Mitsubishi PUHZ-P200YHA(3), PUHZ-P250YHA(3) Service Manual

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SERVICE MANUAL
R410A
Outdoor unit [model names]
[Service Ref.]
PUHZ-P200YHA PUHZ-P250YHA PUHZ-P200YHA3 PUHZ-P250YHA3
February 2009
No.OCH424
REVISED EDITION-A
Revision:
PUHZ-P200/250YHA3
are added in REVISED EITION-A.
Some descriptions have
been modified.
Please void OCH424.
Note:
This manual describes only
service data of the outdoor units.
RoHS compliant products
have <G> mark on the spec name plate.
CONTENTS
1. TECHNICAL CHANGES
2. REFERENCE MANUAL
3. SAFETY PRECAUTION
4. FEATURES
5. SPECIFICATIONS
6. DATA
7. OUTLINES AND DIMENSIONS
8. WIRING DIAGRAM
9. WIRING SPECIFICATIONS
10.
REFRIGERANT SYSTEM DIAGRAM
11. TROUBLESHOOTING
12. FUNCTION SETTING
13.
MONITORING THE OPERATION DATA BY THE REMOTE CONTROLLER
14. EASY MAINTENANCE FUNCTION
15. DISASSEMBLY PROCEDURE
......................................................
...............................................................
.................................
..................................
..................................
...........................................
....................
.......................................
..........................
...............
...................................
....................................
..........
76
..............
.....................
89
PARTS CATALOG (OCB424)
10
11
12 17 19 69
86
2 2 3 6 7
8
1
TECHNICAL CHANGES
PUHZ-P200YHA PUHZ-P200YHA3 PUHZ-P250YHA PUHZ-P200YHA3
• OUTDOOR CONTROLLER BOARD (C.B.) has been changed. (S/W has been changed: Corresponding to the additional combination between PKA-RPHAL/KAL, PCA-RPKA and PEAD-RP•JA(L))
2
REFERENCE MANUAL
INDOOR UNIT’S SERVICE MANUAL
Model name Service Ref.
PLA-RP35/50/60/71/100/125/140BA PLA-RP71/100/125/140BA2
PCA-RP50/60/71/100/125/140GA PCA-RP50/60/71/100/125/140GA(#1) PCA-RP50GA2 PCA-RP50GA2(#1)
PCA-RP71/125HA
PKA-RP35/50GAL PKA-RP35/50GAL(#1)
PKA-RP60/71/100FAL PKA-RP60/71/100FAL(#1) PKA-RP50FAL2 PKA-RP50FAL2(#1)
PEAD-RP50/60/71/125/140EA PEAD-RP35/100EA2
PEAD-RP60/71/100GA
PLA-RP35/50/60/71/100/125/140BA(#2).UK PLA-RP35/50/60/71BA PLA-RP71/100/125BA2.UK PLA-RP140BA2R1.UK
PCA-RP71/125HA(#1)
PEAD-RP50/60/71/125/140EA(#1).UK PEAD-RP35/100EA2(#1).UK
PEAD-RP60/71/100GA(#1).UK
1.UK
Service
Manual No.
OCH412 OCB412
OC328
OC329
OC330
OC331
HWE0521
HWE0506
PEA-RP200/250/400/500GA
PKA-RP60/71/100KAL
PCA-RP50/60/71/100/125/140KA
PKA-RP35/50HAL
PEA-RP200/250/400/500GA.TH-AF PEA-RP200/250GA.TH-AFMF
PKA-RP60/71/100KAL.TH
PCA-RP50/60/71/100/125/140KA
PKA-RP35/50HAL
2
HWE0708A
OCH452
OCB452
OCH454
OCB454 OCH453
OCB453
3
SAFETY PRECAUTION
3-1. ALWAYS OBSERVE FOR SAFETY
Before obtaining access to terminal, all supply circuits must be disconnected.
3-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R410A
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with the followings.
· Be sure to clean the pipes and make sure that the insides of the pipes are clean.
· Change flare nut to the one provided with this product. Use a newly flared pipe.
· Avoid using thin pipes.
Make sure that the inside and outside of refrige­rant piping is clean and it has no contamination such as sulfur hazardous for use, oxides, dirt, shaving particles, etc. In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterio­ration of refrigerant oil etc.
Store the piping to be used indoors during installation and both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrige­rant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Tools for R410A Gauge manifold Charge hose
Gas leak detector
Torque wrench
Flare tool Size adjustment gauge Vacuum pump adaptor
Electronic refrigerant charging scale
Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigerant oil applied to flares and flange connections.
If large amount of mineral oil enters, that can cause deterio­ration of refrigerant oil etc.
Charge refrigerant from liquid phase of gas cylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera­nt will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
3
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously. Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Tool name Specifications
1 Gauge manifold · Only for R410A
· Use the existing fitting
· Use high-tension side pressure of 5.3MPa·G or over.
2 Charge hose · Only for R410A
· Use pressure performance of 5.09MPa·G or over.
3 Electronic scale
4 Gas leak detector · Use the detector for R134a, R407C or R410A.
5 Adaptor for reverse flow check · Attach on vacuum pump.
6 Refrigerant charge base
7 Refrigerant cylinder · Only for R410A · Top of cylinder (Pink)
· Cylinder with syphon
8 Refrigerant recovery equipment
specifications
. (UNF1/2)
4
Cautions for refrigerant piping work
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working pressure of R410A is 1.6 time higher than that of R22, their sizes of flared sections and flare nuts are different.
1Thickness of pipes Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness shown below. (Never use pipes of 0.7mm or below.)
Diagram below: Piping diameter and thickness
Nominal
dimensions(inch)
1/4 3/8 1/2 5/8 3/4
Outside
diameter
6.35
9.52
12.70
15.88
19.05
(mm)
Thickness
R410A R22
0.8
0.8
0.8
1.0
(mm)
0.8
0.8
0.8
1.0
1.0
2Dimensions of flare cutting and flare nut The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that, R410A is a refrigerant, which has higher risk of leakage because its working pressure is higher than that of other refriger­ ants. Therefore, to enhance airtightness and intensity, flare cutting dimension of copper pipe for R410A have been speci­ fied separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also have partly been changed to increase intensity as shown below. Set copper pipe correctly referring to copper pipe flaring dimensions for R410A below. For 1/2 and 5/8 inch, the dimension B changes. Use torque wrench corresponding to each dimension.
Dimension A
Flare cutting dimensions
Nominal
dimensions(inch)
1/4 3/8 1/2 5/8 3/4
Outside
diameter
6.35
9.52
12.70
15.88
19.05
Dimension A
R410A R22
9.1
13.2
16.6
19.7
24.0
(mm)
+0
( )
-0.4
9.0
13.0
16.2
19.4
23.3
Flare nut dimensions
Nominal
dimensions(inch)
1/4 3/8 1/2 5/8 3/4
Outside
diameter
6.35
9.52
12.70
15.88
19.05
3Tools for R410A (The following table shows whether conventional tools can be used or not.)
Tools and materials Use R410A tools Can R22 tools be used? Gauge manifold
Charge hose Gas leak detector
Refrigerant recovery equipment Refrigerant cylinder Applied oil
Safety charger
Charge valve Vacuum pump
Flare tool
Bender Pipe cutter Welder and nitrogen gas cylinder Refrigerant charging scale
Vacuum gauge or thermis­tor vacuum gauge and vacuum valve Charging cylinder
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.) : Tools for other refrigerants can be used under certain conditions. : Tools for other refrigerants can be used.
Air purge, refrigerant charge and Operation check Gas leak check Refrigerant recovery Refrigerant charge Apply to flared section
Prevent compressor malfunction when charging refrigerant by
spraying liquid refrigerant Prevent gas from blowing out
when detaching charge hose Vacuum drying and air purge
Flaring work of piping
Bend the pipes Cut the pipes Weld the pipes Charge refrigerant Check the degree of vacuum. (Vacuum
valve prevents back flow of oil and refri­gerant to thermistor vacuum gauge) Refrigerant charge
Tool exclusive for R410A Tool exclusive for R410A Tool for HFC refrigerant Tool exclusive for R410A Tool exclusive for R410A
Ester oil, ether oil and alkylbenzene
Tool exclusive for R410A
Tool exclusive for R410A Tools for other refrigerants can
be used if equipped with adop­ter for reverse flow check Tools for other refrigerants
can be used by adjusting flaring dimension Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used
Tool exclusive for R410A
oil
(minimum amount)
(Usable if equipped
with adopter for rever­ se flow)
(Usable by adjusting flaring dimension)
Dimension B
(mm)
Dimension B
R410A R22
17.0
22.0
26.0
29.0
36.0
Can R407C tools be used?
Ester oil, ether oil: Alkylbenzene oil: minimum amount
(Usable if equipped
with adopter for rever­ se flow)
(Usable by adjusting
flaring dimension)
17.0
22.0
24.0
27.0
36.0
5
4
CHARGELESS SYSTEM PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT. (Max.30m)
The refrigerant circuit with LEV (Linear Expansion Valve) and Accumulator always control the optimal refrigerant level regardless of the length (30m max. and 5m min.) of piping. The additional refrigerant charging work during installation often causes problems. It is completely eliminated by chargeless system. This unique system improves the quality and reliabil­ity of the work done. It also helps to speed up the installation time.
FEATURES
6
5
SPECIFICATIONS
Service Ref.
Mode
Power supply (phase, cycle, voltage) Running current Max. current External finish Refrigerant control Compressor Model
Motor output Starter type Protection devices
Crankcase heater Heat exchanger Fan Fan(drive) % No. Fan motor output
OUTDOOR UNIT
Airflow Defrost method Noise level
Dimensions
Weight Refrigerant Charge Oil (Model) Pipe size O.D.
Connection method Between the indoor &
outdoor unit
REFRIGERANT PIPING
*
Cooling Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
mm(in.) mm(in.) mm(in.)
kg(lbs) kg(lbs)
mm(in.) mm(in.)
A A
kW
W
kW
/min(L/s
dB dB
L
PUHZ-P200YHA PUHZ-P200YHA3
Cooling
9.47
)
126(278)
5.8(12.8)
9.52(3/8)
25.4(1)
Heating
3 phase 50Hz, 400V
9.88
19
YHA: ANB52FFJMT or ANB52FFPMT
4.7
59 59
Munsell 3Y 7.8/1.1
Linear Expansion Valve
Hermetic
YHA3: ANB52FFPMT
Line start
HP switch
Discharge thermo
Plate fin coil
Propeller fan % 2
0.150 + 0.150 130(2170)
Reverse cycle
950(37-3/8)
330 + 30(13+1-3/16)
1,350(53-1/8)
R410A
2.30(FV50S)
Flared
Flared & Brazing
Max. 30m Max. 70m
PUHZ-P250YHA PUHZ-P250YHA3
Cooling
11.0
YHA: 133(294)/ YHA3: 135(298)
7.1(15.7)
12.7(1/2)
25.4(1)
Heating
12.0
21
5.5
59 59
7
6
DATA
6-1. REFILLING REFRIGERANT CHARGE (R410A : kg)
Service Ref.
PUHZ-P200YHA PUHZ-P200YHA3
PUHZ-P250YHA PUHZ-P250YHA3
10m
4.8
5.9
20m
5.3
6.5
6-2. COMPRESSOR TECHNICAL DATA
Unit
Compressor model
Winding
Resistance
( )
U-V
U-W
W-V
PUHZ-P200, 250YHA PUHZ-P200, 250YHA3
ANB52FFJMT ANB52FFPMT
0.30
0.30
0.30
Piping length (one way)
30m
5.8
7.1
40m
6.7
8.3
For pipe longer than 30m, addi­tional charge is required.
(at 20°C)
ANB52FFPMT
0.30
0.30
0.30
50m
7.6
9.5
60m
8.5
10.7
70m
9.4
11.9
Factory
charged
5.8
7.1
6-3. NOISE CRITERION CURVES
MICROPHONE
1m
UNIT
1.5m
GROUND
PUHZ-P200YHA PUHZ-P250YHA PUHZ-P200YHA3 PUHZ-P250YHA3
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
NOISE
10
63 125 250 500 1000 2000 4000 8000
SPL(dB)
MODE
COOLING
HEATING
BAND CENTER FREQUENCIES, Hz
LINE 59 59
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
8
6-4. STANDARD OPERATION DATA
Representative matching
Mode
Capacty
Total
Input
Indoor unit
Phase , Hz Voltage Input Current
Outdoor unit
Electrical circuitRefrigerant circuitIndoor side
Phase , Hz Voltage Current Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
side
Outdoor
SHF
BF
D.B.
W.B.
D.B. D.B.
W.B.
W
kW
V
kW
A
V A
MPa
(kgf/%)
MPa
(kgf/%)
°C °C °C
m °C °C °C °C °C
PEA-RP250GAPEA-RP200GA
HeatingCooling
19,000 22,400 22,000 27,000
7.21 7.36 8.44 8.47
PEA-RP200GA
PUHZ-P200YHA
PUHZ-P200YHA3
2.96
(30.2)
0.87
(8.87)
0.81
3, 50
400
1.00
400
9.889.47
2.59
(26.4)
0.64
(6.53)
43.249.7
-0.88.0
7.57.5 2027 1519
35.717.1 735 624
— —
PEA-RP250GA
3, 50
400
1.18
2.302.00
PUHZ-P250YHA
PUHZ-P250YHA3
3, 503, 50
400
2.94
(30.0)
0.86
(8.75)
0.86
0.150.18
HeatingCooling
12.011.0
2.67
(27.2)
0.62
(6.32)
74.074.873.775.6
45.149.6
-2.37.1
7.57.5 2027 1519
39.115.4
— —
735 624
The unit of pressure has been changed to MPa based on international SI system. The conversion factor is: 1(MPa)=10.2(kgf/cm²)
9
Rear piping cover
Front piping cover
Side Air Intake
Handle for moving
Piping Knockout Hole Details
637323
5527
92
65
4045
Power supply wiring hole
(2-:27Knockout)
Rear trunking hole
(Knockout)
Rear piping hole
(Knockout)
:92
922723
6373
4075
92
5519
Power supply wiring hole
(2-:27Knockout)
Right trunking hole
(Knockout)
Right piping hole
(Knockout)
:92
6373
23
5527
40 45
65
92
Power supply wiring hole
(2-:27Knockout)
Front trunking hole
(Knockout)
Front piping hole
(Knockout)
:92
Over
Over
Over
Over
Less than
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
4 PIPING-WIRING DIRECTIONS
3 FOUNDATION BOLTS2 SERVICE SPACE
1 FREE SPACE (Around the unit)
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
<Foundation bolt height>
Dimensions of space needed
for service access are
shown in the below diagram.
The diagram below shows a basic
example.
Explantion of particular details are
given in the installation manuals etc.
30
FOUNDATION
10
500
500
150
Service space
FREE
Over 10mm
Over 10mm
Over 150mm
Ove
r 1000mm
53
40560
70
175600175
33030
37028 19
417
60 37
2-12%36 oval holes
(Foundation Bolt M10)
2-U Shaped notched holes
(foundation Bolt M10)
Side Air Intake
Rear Air Intake
Air Discharge
Installation Feet
999 995
*1 A
*2 339
950
322
23
371
635
1350
*1 439
Handle for moving
Handle for moving
Terminal Connections
Left···Power supply wiring
Right···Indoor/Outdoor wiring
Service Panel
(
Earth terminal
Brazing
)
PUHZ-P250YHA
PUHZ-P250YHA3
PUHZ-P200YHA
PUHZ-P200YHA3
:9.52
(3/8 inch)
:12.7
(1/2 inch)
421
A
447
· · · ·Refrigerant GAS pipe connction (FLARE):19.05(3/4 inch)
· · · ·Refrigerant LIQUID pipe connection (FLARE) *1· · · ·Indication of STOP VALVE connection location
*2· · · ·Refrigerant GAS PIPE connention(BRAZING) O.D:25.4
Example of Notes
14514514522030
81
219
71
71
Drain hole
(5-:33)
Bottom piping hole
(Knockout)
Side Air Intake
Air Intake
Rear Air Intake
Handle for moving
Handle for moving
7 OUTLINES AND DIMENSIONS
Unit : mm
10
8 WIRING DIAGRAM
PUHZ-P200YHA PUHZ-P250YHA PUHZ-P200YHA3 PUHZ-P250YHA3
[LEGEND]
SYMBOL TB1 TB2 Terminal Block<Indoor/Outdoor> MC MF1,MF2 21S4 63H TH3 TH4 TH6 TH7 LEV-A ACL4 DCL CB1,CB2 RS FUSE1, FUSE2 CY1,CY2 P.B.
Terminal Block<Power Supply> Motor for Compressor
Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch
Thermistor<Outdoor Pipe>
Thermistor<Discharge> Thermistor<Outdoor 2-Phase Pipe> Thermistor<Outdoor> Electronic Expansion Valve
Reactor Reactor Main Smoothing Capacitor Rush Current Protect Resistor
Fuse< Capacitor
Power Circuit Board Connection Terminal<U/V/W -Phase>
SC-U/V/W
C. B.
1
MF1
MS
3~
1
MF2
MS
3~
CNS
(WHT)
31
CY2
CY1
TB2
S1
INDOOR UNIT
S2 S3
NAME SYMBOL NAME SYMBOL NAME
T15AL250V>
TH7TH6 TH3 TH4
tt t t
CNF1
BRN
ORN
7
(WHT)
CNF2
7
(WHT)
3
1
2
CNDC (PNK)
WHT
FUSE1
WHT
YLW
TRANS
CNAC (WHT)
21
43
REDRED
FUSE2
412121 TH7/6 (RED)
TH3
(WHT)
1
7
2
2
RS
RED
TH4
(WHT)
(WHT)
F3
F4
CN2
TB-L1/L2/L3 TB-P1 TB-P2 TB-C1 TB-N1 X52A
N.F.
LI1/ LI2/LI3/NI LO1/ LO2/LO3 GD1,GD2
C.B.
SW1 SW4
SW5 SW6 SW7 SW8 SW9
63H
31
63H
(YLW)
7
7
P. B .
7
CN2
(WHT)
1 2
CN4
(WHT)
1 2
CN5
(RED)
1
X52A
BLK
BLK
TB-P1
DCL
Connection Terminal<L1/L2/L3-Power supply>
Connection Terminal Connection Terminal
Connection Terminal
Connection Terminal
52C Relay
Noise Filter Circuit Board Connection Terminal< Connection Terminal< Connection Terminal<Ground>
Controller Circuit Board Switch<Forced Defrost, Defect History Record Reset, Refrigerant Address> Switch<Test Operation> Switch<Function Switch> Switch<Model Select> Switch<Function Setup> Switch<Function Setup> Switch
LED1
LED2
21S4
TB-P2
RED
L1/L2/L3/NI-Power supply> L1/L2/L3-Power supply>
LEV-A
M
35
61
CNVMNT
LEV-A
(WHT)
(WHT)
CNM
(WHT)
CN4
(WHT)
12
2
X52
21S4
(GRN)
TB-C1 TB-N1
WHT
CB1 CB2
31
51
CNMNT
(WHT)
141
1313
SC-W SC-V SC-U
TB-L3 TB-L2 TB-L1
BLK
SW5SW8SW4
SWP
X51
SS
(WHT)
+1+1
SW6SW1
CN31
BLK WHT RED
SWP CN31 LED1,LED2 F3,F4 SS CNM CNMNT
CNVMNT
CNDM CN3S
CN51 X51,X52
SW7
SW9
131315
CN3S
(WHT)
(WHT)
CNDM
CN51
(WHT)
BLK
W
WHT
V
RED
U
5
+1 MODEL SELECT
MODEL
+2 SW5 -1 to 5 : Function Switch
MC MS
3~
Switch<Pump Down> Connector<Emergency Operation> LED<Operation Inspection Indicators>
Fuse< T6.3AL250V>
Connector<Connection for Option> Connector<A-Control Service Inspection Kit> Connector <Connected to Optional M-NET Adapter Board> Connector <Connected to Optional M-NET Adapter Board> Connector < Connected for Option (Contact Input)> Connector<Connection for Option> Connector<Connection for Option> Relay
When M-NET adapter is connected
5
SW1
CN5
(WHT)
1
LED2 LED3 LED4
M-NET SUBSTRATE
2 1
CN2M
(WHT)
(WHT)
LED1
LED5
ABS
3
TB7
M-NET
SW6
ON
200Y
OFF
12345678
ON
250Y
OFF
12345678
SW11
SW12
CND
31
ON OFF
ON OFF
SW5-6 +2
123456
123456
POWER SUPPLY 3N~ 400V 50Hz
BREAKER
TB1
2
N. F.
CNAC1
(WHT)
31
LI 1
RED
L1 L2 L3
N
WHT
BLK
BLU
GRN/YLW
LI 2
LI 3
UU
U
NI
U
U
GD2GD1
BLK
CNDC
(PNK)
BLK
CNCT (RED)
31
2
WHT
CNAC2
(RED)
3112
LO 1
RED
LO 2
WHT
LO3
BLK
M-NET ADAPTER
SYMBOL
TB7
Terminal Block(M-NET connection)
CN5
Connector<Transmission>
CND
Connector<Power Supply>
U
13
CNL
(BLU)
ACL4
WHT
Connector<M-NET communication>
CN2M SW1
Switch<Status of communication>
SW11
Switch<Address setting:1st digit>
SW12
Switch<Address setting:2nd digit>
LED1
LED<Power Supply:DC5V>
LED2
LED<Connection to Outdoor Unit>
LED3
LED<Transmission:Sending>
LED4
LED<Transmission:Receiving>
LED5
LED<Power Supply:DC12V>
NAME
11
9 WIRING SPECIFICATIONS
9-1. FIELD ELECTRICAL WIRING (power wiring specifications)
P200, P250
Outdoor unit model P200, 250 Outdoor unit Power supply Outdoor unit input capacity *1 Main switch (Breaker)
Wiring
Wire No. %
size(mm²)
Outdoor unit power supply 5 % Min. 4 Indoor unit-Outdoor unit *2 Cable length 50 m : 3 % 4 (Polar)/Cable length 80 m : 3 % 6 (Polar) Indoor unit-Outdoor unit earth 1 % Min. 2.5 Remote controller-Indoor unit *3 2 % 0.3 (Non-polar) Outdoor unit L1-N, L2-N, L3-N AC 230 V
Circuit rating
Indoor unit-Outdoor unit S1-S2 *4 AC 230 V Indoor unit-Outdoor unit S2-S3 *4 DC 24 V Remote controller-Indoor unit *4 DC 12 V
*1 A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV). *2 Max. 80 m Total Max. including all indoor/indoor connection is 80 m. Use one cable for S1 and S2 and another for S3 as shown in the picture. Max. 50m Total Max. for PEA-200, 250, 400, 500 Wiring size 3%1.5 (Polar) *3 The 10 m wire is attached in the remote controller accessory. *4 The figures are NOT against the ground. S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulated by the transformer or other device.
Caution: Be sure to install N-line. Without N-line, it could damage the unit.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and Indoor unit/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed fexible cord. (Design 60245 IEC 57)
3. Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied.
Phase Frequency & Voltage
400V 3 phase
3N~(3ph 4-wires), 50 Hz,
400 V
32 A
Isolator
A-Control
Outdoor Unit
S1
S2
S3
3 poles isolator
S1
S2
S3
A-Control
Indoor Unit
Warning: In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use
Synchronized twin and triple system Electrical wiring
• Synchronized twin • Synchronized triple
Outdoor
Unit power supply
Earth leakage breaker wiring circuit breaker or
isolating switch
Outdoor unit
unit
L1 L2 L
3
N
Indoor/outdoor unit connection cable
S1 S2 S3
Indoor unit
S1 S2 S3
1
Remote controller
2
Indoor unit
1 2
S1 S2 S3
Unit power supply
Earth leakage breaker wiring circuit breaker or
isolating switch
Outdoor unit
L1 L2 L
3
N
Indoor/outdoor connection cable
S1 S2 S3
Indoor unit
S1 S2 S3
1 2
Remote controller
Indoor unit
1 2
S1 S2 S3
Indoor unit
1 2
S1 S2 S3
12
1:1 System (Indoor : PEA-200, 250) 1:2 System (Indoor : PEA-400, 500)
Indoor unit
L1 L2 L3
N
S1 S2 S3
Outdoor unit No.1
1
Remote controller
2
supply
Unit power
Unit
power supply
Earth leakage breaker wiring circuit breaker or
isolating switch
Unit power
supply
L1 L2
L3
N
Indoor/outdoor unit connection cable
S1 S2 S3
Outdoor unit No.2
1
L L2
L3
N
Indoor/outdoor unit connection cable
S1 S2 S3
Indoor unit
L1 L2 L3
N
S1 S2 S3
TB4-1
TB4-2
S1 S2 S3
1 2
Unit power
supply
Earth leakage breaker wiring circuit breaker or
isolating switch
Outdoor unit
1
L L2
L3
N
Indoor/outdoor unit connection
cable S1 S2 S3
9-2. SEPARATE INDOOR UNIT/ OUTDOOR UNIT POWER SUPPLIES
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Simultaneous twin/triple/four system
<For models without heater>
The optional indoor power supply terminal kit is required.
*

L
   
N
S1 S2 S3
L
N
S1 S2
S3
1
2
L
N
S1

S2
S3
1 2
L N
S1 S2 S3
1 2
L
N
S1 S2 S3
1 2
Outdoor unit power supply
Earth leakage breaker
Wiring circuit breaker or isolating switch
Outdoor unit
Indoor unit/outdoor unit connecting cales
Remote controller
Indoor unit
Option
Indoor unit power supply
Indoor unit earth
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
If the indoor and outdoor units have separate power supplies, refer to the table below. If the optional indoor power supply terminal kit is used, change the indoor unit electrical box wiring referring to the figure in the right and the DIP switch settings of the outdoor unit control board.
Indoor unit specifications Indoor power supply terminal kit (option) Indoor unit electrical box connector con­nection change Label affixed near each wiring diagram for the indoor and outdoor units Outdoor unit DIP switch settings (when using separate indoor unit/outdoor unit power supplies only)
ON OFF
Required Required
Required
3
1 2 (SW8)
Electric heater (For models with heater)
L
N
S1 S2 S3
Indoor unit power supplied from outdoor unit (when shipped from factory)
Connectors (connections when shipped from the factory are for indoor unit power supplied from outdoor unit.)
BLUE
BLUE
YELLOW
YELLOW
ORANGE
CND
CND
Indoor unit
control board
Electric heater (For models with heater)
N
L
Set the SW8-3 to ON.
* There are 3 types of labels (Labels A, B, and C). Affix the appropriate labels to
the units according to the wiring method.
Indoor unit model Indoor unit power supply Indoor unit input capacity Main switch (Breaker)
Indoor unit power supply Indoor unit power supply earth
)
2
Indoor unit-Outdoor unit
(mm
Wiring
Indoor unit-Outdoor unit earth
Wire No. % size
Remote controller-Indoor unit
Indoor unit L-N *4
Indoor unit-Outdoor unit S1-S2 *4 Indoor unit-Outdoor unit S2-S3 *4
rating
Circuit
Remote controller-Indoor unit *4
*1
*2
*3
RP35~140
~/N (single), 50 Hz, 230 V
16 A
2% Min. 1.5 1% Min. 1.5 2% Min. 0.3
2 % 0.3 (Non-polar)
AC 230 V
– DC24 V DC12 V
*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV). The breaker shall be provided to ensure disconnection of all active phase conductor of the supply. *2. Max. 120 m *3. The 10 m wire is attached in the remote controller accessory. Max. 500 m *4. The figures are NOT always against the ground.
S1 S2 S3
Separate indoor unit/outdoor unit power supplies
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cables and indoor unit/outdoor unit connecting cables shall not be lighter than polychloroprene sheathed flexible cable. (Design 60245 IEC 57)
3. Install an earth longer than other cables.
13
Remote controller
If the indoor and outdoor units have separate power supplies, change the connections of the connectors as shown in the following figure.
YELLOW
BLUE
YELLOW
BLUE
CND
Unit power supply
Connectors
ORANGE CND
Indoor unit
control board
9-3. INDOOR – OUTDOOR CONNECTING CABLE
WIRING SPECIFICATIONS FOR 220-240 V 50 Hz (INDOOR-OUTDOOR CONNECTING CABLE)
Cross section of cable Wire size (mm2) Number of wires Polarity L (m)*6
Round
Flat
Flat
Round
2.5 3
2.5 3
1.5 4
2.5 4
Clockwise : S1-S2-S3 * Pay attention to stripe of yellow and green.
Not applicable (Because center wire has no cover finish)
From left to right : S1-Open-S2-S3
Clockwise : S1-S2-S3-Open *Connect S1 and S3 to the opposite angle.
Not applicable
(30)
*2
*5
(18)
*3
(30)
*4
*1 : Power supply cords of appliances shall not be lighter than design 60245 IEC or
227 IEC. *2 : In case that cable with stripe of yellow and green is available. *3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5 mm. *4 : In case of regular polarity connection (S1-S2-S3). *5 : In the flat cables are connected as this picture, they can be used up to 30 m.
2
Indoor/Outdoor separate power supply
Indoor unit-Outdoor unit Indoor unit-Outdoor unit earth
*6 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, Humidity or materials, etc.
Wire No. % Size ($)
Max. 120m
2 % Min. 0.3
(3C Flat cable × 2)
+ The optional indoor power supply terminal kit is necessary.
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections). Intermediate connections can lead to communication errors if water enters the cables and causes insufficient insulation to earth or a poor electrical contact at the intermediate connection point.
14
9-4. M-NET WIRING METHOD
(Points to notice) (1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from
making an influence on the signal communication. Place them at intervals of more than 5cm. Do not put them in the same
conduit tube. (2) Terminal block (TB7) for transmission wires should never be connected to 220~240V power supply. If it is connected, electronic parts on M-NET P.C. board may burn out. (3) Use 2-core x 1.25mm² shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be sent or
received normally if different types of transmission wires are put together in the same multi-conductor cable. Never do this
because this may cause a malfunction.
Group remote controller
It would be ok if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Earth only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise. “Ed” error will appear on the LED display of outdoor unit. “0403” error will appear on the central-control remote controller.
M-NET transmission wire
Power supply unit for transmission wire
A-control remote controller
Bad example (Multi spot earthing of shield wire)
×
Central remote controller
Power supply appliance
Refrigerant address 00
M-NET address 01
M-NET type outdoor unit
M-NET type outdoor unit
A-control remote controller
Refrigerant address 00
M-NET address 02
M-NET type outdoor unit
Refrigerant address 00
M-NET address 03
A-control remote controller
Good example 1 (Single spot earthing of shield wire)
Central remote controller
M-NET transmission wire
Good example 2 (Single spot earthing of shield wire)
Central remote controller
M-NET transmission wire
If there are more than 2 earthing spots on the shield wire, noise may enter into the shield wire because the earth wire and
shield wire form 1 circuit and the electric potential difference occurs due to the impedance difference among earthing spots.
In case of single spot earthing, noise does not enter into the shield wire because the earth wire and shield wire do not form
1 circuit.
To avoid communication errors caused by noise, make sure to observe the single spot earthing method described in the
installation manual.
Power supply appliance
Power supply appliance
M-NET type outdoor unit
M-NET type outdoor unit
M-NET type outdoor unit
M-NET type outdoor unit
M-NET type outdoor unit
M-NET type outdoor unit
15
 M-NET wiring
(1) Use 2-core x 1.25mm² shield wire for electric wires. (Excluding the case connecting to system controller.) (2) Connect the wire to the M-NET terminal block. Connect one core of the
M-NET terminal block
Earth wire
transmission wire (non-polar) to M1 terminal and the other to M2. Peel the shield wire, twist the shield part to a string and connect it to S terminal. (3) In the system which several outdoor units are being connected, the terminal (M1, M2, S) on M-NET terminal block should be individually wired to the other
M1 M2 S
Transmission
wire
Shield part
outdoor unit’s terminal, i.e. M1 to M1, M2 to M2 and S to S. In this case, choose one of those outdoor units and drive a
screw to fix an earth wire on the plate as shown on the right figure.
9-4-1. M-NET address setting
In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to CITY MULTI system, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as that of the indoor unit in CITY MULTI system), and the address number should be consecutively set in a same group.
Address number can be set by using rotary switches (SW11 for ones digit and SW12 for tens digit), which is located on the M-NET board of outdoor unit. (Initial setting: all addresses are set to “0”.)
<Setting example>
M-NET Address No.
SW11
Switng setting
ones digit
SW12 tens digit
12
3
3
4
4
2
2
5
1
0
9
2
1
0
9
5
1
6
6
0
7
7
9
8
8
3
3
4
4
2
5
5
1
6
6
0
7
7
9
8
8
50
3
4
2
5
1
6
0
7
9
8
~
3
4
2
5
1
6
0
7
9
8
9-4-2. Refrigerant address setting
In case of multiple grouping system (multiple refrigerant circuits in one group), indoor units should be connected by remote controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to “00” if the group set­ting is not conducted. Set the refrigerant address by using DIP SW1-3 to -6 on the outdoor controller board. [Initial setting: all switches are OFF. (All refrigerant addresses are “00”.)]
Refrigerant address
ON
OFF
1
ON
OFF
1
ON
OFF
1
3
4
5
2
6
0
ON
OFF
1
3
4
5
2
6
8
ON
OFF
1
3
4
5
2
6
1
ON
OFF
1
3
4
5
2
6
9
ON
OFF
1
3
4
5
2
6
2
ON
OFF
1
3
4
5
2
6
10
ON
OFF
3
4
5
2
6
3
ON
OFF
3
4
5
2
6
11
ON
OFF
1
2
1
2
1
3
4
5
6
4
ON
OFF
1
3
4
5
6
12
ON
OFF
1
3
4
5
2
6
5
ON
OFF
1
3
4
5
2
6
13
ON
OFF
1
3
4
2
6
3
4
2
14
3
5
5
4
5
2
6
OFF
6
6
7
ON
1
3
4
5
2
6
15
9-4-3. Regulations in address settings
In case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above sec­tion. Set the lowest number in the group for the outdoor unit whose refrigerant address is “00” as its M-NET address.
Group A Group B Group C
System controller
Power supply unit for transmission wire
Refrigerant address 00
M-NET address 01
A-control remote controller
w Refrigerant addresses can be overlapped if they are in the different group.
Group A Group B
System controller
Power supply unit for transmission wire
Refrigerant address 00
M-NET address 01
A-control remote controller
Refrigerant address 00
M-NET address 02
A-control remote controller
Refrigerant address 01
M-NET address 02
Refrigerant address 01
M-NET address 03
TB5
TB5
A-control remote controller
Refrigerant address 00
M-NET address 04
Refrigerant address 00
M-NET address 04
A-control remote controller
Refrigerant address 01
M-NET address 03
Refrigerant address 02
M-NET address 05
w In group B, M-NET address of the outdoor unit whose refrigerant address is “00” is not set to the minimum in the group. As
“3” is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address in the group for the outdoor unit whose refrigerant address is “00”.
16
10 REFRIGERANT SYSTEM DIAGRAM
PUHZ-P200YHA PUHZ-P250YHA PUHZ-P200YHA3 PUHZ-P250YHA3
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant GAS pipe :25.4(:1 inch)
Refrigerant LIQUID pipe P200 : :9.52(:3/8 inch) P250 : :12.7(:1/2 inch)
Ball valve
Strainer
Accumulator
Stop valve (with service port)
Service port
(check)
(#50)
Strainer (#40)
4-way valve
Strainer (#100)
Strainer (#100)
Service port
(check)
High pressure protect switch
Muffler
Thermistor (TH4)
Compressor
Linear expansion valve
Strainer (#100)
Outdoor heat exchanger
Thermistor (TH7)
Thermistor (TH6)
Thermistor (TH3)
Distributor
17
1. Refrigerant recovering (pump down)
Perform the following procedures to recover refrigerant when moving the indoor unit or the outdoor unit. 1Turn on the power supply (circuit breaker). wWhen power is supplied, make sure that “CENTRALLY CONTROLLED” is not displayed on the remote controller. If “CENTRALLY CONTROLLED” is displayed, the refrigerant recovering (pump down) cannot be completed normally. 2After the liquid stop valve is closed, set the SWP switch on the control board of the outdoor unit to ON. The compressor (outdoor unit) and fan (indoor and outdoor units) start operating and refrigerant recovering operation begins. LED1 and LED2 on the control board of the outdoor unit are lit. wSet the SWP switch (push-button type) to ON in order to perform refrigerant recovering operation only when the unit is stopped. However, refrigerant recovering operation cannot be performed until compressor stops even if the unit is stopped. Wait for 3 minutes until compressor stops and set the SWP switch to ON again. 3Because the unit automatically stops in about 2 to 3 minutes after the refrigerant recovering operation (LED1 is not lit and LED2 is lit), be sure to quickly close the gas stop valve. wIn case the outdoor unit is stopped when LED1 is lit and LED2 is not lit, open the liquid stop valve completely, and then repeat step 2 3 minutes later. wIf the refrigerant recovering operation has been completed normally (LED1 is not lit and LED2 is lit), the unit will remain stopped until the power supply is turned off. 4Turn off the power supply (circuit breaker).
2. Start and finish of test run
Operation from the indoor unit
Execute the test run using the installation manual for the indoor unit.
Operation from the outdoor unit
By using the DIP switch SW4 on the control board of outdoor unit, test run can be started and finished, and its operation mode (cooling/heating) can be set up.
1Set the operation mode (cooling/heating) using SW4-2. 2Turn on SW4-1 to start test run with the operation mode set by SW4-2. 3Turn off SW4-1 to finish the test run.
There may be a faint knocking sound around the machine room after power is supplied, but this is
no problem with product because the linear expansion valve is just moving to adjust opening pulse.
There may be a knocking sound around the machine room for several seconds after compressor
starts operating. But this is not a problem with product because the check valve itself generates the sound due to small pressure difference in the refrigerant circuit.
Note: The operation mode cannot be changed by SW4-2 during test run. (To change test run mode, stop the unit by SW4-1, change the operation mode and restart the test run by SW4-1.)
Stop Operation Cooling Heating
<SW4>

ON OFF
12

18
11 TROUBLESHOOTING
11-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring at service, are summarized in the table below. Check the contents below before investigating details.
Unit conditions at service
The trouble is reoccurring.
The trouble is not reoccurring.
Error code
Displayed
Not displayed
Logged
Not logged
Actions to be taken for service (summary)
Judge what is wrong and take a corrective action according to “11-4. Self-diagnosis action table”.
Conduct troubleshooting and ascertain the cause of the trouble according to “11-5. Troubleshooting by inferior phenomena”.
Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise and etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the trouble occurred, matters related to wiring and etc. Reset error code logs and restart the unit after finishing service. There is no abnormality in electrical component, controller board, remote controller and etc.
Re-check the abnormal symptom.Conduct trouble shooting and ascertain the cause of the
trouble phenomena”. Continue to operate unit for the time being if the cause is not ascertained. There is no abnormality concerning of parts such as electrical component, controller board, remote controller and etc.
according to “11-5. Troubleshooting
by inferior
11-2. CHECK POINT UNDER TEST RUN
(1) Before test run
After installation of indoor and outdoor units, piping work and electric wiring work, re-check that there is no refrigerant leak-
age, loosened connections and incorrect polarity.
Measure impedance between the ground and the power supply terminal block (L, N) on the outdoor unit by 500V Megger
and check that it is 1.0M" or over.
wDo not use 500V Megger to indoor/outdoor connecting wire terminal block (S1, S2, S3) and remote controller terminal block (1, 2). This may cause malfunction.
Make sure that test run switch (SW4) is set to OFF before turning on power supply.
Turn on power supply 12 hours before test run in order to protect compressor.
For specific models which requires higher ceiling settings or auto-recovery feature from power failure, make proper changes
of settings referring to the description of “Selection of Functions through Remote Controller”.
Make sure to read operation manual before test run. (Especially items to secure safety.)
19
"TEST RUN" and the currently selected operation mode are displayed altemately.
Displays the remaining test run time.
[TEST] button
Pipe (liquid) temperature
Operating procedures
1. Turn on the main power supply.
2. Press TEST button twice.
3. Press OPERATION SWITCH button.
4. Press AIR DIRECTION button.
5. Check the outdoor unit fan for correct running.
6. Press the ON/OFF button to reset the test run in progress.
7. Register the contact number.
While the room temperature display on the remote controller is “PLEASE WAIT”, the remote controller is disabled. Wait until “PLEASE WAIT” disappears before using remote controller. “PLEASE WAIT” appears for about 2 minutes after power supply is turned on. +1
The TEST RUN appears on the screen. Cooling mode:
Heating mode: Check if warm air blows. (It takes a little while until warm air blows.)
Check for correct motion of auto-vanes. The outdoor unit features automatic capacity control to
provide optimum fan speeds. Therefore, the fan keeps running at a low speed to meet the current outside air condition unless it exceeds its available maximum power. Then, in actuality, the fan may stop or run in the reverse direction depending on the outside air, but this does not mean malfunction.
Check if cool air blows and water is drained.
• In case of test run, the OFF timer will be activated, and the test run will automatically stop after 2 hours.
• The room temperature display section shows the pipe temperature of indoor units during the test run.
• Check that all the indoor units are running properly in case of simultaneous twin and triple operation. Malfunctions may not be displayed regardless of incorrect wiring. w1 After turning on the power supply, the system will go into startup mode, “PLEASE WAIT” will blink on the display section of the room temperature, and lamp (green) of the remote controller will flash. As to INDOOR BOARD LED, LED1 will be lit up, LED2 will either be lit up in case the address is 0 or turned off in case the address is not 0. LED3 will blink. As to OUTDOOR BOARD LED, LED1 (green) and LED2 (red) will be lit up. (After the startup mode of the system finishes, LED2 (red) will be turned off.)
In case OUTDOOR BOARD LED is digital display, and will be displayed alternately every second.
• If one of the above operations doesn’t function correctly, the causes written below should be considered. Find causes from the symptoms. The below symptoms are under test run mode. “startup” in the table means the display status of w1 written above.
Symptoms in test run mode
Remote Controller Display
Remote controller displays “PLEASE WAIT”, and
After power is turned on, “PLEASE WAIT” is displayed for 3 minutes, then error code is displayed.
No display appears even when remote controller operation switch is turned on. (Operation lamp does not light up.)
Display appears but soon disappears even when remote controller is operated.
cannot be operated.
OUTDOOR BOARD LED Display
< > indicates digital display.
After “startup” is displayed, only green lights up. <00> After “startup” is displayed,
green(once) and red(once) blink alternately. <F1>
After “startup” is displayed, green(once) and red(twice) blink
alternately. <F3, F5, F9> After “startup” is displayed,
green(twice) and red(once) blink alternately. <EA. Eb>
After “startup” is displayed, only green lights up. <00>
After “startup” is displayed, only green lights up. <00>
• After power is turned on, “PLEASE WAIT” is displayed for 2 minutes during
• Incorrect connection of outdoor terminal block (L S1, S2, S3.)
• Outdoor unit’s protection device connector is open.
• Incorrect wiring between the indoor and outdoor unit (Polarity is wrong for S1, S2, S3.)
• Remote controller transmission wire short.
• There is no outdoor unit of address 0. (Address is other than 0.)
• Remote controller transmission wire open.
• After canceling function selection, operation is not possible for about 30 seconds. (Normal)
system startup. (Normal)
Cause
1, L2, L3 and
w Press the remote controller’s CHECK button twice to perform self-diagnosis. See the table below for the contents of LCD display.
LCD
Abnormality of room temperature thermistor
P1
Abnormality of pipe temperature thermistor/Liquid
P2
Abnormality of drain sensor/Float switch connector open
P4
Drain overflow protection is working.
P5
Freezing/overheating protection is working.
P6
Abnormality of pipe temperature
P8
Abnormality of pipe temperature thermistor/Cond./Eva
P9
Abnormality of indoor controller board
Fb
Contents of trouble
LCD
Malfunction outdoor unit
U1~UP
F3~F9
Malfunction
E0~E5
Remote controller transmitting error
E6~EF
Indoor/outdoor unit communication error
----
No error history
FFFF
No applied unit Forced compressor stop (due to water leakage abnormality)
PA
outdoor unit
Contents of trouble
See the table below for details of the LED display (LED 1, 2, 3) on the indoor controller board.
(microcomputer power supply)
LED1
(remote controller)
LED2
(indoor/outdoor communication)
LED3
Lights when power is supplied. Lights when power is supplied for wired remote controller. The indoor unit should be connected to the outdoor unit with address “0” setting.
Flashes when indoor and outdoor unit are communicating.
20
,
ON/OFF
MODE
CHECK
TEST RUN
SET
TEST RUN
FAN
VANE
LOUVER
RESET
CLOCK
TEMP
AUTO STOP
AUTO START
h
min
Test run [for wireless remote controller]
Measure an impedance between the power supply terminal block on the outdoor unit and ground with a 500V Megger and check that it is equal to or greater than 1.0M".
1 Turn on the main power to the unit. 2 Press the button twice continuously.
(Start this operation from the status of remote controller display
turned off.)
TEST RUN
A and current operation mode are displayed. 3 Press the ( ) button to activate mode, then
check whether cool air is blown out from the unit.
4 Press the ( ) button to activate mode, then
check whether warm air is blown out from the unit.
5 Press the button and check whether strong air is blown out
from the unit.
6 Press the button and check whether the auto vane operates
properly.
7 Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver while following steps 2 to 7.
• It is not possible to run in FAN, DRY or AUTO mode.
TEST RUN
MODE
MODE
FAN
VANE
COOL
HEAT
21
11-3. HOW TO PROCEED "SELF-DIAGNOSIS"
11-3-1. When a Problem Occurs During Operation
If a problem occurs in the air conditioner, the indoor and outdoor units will stop, and the problem is shown in the remote controller display.
[CHECK] and the refrigerant address are displayed on the temperature display , and the error code and unit number are displayed alternately as shown below. (If the outdoor unit is malfunctioning, the unit number will be "00".)
In the case of group control, for which one remote controller controls multiple refrigerant systems, the refrigerant address and error code of the unit that first experienced trouble (i.e., the unit that transmitted the error code) will be displayed.
T o clear the error code, press the button.
Error code (2 or 4 digits)
ON/OFF
(Alternating Display)
Address (3 digits) or unit number (2 digits)
When using remote-/local-controller combined operation, cancel the error code after turning off remote operation. During central control by a MELANS controller, cancel the error code by pressing the
ON/OFF
button.
11-3-2. Self-Diagnosis During Maintenance or Service
Since each unit has a function that stores error codes, the latest check code can be recalled even if it is cancelled by the remote controller or power is shut off.
Check the error code history for each unit using the remote controller.
Switch to self-diagnosis mode.
Press the will change as shown below.
CHECK
button twice within 3 seconds. The display content
Unit number or refrigerant address to be diagnosed
Set the unit number or refrigerant address you want to diagnose.
Press the [TEMP] buttons ( and ) to select the desired number or address. The number (address) changes between [01] and [50] or [00]
and
[15].
The refrigerant address will begin to flash approximately 3 seconds after being selected and the self-diagnosis process will begin.
Display self-diagnosis results.
<When there is error code history>
Error code (2 or 4 digits)
<When there is no error code history> <When there is no corresponding unit>
Reset the error history.
Display the error history in the diagnosis result display screen (see step
(Alternating Display)
Address (3 digits) or unit number (2 digits)
).
22
Press the
address or refrigerant address will blink.
Cancel self-diagnosis.
Self-diagnosis can be cancelled by the following 2 methods.
Press the
Press the
ON/OFF
CHECK
ON/OFF
button twice within 3 seconds. The self-diagnosis
button twice within 3 seconds. Self-diagnosis will be cancelled and the screen will return to the previous state in effect before the
button. Self-diagnosis will be cancelled and the indoor unit will stop.
start of self-diagnosis.
When the error history is reset, the display will look like the one shown below. However, if you fail to reset the error history, the error content will be displayed again.
11-3-3. Remote Controller Diagnosis
If the air conditioner cannot be operated from the remote controller, diagnose the remote controller as explained below.
First, check that the power-on indicator is lit.
If the correct voltage (DC12 V) is not supplied to the remote controller, the indicator will not light. If this occurs, check the remote controller's wiring and the indoor unit.
Power on indicator
Switch to the remote controller self-diagnosis mode.
Press the
will change as shown below.
CHECK
button for 5 seconds or more. The display content
Press the
FILTER
button to start self-diagnosis.
Remote controller self-diagnosis result
[When the remote controller is functioning correctly]
Check for other possible causes, as there is no problem with the remote controller.
[Where the remote controller is not defective, but cannot be operated.] (Error display 2) [E3], [6833] or [6832] blinks.
There might be noise or interference on the transmission path, or the indoor unit or other remote controllers are defective. Check the transmission path and other controllers.
© Transmission is not possible.
[When the remote controller malfunctions] (Error display 1) "NG" blinks. ©The remote controller's transmitting-receiv-
The remote controller must be replaced with a new one.
(Error display 3)
The number of data errors is the difference between the number of bits sent from the remote controller and the number actually transmitted through the transmission path. If such a problem is occurring, the transmitted data is affected by noise, etc. Check the transmission path.
ing circuit is defective.
"ERC" and the number of data errors are displayed.
© Data error has occurred.
When the number of data errors is "02": Transmission data from remote controller Transmission data on transmission path
To cancel remote controller diagnosis
Press the
approximately 30 seconds, the state in effect before the diagnosis will be restored.
CHECK
button for 5 seconds or more. Remote controller diagnosis will be cancelled, "PLEASE WAIT" and operation lamp will blink. After
23
11-3-4. Malfunction-diagnosis method by wireless remote controller
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop.
<Malfunction-diagnosis method at maintenance service>
[Procedure]
CHECK display
ON/OFF button
CHECK button
ON/OFF
MODE
CHECK
TEST RUN
SET
CHECK
FAN
VANE
LOUVER
RESET
TEMP
AUTO STOP
AUTO START
CLOCK
h
min
Refrigerant address display
Temperature button
HOUR button
1. Press the CHECK button twice.
2. Press the temperature buttons.
3. Point the remote controller at the sensor on the indoor unit and press the HOUR button.
• "CHECK" lights, and refrigerant address "00" blinks.
• Check that the remote controller's display has stopped before continuing.
• Select the refrigerant address of the indoor unit for the self-diagnosis. Note: Set refrigerant address using the outdoor unit’s DIP switch (SW1). (For more information, see the outdoor unit installation manual.)
• If an air conditioner error occurs, the indoor unit's sensor emits an intermit­ tent buzzer sound, the operation lamp blinks, and the error code is output. (It takes 3 seconds at most for error code to appear.)
4. Point the remote controller at the sensor on the indoor unit and press the ON/OFF button.
• The check mode is cancelled.
24
• Refer to the following tables for details on the check codes. [Output pattern A]
Beeper sounds OPERATION
INDICATOR lamp blink pattern
Beep
Self-check starts (Start signal received)
Beep Beep Beep Beep Beep Beep
1st2nd3
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “P5”)
rd
n
On
0.5 sec.
th
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
1st2
Number of blinks/beeps in pattern indicates the check code in the following table
nd
· · · Repeated
[Output pattern B]
Beeper sounds OPERATION
INDICATOR lamp blink pattern
Beep Beep Beep Beep Beep Beep Beep
1st2nd3
Off
Self-check starts (Start signal received)
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “U2”)
rd
th
n
On
0.5 sec.
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check code in the following table
1st2
nd
· · · Repeated
[Output pattern A] Errors detected by indoor unit
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks Check code
Wired remote controller
Symptom Remark
(Number of times)
1P1 2
P2 Pipe (TH2) sensor error P9 Pipe (TH5) sensor error
3E6,E7
Intake sensor error
Indoor/outdoor unit communication error
4 P4 Drain sensor error/Float switch connector open 5 6
7
P5 PA P6 EE
8P8
Drain pump error Forced compressor stop (due to water leakage abnormality) Freezing/Overheating protection operation Communication error between indoor and outdoor units Pipe temperature error
As for indoor unit, refer to indoor unit's service manual.
9 E4, E5 Remote controller signal receiving error 10 11 12
[Output pattern B]
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wireless remote controller
– –
Fb E0, E3
E1, E2
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks Check code
– –
Indoor unit control system error (memory error, etc.) Remote controller transmission error
Remote controller control board error
Symptom Remark
(Number of times)
1
2
3
4
5
6
7
8
9 10
11
12 13 14
E9 UP
U3,U4 UF
U2 U1,Ud U5
U8 U6 U7
U9,UH
– –
Others
*1If the beeper does not sound again after the initial
the OPERATION INDICATOR lamp does not come on,
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
Compressor overcurrent interruption Open/short of outdoor unit thermistors Compressor overcurrent interruption (When compressor locked) Abnormal high discharging temperature/insufficient refrigerant Abnormal high pressure (63H worked)/Overheating
protection operation Abnormal temperature of heatsink
Outdoor unit fan protection stop
Compressor overcurrent interruption/Abnormality of power module Abnormality of superheat due to low discharge temperature Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
– Other errors (Refer to the technical manual for the outdoor unit.)
2 beeps to confirm the self-check start signal was received and
there are no error records.
For details, check the LED display of the outdoor controller board.
*2If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
25
11-4. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is turned on>
Error Code
Abnormal point and detection method
1 No voltage is supplied to terminal
block(TB1) of outdoor unit. a) Power supply breaker is
b) Contact failure or disconnec-
terminal c) Open phase (L2 or N phase)
(Note 1) Refer to indoor unit section for code P and code E. (P.32, 33)
Case
1 Check following items.
a) Power supply breaker b), c) Connection of power supply terminal
turned off.
tion of power supply
Judgment and action
block (TB1)
None
F5
(5201)
63H connector open
Abnormal if 63H connector circuit is open for 3 minutes continuously after power sup­ply. 63H: High-pressure switch
2 Electric power is not supplied to
outdoor controller circuit board. a) Disconnection of connector
(CNDC)
3 Disconnection of reactor
(ACL4)
4 Disconnection of outdoor noise
filter circuit board or parts fail­ure in outdoor noise filter circuit board
5 Defective outdoor controller circuit board
1 Disconnection or contact failure
of 63H connector on outdoor controller circuit board
2 Disconnection or contact failure
of 63H
3 63H is working due to defective
parts.
4 Defective outdoor controller circuit board
2 Check connection of the connector (CNDC)
on the outdoor controller circuit board.
Check connection of the connector CNDC on
the outdoor noise filter circuit board.
Refer to 11-9.
3 Check connection of reactor. (ACL4)
4 a) Check connection of outdoor noise filter
circuit board. b) Replace outdoor noise filter circuit board.
Refer to 11-9.
5 Replace controller board (When items above
are checked but the units cannot be repaired).
1 Check connection of 63H connector on outdoor controller circuit board. Refer to 11-9.
2 Check the 63H side of connecting wire.
3 Check continuity by tester.
Replace the parts if the parts are defective. 4 Replace outdoor controller circuit board.
26
Error Code
EA
(6844)
Eb
(6845)
Abnormal point and detection method
Indoor/outdoor unit connector miswiring, excessive number of units
1. Outdoor controller circuit board can automatically check the number of connected indoor units. Abnormal if the
number cannot be checked automati­cally due to miswiring of indoor/outdoor unit connecting wire and etc. after power is turned on for 4 minutes.
2. Abnormal if outdoor controller circuit board recognizes excessive number of indoor units.
Miswiring of indoor/outdoor unit connecting wire (converse wiring or dis­connection)
Outdoor controller circuit board can automatically set the unit number of indoor units. Abnormal if the indoor unit number can­not be set within 4 minutes after power on because of miswiring (converse wiring or disconnection) of indoor/outdoor unit con­necting wire.
Case
1 Contact failure or miswiring of
indoor/outdoor unit connecting wire
2 Diameter or length of indoor/
outdoor unit connecting wire is out of specified capacity.
3 Excessive number of indoor
units are connected to 1 out­door unit. (5 units or more)
4 Defective transmitting receiving
circuit of outdoor controller
circuit board 5 Defective transmitting receiving
circuit of indoor controller board
6 Defective indoor power board 7 2 or more outdoor units have
refrigerant address “0” .
(In case of group control) 8 Noise has entered into power supply or indoor / outdoor unit connecting wire.
1 Contact failure or miswiring of
indoor/outdoor unit connecting wire
2 Diameter or length of indoor/
outdoor unit connecting wire is out of specified capacity.
4 Defective transmitting receiving
circuit of outdoor controller circuit board
5 Defective transmitting receiving
circuit of indoor controller board
6 Defective indoor power board 7 2 or more outdoor units have
refrigerant address “0”.
(In case of group control) 8 Noise has entered into power
supply or indoor/outdoor unit connecting wire.
Judgment and action
1 Check disconnection or looseness or polar-
ity of indoor/outdoor unit connecting wire of indoor and outdoor units.
2 Check diameter and length of indoor/outdoor
unit connecting wire. Total wiring length: 80m (Including wiring connecting each indoor unit
and between indoor and outdoor unit) Also check if the connection order of flat
cable is S1, S2, S3.
3 Check the number of indoor units that are
connected to one outdoor unit. (If EA is
detected.)
4~6 Turn the power off once, and on again to check. Replace outdoor controller circuit board, indoor controller board or indoor power board if abnormality occurs again.
7 Check if refrigerant addresses (SW1-3 to
SW1-6 on outdoor controller circuit board)
are overlapping in case of group control system.
8 Check transmission path, and remove the
cause.
w The descriptions above, 1-8, are for EA, Eb
and EC.
EC
(6846)
Start-up time over
The unit cannot finish start-up process within 4 minutes after power on.
1 Contact failure of indoor/ outdoor unit connecting wire 2 Diameter or length of indoor/
outdoor unit connecting wire is out of specified capacity.
7 2 or more outdoor units have
refrigerant address “0” .
(In case of group control) 8 Noise has entered into power
supply or indoor/outdoor unit connecting wire.
27
<Abnormalities detected while unit is operating>
Error Code
U1
(1302)
Abnormal point and detection method
High pressure (High-pressure switch 63H worked)
Abnormal if high-pressure switch 63H worked ( w ) during compressor operation. w 4.15 MPa
63H: High-pressure switch
Case
1 Short cycle of indoor unit 2 Clogged filter of indoor unit 3 Decreased airflow caused by
dirt of indoor fan
4 Dirt of indoor heat exchanger 5 Locked indoor fan motor 6 Malfunction of indoor fan motor 7 Defective operation of stop
valve (Not full open)
8 Clogged or broken pipe 9 Locked outdoor fan motor
0 Malfunction of outdoor fan
motor
1 Short cycle of outdoor unit 2 Dirt of outdoor heat exchanger 3 Decreased airflow caused by
defective inspection of outside temperature thermistor
(It detects lower temperature
than actual temperature.)
4 Disconnection or contact failure
of connector (63H) on outdoor controller board
5 Disconnection or contact failure
of 63H connection
6 Defective outdoor controller
board
7 Defective action of linear
expansion valve
8 Malfunction of fan driving circuit
Judgment and action
1~6 Check indoor unit and repair defect.
7 Check if stop valve is fully open.
8 Check piping and repair defect. 9~2 Check outdoor unit and repair defect.
3 Check the inspected temperature of outside
temperature thermistor on LED display.
(SW2 on A-Control Service Tool : Refer to
11-10.)
4~6 Turn the power off and check F5 is displayed when the power is turned again. When F5 is displayed, refer to “Judgment
and action” for F5.
7 Check linear expansion valve. Refer to 11-6. 8 Replace outdoor controller board.
U2
(1102)
U3
(5104)
High discharging temperature
(1) Abnormal if discharge temperature ther-
mistor (TH4) exceeds 125: or 110: continuously for 5 minutes.
Abnormal if condenser/evaporator tem-
perature thermistor (TH5) exceeds 40: during defrosting and discharge temper­ature thermistor (TH4) exceeds 110:.
(2) Abnormal if discharge superheat
(Cooling: TH4 – TH5 / Heating: TH4 – TH6) exceeds 70: continuously for 10 minutes.
Open/short circuit of discharge temperature thermistor (TH4)
Abnormal if open (3: or less) or short (217: or more) is detected during compressor operation. (Detection is inoperative for 10 minutes of compressor starting process and for 10 minutes after and during defrosting.)
1 Overheated compressor opera-
tion caused by shortage of refrigerant
2 Defective operation of stop
valve
3 Defective thermistor 4 Defective outdoor controller
board
5 Defective action of linear
expansion valve
6 Clogging with foreign objects in
refrigerant circuit
w Clogging occurs in the parts
which become below freez­ing point when water enters in refrigerant circuit.
1 Disconnection or contact failure of connector (TH4) on
the outdoor controller circuit board
2 Defective thermistor
3 Defective outdoor controller
circuit board
1 Check intake superheat. Check leakage of refrigerant. Charge additional refrigerant.
2 Check if stop valve is fully open.
34 Turn the power off and check if U3 is dis-
played when the power is turned on again.
When U3 is displayed, refer to “Judgement
and action” for U3.
5 Check linear expansion valve. Refer to 11-6. 6 After recovering refrigerant, remove water
from entire refrigerant circuit under vacuum more than 1 hour.
1 Check connection of connector (TH4) on the
outdoor controller circuit board. Check breaking of the lead wire for thermistor (TH4). Refer to 11-9. 2 Check resistance value of thermistor (TH4) or
temperature by microcomputer. (Thermistor/TH4: Refer to 11-6.) (SW2 on A-Control Service Tool: Refer to
11-10.) 3 Replace outdoor controller board.
28
Loading...
+ 64 hidden pages