Before obtaining access to terminal, all supply
circuits must be disconnected.
3-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilising refrigerant R410A
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with
the followings.
· For RP100, 125 and 140, be sure to perform replace ment operation before test run.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
Store the piping to be used indoors during
installation and both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
If large amount of mineral oil enters, that can cause deterioration of refrigerant oil etc.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
3
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Tool name Specifications
1Gauge manifold · Only for R410A
· Use the existing fitting
· Use high-tension side pressure of 5.3MPa·G or over.
2Charge hose · Only for R410A
· Use pressure performance of 5.09MPa·G or over.
3 Electronic scale
4Gas leak detector · Use the detector for R134a, R407C or R410A.
5Adaptor for reverse flow check · Attach on vacuum pump.
6Refrigerant charge base
7Refrigerant cylinder · Only for R410A · Top of cylinder (Pink)
· Cylinder with syphon
8Refrigerant recovery equipment
specifications
. (UNF1/2)
4
Liquid pipe
PART NAMES AND FUNCTIONS
Drain pipe
Filter
Air outlet
Gas pipe
i-see sensor
(option)
Vane
Air intake
(Intake grille)
4
Wiredremote controller
Display Section
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc.
*Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the
remote controller has been prohibited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, the time to be
switched off is shown.
TIME SUN MON TUE WED THU FRI SAT
TIMER
AFTER
ERROR CODE
°F°C
Hr
AFTER
°F°C
ONLY1Hr.
Up/Down Air Direction indicator
The indicator shows the direction of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to
low or downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off in 1 hour,
when the airflow direction
also changes.
Room Temperature display
Shows the room temperature. The room
temperature display range is 8–39.
The display blinks if the temperature
is less than 8 or 39 or more.
Louver display
Indicates the action of the swing louver.
Does not appear if the louver is not
running.
(Power On indicator)
Indicates that the power is on.
ON
OFF
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
To be displayed on when it is time to
clean the filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Operation Section
Temperature setting buttons
Down
Up
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button
(Set Day button)
Opening the
lid
Note:
L
“PLEASE WAIT” message
TEMP.
MENU
BACKDAY
MONITOR/SET
PAR-21MAA
CLOCK
ON/OFF
OPERATION
ON/OFF
FILTER
CHECK
TEST
CLEAR
Built-in temperature sensor
This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power failure.
L
“NOT AVAILABLE” message
This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have).
If a single remote controller is used to operate multiple indoor units simultaneously that are different types, this message will not be displayed as
far as any of the indoor units is equipped with the function.
ON/OFF button
Fan Speed button
Filter button
(<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button
( Operation button)
To return operation
number
Ventilation button
( Operation button)
To go to next operation
number
5
Wirelessremote controller
CHECK
TEST RUN
display
CHECK and TEST RUN display indicate that
the unit is being checked or test-run.
MODEL SELECT
Blinks when model is selected.
display
display
Lights up while the signal is transmitted to
the indoor unit when the button is pressed.
display
SET TEMP. display indicates the desired
temperature which is set.
display
OPERATION MODE display
Operation mode display indicates which
operation mode is in effect.
display
The vertical direction of air flow is indicated.
display
FAN SPEED display indicates which fan
speed has been selected.
ON/OFF button
The unit is turned ON and OFF alternately
each time the button is pressed.
FAN SPEED SELECT button
Used to change the fan speed.
MODE SELECT button
Used to switch the operation mode between
cooling, drying, heating, auto and fan mode.
CHECK
TEST RUN
MODEL SELECT
NOT AVAILABLE
ON/OFF TEMP
FAN
MODE
CHECK
VAN E
LOUVER
TEST RUN
RESETSETCLOCK
°C
AMPM
AMPM
AUTO STOP
AUTO START
h
min
CLOCK display
Displays the current time.
TIMER display
Displays when in timer operation or when
setting timer.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
button
SET TEMPERATURE button sets any desired
room temperature.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be
automatically stopped at the preset time.
AUTO START (ON timer): when this switch is
set, the air conditioner will be automatically
started at the preset time.
h and min buttons
Buttons used to set the “hour and minute” of
the current time and timer settings.
CHECK-TEST RUN button
Only press this button to perform an
inspection check or test operation.
Do not use it for normal operation.
VANE CONTROL button
Used to change the air flow direction.
LOUVER button
Changes left/right airflow direction.
(Not available for this model.)
CLOCK button
RESET button
SET button
6
5
SPECIFICATIONS
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Input
Running current
External finish (Panel)
Heat exchanger
Fan Fan (drive) % No.Fan motor output
External static pressure
Booster heater
INDOOR UNIT
Operation control & Thermostat
Noise level (Low-Medium2-Medium1-High)
Field drain pipe O.D.
Dimensions
Weight
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Input
Running current
External finish (Panel)
Heat exchanger
Fan Fan (drive) % No.Fan motor output
External static pressure
Booster heater
INDOOR UNIT
Operation control & Thermostat
Noise level (Low-Medium2-Medium1-High)
Field drain pipe O.D.
Dimensions
Weight
Airflow (Low-Medium2-Medium1-High)
Airflow (Low-Medium2-Medium1-High)
*/min(CFM)
Pa(mmAq)
W
D
H
*/min(CFM)
Pa(mmAq)
W
D
H
kW
A
kW
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A
kW
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
PLA-RP35BA.UK PLA-RP35BA1.UK PLA-RP35BA#2.UK
Cooling
0.03
0.22
UNIT : 840 (33-1/16)PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16)PANEL : 950 (37-3/8)
UNIT : 258 (10-3/16)PANEL : 35 (1-3/8)
PLA-RP50BA.UK PLA-RP50BA
Cooling
0.05
0.36
UNIT : 840 (33-1/16)PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16)PANEL : 950 (37-3/8)
UNIT : 258 (10-3/16)PANEL : 35 (1-3/8)
Single phase, 50Hz, 230V
Munsell 6.4Y 8.9/0.4
Plate fin coil
Turbo fan (direct) % 1
0.050
11-12-13-15(390-425-460-530)
0(direct blow)
–
Remote controller & built-in
27-28-29-31
32 (1-1/4)
UNIT : 22 (49)PANEL: 6 (13)
1.UK PLA-RP50BA#2.UK
Single phase, 50Hz, 230V
Munsell 6.4Y 8.9/0.4
Plate fin coil
Turbo fan (direct) % 1
0.050
12-14-16-18(425-495-565-635)
0(direct blow)
–
Remote controller & built-in
28-29-31-32
32(1-1/4)
UNIT : 22 (49) PANEL: 6 (13)
Heating
0.02
0.14
Heating
0.04
0.29
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Input
Running current
External finish (Panel)
Heat exchanger
Fan Fan (drive) % No.Fan motor output
External static pressure
Booster heater
INDOOR UNIT
Operation control & Thermostat
Noise level (Low-Medium2-Medium1-High)
Field drain pipe O.D.
Dimensions
Weight
Airflow (Low-Medium2-Medium1-High)
*/min(CFM)
Pa(mmAq)
W
D
H
kW
A
kW
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
PLA-RP60BA.UK PLA-RP60BA1.UK PLA-RP60BA#2.UK
Cooling
Single phase, 50Hz, 230V
0.05
0.36
Munsell 6.4Y 8.9/0.4
Plate fin coil
Turbo fan (direct) % 1
0.050
12-14-16-18(425-495-565-635)
0(direct blow)
–
Remote controller & built-in
28-29-31-32
32(1-1/4)
UNIT : 840 (33-1/16)PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16)PANEL : 950 (37-3/8)
UNIT : 258 (10-3/16)PANEL : 35 (1-3/8))
UNIT : 23 (51)PANEL: 6 (13)
Heating
0.04
0.29
7
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Input
Running current
External finish (Panel)
Heat exchanger
Fan Fan (drive) % No.Fan motor output
External static pressure
Booster heater
INDOOR UNIT
Operation control & Thermostat
Noise level (Low-Medium2-Medium1-High)
Field drain pipe O.D.
Dimensions
Weight
Airflow (Low-Medium2-Medium1-High)
W
D
H
kW
A
kW
*/min(CFM)
Pa(mmAq)
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
PLA-RP71BA.UK PLA-RP71BA1.UK PLA-RP71BA#2.UK
Cooling
Single phase, 50Hz, 230V
0.07
0.51
Munsell 6.4Y 8.9/0.4
Plate fin coil
Turbo fan (direct) % 1
0.050
14-16-18-21(485-565-635-740)
0(direct blow)
–
Remote controller & built-in
28-30-32-34
32(1-1/4)
UNIT : 840 (33-1/16)PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16)PANEL : 950 (37-3/8)
UNIT : 258 (10-3/16)PANEL : 35 (1-3/8)
UNIT : 23 (51)PANEL: 6 (13)
Heating
0.06
0.43
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Input
Running current
External finish (Panel)
Heat exchanger
Fan Fan (drive) % No.Fan motor output
External static pressure
Booster heater
INDOOR UNIT
Operation control & Thermostat
Noise level (Low-Medium2-Medium1-High)
Field drain pipe O.D.
Dimensions
Weight
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Input
Running current
External finish (Panel)
Heat exchanger
Fan Fan (drive) % No.Fan motor output
External static pressure
Booster heater
INDOOR UNIT
Operation control & Thermostat
Noise level (Low-Medium2-Medium1-High)
Field drain pipe O.D.
Dimensions
Weight
Airflow (Low-Medium2-Medium1-High)
Airflow (Low-Medium2-Medium1-High)
*/min(CFM)
Pa(mmAq)
W
D
H
*/min(CFM)
Pa(mmAq)
W
D
H
kW
A
kW
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A
kW
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
PLA-RP100BA.UK PLA-RP100BA#2.UK
Cooling
Single phase, 50Hz, 230V
0.14
0.94
Munsell 6.4Y 8.9/0.4
Plate fin coil
Turbo fan (direct) % 1
0.120
20-23-26-30(710-810-920-1,060)
0(direct blow)
–
Remote controller & built-in
32-34-37-40
32(1-1/4)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 298 (11-3/4) PANEL : 35 (1-3/8)
UNIT : 25 (55)PANEL : 6 (13)
PLA-RP125BA.UK PLA-RP125BA#2.UK
Cooling
Single phase, 50Hz, 230V
0.15
1.00
Munsell 6.4Y 8.9/0.4
Plate fin coil
Turbo fan (direct) % 1
0.120
22-25-28-31(780-880-990-1,090)
0(direct blow)
–
Remote controller & built-in
34-36-39-41
32(1-1/4)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 298 (11-3/4) PANEL : 35 (1-3/8)
UNIT : 25 (55)PANEL : 6 (13)
Heating
0.13
0.87
Heating
0.14
0.94
8
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Input
Running current
External finish (Panel)
Heat exchanger
Fan Fan(drive) % No.Fan motor output
External static pressure
Booster heater
INDOOR UNIT
Operation control & Thermostat
Noise level (Low-Medium2-Medium1-High)
Field drain pipe O.D.
Dimensions
Weight
Airflow (Low-Medium2-Medium1-High)
*/min(CFM)
Pa(mmAq)
W
D
H
kW
A
kW
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
PLA-RP140BA.UK PLA-RP140BA#2.UK
Cooling
Single phase, 50Hz, 230V
0.16
1.07
Munsell 6.4Y 8.9/0.4
Plate fin coil
Turbo fan (direct) % 1
0.120
24-26-29-32(850-920-1,020-1,130)
0(direct blow)
–
Remote controller & built-in
36-39-42-44
32(1-1/4)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 298 (11-3/4) PANEL : 35 (1-3/8)
UNIT : 27 (60)PANEL : 6 (13)
Heating
0.15
1.00
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Input
Running current
External finish (Panel)
Heat exchanger
Fan Fan (drive) % No.Fan motor output
External static pressure
Booster heater
INDOOR UNIT
Operation control & Thermostat
Noise level (Low-Medium2-Medium1-High)
Field drain pipe O.D.
Dimensions
Weight
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Input
Running current
External finish (Panel)
Heat exchanger
Fan Fan (drive) % No.Fan motor output
External static pressure
Booster heater
INDOOR UNIT
Operation control & Thermostat
Noise level (Low-Medium2-Medium1-High)
Field drain pipe O.D.
Dimensions
Weight
Airflow (Low-Medium2-Medium1-High)
Airflow (Low-Medium2-Medium1-High)
*/min(CFM)
Pa(mmAq)
W
D
H
*/min(CFM)
Pa(mmAq)
W
D
H
kW
A
kW
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A
kW
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Cooling
0.07
0.51
UNIT : 840 (33-1/16)PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16)PANEL : 950 (37-3/8)
UNIT : 258 (10-3/16)PANEL : 35 (1-3/8)
UNIT : 23 (51)PANEL: 6 (13)
Cooling
0.15
1.00
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 298 (11-3/4) PANEL : 35 (1-3/8)
UNIT : 27(60)PANEL : 6 (13)
PLA-RP71BA2.UK
Heating
Single phase, 50Hz, 230V
0.06
0.43
Munsell 6.4Y 8.9/0.4
Plate fin coil
Turbo fan (direct) % 1
0.050
14-16-18-21(485-565-635-740)
0(direct blow)
–
Remote controller & built-in
28-30-32-34
32(1-1/4)
PLA-RP100BA2.UK
Heating
Single phase, 50Hz, 230V
0.14
0.94
Munsell 6.4Y 8.9/0.4
Plate fin coil
Turbo fan (direct) % 1
0.120
20-23-26-30(710-810-920-1,060)
0(direct blow)
–
Remote controller & built-in
32-34-37-40
32(1-1/4)
9
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Input
Running current
External finish (Panel)
Heat exchanger
Fan Fan (drive) % No.Fan motor output
External static pressure
Booster heater
INDOOR UNIT
Operation control & Thermostat
Noise level (Low-Medium2-Medium1-High)
Field drain pipe O.D.
Dimensions
Weight
Airflow (Low-Medium2-Medium1-High)
*/min(CFM)
Pa(mmAq)
W
D
H
kW
A
kW
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Cooling
PLA-RP125BA2.UK
Single phase, 50Hz, 230V
0.16
1.07
Munsell 6.4Y 8.9/0.4
Plate fin coil
Turbo fan (direct) % 1
0.120
22-25-28-31(780-880-990-1,090)
0(direct blow)
–
Remote controller & built-in
34-36-39-41
32(1-1/4)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 298 (11-3/4) PANEL : 35 (1-3/8)
UNIT : 27(60)PANEL : 6 (13)
Heating
0.15
1.00
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Input
Running current
External finish (Panel)
Heat exchanger
Fan Fan(drive) % No.Fan motor output
External static pressure
Booster heater
INDOOR UNIT
Operation control & Thermostat
Noise level (Low-Medium2-Medium1-High)
Field drain pipe O.D.
Dimensions
Weight
Airflow (Low-Medium2-Medium1-High)
*/min(CFM)
Pa(mmAq)
W
D
H
kW
A
kW
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Cooling
PLA-RP140BA2.UK
Single phase, 50Hz, 230V
0.16
1.07
Munsell 6.4Y 8.9/0.4
Plate fin coil
Turbo fan (direct) % 1
0.120
24-26-29-32(850-920-1,020-1,130)
0(direct blow)
–
Remote controller & built-in
36-39-42-44
32(1-1/4)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 298 (11-3/4) PANEL : 35 (1-3/8)
UNIT : 27 (60)PANEL : 6 (13)
Heating
0.15
1.00
10
6
NOISE CRITERION CURVES
PLA-RP35BA.UK
PLA-RP35BA1.UK
PLA-RP35BA#2.UK
90
80
70
60
50
40
30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
631252505001000200040008000
BAND CENTER FREQUENCIES, Hz
NOTCH SPL(dB)LINE
High31
Medium129
Medium228
Low27
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PLA-RP50BA.UK
PLA-RP50BA1.UK
PLA-RP50BA#2.UK
90
80
70
60
50
40
30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
631252505001000200040008000
BAND CENTER FREQUENCIES, Hz
NOTCH SPL(dB)LINE
High32
Medium131
Medium229
Low28
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
PLA-RP60BA.UK
PLA-RP60BA1.UK
PLA-RP60BA#2.UK
90
80
70
60
50
40
30
APPROXIMATE
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
Note1. Please choose the grille from a standard grille, auto-grille.
2. As for drain pipe, please use VP-25(O.D.
:
32 PVC TUBE).
Drain pump is included.
Max. lifting height is 850mm from the ceiling.
3. As for suspension bolt, please use M10 or W3/8.
(Procured at local site)
4. Electrical box may be removed for the service purpose.
Make sure to slack the electrical wire little bit for control/power wires connection.
5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional multi-functional casement.
1) Requires E or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions + marked on the figure.
3) The optional high efficiency filter must be used jointly with the optional multi-functional casement.
7. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
(It becomes the cause of dew drops/Water dew.)
8. As for necessary installation/service space, please refer to the left figure.
1.SymboIs used in wiring diagram above are, :Connector, : Terminal (block).
2.Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers
(S1, S2, S3) for correct wirings.
3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric
wiring diagram for servicing.
4.This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V),
adopting superimposed system for power and signal.
+1:If indoor and outdoor units have separate power supplies, refer to Fig.1.
+2:For power supply system of this unit, refer to the caution label located near this diagram.
Refrigerant flow in cooling
Refrigerant flow in heating
16
10
TROUBLESHOOTING
10-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.
Actions to be taken for service and the trouble reoccurrence at field are summarized in the table below. Check the contents
below before investigating details.
Unit conditions at service
The trouble is reoccurring.
The trouble is not reoccurring.
Error code
Displayed
Not displayed
Logged
Not logged
Actions to be taken for service (summary)
Judge what is wrong and take a corrective action according
to “10-3. Self-diagnosis action table”.
Conduct troubleshooting and ascertain the cause of the
trouble according to “10-4. Troubleshooting by inferior
phenomena”.
Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
trouble occurred, matters related to wiring and etc.
Reset error code logs and restart the unit after finishing
service.
There is no abnormality in electrical component,
controller board, remote controller and etc.
Re-check the abnormal symptom.
Conduct trouble shooting and ascertain the cause of
the trouble
inferior phenomena”.
Continue to operate unit for the time being if the cause
is not ascertained.
There is no abnormality concerning of parts such as
10-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<Malfunction-diagnosis method at maintenance service>
[Procedure]
CHECK
display
ON/OFF
button
CHECK
button
ON/OFF
MODE
CHECK
TEST RUN
SET
CHECK
FAN
VAN E
LOUVER
RESET
TEMP
AUTO STOP
AUTO START
CLOCK
h
min
Refrigerant
address
display
Temperature
button
HOUR
button
1. Press the CHECK button twice.
2. Press the temperature
buttons.
3. Point the remote controller at the
sensor on the indoor unit and
press the HOUR button.
• "CHECK" lights, and refrigerant
address "00" flashes.
• Check that the remote controller's
display has stopped before continuing.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermit tent buzzer sound, the operation light
flashes, and the error code is
output.
(It takes 3 seconds at most for error
code to appear.)
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
• The check mode is cancelled.
18
• Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds
OPERATION
INDICATOR
lamp flash
pattern
Beep
Self-check
starts
(Start signal
received)
Beep Beep BeepBeepBeep Beep
1st2nd3
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
rd
0.5 sec.
th
n
On
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates
the check code in the following table
1st2
nd
· · · Repeated
[Output pattern B]
Beeper sounds
OPERATION
INDICATOR
lamp flash
pattern
BeepBeep Beep BeepBeepBeep Beep
1st2nd3
Off
Self-check
starts
(Start signal
received)
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “U2”)
rd
th
n
On
0.5 sec.
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates
the check code in the following table
4P4Drain sensor error/Float switch connector (CN4F) open
5
P5
PA
Drain pump error
Forced compressor stop(due to water leakage abnormality)
6P6Freezing/Overheating protection operation
7EECommunication error between indoor and outdoor units
8P8Pipe temperature error
9E4, E5Remote controller signal receiving error
10
11
–
–
–
–
12FbIndoor unit control system error (memory error, etc.)
–
E0, E3
Remote controller transmission error
–E1, E2Remote controller control board error
[Output pattern B]
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote controller
Check code
Symptom
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
*1 If the beeper does not sound again after the initial
the OPERATION INDICATOR lamp does not come on,
*2 If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller
Check code displayed in the LCD.
E9
UP
U3,U4
UF
U2
U1,Ud
U5
U8
U6
U7
U9,UH
–
–
Others
Indoor/outdoor unit communication error
(Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49C worked/
insufficient refrigerant
Abnormal high pressure (63H worked)/Overheating
protection operation
Abnormal temperature of heat sink
Outdoor unit fan protection stop
Compressor overcurrent interruption/Abnormal of power module
Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
–
–
Other errors (Refer to the technical manual for the outdoor unit.)
2 beeps to confirm the self-check start signal was received and
there are no error records.
19
1st2
nd
· · · Repeated
Remark
For details, check
the LED display
of the outdoor
controller board.
As for outdoor
unit, refer to
outdoor unit's
service manual.
• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller
Check code displayed in the LCD.
If the unit cannot be operated properly after test run, refer to the following table to find the cause.
•
Symptom
Wired remote controllerLED 1, 2 (PCB in outdoor unit)
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not
appear even when operation
switch is turned ON (operation
lamp does not light up).
On the wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller can be received.
• Operation lamp is blinking.
• The buzzer makes a short ping sound.
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer)Indicates whether control power is supplied. Make sure that this LED is
LED2 (power for remote controller)
LED3 (communication between indoor and
outdoor units)
For about 2
minutes after
power-on
Subsequent to
about 2 minutes
after power-on
After LED 1, 2 are lighted, LED 2 is
turned off, then only LED 1 is
lighted.
(Correct operation)
Only LED 1 is lighted. →
Only LED 1 is lighted.
always lit.
Indicates whether power is supplied to the remote controller.
This LED lights only in the case of the indoor unit which is connected to the
outdoor unit refrigerant addresses “0”.
Indicates state of communication between the indoor and outdoor units.
Make sure that this LED is always blinking.
LED 1, 2 blink.
→
LED 1 blinks twice,
LED 2 blinks once.
•For about 2 minutes following power-on,operation of the remote controller is not possible
due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection
device is not connected.
•Reverse or open phase wiring for the outdoor
unit’s power terminal block (L1, L2, L3)
•Incorrect wiring between indoor and outdoor
units (incorrect polarity of S1, S2, S3)
•Remote controller wire short
Cause
20
10-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
Abnormal point and detection method
Room temperature thermistor (TH1)
1 The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 minutes. (The unit returns to normal opera-
tion, if it has been reset normally.)
2 Constantly detected during cooling,
drying, and heating operation.
Short: -90: or more
Open: -40: or less
1 Defective thermistor
characteristics
2 Contact failure of connector
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective indoor controller
Note: Refer to the manual of outdoor unit for the details of display
such as F, U, and other E.
Cause
(CN20) on the indoor controller
board (Insert failure)
board
Countermeasure
1–3 Check resistance value of thermistor.
0: 15.0k"
10: 9.6k"
20: 6.3k"
30: 4.3k"
40: 3.0k"
If you put force on (draw or bend) the lead wire
while measuring resistance value of thermistor, breaking of wire or contact failure can be
detected.
2 Check contact failure of connector (CN20)
on the indoor controller board. Refer to 10-7.
Turn the power on again and check restart
after inserting connector again.
4 Check room temperature display on remote
controller.
Replace indoor controller board if there is
abnormal difference with actual room
temperature.
Turn the power off, and on again to operate
after check.
P2
P4
P5
Pipe temperature thermistor/Liquid
(TH2)
1 The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 minutes. (The unit returns to normal opera-
tion, if it has been reset normally.)
2 Constantly detected during cooling,
drying, and heating (except defrosting)
operation
Short: 90: or more
Open: -40: or less
Contact failure of drain float switch
(CN4F)
• Extract when the connector of drain float
switch is disconnected.
(3 and 4 of connector CN4F is not
short-circuited.)
• Constantly detected during operation
Drain over flow protection operation
1 Suspensive abnormality, if drain float
switch is detected to be underwater for
1 minute and 30 seconds continuously
with drain pump on.
Compressor and indoor fan will be
turned off.
2 Drain pump is abnormal if the condition
above is detected during suspensive
abnormality.
3 Constantly detected during drain pump
operation
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN44) on the indoor controller
board (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective refrigerant circuit is
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN44)
on the indoor controller board. Refer to 10-7.
Turn the power on and check restart after
inserting connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid>
temperature is extremely low (in cooling
mode) or high (in heating mode), refrigerant
circuit may have defective.
5 Check pipe <liquid> temperature with
remote controller in test run mode. If there is
extremely difference with actual pipe <liquid>
temperature, replace indoor controller board.
Turn the power off, and on again to operate
after check.
Check contact failure of float switch connector.
1
Turn the power on again and check after
inserting connector again.
2 Operate with connector (CN4F) short-
circuited.
Replace indoor controller board if abnormality
reappears.
1 Check if drain pump works.
2 Check drain function.
3 Remove drain float switch connector CN4F
and check if it is short (Switch On) with the
moving part of float switch UP, or OPEN with
the moving part of float switch down.
Replace float switch if it is short with the
moving part of float switch down.
4 Replace indoor controller board if it is short-
circuited between 3-4 of the drain float
switch connector CN4F and abnormality
reappears.
21
It is not abnormal if there is no problem about
the above-mentioned
Turn the power off, and on again to operate
after check.
Error Code
Abnormal point and detection method
Freezing/overheating protection is working
1 Freezing protection (Cooling mode)
The unit is in 6-minute resume prevention mode if pipe <liquid or condenser/
evaporator> temperature stays under
-15: for 3 minutes, 3 minutes after the
compressor started. Abnormal if it stays
under -15: for 3 minutes again within
16 minutes after 6-minute resume prevention mode.
Cause
(Cooling or drying mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Low-load (low temperature)
operation out of the tolerance
range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defective.
Countermeasure
(Cooling or drying mode)
1 Check clogs of the filter.
2 Remove blockage.
4 Refer to 10-6.
P6
P8
2 Overheating protection (Heating mode)
The units is in 6 minute resume
prevention mode if pipe <liquid or condenser/evaporator> temperature is
detected as over 70: after the compressor started. Abnormal if the temperature of over 70: is detected again
within 30 minutes after 6 minute resume
prevention mode.
Pipe temperature
<Cooling mode>
Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes after compressor start and 6 minutes
after the liquid or condenser/evaporator
pipe is out of cooling range.
Note 1) It takes at least 9 minutes to
detect.
Note 2) Abnormality P8 is not detected in
drying mode.
Cooling range : -3 °C ] (TH-TH1)
TH: Lower temperature between: liquid
pipe temperature (TH2) and condenser/evaporator temperature (TH5)
TH1: Intake temperature
<Heating mode>
When 10 seconds have passed after the
compressor starts operation and the hot
adjustment mode has finished, the unit is
detected as abnormal when condenser/
evaporator pipe temperature is not in heating range within 20 minutes.
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
(clogs)
(Heating mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Over-load (high temperature)
operation out of the tolerance
range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defective.
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
(clogs)
8 Bypass circuit of outdoor unit
is defective.
1 Slight temperature difference
between indoor room
temperature and pipe <liquid
or condenser/evaporator>
temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
<liquid or condenser/
evaporator> thermistor
• Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units
connection)
3 Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
4 Defective detection of indoor
room temperature and pipe
<condenser/evaporator>
temperature thermistor
5 Stop valve is not opened
completely.
5 Check outdoor fan motor.
67 Check operating condition of refrigerant
circuit.
(Heating mode)
1 Check clogs of the filter.
2 Remove blockage.
4 Refer to 10-6.
5 Check outdoor fan motor.
6~8 Check operating condition of refrigerant
circuit.
1~4 Check pipe <liquid or condenser/evapora-
tor> temperature with room temperature
display on remote controller and outdoor
controller circuit board.
Pipe <liquid or condenser/evaporator>
temperature display is indicated by setting SW2 of outdoor controller circuit
board as follows.
Conduct temperature check with outdoor
controller circuit board after connecting
(
‘A-Control Service Tool(PAC-SK52ST)’.
23 Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
)
Note 3) It takes at least 27 minutes to
detect abnormality.
Note 4) It excludes the period of defrosting.
(Detection restarts when defrosting
mode is over.)
Heating range : 3 °C [ (TH5-TH1)
22
Error Code
P9
E0
or
E4
Abnormal point and detection method
Pipe temperature thermistor/
Condenser-Evaporator (TH5)
1 The unit is in 3-minute resume protec-
tion mode if short/open of thermistor is
detected. Abnormal if the unit does not
get back to normal within 3 minutes. (The
unit returns to normal operation, if it has
been reset normally.)
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN44) on the indoor controller
board (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Temperature of thermistor is
90: or more or -40: or less
caused by defective refrigerant
circuit.
5 Defective indoor controller
board
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as “sub” remote controller.
In this case, E0 is displayed
on remote controller, and E4
is displayed at LED (LED1,
LED2) on the outdoor controller
circuit board.
3 Miswiring of remote controller
4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board
of refrigerant addresses “0”.
6 Noise has entered into the
transmission wire of remote
controller.
Countermeasure
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN44)
on the indoor controller board.
Refer to 10-7.
Turn the power on and check restart after
inserting connector again.
4 Operate in test run mode and check pipe
<condenser/evaporator> temperature with
outdoor controller circuit board. If pipe
<condenser/evaporator> temperature is
extremely low (in cooling mode) or high (in
heating mode), refrigerant circuit may have
defect.
5 Operate in test run mode and check pipe
<condenser/evaporator> temperature with
outdoor control circuit board. If there is
extreme difference with actual pipe
<condenser / evaporator> temperature,
replace indoor controller board.
There is no abnormality if none of above
comes within the unit.
Turn the power off and on again to operate.
In case of checking pipe temperature
with outdoor controller circuit board,
be sure to connect A-control service
(
tool (PAC-SK52ST).
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main”
if there is no problem with the action above.
3 Check wiring of remote controller.
• Total wiring length: max. 500m
(Do not use cable x 3 or more.)
• The number of connecting indoor units:
max. 16 units
• The number of connecting remote controller: max. 2 units
When it is not the above-mentioned problem of
1~3
4 Diagnose remote controllers.
a) When “RC OK” is displayed,
Remote controllers have no problem.
Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
b) When “RC NG” is displayed,
Replace remote controller.
c) When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormality.
* If the unit is not normal after replacing
indoor controller board in group control,
indoor controller board of address “0” may
be abnormal.
data at the same time and compares the
received and transmitted data. Abnormal
if these data are judged to be different
30 continuous times. (Error code: E3)
mitted data at the same time and compares the received and transmitted data.
Abnormal if these data are judged to
be different 30 continuous times. (Error
code: E5)
1 2 remote controllers are set as
“main.”
(In case of 2 remote con trollers)
2 Remote controller is connected
with 2 indoor units or more.
3 Repetition of refrigerant
address
4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board
6 Noise has entered into trans-
mission wire of remote control-
ler.
23
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting.
4~6 Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem.
Turn the power off,and on again to check.
When becoming abnormal again, replace
indoor controller board.
b) When “RC NG” is displayed, replace
remote controller.
c) When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormality.
Error Code
E6
Abnormal point and detection method
Indoor/outdoor unit communication
error (Signal receiving error)
1 Abnormal if indoor controller board
cannot receive any signal normally for 6
minutes after turning the power on.
2 Abnormal if indoor controller board
cannot receive any signal normally for 3
minutes.
3 Consider the unit abnormal under the fol-
lowing condition: When 2 or more indoor
units are connected to an
outdoor unit, indoor controller board
cannot receive a signal for 3 minutes
from outdoor controller circuit board, a
signal which allows outdoor controller
circuit board to transmit signals.
Cause
1 Contact failure, short circuit or,
miswiring (converse wiring) of
indoor/outdoor unit connecting
wire
2 Defective transmitting receiving
circuit of indoor controller board
3 Defective transmitting receiving
circuit of indoor controller board
4 Noise has entered into indoor/
outdoor unit connecting wire.
Countermeasure
* Check LED display on the outdoor control
circuit board. (Connect A-control service
tool, PAC-SK52ST.)
Refer to outdoor unit service manual.
1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or
outdoor unit.
Check all the units in case of twin triple
indoor unit system.
2-4 Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board or outdoor
controller circuit board.
* Other indoor controller board may have
defect in case of twin triple indoor unit
system.
E7
Fb
E1
or
E2
PA
Indoor/outdoor unit communication
error (Transmitting error)
Abnormal if “1” receiving is detected 30
times continuously though indoor controller
board has transmitted “0”.
Indoor controller board
Abnormal if data cannot be read normally
from the nonvolatile memory of the indoor
controller board.
Remote controller control board
1 Abnormal if data cannot be read nor-
mally from the nonvolatile memory of the
remote controller control board.
(Error code: E1)
2 Abnormal if the clock function of remote
controller cannot be operated normally.
(Error code: E2)
Forced compressor stop
(due to water leakage abnormality)
1 The unit has a water leakage abnor-
mality when the following conditions, a)
and b), are satisfied while the abovementioned detection is performed.
a) The intake temperature subtracted
with liquid pipe temperature detects
to be less than -10: for a total of
30 minutes. (When the drain sensor
is detected to be NOT soaked in the
water, the detection record of a) and b)
will be cleared.)
b) Drain float switch detects to be in the
water for more than 15 minutes.
*Once the water leakage abnormality is
detected, abnormality state will not be
released until the main power is reset.
3 Open circuit of float switch
4 Contact failure of float switch
connector
5 Dew condensation on float
switch
· Drain water descends along
lead wire.
· Drain water waving due to
filter clogging.
6 Extension piping connection
difference at twin, triple, quadruple system.
1-3 Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
1 Replace indoor controller board.
1 Check the drain pump.
2 Check whether water can be drained.
3 Check the resistance of the float switch.
4 Check the connector contact failure.
5 Check the float switch leadwire mounted.
Check the filter clogging.
6 Check the piping connection.
7 Miswiring of indoor/ outdoor
connecting at twin, triple, quadruple system.
8 Room temperature thermistor/
liquid pipe temperature thermistor detection is defective.
24
7 Check the indoor/outdoor connecting wires.
8 Check the room temperature display of
remote controller.
Check the indoor liquid pipe temperature dis
play of outdoor controller board.
10-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Phenomena
(1)LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is also off.
1 Power supply of rated voltage is not supplied to out-
door unit.
2 Defective outdoor controller circuit board
3 Power supply of 220~240V is not supplied to indoor
unit.
4 Defective indoor controller board
Cause
Countermeasure
1 Check the voltage of outdoor power
supply terminal block (L, N) or (L
• When AC 220~240V is not detected,
check the power wiring to outdoor unit
and the breaker.
• When AC 220~240V is detected, check
2 (below).
2 Check the voltage between outdoor
terminal block S1 and S2.
• When AC 220~240V is not detected,
—check the fuse on outdoor controller
circuit board.
—check the wiring connection.
• When AC 220~240V is detected, check
3 (below).
3 Check the voltage between indoor termi-
nal block S1 and S2.
• When AC 220~240V is not detected,
check indoor/outdoor unit connecting
wire for miswiring.
• When AC 220~240V is detected,
check 4 (below).
4 Check the fuse on indoor controller
board.
Check the wiring connection.
If no problem are found, indoor controller
board is defective.
3, N).
(For the separate indoor/outdoor unit power sup-
ply system)
1 Power supply of 220~240V AC is not supplied to
indoor unit.
2 The connectors of the optional replacement kit are
not used.
3 Defective indoor controller board
• When LED1 on indoor controller board is lit.
1 Mis-setting of refrigerant address for outdoor unit
(There is no unit corresponding to refrigerant
address “0”.)
1 Check the voltage of indoor power supply
terminal block (L,N).
• When AC220~240V is not detected,
check the power supply wiring.
• When AC220~240V is detected,
check 2 (below).
2 Check that there is no problem in the
method of connecting the connectors.
• When there are problems in the method
of connecting the connectors,
connect the connector correctly refer-
ring to installation manual of an optional
kit.
• When there is no problem in the method of connecting the connectors,
check 3 (below).
3 Check the fuse on indoor controller
board.
Check the wiring connection.
If no problem are found, indoor controller
board is defective.
1 Check again the setting of refrigerant
address for outdoor unit.
Set the refrigerant address to “0”.
(For grouping control system under
25
which 2 or more outdoor units are
connected, set one of the units to “0”.)
Set refrigerant address using SW1 (3-6)
on outdoor controller circuit board.
Phenomena
(2)LED2 on indoor controller board
is blinking.
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Cause
• When LED1 on indoor controller board is also blinking.
Connection failure of indoor/outdoor unit connecting
wire
Countermeasure
Check indoor/outdoor unit connecting wire
for connection failure.
(3)Upward/downward vane
performance failure
• When LED1 is lit.
1 Miswiring of remote controller wires
Under twin triple indoor unit system, 2 or more indoor
units are wired together.
2 Refrigerant address for outdoor unit is wrong or not
set.
Under grouping control system, there are some units
whose refrigerant address is 0.
3 Short-cut of remote controller wires
4 Defective remote controller
1 The vane is not downward during defrosting and heat
preparation and when the thermostat is OFF in HEAT
mode. (Working of COOL protection function)
2 Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
3 Upward/downward vane does not work.
• The vane is set to fixed position.
1 Check the connection of remote con troller wires in case of twin triple indoor
unit system. When 2 or more indoor units
are wired in one refrigerant system,
connect remote controller wires to one of
those units.
2 Check the setting of refrigerant address
in case of grouping control system.
If there are some units whose refrigerant
addresses are 0 in one group, set one of
the units to 0 using SW1 (3-6) on outdoor
controller circuit board.
34 Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the shortcut of remote controller wires.
• When LED2 is lit, connect remote
controller wires again and:
if LED2 is blinking, remote controller
is defective; if LED2 is lit, connection
failure of remote controller terminal
block etc. has returned to normal.
1 Normal operation (The vane is set to
horizontal regardless of remote control.)
2 Check 2 (left).
• Check the vane motor. (Refer to “How
to check the parts”.)
• Check for breaking of wire or connection failure of connector.
3 Normal operation (Each connector on
vane motor side is disconnected or setting the fixed vanes by wired remote
controller.)
(4)Receiver for wireless remote
controller
1 Weak batteries of wireless remote controller.
2 Contact failure of connector (CNB) on wireless
remote controller board
(Insert failure)
3 Contact failure of connector (CN90) on indoor con-
troller board (Insert failure)
4 Contact failure of connector between wireless remote
controller board and indoor controller board
1 Replace batteries of wireless remote con-
troller.
2~4
Check contact failure of each connector. If no problems are found of connector,
replace indoor controller board.
When the same trouble occurs even if
indoor controller board is replaced,
replace wireless remote controller
board.
26
10-5. EMERGENCY OPERATION
10-5-1. When wireless remote controller fails or its battery is exhausted
When the remote controller cannot be used
When the batteries of the remote controller run out or the remote controller malfunctions, the emergency operation can be done using the emergency buttons on the grille.
Operation modeCOOLHEAT
Set temperature24°C24°C
Fan speedHighHigh
Air ow directionHorizontalDownward 5
Stopping operation
• To stop operation, press the
for more than 2
for more than 2
means the start of operation.
button or the button .
10-5-2. When wired remote controller or indoor unit microcomputer fails
1. When the wired remote control or the indoor unit microcomputer has failed, but all other components work properly,
if you set the switch (SWE) on the indoor controller board ON, the indoor unit will begin Emergency Operation.
When Emergency Operation is activated, the indoor unit operates as follows:
(1) Indoor fan is running at high speed. (2) Drain-up machine is working.
+ Note on the wireless remote control
When the remote control does not function, it is possible to activate.
Emergency Operation by using the indoor unit Emergency operation switch (SW1, SW2 of the wireless signal
receiver board).
However, if the indoor unit microcomputer has failed, it is nesessary to proceed with points 2 and 3 below as in the
case of the wired remote control.
2. When you activate Emergency operation of the cooling or heating, you have to set the switch (SWE) on the indoor
controller board and activate Emergency operation of the outdoor unit.
For details on how to activate Emergency operation of the outdoor unit, refer to the outdoor unit wiring diagram.
Note: Emergency operation will not work unless outdoor unit is PU series.
3. Before you activate Emergency operation, check the following points:
(1) Emergency operation cannot be activated when:
• the outdoor unit malfunctions. • the indoor fan malfunctions.
• when it has detected the malfunction of drain-up machine during self-diagnosing.
(2) Emergency operation becomes continuous only by switching the power source on/off.
ON/OFF on the remote control or temperature control etc. does not function.
(3) Avoid operating for a long time when the outdoor unit begins defrosting
while Emergency operation of the heating is activated, because it will start to blow cold air.
(4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze).
(5) After Emergency operation has been deactivated, set the switches etc. to their original positions.
(6) Movement of the vanes does not work in Emergency operation, therefore
you have to slowly set them manually to the appropriate position.
27
10-6. HOW TO CHECK THE PARTS
PLA-RP35BA.UK PLA-RP50BA.UK PLA-RP60BA.UK PLA-RP71BA.UK
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature of 10~30)
Normal
4.3k~9.6k
Abnormal
Open or short
(Refer to the thermistor.)
Vane motor (MV)
White
Orange
Red
Blue
Yellow
Drain pump (DP)
YLW
1
3
YLW
Drain float switch (FS)
Moving part
1
2
3
4
i-see sensor
(Option)
Measure the resistance between the terminals with a tester.
(At the ambient temperature of 20~30)
Connector
Normal
Abnormal
Red - Yellow (-, -, -, -)
Red - Blue (-, -, -, -)
Red - Orange (-, -, -, -)
300
Open or short
Red - White (-, -, -, -)
Measure the resistance between the terminals with a tester.
(Winding temperature 20)
NormalAbnormal
290 Open or short
Measure the resistance between the terminals with a tester.
State of moving part
UP
DOWNOther than open
Normal
ShortOther than short
Open
Abnormal
Switch
Magnet
Moving
Part
Turn on the indoor unit with the black plastic tape on the outside of
i-see sensor controller board.
With electricity being turned on, measure the power voltage between connectors with tester.
i-see sensor rotates and pull out the connector of motor for i-see sensor.
4321
431
2
Blue
Black
Brown
Pink
Vane motor for
i-see sensor (Option)
White
Orange
Red
Blue
Yellow
Do not disassemble corner panel
with i-see sensor.
Black plastic tape
i-see sensor (At the ambient temperature of 10~40)
i-see sensor connector
(–)—(+)
(+)—(–)Other than the normal
Normal
DC 1.857V ~ 3.132VOther than the normal
DC 0.939V ~ 1.506V
NOTE : Be careful not to discharge static electricity into electronics.
Measure the resistance between the terminals with a tester.
(At the ambient temperature of 20~30)
Connector
Normal
Abnormal
Red - Yellow
Red - Blue
Red - Orange
250
Open or short
Red - White
28
Abnormal
10-6-1. Thermistor
<Thermistor Characteristic graph>
Thermistor for
lower temperature
Room temperature thermistor (TH1)
Pipe temperature thermistor/liquid (TH2)
Condenser/evaporator temperature
thermistor (TH5)
< Thermistor for lower temperature >
50
40
Thermistor R0=15k' ± 3%
Fixed number of B=3480 ± 2%
CN90
Connect to the wireless
remote controller board
(CNB)
CN4Y
i-see sensor
CN6Y
i-see sensor motor output
12V DC pulse output
1.UK
LED3
Transmission (Indoor/outdoor)
CN3G
Connect to the auto grille controller board (CN3G)
13V pulse output
CNV
Vane motor output (MV)
12V pulse output
SW1
Model selection
SW2
Capacity setting
LED2
Power supply (R.B)
CN4F
Drain float switch (FS)
CN44
Pipe temperature
thermistor
1-2 : Liquid (TH2)
3-4 :
Condenser/Evaporator(TH5)
CN20
Room temperature
thermistor (TH1)
LED1
Power supply (I.B)
CNMF
Fan motor
1-4: DC 310~340V
5-4: DC15V
Jumper wire J41,J42
Pair No. setting for wireless
remote controller
CN2L
Connector (LOSSNAY)
SWE
Emergency operation
CN41
Connector
(HA terminal-A)
CN32
Connector
(Remote switch)
CN22
Connect to the terminal
block (TB5)
(Remote controller connecting wire)
(10.4~14.6V DC)
CN3C
Transmission
(Indoor/outdoor)
(0~24V DC)
: Voltage between pins of
V
CC
C955 15VDC
(Same as 5(+)–4(-) of CNMF)
CNP
Drain-pump output (DP)
(220-240V AC)
CNAC
Connect to the auto grille
controller board (CN3A)
(220-240V AC)
CN01
Connect to the Terminal Block (TB4)
(Indoor/outdoor connecting line)
Between 3 and 5
220-240V AC
FUSE 6.3A /250V
30
10-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control P.C. board.
The black square (■) indicates a switch position
Jumper wire ( : Short : Open)
Jumper wire
SW1
SW2
J41
J42
Functions
Model
settings
Capacity
settings
Pair number
setting with
wireless
remote
controller
Setting by the dip switch and jumper wire
MODELS
PLA-RP·BA
PLA-RP71BA2
PLA-RP100BA2
PLA-RP125BA2
PLA-RP140BA2
MODELS
PLA-RP35BA
PLA-RP50BA
PLA-RP60BA
PLA-RP71BA(2)
Wireless remote
controller setting
0
1
2
3 ~ 9
SETTING
1 2 3 4 5
12345
23451
SETTING
12345
12345
12345
12345
PLA-RP100BA(2)
ON
OFF
PLA-RP125BA(2)
ON
OFF
PLA-RP140BA(2)
ON
OFF
ON
OFF
Control PCB setting
J41J42
ON
OFF
ON
OFF
ON
OFF
MODELS
SETTING
12345
12345
12345
Remarks
ON
OFF
ON
OFF
ON
OFF
<Initial setting>
Wireless remote controller: 0
Control PCB: (for both J41 and J42)
4 pair number settings are supported.
The pair number settings of the wireless remote
controller and indoor control PCB (J41/J42) are
given in the table on the left.
(' ' in the table indicates the jumper wire is dis connected.)
JP1
JP3
Unit type
setting
Indoor
controller
board type
setting
Model
Without TH5
With TH5
Indoor controller board type
For product
Service parts
JP1
There is no jumper (JP1) because these models
have the cond./eva. temperature thermistor (TH5).
JP3
31
11
SPECIAL FUNCTION
11-1. HOW TO PERFORM THE UP/DOWN OPERATION OF THE AIR INTAKE GRILLE
11-1-1. Setting up the lowering distance of air intake grille
You can set up 8 different stages of lowering distance for
the air intake grille according to the set up location if desired.
* As a factory default, the decorative panel will automatically
stop at 1.6 m from the ceiling surface. The distance is a
rough indication, check by actually lowering it.
1) Take the cover off the electric box of the decorative panel. (2 screws)
2) Set up the dip switches of SW22 or SW2 on the control board of the
decorative panel as followed.
Dip SW 22Dip SW 2
Decorative
panel
Cover for
Electric Box of
the decorative
panel
Screws
Control board of
the decorative
panel
SW 22 or SW2
Unit
The black square (■) indicates a switch position.The black square (■) indicates a switch position.
Lowering distance
(Rough indication
of the ceiling height)
1.2m
(~ 2.4m)
2.0m
(2.8m ~ 3.2m)
2.8m
(3.6m ~ 4.0m)
3.6m
(4.4m ~ 4.8m)
SW22
(Lowering distance)
* Airflow outreach distance is different depending on indoor units and
air volume (ceiling height), so airflow may not reach the indicated
ceiling height as shown in the above table.
Lowering distance
(Rough indication
of the ceiling height)
1.6m
(2.4m ~ 2.8m)
2.4m
(3.2m ~ 3.6m)
3.2m
(4.0m ~ 4.4m)
4.0m
(4.8m ~ 5.2m)
SW22
(Lowering distance)
Initial setting
Lowering distance
(Rough indication
of the ceiling height)
1.2m
(~ 2.4m)
2.0m
(2.8m ~ 3.2m)
2.8m
(3.6m ~ 4.0m)
3.6m
(4.4m ~ 4.8m)
SW2
(Lowering distance)
Lowering distance
(Rough indication
of the ceiling height)
1.6m
(2.4m ~ 2.8m)
2.4m
(3.2m ~ 3.6m)
3.2m
(4.0m ~ 4.4m)
4.0m
(4.8m ~ 5.2m)
* Airflow outreach distance is different depending on indoor units and
air volume (ceiling height), so airflow may not reach the indicated
ceiling height as shown in the above table.
3) Put the cover back on the electric box of the decorarive panel.
11-1-2. How to perform the up/down operation using wireless remote controller
1) Ensure that the air-conditioner is not running.
2) Press the "Down" button to lower the air intake grille.
Warning:
* By default, the air intake grille will automatically stop at a lowering distance of 1.6 m from the ceiling level.
The distance can be changed to 1.2 m, 2.0 m, 2.4 m, 2.8 m, 3.2 m, 3.6 m and 4.0 m. These should be used
only as a guide. You should lower the air intake grille yourself to check the exact distance.
* When you want to stop the air intake grille while it is lowering, press the "Stop" or "Up" button on the remote
controller to stop at that position.
3) Remove the filter or air intake grille and clean them.
4) Attach the filter and air intake grille.
5) Press the "Up" button on the remote controller to put the air intake grille in place.
* If the air intake grille is not placed in the correct position at a time, the operation is automatically retried.
* When you want to stop the air intake grille while it is rising, press the "Stop" or "Down" button on the remote controller
to stop at that position.
Ensure that the air-conditioner is not running.
• Otherwise, it may cause an injury or a failure.
Wireless remote
controller for
Automatic Filter
Elevation Panel
SW2
(Lowering distance)
Initial setting
32
11-1-3. How to perform the up/down operation using wired remote controller (PAR-21MAA)
■General Operation
* Raise or lower all the air intake grilles managed by the remote controller at the same time.
Install the remote controller in a place where you can observe all the air-conditioners. Otherwise, the lowering grille may make
contact with something and cause damage to it.
1) Ensure that the air-conditioner is not running.
* The up/down operation mode is only available when the
airconditioner is "OFF".
Warning:
Ensure that the air-conditioner is not running.
• Otherwise, it may cause an injury or a failure.
2) Press both the "FILTER" and "Ventilation" buttons simultaneously for 2 seconds or more to enter the up/down
operation mode.
"Up/down operation
mode" display
3) Press the TEMP. ( ) button. After a while, the air intake grille will begin lowering.
"Stand by for lowering"
display
"Lowering" display
(blinking)
"Stopped" display
(when finished lowering)
Alternately
[
]
Note:
• You cannot stop the operation while the air intake grille is lowering.
* If you press the ( ) button while the air intake grille is moving down, the air intake grille
may stop lowering, but it will not stop immediately.
• By default, the air intake grille will automatically stop at the lowering distance of 1.6 m
from the ceiling level.
* The distance can be changed to 1.2 m, 2.0 m, 2.4 m, 2.8 m, 3.2 m, 3.6 m, and 4.0 m.
These should be used only as a guide. You should lower the air intake grille yourself to check
the exact distance.
the air intake grille
4) Remove the filter and/or air intake grille to clean them.
5) Press the TEMP. ( ) button. After a while, the air intake grille will begin to rise and then be put back into place.
"Stand by for raising" display
"Raising" display (blinking)
"Stopped" display (when the air intake
grille has been put back into place)
Alternately
[
]
Note:
• You cannot stop the operation while the air intake grille is rising.
* If you press the ( ) button while the intake grille is moving up, the air
intake grille may stop rising, but it will not stop immediately.
6) Exit the up/down mode either by pressing the "ON/OFF" button or by pressing both the "FILTER" and "Ventilation"
buttons simultaneously for 2 seconds or more.
* After exiting the up/down mode, wait for
about 30 seconds to perform the next
operation. The remote controller will not
accept any operation for that period.
Operation status
display
Down/Up
buttons
TEMP.
MENU
MONITOR/SET
BACKDAY
PAR-21MAA
CLOCK
ON/OFF
OPERATION
ON/OFF
FILTER
CHECK
CLEAR
Button to exit the up/down
operation mode
Buttons to enter the up/down
operation mode (Press them
TEST
simultaneously for 2 seconds.)
3333
■
Up/down operation with the individual specified air-conditioner (when used in combination with Mr. SLIM model)
* Raise or lower the air intake grille of the specific air-conditioner that you select from all that are managed by that remote controller.
1) Ensure that the air-conditioner is not running.
* The up/down operation mode is only available when the
Warning:
Ensure that the air-conditioner is not running.
• Otherwise, it may cause an injury or a failure.
air-conditioner is "OFF".
2) Press both the "FILTER" and "Ventilation" buttons simultaneously for 2 seconds or more to enter the up/down
operation mode.
Up/down operation mode
3) Press the "Ventilation" button. After a while, it will switch to the "individually-specified up/down operation
mode".
Up/down operation mode
Individually-specified up/down operation mode
Unit No.
Refrigerant address No.
In the upper right figure, the air-conditioner
for which the refrigerant address is "00"
If the number of the target airconditioner is unknown, go to 4).
and the unit No. is "1" is currently
selected.
If the number of the target airconditioner is known, go to 5).
4) If you press the "FILTER" button when the "Unit No." or "Refrigerant address No." is blinking, after a while,
the up/down airflow direction of the displayed air-conditioner will be switched downward; and the airflow
direction of the other vents will all be blocked.
■ In Step 5) described below, identify the target
air-conditioner by changing the "Unit No." and
"Refrigerant address No." and by pressing the "FILTER"
button to check the up/down airflow direction.
[Remarks:]
■ If "Err" is displayed when you press the "FILTER" button to check the target
air-conditioner, the air-conditioner with that "Unit No." or "Refrigerant
address" may not exist. Check and set that air-conditioner again.
5) Select the "Unit No." and "Refrigerant address No.".
■ "Unit No." and "Refrigerant address No." can be changed by using the "TEMP." buttons ( ) ( ) when the panel
displays (a) or (b).
■ Every time you press the "Mode selection" button, the target of operation will change as illustrated below.
(a) "Unit No." selection
display
(c) "Standby for up/down operation" display
[Remarks:]
■ Each pressing action changes the unit No. from "1 - 4" to "0".
(Unit No. "0" means that all of 1 - 4 are targeted.)
(b) "Refrigerant address No." selection display
■ Each press changes the "Refrigerant address" from "0 to 15".
6) Continue to press the "Mode selection" button until "Waiting for up/down operation" is displayed.
"Waiting for up/down operation" display
The following steps are the same as steps 3) - 6) described in the "General Operation" section. Refer to that
section.
Operation status display
Down/Up buttons (for selecting
unit No. and refrigerant
address)
Mode selection
TEMP.
MENU
MONITOR/SET
BACKDAY
PAR-21MAA
CLOCK
ON/OFF
OPERATION
ON/OFF
CHECK
CLEAR
FILTER
TEST
Button to exit the up/down
operation mode
Buttons to enter the up/down
operation mode (Hold them
down simultaneously for 2
seconds.)
UP/DOWN
Air intake grille is raised/lowered by
commands of UP and DOWN.
Air intake grille does not move under the
state of no-load detection or obstacle detection.
Air intake grille stops automatically at the set lowering
distance from the ceiling level.
STOP
It stops in the cases below :
• When it reaches at the set lowering distance from
the ceiling level.
It automatically stops after a predetermined period
of lowering.
• When it is stored in the panel.
The air intake grille is judged to be stored in the panel
when the storage detection switch is pressed for 3 seconds continuously.
• When receiving commands of STOP, DOWN while moving up or UP while moving down.
The STOP button is only available on the automatic filter elevation panel remote controller.
When the wired remote controller is used, there will be a slight delay in stopping due to transmission speed.
• When both wire 1b and 2b are not loaded.
Only the wire b in each UP/DOWN Machine has a tension detection switch.
UP/DOWN
Machine 1
Detection
switch
Wire 1a
Wire 1b
UP/DOWN
Machine 2
Wire 2a
Fig.1
Wire 2b
(2) Special operation
Storage operation
Case : Obstruction of the raising grille before storage or malfunction of storage detection switch
Storage operation will be performed when the intake grille has been raised the set distance but the
storage detection switch is not engaged.
In this case, the operation below will be repeated up to 4 times.
10 cm down 30 cm up ···· 10 cm down 30 cm up
No-load detection
Case : UP/DOWN commands with no grille suspended.
When both wire 1b and wire 2b are not loaded, the wires will not move.
Obstacle detection
Case : Making contact with something while lowering.
Should the loads on the wire 1b and wire 2b be removed due to the grille making contact with something while lowering,
the lowering operation will stop. The grille will then be raised 10 cm and stop again.
[Emergency operation]
• When the wireless remote controller cannot be used (in the case of battery discharge, misplacing of the wireless
remote controller, malfunctioning and so on), the emergency switch on the receiver can be used as an alternative.
* When doing this, particular caution must be taken not to fall.
To lower the air intake grille : Press the button once.
(For emergency heating operation, press and hold this button.)
To raise the air intake grille : Press the button once.
(For emergency cooling operation, press and hold this button.)
• To stop the air intake grille from moving, use the opposite buttons to those used to initiate movement.
(To stop it from lowering, press the UP button; To stop it from rising, press the Down button.)
• If up/down machine is out of order, fix air intake grille temporarily and the indoor unit can be operated.
+ For details, refer to installation manual for the attachment of grille.
35
11-3. ELECTRICAL CIRCUIT (Controller board and wiring diagram (Panel))
11-3-3. Check point of trouble
<LED (SW22 type) /LED2 (SW2 type) display>
Turn OFF : No power supply
Blink: Storage detection switch ON (short)
One blink : Storage detection switch OFF (open)
Two blinks : Tension detection switch OFF (open)
switch
MotorCN2B, CN2C5~20 Check if it is not open or short.
Entwining wiresPull wire
CN2Eopen or shortCheck if it is short when pressing push switch.
CN2F, CN2Gopen or shortCheck if it is short when wire b is tensioned.
Retension:
about 2 kgf
Check if wire is drawn out by pulling with 3 kgf.
11-4. TROUBLESHOOTING
•
Check the following points.
ProblemPossible ReasonCorrective Action
Air intake grille does not
function with operation of the
wireless remote controller.
Air intake grille cannot be
fixed in place.
Air intake grille stops lowering.
(Air intake grille would not
lower any further.)
Noises are made during
up/down operation.
(While air intake grille is
moving up/down.)
Air-conditioner is running.Stop running the air-conditioner and try again.
Power failure
Batteries are not inserted into the wireless remote controller.
Or battery power is running low.
There is something on the air intake grille.
Or something is stuck in the air intake grille.
There is something on the air intake grille.
Filter is not properly installed.
Air intake grille is not hung with all 4 hooks.
The air intake grille has finished lowering to the auto-stop
position.
This is the noise made when the wire is wound and
unwound.
After recovering from power failure, try again.
Insert or replace the battery.
Remove the objects or obstacles from the
air intake grille.
Or, remove the stuck object.
Remove the objects or obstacles from the
air intake grille.
Lower the air intake grille again and check
whether the filter is installed in the correct
position.
Lower the air intake grille again and hook
on the air intake grille.
This is normal.
Noises are made while putting
the air intake grille into place.
Air intake grille repeats rising
and lowering several times
while being put into place.
Air intake grille leans toward
one side during the up/down
operation.
This is the operational noise for putting the air intake
grille into place.
This is the operation for putting the air intake grille into
place.
The speeds of winding/unwinding wires are slightly
different for each wire.
37
This is normal.
11-5. ROTATION FUNCTION (AND BACK-UP FUNCTION, 2ND STAGE CUT-IN FUNCTION)
11-5-1. Operation
(1) Rotation function (and Back-up function)
• Outline of functions
· Main and sub unit operate alternately according to the interval of rotation setting.
w Main and sub unit should be set by refrigerant address. (Outdoor Dip switch setting)
Refrigerant address "00" Main unit
Refrigerant address "01" Sub unit
· When error occurs to one unit, another unit will start operation.(Back-up function)
• System constraint
· This function is available only by the grouping control system (INDOOR UNIT : OUTDOOR UNIT=1:1) of 2 refrigerant
groups. (Refer to Fig. 1)
· Main indoor unit should be connected for wired remote controller and the transmission line (TB5) for main and sub unit
should also be connected. (Refer to Fig. 1)
(This function cannot be set by wireless remote controller.)
· Set refrigerant address of each unit. (Dip switch on the outdoor unit···Refrigerant address 00/01)
Operation pattern
[Back-up function only]··· Request code number "312"
Start operation
Main
unit
IC-1
Sub
unit
IC-2
[Rotation function] & [Back-up function]··· Request code number "313~318"
Start operation
Main
unit
IC-1
Sub
unit
IC-2
(Ex:When the request code number is "313", each unit operates alternately in daily cycle.)
Run
Stop
Main SubMain SubMain Sub
Run
Stop
1~28 days1~28 days
Error occurs on main unit.
Main Sub
Abnormal condition
Run
Stop
Run
Run
StopRun
Error occurs on main unit.
Abnormal condition
Main
unit
2
Refrigerant address
"00"
OC-1
3(2)
IC-1
2
RC
Fig. 1
OC : Outdoor unit
IC : Indoor unit
RC : Wired remote controller
Refrigerant address
"01"
OC-2
Sub
3(2)
unit
IC-2
Note:
· When the unit is restarted to operate after turning off the power or OFF operation, the unit which was operationg will start
operation.
· To operate the main unit, refer to the 11-5-2. and set the request code No. which is not the same as the current one, and set
again the former request code No.
(2) 2nd stage cut-in function
Outline of functions
· When the 1st unit can NOT supply with sufficient capacity for exceptionally high-demand conditions and the actual room
temperature reaches set point *, the 2nd unit starts operation in conjunction with the 1st unit.
· Once the actual room temperature goes down to 4degrees C below set point *, the 2nd unit stops operation automatically.
(* set point = set temperature by R/C (remote controller) + 4, 6, 8: (selectable) )
· Number of operating units is determined according to the room temperature and set point.
· When room temperature becomes higher than set point, standby unit starts.(2 units operation)
· When room temperature falls below set point -4:, standby unit stops.(1 unit operation)
38
• System constraint
· This function is available only in cooling mode.
Ex.) Set temp. by R/C = 20:
Set point = 26:
When request code number is “323”.
26: 2nd unit Cut-in
4 degree C
22: 2nd unit Cut-out
[2nd stage cut-in function]··· Request code number "322~324"
Start operationSub unit start operation
Main
unit
IC-1
Sub
unit
IC-2
Room temp. Set point
Run
StopStopRun
20:
11-5-2. How to set rotation function (Back-up function, 2nd stage cut-in function)
You can set these functions by wired remote controller. (Maintenance monitor)
NOTICE
Both main and sub unit should be set in same setting.
Every time replacing indoor controller board for servicing, the function should be set again.
(1) Request Code List
Rotation setting
Setting No.
(Request code)
No.1
(310)
No.2
(311)
No.3
(312)
No.4
(313)
No.5
(314)
No.6
(315)
No.7
(316)
No.8
(317)
No.9
(318)
Setting contents
Monitoring the request code of current setting.
Rotation and Back-up OFF (Normal group control operation)
Back-up function only
Rotation ON (Alternating interval = 1day) and back-up function
Rotation ON (Alternating interval = 3days) and back-up function
Rotation ON (Alternating interval = 5days) and back-up function
Rotation ON (Alternating interval = 7days) and back-up function
Rotation ON (Alternating interval = 14days) and back-up function
Rotation ON (Alternating interval = 28days) and back-up function
Initial
setting
Room temp. < Set point -4
Sub unit stop
2nd unit cut-in setting
Setting No.
(Request code)
No.1
(320)
No.2
(321)
No.3
(322)
No.4
(323)
No.5
(324)
Setting contents
Monitoring the request code of current setting.
Cut-in function OFF
Cut-in function ON(Set point = Set temp.+ 4(7.2F)
Cut-in function ON(Set point = Set temp.+ 6(10.8F)
Cut-in function ON(Set point = Set temp.+ 8(14.4F)
39
Initial
setting
(2) Setting method of each function by wired remote controller
1. Stop operation().
2. Press the button () for 3 seconds so that [Maintenance mode] appears on the screen ().
After a while, [00] appears in the refrigerant address number display area. (at )
3. Press the button () for 3 seconds to switch to [Maintenance monitor].
Note) It is not possible to switch to [Maintenance monitor] during data request in maintenance mode
[----] appears on the screen () when [Maintenance monitor] is activated.
(The display () now allows you to set a request code No.)
TEST
CHECK
(i.e., while “----” is blinking) since no buttons are operative.
B: Refrigerant address
C: Data display area
D: Request code display area
4. Press the [TEMP ( and )] buttons () to select the desired refrigerant address.
[ScreenB]
5. Press the [CLOCK ( and )] buttons () to set the desired request code No. (“311~318”, “321~324”)
6. Press the button () to perform function setting.
If above setting operations are done correctly, "Request code number will appear in data display area.()
[Example: When the "311" of "Request code number" is set, [311] appears on the screen.()]
[Refererence]
You can check current "request code number" setting by setting the "request code number" (“310” or “320”) and
pressing the button.()
[Example: When the current setting is "Setting No.2 (Request code 311)", [311] appears on the screen.()]
7. To return to normal mode, press the button ().
(1) Slide the knob of air intake grille toward the arrow 1 to
open the air intake grille.
(2) Remove drop prevention hook from the panel.
(3) Slide the shaft in the hinge to the direction of the arrow 2
and remove the air intake grille.
2. Removing the room temperature thermistor (TH1)
(1) Remove the air intake grille and the filter. (See Figure 1)
(2) Remove the 2 screws from the electrical box.
(3) Disconnect the connector CN20 (Red) from the indoor con troller board.
(4) Remove the room temperature thermistor and holder.
3. Removing the reactor (DCL)
(1) Remove the air intake grille and the filter. (See Figure 1)
(2) Remove the 2 screws from the reactor cover.
(3) Disconnect the relay connector of reactor.
(4) Remove 2 reactor fixing screws and remove the reactor.
PHOTOS & ILLUSTRATIONS
Figure 1
Photo 1
Filter
Reactor cover
Fixing
screw
(reactor)
4. Removing the indoor controller board (I.B)
(1) Remove the air intake grille and the filter. (See Figure 1)
(2) Remove the 2 screws from the electrical box cover.
(3) Disconnect the connectors :
CNMF (White/7P) for fan motor
CN44 (White/4P) for thermistor (TH2/TH5)
CNP (Blue/3P) for drain pump
CN4F (White/4P) for float switch
CN01 (Black/5P) for earth and reactor
CNV (White/20P) for vane motor
(4) Remove the 6 supports from indoor controller board.
(5) Remove the indoor controller board.
5. Removing the electrical box
(1) Remove the air intake grille and the filter. (See Figure 1)
(2) Remove the 2 screws from the electrical box cover.
(3) Disconnect the connectors. (Refer to 4.)
Remove 2 electrical box fixing screws and remove 2 hooks.
(4)
(5) Pull the electrical box.
<Electrical parts in the electrical box>
Indoor controller board
Terminal block (TB4)(TB5)
Electrical box cover
Photo 2
Electrical box
Fixing screw
Electrical box
Fixing screw
(Electrical box)
Bell mouth
Indoor controller
board (I.B)
Room temp.
thermistor (TH1)
Turbo fan
Electrical box
Fixing screw
4141
OPERATING PROCEDURE
6. Removing the fan and fan motor (MF)
(1) Remove the electrical box. (See Photo 2)
(2) Remove the bell mouth (3 screws). (See Photo 2)
(3) Remove the turbo fan nut.
(4) Pull out the turbo fan.
(5) Remove the wire cover (3 screws).
(6) Remove 2 wiring clamps.
(7) Disconnect the connector of the fan motor (CNMF).
(8) Remove the 3 nuts and washers and rubber mounts of the
fan motor.
7. Removing the panel
(1) Remove the air intake grille and the filter. (See Figure 1)
(2) Disconnect the connector CNV (White/20P).
Corner panel (See Figure 2)
(3) Remove the corner screw.
(4) Slide the corner panel to the direction of the arrow 1, and
remove the corner panel.
Panel (See Photo 4, 5)
(5) Remove the 2 screws from the panel which fix to the oval
holes.
(6) Rotate the panel a little to come to the bell shaped hole
where the screw is large and remove the panel.
PHOTOS & ILLUSTRATIONS
Photo 3
Fan motor
Figure 2
Corner panel
Photo 4
Screw
Detail
Screw
Ball shaped hole
Coil plate
Corner panel
Oval hole
Clamp
Wire cover
fixing screw
Nut
Washer
Rubber mount
Panel
Photo 5
8. Removing the drain pan
(1) Remove the air intake grille and the filter. (See Figure 1)
(2) Remove the 2 screws from the electrical box cover.
(3) Disconnect the connectors. (Refer to 4.)
(4) Remove the panel. (See Photo 4, 5)
(5) Remove the electrical wiring service panel (3 screws).
(6) Remove the electrical box. (See Photo 2)
(7) Remove the bell mouth. (See Photo 2)
(8) Remove the 4 screws and pull out the drain pan.
w Pull out the left and right of the pan gradually.
Be careful not to crack or damage the pan.
9. Removing the pipe temperature thermistor (TH2)
and condenser evaporator temperature thermistor (TH5)
(1) Remove the drain pan. (See Photo 6)
(2) Remove the turbo fan. (See Photo 3)
(3) Remove the 2 wiring clamps. (See Photo 3)
(4) Remove the coil plate (2 screws).
(5) Remove the thermistors which are inserted into the holders
installed to the thin copper pipe.
(6) Disconnect the 4-pin white connector (CN44).
Photo 6
Drain pan
fixing screw
Electrical wiring
service panel
Drain pan
fixing screw
Photo 7
Electrical wiring service panel fixing screw
Liquid pipe temp. thermistor (TH2)
Drain pan
Drain pan
fixing screw
42
Cond./ eva. thermistor (TH5)
OPERATING PROCEDURE
PHOTOS & ILLUSTRATIONS
10. Removing the drain pump (DP) and float switch (FS)
(1) Remove the drain pan. (See Photo 6)
(2) Cut the hose band and remove the hose.
(3) Remove the drain pump assembly (3 screws and 2 hooks).
(4) Remove the drain pump (3 screws).
(5) Remove the float switch (2 screws).
Photo 8
Float switch
Hose band
Drain pump
Drain pump
assembly fixing screw
Photo 9
11. Removing the heat exchanger
(1) Remove the drain pan. (See Photo 6)
(2) Remove the 3 screws of the piping cover, and pull out
piping cover.
(3) Remove the 2 screws of coil plate.
(4) Remove the 2 screws of the coil.
(5) Remove the screw of the coil support.
(6) Pull out the heat exchanger.
Drain pump fixing screw
Photo 10
Piping cover
Coil plate
Heat exchanger
fixing screw
Coil support fixing screw
Float switch fixing screw
Heat exchanger
Coil support
43
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Aug. 2009 No.OCH412 REVISED EDITION-E PDF 6
Distributed in Mar. 2009 No.OCH412 REVISED EDITION-D PDF 6
Distributed in Apr. 2008 No.OCH412 REVISED EDITION-C PDF 7
Distributed in Feb. 2008 No.OCH412 REVISED EDITION-B PDF 7
Distributed in Oct. 2007 No.OCH412 REVISED EDITION-A PDF 7
Distributed in Mar. 2007 No.OCH412 PDF 7
Made in Japan
New publication, effective Aug. 2009
Specifications subject to change without notice
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.