Mitsubishi PLA-RP_AA PLH-P_AAH, PMH-P_BA, PEAD-RP_EA PEHD-P_EAH, PEAD-RP_GA, PKA-RP_GAL PKH-P_GALH TECHNICAL MANUAL

...
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS
July 2005
No. OCS02
TECHNICAL DATA BOOK
<Indoor unit> [Model names]
<Outdoor unit> [Model names]
PLA-RP·AA PLH-P·AAH PMH-P·BA PEAD-RP·EA PEHD-P·EAH PEAD-RP·GA PKA-RP·GAL PKH-P·GALH PKA-RP·FAL PKH-P·FALH PCA-RP·GA PCH-P·GAH PCA-RP·HA PSA-RP·GA PSH-P·GAH
PUH-P25/35/50/60/71/100VGAA
R407C
PUH-P35/50/60/71/100/125/140YGAA PU-P35/50/60/71/100VGAA PU-P35/50/60/71/100/125/140YGAA
CONTENTS
1. REFERENCE SERVICE MANUAL·············································2
2. SPECIFICATIONS ······································································3
3. OUTLINES AND DIMENSIONS················································36
4. WIRING DIAGRAM···································································58
5. REFRIGERANT SYSTEM DIAGRAM ······································70
6. PERFORMANCE CURVES······················································73
7. CORRECTION FACTORS························································75
9. NOISE CRITERION CURVES ··················································91
10. OPTIONAL PARTS ··································································105
kW Model
1-1. INDOOR UNIT
Model name Service Ref. Service
Manual No. PLA-RP35/50/60/71AA PLA-RP35/50/60/71AA.UK OC335 PLA-RP100/125/140AA PLA-RP100/125/140AA.UK PLH-P35/50/60/71AAH PLH-P35/50/60/71AAH.UK PLH-P100/125/140AAH PLH-P100/125/140AAH.UK PMH-P25/35/50BA PMH-P25/35/50BA OC333
PCA-RP50/60/71/100/125/140GA PCA-RP50/60/71/100/125/140GA OC328 PCH-P50/60/71/100/125/140GAH PCH-P50/60/71/100/125/140GAH PCA-RP71/125HA PCA-RP71/125HA OC329
PKA-RP35/50GAL PKA-RP35/50GAL OC330 PKH-P35/50GALH PKH-P35/50GALH PKA-RP60/71/100FAL PKA-RP60/71/100FAL OC331 PKH-P60/71/100FALH PKH-P60/71/100FALH PSA-RP71/100/125/140GA PSA-RP71/100/125/140GA OC332 PSH-P71/100/125/140GAH PSH-P71/100/125/140GAH PEAD-RP35/50/60/71EA PEAD-RP35/50/60/71EA.UK ­PEAD-RP100/125/140EA PEAD-RP100/125/140EA.UK PEHD-P35/50/60/71EAH PEHD-P35/50/60/71EAH.UK ­PEHD-P100/125/140EAH PEHD-P100/125/140EAH.UK PEAD-RP60/71/100GA PEAD-RP60/71/100GA.UK -
1-2. OUTDOOR UNIT
Model name Service Ref. Service
Manual No. PUH-P25/35/50/60/71/100VGAA PUH-P25/35/50/60/71/100VGAA.UK OC336 PUH-P35/50/60/71YGAA PUH-P35/50/60/71YGAA.UK PUH-P100/125/140YGAA PUH-P100/125/140YGAA.UK
PU-P35/50/60/71/100VGAA PU-P35/50/60/71/100VGAA.UK PU-P35/50/60/71YGAA PU-P35/50/60/71YGAA.UK PU-P100/125/140YGAA PU-P100/125/140YGAA.UK
1
REFERENCE SERVICE MANUAL
For information on service refer to the service manual as follows.
2
2
2-1. CEILING CASSETTE TYPE
2-1-1.HEAT PUMP (without HEATER) AND COOLING ONLY TYPE
Model name Indoor unit PLA-RP35AA PLA-RP50AA
Outdoor unit H/P PUH-P35VGAA PUH-P35YGAA PUH-P50VGAA PUH-P50YGAA
C/O PU-P35VGAA PU-P35YGAA PU-P50VGAA PU-P50YGAA
Cooling Capacity Btu/h 15,400 19,100
kW 4.5 5.6 Total input kW 1.72 2.53 EER 2.62 2.21 Energy label class D F SHF 0.75 0.82
Heating * Capacity Btu/h 16,900 21,700
kW 4.95 6.35 Total input kW 1.70 2.20 COP 2.91 2.89 Energy label class D D Booster heater kW - -
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 16 16 25 16
Indoor unit Air flow CMM 11-12-13-14 14-15-16-18
(Low-Medium2-Medium1-High)
CFM 390-425-460-495 495-530-565-635 External pressure Pa 0 0 Sound level dB(A) 27-28-29-31 28-29-31-33 (Low-Medium2-Medium1-High) External finish (Panel) White Munsell 0.70Y 8.59/0.97 Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 258 (30)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8) H : inch 10-3/16 (1-3/16)
Weight kg 24 (5)
Unit (Panel) lbs 53 (11)
Unit drain pipe I.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 45 55
CFM 1,590 1,940 Sound level at cooling dB(A) 47 48 Sound level at heating * dB(A) 49 50 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 650 855
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 25-5/8 33-5/8
Weight kg 54 74
lbs 119 163 Refrigerant pipe Gas side O.D. mm 15.88 size inch 5/8
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 40 length Length m Max. 40
* HEAT PUMP TYPE
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
SPECIFICATIONS
3
Model name Indoor unit PLA-RP60AA PLA-RP71AA
Outdoor unit H/P PUH-P60VGAA PUH-P60YGAA PUH-P71VGAA PUH-P71YGAA
C/O PU-P60VGAA PU-P60YGAA PU-P71VGAA PU-P71YGAA
Cooling Capacity Btu/h 22,900 26,300
kW 6.7 7.7 Total input kW 2.57 3.42 EER 2.61 2.25 Energy label class D F SHF 0.72 0.74
Heating * Capacity Btu/h 24,900 31,400
kW 7.3 9.2 Total input kW 2.40 3.48 COP 3.04 2.64 Energy label class D E Booster heater kW
-
--
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 25 16 32 16
Indoor unit Air flow CMM 14-15-16-18 15-16-18-20
(Low-Medium2-Medium1-High)
CFM 495-530-565-635 530-565-635-705 External pressure Pa 0 0 Sound level dB(A) 28-29-31-33 28-30-32-34 (Low-Medium2-Medium1-High) External finish (Panel) White Munsell 0.70Y 8.59/0.97 Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 258 (30)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8) H : inch 10-3/16 (1-3/16)
Weight kg 24 (5)
Unit (Panel) lbs 53 (11)
Unit drain pipe I.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 50
CFM 1,770 Sound level at cooling dB(A) 48 49 Sound level at heating* dB(A) 50 51 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 855
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 33-5/8
Weight kg 79
lbs 174 Refrigerant pipe Gas side O.D. mm 15.88 size inch 5/8
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 50 length Length m Max. 50
* HEAT PUMP TYPE
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
4
Model name Indoor unit PLA-RP100AA PLA-RP125AA PLA-RP140AA
Outdoor unit H/P PUH-P100VGAA PUH-P100YGAA PUH-P125YGAA PUH-P140YGAA
C/O PU-P100VGAA PU-P100YGAA PU-P125YGAA PU-P140YGAA
Cooling Capacity Btu/h 32,800 45,400 48,500
kW 9.6 13.3 14.2 Total input kW 3.68 5.09 5.90 EER 2.61 2.61 2.41 Energy label class D D E SHF 0.78 0.72 0.69
Heating * Capacity Btu/h 35,800 53,200 58,000
kW 10.5 15.6 17.0 Total input kW 3.91 5.54 6.35 COP 2.69 2.82 2.68 Energy label class E D E Booster heater kW - - -
Power supply Phase [ 13 3
Cycle Hz 50 50 50 Voltage V 230 400 400 Breaker size A 32 16 25
Indoor unit Air flow CMM 20-23-26-28 22-25-28-30
(Low-Medium2-Medium1-High)
CFM 705-810-920-990 775-880-990-1060 External pressure Pa 0 Sound level dB(A) 33-36-39-41 37-40-43-45 (Low-Medium2-Medium1-High) External finish (Panel) White Munsell 0.70Y 8.59/0.97 Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 298 (30)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8) H : inch 11-3/4 (1-3/16)
Weight kg 30 (5) 32(5)
Unit (Panel) lbs 66 (11) 71(11)
Unit drain pipe I.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 85 95 100
CFM 3,000 3,360 3,530 Sound level at cooling dB(A) 51 55 57 Sound level at heating* dB(A) 53 56 58 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900 1050
D : mm 330+20 H : mm 1260
W : inch 35-7/16 41-5/16
D : inch 13 + 3/4 H : inch 49-5/8
Weight kg 97 125
lbs 214 276 Refrigerant pipe Gas side O.D. mm 19.05 size inch 3/4
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 50 length Length m Max. 50
* HEAT PUMP TYPE
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
5
2-1-2.HEAT PUMP (with HEATER) TYPE
Model name Indoor unit PLH-P35AAH PLH-P50AAH
Outdoor unit PUH-P35VGAA PUH-P35YGAA PUH-P50VGAA PUH-P50YGAA
Cooling Capacity Btu/h 15,400 19,100
kW 4.5 5.6 Total input kW 1.72 2.53 EER 2.62 2.21 Energy label class D F SHF 0.75 0.82
Heating Capacity Btu/h 16,900 21,700
kW 4.95 6.35 Total input kW 1.70 2.20 COP 2.91 2.89 Energy label class D D Booster heater kW 1.29 1.29
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 16 16 25 16
Power supply Phase [ 1 for heater Cycle Hz 50
Voltage V 230 Breaker size A 16
Indoor unit Air flow CMM 11-12-13-14 14-15-16-18
(Low-Medium2-Medium1-High)
CFM 390-425-460-495 495-530-565-635 External pressure Pa 0 0 Sound level dB(A) 27-28-29-31 28-29-31-33 (Low-Medium2-Medium1-High) External finish (Panel) White Munsell 0.70Y 8.59/0.97 Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 258 (30)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8) H : inch 10-3/16 (1-3/16)
Weight kg 26(5)
Unit (Panel) lbs 57 (11)
Unit drain pipe I.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 45 55
CFM 1,590 1,940 Sound level at cooling dB(A) 47 48 Sound level at heating dB(A) 49 50 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 650 855
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 25-5/8 33-5/8
Weight kg 54 74
lbs 119 163 Refrigerant pipe Gas side O.D. mm 15.88 size inch 5/8
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 40 length Length m Max. 40
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
6
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
Model name Indoor unit PLH-P60AAH PLH-P71AAH
Outdoor unit PUH-P60VGAA PUH-P60YGAA PUH-P71VGAA PUH-P71YGAA
Cooling Capacity Btu/h 22,900 26,300
kW 6.7 7.7 Total input kW 2.57 3.42 EER 2.61 2.25 Energy label class D F SHF 0.72 0.74
Heating Capacity Btu/h 24,900 31,400
kW 7.3 9.2 Total input kW 2.40 3.48 COP 3.04 2.64 Energy label class D E Booster heater kW 1.93 1.93
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 25 16 32 16
Power supply Phase [ 1 for heater Cycle Hz 50
Voltage V 230 Breaker size A 16
Indoor unit Air flow CMM 14-15-16-18 15-16-18-20
(Low-Medium2-Medium1-High)
CFM 495-530-565-635 530-565-635-705 External pressure Pa 0 0 Sound level dB(A) 28-29-31-33 28-30-32-34 (Low-Medium2-Medium1-High) External finish (Panel) White Munsell 0.70Y 8.59/0.97 Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 258 (30)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8) H : inch 10-3/16 (1-3/16)
Weight kg 26(5)
Unit (Panel) lbs 57 (11)
Unit drain pipe I.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 50
CFM 1,770 Sound level at cooling dB(A) 48 49 Sound level at heating dB(A) 50 51 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 855
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 33-5/8
Weight kg 79
lbs 174 Refrigerant pipe Gas side O.D. mm 15.88 size inch 5/8
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 50 length Length m Max. 50
7
Model name Indoor unit PLH-P100AAH PLH-P125AAH PLH-P140AAH
Outdoor unit PUH-P100VGAA PUH-P100YGAA PUH-P125YGAA PUH-P140YGAA
Cooling Capacity Btu/h 32,800 45,400 48,500
kW 9.6 13.3 14.2 Total input kW 3.68 5.09 5.90 EER 2.61 2.61 2.41 Energy label class D D E SHF 0.78 0.72 0.69
Heating Capacity Btu/h 35,800 53,200 58,000
kW 10.5 15.6 17.0 Total input kW 3.91 5.54 6.35 COP 2.69 2.82 2.68 Energy label class E D E Booster heater kW 2.39 2.76 2.76
Power supply Phase [ 13 3
Cycle Hz 50 50 50 Voltage V 230 400 400 Breaker size A 32 16 25
Power supply Phase [ 1 for heater Cycle Hz 50
Voltage V 230 Breaker size A 16
Indoor unit Air flow CMM 20-23-26-28 22-25-28-30
(Low-Medium2-Medium1-High)
CFM 705-810-920-990 775-880-990-1060 External pressure Pa 0 Sound level dB(A) 33-36-39-41 37-40-43-45 (Low-Medium2-Medium1-High) External finish (Panel) White Munsell 0.70Y 8.59/0.97 Dimension W : mm 840 (950)
Unit (Panel) D : mm 840 (950)
H : mm 298 (30)
W : inch 33-1/16 (37-3/8)
D : inch 33-1/16 (37-3/8) H : inch 11-3/4 (1-3/16)
Weight kg 32 (5) 34(5)
Unit (Panel) lbs 71 (11) 75(11)
Unit drain pipe I.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 85 95 100
CFM 3,000 3,360 3,530 Sound level at cooling dB(A) 51 55 57 Sound level at heating dB(A) 53 56 58 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900 1050
D : mm 330+20 H : mm 1260
W : inch 35-7/16 41-5/16
D : inch 13 + 3/4 H : inch 49-5/8
Weight kg 97 125
lbs 214 276 Refrigerant pipe Gas side O.D. mm 19.05 size inch 3/4
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 50 length Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
8
2-1-3.HEAT PUMP (without HEATER) TYPE (PMH series)
Model name Indoor unit PMH-P25BA PMH-P35BA
Outdoor unit PUH-P25VGAA PUH-P35VGAA PUH-P35YGAA
Cooling Capacity Btu/h 10,600 14,800
kW 3.1 4.35 Total input kW 1.14 1.66 EER 2.72 2.62 Energy label class D D SHF 0.77 0.70
Heating Capacity Btu/h 11,400 16,900
kW 3.35 4.95 Total input kW 1.05 1.64 COP 3.19 3.02 Energy label class D D Booster heater kW - -
Power supply Phase [ 13
Cycle Hz 50 50 Voltage V 230 400 Breaker size A 16 16
Indoor unit Air flow CMM 6.3-6.8-7.6-8.4 7-8-9-10
(Low-Medium2-Medium1-High)
CFM 220-240-270-300 250-280-320-350 External pressure Pa 0 Sound level dB(A) 29-31-33-35 34-36-38-40 (Low-Medium2-Medium1-High) External finish (Panel) White Munsell 0.98Y 8.99/0.63 Dimension W : mm 854(1000)
Unit (Panel) D : mm 395(470)
H : mm 230(30) W : inch 33-5/8(39-3/8) D : inch 15-9/16(18-1/2) H : inch 9-1/16(1-3/16)
Weight kg 14(3)
Unit (Panel) lbs 31(6.6)
Unit drain pipe I.D. mm 26
inch 1
Outdoor unit Air flow CMM 45
CFM 1,590 Sound level at cooling dB(A) 47 Sound level at heating dB(A) 49 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20
H : mm 650 W : inch 35-7/16 D : inch 13 + 3/4 H : inch 25-5/8
Weight kg 50 54
lbs 110 119 Refrigerant pipe Gas side O.D. mm 12.7 15.88 size inch 1/2 5/8
Liquid side O.D. mm 6.35 9.52
inch 1/4 3/8 Refrigerant pipe Height difference m Max. 30 Max. 40 length Length m Max. 30 Max. 40
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
9
Model name Indoor unit PMH-P50BA
Outdoor unit PUH-P50VGAA PUH-P50YGAA
Cooling Capacity Btu/h 18,300
kW 5.35 Total input kW 2.31 EER 2.32 Energy label class F SHF 0.67
Heating Capacity Btu/h 21,200
kW 6.2 Total input kW 2.37 COP 2.62 Energy label class E Booster heater kW -
Power supply Phase [ 13
Cycle Hz 50 50 Voltage V 230 400 Breaker size A 25 16
Indoor unit Air flow CMM 8-9-10-11
(Low-Medium2-Medium1-High)
CFM 282-318-353-388 External pressure Pa 0 Sound level dB(A) 36-38-40-42 (Low-Medium2-Medium1-High) External finish (Panel) White Munsell 0.98Y 8.99/0.63 Dimension W : mm 854(1000)
Unit (Panel) D : mm 395(470)
H : mm 230(30)
W : inch 33-5/8(39-3/8)
D : inch 15-9/16(18-1/2) H : inch 9-1/16(1-3/16)
Weight kg 14(3)
Unit (Panel) lbs 31(6.6)
Unit drain pipe I.D. mm 26
inch 1
Outdoor unit Air flow CMM 55
CFM 1,940 Sound level at cooling dB(A) 48 Sound level at heating dB(A) 50 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 855
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 33-5/8
Weight kg 74
lbs 163 Refrigerant pipe Gas side O.D. mm 15.88 size inch 5/8
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 40 length Length m Max. 40
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
10
2-2. CEILING-CONCEALED TYPE
2-2-1.HEAT PUMP (without HEATER) AND COOLING ONLY TYPE
Model name Indoor unit PEAD-RP35EA PEAD-RP50EA
Outdoor unit H/P PUH-P35VGAA PUH-P35YGAA PUH-P50VGAA PUH-P50YGAA
C/O PU-P35VGAA PU-P35YGAA PU-P50VGAA PU-P50YGAA
Cooling Capacity Btu/h 15,100 19,100
kW 4.45 5.6 Total input kW 1.71 2.53 EER 2.60 2.21 Energy label class E F SHF 0.72 0.74
Heating * Capacity Btu/h 16,500 21,400
kW 4.85 6.3 Total input kW 1.73 2.20 COP 2.80 2.86 Energy label class E D Booster heater kW - -
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 16 16 25 16
Indoor unit Air flow CMM 11-14 13.5-17
(Low-High) CFM 388-494 476-600 External pressure Pa 30(70) Sound level dB(A) 34-38 36-40 (Low-High) (70Pa : 36-43) (70Pa : 38-44) External finish Galvanized sheets Dimension W : mm 935
D : mm 700 H : mm 295
W : inch 36-13/16
D : inch 27-5/8 H : inch 11-5/8
Weight kg 33 35
lbs 73 77
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 45 55
CFM 1,590 1,940 Sound level at cooling dB(A) 47 48 Sound level at heating * dB(A) 49 50 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 650 855
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 25-5/8 33-5/8
Weight kg 54 74
lbs 119 163 Refrigerant pipe Gas side O.D. mm 15.88 size inch 5/8
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 40 length Length m Max. 40 * HEAT PUMP TYPE
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
11
Model name Indoor unit PEAD-RP60EA PEAD-RP71EA
Outdoor unit H/P PUH-P60VGAA PUH-P60YGAA PUH-P71VGAA PUH-P71YGAA
C/O PU-P60VGAA PU-P60YGAA PU-P71VGAA PU-P71YGAA
Cooling Capacity Btu/h 22,500 25,900
kW 6.6 7.6 Total input kW 2.65 3.35 EER 2.49 2.27 Energy label class E F SHF 0.71 0.78
Heating * Capacity Btu/h 24,300 30,800
kW 7.15 9.05 Total input kW 2.36 3.18 COP 3.03 2.85 Energy label class D D Booster heater kW - -
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 25 16 32 16
Indoor unit Air flow CMM 17-21 20-25
(Low-High) CFM 600-741 706-883 External pressure Pa 30(70) 70(130) Sound level dB(A) 37-41 37-41 (Low-High) (70Pa : 39-46) (130Pa : 40-45) External finish Galvanized sheets Dimension W : mm 1175
D : mm 700 H : mm 295
W : inch 46-1/8
D : inch 27-5/8 H : inch 11-5/8
Weight kg 42 44
lbs 92 97
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 50
CFM 1,770 Sound level at cooling dB(A) 48 49 Sound level at heating * dB(A) 50 51 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 855
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 33-5/8
Weight kg 79
lbs 174 Refrigerant pipe Gas side O.D. mm 15.88 size inch 5/8
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 50 length Length m Max. 50 * HEAT PUMP TYPE
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
12
Model name Indoor unit PEAD-RP100EA PEAD-RP125EA PEAD-RP140EA
Outdoor unit H/P PUH-P100VGAA PUH-P100YGAA PUH-P125YGAA PUH-P140YGAA
C/O PU-P100VGAA PU-P100YGAA PU-P125YGAA PU-P140YGAA
Cooling Capacity Btu/h 32,700 41,600 47,700
kW 9.6 12.2 14 Total input kW 3.83 4.87 5.81 EER 2.51 2.51 2.41 Energy label class E E E SHF 0.75 0.74 0.74
Heating * Capacity Btu/h 35,100 47,700 56,600
kW 10.3 14 16.6 Total input kW 4.00 4.74 5.90 COP 2.58 2.95 2.81 Energy label class F D D Booster heater kW - - -
Power supply Phase [ 13 3
Cycle Hz 50 50 50 Voltage V 230 400 400 Breaker size A 32 16 25
Indoor unit Air flow CMM 27-34 33.5-42 36.5-46
(Low-High) CFM 953-1200 1183-1483 1288-1624 External pressure Pa 70(130) Sound level dB(A) 41-46 44-50 46-51 (Low-High) (130Pa : 42-48) (130Pa : 46-52) (130Pa : 47-53) External finish Galvanized sheets Dimension W : mm 1415 1715
D : mm 700 740 H : mm 295 325
W : inch 55-11/16 67-1/2
D : inch 27-5/8 29-1/8 H : inch 11-5/8 12-13/16
Weight kg 62 65 70
lbs 136 143 154
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 85 95 100
CFM 3,000 3,360 3,530 Sound level at cooling dB(A) 51 55 57 Sound level at heating * dB(A) 53 56 58 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900 1050
D : mm 330+20 H : mm 1260
W : inch 35-7/16 41-5/16
D : inch 13 + 3/4 H : inch 49-5/8
Weight kg 97 125
lbs 214 276 Refrigerant pipe Gas side O.D. mm 19.05 size inch 3/4
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 50 length Length m Max. 50 * HEAT PUMP TYPE
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
13
Model name Indoor unit PEAD-RP60GA PEAD-RP71GA
Outdoor unit H/P PUH-P60VGAA PUH-P60YGAA PUH-P71VGAA PUH-P71YGAA
C/O PU-P60VGAA PU-P60YGAA PU-P71VGAA PU-P71YGAA
Cooling Capacity Btu/h 22,500 25,900
kW 6.6 7.6 Total input kW 2.74 3.35 EER 2.41 2.27 Energy label class E F SHF 0.72 0.76
Heating * Capacity Btu/h 24,300 30,800
kW 7.15 9.05 Total input kW 2.50 3.18 COP 2.86 2.85 Energy label class D D Booster heater kW - -
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 25 16 32 16
Indoor unit Air flow CMM 16.5-21 20-25
(Low-High) CFM 582-741 706-883 External pressure Pa 10/50/70 Sound level dB(A) 33-37/35-40/36-42 35-38/37-41/37-43 (Low-High) (10/50/70Pa) (10/50/70Pa) External finish Galvanized sheets Dimension W : mm 1171
D : mm 740 H : mm 275
W : inch 46-1/8
D : inch 29-1/8 H : inch 10-13/16
Weight kg 42
lbs 93
Unit drain pipe O.D. mm 32
inch 1-1/4
Outdoor unit Air flow CMM 50
CFM 1,770 Sound level at cooling dB(A) 48 49 Sound level at heating * dB(A) 50 51 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 855
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 33-5/8
Weight kg 79
lbs 174 Refrigerant pipe Gas side O.D. mm 15.88 size inch 5/8
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 50 length Length m Max. 50 * HEAT PUMP TYPE
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
14
Model name Indoor unit PEAD-RP100GA
Outdoor unit H/P PUH-P100VGAA PUH-P100YGAA
C/O PU-P100VGAA PU-P100YGAA
Cooling Capacity Btu/h 32,700
kW 9.6 Total input kW 3.68 EER 2.61 Energy label class D SHF 0.75
Heating * Capacity Btu/h 35,100
kW 10.3 Total input kW 3.67 COP 2.81 Energy label class D Booster heater kW -
Power supply Phase [ 13
Cycle Hz 50 50 Voltage V 230 400 Breaker size A 32 16
Indoor unit Air flow CMM 26.5-33
(Low-High) CFM 935-1165 External pressure Pa 10/50/70 Sound level dB(A) 40-43/42-45/42-46 (Low-High) (10/50/70Pa) External finish Galvanized sheets Dimension W mm 1411
D mm 740 H mm 275
W inch 55-9/16
D inch 29-1/8 H inch 10-13/16
Weight kg 50
lbs 111
Unit drain pipe mm 32
inch 1-1/4
Outdoor unit Air flow CMM 85
CFM 3,000 Sound level at cooling dB(A) 51 Sound level at heating * dB(A) 53 External finish Ivory Munsell 5Y 7/1 Dimension W mm 900
D mm 330+20 H mm 1260
W inch 35-7/16
D inch 13 + 3/4 H inch 49-5/8
Weight kg 97
lbs 214 Refrigerant pipe Gas side O.D. mm 19.05 size inch 3/4
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 50 length Length m Max. 50 * HEAT PUMP TYPE
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
15
2-2-2.HEAT PUMP (with HEATER) TYPE
Model name Indoor unit PEHD-P35EAH PEHD-P50EAH
Outdoor unit PUH-P35VGAA PUH-P35YGAA PUH-P50VGAA PUH-P50YGAA
Cooling Capacity Btu/h 15,100 19,100
kW 4.45 5.6 Total input kW 1.71 2.53 EER 2.60 2.21 Energy label class E F SHF 0.72 0.74
Heating Capacity Btu/h 16,500 21,400
kW 4.85 6.3 Total input kW 1.73 2.20 COP 2.80 2.86 Energy label class E D Booster heater kW 0.9 0.9
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 16 16 25 16
Power supply Phase [ 1 for heater Cycle Hz 50
Voltage V 230 Breaker size A 16
Indoor unit Air flow CMM 11-14 13.5-17
(Low-High) CFM 388-494 476-600 External pressure Pa 30(70) Sound level dB(A) 34-38 36-40 (Low-High) (70Pa : 36-43) (70Pa : 38-44) External finish Galvanized sheets Dimension W : mm 935
D : mm 700 H : mm 295
W : inch 36-13/16
D : inch 27-5/8 H : inch 11-5/8
Weight kg 35 37
lbs 77 82
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 45 55
CFM 1,590 1,940 Sound level at cooling dB(A) 47 48 Sound level at heating dB(A) 49 50 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 650 855
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 25-5/8 33-5/8
Weight kg 54 74
lbs 119 163 Refrigerant pipe Gas side O.D. mm 15.88 size inch 5/8
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 40 length Length m Max. 40
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
16
Model name Indoor unit PEHD-P60EAH PEHD-P71EAH
Outdoor unit PUH-P60VGAA PUH-P60YGAA PUH-P71VGAA PUH-P71YGAA
Cooling Capacity Btu/h 22,500 25,900
kW 6.6 7.6 Total input kW 2.65 3.35 EER 2.49 2.27 Energy label class E F SHF 0.71 0.78
Heating Capacity Btu/h 24,300 30,800
kW 7.15 9.05 Total input kW 2.36 3.18 COP 3.03 2.85 Energy label class D D Booster heater kW 1.4 1.9
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 25 16 32 16
Power supply Phase [ 1 for heater Cycle Hz 50
Voltage V 230 Breaker size A 16
Indoor unit Air flow CMM 17-21 20-25
(Low-High) CFM 600-741 706-883 External pressure Pa 30(70) 70(130) Sound level dB(A) 37-41 37-41 (Low-High) (70Pa : 39-46) (130Pa : 40-45) External finish Galvanized sheets Dimension W : mm 1175
D : mm 700 H : mm 295
W : inch 46-1/8
D : inch 27-5/8 H : inch 11-5/8
Weight kg 44 46
lbs 97 101
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 50
CFM 1,770 Sound level at cooling dB(A) 48 49 Sound level at heating dB(A) 50 51 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 855
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 33-5/8
Weight kg 79
lbs 174 Refrigerant pipe Gas side O.D. mm 15.88 size inch 5/8
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 50 length Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
17
Model name Indoor unit PEHD-P100EAH PEHD-P125EAH PEHD-P140EAH
Outdoor unit PUH-P100VGAA PUH-P100YGAA PUH-P125YGAA PUH-P140YGAA
Cooling Capacity Btu/h 32,700 41,600 47,700
kW 9.6 12.2 14 Total input kW 3.83 4.87 5.81 EER 2.51 2.51 2.41 Energy label class E E E SHF 0.75 0.74 0.74
Heating Capacity Btu/h 35,100 47,700 56,600
kW 10.3 14 16.6 Total input kW 4.00 4.74 5.90 COP 2.58 2.95 2.81 Energy label class F D D Booster heater kW - - -
Power supply Phase [ 13 3
Cycle Hz 50 50 50 Voltage V 230 400 400 Breaker size A 32 16 25
Power supply Phase [ 1 for heater Cycle Hz 50
Voltage V 230 Breaker size A 16
Indoor unit Air flow CMM 27-34 33.5-42 36.5-46
(Low-High) CFM 953-1200 1183-1483 1288-1624 External pressure Pa 70(130) Sound level dB(A) 41-46 44-50 46-51 (Low-High) (130Pa : 42-48) (130Pa : 46-52) (130Pa : 47-53) External finish Galvanized sheets Dimension W : mm 1415 1715
D : mm 700 740 H : mm 295 325
W : inch 55-11/16 67-1/2
D : inch 27-5/8 29-1/8 H : inch 11-5/8 12-13/16
Weight kg 65 68 73
lbs 143 150 161
Unit drain pipe R1(External thread)
Outdoor unit Air flow CMM 85 95 100
CFM 3,000 3,360 3,530 Sound level at cooling dB(A) 51 55 57 Sound level at heating dB(A) 53 56 58 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900 1050
D : mm 330+20 H : mm 1260
W : inch 35-7/16 41-5/16
D : inch 13 + 3/4 H : inch 49-5/8
Weight kg 97 125
lbs 214 276 Refrigerant pipe Gas side O.D. mm 19.05 size inch 3/4
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 50 length Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
18
2-3. WALL-MOUNTED TYPE
2-3-1.HEAT PUMP (without HEATER) AND COOLING ONLY TYPE
Model name Indoor unit PKA-RP35GAL PKA-RP50GAL
Outdoor unit H/P PUH-P35VGAA PUH-P35YGAA PUH-P50VGAA PUH-P50YGAA
C/O PU-P35VGAA PU-P35YGAA PU-P50VGAA PU-P50YGAA
Cooling Capacity Btu/h 15,100 18,300
kW 4.45 5.35 Total input kW 1.70 2.33 EER 2.62 2.30 Energy label class D F SHF 0.77 0.70
Heating * Capacity Btu/h 16,900 21,200
kW 4.95 6.2 Total input kW 1.79 2.34 COP 2.77 2.65 Energy label class E E Booster heater kW - -
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 16 16 25 16
Indoor unit Air flow CMM 9-10-11-12
(Low-Medium2-Medium1-High)
CFM 320-355-390-425 External pressure Pa 0 Sound level dB(A) 36-38-41-43 (Low-Medium2-Medium1-High) External finish White Munsell 0.70Y 8.59/0.97 Dimension W : mm 990
D : mm 235 H : mm 340
W : inch 39
D : inch 9-1/4 H : inch 13-3/8
Weight kg 16
lbs 35
Unit drain pipe O.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 45 55
CFM 1,590 1,940 Sound level at cooling dB(A) 47 48 Sound level at heating * dB(A) 49 50 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 650 855
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 25-5/8 33-5/8
Weight kg 54 74
lbs 119 163 Refrigerant pipe Gas side O.D. mm 15.88 size inch 5/8
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 40 length Length m Max. 40 * HEAT PUMP TYPE
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
19
Model name Indoor unit PKA-RP60FAL PKA-RP71FAL
Outdoor unit H/P PUH-P60VGAA PUH-P60YGAA PUH-P71VGAA PUH-P71YGAA
C/O PU-P60VGAA PU-P60YGAA PU-P71VGAA PU-P71YGAA
Cooling Capacity Btu/h 22,000 26,800
kW 6.45 7.85 Total input kW 2.65 3.43 EER 2.43 2.29 Energy label class E F SHF 0.80 0.74
Heating * Capacity Btu/h 25,100 32,100
kW 7.35 9.4 Total input kW 2.63 3.61 COP 2.79 2.60 Energy label class E F Booster heater kW - -
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 25 16 32 16
Indoor unit Air flow CMM 15-20
(Low-High) CFM 530-705 External pressure Pa 0 Sound level dB(A) 39-45 (Low-High) External finish Munsell 3.4Y 7.7/0.8 Dimension W : mm 1400
D : mm 235 H : mm 340
W : inch 55-1/8
D : inch 9-1/4 H : inch 13-3/8
Weight kg 24
lbs 53
Unit drain pipe O.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 50
CFM 1,770 Sound level at cooling dB(A) 48 49 Sound level at heating * dB(A) 50 51 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 855
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 33-5/8
Weight kg 79
lbs 174 Refrigerant pipe Gas side O.D. mm 15.88 size inch 5/8
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 50 length Length m Max. 50 * HEAT PUMP TYPE
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
20
Model name Indoor unit PKA-RP100FAL
Outdoor unit H/P PUH-P100VGAA PUH-P100YGAA
C/O PU-P100VGAA PU-P100YGAA
Cooling Capacity Btu/h 32,100
kW 9.4 Total input kW 3.59 EER 2.62 Energy label class D SHF 0.76
Heating * Capacity Btu/h 36,800
kW 10.8 Total input kW 3.77 COP 2.86 Energy label class D Booster heater kW -
Power supply Phase [ 13
Cycle Hz 50 50 Voltage V 230 400 Breaker size A 32 16
Indoor unit Air flow CMM 22-28
(Low-High) CFM 780-990 External pressure Pa 0 Sound level dB(A) 41-46 (Low-High) External finish Munsell 3.4Y 7.7/0.8 Dimension W : mm 1680
D : mm 235 H : mm 340
W : inch 66-1/8
D : inch 9-1/4 H : inch 13-3/8
Weight kg 28
lbs 62
Unit drain pipe O.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 85
CFM 3,000 Sound level at cooling dB(A) 51 Sound level at heating * dB(A) 53 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 1260
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 49-5/8
Weight kg 97
lbs 214 Refrigerant pipe Gas side O.D. mm 19.05 size inch 3/4
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 50 length Length m Max. 50 * HEAT PUMP TYPE
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
21
2-3-2.HEAT PUMP (with HEATER) TYPE
Model name Indoor unit PKH-P35GALH PKH-P50GALH
Outdoor unit PUH-P35VGAA PUH-P35YGAA PUH-P50VGAA PUH-P50YGAA
Cooling Capacity Btu/h 15,100 18,300
kW 4.45 5.35 Total input kW 1.70 2.33 EER 2.62 2.30 Energy label class D F SHF 0.77 0.70
Heating Capacity Btu/h 16,900 21,200
kW 4.95 6.2 Total input kW 1.79 2.34 COP 2.77 2.65 Energy label class E E Booster heater kW 0.73 0.73
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 16 16 25 16
Power supply Phase [ 1 for heater Cycle Hz 50
Voltage V 230 Breaker size A 16
Indoor unit Air flow CMM 9-10-11-12
(Low-Medium2-Medium1-High)
CFM 320-355-390-425 External pressure Pa 0 Sound level dB(A) 36-38-41-43 (Low-Medium2-Medium1-High) External finish White Munsell 0.70Y 8.59/0.97 Dimension W : mm 990
D : mm 235 H : mm 340
W : inch 39
D : inch 9-1/4 H : inch 13-3/8
Weight kg 17
lbs 37
Unit drain pipe O.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 45 55
CFM 1,590 1,940 Sound level at cooling dB(A) 47 48 Sound level at heating dB(A) 49 50 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 650 855
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 25-5/8 33-5/8
Weight kg 54 74
lbs 119 163 Refrigerant pipe Gas side O.D. mm 15.88 size inch 5/8
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 40 length Length m Max. 40
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
22
Model name Indoor unit PKH-P60FALH PKH-P71FALH
Outdoor unit PUH-P60VGAA PUH-P60YGAA PUH-P71VGAA PUH-P71YGAA
Cooling Capacity Btu/h 22,000 26,800
kW 6.45 7.85 Total input kW 2.65 3.43 EER 2.43 2.29 Energy label class E F SHF 0.80 0.74
Heating Capacity Btu/h 25,100 32,100
kW 7.35 9.4 Total input kW 2.63 3.61 COP 2.79 2.60 Energy label class E F Booster heater kW 1.93 1.93
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 25 16 32 16
Power supply Phase [ 1 for heater Cycle Hz 50
Voltage V 230 Breaker size A 16
Indoor unit Air flow CMM 15-20
(Low-High) CFM 530-705 External pressure Pa 0 Sound level dB(A) 39-45 (Low-High) External finish Munsell 3.4Y 7.7/0.8 Dimension W : mm 1400
D : mm 235 H : mm 340
W : inch 55-1/8
D : inch 9-1/4 H : inch 13-3/8
Weight kg 26
lbs 57
Unit drain pipe O.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 50
CFM 1,770 Sound level at cooling dB(A) 48 49 Sound level at heating dB(A) 50 51 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 855
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 33-5/8
Weight kg 79
lbs 174 Refrigerant pipe Gas side O.D. mm 15.88 size inch 5/8
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 50 length Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
23
Model name Indoor unit PKH-P100FALH
Outdoor unit PUH-P100VGAA PUH-P100YGAA
Cooling Capacity Btu/h 32,100
kW 9.4 Total input kW 3.59 EER 2.62 Energy label class D SHF 0.76
Heating Capacity Btu/h 36,800
kW 10.8 Total input kW 3.77 COP 2.86 Energy label class D Booster heater kW 2.20
Power supply Phase [ 13
Cycle Hz 50 50 Voltage V 230 400 Breaker size A 32 16
Power supply Phase [ 1 for heater Cycle Hz 50
Voltage V 230 Breaker size A 16
Indoor unit Air flow CMM 22-28
(Low-High) CFM 780-990 External pressure Pa 0 Sound level dB(A) 41-46 (Low-High) External finish Munsell 3.4Y 7.7/0.8 Dimension W : mm 1680
D : mm 235 H : mm 340
W : inch 66-1/8
D : inch 9-1/4 H : inch 13-3/8
Weight kg 30
lbs 66
Unit drain pipe O.D. mm 20
inch 13/16
Outdoor unit Air flow CMM 85
CFM 3,000 Sound level at cooling dB(A) 51 Sound level at heating dB(A) 53 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900
D : mm 330+20 H : mm 1260
W : inch 35-7/16
D : inch 13 + 3/4 H : inch 49-5/8
Weight kg 97
lbs 214 Refrigerant pipe Gas side O.D. mm 19.05 size inch 3/4
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 50 length Length m Max. 50
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
24
2-4. CEILING-SUSPENDED TYPE
2-4-1.HEAT PUMP (without HEATER) AND COOLING ONLY TYPE
Model name Indoor unit PCA-RP50GA PCA-RP60GA
Outdoor unit H/P PUH-P50VGAA PUH-P50YGAA PUH-P60VGAA PUH-P60YGAA
C/O PU-P50VGAA PU-P50YGAA PU-P60VGAA PU-P60YGAA
Cooling Capacity Btu/h 18,300 22,500
kW 5.35 6.6 Total input kW 2.35 2.62 EER 2.28 2.52 Energy label class F E SHF 0.72 0.75
Heating * Capacity Btu/h 21,200 24,700
kW 6.2 7.25 Total input kW 2.36 2.66 COP 2.63 2.73 Energy label class E E Booster heater kW - -
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 25 16 25 16
Indoor unit Air flow CMM 10-11-12-13 14-15-16-18
(Low-Medium2-Medium1-High)
CFM 355-390-425-460 495-530-565-635 External pressure Pa 0 0 Sound level dB(A) 37-38-40-42 37-39-41-43 (Low-Medium2-Medium1-High) External finish White Munsell 0.70Y 8.59/0.97 Dimension W : mm 1000 1310
D : mm 680 H : mm 210
W : inch 39-3/8 51-9/16
D : inch 26-3/4 26-3/4 H : inch 8-1/4
Weight kg 27 34
lbs 60 75
Unit drain pipe I.D. mm 26
inch 1
Outdoor unit Air flow CMM 55 50
CFM 1,940 1,770 Sound level at cooling dB(A) 48 48 Sound level at heating * dB(A) 50 50 External finish Ivory Munsell 5Y 7/1 Ivory Munsell 5Y 7/1 Dimension W : mm 900 900
D : mm 330+20 330+20 H : mm 855 855
W : inch 35-7/16 35-7/16
D : inch 13 + 3/4 13 + 3/4 H : inch 33-5/8 33-5/8
Weight kg 74 79
lbs 163 174 Refrigerant pipe Gas side O.D. mm 15.88 15.88 size inch 5/8 5/8
Liquid side O.D. mm 9.52 9.52
inch 3/8 3/8 Refrigerant pipe Height difference m Max. 40 Max. 50 length Length m Max. 40 Max. 50 * HEAT PUMP TYPE
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
25
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
Model name Indoor unit PCA-RP71GA PCA-RP100GA
Outdoor unit H/P PUH-P71VGAA PUH-P71YGAA PUH-P100VGAA PUH-P100YGAA
C/O PU-P71VGAA PU-P71YGAA PU-P100VGAA PU-P100YGAA
Cooling Capacity Btu/h 25,400 32,800
kW 7.45 9.6 Total input kW 3.37 3.62 EER 2.21 2.65 Energy label class F D SHF 0.73 0.76
Heating * Capacity Btu/h 31,200 36,200
kW 9.15 10.6 Total input kW 3.48 3.81 COP 2.63 2.78 Energy label class E E Booster heater kW - -
Power supply Phase [ 13 1 3
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 32 16 32 16
Indoor unit Air flow CMM 14-15-16-18 20-21-23-25
(Low-Medium2-Medium1-High)
CFM 495-530-565-635 705-840-810-885 External pressure Pa 0 0 Sound level dB(A) 37-39-41-43 40-41-43-45 (Low-Medium2-Medium1-High) External finish White Munsell 0.70Y 8.59/0.97 Dimension W : mm 1310
D : mm 680 H : mm 210 270
W : inch 51-9/16
D : inch 26-3/4 H : inch 8-1/4 10-5/8
Weight kg 34 37
lbs 75 82
Unit drain pipe I.D. mm 26
inch 1
Outdoor unit Air flow CMM 50 85
CFM 1,770 3,000 Sound level at cooling dB(A) 49 51 Sound level at heating * dB(A) 51 53 External finish Ivory Munsell 5Y 7/1 Ivory Munsell 5Y 7/1 Dimension W : mm 900 900
D : mm 330+20 330+20 H : mm 855 1260
W : inch 35-7/16 35-7/16
D : inch 13 + 3/4 13 + 3/4 H : inch 33-5/8 49-5/8
Weight kg 79 97
lbs 174 214 Refrigerant pipe Gas side O.D. mm 15.88 19.05 size inch 5/8 3/4
Liquid side O.D. mm 9.52 9.52
inch 3/8 3/8 Refrigerant pipe Height difference m Max. 50 Max. 50 length Length m Max. 50 Max. 50 * HEAT PUMP TYPE
26
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
Model name Indoor unit PCA-RP125GA PCA-RP140GA
Outdoor unit H/P PUH-P125YGAA PUH-P140YGAA
C/O PU-P125YGAA PU-P140YGAA
Cooling Capacity Btu/h 42,000 48,500
kW 12.3 14.2 Total input kW 4.91 5.89 EER 2.51 2.41 Energy label class E E SHF 0.77 0.74
Heating * Capacity Btu/h 50,500 58,000
kW 14.8 17.0 Total input kW 5.11 6.24 COP 2.90 2.72 Energy label class D E Booster heater kW - -
Power supply Phase [ 3
Cycle Hz 50 Voltage V 400 Breaker size A 25
Indoor unit Air flow CMM 27-30-32-34
(Low-Medium2-Medium1-High)
CFM 955-1060-1130-1200 External pressure Pa 0 Sound level dB(A) 41-43-45-46 42-44-46-48 (Low-Medium2-Medium1-High) External finish White Munsell 0.70Y 8.59/0.97 Dimension W : mm 1620
D : mm 680 H : mm 270
W : inch 63-3/4
D : inch 26-3/4 H : inch 10-5/8
Weight kg 43 45
lbs 95 99
Unit drain pipe I.D. mm 26
inch 1
Outdoor unit Air flow CMM 95 100
CFM 3,360 3,530 Sound level at cooling dB(A) 55 57 Sound level at heating * dB(A) 56 58 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 1050
D : mm 330+20 H : mm 1260
W : inch 41-5/16
D : inch 13 + 3/4 H : inch 49-5/8
Weight kg 125
lbs 276 Refrigerant pipe Gas side O.D. mm 19.05 size inch 3/4
Liquid side O.D. mm 9.52
inch 3/8 Refrigerant pipe Height difference m Max. 50 length Length m Max. 50 * HEAT PUMP TYPE
27
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
Model name Indoor unit PCA-RP71HA PCA-RP125HA
Outdoor unit H/P PUH-P71VGAA PUH-P71YGAA PUH-P125YGAA
C/O PU-P71VGAA PU-P71YGAA PU-P125YGAA
Cooling Capacity Btu/h 25,600 44,400
kW 7.5 13.0 Total input kW 3.36 4.90 EER 2.23 2.65 Energy label class F D SHF 0.72 0.72
Heating * Capacity Btu/h 31,400 54,600
kW 9.2 16.0 Total input kW 3.41 4.98 COP 2.70 3.21 Energy label class E C Booster heater kW - -
Power supply Phase [ 13 3
Cycle Hz 50 50 50 Voltage V 230 400 400 Breaker size A 32 16 25
Indoor unit Air flow CMM 17-19 30-38
(Low-High) CFM 600-670 1060-1350 External pressure Pa 0 0 Sound level dB(A) 34-38 44-50 (Low-High) External finish Stainless steel Dimension W : mm 1136 1520
D : mm 650 H : mm 280
W : inch 44-3/4 59-7/8
D : inch 25-5/8 H : inch 11
Weight kg 41 56
lbs 90 124
Unit drain pipe I.D. mm 26
inch 1
Outdoor unit Air flow CMM 50 95
CFM 1,770 3,360 Sound level at cooling dB(A) 49 55 Sound level at heating * dB(A) 51 56 External finish Ivory Munsell 5Y 7/1 Dimension W : mm 900 1050
D : mm 330+20 330+20 H : mm 855 1260
W : inch 35-7/16 41-5/16
D : inch 13 + 3/4 13 + 3/4 H : inch 33-5/8 49-5/8
Weight kg 79 125
lbs 174 276 Refrigerant pipe Gas side O.D. mm 15.88 19.05 size inch 5/8 3/4
Liquid side O.D. mm 9.52 9.52
inch 3/8 3/8 Refrigerant pipe Height difference m Max. 50 Max. 50 length Length m Max. 50 Max. 50 * HEAT PUMP TYPE
28
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
2-4-2.HEAT PUMP (with HEATER) TYPE
Model name Indoor unit PCH-P50GAH PCH-P60GAH
Outdoor unit PUH-P50VGAA PUH-P50YGAA PUH-P60VGAA PUH-P60YGAA
Cooling Capacity Btu/h 18,300 22,500
kW 5.35 6.6 Total input kW 2.35 2.62 EER 2.28 2.52 Energy label class F E SHF 0.72 0.75
Heating Capacity Btu/h 21,200 24,700
kW 6.2 7.25 Total input kW 2.36 2.66 COP 2.63 2.73 Energy label class E E Booster heater kW 1.29 1.93
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 25 16 25 16
Power supply Phase [ 1 for heater Cycle Hz 50
Voltage V 230 Breaker size A 16
Indoor unit Air flow CMM 10-11-12-13 14-15-16-18
(Low-Medium2-Medium1-High)
CFM 355-390-425-460 495-530-565-635 External pressure Pa 0 0 Sound level dB(A) 37-38-40-42 37-39-41-43 (Low-Medium2-Medium1-High) External finish White Munsell 0.70Y 8.59/0.97 Dimension W : mm 1000 1310
D : mm 680 H : mm 210
W : inch 39-3/8 51-9/16
D : inch 26-3/4 26-3/4 H : inch 8-1/4
Weight kg 28.5 36
lbs 63 79
Unit drain pipe I.D. mm 26
inch 1
Outdoor unit Air flow CMM 55 50
CFM 1,940 1,770 Sound level at cooling dB(A) 48 48 Sound level at heating dB(A) 50 50 External finish Ivory Munsell 5Y 7/1 Ivory Munsell 5Y 7/1 Dimension W : mm 900 900
D : mm 330+20 330+20 H : mm 855 855
W : inch 35-7/16 35-7/16
D : inch 13 + 3/4 13 + 3/4 H : inch 33-5/8 33-5/8
Weight kg 74 79
lbs 163 174 Refrigerant pipe Gas side O.D. mm 15.88 15.88 size inch 5/8 5/8
Liquid side O.D. mm 9.52 9.52
inch 3/8 3/8 Refrigerant pipe Height difference m Max. 40 Max. 50 length Length m Max. 40 Max. 50
29
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F) Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F) Heating Indoor: D.B. 20: (68˚F) Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Lower limit
D.B. 19˚C, W.B. 15˚C D.B. -5˚C
Heating
Upper limit
D.B. 28˚C
D.B. 24˚C, W.B. 18˚C
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
4. Above data based on indicated voltage Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz / 3phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3phase
Model name Indoor unit PCH-P71GAH PCH-P100GAH
Outdoor unit PUH-P71VGAA PUH-P71YGAA PUH-P100VGAA PUH-P100YGAA
Cooling Capacity Btu/h 25,400 32,800
kW 7.45 9.6 Total input kW 3.37 3.62 EER 2.21 2.65 Energy label class F D SHF 0.73 0.76
Heating Capacity Btu/h 31,200 36,200
kW 9.15 10.6 Total input kW 3.48 3.81 COP 2.63 2.78 Energy label class E E Booster heater kW 1.93 2.48
Power supply Phase [ 1313
Cycle Hz 50 50 50 50 Voltage V 230 400 230 400 Breaker size A 32 16 32 16
Power supply Phase [ 1 for heater Cycle Hz 50
Voltage V 230 Breaker size A 16
Indoor unit Air flow CMM 14-15-16-18 20-21-23-25
(Low-Medium2-Medium1-High)
CFM 495-530-565-635 705-840-810-885 External pressure Pa 0 0 Sound level dB(A) 37-39-41-43 40-41-43-45 (Low-Medium2-Medium1-High) External finish White Munsell 0.70Y 8.59/0.97 Dimension W : mm 1310
D : mm 680 H : mm 210 270
W : inch 51-9/16
D : inch 26-3/4 H : inch 8-1/4 10-5/8
Weight kg 36 39.5
lbs 79 87
Unit drain pipe I.D. mm 26
inch 1
Outdoor unit Air flow CMM 50 85
CFM 1,770 3,000 Sound level at cooling dB(A) 49 51 Sound level at heating dB(A) 51 53 External finish Ivory Munsell 5Y 7/1 Ivory Munsell 5Y 7/1 Dimension W : mm 900 900
D : mm 330+20 330+20 H : mm 855 1260
W : inch 35-7/16 35-7/16
D : inch 13 + 3/4 13 + 3/4 H : inch 33-5/8 49-5/8
Weight kg 79 97
lbs 174 214 Refrigerant pipe Gas side O.D. mm 15.88 19.05 size inch 5/8 3/4
Liquid side O.D. mm 9.52 9.52
inch 3/8 3/8 Refrigerant pipe Height difference m Max. 50 Max. 50 length Length m Max. 50 Max. 50
30
Loading...