Mitsubishi PS-3GJA1, PS-4GJSA1 Service Manual

SPLIT-TYPE AIR CONDITIONERS
ADVANCED AND EVER ADVANCING
TECHNICAL & SERVICE MANUAL
1997
No. OC141
Floor StandingSeries PS
Indoor unit [Model names]
PS-3GJA PS-4GJSA
[Service Ref.]
PS-3GJA PS-4GJSA
This manual does not cover the following outdoor units. When serving them, please refer to the service manual No. OC149 and this manual in a set.
[Service Ref.] PU-3VJA PU-3YJA PU-3NJA PU-4VLJSA PU-4YJSA PU-4TJSA
CONTENTS
1. FEATURES..........................................2
2. PART NAMES AND FUNCTIONS ......3
3. SPECIFICATIONS...............................5
4. DATA ...................................................7
5. OUTLINES AND DIMENSIONS ........10
6. WIRING DIAGRAM ...........................12
7.
REFRIGERANT SYSTEM DIAGRAM
8. OPERATION FLOW-CHART ............14
9. MICROPROCESSOR CONTROL .....17
10. TROUBLESHOOTING ......................25
11. DISASSEMBLY PROCEDURE .........27
12. PARTS LIST......................................30
13. OPTIONAL PARTS ...........................34
2.UK
2.UK
1.UK
2.UK
2.UK
1.UK
..13
The Slim Line. From Mitsubishi Electric.
1 FEATURES
i
.
Floor StandingSeries PS
(The controller is built in the indoor unit)
Indoor unit
controller
Service Ref. Cooling capacity/50/60Hz
W Btu/h
PS-3GJA PS-4GJSA
Rating condition (JIS B8616)
Indoor : 27°CDB, 19°CWB Outdoor : 35°CDB, 24°CWB
1 7,200/7,900 24,600/27,000
1 9,800/10,900 33,400/37,200
1. OPTIMAL PERFORMANCE AND EFFICIENT MAINTENANCE
(1) PEACEFUL SILENCE THROUGH WHISPER-QUIET OPERATION
This top quality floor-standing model guarantees near-silent operation through a newly developed low-noise fan. Air-duct design has also been optimized through the adoption of microslit fans. Perfect for shops and office meeting-rooms.
(2) LONG LIFE FILTER
The long life filter allows 2,500 hours of maintenance-free operation in office environments not so dusty.
(3) SMOOTH REMOVAL
An open grill system permits filters to be removed smoothly and easily.
(4) EASY CLEANING
Dirt can be cleaned off simply because vanes are flockless.
2. INSTALLATION TIME GREATLY REDUCED
(1) EFFECTIVE PIPE CONNECTION
Raising the pipe connection position facilitates pipe arrangement, thus shortening installation time.
(2) CONVENIENT WIRING
A raised wire connection position means that wiring work can be conveniently implemented.
(3) WEIGHT REDUCTION
The use of plastics as assembly materials has realized a reduction in weight of 22kg. (PS-5 GJSA 72kg ➔ 51kg)
(4) PIPE DIRECTIONS
Pipes can be installed in four directions (rear, left, right, and bottom sides.)
2
PART NAMES AND FUNCTIONS2
Disperses air up and down
Disperses air left and right.
Removes dust and pollutants from inhaled air.
(Inhales air from room.)
Indoor (Main) Unit PS-3GJA
PS-4GJSA1
1
3
Controller
i
.
Settings remain in effect' until changed. The air conditioner can be operated by simply pressing ON/OFF button once settings have been made.
TIMER/TEMP. button
This button is used to
change between display of room temperature and
display of remaining time
on the timer during “AUTO
STOP” operation. Green lamps light in selected display mode.
Lamps display remaining time on the timer or room temperature. Remaining timer time display
Lamps indicate time remaining
until timer stops operation. Green lamps display the
remaining number of hours.
Room temperature display
Lamps display temperature
settings actual room
temperatures.
Temperature settings :
Green lamps light.
Temperature in room :
Green lamps flash.
(Example display readings are
for explanations only, so actual
display readings will differ.)
Display panel
Operating panel
UP and DOWN buttons
Temperature control (While green “TEMP” lamp
is lighting.) Use UP and DOWN buttons to set desired temperature between 18 and 29 °C.
Timed operation (While green “TIMER“ lamp is
lighting.) Use UP and DOWN buttons to set timed operation between one and twelve hours.
ON/OFF button
Pressing button starts operation. Pressing again stops operation. Green lamp remains lit during operation.
MODE SELECT button
This button is used to change between cooling, DRYING and ventilation operation modes. One of three green lamps lights to indicate mode in effect.
FAN SPEED button
This button is used to change between low and high fan speeds. One of two green lamps lights to indicate which fan speed is in effect.
LOUVER button
This button is used to switch swing louver ON/OFF.
TIMER MODE button
Used to select timed starting or stopping. Green lamp lights to indicate timer mode selected.
Attention
Pressing the UP and DOWN buttons together for more than two seconds will initiate the “test run” or “self-diagnostic” mode. Avoid pressing these buttons simultaneously during normal operation. Press the ON/OFF button to cancel test run or self­diagnostic mode.
All green lamps turn off when air conditioner is OFF.
Avoid operation of buttons with fingernails or other sharp objects. Sharp objects may scratch operating panel.
4
SPECIFICATIONS3
Cooling capacity W1
Total input (50/60Hz) Indoor
unit
Cooling capacity (SSA) W2
Outdoor
unit
Service Ref.
External finish Fan motor output
Airflow Hi-Lo
External static pressure Operation control & Thermostat
Noise level High-Low
Cond. drain connection O.D.
Dimensions
Weight
Service Ref.
External finish Refrigerant (R-22) control
Crankcase heater Compressor output Protection devices Fan motor output
Air flow
Noise level
Dimensions
Weight
50Hz
60Hz
50Hz
60Hz
50Hz 60Hz
H
W
D
60Hz
50/60Hz
50Hz 60Hz
50/60Hz
W
D H
W
Btu/h
W
Btu/h
kW
kW
m
3
/min
CFM
m
3
/min
CFM
mmAq,Pa
dB (A)
dB (A) mm (in.) mm (in.) mm (in.) mm (in.)
kg (lbs)
W
Btu/h
W
kW
kW
m
3
/min(CFM)
m
3
/min(CFM)
dB (A) mm (in.) mm (in.) mm (in.)
kg (lbs)
Service Ref.
Item
7,200
24,600
7,900
27,000
6,800
23,200
3.32/3.60
Munsell 0.70 Y 8.59/0.97
PS-3GJA
1 PS-4GJSA1
0.03
17 -14
600 - 494
17 -14
600 - 494
0 (Direct blow)
Built-in 42 - 37 42 - 37
26(1)
1900(74 - 13/16)
600(23 - 5/8) 270(10 - 5/8)
43(95)
Munsell 5Y 7/1
Capillary tube
PU-3VJA2.UK,3YJA2.UK,3NJA1.UK
PU-4VLJSA2.UK,4YJSA2.UK,4TJSA1.UK
32/32
2.2 W5
0.085 50 (1765) 50 (1765)
52/53
870 (34-1/4)
295(11 - 5/8)
850 (33-7/16)
73 (161)
PS-4GJSA
1
9,800 33,400 10,900 37,200
9,400 32,000
3.57/4.53
0.07
28 - 22
988 - 776
30 - 22
1059 - 776
47 - 42 48 - 42
26(1)
1900(74 - 13/16)
600(23 - 5/8) 350(13 - 3/4)
51(112)
32/32
2.7
0.065 + 0.065 95 (3352) 95 (3352)
54/55
870 (34-1/4)
295(11 - 5/8)
1,258 (49-1/2)
94 (207)
PS-3GJA
1
1. STANDARD SPECIFICATIONS
Notes :
W1 Rating conditions (JIS B8616) W4 Capacity of crankcase heater (W) based on 220 volts.
Indoor : 27°C (80°F) DB, 19°C (66°F)WB W5V, N Outdoor : 35°C (95°F) DB, 24°C (75°F)WB T, Y Refrigerant piping length (one way) : 5m (16ft) Thermal relay (PU-3YJSA
W2 Rating conditions (SSA 385, 386) VL
Indoor : 29°C (84°F) DB, 19°C (66°F)WB Thermal switch. Outdoor : 46°C (115°F) DB, 24°C (75°F)WB
W3 Total input bassed on indicated voltage
Service Ref.
50Hz 60Hz
PS-3GJA1
1ph 220V/1ph 220V 1ph 220V/1ph 220V
(Indoor / Outdoor)
PS-4GJSA1
1ph 220V/3ph 380V 1ph 220V/3ph 220V
...
Inner thermostat, HP switch, LP switch.
...
Thermal switch, Reversed-phase protector, HP switch, LP switch,
...
Inner thermostat,HP switch,LP switch
2, PU-4YJSA2, PU-4TJSA2)
5
2. POWER SUPPLY & MODEL NAMES
50Hz
60Hz
1 ph. 3 ph. 1 ph. 3 ph.
220, 230, 240V 380/220, 400/230, 415/240V 220V 220V
PU-3VJA
2.UK
PU-3YJA2.UK PU-3NJA1.UK
PU-4VLJSA
2.UK
PU-4YJSA2.UK
PU-4TJSA
1.UK
PS-3GJA1 PS-4GJSA1
Service Ref. (Indoor unit)
Service Ref. (Outdoor unit)
Power supply
Service Ref.
Current Input Starting current Outdoor unit
A
kW
A
V : 220V 50Hz
PS-3GJA
1
0.64
0.14
0.8
PU-3
PS-4GJSA
1
1.02
0.22
1.5
PU-4
V : 230V 50Hz
PS-3GJA
1
0.66
0.15
1.5
PU-3
PS-4GJSA
1
1.06
0.24
1.5
PU-4
Power supply (1 Phase)
Service Ref.
Current Input Starting current Outdoor unit
A
kW
A
V : 240V 50Hz
PS-3GJA
1
0.68
0.16
0.8
PU-3
PS-4GJSA
1
1.10
0.26
1.5
PU-4
Power supply (1 Phase)
N : 220V 60Hz
0.73
0.16
0.8
PU-3
1.20
0.26
1.5
PU-4
PS-3GJA
1 PS-4GJSA1
Service Ref.
Current Input Starting current Outdoor unit
A
kW
A
N : 220V 60Hz
PS-3GJA
1
0.73
0.16
0.8
PU-3
PS-4GJSA
1
1.20
0.26
1.5
PU-4
Power supply (1 Phase)
Notes : 1. Power supply key N
.......
1ph, 220V,60Hz T
...
V(L)
1ph, 220, 230, 240V 50Hz Y
2. Primary power supplies for all indoor units are single-phase. 50Hz, 4 wires
3. ELECTRICAL SPECIFICATIONS
(1). Rating conditions -JIS B 8616 Series PS Indoor Unit (Single Phase)
Indoor : 27°C (80°F) DB, 19°C (66°F) WB
{
Outdoor : 35°C (95°F) DB
...
3ph. 220V, 60Hz
...
3ph. 380/220, 400/230, 415/240V,
(2). Rating conditions -SSA385,386
Series PS Indoor Unit (Single Phase)
6
Indoor : 29°C (84°F) DB, 19°C (66°F) WB
{
Outdoor : 46°C (115°F) DB,24°C (75°F) WB
DATA4
Indoor WBOutdoor DB
PS-3GJA
1
T.C.
C.F.
(T.I.)
PS-4GJSA
1
T.C.
C.F.
(T.I.)
Service Ref.
Temperature
16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C
19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C
(60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F)
(66.2$F)
(67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F)
7.2
7.7
7.9
8.0
8.2
8.7
7.1
7.5
7.8
7.9
8.0
8.5
6.8
7.3
7.5
7.6
7.7
8.2
6.7
7.1
7.4
7.5
7.6
8.1
6.5
7.0
7.2
7.3
7.4
7.9
6.2
6.7
6.9
7.0
7.1
7.6
6.2
6.6
6.9
6.9
7.1
7.6
5.9
6.4
6.6
6.7
6.8
7.3
5.9
6.3
6.5
6.6
6.7
7.2
5.6
6.0
6.2
6.3
6.5
6.9
5.5
5.9
6.1
6.2
6.3
6.8
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
9.8
10.5
10.8
10.9
11.1
11.8
9.6
10.2
10.6
10.7
10.9
11.6
9.3
9.9
10.2
10.3
10.5
11.2
9.1
9.7
10.0
10.2
10.3
11.0
8.9
9.5
9.8
9.9
10.1
10.8
8.5
9.1
9.4
9.5
9.7
10.3
8.4
9.0
9.3
9.5
9.6
10.3
8.1
8.6
8.9
9.1
9.3
9.9
8.0
8.6
8.9
9.0
9.2
9.8
7.6
8.2
8.5
8.6
8.8
9.4
7.4
8.0
8.3
8.4
8.6
9.2
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
21$C (69.8$F)
25$C (77$F)
30$C (86$F)
32.2$C (90$F)
35$C (95$F)
40$C (104$F)
40.6$C (105$F)
45$C (113$F)
46$C (115$F)
50$C (122$F)
52$C (125.5$F)
17
0.10
0.70
28
0.16
0.76
Evaporator airflow (CMM)
Bypass factors
S.H.F. at rating conditions
PS-3GJA1 PS-4GJSA1
Refrigerant piping Iength (one way)
5m (16ft)
1.0
1.0
10m (33ft)
0.978
0.984
5m (49ft)
0.962
0.974
20m (66ft)
0.948
0.964
25m (82ft)
0.934
0.954
30m (98ft)
0.921
0.944
35m (115ft)
0.935
40m (131ft)
0.926
45m (148ft)
— —
Service Ref.
1. PERFORMANCE DATA
Cooling capacity
50Hz
Notes : 1. T.C. : Total capacity ( 103W)
Cooling capacity correction factors
C.F. (T.I.) : Correction factors of Total input (Indoor unit input + Outdoor unit input)
2. (°F) = 32 + 9 / 5 (°C)
3. Guaranteed operating range (cooling)
...
(Btu / h)
. =
. (W) 3.4, (kcal / h) = (W) 0.86
Lower limit ... Indoor : 21°C (70°F) DB, 15.5°C (60°F) WB, Outdoor : 21°C (70°F) DB.
{
Upper limit
50Hz
...
Indoor : 35°C (95°F) DB, 22.5°C (72.5°F) WB, Outdoor : 52°C (125.5°F) DB.
WVL
...
Outdoor : 46°C (115°F) DB.
7
Cooling capacity
60Hz
Service Ref.
Temperature
Indoor WBOutdoor DB
21$C (69.8$F)
25$C (77$F)
30$C (86$F)
32.2$C (90$F)
35$C (95$F)
40$C (104$F)
40.6$C (105$F)
45$C (113$F)
46$C (115$F)
50$C (122$F)
52$C (125.5$F)
16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C
19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C 22$C 16$C 18$C 19$C
19.4$C 20$C
22$C
(60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F)
(66.2$F)
(67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F) (71.6$F) (60.8$F) (64.4$F) (66.2$F) (67$F) (68$F)
(71.6$F)
Evaporator airflow (CMM)
Bypass factors
S.H.F. at rating conditions
Notes : 1. T.C. : Total capacity ( 103W)
C.F. (T.I.) : Correction factors of Total input (Indoor unit input + Outdoor unit input)
2. (°F) = 32 + 9 / 5 (°C)
3. Guaranteed operating range (cooling)
...
(Btu / h)
PS-3GJA
T.C.
7.9
8.4
8.7
8.8
9.0
9.5
7.8
8.3
8.5
8.6
8.8
9.4
7.5
8.0
8.2
8.3
8.5
9.0
7.3
7.8
8.1
8.2
8.3
8.9
7.2
7.6
7.9
8.0
8.2
8.7
6.8
7.3
7.6
7.7
7.8
8.3
6.8
7.3
7.5
7.6
7.8
8.3
6.5
7.0
7.2
7.3
7.5
8.0
6.4
6.9
7.1
7.2
7.4
7.9
6.2
6.6
6.9
6.9
7.1
7.6
6.0
6.5
6.7
6.8
6.9
7.4
. =
. (W) 3.4, (kcal / h) = (W) 0.86
Lower limit ... Indoor : 21°C (70°F) DB, 15.5°C (60°F) WB, Outdoor : 21°C (70°F) DB.
{
Upper limit
1
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
17
0.10
0.69
...
Indoor : 35°C (95°F) DB, 22.5°C (72.5°F) WB, Outdoor : 52°C (125.5°F) DB.
1.31
T.C.
10.9
11.7
12.0
12.2
12.4
13.1
10.7
11.4
11.8
11.9
12.1
12.9
10.3
11.0
11.3
11.5
11.7
12.5
10.1
10.8
11.2
11.3
11.5
12.3
10.5
10.9
11.0
11.3
12.0
10.1
10.4
10.6
10.8
11.5
10.0
10.4
10.5
10.7
11.4
10.0
10.1
10.3
11.0
10.0
10.2
10.9
10.5
10.3
9.9
9.4
9.4
9.0
9.6
8.9
9.5
9.9
8.5
9.1
9.5
9.6
9.8
8.3
8.9
9.2
9.4
9.6
PS-4GJSA
1
30
0.16
0.74
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
Cooling capacity correction factors
Service Ref.
PS-3GJA1 PS-4GJSA1
8
5m (16ft)
1.0
1.0
10m (33ft)
0.971
0.980
60Hz
5m (49ft)
0.950
0.966
Refrigerant piping Iength (one way) 20m (66ft)
0.931
0.952
25m (82ft)
0.913
0.939
30m (98ft)
0.896
0.926
35m (115ft)
0.914
40m (131ft)
0.902
45m (148ft)
— —
Mode
Total
Electrical circuit
Refrigerant circuit
Indoor unit
Outdoor
unit
Capacity
Input
Indoor unit Service Ref.
Phase, Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase, Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discahrge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
W
kW
$C
$C
$C
m
DB$C
WB$C
DB$C
DB$C
WB$C
PS-3GJA
1
Cooling
7,200
3.32
PS-3GJA
1
1, 50
220
0.64
PU-3VJA
2.UK
1, 50
220
15.1
61.5
2.6
5.8
5
27
19
12.3
35
24
Cooling
7,900
3.60
1, 60
220
0.73
PU-3NJA
1.UK
1, 60
220
17.6
70.1
5.5
4.0
5
27
19
11.5
35
24
PS-4GJSA
1
Cooling
9,800
3.57
PS-4GJSA
1
1, 50
220
1.02
PU-4YJSA
2.UK
3, 50
380
5.7
64.9
48.9
6.3
5
27
19
14.1
35
24
Cooling
10,900
4.53
1, 60
220
1.20
PU-4TJSA
1.UK
3, 60
220
12.2
75.0
52.0
4.9
5
27
19
14.6
35
24
Service Ref.
V
A
V
A
MPa·G
(Of/F·G)
MPa·G
(Of/F·G)
2.0
(20.4)
2.14
(21.8)
1.83
(18.7)
1.99
(20.3)
0.47 (4.8)
0.45 (4.6)
0.50 (5.1)
0.47
(4.8)
3. STANDARD OPERATION DATA
PS-3GJA1
PS-4GJSA1
Outdoor unit precharged (kg)
(up to 20)
V…3.08,Y…2.88,N…3.5
VL…3.8,Y…4.6, T…4.6
0.06(0.13)
0.15(0.33)
0.12(0.26)
0.30(0.66)—0.45(0.99)—0.6(1.32)
— —
25m(82ft) 30m(98ft) 35m(115ft) 40m(131ft) 45m(148ft)
Piping length(one way)
20m(66ft)
0 0
Service Ref.
Standard
Air flow m3/min
Air speed m/sec
Coverage range m
PS-3GJA
1
17
2.6
8.4
PS-4GJSA
1
28
4.2
13.6
The unit or pressure has been changed to Mpa based on the international SI system. The conversion factor is :
4. ADDITIONAL REFRIGERANT CHARGE (R-22 : kg (Ibs))
5. OUTLET AIR SPEED AND COVERAGE RANGE
1(Mpa·G)=10(Of/F·G)
9
5 OUTLINES AND DIMENSIONS
125
240
Front side
Metal fixture
against overturning
controller
Rear side
Front side
Rear side
Knock out hole
for branch duct
Knock out hole
for bottom fixing
Knock out hole
for under-piping
Knock out hole for
under-piping(120 70 oval)
100
10 3838
50260
130130
766
1900
608
50
115
714 123
767
110
480
590
216
40
82730
2010
111
15
130
132
277
160
20
218
175
90
55143
100
340
370
520
260
240
130 71
530
600
270
250
70
180
235
Knock out hole for
wiring. 27
(Provided on both sides)
Knock out hole for refrigerant and drainage.
90 60 oval (Provided on both sides)
Knock out hole for piping and wiring
(140 80 oval)
20
105
Terminal block
for control
Electrical parts box
Liquid pipe 9.52(3/8F)
1. Service access allows for
insertion of screw driver.
2. Adjustable
Gas pipe 15.88(5/8F)
Drain pipe
Terminal block
for power supply
95
46122
47
95
40 66
186
100 or more 100 or more
2
5 or more
1
300 or more
Front 1,000 or more
1. INDOOR UNIT PS-3GJA
1
Unit : mm
10
PS-4GJSA1
125
240
Front side
Metal fixture
against overturning
controller
Rear side
Front side
Rear side
Knock out hole
for branch duct
Knock out hole
for bottom fixing
Knock out hole
for under-piping
Knock out hole for
under-piping(120 70 oval)
100
10 3838
50260
130130
766
1900
608
50
115
714 123
767
110
480
590
216
40
82730
2010
111
15
130
132
277
120
20
218
255
140
77
201
120
340
370
520
260
240
130 71
530
600
350
330
70
260
315
Knock out hole for
wiring. 27 (Provided on both sides)
Knock out hole for refrigerant and drainage.
90 60 oval (Provided on both sides)
Knock out hole for piping and wiring
(140 80 oval)
20
105
Terminal block
for control
Electrical parts box
Liquid pipe 9.52(3/8F)
1. Service access allows for
insertion of screw driver.
2. Adjustable
Gas pipe 19.05(3/4)
Drain pipe
Terminal block
for power supply
95
46122
47
95
40 66
261
100 or more 100 or more
2
5 or more
1
300 or more
Front 1,000 or more
Unit : mm
11