Mitsubishi PRH-P8MYA, PRH-P10MYA, PRH-P16MYA, PRH-P20MYA TECHNICAL MANUAL

TECHNICAL & SERVICE MANUAL
AIR-COOLED ROOFTOP PACKAGED AIR CONDITIONERS
For use with the R407C
2004
HEAT PUMP PRH-P8MYA
Models
<Unit>
....................................
...................................
..............................................................................................................................
................................................................................................................
.........................................................................................................................
.....................................................................................................
.....................................................................................
..................................................................................
............................................................................................
....................................................................................................................
.................................................................................................................
.......................................................................................................
.........................................................................................................
...........................................................................................
....................................................................................................................................
.......................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
..............................................................................................
...........................................
.......................................................................................................
.........................................................................
..............................................................................................................
...............................................................................................................
...........................................................................................................................
........................................................................................................................
.................................................................................................
.............................................................................................................
...........................................................................................................
................................................................................................................
..................................................................................................
Contents
Page
1
PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANT
[1] Necessary Apparatus and Materials and Notes on Their Handling [2] Brazing [3] Airtightness T est [4] Vacuuming [5] Charging of Refrigerant
2
TYPICAL INSTALLATION EXAMPLE
3
MODEL-DESIGNATION BREAKDOWN
4
PART NAMES AND FUNCTIONS
5
SPECIFICATIONS
6
ELECTRICAL DATA
7
EXTERNAL DIMENSIONS
8
REMOTE CONTROLLER
9
ELECTRICAL WIRING DIA GRAM
[1] Unit [2] Skeleton of Transmission Line Connection
0
Technical Data to Meet LVD
[1] Standard Operation Data [2] Cooling Capacity Curves [3] Heating Capacity Curves [4] Reduction Ratio by Frosting [5] Capacity/Input Ratio against Changes in Room Airflow Rate [6] Bypass Factor Curves [7] Cooling Sensible Heating Capacity Table [8] Fan Performance [9] Center of Gravity [10] NC Curve
A SERVICE DATA
[1] Appearance of Equipment [2] Refrigerant Circuit [3] Refrigerant Charge [4] Operation Range [5] Safety & Control Devices
1 2 3 4 4 5 6 6 7
9 11 12 14 15 15 16 17 17 19 19 19 20 22 22 24 30 32 34 34 38 38 38 39
................................................................................................................................
......................................................................................................
........................................................................................................
........................................................
............................................................
...............................................................................................
.................................................................................................................
............................................................................................
........................................................................................................
...................................................................................
....................................................................................................................................
...................................................................................................................
...........................................................................................................
....................................................................................................................
..............................................................................................
.......................................................................................................................
.............................................................................................
........................................................................................................
..............................................................................................................
...................................................................................................................
.......................................................................................................................
......................................
........................................................................................
Page
B CONTROL
[1] Composition of Control [2] Control specifications [3] Function of switches and connectors (outdoor-side) [4] Function of switch on indoor-side controller board [5] Simple parts check method [6] Reference Data [7] Troubleshooting of each part [8] Emergency operation [9] Self-diagnosis and troubleshooting
C Test run
[1] Before test run [2] Test run procedures [3] Self-diagnosis [4] Remote controller diagnosis
D INSTALLATION
[1] Space required around units [2] Installation of the unit [3] Duct construction [4] Lifting method [5] Drain piping [6] Modification method of fan direction (From side flow to top flow) [7] The putting condition of the belt
40 40 41 45 52 53 54 55 58 60 70 70 70 73 75 76 76 78 79 80 81 82 83
1
PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANT
Caution
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
• The refrigerator oil will degrade if it is mixed with a large amount of mineral oil.
Use liquid refrigerant to seal the system.
• If gas refrigerant is used to seal the system, the com­position of the refrigerant in the cylinder will change and performance may drop.
Do not use a refrigerant other than R407C.
• If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerator oil to de­teriorate.
Be especially careful when managing the tools.
• If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
If the refrigerant leaks, recover the refrigerant in the refrigerant cycle, then recharge the cycle with the specified amount of the liquid refrigerant indicated on the air conditioner.
•Since R407C is a nonazeotropic refrigerant, if addi­tionally charged when the refrigerant leaked, the com­position of the refrigerant in the refrigerant cycle will change and result in a drop in performance or abnor­mal stopping.
Use a vacuum pump with a reverse flow check valve.
• The vacuum pump oil may flow back into the refriger­ant cycle and cause the refrigerator oil to deteriorate.
Do not use the following tools that have been used with conventional refrigerants. (Gauge manifold, charge hose, gas leak detector, re­verse flow check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment)
• If the conventional refrigerant and refrigerator oil are mixed in the R407C, the refrigerant may deterio­rated.
• If water is mixed in the R407C, the refrigerator oil may deteriorate.
• Since R407C does not contain any chlorine, gas leak detectors for conventional refrigerants will not react to it.
Do not use a charging cylinder.
• Using a charging cylinder may cause the refrigerant to deteriorate.
- 1 -
[1] Necessary Apparatus and Materials and Notes on Their Handling
The following tools should be marked as dedicated tools for R407C.
<<Comparison of apparatus and materials used for R407C and for R22>>
Apparatus Used Use R22 R407C
Gauge manifold Evacuating, refrigerant filling Current product Charging hose Operation check Current product Charging cylinder Refrigerant charging Current product Do not use Gas leakage detector Gas leakage check Current product Shared with R134a Refrigerant collector Refrigerant collection R22 For R407C use only Refrigerant cylinder Refrigerant filling R22 Identification of dedi-
cated use for R407C: Record refrigerant name and put brown belt on upper part of cylinder.
Vacuum pump Vacuum drying Current product Can be used by attach-
ing an adapter with a
check valve. Vacuum pump with a check valve Current product Flare tool Flaring of pipes Current product Bender Bending of pipes Current product Application oil Applied to flared parts Current product Ester oil or Ether oil or
Alkybenzene (Small
amount) Torque wrench Tightening of flare nuts Current product Pipe cutter Cutting of pipes Current product Welder and nitrogen cylinder Welding of pipes Current product Refrigerant charging meter Refrigerant charging Current product Vacuum gauge Checking the vacuum degree Current product
Symbols: To be used for R407C only. Can also be used for conventional refrigerants.
Tools for R407C must be handled with more care than those for conventional refrigerants. They must not come into contact
with any water or dirt.
- 2 -
[2] Brazing
No changes from the conventional method, but special care is required so that foreign matter (ie. oxide scale, water, dirt, etc.) does not enter the refrigerant circuit.
Example: Inner state of brazed section
When non-oxide brazing was not used When non-oxide brazing was used
Items to be strictly observed:
1. Do not conduct refrigerant piping work outdoors on a rainy day.
2. Apply non-oxide brazing.
3. Use a brazing material (BCuP-3) which requires no flux when brazing between copper pipes or between a copper pipe and copper coupling.
4. If installed refrigerant pipes are not immediately connected to the equipment, then braz e and seal both ends of them.
Reasons:
1. The new refriger ant oil is 10 times more hygroscopic than the conventional oil. The probability of a machine failure if water infiltrates is higher than with conventional refrigerant oil.
2. A flux generally contains chlorine. A residual flux in the refrigerant circuit may generate sludge.
Note:
Commercially available antioxidants may have adverse effects on the equipment due to its residue, etc. When
applying non-oxide brazing, use nitrogen.
- 3 -
[3] Airtightness Test
No changes from the conventional method. Note that a refrigerant leakage detector for R22 cannot detect R407C leakage.
Halide torch R22 leakage detector
Items to be strictly observed:
1. Pressurize the equipment with nitrogen up to the design pressure and then judge the equipment’ s airtightness, taking temperature variations into account.
2. When investigating leakage locations using a refrigerant, be sure to use R407C.
3. Ensure that R407C is in a liquid state when charging.
Reasons:
1. Use of oxygen as the pressurized gas may cause an explosion.
2. Charging with R407C gas will lead the composition of the remaining refrigerant in the cylinder to change and this refrigerant can then not be used.
Note:
•A leakage detector for R407C is sold commercially and it should be purchased.
[4] Vacuuming
1. Vacuum pump with check valve A vacuum pump with a check valve is required to prevent the vacuum pump oil from flowing back into the refrigerant circuit when the vacuum pump power is turned off (power failure). It is also possible to attach a check valve to the actual vacuum pump afterwards.
2. Standard degree of vacuum for the vacuum pump Use a pump which reaches 0.5 Torr (500 MICRON) or below after 5 minutes of operation. In addition, be sure to use a vacuum pump that has been properly maintained and oiled using the specified oil. If the vacuum pump is not properly maintained, the degree of vacuum may be too low.
3. Required accuracy of the vacuum gauge Use a vacuum gauge that can measure up to 5 Torr. Do not use a general gauge manifold since it cannot measure a vacuum of 5 Torr.
4. Evacuating time
•Evacuate the equipment for 1 hour after –755 mmHg (5 Torr) has been reached.
After envacuating, leave the equipment for 1 hour and make sure the that vacuum is not lost.
5. Operating procedure when the vacuum pump is stopped In order to prevent a backflow of the vacuum pump oil, open the relief valve on the vacuum pump side or loosen the charge hose to drawn in air before stopping operation.
The same operating procedure should be used when using a vacuum pump with a check valve.
NO
NO
- 4 -
[5] Charging of Refrigerant
R407C must be in a liquid state when charging, because it is a non-azeotropic refrigerant.
For a cylinder with a syphon attached For a cylinder without a syphon attached
Cylinder color identification R407C-Gray Charged with liquid refrigerant
R410A-Pink
Reasons:
1. R407C is a mixture of 3 refrigerants, each with a different evaporation temperature. Therefore, if the equipment is charged with R407C gas, then the refrigerant whose evaporation temperature is closest to the outside temperature is charged first while the rest of refrigerants remain in the cylinder.
Note:
In the case of a cylinder with a syphon, liquid R407C is charged without turning the cylinder up side down. Check the
type of cylinder before charging.
Cylin-
der
Cylin-
der
Valve
Valve
Liquid
Liquid
- 5 -
2
TYPICAL INSTALLATION EXAMPLE
3
MODEL-DESIGNATION BREAKDOWN
Series symbol Self-contained type (rooftop type)
Refrigerant P=R407C
Heat pump type
Series symbol Y=3-phase 380V,400V,415V,50Hz,3N~
Design sequence
Compressor horse power P8=8HP P10=10HP P16=16HP P20=20HP
Design sequence
Service reference
PRH
P R H P 1 0 M Y A E U
- 6 -
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
ßC
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
ßC
1Hr.
NOT AVAILABLE
STAND BY DEFROST
FILTER
CHECK
TEST
TEMP.
TIMER SET
1
2 3
3
0
1
2
Unit
• Return air : Sucks the ambient air in.
• Supply air : Blows the air back out into
Supply air
Return air
the room.
Remote controller (PAR-20MAA)
• Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
[Operation buttons]
[Room temperature adjustment] Button [Timer/continuous] Button [Selecting operation] Button [Time selection] Button [Time-setting] Button [Louver] Button (This button does not operate in this model) [Fan speed adjustment] Button [Up/down airflow direction] Button (This button does not operate in this model) [Ventilation] Button [Checking/built-in] Button [Test run] Button [Filter] Button (This button does not operate in this model) [ON/OFF] Button Position of built-in room temperature
•Never expose the remote controller to direct sunlight. Doing so can result in the erroneous measurement of room tem­perature.
•Never place any obstacle around the lower right-hand section of the remote controller. Doing so can result in the errone­ous measurement of room temperature.
456879
4
PART NAMES AND FUNCTIONS
1 2 3 4
5 6 7 8 9
0 1 2 3
- 7 -
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
ßC
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
ßC
1Hr.
NOT AVAILABLE
STAND BY DEFROST
TEMP.
D U T S Q C
GH JKLI
B A
R P
O N M
E
F
[Display]
Caution:
• Only the Power display lights when the unit is stopped and power supplied to the unit.
• When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a malfunction.
• When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button and
TEMP. adjustment button do not operate.
• “NOT AVAILABLE” is displayed when the Airflow direction button or Louver button are pressed. This indicates that this room unit is not equipped with the fan direction adjustment function and the louver function.
• When power is turned ON for the first time, it is normal that “H0” is displayed on the room temperature indication (For max. 2 minutes). Please wait until this “H0” indication disappear then start the operation.
A Current time/Timer C Centralized control D Abnormality control E Operation mode: COOL, AUTO,
FAN, HEAT
F Preparing f or Heating mode G Defrost mode H Set temperature I Power ON J Louver
K Not available function L Ventilation M Function setting mode N Test run mode O Error check mode P Filter sign Q Set effective for 1 hr. R Sensor position S Room temperature T Airflow U
Fan speed
- 8 -
5
SPECIFICATIONS
Model name PRH-P8MYA PRH-P10MYA Mode
Capacity
Cooling Heating Cooling Heating
20.9
kW
kcal/h
Btu/h
kW
A
CMM
Pa
kW
CMM
kW
kW
kW
mm
dB(A)
kg
23.7 26.0 30.5 18,000 19,000 22,400 26,200 71,430 75,400 88,890 104,000
R407C
3N~ 380/400/415V 50Hz
Convertible(Side flow<factory setting> or top flow)
Sirrocco fan x 2
8.12 8.02 10.22 9.82
14.7 14.5 18.8 18.2
19
°
C to 30°C 17°C to 28°C 19°C to 30°C 17°C to 28°C
70
100
59
407
5.5
Three-phase induction motor
1.1
90
100
60
412
7.5
1.5
Cross fin
Propeller fan x 1
185
Three-phase induction motor
0.38
Cross fin
Hermetic
FVC68D(ether oil)
0.05 (240V)
Polyester powder (MUNSELL 5Y8/1)
1,715 x 2,000 x 926
Field supplied
R1
Refrigerant Power source Electrical
characteristics
Power consumption Operating current
Type x Quantity Air flow rate External static pressure Motor type Motor output
Type x Quantity Air flow rate Motor type Motor output
Type Motor output Oil type Crankcase heater
H x W x D
Remote controller temperature setting range Indoor-side air flow direction Indoor-side fan
Indoor-side heat exchanger type
Outdoor-side fan
Outdoor-side heat exchanger type Compressor
External finish External dimension Air filter Drain pipe Thread Noise level Net weight Protection devices High pressure switch , Low pressure switch , fuse
Over current relay(compressor , indoor-side fan motor) inner thermal switch in outdoor-side fan motor
Note 1. Cooling and Hetaing capacity indicates the maximum value at operation under the following condition.
Cooling Indoor : 27
°
CDB/19°CWB Outdoor : 35°CDB
Heating Indoor : 20
°
CDB Outdoor : 7°CDB/6°CWB
2. The operating noise measuring point is 1m from the bottom of unit (1m from the front of the unit) in an anechoic room. (Noise level is A-scale value)
3. Refrigerant charge volumes are factory charged.
4. The range of working voltage is with in ±10% voltage of power supply.
5. Specification subject to change without notice.
Specifications of air-source heat pump type packaged air conditioner
(Rooftop unit)
- 9 -
Model name PRH-P16MYA PRH-P20MYA Mode
Capacity
Cooling Heating Cooling Heating
41.8
kW
kcal/h
Btu/h
kW
A
CMM
Pa
kW
CMM
kW
kW
kW
mm
dB(A)
kg
47.4 52.0 61.0
36,000 40,800 44,800 52,400
142,860 150,800 177,780 208,000
R407C
3N~ 380/400/415V 50Hz
Convertible(Side flow<factory setting> or top flow)
Sirrocco fan x 2
16.60 15.94 21.44 19.24
29.6 29.2 36.6 35.4
19
°
C to 30°C 17°C to 28°C 19°C to 30°C 17°C to 28°C
140 200
62
857
5.5 x 2
Three-phase induction motor
2.2
180 200
63
872
7.5 x 2
3.7
Cross fin
Propeller fan x 2
185 x 2
Three-phase induction motor
0.38 x 2
Cross fin
Hermetic
FVC68D(ether oil)
0.05 (240V) x 2
Polyester powder (MUNSELL 5Y8/1)
1,735 x 2,000 x 2,130
Field supplied
R1
Refrigerant Power source Electrical
characteristics
Power consumption Operating current
Type x Quantity Air flow rate External static pressure Motor type Motor output
Type x Quantity Air flow rate Motor type Motor output
Type Motor output Oil type Crankcase heater
H x W x D
Remote controller temperature setting range Indoor-side air flow direction Indoor-side fan
Indoor-side heat exchanger type
Outdoor-side fan
Outdoor-side heat exchanger type Compressor
External finish External dimension Air filter Drain pipe Thread Noise level Net weight Protection devices High pressure switch , Low pressure switch , fuse
Over current relay(compressor , indoor-side fan motor) inner thermal switch in outdoor-side fan motor
Note 1. Cooling and Hetaing capacity indicates the maximum value at operation under the following condition.
Cooling Indoor : 27
°
CDB/19°CWB Outdoor : 35°CDB
Heating Indoor : 20
°
CDB Outdoor : 7°CDB/6°CWB
2. The operating noise measuring point is 1m from the bottom of unit (1m from the front of the unit) in an anechoic room. (Noise level is A-scale value)
3. Refrigerant charge volumes are factory charged.
4. The range of working voltage is with in ±10% voltage of power supply.
5. Specification subject to change without notice.
Specifications of air-source heat pump type packaged air conditioner
(Rooftop unit)
- 10 -
6
ELECTRICAL DAT A
VOLT
TOTAL INPUT TOTAL RATED CURRENT POWER FACTOR START CURRENT COMPRESSOR INPUT RATED CURRENT O/D FAN INPUT RATED CURRENT I/D FAN External static pressure INPUT RATED CURRENT TOTAL INPUT TOTAL RATED CURRENT POWER FACTOR START CURRENT COMPRESSOR INPUT RATED CURRENT O/D FAN INPUT RATED CURRENT I/D FAN External static pressure INPUT RATED CURRENT TOTAL INPUT TOTAL RATED CURRENT POWER FACTOR START CURRENT COMPRESSOR INPUT RATED CURRENT O/D FAN INPUT RATED CURRENT I/D FAN External static pressure INPUT RATED CURRENT
415V
400V
380V
kW
A
%
A
kW
A
kW
A
Pa
kW
A
kW
A
%
A
kW
A
kW
A
Pa
kW
A
kW
A
%
A
kW
A
kW
A
Pa
kW
A
8.12
14.7 76
111
6.96
11.9
0.31
1.1
100
0.85
1.7
8.12
14.7 79
111
6.96
11.9
0.31
1.1
100
0.85
1.7
8.12
14.7 83
111
6.96
11.9
0.31
1.1
100
0.85
1.7
8.02
14.5 76
111
6.86
11.7
0.31
1.1
100
0.85
1.7
8.02
14.5 79
111
6.86
11.7
0.31
1.1
100
0.85
1.7
8.02
14.5 84
111
6.86
11.7
0.31
1.1
100
0.85
1.7
10.22
18.8 75
134
8.71
14.9
0.31
1.1
100
1.2
2.8
10.22
18.8 78
134
8.71
14.9
0.31
1.1
100
1.2
2.8
10.22
18.8 82
134
8.71
14.9
0.31
1.1
100
1.2
2.8
9.82
18.2 75
134
8.31
14.3
0.31
1.1
100
1.2
2.8
9.82
18.2 77
134
8.31
14.3
0.31
1.1
100
1.2
2.8
9.82
18.2 81
134
8.31
14.3
0.31
1.1
100
1.2
2.8
ITEM
PRH-P8MYA PRH-P10MYA
Cooling
VOLT
TOTAL INPUT TOTAL RATED CURRENT POWER FACTOR START CURRENT COMPRESSOR INPUT RATED CURRENT O/D FAN INPUT RATED CURRENT I/D FAN External static pressure INPUT RATED CURRENT TOTAL INPUT TOTAL RATED CURRENT POWER FACTOR START CURRENT COMPRESSOR INPUT RATED CURRENT O/D FAN INPUT RATED CURRENT I/D FAN External static pressure INPUT RATED CURRENT TOTAL INPUT TOTAL RATED CURRENT POWER FACTOR START CURRENT COMPRESSOR INPUT RATED CURRENT O/D FAN INPUT RATED CURRENT I/D FAN External static pressure INPUT RATED CURRENT
415V
400V
380V
kW
A
%
A
kW
A
kW
A
Pa
kW
A
kW
A
%
A
kW
A
kW
A
Pa
kW
A
kW
A
%
A
kW
A
kW
A
Pa
kW
A
16.60
29.6 78
126
14.38
23.8
0.62
2.2
200
1.6
3.6
16.60
29.6 80
126
14.38
23.8
0.62
2.2
200
1.6
3.6
16.60
29.6 85
126
14.38
23.8
0.62
2.2
200
1.6
3.6
15.94
29.2 75
126
13.72
23.4
0.62
2.2
200
1.6
3.6
15.94
29.2 78
126
13.72
23.4
0.62
2.2
200
1.6
3.6
15.94
29.2 82
126
13.72
23.4
0.62
2.2
200
1.6
3.6
21.44
36.6 81
152
18.82
29.8
0.62
2.2
200
2.0
4.6
21.44
36.6 84
152
18.82
29.8
0.62
2.2
200
2.0
4.6
21.44
36.6 89
152
18.82
29.8
0.62
2.2
200
2.0
4.6
19.24
35.4 75
151
16.62
28.6
0.62
2.2
200
2.0
4.6
19.24
35.4 78
151
16.62
28.6
0.62
2.2
200
2.0
4.6
19.24
35.4 82
151
16.62
28.6
0.62
2.2
200
2.0
4.6
ITEM
PRH-P16MYA PRH-P20MYA
Cooling Heating HeatingCooling
Heating HeatingCooling
- 11 -
• Models PRH-P8MYA/P10MYA
7
EXTERNAL DIMENSIONS
Drain R1
Fresh air
intake
(Both side)
28- ø 3 Holes
18- ø 3 Holes
Supply air
duct flange
Return air
duct flange
Note 3
Y
Y
Y-Y
X-X
Left side view
ø 25.4 Knockout hole
<Bottom side hole for
the controller wiring>
Note 1
ø 38.1 Knockout hole
<Bottom side hole for
the power supply wiring>
Top view
Drain R1
6-14X20 holes
<For mounting
anchor bolt M8>
[Field supply]
6-
ø 3.9 holes
(Both side)
Return
air
Supply
air
Service panel
Knockout hole
ø 27 hole
<Front side hole for
the controller wiring>
(Accessory plate)
Service panel
Front view
Note 2
ø 40 hole
<Front side hole for
the power supply wiring>
(Accessory plate)
X
X
Note 1. It is possible to change to ø 27 or
ø 34 by selecting the conduit
mounting plate.
2. The hole size can be selected to
ø 27 or ø 34 or ø 40 by selecting
the conduit mounting plate.
3. These dimension of supply air and
return air duct flange are the same.
<Accessory>
• Conduit mounting plate
(Painted the same color as the unit body)
ø 27
..................................................
1pc.
ø 34
..................................................
1pc.
ø 40 and ø 27
.................................
1pc.
• Tapping screw 4X12
........................
4pcs.
Air inlet
Air outlet
Air inlet
Right side view
ø 38.1 Knockout hole
<Right side hole for
the power supply wiring>
ø 25.4 Knockout hole
<Right side hole for
the controller wiring>
270 1569
250 1579
69
18518595 350105
149
495
585
86
144
1932
2000
7X130Pitch=910
84
5X135Pitch=675
56
68
50
121
155 611
23
4646
36.5
135
36.5
748
10 800 800
1515
840
880
910
961
1399
10
10
43 151001001543
130
23038699560
1715
82960
165 794
65
6084
- 12 -
4X150Pitch=600
10
65 65
(730)
(434)
10
150
44 13X150Pitch=1950 44
10
67
150
150
67
10
(2038)
(1312)
56 8X150Pitch=1200 56
150
50 50
5
56
6
165 794
80
169 104
839
89
155155105
290115
1030
293 525
434202
46 2038 46
1312
73080
65
80104
1661
1671
200
180
1549
2170
2200
1515
68 1932
800 800 144
2000
2130
585
495
585
111
155 611
1735
150
23
• Models PRH-P16MYA/P20MYA
Supply air cover
for top flow
Air
inlet
Air
inlet
Air
outlet
Y
Service panel
air
Return
air
Air
inlet
Fresh air
intake
(Both side)
Drain
R1
Supply air
Return air
duct flange
Note 2
duct flange
Note 2
Y
Y-Y
X-X
Left side view
ø25.4 Knockout hole
<Bottom side hole for
the controller wiring>
Note 1
ø50.8 Knockout hole
<Bottom side hole for
the power supply wiring>
Top view
Drain R1
6-14X20 holes
<For mounting
6-
ø3.9 holes
(Both side)
anchor bolt M10>
[Field supply]
ø27 hole
<Front side hole for
the controller wiring>
(Accessory plate)
Supply
Knockout hole
Service panel
Front view
Note 1
ø52 hole
<Front side hole for
the power supply wiring>
(Accessory plate)
XX
Note 1.It is possible to change to
ø40 by
selecting the conduit mounting plate.
2.Dimension of supply air and return air
duct flange are shown below.
<Accessory>
• Conduit mounting plate
(Painted the same color as
the unit body)
ø40 ············ 1pc.
············ 1pc.
············ 4pcs.
ø52 and ø27
• Tapping screw 4X12
Air
outlet
Right side view
ø50.8 Knockout hole
<Right side hole for
the power supply wiring>
ø25.4 Knockout hole
<Right side hole for
the controller wiring>
Return air
duct flange
38- ø3 Holes
24-
ø3 Holes
Supply air
duct flange
- 13 -
• Model PAR-20MAA
8
REMOTE CONTROLLER
- 14 -
(Front view) (Side view) (Rear view)
120
130
19
83.5
46
[1] Unit
9
• Models PRH-P8MYA/P10MYA
ELECTRICAL WIRING DIAGRAM
Symbol Name Symbol Name Symbol Name
IN DOOR
-SIDE
OUT DOOR
-SIDE
SURGE KILLER
COND/EVA TEMP
LIQUID PIPE TEMP
ROOM TEMP
COND/EVA TEMP
DISCHARGE TEMP
THERMISTOR
FERRITE CORE
FB1,FB2
CR
TH6
TH5
TH4
TH3
TH2
TH1
LIQUID PIPE TEMP
PRESSURE SWITCH (FOR CONTROL)
PRESSURE SWITCH (HIGH PRESSURE)
OVER CURRENT RELAY (INDOOR-SIDE FAN MOTOR)
FAN MOTOR (INDOOR-SIDE)
TERMINAL BLOCK
ELECTRONIC EXPANSION VALVE
CRANK CASE HEATER (COMPRESSOR)
SOLENOID VALVE
4-WAY VALVE
FAN MOTOR (OUTDOOR-SIDE)
PRESSURE SWITCH (LOW PRESSURE)
MAGNETIC CONTACTOR (COMPRESSOR)
MAGNETIC CONTACTOR (INDOOR-SIDE FAN MOTOR)
52F
51F
MF1
TB1,5
LEV
CH
SV1
21S4
OVER CURRENT RELAY (COMPRESSOR)
COMPRESSOR MOTOR
TRANSFORMERTR
MF2
MC
63H2
63H1
63L
52C
51C
FUSE (15A 250VAC CLASS T)F1,F2
Symbol Name
TERMINAL BLOCKTB6
REMOTE CONTROLLER
LED (FOR SERVICE) AUXILIARY RELAY SWITCHSW1-5
LED1 X01-X05
FUSE (6.3A 250VAC CLASS F)F01-F04
FUSE (6.3A 250VAC CLASS F)F10-F30
INDOOR-SIDE
CONTROLLER BOARD
X4-6 SW1 SW2 SWE LED1 LED2 LED3
LED (TRANSMISSION<INDOOR-SIDE·OUTDOOR-SIDE>)
LED (POWER SUPPLY<REMOTE CONTROLLER>)
LED (POWER SUPPLY)
SWITCH (EMERGENCY OPERATION)
SWITCH (CAPACITY CORD)
SWITCH (MODEL SELECTION)
AUXILIARY RELAY
INDOOR-SIDE
POWER
BOARD
OUTDOOR-SIDE
CONTROLLER BOARD
N.F
BOARD
F1 ZNR
FUSE (4A 250VAC CLASS T)
VARISTOR
BLACK (WITH INDOOR POWER BOARD)
BK
3
51F
PE
PE
CN90
CN2L CN22
CN32
CN41
CN29
CN21
CN2D DC14V
51
CN03
157
FAN
3
5321
X4 X5 X6
LCD
F1
ZNR
CN01
CN02
52F
TH6
TH5
TH4
TB5
FB1
CN2S DC14V
SWE
SW1
REMOTE CONTROLLER
LED1 LED2 LED3
DC 14V
CN
OFF
ON
1 2 3 4
(*3)SW2
CN20
4
OFF
ON
OFF
ON
1234
INDOOR-SIDE
POWER BOARD
INDOOR-SIDE CONTROLLER BOARD
FB2
REMOTE CONTROLLER
BOARD
1 2
RETURN AIR DUCT
SUPPLY AIR DUCT
CR
3
2
32
1
1
1
1 2 3 4
2
1
1 2 3
1 2
1 2
2
9
5
1 2
X6X51X4
2
6 7 8
1
TB6
2
F1
F2
5 3
531
BLACK
WHITE
RED
CNIN
LED1
SW3
12
OFF
ON
3456
(*2)SW5
65112
OFF
ON
OUTDOOR-SIDE CONTROLLER BOARD
12
OFF
ON
SW2
34
TR
SW1SW4
OFF
C14
63H2
121
3
CN51
CN81
CN27
CN24
CN3D
DC POWER SUPPLY
CN3N
CN3S
CN34CN28
3131
TRANSMISSION
CIRCIT
31
CNS3
CH 63L63H1
SV1
21S4
TH3TH2TH1
LEV
X05
X02
X03
X01
12
CN4
12
CN312CN2CN40CNMNTCNVMNT
CNFG
F01 F04 F02 F03
13
CN20
CNFC1
CN52
CN53
CN25
CN26
X04
CN21
CN22
CN23
52C
52C
51C
7
1
1
6
1
5
1 3
1 3
5
1 3
1 3
1 3
1
531
CNOUT1
PE
31
1
MF1
51F
52F
WHITE
1
BLUE3BLACK
RED
F30
WHITE
F20
F10
7
5
3
31
BLACK
CNOUT2
1
3
MC
L1
51C
52C
MF2
RED
TB1
ON
432
L25L3 NPE
PE
(*1)
6
POWER SUPPLY 3N
~PE
380/400/415V 50HZ
31
CNPOW
CNFC2
CNFAN
C11
CIRCUIT BREAKER (FIELD SUPPLY) PRH-P8MYA : 63A PRH-P10MYA: 63A
N
L1
N.F.BOARD
L3
L2
PE
GREEN/YELLOW
F.C. BOARD
C12
CONTROL BOX
Note:1.The dotted lines show field wiring.
2. Color of earth wire is yellow and green twisting.
3. Specification subject to change without notice.
4.This motor(*1) includes auto reset type internal thermostat.
5. SW5(
*
2)[outdoor-side controller board] is shown
In case of PRH-P8MYA setting is shown as below.
PRH-P10MYA setting.
6. SW2(
*
3)[indoor-side controller board] is shown
In case of PRH-P8MYA setting is shown as below.
PRH-P10MYA setting.
7. Emergency operation If a trouble occurs with either the remote controller or the unit microcomputer and no other trouble exists, emergency operation for cooling or heating can be performed by changing the setting of switch (SWE) on the indoor-side controller board.
8. mark is connector.
Caution,
1. To protect compressor and fan motor (indoor-side) from
abnormal current, over current
relays is installed. Therefore, do not change factory over current relays is installed. Therefore, do not change
factory set value of over current relays.
ON OFF
SW5
(*2)
ON OFF
SW2
4321
(*3)
[intdoor-side controller board]
[outdoor-side controller board]
4321
- 15 -
• Models PRH-P16MYA/P20MYA
[2] Skeleton of Transmission Line Connection
(1) System
Unit
Remote controller
Transmission line
Symbol Name Symbol Name Symbol Name
IN DOOR
OUT DOOR
SURGE KILLER
COND/EVA TEMP
LIQUID PIPE TEMP
ROOM TEMP
COND/EVA TEMP
DISCHARGE TEMP
THERMISTOR
FERRITE CORE
FB11,12,21,22
CR
TH6-1,TH6-2
TH5-1,TH5-2
TH4-1,TH4-2
TH3-1,TH3-2
TH2-1,TH2-2
TH1-1,TH1-2
LIQUID PIPE TEMP
PRESSURE SWITCH (FOR CONTROL)
PRESSURE SWITCH (HIGH PRESSURE)
OVER CURRENT RELAY (INDOOR FAN MOTOR)
FAN MOTOR (INDOOR)
TERMINAL BLOCK
ELECTRONIC EXPANSION VALVE
CRANK CASE HEATER (COMPRESSOR)
SOLENOID VALVE
4-WAY VALVE
FAN MOTOR (OUTDOOR)
PRESSURE SWITCH (LOW PRESSURE)
MAGNETIC CONTACTOR (COMPRESSOR)
51F
MF1
TB1,5,11,21
LEV1,LEV2
CH1,CH2
SV11,SV12
21S41,21S42
MAGNETIC CONTACTOR (INDOOR FAN MOTOR)
52F
OVER CURRENT RELAY (COMPRESSOR)
TR1,TR2
MF21,MF22
MC1,MC2
63H21,63H22
63H11,63H12
63L1,63L2
52C1,52C2
51C1,51C2
COMPRESSOR MOTOR
F11,12,21,22
TRANSFORMER
FUSE (15A 250VAC CLASS T)
Symbol Name
TERMINAL BLOCKTB6
REMOTE CONTROLLER
LED (FOR SERVICE) AUXILIARY RELAY SWITCHSW1-5
LED1 X01-X05
FUSE (6.3A 250VAC CLASS F)F01-F04
FUSE (6.3A 250VAC CLASS F)F10-F30
INDOOR
CONTROLLER BOARD
X4-6 SW1 SW2 SWE LED1 LED2 LED3
LED (TRANSMISSION<INDOOR·OUTDOOR>)
LED (POWER SUPPLY<REMOTE CONTROLLER>)
LED (POWER SUPPLY)
SWITCH (EMERGENCY OPERATION)
SWITCH (CAPACITY CORD)
SWITCH (MODEL SELECTION)
AUXILIARY RELAY
INDOOR
POWER
BOARD
OUTDOOR
MAIN BOARD
N.F
BOARD
F1 ZNR
FUSE (4A 250VAC CLASS T)
VARISTOR
Note:1.The dotted lines show field wiring.
2. Color of earth wire is yellow and green twisting.
3. Specification subject to change without notice.
4.This motor(*1) includes auto reset type internal thermostat.
5. SW5(
*
2)[outdoor main board] shows PRH-P20MYA setting.
Control box no.1
In case of PRH-P16MYA setting is shown as below.
6. SW2(
*
3)[indoor controller board] shows
In case of PRH-P16MYA setting is shown as below.
PRH-P20MYA setting.
7. Emergency operation If a trouble occurs with either the remote controller or the unit microcomputer and no other trouble exists, emergency operation for cooling or heating can be performed by changing the setting of switch (SWE) on the indoor controller board.
8. mark is connector.
Caution,
1. To protect compressor and fan motor (indoor) from abnormal current, over current relays is installed. Therefore, do not change factory set value of over current relays.
ON OFF
SW5(*2)
ON OFF
SW2
4321
(*3)
[intdoor controller board]
[outdoor main board]
4321
Control box no.2
ON OFF
SW5(*2)
[outdoor main board]
4321
CONTROL BOX NO.2CONTROL BOX NO.1
BLACK
WHITE
RED
1 3
C19
X22
1
2
1 2
36
3
1
GREEN/YELLOW
BLUE
BLACK
WHITE
RED
L1
L2
L3
N
PE
1
2
2
1
X11
63
31
PE N L3 L2 L1
6 5 4 3 2 11
2
3
4
5
6
TB1
POWER SUPPLY 3N
~PE 380/400/415V 50HZ
L1
L2
L3
63H22
LED1
SW3
(*2)SW5
OUTDOOR MAIN BOARD
OFFON
SW2
TR2
SW1
SW4
OFF
C14
13
CN51
CN3D
DC POWER SUPPLY
CN34
CN28
3
1
TRANSMISSION CIRCUIT
3
1
CNS3
CH2
63L2
63H12
21S42
TH3-2
LEV2
X05X02
X03
X01
1 2
CN4
CNMNT
CNVMNT
CNFG
F01
1 3
CN20
CNFC1
CN52
X04
52C2
51C2
1
ON
L3
2
1
2
1
TH2-2
TH1-2
CN3
CN2
CN40
CN3S CN3N CN24 CN27 CN81
12
1
3
F04 F02 F03
357
L2NL1
61
51
CN53CN25
3131531313131
CN26CN21CN22CN23
ON OFF ONOFF
X22
1
2
3
4
5
6
2 1
4 3 2 1
52C2
SV12
MF22
(*1)
C12
C11
3 1
3 1
5 3 1
CNFC2
CNFAN
F.C . BOARD
16
3 1
5
5 3 1
CNOUT1
CNOUT2
3 1
N.F.BOARD
F20
F30
F10
7513
CNIN
CNPOW
PE
MC2
BLACK RED
WHITE
51C2
52C2
BLUE BLACK
RED
WHITE
TB21
GREEN/YELLOW
GREEN/YELLOW
RED
WHITE
BLACK
RED
WHITE
BLACK
WHITE
BLACK
753
5 3 1
3 1
MF21
1
2
3
4
1
2
6 5 4 3 2 1
X11
OFFONOFFON
CN23 CN22 CN21 CN26
1313131351313
CN25 CN53
151 6
L1 N L2
753
F03F02F04
3
1
21
CN81CN27CN24CN3NCN3S
CN40
CN2
CN3
TH1-1
TH2-1
1 2
1 2
N
PE
PE
CIRCUIT BREAKER (FIELD SUPPLY) PRH-P16MYA: 63A PRH-P20MYA: 70A
C12
F.C . BOARD
PE
L3
N.F.BOARD
C11
CNFAN
CNFC2
CNPOW
1
3
6
(*1)
5
ON
TB11
52C1
51C1
MC1
3
1
CNOUT2
RED
1
3
F10
F20
F30
BLUE
1
52F
51F
MF1
1
PE
CNOUT1
1
51C1
52C1
52C1
X04
CN52
CNFC1
CN20
3
1
F01
CNFG
CNVMNT
CNMNT
CN4
2
1
X01
X03
X02
X05
LEV1
TH3-1
21S41 SV11
63H11
63L1
CH1
CNS3
1 3
TRANSMISSION CIRCUIT
1
3
CN28
CN34
DC POWER SUPPLY
CN3D
CN51
31
63H21
C14
OFF
SW4
SW1
TR1
SW2
ON OFF
OUTDOOR MAIN BOARD
(*2)SW5
SW3
LED1
CNIN
1
3
5
C28
X2
X1
INDOOR POWER BOARD
BLACK
(WITH INDOOR POWER BOARD)
C18
C18
C28
X1
X2
51F
52F
CR
F22 F12
TH4-2
TH5-2 TH6-2
FB22
1234
CN41
12 12
12
CN29CN21 CN20
1 2 3 4
SW2
(*3)
1 2 3 4 5
SW1
SWE
X4
X5
X6
X6 X5 X4
1 3 5 7
FAN
3
1
5
CN03
123
CN32
INDOOR CONTROLLER BOARD
1 2
CN2D DC14V
1122
CN22CN2L
789123456
CN90
FB12
2
3 1
CN01
213
BK
CN02
ZNRF1
DC14V
1
2
CN2S DC14V
LED1 LED2 LED3
REMOTE CONTROLLER
BOARD
TB6
CN
LCD
LED1LED2 LED3
PE
987654123
2121
32
5
3
1
7
5
3
X4
X5
ONOFF
SWE
1 2 3 4
ONOFF
SW2(*3)
1 2 3 4 5
ONOFF ONOFFON OFFONOFF
SW1
12
1212432
F21
F11
X4
X5
X6
2
1
1
2
1
1
1
2
3
23
SUPPLY AIR DUCT
RETURN AIR DUCT
21
FB21
INDOOR CONTROLLER BOARD
INDOOR POWER BOARD
CN20
1
DC14V
REMOTE CONTROLLER
CN2S DC14V
FB11
TB5
TH4-1
TH5-1 TH6-1
CN02
CN01
ZNR
F1
X6
FAN
1
CN03
CN2D DC14V
CN21
CN29
CN41
CN32
CN22CN2L
CN90
PE
BK
(WITH INDOOR POWER BOARD)
BLACK
- 16 -
(2) PRH-P10MYA
(1) PRH-P8MYA
[1] Standard Operation Data
0
Technical Data to Meet LVD
380 400 415 380 400 415
50 50 50 50 50 50
27/19 27/19 27/19 20/– 20/– 20/–
35/– 35/– 35/– 7/6 7/6 7/6
7.7 7.7 7.7 7.7 7.7 7.7
14.7 14.7 14.7 14.5 14.5 14.5
11.9 11.9 11.9 11.7 11.7 11.7
1.1 1.1 1.1 1.1 1.1 1.1
1.7 1.7 1.7 1.7 1.7 1.7
2.25 2.25 2.25 1.72 1.72 1.72
0.56 0.56 0.56 0.38 0.38 0.38 77 77 77 66 66 66 10 10 10 -1 -1 -1 48 48 48 0 0 0 33 33 33 28 28 28
Operating condition
Operating condition Cooling Heating Voltage V Power source frequency Hz Indoor air condition (DB/WB) °C Outdoor air condition (DB/WB) °C Refrigerant charge kg
Rated current A
Compressor current A
Rated currentO/D FAN A
Rated current A Discharge pressure MPa Suction pressure MPa Discharge refrigerant temperature °C Suction refrigerant temperature °C Liquid pipe temperature
(at piping sensor)
°C
Compressor shell bottom temperature °C
Total
I/D FAN
Refrigerant circuit
Electrical characteristics
380 400 415 380 400 415
50 50 50 50 50 50
27/19 27/19 27/19 20/– 20/– 20/–
35/– 35/– 35/– 7/6 7/6 7/6
8.2 8.2 8.2 8.2 8.2 8.2
18.8 18.8 18.8 18.2 18.2 18.2
14.9 14.9 14.9 14.3 14.3 14.3
1.1 1.1 1.1 1.1 1.1 1.1
2.8 2.8 2.8 2.8 2.8 2.8
2.31 2.31 2.31 1.83 1.83 1.83
0.55 0.55 0.55 0.37 0.37 0.37 78 78 78 70 70 70
999–1–1–1 48 48 48 3 3 3 32 32 32 25 25 25
Operating condition
Operating condition Cooling Heating Voltage V Power source frequency Hz Indoor air condition (DB/WB) °C Outdoor air condition (DB/WB) °C Refrigerant charge kg
Rated current A
Compressor current A
Rated current A
Rated current A Discharge pressure MPa Suction pressure MPa Discharge refrigerant temperature °C Suction refrigerant temperature °C Liquid pipe temperature
(at piping sensor)
°C
Compressor shell bottom temperature °C
Total
I/D FAN
O/D FAN
Refrigerant circuit
Electrical characteristics
- 17 -
1: For each refrigerant circuit
1: For each refrigerant circuit
(4) PRH-P20MYA
(3) PRH-P16MYA
380 400 415 380 400 415
50 50 50 50 50 50
27/19 27/19 27/19 20/– 20/– 20/–
35/– 35/– 35/– 7/6 7/6 7/6
7.7 7.7 7.7 7.7 7.7 7.7
Operating condition
Operating condition Cooling Heating Voltage V Power source frequency Hz Indoor air condition (DB/WB) °C Outdoor air condition (DB/WB) °C Refrigerant charge
1kg
Rated current A
Compressor current A
Rated currentO/D FAN A
Rated current A Discharge pressure MPa Suction pressure MPa Discharge refrigerant temperature °C Suction refrigerant temperature °C Liquid pipe temperature
(at piping sensor)
°C
Compressor shell bottom temperature °C
Total
I/D FAN
Refrigerant circuit
Electrical characteristics
380 400 415 380 400 415
50 50 50 50 50 50
27/19 27/19 27/19 20/– 20/– 20/–
35/– 35/– 35/– 7/6 7/6 7/6
8.2 8.2 8.2 8.2 8.2 8.2
29.6
23.8
2.2
3.6
2.27
0.52 79
7 49 31
29.2
23.4
2.2
3.6
1.80
0.40 68
0 2
25
36.6
29.8
2.2
4.6
2.28
0.52 79
7 49 31
35.4
28.6
2.2
4.6
1.80
0.40 68
0 2
25
29.6
23.8
2.2
3.6
2.27
0.52 79
7 49 31
29.6
23.8
2.2
3.6
2.27
0.52 79
7 49 31
29.2
23.4
2.2
3.6
1.80
0.40 68
0 2
25
36.6
29.8
2.2
4.6
2.28
0.52 79
7 49 31
35.4
28.6
2.2
4.6
1.80
0.40 68
0 2
25
29.2
23.4
2.2
3.6
1.80
0.40 68
0 2
25
36.6
29.8
2.2
4.6
2.28
0.52 79
7 49 31
35.4
28.6
2.2
4.6
1.80
0.40 68
0 2
25
Operating condition
Operating condition Cooling Heating Voltage V Power source frequency Hz Indoor air condition (DB/WB) °C Outdoor air condition (DB/WB) °C Refrigerant charge
1kg
Rated current A
Compressor current A
Rated current A
Rated current A Discharge pressure MPa Suction pressure MPa Discharge refrigerant temperature °C Suction refrigerant temperature °C Liquid pipe temperature
(at piping sensor)
°C
Compressor shell bottom temperature °C
Total
I/D FAN
O/D FAN
Refrigerant circuit
Electrical characteristics
- 18 -
[4] Reduction Ratio by Frosting
6 1.0 4 0.98 2 0.88
0 0.85 –2 0.86 –4 0.89 –6 0.92 –8 0.92
–10 0.92
Outdoor unit inlet wet bulb temperature
Heating capacity reduction ratio
(°CWB)
[2] Cooling Capacity Curves
•PRH-P8MYA/P10MYA/P16MYA/P20MYA
[3] Heating Capacity Curves
•PRH-P8MYA/P10MYA/P16MYA/P20MYA
Indoor inlet air wet
bulb
tem
p.
<˚CW
B>
inlet air wet
bulb temp. <˚CWB>
Indoor
Indoor inlet air dry
bulb
temp. <˚CDB>
Indoor inlet air dry
bulb
temp. <˚CDB>
Outdoor
air
temperature
<˚CWB>
Outdoor
air temperature
<˚CWB>
Outdoor air temperature
<˚CDB>
Outdoor
air
temperature
<˚CDB>
- 19 -
1.4
1.2
1
Capacity ratio
0.8
1.22 22
20
1.1
22 20 18
16
Input ratio
0.9
18 16
0.6
-5 -3 -1 1 3 5 7 9 11 13 151719212325272931333537394143
1.4
1.2
1
Capacity ratio
0.8
0.6
-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18
0.7
-5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37
1.4 15 20 25
1.2
1
Input ratio
0.8
0.6
-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18
39 41 43
25
20 15
Capacity/Input ratio
Heating
Airflow rate (m3/min)
Capacity/Input ratio
Cooling
Airflow rate (m3/min)
Capacity/Input ratio
Airflow rate (m3/min)
Cooling
Capacity/Input ratio
Heating
Airflow rate (m3/min)
[5] Capacity/Input Ratio against Changes in Room Airflow Rate
• Model PRH-P8MYA
• Model PRH-P10MYA
0.9
1
1.1
55 65 75 85
Capacity Input
1.1
0.9
1
55 65 75 85
Capacity Input
0.9
1
1.1
70 80 90 100 110
Capacity Input
0.9
1
1.1
70 80 90 100 110
Capacity Input
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
- 20 -
0.9
1.1
112 120 130 140 150 160 168
1
0.9
1
1.1
112 120 130 140 150 160 168
0.9
1
1.1
144 150 160 170 180 190 200 210 216
0.9
1
1.1
144 150 160 170 180 190 200 210 216
Capacity/Input ratio
Airflow rate (m3/min)
Capacity/Input ratio
Airflow rate (m3/min)
Capacity/Input ratio
Airflow rate (m3/min)
Capacity/Input ratio
Airflow rate (m3/min)
Capacity
Input
Capacity
Input
Capacity
Input
Capacity
Input
• Model PRH-P16MYA
• Model PRH-P20MYA
Capacity Input
Capacity Input
Cooling
Heating
Capacity Input
Capacity Input
Heating
Cooling
- 21 -
- 22 -
Bypass factor
Airflow rate (m3/min)
55
0.30
0.25
0.20
0.15
0.10
PRH-P8MYA
PRH-P10MYA
Bypass factor
Airflow rate (m3/min)
70 80 90 100 11060 65 70 75 80 85
0.30
0.25
0.20
0.15
0.10
PRH-P16MYA PRH-P20MYA
[6] Bypass Factor Curves
[7] Cooling Sensible Heating Capacity Table
(1) PRH-P8MYA (Airflow rate 70m3/min)
Outdoor
temp.
(°C)
20 25 30 35 40 43
Indoor inlet air temperature (DB/WB°C)
CA 18100 17500 16900 16200 15300 14800
SHC 14400 14100 13900 13600 13200 12900
CA 19300 18700 18100 17400 16600 16000
SHC 14300 14100 13800 13500 13200 12900
CA 20000 19500 18900 18000 17400 16900
SHC 15300 15100 14800 14500 14200 14000
CA 20800 20300 19700 19000 18200 17700
SHC 15300 15100 14900 14600 14300 14100
CA 21900 21500 20900 20200 19500 19000
SHC
(unit : kcal/h)
15000 14900 14700 14400 14200 14000
23/16 25/18 27/19 28/20 30/22
112 120 130 140 150 160 168
Bypass factor
0.2
0.15
0.1
0.05 Airflow rate (m3/min)
144 150 160 170 180 190 216200 210
Bypass factor
0.1
0.15
0.2
0.3
0.25
Airflow rate (m3/min)
(3) PRH-P16MYA (Airflow rate 140m3/min)
(4) PRH-P20MYA (Airflow rate 180m
3
/min)
(2) PRH-P10MYA (Airflow rate 90m3/min)
Outdoor
temp.
(°C)
20 25 30 35 40 43
Indoor inlet air temperature (DB/WB°C)
CA 36200 35000 33800 32400 30600 29600
SHC 29500 28900 28400 27800 27000 26500
CA 38600 37400 36200 34800 33200 32000
SHC 29300 28700 28200 27700 27000 26500
CA 40000 39000 37800 36000 34800 33800
SHC 31300 30900 30400 29700 29200 28800
CA 41600 40600 39400 38000 36400 35400
SHC 31300 30900 30400 29900 29300 28900
CA 43800 43000 41800 40400 39000 38000
SHC
(unit : kcal/h)
(unit : kcal/h)
30800 30500 30000 29500 29000 28700
23/16 25/18 27/19 28/20 30/22
Outdoor
temp.
(°C)
20 25 30 35 40 43
Indoor inlet air temperature (DB/WB°
C)
CA 45000 43600 42000 40200 38200 36800
SHC 36000 35300 34600 33800 32900 32300
CA 48000 46600 45000 43200 41200 40000
SHC 35700 35100 34500 33700 32900 32400
CA 49800 48600 47000 44800 43200 42000
SHC 38200 37700 37100 36200 35500 35000
CA 51600 50400 49000 47200 45400 44000
SHC 38100 37600 37100 36400 35700 35100
CA 54600 53400 52000 50400 48400 47200
SHC 37600 37100 36600 36000 35300 34900
23/16 25/18 27/19 28/20 30/22
(unit : kcal/h)
Outdoor
temp.
(°C)
20 25 30 35 40 43
Indoor inlet air temperature (DB/WB°
C)
CA 22500 21800 21000 20100 19100 18400
SHC 18000 17700 17300 16900 16500 16200
CA 24000 23300 22500 21600 20600 20000
SHC 17900 17600 17200 16900 16400 16200
CA 24900 24300 23500 22400 21600 21000
SHC 19100 18900 18500 18100 17800 17500
CA 25800 25200 24500 23600 22700 22000
SHC 19100 18800 18500 18200 17800 17600
CA 27300 26700 26000 25200 24200 23600
SHC 18800 18600 18300 18000 17700 17400
23/16 25/18 27/19 28/20 30/22
- 23 -
- 24 -
[8] Fan Performance
PRH-P8MYA
PRH-P10MYA
Air flow
85 (CMM)
(L/S)
Total static pressure (Pa)
1.1kW
1.5kW
2.2kW
1.5kW
* : factory pre setting ESP = 100 Pa
Air flow
* : factory pre setting ESP = 100 Pa
110
1830
(CMM) (L/S)
105100
1670
9590
1500
8580
1330
7570
1170
80
1330
7570
1170
6560
1000
55
0
800
700
600
500
400
300
200
100
0
100
200
300
400
500
600
Total static pressure (Pa)
Fan speed <rpm>
Fan speed <rpm>
internal static pressure
internal static pressure
900
1000
1100
1200
1300
800
900
1000
1100
1200
1300
1400
1500
1400
1500
1600
1700
Loading...
+ 60 hidden pages