VHA
1
VHA
VHA1
YHA
VHA
VHA1
YHA
VHA
VHA1
YHA
6
3
22.5
VHAVHAVHA
VHA
1
1.6
——
—
—
—
—
—
————
———
4PART NAMES AND FUNCTIONS
CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT.
(Max.30m(PUHZ-RP1.6~RP6))
The refrigerant circuit with LEV(Linear Expansion Valve) and power receiver always control the optimal refrigerant
level regardless of the length (30m max. and 5m min.) of piping. The additional refrigerant charging work during
installation often causes problems. Heretofore it is completely eliminated. This unique system improves the quality
and reliability of the work done.It also helps to speed up the installation time.
7
5SPECIFICATIONS
Service Ref.
Function
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Crankcase heater
Heat exchanger
FanFan(drive) o No.
OUTDOOR UNIT
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
REFRIGERANT PIPING
Running current
Model
Motor output
Starter type
Protection devices
Fan motor output
Airflow
Charge
Oil (Model)
K
/min(CFM
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
PUHZ-RP1.6VHA
PUHZ-RP2VHA
COOLING
MODE
HEATING
44
SPL(dB)
46
LINE
MICROPHONE
1m
1.5m
UNIT
GROUND
PUHZ-RP2.5VHA, VHA1
PUHZ-RP3VHA, VHA1
90
80
MODE
COOLING
HEATING
SPL(dB)
47
48
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
63125250500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
13
7OUTLINES AND DIMENSIONS
Service panel
for charge plug
w 1 In the place where short cycle tends to occur, cooling and heating
capacity and power consumption might get lowered 10%. Air outlet
guide (optional PAC-SG58SG) will help them improve.
w 2 If air discharges to the wall, the surface might get stained.
Minimum installation space for outdoor unit
100 mm or more as long as
no obstacle is placed on the
rear and light-and-left sides
of the unit.
2 sides should be open in
the right, left and rear side.
w 2
w 1
100 mm or more
500 mm or more
Basically open
100 mm or more
Free space around the outdoor unit
(basic example)
350 mm or more
w 1
Air intake
Air discharge
Air intake
Connection for
gas pipe
Service port
Connection for
liquid pipe
Service panel
4-10 o 21 oval hole
(M10 foundation bolt)
[33 drain hole
[33 drain hole
43.6
152
155
400
347.5
45.4
365
330
300
40
Handle for
moving
600
10
300
150
287.5
Installation bolt pitch: 500
800
69
35
43
183
90
155
23
32.5
18
1. FOUNDATION BOLTS
2. PIPING-WIRING DIRECTION
Piping and wiring connection can
be made from the rear direction only.
3. ATTACHING THE CONDUIT
In order to attach the conduit, it is
necessary to fix the metal plate with
2 screws to the back panel. Procure
the metal plate and make screw holes
locally. It is recommended to use the
metal plate shown below. Align the
metal plate to the marks on the unit
and attach it.
<Foundation bolt height>
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts, washer and nut must
be purchased locally.)
18 or below
40
20
60
80
w Conduit hole
w The position and the size of
conduit hole depend on the
conduit to be used.
Holes for metal plate fixing screw
w The size of hole depends on the
screw to be used.
FOUNDATION
PUHZ-RP1.6VHA
PUHZ-RP2VHA
Unit : mm15Unit : mm
14
PUHZ-RP2.5VHA
Over 10mm
FRE
E
Over 500mm
Over 100mm
Over 10mm
PUHZ-RP2.5VHA1
PUHZ-RP3VHA
PUHZ-RP3VHA1
2
1
Handle for moving
Service panel
Handle for moving
Handle for moving
Rear Air Intake
Air intake
Rear piping cover
Front piping cover
Side Air Intake
Handle for moving
Piping Knock-Out Hole Details
Example of Notes
• • •
Refrigerant GAS pipe connction (FLARE)[15.88 (5/8F)
Connector <Connect to Optional M-NET Adapter Board>
Connector <Connect to Optional M-NET Adapter Board>
CN3S
Connector < Connection for Option>
CNDM
Connector < Connection for Option>
CN51
Connector < Connection for Option>
SS
Connector <Connection for Option>
LEV-A
(WHT)
LEV
4 56321
31
321
3
321
321
3 1
31
2121
21
13
LEV-B
(RED)
LEV
4 56321
CNVMNT
(WHT)
CN4
(WHT)
CNMNT
(WHT)
CNM
CN3S
(WHT)
CNDM
(WHT)
CN51
(WHT)
321
321321
4 5321
4 5321
CN5
(WHT)
1 23
LED2
SW1
SW11
SW12
LED3
LED4
TB7
LED1
LED5
4 5321
21
CND
(WHT)
CN2M
(WHT)
M-NET
A B S
M-NET ADAPTER (OPTION)
SW7
SW6
SW1
SW9
SW4
SW10
SWPSW5SW8
CN31
w1
w1
1110 121314
65 7 8 91 2 3 4
65 71 2 3 4
65 71 2 3 4
1 2
3 4
2 1
LED1
LED2
TH7/6
(RED)
CN3N
63L
(RED)
63H
(YLW)
TH3
(WHT)
CNS
(WHT)
13
21S4
(GRN)
TH4
(WHT)
TH7 TH6 TH3 TH4
63H 63L
43212121
4 5671
4 5671
MF1
TRANS
MF2
CNF1
(WHT)
CNF2
(WHT)
13
CNDC
(PNK)
CN2
(WHT)
CNAC
(WHT)
21S4
13
SV2
(BLU)
X55
X51
X52
13
SS
(WHT)
SV
+
-
-
+
ACL1
ACL2
ACL3
ACL4
CN7
(WHT)
CN2
(WHT)
CT2
TB-P2
CB1 CB2CK
TB-C1
L3-OU
L2-OU
L1-OU
L3-A2
L2-A2
L1-A2
L1-A1
L1-IN
N-IN
CK-OU
TB-N1
TB-W
BLK
WHT
RED
BLK
WHT
RED
BLK
BLU
WHT
RED
BLK
BLU
WHT
RED
TB-V
TB-U
TB-L3
TB-L2
TB-L1
CT1
W
V
U
MC
CN4
(WHT)
RED
ORN
CNAC1
(WHT)
CN7
(WHT)
CN5
(RED)
CNCT
(RED)
CNAC2
(RED)
CNL
(BLU)
31
CNDC
(PNK)
RS
P.B.
C.B.
N.F.
CONV.B.
LO1
GD1
GD2
LO2
LO3
NO
LI1
LI2
LI3
NI
L1
L2
L3
N
TB1
NO FUSE
BREAKER
TB2
S1
S2
S3
POWER SUPPLY
3N~
400V
50Hz
INDOOR
UNIT
12
F2
F5
F1
F3
F4
31
MODELS
RP4Y
SW6SW10
RP5Y
RP6Y
<w1 MODEL SELECT>
ON
OFF
123456
ON
OFF
12
ON
OFF
12
ON
OFF
12
ON
OFF
123456
ON
OFF
123456
PUHZ-RP5YHA
PUHZ-RP6YHA
19
9WIRING SPECIFICATIONS
Indoor unit – Outdoor unit wiring for PUHZ-RP1.6-6VHA and PUHZ-RP1.6-6VHA1
The cable shall not be lighter than design 245 IEC or 227 IEC.
The cable length may vary depending on the condition of installation, humidity or materials, etc.
Cross section
of cable
Wire size
2
)
(mm
Number
of wires
PolarityL(m) ✽5
Round
2.5
3
Clockwise : S1-S2-S3
Flat
2.5
3
Not applicable
(Because center wire has no cover finish)
Flat
1.5
4
From left to right : S1-Open-S2-S3
Round
2.5
4
Clockwise : S1-S2-S3-Open
Connect S1 and S3 to the opposite angle
✽1 : In case that cable with stripe of yellow and green is available.
✽2 : In the flat cables are connected as this picture, they can be used up to 30m.
(30)
✽1
Not
applicable
✽2
(18)
✽3
30
✽4
(3C Flat cable ✕ 2)
S1 S2 S3
2
✽3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5mm
.
✽4 : In case of regular polarity connection (S1-S2-S3).
✽5 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, humidity or materials, etc.
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate
connections).
Intermediate connections can lead to communication errors if water enters the cables and causes
insufficient insulation to ground or a poor electrical contact at the intermediate connection point.
(If an intermediate connection is necessary, be sure to take measures to prevent water from entering
the cables.)
20
Indoor unit – Outdoor unit wiring for PUHZ-RP4, 5, 6YHA
The cable shall not be lighter than design 245 IEC or 227 IEC.
The cable length may depending on the condition of installation, humidity or materials, etc.
Indoor unit-Outdoor unit
Max. 45m
3 o 1.5 (polar)
1 o Min. 1.5
If 1.5E used, Max. 45m.
If 2.5E used, Max. 50m.
If 2.5E used and S3 separated, Max. 80m.
Max. 50m
3 o 2.5 (polar)
1 o Min. 2.5
Max. 80m
3 o 2.5 (polar) and S3 separated
1 o Min. 2.5
Indoor unit-Outdoor unit earth
Wire No. o Size (E)
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate
connections).
Intermediate connections can lead to communication errors if water enters the cables and causes
insufficient insulation to ground or a poor electrical contact at the intermediate connection point.
(If an intermediate connection is necessary, be sure to take measures to prevent water from entering
the cables.)
For 4, 5, 6Y application, use shield wire. (For EMC DIRECTIVE)
The shield part must be grounded with the indoor unit or the outdoor unit, not with both.
When the shield line is not used, several dB is exceeded with 30 ~ 40 MHz .
(There is a possibility to be used by the wireless for the ship etc. though it is not used for
radio and TV.)
<Table 2> Additional refrigerant charging amount for pipe of standard diameter
<Table 3>
Outdoor unit
Permitted
pipe length
Additional refrigerant charging amount for pipe
length exceeding 30 m (kg)
PUHZ-RP1.6, 2VHA
PUHZ-RP2.5, 3VHA, 2.5, 3VHA
1
PUHZ-RP4-6VHA, RP4-6VHA1, RP4-6YHA
Outdoor unit
Number of
bends
Height
difference
50m or less
50m or less
75m or less
Permitted
pipe length
50m or less
50m or less
75m or less
75m or less
2.1
3.1
5.1
4.6
11 — 20m 21 — 30m
2.3
3.3
5.3
4.8
2.5
3.5
5.5
5.0
31 — 40m
2.7
(0.2)
4.1
(0.6)
6.1
(0.6)
5.6
(0.6)
2.9
(0.4)
4.7
(1.2)
6.7
(1.2)
6.2
(1.2)
—
—
—
—
7.3
(1.8)
6.8
(1.8)
—
—
—
—
7.9
(2.4)
7.4
(2.4)
41 — 50m 51 — 60m 61 — 75m
Recharge refrigerant amount or additional amount in parentheses
PUHZ-RP1.6, 2VHA
PUHZ-RP2.5, 3VHA
PUHZ-RP2.5, 3VHA
1
PUHZ-RP4-6VHA
PUHZ-RP4-6VHA
1
PUHZ-RP4-6YHA
Liquid
pipe
(mm)
Gas
pipe
(mm)
[6.35
[9.52[12.7
[9.52
OD
Thick-
ness
OD
Thick-
ness
RP1.6
RP2
RP2.5
RP3
RP4
RP5
RP6
t0.8
[12.7
t0.8
[15.88
t1.0
[12.7
t0.8
[15.88
t1.0
[19.05
t1.0
[15.88
t1.0
[19.05
t1.0
t0.8
t0.8
: Standard piping
: It can be used, however, additional refrigerant charge is required when the pipe length exceeds 20m. Refer to <table 4>.
: It cannot be used.
: It can be used.
: It can be used, however, the capacity is lowered. Refer to (c) Capacity correction.
<Table 1> Pipe length for 1:1 system
*1: Set DIP SW8-1 on outdoor unit controller board to ON.
*2: The maximum length is 50 m in case of using existing pipes.
[Marks in the table above]
50m
t0.8
30m30m
10m30m30m
50m
30m
50m
50m
10m
50m
(*1)
75m
(*2)
50m
10m30m30m10m50m
75m
(*2)
75m
(*2)
50m
(*1)
30m
(*1)
50m
(*1)
50m
(*1)
50m
(*1)
50m
(*1)
50m10m30m30m30m
(*1)
<Table 4>
Required additional charge when the pipe size is larger than the standard diameter
[9.52
[12.7
[12.7
RP1.6, 2
RP2.5, 3
RP4-6
Liquid pipe dia
Chargeless
30m
30m
50m
60 g per 1 m longer than 20 m
100 g per 1 m longer than 20 m
100 g per 1 m longer than 20 m
20m
20m
20m
Max. pipe length
Refrigerant amount to be added
The height difference between indoor and outdoor unit should be kept within 30 m for all models.
(1) 1:1 system
(a) Maximum pipe length
(b) Adjusting the amount of refrigerant
• Additional refrigerant charge is not necessary for the pipe length up to 30 m. When the pipe length exceeds 30 m or service
(refrigerant replacement) is performed, charge proper amount of refrigerant for each pipe length referring to table below.
Use refrigerant R410A. Use charge hose exclusive for R410A.
• When charging additional refrigerant, charge the refrigerant from low-pressure side of the port valve using a safety charger.
• Make sure that air purge for this unit at refrigerant replacement is performed from both high-pressure check valve and ser-
vice port. If air purge is performed only from one of them, air in not purged enough.
• When replacing refrigerant, charge the refrigerant from service port. When charged refrigerant is less than specified amount,
charge the refrigerant again from low pressure side of the port valve using a safety charger.
• Tighten the service port cap (nut) of stop valve firmly. The tightening torque is 12 to 16 N·m. (to prevent slow-leak)
• Check additional refrigerant charging amount referring to table 4 when liquid pipe is one size larger than standard diameter,
and table 2 when the pipe is standard diameter.
24
(c) Capacity correction
Cooling
Heating
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below. When the diameter of gas pipe is one size smaller than standard diameter, cooling capacity is lowered comparing to the standard diameter. The lowered capacity can be obtained by referring to capacity curves for gas pipe which is
one size smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m)
11
Capacity curves for PUHZ-RP • HA model <Standard size>
100
95
90
85
80
Capacity ratio [%]
75
Note: The permitted pipe length is up to 55m for RP1.6, 2, 2.5, 3 model.
70
5101520253035404550556065707580
Corrected pipe length
22
Capacity curve for PUHZ-RP1.6, 2 models
<When gas pipe is one size smaller than standard size>
100
Cooling RP1.6, 2.5 models
Cooling RP3 model
Heating RP1.6, 2, 2.5,
3, 4, 5 and 6 models
(Up to 55m for RP1.6,
2, 2.5, 3 model)
Cooling RP2, 4 models
Cooling RP5 model
Cooling RP6 model
Heating RP1.6, RP2
95
90
Cooling RP2
Capacity ratio [%]
85
Cooling RP1.6
80
510152025303540455055
Corrected pipe length
25
33
Capacity curve for PUHZ-RP2.5, 3 models
<When gas pipe is one size smaller than standard size>
100
95
90
Capacity ratio [%]
85
80
510152025303540455055
Heating RP2.5, RP3
Cooling RP2.5
Cooling RP3
Corrected pipe length
44
When gas pipe is one size larger than standard size for PUHZ-RP4, 5 and 6.
1 Capacity can be obtained by referring to capacity curves of standard size.
26
1. Refrigerant collecting (pump down)
TEST RUN
OFF
12
ON
<SW4>
A B
C D
A Stop C operation
B Cooling D Heating
Perform the following procedures to collect the refrigerant when moving the indoor unit or the outdoor unit.
1Before collecting the refrigerant, first make sure that the all of the SW5 DIP switches for function changes on the control
board of the outdoor unit are set to OFF. If all of the SW5 switches are not set to OFF, record the settings and then set all of
the switches to OFF. Now, start refrigerant collecting operation. After moving the unit to a new location and completing the
test run, set the SW5 switches to the previously recorded settings.
2Turn on the power supply (circuit breaker).
wWhen power is supplied, make sure that “CENTRALLY CONTROLLED” is not displayed on the remote controller. If
“CENTRALLY CONTROLLED” is displayed, the refrigerant collecting (pump down) cannot be completed normally.
3After the liquid stop valve is closed, set the SWP switch on the control board of the outdoor unit to ON. The compressor
(outdoor unit) and ventilators (indoor and outdoor units) start operating and refrigerant collecting operation begins. LED1 and
LED2 on the control board of the outdoor unit are lit.
wSet the SWP switch (push-button type) to ON in order to perform refrigerant collecting operation only when the unit is
stopped. However, refrigerant collecting operation cannot be performed until compressor stops even if the unit is stopped.
Wait three minutes until compressor stops and set the SWP switch to ON again.
4Because the unit automatically stops in about two to three minutes after the refrigerant collecting operation (LED1 is not lit
and LED2 is lit), be sure to quickly close the gas stop valve.
wIn case the outdoor unit is stopped when LED1 is lit and LED2 is not lit, open the liquid stop valve completely, and then
repeat step 3 three minutes later.
wIf the refrigerant collecting operation has been completed normally (LED1 is not lit and LED2 is lit), the unit will remain
stopped until the power supply is turned off.
5Turn off the power supply (circuit breaker.)
2. Unit replacement operation
When reusing the existing pipes that carried R22 refrigerant for the RP4, RP5 and RP6 models, replacement operation
must be performed before performing a test run.
1If new pipes are used, these procedures are not necessary.
2If existing pipes that carried R22 refrigerant are used for the RP3 model, these procedures are not necessary. (The replace-
ment operation cannot be performed.)
3During replacement operation, “C5” is displayed on “A-Control Service Tool(PAC-SK52ST)”. (This is applied to only RP4,
RP5 and RP6 models.)
• Replacement operation procedures
1Turn on the power supply.
2Set DIP switch SW8-2 on the control board of the outdoor unit to ON to start replacement operation.
• The replacement operation is performed using the cooling system. Cool air will flow from the indoor unit during the replacement operation.
• During the replacement operation, is displayed on the remote controller and LED1 (green) and LED2 (red) on the
control board of the outdoor unit flash together.
3Replacement operation requires at least two hours to complete.
• After setting switch SW8-2 to ON, the unit automatically stops after two hours.
• Replacement operation can be performed repeatedly by setting switch SW8-2 from OFF to ON. Make sure to perform the
operation more than 2 hours. (If the operation is performed less than 2 hours, the existing pipes cannot be cleaned
enough and the unit may be damaged.)
• If replacement operation is performed over 2 hours, this action is recorded into nonvolatile memory of control board.
4Set switch SW8-2 to OFF. (Replacement operation is completed.)
wThe unit can be operated normally by remote controller even if SW8-2 remains ON.
wIf the indoor temperature is less than 15:, the compressor will operate intermittently but the unit is not faulty.
3. Start and finish of test run
• Operation from the indoor unit
Execute the test run using the installation manual for the indoor unit.
• Operation from the outdoor unit
By using the DIP switch SW4 on the control board of outdoor unit, test run can be started and finished, and its operation
mode (cooling/heating) can be set up.
1Set the operation mode (cooling/heating) using SW4-2.
2Turn on SW4-1 to start test run with the operation mode set by SW4-2.
3Turn off SW4-1 to finish the test run.
• There may be a faint knocking sound around the machine room after power is supplied, but this is
no problem with product because the linear expansion pipe is just moving to adjust opening pulse.
• There may be a knocking sound around the machine room for several seconds after compressor
starts operating, but this is no problem with product because the check valve, itself, generates the
sound because pressure difference is small in the refrigerant circuit.
Note:
The operation mode cannot be changed by SW4-2 during test run. (To change test run mode, stop the unit by SW4-1,
change the operation mode and restart the test run by SW4-1.)
27
11TROUBLESHOOTING
Unit conditions at service
Error code
Actions to be taken for service (summary)
The inferior phenomenon is
reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according
to “11-4. Self-diagnosis action table”.
Conduct trouble shooting and ascertain the cause of the
inferior phenomenon according to “11-5. Troubleshooting
by inferior phenomena”.
The inferior phenomenon is
not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
inferior phenomenon occurred, matters related to wiring
and etc.
2Reset error code logs and restart the unit after finishing
service.
3There is no abnormality concerning of parts such as
electrical component, controller board, remote controller
and etc.
1Re-check the abnormal symptom.
2Conduct trouble shooting and ascertain the cause of the
inferior phenomenon according to “11-5. Troubleshooting
by inferior phenomena”.
3Continue to operate unit for the time being if the cause
is not ascertained.
4There is no abnormality concerning of parts such as
electrical component, controller board, remote controller
and etc.
11-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit.
Actions to be taken for service, which depends on whether or not the inferior phenomenon is reoccurring at service, are summarized in the table below. Check the contents below before investigating details.
28
11-2. CHECK POINT UNDER TEST RUN
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN
FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY
DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
TEST RUN button
TEST RUN display
LIQUID PIPE TEMPERATURE display
(MA remote controller)
(1) Before test run
• After installation of indoor and outdoor units, piping work and electric wiring work, re-check that there is no refrigerant leak-
age, loosened connections and incorrect polarity.
• Measure impedance between the ground and the power supply terminal block(L, N) on the outdoor unit by 500V Merger and
check that it is 1.0M" or over.
wDon’t use 500V Merger to indoor/outdoor connecting wire terminal block(S1, S2, S3) and remote controller terminal block
(1, 2). This may cause malfunction.
• Make sure that test run switch (SW4) is set to OFF before turning on power supply.
• Make sure that all of the SW5 switches for function changes on the control board of the outdoor unit are set to OFF. If all of
the SW5 switches are not set to OFF, record the settings and then set all of the switches to OFF. And perform emergency
operation. After finishing emergency operation, set the SW5 switches to the recorded settings.
• Turn on power supply twelve hours before test run in order to protect compressor.
• For specific models which requires higher ceiling settings or auto-recovery feature from power failure, make proper changes
of settings referring to the description of “Selection of Functions through Remote Controller”.
Make sure to read operation manual before test run. (Especially items to secure safety.)
11-2-1. Test run by remote controller
Operating procedures
1. Turn on the main power supply.
2. Press TEST RUN button twice.
3. Press OPERATION SWITCH
button.
4. Press AIR DIRECTION button.
5. Check the outdoor unit fan for
correct running.
While the room temperature display on the remote
controller is “H0”, the remote controller is disabled.
Wait until “H0” disappears before using remote controller.
“H0” appears for about 2 minutes after power supply is
turned on. w1
The TEST RUN appears on the screen.
Cooling mode:
Heating mode: Check if warm air blows. (It takes a little
while until warm air blows.)
Check for correct motion of auto-vanes.
The outdoor unit features automatic capacity control to
provide optimum fan speeds. Therefore, the fan keeps
running at a low speed to meet the current outside air
condition unless it exceeds its available maximum power.
Then, in actuality, the fan may stop or run in the reverse
direction depending on the outside air, but this does not
mean malfunction.
Check if cool air blows and water is drained.
6. Press the ON/OFF button to reset the test run in progress.
7. Turn off the main power supply.
• In case of test run, the OFF timer will be activated, and the test run will automatically stop after two hours.
• The room temperature display section shows the pipe temperature of indoor units during the test run.
• Check that all the indoor units are running properly in case of simultaneous twin and triple operation. Malfunctions may not
be displayed regardless of incorrect wiring.
w1 After turning on the power supply, the system will go into startup mode, “H0” will blink on the display section of the room
temperature, and lamp(red) of the remote controller will flash.
As to INDOOR BOARD LED, LED1 and LED2 will be lit up in case the address is 0, or turned off in case the address is not
0. LED3 will blink.
As to OUTDOOR BOARD LED, LED1(green) and LED2(red) will light up. (After the startup mode of the system finishes,
LED2(red) will be turned off.)
In case OUTDOOR BOARD LED is digital display, — and —will be displayed alternately every second.
• If one of the above operations doesn’t function correctly, the causes written below should be considered. Find causes from
the symptoms.
The below symptoms are under test run mode. “startup” in the table means the display status of w1 written above.
Symptoms in test run mode
Remote Controller Display
Remote controller displays “H0”, and
cannot be operated.
After power is turned on, “H0” is displayed
for 3 minutes, then error code is
displayed.
No display appears even when remote
controller operation switch is turned on.
(Operation lamp does not light up.)
Display appears but soon disappears
even when remote controller is operated.
OUTDOOR BOARD LED Display
< > indicates digital display.
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed,
green(once) and red(once) blink
alternately. <F1>
After “startup” is displayed,
green(once) and red(twice) blink
alternately. <F3, F4, F9>
After “startup” is displayed,
green(twice) and red(once) blink
alternately. <EA. Eb>
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed, only
green lights up. <00>
29
Cause
• After power is turned on, “H0” is displayed for 2 minutes during
system startup. (Normal)
• Incorrect connection of outdoor terminal block (L, N and S1,
S2, S3.)
• Outdoor unit’s safeguard installation connector is open.
• Incorrect wiring between the indoor and outdoor unit (Polarity
is wrong for S1, S2, S3.)
• Remote controller transmission wire short.
• There is no outdoor unit of address 0.
(Address is other than 0.)
• Remote controller transmission wire burnout.
• After canceling function selection, operation is not possible for
about 30 seconds. (Normal)
wPress the remote controller’s CHECK button twice to perform self-diagnosis. See the table below for the
LCD
Contents of inferior phenomena
P1
P2
P4
P5
P6
P8
P9
Abnormality of room temperature thermistor
Abnormality of pipe temperature thermistor/Liquid
Abnormality of drain sensor
Drain overflow protection is working.
Freezing/overheating protection is working.
Abnormality of pipe temperature
Abnormality of pipe temperature thermistor/Cond./Eva
LCD
Contents of inferior phenomena
U1~UP
F3~F9
E0~E5
E6~EF
----
FFFF
Malfunction outdoor unit
Malfunction
outdoor unit
Remote controller transmitting error
Indoor/outdoor unit communication error
No error history
No applied unit
LED1
(microcomputer power supply)
LED2
(remote controller)
LED3
(indoor/outdoor communication)
Lits when power is supplied.
Remote controller
The indoor unit should be connected to the outdoor unit with address “0” setting.
Flash when indoor and outdoor unit are communicating.
ON
SW4
1 2
A Stop
B Cooling
C Operation
D Heating
A
C D
B
(Factory setting)
contents of LCD display.
See the table below for details of the LED display (LED 1, 2, 3) on the indoor controller board.
11-2-2. Test run by outdoor unit SW4
The setting of test run (ON/OFF) and its operation mode (cooling/heating) can be set by SW4 on the controller board of outdoor unit. Check that SW5-1 is set to OFF before performing test run. If SW5-1 is set to ON, turn it OFF and then perform test
run. After finishing test run, set SW5-1 back to ON.
1Set operation mode(cooling or heating) by SW4-2.
2Start test run by setting SW4-1 to ON ( ) with the indicated operation mode of SW4-2.
3Finish test run by setting SW4-1 to OFF ( ).
• Operation mode cannot be changed by SW4-2 during test run.
Stop test run to change operation mode by SW4-1, and restart test run by SW4-1 after
the mode is changed.
• Test run automatically stops 2 hours later by 2-hour OFF timer function.
• Test run can be performed by the remote controller.
• The remote controller display of test run by outdoor unit is the same as that of test run by
remote controller.
30
Loading...
+ 92 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.