OUTDOOR CONTROLLER BOARD (C.B) has been changed.
(Corresponding to the additional combination between PKA-RP
* In case of UL error, the compressor may be damaged if the unit is restarted by remote controller.
To avoid the damage, unit has the system that is not able to be restarted unless the power is turned OFF once.
In case of using the existing pipes for R22, be careful with
the followings.
· Be sure to clean the pipes and make sure that the insides
of the pipes are clean.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
Store the piping to be used indoors during
installation and both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
If large amount of mineral oil enters, that can cause deterioration of refrigerant oil etc.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
3
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Tool name Specifications
1Gauge manifold · Only for R410A
· Use the existing fitting
· Use high-tension side pressure of 5.3MPa·G or over.
2Charge hose · Only for R410A
· Use pressure performance of 5.09MPa·G or over.
3 Electronic scale
4Gas leak detector · Use the detector for R134a, R407C or R410A.
5Adaptor for reverse flow check · Attach on vacuum pump.
6Refrigerant charge base
7Refrigerant cylinder · Only for R410A · Top of cylinder (Pink)
· Cylinder with syphon
8Refrigerant recovery equipment
specifications
. (UNF1/2)
4
Cautions for refrigerant piping work
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same
as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore, as the working
pressure of R410A is 1.6 time higher than that of R22, their sizes of flared sections and flare nuts are different.
1Thickness of pipes
Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness
shown below. (Never use pipes of 0.7mm or below.)
Diagram below: Piping diameter and thickness
Nominal
dimensions(inch)
1/4
3/8
1/2
5/8
3/4
Outside
diameter
6.35
9.52
12.70
15.88
19.05
(mm)
Thickness
R410AR22
0.8
0.8
0.8
1.0
—
(mm)
0.8
0.8
0.8
1.0
1.0
2Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that,
R410A is a refrigerant, which has higher risk of leakage because its working pressure is higher than that of other refriger ants. Therefore, to enhance airtightness and intensity, flare cutting dimension of copper pipe for R410A have been speci fied separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also
have partly been changed to increase intensity as shown below. Set copper pipe correctly referring to copper pipe flaring
dimensions for R410A below. For 1/2 and 5/8 inch, the dimension B changes.
Use torque wrench corresponding to each dimension.
Dimension A
Flare cutting dimensions
Nominal
dimensions(inch)
1/4
3/8
1/2
5/8
3/4
Outside
diameter
6.35
9.52
12.70
15.88
19.05
Dimension A
R410AR22
9.1
13.2
16.6
19.7
—
+0
( )
-0.4
9.0
13.0
16.2
19.4
23.3
(mm)
Flare nut dimensions
dimensions(inch)
Nominal
1/4
3/8
1/2
5/8
3/4
Outside
diameter
6.35
9.52
12.70
15.88
19.05
R410A
17.0
22.0
26.0
29.0
—
3Tools for R410A (The following table shows whether conventional tools can be used or not.)
Tools and materialsUseR410A toolsCan R22 tools be used?
Gauge manifold
Bender
Pipe cutter
Welder and nitrogen gas cylinder
Refrigerant charging scale
Vacuum gauge or thermistor vacuum gauge and
vacuum valve
Charging cylinder
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.)
: Tools for other refrigerants can be used under certain conditions.
: Tools for other refrigerants can be used.
Air purge, refrigerant charge and
Operation check
Gas leak check
Refrigerant recovery
Refrigerant charge
Apply to flared section
Prevent compressor malfunction
when charging refrigerant by
spraying liquid refrigerant
Prevent gas from blowing out
when detaching charge hose
Vacuum drying and air
purge
Flaring work of piping
Bend the pipes
Cut the pipes
Weld the pipes
Refrigerant charge
Check the degree of vacuum. (Vacuum
valve prevents back flow of oil and refrigerant to thermistor vacuum gauge)
Refrigerant charge
Tool exclusive for R410A
Tool exclusive for R410A
Tool for HFC refrigerant
Tool exclusive for R410A
Tool exclusive for R410A
Ester oil and alkylbenzene
oil (minimum amount)
Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can
be used if equipped with adopter for reverse flow check
Tools for other refrigerants
can be used by adjusting
flaring dimension
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants
can be used
CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT.
(Max.30m (PUHZ-P125/P140))
The refrigerant circuit with LEV (Linear Expansion Valve) and Accumulator always control the optimal refrigerant
level regardless of the length (30m max. and 5m min.) of piping. The additional refrigerant charging work during
installation often causes problems. Heretofore it is completely eliminated. This unique system improves the quality
and reliability of the work done. It also helps to speed up the installation time.
PUHZ-P140VHA3.UK
1.UK
6
5SPECIFICATIONS
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Running current
Max. current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan Fan(drive) % No.Fan motor output
Airflow
mm(in.)
Indoor side
Outdoor side
Height difference
Piping length
A
A
kW
W
kW
dB
dB
L
PUHZ-P100VHA2.UK
PUHZ-P100VHA3.UK
Cooling
Heating
Single, 50Hz, 230V
12.26
12.62
28
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
TNB220FLHMT
2.9
Inverter
HP switch
Discharge thermo
—
Plate fin coil
Propeller fan % 1
0.060
)
60(2120)
Reverse cycle
50
54
950(37-3/8)
330+30(13+1-3/16)
943(37-1/8)
75(165)
R410A
3.0(6.6)
0.87(FV50S)
9.52(3/8)
15.88(5/8)
Flared
Flared
Max. 30m
Max. 50m
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Running current
Max. current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan Fan(drive) % No.Fan motor output
Airflow
Connector<A-Control Service Inspection Kit>
Connector<Connected to Optional M-NET Adapter Board>
CNMNT
CNVMNT
Connector<Connected to Optional M-NET Adapter Board>
CNDM
Connector<Connected for Option (Contact Input)>
X51,X52,X54,X55
Relay
+ 2
MF1
MS
3~
MF2
MS
3~
C.B.
1
1
CNS
WHT)
(
31
TH8
CB
63H
TH7 TH6 TH3 TH4
TRANS
CNAC
(
12
34
tttt
14
TH7/6
(RED)
WHT)
122
1
TH3
TH4
(WHT)
(WHT)
1
63H
(YLW)
CN2
(WHT)
17
7
F3
F4
7
CNF1
(WHT)
7
CNF2
WHT)
(
3
2
1
CNDC
(
PNK)
F2
F1
LED2
3
21S4
(GRN)
LEV-A
M
16
LEV-A
(WHT)
LED1
1
CN4
(WHT)
12
2
X52
X55
31
31
21S4
SV2
(BLU)
SV
+ 2
3
3
1
CNVMNT
(WHT)
CNM
(WHT)
X54
31
SV1/CH
(GRY)
CH
+
2
1
CNMNT
(WHT)
CN52C
(RED)
1
5
5
SW5SW8SW4 SWP
14
2
2
X51
31
SS
(WHT)
When M-NET adaptor is connected
5
+ 1+ 1
SW7
SW6SW1
SW9
CN31
1
3
CNDM
(WHT)
1
CN51
(WHT)
5
ABS
5
SW1
CN5
(WHT)
1
LED2
LED3
LED4
M-NET SUBSTRATE
2
1
CN2M
(WHT)
LED5
TB7
M-NET
SW11
SW12
CND
(WHT)
31
LED1
3
N.F.
LO
NO
1
52C
P. B .
4
1
CNAF
(WHT)
6
7
1
CN2
IPM
(WHT)
+
7
1
CN3
(WHT)
2
1
(RED)
2
1
(WHT)
2
TABN
TABP
CN5
CN4
TAB P2
TAB URED
UVW
t
2
2
+
MS
3~
TABVWHT
BLK
MC
–
TABW
+
CNDC
(PNK)
1
3
2
TAB N1
TABT
DS3
–~
+
~
TABS
DS2
–
~
+
~
TABP1
U
TAB N2
3
1
(RED)
CNAC2
3
1
(WHT)
CNAC1
LI
U
NI
U
2
CN52C
E2
1
2
CN5
EI
2
(BLK)
2
(RED)
DCL
+
—
ACTM
L1 L2
4
16
P
N1
N2
Io
POWER SUPPLY
~/N 230V 50Hz
13
INDOOR
UNIT
CY1
CY2
+ 1 MODEL SELECT
S3S2S1NL
TB1
MODEL
SW5-6
ON
100V
OFF
123456
ON
125V
OFF
123456
ON
140V
OFF
123456
+ 2 P125, P140 only
+ 3 SW5-1 to 5: Function Switch
+
3
SW6
ON
OFF
123456
78
ON
OFF
123456
78
ON
OFF
123456
78
9WIRING SPECIFICATIONS
9-1. FIELD ELECTRICAL WIRING (power wiring specifications)
Outdoor unit model
Outdoor unit power supply
Outdoor unit input capacity*1
Main switch (Breaker)
Outdoor unit power supply
)
2
Outdoor unit power supply earth
ing
Indoor unit-Outdoor unit*2
Wir
Indoor unit-Outdoor unit earth*2
Wire No. %
size (mm
Remote controller-Indoor unit*3
Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)
Indoor unit-Outdoor unit S1-S2*4
Indoor unit-Outdoor unit S2-S3*4
Circuit rating
Remote controller-Indoor unit*4
*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use earth leakage breaker(NV).
*2. Refer to 8-3.
*3. The 10 m wire is attached in the remote controller accessory.
*4. The figures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.
P100, 125VP140V
~/N (single), 50 Hz,~/N (single), 50 Hz,
230 V230 V
32 A40 A
2 % Min. 42 % Min. 6
1 % Min. 41 % Min. 6
3 % 1.5 (Polar)3 % 1.5 (Polar)
1 % Min. 1.51 % Min. 1.5
2 % 0.3 (Non-polar)2 % 0.3 (Non-polar)
*4
AC 230 VAC 230 V
AC 230 VAC 230 V
DC 24 VDC 24 V
DC 12 VDC 12 V
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and Indoor/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
3. Install an earth longer than other cables.
230V
Single phase
Isolator
S1
3 poles isolator
S1
A-Control
Outdoor Unit
S2
S3
S2
S3
A-Control
Indoor Unit
Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line
and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is
energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
1:1 systemSynchronized twin and triple system Electrical wiring
• Synchronized twin
Unit
power
supply
Earth leakage breaker
wiring circuit breaker or
isolating switch
Outdoor
unit
L
N
Indoor/outdoor
unit connection
cable
S1
S2
S3
Indoor
unit
S1
S2
S3
1
Remote
controller
2
Unit
power
supply
Earth leakage breaker
wiring circuit breaker or
isolating switch
Outdoor
unit
L
N
Indoor/outdoor
unit connection
cable
S1
S2
S3
Indoor
unit
S1
S2
S3
1
2
• Synchronized triple
Remote
controller
Indoor
unit
1
2
S1
S2
S3
Unit
power
supply
Earth leakage breaker
wiring circuit breaker or
isolating switch
14
Outdoor
unit
L
N
Indoor/outdoor
connection cable
S1
S2
S3
Indoor
unit
S1
S2
S3
1
2
Remote
controller
Indoor
unit
1
2
S1
S2
S3
Indoor
unit
1
2
S1
S2
S3
9-2. SEPARATE INDOOR UNIT/OUTDOOR UNIT POWER SUPPLIES
The following connection patterns are available.
The outdoor unit power supply patterns vary on models.
<For models without heater>
1:1 System
* The optional indoor power supply terminal kit is required.
L
N
S1
S2
S3
L
N
S1
S2
S3
1
2
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Simultaneous twin/triple system
<For models without heater>
* The optional indoor power supply terminal kits are required.
L
N
S1
S2
S3
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
If the indoor and outdoor units have separate power supplies, refer to the table below.
If the optional indoor power supply terminal kit is used, change the indoor unit
electrical box wiring refering to the figure in the right and the DIP switch settings of
the outdoor unit control board.
Indoor unit specifications
Indoor power supply terminal kit (option)
Indoor unit electrical box connector connection change
Label affixed near each wiring diagram
for the indoor and outdoor units
Outdoor unit DIP switch settings (when
using separate indoor unit/outdoor unit
power supplies only)
Required
Required
Required
ON
OFF 12
Set the SW8-3 to ON.
3
(SW8)
L
L
N
N
S1
S1
S2
S3
1
2
S2
S3
1
2
Electric heater
(For models with
heater)
L
N
S1
S2
S3
Indoor unit power supplied from outdoor unit
(when shipped from factory)
L
L
N
N
S1
S1
S2
S2
S3
S3
1
1
2
2
Connectors (connections when shipped
from the factory are for indoor unit power
supplied from outdoor unit)
BLUE
BLUE
YELLOW
YELLOW
CND or
CN01
control board
Indoor unit
* There are three types of labels (labels A, B and C). Affix the appropriate labels to
the units according to the wiring method.
Outdoor unit power supply
Earth leakage breaker
Wiring circuit breaker or isolating switch
Outdoor unit
Indoor unit/outdoor unit connecting cords
Remote controller
Indoor unit
Option
Indoor unit power supply
Outdoor unit power supply
Earth leakage breaker
Wiring circuit breaker or isolating switch
Outdoor unit
Indoor unit/outdoor unit connecting cords
Remote controller
Indoor unit
Option
Indoor unit power supply
Indoor unit earth
If the indoor and
outdoor units have
separate power
supplies, change the
connections of the
connectors as shown
in the following
figure.
Electric heater
(For models with
heater)
L
N
S1
S2
S3
Separate indoor unit/outdoor unit power
supplies
YELLOW
BLUE
BLUE
YELLOW
CN01
CND or
Connectors
Indoor unit
control board
Indoor unit model
Indoor unit power supply
Indoor unit input capacity
Main switch (Breaker)
Indoor unit power supply
Indoor unit power supply earth
)
2
Indoor unit-Outdoor unit
(mm
Wiring
Indoor unit-Outdoor unit earth
Wire No. % size
Remote controller-Indoor unit
Indoor unit L-N*4
Indoor unit-Outdoor unit S1-S2*4
Indoor unit-Outdoor unit S2-S3*4
rating
Circuit
Remote controller-Indoor unit*4
*1
*2
*3
RP35~140
~/N (single), 50 Hz, 230 V
16 A
2 % Min. 1.5
1 % Min. 1.5
2 % Min. 0.3
–
2 % 0.3 (Non-polar)
AC 230 V
–
DC24 V
DC12 V
*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
*2. Max. 120 m
*3. The 10 m wire is attached in the remote controller accessory. Max. 500 m
*4. The figures are NOT always against the ground.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord.
(Design 60245 IEC 57)
3. Install an earth longer than other cables.
15
9-3. INDOOR – OUTDOOR CONNECTING CABLE
The cable shall not be lighter than design 60245 IEC or 60227 IEC.
The cable length may vary depending on the condition of installation, humidity or materials, etc.
Cross section
of cable
Round
Wire size
2
)
(mm
2.5
Number
of wires
3
PolarityL(m) *5
Clockwise : S1-S2-S3
50
*1
Flat
2.5
3
Not applicable
(Because center wire has no cover finish)
Flat
1.5
4
From left to right : S1-Open-S2-S3
Round
2.5
*1 : In case that cable with stripe of yellow and green is available.
*2 : In case that the flat cables are connected as this picture, they can be used up to 80m.
(3C Flat cable × 2)
S1 S2 S3
*3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5mm
*4 : In case of regular polarity connection (S1-S2-S3)
*5 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, humidity or materials, etc.
4
Clockwise : S1-S2-S3-Open
Connect S1 and S3 to the opposite angle
2
.
Not
applicable
*2
45
*3
60
*4
Wire No. % Size ($)
Outdoor power supply
Max. 45m
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
+ The Max. cable length may vary depending on the condition of installation, humidity or materials, etc.
3 % 1.5 (polar)
1 % Min. 1.5
Indoor/Outdoor separate
power supply
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
+ The optional indoor power supply terminal kit is necessary.
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication errors if water enters the cables and causes insufficient insulation to
earth or a poor electrical contact at the intermediate connection point.
Max. 50m
3 % 2.5 (polar)
1 % Min. 2.5
Wire No. % Size ($)
2 % Min. 0.3
Max. 80m
3 % 2.5 (polar) and S3 separated
1 % Min. 2.5
Max. 120m
—
16
9-4. M-NET WIRING METHOD
(Points to notice)
(1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from
making an influence on the signal communication. Place them at intervals of more than 5cm. Do not put them in the same
conduit tube.
(2) Terminal block (TB7) for transmission wires should never be connected to V power supply. If it is connected,
electronic parts on M-NET P.C. board may be burn out.
(3) Use 2-core x 1.25mm² shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be sent or
received normally if different types of transmission wires are put together in the same multi-conductor cable. Never do this
because this may cause a malfunction.
Group
remote
controller
Power
supply
unit for
transmission
wire
A-control
remote
It would be ok if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Earth only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise.
“Ed” error will appear on the LED display of outdoor unit.
“0403” error will appear on the central-control remote controller.
Bad example (Multi spot earthing of shield wire)
Central
remote
controller
M-NET transmission wire
controller
Power
supply
appliance
Refrigerant
address 00
M-NET
address 01
M-NET type
outdoor unit
M-NET type
outdoor unit
A-control
remote
controller
Refrigerant
address 00
M-NET
address 02
M-NET type
outdoor unit
A-control
remote
controller
Refrigerant
address 00
M-NET
address 03
Good example 1 (Single spot earthing of shield wire)
Central
remote
controller
M-NET transmission wire
Good example 2 (Single spot earthing of shield wire)
Central
remote
controller
M-NET transmission wire
If there are more than 2 grounding spots on the shield wire, noise may enter into the shield wire because the earth wire
and shield wire form 1 circuit and the electric potential difference occurs due to the impedance difference among earthing
spots. In case of single spot grounding, noise does not enter into the shield wire because the earth wire and shield wire do
not form 1 circuit.
To avoid communication errors caused by noise, make sure to observe the single spot grounding method described in the
installation manual.
Power
supply
appliance
Power
supply
appliance
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
17
M-NET wiring
(1) Use 2-core x 1.25mm² shield wire for electric wires.
(Excluding the case connecting to system controller.)
(2) Connect the wire to the M-NET terminal block. Connect one core of the trans-
mission wire (non-polar) to A terminal and the other to B. Peel the shield wire,
twist the shield part to a string and connect it to S terminal.
(3) In the system which several outdoor units are being connected, the terminal
(A, B, S) on M-NET terminal block should be individually wired to the other
M-NET
terminal
block
ABS
Transmission
wire
Earth
wire
Shield
part
outdoor unit’s terminal, i.e. A to A, B to B and S to S. In this case, choose one of those outdoor units and drive a screw
to fix an ground wire on the plate as shown on the right figure.
9-4-1. M-NET address setting
In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to CITY MULTI
system, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the
setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as
that of the indoor unit in CITY MULTI system), and the address number should be consecutively set in a same group.
Address number can be set by using rotary switches
(SW11 for ones digit and SW12 for tens digit), which
is located on the M-NET board of outdoor unit.
(Factory setting: all addresses are set to “0”.)
<Setting example>
M-NET Address No.
SW11
Switng
setting
ones
digit
SW12
tens
digit
12
3
3
4
4
2
2
5
1
0
9
2
1
0
9
5
1
6
6
0
7
7
9
8
8
3
3
4
4
2
5
5
1
6
6
0
7
7
9
8
8
50
3
4
2
5
1
6
0
7
9
8
~
3
4
2
5
1
6
0
7
9
8
9-4-2. Refrigerant address setting
In case of multiple grouping system (multiple refrigerant circuits in one group), indoor units should be connected by remote
controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to “00” if the group setting is not conducted. Set the refrigerant address by using DIP SW1-3 to -6 on the outdoor controller board. [Initial setting: all
switches are OFF. (All refrigerant addresses are “00”.)]
Refrigerant
address
ON
OFF
1
ON
OFF
1
ON
OFF
1
3
4
5
2
6
0
ON
OFF
1
3
4
5
2
6
8
ON
OFF
1
3
4
5
2
6
1
ON
OFF
1
3
4
5
2
6
9
ON
OFF
1
3
4
5
2
6
2
ON
OFF
1
3
4
5
2
6
10
ON
OFF
1
3
4
5
2
6
3
ON
OFF
1
3
4
5
2
6
11
ON
OFF
1
3
4
5
2
6
4
ON
OFF
1
3
4
5
2
6
12
ON
OFF
1
3
4
5
2
6
5
ON
OFF
1
3
4
5
2
6
13
ON
OFF
1
3
4
2
6
3
4
2
14
3
5
5
4
5
2
6
OFF
6
6
7
ON
1
3
4
5
2
6
15
9-4-3. Regulations in address settings
In case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above section. Set the lowest number in the group for the outdoor unit whose refrigerant address is “00” as its M-NET address.
Group AGroup BGroup C
System
controller
Power
supply
unit for
transmission
wire
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
w Refrigerant addresses can be overlapped if they are in the different group.
Group AGroup B
System
controller
Power
supply
unit for
transmission
wire
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
Refrigerant
address 00
M-NET
address 02
A-control
remote
controller
Refrigerant
address 01
M-NET
address 02
TB5
TB5
Refrigerant
address 01
M-NET
address 03
Refrigerant
address 00
M-NET
address 04
A-control
remote
controller
Refrigerant
address 00
M-NET
address 04
A-control
remote
controller
Refrigerant
address 01
M-NET
address 03
Refrigerant
address 02
M-NET
address 05
w In group B, M-NET address of the outdoor unit whose refrigerant address is “00” is not set to the minimum in the group. As
“3” is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address in the
group for the outdoor unit whose refrigerant address is “00”.
18
10REFRIGERANT SYSTEM DIAGRAM
PUHZ-P100VHA2.UK
PUHZ-P100VHA2.UK
PUHZ-P100VHA3.UK
Unit : mm(inch)
Refrigerant flow in cooling
Refrigerant flow in heating
Perform the following procedures to recover the refrigerant when moving the indoor unit or the outdoor unit.
1Turn on the power supply (circuit breaker).
wWhen power is supplied, make sure that “CENTRALLY CONTROLLED” is not displayed on the remote controller. If
“CENTRALLY CONTROLLED” is displayed, the refrigerant recovering (pump down) cannot be completed normally.
2After the liquid stop valve is closed, set the SWP switch on the control board of the outdoor unit to ON. The compressor
(outdoor unit) and ventilators (indoor and outdoor units) start operating and refrigerant recovery operation begins. LED1 and
LED2 on the control board of the outdoor unit are lit.
wSet the SWP switch (push-button type) to ON in order to perform refrigerant recovery operation only when the unit is
stopped. However, refrigerant recovery operation cannot be performed until compressor stops even if the unit is stopped.
Wait 3 minutes until compressor stops and set the SWP switch to ON again.
3Because the unit automatically stops in about 2 to 3 minutes after the refrigerant recovering operation (LED1 is not lit and
LED2 is lit), be sure to quickly close the gas stop valve.
wIn case the outdoor unit is stopped when LED1 is lit and LED2 is not lit, open the liquid stop valve completely, and then
repeat step 2 3 minutes later.
wIf the refrigerant recovering operation has been completed normally (LED1 is not lit and LED2 is lit), the unit will remain
stopped until the power supply is turned off.
4Turn off the power supply (circuit breaker.)
2. Start and finish of test run
• Operation from the indoor unit
Execute the test run using the installation manual for the indoor unit.
• Operation from the outdoor unit
By using the DIP switch SW4 on the control board of outdoor unit, test run can be started and finished, and its operation
mode (cooling/heating) can be set up.
1Set the operation mode (cooling/heating) using SW4-2.
2Turn on SW4-1 to start test run with the operation mode set by SW4-2.
3Turn off SW4-1 to finish the test run.
• There may be a faint knocking sound around the machine room after power is supplied, but this is
no problem with product because the linear expansion pipe is just moving to adjust opening pulse.
• There may be a knocking sound around the machine room for several seconds after compressor
starts operating. But this is not a problem with product because the check valve itself generates the
sound due to small pressure difference in the refrigerant circuit.
Note:
The operation mode cannot be changed by SW4-2 during test run. (To change test run mode, stop the unit by SW4-1,
change the operation mode and restart the test run by SW4-1.)
Stop Operation
Cooling Heating
<SW4>
ON
OFF
12
20
11TROUBLESHOOTING
11-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit.
Actions to be taken for service, which depends on whether or not the trouble is reoccurring at service, are summarized in the
table below. Check the contents below before investigating details.
Unit conditions at service
The trouble is reoccurring.
The trouble is not reoccurring.
Error code
Displayed
Not displayed
Logged
Not logged
Actions to be taken for service (summary)
Judge what is wrong and take a corrective action according
to “11-4. Self-diagnosis action table”.
Conduct trouble shooting and ascertain the cause of the
trouble according to “11-5. Troubleshooting by inferior
phenomena”.
Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
trouble occurred, matters related to wiring and etc.
Reset error code logs and restart the unit after finishing
service.
There is no abnormality concerning of parts such as
electrical component, controller board, remote controller
and etc.
Re-check the abnormal symptom.
Conduct trouble shooting and ascertain the cause
of the trouble
by inferior phenomena”.
Continue to operate unit for the time being if the cause
is not ascertained.
There is no abnormality concerning of parts such as
electrical component, controller board, remote controller
and etc.
according to “11-5. Troubleshooting
11-2. CHECK POINT UNDER TEST RUN
(1) Before test run
• After installation of indoor and outdoor units, piping work and electric wiring work, re-check that there is no refrigerant leak-
age, loosened connections and incorrect polarity.
• Measure impedance between the ground and the power supply terminal block(L, N) on the outdoor unit by 500V Megger and
check that it is 1.0M" or over.
wDo not use 500V Megger to indoor/outdoor connecting wire terminal block(S1, S2, S3) and remote controller terminal block
(1, 2). This may cause malfunction.
• Make sure that test run switch (SW4) is set to OFF before turning on power supply.
• Turn on power supply 12 hours before test run in order to protect compressor.
• For specific models which requires higher ceiling settings or auto-recovery feature from power failure, make proper changes
of settings referring to the description of “Selection of Functions through Remote Controller”.
Make sure to read operation manual before test run. (Especially items to secure safety.)
21
"TEST RUN" and the currently selected
operation mode are displayed alternately.
Displays the remaining
test run time.
[TEST] button
Pipe (liquid) temperature
Operating procedures
1. Turn on the main power supply.
2. Press TEST button twice.
3. Press OPERATION SWITCH
button.
4. Press AIR DIRECTION button.
5. Check the outdoor unit fan for
correct running.
6. Press the ON/OFF button to reset the test run in progress.
7. Register the contact number.
While the room temperature display on the remote
controller is “PLEASE WAIT”, the remote controller is disabled.
Wait until “PLEASE WAIT” disappears before using remote controller.
“PLEASE WAIT” appears for about 2 minutes after power
supply is turned on. +1
The TEST RUN appears on the screen.
Cooling mode:
Heating mode: Check if warm air blows. (It takes a little
while until warm air blows.)
Check for correct motion of auto-vanes.
The outdoor unit features automatic capacity control to
provide optimum fan speeds. Therefore, the fan keeps
running at a low speed to meet the current outside air
condition unless it exceeds its available maximum power.
Then, in actuality, the fan may stop or run in the reverse
direction depending on the outside air, but this does not
mean malfunction.
Check if cool air blows and water is drained.
• In case of test run, the OFF timer will be activated, and the test run will automatically stop after 2 hours.
• The room temperature display section shows the pipe temperature of indoor units during the test run.
• Check that all the indoor units are running properly in case of simultaneous twin and triple operation. Malfunctions may not
be displayed regardless of incorrect wiring.
w1 After turning on the power supply, the system will go into start up mode, “PLEASE WAIT” will blink on the display section of
the room temperature, and lamp(green) of the remote controller will blink.
As to INDOOR BOARD LED, LED1 will be lit up, LED2 will either be lit up in case the address is 0 or turned off in case the
address is not 0. LED3 will blink.
As to OUTDOOR BOARD LED, LED1(green) and LED2(red) will light up. (After the start up mode of the system finishes,
LED2(red) will be turned off.)
In case OUTDOOR BOARD LED is digital display, — and — will be displayed alternately every second.
• If one of the above operations doesn’t function correctly, the causes written below should be considered. Find causes from
the symptoms.
The below symptoms are under test run mode. “start up” in the table means the display status of w1 written above.
Symptoms in test run mode
Remote Controller Display
Remote controller displays “PLEASE
WAIT”, and
After power is turned on, “PLEASE WAIT”
is displayed for 3 minutes, then error code
is displayed.
No display appears even when remote
controller operation switch is turned on.
(Operation lamp does not light up.)
Display appears but soon disappears
even when remote controller is operated.
cannot be operated.
OUTDOOR BOARD LED Display
< > indicates digital display.
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed,
green(once) and red(once) blink
alternately. <F1>
After “startup” is displayed,
green(once) and red(twice) blink
alternately. <F3, F5, F9>
After “startup” is displayed,
green(twice) and red(once) blink
alternately. <EA. Eb>
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed, only
green lights up. <00>
• After power is turned on, “PLEASE WAIT” is displayed for 2
minutes during
• Outdoor unit’s protection device connector is open.
• Incorrect wiring between the indoor and outdoor unit (Polarity
is wrong for S1, S2, S3.)
• Remote controller transmission wire short.
• There is no outdoor unit of address 0.
(Address is other than 0.)
• Remote controller transmission wire open.
• After canceling function selection, operation is not possible for
about 30 seconds. (Normal)
system startup. (Normal)
Cause
1, L2, L3 and
w Press the remote controller’s CHECK button twice to perform self-diagnosis. See the table below for the contents of LCD
display.
LCD
P1
Abnormality of room temperature thermistor
P2
Abnormality of pipe temperature thermistor/Liquid
P4
Abnormality of drain sensor/Float switch connector open
P5
Drain overflow protection is working.
Freezing/overheating protection is working.
P6
Abnormality of pipe temperature
P8
Abnormality of pipe temperature thermistor/Cond./Eva
P9
Abnormality of indoor controller board
Fb
Contents of trouble
LCD
U1~UP
Malfunction outdoor unit
F3~F9
Malfunction
E0~E5
Remote controller transmitting error
Indoor/outdoor unit communication error
E6~EF
No error history
---No applied unit
FFFF
Forced compressor stop(due to water leakage abnormality)
PA
outdoor unit
Contents of trouble
See the table below for details of the LED display (LED 1, 2, 3) on the indoor controller board.
(microcomputer power supply)
LED1
(remote controller)
LED2
(indoor/outdoor communication)
LED3
Lights when power is supplied.
Lights when power is supplied for wired remote controller.
The indoor unit should be connected to the outdoor unit with address “0” setting.
Flash when indoor and outdoor unit are communicating.
22
N
N
,
ON/OFF
MODE
CHECK
TEST RUN
SET
TEST RUN
FAN
VAN E
LOUVER
RESET
CLOCK
TEMP
AUTO STOP
AUTO START
h
min
Test run [for wireless remote controller]
Measure an impedance between the power supply terminal block on
the outdoor unit and ground with a 500V Megger and check that it is
equal to or greater than 1.0M".
1 Turn on the main power to the unit.
2 Press the button twice continuously.
(Start this operation from the status of remote controller display
turned off.)
TEST RU
and current operation mode are displayed.
3 Press the ( ) button to activate mode, then
check whether cool air is blown out from the unit.
4 Press the ( ) button to activate mode, then
check whether warm air is blown out from the unit.
5 Press the button and check whether strong air is blown out
from the unit.
6 Press the button and check whether the auto vane operates
properly.
7 Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver
while following steps 2 to 7.
• It is not possible to run in FAN, DRY or AUTO mode.
TEST RU
MODE
MODE
FAN
VAN E
COOL
HEAT
23
11-3. HOW TO PROCEED "SELF-DIAGNOSIS"
11-3-1. When a Problem Occurs During Operation
If a problem occurs in the air conditioner, the indoor and outdoor units will stop,
and the problem is shown in the remote controller display.
[CHECK] and the refrigerant address are displayed on the temperature
display, and the error code and unit number are displayed alternately as
shown below.
If the outdoor unit is malfunctioning, the unit number will be "00".
In the case of group control, for which one remote controller controls
multiple refrigerant systems, the refrigerant address and error code of the
unit that first experienced trouble (i.e., the unit that transmitted the error
code) will be displayed.
To clear the error code, press the
ON/OFF
button.
Error code (2 or 4 digits)
(Alternating Display)
Address (3 digits) or unit number (2 digits)
When using remote-/local-controller combined operation, cancel the error code after turning off remote operation. During
central control by a MELANS controller, cancel the error code by pressing the
ON/OFF
button.
11-3-2. Self-Diagnosis During Maintenance or Service
Since each unit has a function that stores error codes, the latest check code can be recalled even if it is cancelled by the
remote controller or power is shut off.
Check the error code history for each unit using the remote controller.
Switch to self-diagnosis mode.
Press the
will change as shown below.
CHECK
button twice within 3 seconds. The display content
Unit number or refrigerant address
to be diagnosed
Set the unit number or refrigerant address you want to diagnose.
Press the [TEMP] buttons ( and ) to select the desired
number or address. The number (address) changes between [01] and
[50] o r [00]
The refrigerant address will begin to flash
approximately 3 seconds after being selected
and the self-diagnosis process will begin.
an d
[15].
Display self-diagnosis results.
<When there is error code history>
(For the definition of each error code, refer to the indoor unit's installation manual or service handbook.)
(Alternating Display)
Error code (2 or 4 digits)
<When there is no error code history><When there is no corresponding unit>
Address (3 digits) or unit number (2 digits)
Reset the error history.
Display the error history in the diagnosis result display screen (see step
).
24
Press the
address or refrigerant address will flash.
Cancel self-diagnosis.
Self-diagnosis can be cancelled by the following two methods.
Press the
Press the
ON/OFF
CHECK
ON/OFF
button twice within 3 seconds. The self-diagnosis
button twice within 3 seconds. Self-diagnosis will be cancelled and the screen will return to the previous state in effect before the start
button. Self-diagnosis will be cancelled and the indoor unit will stop.
of self-diagnosis.
When the error history is reset, the display will look like the one shown below.
However, if you fail to reset the error history, the error content will be displayed again.
11-3-3. Remote Controller Diagnosis
If the air conditioner cannot be operated from the remote controller, diagnose the remote controller as explained below.
First, check that the power-on indicator is lit.
If the correct voltage (DC12 V) is not supplied to the remote controller, the
indicator will not light.
If this occurs, check the remote controller's wiring and the indoor unit.
Power on indicator
Switch to the remote controller self-diagnosis mode.
Press the
change as shown below.
CHECK
button for 5 seconds or more. The display content will
Press the
FILTER
button to start self-diagnosis.
Remote controller self-diagnosis result
[When the remote controller is functioning correctly]
Check for other possible causes, as there is no problem with the remote
controller.
There might be noise or interference on the transmission path, or the indoor unit
or other remote controllers are defective. Check the transmission path and other
controllers.
The remote controller must be replaced with a new one.
(Error display 3)
The number of data errors is the difference between the number of bits sent from
the remote controller and the number actually transmitted through the transmission path. If such a problem is occurring, the transmitted data is affected by noise,
etc. Check the transmission path.
approximately 30 seconds, the state in effect before the diagnosis will be restored.
CHECK
button for 5 seconds or more. Remote controller diagnosis will be cancelled, "PLEASE WAIT" and operation lamp will flash. After
25
11-3-4. Malfunction-diagnosis method by wireless remote controller
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<Malfunction-diagnosis method at maintenance service>
[Procedure]
CHECK
display
ON/OFF
button
CHECK
button
ON/OFF
MODE
CHECK
TEST RUN
SET
CHECK
FAN
VAN E
LOUVER
RESET
TEMP
AUTO STOP
AUTO START
CLOCK
h
min
Refrigerant
address
display
Temperature
button
HOUR
button
1. Press the CHECK button twice.
2. Press the temperature
buttons.
3. Point the remote controller at the
sensor to the indoor unit and
press the HOUR button.
• "CHECK" lights, and refrigerant
address "00" flashes.
• Check that the remote controller's
display has stopped before continuing.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermit tent buzzer sound, the operation light
flashes, and the error code is
output.
(It takes 3 seconds at most for error
code to appear.)
4. Point the remote controller at the
sensor to the indoor unit and
press the ON/OFF button.
• The check mode is cancelled.
26
• Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds
OPERATION
INDICATOR
lamp blink
pattern
Beep
Self-check
starts
(Start signal
received)
Beep Beep BeepBeepBeep Beep
1st2nd3
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
rd
0.5 sec.
th
n
On
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates
the check code in the following table
1st2
nd
· · · Repeated
[Output pattern B]
Beeper sounds
OPERATION
INDICATOR
lamp
blink
pattern
BeepBeep Beep BeepBeepBeep Beep
1st2nd3
Off
Self-check
starts
(Start signal
received)
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “U2”)
rd
th
n
On
0.5 sec.
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
Number of blinks/beeps in pattern indicates
the check code in the following table
Indoor/outdoor unit communication error
4P4Drain sensor error/Float switch connector open
5P5Drain pump error
PAForced compressor stop (Due to water leakage abnormality)
6P6Freezing/Overheating protection operation
7EECommunication error between indoor and outdoor units
8P8Pipe temperature error
9E4, E5Remote controller signal receiving error
10
11
–
–
–
–
12FbIndoor unit control system error (memory error, etc.)
–
E0, E3
Remote controller transmission error
–E1, E2Remote controller control board error
[Output pattern B]
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinksCheck code
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote controller
SymptomRemark
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
*1 If the beeper does not sound again after the initial
the OPERATION INDICATOR lamp does not come on,
*2 If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
E9
UP
U3,U4
UF
U2
U1,Ud
U5
U8
U6
U7
U9,UH
–
–
Others
Indoor/outdoor unit communication error
(Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49 worked/
insufficient refrigerant
Abnormal high pressure (63H worked)/Overheating
protection operation
Abnormal temperature of heatsink
Outdoor unit fan protection stop
Compressor overcurrent interruption/Abnormal of power module
Abnormality of superheat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
–
–
Other errors
2 beeps to confirm the self-check start signal was received and
there are no error records.
nd
· · · Repeated
As for indoor unit,
refer to indoor
units service
manual.
For details, check
the LED display
of the outdoor
controller board.
27
11-4. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is turned on>
Error Code
None—
Abnormal points and detection method
1 No voltage is supplied to terminal
block(TB1) of outdoor unit.
a) Power supply breaker is
turned off.
b) Contact failure or disconnec-
tion of power supply
terminal
c) Open phase (L or N phase)
2 Electric power is not supplied
to power supply terminal of outdoor power circuit board.
a) Contact failure of power
supply terminal
b) Open phase on the outdoor
power circuit board
:Disconnection of connector
TABT or TABS
3 Electric power is not supplied to
outdoor controller circuit board.
a) Disconnection of connector
(CNDC)
4 Disconnection of reactor (DCL)
(Note 1) Refer to indoor unit section for code P and code E. (P.33~35)
Case
1 Check following items.
a) Power supply breaker
b) Connection of power supply terminal block
(TB1)
c) Connection of power supply terminal block
(TB1)
2 Check following items.
a) Connection of power supply terminal block
(TB1)
b) Connection of terminal on outdoor
Disconnection of connector TABT or TABS
Refer to 11-9.
3 Check connection of the connector (CNDC)
on the outdoor controller circuit board.
Check connection of the connector (CNDC)
on the outdoor power circuit board
Refer to 11-9.
4 Check connection of reactor. (DCL)
Check connection of “L1” and “L2” on the
active filter module.(ACTM)
Judgment and action
power circuit board
F5
(5201)
63H connector open
Abnormal if 63H connector circuit is open
for 3 minutes continuously after power supply.
63H: High-pressure switch
5 Disconnection of outdoor noise
filter circuit board or parts failure in outdoor noise filter circuit
board
It is especially needed to check
the resistance RS1 on the noise
filter cuircuit board.
6 Defective outdoor power circuit
board
7 Defective outdoor controller
circuit board
1 Disconnection or contact failure
of 63H connector on outdoor
controller circuit board
2 Disconnection or contact failure
of 63H
3 63H is working due to defective
parts.
4 Defective outdoor controller
circuit board
5 a) Check connection of outdoor noise filter
circuit board.
b) Replace outdoor noise filter circuit board.
Refer to 11-9.
6 Replace outdoor power circuit board.
7 Replace outdoor controller circuit board (When
items above are checked but the units cannot
be repaired).
1 Check connection of 63H connector on
outdoor controller circuit board.
Refer to 11-9.
2 Check the 63H side of connecting wire.
3 Check continuity by tester.
Replace the parts if the parts are defective.
4 Replace outdoor controller circuit board.
28
Error Code
EA
(6844)
Eb
(6845)
EC
(6846)
Abnormal points and detection method Judgment and action
Indoor/outdoor unit connector
miswiring, excessive number of units (4
units or more)
1. Outdoor controller circuit board can
automatically check the number of
connected indoor units. Abnormal if the
number cannot be checked automatically
due to miswiring of indoor/outdoor unit
connecting wire and etc. after power is
turned on for 4 minutes.
2. Abnormal if outdoor controller circuit
board recognizes the number of
connected indoor units as “4 units or
more”.
Miswiring of indoor/outdoor unit
connecting wire (converse wiring or disconnection)
Outdoor controller circuit board can
automatically set the unit number of indoor
units.
Abnormal if the indoor unit number can
not be set within 4 minutes after power on
because of miswiring (converse wiring or
disconnection) of indoor/outdoor unit connecting wire.
Start-up time over
The unit cannot finish start-up process
within 4 minutes after power on.
1 Contact failure or miswiring of
indoor/outdoor unit connecting
wire
2 Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
3 4 or more indoor units are
connected to one outdoor unit.
4 Defective transmitting receiving
circuit of outdoor controller
circuit board
5 Defective transmitting receiving
circuit of indoor controller board
6 Defective indoor power board
7 2 or more outdoor units have
refrigerant address “0” .
(In case of group control)
8 Noise has entered into power
supply or indoor / outdoor unit
connecting wire.
1 Contact failure or miswiring of
indoor/outdoor unit connecting
wire
2 Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
4 Defective transmitting receiving
circuit of outdoor controller circuit
board
5 Defective transmitting receiving
circuit of indoor controller board
6 Defective indoor power board
7 2 or more outdoor units have
refrigerant address “0” .
(In case of group control)
8 Noise has entered into power
supply or indoor/outdoor unit
connecting wire.
1 Contact failure of indoor/
outdoor unit connecting wire
2 Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
7 2 or more outdoor units have
refrigerant address “0” .
(In case of group control)
8 Noise has entered into power
supply or indoor/outdoor unit
connecting wire.
Case
1 Check disconnection or looseness or polar-
ity of indoor/outdoor unit connecting wire of
indoor and outdoor units.
2 Check diameter and length of indoor/outdoor
unit connecting wire.
Total wiring length: 80m
(including wiring connecting each indoor unit
and between indoor and outdoor unit)
Also check if the connection order of flat
cable is S1, S2, S3.
3 Check the number of indoor units that are
connected to one outdoor unit. (If EA is
detected.)
4~6 Turn the power off once, and on again to
check.
Replace outdoor controller circuit board,
indoor controller board or indoor power
board if abnormality occurs again.
7 Check if refrigerant addresses (SW1-3 to
SW1-6 on outdoor controller circuit board)
are overlapping in case of group control
system.
8 Check transmission path, and remove the
cause.
w The descriptions above, 1-8, are for EA, Eb
and EC.
29
<Abnormalities detected while unit is operating>
Error Code
U1
(1302)
U2
(1102)
Abnormal points and detection method
High pressure (High-pressure switch
63H worked)
Abnormal if high-pressure switch 63H
worked ( w ) during compressor operation.
w 4.15 MPa
63H: High-pressure switch
High discharging temperature
(1) Abnormal if discharge temperature
thermistor (TH4) exceeds 125: or
110: continuously for 5 minutes.
Abnormal if condenser/evaporator
temperature thermistor (TH5) exceeds
40: during defrosting and discharge
temperature thermistor (TH4) exceeds
110:.
(2) Abnormal if discharge super heat
(Cooling: TH4 – TH5/Heating: TH4 –
TH6) increases.
All the conditions in A or B are detected
simultaneously for 10 minutes
continuously after 6 minutes past from
compressor start-up (including the
thermostat indication or recovery from
defrosting).
<Condition A>
• Heating mode
• When discharge super heat is less
than 70 deg.
• When the TH6 temp is more than the
value obtained by TH7 – 5 deg.
• When the condensing temp of TH5 is
less than 35:.
Case
1 Short cycle of indoor unit
2 Clogged filter of indoor unit
3 Decreased airflow caused by
dirt of indoor fan
4 Dirt of indoor heat exchanger
5 Locked indoor fan motor
6 Malfunction of indoor fan motor
7 Defective operation of stop
valve (Not fully open)
8 Clogged or broken pipe
9 Locked outdoor fan motor
0 Malfunction of outdoor fan
motor
1 Short cycle of outdoor unit
2 Dirt of outdoor heat exchanger
3 Decreased airflow caused by
defective inspection of outside
temperature thermistor