• PLH-P3AAH1.UK, PLHP4AAH1.UK, PLH-P5AAH1.UK
and PLH-P6AAH1 are added in
REVISED EDITION-A.
Outdoor units PUHP3,4VGAA.UK and PUHP3,4,5,6YGAA.UK which are connected to those indoor units are
also added in it.
• Please void OC236.
• Refer to the OCT03 REVISED
EDITION-C as for control relation.
This manual does not cover
outdoor units. When serving
them, please refer to the service
manual No.OC180REVISED EDITION-A, OC261 and this manual
in a set.
● REMOTE CONTROLLER has changed.(PAR-S27A-E ➔ PAR-20MAA-E, PAR-SL95A-E ➔ PAR-SL97A-E)
● Outdoor units which are connected to PLH-P•AAH.UK and PLH-P•AAH1.UK have been added.
2
3
COMBINATION OF INDOOR AND OUTDOOR UNITS
SAFETY PRECAUTION
Cautions for devices that use R407C refrigerant.
· Do not use the existing refrigerant piping.
-The old refrigerant and lubricating oil in the existing piping contains a large amount of chlorine which may cause the lubricating
oil of the new unit to deteriorate.
· Use “low residual oil piping”.
-If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricating oil will
result.
· Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before
brazing. (Store elbows and other joints in a plastic bag.)
-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
· Use Suniso 4GS or 3GS (small amount) as the lubricating oil to coat flares and flange connection parts.
-The lubricating oil used with the air conditioner is highly hygroscopic. If it is used, water may be mixed in and deterioration
of the lubricating oil may result.
· Use liquid refrigerant to charge the system.
-If gas refrigerant is used to charge the system, the composition of the refrigerant in the cylinder will change and perfor-
mance may drop.
· Do not use a refrigerant other than R407C.
-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the lubricating oil to deteriorate.
· Use a vacuum pump with a reverse flow check valve.
-The vacuum pump oil may flow back into the refrigerant cycle and cause the lubricating oil to deteriorate.
2
Page 3
[1] Service tools
Gravimeter
Unit
Use the below service tools as exclusive tools for R407C refrigerant.
No. Tool nameSpecifications
1Gauge manifold·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 35kgf/cm2or over.
2Charge hose·Only for R407C.
·Use pressure performance of 52kgf/cm2or over.
3Electronic scale
4Gas leak detector·Use the detector for R134a or R407C.
5Adapter for reverse flow check.·Attach on vacuum pump.
6Refrigerant charge base.
7Refrigerant cylinder.·For R407C ·Top of cylinder (Brown)
·Cylinder with syphon
8Refrigerant recovery equipment.
[2] Notice on repair service
·After recovering all the refrigerant in the unit, work may be started.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the system with the specified amount of the
liquid refrigerant.
[3] Refrigerant recharging
(1) Refrigerant recharging process
Direct charging from the cylinder.
·Confirm that the cylinder is suitable for syphoning.
·Raise the cylinder and recharge the unit by syphoning liquid refrigerant.
(2) Recharge when refrigerant leakage has occurred.
·After recovering all the refrigerant in the unit, work may be started.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the system with the specified amount of
the liquid refrigerant.
This switches between continuous
operation and the timer operation.
button
Press this button to switch the cooling,
electronic dry (dehumidify), automatic
and heating modes.
TEMP. button
This sets the room temperature, The
temperature setting can be performed
in 1°C units
Setting range
Cooling 19°C to 30°C
Heating 17°C to 28°C
button
This sets the current time. start
time and stop time.
button
This sets the ventilation fan
speed.
ON/OFF button
This switches between the operation
and stop modes each time it is
pressed. The lamp on this button
lights during operation.
button
This adjusts the vertical angle of the
ventilation.
FILTER button
This resets the filter cleaning indica-
tion display.
This model name of the remote controller is indicated.
button
This switches the horizontal fan
motion ON and OFF.
(Not available for this model.)
button
This sets the ventilation fan speed.
4
CHECK-TEST RUN button
Only press this button to per-
form an inspection check or test
operation, Do not use it for normal operation.
Page 5
● Display
CENTRALLY
CONTROLLED display
This indicates when the unit is con-
trolled by optional features such as
central control type remote controller.
CHECK display
This indicates when a malfunction
has occurred in the unit which should
be checked.
OPERATION MODE display
This indicates the operation mode.
STANDBY display
The [STANDBY] symbol is only dis-
played from the time the heating
operation starts until the heated air
begins to blow.
display
The current time , start time and stop
time can be displayed in ten second
intervals by pressing the time setting
button. The start time or stop time is
always displayed during the timer
operation.
display
This displays the air
direction.
In this display example on the bottom left, a condition where all display lamps light is shown for explanation purposes although this differs
from actual operation.
display
The selected fan speed is displayed.
display
The temperature of the suction air is
displayed during operation. The display range is 10° to 35°C. The display flashes 10°C when the actual
temperature is less than 10° and
flashes 35°C when the actual temperature is greater than 35°C.
Operation lamp
This lamp lights during operation,
goes off when the unit stops and
flashes when a malfunction occurs.
DEFROST display
This indicates when the defrost oper-
ation is performed.
CHECK MODE
TEST RUN
This display lights in the check mode
or when a test operation is performed.
display
display
This indicates when the continuous
operation and time operation modes
are set.
It also display the time for the timer
operation at the same time as when
it is set.
display
This displays the selected setting
temperature.
display
This lamp lights when electricity is
supplied to the unit.
Caution
● Only the display lights when the unit is stopped and power supplied to the unit.
● When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a
malfunction.
● When the central control remote control unit, which is sold separately, is used the ON-OFF button, button and
TEMP. button do not operate.
● “NOT AVAILABLE” is displayed when the button are pressed.This indicates that this room unit is not equipped
with the fan direction adjustment function and the louver function.
● When power is turned ON for the first time , it is normal that “HO” is displayed on the room temperature indication (For max.
2minutes ).
Please wait until this “HO” indication disappear than start the operation.
FILTER
This lamp lights when the filter need
to be cleaned.
display
5
Page 6
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN
FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY
DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
Press this button to switch the cooler,
electronic dry (dehumidify), automatic
and heater modes.
OPERATION SWITCH button
This sets the room temperature. The
temperature setting can be performed
in 1: units
Setting range
Cooler 19: to 30:
Heater 17: to 28:
TEMP. ADJUSTMENT button
This switches between continuous
operation and the timer operation.
TIMER button
This switches between the operation
and stop modes each time it is pressed.
The lamp on this button lights during
operation.
ON/OFF button
Only press this button to perform an
inspection check or test operation.
Do not use it for normal operation.
CHECK-TEST RUN button
This switch the horizontal fan motion
ON and OFF.
(Not available for this model.)
LOUVER button
This adjusts the vertical angle of the
ventilation.
AIR DIRECTION button
This resets the filter service indication
display
FILTER button
This sets the current time, start time
and stop time.
trolled by optional features such as
central control type remote controller.
TIMER display
This indicates when the continuous
operation and time operation modes
are set.
It also display the time for the timer
operation at the same time as when
it is set.
OPERATION MODE display
This indicates the operation mode.
STANDBY display
The [STANDBY] symbol is only dis-
played from the time the heating
operation starts unit the heated air
begins to blow.
DEFROST display
This indicates when the defrost oper-
ation is performed.
CLOCK display
The current time , start time and stop
time can be displayed in ten second
intervals by pressing the time switch
button. The start time or stop time is
always displayed during the timer
operation.
In this display example on the bottom left, a condition where all display lamps light is shown for explanation purposes although this differs
from actual operation.
AIR DIRECTION display
This displays the air direction.
AIR SPEED display
The selected fan speed is displayed.
ROOM TEMPERATURE display
The temperature of the suction air
is displayed during operation. The
display range is 8°C to 39°C. The
display flashes 8°C when the actual
temperature is less than 8°C and
flashes 39°C when the actual temperature is greater than 39°C.
Operation lamp
This lamp lights during operation,
goes off when the unit stops and
flashes when a malfunction occurs.
This display lights in the check mode
or when a test operation is performed.
CHECK MODE
TEST RUN
display
FILTER display
CHECK display
This indicates when a malfunction
has occurred in the unit which should
be checked.
SET TEMPERATURE display
This displays the selected setting
temperature.
Caution
● Only the Power display lights when the unit is stopped and power supplied to the unit.
● When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button
and TEMP. adjustment button do not operate.
● “NOT AVAILABLE” is displayed when the Air speed button are pressed.This indicates that this room unit is not equipped
with the fan direction adjustment function and the louver function.
● When power is turned ON for the first time, it is normal that “H0” is displayed on the room temperature indication (For max.
2minutes). Please wait until this “H0” indication disappear then start the operation.
POWER display
This lamp lights when electricity is
supplied to the unit.
This lamp lights when the filter need
to be cleaned.
Lights up while transmission to the indoor unit
is mode using switches.
display
OPERATION MODE display
Operation mode display indicates which operation mode is in effect.
• FUNCTION
Lights up when function are set.
display
• TEST RUN • CHECK display
CHECK&TEST RUN display indicates that the
unit is being checked or test-run.
display
Displays when batteries are dead.
display
ADDRESS display
Displays the refrigerant address.
UNIT NO. display
Displays the number of unit..
FUNCTION NO. display
Displays the mode.
SELECTION NO. display
Displays the selection number..
display
SET TEMP. display indicates desired temperature set.
CLOCK display
DIsplays the current time.
“ ”display
Flashes when the current time is displayed.
TIMER display
Displays when in timer operation or when setting timer.
➡
“ ” “ ” display
➡
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
The vertical direction of airflow is indicated.
display
FAN SPEED display indicates which fan
speed has been selected.
display
The unit is turned ON and OFF alternately
each time the button is pressed.
● When cover is open.
MODE SELECT button
Used to switch the operation mode between
cooling , drying , blowing , heating and auto
mode.
FAN SPEED SELECT button
Used to change the fan speed.
VANE CONTROL button
Used to change the airflow direction.
▼
“ ” “ ” display
Displays when the current time and the timer
time can be changed.
▼
TEMP. button
SET TEMPERATURE button sets any desired
room temperature.
TIMER CONTROL buttons
STOP (OFF timer): when this switch is set,
the air conditioner will be automatically
stopped at the preset time.
START(ON timer): when this switch is set, the
air conditioner will be automatically started at
the preset time.
HR. and MIN.buttons
Buttons used to set the “hour and minute” of
the current time and timer settings.
The unit is turned ON and OFF alternately
each time the button is pressed.
LOUVER button
This switch the horizontal fan motion ON
and OFF.
(Not available for this model.)
MODE SELECT button
Used to switch the operation mode between
cooling, drying, blowing, heating and auto
mode.
CHECK-TEST RUN button
Only press this button to perform an inspection check or test operation.
Do not use it for normal operation.
FAN SPEED SELECT button
Used to change the fan speed.
TIMER display
Displays when in timer operation or when
setting timer.
button
SET TEMPERATURE button sets any desired
room temperature.
CLOCK display
Displays the current time.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
Buttons used to set the “hour and minute” of
the current time and timer settings.
h and min buttons
display
SET TEMP. display indicates desired temperature set.
display
FAN SPEED display indicates which fan
speed has been selected.
display
The vertical direction of air flow is indicated.
display
Blinks when model is selected.
display
Lights up while transmission to the indoor
unit is mode using switches.
display
CHECK&TEST RUN display indicates that
the unit is being checked or test-run.
display
OPERATION MODE display
Operation mode display indicates which operation mode is in effect.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be automatically stopped at the preset time.
AUTO START (ON timer): when this switch
is set, the air conditioner will be automatically started at the preset time.
MODEL SELECT
CHECK
TEST RUN
● When cover is open. [ PAR-SL97A-E ]
9
Page 10
LING
SSETTE
Service Ref.
Item
Function
Capacityw1
Btu/h
W
Total inputw1kW
Service Ref.
Power supply (phase, cycle,voltage)
Inputw2kW
Running current w2A
Starting current w2A
External finish
Heat exchanger
Fan
Fan (drive) o No.
Fan motor outputkW
Airflow (Lo-Mi2-Mi1-Hi)
K / min (CFM)
External static pressurePa (mmAq)
Booster heaterkW
Operation control & Thermostat
Sound level (Lo-Mi2-Mi1-Hi)dB
Unit drain pipe I.D.mm (in.)
Dimensions
Indoor unit
Wmm (in.)
Dmm (in.)
Hmm (in.)
Weight
kg (lbs.)
Service Ref.
Power supply (phase, cycle, voltage)
Running currentA
Starting currentA
External finish
Refrigerant control
Compressor
Model
Motor outputkW
Starter type
Protection devices
Heat exchanger
Fan (drive) o No.
FanFan motor outputkW
AirflowK
/ min (CFM)
Crankcase heaterW
Defrost method
Sound level
Dimensions
CoolingdB
HeatingdB
Wmm (in.)
Dmm (in.)
Hmm (in.)
Outdoor unitRefrigerant piping
Weightkg (lbs.)
Refrigerant
Chargekg (lbs.)
Oil (Model)L
Pipe size O.D.
PLH-P3AAH.UK
CoolingHeating
26,600 31,700 [38,900]
7,8009,300 [11,400]
3.513.65 [5.75]
PLH-P3AAH.UK
Single phase, 50Hz, 220–230–240V
0.17 0.17 <2.10>
0.81 0.81 <8.75>
1.0 1.0 <8.75>
Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct) o 1
0.070
15-16-18-20 (530-565-635-705)
0 (direct blow)
<2.1>
Remote controller & built-in
28-30-32-34
32 (1-1/4)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 258 (10-1/2) PANEL : 30 (1-3/16)
UNIT : 26 (57) PANEL : 5 (11)
PUH-P3VGA / PUH-P3YGA
Single phase, 50Hz, 220–230–240V / 3 phases, 50Hz, 380–400–415V (4wires)
14.64/5.46 15.43/5.76
93/41
Munsell 5Y 8/1
Linear expansion valve
Hermetic
NE52VNJM / NE52YDJM
2.5
Line start
Internal thermostat, HP switch, Discharge thermo. / Thermal relay, Discharge thermo., HP switch, Anti-phase protector
Correcting the capacity line influenced by frosting
Not correcting the capactiy line influenced by frosting
1.4
1.2
1.0
0.8
10
22
20
18
16
22
20
18
16
203046400-5
1.2
1.0
0.8
0.6
0.4
INDOOR
W.B.(°C)
CAPACITY (RATIO)TOTAL INPUT (RATIO)
INDOOR
W.B.(°C)
OUTDOOR D.B.(°C)
1.3 Correction factors
Cooling capacity correction factors
Service Ref.
PLH-P3AAH.UK
PLH-P3AAH1.UK
PLH-P4AAH.UIK
PLH-P4AAH1.UK
PLH-P5AAH.UK
PLH-P5AAH
PLH-P6AAH.UK
PLH-P6AAH
1.UK
1.UK
5m10m15m20m25m30m35m40m45m50m
1.000.9810.9680.9520.9400.9250.9130.9000.886
1.000.9890.980
1.000.9810.9680.9520.9400.9250.9130.9000.886
1.000.9750.9550.9350.9180.9000.8840.8690.855
Heating capacity correction factors
Service Ref.
PLH-P3AAH.UK
PLH-P3AAH
PLH-P4AAH.UK
PLH-P4AAH1.UK
PLH-P5AAH.UK
PLH-P5AAH1.UK
PLH-P6AAH.UK
PLH-P6AAH1.UK
1.UK
5m10m15m20m25m30m35m40m45m50m
1.000.9980.9950.9930.9900.9880.9850.9830.9800.978
1.000.9980.9950.9930.9900.9880.9850.9830.9800.978
1.000.9980.9950.9930.9900.9880.9850.9830.9800.978
1.000.9980.9550.9930.9900.9880.9850.9830.9800.978
Refrigerant piping length (one way)
0.970
0.9600.950
Refrigerant piping length (one way)
0.940
0.9300.920
0.874
0.910
0.874
0.840
2. PERFORMANCE CURVE
Cooling performance curve(50Hz)
Heating performance curve(50Hz)
35
Page 36
Model
Indoor unit
Outdoor unit
Mode
Capacity (W)
Total Input (kW)
Input (kW)
Current (A)
Current (A)
Starting current (A)
Heat
9,100
(10,860)
3.61
(5.37)
0.15
<1.76>
0.78
<8.00>
5.84
38
Cool
7,600
3.47
0.15
0.78
5.54
38
Heat
9,100
(10,860)
3.61
(5.37)
0.15
<1.76>
0.78
<8.00>
16.4
84
PLH-P3AAH.UK
Cool
7,600
3.47
0.15
0.78
15.55
84
Heat
10,400
(12,580)
3.75
(5.93)
0.24
<2.18>
1.25
<9.91>
5.86
41
Cool
9,500
3.57
0.24
1.25
5.55
41
Indoor unit ...... 220V 50Hz Single phaseOutdoor unit.... 220V 50Hz Single phase / 380V 50Hz 3 phases
PUH-P3VGAPUH-P3YGA
PLH-P4AAH.UK
PUH-P4YGA
w ( ) shows the total rating. < > shows the only booster heater rating.
Model
Indoor
unit
Outdoor unit
Mode
Capacity (W)
Total Input (kW)
Input (kW)
Current (A)
Indoor
unit
Heat
9,200
(11,130)
3.63
(5.56)
0.16
<1.93>
0.79
<8.39>
Cool
7,700
3.49
0.16
0.79
Outdoor
unit
Heat
9,200
(11,130)
3.63
(5.56)
0.16
<1.93>
0.79
<8.39>
PLH-P3AAH.UK
Cool
7,700
3.49
0.16
0.79
Heat
10,500
(12,890)
3.78
(6.17)
0.25
<2.39>
1.25
<10.39>
Cool
9,600
3.60
0.25
1.25
Current (A)
5.755.4615.8915.085.785.48
Starting current (A)
404089894343
Indoor unit ...... 230V 50Hz Single phaseOutdoor unit.... 230V 50Hz Single phase / 400V 50Hz 3 phases
PUH-P3VGAPUH-P3YGA
PLH-P4AAH.UK
PUH-P4YGA
w ( ) shows the total rating. < > shows the only booster heater rating.
Model
Indoor unit
Outdoor unit
Mode
Capacity (W)
Total Input (kW)
Input (kW)
Current (A)
Starting current (A)
Heat
9,300
(11,400)
3.65
(5.75)
0.17
<2.10>
0.81
<8.75>
41
Cool
7,800
3.51
0.17
0.81
41
Heat
9,300
(11,400)
3.65
(5.75)
0.17
<2.10>
0.81
<8.75>
93
PLH-P3AAH.UK
Cool
7,800
3.51
0.17
0.81
93
Heat
10,600
(13,200)
3.80
(6.40)
0.26
<2.60>
1.25
<10.83>
45
Cool
9,700
3.62
0.26
1.25
Current (A)
5.765.4615.4314.645.795.49
45
Indoor unit ...... 240V 50Hz Single phaseOutdoor unit.... 240V 50Hz Single phase / 415V 50Hz 3 phases
PUH-P3VGAPUH-P3YGA
PLH-P4AAH.UK
PUH-P4YGA
w ( ) shows the total rating. < > shows the only booster heater rating.
(In + Out)
(in + Out + Heater)
(In + Out)
(in + Out + Heater)
(In + Out)
(in + Out + Heater)
Indoor
unit
Outdoor
unit
Indoor
unit
Outdoor
unit
3. ELECTRICAL DATA
36
Page 37
Indoor unit ...... 220V 50Hz Single phaseOutdoor unit.... 380V 50Hz 3 phases
Model
Mode
Capacity (W)
Total Input (kW)
Indoor
Outdoor
w ( ) shows the total rating. < > shows the only booster heater rating.
Indoor unit ...... 230V 50Hz Single phaseOutdoor unit.... 400V 50Hz 3 phases
ModelIndoor unit
Mode
Capacity (W)
Total Input (kW)
Indoor
Indoor unit
Outdoor unit
(In + Out)
(in + Out + Heater)
Input (kW)
unit
Current (A)
Starting current (A)
Current (A)
unit
Outdoor unit
(In + Out)
(in + Out + Heater)
Input (kW)
unit
Current (A)
Starting current (A)
PLH-P5AAH.UK
PUH-P5YGA
Cool
12,600
5.51
0.28
1.43
72
8.92
PLH-P5AAH.UK
PUH-P5YGA
Cool
12,700
5.53
0.29
1.43
76
15,800
(18,320)
(8.41)
<2.52>
<11.45>
15,900
(18,660)
(8.67)
<2.76>
<12.00>
Heat
5.89
0.28
1.43
72
9.29
Heat
5.91
0.29
1.43
76
PLH-P6AAH.UK
PUH-P6YGA
Cool
14,100
6.60
0.32
1.64
77
10.72
PLH-P6AAH.UK
PUH-P6YGA
Cool
14,200
6.65
0.33
1.64
81
Heat
16,400
(18,920)
(9.25)
0.32
<2.52>
1.64
<11.45>
10.94
Heat
16,600
(19,360)
6.75
(9.51)
<2.76>
1.64
<12.00>
6.73
77
0.33
81
Current (A)
Outdoor
unit
w ( ) shows the total rating. < > shows the only booster heater rating.
Indoor unit ...... 240V 50Hz Single phaseOutdoor unit.... 415V 50Hz 3 phases
ModelIndoor unit
Outdoor unit
Mode
Capacity (W)
Total Input (kW)
Input (kW)
Indoor
unit
Current (A)
Starting current (A)
Current (A)
Outdoor
unit
w ( ) shows the total rating. < > shows the only booster heater rating.
(In + Out)
(in + Out + Heater)
8.59
PLH-P5AAH.UK
PUH-P5YGA
Cool
12,800
5.55
0.30
1.43
79
8.39
8.95
Heat
16,000
(19,000)
5.93
(8.93)
0.30
<3.00>
1.43
<12.50>
79
8.74
10.36
PLH-P6AAH.UK
PUH-P6YGA
Cool
14,300
6.70
0.34
1.64
84
10.17
10.53
16,800
(19,800)
(9.77)
<3.00>
1.64
<12.50>
10.28
Heat
6.77
0.34
84
37
Page 38
Service
Ref.
Indoor unit
Outdoor unit
Mode
Capacity (W)
Total Input (kW)
Input (kW)
Current (A)
Current (A)
Starting current (A)
Heat
9,100
(10,860)
3.47
(5.23)
0.15
<1.76>
0.78
<8.00>
6.15
43
Cool
7,600
3.40
0.15
0.78
5.78
43
Heat
9,100
(10,860)
3.47
(5.23)
0.15
<1.76>
0.78
<8.00>
17.19
85
PLH-P3AAH.UK
PLH-P3AAH
1.UK
Cool
7,600
3.40
0.15
0.78
16.16
85
Heat
10,400
(12,160)
3.88
(5.64)
0.24
<2.18>
1.25
<9.91>
18.08
91
Cool
9,500
3.66
0.24
1.25
17.13
91
Indoor unit ...... 220V 50Hz Single phaseOutdoor unit .... 220V 50Hz Single phase / 380V 50Hz 3 phases
PUH-P•GAA.UK
PLH-P4AAH.UK
PLH-P4AAH
1.UK
w ( ) shows the total rating. < > shows the only booster heater rating.
Indoor unit ...... 230V 50Hz Single phaseOutdoor unit .... 230V 50Hz Single phase / 400V 50Hz 3 phases
w
( ) shows the total rating. < > shows the only booster heater rating.
Indoor unit ...... 240V 50Hz Single phaseOutdoor unit .... 240V 50Hz Single phase / 415V 50Hz 3 phases
w
( ) shows the total rating. < > shows the only booster heater rating.
(In + Out)
(in + Out + Heater)
Indoor
unit
Outdoor
unit
Heat
Cool
4Y4V3Y
3V
10,400
(12,160)
3.88
(5.64)
0.24
<2.18>
1.25
<9.91>
6.40
44
9,500
3.66
0.24
1.25
6.06
44
9,200
(11,130)
3.48
(5.41)
0.16
<1.93>
0.79
<8.39>
7,700
3.42
0.16
0.79
9,200
(11,130)
3.48
(5.41)
0.16
<1.93>
0.79
<8.39>
7,700
3.42
0.16
0.79
10,500
(12,430)
3.91
(5.84)
0.25
<2.39>
1.25
<10.39>
9,600
3.68
0.25
1.25
5.845.4916.4515.4517.3016.39
454589899595
10,500
(12,430)
3.91
(5.84)
0.25
<2.39>
1.25
<10.39>
6.08
47
9,600
3.68
0.25
1.25
5.76
47
9,300
(11,400)
3.50
(5.60)
0.17
<2.10>
0.81
<8.75>
47
7,800
3.44
0.17
0.81
47
9,300
(11,400)
3.50
(5.60)
0.17
<2.10>
0.81
<8.75>
93
7,800
3.44
0.17
0.81
93
10,600
(12,700)
3.93
(6.03)
0.26
<2.60>
1.25
<10.83>
99
9,700
3.69
0.26
1.25
5.635.2915.7614.8116.5815.71
99
10,600
(12,700)
3.93
(6.03)
0.26
<2.60>
1.25
<10.83>
5.86
49
9,700
3.69
0.26
1.25
5.55
49
Service
Ref.
Indoor unit
Outdoor unit
Mode
Capacity (W)
Total Input (kW)
Input (kW)
Current (A)
Current (A)
Starting current (A)
HeatCoolHeat
PLH-P3AAH.UK
PLH-P3AAH
1.UK
CoolHeat
Cool
PUH-P•GAA.UK
PLH-P4AAH.UK
PLH-P4AAH
1.UK
(In + Out)
(in + Out + Heater)
Indoor
unit
Outdoor
unit
Heat
Cool
4Y4V3Y
3V
Service
Ref.
Indoor unit
Outdoor unit
Mode
Capacity (W)
Total Input (kW)
Input (kW)
Current (A)
Current (A)
Starting current (A)
HeatCoolHeat
PLH-P3AAH.UK
PLH-P3AAH
1.UK
CoolHeat
Cool
PUH-P•GAA.UK
PLH-P4AAH.UK
PLH-P4AAH
1.UK
(In + Out)
(in + Out + Heater)
Indoor
unit
Outdoor
unit
Heat
Cool
4Y4V3Y
3V
38
Page 39
Indoor unit ...... 220V 50Hz Single phaseOutdoor unit.... 380V 50Hz 3 phases
Service
Ref.
Indoor unit
Outdoor unit
Mode
Capacity (W)
Total Input (kW)
Input (kW)
Indoor
unit
Current (A)
Starting current (A)
(In + Out)
(in + Out + Heater)
PLH-P5AAH.UK
PLH-P5AAH
PUH-P•GAA.UK
5Y
Cool
12,600
4.96
0.28
1.43
65.5
Heat
14,700
(17,210)
5.30
(7.82)
0.28
<2.52>
1.43
<11.45>
65.5
1.UK
PLH-P6AAH.UK
PLH-P6AAH
1.UK
6Y
Cool
14,100
5.85
0.32
1.64
Heat
16,900
(19,420)
6.33
(8.85)
0.32
<2.52>
1.64
<11.45>
74
74
Current (A)
Outdoor
unit
w ( ) shows the total rating. < > shows the only booster heater rating.
8.30
8.90
9.86
10.44
Indoor unit ...... 230V 50Hz Single phaseOutdoor unit.... 400V 50Hz 3 phases
Service
Ref.
Indoor unit
Outdoor unit
Mode
Capacity (W)
Total Input (kW)
(In + Out)
(in + Out + Heater)
Input (kW)
Indoor
unit
Current (A)
Starting current (A)
Current (A)
Outdoor
unit
w ( ) shows the total rating. < > shows the only booster heater rating.
PLH-P5AAH.UK
PLH-P5AAH
5Y
Cool
12,700
4.98
0.29
1.43
14,800
(17,560)
(8.08)
<2.76>
<12.00>
65.5
7.89
1.UK
PUH-P•GAA.UK
Heat
5.32
0.29
1.43
65.5
8.46
PLH-P6AAH.UK
PLH-P6AAH
6Y
Cool
14,200
5.90
0.33
1.64
Heat
17,000
(19,760)
(9.11)
0.33
<2.76>
1.64
<12.00>
74
9.37
1.UK
6.35
74
9.92
Indoor unit ...... 240V 50Hz Single phaseOutdoor unit.... 415V 50Hz 3 phases
Service
Ref.
Indoor unit
Outdoor unit
Mode
Capacity (W)
Total Input (kW)
Input (kW)
Indoor
unit
Current (A)
Starting current (A)
(In + Out)
(in + Out + Heater)
PLH-P5AAH.UK
PLH-P5AAH
5Y
Cool
12,800
5.00
0.30
1.43
14,900
(17,900)
(8.34)
<3.00>
<12.50>
65.5
1.UK
PUH-P•GAA.UK
Heat
5.34
0.30
1.43
65.5
PLH-P6AAH.UK
PLH-P6AAH
6Y
Cool
14,300
5.94
0.34
1.64
Heat
17,100
(20,100)
(9.36)
0.34
<3.00>
1.64
<12.50>
74
1.UK
6.36
74
Current (A)
Outdoor
unit
w ( ) shows the total rating. < > shows the only booster heater rating.
7.60
8.15
39
9.03
9.56
Page 40
Total
Electrical circuit
Refrigerant circuitIndoor side
Outdoor
side
Service Ref.
SHF
BF
W
kW
Mode
Capacity
Input
PLH-P3AAH.UKPLH-P4AAH.UKPLH-P5AAH.UKPLH-P6AAH.UK
PLH-P3AAH.UKPLH-P4AAH.UKPLH-P5AAH.UKPLH-P6AAH.UK
Cooling
7,800
3.51
Heating
9,300
3.65
Cooling
9,700
3.62
Heating
10,600
3.80
Cooling
12,800
5.55
(kgf/F)
(kgf/F)
Heating
16,000
5.93
Cooling
14,300
6.70
Heating
16,800
6.77
(23.2)
(4.7)
(26.4)
(4.21)
(23.2)
(4.6)
(24.1)
(4.2)
(20.2)
(5.5)
(21.6)
(4.3)
(23.4)
(4.8)
(24.3)
(4.0)
14.64/5.46
2.30
0.47
81.0
44.0
4.8
5
27
19
13.4
35
24
0.74
0.13
15.43/5.76
2.38
0.39
88.0
45.0
0
5
20
15
45.1
7
6
—
—
5.49
1.98
0.54
71.0
42.0
7.5
5
27
19
14.0
35
24
0.78
0.12
5.79
2.12
0.42
7.5
47.0
0.6
5
20
15
40.1
7
6
—
—
8.39
2.27
0.46
78.6
41.0
4.4
5
27
19
12.3
35
24
0.72
0.10
8.74
2.59
0.41
86.6
44.0
4.2
5
20
15
49.3
7
6
—
—
10.17
2.27
0.45
80.6
45.0
2.4
5
27
19
11.3
35
24
0.69
0.09
10.28
2.36
0.41
83.5
46.0
-1.0
5
20
15
50.7
7
6
—
—
1,50
240
0.81
1/3, 50
240/415
1,50
240
1.25
PUH-P4YGA
3, 50
415
1,50
240
1.43
PUH-P5YGA
3, 50
415
1,50
240
1.64
PUH-P6YGA
3, 50
415
Phase,Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase,Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
V
A
V
A
Mpa
Mpa
°C
°C
°C
m
°C
°C
°C
°C
°C
Indoor unit Service Ref.
D.B.
W.B.
D.B.
D.B.
W.B.
PUH-P3VGA
PUH-P3YGA
4. STANDARD OPERATION DATA
The unit of pressure has been changed to Mpa based on international SI system.
The conversion factor is : 1(Mpa)=10.2(kgf/ff)
40
Page 41
Service Ref.
PLH-P3AAH.UK
PLH-P3AAH
1.UK
28
4.9
7.4
30
6.6
8.9
30
5.2
7.9
Air flow
Air speed
Coverage range
m
3
/min
m/sec.
m
20
4.0
5.7
Service Ref.
PLH-P6AAH.UK
PLH-P6AAH
1.UK
PLH-P5AAH.UK
PLH-P5AAH
1.UK
PLH-P4AAH.UK
PLH-P4AAH1.UK
Mode
Capacity
Total
Input
Indoor unit Service Ref.
Phase,Hz
PLH-P3AAH.UK
PLH-P3AAH
Cooling
W
7,800
kW
PLH-P3AAH.UK
PLH-P3AAH
3.44
1,50
1.UK
Heating
9,300
3.50
1.UK
PLH-P4AAH.UK
PLH-P4AAH
Cooling
9,700
3.69
1.UK
Heating
10,600
3.93
PLH-P4AAH.UK
PLH-P4AAH
1.UK
1,50
PLH-P5AAH.UK
PLH-P5AAH
Cooling
12,800
5.00
1.UK
Heating
14,900
5.34
PLH-P5AAH.UK
PLH-P5AAH
1.UK
1,50
PLH-P6AAH.UK
PLH-P6AAH
Cooling
14,300
5.94
1.UK
Heating
17,100
6.36
PLH-P6AAH.UK
PLH-P6AAH
1.UK
1,50
Volts
Amperes
Outdoor unit Service Ref.
Electrical circuit
Phase,Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Refrigerant circuitIndoor side
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
side
Outdoor
SHF
BF
D.B.
W.B.
D.B.
D.B.
W.B.
V
A
V
A
Mpa
(kgf/F)
Mpa
(kgf/F)
°C
°C
°C
m
°C
°C
°C
°C
°C
240
0.81
PUH-P3VGAA.UK
PUH-P3YGAA.UK
1/3, 50
240/415
14.81/5.29
2.30
(23.4)
0.47
(4.8)
81.0
44.0
13.4
0.74
0.13
4.8
5
27
19
35
24
15.76/5.63
2.38
(24.3)
0.39
(4.0)
88.0
45.0
0
5
20
15
45.1
7
6
—
—
240
1.25
PUH-P4VGAA.UK
PUH-P4YGAA.UK
1/3, 50
240/415
15.71/5.55
1.98
(20.2)
0.54
71.0
42.0
14.0
0.78
0.12
(5.5)
7.5
5
27
19
35
24
16.58/5.86
2.12
(21.6)
0.42
(4.3)
7.5
47.0
0.6
5
20
15
40.1
7
6
—
—
240
1.43
PUH-P5YGAA.UK
3, 50
415
7.60
2.27
(23.2)
0.46
(4.7)
78.6
41.0
4.4
8.15
2.59
(26.4)
0.41
(4.21)
86.6
44.0
4.2
5
27
19
12.3
20
15
47.3
35
24
0.72
0.10
—
—
PUH-P6YGAA.UK
9.03
2.27
(23.2)
0.45
(4.6)
80.6
45.0
2.4
5
27
19
11.3
7
6
35
24
0.69
0.09
240
1.64
3, 50
415
9.56
2.36
(24.1)
0.41
(4.2)
83.5
46.0
-1.0
5
5
20
15
51.2
7
6
—
—
The unit of pressure has been changed to Mpa based on international SI system.
The conversion factor is : 1(Mpa)=10.2(kgf/ff)
5. OUTLET AIR SPEED AND COVERAGE RANGE
w The air coverage range is the value up to the position where the air speed is 0.25m/sec.
When air is blown out horizontally from the unit at the Hi notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the
furniture inside the room.
41
Page 42
Ambient temperature 27:
Test conditions are based on JIS Z8731
UNIT
1.5m
MICROPHONE
CEILING
PLH-P3AAH.UK
PLH-P3AAH
1
.UK
PLH-P4AAH.UK
PLH-P4AAH1.UK
PLH-P5AAH.UK
PLH-P5AAH
1
.UK
PLH-P6AAH.UK
PLH-P6AAH1.UK
NOTCH SPL(dB) LINE
Hi34
Mi132
Mi230
Lo28
NOTCH SPL(dB) LINE
Hi41
Mi139
Mi236
Lo33
NOTCH SPL(dB) LINE
Hi43
Mi141
Mi238
Lo35
NOTCH SPL(dB) LINE
Hi45
Mi143
Mi240
Lo37
90
80
70
60
50
40
30
20
10
631252505001000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
90
80
70
60
50
40
30
20
10
631252505001000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
6. NOISE CRITERION CURVES
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
631252505001000 2000 4000 8000
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
631252505001000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
42
Page 43
7
Unit: mm
Air outlet hole
Vane motor
Auto vane
Drain hole
Grille
Drain pipe
VP-25connection
(O.D.{32)
Branch duct hole
(Cut out hole)
Ceiling surface
Suspension bolt pitch
Ceiling hole
Branch
duct hole
Suspension bolt pitch
Ceiling hole
Air outlet hole
Air intake hole
411
Air intake hole
Air intake grille
Receiver
Operation lamp
DEFROST/STAND BY lamp
Emergency operation switch (cooling)
High efficiency filter
& Fresh air intake casement (option)
NAME
INDOOR POWER BOARD
FUSE(4A)
VARISTOR
INDOOR CONTROLLER BOARD
CONNECTOR(LOSSNAY)
CONNECTOR(REMOTE SWITCH)
CONNECTOR(HA TERMINAL-A)
JUMPER WIRE(MODEL SELECTION)
JUMPER WIRE(CAPACITY CORD)
SWITCH(EMERGENCY OPERATION)
RELAY(DRAIN PUMP)
RELAY(FAN MOTOR)
FAN PHASE CONTROL
POWER SUPPLY(I.B)
POWER SUPPLY(R.B)
TRANSMISSION(INDOOR-OUTDOOR)
CAPACITOR(FAN MOTOR)
FAN MOTOR
Disconnect the connector then measure the resistance using a tester.
(Surrounding temperature 10:~30:)
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:)
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:)
Measure the resistance between the terminals using a tester.
Measure the resistance after 3 minutes have passed since the power supply was intercepted.
(Surrounding temperature 0:~60:)
Vane motor
Drain pump
Drain sensor
(Refer to the thermistor)
(Refer to the thermistor)
Room temperature
thermistor (TH1)
Pipe temperature
thermistor (TH2)
Condenser/Evaporator
temperature thermistor
(TH5)
1
2
Red
Red
1
2
3
Normal
4.3k"~9.6k"
Abnormal
Open or short
Abnormal
Open or short
Normal
0.6k"~6.0k"
NormalAbnormal
15k"Open or short
NormalAbnormal
290"Open or short
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:)
(1) Slide the knob of air intake grille toward the arrow 1 to
open the air intake grille.
(2) Remove drop prevention hook from the panel.
(3) Slide the shaft in the hinge to the direction of the arrow2
and remove the air intake grille.
2. Removing the fan guard
(1) Open the air intake grille.
(2) Remove the 3 screws of fan guard.
3. Removing the room temperature thermistor
(1)Remove the fan guard.(See photo 1)
(2) Remove the screw in the room temperature thermistor
holder to remove the holder and the room temperature
thermistor.
(3) Remove the 1 screw from the bell mouth, and unscrew the
other 2 screws (fix to the oval hole which has a different
diameter) to remove the bell mouth.
(4) Hold the holder claw, and remove the room temperature
thermistor and holder.
(5) Disconnect the connector (red) from the indoor control
board.
Figure 1
Air intake grille
Grille
Air intake grille knob
Photo 1
Screws
Fan guard
Air intake grille
Photo 2
Screws
Bell mouth
Room
temperature
thermistor
Air intake grille
4. Removing the electrical box
(1) Remove the fan guard.(See photo 1)
(2) Disconnect the lead wire of the vane motor from the clamp,
and disconnect the white connector (8P).
(3) Remove the room temperature thermistor with the holder.
(4) Remove the bell mouth.(See photo 2)
(5) Disconnect the relay connector in the electrical box.
Red (3P) for ran motor power supply
White (2P) for pipe temperature detecting thermistor
Blue (2P) for drain pump
White (3P) for drain sensor
Green (6P) for auxiliary heater
(6) Remove the 3 screws of the electrical box and loosen the
other 2 screws to remove the box.
<Electrical parts in the electrical box>
Indoor controller board
Power supply board
Terminal block
Capacitor
Heater contactor
49
Photo 3
Turbo fan
Electrical
box
Power
supply
board
Connector
Nut
Indoor controller board
Capacitor
Heater
contactor
Terminal
block
Connector
Page 50
OPERATING PROCEDURE
PHOTOS & ILLUSTRATIONS
5. Remove the fan motor
(1) Remove the fan guard.(See photo 1)
(2) Remove the bell mouth.(See photo 2)
(3) Remove the electrical box.(See photo 3)
(4) Remove the turbo fan nut.
(5) Pull out the turbo fan.
(6) Disconnect the connector of the fan motor lead wire.
(7) Remove the 4 nuts of the fan motor.
6. Removing the pipe temperature thermistor
and condenser evaporator temperature thermistor
(1) Remove the fan guard.(See photo 1)
(2) Remove the bell mouth.(See photo 2)
(3) Remove the electrical box.(See photo 3)
(4) Remove the turbo fan.
(5) Remove the screw of the service panel.
(6) Remove the service panel.
(7) Remove the pipe temperature thermistor which is inserted
into the holder installed to the thin copper pipe.
(8) Disconnect the 2-pin white connector.
Photo 4
Photo 5
Fan motor
Nuts
Pipe temperature thermistor
Connector
Nut
7. Removing the panel
(1) Remove the air intake grille.(See figure 1)
Corner panel (See figure 2)
(1) Remove the corner screw.
(2) Slide the corner panel to the direction of the arrow3, and
remove the corner panel.
Panel (See photo 6)
(1) Disconnect the connector that connects with the unit.
(2) Remove the 2 screws from the panel and loosen another 2
screws, which fix to the oval holes, have different diameters.
(3) Rotate the panel a little to remove the panel.
8. Removing the drain pan
(1) Remove the panel. (See photo 6)
(2) Remove the drain plug (Larger one), drain the remaining
water in the drain pan.
(3) Remove the corner cover. (2 screws)
(4) Remove the bell mouth (See photo 2)
(5) Remove the electrical box. (See photo 3)
(6) Remove the lead wire holder. (1 screw)
(7) Remove the 4 screws and pull out the drain pan.
w Pull out the left and right of the pan gradually.
Be careful not to crack or damage the pan.
Figure 2
Corner
panel
Photo 6
Connector
Screws
Photo 7
Screw
Drain pan
Screw
Service access
Screw
Corner
panel
Panel
Screws
Panel
Screw
Screw
50
Lead
wire
holder
Drain plug(Larger)
Corner cover
Page 51
OPERATING PROCEDUREPHOTOS & ILLUSTRATIONS
9. Removing the drain pump and drain sensor
(1) Remove the panel. (See photo 6)
(2) Remove the fan guard. (See photo 1)
(3) Remove the bell mouth. (See photo 2)
(4) Remove the electrical box. (See photo 3)
(5) Remove the drain pan. (See photo 7)
(6) Remove the 3 screws of the drain pump.
(7) Cut the drain hose band, pull out the drain hose from the
drain pump.
(8) Pull out the drain pump.
(9) Remove the drain sensor and the holder.
10. Removing the heat exchanger
(1) Remove the panel. (See photo 6)
(2) Remove the fan guard. (See photo 1)
(3) Remove the bell mouth. (See photo 2)
(4) Remove the electrical box. (See photo 3)
(5) Remove the drain pan. (See photo 7)
(6) Remove the turbo fan. (See photo 4)
(7) Remove the 3 screws of the piping cover, and pull out
piping cover.
(8) Remove the 4 screws of the outer wall cover, and pull out
the outer wall cover.
(9) Remove the screw of the coil support.
(10) Remove the 2 screws of the coil.
(11) Pull out the heat exchanger.
Photo 8
Screw
Drain hose
Photo 9
Heat exchanger
Coil
support
Fixing band
Coil support
Drain sensor
Screw
Drain pump
Coil screws
Coil
support
11. Removing the heater
(1) Remove the panel. (See photo 6)
(2) Remove the electrical box. (See photo 3)
(3) Remove the bell mouth.(See photo 2)
(4) Remove the drain pan.(See photo 7)
(5) Remove the turbo fan.(See photo 4)
(6) Remove the 5 screws of the heater assembly.
(7) Remove the clamp(1 screw) securing the lead wire.
(8) Pull the heater assembly out..
FUNCTIONAL PARTS
PLH-P3AAH.UK,PLH-P4AAH.UK,
PLH-P3AAH1.UK, PLH-P4AAH1.UK
1
2
3
19
1817
16
2
No.
Parts No.
S70 003 687
1
S70 E01 130
2
S70 005 688
3
S70 007 688
S70 E00 130
4
S70 E00 114
5
S70 E01 114
S70 08K 097
6
S70 E07 300
7
S70 E06 300
S70 E20 480
8
S70 E21 480
S70 17J 202
9
S70 E20 202
10
S70 20J 303
11
S70 46K 700
12
S70 E02 706
13
S70 E03 706
14
S70 E01 659
15
S70 E03 659
S70 E02 130
16
S70 E06 762
17
S70 E07 762
S70 A41 105
18
S70 006 688
19
S70 008 688
4
5
SPL WASHER
6
7
8
Parts Name
BASE
LEG
DRUM 1 ASSY
DRUM 1 ASSY
LEG
TURBO FAN
TURBO FAN
SPL WASHER
HEATER ELEMENT
HEATER ELEMENT
HEAT EXCHANGER
HEAT EXCHANGER
PIPE TEMPERATURE THERMISTOR
CONDENSER EVAPORATOR TEMPERATURE THERMISTOR
INSULATOR
HEATER THERMAL SWITCH
THERMAL FUSE
THERMAL FUSE
INNER COVER
INNER COVER
LEG
FAN MOTOR
FAN MOTOR
MOTOR MOUNT
DRUM 2 ASSY
DRUM 2 ASSY
Specification
240V/700W
240V/867W
50°C OFF
104°C, 16A
72°C, 16A
D17B6P70MS
D176P120MS
PLH -P3
AAH.UK
1
2
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
4
1
AAH1.UK
Q'ty / set
AAH.UK
1
2
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
4
1
PLH -P4
AAH1.UK
1
2
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
4
1
Remarks
(Drawing No.)
1
2
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
4
1
15
THERMAL FUSE
14
ASSY
13
THERMAL FUSE
12
HEATER THERMAL
SWITCH
11
10
CONDENSER
EVAPORATOR
TEMPERATURE
THERMISTOR
9
PIPE TEMPERATURE
THERMISTOR
Wiring
Recom-
Diagram
mended
Symbol
TH2
TH5
26H
FS2
FS1
H1
H1
MF
MF
Q'ty
Unit
Price
Amount
53
Page 54
No.
Parts No.
Parts Name
Wiring
Diagram
Symbol
Recommended
Q'ty
Unit
Price
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
BASE
LEG
DRUM 1 ASSY
LEG
TURBO FAN
SPL WASHER
HEATER ELEMENT
HEAT EXCHANGER
HEAT EXCHANGER
PIPE TEMPERATURE THERMISTOR
CONDENSER EVAPORATOR TEMPERATURE THERMISTOR
INSULATOR
HEATER THERMAL SWITCH
THERMAL FUSE
THERMAL FUSE
INNER COVER
LEG
FAN MOTOR
MOTOR MOUNT
DRUM 2 ASSY
FUNCTIONAL PARTS
PLH-P5AAH.UK,PLH-P6AAH.UK
PLH-P5AAH1.UK, PLH-P6AAH1.UK
1
2
DRAIN PLUG
18
3
4
5
6
7
8
Part number that is circled is not shown in the figure.
DRAIN PLUG
17
16
CAPACITOR
15
RELAY
14
TERMINAL BLOCK
13
TERMINAL BLOCK
12
TERMINAL BLOCK
11
ROOM
10
TEMPERATURE
THERMISTOR
9
56
Page 57
13
28˚C
26
˚C
8:00
Normal
operation
23:00
Setback
operation
8:00
Normal
operation
OPTIONAL PARTS
1. TIMER
Part No.
Model Name
1-1 Program timer specifications
Part name
Parts No.
Exterior dimensions (inch)
Installation
Type of clock
Clock accuracy
Display-Time
-Week
-Timer setting unit
Program cycle
Timer setting unit
No. of set points
Power rating
PAC-SC32PTA(with set back function)
Program timer
Program timer
PAC-SC32PTA
5-4/32
✕4-23/32✕23/32 (130✕120✕18mm)
Wall mount
Quartz
+
_
50 second / month at 25:
Liquid crystal display
Liquid crystal display
Liquid crystal display
24 hours
30 minutes
48 / day
+
5V DC 5% (Supplied by Remote Controller)
_
1-2 Feature of program timer
(1) Daily timer function
Daily timer can be set in 30 minutes units for up to 24 hours.
Each unit can be set for unit ON, unit OFF, or setback operation.
(2) Setback operation
Set back operation is useful for reducing running costs
e.g. At a hotel with a 24-hour system
8:00~23:00 Cooling operation with set temperature at 26°C
23:00~8:00 Setback operation with 2 degrees of setback
As shown in the chart on the right, the set temperature rises 2 degrees
automatically during the setback operation. When the setback operation
ends, normal operation will begin.
(3) Weekly timer function
Daily timer function can apply to each day of the week.
57
Page 58
SET/MONITOR
SET
SMTWTF S
MONITOR
PROERAN TIMER
PAC-SC32PTA
TODAY
ON
WEEKLY
SETTING
OFF
ON
SET BACK
OFF
CLOCKDAILY TIMER
SET BACK
SET BACK
DAILY
SETTING
12 15 18 21 24
0361215
FILTER
CHECK MODE
TEST RUN
Connect to indoor unit
with 2-wire cable.
Use 5-wire cable
Connect to CN1Connect to CN1
4
1-3. How to connect program timer
SET/MONITOR
SET
SMTWT F S
MONITOR
PROERAN TIMER
PAC-SC32PTA
TODAY
ON
WEEKLY
SETTING
OFF
ON
SET BACK
OFF
CLOCKDAILY TIMER
SET BACK
SET BACK
DAILY
SETTING
12 15 18 21 24
0361215
(1) Install the program timer next to the remote controller the same way as the remote controller is installed.
(2) Connect the program timer and the remote controller with a 5-wire cable as shown in the figure below.
NOTE:While the program timer is connected to the remote controller, the
24hour ON/OFF timer on the remote controller will not operate.
1-4. Names and functions
<PAC-SC32PTA>
WEEKLY TIMER SETTING DISPLAY
CURRENT TIME DISPLAY
SET BACK DISPLAY
DAILY TIMER SETTING DISPLAY
Used for selection of if or not the day operation pattern set by PATTERN SETTING is to
be applied in weekly day unit,
setting.
SET/MONITOR DISPLAY
During SET is display, clock adjustment,
change of weekly day, daily and weekly timer
setting can be performed.
During MONITOR is display, all switches
except SET/MONITOR SW are invalidated.
This is normal status.
WEEK DAY SETTING SW
Used for week day setting.
MODE SELECTOR SW
Using this switch select “MONITOR” or “SET”
Mode.
“MONITOR” :Indicates the current timer set-
“SET”: Set to “SET” mode for clock adjust-
ting. All switch expect MODE
SELECTOR SW are invalidated
then.This is the normal status.
ment, charge of week day, daily and
weekly timer setting.
During MONITOR status,current
time is display.
During Daily timer setting, a
Indicates the setting set
back range.
time desire for timer setting is
displayed.
CLOCK ADJUSTMENT SW
Used for adjustment of the current time.
Push SW to advance the time. Each time the button is
pushed the time advance by 1 minute, pushing continuously
advances by 1 minute at 0.5 second interval, and when the
lower digit of minute becomes 0 indication advances in 10 minutes unit.
SW is used for reversing the time. Each time the button is
pushed the time reverses by 1 minute, pushing continuously
reverses the time by 1 minute at 0.5 second interval, and when
the lower digit of minute becomes 0 indication reverses in 10
minutes unit.
24 hours is divided into 48 blocks and each
block express 30 minutes.
The block display consists of 3 pattern.
Set back can be done in the range of 1,2,4,6
and 8°C.
SET BACK SETTING SW
Used for set back setting.
ON/SET BACK/OFF SW
Used to specify the time setting pattern.
DAILY TIMER SW
Used for timer setting in 30 minutes unit.
WEEKLY TIMER SW
Used for setting timer in day of week unit.
Pushing SW moves the week day light
display in order of
S → M → T → W
enabling to set the week day.
…
58
Page 59
2. Multi-Functional Casement
Part No.
Applied Service Ref.
PLH-P3/4/5/6AAH.UK, PLH-P3/4/5/6AAH
PAC-SG03TM-E
1.UK
3. High-Efficiency Filter Element (2. Multi-Functional Casement is needed.)
Part No.
Applied Service Ref.
PLH-P3/4/5/6/AAH.UK, PLH-P3/4/5/6AAH
PAC-SG01KF
1.UK
4. Grille + Wireless Remote Controller
Part No.
Applied Service Ref.
PLP-6AALA
PLH-P3/4/5/6/AAH.UK
PLP-6AALM
PLH-P3/4/5/6AAH1.UK
5. Grille + Wired Remote Controller
Part No.
Applied Service Ref.
PLP-6AAA
PLH-P3/4/5/6/AAH.UK
PLP-6AAM
PLH-P3/4/5/6AAH1.UK
6. Remote Sensor
Part No.
Applied Service Ref.
PLH-P3/4/5/6/AAH.UK, PLH-P3/4/5/6AAH
7. Remote Operation Adapter
Part No.
Applied Service Ref.
PLH-P3/4/5/6/AAH.UK, PLH-P3/4/5/6AAH
8. Remote ON/OFF Adapter
Part No.
Applied Service Ref.
PLH-P3/4/5/6/AAH.UK, PLH-P3/4/5/6AAH
9. Air Outlet Shutter Plate (20set , 2pcs/set)
Part No.
Applied Service Ref.
PLH-P3/4/5/6/AAH.UK, PLH-P3/4/5/6AAH
PAC-SE41TS-E
1.UK
PAC-SF40RM-E
1.UK
PAC-SE55RA-E
1.UK
PAC-SG06SP-E
1.UK
59
Page 60
HEAD OFFICE : MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI CHIYODA-KU, TOKYO100-8310, JAPAN
cCopyright 2001 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Sep. 2001 NO. OC236 REVISED EDITION-A 250
Distributed in Apr. 2001 NO. OC236 225
Made in Japan
New publication, effective Sep. 2001
Specifications subject to change without notice