Mitsubishi Electronics PLA-A-AA User Manual

Page 1
Air-Conditioners
PLA-A·AA
Deutsch
INSTALLATION MANUAL
For safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing the air-conditioner unit.
FOR INSTALLER
Nederlands
Español
Italiano
ППЛУИО¿
Português
Svenska
English
MANUAL DE INSTALACIÓN
Para un uso correcto y seguro, lea detalladamente este manual y el manual de instalación de la unidad exterior antes de instalar la unidad de aire acondicionado.
PARA EL INSTALADOR
Español
Page 2
Contents
1. Safety precautions ................................................................................... 2
2. Installation location .................................................................................. 3
3. Installing the indoor unit ........................................................................... 3
4. Installing the refrigerant piping ................................................................. 5
5. Drainage piping work ............................................................................... 6
1. Safety precautions
s Before installing the unit, make sure you read all the “Safety precau-
tions”.
s Please report to your supply authority or obtain their consent before
connecting this equipment to the power supply system.
Warning: Describes precautions that must be observed to prevent danger of injury or death to the user.
Caution: Describes precautions that must be observed to prevent damage to the unit.
Warning:
• Ask a dealer or an authorized technician to install the unit.
• For installation work, follow the instructions in the Installation Manual and use
tools and pipe components specifically made for use with refrigerant specified in the outdoor unit installation manual.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incor­rectly installed unit may fall down and cause damage or injuries.
• The unit must be securely installed on a structure that can sustain its weight.
• If the air conditioner is installed in a small room, measures must be taken to
prevent the refrigerant concentration in the room from exceeding the safety limit in the event of refrigerant leakage. Should the refrigerant leak and cause the concentration limit to be exceeded, hazards due to lack of oxygen in the room may result.
6. Electrical work .......................................................................................... 7
7. Test run .................................................................................................. 12
8. System control ....................................................................................... 15
9. Installing the grille .................................................................................. 15
10. Easy maintenance function .................................................................... 17
After installation work has been completed, explain the “Safety Precautions,” use, and maintenance of the unit to the customer according to the information in the Op­eration Manual and perform the test run to ensure normal operation. Both the Instal­lation Manual and Operation Manual must be given to the user for keeping. These manuals must be passed on to subsequent users.
: Indicates a part which must be grounded.
Warning:
Carefully read the labels affixed to the main unit.
• Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
• All electric work must be performed by a qualified technician according to local regulations and the instructions given in this manual.
• Use only specified cables for wiring.
• The terminal block cover panel of the unit must be firmly attached.
• Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them.
• The user should never attempt to repair the unit or transfer it to another loca­tion.
• After installation has been completed, check for refrigerant leaks. If refriger­ant leaks into the room and comes into contact with the flame of a heater or portable cooking range, poisonous gases will be released.
1.1. Before installation (Euvironment)
Caution:
• Do not use the unit in an unusual environment. If the air conditioner is in­stalled in areas exposed to steam, volatile oil (including machine oil), or sulfuric gas, areas exposed to high salt content such as the seaside, the performance can be significantly reduced and the internal parts can be damaged.
• Do not install the unit where combustible gases may leak, be produced, flow, or accumulate. If combustible gas accumulates around the unit, fire or explo­sion may result.
• Do not keep food, plants, caged pets, artwork, or precision instruments in the direct airflow of the indoor unit or too close to the unit, as these items can be damaged by temperature changes or dripping water.
1.2. Before installation or relocation
Caution:
• Be extremely careful when transporting the units. Two or more persons are needed to handle the unit, as it weighs 20 kg, 44lbs or more. Do not grasp the packaging bands. Wear protective gloves as you can injure your hands on the fins or other parts.
• Be sure to safely dispose of the packaging materials. Packaging materials, such as nails and other metal or wooden parts may cause stabs or other injuries.
1.3. Before electric work
Caution:
• Be sure to install circuit breakers. If not installed, electric shock may result.
• For the power lines, use standard cables of sufficient capacity. Otherwise, a short circuit, overheating, or fire may result.
• When installing the power lines, do not apply tension to the cables.
• When the room humidity exceeds 80% or when the drainpipe is clogged, wa­ter may drip from the indoor unit. Do not install the indoor unit where such dripping can cause damage.
• When installing the unit in a hospital or communications office, be prepared for noise and electronic interference. Inverters, home appliances, high-fre­quency medical equipment, and radio communications equipment can cause the air conditioner to malfunction or breakdown. The air conditioner may also affect medical equipment, disturbing medical care, and communications equip­ment, harming the screen display quality.
• Thermal insulation of the refrigerant pipe is necessary to prevent condensa­tion. If the refrigerant pipe is not properly insulated, condensation will be formed.
• Place thermal insulation on the pipes to prevent condensation. If the drain­pipe is installed incorrectly, water leakage and damage to the ceiling, floor, furniture, or other possessions may result.
• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all flare nuts to specification using a torque wrench. If tightened too much, the flare nut can break after an extended period.
• Be sure to ground the unit. If the unit is not properly grounded, electric shock may result.
• Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and molded case circuit breaker) with the specified capacity. If the circuit breaker capacity is larger than the specified capacity, breakdown or fire may result.
1.4. Before starting the test run
Caution:
• Turn on the main power switch more than 12 hours before starting operation. Starting operation just after turning on the power switch can severely dam­age the internal parts.
• Before starting operation, check that all panels, guards and other protective parts are correctly installed. Rotating, hot, or high voltage parts can cause injuries.
2
• Do not operate the air conditioner without the air filter set in place. If the air filter is not installed, dust may accumulate and breakdown may result.
• Do not touch any switch with wet hands. Electric shock may result.
• Do not touch the refrigerant pipes with bare hands during operation.
• After stopping operation, be sure to wait at least five minutes before turning off the main power switch. Otherwise, water leakage or breakdown may result.
Page 3
2. Installation location
7-9/16
6-1/4
6-1/4
3-27/32
6-1/4
33-27/32 to 35-13/16
25/32 to 1-25/32
25/32 to 1-25/32
25/32 to 1-25/32
31-7/8
37-3/8
33-1/16
7-3/4
23-13/16
33-1/16
37-3/8
33-27/32 to 35-13/16
A
B
C
D
C
B
D
A
6-1/4
25/32 to 1-25/32
5-5/16
F
G
E
11/16
+3/16
0
11/16
+3/16
0
4-1/8
1-3/16
C
D
Min. 40
Min. 20
F
H
E
1-15/16 to 2-3/4
5/8
3-1/2
A
7-9/16
G
A
6-11/16
5-1/2
7-15/32
2-3/8 11-1/4 14-23/32
AFDE
B
C
Refer to the outdoor unit installation manual.
3. Installing the indoor unit
Caution:
Install the indoor unit at least 2.4 m, 8 ft above floor or grade level.
1
3
5
7
2
4
6
3.1. Check the indoor unit accessories (Fig. 3-1)
The indoor unit should be supplied with the following accessories.
Accessory name Q’ty
1 Installation template 1 2 Washers (with insulation) 4
Washers (without insulation) 4
3 Pipe cover (for refrigerant piping joint)
Small diameter 1 Large diameter 1
4 Band 8 5 Screw with washer (M5 × 25) for mounting grille 4 6 Drain socket 1 7 Insulation 1
Fig. 3-1
Fig. 3-2
(inch)
3.2. Ceiling openings and suspension bolt installation locations (Fig. 3-2)
Using the installation template (top of the package) and the gauge (supplied as an
accessory with the grille), make an opening in the ceiling so that the main unit can be installed as shown in the diagram. (The method for using the template and the gauge are shown.)
* Before using, check the dimensions of template and gauge, because they
change due to fluctuations of temperature and humidity.
* The dimensions of ceiling opening can be regulated within the range shown in
following diagram; so center the main unit against the opening of ceiling, en­suring that the respective opposite sides on all sides of the clearance between them becomes identical.
Use M10 (3/8) suspension bolts.
* Suspension bolts are to be procured at the field.
Install securely, ensuring that there is no clearance between the ceiling panel &
grille, and between the main unit & grille.
A Outer side of main unit B Bolt pitch C Ceiling opening D Outer side of Grille E Grille F Ceiling G Multi function casement (option) H Entire periphery
* Note that the space between ceiling panel of the unit and ceiling slab and etc must be 10 to
15 mm, 25/64-19/32 inch.
Models C D
A12, A18, A24, A30
241, 9-1/2 258, 10-3/16
A36, A42 281, 11-1/16 298, 11-3/4
(mm, inch)
Fig. 3-3
(mm, inch)
Models A
A12, A18, A24, A30
A36, A42 84, 3-5/16
(inch)
80, 3-5/32
3.3. Refrigerant and drainage piping locations of indoor unit
The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional multi function casement. (Fig. 3-3)
A Drain pipe B Ceiling C Grille D Refrigerant pipe (liquid) E Refrigerant pipe (gas) F Water supply inlet G Main unit
When the optional multi-functional casement is installed, add 135 mm, 5-5/16 inch
to the dimensions marked on the figure.
3
Page 4
3. Installing the indoor unit
A
B
C
J
H
I
D
E
F
G
23-13/16
31-57/64
A
D
C
B
A=11/16
+3/16
0
C
D
B
A
11/16
4-1/8(9-29/64)
+3/16
0
A
B
A
C
D
E
F
C
B
G
Min. 1-3/16
D
E
A
C
A
B
3-17/32
3-15/16
5-1/8
13-25/32
70°
G
F
H
I
J
6-3/32
6-9/16
3-15/16
3-17/32
3-15/16
L
K
M
N
O
6-7/32
120°
120°
1
D Ceiling E Rafter F Beam G Roof beam
Fig. 3-4
2
Fig. 3-5
(inch)
A Unit B Grille C Pillar
H Use inserts rated at 100-150 kg,
250-350 lbs each (procure locally)
I Suspension bolts M10 (3/8”) (procure
locally)
J Steel reinforcing rod
(inch)
3.4. Branch duct hole and fresh air intake hole (Fig. 3-4)
At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when required.
A fresh air intake hole for the optional multi function casement can also be made.
Note: The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional multi function casement. When installing the optional multi function casement, add 135 mm, 5-5/16 inch to the dimensions marked on the figure. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur.
A Branch duct hole B Indoor unit C Fresh air intake hole D Drain pipe E Refrigerant pipe F Branch duct hole diagram (view from
either side)
G Cut out hole H 14-ø2.8 mm, ø1/8 inch burring hole
I ø150 mm, ø5-29/32 inch cut out hole J ø175 mm, ø6-7/8 inch burring hole pitch K Fresh air intake hole diagram L 3-ø2.8 mm, ø1/8 inch burring hole M ø125 mm, ø4-29/32 inch burring hole pitch N ø100 mm, ø3-15/16 inch cut out hole O Ceiling
3.5. Suspension structure (Give site of suspension strong structure) (Fig. 3-5)
The ceiling work differs according to the construction of the building. Building con-
structors and interior decorators should be consulted for details.
(1) Extent of ceiling removal: The ceiling must be kept completely horizontal and the
ceiling foundation (framework: wooden slats and slat holders) must be reinforced
in order to protect the ceiling from vibration. (2) Cut and remove the ceiling foundation. (3) Reinforce the ends of the ceiling foundation where it has been cut and add ceiling
foundation for securing the ends of the ceiling board. (4) When installing the indoor unit on a slanting ceiling, attach a pillar between the
ceiling and the grille and set so that the unit is installed horizontally.
1 Wooden structures
Use tie beams (single storied houses) or second floor beams (two story houses) as
reinforcing members.
Wooden beams for suspending air conditioners must be sturdy and their sides
must be at least 6 cm, 2-3/8 inch long if the beams are separated by not more than 90 cm, 35-7/16 inch and their sides must be at least 9 cm, 3-9/16 inch long if the beams are separated by as much as 180 cm, 70-7/18 inch. The size of the suspen­sion bolts should be ø10 (3/8). (The bolts do not come with the unit.)
2 Ferro-concrete structures Secure the suspension bolts using the method shown, or use steel or wooden hang­ers, etc. to install the suspension bolts.
A Suspension bolt B Ceiling C Nut D Washer (with insulation) E Mounting plate F Washer (without insulation) G Check using the Installation gauge
(inch)
3.6. Unit suspension procedures (Fig. 3-6)
Suspend the main unit as shown in the diagram. Figures given in parentheses represent the dimensions in case of installing optional multi function casement.
1. In advance, set the parts onto the suspension bolts in the order of the washers
(with insulation), washers (without insulation) and nuts (double).
Fit the washer with cushion so that the insulation faces downward.
In case of using upper washers to suspend the main unit, the lower washers (with
insulation) and nuts (double) are to be set later.
2. Lift the unit to the proper height of the suspension bolts to insert the mounting
plate between washers and then fasten it securely.
3. When the main unit can not be aligned against the mounting hole on the ceiling, it
is adjustable owing to a slot provided on the mounting plate.
Make sure that step A is performed within 17-22 mm, 11/16-7/8 inch. Damage could result by failing to adhere to this range. (Fig. 3-7)
Fig. 3-6
A Main unit B Ceiling C Gauge D Ceiling opening dimensions
Fig. 3-7
Caution:
Use the top half of the box as a protective cover to prevent dust or debris from getting inside the unit prior to installation of the decorative cover or when ap­plying ceiling materials.
3.7. Confirming the position of main unit and tighten­ing the suspension bolts (Fig. 3-8)
A Main unit
4
Fig. 3-8
B Ceiling C Installation template (top of the
package)
D Screw with washer (Accessory)
Using the gauge attached to the grille, ensure that the bottom of the main unit is
properly aligned with the opening of the ceiling. Be sure to confirm this, otherwise condensation may form and drip due to air leakage etc.
Confirm that the main unit is horizontally levelled, using a level or a vinyl tube filled
with water.
After checking the position of the main unit, tighten the nuts of the suspension bolts
securely to fasten the main unit.
The installation template (top of the package) can be used as a protective sheet to
prevent dust from entering the main unit when the grilles are left unattached for a while or when the ceiling materials are to be lined after installation of the unit is finished.
* As for the details of fitting, refer to the instructions given on the Installation template.
Page 5
B
90° ±0.5°
øA
R1/64 to R1/32
A
45°±2°
4. Installing the refrigerant piping
C
D
4.1. Precautions
4.1.1. For devices that use R410A refrigerant
Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil applied to the flared sections.
Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses specified in the table to the below. Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sulfuric com­pounds, oxidants, debris, or dust.
Warning: When installing or moving the air conditioner, use only the specified refriger­ant (R410A) to charge the refrigerant lines. Do not mix it with any other refriger­ant and do not allow air to remain in the lines. Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards.
A12, A18 A24, A30, A36, A42
Liquid pipe
Gas pipe
Do not use pipes thinner than those specified above.
ø6.35 mm, ø1/4 inch ø9.52 mm, ø3/8 inch
thickness 0.8 mm, 1/32 inch thickness 0.8 mm, 1/32 inch
ø12.7 mm, ø1/2 inch ø15.88 mm, ø5/8 inch
thickness 0.8 mm, 1/32 inch thickness 1.0 mm, 3/64 inch
Fig. 4-1
A Flare cutting dimensions
Copper pipe O.D. Flare dimensions
(mm, inch) øA dimensions (mm, inch)
ø6.35, 1/4 8.7 - 9.1, 11/32 - 23/64 ø9.52, 3/8 12.8 - 13.2, 1/2 - 33/64 ø12.7, 1/2 16.2 - 16.6, 41/64 - 21/32
ø15.88, 5/8 19.3 - 19.7, 49/64 - 25/32
(inch)
4.2. Connecting pipes (Fig. 4-1)
When commercially available copper pipes are used, wrap liquid and gas pipes
with commercially available insulation materials (heat-resistant to 100 °C, 212 °F or more, thickness of 12 mm, 1/2 inch or more).
The indoor parts of the drain pipe should be wrapped with polyethylene foam insu-
lation materials (specific gravity of 0.03, thickness of 9 mm, 23/64 inch or more).
Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening
flare nut.
Use two wrenches to tighten piping connections.
Use refrigerant piping insulation provided to insulate indoor unit connections. Insu-
late carefully.
B Flare nut tightening torque
Copper pipe O.D. Flare nut O.D. Tightening torque
(mm, inch) (mm, inch) (N·m, ft·lbs)
ø6.35, 1/4 17, 43/64 14 - 18, 10 -13 ø9.52, 3/8 22 ø12.7, 1/2 26
ø15.88, 5/8 29
C Apply refrigerating machine oil over the entire flare seat surface.
D Use correct flare nuts meeting the pipe size of the outdoor unit.
Available pipe size
A12, A18
Liquid side
Gas side –ø15.88
? : Factory flare nut attachment to the heat-exchanger.
ø6.35
–ø9.52
ø12.7
––
, 7/8 , 1-3/64 , 1-9/64
A24, A30,
A36, A42
34 - 42 49 - 61 68 - 82
, 25 - 30 , 35 - 44 , 49 - 59
5
Page 6
4. Installing the refrigerant piping
B
D
E
A
C
F
J
H
I
B,C
F
G
Max. 65ft
5 to 7ft
A
B
C
B
M
L
K
D
E
D
H
I
G
D
F
F
F
Max. 6inch
J
F
G
7/16
111
B
A
C
C
F
K
H
DEE
I
J
C
Fig. 4-2
5. Drainage piping work
A Refrigerant pipe and insulating ma-
terial
B Pipe cover (large) C Pipe cover (small) D Refrigerant pipe (gas) E Refrigerant pipe (liquid) F Band G Cross-sectional view of connection H Pipe I Insulating material J Squeeze
4.3. Indoor unit (Fig. 4-2)
Heat insulation for refrigerant pipes:
1 Wrap the enclosed large-sized pipe cover around the gas pipe, making sure that
the end of the pipe cover touches the side of the unit.
2 Wrap the enclosed small-sized pipe cover around the liquid pipe, making sure
that the end of the pipe cover touches the side of the unit.
3 Secure both ends of each pipe cover with the enclosed bands. (Attach the bands
20 mm from the ends of the pipe cover.)
After connecting the refrigerant piping to the indoor unit, be sure to test the pipe connections for gas leakage with nitrogen gas. (Check that there is no refrigerant leakage from the refrigerant piping to the indoor unit.)
4.4. For twin/triple combination
Refer to the outdoor unit installation manual.
5.1. Drainage piping work (Fig. 5-1)
Use VP25 (O.D. ø32 mm, 1-1/4 inch PVC TUBE) for drain piping and provide 1/100 or more downward slope.
Be sure to connect the piping joints using a polyvinyl type adhesive.
Observe the figure for piping work.
Use the included drain hose to change the extraction direction.
1 Correct piping 2 Wrong piping
A Insulation (9 mm, 3/8 inch or more) B Downward slope (1/100 or more)
Grouped piping
D O.D. ø32 mm, 1-1/4 inch PVC TUBE E Make it as large as possible F Indoor unit G Make the piping size large for grouped piping. H Downward slope (1/100 or more)
C Support metal K Air bleeder L Raised M Odor trap
I O.D. ø38 mm, 1-1/2 inch PVC TUBE for
grouped piping. (9 mm, 3/8 inch or more insulation)
J Up to 85 cm, 33-7/16 inch
6
Fig. 5-1
(inch)
Fig. 5-2
1. Connect the drain socket (supplied with the unit) to the drain port. (Fig. 5-2)
(Affix the tube using PVC adhesive then secure it with a band.)
2. Install a locally purchased drain pipe (PVC pipe, O.D. ø32 mm, 1-1/4 inch).
(Affix the pipe using PVC adhesive then secure it with a band.)
3. Insulate the tube and pipe. (PVC pipe, O.D. ø32 mm, 1-1/4 inch and socket)
4. Check that drain flows smoothly.
5. Insulate the drain port with insulating material, then secure the material with a
band. (Both insulating material and band are supplied with the unit.)
A Unit B Insulating material C Band D Drain port (transparent) E Insertion margin F Matching
G Drain pipe
(O.D. ø32 mm, 1-1/4 inch PVC TUBE)
H Insulating material (purchased locally) I Transparent PVC pipe J O.D. ø32 mm, 1-1/4 inch PVC TUBE
(Slope 1/100 or more)
K Drain socket
Page 7
6. Electrical work
A
E
D
J,K
B
C
I
G
F
H
L2GRL1
S3S2S1
12
S1
S2
L1 L2
GR
1 2
S1 S2 S3
S3
AB
C
D
E
F
G
S1 S2
L1 L2
GR
1 2
S1 S2 S3
1 2
S1 S2 S3
S3
AB
C
E
FF
GG
D
6.1. Indoor unit (Fig. 6-1)
1. Remove the two electrical wiring service panels.
2. Wire the power cable and control cable separately through the respective wiring
Do not allow slackening of the terminal screws.
Leave excess cable so that the electrical box can be suspended below the unit
Fig. 6-1
6.1.1. Indoor unit power supplied from outdoor unit (A-control application)
The following connection patterns are available. The outdoor unit power supply patterns vary on models.
1:1 System
entries given in the diagram.
during servicing. (Approx. 50 to 100 mm, 2 to 4 inch)
A Entry for control cable B Entry for power C Clamp D Service panel for indoor controller switch setting E Service panel for electrical wiring F Power supply terminals (separate indoor/outdoor unit power supplies,
K-control application)
G Indoor / Outdoor unit connecting terminals H Remote controller connector
I Secure with the clamp J Intake sensor K Holder
A Outdoor unit power supply B Wiring circuit breaker or isolating switch C Outdoor unit D Indoor unit/outdoor unit connecting cords E Remote controller F Indoor unit G Indoor unit earth
* Affix a label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Simultaneous twin system
* Affix a label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Indoor unit model Indoor unit power supply Minimum circuit ampacity Maximum rating of overcurrent protective device
Indoor unit power supply Indoor unit power supply earth Indoor unit-Outdoor unit *1
Wiring
Indoor unit earth
Wire No. × size
Remote controller-Indoor unit *2 Indoor unit L1-L2 *3 Indoor unit-Outdoor unit S1-S2 *3 Indoor unit-Outdoor unit S2-S3 *3
rating
Circuit
Remote controller-Indoor unit *3
*1. Max. 50 m, 165 ft *2. The 10 m, 30 ft wire is attached in the remote controller accessory. Max. 500 m, 1500 ft *3. The figures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulataed by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Use copper supply wires.
3. Use wires rated 300V or more for the power supply cables and the indoor unit/outdoor unit connecting cables.
4. Install an earth longer than other cables.
PLA-A12, 18, 24, 30 PLA-A36, 42
––
1A 2A
15A 15A
–– ––
3 × AWG16 (polar) 3 × AWG16 (polar)
1 × Min. AWG16 1 × Min. AWG16
2 × AWG22 (Non-polar) 2 × AWG22 (Non-polar)
––
AC 208/230 V AC 208/230 V
DC24 V DC24 V DC12 V DC12 V
A Outdoor unit power supply B Wiring circuit breaker or isolating switch C Outdoor unit D Indoor unit/outdoor unit connecting cords E Remote controller F Indoor unit G Indoor unit earth
7
Page 8
6. Electrical work
S1 S2
L1 L2
GR
GR
1 2
L1 L2
S1 S2 S3
S3
A
B
C
G
D
B
E
F
ON OFF 1 2
(SW8)
3
S1 S2
L1
GR
L2
1 2
L1 L2 GR GR
S1 S2 S3
1 2
L1 L2
S1 S2 S3
S3
AB
C
D
GB
E
FF
S1 S2 S3
L1 L2 GR
BLUE
BLUE
YELLOW
YELLOW
CND
CND
ORANGE
CND
ORANGE
S1 S2 S3
L1 L2
GR
YELLOW
BLUE
BLUE
YELLOW
CND
6.1.2. Separate indoor unit/outdoor unit power supplies (A-control application)
The following connection patterns are available. The outdoor unit power supply patterns vary on models.
1:1 System
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Simultaneous twin system
A Outdoor unit power supply B Wiring circuit breaker or isolating switch C Outdoor unit D Indoor unit/outdoor unit connecting cords E Remote controller F Indoor unit G Indoor unit power supply
A Outdoor unit power supply B Wiring circuit breaker or isolating switch C Outdoor unit D Indoor unit/outdoor unit connecting cords E Remote controller F Indoor unit G Indoor unit power supply
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
If the indoor and outdoor units have separate power supplies, refer to the table at the below. Change the indoor unit electrical box wiring refering to the figure in the right and the DIP switch settings of the outdoor unit control board.
Indoor unit specifications Indoor unit electrical box connector con­nection change
Label affixed near each wiring diagram for the indoor and outdoor units
Required
Required
Outdoor unit DIP switch settings (when using separate indoor unit/outdoor unit power supplies only)
* There are three types of labels (labels A, B, and C). Affix the appropriate labels to
the units according to the wiring method.
Indoor unit model Indoor unit power supply Minimum circuit ampacity Maximum rating of overcurrent protective device
Indoor unit power supply Indoor unit power supply earth Indoor unit-Outdoor unit *1
Wiring
Indoor unit earth
Wire No. × size
Remote controller-Indoor unit *2 Indoor unit L1-L2 *3 Indoor unit-Outdoor unit S1-S2 *3 Indoor unit-Outdoor unit S2-S3 *3
rating
Circuit
Remote controller-Indoor unit *3
*1. Max. 50 m, 165 ft *2. The 10 m, 30 ft wire is attached in the remote controller accessory. Max. 500 m, 1500 ft *3. The figures are NOT always against the ground.
PLA-A12, 18, 24, 30 PLA-A36, 42
Single 208/230 V, 60 Hz Single 208/230 V, 60 Hz
1 A 2A
15A 15A 2 × Min. AWG16 2 × Min. AWG16 1 × Min. AWG16 1 × Min. AWG16
2 × AWG22 (polar) 2 × AWG22 (polar)
2 × AWG22 (Non-polar) 2 × AWG22 (Non-polar)
––
AC 208/230 V AC 208/230 V
––
DC24 V DC24 V DC12 V DC12 V
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Use copper supply wires.
3. Use wires rated 300V or more for the power supply cables.
4. Install an earth longer than other cables.
8
Connectors (connections when shipped from the factory are for indoor unit power supplied from outdoor unit)
Indoor unit
control board
Indoor unit power supplied from outdoor unit (when shipped from factory)
If the indoor and outdoor units have separate power supplies, change the connections of the connectors as shown in the following figure.
Connectors
Indoor unit
control board
Separate indoor unit/outdoor unit power supplies
Page 9
6. Electrical work
S1 S2
L1 L2
GR
GR
1 2
L1 L2
S1 S2 S3
S3
A
B
C
H
D
B
E
F
S1 S2
L1 L2
GR
GR
1 2
L1 L2
S1 S2 S3
S3
A
B
C
H
D
B
E
G
1
SW5
Set the DIP switch of the indoor unit control board.
SW5–1 : ON SW5–2, 3 : OFF
2
3
1
SW5
Set the DIP switch of the indoor unit control board.
SW5–1, 2 : ON SW5–3 : OFF
2
3
S1 S2
L1
GR
L2
1 2
L1 L2 GR GR
S1 S2 S3
1 2
L1 L2
S1 S2 S3
S3
AB
C
D
HB
E
FG
S1 S2
1 2
S1 S2 S3
1 2
S1 S2 S3
S3
AB
C
D
HB
E
JK
L1 L2 GR
L1 L2 GR
L1 L2 GR
1
SW5
Set the DIP switch of the indoor unit control board.
SW5–1 : ON SW5–2 : OFF SW5–3 : OFF
2
3
1
SW5–1 : ON SW5–2 : OFF SW5–3 : ON
2
3
G
Main indoor
H
Sub indoor
1
SW5
Set the DIP switch of the indoor unit control board.
SW5–1 : ON SW5–2 : ON SW5–3 : OFF
2
3
1
SW5–1 : ON SW5–2 : ON SW5–3 : ON
2
3
K
Main indoor
L
Sub indoor
S1 S2 S3
L1 L2 GR
BLUE
BLUE
YELLOW
YELLOW
CND
CND
ORANGE
CN3C
BLUE
CN30
BLACK
S1 S2 S3
L1 L2 GR
BLUE
YELLOW
YELLOW
BLUE
CND
CND
ORANGE
CN3C
BLUE
CN30
CN30 CN30 CN3C
CN3C
BLACK
INDOOR UNIT CONTROL BOARD
INDOOR UNIT CONTROL BOARD
Connectors
To change to the K-control, make sure to change the connectors as shown in the figure.
BLUE
BLUE
BLACK
BLACK
BLUE
BLUE
BLACK
BLACK
6.1.3. K-control application
The following connection patterns are available. The outdoor unit power supply patterns vary on models.
1:1 System
<For heat pump models>
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
<For heat pump models>
<For cooling only models>
Simultaneous twin system
<For cooling only models>
A Outdoor unit power supply B Wiring circuit breaker or isolating switch C Outdoor unit D Indoor unit/outdoor unit connecting cords E Remote controller F Indoor unit <For heat pump models> G Indoor unit <For cooling only models> H Indoor unit power supply
A Outdoor unit power supply B Wiring circuit breaker or isolating switch C Outdoor unit D Indoor unit/outdoor unit connecting cords E Remote controller F Main indoor unit <For heat pump models> G Sub indoor unit <For heat pump models> H Indoor unit power supply J Main indoor unit < K Sub indoor unit <
For cooling only models
For cooling only models
> >
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
To change to K-control, set the DIP switch (SW5) of the indoor unit control board as shown in the above figure and change the electric wiring of the indoor unit as shown in the right figure. Set up Dip switch after turning off Power supply switch. Be careful that setting the DIP switch (SW5) of the indoor unit control board varies between the heat pump models and cooling models of the outdoor unit.
DIP switch (SW5)
SW5–1A–CONTROL K–CONTROL SW5–2 heat pump models cooling only models SW5–3 MAIN SUB
* There are three types of labels (labels A, B, and C). Affix the appropriate labels to
the units according to the wiring method.
Indoor unit model Indoor unit power supply Minimum circuit ampacity Maximum rating of overcurrent protective device
*1. Max. 50 m, 165 ft *2. The 10 m, 30 ft wire is attached in the remote controller accessory. Max. 500 m, 1500 ft *3. The figures are NOT always against the ground.
Notes: 1. Wiring size must comply with the applicable local and national code.
Indoor unit power supply Indoor unit power supply earth
Indoor unit-Outdoor unit *1
Wiring
Indoor unit earth
Wire No. × size
Remote controller-Indoor unit *2 Indoor unit L1-L2 *3 Indoor unit-Outdoor unit S1-S2 *3
Circuit
rating
Indoor unit-Outdoor unit S1-S3 *3 Remote controller-Indoor unit *3
2. Use copper supply wires.
3. Use wires rated 300V or more for the power supply cables.
4. Install an earth longer than other cables.
OFF ON
Dip switch SW5-2 and SW5-3 is effective only
}
when Dip switch SW5-1 (K-CONTROL) is ON.
PLA-A12, 18, 24, 30 PLA-A36, 42
Single 208/230 V, 60 Hz Single 208/230 V, 60 Hz
1 A 2A
15A 15A 2 × Min. AWG16 2 × Min. AWG16 1 × Min. AWG16 1 × Min. AWG16
H/P: 3 × AWG22 (polar) H/P: 3 × AWG22 (polar)
C/O: 2 × AWG22 (polar) C/O: 2 × AWG22 (polar)
––
2 × AWG22 (Non-polar) 2 × AWG22 (Non-polar)
AC 208/230 V AC 208/230 V
DC12V DC12V DC12V DC12V DC12V DC12V
9
Page 10
A
6. Electrical work
MODEL SELECT
MODEL SELECT
1-3/16
1-37/64
1-3/16
1-3/16
4-23/32
3-9/32
A
B
C
F
A
H
C
D
E
G
I
I
I
H
B
AB TB6
B
D
B
1
C
A
2
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
2,4
3
A
J
H
Fig. 6-2
B-1. B-2.
Fig. 6-3
Fig. 6-4
(inch)
6.2. Remote controller
6.2.1. For wired remote controller
1) Installing procedures
(1) Select an installing position for the remote controller. (Fig. 6-2) The temperature sensors are located on both remote controller and indoor unit.
s Procure the following parts locally:
Two piece switch box Thin copper conduit tube Lock nuts and bushings
A Remote controller profile B Required clearances surrounding the remote controller C Installation pitch
(2) Seal the service entrance for the remote controller cord with putty to prevent pos-
sible invasion of dew drops, water, cockroaches or worms. (Fig. 6-3)
A For installation in the switch box: B For direct installation on the wall select one of the following:
Prepare a hole through the wall to pass the remote controller cord (in order to run the remote controller cord from the back), then seal the hole with putty.
Run the remote controller cord through the cut-out upper case, then seal the cut­out notch with putty similarly as above.
B-1. To lead the remote controller cord from the back of the controller: B-2. To run the remote controller cord through the upper portion:
(3) For direct installation on the wall
C Wall D Conduit E Lock nut F Bushing G Switch box H Remote controller cord I Seal with putty J Wood screw
2) Connecting procedures (Fig. 6-4)
1 Connect the remote controller cord to the terminal block.
A To TB5 on the indoor unit B TB6 (No polarity)
3) Two remote controllers setting
If two remote controllers are connected, set one to “Main” and the other to “Sub”. For setting procedures, refer to Function selection of remote controller in the operation manual for the indoor unit.
10
Fig. 6-5
6.2.2. For wireless remote controller
1) Installation area
Area in which the remote controller is not exposed to direct sunshine.
Area in which there is no nearby heating source.
Area in which the remote controller is not exposed to cold (or hot) winds.
Area in which the remote controller can be operated easily.
Area in which the remote controller is beyond the reach of children.
2) Installation method (Fig. 6-5)
1 Attach the remote controller holder to the desired location using two tapping screws. 2 Place the lower end of the controller into the holder.
A Remote controller B Wall C Display panel D Receiver
The signal can travel up to approximately 7 meters, 23 ft (in a straight line) within 45 degrees to both right and left of the center line of the receiver.
3) Setting (Fig. 6-6)
1 Insert batteries.
Fig. 6-6
2 Press the SET button with something sharp at the end.
blinks and Model No. is lighted.
3 Press the temp
button to set the Model No.
4 Press the SET button with something sharp at the end.
and Model No. are lighted for three seconds, then turned off.
Indoor Outdoor A Model No.
PLA, PCA, PKA (A12, A18)
PKA (A24, A30, A36)
heat pump models 001
cooling only models 033
heat pump models 003
cooling only models 035
Page 11
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
A
B
D
C
G
E
F
1
2
4
3
4
1
1
2
MODEL SELECT
min
CHECK
CHECK
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
CHECK
E
C,D
F
A
B
CHECK
CHECK
6. Electrical work
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
1,4
3
A
2
CHECK
CHECK
h
min
h
h
Fig. 6-7
Fig. 6-8
1
Mode number
2
Setting number
3
Refrigerant address
4
Unit number
4) Assigning a remote controller to each unit (Fig. 6-7)
Each unit can be operated only by the assigned remote controller. Make sure each pair of an indoor unit PC board and a remote controller is assigned to the same pair No.
5) Wireless remote controller pair number setting operation
1 Press the SET button with something sharp at the end.
Start this operation from the status of remote controller display turned off.
blinks and Model No. is lighted.
2 Press the
button twice continuously.
Pair No. “0” blinks.
3 Press the temp
button to set the pair number you want to set.
4 Press the SET button with something sharp at the end.
Set pair number is lighted for three seconds then turned off.
A Pair No. of wireless remote controller Indoor PC board
0 Factory setting 1 Cut J41 2 Cut J42
3–9 Cut J41, J42
6.3. Function settings
6.3.1. Function setting on the unit (Selecting the unit functions)
1) For wired remote controller (Fig. 6-8)
Changing the power voltage setting
Be sure to change the power voltage setting depending on the voltage used. 1 Go to the function setting mode.
Switch OFF the remote controller. Press the A and B buttons simultaneously and hold them for at least 2 seconds. FUNCTION will start to flash.
2 Use the C button to set the refrigerant address (3) to 00. 3 Press D and [--] will start to flash in the unit number (4) display. 4 Use the C button to set the unit number (4) to 00. 5 Press the E MODE button to designate the refrigerant address/unit number. [--]
will flash in the mode number (1) display momentarily.
6 Press the F buttons to set the mode number (1) to 04. 7 Press the G button and the current set setting number (2) will flash.
Use the F button to switch the setting number in response to the power supply voltage to be used. Power supply voltage
8 Press the MODE button E and mode and the setting number (1) and (2) will
change to being on constantly and the contents of the setting can be confirmed.
9 Press the FILTER A and TEST RUN B buttons simultaneously for at least two
seconds. The function selection screen will disappear momentarily and the air conditioner OFF display will appear.
230 V : setting number = 1 208 V : setting number = 2
2) For wireless remote controller (Fig. 6-9)
1
2
Changing the power voltage setting
Be sure to change the power voltage setting depending on the voltage used. 1 Go to the function select mode
Press the
button F twice continuously.
(Start this operation from the status of remote controller display turned off.)
is lighted and “00” blinks.
Press the temp
3
4
toward the receiver of the indoor unit and press the
button C once to set “50”. Direct the wireless remote controller
button A.
2 Setting the unit number Press the temp
remote controller toward the receiver of the indoor unit and press the
button C and D to set the unit number “00. Direct the wireless
button B.
3 Selecting a mode Enter 04 to change the power voltage setting using the
C and D buttons.
Direct the wireless remote controller toward the receiver of the indoor unit and press the
button A.
Current setting number: 1 = 1 beep (one second)
2 = 2 beeps (one second each) 3 = 3 beeps (one second each)
4 Selecting the setting number
Fig. 6-9
Use the
C and D buttons to change the power voltage setting to 01 (240 V).
Direct the wireless remote controller toward the sensor of the indoor unit and press
button A.
the 5 To select multiple functions continuously
Repeat steps 3 and 4 to change multiple function settings continuously. 6 Complete function selection Direct the wireless remote controller toward the sensor of the indoor unit and press
the
button E.
Note: Whenever changes are made to the function settings after installation or main­tenance, be sure to record the changes with a mark in the “Setting” column of the Function table.
6.3.2. Function setting on the remote controller
Refer to the indoor unit operation manual.
11
Page 12
6. Electrical work
TEST RUN
TEST RUN
MODE
MODE
FAN
VANE
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
TEST RUN
5
7
A
3,4
2
6
˚C
˚C
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
TEST RUN COOL, HEAT
A
F
C
E
D
B
M
IH
G
Function table
Select unit number 00
Mode Power failure automatic recovery
Indoor temperature detecting
LOSSNAY connectivity
Power voltage
Auto mode (only for PUZ)
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode Filter sign
Fan speed
No. of air outlets
Installed options (high-performance filter)
Up/down vane setting
Energy saving air flow (Heating mode)
*1 When the power supply returns, the air conditioner will start 3 minutes later.
Settings Not available Available *1 Indoor unit operating average Set by indoor units remote controller Remote controllers internal sensor Not Supported Supported (indoor unit is not equipped with outdoor-air intake) Supported (indoor unit is equipped with outdoor-air intake) 230 V 208 V Energy saving cycle automatically enabled Energy saving cycle automatically disabled
Settings 100Hr 2500Hr No filter sign indicator Standard (PLA)/Silent (PCA) High ceiling 1
(PLA)/Standard (PCA) High ceiling 2 (PLA)/High ceiling (PCA) 4 directions 3 directions 2 directions Not supported Supported Equipped with vanes (vanes angle setup 3) Equipped with vanes (vanes angle setup 1) Equipped with vanes (vanes angle setup 2) Disabled Enabled
Mode no. Setting no.
01
1 2 1
02 2
3 1
03 2
3
04
05
1 2 1 2
Mode no. Setting no.
1
07 2
3 1
08 2
3 1
09 2
3
10
1 2 1
11
2 3
12
1 2
Initial setting
Initial setting
setting
setting
7. Test run
7.1. Before test run
s After completing installation and the wiring and piping of the indoor and outdoor
units, check for refrigerant leakage, looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply.
s Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0 M
Fig. 7-1
12
Fig. 7-2
ΩΩ
Ω.
ΩΩ
A ON/OFF button B Test run display C Indoor temperature liquid line
temperature display
D ON/OFF lamp E Power display F Error code display
Test run remaining time dis­play
G Set temperature button H Mode selection button I Fan speed button M TEST button
s Do not carry out this test on the control wiring (low voltage circuit) termi-
nals. Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0 M
ΩΩ
Ω.
ΩΩ
Insulation resistance
7.2. Test run
The following 3 methods are available.
7.2.1. Using wired remote controller (Fig. 7-1)
1 Turn on the power at least 12 hours before the test run. 2 Press the [TEST] button twice. TEST RUN liquid crystal display 3 Press the [Mode selection] button. Make sure that wind is blown out. 4 Press the [Mode selection] button and switch to the cooling (or heating) mode.
Make sure that cold (or warm) wind is blown out.
5 Press the [Fan speed] button. Make sure that the wind speed is switched. 6 Check operation of the outdoor unit fan. 7 Release test run by pressing the [ON/OFF] button. Stop 8 Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error occurs can be registered in the remote controller. The telephone number will be displayed when an error occurs. For registration procedures, refer to the opera­tion manual for the indoor unit.
7.2.2. Using wireless remote controller (Fig. 7-2)
1 Turn on the power to the unit at least 12 hours before the test run. 2 Press the
(Start this operation from the status of remote controller display turned off.)
A
3 Press the
cool air is blown out from the unit.
4 Press the
warm air is blown out from the unit.
5 Press the
6 Press the 7 Press the ON/OFF button to stop the test run.
Note:
Point the remote controller towards the indoor unit receiver while following steps 2 to 7.
It is not possible to run the in FAN, DRY or AUTO mode.
button twice continuously.
and current operation mode are displayed.
button to activate mode, then check whether
button to activate mode, then check whether
button and check whether fan speed changes.
button and check whether the auto vane operates properly.
Page 13
CHECK
CHECK
h
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
CHECK
2
4
A
3
B
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
C
B
A
B
F
E
E
D
7. Test run
7.2.3. Using SW4 in outdoor unit
Refer to the outdoor unit installation manual.
7.3. Self-check
7.3.1. Wired remote controller (Fig. 7-3)
1 Turn on the power. 2 Press the [CHECK] button twice. 3 Set refrigerant address with [TEMP] button if system control is used. 4 Press the [ON/OFF] button to stop the self-check.
A CHECK button B Refrigerant address C TEMP. button D IC: Indoor unit
OC: Outdoor unit
E Check code F Unit address
7.3.2. Wireless remote controller (Fig. 7-4)
1 Turn on the power. 2 Press the
(Start this operation from the status of remote controller display turned off.)
A
Fig. 7-4
B 00 begins to blink.
3 While pointing the remote controller toward the unit’s receiver, press the
button. The check code will be indicated by the number of times that the buzzer sounds from the receiver section and the number of blinks of the operation lamp.
Fig. 7-3
4 Press the ON/OFF button to stop the self-check.
Refer to the following tables for details on the check codes. (Wireless remote controller) [Output pattern A]
Beeper sounds
OPERATION INDICATOR lamp flash pattern
Beep
Self-check starts (Start signal received)
Beep Beep Beep Beep Beep Beep
1st2nd3
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates the check code in the following table (i.e., n=5 for “P5”)
rd
th
n
On
0.5 sec.
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
1st2
Number of flashes/beeps in pattern indicates the check code in the following table
[Output pattern B]
Beeper sounds
OPERATION INDICATOR lamp flash pattern
Beep Beep Beep Beep Beep Beep Beep
th
n
On
0.5 sec.
Self-check starts (Start signal received)
1st2nd3
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates the check code in the following table (i.e., n=5 for U2)
rd
[Output pattern A] Errors detected by indoor unit
Wireless remote controller
Wired remote
controller
Beeper sounds/OPERATION Symptom Remark
INDICATOR lamp flashes Check code
(Number of times)
1 P1 Intake sensor error 2 P2, P9 Pipe (Liquid or 2-phase pipe) sensor error 3 E6, E7 Indoor/outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing/Overheating safeguard operation 7 EE Communication error between indoor and outdoor units 8 P8 Pipe temperature error
9 E4 Remote controller signal receiving error 10 –– 11 –– 12 Fb Indoor unit control system error (memory error, etc.)
No sound – – No corresponding
button twice.
begins to light.
nd
· · · Repeated
1st2
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates the check code in the following table
nd
· · · Repeated
13
Page 14
7. Test run
A
B
C
D
E
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wireless remote controller
Beeper sounds/OPERATION Symptom Remark
INDICATOR lamp flashes Check code
(Number of times)
1 E9 Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit) 2 UP Compressor overcurrent interruption 3 U3, U4 Open/short of outdoor unit thermistors 4 UF Compressor overcurrent interruption (When compressor locked) 5 U2 Abnormal high discharging temperature/49C worked/insufficient refrigerant 6 U1, Ud Abnormal high pressure (63H worked)/Overheating safeguard operation 7 U5 Abnormal temperature of heat sink 8 U8 Outdoor unit fan safeguard stop
9 U6 Compressor overcurrent interruption/Abnormal of power module 10 U7 Abnormality of super heat due to low discharge temperature 11 U9, UH Abnormality such as overvoltage or voltage shortage and abnormal synchronous
12 –– 13 –– 14 Others Other errors (Refer to the technical manual for the outdoor unit.)
*1 If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not come on,
there are no error records.
*2 If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm the self-check start signal was received, the
specified refrigerant address is incorrect.
On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit. Blink of operation lamp
On wired remote controller Check code displayed in the LCD.
If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
Wired remote controller LED 1, 2 (PCB in outdoor unit)
PLEASE WAIT
PLEASE WAIT Error code
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).
Wired remote
controller
For about 2 minutes following power-on
After about 2 minutes has expired following power-on
signal to main circuit/Current sensor error
Symptom
After LED 1, 2 are lighted, LED 2 is turned off, then only LED 1 is lighted. (Correct operation)
Only LED 1 is lighted. LED 1, 2 blink.
Only LED 1 is lighted. LED 1 blinks twice, LED 2 blinks once.
For details, check the LED display of the outdoor controller board.
Cause
For about 2 minutes following power-on, operation of the remote controller is not possible due to system start-up. (Cor­rect operation)
Connector for the outdoor units protection device is not con­nected.
Reverse or open phase wiring for the outdoor units power terminal block (L1, L2, GR)
Incorrect wiring between indoor and outdoor units (incorrect polarity of S1, S2, S3)
Remote controller wire short
On the wireless remote controller with condition above, following phenomena takes place.
No signals from the remote controller are accepted.
OPE lamp is blinking.
The buzzer makes a short pipng sound.
Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED 1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED is always lit. LED 2 (power for remote controller) Indicates whether power is supplied to the remote controller. This LED lights only in the case of the
LED 3 (communication between indoor and outdoor units only Indicates state of communication between the indoor and outdoor units. Make sure that this LED is A-control) always blinking.
indoor unit which is connected to the outdoor unit refrigerant address “0”.
7.4. Check of drainage (Fig. 7-5)
During the test run, ensure the water is being properly drained out and that no water is leaking from joints.
Always check this during installation even if the unit is not required to provide cool-
A Insert the pump end 3 to 5 cm,
1-3/16 to 2 inch
B Cover of water supply inlet C About 1000 cc, 1/4 gal D Water E Drain plug
Fig. 7-5
ing/drying at that time.
Similarly, check the drainage before finishing ceiling installation in a new premises.
(1) Remove the cover of the water supply inlet and add about 1000 cc, 1/4 gal of
water using a water supply pump etc. During this process, be careful not to spray water into the drain pump mechanism.
(2) Confirm that water is being drained out through the drainage outlet, after switch-
ing over from remote control mode to test run mode.
(3) After checking the drainage, ensure that the cover is replaced and the power
supply is isolated.
(4) After confirming the drainage system is functioning, replace the drain plug.
14
Page 15
19/32 to 25/32
A
B
ø20
A
D
C
B
A=11/16
+3/16
0
B
A
C
1
1
D
E
2
F
G
F
B
1
8. System control
Refer to the outdoor unit installation manual.
9. Installing the grille
1
2 3
4 5
6
Fig. 9-1
Fig. 9-2
9.1. Checking the contents (Fig. 9-1)
This kit contains this manual and the following parts.
1 Grille 1 2 Screw with captive washer 4 M5 × 0.8 × 25 3 Gauge 1 (Divided into four parts) 4 Fastener 2 5 Screw 4 4 × 8 6 Wired remote controller 1 for PLP-42AAMD
Accessory name Q’ty Remark
950 × 950 (mm), 37 - 3/8 × 37 - 3/8 inch
9.2. Preparing to attach the grille (Fig. 9-2)
With the gauge 3 supplied with this kit, adjust and check the positioning of the unit
relative to the ceiling. If the unit is not properly positioned relative to the ceiling, it may allow air leaks or cause condensation to collect.
Make sure that the opening in the ceiling is within the following tolerances:
860 × 860 - 910 × 910 mm, 33 - 7/8 × 33 - 7/8 to 35 - 13/16 × 35 - 13/16 inch.
Make sure that step A is performed within 17-22 mm, 11/16-7/8 inch. Damage
could result by failing to adhere to this range.
A Main unit B Ceiling C Gauge 3 (inserted into the unit) D Ceiling opening dimensions
Blowout direction patterns
Blowout direction patterns
Fig. 9-3
Fig. 9-4
4-directional 3-directional
One pattern: 4 patterns: Factory setting One air outlet fully closed
2-directional
6 patterns: Two air outlet fully closed
9.2.1. Removing the intake grille (Fig. 9-3)
Slide the levers in the direction indicated by the arrow 1 to open the intake grille.
Unlatch the hook that secures the grille.
* Do not unlatch the hook for the intake grille.
With the intake grille in the open position, remove the hinge of the intake grille from the grille as indicated by the arrow 2.
9.2.2. Removing the corner panel (Fig. 9-4)
Remove the screw from the corner of the corner panel. Slide the corner panel as indicated by the arrow 1 to remove the corner panel.
A Intake grille B Grille C Intake grille levers D Grille hook
E Hole for the grilles hook F Corner panel G Screw
9.3. Selection of the air outlets
For this grille the discharge direction is available in 11 patterns. Also, by setting the Remote controller to the appropriate settings, you can adjust the air-flow and speed. Select the required settings from the Table according to the location in which you want to install the unit.
1) Decide on the discharge direction pattern.
2) Be sure to set the remote contoller to the appropriate settings, according to the
number of air outlets and the height of the ceiling on which the unit will be in­stalled.
Note: For 3 and 2-directional, please use the air outlet shutter plate (option).
9.4. Installing the grille
A Main unit B Screw with
captive washer
Fig. 9-5
9.4.1. Preparations (Fig. 9-5)
Install the two enclosed screws with washer 2 in the main unit (at the corner drain pipe area and at the opposite corner) as shown in the diagram.
15
Page 16
E
A
D
C
B
CN90
A
C
D
E
F
I
G
H
A
C
D
B
E
A
D
C
B
E
9. Installing the grille
C
B
A
D
B
AD
Fig. 9-6
9.4.2. Temporary installation of the grille (Fig. 9-6)
Temporarily secure the grille using the bell shaped holes by aligning the corner drain pipe area of the main unit with the two holes of the grille that are marked A and B.
* Make sure that the lead wiring of the grille does not get pinched between the
grille and the main unit.
A Main unit B Detailed diagram of installed screw with
washer 2.
C Corner drain pipe area D Screw with washer 2 (for temporary use) E Grille F Screw with washer 2 G Hole A H Hole B I Bell shaped hole
A Ceiling B Main unit C Grille D Make sure that there are no gaps. E Adjust the nut of the main unit using a
wrench, etc.
Fig. 9-7
A Clamp of the main unit B Tube C Connector of the main unit D Grille connector E Fastener
Fig. 9-8
A Button B Vane motor C Up/down vanes D Connector
9.4.3. Securing the grille (Fig. 9-7)
Secure the grille to the main unit by tightening the previously installed two screws (with captive washer) as well as the two remaining screws (with captive washer).
* Make sure that there are no gaps between the main unit and the grille or the
grille and the ceiling.
Fixing gaps between the grille and the ceiling
With the grille attached, adjust the height of the main unit to close the gap.
9.4.4. Wire connection (Fig. 9-8)
Be sure to connect the unit to the connector (white, 10-pole). Next, attach the white glass tube that comes with the main unit so that the tube covers the connector. Close the opening of the glass tube with the fastener.
Make sure that there is no slack in the lead wire at the clamp of the main unit.
Warning: If the connector is not covered with the glass tube, tracking resulting in fire may occur.
9.5. Locking the up/down airflow direction (Fig. 9-9)
The vanes of the unit can be set and locked in up or down orientations depending upon the environment of use.
Set according to the preference of the customer.
The operation of the fixed up/down vanes and all automatic controls cannot be performed using the remote controller. In addition, the actual position of the vanes may differ from the position indicated on the remote controller.
1 Turn off the main power switch.
Injuries and or an electrical shock may occur while the fan of the unit is rotating. 2 Disconnect the connector for the vane motor of the vent that you want to lock.
(While pressing the button, remove the connector in the direction indicated by the
arrow as shown in the diagram.) After removing the connector, insulate it with
tape.
Fig. 9-9
9.6. Installing the wireless sensor (Fig. 9-10)
Pull out the wireless sensor cable from the square hole in the corner panel of the
refrigerant piping section of the main unit.
Feed the cable through the electric component box of the main unit as shown in the
illustration, and then connect it to CN90 on the control board. Adjust the length of the cable so the corner panel can be removed, and then secure the cable with the
16
Fig. 9-10
A Clamp B Cable C Corner panel D Hole E Screw
clamp.
9.7. Check
Make sure that there is no gap between the unit and the grille, or between the grille
and the surface of the ceiling. If there is any gap between the unit and the grille, or between the grille and the surface of the ceiling, it may cause dew to collect.
Make sure that the wires have been securely connected.
Page 17
9. Installing the grille
C
A
B
D
H
G
E
F
TEST
MAINTENANCE
MENU
ON/OFF
COMP ON x10 HOURS
COMP ON x100 TIMES
COMP ON CURRENT (A)
OUTDOOR UNIT H·EXC. TEMP
OUTDOOR UNIT OUTLET TEMP
OUTDOOR UNIT OUTDOOR TEMP
INDOOR UNIT INLET TEMP
INDOOR UNIT H·EXC. TEMP
INDOOR UNIT FILTER USE H
FILTER
TEST
ON/OFF
COOL STABLE MODE
HEAT STABLE MODE
STABLE MODE CANCEL
MODE
FILTER
D
A
C B
9.8. Installing the intake grille (Fig. 9-11)
Note: When reinstalling the corner panels (each with a safety wire attached), connect the other end of each safety wire to the grille using a screw (4 pcs,
××
4
× 8) as shown in the illustration.
××
* If the corner panels are not attached, they may fall off while the unit is operating.
Perform the procedure that is described in 9.2. Preparing to attach the grille in reverse order to install the intake grille and the corner panel.
Multiple units can be installed with grille so that the position of the logo on each corner panel is consistent with the other units regardless of the orientation of the intake grille. Align the logo on the panel according to the wishes of the customer as shown in the diagram to the left. (The position of the grille can be changed.)
A Screw (4 × 8) 5 B Corner panel C Safety wire
Fig. 9-11
D Refrigerant piping of the main unit E Drain piping of the main unit F Position of the corner panel when sent from the factory (logo attached).
* Installation in any position is possible.
G Position of the levers on the intake grille when sent from the factory.
* Although the clips can be installed in any of four positions, the configuration shown here is
recommended.
(It is not necessary to remove the intake grille when maintenance is performed on the elec­tric component box of the main unit.)
H Receiver (Only PLP-6AALM Panel)
10. Easy maintenance function [This function only for A-control]
Display example (Comp discharge temperature 147 °F)
Maintenance mode operation procedures
(1) Press the
activate the maintenance mode.
(2) Press the TEMP. buttons to set the refrigerant address.
(3) Select the data you want to display.
Compressor information
Outdoor unit information
button for three seconds to
Cumulative operation time
Display A
Heat exchanger temperature
Display A
Display A
Display B
ON/OFF number
Comp discharge temperature
By using the maintenance mode, you can display many types of maintenance data on the remote controller such as the heat exchanger temperature and compressor current consumption for the indoor and outdoor units. This function can be used whether the air conditioner is operating or not. During air conditioner operation, data can be checked during either normal operation or maintenance mode stable operation. * This function cannot be used during the test run. * The availability of this function depends on the connecting outdoor unit. Refer to
the brochures.
Operation current
Outdoor ambient temperature
Indoor unit information
Display A
Indoor room temperature
Heat exchanger temperature
Filter operation time
* The filter operation time displayed is the number of hours the filter has been
used since the filter reset was performed.
(4) Press the
(5) The data is displayed in C.
* Repeat steps (2) to (5) to check another date.
(6) Press the
deactivate the maintenance mode.
button.
(Airflow temperature display example)
button for three seconds or press the
Display C
Flashing
Waiting for response
Approx.
10 sec.
147 °F
button to
Stable operation
Using the maintenance mode, the operation frequency can be fixed and the op­eration can be stabilized. If the air conditioner is stopped, use the following pro­cedure to start this operation.
Press the
Display A
Press the
Waiting for stable operation
Display D
button to select the operation mode.
Stable cooling operation
Stable heating operation
button.
Stable operation cancellation
10-20 min.
Stable operation
* You can check the data using steps (3) to (5) of the maintenance mode opera-
tion procedures while waiting for the stable operation.
17
Page 18
This product is designed and intended for use in the residential,
commercial and light-industrial environment.
Please be sure to put the contact address/telephone number on
this manual before handing it to the customer.
BG79U795H01
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Printed in JAPAN
Loading...