Mitsubishi PLH-1.6KKHB.UK, PLH-2.5KKHB.UK, PLH-2KKHB.UK Service Manual

Page 1
TECHNICAL & SERVICE MANUAL
SPLIT-TYPE, HEAT PUMP, AIR CONDITIONERS
Indoor unit [Model names]
PLH-1.6KKHB PLH-2KKHB PLH-2.5KKHB
[Service Ref.]
·
UK
PLH-2KKHB
·
UK
·
UK
No. OC147
1997
Ceiling CassettesSeries PLH
This manual does not cover the following outdoor units. When servicing them, please refer to the service manual No.OC150 and this manual in a set.
[Service Ref.] PUH-1.6VKA3·UK PUH-2VKA
2
·UK
PUH-2.5VKA
2
·UK
1. FEATURES..........................................2
2. PART NAMES AND FUNCTIONS ......3
3. SPECIFICATIONS...............................6
4. DATA ...................................................9
5. OUTLINES AND DIMENSIONS ........13
6. WIRING DIAGRAM ...........................15
7.
REFRIGERANT SYSTEM DIAGRAM .....
16
8. OPERATION FLOW-CHART ............17
9. MICROPROCESSOR CONTROL .....21
10. TROUBLESHOOTING ......................43
11. 4-WAY AIR FLOW SYSTEM .............51
12. SYSTEM CONTROL .........................52
13. DISASSEMBLY PROCEDURE.........57
14. PARTS LIST......................................60
15. OPTIONAL PARTS ...........................64
CONTENTS
INDOOR UNIT
FILTER
CHECK MODE
TEST RUN
REMOTE CONTROLLER
The Slim Line. From Mitsubishi Electric.
Page 2
2
1 FEATURES
1.PURSUING CONPACTNESS
(1)Panel size and body volume reduced to 64% of previous models
The width and depth of the panel have been reduced by 19cm respectively, resulting in a compact model which fits smaller environments (like shops) perfectly.
(2)Multi-application panels flexibly adapt to installation conditions.
Space panel and Wide panel may be installed on ceilings with shallow depth using the exiting opening .
2."SMUDGE-FREE", PRECISELY TARGETED AIRFLOW SYSTEM
The new control system regulates airflow to prevent smudging. A projection inside the air passage distributes air evenly over the top and bottom of the vane. Two projections on the air outlet work to prevent cooled air from rising to the celling, and also to stop outside air being dragged into the cooled air stream.
3.AIRFLOW ADJUSTABLE TO ANY INDOOR ENVIRONMENT
Airflow can be adjusted according to celling height and the number of air outlets. "Wide Zoming Flow" creates anoptimum airflow for any indoor environment.
4.A FURTHER REFINEMENT OF COMFORT WITH NOISE SUPPRESION
The celling 4-way airflow cassette has a special "silent-design". The "2-Tap"system allows a choice between silent and standard modes according to the height of the cellig. For ordinary residenced which have a low celling, selection of the silent mode will result in remarkable noise reductions.
5.ECONOMICAL AND EASY MAINTENANCE
(1)Push-open grill
Filter clogging is widely recognized as a cause of reduced perfomance, but up until now it has been troublesome to clean filters. With the "push-open grill" the fillter can be smoothly opened out at the push of a button, enabling speedy cleaning.
(2)An unprecedented level of vane-cleaning
The unique airflow system prevents the intake of indoor air. Dewing therefore does not occur, and the vane is flockless. The resulting level of dirt on the vane due to tobacco smoke, dust, etc. is very light,and can be wiped off easily with a neutral detergent
(3)Long-life fillter
This new celling 4-way airflow cassette employs a long life fillter which requires no maintenance for up to 2,500 hours of operation in general office environments. It adds uo to an ideal blend of comfort and low maintenance.
Indoor unit
Ceiling Cassettes
Series PLH
Remote controller
FILTER
CHECK MODE
TEST RUN
Service Ref.
Cooling capacity/Heating capacity
W Btu/h
PLH-1.6KKHB.UK 4,400/4,650[6,050] 15,000/15,900[20,600] PLH-2KKHB.UK 5,400/5,800[7,200] 18,400/19,800[24,600] PLH-2.5KKHB.UK 6,300/[7,200/9,300] 21,500/24,600[31,700]
Page 3
3
6.COMPACT DIMENSIONS MEAN EASY INSTALLATION
(1)Carefree suspension work with lightweight unit
The new unit weighs in at 20kg (9kg lighter than the previous model) and is easy to handle and install. What's more, suspension work is facillitated by compact dimensions ensuring a snug fit.
(2)Smooth installation with "one-direction"bolts
Suspension bolts can be fixes consistently from one direction easing suspension work.
(3)Trouble-free fitting work with slender refrigerant piping
Refrigerant piping has been reduced in size, and pipe-curving work at the installation site can now be completed quickly and economically. In addition, refrigerant and drain piping are set at different corners, which means that flare connections and drain piping heat insulation work can be smoothly and reliably implemented.
(4)Easy-access terminal and control panels for efficient wiring
When performing wiring work, progress can be checked on the power source terminal and control panels simply by removing the electrical parts cover. Adress setting can also be done easily from beneath at a convenient angle.
(5)"One-push"to provisionally position front panel
Panel weight has been redused from 7kg to 3.7kg. The previous 3-step process for provisionally positioning the panel has been streamlined, and now a simple "one-push" action at the diagonal corners fixed it into place, resulting in major time-saving.
2 PART NAMES AND FUNCTIONS
Indoor (Main) Unit
PLH-1.6KKHB·UK PLH-2KKHB·UK PLH-2.5KKHB·UK
Auto Air Swing Vane Disperses airflow up and down and adjusts the angle of airflow direction.
Grill
Filters Remove dust and pollutants from inhaled air
Horizontal Air Outlet Sets airflow horizontal automatically during cooling or dehumidifying.
Downward Air Outlet Sets airflow downward automatically during heating.
Air Intake Inhales air from room.
Page 4
4
Remote controller
Operation buttons
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
This switches between continuous operation and the timer operation.
button
This sets the ventilation fan speed.
button
button
This sets or switches the current time. start time and stop time.
button
This switches the horizontal fan motion ON and OFF.
button
Press this button to switch the cooler electronic dry (dehumidify) automatic and heater modes.
button
This resets the filter service indication display.
FILTER button
This switches between the operation and stop modes each time it is pressed. The lamp on this butoon lights during operation.
ON/OFF button
This sets the room temparature The temparature setting can be performed in 1°C units
Setting range
Cooler 19°C to 30°C Heater 17°C to 28°C
TEMP button
This model name of the remote controller is indicated.
This adjusts the vertical angle of the ventilation.
(This button dose not operate in this model)
CHECK-TEST RUN button
Only press this button to perform an inspection check or test operation. Do not use it for normal operation.
4
FILTER
CHECK MODE
TEST RUN
Page 5
5
Caution
Only the display lights when the unit is stopped and power supplied to the unit.
When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a malfunction.
When the central control remote control unit, which is sold separately, is used the ON-OFF button, button and TEMP
button do not operate.
“NOT AVAILABLE” is displayed when the
k button are pressed.This indicates that this room unit is not equipped with the fan
direction adjustment function and the louver function.
FILTER
CHECK MODE
TEST RUN
240KA
CENTRALLY CONTROLLED display
This indicates when the unit is controlled by optional features such as central control type remote controller.
display
This indicates when the continous operation and time operation modes are set. It also display the time for the timer operation at the same time as when it is set.
OPERATION MODE display
This indicates the operation mode.
STANDBY display
This indicates when the standby mode is set from the time the sleep operation starts until the heating air is discharged.
DEFROST display
This indicates when the defrost operation is performed.
CHECK display
This indicates when a malfunction has occurred in the unit which should be checked.
display
This lamp lights when electricity is supplied to the unit.
display
This displays the selected setting temperature.
display
The current time , start time and stop time can be displayed in tensecond intervals by pressing the time switch button. The start time or stop time is always displayed during the timer operation.
display
This displays the air direction.
Display
In this display example on the bottom left, a condition where all display lamps light is shown for explanation purposes although this differs from actual operation.
display
This display lights in the check mode or when a test operation is performed.
CHECK MODE
TEST RUN
Display
FILTER
This lamp lights when the filter need to be cleaned.
display
The temperature of the suction air is displayed during operation. The display range is 8° to 39°C. The display flashes 8°C when the actual temperature is less than 8° and flashes 39°C when the actual temperature is greater than 39°C.
display
The selected fan speed is displayed.
Operation lamp
This lamp lights during operation, goes off when the unit stops and flashes when amalfunction occurs.
Page 6
6
3
SPECIFICATIONS
Service Ref.
Item Function
Capacity
Btu/h
W
Total input kW
kW
INDOOR UNIT
Service Ref.
Power supply(phase, cycle,voltage)
Input
ARunning current
AStarting current External finish Heat exchanger
Booster heater Operation control & Thermostat
Fan(drive) x No.
kWFan motor output
K/min(CFM)Airflow(Low-High)
kW
mmAq,Pa
Noise level(Low-High) dB(A) Cond. drain conn. O.D.
Weight
mm,(in.)
Dimensions
mm,(in.)W mm,(in.)D mm,(in.)
kg,(lbs)
H
External static pressure
kW
OUTDOOR UNIT
REEFRIGERANT PIPING
Service Ref.
Power supply (phase, cycle, voltage)
Input
ARunning current
AStarting current External finish Refrigerant control Compressor
Fan motor output
Heat exchanger
Model
Starter type
kW
kg,(lbs)
Motor output
Protection devices
kW
Airflow K/min(CFM)
Fan(drive) x No.
Defrost method Noise level
Weight Refrigerant
Dimensions
mm,(in.)W
Pipe size O.D.
mm,(in.)Liquid mm,(in.)Gas
Connection method
Indoor side Outdoor side
Between the indoor & outdoor unit
Height difference Piping length
mm,(in.)D mm,(in.)
kg,(lbs)
H
Charge
dB(A)
PLH-1.6KKHB.UK
Cooling
15,000
4,400
1.59
Heating
15,900[20,600]
4,650[6,050]
1.51[2.91]
0.15
0.64
0.70
0.10[1.50]
0.45[6.28]
0.50[6.63]
UNIT : 660(26) UNIT : 660(26) UNIT : 253(10)
UNIT : 20(44)
PANEL : 760(30) PANEL : 760(30)
PANEL : 30(1-1/8)
PANEL :3.7(8)
1.44
6.74
1.41
6.60
PLH-1.6KKHB.UK
Single. 50Hz. 220-240V
Galvanized sheets with gray heat insulation
Plate fin coil
Turbo fan (direct) x 1
0.030
13-16(460-565)
0(direct blow)
[1.4]
Remote controller & built-in
32-37
32(1-1/4)
PUH-1.6VKA
3.UK
Single. 50Hz. 220-240V
33
Munsell 5Y 7/1
Capillary tube
Hermetic
RH247VFC
1.2
Line start
Inner thermostat, High pressure switch
Plate fin coil
Propeller (direct) x1
0.065
45(1,590)
Reverse cycle
49
870(34-1/4)
295+24 (11-5/8 add 1)
650(25-5/8)
53(117)
R-22
2.2(4.8)
9.52 (3/8)
15.88(5/8) Flared Flared
Max. 40m Max. 40m
Page 7
7
Service Ref.
Item Function
Capacity
Btu/h
W
Total input kW
Service Ref.
Power supply(phase, cycle,voltage)
Input
kW
ARunning current
AStarting current External finish Heat exchanger
Fan(drive) x No.
kWFan motor output
K/min(CFM)Airflow(Low-High)
Booster heater
INDOOR UNIT
External static pressure
mmAq,Pa
kW Operation control & Thermostat Noise level(Low-High) dB(A) Cond. drain conn. O.D.
mm,(in.) mm,(in.)W
Dimensions
H
Weight
mm,(in.)D mm,(in.)
kg,(lbs)
Service Ref.
Power supply (phase, cycle, voltage)
Input
kW
ARunning current
AStarting current External finish Refrigerant control Compressor
Model Motor output
kW Starter type Protection devices
Heat exchanger
OUTDOOR UNIT
Fan(drive) x No. Fan motor output
kW Airflow K/min(CFM)
Defrost method Noise level
dB(A)
mm,(in.)W
Dimensions
H
Weight
mm,(in.)D mm,(in.)
kg,(lbs)
Refrigerant
Charge
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
REEFRIGERANT PIPING
Indoor side Outdoor side Height difference Piping length
kg,(lbs) mm,(in.)Liquid mm,(in.)Gas
PLH-2KKHB.UK
Cooling
18,400
5,400
2.34
Heating
19,800[24,600]
5,800[7,200]
2.32[3.72]
PLH-2KKHB.UK
Single. 50Hz. 220-240V
0.14
0.65
0.72
0.10[1.50]
0.45[6.28]
0.50[6.63]
Galvanized sheets with gray heat insulation
Plate fin coil
Turbo fan (direct) x 1
0.030
13-16(460-565)
0(direct blow)
[1.4]
Remote controller & built-in
32-37
32(1-1/4) UNIT : 660(26) UNIT : 660(26) UNIT : 253(10)
UNIT : 20(44)
PUH-2VKA
PANEL : 760(30) PANEL : 760(30)
PANEL : 30(1-1/8)
PANEL :3.7(8)
2.UK
Single. 50Hz. 220-240V
2.20
9.86
2.22
9.95
45
Munsell 5Y 7/1
Capillary tube
Hermetic
NH38VMD
1.7
Line start
Inner thermostat, HP switch
Plate fin coil
Propeller (direct) x1
0.065
45(1590)
Reverse cycle
49
870(34-1/4)
295+24 (11-5/8 add 1)
650(25-5/8)
64(141)
R-22
2.2(4.8)
9.52 (3/8)
15.88(5/8) Flared Flared
Max. 40m Max. 40m
Page 8
8
Service Ref.
Item Function
Capacity
Btu/h
W
Total input kW
kW
INDOOR UNIT
Service Ref.
Power supply(phase, cycle,voltage)
Input
ARunning current
AStarting current External finish Heat exchanger
Booster heater Operation control & Thermostat
Fan(drive) x No.
kWFan motor output
K/min(CFM)Airflow(Low-High)
kW
mmAq,Pa
Noise level(Low-High) dB(A) Cond. drain conn. O.D.
Weight
mm,(in.)
Dimensions
mm,(in.)W mm,(in.)D mm,(in.)
kg,(lbs)
H
External static pressure
kW
OUTDOOR UNIT
REEFRIGERANT PIPING
Service Ref.
Power supply (phase, cycle, voltage)
Input
ARunning current
AStarting current External finish Refrigerant control Compressor
Fan motor output
Heat exchanger
Model
Starter type
kW
kg,(lbs)
Motor output
Protection devices
kW
Airflow K/min(CFM)
Fan(drive) x No.
Defrost method Noise level
Weight Refrigerant
Dimensions
mm,(in.)W
Pipe size O.D.
mm,(in.)Liquid mm,(in.)Gas
Connection method
Indoor side Outdoor side
Between the indoor & outdoor unit
Height difference Piping length
mm,(in.)D mm,(in.)
kg,(lbs)
H
Charge
dB(A)
PLH-2.5KKHB.UK
Cooling
21,500
6,300
2.60
Heating
24,600[31,700]
7,200[9,300]
2.33[4.43]
0.14
0.61
0.67
0.10[2.20]
0.45[9.20]
0.50[9.55]
UNIT : 660(26) UNIT : 660(26) UNIT : 253(10)
UNIT : 21(46)
PANEL : 760(30) PANEL : 760(30)
PANEL : 30(1-1/8)
PANEL :3.7(8)
2.46
10.68
2.23
9.78
PLH-2.5KKHB.UK
Single. 50Hz. 220-240V
Galvanized sheets with gray heat insulation
Plate fin coil
Turbo fan (direct) x 1
0.030
14-17(495-600)
0(direct blow)
[2.1]
Remote controller & built-in
35-39.5
32(1-1/4)
PUH-2.5VKA
2.UK
Single. 50Hz. 220-240V
52
Munsell 5Y 7/1
Capillary tube
Hermetic
NH41VMD
2.0
Line start
Inner thermostat, HP switch
Plate fin coil
Propeller (direct) x1
0.085
50(1764)
Reverse cycle
52
870(34-1/4)
295+24 (11-5/8 add 1)
850(34-1/4)
68(150)
R-22
2.8(6.2)
9.52 (3/8)
15.88(5/8) Flared Flared
Max. 50m Max. 50m
Page 9
9
DATA4
1. PERFORMANCE DATA
1) COOLING CAPACITY
Note CA:Capacity (W)
P.C.:Power consumption (kW)
Cooling capacity correction factors
PLH-1.6KKHB.UK
PLH-2KKHB.UK
PLH-2.5KKHB.UK
Indoor intake
air
WB$C
16 18 20 22 16 18 20 22 16 18 20 22
Outdoor intake air DB$C
20
CA 4,439 4,726 5,017 5,310 5,448 5,800 6,157 6,517 6,356 6,767 7,183 7,603
P.C.
1.27
1.30
1.32
1.35
1.88
1.91
1.95
1.99
2.08
2.13
2.17
2.21
25
CA 4,317 4,602 4,899 5,209 5,299 5,648 6,012 6,392 6,182 6,589 7,014 7,458
P.C.
1.33
1.36
1.38
1.41
1.96
2.00
2.04
2.08
2.17
2.22
2.26
2.31
30
CA 4,159 4,434 4,724 5,028 5,104 5,442 5,798 6,171 5,955 6,349 6,764 7,199
P.C.
1.43
1.46
1.50
1.53
2.11
2.15
2.20
2.25
2.34
2.39
2.45
2.50
35
CA 3,990 4,258 4,542 4,840 4,897 5,226 5,574 5,940 5,713 6,097 6,503 6,930
P.C.
1.53
1.57
1.61
1.65
2.26
2.31
2.37
2.42
2.51
2.57
2.63
2.69
40
CA 3,812 4,074 4,352 4,645 4,678 5,000 5,341 5,700 5,472 5,841 6,232 6,645
P.C.
1.64
1.68
1.72
1.77
2.41
2.47
2.54
2.61
2.68
2.74
2.82
2.90
45
CA 3,624 3,882 4,154 4,442 4,447 4,764 5,099 5,451 5,207 5,571 5,954 6,359
P.C.
1.74
1.79
1.84
1.90
2.56
2.63
2.71
2.80
2.85
2.92
3.01
3.11
Service Ref.
Refrigerant piping length(one way)
30m
0.961
0.959
0.950
35m
0.956
0.950
0.940
40m
0.948
0.945
0.930
45m
0.920
50m
0.910
PLH-1.6KKHB.UK
PLH-2KKHB.UK
PLH-2.5KKHB.UK
5m
1.00
1.00
1.00
10m
0.993
0.992
0.989
15m
0.984
0.983
0.980
20m
0.978
0.978
0.970
25m
0.969
0.966
0.960
Service Ref.
Cooling performance curve(50Hz)
1.4
1.2
1.0
0.8
0.6
1.4
1.2
1.0
0.8
0.6
0.4
-5 5 15 253546 OUTDOOR DB(°C)
TOTAL INPUT (RATIO) CAPACITY (RATIO)
INDOOR WB(°C)
INDOOR WB(°C)
22 20 18 16
22 20 18 16
Page 10
10
2) HEATING CAPACITY
Note CA:Capacity (W)
P.C.:Power consumption (kW)
Heating capacity correction factors
PLH-1.6KKHB.UK
PLH-2KKHB.UK
PLH-2.5KKHB.UK
Indoor intake
air
DB$C
15 20 25 15 20 25 15 20 25
Outdoor intake air WB$C
-10
CA 3,184 3,049 2,930 3,972 3,803 3,655 4,931 4,721 4,537
P.C.
1.03
1.11
1.18
1.58
1.71
1.81
1.59
1.71
1.82
-5
CA 3,650 3,506 3,364 4,552 4,373 4,196 5,651 5,429 5,209
P.C.
1.14
1.23
1.31
1.75
1.89
2.01
1.76
1.89
2.02
0
CA 4,160 4,003 3,844 5,188 4,993 4,795 6,441 6,198 5,952
P.C.
1.25
1.35
1.44
1.93
2.08
2.22
1.93
2.09
2.23
5
CA 4,714 4,538 4,370 5,880 5,661 5,451 7,299 7,027 6,767
P.C.
1.38
1.48
1.59
2.11
2.28
2.44
2.12
2.29
2.45
10
CA 5,312 5,112 4,942 6,625 6,376 6,165 8,225 7,916 7,653
P.C.
1.51
1.62
1.74
2.31
2.49
2.67
2.32
2.50
2.68
15
CA 5,952 5,724 5,560 7,424 7,139 6,935 9,216 8,863 8,609
P.C.
1.64
1.77
1.90
2.52
2.71
2.91
2.53
2.73
2.92
Service Ref.
Refrigerant piping length(one way)
30m
1.00
1.00
1.00
35m
0.998
0.998
0.998
40m
0.995
0.995
0.995
45m
0.993
50m
0.990
PLH-1.6KKHB.UK
PLH-2KKHB.UK
PLH-2.5KKHB.UK
5m
1.00
1.00
1.00
10m
1.00
1.00
1.00
15m
1.00
1.00
1.00
20m
1.00
1.00
1.00
25m
1.00
1.00
1.00
Service Ref.
Heating performance curve(50Hz)
1.4
1.2
1.0
0.8
0.6
1.4
1.2
1.0
0.8
0.6
0.4
-12-10 -5 0 5 10 15 OUTDOOR WB($C)
INDOOR DB ($C)
INDOOR DB ($C)
15 20 25
25 20 15
TOTAL INPUT (RATIO) CAPACITY (RATIO)
Page 11
11
2. ELECTRICAL DATA
Indoor unit77220V 50Hz 1phase Outdoor unit7220V 50Hz 1phase
Indoor unit77230V 50Hz 1phase Outdoor unit7230V 50Hz 1phase
Indoor unit77240V 50Hz 1phase Outdoor unit7240V 50Hz 1phase
Indoor unit
Service Ref.
Outdoor unit
PLH-1.6KKHB.UK
PUH-1.6VKA
3.UK PUH-2VKA2.UK PUH-2.5VKA2.UK
PLH-2KKHB.UK
PLH-2.5KKHB.UK
Mode
Capacity (W)
Total Input (kW)
Input (kW)
Current (A)
Starting current (A)
Input (kW)
Current (A)
Starting current (A)
Outdoor unit Indoor unit
Indoor unit
Service Ref.
Outdoor unit
Mode
Capacity (W)
Total Input (kW)
Input (kW)
Current (A)
Starting current (A)
Input (kW)
Current (A)
Starting current (A)
Outdoor unit Indoor unitIndoor unitOutdoor unit
Cool
4,300
1.48
0.12
0.60
0.66
4,550[5,720]
1.40[2.57]
0.08[1.25]
0.41[5.75]
0.45[6.14]
1.36
6.79
30
PLH-1.6KKHB.UK
PUH-1.6VKA
Cool
4,350
1.54
0.14
0.62
0.68
4,600[5,890]
1.45[2.74]
0.09[1.38]
0.43[6.02]
0.47[6.39]
1.40
6.76
32
Heat
1.32
6.59
30
Cool
5,300
2.24
0.12
0.61
0.67
2.12
9.83
43
Heat
5,700[6,870]
2.22[3.39]
0.08[1.25]
0.42[5.76]
0.46[6.14]
2.14
9.93
43
PLH-2KKHB.UK
3.UK PUH-2VKA2.UK PUH-2.5VKA2.UK
Heat
1.36
6.57
32
Cool
5,350
2.29
0.13
0.63
0.69
2.16
9.78
44
Heat
5,750[7,040]
2.27[3.56]
0.09[1.38]
0.44[6.03]
0.48[6.39]
2.18
9.87
44
Cool
6,200
2.53
0.12
0.57
0.63
2.41
11.18
52
PLH-2.5KKHB.UK
Cool
6,250
2.57
0.13
0.59
0.65
2.44
10.94
52
Heat
6,900[8,660]
2.25[4.01]
0.09[1.85]
0.42[8.44]
0.46[8.79]
2.16
10.02
52
Heat
7,050[8,980]
2.29[4.22]
0.09[2.02]
0.43[8.82]
0.47[9.19]
2.20
9.86
52
Indoor unit
Service Ref.
Outdoor unit
Mode
Capacity (W)
Total Input (kW)
Input (kW)
Current (A)
Starting current (A)
Input (kW)
Current (A)
Starting current (A)
PLH-1.6KKHB.UK
PUH-1.6VKA
Cool
4,400
1.59
0.15
0.64
0.70
4,650[6,050]
1.51[2.91]
0.10[1.50]
0.45[6.28]
0.50[6.63]
1.44
6.74
33
PLH-2KKHB.UK
3.UK PUH-2VKA2.UK PUH-2.5VKA2.UK
Heat
1.41
6.60
33
Cool
5,400
2.34
0.14
0.65
0.72
2.20
9.86
45
Heat
5,800[7,200]
2.32[3.72]
0.10[1.50]
0.45[6.28]
0.50[6.63]
2.22
9.95
45
PLH-2.5KKHB.UK
Cool
6,300
2.60
0.14
0.61
0.67
7,200[9,300]
2.33[4.43]
0.10[2.20]
0.45[9.20]
0.50[9.55]
2.46
10.68
52
Heat
2.23
9.78
52
Page 12
12
Mode
Total
Electrical circuit
Refrigerant circuit
Indoor side
Outdoor
side
Capacity
Input
Indoor unit Service Ref.
Phase,Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase,Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
SHF
BF
W
kW
MPa·G
MPa·G
$C
$C
$C
m
DB$C
WB$C
DB$C
DB$C
WB$C
PLH-1.6KKHB.UK
Cooling
4,400
1.59
PLH-1.6KKHB.UK
1,50
240
0.64
Heating
4,650
1.51
0.45
PLH-2KKHB.UK
Cooling
5,400
2.34
PLH-2KKHB.UK
1,50
240
0.65
Heating
5,800
2.32
0.45
PLH-2.5KKHB.UK
Cooling
6,300
2.60
PLH-2.5KKHB.UK
1,50
240
0.61
Heating
7,200
2.33
0.45
PUH-1.6VKA
3.UK
1,50
240
PUH-2VKA2.UK
1,50
240
PUH-2.5VKA2.UK
1,50
240
6.74
1.80
0.54
78.7
48.5
8.5
5
27
19
16.1
35
24
0.83
0.21
6.60
1.70
0.40
77.2
0.7
5
20
15
35.2
7
6
9.86
1.90
0.46
84.0
50.7
4.8
5
27
19
15.0
35
24
0.76
0.21
9.95
1.94
0.34
86.4
–1.8
5
20
15
39.4
7
6
10.68
1.95
0.50
82.8
51.8
6.7
5
27
19
13.8
35
24
0.75
0.14
9.78
1.71
0.36
76.0
–1.5
5
20
15
41.2
7
6
Service Ref.
V
A
V
A
(O/F·G)
(O/F·G)
(18.3)
(5.51)
(17.3)
(4.08)
(19.3)
(4.69)
(19.7)
(3.47)
(19.8)
(5.1)
(17.4)
(3.67)
High ceiling Standard
Air flow m3/min
Air speed m/sec.
Coverage range m
Air flow m
3
/min
Air speed m/sec.
Coverage range m
Total width of dischsrge outlets mm
PLH-1.6KKHB.UK
16.0
5.6
6.0
17.0
5.9
6.4
0
PLH-2KKHB.UK
16.0
5.6
6.0
17.0
5.9
6.4
0
PLH-2.5KKHB.UK
17.0
5.9
6.4
18.0
6.3
6.8
0
Service Ref.
3. STANDARD OPERATION DATA
4. OUTLET AIR SPEED AND COVERAGE RANGE
wThe air coverage range is the value up to the position where the air speed is 0.25m/sec.
When air is blown out horizontally from the unit at the Hi notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room.
The unit of pressure has been changed to Mpa on the international system of unit (SI unit system.) The converted score against the traditional unit system can be gotten according to the formula below.
1 (Mpa·G)=10.2(O/F·G)
Page 13
13
OUTLINES AND DIMENSIONS5
Unit : mm
Ceiling hole
Suspension bolt pitch
Suspension bolt M10 or
Air intake hole
Air outlet hole
Air intake grill
690~710 25~3525~35
640
660
466
460
66 35
760
117 117
117
435
13545
117
Ceiling hole
Suspension bolt pitch
Suspension bolt lower edge
Air outlet hole
Air outlet hole
690~710
25~35
25~35
65~80
760
460
466
6635
115
243
253
29330
54
+3
- 2
507
660
54
53
Terminal block for control
Terminal block for
remote controller
Terminal block for
power supply
Drain hole
Drain hole
VP-25 connection
W3/8
Feeding hole
(Drain pump)
Leave space of 10~15mm between the
top surface of the unit and the ceiling slab.
Ceiling surface
4-Auto vanes
Intake grill opening/closing side
Vane motor
Decorative panel
Control wire entry
Refrigerant piping side
electric wire entry side
Power line entry
41 25
Liquid pipe
Gas pipe
Optional high-efficiency hilter
NOTE1. For electrical parts box may be removed during servicing. When
connecting the power line and the control wire, provide enough length to
the electric wires.
NOTE2. When installing the optional high-efficiency filter, the dimension
between the transom and ceiling shall be more than 440mm. Also,when
installing the optional casement, the dimension between the transom
and ceiling shall be more than 440m. (The optional highefficiency filter
can also be installed.)
1 2
Refrigerant pipe {9.52
Flared connection 3/8F
Refrigerant pipe {15.88
Flared connection 5/8F
1.6/2/2.5KK
1. INDOOR UNIT PLH-1.6KKHB.UK PLH-2KKHB.UK PLH-2.5KKHB.UK
Page 14
14
Unit : mm (inch)
2. REMOTE CONTROLLER
18
130
Rear side wiring arrangement opening.
120
FILTER
CHECK MODE
TEST RUN
FILTER
CHECK MODE
TEST RUN
46
83.5
SW18
SW17
CAUTION
Page 15
15
WIRING DIAGRAM6
NOTES :
1. Since the indoor transformer (T)is connected with 240Vpower. If 220, 230v power is used. change the wiring connection showing fig: w2
When power supply is
2. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
3. Indoor and outdoor connecting wires are made with polarities. make wiring matching terminal numbers.
4. Symbols used in wiring diagram above are. / : Terminal block, : Connector.
5. Emergency operation
If remote controller or microcomputer fails but there is no other truble,. emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor
controller board. [Check items] (1)Make sure that no other trouble exists the outdoor unit. Trouble with the outdoor unit prevents emergency operation.
(If any trouble exists the outdoor unit error code “P8”will be displayed on the remote controller and the trouble position will be shown on the outdoor controller
board LED. See electric wiring diagram of the outdoor unit for details.) (2)Make sure that there is no trouble with the indoor fan.
Emergency operation will be continuous run with the power ON/OFF (ON/OFF with the remote controller is not possible). [Emergency operation procedure] (1)Switch the fan connector on the indoor controller board from FAN 1 to FAN 2.
(2)Set the dip switch (SW3<I.B>) on the indoor controller board to 1 on and 2 off for cooling and 1 - 2 on for heating.
(3)Turn on the outdoor unit side circuit breaker, then the indoor unit side circuit breaker. (4)During emergency operation indoor fan runs at High speed but auto-vane does not work. (5)Thermostat will not function. Cold air blows out for defrosting during heating thus do not operate defrosting for a long time. (6)Emergency cooling should be limited to 10 hours maximum. (the indoor unit heat exchanger may freeze). (7)After every operation, switch the fan connector to FAN1, and set all dip switches (SW3<I.B>) to OFF. NOTE: If the drain water lift up mechanism is identified to be defective with the microcomputer doctor during cooling, do not use emergency operation
(it causes drain overflow)
fig:w2
240V
230V
220V
230V 220V
YELLOW ORANGE RED
SYMBOL NAME R.B
REMOTE CONTROLLER BOARD SW17<R.B> ADDRESS SELECTOR SW18<R.B> FUNCTION SELECTOR CN1<R.B>
PROGRAM TIMER CONNECTOR CN2<R.B>
REMOTE SWITCH CONNECTOR MV VANE MOTOR LS LIMIT SWITCH H2 DEW PREVENTION HEATER RT1
ROOM TEMP. THERMISTOR(0°C/15K1,25°C5.4K1) RT2
INDOOR COIL THERMISTOR(0°C/15K1,25°C5.4K1) T TRANSFORMER MF INDOOR FAN MOTOR C1 FAN MOTOR CAPACITOR TB2~6 TERMINAL BLOCK I.B INDOOR CONTROLLER BOARD
SYMBOL NAME CN2L<I.B>
LOSSNAY CONNECTOR
CN51<I.B>
CENTRALLY CONTROL CONNECTOR
FAN2<I.B>
EMERGENCY OPERATION CONNECTOR F.C<I.B> FAN PHASE CONTROL SW1<I.B> MODE SELECTOR SW2<I.B> ADDORESS SELECTOR SW3<I.B>
EMERGENCY OPERATION SWITCH SW5, SW7<I.B> MODEL SELECTOR SW6<I.B> TWIN, TRIPLE SWITCH SWA<I.B>
HIGH SEILING, NOISE SAVING SELECTOR SWB<I.B>
NUMBER OF AIR OUTLETS SELECTOR SWC<I.B> OPTION SELECTOR ZNR<I.B> VARISTOR X1<I.B>
DRAIN PUMP/D.HEATER RELAY
SYMBOL NAME X3<I.B>
VANE MOTOR RELAY
X4<I.B>
FAN MOTOR RELAY F1<I.B> FUSE (6.3A) LED1<I.B> DC 12V POWER LED LED2<I.B> DC 5V POWER LED CNP<I.B> DRAIN PUMP CONNECTOR CN50<I.B> DRAIN SENSOR CONNECTOR DP DRAIN PUMP DS DRAIN SENSOR H1 HEATER FS1,2 THERMAL FUSE 26H HEATER THERMAL SWITCH 88H HEATER CONNECTOR CNV<I.B> VANE MOTOR CONNECTOR
PLH-1.6KKHB·UK/PLH-2KKHB·UK/PLH-2.5KKHB·UK
2.5KK
2KK1.6KK
MODELS
SW7
OFF
ON
32
1
OFF
ON
32
1
OFF
ON
32
1
fig:1
YLW
YLW
YLW
BLU
RED
BLU
RED
YLW
*PLH-1.6,2,2.5KKHB(with heater)
26H
1 2
POWER SUPPLY ~(1PHASE) 220-240V 50Hz
H1
L N
3
88H
TB2
3
1
5
FS1
FS2
HEATER CN24
1
6
88H
1
2
2
1
3 4
1
5
4
3
2
1
3
2
5
4
3
2
1
1
3
5
1
0
DP
6
1
7
2
MV
MF
31 5
1
5
4
3
2
4
3
2
1
2
1
4
3
2
1
2
1
2
1
1
3
2
2
1
2
1
1234
31313131
5
B
R
N
B
R
N
LS
Showing fig:1
12V POWER
LED1
5V POWER
LED2
X1X3
X4
STD
OP
SWC
SW7 SW3
2
1321
4
3
2
SWB
1
2
3
SWA
10987432165
4321
SW6
432165432
1
SW1
SW5
CN24
HEATER
OFF
ON
SW2
RT2
DS
RT1
CN51
CONTROL
CENTRALLY
DRAIN
CN50
CN41
POWER
REMOCON
CN40
INTAKE
CN20
PIPE
CN21
CN22
TO REMOCON
CN30
OUTDOOR
CN23
VANE
CN2L
LOSSNAY
R
.B
.
OFF
OFF
ON
TB6
SW17
SW18
CN1
CN2
2
1
2
1
BLU
BLU
TRNSMISSION WIRES DC12V
BRN
ORN
YLW
TRNSMISSION WIRES DC12V
OUTDOOR
UNIT
3
2
1
1
3
2
TB3
TB4
BLK WHT
G
RILL
H2
B
L
U
B
LU
B
R
N
B
R
N
BRN
BRN
CN4T
TRANS
11.1V AC
14.2V AC
BRN
RED
T
YLW
ORN
YLW
RED
RED
BLU
RED
GRN/YLW
POWER SUPPLY
~(1PHASE)
220-240V 50Hz
220V 60Hz
N
L
TB2
YLW
YLW
C1
RED
FAN2
F1
ZNR
X1X3
X4
F.C
TRANSPOWERD.U.M.VANEFAN
CNTCNDCNPCNVFAN1
BG79Y408H01
ON
Page 16
16
7
REFRIGERANT SYSTEM DIAGRAM
Service port
Capillary tube
Indoor heat exchanger
Indoor coil thermistor (RT2)
Distributor with strainer
PLH-1.6 (O.D.3.2 I.D.1.6 –R 630) PLH-2.5 (O.D.3.2 I.D.1.8 –R 430)
wPLH-1.6 (O.D.3.2 I.D.1.8 –R 400)
PLH-2 (O.D.4.0 I.D.2.0 –R 430) PLH-2.5 (O.D.4.2 I.D.2.4 –R 1550)
PLH-2 (O.D.3.2 I.D.1.8 –R 630)
Restrictor valve
Refrigerant pipe (option)
9.52mm( 3.8") (with heat insulator)
Ball valve (with service port)
Indoor unit
Strainer
Refrigerant pipe (option)
15.88mm( 5/8") (with heat insulator)
Flexible tube
Flared connection
Ball valve
Strainer
4-way valve
Oil separator
Service port
High pressure control switch
High pressure protect switch
Outdoor unit
Outdoor heat exchanger
Flow of refrigerant (cooling) Flow of refrigerant (heating)
Outdoor coil thermistor (TH)
Bypass valve
Restrictor valve
w
Capillary tube
Strainer
Compressor
Accumulator
Refrigerant flow in cooling Refrigerant flow in heating
R.V.coil Heating ON Cooling OFF
PLH-1.6KKHB·UK/PUH-1.6VKA3·UK PLH-2KKHB·UK/PUH-2VKA
2·UK
PLH-2.5KKHB·UK/PUH-2.5VKA
2·UK
Unit : mm
Page 17
17
OPERATION FLOW-CHART
8
START
Power circuit
breaker
Check SW
ON twice
Operation SW
ON
“OFF” timer
“ON” timer
STOP
Set time complete
Set time complete
1
NO
NO
NO NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
PROTECTION DEVICE
SELF HOLD RELEASE
Remote controller indicator lamp OFF
Trouble STOP
Remote controller
operation display
Operating mode
(COOL)
Operating mode
(DRY)
Operating mode
(HEAT)
Operating mode
(FAN)
Auto COOL/HEAT
operation
COOL operation
DRY operation
HEAT operation
FAN operation
Trouble
PROTECTION DEVICE
SELF HOLD
Remote controller
trouble display
Indoor side
Outdoor side
Fan STOP
Auxiliary heater OFF
Compressor OFF
Fan STOP
Four-way valve OFF
w1
w2
w3
w6
w4
w7
w5
MAIN OPERATION
w1 In addition, the centralized control and remote control can be operated. w2 The modes which indicate the sources of trouble are listed below.
EO-Signal transmitting/receiving error
P1-Room temperature thermistor malfunction
P2-Indoor coil thermistor malfunction
P4-Drain sensor malfunction
P5-Drain overflow
P6-Coil frost/overheat protection
P7-System error
P8-Outdoor unit trouble
w3 The CHECK swich will show if an error has occurred in the past. w4 Fan runs on low speed for 1 minute in order to remove overheat air. w5 The 3-minute (6 minutes …heating mode) time-delay functions after compressor stops. w6 FAN or AUTO mode is selected by the indoor dipswitch setting. w7 In FAN mode, fan speed and vane operation depend on the remote controller setting. (Compressor is OFF.)
Page 18
18
COOL operation
Four-way valve/OFF
Initial
COOLING
NO
NO
NO
NO
NO
NO
YESw8
YES
YES
YES
YES
YES
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
Vane initial
setting
Vane 55 deg downward angle 70 deg downward angle
Fan speed
LOW
Downward discharge
1 hour
Vane setting notch
Vane horizontal
airflow
Compressor
thermostat
ON
Allowance
cancel
3-minute
time delay
6-minute
time delay
3-minute
compressor operation
Coil frost
prevention
Cooling area
10-minute
compressor operation
Allowance cancel
Coil frost protection
16-minute
compressor operation
Indoor pipe
temperature is
1$C or lower
Compressor ON
1
Coil frost
prevention
Compressor OFF
Indoor coil tempreature is 10$C or higher
3-minute
time delay
Coil frost
prevention release
Allowance
period
6 minute
time delay
Allowance set
1 min continue
Coil frost protection
FAN speed
LOW
FAN speed
LOW 5 min
elapse
Outdoor unit
trouble
w9
w10
w11
COOLING OPERATION
w8 When operation stops or changes to cooling or dry mode, the auto vane tums to a horizontal angle. If operation changes
during auto vane SWING, the auto vane will continue to swing.
w9 When operating TEST RUN, the thermostat will be continuously ON. w10 After 3 minute compressor operation, if the indoor coil thermistor reads -15°C or below for 3 minutes, the compressor will
stop for 6 minutes.
w11 Cooling area : Indoor coil temperature is more than 5 degrees above the room temperature.
Heating area : Indoor coil temperature is more than 5 degrees below the room temperature. FAN area : Indoor coil temperature is within 5 degrees either way of the room temperature.
Page 19
19
HEATING OPERATION
AUTOMATIC COOLING/HEATING OPERATION
w15 ( i ) Until Low airflow is set while hot adjustment
(ii)While defrosting (FAN STOP) (iii)When thermostat is OFF In the case of( i ), (ii) and (iii) above, airflow is horizontal regardless the VANE setting.
w16 When AUTO operation is started, COOL or HEAT mode is selected automatically. w17 T1 : Room temperature.
To : Set temperature
Heat operation
NO
Initial
HEATING
Vane setting notch
Vane initial setting
Defrosting
Four-way valve ON
Hor adjust in process
Compressor ON
Compressor
w9
thermostat ON
Allowance cancel
NO
Indoor piping
-15$C or lower
Outdoor unit
trouble
FAN SPEED
Very low airflow
Compressor OFF
Auto COOL/HEAT
operation
NO
Initial mode
w17
1 T0
T
COOL mode HEAT mode
A
Type
OFF
NO
NO
NO
NO
NO
NO
YES
FAN setting notch
B
YES
YES
w10
w11
NO
Heating area
NO
Defrost
30 min. elapse
YES
Outdoor unit trouble
1
A
Outdoor unit
trouble
YES
Defrost release
NO
Indoor piping 55$C or lower
NO
Auxiliary heater
NO
Indoor piping
60$C or higher
YES
Auxiliary heater OFF
Overheat remote
NO
Indoor unit
70$C or higher
Allowance
Overload protect
B
ON
START
period
1
2
NO
YES
YES
YES
YES
NO
Auxiliary heater
thermostat ON
Auxiliary heater ON
NO
6-minute restart
Allowance set
Compressor OFF
prevention
YES
YES
35$C or higher
FAN SPEED
FAN SPEED
setting nitch
Hot adjust
w15
YES
YES
NO
YES
NO
YES
NO
YES
3 min.restart
prevention
YES
2
YES
1
w16
YES
NO > =
YES
NO
6 min. restart
prevention
NO
Hot adjust start
FAN SPEED very low
Compressor ON
NO
compressor
Allowance cancel
Heating
FAN STOP
w11
Airflow area
20 min.elaspe
YES
Airflow area Heating area
w11
Airflow area Cooling area
Defrost operation
Four-way valve
10-minute
operation
YES
area
NO
NO
YES
START
OFF
Indoor piping
NO
HOT adjust
6 min. elapse
YES
Low
FAN SPEED
Low 2 min.
elapse
YES
release
PLH-KKHB
3-minute
Auxiliary heater
Indoor coil
thermstor is 60$C
or higher
FAN speed
Low notti
Airflow 10% up
NO
NO
1
<(T0-2)
T
YES
YES
NO
NO
1>(T0 + 2)
T
YES
NO
11
YES
After 15min.
T1>(T0 + 2)
NO
HEAT operation
YES
Cool mode
set
COOL mode
NO
1 < (T0 - 2)
T
After 15min.
COOL operation HEAT operation
Page 20
20
w8—9 Refer to page 26~27. w12 When room temperature is 18°C or below, the compressor cannot operate.
When room temperature rises over 18°C, the compressor starts after a 3-minute time delay.
w13 Compressor ON time is decided by room temperature. Refer to page 26~27 . w14 In dry operation, compressor ON makes the fan speed LOW and compressor OFF stops the fan.
It is not possible to set the fan speed with the remote controller
DRY OPERATION
DRY
operation
Four-way valve / OFF
Initial dry
operation
Room tempereature is
18°C or lower
During
compressor ON
Compressor &
thermostat ON
Vane initial setting
Vane
setting notch
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
3-minute
time delay
10-minute
compressor
OFF
Compressor ON
time set
Compressor ON
Fan speed LOW
1
Compressor &
thermostat
ON
3-minute
compressor
operation
Compressor ON
time completes
NO
YES
NO
NO
YES
w
14
w
14
w
13
YES
YES
NO
YES
NO
NO
w
9
YES
YES
w
9
NO
NO
w
12
YES
NO
YES
w
8
Page 21
21
MICROPROCESSOR CONTROL
9
Compressor and outdoor fan : ON­OFF
Operation mode change :COOL­HEAT.
1.OUTLINE OF MICROPROCESSOR CONTROL
OFF-ON switching.
COOL/DRY-AUTO-HEAT selector switching.
Thermostat setting.
TIMER mode selector-switching and Timer
setting.
HIGH-LOW fan speed switching.
AUTO Vane selector (AIR DISCHARGE)
switching.
TEST RUN switching.
CHECK mode switching.
(Self diagnostic trouble shooting)
Room temperature thermistor (RT1)
Indoor coil thermistor (RT2)
Drain sensor
Autovane’s angle setting.
Booster heater ON-OFF Control.
Drain pump : ON-OFF.
Emergency stop.
Compressor
protectiondevice working
Defrosting START-STOP
Fan speed control.
Crankcase heater control
ON-OFF.
Self diagnostic function
Independent Control of Outdoor Unit
OUTPUT to indoor unit
INPUT from indoor unit
INPUT to remote controller
Remote controller board
Processes and transmits orders.
OUTPUT to remote controller
Indoor controller board
Receives orders from remote controller and temperature data from indoor unit.
Processes orders and data.
Controls indoor and outdoor operation.
Self diagnostic function.
w System control operation. w Emergency operation. w Set by dipswitch on indoor controller board.
Transmits the power to remote controller.
OUTPUT to outdoor unit
12VDC
Non-polar, two-wire cable maxinmum length 500 meters
Signal
Remote controller
LCD indicator
Polar three-wire cable
12VDC
123
1 2 3
Indoor unit
Outdoor unit
FILTER
CHECK MODE
TEST RUN
240KA
Page 22
22
2. INDOOR UNIT CONTROL
2-1COOL operation
(1) Compressor control
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when room temperature is higher than set temperature.
The compressor stops when room temperature is equal to or lower than the set temperature.
3 The compressor stops in check mode or during protective functions. 4 Coil frost prevention
To prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 1: or below after the compressor has been continuously operated for at least 16 minutes or more. When the indoor coil temperature rises to
10: or above, the compressor will start after a 3-minute time delay. NOTE : By turning OFF the dipswitch SW1-5 on indoor controller board, the start temperature of coil frost prevention
changes from 1: to -3:.
<How to operate>
1 Press POWER ON/OFF button.
2
Press the button to display “
3
Press the TEMP button to set the desired temperature.
NOTE: Set temperature changes 1°C when the or
button is pressed one time. Cooling 19 to 30°C
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Drain pump
Booster heater
Compressor
ON
ON
LOW or HIGH
Initally 30 degrees
(Changeable by remote controller setting)
LOW or HIGH
ON
ON
OFF
OFF
discharge position
30
3 minutes
OFF
OFF
OFF
OFF
Operation starts by POWER button ON.
Operation stops by POWER button OFF.
Room temperature becomes equal to set temperature.
Room temperature rises above set temperature.
air flow position
30
<COOL operation time chart>
w1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period has ended.
FILTER
CHECK MODE
TEST RUN
240KA
Page 23
23
5 Coil frost protection
When indoor coil temperatuer becomes -15°C or below,coil frost protection will proceed as follows.
<Start condition>
After the compressor has been continuously operated for 3 minutes or more,and the indoor coil temperature has been ­15° or below for 3 minutes,the coil frost protection will start.
<Coil frost protection>
Compressor stops for 6 minutes,and then restarts. lf the start condition is satisfied again during the first 10 minutes of compressor operation,both the indoor and outdoor units stop,displaying a check code of“P8”on the remote controller.
<Termination conditions>
Coil frost protection is released when the start condition is not satisfied again during the allowance, or when the COOL mode stops or changes to another mode.
(2) Indoor fan control
Indoor fan speed LOW/HIGH depends on the remote controller setting. However, if an outdoor unit abnormality is detected, the indoor fan speed will be LOW, regardless of the remote controller setting.
When the outdoor unit abnormality detection is released and the fan speed returns to the set speed, the quiet cycle control will work. (a) Normal control
( i ) Fan speed LOW/HIGH depends on the remote controller setting regardless of the thermostat ON/OFF. (ii) Fan speed will remain on LOW if an abnormality in outdoor unit is detected. (5 minutes)
When the abnormality detection is released, the fan speed returns to the set speed.
1 Start-up of outdoor unit abnormality
detection.
2 Release of outdoor unit abnormality
detection.
3 Unit stop due to outdoor unit abnormality
with P8 indication.
NOTE 1 : Fan stops immediately if the unit stops or the check mode is started.
5 minutes
SET
LOW
5 minutes
SET
LOW
OFF
Page 24
24
(3) Auto vane control
Auto vane position is set to 35degrees airflow at the start-up of COOL operation. It can then be changed by the remote controller.
(a) Stop mode (fixed operation) ( i ) At start-up of COOL operation, the auto vane is set to 10 degrees air flow direction. ( ii ) Airflow direction can be changed with botton.
(b) SWING mode ( i ) The vane motor turns ON when the SWING mode is selected.
The vane motor is continuously ON during SWING mode.
When 55 degrees or 70 degrees air flow is selected with the LOW fan speed in COOL operation, “AUTO RETURN” will appear below the temperature display. One hour later, the air flow direction returns to 30 degrees automatically and “AUTO RETURN” will disappear. If the air flow direction is set to 30 degrees during “AUTO RETURN” indication, the time counting for AUTO RETURN is cancelled.
1 Fan speed : LOW
2 Fan speed : HIGH
30°
55°
70°
30°
55°
70°
SWING
SWING
(SW5-3:OFF/ON)
(SW5-3:OFF/ON)
45°
30
30
55
45
70
AUTO RETURN AUTO RETURN
55
70
<AUTO RETURN>
1 Fan speed : LOW
2 Fan speed : HIGH
Page 25
25
<Auto vane drive> (a) The auto vane is driven by a 2.5 rpm motor. (b) Airflow direction can be selected between the No.1 and No.2 setting. (Initial setting is No.1)
(d) Airfiow direction is based on the horizontal position detected by the vane motor limit switch. When the horizontal
position can not be determined, the vane motor will remain ON until it is determined.
1 If the horizontal position still can not be detected, despite the 10minute detection, the vane motor will turn OFF.
Remote controller indication continues.
2 After, if the vane motor receives the “auto vane ON” command again, it will restart detecting the horizontal position.
If the horizontal position still can not be determined, despite the 10-minute detection, the vane motor will turn OFF.
(4) Detecting abnormalities in the outdoor unit
After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperature and room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the difference is still out of RANGE C,the outdoor unit is functioning abnormally. Thus, the compressor stops and check code “P8” appears on remote controler. RANGE A : Indoor coil temperature is more than 5 degrees above room temperature. RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature. RANGE C : Indoor coil temperature is more than 5 degrees below room tempetature.
1
30°
2
45°
3
55°
4
70°
50Hz
Airflow direction change
Downward C Horizontal 41
Rise
Horizontal Downward A 12
2.4
Downward B Downward C 34
2.3
Downward A Downward B 23
1.3
(c) Vane motor drive time
Indoor coil temperature minus room temperature
+5
0
-5
RANGE A
RANGE B
RANGE C
(degree)
(5) Drain pump control
The drain pump works in COOL or DRY operation. When operation stops or changes to HEAT mode, the drain pump continues to operate for 3 more minutes. The drain pump does not work in check mode.
<Drain sensor>
When both the drain pump and unit are operating, the drain sensor detects the temperature. This temperature tells whether the drain water level is above or under the drain sensor. If the drain water level rises above the drain sensor due to a drain pump malfunction, the unit will stop operating in order to prevent drain from overflowing. The check code “P5” on the remote controller will display this occurrence. When both of the following conditions are satisfied, the drain sensor is determined to be under water.
Though the drain sensor has been heated by the drain sensor heater for more than 40 seconds, its temperature rise is less than 20 degrees.
The drain sensor temperature is below 63°C.
(6) Dew prevention heater
To prevent dew from accumulating on the grill, the dew prevention heater is continuously ON during COOL operation. It is independant of the thermostat ON/OFF
Unit : sec
Page 26
26
<DRY operation time chart>
Minimum 3 minutes w1
ON
30
Thermostat
Indoor fan
Auto vane
Drain pump
Booster heater
Compressor
ON
ON
LOW speed
Initally 30 degrees discharge
(
Changeable by remote controller setting
)
LOW speed
ON
ON
OFF
OFF
discharge position
3 minutes
OFF
OFF
OFF
OFF
Operation starts by POWER button ON.
Operation stops by POWER button OFF.
Room temperature becomes equal to set temperature.
Room temperature rises above set temperature.
30
discharge position
w1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period has ended.
2-2 DRY operation
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2The compressor runs when the room temperature is higher than the set temperature.
The compressor stops when the room temperature is equal to or lower than the set temperature.
3The compressor stops in check mode or during protective functions.
FILTER
CHECK MODE
TEST RUN
240KA
<How to operate>
1 Press POWER ON/OFF button.
2 Press the button to display “ ”
3 Press the TEMP button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is pressed one time.
Heat 19 to 30°C
Page 27
Dry mode
EXTRA-LOW speed
LOW speed
Fan operationIndoor coil temperature
Below -10°C
-10 to 0°C Above 0°C
27
4The compressor will not start when the room temperature is below 18°C.
The compressor starts intermittent operation when the power is turned ON with room temperature above 18°C. The compressor ON/OFF time depends on the thermostat ON/OFF and the following room temperatures.After 3-minute compressor operation,
If the room temperature thermistor reads above 28°C with thermostat ON, the compressor will operate for 6 more
minutes and then stop for 3 minutes.
If the room temperature thermistor reads 26°C~28°C with thermostat ON, the compressor will operate for 4 more
minutes and then stop for 3 minutes.
If the room themperature thermistor reads 24°C~26°C with thermostat ON, the compressor will operate for 2 more
minutes and then stop for 3 minutes.
If the room temperature thermistor reads below 24°C with thermostat ON, the compressor will stop for 3 minutes.
If the thermostat is OFF regardless of room temperature, the compressor will stop for 10 minutes.
5Coil frost protection
Coil frost protection in DRY operation is the same as in COOL operation.
6Coil frost prevention
Coil frost prevention does not operate in DRY operation.
(2) Indoor fan control
The indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote controller. Also, the indoor fan does not run during compressor OFF. (a)During compressor OFF
When the indoor coil temperature is 6°C or above, the indoor fan will stop.
When the indoor coil temperature is below 6°C, the indoor fan will run in DRY mode.
(b)During compressor ON
The indoor fan runs on EXTRA-LOW speed for the first 1 minute after the compressor is turned on.
After, the indoor fan runs in DRY mode.
<Dry mode>
The fan notch is controlled by the indoor coil temperature every 30 seconds.
During compressor OFF, when the indoor coil temperature becomes 6°C or above, the indoor fan turns OFF immediately.
(3) Auto vane & drain pump controls
Same as in COOL operation
(4) Detecting abnormalities in the outdoor unit
An abnormality in the outdoor unit can not be detected in DRY operation.
Page 28
28
2-3 HEAT operation
Depends on remote controller setting
Depends on remote controller setting
Horizontal Horizontal
Minimum 3 minutes w 2
ON
Thermostat
Indoor fan
Auto vane
Drain pump
Booster heater
Compressor
Power ON lamp
STAND BY lamp
ON
ON
LOW or HIGH
Extra LOW w1 LOW
LOW or HIGH
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
Hot adjustrment Hot adjustrment
OFF
OFF
ON
OFF
ON
OFF
Operation starts by POWER button ON.
Operation stops by POWER button OFF.
Room temperature becomes equal to set temperature.
Room temperature rises above set temperature.
Extra LOW w1
1 Changeable by indoor dipswitch SW1-7 and SW1-8.
OFF---during thermostat OFF
hot adjustment defrosting
From POWER ON until
warm begins to blow
w2 Even if the room temperature falls below the set temperature during this period, the compressor will not start until this period has ended.
<HEAT operation time chart>
FILTER
CHECK MODE
TEST RUN
240KA
<How to operate>
1 Press POWER ON/OFF button. 2 Press the button to display “ ”
3 Press the TEMP button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is pressed one time.
Heat 17 to 28°C
<Display in HEAT operation>
[DEFROST]
The [DEFROST] symbol is displayed during the defrost operation.
[STAND BY]
The [STAND BY] symbol is displayed from the time the heating operation starts until the heated air begins to blow.
Page 29
29
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2The compressor runs when the room temperature is lower than the set temperature.
The compressor stops when the room temperature is equal to or higher than the set temperature.
3The compressor stops in check mode or during protective functions. 4Overheat protection
<Start condition>
When the indoor coil thermistor reads 70°C or above, the overheat protection will start.
<Overheat protection>
The compressor stops for 6 minutes, and then restarts. If the start condition is satisfied again within 10 minutes of compressor operation, both the indoor and outdoor units stop, displaying a check code of “P6” on the remote controller.
<Termination conditions>
Overheat protection is terminated when the start condition is not satisfied again during the allowance (10-minute compressor operation), when operation mode changes to other mode, or when thermostat turns OFF.
(2) Indoor fan control
(a) Normal control
( i )The indoor fan runs on EXTRA-LOW speed during the thermostat OFF.
EXTRA-LOW speed can be changed to LOW or HIGH speed by setting the dipswitch SW1-7 and SW1-8, If the indoor coil temperature becomes more than 5 degrees below the room temperature during the thermostat OFF, the indoor fan will stop. After, when the indoor coil temperature becomes within 5 degrees of room temperature, the indoor fan will run on EXTRA-LOW speed.
( ii )Hot adjustment
Hot adjustment is a warm-up for HEAT operation <Start conditions> The hot adjustment works under any of the follwing conditions.
HEAT operation starts.
Defrosting ends.
Thermostat turns ON.
<Hot adjustment> Initially, the indoor fan runs on EXTRA-LOW speed. When 5 minutes have passed or the indoor coil temperature exceeds 35°C, the fan speed changes to LOW. Two minutes later, the hot adjustment ends. Then, the fan speed
depends on the remote controller setting. (iii)The indoor fan stops when the indoor coil temperature is within 5 degrees either way of room temperature. (iv)To eliminate the remaining heat, the indoor fan runs for the first 1 minute after the booster heater is turned OFF.
(3) Auto vane control
(a) STOP mode (fixed operation)
( i ) The airflow direction at the start-up of HEAT operation is the same as that of the previous operation. ( ii ) The airflow direction can be charged by the remote controller setting.
In the following cases, air flow direction becomes 30° regardless of the remote controller setting.
1 During the hot adjustment with fan speed at EXTRA-LOW 2 During defrosting within door fan OFF 3 During the thermostat OFF
(b) SWING mode
( i ) The vane motor turns ON when the SWING mode is selected.
The vane motor is continuously ON during SWING mode.
( ii ) In the following cases, the air flow direction is 30 regardless of the remote controller setting.
1 During the hot adjustment with fan speed at EXTRA-LOW 2 During defrosting with indoor fan OFF 3 During thermostat OFF
30°
45° 55°
70°
SWING
(SW5-3 : OFF/ON)
Page 30
30
Indoor coil temperature minus room temperature
+5
0
-5
RANGE A
RANGE B
RANGE C
(degree)
Fig.1
(4) Booster heater control
When the room temperature is 3 degrees below the set temperature, the booster heater will turn ON. When the room temperature is equal to the set temperature, booster heater will turn OFF. During the hot adjustment, the booster heater will not work.
<Overheat prevention>
When the indoor coil thermistor rises to 60°C or above, the booster heater cannot work. When the indoor coil thermistor falls to 55°C or below, the booster heater can work.
(5) Detecting abnormalities in the outdoor unit
When the outdoor unit is determined to be abnormal by the following causes, the compressor will stop and the check code “ P8 ” will appear on the remote controller display.
1 During compressor ON after hot adjustment W1 (See the next page.)
1 If the difference between the indoor coil temperature and room temperature is in the RANGE B, the indoor fan will
stop. 2 Within 20 minutes after entering RANGE B (except for the first 10 seconds), a) If the temperature difference enters RANGE A, the hot adjustment stasrts, b) If the temperature difference is still in RANGE B, the outdoor unit is deemed abnormal. c) If the temperature difference enters RANGE C, defrosting starts.
Within 20 minutes after entering RANGE C,
If the temperature difference does not return to RANGE B,the outdoor unit is deemed abnormal.
If the temperature difference returns to RANGE B, the next 20 minutes is an allowance period. If the difference enter
RANGE A during the allowance, defrosting ends and the hot adjustment starts. If the difference does not enter RANGE A during the allowance, the outdoor unit is deemed abnormal.
2 During compressor ON in hot adjustment
After 30 minutes of defrosting in hot adjustment, if the temperature difference is still in RANGE C, the outdoor unit is determined to be abnormal.
3 During compressor OFF
After 20 minutes of thermostat OFF, if the indoor coil thermistor reads -25°C or below, the outdoor unit is determined to be abnormal.
(6) Indoor coil thermistor abnormality detection
An abnormality can be detected during compressor ON, except for the following.
For the first 30 minutes after the temperature difference between the indoor coil temperature and room temperature enters the RANGE C.(See the below figure 1.)
When the temperature difference enters the RANGE C until it moves to the RANGE B.
(7) Defrosting operation
After the outdoor unit starts the defrosting operation, when the temperature difference beetween the indoor coil temperature and room temperature gets out of RANGE A and into RANGE B, the indoor unit starts the defrosting mode. After the outdoor unit stops the defrosting operation, when the temperature difference returns to the RANGE A, the indoor unit stops the defrosting mode. While the indoor unit is in the defrosting mode, the indoor fan and the booster heater stop.
w1 RANGE A : Indoor coil temperature is more than 5 degrees above room temperataure.
RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature. RANGE C : Indoor coil temperature is more than 5 degrees below room temperature
Page 31
31
2-4 AUTO operation (Automatic COOL/HEAT change over operation)
(1) Initial mode
1 When AUTO operation starts after unit OFF.
If the room temperature is higher than the set temperature, operation starts in COOL mode.
If the room temperature is equal to or lower than the set temperature, operation starts HEAT mode.
2 When AUTO operation starts after COOL or HEAT operation, the previous mode continues.
(2) Mode change
1 HEAT mode changes to cool mode when 15 minutes have passed since the room temperature became 2 degrees
above the set temperature.
2 COOL mode changes to HEAT mode when 15 minutes have passed since the room temperature became 2 degrees
below the set temperature.
(3) Temperature range
AUTO operation is available under the outside air temperatures as follows.
1Mode change (HEAT COOL)
When room temperature becomes2degrees above the set temperature, the operation mode can not be changed for 15 minutes.
(degree)
To +2
To:Set temperature (19 28 )
To +1
To
To - 1
To - 2
Compressor
Start
HEAT mode HEAT mode
2Mode change
15 minutes
Minimum 3 minutes
15 minutes
Minimum 3 minutes
COOL mode
(COOL HEAT)
ON OFF
-9 0 1020304046
-8.5
Cooling range
(Outside air temperature)
Heating range
-5
FILTER
CHECK MODE
TEST RUN
240KA
<How to operate>
1 Press POWER ON/OFF button.
2
Press the button to display “
3
Press the TEMP button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is pressed one time.
Automatic 19 to 28°C
“AUTOMATIC” works to change by itself the operation mode either to cooling or heating according to the room temparature.
Page 32
32
<How to operate>
To change the air flow direction, press button.
NOTE: Airfiow direction can be set by the indoor dipswitch SW5-1.
(1) COOL/DRY operation
At the start-up of COOL or DRY operation, the air flow direction in automatically set to 30°. After, it can be changed to another direction with button on the remote controller.
<Auto return>
When 55° or 70° airflow is set with fan speed in LOW, “AUTO RETURN” appears below the room temperature display. One hour later the direction changes to 30° degrees, automatically and “AUTO RETURN” disappears.
(2) HEAT operation
At the start-up of HEAT operation, air flow direction depends on the setting of the last operation. After, it can be changed to another direction with button. The airflow direction shifts to 30° regardless of the remote
controller settings under any of the following conditions.
Thermostat OFF
Defrosting
Indoor fan speed EXTRA-LOW in hot adjustment
Available in COOL operation with fan speed on HIGH or in HEAT operation. Unavailable in DRY operation. If fan speed changes from LOW to HIGH during 45° downward discharge in COOL mode, the direction automatically changes to 30°.
30$
1
45$
2
55$
3
60$
4
swing
5
2-5 Auto vane control
FILTER
CHECK MODE
TEST RUN
240KA
Changes by pressing the button.
Page 33
33
<Timer function>
AUTO STOP ·········The air conditioner stops after the set time lapses. AUTO START ········The air conditioner starts after the set time lapses. TIMER OFF ··········Timer is not active.
<How to operate>
1. Press POWER ON/OFF button.
2. Press “ ” button to select AUTO STOP or AUTO START.
3. Press “ ” button to set desired time. Time setting is in 1 hour units for up to 24 hours.
Each time HOURS button is pressed, set time increases by 1 hour. When HOURS button is pressed and held, the set time increases by 1 hour every 0.5 seconds.
4. To cancel the timer operation, press POWER ON/OFF button.
2-7 Test run <Before test run>
After installing, wiring, and piping the indoor and outdoor units, check for refrigerant leakage, looseness in power supply or contorol wiring, and mistaken polarity.
Use a 500-volt megger to check the resistance between the power supply terminal block and ground to make sure that it is at least 1.0M1.
Attention: Do not use the air conditioner if resistance is less than 1.0M1.
This setting will stop the air conditioner in 8 hours. With the lapse of time, time display changes in 1 hour units, showing remaining time.
<Timer setting example>
2-6 TIMER operation
OFF
TEST RUN button
TEST RUN
Indoor coil temperature code
Display
Display
FILTER
CHECK MODE
TEST RUN
240KA
Remote controller
1
Turn on main switch.12 hours before proceeding to step 2 to allow
for crankcase heater operation.
2
Push the TEST RUN button twice and indication of TEST RUN will
be shown on the liquid crystal display.
4
Push button LOW/HIGH to check that the fan speed changes
properly.
6
After the check is finished leave the test run mode,push the power
ON/OFF button.
It can also be stopped by pushing the timer MODE button.
5
Check the operation of outdoor unit fans.This unit controls the
rotation speed and performance capacity of fans.ln some cases,it may rotate at low speed as the condition of outside air requires and the speed will be kept unless the performance has become deficient.
Therefore,when the condition of outside air demands,there may be
such cases as the fan stops or rotates reversely.
Please note that these symptoms are not mulfunction.
3
Press the button to display ,COOL/DRY(or HEAT)to
confirm that cool (or warm)air is blown out.
(At heating operation,there may be a short delay before warm air
begins to blow out.)
*The above figure shows the state of TEST RUN at cooling operation.
When a TEST RUN is started,the timer shall be set to 2 hours. The unit will automatically turn off after 2 hours.
FILTER
CHECK MODE
TEST RUN
240KA
Page 34
34
(1) Indoor coil temperature code
During the test run, the indoor coil temperature code from 1 to 15 is displayed on the remote controller instead of room temperature. The code should fall with the lapse of time in normal COOL operation, and should rise in normal HEAT operation.
(2) Trouble during test run
If the unit malfunctions during the test run, refer to section 10 in this manual entitled “TROUBLESHOOTING.”
When the optional program timer is connected to the conditioner, refer to its operating instructions.
2-8 Emergency operation
When the remote controller or microprocessor malfunctions but all other parts are normal, emergency operation is started by setting the dipswitch SW3 on the indoor controller board.
<Before emergency operation>
1. Make sure the compressor and the indoor fan are operating normally.
2. Locate the defect with the self-diagnostic function. When the self-diagnostic function indicates “protective function is working”, release the protective function before starting the emergency operation. CAUTION: When the self-diagnostic function indicates a check code of “P5” (drain pump malfunction), DO NOT start
the emergency operation because the drain may overflow.
<How to operate>
1. For emergency cooling, set the dipswitch SW3-1 to ON and SW3-2 to OFF. For emergency heating, set the dipswitch SW3-1,2 to ON.
6
~30$C
14
~90$C
7
~35$C
15
Thermistor
abnormality
8
~40$C
4
~20$C
12
~60$C
5
~25$C
13
~70$C
3
~15$C
11
~55$C
Indoor coil
temperature
Code
Indoor coil
temperature
1
-40~1$C 9
~45$C
2
~10$C
10
~50$C
Code
2. Turn ON the outdoor unit breaker and then ON the indoor unit breaker. Emergency operation will now start.
3. During emergency operation, the indoor fan operates on high speed, but the swing louvers and the auto vanes do not operate.
4. To stop emergency operation, turn OFF the indoor unit breaker.
NOTE: The remote controller POWER ON/OFF button can not start/stop emergency operations.
CAUTION: Do not use emergency cooling for more than 10 hours, as the indoor coil may freeze.
1 ON
1
2
1.2 ON
1
2
1.2 OFF
1
2
Emergency cooling
Emergency heating
Normal operation
Microcessor board
Page 35
35
2-9 Interlock with ventilation system (LOSSNAY)
Mr. SLIM/LOSSNAY interlock operation is available by using the optional parts listed below.
(1) System organization
NOTE: For further information, refer to the
LOSSNAY technical & service manual.
(2) LOSSNAY models connectable to Mr. SLIM are : LGH-15RS-E, LGH-50RS-E
LGH-25RS-E, LGH-80RS-E LGH-35RS-E, LGH-100RS-E
(3) Reqired parts are:
Relay box (PZ-12RB-E)…Contact capacity 10A
Remote display adapter (PAC-SA88HA-E)…An optional part for Mr. SLIM
LOSSNAY control switch (PZ-05SLB
2-E)
For LOSSNAY individual operation
(4) Operation
1LOSSNAY turns ON/OFF according to Mr. SLIM ON/OFF 2While Mr. SLIM is OFF, LOSSNAY individual operation is available by using the LOSSNAY control switch.
When Mr. SLIM turns OFF with the LOSSNAY control switch at ON, LOSSNAY will continue to operate.
(5) Wiring.
Relay box
Relay box (PZ-12RB-E)
LOSSNAY
LOSSNAY
LOSSNAY control switch (PZ-05SLB
2-E) LOSSNAY control switch
(PZ-05SLB
2-E)
Mr. SLIM
Mr. SLIM
Remote controller
Remote controller
Remote display adapter (PAC-SA88HA-E)
Power supply
Power supply
2When the LOSSNAY control switch is not used:1When the LOSSNAY control switch is used
Remote controller
Insulation is needed
10m
Connecting wire
2
0.13mm or over
Connecting wire solid wire,
1.6 or 2.0 (field supplied)
Circuit breaker (field supplied)
L
Power supply
N
50Hz 220 240V
N L
PL N
HIGH
LOSSNAY control switch (PZ-05SLB
LOW
DAMPER
2-E)
Mr. SLIM
Indoor controller
board
Connector
CN51
GRN
ORN
YLW
RED
BRN
Power supply for Mr. SLIM 220 240V AC
Relay box
(PZ-12RB-E)
YLW
A
ORN
B
RED
L
WHT
N
RED
HIGH
N
WHT
LOSSNAY
Terminal block
8
7
4
6 2
5
3
1
ORN
LOW
RED
HIGH
WHT
N
RED
DAMPER
ORN
DAMPER
WHT
Junction box (field supplied)
Relay box
(PZ-12RB-E)
Terminal block
A B L N HIGH N
Mr.SLIM CN51 12V DC
L
N
Power supply 220 240V AC
Circuit breaker
LOSSNAY
Terminal block
ORN
LOW
RED
HIGH
WHT
N
RED
DAMPER
ORN
DAMPER
WHT
Page 36
36
2-10 Dip switch functions
Each figure shows the initial factory setting.
1 On remote controller board
(1) SW17(Address selector)
SW17-1~6) For address setting SW17-7) When two remote controllers are used,this switch sets the controller function.
OFF:The remote controller is set as a main controller. ON:The remote controller is set as a sub controller.
SW17-8) Switch for system back-up
OFF:Without back-up ON:With back-up
(1) SW18(Function selector)
SW18-1) Switch for timer
OFF:Single day ON:timer every day
SW18-2) Switch for filter sign
OFF:filter sign adsent ON:filter sign present
SW18-3) Switch for filter sign time setting.
OFF:100Hr ON:2500Hr
SW18-4) Not yet used.
2 On indoor controller board
(1) SW1 (Mode selector)
SW1-1) Switch that changes between FAN mode and AUTO mode
OFF:Fan mode for models without heat pump ON: AUTO mode for models with heat pump
SW1-2) Switch for auto vanes
OFF:Unit without auto vanes ON: Unit with auto vanes
SW1-3) Switch for drain pump
OFF:The drain pump works in only COOL operation. ON: The drain pump works in both COOL and HEAT operation.
SW1-4) Switch to change the temperature to start coil frost prevention
OFF:–3°C(For previous special models) ON: 1°C(For all current models)
SW1-5) Switch for set temperature adjustment in HEAT mode
During HEAT operation, warm air collects near the ceiling. When the indoor unit is installed near the ceiling, the temperature read by room temperature thermistor differs from the actual living-space temperature by about 4 degrees. Therefore, the room temperature read by room temperature thermistor must be lowered by 4 degrees. OFF:4-degree adjustment ON: NO adjustment
SW1-6) Switch for fan speed during thermostat OFF in HEAT operation
OFF:EXTRA LOW ON: LOW
SW1-7) Switch for fan speed during thermostat OFF in HEAT operation
OFF:EXTRA LOW or LOW(set with SW1-6) ON: LOW or HIGH(set with remote controller)
SW1-8) Switch for detecting abnormalities in the outdoor unit abnoamality detection
OFF:When an abnormality occurs, it is detected. ON: Even if an abnormality occurs, it can not be detected.
SW1-9) Switch for auto restart function
OFF:This function does not work. ON: This function works.
1 2 3 4 5 6 7 8
ON OFF
1 2 3 4
ON OFF
1 2 3 4 5 6 7 8 9 0
ON OFF
Page 37
37
(3) SW3 (Emergency operation switch)
1 2
Normal operation
ON OFF
1 2
For emergency cooling
ON OFF
1 2
For emergency heating
ON OFF
(4) SW5 (Model selector)
(2) SW2 (Address selector)
1 2 3 4
ON OFF
SW5-1) Not for use. SW5-2) OFF:For models with heat pump
ON:For models without heat pump SW5-3) Not for use. SW5-4) This switch is unavailable for PLH-KK(H)V. Keep this switch at OFF.
(5) SW6 (Twin,Triple selector)
1 2 3 4
ON OFF
Single control Twin control Triple control SW6-1 OFF ON(Twin NO.1) ON(Triple NO.1) SW6-2 OFF ON(Twin NO.2) ON(Triple NO.2) SW6-3 OFF OFF ON(Triple NO.3) SW6-4 OFF OFF ON
(6) SW7 (Model selector)
Switch to set the output of phase-controlled indoor fan motor. Address setting is available at any time. The initial factory setting by is based on each capacity.
Service Ref.
SW7
PLH-1.6KKHB·UK PLH-2KKHB·UK
PLH-2.5KKHB·UK
1 2 3
ON OFF
1 2 3
ON OFF
(7) SWA (High seiling, noise saving selector)
High ceiling 2 High ceiling 1 Standard
(8) SWB (Air outlet number selector)
(Not used)
3-direction airflow 4-direction airflow (Standard)
(9) SWC (Option selector)
Option
Standard
When mounting the optional high efficiency filter, set this switch to “option”
SWA
4-direction airflow 3-direction airflow
Standard
2.4
2.7
High ceiling
2.7
3.0
High ceiling
3.0
3.3
Ceiling height & airflow direction
(Unit : m)
SWB
1 2 3 4 5 6
ON OFF
Used in setting the unit-address for group control. For further information,refer to page 53.
Page 38
38
PLH-1.6KKHB·UK
PLH-2KKHB·UK
PLH-2.5KKHB·UK
Voltage
[V] 220 230 240 220 230 240 220 230 240
100% rotational frequency (rpm)
50Hz
586 608 629 586 608 629 611 634 657
Service Ref.
2-11. INDOOR FAN CONTROL
(1)Fan motor max. rotational frequency for PLH-KKHB
(2)Indoor fan relay output
(a)During fan ON
The indoor fan relay turns ON. One second later, the phase control will start.
(b)During fan OFF
The phase control turns OFF. One second later, the indoor fan relay will turn OFF.
Page 39
39
3. OUTDOOR UNIT CONTROL
3-1 Outdoor fan control
The rotational frequency of outdoor fan is phase-controlled according to the outdoor coil temperature. This control allows the cooling operation even with the low outside-air temperature and the heating operation even with the high outside-air temperature.
3-2 Outdoor unit control
The outdoor unit turns ON/OFF the cooling/heating operation according to orders given from the indoor unit.
3-3 Protective functions
1 If an reversed-phase, an open phase, or an indoor controller abnormality is detected, the outdoor unit will stop operation
and the check mode will start. (For the check mode details, see page 49.)
2 If a protective function works, the compressor will stop running. Three minutes later, the compressor will restart. If the
protective function works again, the compressor will stop running and the check mode will start.
3 The protective function is memorized. 4 The memory is cleared when the [ON/OFF button on the remote controller is turned OFF. However, the check mode
display continues until the outdoor unit receives the “operation ON” command from the indoor unit.
3-4 COOL/HEAT operation time chart
10 minutes 1
ON
Thermostat
Outdoor fan
4-way valve (COOL)
4-way valve (HEAT)
Bypass valve
Compressor
Crankcase heater (with jumper wire J3)
Crankcase heater (without jumper wire J3)
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON OFF
60 minutes 60 minutes 60 minutes 60 minutes 60 minutes
3 minutes
10 minutes
3 minutes
Repeats 60-minute ON/OFF
60 minutes
60 minutes
Operation starts by POWER button ON.
Operation stops by POWER button OFF.
Room temperature becomes equal to set temperature.
Room temperature becomes different from set temperature.
w1 If compressor restarts within 10 minutes, 4-way valve remains ON.
Page 40
40
(1) Start conditions
A. When all of the following conditions are satisfied, defrosting will start. However, when the bypass valve turns OFF,
defrosting starts 10 minutes later.
(a) More than seven minutes have passed since the compressor start-up. (b) The outdoor coil thermistor reads -5°C or below. (c) The outdoor fan motor output step is 100% (d) Total time of compressor operation exceeds 30 minutes, and the outdoor coil temperature has fallen by 8 degrees or
more in comparison with that of 10 minutes after the compressor start-up.
NOTE: The outdoor coil temperature of 10 munites after the compressor start-up is memorized until the defrosting
operation has ended.
B. When all of the following conditions are satisfied, defrosting will start.
(a) ~ (c) The same as above (a) ~ (c) in item A. (d) Total time of compressor operation exceeds “defrost interval”.
Further information on the defrost interval is described in (3).
C. After the total time of compressor operation exceeds the defrost interval, the thermostat repeats ON/OFF three times.
Two minutes after the fourth “ON” of the thermostat, if the outdoor coil thermistor reads -5°C or below and the fan output output is 100%, defrosting will start.
NOTE: The count of the thermostat ON/OFF is cleared by the compressor-OFF command or defrosting start-up.
(2) During defrosting
Even if the thermostat turns OFF, defrosting continues.
The 4-way valve, bypass valve, outdoor fan, and indoor fan are OFF.
ON
Outdoor fan
Compressor
4-way valve
Bypass valve
Auto vane
Indoor fan
35degrees (SW5-3 OFF) or 20degrees (SW5-3:ON) airflow direction
(Remote controller still displays set direction.)
Outdoor unit
Indoor unit
ON
Set direction
ON
OFF
OFF
OFF
ON OFF
ON
OFF
ON
OFF
Set direction
Defrosting starts.
Defrosting stops.
3-5 Defrosting in HEAT mode <Defrosting time chart>
Page 41
41
(3) Defrost interval
The defrost interval time is determined as follows.
Initial defrost interval is 50 minutes.
The defrost interval after defrosting depends on the preceding defrosting time as shown below.
NOTE1:If the unit stops during defrosting , the next defrost interval will be 50 minutes. NOTE2:If a protection function works for the first time during defrosting, the compressor will stop.
After a 3-minute time delay, defrosting will restart. In this case, a 3-minute time delay is included with the defrosting time. If the protection function works for the second time, the unit stops operation and displays the check code. The next defrost interval will be 30 mimutes.
NOTE3:When the defrosting has ended, the total time of the compressor operation is cleard.
(4) Termination conditions
Defrosting finishes when any of the following conditions are satisfied.
1Defrosting has continued for 15 munites. 2Outdoor coil thermistor reads 22°C or above for the first 75 seconds after defrosting start-up. 3Outdoor coil thermistor reads 8°C or above after the 75-second defrosting. 4Power ON/OFF button is turned OFF during defrosting.
3-6 Actuators (1) Bypass valve control
<Cooling mode> 1When the unit stops due to the coil frost prevention, the bypass valve turns ON. When one hour ahs passed since the
compressor stopped, the bypass valve returns to OFF.
2When the compressor operates with the bypass valve at ON for more than 30 minutes, the bypass valve turns OFF. 3When the compressor stops with the bypass valve at OFF, the bypass valve turns ON and remains ON for three
minutes.
<Heating mode> 1When the unit starts for the first time after the circuit breaker has been turned ON, or when it starts after the compressor
OFF of 30 minutes or more, if the outdoor coil thermistor reads 12°C or more, the bypass valve turns ON.
2When the high pressure switch (63H1) works, the bypass valve turns ON. 3When the bypass has been ON for 30 minutes:
If the high pressure switch has already returned, the bypass valve turns to OFF.
If not, the fan output step keeps 70 for three minutes. Meanwhile, if the high pressure switch returns, the bypass valve
turns OFF. Otherwise the normal fan control starts.
4When the operation mode changes or stops, the bypass valve turns ON and remains ON for three minutes. <Defrosting operation>
1The bypass valve is OFF.
(2) Crankcase heater control
1With jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and then turns ON one hour after the compressor stops.
2Without jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and repeats 1-hour ON and 1-hour OFF.
Defrosting operation time Next defrost interval 3 minutes or below 120 minutes 3 to 7 minutes 80 minutes 7 to 10 minutes 60 minutes 10 to 15 minutes 40 minutes 15 minutes (Maximum) 30 minutes
Page 42
42
3-7 Service functions (1) Compulsory defrositng
1When all of the following conditions are satisfied, pressing SW2 starts the compulsory defrosting.
During HEAT mode
The compressor is ON.
The outdoor coil temperature is being displayed by LED. (Outdoor controller board dip switch SW3-1 : OFF, SW3-2 :
ON)
The outdoor coil thermistor reads 8°C or below.
2The operation state and the termination conditions of the compulsory defrosting are the same as those of the normal
defrosting. As an exception, the defrost interval after the defrosting completion is 50 minutes.
(2) Fixed fan-output
While the compressor is operating (exept during defrosting) and the fan output step is indicated by LED, pressing SW2 fixes the fan output. The fixed fan-output can be released when any of the following conditions are satisfied.
1SW2 is pressed again. 2SW3 setting os changed. 3The compressor stops. 4Defrosting operation starts.
(3) Function of switches on the outdoor controller board
SW1: Clears the check code memory (push-button switch) SW2: Switches the output state indication and the check code display (push-button switch) SW3-1,2: Switches the output state indication items (dip swtich) For further information, refer to page 36.
(4) 100% fan output
Fan output is fixed to 100% by shorting the connector CN22. However, the fan stops during compressor OFF or defrosting. Open-circuit of CN22 restarts the normal fan control.
(5) Time shorterning
Short circuit of the connector CN21 shortens the time as follows
1Fan control period: 30 seconds 3 seconds 2Three-minutes time delay function : 3 minites 3 seconds 3Max. time of defrosting : 15 minites 15 seconds 4Defrost interval : 30 ~ 120 minutes 3 ~ 12 seconds 5Compressor ON/OFF time for bypass valve ON/OFF : 30 minutes 3 seconds 6Compressor ON time to start other functions : x minutes x seconds 7Crankcase heater operation : 1 hour 6 seconds
Page 43
43
TROUBLESHOOTING
10
Symptom Cause Check points
The display “CENTRALLY CONTROLLED” on remote controller dose not disappear.
1) Wrong address setting of remote controller/indoor controller board.
2) Timer adapter is connected to the remote controller.
3) Singnal transmission error between indoor unit and remote controller.
1) Check the address setting of remote controller and indoor controller.
2) Make sure the timer adapter is used correctly.
3) 1 Turn another remote controller’s DIP SW17­7 ON to make it sub controller. 2 Connect the sub controller to the unit, and
turn circuit breaker ON.
If the display “centrally controlled”
disappears, replace the original remote controller.
If the display remains the same, replace the
When remote controller POWER button is turned ON, the check code “EO”appears.
1) Signal transmission error between indoor unit and remote controller
1) 1 Connect a sub remote controller. 2 Turn circuit breaker ON.
If the display “centrally controlled” remains, replace the indoor controller board.
3 If the display disappears, turn the remote
controller POWER button ON and check as follows.
When remote controller POWER button is turned ON, operating display appears, but disappears soon.
1) Short circuit of indoor/outdoor connecting wire
2) Short circuit of transmission wire.
3) Short circuit of drain sensor heater circuit.
4) Wrong operation of remote controller due to noise wave emitted by other appliances.
1), 2) Check the wire
3) Measure the resistance of the drain sensor connector CN50 1 ~ 3. Normal resistance should be 821.
4) Turn the circuit breaker OFF, and then turn ON.
If the remote controller remains abnormal, despite the above measures, replace the indoor controller board.
Despite turning POWER button ON, the remote controller display does not appear.
1) Damaged remote controller.
2) Short circuit of transmission wire.
3) Bad contact of indoor CN40.
4) CN40 is attached to a sub unit.
5) Damaged transformer.
6) Bad contact of CN4T.
7) Blown fuse.
8) Circuit breaker OFF.
1) Measure the voltage between terminals of remote controller. If no voltage, remove the terminals and measure the voltage between wires. If the voltage is between 6VDC and 12V, replace the remote controller.
2) ~ 8) Check each point.
If it is not defective, replace the indoor controller board.
1.TROUBLE IN TEST RUN
1
2
3
4
Remote controller
Operating Display
Operating Display
No Display
No Display
Sub remote controller
EO Display
Operating Display
EO Display
Operating Display
Malfunction
Malfunction of indoor Unit
Malfunction of Remote controller
Malfunction of indoor Unit and Remote Controller
Malfunction of Remote controller
Page 44
44
2. SELF DIAGNOSTIC FUNCTION WITH REMOTE CONTROLLER
2-1 When malfunction occurs during operation
When a malfunction occurs, the indoor and outdoor units stop and the malfunction is displayed on the LCD of the remote controller. (A) ON the set temperature display part, “CHECK” appears, and the unit
address and the check code are diplayed alternately at one-second intervals. (Check mode)
2-2 How to use the self diagnostic function for service A. For normal control with one unit and one remote controller
(1) Pressing the CHECK button on the remote controller twice starts the self diagnostic function. (2) During the self diagnostic function, “CHECK” appears at two positions on the remote controller display. Then, at least
10 seconds later, the unit address and the check code is alternately displayed at one-second intervals.
(3) Check and repair the unit according to the check code. (Refer to the next page.)
2-3 For group control using one remote controller
(1) Press the TEMP. or TEMP. button on the remote controller to advance or go back to the unit address.
Each time TEMP. button is pressed, the unit address advances by one. Each time TEMP. button is pressed, the unit address goes back by one. The check code and the unit address, appear alternately.
(2) The check code “U8” means no malfunction has occurred since installation.
The check code “EO” means the following conditions:
The unit address displayed on the remote controller does not apply to any unit.
Power is not supplied to the unit.
Signal transmitting/receiving circuit is abnormal.
(3) Check and repair the unit according to the check code. (Refer to the next page.)
CHECK
°C
CHECK
°C
Example
Altenately
displayed
Unit address Check code
(2) When one remote controller controls several units in the group
control, the LCD shows the unit address and check code of the first malfunctioning unit.
(3) To cancel the check mode, press the [ON/OFF button. In remote
ON/OFF control, press the remote [ON/OFF switch. In centralized control, turn OFF the [ON/OFF button of centralized controller.
NOTE: The latest check code is memorized, even if the check mode is cancelled by the way mentioned above. It takes
60 seconds maximum to display the memorized check code.
FILTER
CHECK MODE
TEST RUN
240KA
Page 45
45
Check
code
Diagnosis of malfunction Cause Check points
EO Signal transmitting/receiving
error
(Indoor controller does not
respond to remote controller signal.)
During individual unit control
1) Bad contact of transmission wire
2) Signal transmitting/receiving circuit is abnormal.
1) Check the transmission wire.
2) Check with another remote controller. If “EO” is still indicated, replace the indoor controller board. If other check code appears. replace the original remote controller.
P3 Signal transmission error
(Remote controller does not
respond to indoor controller signal.)
1) Bad contact of transmission wire
2) Signal transmitting/receiving circuit is abnormal.
3) Wrong operation due to noise wave emitted by other appliances
1) Check the transmission wire.
2) Check with another remote controller. If “P3” is still indicated, replace the indoor board. If other check code appears, replace the original remote controller.
3) Short-circuit between 1 and 2 of CN40 and attach CN40 to the following units.
Second unit in twin control
Second and third units in triple control
Sub units in group control
P4 Abnormality of drain sensor 1) Bad contact of transmission
wire
2) Damaged thermistor
1) Check the connector.
2) Measure the resistance of the thermistor 4 ~
5. As for the normal resistance, refer to the case of P1.
If the resistance is normal, replace the indoor controller board.
P5 Malfunction of drain pump 1) Malfunction of drain pump
2) Damaged drain sensor
1) Check the drain pump.
2) Check the drain sensor.
Check the drain sensor heater. Normal
resistance should be 821. If the resistance is normal, replace the indoor controller board.
P6 Coil frost protection is
working.
1) Short cycle of air cycle
2) Dirty air filter
3) Damaged fan
4) Abnormal refrigerant
1) Clear obstructions from the air cycle.
2) Clean the air filter
3) Check the fan.
4) Check the refrigerant temperature.
P7 System error 1) Wrong address-setting
2) Signal transmitting/receiving circuit of remote controller is abnormal.
3) Wrong SW6-setting
1) Check the address-setting.
2) Check with another remote controller. If check code other than “P7” appears, replace the original remote controller.
3) Check SW6 setting.
P8 Abnormality in outdoor unit 1) Wrong wiring of indoor/outdoor
connecting wire
2) Reversed phase
3) Protection device is working
4) Damaged outdoor coil thermistor
1) Check the indoor/outdoor connecting wire.
2) Change the connection of electric wiring.
3) Check the protection device.
4) Measure the resistance of the outdoor coil thermistor. If the resistance is normal, replace the outdoor controller board.
P1P2Abnormality of room
temperature thermistor (RT1)
Abnormality of indoor coil
thermistor (RT2)
1) Bad contact of thermistor
2) Damaged thermistor
1) Check the thermistor.
2) Measure the resistance of the thermistor. Normal resistance should be as follows.
0 C ···15k1 30 C·····4.3k1 10 C······9.6k1 40 C·····3.0k1 20 C······6.3k1 If the resistance is normal, replace the indoor controller board.
Page 46
46
3.SERVICE DATA INDICATION BY SWITCHES ON OUTDOOR CONTROLLER BOARD
Setting dip switchs SW2 and SW3 on the outdoor controller board enables LED to show the output state and check code. Output state is shown by LED lighting, and check code by blinking.
SW1 : Turning SW1 ON clears the check code. If SW1 is turned ON while the check code is blinking , the indication
changes to output state indication.
NOTE : SW1 is usually available independant of SW3 setting. As an exception, when the check code shows a
reversed phase or an open phase during the power-on-reset state, SW1 is not available.
SW2 : SW2 is turned ON by pressing, and OFF by releasing.
When SW3-1 and SW3-2 are OFF, pressing SW2 changes indication between output state and check code alternately. When SW2 is turned On with SW3-1 OFF and SW3-2 ON, the compulsory defrosting starts.
SW3 : Output state indication items depend on the combination of SW3-1 ON/OFF and SW3-2 ON/OFF.
Changed alternately by pressing SW2.
Lighting
Outdoor coil temperature
(bit)
OFF
ON
1
2
4
8
16
32
64
128
Fan output
step
(bit)
ON
OFF
1
2
4
8
16
32
64
128
Total time of
compressor
operation(Hr)
ON
ON
256
512
1024
2048
4096
8192
16384
32768
SW3-1
SW3-2
LED
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
Check code
OFF
OFF
Blinking
Reversed phase
Open phase
Outdoor coil thermistor is abnormal.
63H2 function
51C function
26C function
Overheat protection
Input circuit on controller board is abnormal
Output state
OFF
OFF
Compressor ON command from indoor controller
Heating operation command from indoor controller
During 63H1 function
Compressor ON
Outdoor fan ON
4-way valve ON
Bypass valve ON
Crankcase heater ON
Page 47
47
3-1 Outdoor coil temperature
To obtain data on the outdoor coil temperature, add the number of bits of lighting LEDs, and see the graph below to find the temperature.
3-2 Fan output step
To obtain data on the fan output step, add the number of bits of lighting LEDs, and see the graph below to find the fan rotational frequency.
3-3 Total time of compressor operation
Compressor operation time is indecated in 256 hour units. To obtain the compressor operation time, add the hours of lighting LEDs. During the compressor operation time indication, SW2 is not available.
3-4 Check code indication
When a protection function works for the first time during operation, the operation stops and restarts after the 3-minutes time delay mode. When the protection function works again, the operation stops. (Check mode) When both SW3-1 and SW3-2 are OFF, the check code is indicated.
If the outdoor controller board receives the compressor ON command from the indoor controller board during check mode the indication changes to output state indication.
By pressing SW2 duirng normal operation. operation will continue.
The latest check code is indicated.
50
Fan output step (bit)
Fan rotational frequency (rpm)
100 150 200 250
800
600
400
200
0
50
Fan output step (bit)
Fan rotational frequency (rpm)
100 150 200 250
800
600
400
200
0
100
C
Temperature
80
60
40
20
0
0
(Open 8 bits)(Open 8 bits)
(Short 238 bits)(Short 238 bits)
Number of bits
50 100 150 200 255
-20
-40
PUH-1.6/2KA type
<50Hz>
PUH-2.5KA type
<50Hz>
Page 48
48
Blinking
LED
Diagnosis of malfunction Cause Check point
LD1 Reversed phase Phases A1, A2, and A3are
connected improperly.
Check the power supply connection.
LD2
Open phase Phase A2is open.
Contact of protector, such as thermal switch, opened when power was turned on.
Check the power supply.
Check each protector.
LD3 Outdoor coil thermistor is
abnormal. (Open circuit or short circuit)
Outdoor coil thermistor is broken.
Thermistor was connected incorrectly.
Measure the resistance of the thermistor.
Check the thermistor. If normal, replace the
outdoor controller board.
LD4 High pressure switch (63H2)
function
62H2 was badly connected.
63H2 was working.
Check 63H2 and the outdoor fan motor.
Check if refrigerant supply is low.
Check if air cycle is short-cycled.
LD5 Thermal relay (51C) function 51C was connected
incorrectly.
51C was working.
Check 51C, the compressor, and power supply.
LD6 Thermal switch (26C) function. 26C was connected
incorrectly.
26C is working.
Check 26C.
Check if refrigerant supply is low.
Check if the capillary tube is clogged.
LD7 Over heat protection The thermistor is broken.
Coil temperature is over
67°C.
Measure the resistance of the thermistor.
Check the outdoor fan motor.
Check if air cycle is short-cycled.
LD8 Input circuit of outdoor
controller board is abnormal.
Pulse input is abnormal. Replace the outdoor controller board.
Cause
1) Indoor/outdoor connecting wires are poorly connected. (Refer to next page.)
2) Power supply is poorly connected.
3) Connector or transformer is broken.
4) Fuse (6A) in the outdoor controller board is blown.
Check points
1) Check the connecting wires.
2) Check the power supply.
3) Check connectors and transformers.
4) Check the fuse.
4. TROUBLESHOOTING ACCORDING TO CHECK CODE
5. WHEN OUTDOOR UNIT DOES NOT WORK
Page 49
49
6. WRONG WIRING ON SITE
6-1 Between remote controller and indoor unit
If the wire is disconnected between the remote controller and the indoor unit, nothing is displayed on the remote controller when the POWER button is pressed. The beep sound will also not be heard.
6-2 Phenomenon due to wrong wiring between indoor and outdoor units
Wrong wiring
Mode
Thermostat
Phenomenon
OutdoorIndoor
1 2 3
1 2 3
COOL
OFF
Operation stops.
ON
4-Way valve turns ON. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF
Cooling operation. Several minutes later, check code “P8” appears on remote controller display.
ON
Normal operation.
OutdoorIndoor
1 2 3
1 2 3
COOL
OFF
Outdoor unit stops.
ON
Operation stops. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF
Operation stops.
ON
Operation stops. 27 minutes later, check code “P8” appears on remote controller display.
OutdoorIndoor
1 2 3
1 2 3
COOL
OFF
Outdoor unit stops.
ON
Operation stops. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF
Operation stops.
ON
Operation stops. 27 minutes later, check code “P8” appears on remote controller display.
OutdoorIndoor
1 2 3
1 2 3
COOL
OFF
Outdoor unit stops.
ON
Operation stops. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF
Operation stops.
ON
Operation stops, 27 minutes later, check code “P8” appears on remote controller display.
OutdoorIndoor
1 2 3
1 2 3
COOL
OFF
Outdoor unit stops.
ON
Operation stops. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF
Operation stops.
ON
Operation stops. 27 minutes later, check “P8” appears on remote controller display.
Disconnection between 1 and 1 or 2 and 2.
COOL
OFF
Operation stops.
ON
Operation stops. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF
Operation stops. 4-way valve turns OFF.
ON
27 minutes later, check code “P8” appears on remote controller display.
Disconnection between 3 and 3.
COOL
Normal operation.
HEAT
OFF
Operation stops. 4-way valve turns ON.
ON
Operation stops. 27 minutes later check code “P8” appears on remote controller display.
Page 50
50
LOSSNAY control switch does not work.
LOSSNAY control switch can not work during interlock
operation.
LOSSNAY control switch is effective only while Mr. SLIM is not
operating.
Symptom
LOSSNAY air speed can not be controlled in interlock operation.
LOSSNAY fan speed is fixed to HIGH during interlock
operation.
LOSSNAY fan speed LOW/HIGH can be switched only during
LOSSNAY individual operation with the LOSSNAY contorl switch.
Cause
For LOSSNAY, troubleshooting refer to the LOSSNAY technical & service manual.
8.MR. SLIM/LOSSNAY INTERLOCK OPERATION
<Symptoms that are not malfunctions>
If any of the following symptoms occur, they are not malfunctions.
Vanes do not work.
Vane motor does not work. Limit swtich does not work. Connector is poorly connected. Vane motor is poorly assembled. Indoor controller board is damaged.
Unit stops after 5 to 20 seconds operation
Protection function is working.
Air discharge display is OFF and button
does not operate.
Indoor controller board deems the auto vanes are not attached to the unit. Horizontal anlgle can not be detected.
In this case, remote controller is normal.
Power ON/OFF button is not available.
Beep sound is heard, but display is turned OFF.
Beep sound is not heard, and display remains OFF.
Indoor/outdoor connecting wire is connected incorrectly. Indoor/outdoor connecting wire shorts. Compressor protector is damaged. Deicer is broken.
Remote controller is damaged. Transmission wire is poorly connected
Transmission wire is damaged. Connector is poorly connected. Indoor terminal block is poorly connected. Remote controller terminal block is poorly connected.
Vane motor is damaged. Vane motor relay is damaged.
Limit switch is damaged. The size of the cam is wrong.
Refer to check code on remote controller display. See page 45.
Indoor controller is
damaged.
Dip switch setting is
wrong.
Indoor controller is
damaged.
Vane motor is
damaged.
Vane motor limit switch
is poorly connected.
Auto vane is wired after
power is turned to ON.
Vane motor limit switch is damaged. Vane motor is damaged.
Poorly connected Disconnected
7. OTHER TROUBLES AND CAUSES
“CENTRALLY CONTROLLED” is displayed.
Page 51
51
4-WAY AIR FLOW SYSTEM11
1.Placement of the air outlets
For this grill, the air flow direction comes in 5 patterns. Also, by setting the dipswitches (SWA and SWB)on the indoor board to the appropriate settings, you can adjust the air flow and speed. Select the settings that are needed from those in Tables 2 and 3 according to the place where you want to install the unit.
1) Decide on the pattern of the airflow direction.
4-direction 3-direction
Airflow direction
pattern
Pattern 1 Pattern 4
Factory setting
One air outlet fully closed
2) According to the number of air outlets and the height of the ceiling to install the unit, be sure to set the dip switches (SWA, SWB, SWC) on the indoor board to the appropriate setting.
Correspondence of ceiling heights to numbers of air outlets.
<Initial setting by factory> SWA : for ceiling height SWB : for number of air outlets SWC : optional filter element
3···High ceiling 2···(Unavailable) STD···Without filter element 2···Standard 3···3 directions OP···With filter element 1···Silent 4···4 directions
<Table 1>
<Table 2>
1
Silent
4-directional
2.4m
2.7m 3.0m
3-directional 2.7m 3.0m 3.3m
2 Standard 3 High ceiling
SWB
SWA
Note 1. For the 3-direction air flow, install the air
outlet shutter plate(PAC-SF38SP-E)
Note 2. The 2-direction airflow is unavailable.
2.Installing the outlet shutter plate (PAC-SF38SP-E)
For the 3-direction air flow, close one air outlet fully by installing the air outlet shutter plate before installing the grill. <Caution> Installing the shutter plate not securely will cause air leak and water dripping.
<How to attach the shutter plate> Peel off the separation sheet from the shutter plate, and attach the shutter plate to the air outlet of the indoor unit.
Indoor unit
Page 52
52
12
SYSTEM CONTROL
1 Group control with
a single remote controller (See page 53.)
Unit
Remote controller
Unit Unit
Many units, installed at different locations, can be started
and controlled with a aingle remote controller. The remote controller can be mounted in a different location using a non-polar two-wire cable, which can be extended up to 500m. A maximum of 50 units can be controlled with a single remote controller. All units operate in the same mode.
2 Both remote
ON/OFF and individual controls (See page 54.)
w Timer adapter
(PAC-SA89TA-E) is needed.
Optional adapter
Remote ON/OFF switch
Remote controller
Relay box
Unit
All units can be turned on or off simultaneously using a
remote ON-OFF switch. Also, each unit can be controlled individually by each remote controller. Duning remote ON-OFF control, a message of “CENTRALLY CONTROLLED” is displayed on the LCD of the remote controller.
This is available for both one unit control and several units
control.
3 Individual control
by grouping remote controllers (See page 55.)
Unit
Remote controller
Unit Unit
By grouping the remote controllers in one place, several
units installed at different locations can be controlled individually, and operation conditions of all units are visible without a special control board. The control method is the same as that of the single unit with a single remote controller.
4 Multiple remote
control display (See page 55.)
w Multiple display
adapter (PAC-SA88HA-E) is needed.
Unit
Remote controll display board
Remote controller
Unit Unit
Several units can be controlled with a remote control
display board. Operation conditions of all the units are visible with the remote control display board.
Individual control by each remote controller is also
possible.
5 Auto restart
function (See page 56.)
Circuit breaker
Remote controller
A unit can be started or stopped with the circuit breaker
on or off. Remote controller is also available. With this function, when the power is restored aftar power
failure, the unit will restart automatically. (However, when
the remote controller POWER ON/OFF button is OFF, the
unit will not start.)
1. VARIETY OF SYSTEM CONTROL FUNCTIONS
Page 53
53
2. GROUP CONTROL WITH A SINGLE REMOTE CONTROLLER
A maximum of 50 units can be started in order according to the dip switch settings
2-1 How to wire
(1) Connect the remote controller to the double terminal block
on the indoor controller board of the master unit (No.0 unit). (See Figure 1.)
(2) Connect the double terminal block of the master unit to the
double terminal block of No.1 unit.
(3) Connect the double terminal block of No.1 unit to the
double terminal block of No.2 unit.
(4) Continue the process until all the units are connected with
two-wire cables. (See Figure 2.)
(5) Remove the connector CN40 from the indoor controller
board of each unit except the master unit. (See Figure 3.)
(6) Set the unit-address of esch unit with SW2 on the indoor
controller board following the instructions below.
2-2 How to set unit-address
The unit-address also serves as a successive-start timer which starts each unit at intervals of 1 second. If two or more units have the same unit-address in a group control, operation stops due to system error. Be sure to set SW2 correctly following the instructions below. (1) Each lever of SW2 shows the number as follows.
SW2-1 : 1 SW2-4 : 8 SW2-2 : 2 SW2-5 : 16 SW2-3 : 4 SW2-6 : 32
(2) Total number of levers turned to ON shows the address of
the unit. For example, to set No.3 unit, turn ON SW2-1 and SW2-2.
(3) In this way, set from the. master unit to the last unit.
Do not forget to set the master (No. 0) unit.
2-3 Unit control
The remote controller can control all units ON/OFF, temperature,air flow, and swing louver. However, the thermostat in each unit turns ON or OFF individually to adijust to the room temperature.
Unit address & start delay in seconds.
SW2
Master (No. 0) unit
0
1
2
3
4
5
6
ALL OFF
No. 1 unit
1
1
2
3
4
5
6
1 ON
No. 2 unit
2
1
2
3
4
5
6
2 ON
No. 4 unit
4
1
2
3
4
5
6
3 ON
No. 8 unit
8
1
2
3
4
5
6
4 ON
No. 16 unit
16
1
2
3
4
5
6
5 ON
No. 32 unit
32
1
2
3
4
5
6
6 ON
Setting examples
To remote controller
To next unit
To next unit
The last unit does not have this wire.
Next unit electrical box
Master unit electrical box
123ANE
123ANE
Master unit
No.1 unit No.2 unit Last unit
2-wire cable
Figure 2
Figure 3
Indoor controller board
Should be removed from all units other than unit 0: (Master Unit)
Figure 1
Page 54
54
NOTE1 : Install the relay box where you can be serviced it easily. NOTE2 : For control circuit wiring, use a wire of No. 14 AWG or a control cable according to the power supply of control
circuit.
NOTE3 : When the power supply of the control circuit is 220/240V AC,
Do not connect the control circuit wire to the remote controller cable directly.
Do not place the control circuit wire and the remote controller cable into the same conduit tube.
3-2 Basic wiring
Caution : Before starting all units simultaneously by the remote ON-OFF switch, be sure to connect a sequence-start timer
into the remote ON-OFF circuit. Otherwise, a rush of starting current may damage the power supply.
w1After all units start together, if SW2 is turned OFF, each unit can be individually stopped by each remote controller. w2After all units stop together, if SW2 is turned OFF, each unit can be individually started by each remote controller.
3-3 Switch function of remote ON-OFF switch
SW1 (Switches between
remote ON and OFF.)
ON
(Start)
OFF
(Stop)
All units start together. Individual control is not available.
All units start together. Individual control is not available.
SW2
(Switches between remote ON-OFF and individual control)
ON
(Remote ON-OFF control)
Each unit can be controlled by each remote controller. Remote ON-OFF switch is not available.
OFF
(Individual control)
w1
w2
Power supply
Remote ON/OFF switch
No.1 unit relay box
No.2 unit relay box
Next unit
T
X2 X2
T
Glow switch or pilot lamp can be combined to easily identify the on-off mode of SW1 and SW2.
To No.1 unit
To No.2 unit
Timer adapter cables
Remote controller
T
X2
SW
1
SW2
T
X2
3. REMOTE ON-OFF AND INDIVIDUAL REMOTE CONTROLS
This method is available to control one unit or any number of units. The following operations are available by connecting a relay, a timer adapter (PAC-SA89TA-E), and a remote ON/OFF switch to the system. Timer adapter is an optional part. Other parts are available on the market. (A) To start all units in order by remote ON-OFF switch (B) To stop all units simultaneously by remote ON-OFF switch (C) To switch between the remote ON-OFF control and the individual remote control
3-1 System
Figure 6 shows the case of three units.The same is the case with any number of units.
Remote controller
power supply of control circuit
Remote ON/OFF
switch
2-wire remote controller cable
Figure 6
Relay box
Timer adapter cables
Timer adapter PAC-SA89TA-E
Page 55
55
4. INDIVIDUAL CONTROL BY GROUPING THE REMOTE CONTROLLERS
Grouping the remote controllers allows individual control and centralized monitoring of units installed in different places without a special control board.
Remote control cables are extendable up to 500m. When the cable length exceeds 12m, use the double-insulated two-care cable such as Belden 9407. Also, the cable thickness must be No. 22 AWG or above.
When gathering the power ON/OFF switches of air conditioners near the remote controllers, you should also install the power ON/OFF switch near each unit to prevent electric trouble during servicing.
Remote controller cable (2-core)
Remote controller
5. MULTIPLE REMOTE CONTROL DISPLAY
You can control serveral units with a multiple remote control display, by wiring an optional multipe display adapter (PAC-SA88HA-E) with relays and lamps on the market.
5-1 How to wire
(1) Connect the multipe display adapter to the connector CN51 on the
indoor controller board.
(2) Wire three of the five wires from the multiple display adapter as shown
in the figure below.
[Notes on Signs] X1:Relay (for check lamp) X2:Relay (for operation lamp) RL:Check Lamp GL:Operation Lamp [Field supplied parts] Relays:12V DC with rated coil power
consumption below 0.9W.
Lamps:Matching to power supply voltage.
CN51
connector(5P)
GREEN
Power supply
Electrical insulation is needed.
Wiring at the actual place
Optional multiple display adapter
The maximum distance between indoor board and relay is 10m.
YELLOW ORANGE
RED
BROWN
5
X1
X1
RL
GL
X2
X2
1
<Wiring >
Power supply
Remote controller cable
Relay box (Field supply)
Remote controller
Remote controller
Remote controller
3wires 3wires 3wires
2wires
No.1 unit No.2 unit No.3 unit
Muitiple remote control ON-OFF display (Field supply)
(Operation check)
<System>
Power supply
RL-1 GL-1
Multiple Remote Control Display
Multiple remote controller adapter
connect to the connector CN51
Relay box
5
X1-1
X2-1
1
<Wiring diagram>
RL-2 GL-2
RL-3
No.1 unit
GL-3
X1
X2
5
1
No.2 unit
X1
X2
5
1
No.3 unit
X1
X2
X1-2
X2-2
X1-3
X2-3
Indoor controller board
Page 56
56
6. AUTO RESTART FUNCTION
By setting the dipswitch SW1-10 to ON, the air conditioner can be started/stopped by power supply ON/OFF. If the air conditioner is OFF before the power failure, it will not start operation by power restore.
Remote controller
A B
Brown
Red
Orange
Remote controller
A B
Brown
Red
Orange
A : an optional timer adapter B : a single-throw switch
For remote control, connect the optional timer adapter (PAC-SA89TA-E)
<Wiring>
Page 57
57
DISASSEMBLY PROCEDURE13
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
1. Removing the air intake grill
(1) Press the button. (2) Open the intake grill 90°. (3) Remove the chip. (4) Slide the shaft in the hinge to the left and remove the
intake grill.
PUSH
4. Removing the fan motor
(1) Remove the fan guard. (2) Remove the turbo-fan nut and radiator aluminum cap. (3) Pull out the turbo fan. (4) Disconnect the connector of the fan motor lead wire. (5) Remove the 3nuts of fan motor.
3. Removing the electrical parts box
(1) Remove the fan grand. (2) Disconnect the lead wire of the vane motor from the clamp,
and disconnect the red connector (8P). (3) Remove 2 of 4 screws from the electorical parts cover. (4) Remove the electorical parts cover. (5) Disconnect the following connectors from the box.
Red (3P) for the fan motor White (2P) for the indoor coil thermistor Blue (2P) for the drain pump White (4P) for the drain sensor
(6) Disconnect the green anti-falling wire of the electrical parts
box. (7) Remove 3 of 4 screws from the electrical parts box, and
loosen the other screw. (8) Pull out the electrical parts box.
Electrical parts inside the box
Terminal block
Transfomer
Indoor fan capacitor
Room temperature thermistor
Indoor controller board
2. Removing the fan guard.
(1) Open the intake grill. (2) Remove the 4 screws of the fan guard.
1. INDOOR UNIT
Be careful on removing heavy parts.
Photo 1
Photo 2
Photo 3
Figure 1
Photo 4
nut
Fan motorConnector
Fan guard screw
Lead wire for vane motor
ConnectorTerminal blockAnti-falling wire
Radiator aluminum cap
Capacitor
Nut
Screws
Box cover
Clamp
Fan guard
Electrical box
Connerctor
Room temperature thermistor
Screws Transformer
Indoor controller board
PUSH button
Shaft
Intake grill
Page 58
58
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
5. Removing the room temperature thermistor
(1) Remove the fan guard. (2) Remove the electrical box cover (3) Remove the holder and the room temperature thermistor
by pulling the catch.
(4) Disconnect the red connector, CN20, on the indoor
controller board.
6. Removing the indoor coil thermistor
(1) Remove the fan guard. (2) Remove the electrical box cover. (3) Remove the electrical box. (4) Remove the turbo fan. (5) Remove the screw of the service panel. (6) Remove the service panel. (7) Remove the indoor coil thermistor from the holder
attached to the copper pipe.
(8) Disconnect the 2-pin white connector.
7. Removing the panel
(1) Open the intake grill. (2) Disconnect the connector the vane motor. (3) Remove 4 screws of the panel. (4) Pulling the temporary handing hook, remove the panel.
8. Removing the drain pan
(1) Remove the panel. (2) Remove the fan guard. (3) Remove the rubber bushing. (4) Drain the remaining water in the drain pan. (5) Remove the electrical box cover. (6) Remove the electrical box. (7) Refmove the screw of the V.A. cover, and remove the V.A.
cover.
(8) Remove each screw of the corner supports 1,2, and 3,
and remove the corner supports 1,2 and 3.
(9) Pull out the drain pan.
wPull the left and right of the pan gradually.
Be careful not to crack or damage the pan.
Photo 8
Photo 7
Photo 6
Photo 5
Indoor controller board
Room temparature thermistor
Mounting hole
Indoor coil thermistor
Corner support 1
Corner support 3
VA cover
Rubber bush
Corner support 2
Screws
screws
screws
Panel
Fan guard
Temporary hanging hook
Temporary hanging hook
Page 59
59
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
9. Removing the drain pump and drain sensor
(1) Remove the panel. (2) Remove the fan guard. (3) Remove the electrical parts cover. (4) Remove the electrical parts box. (5) Remove the drain pan. (6) Remove 4 screws of the drain pump. (7) Pulling the clip of the drain hose, pull out the drain hose
from the drain pump. (8) Remove the drain senser and the holder. (9) Pull out the drain pump.
10. Removing the heater
(for the only PLH-1.6/2/2.5KKHB) (1) Remove the panel. (2) Remove the fan guard. (3) Remove the electrical parts cover. (4) Remove the electrical parts box. (5) Remove the drain pan. (6) Remove the turbo fan. (7) Remove the 5 screws of the hearter assembly. (8) Remove the clamp (1 screw) securing the lead wire. (9) Pull the heater assembly out.
11. Removing the heat exchanger
(1) Remove the panel. (2) Remove the fan guard. (3) Remove the electrical parts cover. (4) Remove the electrical parts box. (5) Remove the drain pan. (6) Remove the turbo fan. (7) Remove the screw of the coil support A. (8) Remove 2 screws of the coil support B. (9) Remove 2 screws of the coil.
(10) Remove 4 screws of the piping cover of the outer wall,
and pull out the piping cover.
Photo 9
Photo 10
Drain hose
Drain pump
Heater screws
Drain sensor
holder
Screws
Clip
Photo 11
Photo 12
Lead wire clamp
Heat exchanger
Heater assembly
Coil support B
Coil support A
Coil screws
Screws of piping cover
Piping cover
Page 60
60
14
PARTS LIST
1 2 3 4 5 6 7
T7W 560 003 R01 29H 500 R01 29H 691 R01 29H 061
— T7W 14K 200 T7W 556 305
AIR OUTLET GRILLE AIR FILTER INTAKE GRILLE HINGE GRILLE HANGER REMOTE CONTROLLER REMOTE CONTROLLER CABLE
12m
1 1 1 2 1 1 1
(BG88H096H01)
R.B
Unit
Amount
Recom­mended
Q’ty
Part No. Part Name
Specification
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
No.
Price
Q’ty/set
PLH-
1.6/2/2.5
KKHB.UK
PANEL PARTS PLH-1.6KKHB·UK PLH-2KKHB·UK PLH-2.5KKHB·UK
7
6
1
2
3
4
5
Page 61
61
PANEL PARTS PLH-1.6KKHB·UK PLH-2KKHB·UK PLH-2.5KKHB·UK
1
4
1
5
1
2
7
6
7
8
9
7
7
10
7
1
3
4
4
Part No. Part Name
No.
1
R01 29H 002
2
R01 29H 085
3
R01 29H 223
4
R01 29H 063
5
T7W 33K 063
6
R01 29H 056
7
R01 29H 047
8
T7W 560 258
9
R01 29H 040
10
R01 29H 041
AUTO VANE AIR GUIDE VANE MOTOR SPRING JOINT 1 SPRING JOINT PUSH BUTTON VANE SUPPORT CORD HEATER GRILLE GEAR (RIGHT) GRILLE GEAR (LEFT)
Specification
240V 28.2W
Q’ty/set
1.6/2/2.5
PLH-
KKHB.UK
4 1 1 1 1 1 8 1 1 1
Remarks
<3/SET>
Wiring
Diagram
Symbol
MV
H1
Recom­mended
Q’ty
Unit
Price
Amount
Page 62
62
FUNCTIONAL PARTS PLH-1.6KKHB·UK PLH-2KKHB·UK PLH-2.5KKHB·UK
37
11
12
13
21
22
23
20
24
32
34
33
36
31
35
30
29
28
23
18
17
16
27
15
25
26
19
14
10
9
8
5
4
3
2
7
6
3
1
2
39
Page 63
63
Part numbers that are cicled are not shown in the figure.
No.
Part No. Part Name
1 2 3 4 5 6 7
8
9 10 11 12 13 14 15
16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39
— —
— T7W E00 762 R01 29H 105
— R01 41N 114 S70 A00 300 S70 A01 300 R01 32K 706 R01 046 700 R01 08K 202 R01 29H 523 T7W 55K 355 R01 W28 226 R01 W28 527 T7W 580 480 R01 38H 480 R01 41H 480 S70 A00 529
— T7W 521 716 T7W 517 716 T7W 515 716 R01 29H 255
— T7W 58K 310 T7W 520 239 T7W 580 799 R01 J07 202
— R01 71G 215 S70 A00 675 R01 08K 097 R01 A48 524 R01 005 533
BASE LEG LEG FAN MOTOR MOTOR MOUNT INNER COVER TURBO FAN HEATER ELEMENT HEATER ELEMENT THERMAL FUSE THERMAL SWITCH INDOOR COIL THERMISTOR DRAIN SOCKET DRAIN PUMP DRAIN SENSOR DRAIN HOSE HEAT EXCHANGER HEAT EXCHANGER HEAT EXCHANGER DRAIN PAN CORNER SUPPORT (1) CORNER SUPPORT (2) CORNER SUPPORT (2) CORNER SUPPORT (3) LEAD WIRE COVER PANEL HOOK TERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK FAN MOTOR CAPACITOR CONTROLLER CASE INDOOR CONTROLLER BOARD FUSE TRANSFORMER ROOM TEMPERATURE THERMISTOR BELL MOUTH ELECTRICAL PARTS COVER RELAY FAN GUARD SPL WASHER DRAIN PLUG SENSOR HOLDER
Specification
467W 240V 700W 240V 77$C 250V 10A OFF42$C ON32$C
3P (L,N,;) 3P (1,2,3) 2P (1,2)
2.5+F 400V
250V 6.3A
LY2F DC12V
Q’ty/set
PLH-1.6
KKHB.UK 1 2 2 1 3 1 1 3
2 1 1 1 1 1 1 1
1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
PLH-2
1 2 2 1 3 1 1 3
2 1 1 1 1 1 1
1
1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
PLH-2.5
(Drawing No.)
1
(BG00T765G01)
2
(BG00K209G01)
2
(BG00K209G02) 1 3 1
(BG00T770G01) 1
3 2 1 1 1 1 1 1
1 1 1
(BG00K210G01) 1
(BG00K211G01) 1
(BG00K212G01) 1
(BG00T856G01) 1
(BG00T861G01) 2
(BG17H174H02) 1 1 1 1 1
(BG25J542H04) 1 1 1 1 1
(BG00L601G21) 1
(BG00A662G17) 1 1 1 1 1
Remarks
Wiring
Diagram
Symbol
MF1
H1
H1 FS1 26H RT2
DP DS
TB2 TB4 TB5
C1
I.B
F1(I.B)
T
RT1
88H
Recom­mended
Q’ty
Unit
Price
Amount
Page 64
64
15
OPTIONAL PARTS
Note 1. How to connect refrigerant pipes.
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as the connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow. If piping length exceeds 5m, an additional charge of refrigerant in needed.
Note 2. The following main parts are cntained in the optional refrigerant piping kit.
Heat insulating cover, vinyl tapes, nipples, sleeve and flange (for wall hole), connecting cables.
2-2 Feature of program timer
(1) Daily timer function
Daily timer can be set in 30 minutes units for up to 24 hours. Each unit can be set for unit ON, unit OFF, or setback operation.
(2) Setback operation (PAC-SK65PT)
Set back operation is useful for reducing running costs e.g. At a hotel with a 24-hour system
8:00~23:00 Cooling operation with set temperature at 26°C
23:00~8:00 Setback operation with 2 degrees of setback As shown in the chart on the right, the set temperature rises 2 degrees automatically during the setback operation. When the setback operation ends, normal operation will begin.
(3) Weekly timer function
Daily timer function can apply to each day of the week.
1. REFRIGERANT PIPES
Service Ref. : PLH-1.6KKHB.UK/PLH-2KKHB.UK/PLH-2.5KKHB.UK
Indoor unit: Flared Outdoor unit: Flared
Liquid:{9.52 Gas:{15.88
PAC-05FFS
5m
PAC-07FFS
7m
PAC-10FFS
10m
PAC-15FFS
15mPipe length Pipe size O.D. Connection method
Part No.
2. TIMER
Product Name
PAC-SC32PT (with set back function)
Program timer
Part No.
2-1 Program timer specifications
Parts No. Exterior dimensions (inch) Installation Type of clock Clock accuracy Display-Time
-Week
-Timer setting unit Program cycle Timer setting unit No. of set points Power rating
Program timer PAC-SC32PTA 5-4/32x4-23/32x23/32 (130x120x18mm) Wall mount Quartz (50 second / month at 25$C Liquid crystal display Liquid crystal display Liquid crystal display 24 hours 30 minutes 48 / day 5V DC (5% (Supplyed by Remote Controller)
Parts name
28˚C
26
˚C
8:00
Normal
operation
23:00
Setback
operation
8:00
Normal
operation
Page 65
65
2-3. How to connect program timer
(1) Install the program timer next to the remote controller the same way as the remote controller is installed. (2) Connect the program timer and the remote controller with a 6-wire cable as shown in the figure below
3. TIMER ADAPTER
This adapter is needed for system control and for operation via extemal contacts. Adapter connection is described on page
54.
2-4. Names and functions
<PAC-SC32PT>
NOTE:While the program timer is connected to the remote controller, the
24hour ON/OFF timer on the remote controller will not operate.
Part No. PAC-SA89TA-E
WEEKLY TIMER SETTING DISPLAY
Used for selection of if or not the day operation pattern set by PATTERN SETTING is to be applied in weekly day unit, setting.
SET/MONITOR
SET
SMTWT F S
MONITOR
PROERAN TIMER
PAC-SC32PTA
TODAY
ON
WEEKLY SETTING
OFF
ON
SET BACK
OFF
CLOCK DAILY TIMER
SET BACK
SET BACK
DAILY
SETTING
12 15 18 21 24
0361215
CURRENT TIME DISPLAY
During MONITOR status,current time is display. During Daily timer setting, a time desire for timer setting is displayed.
SET BACK DISPLAY
Indicates the setting set back range.
DAILY TIMER SETTING DISPLAY
24 hours is divided into 48 blocks and each block express 30 minutes. The block display consists of 3 pattern.
“MONITOR” :Indicates the current timer
setting. All switch expect MODE SELECTOR SW are invalidated then.This is the normal status.
“SET”: Set to “SET” mode for clock
adjustment, charge of week day, daily and weekly timer setting.
Push SW to advance the time. Each time the button is
pushed the time advance by 1 minute, pushing continuously advances by 1 minute at 0.5 second interval, and when the lower digit of minute decomes 0 indication advances in 10 minutes unit.
SW is used for reversing the time. Each time the button is pushed the time reverses by 1 minute, pushing continuously reverses the time by 1 minute at 0.5 second interval, and when the lower digit of minute decomes 0 indication reverses in 10 minutes unit.
Pushing SW moves the week day light display in order of S M → T → W
enabling to set the week day.
SET BACK SETTING SW
Used for set back setting.
SET/MONITOR DISPLAY
During SET is display, clock adjustment, change of weekly day, daily and weekly timer setting can be performed. During MONITOR is display, all switches except SET/MONITOR SW are invalidated. This is normal status.
WEEK DAY SETTING SW
Used for week day setting.
MODE SELECTOR SW
Using this switch select “MONITOR” or “SET” Mode.
CLOCK ADJUSTMENT SW
Used for adjustment of the current time.
WEEKLY TIMER SW
Used for setting timer in day of week unit.
Set back can be done in the range of 1,2,4,6 and 8°C.
ON/SET BACK/OFF SW
Used to specify the time setting pattern.
DAILY TIMER SW
Used for timer setting in 30 minutes unit.
2-wire cable
4
Connector CN1 Connector CN1
To indoor unit
FILTER
CHECK MODE
TEST RUN
6-wire cable
SET MONITOR
SET/MONITOR
PROERAN TIMER PAC-SC32PTA
SMTWTF S
WEEKLY
TODAY
SET BACK
SETTING
ON
CLOCK DAILY TIMER
OFF
SET BACK
0361215
12 15 18 21 24
ON
SET BACK
OFF
DAILY
SETTING
ORN 1 BRN
RED
2 3
Page 66
66
1 2 3 4 5
BRN RED ORN YLW GRN
BACK
ACTIVE BYPASS
POWER ON/OFF
DUAL
CENTRAL
AHEAD
MITSUBISHI ELECTRIC
ENGAGED
GROUP
ACTIVE BYPASS
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
DUAL CENTRAL
12345678910
117
117
BACK
ACTIVE BYPASS
POWER ON/OFF
DUAL
CENTRAL
AHEAD
ENGAGED
GROUP
ACTIVE BYPASS
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
DUAL CENTRAL
12345678910
113
113
12
10 9 8 7 6 5 4 3 2 1
56.5
11
23.5
8
BACK
ACTIVE
BYPASS
POWER ON/OFF
DUAL
CENTRAL
AHEAD
MITSUBISHI ELECTRIC
ENGAGED
GROUP
ACTIVE BYPASS
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
DUAL CENTRAL
12345678910
4. MULTIPLE REMOTE CONTROLLER ADAPTER
This adapter is needed for remote indication (operation/check).
5. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units. When using the PAC-805RC, the program timer adapter (PAC­825AD)is also needed. See page 68.
Part No. PAC-SA88HA-E
Part No. PAC-805RC
5-1. Dimensions Unit : mm
5-2. Functions
"ENGAGED" indicator When this indicator is lit, transmission is in progress and all switches are inoperative.
DUAL/CENTRAL switch This change-over switch governing the
operation of the accessory remote controller.
"DUAL" Instructions from both the accessory remote controller and the centralized remote controller are valid. (Priority given to the last instruction received.)
"CENTRAL" ON/OFF switching by the accessory remote controller is invalidated. Control is by the centralized remote controller only. Initial setting is "DUAL".
LCD Matrix Display This display indicates the operational status of all connected units either by steady lighting or by flashing.
POWER ON/OFF switch Operation ON/OFF switch.
BACK AHEAD buttons These buttons are used to designate the attached unit(s). (They designate the unit to be centrally controlled.)
When group “00” is designated; collective ON/OFF instruction is sent to all units.
When group “01”-“16“ is designated; ON/OFF instruction is sent to the designated units only.
ACTIVE/BYPASS switch This is a change-over switch for the program timer. (It selects timer operation on the program timer.) Use “BYPASS” when a program timer is not connected. “ACTIVE” The switch tums ON/OFF operational instructions from the program timer automatically. “BYPASS” ON/OFF Operation is by the centralized remote controller only. Initial setting is “BYPASS”.
Independent “DUAL / CENTRAL” and “ACTIVE / BYPASS” setting of all the groups is possible. When the power supply to the centralized remote controller is cut due to power failure, all settings will return to original “DUAL” and “BYPASS”.
Page 67
67
5-3 Connection method
(1) Connections in the power supply cord.
1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-wrap. Connect a single phase 200V AV (220, 230, 240V) to AN.
As E is the GND terminal, be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap. Use a {1.6 (AWG 14) or above two-wire cable for the transmission line.
CAUTION : Never connect the power supply cord to the transmission terminal-block.
(2) Connection method of centralized remote controller and power supply board.
1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable.
2. Wiring diagram 3. Be sure to set the maximum address number with the
dipswitch SW17 on the centralized remote controller.
TERMINAL-BLOCK FOR TRANSMISSION
TERMINAL-BLOCK OF POWER SUPPLY
Transmission
Tie-wrap
TRANSFORMER
ANE
Fuse(5A)
Tie-wrap
(W) (R) (O)
(BR)
200
220
230
T
(Y)
240
5A
A
N
E
Wiring has to be changed when a 200,230 or 240V power is used.
To adaptor's terminal-block
Power supply board box
POWER SUPPLY
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
BACK
ACTIVE BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER ON/OFF
AHEAD
To adaptor's
Non-polar, two-wire cable
terminal-block
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
Centralized remote controller
BACK
ACTIVE BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER ON/OFF
AHEAD
Dip switch SW17
Centralized remote controller
Power supply board
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
Page 68
68
6. PROGRAM TIMER ADAPTER
This adapter is needed when a centralized remote controller(PAC-805RC)is used.
6-2 Connection method
Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out the work.
6-1 Parts included
Part No. PAC-825AD
(2) When the centralized remote controller is used, set the address number with the dipswitch SW1 of the
program timer adapter.
1 ADAPTER ·························1P 2 3-core cable ···························1P
4 4-core cable···························1P
Length : 2m (6' 7")
3 3-core cable···························1P
Length : 2m (6' 7")
5 5-core cable···························1P
Length : 2m (6' 7")
(1) Connections in the adapter box
1. Connect the power supply cord to the terminal-block and fix it in-place with a tie-wrap. Connect a single phase 200V (220, 230, 240V) AC to . As is the GND terminal, be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap (when a centralized remote controller is being used). CAUTION : Never connect the power supply cord to the transmission terminal-block
E
A N
Length : 2m (6' 7")
Fig-1 Fig-2
TERMINAL-BLOCK FOR TRANSMISSION
Tie-wrap
Transmission cord
CN22
Dip switch
TRANS
CN1 CN21 CN51 CN30CN42 CN50 CN40
Fuse(5A)
TRANSFORMER
(AG)
SW1
ANE
POWER SUPPLY CORD
TERMINAL-BLOCK FOR POWER SUPPLY
Tie-wrap
Terminal block for transmission to program timer or centralized remote controller
Wiring has to be changed when 200V power supply is used.
(W)
CN22
TRANS
(B)
200
SW1
T
(Y)
240
220
5A
A N E
POWER SUPPLY
Page 69
69
(3) Connections from adaptor
6-3 Dimecsions
Fig.3
To program timer or centralized remote controller
Adaptor
CN30 CN50
200~240V AC
Fig. 4
35
3-core cable 5-core cable
CN51
Remote controller Indoor unit
Max. length of each calbe is 10m.
(Unit : mm)
40 80 40 27
220
4Fixing screw holes
95
5.5
22
12
2 2holes 2.9
74 7
30
8
120
200
18
86 70
22
3holes
27
65
15
52
hole
230
15 15
35
Page 70
70
Part No. PAC-SE01AS-E
Applied Service Ref. PLH-1.6KKHB.UK/PLH-2KKHB.UK/PLH-2.5KKHB.UK
7. SPACE PANEL
Part No. PAC-SE06WP-E
Applied Service Ref. PLH-1.6KKHB.UK/PLH-2KKHB.UK/PLH-2.5KKHB.UK
8. WIDE PANEL
Part No. PAC-SF38SP-E
Applied Service Ref. PLH-1.6KKHB.UK/PLH-2KKHB.UK/PLH-2.5KKHB.UK
9. AIR OUTLET SHUTTER PLATE
750
Hole
16
R7.8
R26
750
R
26
R7.8
965
Hole
965
R25
R37
R
6
R31
R25
R37
R
6
R31
R18047.5
R18102.5
13
99
42
65
122
440
Page 71
71
Part No. PAC-SE21TM-E
Applied Service Ref. PLH-1.6KKHB.UK/PLH-2KKHB.UK/PLH-2.5KKHB.UK
10. MULTI-FUNCTIONAL CASEMENT
Part No. PAC-SE13KF-E
Applied Service Ref. PLH-1.6KKHB.UK/PLH-2KKHB.UK/PLH-2.5KKHB.UK
11. HIGH-EFICIENCY FILTER ELEMENT
Parts included :
Casement
Screw with
washer
Duct flange
Tapping
screw
Hook Band
1 pc 4 pcs
M5✕0.8✕15
1 pc 6 pcs
410
2 pcs 1 pc
Page 72
Issued in Jun. 1997 No. OC147 560
New publication, effective Jun. 1997 Specifications subject to change without notice
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100 TELEX J24532 CABLE MELCO TOKYO
CCopyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD.
Loading...