Mitsubishi PRHG-8, PRHG-10, PRHG-15, PRHG-20 DATA BOOK

AIR-COOLED ROOFTOP PACKAGED AIR CONDITIONERS
Series
HEAT PUMP : PRHG-8,10,15,20
DATA BOOK
Specifications subject to change without notice.
CONTENTS
SAFETY FOR USE FEATURES TYPICAL INSTALLATION EXAMPLE MODEL-DESIGNATION BREAKDOWN SPECIFICATIONS ELECTRICAL DATA SELECTION PROCEDURE CAPACITY TABLES OPERATION RANGE FAN PERFORMANCE NC CURVES OUTLINE DIMENSIONS WIRING DIAGRAMS ELECTRICAL OPERATION FLOW CHARTS REFRIGERANT CYCLE SCHEMATIC SAFETY & CONTROL DEVICES ACCESSORY AVAILABILITY INSTALLATION INSTRUCTIONS FOR USE HOW TO OPERATE
(LCD remote controller PAC-204RC) LOW AMBIENT COOLING PARTS;
OPTION PAC-205FC (Fan controller)
1 3 4 4 5 6 7 9 18 19 24 26 28 32 34 35 35 36 43
47
51
fire may result. If you need to have the unit
Ask your dealer or specialized subcontractor for installation.
For installation, conduct the work correctly by following the Installation Manual.
Install the unit on a spot sufficiently durable against the unit weight.
All electric work must be performed by licensed technician, according to local regulations and the instructions given in this manual. The units should be powered by dedicated power lines.
Use only the specified cables for wiring. The connections must be made secured without tension the terminals.
The unit should be installed according to the instructions in order to minimize the risk of damage from earthquakes, typhoons or strong winds.
The outdoor unit must be installed on stable, level surface, in a place where there is no accumulation of snow , leaves or rubbish.
The outdoor unit should be installed in a location where air and noise emitted by the unit will not disturb the neighbors. The indoor unit should be securely installed.
Never repair the unit, remodel or transfer it to another site by yourself.
Use only the specified refrigerant (R-22) to charge the refrigerant circuit. Do not mix it with any other refrigerant and do not allow air to remain in the circuit.
Ventilate the room if refrigerant leaks during Installation.
After completing installation work, make sure that refrigerant gas has not leaked.
Take a proper measure to suppress the critical concentration of refrigerant if leaked when installing the unit in a small room.
The terminal block cover of unit must be firmly attached to prevent entry of dust and moisture.
Use only optional parts authorised by Mitsubishi Electric.
Before conducting installation work, please read this “SAFETY FOR USE” carefully
for
correct installation.
Since the caution items shown here contain important description relative to safety, please
observe them without fail.
After reading, please keep it with you together the Instruction Manual, and read it again at the
movement of the unit.
Conducting installation work by yourself improperly may cause a fire, electric shock or water leakage.
Improper installation may cause a fire, electrical shock or water leakage.
Insufficient durability can cause an injury by the falling down of unit.
Power lines with insufficient capacity or improper electrical work may result in electric shock or fire.
Improper connection or fastening can cause a fire or electrical shock.
Improper installation work can cause an injury by the falling down of the unit.
If the unit is loosely mounted, it may fall, and cause injury.
If they are performed improperly, water leakage, electric shock or repaired or moved, consult your dealer.
Air enclosed in the circuit can cause high pressure resulting in a rupture and other hazards.
The refrigerant heated generates poisonous gas by decomposition which can cause poisoning.
If refrigerant gas has leaked and exposed to fan heater, Please do the gas leakage inspection before starting.
stove, oven and so on, it may generate noxious gases.
The limit density is made not to be exceeded even if the refrigerant leaks by any chance. You are necessary to ventilation measures to prevent the accident. If the refrigerant leaks, hypoxia accident may caused. For the countermeasure to be taken, consult your dealer.
Improper mounting of the cover cause electric shock or fire.
If the accessories are installed improperly, water leakage, electric shock or fire may result. Ask your dealer or an authorised company to install them.
Erroneous handling gives a high possibility to induce serious results such as
death or heavy injury.
Erroneous handling may induce serious injury depending on the situation.
Warning
Caution
The heating of refrigerant is noted.
When the refrigerant touches the fire etc., it was decom­posed and a poisonous gas is generated. Do not use the welding machine etc., in the room close up of the installation of the air conditioner.
Warning
SAFETY FOR USE
-1-
Caution
The poor mounting of the panel or terminal cover may cause the heat generation of the terminal connection, a fire or electrical shock.
Otherwise electric shock can be resulted.
The unit should not be carried by only one person if it is more than 20kg. It occasionally causes the damage of the unit and health to be impaired. Some unit use PP bands for packing. Do not use any PP band for delivery purpose. It may cause the injury. Do not touch the heat exchanger fins with your bear hands. Doing so may cut your hands. When carrying in outdoor unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make outdoor unit unstable, resulting in a fall of it. Be sure to safety dispose the packing materials. Packing materials, such as catches and other metal or wooden parts, may cause stabs or other injuries.
The damaged base may cause the falling down of the unit which may give injury.
Do not turn the main power switch OFF during seasons of heavy use, doing so can result in failure.
Touching directly such part can cause a burn or frostbite as it becomes high or low temperature according to the refrigerant state.
Touching directly it may injure your hands.
You could be injured if you touch rotating, hot or high­voltage parts.
Dust may accumulate, and cause a failure.
Continuing the operation without eliminating the emergency state may cause a machine trouble, fire, or electrical shock.
Otherwise, water leakage or unit failure may occur.
If washed with water, electric shock may be caused.
Do not wash the unit with water.
Arrange the configuration of wiring not to bring up the panel and terminal cover, and fasten the panel and terminal cover securely.
occur.
The gas may ignite or explode when the gas leaks and collects in surround of the unit.
The erroneous operation of air conditioner may be induced by inverter equipment, independent power device, medical equipment or communication equipment.
As the use for the applications other than that designed originally may result in the deterioration of the quality. Consult your dealer in this regard.
Installing the unit at the following places may cause a trouble, a place where is much machine oil, salt , humidity or dust, spa district, a place full of sulfur gas, volatile gas, or corrosive gas, a place near high frequency processing machine.
If the drain pipes are not properly insulated, condensation will result and drip on ceiling, floor or other possessions.
When the unit inclines, it causes the water leak and the breakdown. Please confirm the horizontal with the spirit level.
Improper drain piping (hose) may cause water leakage and damage to furniture or other possessions.
Do not connect the earth wire to gas pipe, city water pipe, lightning rod or telephone earth wire. Improper earth connection may cause electrical shock.
Failure to mount the electric leak breaker may cause electrical shock.
Using a wire or copper wire instead of proper capacity can cause fire or trouble. Other appliances connected to the same line could cause an overload.
Otherwise, current leakage, overheating or fire may
The tighten or loosen the connections may cause generate heat and cause fire.
Never install on the place where a combustible gas might leak.
When the unit is installed at telecommunication centers or hospitals, take a proper provision against noise.
For special use as for foods, animals/plants, precision equipment or art objects, the applicability should be confirmed beforehand.
Do not use the unit under a special atmosphere.
Thermal insulation of the drain pipes is necessary prevent dew condensation.
The unit should be securely installed level surface.
Install drain piping (hose) according to this Installation Manual to ensure proper drainage.
The unit must be properly earth connected.
When installing at a watery place, provide an electric leak breaker.
Make sure that each appliance has a main power switch.
Use breaker or fuse with proper capacity.
For the power lines, use standard cables of sufficient current capacity.
When installing the power lines, do not apply tension to the cables.
When the room is high humidity or when the drain pipe is clogged, water may drip from the indoor unit.
Do not place objects under the units to avoid damage of condensation.
Do not handle the switch with wet hands.
Be very careful about unit transportation.
Do not leave the mounting base being damaged.
Turn on the main power switch more than 6 hours before starting operation.
Do not touch the compressor or refrigerant piping without wearing glove on your hands.
Do not touch the metal edges inside the unit without wearing glove on your hands.
Do not remove the panel or the fan guard from the unit when it is running.
Do not operate the air conditioner without the air filter set place.
At emergency (if you smell something burning), stop operation and turn the power source switch off.
After stopping operation, be sure to wait for five minutes before turning off the main power switch.
Remote controller is not installed for the place where direct sunshine strikes.
Remote controller may be broken.
Remote controller should be pushed with finger.
-2-
FEATURES
Highly Efficient operation
The EER(Energy Efficiency Ratio) on these models is greatly improved by revised design specifications and by being manufactured stringently to Mitsubishi Electric high quality standards.
High sensible cooling capacity
The sensible cooling capacity has been significantly improved through balanced optimised heat exchanger design.
Flexible Installation (Convertible Airflow)
The customer can select whichever side flow and down flow in the PRHG series. The standard specifi­cation is side flow. Also the PRHG series can install more flexible in local work, too.
Labor Saving Installation
Because of the single unit configuration, all refrigeration work can be omitted. The unit operation can commence immediately after connection to the power supply, drain piping, ducting and control system.
Minimum Floor Space
The PRHG series feature a compact design and has been succeeded in reducing more floor space.
Flexibility of Supply Air Delivery
All series feature belt driven Supply Air fans enabling accurate matching of actual airflow rates to the specified quantities. Accurate commissioning is assisted by the capability to exchange pulleys and belts if necessary to achieve the desired air balance.
Comfort heating
The PRHG series are designed to provide effective heating even when the outside temperature is down to -15˚C. <Merit up at defrost> Cold air stop is introduced during defrost in PRHG8, 10.
Global Remote Controller
Wide Electrical Control Capability
All series is flexible mechanical control configulation. In addition Global Remote Controller is prepared on standard. The Global Remote Controller give the programmable weekly timer, compressor anti-short cycle timer(3 min), cool/heat/fan/auto changeover etc. This controller utlises a microprocessor and includes liquid crystal display with touch pad for adjustment for control program. The factory standard is for provision of 24volt terminal block to enable a field wired control of contractors choice to be connected. Please consult your local Mitsubishi Electric Sales office for application advice on these control.
Low Ambient Cooling Kit (option)
In applications with relatively high internal loads, there may be a requirment for all series to operate on cooling at low ambient conditions. An optional accessory is available to maintain the refrigeration circuit in balance at outdoor temperatures as low as -5˚C. Please consult your local Mitsubishi Electric Sales office for application advice on this accessory.
-3-
TYPICAL INSTALLATION EXAMPLE
Series symbol Self-contained type (rooftop type)
Series symbol global type
Heat pump type
Series symbol Y=3-phase 380V,400V,415V,50Hz,4 wires
Design sequence
Compressor horse power 8=8HP 10=10HP 15=15HP 20=20HP
Design sequence
Service reference
MODEL-DESIGNATION BREAKDOWN
PRHG
P R H G 1 0 M Y A E U
-4-
SPECIFICATIONS
Model name Service reference Power supply
PRHG-8MYA PRHG-10MYA PRHG-15MYA PRHG-20MYA
PRHG-8MYA-EU(S)
PRHG-10MYA-EU(S) PRHG-15MYA-EU(S) PRHG-20MYA-EU(S)
23.8 29.7
3N~ 380~415V 50Hz
46.3 60.8
Total cooling capacity
Btu/h 81,300 101,400 158,000 207,500
(Gross)
kcal/h 20,500 25,600 39,900 52,300
kW
kW
19.0 23.8 37.0 48.6
Sensible cooling capacity
Btu/h 64,900 81,300 126,300 165,900
(Gross)
Total cooling capacity
(Net)
kcal/h
kW
Btu/h
kcal/h
16,400 20,500 31,900 41,800
23.0/22.6 28.3/27.8 44.8/44.1 58.3/57.2 78,500/77,200 96,600/94,900 152,900/150,500 199,000/195,200 19,800/19,500 24,400/24,000 38,600/38,000 50,200/49,200
kW 22.6/23.0 31.5/32.0 44.8/45.5 60.1/61.2
Total heating capacity
Btu/h 77,200/78,600 107,500/109,100 152,900/155,100 205,100/208,700
(Net)
kcal/h 19,500/19,800 27,100/27,600 38,600/39,200 51,700/52,700
kW 21.8 30.1 43.3 57.6
Total heating capacity
Btu/h 74,400 102,800 147,800 196,600
(Gross)
kcal/h 18,800 25,900 37,300 49,600
Capacity steps % 0-100 0-50-100 Refrigerant R-22
Refrigerant charge 2x5.62x4.74.7 5.6 Refrigerant control Capillary tube External finish Acrylic resin coating Color MUNSELL 5Y8/1
Height mm 1,000 1,200
Dimension
Width mm 1,300 1,990
Depth mm 1,530 1,800
Net weight kg
kg
385 415 700 800 Compressor Hermetic line start (reciprocating) No. x Motor output kW 5.5 7.5 2x5.5 2x7.5 Indoor coil Cross fin coil Indoor fan Centrifugal (galvanized steel) - belt drive Indoor fan motor Three phase cage induction motor No. x Motor output kW 1.1 1.5 2.2 3.7
CMM 80 100 160 190
Indoor fan air flow
CFM 2,826 3,532 5,651 6,710
L/S 1,333
5/10
50/100
1,667
6.2/10
62/100
2,667
10/20
100/200
3,167
External static pressure
mmAq
Pa Outdoor coil Cross fin coil Outdoor fan Propeller - direct drive Outdoor fan motor Three phase cage induction motor No. x Motor output kW 0.55 2x0.55
CMM 160 320
Condenser fan air flow
CFM 5,651 11,302
L/S 2,667 5,333
66 70 Sound pressure level dB(A)
Drain connection mm 25.4
High pressure switch, fuse
Protection devices
Over current relay (compressor, indoor fan and outdoor fan) Internal thermostat (compressor and outdoor fan motor)
Note 1.Cooling & Heating capacity is based on the following conditions.
Cooling : Indoor:27˚CDB , 19˚CWB ; Outdoor:35˚CDB Heating : Indoor:21˚CDB ; Outdoor:7˚CDB , 6˚CWB
2.Refrigerant charge volumes are factory charged.
3.Gross capacity do not include a deduction for evaporator fan motor heat.
4.The measuring point of the Sound pressure level is 1m from the unit surface.
5.The range of working voltage is with in ±10% voltage of power supply.
6.Specification subject to change without notice.
-5-
ELECTRICAL DATA
VOLT
TOTAL INPUT TOTAL RUN CURRENT POWER FACTOR START CURRENT COMPRESSOR INPUT RUN CURRENT O/D FAN INPUT RUN CURRENT I/D FAN External static pressure INPUT RUN CURRENT TOTAL INPUT TOTAL RUN CURRENT POWER FACTOR START CURRENT COMPRESSOR INPUT RUN CURRENT O/D FAN INPUT RUN CURRENT I/D FAN External static pressure INPUT RUN CURRENT TOTAL INPUT TOTAL RUN CURRENT POWER FACTOR START CURRENT COMPRESSOR INPUT RUN CURRENT O/D FAN INPUT RUN CURRENT I/D FAN External static pressure INPUT RUN CURRENT
415V
400V
380V
kW
A
%
A
kW
A
kW
A
Pa
kW
A
kW
A
%
A
kW
A
kW
A
Pa
kW
A
kW
A
%
A
kW
A
kW
A
Pa
kW
A
7.9/8.3
13.3/14.0 82%
77.8
6.6
10.4
0.5
1.5
62/100
0.8/1.2
1.4/2.1
7.9/8.3
13.8/14.5 82%
80.8
6.6
10.7
0.5
1.6
50/100
0.8/1.2
1.5/2.2
7.9/8.3
14.5/15.3 82%
85.0
6.6
11.4
0.5
1.6
50/100
0.8/1.2
1.5/2.3
6.6/7.0
11.1/11.8 83%
77.8
5.3
8.2
0.5
1.5
62/100
0.8/1.2
1.4/2.1
6.6/7.0
11.6/12.3 83%
80.8
5.3
8.5
0.5
1.6
50/100
0.8/1.2
1.5/2.2
6.6/7.0
12.1/12.9 83%
85.0
5.3
9.0
0.5
1.6
50/100
0.8/1.2
1.5/2.3
10.9/11.4
17.8/18.5 86%
76.3
9.0
14.5
0.5
1.3
62/100
1.4/1.9
2.0/2.7
10.9/11.4
18.5/19.2 86%
79.1
9.0
15.1
0.5
1.3
62/100
1.4/1.9
2.1/2.8
10.9/11.4
19.4/20.2 86%
83.3
9.0
15.9
0.5
1.4
62/100
1.4/1.9
2.1/2.9
9.4/9.9
15.3/16.0 86%
76.3
7.5
12.0
0.5
1.3
62/100
1.4/1.9
2.0/2.7
9.4/9.9
15.8/16.5 86%
79.1
7.5
12.4
0.5
1.3
62/100
1.4/1.9
2.1/2.8
9.4/9.9
16.6/17.4 86%
83.3
7.5
13.1
0.5
1.4
62/100
1.4/1.9
2.1/2.9
ITEM
PRHG-8MYA PRHG-10MYA
Cooling Heating HeatingCooling
VOLT
TOTAL INPUT TOTAL RUN CURRENT POWER FACTOR START CURRENT COMPRESSOR INPUT RUN CURRENT O/D FAN INPUT RUN CURRENT I/D FAN External static pressure INPUT RUN CURRENT TOTAL INPUT TOTAL RUN CURRENT POWER FACTOR START CURRENT COMPRESSOR INPUT RUN CURRENT O/D FAN INPUT RUN CURRENT I/D FAN External static pressure INPUT RUN CURRENT TOTAL INPUT TOTAL RUN CURRENT POWER FACTOR START CURRENT COMPRESSOR INPUT RUN CURRENT O/D FAN INPUT RUN CURRENT I/D FAN External static pressure INPUT RUN CURRENT
415V
400V
380V
kW
A
%
A
kW
A
kW
A
Pa
kW
A
kW
A
%
A
kW
A
kW
A
Pa
kW
A
kW
A
%
A
kW
A
kW
A
Pa
kW
A
15.7/16.4
26.3/27.5 83%
104.5
13.2
20.9
1.0
2.8
100/200
1.5/2.2
2.6/3.8
15.7/16.4
27.3/28.5 83%
108.4
13.2
21.7
1.0
2.9
100/200
1.5/2.2
2.7/3.9
15.7/16.4
28.7/30.0 83%
114.2
13.2
22.7
1.0
3.1
100/200
1.5/2.2
2.9/4.2
14.0/14.7
23.5/24.7 83%
101.7
11.5
18.1
1.0
2.8
100/200
1.5/2.2
2.6/3.8
14.0/14.7
24.4/25.6 83%
105.5
11.5
18.8
1.0
2.9
100/200
1.5/2.2
2.7/3.9
14.0/14.7
25.7/27.0 83%
111.1
11.5
19.7
1.0
3.1
100/200
1.5/2.2
2.9/4.2
21.0/22.1
34.2/35.7 86%
110.6
17.5
28.2
1.0
2.6
100/200
2.5/3.6
3.4/4.9
21.0/22.1
35.4/37.0 86%
114.7
17.5
29.2
1.0
2.7
100/200
2.5/3.6
3.5/5.1
21.0/22.1
37.4/39.0 86%
120.7
17.5
30.8
1.0
2.8
100/200
2.5/3.6
3.8/5.4
18.2/19.3
29.7/31.2 86%
106.1
14.7
23.7
1.0
2.6
100/200
2.5/3.6
3.4/4.9
18.2/19.3
30.8/32.4 86%
110.1
14.7
24.6
1.0
2.7
100/200
2.5/3.6
3.5/5.1
18.2/19.3
32.5/34.1 86%
115.8
14.7
25.9
1.0
2.8
100/200
2.5/3.6
3.8/5.4
ITEM
PRHG-15MYA PRHG-20MYA
Cooling Heating HeatingCooling
-6-
1. Model Selection (With actual examples)
First step, to select the approximate model:
Based on the cooling load and the cooling capacity listed in the capacity table, select the applicable model.
Notes:
*1. The correct WB is required since it has a serious effect on the capacity. *2. The cooling capacity decreases as the outdoor temperature increases. Therefore, the estimated highest
temperature during an air conditioning time frame is the designed outdoor temperature. However, it is recommended that the abnormal outdoor temperature which may occur once or twice a year be excluded from the calculation to avoid selection of an excessively large capacity model.
*3. The wind pressure loss of an air duct should be calculated correctly. If a value having an excessive allowance is
used, an excessively large model will be selected. Moreover, an excessively high air flow will be induced during actual operation causing the generation of high operating sounds and carry-over of condensed water.
(Step-1) Confirmation of operation range
Confirm that the conditions given above for the model to be selected are within the operation range listed on Page 18.
(Step-2) Calculation of actual air flow, external static pressure, and fan motor input
Based on the designed air flow and external static pressure, obtain the actual air flow and fan motor power from the fan performance table for the model input selected. For an explanation of how to use the fan performance table, see the following examples.
Example: PRHG-10, 50Hz
Example 1. (To operate with values near to the designed air flow and external static pressure.)
Condition : Designed air flow 100CMM
Designed external static pressure 60Pa
Calculation : The designed point is A. Therefore, duct
resistance line passing A is dotted line. Therefore, actual point is B for fan speed 1088rpm. (Select a pulley near A point to fan speed.)
Actual air flow = 110CMM
Second step, to select the model:
To select the model, the following conditions must be known: (1) Total cooling load or sensible cooling load (2) Indoor conditioned temperature (WB*1, DB) (3) Designed outdoor temperature (DB)*2 (4) Designed air flow (5) Designed external static pressure (= Wind pressure loss of air duct)*3
internal static pressure
Air flow
1500
90 95 100 105
1670
(CMM) (L/S)
1.5kw
2.2kw
900
1000
1100
1200
1300
1400
100
200
300
400
500
Total static pressure (Pa)
Fan speed <rpm>
1500
110 115
1830
120
2000
600
700
800
1600
1700
SELECTION PROCEDURE
A
B
60Pa
-7-
At 26˚CDB, 19˚CWB of Indoor, Q = 28.3, SHC = 22.6, W = 9.6
Therefore, when Air flow is 110 (CMM) Q = 28.3 1.012 28.6 (kW)
SHC = 22.6 W = 9.6 Note * : crrection factors of air flow
(Step-3) Calculation of net capacity
Example: PRHG-10, 50Hz cooling
Condition: Indoor conditioned temp. : 26˚CDB, 19˚CWB Designed outdoor temp. : 40˚CDB Actual air flow : 110CMM Indoor fan motor input : 1.9kW (See P.6, 17) Outdoor fan motor input : 0.5kW (See P.6) Calculation : The sections of the gross capacity table applicable for the above conditions are shown right.
Therfore, the net capacity is, Net total cooling capacity = 28.6 (kw) - 1.9 (kW)
= 26.7 (kW)
Net sensible cooling capacity = 22.9 (kW) - 1.9 (kW)
= 21.0 (kW)
Refrigerant cycle energy efficienty
(1) COP =
(2) EER =
System energy efficienty
(1) COP =
(2) EER =
Notes:
1. COP : Coefficient of performance
2. EER : Energy efficiency ratio
3. Temperature condition of COP, EER (ARI Standard Ratings) Indoor entering air temp. : 80˚FDB (=27˚CDB), 66˚FWB(=19˚CWB) Outdoor entering air temp. : 95˚FDB (=35˚CDB)
4. Total input = Compressor input + Indoor fan motor input (page 17) + Outdoor fan motor input (page 6).
Gross total cooling capacity (kW)
Compressor input (kW)
Gross total cooling capacity (kW)
Total input (kW)
Net cooling capacity (kW)
Compressor input (kW)
Net cooling capacity (kW)
Total input (kW)
1kW = 3412Btu/h
2. Efficiency Calculation
Based on the indoor conditioned temperature (WB,DB), designed outdoor temperature (DB), and the actual air flow obtained in Step-2, obtain the gross capacity from the gross capacity tables (pages 9~16). Then, calculate the net capacity from the formula below by using the fan motor input obtained in Step-2. Net capacity (kW) = Gross capacity (kW) - Fan motor input (kW)
1.012 22.9 (kW)
1.003 9.63 (kW)
28.3 22.6 0.77 9.6
OUTDOOR DB˚C
INDOOR INDOOR
40.0
Q kW
SHC kW
SHF W kW
DB˚CWB˚C
26 19.0
29.2 20.4 9.8
20.0
Factor for Various Air Flow
Air Volume
CMM
l/s Cooling capacity Compressor input
90
1500
0.987
0.996
100
1670
1.000
1.000
110
1830
1.012
1.003
120
2000
1.022
1.007
-8-
Outdoor DB°C
CAPACITY TABLES
Factor for Various Air Flow
Cooling Capacity (Standard Air Flow)
PRHG-8MYA
20.0
Indoor
WB°C
15161715161718191617181920211819202122231920212223242021222324
Q
kW
22.8
23.5
24.2
22.8
23.5
24.2
25.0
25.7
23.5
24.2
25.0
25.7
26.5
27.3
25.0
25.7
26.5
27.3
28.1
29.0
25.7
26.5
27.3
28.1
29.0
30.0
26.5
27.3
28.1
29.0
30.0
SHC
kW
16.2
14.8
13.3
19.2
17.6
16.2
14.8
13.4
20.4
18.9
17.5
15.9
14.6
13.1
20.5
18.8
17.2
15.8
14.3
13.1
21.6
20.1
18.6
17.1
15.7
14.4
22.8
21.6
20.0
18.6
17.1
SHF
0.71
0.63
0.55
0.84
0.75
0.67
0.59
0.52
0.87
0.78
0.70
0.62
0.55
0.48
0.82
0.73
0.65
0.58
0.51
0.45
0.84
0.76
0.68
0.61
0.54
0.48
0.86
0.79
0.71
0.64
0.57
W
kW
5.2
5.2
5.3
5.2
5.2
5.3
5.3
5.4
5.2
5.3
5.3
5.4
5.5
5.6
5.3
5.4
5.5
5.6
5.7
5.8
5.4
5.5
5.6
5.7
5.8
5.9
5.5
5.6
5.7
5.8
5.9
25.0
Q
kW
22.3
22.9
23.6
22.3
22.9
23.6
24.4
25.2
22.9
23.6
24.4
25.2
25.9
26.7
24.4
25.2
25.9
26.7
27.5
28.4
25.2
25.9
26.7
27.5
28.4
29.3
25.9
26.7
27.5
28.4
29.3
SHC
kW
15.8
14.4
13.0
19.0
17.4
15.8
14.4
13.1
20.2
18.6
17.3
15.6
14.2
12.8
20.3
18.6
17.1
15.8
14.3
12.8
21.4
19.9
18.4
16.8
15.3
14.1
22.5
21.4
19.8
18.2
16.7
SHF
0.71
0.63
0.55
0.85
0.76
0.67
0.59
0.52
0.88
0.79
0.71
0.62
0.55
0.48
0.83
0.74
0.66
0.59
0.52
0.45
0.85
0.77
0.69
0.61
0.54
0.48
0.87
0.80
0.72
0.64
0.57
W
kW
5.5
5.5
5.6
5.5
5.5
5.6
5.7
5.8
5.5
5.6
5.7
5.8
5.9
6.0
5.7
5.8
5.9
6.0
6.1
6.2
5.8
5.9
6.0
6.1
6.2
6.4
5.9
6.0
6.1
6.2
6.4
30.0
Q
kW
21.7
22.3
23.0
21.7
22.3
23.0
23.7
24.5
22.3
23.0
23.7
24.5
25.2
25.9
23.7
24.5
25.2
25.9
26.7
27.6
24.5
25.2
25.9
26.7
27.6
28.5
25.2
25.9
26.7
27.6
28.5
SHC
kW
15.6
14.3
12.7
18.7
17.2
15.6
14.2
13.0
19.8
18.6
17.1
15.4
14.1
12.7
19.9
18.4
16.9
15.5
14.2
12.7
21.1
19.7
18.1
16.6
15.2
14.0
22.2
21.0
19.5
17.9
16.5
SHF
0.72
0.64
0.55
0.86
0.77
0.68
0.60
0.53
0.89
0.81
0.72
0.63
0.56
0.49
0.84
0.75
0.67
0.60
0.53
0.46
0.86
0.78
0.70
0.62
0.55
0.49
0.88
0.81
0.73
0.65
0.58
W
kW
5.8
5.9
6.0
5.8
5.9
6.0
6.1
6.2
5.9
6.0
6.1
6.2
6.3
6.4
6.1
6.2
6.3
6.4
6.6
6.7
6.2
6.3
6.4
6.6
6.7
6.8
6.3
6.4
6.6
6.7
6.8
35.0
Q
kW
21.0
21.6
22.3
21.0
21.6
22.3
23.0
23.8
21.6
22.3
23.0
23.8
24.5
25.2
23.0
23.8
24.5
25.2
26.0
26.8
23.8
24.5
25.2
26.0
26.8
27.7
24.5
25.2
26.0
26.8
27.7
SHC
kW
15.3
14.0
12.5
18.3
16.8
15.4
14.0
12.6
19.7
18.3
16.8
15.2
13.7
12.3
19.6
18.1
16.7
15.4
13.8
12.3
20.7
19.4
17.9
16.4
15.0
13.6
22.1
20.7
19.2
17.7
16.3
SHF
0.73
0.65
0.56
0.87
0.78
0.69
0.61
0.53
0.91
0.82
0.73
0.64
0.56
0.49
0.85
0.76
0.68
0.61
0.53
0.46
0.87
0.79
0.71
0.63
0.56
0.49
0.90
0.82
0.74
0.66
0.59
W
kW
6.1
6.2
6.4
6.1
6.2
6.4
6.5
6.6
6.2
6.4
6.5
6.6
6.7
6.9
6.5
6.6
6.7
6.9
7.0
7.1
6.6
6.7
6.9
7.0
7.1
7.3
6.7
6.9
7.0
7.1
7.3
40.0
Q
kW
20.3
20.9
21.6
20.3
20.9
21.6
22.3
23.0
20.9
21.6
22.3
23.0
23.7
24.4
22.3
23.0
23.7
24.4
25.2
26.0
23.0
23.7
24.4
25.2
26.0
26.8
23.7
24.4
25.2
26.0
26.8
SHC
kW
15.0
13.8
12.1
17.9
16.5
15.1
13.8
12.4
19.4
18.1
16.7
15.0
13.5
12.2
19.2
17.7
16.4
15.1
13.6
12.2
20.5
19.0
17.6
16.1
14.6
13.1
21.8
20.5
18.9
17.4
16.1
SHF
0.74
0.66
0.56
0.88
0.79
0.70
0.62
0.54
0.93
0.84
0.75
0.65
0.57
0.50
0.86
0.77
0.69
0.62
0.54
0.47
0.89
0.80
0.72
0.64
0.56
0.49
0.92
0.84
0.75
0.67
0.60
W
kW
6.5
6.6
6.8
6.5
6.6
6.8
6.9
7.0
6.6
6.8
6.9
7.0
7.2
7.3
6.9
7.0
7.2
7.3
7.5
7.6
7.0
7.2
7.3
7.5
7.6
7.8
7.2
7.3
7.5
7.6
7.8
46.0
Q
kW
19.4
20.1
20.7
19.4
20.1
20.7
21.3
22.0
20.1
20.7
21.3
22.0
22.7
23.4
21.3
22.0
22.7
23.4
24.1
24.9
22.0
22.7
23.4
24.1
24.9
25.6
22.7
23.4
24.1
24.9
25.6
SHC
kW
14.7
13.5
11.8
17.5
16.3
14.7
13.4
11.9
19.1
17.6
16.2
14.5
13.2
11.7
18.7
17.4
15.9
14.5
13.0
11.7
20.0
18.6
17.3
15.7
14.2
12.8
21.3
20.1
18.6
17.2
15.6
SHF
0.76
0.67
0.57
0.90
0.81
0.71
0.63
0.54
0.95
0.85
0.76
0.66
0.58
0.50
0.88
0.79
0.70
0.62
0.54
0.47
0.91
0.82
0.74
0.65
0.57
0.50
0.94
0.86
0.77
0.69
0.61
W
kW
7.0
7.1
7.3
7.0
7.1
7.3
7.4
7.5
7.1
7.3
7.4
7.5
7.7
7.9
7.4
7.5
7.7
7.9
8.0
8.2
7.5
7.7
7.9
8.0
8.2
8.3
7.7
7.9
8.0
8.2
8.3
Indoor
DB°C
20
22
24
26
28
30
Q; Cooling Capacity, SHC; Sensible Heat Capacity, W; Compressor Input
Total input = Compressor input + indoor fan motor input + outdoor fan motor input
Air Volume
CMM
l/s
Cooling capacity
Compressor input
80
1330
1.000
1.000
85
1420
1.006
1.001
90
1500
1.012
1.001
95
1580
1.017
1.003
-9-
Outdoor DB°C
Factor for Various Air Flow
Cooling Capacity (Standard Air Flow)
PRHG-8MYA (Use for Low ambient cooling parts)
Heating Capacity (Standard Air Flow)
PRHG-8MYA
–5.0
Indoor
WB°C
15161715161718191617181920211819202122231920212223242021222324
Q
kW
25.3
26.2
27.0
25.3
26.2
27.0
27.9
28.8
26.2
27.0
27.9
28.8
29.7
30.7
27.9
28.8
29.7
30.7
31.6
32.7
28.8
29.7
30.7
31.6
32.7
33.9
29.7
30.7
31.6
32.7
33.9
SHC
kW
17.7
16.2
14.6
20.5
19.1
17.5
16.2
14.7
22.2
20.8
19.3
17.5
16.0
14.4
22.3
20.4
19.0
17.5
15.8
14.4
23.3
21.7
20.2
18.7
17.3
15.9
24.7
23.3
21.8
20.3
18.6
SHF
0.70
0.62
0.54
0.81
0.73
0.65
0.58
0.51
0.85
0.77
0.69
0.61
0.54
0.47
0.80
0.71
0.64
0.57
0.50
0.44
0.81
0.73
0.66
0.59
0.53
0.47
0.83
0.76
0.69
0.62
0.55
W
kW
4.4
4.4
4.5
4.4
4.4
4.5
4.5
4.6
4.4
4.5
4.5
4.6
4.6
4.7
4.5
4.6
4.6
4.7
4.8
4.9
4.6
4.6
4.7
4.8
4.9
5.0
4.6
4.7
4.8
4.9
5.0
0.0
Q
kW
24.9
25.7
26.5
24.9
25.7
26.5
27.4
28.2
25.7
26.5
27.4
28.2
29.2
30.1
27.4
28.2
29.2
30.1
31.0
32.1
28.2
29.2
30.1
31.0
32.1
33.2
29.2
30.1
31.0
32.1
33.2
SHC
kW
17.4
15.9
14.3
20.4
19.0
17.5
15.9
14.4
22.1
20.4
18.9
17.2
15.8
14.1
21.9
20.1
18.7
17.2
15.5
14.1
22.9
21.3
19.9
18.3
17.0
15.6
24.2
22.9
21.4
19.9
18.3
SHF
0.70
0.62
0.54
0.82
0.74
0.66
0.58
0.51
0.86
0.77
0.69
0.61
0.54
0.47
0.80
0.71
0.64
0.57
0.50
0.44
0.81
0.73
0.66
0.59
0.53
0.47
0.83
0.76
0.69
0.62
0.55
W
kW
4.4
4.4
4.5
4.4
4.4
4.5
4.5
4.6
4.4
4.5
4.5
4.6
4.6
4.7
4.5
4.6
4.6
4.7
4.8
4.9
4.6
4.6
4.7
4.8
4.9
5.0
4.6
4.7
4.8
4.9
5.0
5.0
Q
kW
24.5
25.3
26.1
24.5
25.3
26.1
27.0
27.8
25.3
26.1
27.0
27.8
28.7
29.6
27.0
27.8
28.7
29.6
30.5
31.6
27.8
28.7
29.6
30.5
31.6
32.7
28.7
29.6
30.5
31.6
32.7
SHC
kW
17.2
15.7
14.1
20.1
18.7
17.2
15.7
14.2
21.8
20.1
18.6
17.0
15.5
13.9
21.9
20.0
18.4
16.9
15.3
13.9
22.8
21.3
19.9
18.0
16.7
15.4
24.1
22.8
21.4
19.9
18.1
SHF
0.70
0.62
0.54
0.82
0.74
0.66
0.58
0.51
0.86
0.77
0.69
0.61
0.54
0.47
0.81
0.72
0.64
0.57
0.50
0.44
0.82
0.74
0.67
0.59
0.53
0.47
0.84
0.77
0.70
0.63
0.55
W
kW
4.5
4.5
4.6
4.5
4.5
4.6
4.6
4.7
4.5
4.6
4.6
4.7
4.7
4.8
4.6
4.7
4.7
4.8
4.9
5.0
4.7
4.7
4.8
4.9
5.0
5.1
4.7
4.8
4.9
5.0
5.1
10.0
Q
kW
24.1
24.9
25.7
24.1
24.9
25.7
26.5
27.3
24.9
25.7
26.5
27.3
28.2
29.1
26.5
27.3
28.2
29.1
30.0
31.0
27.3
28.2
29.1
30.0
31.0
32.1
28.2
29.1
30.0
31.0
32.1
SHC
kW
17.1
15.7
14.1
20.0
18.7
17.2
15.7
13.9
21.7
20.0
18.6
16.9
15.2
13.7
21.5
19.7
18.3
16.9
15.3
13.6
22.4
20.9
19.5
18.0
16.4
15.1
23.7
22.4
21.0
19.5
18.0
SHF
0.71
0.63
0.55
0.83
0.75
0.67
0.59
0.51
0.87
0.78
0.70
0.62
0.54
0.47
0.81
0.72
0.65
0.58
0.51
0.44
0.82
0.74
0.67
0.60
0.53
0.47
0.84
0.77
0.70
0.63
0.56
W
kW
4.7
4.7
4.8
4.7
4.7
4.8
4.8
4.9
4.7
4.8
4.8
4.9
4.9
5.0
4.8
4.9
4.9
5.0
5.1
5.2
4.9
4.9
5.0
5.1
5.2
5.3
4.9
5.0
5.1
5.2
5.3
15.0
Q
kW
23.7
24.4
25.2
23.7
24.4
25.2
26.0
26.8
24.4
25.2
26.0
26.8
27.6
28.5
26.0
26.8
27.6
28.5
29.4
30.3
26.8
27.6
28.5
29.4
30.3
31.4
27.6
28.5
29.4
30.3
31.4
SHC
kW
16.8
15.4
13.8
19.9
18.3
16.9
15.4
13.9
21.2
19.6
18.2
16.6
15.2
13.7
21.3
19.5
18.0
16.5
15.0
13.7
22.2
20.7
19.4
17.6
16.4
15.1
23.5
22.2
20.8
19.4
17.6
SHF
0.71
0.63
0.55
0.84
0.75
0.67
0.59
0.52
0.87
0.78
0.70
0.62
0.55
0.48
0.82
0.73
0.65
0.58
0.51
0.45
0.83
0.75
0.68
0.60
0.54
0.48
0.85
0.78
0.71
0.64
0.56
W
kW
4.9
4.9
5.0
4.9
4.9
5.0
5.0
5.1
4.9
5.0
5.0
5.1
5.2
5.3
5.0
5.1
5.2
5.3
5.4
5.5
5.1
5.2
5.3
5.4
5.5
5.6
5.2
5.3
5.4
5.5
5.6
Indoor
DB°C
20
22
24
26
28
30
Q; Cooling Capacity, SHC; Sensible Heat Capacity, W; Compressor Input
Total input = Compressor input + indoor fan motor input + outdoor fan motor input
Air Volume
CMM
l/s
Cooling capacity
Compressor input
80
1330
1.000
1.000
85
1420
1.006
1.001
90
1500
1.012
1.001
95
1580
1.017
1.003
Factor for Various Air Flow
Air Volume
CMM
l/s
Heating capacity
Compressor input
80
1330
1.000
1.000
85
1420
1.004
0.996
90
1500
1.090
0.992
95
1580
1.015
0.987
Indoor
DB°C
15161718192021222324252627
Q
kW
15.4
15.3
15.2
15.1
15.1
15.0
14.9
14.8
14.7
14.7
14.6
14.5
14.5
W
kW
3.6
3.6
3.6
3.6
3.6
3.7
3.7
3.7
3.7
3.8
3.8
3.8
3.8
Q
kW
13.5
13.4
13.3
13.2
13.2
13.1
13.0
12.9
12.8
12.8
12.7
12.6
12.6
W
kW
3.4
3.4
3.4
3.4
3.4
3.5
3.5
3.5
3.5
3.6
3.6
3.6
3.6
–10–15
Q
kW
17.6
17.5
17.4
17.3
17.3
17.2
17.1
17.0
17.0
16.9
16.8
16.7
16.7
W
kW
3.9
3.9
3.9
3.9
4.0
4.0
4.0
4.1
4.1
4.1
4.2
4.2
4.2
–5
Q
kW
20.1
20.0
19.9
19.9
19.8
19.7
19.6
19.5
19.5
19.4
19.3
19.2
19.2
W
kW
4.4
4.4
4.4
4.5
4.5
4.6
4.6
4.6
4.7
4.7
4.8
4.8
4.8
0
Q
kW
22.9
22.8
22.7
22.6
22.6
22.5
22.4
22.3
22.2
22.2
22.1
22.0
22.0
W
kW
4.8
4.9
4.9
5.0
5.1
5.1
5.2
5.2
5.3
5.3
5.4
5.4
5.4
5
Q
kW
26.0
25.9
25.9
25.8
25.7
25.6
25.5
25.5
25.4
25.3
25.2
25.1
25.1
W
kW
5.4
5.5
5.5
5.6
5.7
5.8
5.8
5.9
5.9
6.0
6.1
6.2
6.2
10 15
Q
kW
29.5
29.5
29.4
29.3
29.2
29.1
29.1
29.0
28.9
28.8
28.7
28.6
28.6
W
kW
6.0
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.7
6.8
6.9
7.0
7.0
OD WB°C
Q; Heating Capacity, W; Compressor Input
-10-
Outdoor DB°C
Factor for Various Air Flow
Cooling Capacity (Standard Air Flow)
PRHG-10MYA
20.0
Indoor
WB°C
15161715161718191617181920211819202122231920212223242021222324
Q
kW
29.4
30.4
31.4
29.4
30.4
31.4
32.4
33.5
30.4
31.4
32.4
33.5
34.6
35.7
32.4
33.5
34.6
35.7
36.8
38.0
33.5
34.6
35.7
36.8
38.0
39.2
34.6
35.7
36.8
38.0
39.2
SHC
kW
21.2
19.5
17.6
24.7
23.1
21.4
19.4
17.4
26.8
25.1
23.3
21.1
19.0
17.1
26.9
24.8
22.8
20.7
18.8
17.1
28.1
26.3
24.6
22.4
20.5
18.8
30.1
28.2
26.1
24.3
22.3
SHF
0.72
0.64
0.56
0.84
0.76
0.68
0.60
0.52
0.88
0.80
0.72
0.63
0.55
0.48
0.83
0.74
0.66
0.58
0.51
0.45
0.84
0.76
0.69
0.61
0.54
0.48
0.87
0.79
0.71
0.64
0.57
W
kW
7.1
7.2
7.3
7.1
7.2
7.3
7.4
7.5
7.2
7.3
7.4
7.5
7.6
7.7
7.4
7.5
7.6
7.7
7.9
8.0
7.5
7.6
7.7
7.9
8.0
8.2
7.6
7.7
7.9
8.0
8.2
25.0
Q
kW
28.4
29.4
30.3
28.4
29.4
30.3
31.3
32.3
29.4
30.3
31.3
32.3
33.4
34.4
31.3
32.3
33.4
34.4
35.4
36.6
32.3
33.4
34.4
35.4
36.6
37.7
33.4
34.4
35.4
36.6
37.7
SHC
kW
20.7
18.8
17.0
24.1
22.6
20.6
18.8
16.8
26.5
24.5
22.8
20.7
18.4
16.5
26.3
24.2
22.4
20.0
18.1
16.5
27.5
25.7
24.1
21.9
20.1
18.1
29.7
27.9
25.5
23.8
21.9
SHF
0.73
0.64
0.56
0.85
0.77
0.68
0.60
0.52
0.90
0.81
0.73
0.64
0.55
0.48
0.84
0.75
0.67
0.58
0.51
0.45
0.85
0.77
0.70
0.62
0.55
0.48
0.89
0.81
0.72
0.65
0.58
W
kW
7.4
7.5
7.7
7.4
7.5
7.7
7.8
7.9
7.5
7.7
7.8
7.9
8.1
8.2
7.8
7.9
8.1
8.2
8.4
8.6
7.9
8.1
8.2
8.4
8.6
8.8
8.1
8.2
8.4
8.6
8.8
30.0
Q
kW
27.3
28.2
29.1
27.3
28.2
29.1
30.0
31.0
28.2
29.1
30.0
31.0
32.1
33.0
30.0
31.0
32.1
33.0
34.0
35.1
31.0
32.1
33.0
34.0
35.1
36.1
32.1
33.0
34.0
35.1
36.1
SHC
kW
20.2
18.3
16.6
23.8
22.0
20.1
18.3
16.4
25.9
23.9
22.2
20.2
18.0
16.2
25.8
23.6
21.8
19.5
17.7
16.1
27.0
25.4
23.4
21.4
19.7
17.7
29.2
27.4
25.2
23.5
21.3
SHF
0.74
0.65
0.57
0.87
0.78
0.69
0.61
0.53
0.92
0.82
0.74
0.65
0.56
0.49
0.86
0.76
0.68
0.59
0.52
0.46
0.87
0.79
0.71
0.63
0.56
0.49
0.91
0.83
0.74
0.67
0.59
W
kW
7.8
8.0
8.1
7.8
8.0
8.1
8.3
8.5
8.0
8.1
8.3
8.5
8.6
8.8
8.3
8.5
8.6
8.8
9.0
9.2
8.5
8.6
8.8
9.0
9.2
9.4
8.6
8.8
9.0
9.2
9.4
35.0
Q
kW
26.1
27.0
27.9
26.1
27.0
27.9
28.7
29.7
27.0
27.9
28.7
29.7
30.6
31.6
28.7
29.7
30.6
31.6
32.5
33.5
29.7
30.6
31.6
32.5
33.5
34.5
30.6
31.6
32.5
33.5
34.5
SHC
kW
19.6
17.8
15.9
23.2
21.6
19.5
17.8
16.0
25.4
23.2
21.5
19.6
17.4
15.8
25.3
23.2
21.1
19.0
17.2
15.4
26.4
24.8
23.1
21.1
19.1
17.3
28.5
26.9
24.7
22.8
20.7
SHF
0.75
0.66
0.57
0.89
0.80
0.70
0.62
0.54
0.94
0.83
0.75
0.66
0.57
0.50
0.88
0.78
0.69
0.60
0.53
0.46
0.89
0.81
0.73
0.65
0.57
0.50
0.93
0.85
0.76
0.68
0.60
W
kW
8.3
8.4
8.6
8.3
8.4
8.6
8.8
9.0
8.4
8.6
8.8
9.0
9.2
9.4
8.8
9.0
9.2
9.4
9.6
9.8
9.0
9.2
9.4
9.6
9.8
10.0
9.2
9.4
9.6
9.8
10.0
40.0
Q
kW
24.4
25.7
26.6
24.4
25.7
26.6
27.4
28.3
25.7
26.6
27.4
28.3
29.2
30.1
27.4
28.3
29.2
30.1
31.0
31.9
28.3
29.2
30.1
31.0
31.9
32.9
29.2
30.1
31.0
31.9
32.9
SHC
kW
18.5
17.2
15.4
22.2
21.1
18.9
17.3
15.6
24.7
22.6
21.1
19.0
16.9
15.4
24.7
22.6
20.4
18.4
16.7
15.0
25.8
24.2
22.6
20.5
18.5
16.8
28.0
26.2
24.2
22.3
20.1
SHF
0.76
0.67
0.58
0.91
0.82
0.71
0.63
0.55
0.96
0.85
0.77
0.67
0.58
0.51
0.90
0.80
0.70
0.61
0.54
0.47
0.91
0.83
0.75
0.66
0.58
0.51
0.96
0.87
0.78
0.70
0.61
W
kW
8.8
9.0
9.2
8.8
9.0
9.2
9.4
9.6
9.0
9.2
9.4
9.6
9.8
10.0
9.4
9.6
9.8
10.0
10.2
10.4
9.6
9.8
10.0
10.2
10.4
10.7
9.8
10.0
10.2
10.4
10.7
46.0
Q
kW
23.3
24.1
24.9
23.3
24.1
24.9
25.7
26.6
24.1
24.9
25.7
26.6
27.4
28.3
25.7
26.6
27.4
28.3
29.1
30.0
26.6
27.4
28.3
29.1
30.0
30.8
27.4
28.3
29.1
30.0
30.8
SHC
kW
18.4
16.6
14.7
22.1
20.5
18.4
16.7
14.9
24.1
22.2
20.3
18.4
16.4
14.7
23.9
21.8
20.0
18.1
16.3
14.4
25.3
23.6
21.8
19.8
18.0
16.0
27.1
25.8
23.3
21.6
19.7
SHF
0.79
0.69
0.59
0.95
0.85
0.74
0.65
0.56
1.00
0.89
0.79
0.69
0.60
0.52
0.93
0.82
0.73
0.64
0.56
0.48
0.95
0.86
0.77
0.68
0.60
0.52
0.99
0.91
0.80
0.72
0.64
W
kW
9.5
9.7
9.9
9.5
9.7
9.9
10.1
10.3
9.7
9.9
10.1
10.3
10.5
10.7
10.1
10.3
10.5
10.7
10.9
11.1
10.3
10.5
10.7
10.9
11.1
11.4
10.5
10.7
10.9
11.1
11.4
Indoor
DB°C
20
22
24
26
28
30
Q; Cooling Capacity, SHC; Sensible Heat Capacity, W; Compressor Input
Total input = Compressor input + indoor fan motor input + outdoor fan motor input
Air Volume
CMM
l/s
Cooling capacity
Compressor input
90
1500
0.987
0.996
100
1670
1.000
1.000
110
1830
1.012
1.003
120
2000
1.022
1.007
-11-
Outdoor DB°C
Factor for Various Air Flow
Cooling Capacity (Standard Air Flow)
PRHG-10MYA (Use for Low ambient cooling parts)
Heating Capacity (Standard Air Flow)
PRHG-10MYA
–5.0
Indoor
WB°C
15161715161718191617181920211819202122231920212223242021222324
Q
kW
32.7
33.8
35.0
32.7
33.8
35.0
36.2
37.5
33.8
35.0
36.2
37.5
38.8
40.1
36.2
37.5
38.8
40.1
41.4
42.8
37.5
38.8
40.1
41.4
42.8
44.3
38.8
40.1
41.4
42.8
44.3
SHC
kW
22.5
21.0
18.9
26.5
24.7
22.8
21.0
19.1
28.8
26.6
25.0
22.9
20.9
18.8
28.6
26.6
24.4
22.5
20.7
18.8
30.4
28.3
26.5
24.4
22.3
20.4
31.8
30.1
28.2
26.1
24.3
SHF
0.69
0.62
0.54
0.81
0.73
0.65
0.58
0.51
0.85
0.76
0.69
0.61
0.54
0.47
0.79
0.71
0.63
0.56
0.50
0.44
0.81
0.73
0.66
0.59
0.52
0.46
0.82
0.75
0.68
0.61
0.55
W
kW
6.3
6.3
6.4
6.3
6.3
6.4
6.5
6.6
6.3
6.4
6.5
6.6
6.7
6.8
6.5
6.6
6.7
6.8
6.9
7.0
6.6
6.7
6.8
6.9
7.0
7.0
6.7
6.8
6.9
7.0
7.0
0.0
Q
kW
32.1
33.3
34.4
32.1
33.3
34.4
35.6
36.8
33.3
34.4
35.6
36.8
38.1
39.4
35.6
36.8
38.1
39.4
40.6
42.0
36.8
38.1
39.4
40.6
42.0
43.4
38.1
39.4
40.6
42.0
43.4
SHC
kW
22.2
20.6
18.6
26.3
24.6
22.7
20.6
18.8
28.6
26.1
24.5
22.5
20.6
18.5
28.1
26.1
24.4
22.4
20.3
18.5
29.8
27.8
26.0
24.0
21.9
20.0
31.6
29.5
27.6
25.6
23.9
SHF
0.69
0.62
0.54
0.82
0.74
0.66
0.58
0.51
0.86
0.76
0.69
0.61
0.54
0.47
0.79
0.71
0.64
0.57
0.50
0.44
0.81
0.73
0.66
0.59
0.52
0.46
0.83
0.75
0.68
0.61
0.55
W
kW
6.3
6.3
6.4
6.3
6.3
6.4
6.5
6.6
6.3
6.4
6.5
6.6
6.7
6.8
6.5
6.6
6.7
6.8
6.9
7.0
6.6
6.7
6.8
6.9
7.0
7.0
6.7
6.8
6.9
7.0
7.0
5.0
Q
kW
31.6
32.8
33.9
31.6
32.8
33.9
35.0
36.3
32.8
33.9
35.0
36.3
37.5
38.7
35.0
36.3
37.5
38.7
40.0
41.4
36.3
37.5
38.7
40.0
41.4
42.7
37.5
38.7
40.0
41.4
42.7
SHC
kW
22.1
20.3
18.3
25.9
24.2
22.4
20.3
18.5
28.2
26.1
24.5
22.5
20.2
18.2
28.0
26.1
24.0
22.1
20.0
18.2
29.7
27.7
26.0
24.0
21.9
20.1
31.5
29.4
27.6
25.6
23.9
SHF
0.70
0.62
0.54
0.82
0.74
0.66
0.58
0.51
0.86
0.77
0.70
0.62
0.54
0.47
0.80
0.72
0.64
0.57
0.50
0.44
0.82
0.74
0.67
0.60
0.53
0.47
0.84
0.76
0.69
0.62
0.56
W
kW
6.4
6.4
6.5
6.4
6.4
6.5
6.6
6.7
6.4
6.5
6.6
6.7
6.8
6.9
6.6
6.7
6.8
6.9
7.0
7.1
6.7
6.8
6.9
7.0
7.1
7.2
6.8
6.9
7.0
7.1
7.2
10.0
Q
kW
31.1
32.2
33.3
31.1
32.2
33.3
34.4
35.6
32.2
33.3
34.4
35.6
36.8
38.0
34.4
35.6
36.8
38.0
39.3
40.6
35.6
36.8
38.0
39.3
40.6
41.9
36.8
38.0
39.3
40.6
41.9
SHC
kW
22.1
20.3
18.3
25.8
24.1
22.3
20.3
18.2
28.0
26.0
24.1
22.1
19.9
17.9
27.5
25.6
23.9
22.1
20.0
17.9
29.2
27.2
25.5
23.6
21.5
19.7
31.3
29.3
27.1
25.2
23.5
SHF
0.71
0.63
0.55
0.83
0.75
0.67
0.59
0.51
0.87
0.78
0.70
0.62
0.54
0.47
0.80
0.72
0.65
0.58
0.51
0.44
0.82
0.74
0.67
0.60
0.53
0.47
0.85
0.77
0.69
0.62
0.56
W
kW
6.6
6.6
6.7
6.6
6.6
6.7
6.8
6.9
6.6
6.7
6.8
6.9
7.0
7.0
6.8
6.9
7.0
7.0
7.2
7.3
6.9
7.0
7.0
7.2
7.3
7.4
7.0
7.0
7.2
7.3
7.4
15.0
Q
kW
30.5
31.6
32.7
30.5
31.6
32.7
33.7
34.9
31.6
32.7
33.7
34.9
36.1
37.3
33.7
34.9
36.1
37.3
38.5
39.7
34.9
36.1
37.3
38.5
39.7
41.0
36.1
37.3
38.5
39.7
41.0
SHC
kW
22.0
19.9
18.0
25.3
23.7
21.9
19.9
18.2
27.8
25.8
23.9
22.0
19.8
17.9
27.3
25.5
23.5
21.6
19.6
17.9
29.0
27.1
25.3
23.5
21.5
19.3
31.0
29.1
26.9
25.0
23.4
SHF
0.72
0.63
0.55
0.83
0.75
0.67
0.59
0.52
0.88
0.79
0.71
0.63
0.55
0.48
0.81
0.73
0.65
0.58
0.51
0.45
0.83
0.75
0.68
0.61
0.54
0.47
0.86
0.78
0.70
0.63
0.57
W
kW
6.8
6.9
7.0
6.8
6.9
7.0
7.0
7.1
6.9
7.0
7.0
7.1
7.2
7.3
7.0
7.1
7.2
7.3
7.5
7.6
7.1
7.2
7.3
7.5
7.6
7.8
7.2
7.3
7.5
7.6
7.8
Indoor
DB°C
20
22
24
26
28
30
Q; Cooling Capacity, SHC; Sensible Heat Capacity, W; Compressor Input
Total input = Compressor input + indoor fan motor input + outdoor fan motor input
Air Volume
CMM
l/s
Cooling capacity
Compressor input
90
1500
0.987
0.996
100
1670
1.000
1.000
110
1830
1.012
1.003
120
2000
1.022
1.007
Factor for Various Air Flow
Air Volume
CMM
l/s
Heating capacity
Compressor input
90
1500
0.991
1.013
100
1670
1.000
1.000
110
1830
1.009
0.987
120
2000
1.017
0.974
Indoor
DB°C
15161718192021222324252627
Q
kW
21.5
21.4
21.3
21.2
21.1
21.0
20.9
20.8
20.7
20.6
20.5
20.5
20.4
W
kW
5.5
5.5
5.5
5.6
5.6
5.6
5.7
5.7
5.7
5.8
5.8
5.8
5.8
Q
kW
18.7
18.6
18.5
18.4
18.3
18.2
18.1
18.0
17.9
17.8
17.8
17.8
17.7
W
kW
5.3
5.3
5.3
5.4
5.4
5.4
5.5
5.5
5.5
5.6
5.6
5.6
5.6
–10–15
Q
kW
24.6
24.5
24.4
24.3
24.2
24.1
24.0
23.9
23.8
23.7
23.5
23.5
23.4
W
kW
5.8
5.8
5.9
5.9
6.0
6.0
6.1
6.1
6.2
6.2
6.3
6.3
6.3
–5
Q
kW
28.0
27.9
27.8
27.7
27.6
27.5
27.4
27.3
27.2
27.1
26.9
26.9
26.8
W
kW
6.3
6.4
6.4
6.5
6.6
6.6
6.7
6.8
6.8
6.9
6.9
7.0
7.0
0
Q
kW
31.9
31.8
31.7
31.6
31.4
31.3
31.2
31.1
30.9
30.8
30.7
30.6
30.5
W
kW
6.9
7.0
7.1
7.1
7.2
7.3
7.4
7.4
7.5
7.6
7.7
7.7
7.8
5
Q
kW
36.5
36.4
36.2
36.1
35.9
35.8
35.7
35.5
35.3
35.2
35.1
35.0
34.8
W
kW
7.7
7.8
7.9
7.9
8.0
8.1
8.2
8.3
8.4
8.5
8.6
8.6
8.7
10 15
Q
kW
41.1
40.9
40.7
40.6
40.4
40.2
40.1
39.9
39.7
39.6
39.4
39.3
39.1
W
kW
8.4
8.5
8.6
8.7
8.8
8.9
9.0
9.1
9.2
9.3
9.4
9.5
9.6
OD WB°C
Q; Heating Capacity, W; Compressor Input
-12-
Outdoor DB°C
Factor for Various Air Flow
Cooling Capacity (Standard Air Flow)
PRHG-15MYA
20.0
Indoor
WB°C
15161715161718191617181920211819202122231920212223242021222324
Q
kW
44.5
45.7
47.2
44.5
45.7
47.2
48.9
50.5
45.7
47.2
48.9
50.5
52.1
53.9
48.9
50.5
52.1
53.9
55.7
57.3
50.5
52.1
53.9
55.7
57.3
59.0
52.1
53.9
55.7
57.3
59.0
SHC
kW
32.0
29.2
26.0
37.8
34.7
31.6
28.9
26.3
40.2
37.3
34.7
31.8
28.7
26.4
40.6
37.4
34.4
31.8
29.0
25.8
43.4
40.1
37.2
34.5
31.5
28.3
45.8
43.1
40.7
37.2
33.6
SHF
0.72
0.64
0.55
0.85
0.76
0.67
0.59
0.52
0.88
0.79
0.71
0.63
0.55
0.49
0.83
0.74
0.66
0.59
0.52
0.45
0.86
0.77
0.69
0.62
0.55
0.48
0.88
0.80
0.73
0.65
0.57
W
kW
10.3
10.4
10.5
10.3
10.4
10.5
10.7
10.9
10.4
10.5
10.7
10.9
11.0
11.2
10.7
10.9
11.0
11.2
11.4
11.5
10.9
11.0
11.2
11.4
11.5
11.7
11.0
11.2
11.4
11.5
11.7
25.0
Q
kW
43.3
44.5
46.0
43.3
44.5
46.0
47.6
49.2
44.5
46.0
47.6
49.2
50.7
52.3
47.6
49.2
50.7
52.3
54.0
55.7
49.2
50.7
52.3
54.0
55.7
57.4
50.7
52.3
54.0
55.7
57.4
SHC
kW
31.2
28.5
25.3
37.2
34.3
31.3
28.1
25.6
39.6
36.8
34.3
31.0
27.9
25.6
40.0
36.9
33.5
30.9
28.1
25.1
42.8
39.5
36.6
34.0
31.2
28.1
45.1
42.4
39.4
36.2
32.7
SHF
0.72
0.64
0.55
0.86
0.77
0.68
0.59
0.52
0.89
0.80
0.72
0.63
0.55
0.49
0.84
0.75
0.66
0.59
0.52
0.45
0.87
0.78
0.70
0.63
0.56
0.49
0.89
0.81
0.73
0.65
0.57
W
kW
10.9
11.1
11.3
10.9
11.1
11.3
11.4
11.6
11.1
11.3
11.4
11.6
11.8
12.0
11.4
11.6
11.8
12.0
12.2
12.4
11.6
11.8
12.0
12.2
12.4
12.6
11.8
12.0
12.2
12.4
12.6
30.0
Q
kW
42.0
43.2
44.7
42.0
43.2
44.7
46.2
47.8
43.2
44.7
46.2
47.8
49.3
50.8
46.2
47.8
49.3
50.8
52.4
54.0
47.8
49.3
50.8
52.4
54.0
55.6
49.3
50.8
52.4
54.0
55.6
SHC
kW
30.7
28.1
25.0
36.5
33.7
30.8
27.7
25.3
39.3
36.2
33.7
30.6
27.6
25.4
39.7
36.3
33.0
30.5
27.8
24.3
42.1
38.9
36.1
33.5
30.2
27.2
44.4
41.7
38.8
35.6
32.2
SHF
0.73
0.65
0.56
0.87
0.78
0.69
0.60
0.53
0.91
0.81
0.73
0.64
0.56
0.50
0.86
0.76
0.67
0.60
0.53
0.45
0.88
0.79
0.71
0.64
0.56
0.49
0.90
0.82
0.74
0.66
0.58
W
kW
11.6
11.8
12.0
11.6
11.8
12.0
12.2
12.4
11.8
12.0
12.2
12.4
12.6
12.8
12.2
12.4
12.6
12.8
13.0
13.2
12.4
12.6
12.8
13.0
13.2
13.5
12.6
12.8
13.0
13.2
13.5
35.0
Q
kW
40.8
42.0
43.3
40.8
42.0
43.3
44.8
46.3
42.0
43.3
44.8
46.3
47.7
49.2
44.8
46.3
47.7
49.2
50.7
52.3
46.3
47.7
49.2
50.7
52.3
53.9
47.7
49.2
50.7
52.3
53.9
SHC
kW
30.2
27.7
24.7
35.9
33.2
30.3
27.3
24.5
39.1
35.9
33.2
30.1
27.2
24.6
39.0
35.7
32.4
30.0
26.9
24.1
41.2
38.2
35.4
32.4
29.8
27.0
43.9
41.3
38.0
35.0
31.8
SHF
0.74
0.66
0.57
0.88
0.79
0.70
0.61
0.53
0.93
0.83
0.74
0.65
0.57
0.50
0.87
0.77
0.68
0.61
0.53
0.46
0.89
0.80
0.72
0.64
0.57
0.50
0.92
0.84
0.75
0.67
0.59
W
kW
12.3
12.5
12.7
12.3
12.5
12.7
13.0
13.2
12.5
12.7
13.0
13.2
13.4
13.6
13.0
13.2
13.4
13.6
13.9
14.1
13.2
13.4
13.6
13.9
14.1
14.4
13.4
13.6
13.9
14.1
14.4
40.0
Q
kW
39.5
40.7
41.9
39.5
40.7
41.9
43.2
44.7
40.7
41.9
43.2
44.7
46.1
47.6
43.2
44.7
46.1
47.6
49.0
50.5
44.7
46.1
47.6
49.0
50.5
52.0
46.1
47.6
49.0
50.5
52.0
SHC
kW
29.6
27.3
23.9
35.2
32.6
29.7
26.8
24.1
38.7
35.6
32.4
29.5
26.7
24.3
38.4
34.9
31.8
29.5
26.5
23.2
40.7
37.3
34.7
31.9
28.8
26.0
43.3
40.9
37.2
34.3
31.2
SHF
0.75
0.67
0.57
0.89
0.80
0.71
0.62
0.54
0.95
0.85
0.75
0.66
0.58
0.51
0.89
0.78
0.69
0.62
0.54
0.46
0.91
0.81
0.73
0.65
0.57
0.50
0.94
0.86
0.76
0.68
0.60
W
kW
13.0
13.3
13.5
13.0
13.3
13.5
13.8
14.1
13.3
13.5
13.8
14.1
14.3
14.6
13.8
14.1
14.3
14.6
14.8
15.0
14.1
14.3
14.6
14.8
15.0
15.3
14.3
14.6
14.8
15.0
15.3
46.0
Q
kW
37.8
39.0
40.1
37.8
39.0
40.1
41.2
42.6
39.0
40.1
41.2
42.6
44.1
45.5
41.2
42.6
44.1
45.5
47.0
48.4
42.6
44.1
45.5
47.0
48.4
49.8
44.1
45.5
47.0
48.4
49.8
SHC
kW
29.1
26.5
23.3
34.4
32.0
28.9
26.0
23.4
37.8
34.9
31.7
28.5
26.0
23.2
37.1
34.1
31.3
28.7
25.9
22.7
39.6
36.6
34.1
31.0
28.1
25.4
41.9
40.0
36.7
33.9
30.9
SHF
0.77
0.68
0.58
0.91
0.82
0.72
0.63
0.55
0.97
0.87
0.77
0.67
0.59
0.51
0.90
0.80
0.71
0.63
0.55
0.47
0.93
0.83
0.75
0.66
0.58
0.51
0.95
0.88
0.78
0.70
0.62
W
kW
13.9
14.2
14.5
13.9
14.2
14.5
14.8
15.1
14.2
14.5
14.8
15.1
15.4
15.7
14.8
15.1
15.4
15.7
16.0
16.2
15.1
15.4
15.7
16.0
16.2
16.4
15.4
15.7
16.0
16.2
16.4
Indoor
DB°C
20
22
24
26
28
30
Q; Cooling Capacity, SHC; Sensible Heat Capacity, W; Compressor Input
Total input = Compressor input + indoor fan motor input + outdoor fan motor input
Air Volume
CMM
l/s
Cooling capacity
Compressor input
120
2000
0.962
0.984
140
2330
0.982
0.991
160
2670
1.000
1.000
180
3000
1.018
1.009
-13-
Outdoor DB°C
Factor for Various Air Flow
Cooling Capacity (Standard Air Flow)
PRHG-15MYA (Use for Low ambient cooling parts)
Heating Capacity (Standard Air Flow)
PRHG-15MYA
–5.0
Indoor
WB°C
15161715161718191617181920211819202122231920212223242021222324
Q
kW
49.4
50.9
52.6
49.4
50.9
52.6
54.6
56.5
50.9
52.6
54.6
56.5
58.4
60.5
54.6
56.5
58.4
60.5
62.7
64.6
56.5
58.4
60.5
62.7
64.6
66.6
58.4
60.5
62.7
64.6
66.6
SHC
kW
35.1
31.0
27.9
41.0
37.6
34.7
31.7
28.8
43.7
41.0
38.2
34.5
31.5
28.4
43.7
40.1
37.4
34.5
31.3
28.4
46.3
43.2
40.6
37.6
34.2
31.3
49.1
46.0
43.2
40.0
37.3
SHF
0.71
0.61
0.53
0.83
0.74
0.66
0.58
0.51
0.86
0.78
0.70
0.61
0.54
0.47
0.80
0.71
0.64
0.57
0.50
0.44
0.82
0.74
0.67
0.60
0.53
0.47
0.84
0.76
0.69
0.62
0.56
W
kW
8.8
8.9
9.0
8.8
8.9
9.0
9.1
9.2
8.9
9.0
9.1
9.2
9.3
9.4
9.1
9.2
9.3
9.4
9.5
9.6
9.2
9.3
9.4
9.5
9.6
9.7
9.3
9.4
9.5
9.6
9.7
0.0
Q
kW
48.6
50.0
51.7
48.6
50.0
51.7
53.7
55.5
50.0
51.7
53.7
55.5
57.4
59.4
53.7
55.5
57.4
59.4
61.5
63.4
55.5
57.4
59.4
61.5
63.4
65.4
57.4
59.4
61.5
63.4
65.4
SHC
kW
34.5
31.0
27.4
40.3
37.0
34.1
31.1
28.3
43.5
40.3
37.6
34.0
31.0
27.9
42.9
39.4
36.7
33.9
30.8
27.9
45.5
42.4
39.8
36.9
33.6
30.7
48.8
45.8
42.4
39.3
36.6
SHF
0.71
0.62
0.53
0.83
0.74
0.66
0.58
0.51
0.87
0.78
0.70
0.61
0.54
0.47
0.80
0.71
0.64
0.57
0.50
0.44
0.82
0.74
0.67
0.60
0.53
0.47
0.85
0.77
0.69
0.62
0.56
W
kW
8.9
9.0
9.1
8.9
9.0
9.1
9.2
9.3
9.0
9.1
9.2
9.3
9.4
9.5
9.2
9.3
9.4
9.5
9.6
9.7
9.3
9.4
9.5
9.6
9.7
9.8
9.4
9.5
9.6
9.7
9.8
5.0
Q
kW
47.9
49.2
50.9
47.9
49.2
50.9
52.8
54.7
49.2
50.9
52.8
54.7
56.5
58.5
52.8
54.7
56.5
58.5
60.5
62.4
54.7
56.5
58.5
60.5
62.4
64.3
56.5
58.5
60.5
62.4
64.3
SHC
kW
34.0
30.5
27.0
39.7
36.4
33.6
30.7
27.9
42.8
39.7
37.0
33.5
30.5
27.5
42.8
39.3
36.1
33.3
30.3
27.4
45.4
42.3
39.8
36.9
33.7
30.2
48.0
45.0
42.4
38.7
36.0
SHF
0.71
0.62
0.53
0.83
0.74
0.66
0.58
0.51
0.87
0.78
0.70
0.61
0.54
0.47
0.81
0.72
0.64
0.57
0.50
0.44
0.83
0.75
0.68
0.61
0.54
0.47
0.85
0.77
0.70
0.62
0.56
W
kW
9.1
9.2
9.3
9.1
9.2
9.3
9.4
9.5
9.2
9.3
9.4
9.5
9.6
9.7
9.4
9.5
9.6
9.7
9.8
9.9
9.5
9.6
9.7
9.8
9.9
10.1
9.6
9.7
9.8
9.9
10.1
10.0
Q
kW
47.1
48.4
50.1
47.1
48.4
50.1
51.9
53.7
48.4
50.1
51.9
53.7
55.4
57.4
51.9
53.7
55.4
57.4
59.4
61.2
53.7
55.4
57.4
59.4
61.2
63.1
55.4
57.4
59.4
61.2
63.1
SHC
kW
33.9
30.5
27.5
39.5
36.3
33.5
30.6
27.9
42.6
39.5
36.9
33.3
30.5
27.6
42.1
38.6
36.0
33.3
30.3
27.5
45.1
41.6
39.0
36.2
33.0
30.3
47.7
44.8
42.2
38.5
36.0
SHF
0.72
0.63
0.55
0.84
0.75
0.67
0.59
0.52
0.88
0.79
0.71
0.62
0.55
0.48
0.81
0.72
0.65
0.58
0.51
0.45
0.84
0.75
0.68
0.61
0.54
0.48
0.86
0.78
0.71
0.63
0.57
W
kW
9.4
9.5
9.6
9.4
9.5
9.6
9.7
9.8
9.5
9.6
9.7
9.8
10.0
10.1
9.7
9.8
10.0
10.1
10.2
10.3
9.8
10.0
10.1
10.2
10.3
10.5
10.0
10.1
10.2
10.3
10.5
15.0
Q
kW
46.2
47.5
49.1
46.2
47.5
49.1
50.9
52.6
47.5
49.1
50.9
52.6
54.3
56.3
50.9
52.6
54.3
56.3
58.2
59.9
52.6
54.3
56.3
58.2
59.9
61.8
54.3
56.3
58.2
59.9
61.8
SHC
kW
33.3
29.9
27.0
38.8
35.6
32.9
30.0
27.4
41.8
38.8
36.1
32.6
29.9
27.0
41.7
38.4
35.3
32.6
29.7
27.0
44.7
41.3
38.8
36.1
33.0
29.7
47.3
44.5
41.9
38.4
35.2
SHF
0.72
0.63
0.55
0.84
0.75
0.67
0.59
0.52
0.88
0.79
0.71
0.62
0.55
0.48
0.82
0.73
0.65
0.58
0.51
0.45
0.85
0.76
0.69
0.62
0.55
0.48
0.87
0.79
0.72
0.64
0.57
W
kW
9.8
9.9
10.0
9.8
9.9
10.0
10.1
10.2
9.9
10.0
10.1
10.2
10.4
10.5
10.1
10.2
10.4
10.5
10.7
10.8
10.2
10.4
10.5
10.7
10.8
11.0
10.4
10.5
10.7
10.8
11.0
Indoor
DB°C
20
22
24
26
28
30
Q; Cooling Capacity, SHC; Sensible Heat Capacity, W; Compressor Input
Total input = Compressor input + indoor fan motor input + outdoor fan motor input
Air Volume
CMM
l/s
Cooling capacity
Compressor input
120
2000
0.962
0.984
140
2330
0.982
0.991
160
2670
1.000
1.000
180
3000
1.018
1.009
Factor for Various Air Flow
Air Volume
CMM
l/s
Heating capacity
Compressor input
120
2000
0.973
1.025
140
2330
0.985
1.013
160
2670
1.000
1.000
180
3000
1.015
0.987
Indoor
DB°C
15161718192021222324252627
Q
kW
31.0
30.8
30.6
30.4
30.2
30.1
29.9
29.8
29.6
29.5
29.4
29.3
29.1
W
kW
7.7
7.7
7.8
7.8
7.9
7.9
8.0
8.0
8.1
8.1
8.2
8.2
8.3
Q
kW
27.5
27.3
27.1
26.9
26.6
26.5
26.3
26.2
26.0
25.9
25.8
25.7
25.5
W
kW
7.0
7.0
7.1
7.1
7.2
7.2
7.4
7.4
7.5
7.5
7.6
7.6
7.7
–10–15
Q
kW
35.1
34.9
34.7
34.5
34.4
34.3
34.1
34.0
33.8
33.7
33.6
33.5
33.3
W
kW
8.5
8.5
8.6
8.6
8.7
8.8
8.8
8.9
8.9
9.0
9.1
9.2
9.3
–5
Q
kW
39.9
39.7
39.5
39.3
39.2
39.0
38.9
38.8
38.7
38.5
38.4
38.2
38.0
W
kW
9.3
9.4
9.5
9.7
9.8
9.9
10.0
10.0
10.1
10.2
10.3
10.4
10.5
0
Q
kW
45.4
45.2
45.0
44.8
44.6
44.5
44.3
44.2
44.1
43.9
43.8
43.6
43.4
W
kW
10.4
10.5
10.6
10.8
10.9
11.1
11.2
11.3
11.4
11.5
11.6
11.7
11.9
5
Q
kW
51.6
51.4
51.2
51.0
50.8
50.6
50.5
50.3
50.2
50.0
49.8
49.6
49.4
W
kW
11.6
11.7
12.0
12.1
12.2
12.4
12.5
12.6
12.7
13.0
13.1
13.2
13.4
10 15
Q
kW
58.8
58.6
58.3
58.1
57.8
57.6
57.4
57.2
57.0
56.7
56.5
56.2
56.0
W
kW
13.0
13.2
13.3
13.5
13.7
13.8
14.1
14.2
14.4
14.5
14.7
14.9
15.0
OD WB°C
Q; Heating Capacity, W; Compressor Input
-14-
Outdoor DB°C
Factor for Various Air Flow
Cooling Capacity (Standard Air Flow)
PRHG-20MYA
20.0
Indoor
WB°C
15161715161718191617181920211819202122231920212223242021222324
Q
kW
59.3
61.3
63.2
59.3
61.3
63.2
65.0
67.0
61.3
63.2
65.0
67.0
69.0
71.2
65.0
67.0
69.0
71.2
73.4
75.7
67.0
69.0
71.2
73.4
75.7
78.0
69.0
71.2
73.4
75.7
78.0
SHC
kW
42.7
39.2
34.8
50.4
46.6
43.0
39.0
34.8
54.6
50.6
46.2
42.2
38.0
34.2
54.0
49.6
45.5
42.0
38.2
34.1
57.0
53.1
49.8
45.5
41.6
37.4
60.0
56.2
52.1
48.4
44.5
SHF
0.72
0.64
0.55
0.85
0.76
0.68
0.60
0.52
0.89
0.80
0.71
0.63
0.55
0.48
0.83
0.74
0.66
0.59
0.52
0.45
0.85
0.77
0.70
0.62
0.55
0.48
0.87
0.79
0.71
0.64
0.57
W
kW
13.7
14.0
14.1
13.7
14.0
14.1
14.3
14.5
14.0
14.1
14.3
14.5
14.8
15.0
14.3
14.5
14.8
15.0
15.2
15.5
14.5
14.8
15.0
15.2
15.5
15.8
14.8
15.0
15.2
15.5
15.8
25.0
Q
kW
57.4
59.5
61.2
57.4
59.5
61.2
63.0
64.9
59.5
61.2
63.0
64.9
66.8
68.9
63.0
64.9
66.8
68.9
71.0
73.3
64.9
66.8
68.9
71.0
73.3
75.6
66.8
68.9
71.0
73.3
75.6
SHC
kW
41.9
38.1
33.7
49.4
45.8
41.6
37.8
34.4
53.6
49.6
45.4
41.5
37.4
33.8
52.9
48.7
44.8
41.3
37.6
33.0
55.8
52.1
48.9
44.7
41.0
37.0
58.8
55.1
51.1
47.6
43.8
SHF
0.73
0.64
0.55
0.86
0.77
0.68
0.60
0.53
0.90
0.81
0.72
0.64
0.56
0.49
0.84
0.75
0.67
0.60
0.53
0.45
0.86
0.78
0.71
0.63
0.56
0.49
0.88
0.80
0.72
0.65
0.58
W
kW
14.5
14.8
15.0
14.5
14.8
15.0
15.2
15.4
14.8
15.0
15.2
15.4
15.7
16.1
15.2
15.4
15.7
16.1
16.4
16.7
15.4
15.7
16.1
16.4
16.7
17.0
15.7
16.1
16.4
16.7
17.0
30.0
Q
kW
55.4
57.6
59.2
55.4
57.6
59.2
60.9
62.7
57.6
59.2
60.9
62.7
64.6
66.6
60.9
62.7
64.6
66.6
68.6
70.8
62.7
64.6
66.6
68.6
70.8
72.8
64.6
66.6
68.6
70.8
72.8
SHC
kW
40.4
37.4
33.2
48.2
44.9
40.8
37.1
33.2
53.0
48.5
44.5
40.8
36.8
32.6
51.8
47.7
43.9
40.6
37.0
32.6
54.5
51.0
48.0
43.9
39.6
35.7
58.1
54.6
50.1
46.7
43.0
SHF
0.73
0.65
0.56
0.87
0.78
0.69
0.61
0.53
0.92
0.82
0.73
0.65
0.57
0.49
0.85
0.76
0.68
0.61
0.54
0.46
0.87
0.79
0.72
0.64
0.56
0.49
0.90
0.82
0.73
0.66
0.59
W
kW
15.2
15.6
15.9
15.2
15.6
15.9
16.2
16.5
15.6
15.9
16.2
16.5
16.7
17.1
16.2
16.5
16.7
17.1
17.5
17.9
16.5
16.7
17.1
17.5
17.9
18.3
16.7
17.1
17.5
17.9
18.3
35.0
Q
kW
53.4
55.5
57.0
53.4
55.5
57.0
58.7
60.8
55.5
57.0
58.7
60.8
62.2
64.0
58.7
60.8
62.2
64.0
66.0
68.0
60.8
62.2
64.0
66.0
68.0
69.9
62.2
64.0
66.0
68.0
69.9
SHC
kW
39.5
36.1
31.9
47.0
43.8
39.9
35.8
32.2
51.6
47.3
43.4
40.1
35.5
32.0
51.1
46.8
42.9
39.7
35.6
31.3
54.1
50.4
46.7
42.9
38.8
35.0
57.2
53.8
49.5
45.6
41.9
SHF
0.74
0.65
0.56
0.88
0.79
0.70
0.61
0.53
0.93
0.83
0.74
0.66
0.57
0.50
0.87
0.77
0.69
0.62
0.54
0.46
0.89
0.81
0.73
0.65
0.57
0.50
0.92
0.84
0.75
0.67
0.60
W
kW
16.2
16.6
16.8
16.2
16.6
16.8
17.2
17.5
16.6
16.8
17.2
17.5
17.9
18.3
17.2
17.5
17.9
18.3
18.6
19.1
17.5
17.9
18.3
18.6
19.1
19.5
17.9
18.3
18.6
19.1
19.5
40.0
Q
kW
51.4
53.2
54.8
51.4
53.2
54.8
56.4
58.0
53.2
54.8
56.4
58.0
59.7
61.4
56.4
58.0
59.7
61.4
63.3
65.0
58.0
59.7
61.4
63.3
65.0
66.7
59.7
61.4
63.3
65.0
66.7
SHC
kW
38.6
35.1
31.2
46.3
43.1
38.9
35.0
31.3
50.5
46.6
42.3
38.9
34.6
31.3
50.2
45.8
41.8
38.7
34.8
30.6
52.8
49.6
45.4
41.8
37.7
34.0
56.1
52.8
48.7
44.9
41.4
SHF
0.75
0.66
0.57
0.90
0.81
0.71
0.62
0.54
0.95
0.85
0.75
0.67
0.58
0.51
0.89
0.79
0.70
0.63
0.55
0.47
0.91
0.83
0.74
0.66
0.58
0.51
0.94
0.86
0.77
0.69
0.62
W
kW
17.1
17.5
17.9
17.1
17.5
17.9
18.3
18.6
17.5
17.9
18.3
18.6
19.0
19.4
18.3
18.6
19.0
19.4
19.9
20.2
18.6
19.0
19.4
19.9
20.2
20.8
19.0
19.4
19.9
20.2
20.8
46.0
Q
kW
48.8
50.4
51.9
48.8
50.4
51.9
53.4
54.9
50.4
51.9
53.4
54.9
56.5
58.2
53.4
54.9
56.5
58.2
59.8
61.1
54.9
56.5
58.2
59.8
61.1
62.5
56.5
58.2
59.8
61.1
62.5
SHC
kW
37.6
34.3
30.1
44.9
41.8
37.9
33.6
29.6
49.4
45.7
41.7
37.3
33.3
30.3
48.6
44.5
40.7
37.8
33.5
28.7
52.2
48.0
44.2
40.7
36.7
32.5
55.4
51.8
47.8
43.4
40.0
SHF
0.77
0.68
0.58
0.92
0.83
0.73
0.63
0.54
0.98
0.88
0.78
0.68
0.59
0.52
0.91
0.81
0.72
0.65
0.56
0.47
0.95
0.85
0.76
0.68
0.60
0.52
0.98
0.89
0.80
0.71
0.64
W
kW
18.3
18.7
19.2
18.3
18.7
19.2
19.6
19.9
18.7
19.2
19.6
19.9
20.3
20.8
19.6
19.9
20.3
20.8
21.4
21.8
19.9
20.3
20.8
21.4
21.8
22.3
20.3
20.8
21.4
21.8
22.3
Indoor
DB°C
20
22
24
26
28
30
Q; Cooling Capacity, SHC; Sensible Heat Capacity, W; Compressor Input
Total input = Compressor input + indoor fan motor input + outdoor fan motor input
Air Volume
CMM
l/s
Cooling capacity
Compressor input
170
2830
0.977
0.995
180
3000
0.987
0.997
200
3330
1.000
1.000
220
3670
1.010
1.003
240
4000
1.020
1.007
-15-
Outdoor DB°C
Factor for Various Air Flow
Cooling Capacity (Standard Air Flow)
PRHG-20MYA (Use for Low ambient cooling parts)
Heating Capacity (Standard Air Flow)
PRHG-20MYA
–5.0
Indoor
WB°C
15161715161718191617181920211819202122231920212223242021222324
Q
kW
65.9
68.2
70.5
65.9
68.2
70.5
72.6
75.0
68.2
70.5
72.6
75.0
77.3
80.0
72.6
75.0
77.3
80.0
82.6
85.3
75.0
77.3
80.0
82.6
85.3
88.1
77.3
80.0
82.6
85.3
88.1
SHC
kW
46.1
42.3
38.8
54.0
50.5
46.5
42.1
38.2
58.0
54.3
50.1
45.7
41.8
37.6
57.4
53.2
49.5
45.6
41.3
37.5
60.7
56.5
52.8
48.7
45.2
41.4
64.2
60.8
57.0
52.9
48.4
SHF
0.70
0.62
0.55
0.82
0.74
0.66
0.58
0.51
0.85
0.77
0.69
0.61
0.54
0.47
0.79
0.71
0.64
0.57
0.50
0.44
0.81
0.73
0.66
0.59
0.53
0.47
0.83
0.76
0.69
0.62
0.55
W
kW
11.9
12.0
12.1
11.9
12.0
12.1
12.3
12.5
12.0
12.1
12.3
12.5
12.6
12.8
12.3
12.5
12.6
12.8
12.9
13.1
12.5
12.6
12.8
12.9
13.1
13.2
12.6
12.8
12.9
13.1
13.2
0.0
Q
kW
64.8
67.0
69.2
64.8
67.0
69.2
71.3
73.6
67.0
69.2
71.3
73.6
76.0
78.5
71.3
73.6
76.0
78.5
81.1
83.7
73.6
76.0
78.5
81.1
83.7
86.4
76.0
78.5
81.1
83.7
86.4
SHC
kW
45.3
41.6
38.1
53.1
49.6
45.7
41.4
37.6
57.0
53.3
49.2
44.9
41.0
36.9
56.3
52.3
48.6
44.8
40.5
36.8
59.6
55.5
51.8
48.6
44.4
40.6
63.0
59.7
55.9
51.9
48.4
SHF
0.70
0.62
0.55
0.82
0.74
0.66
0.58
0.51
0.85
0.77
0.69
0.61
0.54
0.47
0.79
0.71
0.64
0.57
0.50
0.44
0.81
0.73
0.66
0.60
0.53
0.47
0.83
0.76
0.69
0.62
0.56
W
kW
12.0
12.2
12.3
12.0
12.2
12.3
12.4
12.6
12.2
12.3
12.4
12.6
12.7
12.9
12.4
12.6
12.7
12.9
13.0
13.2
12.6
12.7
12.9
13.0
13.2
13.4
12.7
12.9
13.0
13.2
13.4
5.0
Q
kW
63.8
66.1
68.2
63.8
66.1
68.2
70.2
72.5
66.1
68.2
70.2
72.5
74.8
77.3
70.2
72.5
74.8
77.3
79.8
82.4
72.5
74.8
77.3
79.8
82.4
85.0
74.8
77.3
79.8
82.4
85.0
SHC
kW
44.7
41.0
37.5
53.0
49.5
45.0
40.7
37.0
56.8
53.2
49.2
45.0
40.4
36.3
56.2
52.2
48.6
44.8
40.7
36.3
59.5
55.3
51.8
48.7
44.5
40.0
62.8
59.5
55.8
51.9
47.6
SHF
0.70
0.62
0.55
0.83
0.75
0.66
0.58
0.51
0.86
0.78
0.70
0.62
0.54
0.47
0.80
0.72
0.65
0.58
0.51
0.44
0.82
0.74
0.67
0.61
0.54
0.47
0.84
0.77
0.70
0.63
0.56
W
kW
12.3
12.5
12.6
12.3
12.5
12.6
12.7
12.9
12.5
12.6
12.7
12.9
13.0
13.2
12.7
12.9
13.0
13.2
13.4
13.5
12.9
13.0
13.2
13.4
13.5
13.7
13.0
13.2
13.4
13.5
13.7
10.0
Q
kW
62.7
64.9
67.0
62.7
64.9
67.0
69.0
71.2
64.9
67.0
69.0
71.2
73.4
75.8
69.0
71.2
73.4
75.8
78.3
80.8
71.2
73.4
75.8
78.3
80.8
83.4
73.4
75.8
78.3
80.8
83.4
SHC
kW
43.9
40.9
36.9
52.1
48.7
44.9
40.7
37.0
56.5
52.3
48.3
44.2
40.4
36.4
55.9
51.3
47.7
44.0
39.9
36.4
59.1
55.1
51.6
47.8
43.6
40.0
62.4
58.4
54.8
50.9
47.5
SHF
0.70
0.63
0.55
0.83
0.75
0.67
0.59
0.52
0.87
0.78
0.70
0.62
0.55
0.48
0.81
0.72
0.65
0.58
0.51
0.45
0.83
0.75
0.68
0.61
0.54
0.48
0.85
0.77
0.70
0.63
0.57
W
kW
12.7
12.9
13.0
12.7
12.9
13.0
13.1
13.3
12.9
13.0
13.1
13.3
13.5
13.6
13.1
13.3
13.5
13.6
13.8
14.0
13.3
13.5
13.6
13.8
14.0
14.2
13.5
13.6
13.8
14.0
14.2
15.0
Q
kW
61.6
63.7
65.7
61.6
63.7
65.7
67.7
69.8
63.7
65.7
67.7
69.8
72.0
74.3
67.7
69.8
72.0
74.3
76.7
79.2
69.8
72.0
74.3
76.7
79.2
81.7
72.0
74.3
76.7
79.2
81.7
SHC
kW
43.7
40.1
36.2
51.7
48.4
44.0
39.9
36.3
56.0
51.9
48.0
44.0
39.6
35.7
55.5
51.0
47.5
43.9
39.9
35.6
58.6
54.7
51.3
47.6
43.6
39.2
61.9
58.0
54.5
50.7
46.5
SHF
0.71
0.63
0.55
0.84
0.76
0.67
0.59
0.52
0.88
0.79
0.71
0.63
0.55
0.48
0.82
0.73
0.66
0.59
0.52
0.45
0.84
0.76
0.69
0.62
0.55
0.48
0.86
0.78
0.71
0.64
0.57
W
kW
13.2
13.4
13.5
13.2
13.4
13.5
13.6
13.8
13.4
13.5
13.6
13.8
14.0
14.2
13.6
13.8
14.0
14.2
14.5
14.7
13.8
14.0
14.2
14.5
14.7
15.0
14.0
14.2
14.5
14.7
15.0
Indoor
DB°C
20
22
24
26
28
30
Q; Cooling Capacity, SHC; Sensible Heat Capacity, W; Compressor Input
Total input = Compressor input + indoor fan motor input + outdoor fan motor input
Air Volume
CMM
l/s
Coolinr capacity
Compressor input
170
2830
0.977
0.995
180
3000
0.987
0.997
200
3330
1.000
1.000
220
3670
1.010
1.003
240
4000
1.020
1.007
Factor for Various Air Flow
Air Volume
CMM
l/s
Heating capacity
Compressor input
170
2830
0.985
1.020
180
3000
0.993
1.013
200
3330
1.000
1.000
220
3670
1.007
0.987
240
4000
1.015
0.974
Indoor
DB°C
15161718192021222324252627
Q
kW
41.2
40.9
40.6
40.4
40.2
40.0
39.8
39.6
39.4
39.2
39.1
38.9
38.6
W
kW
9.9
9.9
10.0
10.1
10.2
10.3
10.3
10.3
10.4
10.5
10.5
10.6
10.7
Q
kW
36.1
35.7
35.3
35.1
34.9
34.7
34.5
34.3
34.1
33.9
33.9
33.7
33.4
W
kW
9.1
9.1
9.2
9.3
9.4
9.4
9.4
9.4
9.5
9.6
9.6
9.7
9.8
–10–15
Q
kW
46.9
46.7
46.5
46.3
46.1
45.9
45.7
45.5
45.3
45.1
44.9
44.7
44.4
W
kW
10.9
11.0
11.1
11.2
11.3
11.4
11.5
11.6
11.7
11.8
11.8
11.9
12.0
–5
Q
kW
53.5
53.3
53.1
52.8
52.6
52.4
52.2
52.0
51.8
51.6
51.4
51.2
50.9
W
kW
12.2
12.3
12.4
12.5
12.6
12.7
12.8
12.9
13.1
13.2
13.2
13.3
13.4
0
Q
kW
60.9
60.6
60.4
60.2
60.0
59.8
59.6
59.4
59.2
59.0
58.7
58.4
58.1
W
kW
13.5
13.7
13.8
14.0
14.1
14.2
14.4
14.5
14.6
14.8
14.9
15.1
15.2
5
Q
kW
69.4
69.1
68.8
68.5
68.3
68.0
67.8
67.6
67.3
67.0
66.7
66.4
66.1
W
kW
15.2
15.4
15.6
15.7
15.9
16.0
16.2
16.3
16.5
16.7
16.8
17.0
17.2
10 15
Q
kW
78.8
78.5
78.2
77.9
77.6
77.3
77.0
76.6
76.3
76.0
75.6
75.3
75.0
W
kW
17.0
17.2
17.4
17.6
17.8
18.0
18.2
18.4
18.6
18.9
19.1
19.3
19.5
OD WB°C
Q; Heating Capacity, W; Compressor Input
-16-
fan speed Indoor fan input fan speed Indoor fan input fan speed Indoor fan input
200
CMM
L/S
rpm
kW
rpm
kW
rpm
kW
300
400
Total SP (Pa)
PRHG8
Indoor fan input
80
1330
967
1.20
1139
1.80
1305
2.42
85 1420 1036
1.27
1139
1.80
1329
2.56
90 1500 1036
1.27
1208
2.02
1329
2.56
95 1580 1036
1.27 1208
2.02
fan speed Indoor fan input fan speed Indoor fan input fan speed Indoor fan input fan speed Indoor fan input
250
CMM
L/S
rpm
kW
rpm
kW
rpm
kW
rpm
kW
350
450
550
Total SP (Pa)
PRHG10
PRHG15
90 1500 1088
1.90
1208
2.26
1450
3.13
1595
3.96
100 1660 1088
1.90
1208
2.26
1450
3.13
110 1830 1139
2.16
1318
2.86
1450
3.13
120 2000 1139
2.16 1318
2.86
fan speed Indoor fan input fan speed Indoor fan input fan speed Indoor fan input fan speed Indoor fan input fan speed Indoor fan input
300
CMM
L/S
rpm
kW
rpm
kW
rpm
kW
rpm
kW
rpm
kW
400
500
600
700
Total SP (Pa)
PRHG20
170
2830
798
2.98 906
3.50 997
3.97
1088
4.44
1208
5.03
180
3000
798
3.06 906
3.66 997
4.17
1088
4.66
1208
5.27
190
3170
798
3.14 906
3.82 997
4.37
1088
4.89
1208
5.51
200
3330
798
3.23 906
3.98 997
4.56
1088
5.11
1208
5.75
200
300
400
500
600
Total SP (Pa)
120
2000
659
1.58 791
1.95 886
2.27 997
2.72
1088
3.07
130
2170
659
1.68 791
2.08 886
2.43 997
2.93
1088
3.3
140
2330
659
1.79 791
2.21 886
2.58 997
3.13
1088
3.52
150
2500
659
1.89 791
2.34 906
2.83 997
3.34
160
2670
659
1.99 791
2.47 906
2.99 997
3.54
170
2830
659
2.1
791
2.6
906
3.15 997
3.75
180
3000
659
2.21 791
2.73 906
3.31 997
3.96
fan speed Indoor fan input fan speed Indoor fan input fan speed Indoor fan input fan speed Indoor fan input fan speed Indoor fan input
CMM
L/S
rpm
kW
rpm
kW
rpm
kW
rpm
kW
rpm
kW
-17-
Loading...
+ 43 hidden pages