13. PARTS LIST········································71
14. OPTIONAL PARTS·····························80
······26
Page 2
1
● PKH-2.5FKA2 ➔ PKH-2.5FKA3
● PKH-3FKA2 ➔ PKH-3FKA3
● PKH-4FKSA2 ➔ PKH-4FKSA3
•NOSE shape has changed.
•UNDER PLATE shape has changed.
•TOP PLATE shape has changed.
•DRAIN PAN shape has changed.
•BOX ASSEMBLY shape has changed.
•The specifications of these power supply voltages have been added: 50Hz 220-230-240V;
TECHNICAL CHANGES
50Hz 380-400-415V.
2
Page 3
2
Air intake
Room air is suctioned
in here.
(Removes dust and dirt from the intake air.)
FilterAir intake grille
Air outletAir outlet
Auto vane
Air flow can be changed to horizontally
by moving the Guide vane to the left or
right.
Guide vane
PART NAMES AND FUNCTIONS
● Indoor Unit
● Remote controller
● Once the operation of the unit is set, subsequent operations can only be performed by pressing the ON/OFF button repeat-
edly.
● Operation buttons
w button
This switches between continuous
operation and the timer operation
button
Press this button to switch the cooler
electronic dry (dehumidify), automatic and heater modes.
i TEMP button
This sets the room temperature. The
temperature setting can be performed in 1°C units.
Setting range :
Cooler 19°C to 30°C
Heater 17°C to 28°C
q button
This sets or switches the current
time, start time and stop time.
CHECK
button
The sets the ventilation fan speed.
FILTER
CHECK MODE
TEST RUN
ON/OFF button
This switches between the operation
and stop modes each time it is
pressed. The lamp on this button
lights during operation.
j button
This adjusts the vertical angle of the
ventilation.
FILTER button
This resets the filter service indication display
The model name of the remote controller is indicated.
PAR-JH241KA(2.5 ~ 4)
PAR-JH150KA(2)
button
This switches the horizontal fan
motion ON and OFF.
(This button does not operate in this
model.)
3
CHECK-TEST RUN button
Only press this button to perform an
inspection check or test operation.
Do not use it for normal operation
Page 4
FILTER
CHECK MODE
CHECK
TEST RUN
● Display
CENTRALLY
CONTROLLED display
This indicates when the unit is con-
trolled by optional features such as
central control type remote controller.
w display
This indicates when the continuous
operation and time operation modes
are set.
It also display the time for the timer
operation at the same time as when
it is set.
OPERATION MODE display
This indicates the operation mode.
STANDBY display
This indicates when the standby
mode is set from the time the sleep
operation starts until the heating air
is discharged.
r display
The current time , start time and stop
time can be displayed in ten second
intervals by pressing the time switch
button. The start time or stop time is
always displayed during the timer
operation.
display
The selected fan speed is displayed.
display
j
This displays the air direction.
In this display example on
the bottom left, a condition
where all display lamps light
is shown for explanation purposes although this differs
from actual operation.
—88°C display
The temperature of the suction air is
displayed during operation. The display range is 8° to 39°C. The display
flashes 8°C when the actual temperature is less than 8° and flashes
39°C when the actual temperature is
greater than 39°C.
Operation lamp
This lamp lights during operation,
goes off when the unit stops and
flashes when a malfunction occurs.
DEFROST display
This indicates when the defrost oper-
ation is performed.
FILTER
This lamp lights when the filter need
to be cleaned.
display
CHECK MODE
TEST RUN
This display lights in the check mode
or when a test operation is performed.
display
CHECK display
This indicates when a malfunction
has occurred in the unit which should
be checked.
—88°C display
This displays the selected setting
temperature.
Caution
● Only the display lights when the unit is stopped and power supplied to the unit.
● When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a
malfunction.
● When the central control remote control unit, which is sold separately, is used the ON-OFF button, button and i
TEMP button do not operate.
● “NOT AVAILABLE” is displayed when the button is pressed. This indicates that this room unit is not equipped with.
Display
This lamp lights when electricity is
supplied to the unit.
The unit of pressure has been changed to MPa on the international system of unit (SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa) = 10.2(kg/FF)
18
Page 19
4. STANDARD OPERATION DATA 60Hz
PKH-2.5FKA
PKH-2.5FKA3
Cooling
7,000
3.01
PKH-2.5FKA2
PKH-2.5FKA3
1.60
220
0.44
PUH-2.5NKA
PUH-2.5NKA2
1.60
220
13.50
2.12
(21.6)
0.52
(5.3)
78.3
54.2
5.8
5
27
19
14
35
24
0.79
0.11
Service Ref.
Mode
Total
Capacity
Input
Indoor unit Service Ref.
Phase, Hz
Volts
Amperes
Outdoor unit Service Ref.
Electrical circuit
Phase, Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Refrigerant circuit
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Indoor side
Intake air temperature
side
Outdoor
SHF
BF
D.B.
W.B.
D.B.
D.B.
W.B.
W
KW
V
A
V
A
Mpa
(kgf/f)
Mpa
(kgf/f)
˚C
˚C
˚C
m
˚C
˚C
˚C
˚C
˚C
PKH-2FKA
Cooling
5,800
2.49
PKH-2FKA3
1.60
220
0.37
PUH-2NKA
PUH-2NKA2
1.60
220
11.07
1.98
(20.2)
0.41
(4.2)
70.2
51.8
2.4
5
27
19
13
35
24
0.70
0.19
3
Heating
6,600
2.53
0.37
1
11.2
2.05
(21.0)
0.34
(3.5)
98.3
53.7
-3.0
5
21
15.5
45.7
7
6
—
—
The unit of pressure has been changed to Mpa based on the international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/FF)
2
Heating
8,000
2.90
0.44
1
13.0
1.82
(18.6)
0.36
(3.7)
82.9
48.0
-3.4
5
21
15.5
40.2
7
6
—
—
Cooling
7,800
3.62
0.44
16.49
2.07
(21.1)
0.45
(4.6)
76.1
56.7
13.1
0.74
0.11
PKH-3FKA
PKH-3FKA3
Heating
9,500
3.43
PKH-3FKA2
PKH-3FKA3
1.60
220
0.44
PUH-3NKA
PUH-3NKA2
1.60
220
15.6
2.02
(20.6)
0.34
(3.5)
83.7
52.2
4.6
5
27
19
15.5
44.0
35
24
-2.9
5
21
7
6
—
—
2
PKH-4FKSA
2
PKH-4FKSA3
Cooling
10,400
4.25
Heating
12,200
4.07
PKH-4FKSA2
PKH-4FKSA3
1.60
220
0.53
1
PUH-4TKSA
0.53
1
3.60
220
11.81
1.97
(20.1)
0.46
(4.7)
81.6
51.1
5.1
5
27
19
13.5
35
24
0.76
0.11
11.30
1.90
(19.4)
0.35
(3.6)
87.1
50.2
-2.9
5
21
15.5
43.5
7
6
—
—
5. OUTLET AIR SPEED AND COVERAGE RANGE
Service Ref.
Air flow
Air speed
Coverage range
K/min
m/sec.
m
PKH-2FKA
13
4.0
9.1
3
PKH-2.5FKA2
PKH-2.5FKA3
20
4.9
12.4
The air coverage range is the value up to the position where the air speed is 0.25m/sec. when air is blown out horizontally
from the unit at the Hi notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room.
PKH-3FKA2
PKH-3FKA3
20
4.9
12.4
PKH-4FKSA2
PKH-4FKSA3
28
5.4
15.3
19
Page 20
5
Pipe position
Left side
Lequid pipe
Gas pipe
Service space required
around indoor unit
(100 for left-hand
side piping)
Right side
130 or less
2 tapping screws
for installation plate
(Necessary clearance for
Unit installation)
Drain pipe
Front
50 or more
2-unit hangers
Unit cennter
Liquid pipe position
Gas pipe position
(Width of unit)
Knock out hole for
left-rear piping
Knock out hole for
left-rear piping
Rear piping hole
2 X5 - 2.9 hole
for tapping screw
Details of installation plate
1 Sleeves are available on
the market.
2 This size shows the lower
end of through hole.
Sleeve
9090~ 100
Through hole
150 or more
Knock out hole for
left-hand side piping
Ref.pipes & drain pipe
215
168
2134
8
20
70
300
47
30 or more
180 or more
80
25
35
60
Left side
Air intake
Front
1250
449 Air intake
Auto vanes
Service panel for
power supply connection
449 Air intake
968 Air intake
48
236
227
Right side
Terminal block
Right side
Knock out hole for right piping
(2:1)
Knock-out hole for
night-hand side piping
Knock out hole
for piping
8
60
Knock out hole for piping
Terminal block for control
Terminal block & pipe position
Drainage
Drainage(Flexible hole: length 1200)
Liquid pipe
Gas pipe
Lower side
Terminal block for
power supply
Knock out hole for under-piping
15 or less
bolt
Installation bolt position
200
B
B
A
A
8
8
60
91
65
20
70
(2:1)
70
Lower side
976
16 -louvers
(manual)
500
479 Air outlet479 Air outlet
26
173
223
222
143
553
635
685
170
190
200
1100
50
1
Knock out hole
for piping
1
2
2
3/8F
5/8F
0355380130
177
227
(178)
(375)
447
190
13- 14
hole
60
1250
330
80
0
53
68- 5
hole
277
Tapping screw
300
625
476
450
405
323
276
229
179
150
70
24
0
70
150
174
224
271
318
374
9
73
405
450
476
486
625
(Height ut unit)
85
45
286X
2
R52.5R52.5R52.5
R52.5R52.5R52.5
OUTLINES AND DIMENSIONS
1. INDOOR UNIT
PKH-2FKA3
Unit : mm21Unit : mm
20
Page 21
235
45
235
45
235
45
235
62.5
13
58
42
340
197
Top
Front
Right side
Left side
1400
1090
Air intake
235
C
Knock out hole for right piping
Refrigerant pipe. Drain pipe
Knock out hole for
left piping
Drain hose for
left-hand side piping
Drain hose
Lower side
Auto vane
(Gas pipe)
Drain hose
Bolt
Gas pipe
15 and less
Terminal block for power supply
Terminal block for control
Terminal block for remote controller
(Liquid pipe)
Liquid pipe 9.52(3/8F)
Gas pipe 15.88(5/8F)
Liquid pipe
A
30
32
39
98
37
74
4 39
100
30
37
74
4
2980
280
3030
18430
60
10
39
37
65
100
ABC
Knock out hole for piping
25
1110
183
240
B
1120
552
55
120
107
111
Air outlet
552
Air outlet
Change vane (manual)
Under panel
Removable at left-hand
side piping
Knock out hole for under-piping
Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping opening
12-ø6 hole for
tapping screw
66-ø6 hole for
tapping screw
Wall fixture
Unit center
32-ø12 hole for bolt
225
18
18
91
900
990
455
285
245
19
240280314
610
90
Drainage range
on left-hand side
Drainage range
on right-hand side
10 91=(910)
180
PKH-2.5FKA2PKH-3FKA2
PKH-2.5FKA3PKH-3FKA3
Page 22
235
45
235
45
235
45
235
45
235
62.5
13
58
42
340
197
Top
Front
Right side
Left side
1680
1370
Air intake
235
C
Knock out hole for right piping
Knock out hole for left piping
Drain hose for left-hand side piping
Drain hose
Drain hose
Lower side
Auto vane
(Gas pipe)
Bolt
Gas pipe
15 and less
Terminal block for power supply
Terminal block for control
Terminal block for remote controller
(Liquid pipe)
Gas pipe 19.05(3/4F)
Liquid pipe 9.52(3/8F)
Liquid pipe
A
30
65
39
98
37
74
4 39
100
30
37
74
4
2980
280
3030
18430
60
10
39
37
65
100
ABC
Knock out hole for wiring
25
1110
183
240
B
1400
55
120
102
111
694
Air outlet
694
Air outlet
Change vane (manual)
Under panel
(Removable at left-hand side piping)
Knock out hole for under-piping
Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping openingRange for left rear piping opening
12-ø6 hole for tapping screw
84-ø6 hole for
tapping screw
Wall fixture
Unit out line
Unit center
41-ø12 hole for bolt
295225
18
18
91
900
1270
595
285
245
19
240280314
750
90
Drainage range
on right-hand side
13 91=(1183)
180
Drainage range
on left-hand side
PKH-4FKSA2
PKH-4FKSA3
Unit : mm
22
Page 23
18
130
Rear side wiring arrangement opening.
120
FILTER
CHECK MODE
TEST RUN
46
83.5
SW18
SW17
CHECK
FILTER
CHECK
CHECK MODE
TEST RUN
CAUTION
2. REMOTE CONTROLLER
Unit : mm(inch)
23
Page 24
6
CN2
OFF
ON
4321
SW18
TB6
A01 B02
OFF
ON
R.B
45231
CN1
3 2 1
87654321
SW17
LED1 12V
POWER
LED2 5V
POWER
SW7
SW2
123456101234
SW5
2 1
CN2L
LOSSNAY
31
LS
MV
3
TRANSMISSION WIRES
DC12V
1
2
1 3 5
FAN2
HEATER
CN24
REMOCON
POWER
CN40
42 13
SW1
ON
OFF
123456789
SW6
1234
123
SW3
ON
OFF
12
TO
REMOCON
CN22
12
RT2
2
N
GRN/YLW
L
I.B
TO OUTDOOR UNIT
CONNECTING WIRES
DC12V
1
T
X4
ZNR
F1
C
MF
1
1
43
2
35
3
211133
FAN1
POWER
OUTDOOR
TRANS
VANE
VANE
TRANS
CND
CN30
CN6V
CN4T
CN23
CNT
INTAKE
CN20
PIPE
CN21
CN51
CENTRALLY
CONTROL
1122
RT1
RED
WHT
BRN
TB5
BLU
BLU
TB4
TB2
ORN
YLW
BRN
BRN
RED
RED
240V
14.2VAC
11.1VAC
230V
220V
BLU
YLW
WHT
RED
BLK
WHT
RED
POWER SUPPLY
~
(1 PHASE)
AC220-240V 50Hz
AC220V 60Hz
RED
ORN
YLW
X4
WIRING DIAGRAM
PKH-2FKA3
SYMBOL
C
CN1<R.B>PROGRAM TIMER CONNECTOR
CN2<R.B>REMOTE SWITCH CONNECTOR
CN2L<I.B>LOSSNAY CONNECTOR
CN51<I.B>CENTRALLY CONTROL CONNECTOR
FAN2EMERGENCY OPERATION CONNECTOR
F1<I.B>FUSE (6.3A 250V)
I.BINDOOR CONTROLLER BOARD
LED1<I.B>DC 12V POWER LED
LED2<I.B>DC 5V POWER LED
LSLIMIT SWITCH
MFFAN MOTOR
MVVANE MOTOR
R.BREMOTE CONTROLLER BOARD
RT1
FAN MOTOR CAPACITOR
ROOM TEMPERATURE THERMISTOR
(0°C/15KΩ. 25°C/5.4KΩ DETECT)
NAME
SYMBOLNAME
RT2
SW1<I.B>
SW2<I.B>
SW3<I.B>
SW5.6<I.B>
SW7<I.B>
SW17<R.B>
SW18<R.B>
T
TB2
TB4
TB5.6
X4<I.B>
ZNR
PIPE TEMPERATURE THERMISTOR
(0°C/15KΩ. 25°C/5.4KΩ DETECT)
MODE SELECTOR
ADDRESS SELECTOR
EMERGENCY OPERATION SWITCH
MODEL SELECTOR
MODEL SELECTOR
ADDRESS SELECTOR
FUNCTION SELECTOR
TRANSFORMER
POWER SUPPLYTERMINAL BLOCK
INDOOR/OUTDOOR CONNECTING WIRE TERMINAL BLOCK
REMOTE CONTROLLER TRANSMISSION LINE TERMINAL BLOCK
FAN MOTOR RELAY
VARISTOR
NOTES:
1. Since the indoor fan motor (MF) is connected with 230, 240V power, using 220V power will require a setting change of the dip switch (SW7<I.B>) on the indoor
controller board as shown in fig :
fig w1
Indoor fan motor (MF) for 220V.
2. Since the indoor transformer (T) is connected with 240V power, if 220,230V power is used. Change the wiring connection showing fig :
fig w2
When power supply is
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers.
5. Symbols used in wiring diagram above are, : Connector. : Terminal block.
6. Emergency operation
If remote controller of microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board.
[Check items]
(1) Make sure that no other trouble exist the outdoor unit. Trouble with the outdoor unit prevents emergency operation.
(If any trouble exists the outdoor unit error code “P8” will be displayed on the remote controller and the trouble position will be shown on the outdoor controller
board LED. See electric wiring diagram of the outdoor unit for details.)
(2)Make sure that there is no trouble with the indoor fan.
Emergency operation will be continuous operation mode due to power ON/OFF(ON/OFF with the remote controller is not possible).
[Emergency operation procedure]
(1)Set the dip switch (SW3<I.B>) on the indoor controller board to
(2)Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker.
In this order.
(3)During emergency operation indoor fan runs at high speed but automatic vane remains stop.
(4)Thermostat will not function. Cold air blows out for defrosting during heating thus do not operate defrosting for along time.
(5)Emergency cooling should be limited to 10 hours maximum.
(The indoor unit heat exchanger may freeze).
(6)After each operation, and set all dip switches (SW3<I.B>) to OFF. BG79N618H01
w
1.
230V
220V
SW5
ON
OFF
240V
230V
220V
2 3 4
1
YELLOW
ORANGE
RED
ON
OFF
1
2 3 4
1 on and 2 off for cooling and 1 - 2 on for heating.
24
w
2.
Page 25
J9
2
CN2
OFF
ON
4321
SW18
87
LED1 12V
POWER
X4
C
MF
L
N
GRN/YLW
SW7
CN51
CENTRALLY
CONTROL
LED2 5V
POWER
3
ON
OFF
TRANSMISSION WIRES
DC12V
1
2
TB6
A01 B02
OFF
ON
R.B
45231
CN1
3 2 1
87654321
SW17
HEATER
CN24
REMOCON
POWER
CN40
42 13
J5
42
SW2
ON
OFF
123456
SW6
1234
109654
J1
1234
SW7SW3
ON
OFF
12
TO
REMOCON
CN22
12
OFF
ON
12341234
4FKSA2.5,3FKAMODELS
RT2
2
CN27
D.U.M
I.B
TO OUTDOOR UNIT
CONNECTING WIRES
DC12V
1
T
ZNR
F2F1
MV
12345
1
6
1
1
43
2
35
3
211133
FAN1
POWER
OUTDOOR
TRANS
VANE
LOSSNAY
TRANS
CND
CN30
CN6V
CN4T
CN2L
CNT
DRAIN
CN50
INTAKE
CN20
PIPE
CN21
1122
RT1
POWER SUPPLY
~ (1 PHASE)
AC220-240V 50Hz
AC220V 60Hz
ROOM TEMPERATURE THERMISTOR
(0°C/15KO. 25°C/5.4KO DETECT)
PIPE TEMPERATURE THERMISTOR
(0°C/15KO. 25°C/5.4KO DETECT)
REMOTE CONTROLLER
TRANSMISSION LINE TERMINAL BLOCK
NAME
NOTES:
1. Since the indoor fan motor (MF) is connected with 230, 240V power, using 220V power will require a setting change of the dip switch (SW7<I.B>) on the indoor
controller board as shown in fig :
fig w1
Indoor fan motor (MF) for 220V.
2. Since the indoor transformer (T) is connected with 240V power, if 220,230V power is used. Change the wiring connection showing fig :
fig w2
When power supply is
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers.
5. Symbols used in wiring diagram above are, : Connector. : Terminal block.
6. Emergency operation
If remote controller or microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board.
[Check items]
(1) Make sure that no other trouble exist the outdoor unit. Trouble with the outdoor unit prevents emergency operation.
(If any trouble exists the outdoor unit error code “P8” will be displayed on the remote controller and the trouble position will be shown on the outdoor controller
board LED. See electric wiring diagram of the outdoor unit for details.)
(2)Make sure that there is no trouble with the indoor fan.
Emergency operation will be continuous operation mode due to power ON/OFF(ON/OFF with the remote controller is not possible).
[Emergency operation procedure]
(1)Set the dip switch (SW3<I.B>) on the indoor controller board to 1 on and 2 off for cooling and 1 - 2 on for heating.
(2)Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker.
In this order.
(3)During emergency operation indoor fan runs at high speed but automatic vane remains stop.
(4)Thermostat will not function. Cold air blows out for defrosting during heating thus do not operate defrosting for along time.
(5)Emergency cooling should be limited to 10 hours maximum.
(The indoor unit heat exchanger may freeze).
(6)After each operation, set all dip switches (SW3<I.B>) to OFF.
w1 In addition, the centralized control and remote control can be operated.
w2 The modes which indicate the sources of trouble are listed below.
● EO=Signal transmitting/receiving error
● P1=Room temperature thermistor malfunction
● P2=Indoor coil thermistor malfunction
● P4=Drain sensor malfunction
● P5=Drain overflow
● P6=Coil frost/overheat protection
● P7=System error
● P8=Outdoor unit trouble
w3 The CHECK switch will show if an error has occurred in the past.
w4 Fan runs on low speed for 1 minute in order to remove overheat air.
w5 The 3-minute (6 minutes … heating mode) time-delay functions after compressor stops.
w6 FAN or AUTO mode is selected by the indoor dip switch setting.
w7 In FAN mode, fan speed and vane operation depend on the remote controller setting. (Compressor is OFF.)
28
Page 29
COOLING OPERATION
COOL operation
Four-way valve/OFF
NO
NO
NO
Vane setting notch
Initial
COOLING
w8
60 deg downward angle
70 deg downward angle
NO
Downward discharge
Vane horizontal
w9
Vane initial
setting
Vane
Fan speed
LOW
1 hour
airflow
Compressor
thermostat
ON
Allowance
cancel
NO
YES
YES
YES
YES
NO
NO
YES
YES
NO
YES
3-minute
time delay
NO
6-minute
time delay
NO
3-minute
compressor operation
YES
w10
Coil frost
prevention
NO
w11
Cooling area
YES
NO
Allowance
period
NO
6 minute
time delay
Allowance set
YES
Coil frost protection
NO
compressor operation
NO
compressor operation
YES
10-minute
YES
Allowance cancel
Coil frost
protection
NO
16-minute
YES
Indoor pipe
temperature is
1°C or lower
NO
Compressor ON
1
YES
YES
Coil frost
prevention
Compressor OFF
Indoor coil
temperature is
10°C or higher
YES
3-minute
time delay
Coil frost
prevention release
NO
NO
1 min continue
FAN speed
FAN speed
LOW 5 min
LOW
elapse
YES
NO
YES
Outdoor unit
trouble
Coil frost protection
pipe temperature detection
PKH-2
PKH-2.5/3/4
SW1-5J1-5
1°CONprovided
-3°COFF
not provided
w8 When operation stops or changes to cooling or dry mode, the auto vane turns to a horizontal angle. If operation changes
during auto vane SWING, the auto vane will continue to swing.
w9 When operating TEST RUN, the thermostat will be continuously ON.
w10After 3 minute compressor operation, if the indoor coil thermistor reads -15°C or below for 3 minutes, the compressor will
stop for 6 minutes.
w11Cooling area : Indoor coil temperature is more than 5 degrees above the room temperature.
Heating area : Indoor coil temperature is more than 5 degrees below the room temperature.
FAN area : Indoor coil temperature is within 5 degrees either way of the room temperature.
29
Page 30
Heat operation
Vane setting notch
Vane initial setting
Defrost release
Outdoor unit trouble
Four-way valve ON
Allowance cancel
Outdoor unit
trouble
FAN SPEED
Very low airflow
Compressor OFF
1
3 min.restart
prevention
6 min. restart
prevention
2
A
B
B
A
1
2
1
Hot adjust start
FAN SPEED very low
Compressor ON
Allowance cancel
FAN STOP
Outdoor unit
trouble
Defrost operation
START
Four-way valve
OFF
Auxiliary heater OFF
Overheat remote
START
Overload protect
Auxiliary heater ON
6-minute restart
prevention
Allowance set
Compressor OFF
FAN SPEED
Low
FAN SPEED
setting notch
Hot adjust
release
Airflow 10% up
FAN setting notch
Auto COOL/HEAT
operation
T1 T0
>
=
COOL modeHEAT mode
COOL mode
T
1[(T0 - 2)
After 15min.
T1[(T0-2)
COOL operation
HEAT operation
1
1
T
1 ](T0 + 2)
HEAT operation
Cool mode
set
NO
NO
NO
NO
NO
NO
NO
YESYES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
w15
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
w9
w11
w11
w11
w10
w16
w17
w11
Initial
HEATING
Defrosting
Hot adjust
in process
Compressor ON
Compressor
thermostat ON
Heating
area
Fan area
20 min.elapse
Fan area
Heating area
Fan area
Cooling area
Heating area
Defrost
30 min. elapse
10-minute
compressor
operation
Indoor piping
55°C or lower
Auxiliary heater
ON
Indoor piping
60°C or higher
Auxiliary heater
thermostat ON
Indoor unit
70°C or higher
Allowance
period
Indoor piping
35°C or higher
HOT adjust
6 min. elapse
FAN SPEED
Low 2 min.
elapse
PKH-FK
Type
3-minute
Auxiliary heater
OFF
Indoor coil
thermistor is 60°C
or higher
FAN speed
Low notch
Initial mode
After 15min.
T
1 ](T0 + 2)
Indoor piping
-15°C or lower
HEATING OPERATION
AUTOMATIC COOLING/HEATING OPERATION
w15 ( i ) Until Low airflow is set while hot adjustment
(ii )While defrosting (FAN STOP)
(iii)When thermostat is OFF
In the case of( i ), (ii) and (iii) above, airflow is horizontal regardless the VANE setting.
w16 When AUTO operation is started, COOL or HEAT mode is selected automatically.
w17 T1 : Room temperature.
To : Set temperature
30
Page 31
DRY OPERATION
DRY
operation
Four-way valve / OFF
Vane
setting notch
NO
YES
NO
Initial dry
operation
YES
Vane initial setting
w12
Room temperature is
18°C or lower
NO
During
compressor ON
YES
3-minute
compressor
operation
YES
Compressor &
thermostat ON
YES
w8
w9
NO
NO
YES
3-minute
time delay
NO
Compressor &
thermostat
ON
NO
YES
w9
Compressor ON
time completes
YES
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
1
w8—9 Refer to page 29.
w12When room temperature is 18°C or below, the compressor cannot operate.
When room temperature rises over 18°C, the compressor starts after a 3-minute time delay.
w13Compressor ON time is decided by room temperature. Refer to page 38.
w14In dry operation, compressor ON makes the fan speed LOW and compressor OFF stops the fan.
It is not possible to set the fan speed with the remote controller
NO
w14
10-minute
compressor
OFF
YES
Compressor ON
time set
Compressor ON
Fan speed LOW
31
NO
w13
w14
Page 32
MICROPROCESSOR CONTROL9
FILTER
CHECK MODE
CHECK
TEST RUN
1. OUTLINE OF MICROPROCESSOR CON-
INPUT to remote controller
● OFF-ON switching.
● COOL/DRY-AUTO-HEAT selector switching.
● Thermostat setting.
● TIMER mode selector-switching and Timer
setting.
● HIGH-LOW fan speed switching.
● AUTO Vane selector (AIR DISCHARGE)
switching.
● TEST RUN switching.
● CHECK mode switching.
(Self diagnostic trouble shooting)
Indoor
unit
INPUT from indoor unit
Remote controller board
● Processes and transmits
orders.
12VDC
Indoor controller board
OUTPUT to remote controller
Remote controller
● LCD indicator
Non-polar, two-wire cable
maximum length 500 meters
Signal
● Room temperature thermistor (RT1)
● Pipe temperature thermistor (RT2)
OUTPUT to indoor unit
● Auto vane’s angle setting.
● Emergency stop.
Independent Control of
Outdoor Unit
● Compressor protection
device working
● Defrosting
START-STOP
● Fan speed control.
● Crankcase heater control
ON-OFF.
● Self diagnostic function
● Receives orders from remote controller and
temperature data from indoor unit.
● Processes orders and data.
● Controls indoor and outdoor operation.
● Self diagnostic function.
w System control operation.
w Emergency operation.
w Set by dip switch on indoor controller board.
● Transmits the power to remote controller.
1 2 3
Polar three-wire cable
Outdoor unit
12VDC
1
2
3
● Compressor and
outdoor fan : ONOFF
● Operation mode
OUTPUT to outdoor unit
change :COOLHEAT.
32
Page 33
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Compressor
ON
LOW or HIGH
Initially 10˚ degrees
LOW or HIGH
ON
OFF
OFF
CLOSECLOSE
OFF
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
(Changeable by remote controller setting)
FILTER
CHECK MODE
CHECK
TEST RUN
2. INDOOR UNIT CONTROL
2-1 COOL operation
<COOL operation time chart>
<How to operate>
1 Press POWER ON/OFF button.
2 Press the button to display “
f ”.
3 Press the i TEMP button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is press one time Cooling 19 to 30°C.
w1 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this
period has ended.
(1) Compressor control
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when room temperature is higher than set temperature.
The compressor stops when room temperature is equal to or lower than the set temperature.
3 The compressor stops in check mode or during protective functions.
4 Coil frost prevention
To prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 1°C or below after the
compressor has been continuously operated for at least 16 minutes or more. When the indoor coil temperature rises to
10°C or above, the compressor will start after a 3-minute time delay.
NOTE : By turning OFF the dip switch SW1-5, PKH-2.5/3/4 for J1-5 on indoor controller board, the start temperature of coil
frost prevention changes 1°C to -3°C.
33
Page 34
5 Coil frost protection
5 minutes
SET
LOW
5 minutes
SET
LOW
OFF
When indoor coil temperature becomes -15°C or below, coil frost protection will proceed as follows.
<Start condition>
After the compressor has been continuously operated for 3 minutes or more,and the indoor coil temperature has been
-15°C or below for 3 minutes,the coil frost protection will start.
<Coil frost protection>
Compressor stops for 6 minutes, and then restarts.
If the start condition is satisfied again during the first 10 minutes of compressor operation, both the indoor and outdoor
units stop, displaying a check code of “P8” on the remote controller.
<Termination conditions>
Coil frost protection is released when the start condition is not satisfied again during the allowance, or when the COOL
mode stops or changes to another mode.
(2) Indoor fan control
Indoor fan speed LOW/HIGH depends on the remote controller setting.
However, if an outdoor unit abnormality is detected, the indoor fan speed will be LOW, regardless of the remote controller
setting.
When the outdoor unit abnormality detection is released and the fan speed returns to the set speed, the quiet cycle control
will work.
(a) Normal control
(i ) Fan speed LOW/HIGH depends on the remote controller setting regardless of the thermostat ON/OFF.
(ii) Fan speed will remain on LOW if an abnormality in outdoor unit is detected. (5 minutes)
When the abnormality detection is released, the fan speed returns to the set speed.
NOTE 1 : Fan stops immediately if the unit stops or the check mode is started.
1 Start-up of outdoor unit abnormality detec-
tion.
2 Release of outdoor unit abnormality detec-
tion.
3 Unit stop due to outdoor unit abnormality
with P8 indication.
34
Page 35
(3) Auto vane control
Auto vane position is set to 10degrees discharge at the start-up of COOL operation. It can then be changed by the remote
controller.
(a) Stop mode (fixed operation)
(
!) At start-up of COOL operation, the auto vane is set to 10 degrees discharge direction.
(@) Discharge direction can be changed with AIR DISCHARGE UP/DOWN button.
1 Fan speed : LOW
10°60°70°
2 Fan speed : HIGH
10°60°70°30°
(b) SWING mode (Only PKH-2.5/3/4FK(S)A)
(!)The vane motor turns ON when the SWING mode is selected.
The vane motor is continuously ON during SWING mode.
<AUTO RETURN>
1 Fan speed : LOW
10°
60°
AUTO
RETURN
70°
AUTO
RETURN
(SWING)
(SWING)
2 Fan speed : HIGH
10°
When 60 degrees or 70 degrees discharge is selected with the LOW fan speed in COOL operation, “1Hr” will appear below
the temperature display. One hour later, the discharge direction returns to 10 degrees automatically and “1Hr” will disappear.
If the discharge direction is set to 10 degrees during “1Hr” indication, the time counting for AUTO RETURN is cancelled.
30°
60°
70°
35
Page 36
<Auto vane drive> (PKH-2FKA3)
(a) The auto vane is driven by a 2.5 rpm motor.
(b) Discharge direction can be selected between the No.1 and No.2 setting. (Initial setting is No.1)
1
10°
(c) Vane motor drive time
Discharge direction change
Downward C → Horizontal 4→1
Horizontal → Downward A1→2
Downward A→ Downward B 2→3
Downward B → Downward C 3→4
(d) Discharge direction is based on the horizontal position detected by the vane motor limit switch. When the horizontal
position can not be determined, the vane motor will remain ON until it is determined.
1 If the horizontal position still can not be detected, despite the 10minute detection, the vane motor will turn OFF
Remote controller indication continues.
2 After, if the vane motor receives the “auto vane ON” command again, it will restart detecting the horizontal position.
If the horizontal position still can not be determined, despite the 10-minute detection, the vane motor will turn OFF.
(PKH-2.5FKA
(PKH-2.5FKA3, PKH-3FKA3, PKH-4FKSA3)
(a) The vane is driven by DC12V motor.
(b) Air discharge direction is selected depends on the number of pulse were sended.
(c) Before start driving the auto vane, detect the standard position first, output the number of pulse to each air discharge.
(d) The speed of the auto vane drive for both open and close are settled at 200 pulse/sec.
(e) Method of driving the auto vane.
1 Detecting the standard position : Output 1600 pulse to the opening direction.
2 Position setting : Output the number of pulse indicated no below chart to the closing direction.
2, PKH-3FKA2, PKH-4FKSA2)
2
30°
3
60°
50Hz
Rise 2.1
0.65
6.7
0.65
4
70°
Unit : sec.
60Hz
Rise 1.75
0.55
5.55
0.55
The number of pulse outputed after
detecting the standard position
Close
Horizontal
Downward A
Downward B
Downward C113
(4) Detecting abnormalities in the outdoor unit
After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperature
and room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the difference is still out of RANGE C,the outdoor unit is functioning abnormally. Thus, the compressor stops and check code
“P8” appears on remote controller.
RANGE A: Indoor coil temperature is more than 5 degrees above room temperature.
RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature.
RANGE C : Indoor coil temperature is more than 5 degrees below room temperature.
Indoor coil temperature
minus room temperature
(degree)
+5
0
-5
RANGE A
RANGE B
RANGE C
1600
680
578
283
36
Page 37
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Compressor
ON
w Refer to (2)
Initially 10˚ degrees discharge
(
Changeable by remote controller setting
)
ON
OFF
OFF
CLOSE
CLOSE
OFF
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
FILTER
CHECK MODE
CHECK
TEST RUN
2-2 DRY operation
<DRY operation time chart>
<How to operate>
1 Press POWER ON/OFF button.
2 Press the button to display “ e ”.
3 Press the i TEMP button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is press one time Cooling 19 to 30°C.
w1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this
period has ended.
37
Page 38
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2The compressor runs when the room temperature is higher than the set temperature.The compressor stops when the
room temperature is equal to or lower than the set temperature.
3The compressor stops in check mode or during protective functions.
4The compressor will not start when the room temperature is below 18°C.
The compressor starts intermittent operation when the power is turned ON with room temperature above 18°C. The compressor ON/OFF time depends on the thermostat ON/OFF and the following room temperatures.
After 3-minute compressor operation,
● If the room temperature thermistor reads above 28°C with thermostat ON, the compressor will operate for 6 more minutes and then stop for 3 minutes.
● If the room temperature thermistor reads 26°C ~ 28°C with thermostat ON, the compressor will operate for 4 more
minutes and then stop for 3 minutes.
● If the room temperature thermistor reads 24°C ~ 26°C with thermostat ON, the compressor will operate for 2 more
minutes and then stop for 3 minutes.
● If the room temperature thermistor reads below 24°C with thermostat ON, the compressor will stop for 3 minutes.
● If the thermostat is OFF regardless of room temperature, the compressor will stop for 10 minutes.
5Coil frost protection
Coil frost protection in DRY operation is the same as in COOL operation.
6Coil frost prevention
Coil frost prevention does not operate in DRY operation.
(2) Indoor fan control
<PKH-2.5/3/4>
The indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote con-
troller. Also, the indoor fan does not run during compressor OFF.
<PKH-2>
(a)During compressor OFF
● When the indoor coil temperature is 6°C or above, the indoor fan will stop.
● When the indoor coil temperature is below 6°C, the indoor fan will run in DRY mode.
(b)During compressor ON
● The indoor fan runs on EXTRA-LOW speed for the first 1 minute after the compressor is turned on.
● After, the indoor fan runs in DRY mode.
<Dry mode>
The fan notch is controlled by the indoor coil temperature every 30 seconds.
Indoor coil temperature
Below -10°C
-10 to 0°C
Above 0°C
During compressor OFF, when the indoor coil temperature becomes 6°C or above, the indoor fan turns OFF immediately.
(3) Auto vane controls
Same as in COOL operation
(4) Detecting abnormalities in the outdoor unit
An abnormality in the outdoor unit can not be detected in DRY operation.
Fan operation
LOW speed
EXTRA-LOW speed
Dry mode
38
Page 39
2-3 HEAT operation
FILTER
CHECK MODE
CHECK
TEST RUN
<HEAT operation time chart>
<How to operate>
1 Press POWER ON/OFF button.
2 Press the button to display “ g ”.
3 Press the i TEMP button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is press one time Cooling 17 to 28°C.
<Display in HEAT operation>
[ DEFROST ]
The [ DEFROST ] symbol is only displayed during the defrost
operation.
[ STANDBY ]
The [ STANDBY ] symbol is displayed from the time the heating operation starts until the heated air begins to blow.
Thermostat
Indoor fan
Auto vane
Compressor
Power ON lamp
STAND BY lamp
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Operation starts by
POWER button
ON.
horizontal
From POWER ON until
warm begins to blow
Room temperature
becomes equal to
set temperature.
LOW
Depends on remote
controller setting
Minimum 3 minutes w2
Room temperature
falls below set temperature.
Extra LOW w1Extra LOW w1
LOW or HIGHLOW or HIGH
horizontalclose
Depends on remote
controller setting
Operation stops by
POWER button
OFF.
w1 Changeable by indoor
dipswitch SW1-7
and SW1-8.
w2 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this
period has ended.
39
Page 40
(1) Compressor control
13-minute time delay.
To prevent overload, the compressor will not start within 3, minutes after stop.
2The compressor runs when the room temperature is lower than the set temperature.The compressor stops when the
room temperature is equal to or higher than the set temperature.
3The compressor stops in check mode or during protective functions.
4Overheat protection
<Start condition>
When the indoor coil thermistor reads 70°C or above, the overheat protection will start.
<Overheat protection>
The compressor stops for 6 minutes, and then restarts.
If the start condition is satisfied again within 10 minutes of compressor operation, both the indoor and outdoor units stop,
displaying a check code of “P6” on the remote controller.
<Termination conditions>
Overheat protection is terminated when the start condition is not satisfied again during the allowance (10-minute compressor operation), when operation mode changes to other mode, or when thermostat turns OFF.
(2) Indoor fan control
(a) Normal control
( i )The indoor fan runs on EXTRA-LOW speed during the thermostat OFF.
EXTRA-LOW speed can be changed to LOW or HIGH speed by setting the dip switch SW1-7 and SW1-8,(PKH-
2.5/3/4 for J1-7, J1-8) If the indoor coil temperature becomes more than 5 degrees below the room temperature during the thermostat OFF, the indoor fan will stop. After, when the indoor coil temperature becomes within 5 degrees of
room temperature, the indoor fan will run on EXTRA-LOW speed.
(ii)Hot adjustment
Hot adjustment is a warm-up for HEAT operation
<Start conditions>
The hot adjustment works under any of the following conditions.
● HEAT operation starts.
● Defrosting ends.
● Thermostat turns ON
<Hot adjustment>
Initially, the indoor fan runs on EXTRA-LOW speed. When 5 minutes have passed or the indoor coil temperature
exceeds 35°C, the fan speed changes to LOW. Two minutes later, the hot adjustment ends. Then, the fan speed
depends on the remote controller setting.
(iii)The indoor fan stops when the indoor coil temperature is within 5 degrees either way of room temperature.
(iv)To eliminate the remaining heat, the indoor fan runs for the first 1 minute after the booster heater is turned OFF.
40
Page 41
(3) Auto vane control
(a) STOP mode (fixed operation)
(!) The discharge direction at the start-up of HEAT operation is the same as that of the previous operation.
(@) The discharge direction can be changed by the remote controller setting.
10°30°60°70°
In the following cases, discharge direction becomes 10° regardless of the remote controller setting.
1 During the hot adjustment with fan speed at EXTRA-LOW
2 During defrosting with indoor fan OFF
3 During the thermostat OFF
(b) SWING mode (Only for PKH-2.5FKA
(!) The vane motor turns ON when the SWING mode is selected.
The vane motor is continuously ON during SWING mode.
(@) In the following cases, the discharge direction is 10° regardless of the remote controller setting.
1 During the hot adjustment with fan speed at EXTRA-LOW
2 During defrosting with indoor fan OFF
3 During thermostat OFF
(4) Detecting abnormalities in the outdoor unit
When the outdoor unit is determined to be abnormal by the following causes, the compressor will stop and the check code
“ P8 ” will appear on the remote controller display.
1 During compressor ON after hot adjustment
1 If the difference between the indoor coil temperature and room temperature is in the RANGE B, the indoor fan will
stop.
2 Within 20 minutes after entering RANGE B (except for the first 10 seconds),
a) If the temperature difference enters RANGE A, the hot adjustment starts.
b) If the temperature difference is still in RANGE B, the outdoor unit is deemed abnormal.
c) If the temperature difference enters RANGE C, defrosting starts.
Within 30 minutes after entering RANGE C,
●If the temperature difference does not return to RANGE B,the outdoor unit is deemed abnormal.
●If the temperature difference returns to RANGE B, the next 20 minutes is an allowance period. If the difference enter
RANGE Aduring the allowance, defrosting ends and the hot adjustment starts. If the difference does not enter
RANGE Aduring the allowance, the outdoor unit is deemed abnormal.
2 During compressor ON in hot adjustment
After 30 minutes of defrosting in hot adjustment, if the temperature difference is still in RANGE C, the outdoor unit is
determined to be abnormal.
3 During compressor OFF
After 20 minutes of thermostat OFF, if the indoor coil thermistor reads -25°C or below, the outdoor unit is determined to
be abnormal.
(5) Indoor coil thermistor abnormality detection
An abnormality can be detected during compressor ON, except for the following.
●For the first 30 minutes after the temperature difference between the indoor coil temperature and room temperature
enters the RANGE C.
●When the temperature difference enters the RANGE C until it moves to the RANGE B.
(6) Defrosting operation
After the outdoor unit starts the defrosting operation, when the temperature difference between the indoor coil temperature
and room temperature gets out of RANGE Aand into RANGE B, the indoor unit starts the defrosting mode. After the outdoor unit stops the defrosting operation, when the temperature difference returns to the RANGE A, the indoor unit stops
the defrosting mode. While the indoor unit is in the defrosting mode, the indoor fan stop.
w1 RANGE A: Indoor coil temperature is more than 5 degrees above room temperature.
RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature.
RANGE C : Indoor coil temperature is more than 5 below room temperature.
Indoor coil temperature
minus room temperature
(degree)
+5
0
-5
RANGE A
RANGE B
RANGE C
41
Page 42
2-4 AUTO operation (Automatic COOL/HEAT change over operation)
Mode change (HEAT COOL)
When room temperature becomes2degrees above the set temperature,the operation mode can not be changed
for 15 minutes.
(degree)
To+2
To:Set temperature (19 28 )
To+1
To
To-1
To-2
Compressor
Start
HEAT modeHEAT mode
Mode change
15 minutes
15 minutes
Minimum 3 minutes
COOL mode
(COOL HEAT)
ON
OFF
-901020304052˚C
21˚C
(PUH-•VK,YK type 46 ˚C)
-8.5˚C
Cooling range
(Outside air temperature)
Heating range
-5˚C
FILTER
CHECK MODE
CHECK
TEST RUN
<How to operate>
1 Press POWER ON/OFF button.
2 Press the button to display “ ”.
3 Press the i TEMP button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is press one time Cooling 19 to 28°C.
●“AUTOMATIC” works to change by itself the operation mode either to cooling or heating according to
the room temperature.
(1) Initial mode
1 When AUTO operation starts after unit OFF.
● If the room temperature is higher than the set temperature, operation starts in COOL mode.
● If the room temperature is equal to or lower than the set temperature, operation starts HEAT mode.
2 When AUTO operation starts after COOLor HEAT operation, the previous mode continues.
(2) Mode change
1 HEAT mode changes to cool mode when 15 minutes have passed since the room temperature became 2 degrees
above the set temperature.
2 COOL mode changes to HEAT mode when 15 minutes have passed since the room temperature became 2 degrees
(3) Temperature range
AUTO operation is available under the outside air temperatures as follows.
42
Page 43
10°
30°
60°
70°
Changes by pressing
the button.
SWING
2-5 Auto vane control
FILTER
CHECK MODE
CHECK
TEST RUN
<Remote controller display>
<How to operate>
To change the air flow direction, press button.
Available in COOL operation with fan speed on HIGH or
in HEAT operation.
Unavailable in DRY operation.
If fan speed changes from LOW to HIGH during 30°
downward discharge in COOL mode, the direction automatically changes to 10°.
(1) COOL/DRY operation
At the start-up of COOL or DRY operation, the discharge direction in automatically set to 10°. After, it can be changed to
another direction with button on the remote controller.
<Auto return>
When 60° or 70° discharge is set with fan speed on LOW, “1Hr” appears below the room temperature display. One hour
later the direction changes to 10° degrees, automatically and “1Hr” disappears.
(2) HEAT operation
At the start-up of HEAT operation, discharge direction depends on the setting of the last operation.
After, it can be changed to another direction with button. The discharge direction shifts to 10° regardless of the remote
controller settings under any of the following conditions.
● Thermostat OFF
● Defrosting
● Indoor fan speed EXTRA-LOW in hot adjustment
43
Page 44
2-6 TIMER operation
OFF
FILTER
CHECK MODE
CHECK
TEST RUN
FILTER
CHECK MODE
CHECK
TEST RUN
TEST RUN button
TEST RUN
Indoor coil temperature code
Display
Display
<Timer setting example>
<Timer function>
AUTO STOP ·········The air conditioner stops after the set time lapses.
AUTO START ········The air conditioner starts after the set time lapses.
AUTO OFF ············Timer is not active.
<How to operate>
1. Press POWER ON/OFF button.
2. Press w button to select AUTO STOP or AUTO START.
3. Press q button to set desired time.
Time setting is in 1 hour units for up to 24 hours.
Each time HOURS button is pressed, set time increases by 1 hour.
When HOURS button is pressed and held, the set time increases
by 1 hour every 0.5 seconds.
4. To cancel the timer operation, press POWER ON/OFF button.
This setting will stop the air conditioner in 8 hours.
With the lapse of time, time display changes in 1 hour units, showing remaining time.
2-7 Test run
<Before test run>
● After installing, wiring, and piping the indoor and outdoor units, check for refrigerant leakage, looseness in power supply or
control wiring, and mistaken polarity.
● Use a 500-volt megger to check the resistance between the power supply terminal block and ground to make sure that it is
at least 1.0MΩ.
Attention:
Do not use the air conditioner if resistance is less than 1.0MΩ.
Remote controller
Turn on main switch. 12 hours before proceeding to step 2
1
to allow for crankcase heater operation.
Push the TEST RUN button twice and indication of TEST
2
RUN will be shown on the liquid crystal display.
Press the button to display f , COOL/DRY
(or HEAT ) to confirm that cool (or warm ) air is blown out.
(AT heating operation, there may be a short delay before
3
warm air begins to be out.)
Push button LOW/HIGH to check that the fan speed
changes properly.
4
Check the operation of outdoor unit fans. This unit controls
the rotation speed and performance capacity of fans. In
some cases, it may rotate at low speed as the condition of
outside air requires and the speed will be kept unless the
performance has become deficient.
5
Therefore, when the condition of outside air demands,
there may be such cases as the fan stops or rotates
reversely.
The above figure shows the state of TEST RUN at
cooling operation.
Please note that these symptoms are not malfunction.
After the check is finished leave the test run mode, push
the power ON/OFF button.
6
It can also be stopped by pushing the timer MODE button.
●When a TEST RUN is started, the timer shall be set to hours. The unit will automatically turn off after 2 hours.
44
Page 45
(1) Indoor coil temperature code
Code
Code
1
-40~1:
9
~45:
2
~10:
10
~50:
3
~15:
11
~55:
4
~20:
12
~60:
5
~25:
13
~70:
6
~30:
14
~90:
7
~35:
15
8
~40:
Thermistor
abnormality
Indoor coil
temperature
Indoor coil
temperature
1 ON
1
2
1.2 ON
1
2
1-2 OFF
1
2
During the test run, the indoor coil temperature code from 1 to 15 is displayed on the remote controller instead of room
temperature. The code should fall with the lapse of time in normal COOL operation, and should rise in normal HEAT
operation.
(2) Trouble during test run
● If the unit malfunctions during the test run, refer to section 10 in this manual entitled “TROUBLESHOOTING.”
● When the optional program timer is connected to the conditioner, refer to its operating instructions.
2-8 Emergency operation
When the remote controller or microprocessor malfunctions but all other parts are normal, emergency operation is started
by setting the dip switch SW3 on the indoor controller board.
<Before emergency operation>
1. Make sure the compressor and the indoor fan are operating normally.
2. Locate the defect with the self-diagnostic function. When the self-diagnostic function indicates “protective function is
working”, release the protective function before starting the emergency operation.
CAUTION: When the self-diagnostic function indicates a check code of “P5” (drain pump malfunction), DO NOT start the
emergency operation because the drain may overflow.
<How to operate>
1. For emergency cooling, set the dip switch SW3-1 to ON and SW3-2 to OFF.
For emergency heating, set the dip switch SW3-1,2 to ON.
Emergency
cooling
Emergency
heating
Normal
operation
Microprocessor board
2. Turn ON the outdoor unit breaker and then ON the indoor unit breaker.
Emergency operation will now start.
3. During emergency operation, the indoor fan operates on high speed, but the swing louvers and the auto vanes do not
operate.
4. To stop emergency operation, turn OFF the indoor unit breaker.
NOTE: The remote controller POWER ON/OFF button can not start/stop emergency operations.
CAUTION: Do not use emergency cooling for more than 10 hours, as the indoor coil may freeze.
45
Page 46
2-9 Interlock with ventilation system (LOSSNAY)
Relay box
Relay box (PZ-12RB-E)
LOSSNAY
LOSSNAY
LOSSNAY control switch
(PZ-05SLB
2-E)
LOSSNAY control switch
(PZ-05SLB2-E)
Mr. SLIM
Mr. SLIM
Remote
controller
Remote
controller
Remote display
adapter
(PAC-SA88HA-E)
Power
supply
Power supply
Relay box
LOSSNAY
ABLN HIGH N
Terminal block
Terminal block
Mr.SLIM
CN51
12V DC
Power supply
220 240V AC
Circuit
breaker
WHT
WHT
N
DAMPER
DAMPER
RED
LOW
HIGH
ORN
ORN
RED
(PZ-12RB-E)
L
N
Mr. SLIM/LOSSNAY interlock operation is available by using the optional parts listed below.
(1) System organization
(2) LOSSNAY models connectable to Mr. SLIM are:LGH-15RS-ELGH-50RS-E
LGH-25RS-ELGH-80RS-E
LGH-35RS-ELGH-100RS-E
(3) Required parts are:
● Relay box (PZ-12RB-E)…Contact capacity 10A
● Remote display adapter (PAC-SA88HA-E)…An optional part for Mr. SLIM
● LOSSNAY control switch (PZ-05SLB
…
2-E)
For LOSSNAY individual operation
(4) Operation
1LOSSNAY turns ON/OFF according to Mr. SLIM ON/OFF
2While Mr. SLIM is OFF, LOSSNAY individual operation is available by using the LOSSNAY control switch.
When Mr. SLIM turns OFF with the LOSSNAY control switch at ON, LOSSNAY will continue to operate.
(5) Wiring.
1When the LOSSNAY control switch is used
Remote
controller
Insulation
is needed
10m
Power
supply
50Hz
220 240V
Connecting wire
0.13mm or over
Connecting wire
solid wire,
1.6 or 2.0
(field supplied)
Circuit breaker
(field supplied)
L
N
PL
HIGH
N
LOSSNAY control switch
(PZ-05SLB
2
Indoor controller
N
L
LOW
DAMPER
2-E)
Mr. SLIM
board
Connector
CN51
ORN
RED
BRN
GRN
YLW
Junction box
(field supplied)
Power supply
for Mr. SLIM
220 240V AC
A
B
RED
L
N
HIGH
N
Terminal
block
ORN
LOW
RED
HIGH
WHT
N
DAMPER
ORN
DAMPER
Relay box
(PZ-12RB-E)
YLW
ORN
WHT
RED
WHT
LOSSNAY
RED
WHT
8
7
4
6
2
5
3
1
46
2When the LOSSNAY control switch is not used:
NOTE: For further information, refer to the
LOSSNAY technical & service manual.
Page 47
2-10 Dip switch and jumper connector functions
Each figure shows the initial factory setting.
1 On remote controller board
(1) SW17(Address selector)
1 2 3 4 5 6 7 8
ON
OFF
SW17-1 — 6) For address setting
SW17-7) When two remote controllers are used, this switch sets the controller function.
SW17-8) Switch for system back-up
(2) SW18 (Function selector)
ON
OFF
SW18-1) Switch for timer
SW18-2) Switch for filter sign
SW18-3) Switch for filter sign time setting
SW18-4) Not yet used.
2 On indoor controller board
For PKH-2FKA
(1) SW1 (Mode selector)
ON
OFF
SW1-1) Switch that changes between FAN mode and AUTO mode
SW1-2) Not for use
SW1-3) Switch for auto vanes
SW1-4) Switch for drain pump
SW1-5) Switch to change the temperature to start coil frost prevention
SW1-6) Switch for set temperature adjustment in HEAT mode
SW1-7) Switch for fan speed during thermostat OFF in HEAT operation
SW1-8) Switch for fan speed during thermostat OFF in HEAT operation.
SW1-9) Switch for detecting abnormalities in the outdoor unit abnormality detection
SW1-10) Switch for auto restart function
OFF: The remote controller is set as a main controller.
ON : The remote controller is set as a sub controller.
OFF: Without back-up
ON : With back-up
1 2 3 4
OFF: single day
ON : timer every day
OFF: filter sign absent
ON : filter sign present
OFF: 100 Hr
ON : 2500 Hr
3 only
1 2 3 4 5 6 7 8 9
OFF: Fan mode for models without heat pump
ON : AUTO mode for models with heat pump
OFF: Unit without auto vanes
ON : Unit with auto vanes
OFF: The drain pump works in only COOL operation.
ON : The drain pump works in both COOL and HEAT operation
OFF: -3°C(For previous special models)
ON : 1°C(For all current models)
During HEAT operation, warm air collects near the ceiling. When the indoor unit is installed near the ceiling, the
temperature read by room temperature thermistor differs from the actual living-space temperature by about 4
degrees. Therefore, the room temperature read by room temperature thermistor must be lowered by 4 degrees.
OFF: 4-degree adjustment
ON : No adjustment
OFF: EXTRA LOW
ON : LOW
OFF: EXTRA LOW or LOW (set with SW1-6)
ON : LOW or HIGH (set with remote controller)
OFF: When an abnormality occurs, it is detected.
ON : Even if an abnormality occurs, it can not be detected.SW
OFF: This function does not work
ON : This function works.
10
47
Page 48
(2) SW2 (Address selector)
1 2 3 4 5 6
ON
OFF
Used in setting the unit-address for group control.
For further information, refer to page 55.
(3) SW3 (Emergency operation switch)
Normal operation
For emergency cooling
For emergency heating
1 2
ON
OFF
ON
OFF
1 2
ON
OFF
(4) SW5 (Model selector)
1 2 3 4
ON
OFF
SW5-1) Power supply
ON :230V/240V
OFF:220V
)(
SW5-2) OFF:For models with heat pump
ON :For models without heat pump
SW5-3) Not for use
SW5-4) This switch is unavailable Keep this switch at OFF.
Switch to set the output of phase-controlled indoor fan motor.
Address setting is available at any time/
The initial factory setting by is based on each capacity.
J1-5) Switch to change the temperature to start coil frost prevention
J1-6) Switch for set temperature adjustment in HEAT mode
J1-7) Switch for fan speed during thermostat OFF in HEAT operation
J1-8) Switch for fan speed during thermostat OFF in HEAT operation.
J1-9) Switch for detecting abnormalities in the outdoor unit abnormality detection.
J1-10) Switch for auto restart function
(2) SW2 (Address selector)
ON
OFF
(3) SW3 (Emergency operation switch)
Normal operationFor emergency coolingFor emergency heating
ON
OFF
(4) J5 (Model selector)
Provided: The drain pump works in only COOL operation
Not provided: The drain pump works in both COOL and HEAT operation
Provided : 1°C (For all current models)
Not provided: -3°C (For previous special models)
During HEAT operation, warm air collects near the ceiling. When the indoor unit is installed near the ceiling, the
temperature read by room temperature thermistor differs from the actual living-space temperature by about 4
degrees. Therefore, the room temperature read by room temperature thermistor must be lowered by 4 degrees.
Provided : 4-degree adjustment
Not provided: No adjustment
Provided : EXTRA LOW
Not provided: LOW
Provided: EXTRA LOW or LOW (set with J1-7)
Not provided: Low or High (set with remote controller)
Provided : When an abnormality occurs, it is detected.
Not provided: Even if an abnormality occurs, it can not be detected.
Provided : This function does not work
Not provided: This function works.
1 2 3 4 5 6
1 2
Used in setting the unit-address for group control.
For further information, refer to page 57.
1 2
ON
OFF
1 2
ON
OFF
24
J5-2) Original:For models with heat pump.
J5-4) Do not cut this jumper wire for PKH-2.5FKA
(5) SW7(Model selector)•For PKH-FKA
ON
OFF
SW7-1) OFF:PKH-2.5/3
SW7-2) POWER SUPPLY
SW7-3
SW7-4
(6) J9Do not cut this jumper wire
2-11 INDOOR FAN CONTROL
Indoor fan relay output.
(a) During fan ON
(b) During fan OFF
Cut:For models without heat pump.
If cut, it causes unit malfunction.
1 2 3 4
2
The indoor fan relay turns ON. One second later, the phase control will start.
The phase control turns OFF. One second later, the indoor fan relay will turn OFF.
Room temperature
becomes equal to set
temperature.
Room temperature
becomes different from
set temperature.
3-1 Outdoor fan control
The rotational frequency of outdoor fan is phase-controlled according to the outdoor coil temperature. This control allows the
cooling operation even with the low outside-air temperature and the heating operation even with the high outside-air temperature.
3-2 Outdoor unit control
The outdoor unit turns ON/OFF the cooling/heating operation according to orders given from the indoor unit.
3-3 Protective functions
1 If an reversed-phase, an open phase, or an indoor controller abnormality is detected, the outdoor unit will stop operation
and the check mode will start. (For the check mode details, see page 56.)
2 If a protective function works, the compressor will stop running. Three minutes later, the compressor will restart. If the pro-
tective function works again, the compressor will stop running and the check mode will start.
3 The protective function is memorized.
4 The memory is cleared when the POWER ON/OFF button on the remote controller is turned OFF. However, the check
mode display continues until the outdoor unit receives the “operation ON” command from the indoor unit.
3-4 COOL/HEAT operation time chart
w1 If compressor restarts within 10 minutes, 4-way valve remains ON.
50
Page 51
ON
Outdoor fan
Compressor
4-way valve
Bypass valve
Auto vane
Indoor fan
10 degrees
(Remote controller still displays set direction.)
Outdoor unit
Indoor unit
ON
Set direction
ON
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
Set direction
Defrosting
starts.
Defrosting
stops.
3-5 Defrosting in HEAT mode
<Defrosting time chart>
(1) Start conditions
A. When all of the following conditions are satisfied, defrosting will start. However, when the bypass valve turns OFF,
defrosting starts 10 minutes later.
(a) More than seven minutes have passed since the compressor start-up.
(b) The outdoor coil thermistor reads -5°C or below.
(c) The outdoor fan motor output step is 100%
(d) Total time of compressor operation exceeds 30 minutes, and the outdoor coil temperature has fallen by 8 degrees or
more in comparison with that of 10 minutes after the compressor start-up.
NOTE: The outdoor coil temperature of 10 minutes after the compressor start-up is memorized until the defrosting
B. When all of the following conditions are satisfied, defrosting will start.
(a) ~ (c) The same as above (a) ~ (c) in item A
(d) Total time of compressor operation exceeds “defrost interval”.
Further information on the defrost interval is described in (3).
C. After the total time of compressor operation exceeds the defrost interval, the thermostat repeats ON/OFF 3 times.
Two minutes after the fourth “ON” of the thermostat, if the outdoor coil thermistor reads -5°C or below and the fan output is 100%, defrosting will start.
NOTE: The count of the thermostat ON/OFF is cleared by the compressor-OFF command or defrosting start-up.
(2) During defrosting
● Even if the thermostat turns OFF, defrosting continues.
● The 4-way valve, bypass valve, outdoor fan, and indoor fan are OFF.
operation has ended.
51
Page 52
(3) Defrost interval
The defrost interval time is determined as follows.
● Initial defrost interval is 50 minutes.
● The defrost interval after defrosting depends on the preceding defrosting time as shown below.
Defrosting operation timeNext defrost interval
3 minutes or below120 minutes
3 to 7 minutes80 minutes
7 to 10 minutes60 minutes
10 to 15 minutes40 minutes
15 minutes (Maximum)30 minutes
NOTE1:If the unit stops during defrosting , the next defrost interval will be 50 minutes.
NOTE2:If a protection function works for the first time during defrosting, the compressor will stop.
After a 3-minute time delay, defrosting will restart. In this case, a 3-minute time delay is included with the defrosting
time.
If the protection function works for the second time, the unit stops operation and displays the check code.
The next defrost interval will be 30 minutes.
NOTE3:When the defrosting has ended, the total time of the compressor operation is cleared.
(4) Termination conditions
Defrosting finishes when any of the following conditions are satisfied.
1Defrosting has continued for 15 minutes.
2Outdoor coil thermistor reads 22°C or above for the first 75 seconds after defrosting start-up.
3Outdoor coil thermistor reads 8°C or above after the 75-second defrosting.
4Power ON/OFF button is turned OFF during defrosting.
3-6 Actuators
(1) Bypass valve control
<Cooling mode>
1When the unit stops due to the coil frost prevention, the bypass valve turns ON. When one hour has passed since the
compressor stopped, the bypass valve returns to OFF.
2When the compressor operates with the bypass valve at ON for more than 30 minutes, the bypass valve turns OFF.
3When the compressor stops with the bypass valve at OFF, the bypass valve turns ON and remains ON for three min-
utes.
<Heating mode>
1When the unit starts for the first time after the circuit breaker has been turned ON, or when it starts after the compressor
OFF of 30 minutes or more, if the outdoor coil thermistor reads 12°C or more, the bypass valve turns ON.
2When the high pressure switch (63H1) works, the bypass valve turns ON.
3When the bypass has been ON for 30 minutes:
● If the high pressure switch has already returned, the bypass valve turns to OFF.
● If not, the fan output step keeps 70 for three minutes. Meanwhile, if the high pressure switch returns, the bypass valve
turns OFF. Otherwise the normal fan control starts.
4When the operation mode changes or stops, the bypass valve turns ON and remains ON for three minutes.
<Defrosting operation>
1The bypass valve is OFF.
(2) Crankcase heater control
1With jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and then turns ON one hour
after the compressor stops.
2Without jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and repeats 1-hour ON and
1-hour OFF.
52
Page 53
3-7 Service functions
(1) Compulsory defrosting
1When all of the following conditions are satisfied, pressing SW2 starts the compulsory defrosting.
● During HEAT mode
● The compressor is ON.
● The outdoor coil temperature is being displayed by LED. (Outdoor controller board dip switch SW3-1 : OFF, SW3-2 :
ON)
● The outdoor coil thermistor reads 8°C or below.
2The operation state and the termination conditions of the compulsory defrosting are the same as those of the normal
defrosting. As an exception, the defrost interval after the defrosting completion is 50 minutes.
(2) Fixed fan-output
While the compressor is operating (except during defrosting) and the fan output step is indicated by LED, pressing SW2
fixes the fan output. The fixed fan-output can be released when any of the following conditions are satisfied.
1SW2 is pressed again.
2SW3 setting is changed.
3The compressor stops.
4Defrosting operation starts.
(3) Function of switches on the outdoor controller board
SW1: Clears the check code memory (push-button switch)
SW2: Switches the output state indication and the check code display (push-button switch)
SW3-1,2: Switches the output state indication items (dip switch)
For further information, refer to page 57.
(4) 100% fan output
Fan output is fixed to 100% by shorting the connector CN22. However, the fan stops during compressor OFF or defrosting.
Open-circuit of CN22 restarts the normal fan control.
(5) Time shortening
Short circuit of the connector CN21 shortens the time as follows
1Fan control period: 30 seconds → 3 seconds
2Three-minutes time delay function : 3 minutes → 3 seconds
3Max. time of defrosting : 15 minutes → 15 seconds
4Defrost interval : 30 ~ 120 minutes → 3 ~ 12 seconds
5Compressor ON/OFF time for bypass valve ON/OFF : 30 minutes → 3 seconds
6Compressor ON time to start other functions : x minutes → x seconds
7Crankcase heater operation : 1 hour → 6 seconds
53
Page 54
10
TROUBLESHOOTING
1. TROUBLE IN TEST RUN
SymptomCauseCheck points
The display “CENTRALLY
CONTROLLED” on remote
controller does not disappear.
When remote controller
POWER button is turned
ON, the check code
“EO”appears.
1) Wrong address setting of remote controller/indoor controller board.
2) Timer adapter is connected to the
remote controller.
3) Signal transmission error between
indoor unit and remote controller.
1) Signal transmission error between
indoor unit and remote controller
1) Check the address setting of remote controller
and indoor controller.
2) Make sure the timer adapter is used correctly.
3) 1 Turn another remote controller’s DIP SW177 ON to make it sub controller.
2 Connect the sub controller to the unit, and
turn circuit breaker ON.
● If the display “centrally controlled” disap-
pears, replace the original remote controller.
● If the display remains the same, replace the
indoor controller board.
1) 1 Connect a sub remote controller.
2 Turn circuit breaker ON.
If the display “centrally controlled” remains,
replace the indoor controller board.
3 If the display disappears, turn the remote
controller POWER button ON and check as
follows.
Remote controller
1
Operating Display
2
Operating Display
3
No Display
4
No Display
Sub remote controller
EO Display
Operating Display
EO Display
Operating Display
Malfunction
Malfunction of
indoor Unit
Malfunction of
Remote controller
Malfunction of
indoor Unit and
Remote Controller
Malfunction of
Remote controller
When remote controller
POWER button is turned
ON, operating display
appears, but disappears
soon.
Despite turning POWER
button ON, the remote
controller display does not
appear.
1) Short circuit of indoor/outdoor connecting wire
2) Short circuit of transmission wire.
3) Short circuit of drain sensor heater circuit.
4) Wrong operation of remote controller
due to noise wave emitted by other
appliances.
1) Damaged remote controller.
2) Short circuit of transmission wire.
3) Bad contact of indoor CN40.
4) CN40 is attached to a sub unit.
5) Damaged transformer.
6) Bad contact of CN4T.
7) Blown fuse.
8) Circuit breaker OFF.
1), 2) Check the wire
3) Measure the resistance of the drain sensor
connector CN50 1 ~ 3. Normal resistance
should be 82Ω.
4) Turn the circuit breaker OFF, and then turn
ON.
If the remote controller remains abnormal,
despite the above measures, replace the indoor
controller board.
1) Measure the voltage between terminals of
remote controller. If no voltage, remove the
terminals and measure the voltage between
wires. If the voltage is between 6VDC and
12V, replace the remote controller.
2) ~ 8) Check each point.
If it is not defective, replace the indoor
controller board.
54
Page 55
2. SELF DIAGNOSTIC FUNCTION WITH REMOTE CONTROLLER
2-1 When malfunction occurs during operation
When a malfunction occurs, the indoor and outdoor units stop and the malfunction is displayed on the LCD of the remote
controller.
(1) ON the set temperature display part, “CHECK” appears, and the unit
address and the check code are displayed alternately at one-second
intervals. (Check mode)
Example
CHECK mode
Check
code
(2) When one remote controller controls several units in the group control,
the LCD shows the unit address and check code of the first malfunctioning unit.
(3) To cancel the check mode, press the ON/OFF button. In remote
ON/OFF control, press the remote ON/OFF switch. In centralized
control, turn OFF the ON/OFF button of centralized controller.
NOTE: The latest check code is memorized, even if the check mode is cancelled by the way mentioned above. It takes
60 seconds maximum to display the memorized check code.
2-2 How to use the self diagnostic function for service
A. For normal control with one unit and one remote controller
(1) Pressing the CHECK button on the remote controller twice starts the self diagnostic function.
(2) During the self diagnostic function, “CHECK MODE” appears at two positions on the remote controller display. Then, at
least 10 seconds later, the unit address and the check code is alternately displayed at one-second intervals.
(3) Check and repair the unit according to the check code. (Refer to the next page.)
B. For group control using one remote controller
(1) Pressing the CHECK button on the remote controller twice starts the self diagnostic function.
(2) Press the TEMP. button or TEMP. button on the remote controller to advance or go back to the unit address.
Each time TEMP. button is pressed, the unit address advances by one. Each time TEMP. button is pressed,
the unit address goes back by one.
The check code and the unit address, appear alternately.
(3) The check code “U8” means no malfunction has occurred since installation.
The check code “EO” means the following conditions:
● The unit address displayed on the remote controller does not apply to any unit.
● power is not supplied to the unit.
● Signal transmitting/receiving circuit is abnormal.
(4) Check and repair the unit according to the check code. (Refer to the next page.)
Unit
address
Check button
55
Page 56
Check
code
EOSignal transmitting/receiving
Diagnosis of malfunctionCauseCheck points
error
(Indoor controller does not
respond to remote controller
signal.)
During individual unit control
1) Bad contact of transmission
wire
2) Signal transmitting/receiving circuit is abnormal.
1) Check the transmission wire.
2) Check with another remote controller. If “EO” is
still indicated, replace the indoor controller
board.
If other check code appears. replace the original remote controller.
P1P2Abnormality of room temper-
ature thermistor (RT1)
Abnormality of indoor coil
thermistor (RT2)
P3Signal transmission error
(Remote controller does not
respond to indoor controller
signal.)
P4Abnormality of drain sensor1) Bad contact of transmission
1) Bad contact of thermistor
2) Damaged thermistor
1) Bad contact of transmission
wire
2) Signal transmitting/receiving circuit is abnormal.
3) Wrong operation due to noise
wave emitted by other appliances
wire
2) Damaged thermistor
1) Check the thermistor.
2) Measure the resistance of the thermistor.
Normal resistance should be as follows.
0 C ···15kΩ30 C·····4.3kΩ
10 C······9.6kΩ 40 C·····3.0kΩ
20 C······6.3kΩ
If the resistance is normal, replace the indoor
controller board.
1) Check the transmission wire.
2) Check with another remote controller.
If “P3” is still indicated, replace the indoor
board.
If other check code appears, replace the original remote controller.
3) Short-circuit between 1 and 2 of CN40 and
attach CN40 to the following units.
● Second unit in twin control
● Second and third units in triple control
● Sub units in group control
1) Check the connector.
2) Measure the resistance of the thermistor 4 ~
5.
As for the normal resistance, refer to the case
of P1.
If the resistance is normal, replace the indoor controller board.
P5Malfunction of drain pump1) Malfunction of drain pump
P6Coil frost protection is work-
ing.
P7
System error
P8Abnormality in outdoor unit1) Wrong wiring of indoor/outdoor
2) Damaged drain sensor
1) Short cycle of air cycle
2) Dirty air filter
3) Damaged fan
4) Abnormal refrigerant
1) Wrong address-setting
2) Signal transmitting/receiving circuit of remote controller is
abnormal.
3) Wrong SW6-setting
connecting wire
2) Reversed phase
3) Protection device is working
4) Damaged outdoor coil thermistor
1) Check the drain pump.
2) ● Check the drain sensor.
● Check the drain sensor heater. Normal resistance should be 82Ω.
If the resistance is normal, replace the indoor controller board.
1) Clear obstructions from the air cycle.
2) Clean the air filter
3) Check the fan.
4) Check the refrigerant temperature.
1) Check the address-setting.
2) Check with another remote controller. If check
code other than “P7” appears, replace the original remote controller.
3) Check SW6 setting.
1) Check the indoor/outdoor connecting wire.
2) Change the connection of electric wiring.
3) Check the protection device.
4) Measure the resistance of the outdoor coil thermistor. If the resistance is normal, replace the
outdoor controller board.
56
Page 57
3. SERVICE DATA INDICATION BY SWITCHES ON OUTDOOR CONTROLLER BOARD
LED
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
SW3-1
SW3-2
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
ON
Blinking
Reversed phase
Open phase
63H2 function
51C function
26C function
Overheat protection
During 63H1 function
Compressor ON
Outdoor fan ON
4-way valve ON
Bypass valve ON
Crankcase heater ON
Lidhting
1
2
4
8
16
32
64
128
1
2
4
8
16
32
64
128
256
512
1024
2048
4096
8192
16384
32768
Outdoor coil thermistor is
abnormal.
Compressor ON command
from indoor controller
Heating operation command
from indoor controller
Input circuit on controller
board is abnormal
Check codeOutput state
Outdoor coil
temperature
(bit)
Outdoor coil
temperature
(bit)
Total time of
compressor
operation(Hr)
Setting dip switches SW2 and SW3 on the outdoor controller board enables LED to show the output state and check code.
Output state is shown by LED lighting, and check code by blinking.
SW1 : Turning SW1 ON clears the check code. If SW1 is turned ON while the check code is blinking , the indication
changes to output state indication.
NOTE : SW1 is usually available independent of SW3 setting. As an exception, when the check code shows a
reversed phase or an open phase during the power-on-reset state, SW1 is not available.
SW2 : SW2 is turned ON by pressing, and OFF by releasing.
When SW3-1 and SW3-2 are OFF, pressing SW2 changes indication between output state and check code alternately.
When SW2 is turned On with SW3-1 OFF and SW3-2 ON, the compulsory defrosting starts.
SW3 : Output state indication items depend on the combination of SW3-1 ON/OFF and SW3-2 ON/OFF.
Changed alternately by pressing SW2.
57
Page 58
3-1 Outdoor coil temperature
50
Fan output step (bit)
Fan rotational frequency (rpm)
100150200250
800
600
400
200
0
50
Fan output step (bit)
Fan rotational frequency (rpm)
100150200250
800
600
400
200
0
To obtain data on the outdoor coil temperature, add the number of bits of lighting LEDs, and see the graph below to find
the temperature.
Short
Temperature
Open
Number of bits
3-2 Fan output step
To obtain data on the fan output step, add the number of bits of lighting LEDs, and see the graph below to find the fan
rotational frequency.
1PUH-2NKA, PUH-4TKSA
PUH-1.6/2KA, PUH-4KSA
2PUH-2.5NKA, PUH-3NKA
PUH2.5VKA, PUH-2.5/3KA
3-3 Total time of compressor operation
Compressor operation time is indicated in 256 hour units. To obtain the compressor operation time, add the hours of lighting LEDs. During the compressor operation time indication, SW2 is not available.
3-4 Check code indication
● When a protection function works for the first time during operation, the operation stops and restarts after the 3-minutes
time delay mode. When the protection function works again, the operation stops. (Check mode) When both SW3-1 and
SW3-2 are OFF, the check code is indicated.
● If the outdoor controller board receives the compressor ON command from the indoor controller board during check
mode the indication changes to output state indication.
● By pressing SW2 during normal operation. operation will continue.
● The latest check code is indicated.
58
Page 59
4. TROUBLESHOOTING ACCORDING TO CHECK CODE
Blinking
LED
LD1Reversed phasePhases L1, L2, and L3are con-
Diagnosis of malfunctionCauseCheck point
Check the power supply connection.
nected improperly.
LD2Open phase● Phase L2is open.
LD3Outdoor coil thermistor is
abnormal. (Open circuit or short
circuit)
LD4High pressure switch (63H2)
function
LD5Thermal relay (51C) function● 51C was connected incor-
LD6Thermal switch (26C) function.● 26C was connected incor-
LD7Over heat protection ● The thermistor is broken.
LD8Input circuit of outdoor con-
troller board is abnormal.
● Contact of protector, such as
thermal switch, opened when
power was turned on.
● Outdoor coil thermistor is
broken.
● Thermistor was connected
incorrectly.
● 62H2 was badly connected.
● 63H2 was working.
rectly.
● 51C was working.
rectly.
● 26C is working.
● Coil temperature is over
67°C.
● Pulse input is abnormal.● Replace the outdoor controller board.
● Check the power supply.
● Check each protector.
● Measure the resistance of the thermistor.
● Check the thermistor. If normal, replace the out-
door controller board.
● Check 63H2 and the outdoor fan motor.
● Check if refrigerant supply is low.
● Check if air cycle is short-cycled.
● Check 51C, the compressor, and power supply.
● Check 26C.
● Check if refrigerant supply is low.
● Check if the capillary tube is clogged.
● Measure the resistance of the thermistor.
● Check the outdoor fan motor.
● Check if air cycle is short-cycled.
5. WHEN OUTDOOR UNIT DOES NOT WORK
Cause
1) Indoor/outdoor connecting wires are poorly connected.
(Refer to next page.)
2) Power supply cord is poorly connected.
3) Connector or transformer is broken.
4) Fuse (6.3A) in the outdoor controller board is blown.
Check points
1) Check the connecting wires.
2) Check the power supply cord.
3) Check connectors and transformers.
4) Check the fuse.
59
Page 60
6. WRONG WIRING ON SITE
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
6-1 Between remote controller and indoor unit
If the wire is disconnected between the remote controller and the indoor unit, nothing is displayed on the remote controller
when the POWER button is pressed. The beep sound will also not be heard.
6-2 Phenomena due to wrong wiring between indoor and outdoor units
Cooling operation. Several minutes later,check code “P8” appears
on remote controller display.
ONNormal operation.
OFFOutdoor unit stops.
Operation stops. 9 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops.
Operation stops. 27 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOutdoor unit stops.
Operation stops. 9 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops.
Operation stops. 27 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOutdoor unit stops.
Operation stops. 9 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops.
Operation stops, 27 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOutdoor unit stops.
Operation stops. 9 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops.
Operation stops. 27 minutes later, check “P8” appears on remote
ON
controller display.
OFFOperation stops.
Operation stops. 9 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops. 4-way valve turns OFF.
27 minutes later, check code “P8” appears on remote controller
ON
display.
Disconnection between 3 and 3.
COOL
HEAT
Normal operation.
–
OFFOperation stops. 4-way valve turns ON.
Operation stops. 27 minutes later, check code “P8” appears on
ON
remote controller display.
60
Page 61
7. OTHER TROUBLES AND CAUSES
Vanes do not work.
Unit stops after 5 to
20 seconds operation
Air discharge display
is OFF and air discharge UP/DOWN
button does not operate.
In this case, remote
controller is normal.
Power ON/OFF button
is not available.
Vane motor does not work.
Limit switch does not work.
Connector is poorly connected.
Vane motor is poorly assembled.
Indoor controller board is damaged.
Protection function is working.
Indoor controller board
deems the auto vanes
are not attached to the
unit.
Horizontal angle can
not be detected.
Beep sound is heard,
but display is turned
OFF.
Beep sound is not
heard, and display
remains OFF.
“CENTRALLY CONTROLLED” is displayed.
Indoor controller is
damaged.
Dip switch setting is
wrong.
Indoor controller is
damaged.
Vane motor is damaged.
Vane motor limit switch
is poorly connected.
Auto vane is wired after
power is turned to ON.
Indoor/outdoor connecting wire is connected
incorrectly.
Indoor/outdoor connecting wire shorts.
Compressor protector is
damaged.
Outdoor controller
board is detective.
Remote controller is
damaged.
Transmission wire is
poorly connected
Vane motor is damaged.
Vane motor relay is damaged.
Limit switch is damaged.
The size of the cam is wrong.
Refer to check code on remote controller display.
See page 56.
Vane motor limit switch
is damaged.
Vane motor is damaged.
Poorly connected
Disconnected
Transmission wire is
damaged.
Connector is poorly
connected.
Indoor terminal block is
poorly connected.
Remote controller terminal block is poorly
connected.
8. MR. SLIM/LOSSNAY INTERLOCK OPERATION
<Symptoms that are not malfunctions>
If any of the following symptoms occur, they are not malfunctions.
Symptom
LOSSNAY control switch can not work during interlock opera-
LOSSNAY control switch does not work.
LOSSNAY air speed can not be controlled in interlock opera-
tion.
For LOSSNAY, troubleshooting refer to the LOSSNAY technical & service manual.
tion.
LOSSNAY control switch is effective only while Mr. SLIM is not
operating.
LOSSNAY fan speed is fixed to HIGH during interlock operation.
LOSSNAY fan speed LOW/HIGH can be switched only during
LOSSNAY individual operation with the LOSSNAY control
switch.
61
Cause
Page 62
9. How to check the parts
0
10
20
30
40
50
-20 -10010 20 30 40 50
< Thermistor for lower temperature >
Temperature (:)
Resistance (K")
1
1
2
2
3
3
Red
White
Black
Relay connector
Protector
Parts nameCheck points
Measure the resistance between the terminals using a tester.
(Winding temperature 20:)
Fan motor (MF)
Abnormal
Open or short
Red–Black
White–Black
Motor terminal
or
Relay connector
PKH-2FKA
3
154.3"
162.0"
PKH-2.5, 3FKA2/3
99.5"
103.9"
PKH-4FKSA
2/3
62.6"
74.0"
Normal
Open or short
Abnormal
Brown–Yellow
Brown–Blue
Red–Orange
Red–Pink
Connector
Normal
186~214"
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:~30:)
Vane motor (MV)
Room temperature
thermistor (RT1)
Pipe temperature
thermistor (RT2)
Disconnect the connector then measure the resistance using a tester.
(Surrounding temperature 10:~30:)
Normal
4.3k"~9.6k"
Abnormal
Open or short
Protector
OFF : 120i5:
ON : OFF–15:
OFF:130i5:
ON :80i20:
<Thermistor Characteristic graph>
Thermistor for
lower temperature
Thermistor R0=15k' ± 3%
Fixed number of B=3480k' ± 2%
Room temperature thermistor(RT1)
Pipe temperature thermistor(RT2)
1
273+t
1
273
62
Page 63
11
Unit
Remote
controller
UnitUnit
Optional
adapter
Remote
ON/OFF
switch
Remote
controller
Relay box
Unit
Unit
Remote
controller
UnitUnit
Unit
Remote controll
display board
Remote
controller
UnitUnit
Circuit breaker
Remote
controller
SYSTEM CONTROL
1. VARIETY OF SYSTEM CONTROL FUNCTIONS
1 Group control with
a single remote
controller
(See page 64.)
2 Both remote
ON/OFF and individual controls
(See page 65.)
w Timer adapter
(PAC-SA89TA-E)
is needed.
3 Individual control
by grouping
remote controllers
(See page 66.)
4 Multiple remote
control display
(See page 67.)
w Multiple display
adapter
(PAC-SA88HA-E)
is needed.
Many units, installed at different locations, can be started
and controlled with a angle remote controller. The remote
controller can be mounted in a different location using a
non-polar two-wire cable, which can be extended up to
500m. Amaximum of 50 units can be controlled with a
single remote controller. All units operate in the same
mode.
All units can be turned on or off simultaneously using a
remote ON-OFF switch. Also, each unit can be controlled
individually by each remote controller. Dunning remote
ON-OFF control, a message of “CENTRALLY CONTROLLED” is displayed on the LCD of the remote controller.
This is available for both one unit control and several units
control.
By grouping the remote controllers in one place, several
units installed at different locations can be controlled individually, and operation conditions of all units are visible
without a special control board. The control method is the
same as that of the single unit with a single remote controller.
Several units can be controlled with a remote control display board. Operation conditions of all the units are visible with the remote control display board.
Individual control by each remote controller is also possible.
5 Auto restart
function
(See page 67.)
A unit can be started or stopped with the circuit breaker
on or off.
Remote controller is also available.
With this function, when the power is restored after power
failure, the unit will restart automatically. (However, when
the remote controller POWER ON/OFF button is OFF, the
unit will not start.)
63
Page 64
2. GROUP CONTROL WITH A SINGLE REMOTE CONTROLLER
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
To remote
controller
To next
unit
To next unit
The last unit
does not have
this wire.
Next unit
electrical box
Master unit
electrical box
123ANE
123ANE
Master
unit
No.1 unitNo.2 unitLast unit
2-wire cable
A maximum of 50 units can be started in order according to the dip switch settings
2-1 How to wire
(1) Connect the remote controller to the double terminal block
on the indoor controller board of the master unit (No.0 unit).
(See Figure 1.)
(2) Connect the double terminal block of the master unit to the
double terminal block of No.1 unit.
(3) Connect the double terminal block of No.1 unit to the dou-
ble terminal block of No.2 unit.
(4) Continue the process until all the units are connected with
two-wire cables. (See Figure 2.)
(5) Remove the connector CN40 from the indoor controller
board of each unit except the master unit. (See Figure 3.)
(6) Set the unit-address of each unit with SW2 on the indoor
controller board following the instructions below.
2-2 How to set unit-address
The unit-address also serves as a successive-start timer which
starts each unit at intervals of 1 second. If two or more units
have the same unit-address in a group control, operation stops
due to system error. Be sure to set SW2 correctly following the
instructions below.
(1) Each lever of SW2 shows the number as follows.
(2) Total number of levers turned to ON shows the address of
the unit.
For example, to set No.3 unit, turn ON SW2-1 and SW2-2.
(3) In this way, set from the. master unit to the last unit.
Do not forget to set the master (No. 0) unit.
Figure 1
Figure 2
Figure 3
Indoor controller board ▼
Should be removed from
all units other than unit
No.0:(Master Unit)
Setting examples
Master (No. 0) unit
ALL OFF
No. 1 unit
1 ON
No. 2 unit
2 ON
No. 4 unit
3 ON
No. 8 unit
4 ON
No. 16 unit
5 ON
SW2
Unit address & start
delay in seconds.
0
1
2
4
8
16
2-3 Unit control
The remote controller can control all units ON/OFF, temperature,air flow, and swing louver. However, the thermostat in
each unit turns ON or OFF individually to adjust to the room temperature.
64
No. 32 unit
6 ON
32
Page 65
3. REMOTE ON-OFF AND INDIVIDUAL REMOTE CONTROLS
Remote
controller
power supply of
control circuit
Remote
ON/OFF
switch
2-wire
remote
controller
cable
Figure 6
Relay box
Timer adapter cables
Timer adapter
PAC-SA89TA-E
This method is available to control one unit or any number of units.
The following operations are available by connecting a relay, a timer adapter (PAC-SA89TA-E), and a remote ON/OFF switch
to the system. Timer adapter is an optional part. Other parts are available on the market.
(A) To start all units in order by remote ON-OFF switch
(B) To stop all units simultaneously by remote ON-OFF switch
(C) To switch between the remote ON-OFF control and the individual remote control
3-1 System
Figure 6 shows the case of three units.The same is the case with any number of units.
65
Page 66
NOTE1 : Install the relay box where you can be serviced it easily.
Power
supply
Remote
ON/OFF
switch
No.1 unit
relay box
No.2 unit
relay box
Next unit
T
X2X2
T
Glow switch or pilot lamp can be
combined to easily identify the
on-off mode of SW1 and SW2.
To
No.1
unit
To
No.2
unit
Timer adapter cables
Remote controller
T
X2
SW
1
SW2
T
X2
Remote
controller cable (2-core)
Remote controller
NOTE2 : For control circuit wiring, use a wire of No. 14 AWG or a control cable according to the power supply of control
circuit.
NOTE3 : When the power supply of the control circuit is 220/240V AC,
● Do not connect the control circuit wire to the remote controller cable directly.
● Do not place the control circuit wire and the remote controller cable into the same conduit tube.
3-2 Basic wiring
Caution : Before starting all units simultaneously by the remote ON-OFF switch, be sure to connect a sequence-start timer
into the remote ON-OFF circuit. Otherwise, a rush of starting current may damage the power supply.
3-3 Switch function of remote ON-OFF switch
SW2
(Switches between remote ON-OFF and individual control)
SW1
(Switches between
remote ON and OFF.)
ON
(Start)
OFF
(Stop)
ON
(Remote ON-OFF control)
All units start together.
w1
Individual control is not available.
All units start together.
w2
Individual control is not available.
Each unit can be controlled by each
remote controller.
Remote ON-OFF switch is not available.
OFF
(Individual control)
w1 After all units start together, if SW2 is turned OFF, each unit can be individually stopped by each remote controller.
w2 After all units stop together, if SW2 is turned OFF, each unit can be individually started by each remote controller.
4. INDIVIDUAL CONTROL BY GROUPING THE
REMOTE CONTROLLERS
● Grouping the remote controllers allows individual control and centralized monitoring of units installed in different places without a
special control board.
● Remote control cables are extendible up to 500m. When the cable
length exceeds 12m, use the double-insulated two-care cable such
as Belden 9407. Also, the cable thickness must be No. 22 AWG or
above.
● When gathering the power ON/OFF switches of air conditioners
near the remote controllers, you should also install the power
ON/OFF switch near each unit to prevent electric trouble during
servicing.
66
Page 67
5. MULTIPLE REMOTE CONTROL DISPLAY
CN51
connector(5P)
GREEN
Power
supply
Electrical insulation is needed.
Local wiring
Optional multiple display
adapter
The maximumdistance between
indoor board and relay is 10m.
YELLOW
ORANGE
RED
BROWN
5
X1
X1
RL
GL
X2
X2
1
<Wiring >
Power
supply
Remote
controller
cable
Relay box
(Field supply)
Remote
controller
Remote
controller
Remote
controller
3wires
3wires
3wires
2wires
No.1 unitNo.2 unitNo.3 unit
Muitiple remote control
ON-OFF display
(Field supply)
(Operation check)
<System>
Power
supply
RL-1
GL-1
Multiple Remote Control Display
Multiple remote
controller adapter
connect to
the connector CN51
Relay box
5
X1-1
X2-1
1
<Wiring diagram>
RL-2
GL-2
RL-3
No.1 unit
GL-3
X1
X2
5
1
No.2 unit
X1
X2
5
1
No.3 unit
X1
X2
X1-2
X2-2
X1-1
X2-1
Remote controller
A
B
Brown
Red
Orange
Remote controller
A
B
Brown
Red
Orange
You can control several units with a multiple remote control display,by
wiring an optional multiple display adapter (PAC-SA88HA-E) with relays
and lamps on the market.
5-1 How to wire
(1) Connect the multiple display adapter to the connector CN51 on the
indoor controller board.
(2) Wire three of the five wires from the multiple display adapter as shown
By setting the dip swich SW1-10 to ON (PKH-2FKA), J1-10 cut (PKH-2.5/3/4FK(S)A) the air conditioner can be
started/stopped by power supply ON/OFF.
If the air conditioner is OFF before the power failure, it will not start operation by power restore.
<Wiring>
For remote control, connect the optional timer adapter (PAC-SA89TA-E)
67
A : an optional timer adapter
B : a single-throw switch
Page 68
12
Metal fixture
Screws
Hanger of indoor unit
Catch of installation plate
Terminal cover
Electrical parts box cover
Indoor controller
board
Right side panel
DISASSEMBLY PROCEDURE
PKH-3FKA2, PKH-3FKA3
OPERATING PROCEDUREPHOTOS&ILLUSTRATION
1. Removing the lower side of the indoor unit from the installation plate
(1) Remove the 2 screws.
Hang the indoor unit hangers to the catches on the installation plate.
Figure 1
2. Removing the right side panel
(1) Remove the 2 screws of the right side panel:one on the
bottom and the other on the upper right-hand side.
(2) Sliding the right side panel to the right, pull it out toward
you.
3. Removing the indoor controller board
(1) Remove the right side panel.
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Disconnect the connectors on the indoor controller board.
(4) To unhook the catches on the right-hand side of the indoor
controller board, pull the left-hand side toward you and lift
up the cover to the right. Then the indoor controller board
can be removed.
Figure 2
Photo 1
Indoor controller
board
Electrical parts
box cover
Catches
4. Removing the electrical parts box
(1) Remove the right side panel.
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Remove the room temperature thermistor and the pipe
temperature thermistor.
(4) Disconnect the vane motor connector on the indoor con-
troller board.
(5) Remove the 2 screws of the electrical parts box.
(6) Disconnect the connector of the heater lead wire connec-
tor.
(7) Disconnect the connector of the fan motor lead wire.
(8) Remove the electrical parts box.
68
Photo 2
Room temperature thermistor
Pipe temperature thermistor
Screws
Electrical parts
box
Page 69
OPERATING PROCEDUREPHOTOS&ILLUSTRATION
Catch on the left side panel
Catch on
the unit
(9) Remove the screws of the indoor controller board case,
and pull out the indoor controller board case.
Then the transformer and the capacitor can be serviced.
5. Removing the vane motor
(1) Remove the right side panel.
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Remove the 2 screws of the vane motor, and remove the
motor from the shaft.
(4) Disconnect the vane motor connector on the indoor con-
troller board.
Photo 3
Capacitor
Indoor controller
board case
Photo 4
Transformer
Electrical parts box
Screws
6 Removing the intake grilles
(1) Remove the right side panel.
(2) To remove the left side panel, remove the screw on the
bottom and the screw on the upper left-hand side.
(See Figure 3.)
1. Press up this side of the left side panel to unhook the
catch on the panel from the catch on the unit.
2. Slide the left side panel to the left to remove the panel.
Note: Fix the unit to the metal fixture securely
(3) Remove the air filters.
(4) Hold and press the center cover to remove.
(5) Remove the screws of the grilles.
(6) Pull the lower side of the grille toward you and slide the
upper to the right to remove the grilles.
7. Removing the drain pan
(1) Remove the left and right side panels.
(2) Remove the grills.
(3) Remove the electrical parts box cover.
(4) Loosen the drain hose band to remove.
(5) Remove the 3 screws of the drain pan, and slide the drain
pan toward you to remove.
Vane motor
Figure 3
Photo 5
Left side panel
Photo 6
Slide to the
right
Screws for grills
Drain pan
Screws
Indoor controller board
Grilles
Drain hose
band
Drain hose
69
Page 70
OPERATING PROCEDUREPHOTOS
8. Removing the lineflow fan and the fan motor
(1) Remove the left and right side panels.
(2) Remove the grilles.
(3) Remove the electrical parts box.
(4) Remove the drain pan.
(5) Loosen the screw that fixes the lineflow fan to the fan
motor. (See Photo 7. )
(6) Remove the 4 screws of the motor fixture, and remove the
fan motor and the motor fixture at a time (See Photo 8.)
(7) Remove the screws of the left and right motor supports,
and remove the motor supports and the fan motor. (See
Photo 9.)
(8) Remove the screw of the center support, and remove the
support. (See Photo 10. )
(9) Remove the 2 screws on the left and right sides of the heat
exchanger, and pull the bearing support toward you. (See
Photo 11.)
(10) Pull the left-hand side of the heat exchanger toward you,
and remove the lineflow fan.
Photo 7
Photo 8
Lineflow fan
Screw
Fan motor
Screws
Fan motor
Photo 11
Heat exchanger
Bearing support
Lineflow fan
Photo 9
Screw
Motor support
Photo 10
Fan motor
Lineflow fan
ScrewCenter support
Motor fixture
Screw
Motor
support
70
Page 71
13
No.
Part No.Part NameSpecification
PKH-2
Wiring
Diagram
Symbol
Recommended
Q'ty
Unit
Amount
Q'ty / set
Price
FRONT PANEL
FRONT PANEL
SCREW CAP
CATCH HOLDER
FILTER CATCH
AIR FILTER
AIR FILTER
SERVICE PANEL
PANEL CATCH
UNDER COVER
CORNER COVER
BOX ASSEMBLY
BACK PLATE
1
4
2
2
2
1
2
1
1
1
1
1
4
2
2
2
1
2
1
1
1
1
(BC25R572H06)
(BC25G057H07)
Remarks
(Drawing No.)
R01 KV5 651
R01 47J 651
R01 KV5 096
—
R01 A20 054
R01 KV5 500
R01 47J 500
T7W 580 058
—
R01 KV5 623
R01 KV5 658
R01 KV5 635
R01 KV5 808
1
2
3
4
5
6
7
8
9
10
11
FKA
1
FKA2
FKA3
FKA
PARTS LIST
STRUCTURAL PARTS
PKH-2FKA
PKH-2FKA1
PKH-2FKA2
PKH-2FKA3
1
2
11
3
10
9
4
2
3
4
5
71
8
2
7
6
Page 72
No.
Part No.Part Name
Specification
Wiring
Diagram
Symbol
Recommended
Q'ty
Unit
Amount
Q'ty / set
Price
1
2
3
4
5
6
7
8
9
10
LEFT SIDE PANEL
UNDER PLATE
UNDER PLATE
NOSE
NOSE
AIR FILTER
INTAKE GRILLE
RIGHT SIDE PANEL
BACK PLATE
TOP PLATE
BOX ASSEMBLY
BOX ASSEMBLY
DRAIN SOCKET
STRUCTURAL PARTS
PKH-2.5FKAPKH-3FKA
PKH-2.5FKA1PKH-3FKA1
PKH-2.5FKA2PKH-3FKA2
PKH-2.5FKA3PKH-3FKA3
1
2
3
8
7
9
5
4
Part number that is circled is not shown in the figure.
6
72
Page 73
STRUCTURAL PARTS
No.
Part No.Part Name
Specification
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Amount
Q'ty / set
Price
1
2
3
4
5
6
7
8
9
10
11
LEFT SIDE PANEL
UNDER PLATE
UNDER PLATE
NOSE
NOSE
AIR FILTER
INTAKE GRILLE
RIGHT SIDE PANEL
BACK PLATE
TOP PLATE
BOX ASSEMBLY
BOX ASSEMBLY
INTAKE GRILLE
DRAIN SOCKET
Part number that is circled is not shown in the figure.
4
6
73
Page 74
ELECTRICAL PARTS
FILTER
CHECK MODE
CHECK
TEST RUN
MITSUBISHI ELECTRIC
-CENTRALLY CONTROLLED STAND BY
DEFROST
ON
CHECK DRY
COOL
HEAT
CHECK
SET TEMP
TIMER OFF
AUTO STOP
AUTO START
C
HR
C
LOW HIGH
AUTO RETURN
CHECK TEST RUN
POWER
ON/OFF
HEAT
SET
TEMPERATURE
AUTO COOL/DRY
COOLERWARMER
TIMER MODE HOURS
FAN SPEED LOW/HIOGH
AIR
DISCHARGE
UP/DOWN
SWING
STOP
CHECK TEST RUN
PKH-2FKA
PKH-2FKA1
PKH-2FKA2
PKH-2FKA3
1
34
2
5
6
3
4
27
28
29
26
33
32
31
14
30
7
13
8
12
19
20
22
21
23
24
25
15
911
10
16
For PKH-2FKA
PKH-2FKA1
17
For PKH-2FKA2
PKH-2FKA3
18
74
Page 75
No.
Part No.Part NameSpecification
FKA
2
FKA3
FKA
FKA
1
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Amount
PKH-2
Q'ty / set
Price
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
BEARING SUPPORT
BEARING MOUNT
SLEEVE BEARING
LINEFLOW FAN
VANE MOTOR
NOZZLE ASSEMBLY
LEFT ROTARY VANE
CENTER SUPPORT
VANE SLEEVE
DRAIN HOSE
TERMINAL COVER
RIGHT ROTARY VANE
ARM
GUIDE VANE
REMOTE CONTROLLER
REMOTE CONTROLLER COVER
REMOTE CONTROLLER
REMOTE CONTROLLER CABLE
CONTROL BOX COVER
INDOOR CONTROLLER BOARD
CONTROLLER CASE
FUSE
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
TRANSFORMER
TRANSFORMER
FAN MOTOR CAPACITOR
THERMISTOR
WATER SHIELD
MOTOR SUPPORT
FAN MOTOR
RUBBER MOUNT
MOTOR COVER
HEAT EXCHANGER
HEAT EXCHANGER
DRAIN SOCKET
DRAIN HOSE
AUTO VANE
ARM
GUIDE VANE
GUIDE VANE(WITH HANDLE)
VANE MOTOR
REMOTE CONTROLLER CABLE
ROOM TEMPERATURE THERMISTOR
PIPE TEMPERATURE THERMISTOR
TERMINAL COVER
FAN MOTOR CAPACITOR
INDOOR CONTROLLER BOARD
INDOOR CONTROLLER BOARD
FUSE
CONTROLLER COVER
CONTROLLER CASE
TRANSFORMER
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
MOTOR BAND
FAN MOTOR
MOTOR LEG
RUBBER MOUNT
MOTOR BAND
RIGHT LINEFLOW FAN
CENTER SUPPORT
SLEEVE BEARING
BEARING MOUNT
REMOTE CONTROLLER
REMOTE CONTROLLER
Specification
2.0+ 440V
250V 6.3A
2P(1/2)
3P(1/2/3)
3P(L/N/;)
D094P40MS
Q'ty / set
PKH-2.5PKH-3
1
FKA
FKA FKA3
FKA2
1
1
2
2
3
3
16
16
4
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
FKA FKA3
1
1
2
2
3
3
16
16
4
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
FKA
FKA2
1
2
3
16
4
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
Remarks
(Drawing No.)
1
1
2
(BG25H301H02)
3
(BG25J821H01)
16
(BG25J821H02)
4
1
1
1
1
(BG02J608H07)
1
1
1
2
(BG02A648G02)
1
(BG25B573H06)
1
1
1
1
1
(BG02H065H01)
1
1
(BG02A534H16)
1
2
(BG02H178H01)
1
1
(BG00R259G07)
1
1
1
1
Wiring
Recom-
Diagram
mended
Symbol
MV
RT1
RT2
C
I.B
I.B
F1,2<I.B>
T
TB5
TB4
TB2
MF
R.B
R.B
Q'ty
Unit
Price
Amount
77
Page 78
No.
Part No.Part Name
Specification
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Amount
Q'ty / set
Price
1
2
3
4
5
6
7
8
9
BEARING MOUNT
SLEEVE BEARING
LEFT LINEFLOW FAN
BEARING BAND
HEAT EXCHANGER
DRAIN PAN
DRAIN PAN
JOINT SHAFT
CENTER COVER
DRAIN HOSE
ELECTRICAL PARTS
PKH-4FKSA
PKH-4FKSA1
PKH-4FKSA2
PKH-4FKSA3
1
2
35
37
For PKH-4FKSA
34
3
36
For
PKH-4FKSA1, PKH-4FKSA2,
PKH-4FKSA3
4
5
32
29
6
33
31
28
30
27
24
8
7
10
12
15
16
25
26
23
22
11
9
13
78
17
14
18
19
20
21
Page 79
No.
Part No.Part Name
R01 16G 002
10
11
12
R01 12G 223
13
T7W 556 305
14
R01 06A 202
15
R01 22A 202
16
17
R01 576 255
18
T7W 503 310
19
T7W 71J 310
T7W 520 239
20
21
22
T7W 50J 799
23
T7W 512 716
24
T7W 517 716
25
T7W 509 716
26
27
R01 571 762
28
29
R01 16G 105
30
31
R01 17G 115
32
33
R01 12G 103
34
R01 KV5 102
35
T7W 53J 200
36
T7W 418 200
37
—
—
—
—
—
—
—
—
—
—
AUTO VANE
ARM
GUIDE VANE
GUIDE VANE(WITH HANDLE)
VANE MOTOR
REMOTE CONTROLLER CABLE
ROOM TEMPERATURE THERMISTOR
PIPE TEMPERATURE THERMISTOR
TERMINAL COVER
FAN MOTOR CAPACITOR
INDOOR CONTROLLER BOARD
INDOOR CONTROLLER BOARD
FUSE
CONTROLLER COVER
CONTROLLER CASE
TRANSFORMER
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
MOTOR BAND
FAN MOTOR
MOTOR LEG
RUBBER MOUNT
MOTOR BAND
RIGHT LINEFLOW FAN
CENTER SUPPORT
SLEEVE BEARING
BEARING MOUNT
REMOTE CONTROLLER
REMOTE CONTROLLER
Specification
3.0+ 440V
250V 6.3A
2P(1/2)
3P(1/2/3)
3P(L/N/;)
D10A4P70MS
Q'ty / set
PKH-4
1
22
FKSA
FKSA2
2
4
2
4
22
4
1
1
1
1
1
1
4
1
1
1
1
1
1
2
4
22
4
1
1
1
1
1
1
FKSA FKSA3
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
(BG25H301H02)
(BG25J821H01)
(BG25J821H02)
(BG02J608H07)
(BG02A648G02)
(BG25B573H06)
(BG02H065H01)
(BG02A534H17)
(BG02H178H01)
(BG00R259G07)
Wiring
Recom-
Diagram
mended
Symbol
MV
RT1
RT2
C
I.B
I.B
F1,2<I.B>
T
TB5
TB4
TB2
MF
R.B
R.B
Q'ty
Unit
Price
Amount
79
Page 80
14
Part No.
Pipe length
Pipe size O.D.
Connection method
PAC-05FFS-E
5m
Liquid:{9.52 Gas:{15.88
Indoor unit:Flared Outdoor unit:Flared
PAC-07FFS-E
7m
PAC-10FFS-E
10m
PAC-15FFS-E
15m
Part No
Model Name
PAC-SC32PTA
Program timer
Parts name
Parts No.
Exterior dimensions (inch)
Installation
Type of clock
Clock accuracy
Display-Time
-Week
-Timer setting unit
Program cycle
Timer setting unit
No. of set points
Power rating
Program timer
PAC-SC32PTA
5-4/32o4-23/32o23/32 (130o120o18mm)
Wall mount
Quartz
±50 second / month at 25:
Liquid crystal display
Liquid crystal display
Liquid crystal display
24 hours
30 minutes
48 / day
5V DC ±5% (Suppled by Remote Controller)
28˚C
26
˚C
8:00
Normal
operation
23:00
Setback
operation
8:00
Normal
operation
Part No.
Pipe length
Pipe size O.D.
Connection method
PAC-SC51PI-E
5m
Liquid:{9.52 Gas:{19.05
Indoor unit:Flared Outdoor unit:Flared
PAC-SC52PI-E
7m
PAC-SC53PI-E
10m
PAC-SC54PI-E
15m
OPTIONAL PARTS
1. REFRIGERANT PIPES
Service Ref. : PKH-2FKA3, PKH-2.5FKA2, PKH-2.5FKA3, PKH-3FKA2, PKH-3FKA3
Service Ref. : PKH-4FKSA2, PKH-4FKSA3
Note 1. How to connect refrigerant pipes.
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as the
connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind
caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made,
open the stop valve on the outdoor unit to allow refrigerant gas to flow.
If piping length exceeds 5m,an additional charge of refrigerant is needed.
Note 2. The following main parts are contained in the optional refrigerant piping kit.
Daily timer can be set in 30 minutes units for up to 24 hours.
Each unit can be set for unit ON, unit OFF, or setback operation.
(2) Setback operation (PAC-SC32PTA)
Set back operation is useful for reducing running costs
e.g. At a hotel with a 24-hour system
(3) Weekly timer function
8:00~23:00 Cooling operation with set temperature at 26°C
23:00~8:00 Setback operation with 2 degrees of setback
As shown in the chart on the right, the set temperature rises 2 degrees
automatically during the setback operation. When the setback operation
ends, normal operation will begin.
Daily timer function can apply to each day of the week.
80
Page 81
SET/MONITOR
SET
S MT W TF S
MONITOR
PROERAN TIMER
PAC-SC32PTA
TODAY
ON
WEEKLY
SETTING
OFF
ON
SET BACK
OFF
CLOCKDAILY TIMER
SET BACK
SET BACK
DAILY
SETTING
12 15 18 21 24
0 3 6 12 15
FILTER
CHECK MODE
CHECK
TEST RUN
4
Use 5-wire cable
Connect 2-wire cable
to indoor unit
Connect to CN1Connect to CN1
2-3. How to connect program timer
1
2
3
4
5
BRN
RED
ORN
YLW
GRN
(1) Install the program timer next to the remote controller the same way as the remote controller is installed.
(2) Connect the program timer and the remote controller with a 5-wire cable as shown in the figure below
NOTE:While the program timer is connected to the remote controller, the
24hour ON/OFF timer on the remote controller will not operate.
2-4. Names and functions
<PAC-SC32PTA>
WEEKLY TIMER SETTING DISPLAY
CURRENT TIME DISPLAY
SET BACK DISPLAY
DAILY TIMER SETTING DISPLAY
Used for selection of if or not the day operation pattern set by PATTERN SETTING is to
be applied in weekly day unit
setting.
During MONITOR status,current
time is display.
During Daily timer setting, a
time desire for timer setting is
Indicates the setting set
back range.
24 hours is divided into 48 blocks and each
block express 30 minutes.
The block display consists of 3 pattern.
displayed.
Set back can be done in the range of 1,2,4,6
and 8°C.
SET BACK SETTING SW
ON
OFF
SET BACK
0 3 6 12 15
12 15 18 21 24
SET BACK
SET BACK
Used for set back setting.
DAILY
ON
SETTING
OFF
ON/SET BACK/OFF SW
Used to specify the time setting pattern.
SET/MONITOR DISPLAY
During SET is display, clock adjustment,
change of weekly day, daily and weekly timer
setting can be performed.
During MONITOR is display, all switches
except SET/MONITOR SW are invalidated.
This is normal status.
SET
MONITOR
SET/MONITOR
PROERAN TIMER
PAC-SC32PTA
S M T W T F S
WEEKLY
TODAY
SETTING
CLOCKDAILY TIMER
WEEK DAY SETTING SW
DAILY TIMER SW
Used for week day setting.
MODE SELECTOR SW
Using this switch select “MONITOR” or “SET”
Mode.
“MONITOR” :Indicates the current timer set-
ting. All switch expect MODE
SELECTOR SW are invalidated
then.This is the normal status.
“SET”: Set to “SET” mode for clock adjustment,
charge of week day, daily and
weekly timer setting.
CLOCK ADJUSTMENT SW
Used for adjustment of the current time.
Push SW to advance the time. Each time the button is
pushed the time advance by 1 minute, pushing continuously
advances by 1 minute at 0.5 second interval, and when the
lower digit of minute becomes 0 indication advances in 10 minutes unit.
SW is used for reversing the time. Each time the button is
pushed the time reverses by 1 minute, pushing continuously
reverses the time by 1 minute at 0.5 second interval, and when
the lower digit of minute becomes 0 indication reverses in 10
3. TIMER ADAPTER
minutes unit.
This adapter is needed for system control and for operation via external contacts. Adapter connection is described on page 65.
Part No.PAC-SA89TA-E
ORN1
BRN
RED
Used for timer setting in 30 minutes unit.
WEEKLY TIMER SW
Used for setting timer in day of week unit.
Pushing SW moves the week day light
display in order of
S → M → T → W
enabling to set the week day.
2
3
…
4. MULTIPLE REMOTE CONTROLLER ADAPTER
This adapter is needed for remote indication (operation/check). Adapter connection is described on page 67.
Part No.PAC-SA88HA-E
81
Page 82
BACK
ACTIVE
BYPASS
POWER
ON/OFF
DUAL
CENTRAL
AHEAD
MITSUBISHI ELECTRIC
ENGAGED
GROUP
ACTIVE BYPASS
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
DUAL CENTRAL
12345678910
117
117
BACK
ACTIVE
BYPASS
POWER
ON/OFF
DUAL
CENTRAL
AHEAD
ENGAGED
GROUP
ACTIVE BYPASS
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
DUAL CENTRAL
12345678910
113
113
12
10 9 8 7 6 5 4 3 2 1
56.3
11
23.5
8
BACK
ACTIVE
BYPASS
POWER
ON/OFF
DUAL
CENTRAL
AHEAD
MITSUBISHI ELECTRIC
ENGAGED
GROUP
ACTIVE BYPASS
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
DUAL CENTRAL
12345678910
5. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units. When using the PAC-805RC, the program timer adapter (PAC825AD)is also needed.
Part No.PAC-805RC
5-1. Dimensions
5-2. Functions
"ENGAGED" indicator
When this indicator is lit, transmission is in
progress and all switches are inoperative.
POWER ON/OFF switch
Operation ON/OFF switch.
▲BACK ▼AHEAD buttons
These buttons are used to designate
DUAL/CENTRAL switch
This change-over switch governing the oper-
ation of the accessory remote controller.
"DUAL"
Instructions from both the accessory
remote controller and the centralized
remote controller are valid. (Priority given
to the last instruction received.)
"CENTRAL"
ON/OFF switching by the accessory
remote controller is invalidated. Operation
is controlled by the centralized remote controller only.
Initial setting is "DUAL".
the attached unit(s). (They designate
the unit to be centrally controlled.)
●When group “00” is designated; collective ON/OFF instruction is sent to all
units.
●When group “01”-“16“ is designated;
ON/OFF instruction is sent to the designated units only.
ACTIVE/BYPASS switch
This is a change-over switch for the
program timer.
(It selects timer operation on the program timer.)
Use “BYPASS” when a program timer
is not connected.
LCD Matrix Display
This display indicates the operational sta-
tus of all connected units either by steady
lighting or by flashing.
“ACTIVE”
The switch turns ON/OFF operational
instructions from the program timer
automatically.
“BYPASS”
ON/OFF Operation is by the central-
Independent “DUAL / CENTRAL” and “ACTIVE / BYPASS” setting of all the groups is possible. When the power supply to the
centralized remote controller is cut due to power failure, all settings will return to original “DUAL” and “BYPASS”.
5-3. Connection method
(1) Connections in the power supply cord.
1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-wrap.
Connect a single phase 200V AC (220, 230, 240V) to
As EEis the GND terminal, be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap. Use a Ø1.6
AA NN
.
ized remote controller only.
Initial setting is “BYPASS”.
(AWG 14) or above two-wire cable for the transmission line.
CAUTION : Never connect the power supply cord to the transmission terminal-block.
82
Page 83
TERMINAL-BLOCK
FOR TRANSMISSION
TERMINAL-BLOCK
OF POWER SUPPLY
Transmission
Tie-wrap
TRANSFORMER
A N E
Fuse(5A)
Tie-wrap
(W)(R) (O)
(BR)
200
220
230
T
(Y)
240
5A
A
N
E
Wiring has to be changed when
a 200,230 or 240V power is used.
(2) Connection method of centralized remote controller and power supply board.
1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable.
To adaptor's
terminal-block
ENGAGED
GROUP
12345678910
GROUP
SELECTION
PROGRAM
ACTIVE BYPASS
TIMER
CONTROLLER
DUAL CENTRAL
OPERATION
Centralized remote
controller
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER
ON/OFF
AHEAD
Non-polar,
two-wire cable
Power supply board box
To adaptor's
terminal-block
POWER
SUPPLY
2. Wiring diagram3. Be sure to set the maximum address number with the
dip switch SW17 on the centralized remote controller.
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER
ON/OFF
AHEAD
Dip switch
SW17
Centralized
remote controller
Power supply
board
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
83
Page 84
Length : 2m (6' 7")
Length : 2m (6' 7")
Length : 2m (6' 7")
6. PROGRAM TIMER ADAPTER
This adapter is needed when a program timer(PAC-SC32PTA)or a centralized remote controller(PAC-805RC)is used.
Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out the work.
(1) Connections in the adapter box
1. Connect the power supply cord to the terminal-block and fix it in-place with a tie-wrap.
Connect a single phase 200V (220, 230, 240V) AV to
As EEis the GND terminal, be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap (when a centralized
remote controller is being used).
CAUTION : Never connect the power supply cord to the transmission terminal-block
Fig-1Fig-2
AA NN
.
TERMINAL-BLOCK
FOR
TRANSMISSION
Tie-wrap
Transmission cord
CN22
Dip switch
TRANS
CN1 CN21 CN51 CN30CN42 CN50 CN40
Fuse(5A)
TRANSFORMER
(AG)
SW1
A N E
POWER SUPPLY CORD
TERMINAL-BLOCK
FOR POWER
SUPPLY
Tie-wrap
Terminal block for
transmission to
program timer or
centralized remote
controller
Wiring has to be changed when 200V power supply is used.
(W)
CN22
TRANS
(B)
200
SW1
T
(Y)
240
220
5A
(2) When the centralized remote controller is used, set the address number with the dip switch SW1 of the