13. PARTS LIST········································67
14. OPTIONAL PARTS·····························76
PKH-2.5FKHA3, PKH-3FKHA3
and PKH-4FKHSA3 are added
in REVISED EDITION-A.
Please void OC130.
This manual does not cover the
following outdoor units. When
servicing them, please refer to
the service manual No.OC128
REVISED EDITION-C and this
manual in a set.
Disperses airflow up and
down as well as adjusts the
angle of air flow direction.
FilterAir intake grille
Air outletAir outlet
Swing louvers
Air flow can be changed to horizontally
by moving the Guide vane to the left or
right.
Guide vane
● Indoor Unit
● Remote controller
● Once the operation of the unit is set, subsequent operations can only be performed by pressing the ON/OFF button
repeatedly.
● Operation buttons
w button
This switches between continuous
operation and the timer operation
button
Press this button to switch the cooler
electronic dry (dehumidify), automatic and heater modes.
i TEMP. button
This sets the room temperature. The
temperature setting can be performed in 1°C units.
Setting range :
Cooler 19°C to 30°C
Heater 17°C to 28°C
q button
This sets or switches the current
time, start time and stop time.
241
The sets the ventilation fan speed.
button
FILTER
CHECK MODE
TEST RUN
ON/OFF button
This switches between the operation
and stop modes each time it is
pressed. The lamp on this button
lights during operation.
j button
This adjusts the vertical angle of the
ventilation.
FILTER button
This resets the filter service indication display
The model name of the remote controller is indicated.
PAR-JH241KA(2.5 / 3 / 4)
PAR-JH150KA(1.6 / 2)
k button
This switches the horizontal fan
motion ON and OFF.
(This button does not operate in this
model.)
3
CHECK-TEST RUN button
Only press this button to perform an
inspection check or test operation.
Do not use it for normal operation
Page 4
● Display
CENTRALLY
CONTROLLED display
This indicates when the unit is con-
trolled by optional features such as
central control type remote controller.
w display
This indicates when the continuous
operation and time operation modes
are set.
It also display the time for the timer
operation at the same time as when
it is set.
OPERATION MODE display
This indicates the operation mode.
STANDBY display
This indicates when the standby
mode is set from the time the sleep
operation starts until the heating air
is discharged.
r display
The current time , start time and stop
time can be displayed in ten second
intervals by pressing the time switch
button. The start time or stop time is
always displayed during the timer
operation.
241
display
The selected fan speed is displayed.
FILTER
CHECK MODE
TEST RUN
In this display example on
the bottom left, a condition
where all display lamps light
is shown for explanation purposes although this differs
from actual operation.
j display
This indicates the air direction.
—88°C display
The temperature of the suction air is
displayed during operation. The display range is 8° to 39°C. The display
flashes 8°C when the actual temperature is less than 8° and flashes
39°C when the actual temperature is
greater than 39°C.
Operation lamp
This lamp lights during operation,
goes off when the unit stops and
flashes when a malfunction occurs.
DEFROST display
This indicates when the defrost oper-
ation is performed.
CHECK MODE
TEST RUN
This display lights in the check mode
or when a test operation is performed.
display
CHECK display
This indicates when a malfunction
has occurred in the unit which should
be checked.
—88°C display
This displays the selected setting
temperature.
Display
This lamp lights when electricity is
supplied to the unit.
Caution
● Only the display lights when the unit is stopped and power supplied to the unit.
● When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a
malfunction.
● When the central control remote control unit, which is sold separately, is used the ON-OFF button, button andi TEMP button do not operate.
● “NOT AVAILABLE” is displayed when the k button are pressed.This indicates that this room unit is not equipped with
the fan direction adjustment function and the louver function.
FILTER
This display lights when the filter
need to be cleaned.
The unit of pressure has been changed to MPa on the international system of unit (SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa) = 10.2(kg/FF)
5. OUTLET AIR SPEED AND COVERAGE RANGE
2
PKH-3FKHA
PKH-3FKHA3
12.4
Air flow m3/
Air speed m/
min
sec
Coverage range m (ft)
PKH-1.6FKHA3
13
4.0
9.1
PKH-2FKHA
13
4.0
9.1
PKH-2.5FKHA
3
PKH-2.5FKHA3
20
4.9
12.4
The air coverage range is the value up to the position where the air speed is 0.25m/sec. when air is blown out horizontally from
the unit at the Hi notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room.
Range for left rear piping openingRange for left rear piping opening
12-ø6 hole for tapping screw
84-ø6 hole for
tapping screw
Wall fixture
Unit out line
Unit center
41-ø12 hole for bolt
295225
18
18
91
900
1270
595
285
245
19
240280314
750
90
Drainage range
on right-hand side
13 91=(1183)
180
Drainage range
on left-hand side
Unit : mm
17
Page 18
18
130
Rear side wiring arrangement opening.
120
FILTER
CHECK MODE
TEST RUN
FILTER
CHECK MODE
TEST RUN
46
83.5
SW18
SW17
CAUTION
2. REMOTE CONTROLLER
Unit : mm(inch)
18
Page 19
6
SYMBOL
C
CN1 <R.B>
CN2 <R.B>
CN2L <I.B>
CN51 <I.B>
FAN2
F1 <I.B>
FS1,2
H
I.B
LED1 <I.B>
LED2 <I.B>
LS
MF
MV
R.B
RT1
NAME
FAN MOTOR CAPACITOR
PROGRAM TIMER CONNECTOR
REMOTE SWITCH CONNECTOR
LOSSNAY CONNECTOR
CENTRALLY CONTROL CONNECTOR
EMERGENCY OPERATION CONNECTOR
FUSE (6.3A 250V)
THERMAL FUSE (121:/10A)
HEATER
INDOOR CONTROLLER BOARD
DC 12V POWER LED
DC 5V POWER LED
LIMIT SWITCH
FAN MOTOR
VANE MOTOR
REMOTE CONTROLLER BOARD
ROOM TEMPERATURE THERMISTOR
(0:/15".25:/5.4"DETECT)
NAME
PIPE TEMPERATURE THERMISTOR
(0:/15".25:/5.4"DETECT)
MODE SELECTOR
ADDRESS SELECTOR
EMERGENCY OPERATION SWITCH
MODEL SELECTOR
MODEL SELECTOR
ADDRESS SELECTOR
FUNCTION SELECTOR
TRANSFORMER
POWER SUPPLY TERMINAL BLOCK
INDOOR/OUTDOOR CONNECTING WIRE
TERMINAL BLOCK
REMOTE CONTROLLER TRANSMISSION LINE
TERMINAL BLOCK
FAN MOTOR RELAY
VARISTOR
HEATER THERMAL SWITCH
HEATER CONTACTOR
WIRING DIAGRAM
PKH-1.6FKHA3 , PKH-2FKHA3
MF
C
I.B
POWER SUPPLY
~(1 PHASE)
AC220-240V 50Hz
AC220V 60Hz
WHT
RED
FAN1
1
FAN2
1 3 5
SW2
ON
OFF
123456101234
BLK
X4
X4
SW5
L
N
WHT
CN6V
VANE
ZNR
1234
LS
MV
31
SW6
RED
RED
BLU
CND
POWER
SW3
SW7
ON
OFF
123
SW1
123456789
REDRED
TB2
RED
BLU
GRN/YLW
WHT
F1
12
88H
53
240V
230V
220V
RED
YLW
ORN
YLW
CNT
TRANS
LED1 12V
POWER
HEATER
CN24
1
BLU
4
T
LED2 5V
POWER
CENTRALLY
CONTROL
FS2
FS1
11.1VAC
14.2VAC
REMOCON
POWER
CN40
CN51
H
RED
43
35
42 13
CN21
PIPE
CN20
INTAKE
RED
211133
LOSSNAY
CN2L
BRN
CN24
HEATER
GRN/YLW
BRN
CN4T
TRANS
TO
REMOCON
CN22
OUTDOOR
CN30
1122
CN23
VANE
I.B
L
N
POWER SUPPLY
~(1 PHASE)
AC220-240V 50Hz
AC220V 60Hz
TB2
2FKHA1.6FKHAMODELS
ON
SW7
OFF
TRANSMISSION WIRES
DC12V
TB5
2
BLU
1
12
3
2
1
BLU
BRN
ORN
YLW
TB4
3
TO OUTDOOR UNIT
2
CONNECTING WIRES
1
DC12V
R.B
RT2
RT1
2 1
GRY
16
88H
BRN
YLW
1 2
63
GRY
ON
OFF
SW18
OFF
ON
4321
SW17
OFF
ON
87654321
26H
123123
TB6
45231
3 2 1
A01 B02
CN1
CN2
NOTES :
1. Since the indoor fan motor (MF) is connected with 230, 240V power. using 220V power will require a setting change of the dip switch (SW7<I.B>) on the indoor
controller board as shown in fig :
fig w1
Indoor fan motor (MF) for 220V.
2. Since the indoor transformer (T) is connected with 240V power if 220,230V power is used. Change the wiring connection showing fig :
fig w2
When power supply is
w1.
230V
220V
SW5
ON
OFF
240V
230V
220V
2 3 4
1
YELLOW
ORANGE
RED
ON
OFF
1
2 3 4
w2.
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers.
5. Symbols used in wiring diagram above are, : Connector, / : Terminal block.
6. Emergency operation
If remote controller or microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board.
[Check items]
(1)Make sure that no other trouble exist the outdoor unit. Trouble with the outdoor unit prevents emergency operation.
(If any trouble exists the outdoor unit error code “P8”will be displayed on the remote controller and the trouble position will be shown on the outdoor controller
board LED. See electric wiring diagram of the outdoor unit for details.)
(2)Make sure that there is no trouble with the indoor fan.
Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with the remote controller is not possible).
[Emergency operation procedure]
(1)Set the dip switch (SW3<I.B>) on the indoor controller board to
(2)Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker.
(3)During emergency operation indoor fan runs at high speed but automatic vane remains stop.
(4)Thermostat will mot function. Cold air blows out for defrosting during heating thus do not operate defrosting for along time.
(5)Emergency cooling should be limited to 10 hours maximum.
(The indoor unit heat exchanger may freeze).
(6)After every operation, set all dip switches (SW3<I.B>) to OFF.
1 on and 2 off for cooling and 1 - 2 on for heating.
19
Page 20
PKH-2.5FKHA2 , PKH-3FKHA2 , PKH-4FKHSA2
J9
2
CN2
OFF
ON
4321
SW18
87
N
L
LED1 12V
POWER
X4
C
MF
L
N
GRN/YLW
SW7
CN51
CENTRALLY
CONTROL
LED2 5V
POWER
I.B
3
YLW
BRN
GRY
GRY
16
26H
1 2
88H
HEATER
CN24
65
GRN/YLW
BLU
RED
TB2
FS2
H
REDRED
BLU
1
2
53
88H
FS1
ON
OFF
TRANSMISSION WIRES
DC12V
1
2
TB6
A01 B02
OFF
ON
R.B
45231
CN1
3 2 1
87654321
SW17
HEATER
CN24
REMOCON
POWER
CN40
42 13
J5
42
SW2
ON
OFF
123456
SW6
1234
109654
J1
1234
SW7SW3
ON
OFF
12
TO
REMOCON
CN22
12
OFF
ON
12341234
PKH-4
PKH-2.5,3
MODELS
RT2
2
CN27
D.U.M
I.B
TO OUTDOOR UNIT
CONNECTING WIRES
DC12V
1
T
ZNR
F2F1
MV
12345
1
6
1
1
43
2
35
3
211133
FAN1
POWER
OUTDOOR
TRANS
VANE
LOSSNAY
TRANS
CND
CN30
CN6V
CN4T
CN2L
CNT
DRAIN
CN50
INTAKE
CN20
PIPE
CN21
1122
RT1
POWER SUPPLY
~(1 PHASE)
AC220-240V 50Hz
AC220V 60Hz
WHT
BLK
RED
TB2
POWER SUPPLY
~(1 PHASE)
AC220-240V 50Hz
AC220V 60Hz
BRN
TB5
BLU
BLU
TB4
6
ORN
YLW
BRN
BRN
RED
RED
220V
14.3VAC
10VAC
230V
240V
BLU
YLW
WHT
RED
YLW
ORN
RED
X4
SYMBOL
C
CN1 <R.B>
CN2 <R.B>
CN2L <I.B>
CN27 <I.B>
CN51 <I.B>
F1.2 <I.B>
FS1.2
H
I.B
J1
J5
J9
LED1 <I.B>
LED2 <I.B>
MF
MV
R.B
NAME
FAN MOTOR CAPACITOR
PROGRAM TIMER CONNECTOR
REMOTE SWITCH CONNECTOR
LOSSNAY CONNECTOR
DRAIN LIFT-UP MECHANISM CONNECTOR
CENTRALLY CONTROL CONNECTOR
FUSE (6.3A 250V)
THERMAL FUSE <117:/PKH-2.5,3:10A PKH-4:16A>
HEATER
INDOOR CONTROLLER BOARD
MODE SELECTOR JUMPER RESISTORS
MODE SELECTOR JUMPER RESISTORS
MODE SELECTOR JUMPER RESISTORS
DC 12V POWER LED
DC 5V POWER LED
FAN MOTOR
VANE MOTOR
REMOTE CONTROLLER BOARD
NAME
ROOM TEMPERATURE THERMISTOR
(0:/15".25:/5.4"DETECT)
PIPE TEMPERATURE THERMISTOR
(0:/15".25:/5.4"DETECT)
ADDRESS SELECTOR
EMERGENCY OPERATION SWITCH
MODEL SELECTOR
MODEL SELECTOR
ADDRESS SELECTOR
FUNCTION SELECTOR
TRANSFORMER
POWER SUPPLY TERMINAL BLOCK
INDOOR/OUTDOOR CONNECTING WIRE TERMINAL BLOCK
REMOTE CONTROLLER TRANSMISSION LINE
TERMINAL BLOCK
FAN MOTOR RELAY
VARISTOR
HEATER THERMAL SWITCH
HEATER CONTACTOR
PKH-2.5FKHA3 , PKH-3FKHA3 , PKH-4FKHSA3
NOTES:
1. Since the indoor fan motor (MF) is connected with 230, 240V power, using 220V power will require a setting change of the dip switch (SW7<I.B>) on the indoor
controller board as shown in fig :
fig w1
Indoor fan motor (MF) for 220V.
2. Since the indoor transformer (T) is connected with 240V power, if 220,230V power is used. Change the wiring connection showing fig :
fig w2
When power supply is
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers.
5. Symbols used in wiring diagram above are, : Connector, / : Terminal block.
6. Emergency operation
If remote controller of microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board.
[Check items]
(1) Make sure that no other trouble exist the outdoor unit. Trouble with the outdoor unit prevents emergency operation.
(If any trouble exists the outdoor unit error code “P8” will be displayed on the remote controller and the trouble position will be shown on the outdoor controller
board LED. See electric wiring diagram of the outdoor unit for details.)
(2)Make sure that there is no trouble with the indoor fan.
Emergency operation will be continuous operation mode due to power ON/OFF(ON/OFF with the remote controller is not possible).
[Emergency operation procedure]
(1)Set the dip switch (SW3<I.B>) on the indoor controller board to 1 on and 2 off for cooling and 1 - 2 on for heating.
(2)Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker.
(3)During emergency operation indoor fan runs at high speed but automatic vane remains stop.
(4)Thermostat will not function. Cold air blows out for defrosting during heating thus do not operate defrosting for along time.
(5)Emergency cooling should be limited to 10 hours maximum.
(The indoor unit heat exchanger may freeze).
(6)After every operation, set all dip switches (SW3<I.B>) to OFF.
w 1.
230V
220V
SW7
ON
OFF
240V
230V
220V
2 3 4
1
YELLOW
ORANGE
RED
ON
OFF
2 3 4
1
20
w 2.
Page 21
7
Indoor
heat
exchanger
Indoor unit
Refrigerant pipe
(option)
19.15mm( 3/4")
(with heat insulator)
Refrigerant pipe
(option)
9.52mm( 3/8")
(with heat insulator)
Flexible tube
Flared
connection
Ball valve
Strainer
Ball valve
(with Service port)
Oil separator
4-way valve
Service
port
(check)
Service
port
High pressure
control switch
Accumulator
Compressor
Strainer
Restrictor
valve
Outdoor heat exchanger
Outdoor coil
thermistor
(TH3)
Pipe
temperature
thermistor
(RT2)
Distributor
with
strainer
Capillary
tube
Capillary
tube
Restrictor
valve
Strainer
Bypass
valve
Outdoor unit
PKH-4 (O.D.4.0 I.D.2.0 L400)
PUH-4 (O.D.3.2 I.D.2.0 L820) 2pcs
Refrigerant flow in cooling
Refrigerant flow in heating
w 1 In addition, the centralized and remote control can be operated.
w 2 The modes which indicate the sources of trouble are listed below.
● EO=Signal transmitting/receiving error
● P1=Room temperature thermistor malfunction
● P2=Indoor coil thermistor malfunction
● P4=Drain sensor malfunction
● P5=Drain over flow
● P6=Coil frost/overheat protection
● P7=System error
● P8=Outdoor unit trouble
w 3 The CHECK switch will show if an error has occurred in the past.
w 4 Fan runs on low speed for 1 minute in order to remove overheat air.
w 5 The 3-minute (6 minutes … heating mode) time-delay functions after compressor stops.
w 6 FAN or AUTO mode is selected by the indoor dip switch setting.
w 7 In FAN mode, fan speed and vane operation depend on the remote controller setting. (Compressor is OFF.)
22
Page 23
COOLING OPERATION
COOL operation
Four-way valve/OFF
NO
NO
NO
Vane setting notch
Initial
COOLING
w8
60 deg downward angle
70 deg downward angle
NO
Vane horizontal
w9
Vane initial
setting
Vane
Fan speed
LOW
Downward
discharge
1 hour
airflow
Compressor
thermostat
ON
Allowance
cancel
NO
YES
YES
YES
YES
NO
NO
YES
YES
NO
w11
YES
3-minute
time delay
6-minute
time delay
3-minute
compressor
operation
w10
Coil frost
prevention
Cooling area
NO
NO
YES
NO
YES
NO
Allowance
period
NO
6 minute
time delay
Allowance set
YES
Coil frost protection
YES
10-minute
NO
compressor
Allowance cancel
NO
compressor
temperature is
Compressor ON
operation
YES
Coil frost
protection
NO
16-minute
operation
YES
Indoor pipe
1°C or lower
NO
1
YES
YES
Coil frost
prevention
Compressor OFF
Indoor coil
temperature is
10°C or higher
YES
3-minute
time delay
Coil frost
prevention release
NO
NO
1 min continue
FAN speed
FAN speed
LOW 5 min.
LOW
elapse
YES
NO
YES
Outdoor unit
trouble
w 8 When operation stops or changes to cooling or dry mode, the auto vane turns to a horizontal angle. IF operation changes
during auto vane SWING, the auto vane will continue to swing.
w 9 When operating TEST RUN, the thermostat will be continuously ON.
w10 After 3 minute compressor operation, if the indoor coil thermistor reads -15°C or below for 3 minutes, the compressor will
stop for 6 minutes.
w11 Cooling area : Indoor coil temperature is more than 5 degrees above the room temperature.
Heating area : Indoor coil temperature is more than 5 degrees below the room temperature.
FAN area : Indoor coil temperature is within 5 degrees either way of the room temperature.
23
Page 24
HEATING OPERATION
Heat operation
Initial
HEATING
YES
NO
Defrosting
NO
Hot adjust
in process
NO
NO
Compressor
thermostat ON
Indoor piping
YES
trouble
1
w15
2
YES
YES
YES
YES
YES
NO
Compressor ON
3 min. restart
prevention
6 min. restart
prevention
Hot adjust start
FAN SPEED
Very low
Vane setting notch
NO
Vane initial setting
Four-way valve ON
Compressor ON
w9
Allowance cancel
NO
-15°C or lower
Outdoor unit
FAN SPEED
Very low airflow
Compressor OFF
NO
10-minute
compressor
operation
Allowance cancel
w11
Heating
FAN STOP
w11
Airflow area
20 min. elapse
YES
Airflow area
Heating area
w11
Airflow area
Cooling area
Defrost operation
START
Four-way valve
area
OFF
YES
NO
YES
w10
YES
YES
NO
w11
Heating area
Defrost
30 min. elapse
Outdoor unit
trouble
1
A
Outdoor unit
trouble
NO
YES
YES
NO
NO
Auxiliary heater
NO
Auxiliary heater
Overheat remote
NO
Overload protect
Defrost release
2
B
Indoor piping
55°C or lower
NO
ON
YES
Indoor piping
60°C or higher
YES
OFF
START
Indoor unit
70°C or higher
YES
Allowance
period
YES
YES
NO
Auxiliary heater
Auxiliary heater
NO
6-minute restart
Allowance set
Compressor OFF
thermostat ON
YES
ON
prevention
YES
Indoor piping
35°C or higher
HOT adjust
6 min. elapse
FAN SPEED Low
FAN SPEED
Low 2 min.
FAN SPEED
setting notch
Hot adjust
release
elapse
Auxiliary heater
Indoor coil
thermistor is 60°C
FAN speed
Low notch
Airflow 10% up
NO
NO
YES
NO
YES
A
PKH-FK
Type
3-minute
OFF
or higher
B
NO
NO
NO
NO
YES
FAN setting notch
Auto COOL/HEAT
operation
Initial mode
YES
>
1 T0
T
=
COOL mode
1{ (T0 - 2)
T
YES
After 15min.
T
1{ (T0-2)
NO
w16
NO
YES
NO
YES
NO
w17
COOL modeHEAT mode
NO
COOL operationHEAT operation
NO
T1] (T0 + 2)
YES
After 15min.
T1] (T0 + 2)
HEAT operation
11
YES
NO
Cool mode set
1
w15 (!) Until Low airflow is set while hot adjustment
(@) While defrosting (FAN STOP)
(#) When thermostat is OFF
In the case of(!), (@) and (#) above, airflow is horizontal regardless the VANE setting.
w16 When AUTO operation is started, COOL or HEAT mode is selected automatically.
w17 T1 : Room temperature.
To : Set temperature
24
Page 25
DRY OPERATION
DRY
operation
Four-way valve / OFF
Vane
setting notch
NO
YES
NO
Initial dry
operation
YES
Vane initial setting
w
Room temperature is
18°C or lower
NO
During
compressor ON
YES
3-minute
compressor
operation
YES
Compressor &
thermostat ON
YES
w
8
12
NO
NO
w
9
YES
3-minute
time delay
NO
Compressor &
thermostat
ON
NO
YES
w
9
Compressor ON
time completes
YES
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
1
w 8 ~ 9 Refer to page 23.
w 12When room temperature is 18°C or below, the compressor cannot operate.
When room temperature rises over 18°C, the compressor starts after a 3-minute time delay.
w 13Compressor ON time is decided by room temperature. Refer to page 32.
w 14In dry operation, compressor ON makes the fan speed LOW and compressor OFF stops the fan.
It is not possible to set the fan speed with the remote controller
NO
W
14
10-minute
compressor
OFF
YES
Compressor ON
time set
Compressor ON
Fan speed LOW
NO
w
13
W
14
25
Page 26
9
FILTER
CHECK MODE
TEST RUN
241
MICROPROCESSOR CONTROL
1. OUTLINE OF MICROPROCESSOR CONTROL
INPUT to remote controller
● OFF-ON switching.
● COOL/DRY-AUTO-HEAT selector switching.
● Thermostat setting.
● TIMER mode selector-switching and Timer
setting.
● HIGH-LOW fan speed switching.
● AUTO Vane selector switching.
● TEST RUN switching.
● CHECK mode switching.
(Self diagnostic trouble shooting)
Indoor
unit
REMOTE CONTROLLER
● Processes and transmits
orders.
Non-polar, two-wire cable
12VDC
OUTPUT to remote controller
Remote controller
● LCD indicator
maximum length 500 meters
Signal
INPUT from indoor unit
● Room temperature thermistor (RT1)
● Pipe temperature thermistor (RT2)
OUTPUT to indoor unit
● Auto vane’s angle setting.
● Booster heater ON-OFF Control.
● Emergency stop.
Independent Control of
Outdoor Unit
● Compressor protection
device working
● Defrosting
START-STOP
● Fan speed control.
● Crankcase heater control
ON-OFF.
● Self diagnostic function
INDOOR CONTROLLER BOARD
● Receives orders from remote controller and
temperature data from indoor unit.
● Processes orders and data.
● Controls indoor and outdoor operation.
● Self diagnostic function.
w System control operation.
w Emergency operation.
w Set by dip switch on indoor controller board.
● Transmits the power to remote controller.
1 2 3
Polar three-wire cable
Outdoor unit
12VDC
1
2
3
● Compressor and
outdoor fan : ONOFF
● Operation mode
OUTPUT to outdoor unit
change :COOLHEAT.
26
Page 27
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Booster heater
Compressor
ON
LOW or HIGH
Initially 10 degrees
(Changeable by remote controller setting)
LOW or HIGH
ON
ON
OFF
OFF
CLOSECLOSE
OFF
OFF
OFF
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
FILTER
CHECK MODE
TEST RUN
241
2. INDOOR UNIT CONTROL
2-1 COOL operation
<COOL operation time chart>
<How to operate>
1 Press POWER ON/OFF button.
2 Press the button to display “ f ”.
3 Press the i TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is press one time Cooling 19 to 30°C.
W1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period has ended.
(1) Compressor control
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when room temperature is higher than set temperature.
The compressor stops when room temperature is equal to or lower than the set temperature.
3 The compressor stops in check mode or during protective functions.
4 Coil frost prevention
To prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 1°C or
below after the compressor has been continuously operated for at least 16 minutes or more. When the indoor coil temperature rises to 10°C or above, the compressor will start after a 3-minute time delay.
NOTE : By turning OFF the dip switch SW1-5, (PKH-2.5/3/4 for cut J1-5) on indoor controller board, the start temperature of
coil frost prevention changes 1°C to -3°C.
5 Coil frost protection
When indoor coil temperature becomes -15°C or below, coil frost protection will proceed as follows.
<Start condition>
After the compressor has been continuously operated for 3 minutes or more,and the indoor coil temperature has been -15°C
or below for 3 minutes,the coil frost protection will start.
<Coil frost protection>
Compressor stops for 6 minutes, and then restarts.
If the start condition is satisfied again during the first 10 minutes of compressor operation, both the indoor and outdoor units
stop, displaying a check code of “P8” on the remote controller.
<Termination conditions>
Coil frost protection is released when the start condition is not satisfied again during the allowance, or when the COOL
mode stops or changes to another mode.
27
Page 28
(2) Indoor fan control
5 minutes
SET
LOW
1213
5 minutes
SET
LOW
OFF
Indoor fan speed LOW/HIGH depends on the remote controller setting.
However, if an outdoor unit abnormality is detected, the indoor fan speed will be LOW, regardless of the remote controller
setting.
When the outdoor unit abnormality detection is released and the fan speed returns to the set speed, the quiet cycle control
will work.
(a) Normal control
(i ) Fan speed LOW/HIGH depends on the remote controller setting regardless of the thermostat ON/OFF.
(ii) Fan speed will remain on LOW if an abnormality in outdoor unit is detected. (5 minutes)
When the abnormality detection is released, the fan speed returns to the set speed.
1 Start-up of outdoor unit abnormality detec-
tion.
2 Release of outdoor unit abnormality detec-
tion.
3 Unit stop due to outdoor unit abnormality
with P8 indication.
NOTE 1 : Fan stops immediately if the unit stops or the check mode is started.
28
Page 29
(3) Auto vane control
Auto vane position is set to 10 degrees airflow at the start-up of COOL operation. It can then be changed by the remote
controller.
(a) Stop mode (fixed operation)
( i ) At start-up of COOLoperation, the auto vane is set to 10 degrees airflow direction.
(ii ) Discharge direction can be changed with button.
1 Fan speed : LOW
10°60°
2 Fan speed : HIGH
10°
(b) SWING mode (Only PKH-2.5FKHA
(Only PKH-2.5FKHA3, PKH-3FKHA3, PKH-4FKHSA3)
( i ) The vane motor turns ON when the SWING mode is selected.The vane motor is continuously ON during SWING mode.
<AUTO RETURN>
1 Fan speed : LOW
10°
30°
2, PKH-3FKHA2, PKH-4FKHSA2)
60°
AUTO
RETURN
60°
70°
AUTO
RETURN
70°
70°
(SWING)
(SWING)
2 Fan speed : HIGH
10°
When 60 degrees or 70 degrees airflow is selected with the LOW fan speed in COOL operation, “ 1Hr ” will appear below the
temperature display. One hour later, the airflow direction returns to 10 degrees automatically and “ 1Hr ” will disappear. If the
airflow direction is set to 10 degrees during “ 1Hr ” indication, the time counting for 1Hr is cancelled.
30°
60°
70°
29
Page 30
<Auto vane drive> (PKH-1.6FKHA3, PKH-2FKHA3)
(a) The auto vane is driven by a 2.5 rpm motor.
(b) Airflow direction can be selected between the No.1 and No.2 setting. (Initial setting is No.1)
1
10°
(c) Vane motor drive time
Airflow direction change
Downward C → Horizontal 4→
Horizontal → Downward A1→
Downward A→ Horizontal B 2→
Horizontal B → Downward C 3→
(d) Airflow direction is based on the horizontal position detected by the vane motor limit switch. When the horizontal posi-
tion can not be determined, the vane motor will remain ON until it is determined.
If the horizontal position still can not be detected, despite the 10minute detection, the vane motor will turn OFF
1
Remote controller indication continues.
After, if the vane motor receives the “auto vane ON” command again, it will restart detecting the horizontal position.
2
If the horizontal position still can not be determined, despite the 10-minute detection, the vane motor will turn OFF.
<Auto vane drive> (PKH-2.5FKHA
(PKH-2.5FKHA3, PKH-3FKHA3, PKH-4FKHSA3)
(a) The vane is driven by DC12V motor.
(b) Airflow direction is selected depends on the number of pulse were sended.
(c) Before start driving the auto vane, detect the standard position first, output the number of pulse to each Airflow.
(d) The speed of the auto vane drive for both open and close are setted at 200 pulse/sec.
(e) Method of driving the auto vane.
Detecting the standard position:
1
Output 1600 pulse to the opening direction.
Position setting:Output the number of pulse indicated no below chart to the closing direction.
2
2
30°
1
2
3
4
2, PKH-3FKHA2, PKH-4FKHSA2)
3
60°
Rise 2.1
4
70°
50Hz
0.65
6.7
0.65
The number of pulse outputed after
detecting the standard position
Close
Horizontal
Downward A
Downward B
Downward C113
(4) Detecting abnormalities in the outdoor unit
After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperature
and room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the difference is still out of
RANGE C,the outdoor unit is functioning abnormally. Thus, the compressor stops and check code “P8” appears on remote
controller.
RANGE A: Indoor coil temperature is more than 5 degrees above room temperature.
RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature.
RANGE C : Indoor coil temperature is more than 5 degrees below room temperature.
Indoor coil temperature
minus room temperature
(degree)
+5
0
RANGE A
RANGE B
1600
680
578
283
-5
RANGE C
30
Page 31
(5) Drain pump control
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Booster heater
Compressor
ON
(
PKH-2.5/3/4
)
wRefer to
page 32
for PKH-1.6/2
Initially 10 degrees discharge
(
Changeable by remote controller setting
)
LOW speedLOW speed
ON
ON
OFF
OFF
CLOSE
CLOSE
OFF
OFF
OFF
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
FILTER
CHECK MODE
TEST RUN
241
The drain pump works in COOL or DRY operation. When operation stops or changes to HEAT mode, the drain pump continues to operate for 3 more minutes. The drain pump does not work in check mode.
<Drain sensor>
When both the drain pump and unit are operating, the drain sensor detects the temperature. This temperature tells whether
the drain water level is above or under the drain sensor. If the drain water level rises above the drain sensor due to a drain
pump malfunction, the unit will stop operating in order to prevent drain from overflowing. The check code “P5” on the
remote controller will display this occurrence. When both of the following conditions are satisfied, the drain sensor is determined to be under water.
● Though the drain sensor has been heated by the drain sensor heater for more than 40 seconds, its temperature rise is
less than 20 degrees.
● The drain sensor temperature is below 63°C.
2-2 DRY operation
<How to operate>
1 Press POWER ON/OFF button.
2 Press the button to display “ e ”.
3 Press the i TEMP button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is press one time DRY 19 to 30°C.
<DRY operation time chart>
w1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period
has ended.
31
Page 32
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2The compressor runs when the room temperature is higher than the set temperature.
The compressor stops when the room temperature is equal to or lower than the set temperature.
3The compressor stops in check mode or during protective functions.
4The compressor will not start when the room temperature is below 18°C.
The compressor starts intermittent operation when the power is turned ON with room temperature above 18°C. The compressor ON/OFF time depends on the thermostat ON/OFF and the following room temperatures.After 3-minute compressor operation,
● If the room temperature thermistor reads above 28°C with thermostat ON, the compressor will operate for 6 more minutes and then stop for 3 minutes.
● If the room temperature thermistor reads 26°C—28°C with thermostat ON, the compressor will operate for 4 more minutes and then stop for 3 minutes.
● If the room temperature thermistor reads 24°C—26°C with thermostat ON, the compressor will operate for 2 more minutes and then stop for 3 minutes.
● If the room temperature thermistor reads below 24°C with thermostat ON, the compressor will stop for 3 minutes.
● If the thermostat is OFF regardless of room temperature, the compressor will stop for 10 minutes.
5Coil frost protection frost protection in DRY operation is the same as in COOL operation.
6Coil frost prevention frost prevention does not operate in DRY operation.
(2) Indoor fan control
<PKH-2.5FKHA
<PKH-2.5FKHA3, PKH-3FKHA3, PKH-4FKHSA3>
The indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote con-
troller. Also, the indoor fan does not run during compressor OFF.
<PKH-1.6FKHA3, PKH-2FKHA3>
(a)During compressor OFF
● When the indoor coil temperature is 6°C or above, the indoor fan will stop.
● When the indoor coil temperature is below 6°C, the indoor fan will run in DRY mode.
(b)During compressor ON
● The indoor fan runs on EXTRA-LOW speed for the first 1 minute after the compressor is turned on.
● After, the indoor fan runs in DRY mode.
<Dry mode>
The fan notch is controlled by the indoor coil temperature every 30 seconds.
2, PKH-3FKHA2, PKH-4FKHSA2>
Indoor coil temperature
Below -10°C
-10 to 0°C
Above 0°C
Fan operation
LOW speed
EXTRA-LOW speed
Dry mode
During compressor OFF, when the indoor coil temperature becomes 6°C or above, the indoor fan turns OFF immedi-
ately.
(3) Auto vane & drain pump controls
Same as in COOL operation
(4) Detecting abnormalities in the outdoor unit
32
Page 33
Minimum 3 minutes w2
ON
Thermostat
Indoor fan
Auto vane
Booster heater
Compressor
Power ON lamp
STAND BY lamp
ON
ON
LOW or HIGHLOW or HIGH
ON
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
Extra LOW w1Extra LOW w1
Hot adjustment
10°
Close
10°Close
From POWER ON until
warm begins to blow
Hot adjustment
Depends on remote
controller setting
Depends on remote
controller setting
w1 Changeable by indoor
dip switch SW1-7
and SW1-8.
(
PKH-2.5/3/4 for
J1-7,J1-8)
OFF during thermostat OFF
hot adjustment
defrosting
LOW
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
falls below set
temperature.
2-3 HEAT operation<How to operate>
FILTER
CHECK MODE
TEST RUN
241
1 Press POWER ON/OFF button.
2 Press the button to display “
3 Press the i TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is press one time Heating 17 to 28°C.
<Display in HEAT operation>
[ DEFROST ]
The [ DEFROST ] symbol is only displayed during the defrost operation.
[ STANDBY ]
The [ STANDBY ] symbol is displayed from the time the heating operation starts until the heated air begins to blow.
<HEAT operation time chart>
g ”.
w
2 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period has ended.
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3, minutes after stop.
2The compressor runs when the room temperature is lower than the set temperature.
The compressor stops when the room temperature is equal to or higher than the set temperature.
3The compressor stops in check mode or during protective functions.
4Overheat protection
<Start condition>
When the indoor coil thermistor reads 70°C or above, the overheat protection will start.
<Overheat protection>
The compressor stops for 6 minutes, and then restarts.
If the start condition is satisfied again within 10 minutes of compressor operation, both the indoor and outdoor units stop,
displaying a check code of “P6” on the remote controller.
<Termination conditions>
Overheat protection is terminated when the start condition is not satisfied again during the allowance (10-minute compressor operation), when operation mode changes to other mode, or when thermostat turns OFF.
33
Page 34
(2) Indoor fan control
(a) Normal control
(
!)The indoor fan runs on EXTRA-LOW speed during the thermostat OFF.
EXTRA-LOW speed can be changed to LOW or HIGH speed by setting the dip switch SW1-7 and SW1-8,(PKH-
2.5/3/4 for J1-7, J1-8) If the indoor coil temperature becomes more than 5 degrees below the room temperature during the thermostat OFF, the indoor fan will stop. After, when the indoor coil temperature becomes within 5 degrees of
room temperature, the indoor fan will run on EXTRA-LOW speed.
(@)Hot adjustment Hot adjustment is a warm-up for HEAT operation
<Start conditions>
The hot adjustment works under any of the following conditions.
● HEAT operation starts.
● Defrosting ends.
● Thermostat turns ON.[Hot adjustment]
Initially, the indoor fan runs on EXTRA-LOW speed. When 5 minutes have passed or the indoor coil temperature
exceeds 35°C, the fan speed changes to LOW. Two minutes later, the hot adjustment ends. Then, the fan speed
depends on the remote controller setting.
(#)The indoor fan stops when the indoor coil temperature is within 5 degrees either way of room temperature.
($)To eliminate the remaining heat, the indoor fan runs for the first 1 minute after the booster heater is turned OFF.
(3) Auto vane control
(a) STOP mode (fixed operation)
(!) The airflow direction at the start-up of HEAT operation is the same as that of the previous operation.
(@) The airflow direction can be changed by the remote controller setting.
(only for PKH-2.5FKHA2, 3FKHA2, 4FKHSA2 )
(only for PKH-2.5FKHA3, 3FKHA3, 4FKHSA3)
10°
In the following cases, airflow direction becomes 10° regardless of the remote controller setting.
1 During the hot adjustment with fan speed at EXTRA-LOW
2 During defrosting with indoor fan OFF
3 During the thermostat OFF
(b) SWING mode (Only for PKH-2.5FKHA
(Only for PKH-2.5FKHA3, PKH-3FKHA3, PKH-4FKHSA3)
(!) The vane motor turns ON when the SWING mode is selected.
The vane motor is continuously ON during SWING mode.
(@) In the following cases, the discharge direction is 10° regardless of the remote controller setting.
1 During the hot adjustment with fan speed at EXTRA-LOW
2 During defrosting with indoor fan OFF
3 During thermostat OFF
30°60°
2, PKH-3FKHA2, PKH-4FKHSA2)
70°
(SWING)
34
Page 35
(4) Booster heater control
When the room temperature is 3 degrees below the set temperature, the booster heater will turn ON.
When the room temperature is equal to the set temperature, booster heater will turn OFF.
During the hot adjustment, the booster heater will not work.
<Overheat prevention>
When the indoor coil thermistor rises to 60°C or above, the booster heater cannot work.
When the indoor coil thermistor falls to 55°C or below, the booster heater can work.
(5) Detecting abnormalities in the outdoor unit
When the outdoor unit is determined to be abnormal by the following causes, the compressor will stop and the check code “
P8 ” will appear on the remote controller display.
1 During compressor ON after hot adjustment
1 If the difference between the indoor coil temperature and room temperature is in the RANGE B, the indoor fan will
stop.
2 Within 20 minutes after entering RANGE B (except for the first 10 seconds),
a) If the temperature difference enters RANGE A, the hot adjustment starts,
b) If the temperature difference is still in RANGE B, the outdoor unit is deemed abnormal.
c) If the temperature difference enters RANGE C, defrosting starts.
Within 30 minutes after entering RANGE C,
●If the temperature difference does not return to RANGE B,the outdoor unit is deemed abnormal.
●If the temperature difference returns to RANGE B, the next 20 minutes is an allowance period. If the difference enter
RANGE Aduring the allowance, defrosting ends and the hot adjustment starts. If the difference does not enter
RANGE Aduring the allowance, the outdoor unit is deemed abnormal.
2 During compressor ON in hot adjustment
After 30 minutes of defrosting in hot adjustment, if the temperature difference is still in RANGE C, the outdoor unit is
determined to be abnormal.
3 During compressor OFF
After 20 minutes of thermostat OFF, if the indoor coil thermistor reads -25°C or below, the outdoor unit is determined to
be abnormal.
(6) Indoor coil thermistor abnormality detection
An abnoirmalidty can be detected during compressor ON, except for the following.
●For the first 30 minutes after the temperature difference between the indoor coil temperature and room temperature
enters the RANGE C.
●When the temperature difference enters the RANGE C until it moves to the RANGE B.
(7) Defrosting operation
After the outdoor unit starts the defrosting operation, when the temperature difference between the indoor coil temperature
and room temperature gets out of RANGE Aand into RANGE B, the indoor unit starts the defrosting mode. After the outdoor unit stops the defrosting operation, when the temperature difference returns to the RANGE A, the indoor unit stops the
defrosting mode. While the indoor unit is in the defrosting mode, the indoor fan and the booster heater stop.
w1 RANGE A: Indoor coil temperature is more than 5 degrees above room temperature.
RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature.
RANGE C : Indoor coil temperature is more than 5 below room temperature.
Indoor coil temperature
minus room temperature
(degree)
+5
0
-5
RANGE A
RANGE B
RANGE C
35
Page 36
Mode change (HEAT COOL)
When room temperature becomes2degrees above the set temperature,the operation mode can not be changed
for 15 minutes.
(degree)
To+2
To+1
To
To-1
To-2
Start
HEAT modeHEAT mode
Mode change
15 minutes
15 minutes
Mininum 3 minutes
COOL mode
(COOL HEAT)
ON
OFF
-901020
21
304046
-8.5
Cooling range
(Outside air temperature)
Heating range
-5
2-4 AUTO operation (Automatic COOL/HEAT change over operation)
FILTER
CHECK MODE
TEST RUN
241
<How to operate>
1 Press POWER ON/OFF button.
2 Press the button to display “ ”.
3 Press the i TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is press one time Auto 19 to 28°C.
●“AUTOMATIC” works to change by itself the operation mode either to cooling or heating according to
the room temperature.
(1) Initial mode
1 When AUTO operation starts after unit OFF.
● If the room temperature is higher than the set temperature, operation starts in COOL mode.
● If the room temperature is equal to or lower than the set temperature, operation starts HEAT mode.
2 When AUTO operation starts after COOL or HEAT operation, the previous mode continues.
(2) Mode change
1 HEAT mode changes to cool mode when 15 minutes have passed since the room temperature became 2 degrees above
the set temperature.
2 COOL mode changes to HEAT mode when 15 minutes have passed since the room temperature became 2 degrees
below the set temperature.
(3) Temperature range
AUTO operation is available under the outside air temperatures as follows.
36
Page 37
10˚
30˚
60˚
70˚
Swing
Changes by pressing
the button.
FILTER
CHECK MODE
TEST RUN
241
2-5 Auto vane control
<How to operate>
To change the airflow direction, press button.
Available in COOL operation with fan speed on HIGH or
in HEAT operation.
Unavailable in DRY operation.
If fan speed changes from LOW to HIGH during 30°
downward airflow in COOL mode, the direction automatically changes to 10°.
(1) COOL/DRY operation
At the start-up of COOL or DRY operation, the airflow direction in automatically set to 10°. After, it can be changed to
another direction with button on the remote controller.
<Auto return>
When 60° or 70° airflow is set with fan speed on LOW, “ 1Hr ” appears below the room temperature display. One hour later
the direction changes to 10° degrees, automatically and “ 1Hr ” disappears.
(2) HEAT operation
At the start-up of HEAT operation, discharge direction depends on the setting of the last operation.
After, it can be changed to another direction with button. The discharge direction shifts to 10° regardless of the remote
controller settings under any of the following conditions.
● Thermostat OFF
● Defrosting
● Indoor fan speed EXTRA-LOW in hot adjustment
37
Page 38
OFF
2-6 TIMER operation
FILTER
CHECK MODE
TEST RUN
241
FILTER
CHECK MODE
TEST RUN
241
<Timer function>
AUTO STOP ·········The air conditioner stops after the set time lapses.
AUTO START ········The air conditioner starts after the set time lapses.
AUTO OFF ············Timer is not active.
<How to operate>
1. Press POWER ON/OFF button.
2. Press w button to select AUTO STOP or AUTO START.
3. Press q button to set desired time.
Time setting is in 1 hour units for up to 24 hours.
Each time HOURS button is pressed, set time increases by 1 hour.
When HOURS button is pressed and held, the set time increases
by 1 hour every 0.5 seconds.
4. To cancel the timer operation, press POWER ON/OFF button.
<Timer setting example>
This setting will stop the air conditioner in 8 hours.
With the lapse of time, time display changes in 1 hour units, showing remaining time.
2-7 Test run
<Before test run>
● After installing, wiring, and piping the indoor and outdoor units, check for refrigerant leakage, looseness in power supply or
control wiring, and mistaken polarity.
● Use a 500-volt megger to check the resistance between the power supply terminal block and ground to make sure that it is
at least 1.0MΩ.
Attention : Do not use the air conditioner if resistance is less than 1.0MΩ.
Remote controller
TEST RUN button
TEST RUN
Indoor coil temperature code
Display
Display
*The above figure shows the state of TEST
RUN at cooling operation.
Turn on main switch.12 hours before proceeding to step 2 to allow
1
for crankcase heater operation.
Push the TEST RUN button twice and indication of TEST RUN will
2
be shown on the liquid crystal display.
Press the button to display ,COOL/DRY(or HEAT)to
confirm that cool (or warm)air is blown out.
3
(At heating operation,there may be a short delay before warm air
begins to blow out.)
Push button LOW/HIGH to check that the fan speed changes
4
properly.
Check the operation of outdoor unit fans.This unit controls the rota-
tion speed and performance capacity of fans.ln some cases,it may
rotate at low speed as the condition of outside air requires and the
speed will be kept unless the performance has become deficient.
5
Therefore,when the condition of outside air demands,there may be
such cases as the fan stops or rotates reversely.
Please note that these symptoms are not malfunction.
After the check is finished leave the test run mode,push the power
ON/OFF button.
6
It can also be stopped by pushing the timer MODE button.
●When a TEST RUN is started,the timer shall be set to 2 hours. The unit will automatically turn off after 2 hours.
38
Page 39
(1) Indoor coil temperature code
Code
Indoor coil
temperature
Indoor coil
temperature
Thermistor
abnormality
Code
1
-40~1˚C
9
~45˚C
2
~10˚C~15˚C~20˚C~25˚C~30˚C
~90˚C
~35˚C~40˚C
101112131415
~50˚C
3
~55˚C
4
~60˚C
5
~70˚C
6
7
8
1 ON
1
2
1.2 ON
1
2
1-2 OFF
1
2
During the test run, the indoor coil temperature code from 1 to 15 is displayed on the remote controller instead of room
temperature. The code should fall with the lapse of time in normal COOL operation, and should rise in normal HEAT
operation.
(2) Trouble during test run
● If the unit malfunctions during the test run, refer to section 10 in this manual entitled “TROUBLESHOOTING.”
● When the optional program timer is connected to the conditioner, refer to its operating instructions.
2-8 Emergency operation
When the remote controller or microprocessor malfunctions but all other parts are normal, emergency operation is started
by setting the dip switch SW3 on the indoor controller board.
<Before emergency operation>
1. Make sure the compressor and the indoor fan are operating normally.
2. Locate the defect with the self-diagnostic function. When the self-diagnostic function indicates “protective function is
working”, release the protective function before starting the emergency operation.
CAUTION: When the self-diagnostic function indicates a check code of “P5” (drain pump malfunction), DO NOT start the
emergency operation because the drain may overflow.
<How to operate>
1. For emergency cooling, set the dip switch SW3-1 to ON and SW3-2 to OFF.
For emergency heating, set the dip switch SW3-1,2 to ON.
Emergency
cooling
Emergency
heating
Normal
operation
Microcessor board
2. Turn ON the outdoor unit breaker and then ON the indoor unit breaker.
Emergency operation will now start.
3. During emergency operation, the indoor fan operates on high speed, but the swing louvers and the auto vanes do not
operate.
4. To stop emergency operation, turn OFF the indoor unit breaker.
NOTE: The remote controller POWER ON/OFF button can not start/stop emergency operations.
CAUTION: Do not use emergency cooling for more than 10 hours, as the indoor coil may freeze.
39
Page 40
2-9 Interlock with ventilation system (LOSSNAY)
Relay box
Relay box (PZ-12RB-E)
LOSSNAY
LOSSNAY
LOSSNAY control switch (PZ-05SLB
2-E)LOSSNAY control switch
(PZ-05SLB
2-E)
Mr. SLIM
Mr. SLIM
Remote
controller
Remote
controller
Remote display
adapter
(PAC-SA88HA-E)
Power
supply
Power supply
Mr. SLIM/LOSSNAY interlock operation is available by using the optional parts listed below.
(1) System organization
(2) LOSSNAY models connectable to Mr. SLIM are: LGH-15RS-E, LGH-50RS-E
LGH-25RS-E, LGH-80RS-E
LGH-35RS-E, LGH-100RS-E
(3) Required parts are:
● Relay box (PZ-12RB-E)…Contact capacity 10A
● Remote display adapter (PAC-SA88HA-E)…An optional part for Mr. SLIM
● LOSSNAY control switch (PZ-05SLB-2-E)…For LOSSNAY individual operation
(4) Operation
1LOSSNAY turns ON/OFF according to Mr. SLIM ON/OFF
2While Mr. SLIM is OFF, LOSSNAY individual operation is available by using the LOSSNAY control switch.
When Mr. SLIM turns OFF with the LOSSNAY control switch at ON, LOSSNAY will continue to operate.
(5) Wiring.
Indoor controller
Remote
controller
Power
supply
50Hz
220 240V
10m
Connecting wire
0.13mm or over
Connecting wire
solid wire,
1.6 or 2.0
(field supplied)
Circuit breaker
(field supplied)
L
N
PL
HIGH
N
LOSSNAY control switch
(PZ-05SLB
Insulation
is needed
2
N
L
DAMPER
2-E)
Connector
LOW
Mr. SLIM
board
CN51
ORN
RED
BRN
YLW
GRN
Power supply
for Mr. SLIM
220 240V AC
Relay box
(PZ-12RB-E)
YLW
A
ORN
B
RED
L
WHT
N
RED
HIGH
N
WHT
LOSSNAY
Terminal
block
ORN
LOW
RED
HIGH
WHT
N
RED
DAMPER
ORN
DAMPER
WHT
7
6
2
5
1
8
4
3
Junction box
(field supplied)
40
2When the LOSSNAY control switch is not used:1When the LOSSNAY control switch is used:
Relay box
(PZ-12RB-E)
Terminal block
ABLN HIGHN
Mr.SLIM
CN51
12V DC
L
Power supply
220 240V AC
N
Circuit
breaker
Terminal block
NOTE: For further information, refer to the
LOSSNAY technical & service manual.
LOSSNAY
LOW
HIGH
N
DAMPER
DAMPER
ORN
RED
WHT
RED
ORN
WHT
Page 41
2-10 Dip switch and jumper connector functions
Each figure shows the initial factory setting.
1. On remote controller board
(1) SW17(Address selector)
1 2 3 4 5 6
ON
OFF
SW17-1 ~ 6) For address setting
SW17-7) When two remote controllers are used, this switch sets the controller function.
OFF: The remote controller is set as a main controller.
ON: The remote controller is set as a sub controller.
SW17-8) Switch for system back-up
OFF: Without back-up
ON: With back-up
(2) SW18 (Function selector)
1 2 3 4
ON
OFF
SW18-1) Switch for timer
OFF: single day
ON: timer every day
SW18-2) Switch for filter sign
OFF: filter sign absent
ON: filter sign present
SW18-3) Switch for filter sign time setting
OFF: 100 Hr
ON: 2500 Hr
SW18-4) Not yet used.
2. On indoor controller board
For PKH-1.6FKHA
(1) SW1 (Mode selector)
1 2 3 4 5 6 7 8 9 0
ON
OFF
SW1-1) Switch that changes between FAN mode and AUTO mode
OFF: Fan mode for models without heat pump
ON: AUTO mode for models with heat pump
SW1-2) Not for use
SW1-3) Switch for auto vanes
OFF: Unit without auto vanes
ON: Unit with auto vanes
SW1-4) Not for use
SW1-5) Switch to change the temperature to start coil frost prevention
OFF: -3°C(For previous special models)
ON: 1°C(For all current models)
SW1-6) Switch for set temperature adjustment in HEAT mode
During HEAT operation, warm air collects near the ceiling. When the indoor unit is installed near the ceiling, the
temperature read by room temperature thermistor differs from the actual living-space temperature by about 4
degrees. Therefore, the room temperature read by room temperature thermistor must be lowered by 4 degrees.
OFF: 4-degree adjustment
ON: No adjustment
SW1-7) Switch for fan speed during thermostat OFF in HEAT operation
OFF: EXTRA LOW
ON: LOW
SW1-8) Switch for fan speed during thermostat OFF in HEAT operation.
OFF: EXTRA LOW or LOW (set with SW1-6)
ON: LOW or HIGH (set with remote controller)
SW1-9) Switch for detecting abnormalities in the outdoor unit adnoamality detection
OFF: When an abnormality occurs, it is detected.
ON: Even if an abnormality occurs, it can not be detected.
SW1-10) Switch for auto restart function
OFF: This function does not work
ON: This function works.
7 8
3, PKH-2FKHA3
41
Page 42
(2) SW2 (Address selector)
1 2 3 4 5 6
ON
OFF
(3) SW3 (Emergency operation switch)
Normal operation
1 2
ON
OFF
(4) SW5 (Model selector)
1 2 3 4
ON
OFF
Used in setting the unit-address for group control.
For further information, refer to page 58.
For emergency cooling
1 2
ON
OFF
For emergency heating
1 2
ON
OFF
SW5-1) Power supply
SW5-2) OFF:For models with heat pump
ON:For models without heat pump
SW5-3) Not for use
SW5-4) This switch is unavailable for PKH-FKHA, PKH-FKHSA. Keep this switch at OFF.
(5) SW6 (Model selector)
1 2 3 4
ON
OFF
(6) SW7 (Model selector)
Switch to set the output of phase-controlled indoor fan motor.
Address setting is available at any time
The initial factory setting by is based on each capacity.
J1-1) Switch that changes between FAN mode and AUTO mode.
Provided: Fan mode for models without heat pump.
Not provided: AUTO mode for models without heat pump.
J1-4) Switch for drain pump
Provided: The drain pump works in only COOL operation
Not provided: The drain pump works in both COOL and HEAT operation
J1-5) Switch to change the temperature to start coil frost prevention
Provided : 1°C (For all current models)
Not provided: -3°C (For previous special models)
2, PKH-3FKHA2, PKH-4FKHSA2
10
42
Page 43
J1-6) Switch for set temperature adjustment in HEAT mode
During HEAT operation, warm air collects near the ceiling. When the indoor unit is installed near the ceiling, the
temperature read by room temperature thermistor differs from the actual living-space temperature by about 4
degrees. Therefore, the room temperature read by room temperature thermistor must be lowered by 4 degrees.
Provided : 4-degree adjustment
Not provided : No adjustment
J1-7) Switch for fan speed during thermostat OFF in HEAT operation
Provided : EXTRA LOW
Not provided : LOW
J1-8) Switch for fan speed during thermostat OFF in HEAT operation.
Provided : EXTRA LOW or LOW (set with J1-7)
Not provided : Low or HIGH (set with remote controller)
J1-9) Switch for detecting abnormalities in the outdoor unit abnormality detection.
Provided : When an abnormality occurs, it is detected.
Not provided : Even if an abnormality occurs, it can not be detected.
J1-10) Switch for auto restart function
Provided : This function does not work
Not provided : This function works.
(2) SW2 (Address selector)
1 2 3 4 5 6
ON
Used in setting the unit-address for group control.
For further information, refer to page 58.
OFF
(3) SW3 (Emergency operation switch)
Normal operationFor emergency coolingFor emergency heating
ON
OFF
1 2
1 2
ON
OFF
1 2
ON
OFF
(4) J5 (Model selector)
24
J5-2) Provided:For models with heat pump.
Not Provided :For models without heat pump.
J5-4) This jumper is unavailable for PKH-FKHA, PKH-FKHSA, keep this
(5) SW6 (Model selector)
ON
OFF
1 2 3 4
SW6-1
SW6-2
SW6-3
SW6-4
Single control
OFF
OFF
OFF
OFF
Twin control
ON(Twin No.1)
ON(Twin No.2)
OFF
OFF
Triple control
ON(Triple No.1)
ON(Triple No.2)
ON(Triple No.3)
ON
(6) SW7
ON
OFF
1 2 3 4
PKH-2.5/3 PKH-4
1 2 3 4
ON
OFF
SW7-1) OFF:PKH-2.5/3SW7-3) Not for use
ON :PKH-4SW7-4) Not for use
SW7-2) POWER SUPPLY
OFF: 220V
ON : 240V
)(
(7) J9 (Model selector)
12
J9-1) Not provided
J9-2) Provided
PKH-FKA, PKH-FKSA
}
2-11 INDOOR FAN CONTROL
Indoor fan relay output.
(a) During fan ON
The indoor fan relay turns ON. One second later, the phase control will start.
(b) During fan OFF
The phase control turns OFF. One second later, the indoor fan relay will turn OFF.
43
Page 44
3. OUTDOOR UNIT CONTROL
10 minutes 1
ON
Thermostat
Outdoor fan
4-way valve
(COOL)
4-way valve
(HEAT)
Bypass valve
Compressor
Crankcase heater
(with jumper wire
J3)
Crankcase heater
(without jumper
wire J3)
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
60 minutes 60 minutes 60 minutes 60 minutes
3 minutes
Repeats
60-minute
ON/OFF
Repeats
60-minute
ON/OFF
60 minutes
60 minutes
Operation
starts by
POWER
button ON.
Operation
stops by
POWER
button OFF.
Room temperature
becomes equal to set
temperature.
Room temperature
becomes different from
set temperature.
60 minutes 60 minutes
10 minutes
3 minutes
3-1 Outdoor fan control
The rotational frequency of outdoor fan is phase-controlled according to the outdoor coil temperature. This control allows the
cooling operation even with the low outside-air temperature and the heating operation even with the high outside-air temperature.
3-2 Outdoor unit control
The outdoor unit turns ON/OFF the cooling/heating operation according to orders given from the indoor unit.
3-3 Protective functions
1 If an reversed-phase, an open phase, or an indoor controller abnormality is detected, the outdoor unit will stop operation
and the check mode will start. (For the check mode details, see page 59.)
2 If a protective function works, the compressor will stop running. Three minutes later, the compressor will restart. If the pro-
tective function works again, the compressor will stop running and the check mode will start.
3 The protective function is memorized.
4 The memory is cleared when the POWER ON/OFF button on the remote controller is turned OFF. However, the check
mode display continues until the outdoor unit receives the “operation ON” command from the indoor unit.
3-4 COOL/HEAT operation time chart
w1 If compressor restarts within 10 minutes, 4-way valve remains ON.
44
Page 45
ON
Outdoor fan
Compressor
4-way valve
Bypass valve
Auto vane
Indoor fan
10º
Outdoor unit
Indoor unit
ON
Set direction
ON
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
Set direction
Defrosting
starts.
Defrosting
stops.
3-5 Defrosting in HEAT mode
<Defrosting time chart>
(1) Start conditions
A. When all of the following conditions are satisfied, defrosting will start. However, when the bypass valve turns OFF,
defrosting starts 10 minutes later.
(a) More than seven minutes have passed since the compressor start-up.
(b) The outdoor coil thermistor reads -5°C or below.
(c) The outdoor fan motor output step is 100%
(d) Total time of compressor operation exceeds 30 minutes, and the outdoor coil temperature has fallen by 8 degrees or
B. When all of the following conditions are satisfied, defrosting will start.
(a) ~ (c) The same as above (a) ~ (c) in item A
(d) Total time of compressor operation exceeds “defrost interval”.
C. After the total time of compressor operation exceeds the defrost interval, the thermostat repeats ON/OFF three times.
Two minutes after the fourth “ON” of the thermostat, if the outdoor coil thermistor reads -5°C or below and the fan output
output is 100%, defrosting will start.
(2) During defrosting
● Even if the thermostat turns OFF, defrosting continues.
● The 4-way valve, bypass valve, outdoor fan, and indoor fan are OFF.
more in comparison with that of 10 minutes after the compressor start-up.
NOTE: The outdoor coil temperature of 10 minutes after the compressor start-up is memorized until the defrosting
operation has ended.
Further information on the defrost interval is described in 3-5-(3).
NOTE: The count of the thermostat ON/OFF is cleared by the compressor-OFF command or defrosting start-up.
45
Page 46
(3) Defrost interval
The defrost interval time is determined as follows.
● Initial defrost interval is 50 minutes.
● The defrost interval after defrosting depends on the preceding defrosting time as shown below.
Defrosting operation timeNext defrost interval
3 minutes or below120 minutes
3 to 7 minutes80 minutes
7 to 10 minutes60 minutes
10 to 15 minutes40 minutes
15 minutes (Maximum)30 minutes
NOTE1:If the unit stops during defrosting , the next defrost interval will be 50 minutes.
NOTE2:If a protection function works for the first time during defrosting, the compressor will stop.
After a 3-minute time delay, defrosting will restart. In this case, a 3-minute time delay is included with the defrosting
time.
If the protection function works for the second time, the unit stops operation and displays the check code.
The next defrost interval will be 30 minutes.
NOTE3:When the defrosting has ended, the total time of the compressor operation is cleared.
(4) Termination conditions
Defrosting finishes when any of the following conditions are satisfied.
1Defrosting has continued for 15 minutes.
2Outdoor coil thermistor reads 22°C or above for the first 75 seconds after defrosting start-up.
3Outdoor coil thermistor reads 8°C or above after the 75-second defrosting.
4Power ON/OFF button is turned OFF during defrosting.
3-6 Actuators
(1) Bypass valve control
<Cooling mode>
1When the unit stops due to the coil frost prevention, the bypass valve turns ON. When one hour has passed since the
compressor stopped, the bypass valve returns to OFF.
2When the compressor operates with the bypass valve at ON for more than 30 minutes, the bypass valve turns OFF.
3When the compressor stops with the bypass valve at OFF, the bypass valve turns ON and remains ON for three minutes.
<Heating mode>
1When the unit starts for the first time after the circuit breaker has been turned ON, or when it starts after the compressor
OFF of 30 minutes or more, if the outdoor coil thermistor reads 12°C or more, the bypass valve turns ON.
2When the high pressure switch (63H1) works, the bypass valve turns ON.
3When the bypass has been ON for 30 minutes:
● If the high pressure switch has already returned, the bypass valve turns to OFF.
● If not, the fan output step keeps 70 for three minutes. Meanwhile, if the high pressure switch returns, the bypass valve
turns OFF. Otherwise the normal fan control starts.
4When the operation mode changes or stops, the bypass valve turns ON and remains ON for three minutes.
<Defrosting operation>
1The bypass valve is OFF.
(2) Crankcase heater control
1With jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and then turns ON one hour
after the compressor stops.
2Without jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and repeats 1-hour ON and
1-hour OFF.
46
Page 47
3-7 Service functions
(1) Compulsory defrosting
1When all of the following conditions are satisfied, pressing SW2 starts the compulsory defrosting.
● During HEAT mode
● The compressor is ON.
● The outdoor coil temperature is being displayed by LED. (Outdoor controller board dip switch SW3-1 : OFF, SW3-2 :
ON)
● The outdoor coil thermistor reads 8°C or below.
2The operation state and the termination conditions of the compulsory defrosting are the same as those of the normal
defrosting. As an exception, the defrost interval after the defrosting completion is 51 minutes.
(2) Fixed fan-output
While the compressor is operating (except during defrosting) and the fan output step is indicated by LED, pressing SW2
fixes the fan output. The fixed fan-output can be released when any of the following conditions are satisfied.
1SW2 is pressed again.
2SW3 setting is changed.
3The compressor stops.
4Defrosting operation starts.
(3) Function of switches on the outdoor controller board
SW1: Clears the check code memory (push-button switch)
SW2: Switches the output state indication and the check code display (push-button switch)
SW3-1,2: Switches the output state indication items (dip switch)
For further information, refer to page 51.
(4) 100% fan output
Fan output is fixed to 100% by shorting the connector CN22. However, the fan stops during compressor OFF or defrosting.
Open-circuit of CN22 restarts the normal fan control.
(5) Time shortening
Short circuit of the connector CN21 shortens the time as follows
1Fan control period: 30 seconds → 3 seconds
2Three-minutes time delay function : 3 minutes → 3 seconds
3Max. time of defrosting : 15 minutes → 15 seconds
4Defrost interval : 30 ~ 120 minutes → 3 ~ 12 seconds
5Compressor ON/OFF time for bypass valve ON/OFF : 30 minutes → 3 seconds
6Compressor ON time to start other functions : x minutes → x seconds
7Crankcase heater operation : 1 hour → 6 seconds
47
Page 48
10TROUBLESHOOTING
1. TROUBLE IN TEST RUN
SymptomCauseCheck points
The display “CENTRALLY
CONTROLLED” on remote
controller dose not disappear.
When remote controller
POWER button is turned
ON, the check code
“EO”appears.
1) Wrong address setting of remote controller/indoor controller board.
2) Timer adapter is connected to the
remote controller.
3) Signal transmission error between
indoor unit and remote controller.
1) Signal transmission error between
indoor unit and remote controller
1) Check the address setting of remote controller
and indoor controller.
2) Make sure the timer adapter is used correctly.
3) 1 Turn another remote controller’s DIP SW17-
7 ON to make it sub controller.
2 Connect the sub controller to the unit, and
turn circuit breaker ON.
● If the display “centrally controlled” disappears, replace the original remote controller.
● If the display remains the same, replace the
indoor controller board.
1) 1 Connect a sub remote controller.
2 Turn circuit breaker ON.
If the display “centrally controlled” remains,
replace the indoor controller board.
3 If the display disappears, turn the remote
controller POWER button ON and check as
follows.
Remote controller
1
Operating Display
2
Operating Display
3
No Display
4
No Display
Sub remote controller
EO Display
Operating Display
EO Display
Operating Display
Malfunction
Malfunction of
indoor Unit
Malfunction of
Remote controller
Malfunction of
indoor Unit and
Remote Controller
Malfunction of
Remote controller
When remote controller
POWER button is turned
ON, operating display
appears, but disappears
soon.
Despite turning POWER
button ON, the remote
controller display does not
appear.
1) Short circuit of indoor/outdoor connecting wire
2) Short circuit of transmission wire.
3) Short circuit of drain sensor heater circuit.
4) Wrong operation of remote controller
due to noise wave emitted by other
appliances.
1) Damaged remote controller.
2) Short circuit of transmission wire.
3) Bad contact of indoor CN40.
4) CN40 is attached to a sub unit.
5) Damaged transformer.
6) Bad contact of CN4T.
7) Blown fuse.
8) Circuit breaker OFF.
1), 2) Check the wire
3) Measure the resistance of the drain sensor
connector CN50 1 - 3. Normal resistance
should be 82Ω.
4) Turn the circuit breaker OFF, and then turn
ON.
If the remote controller remains abnormal,
despite the above measures, replace the indoor
controller board.
1) Measure the voltage between terminals of
remote controller. If no voltage, remove the
terminals and measure the voltage between
wires. If the voltage is between 6VDC and
12V, replace the remote controller.
2) ~ 8) Check each point.
If it is not defective, replace the indoor
controller board.
48
Page 49
2. SELF DIAGNOSTIC FUNCTION WITH REMOTE CONTROLLER
2-1 When malfunction occurs during operation
When a malfunction occurs, the indoor and outdoor units stop and the malfunction is displayed on the LCD of the remote
controller.
(1) ON the set temperature display part, “CHECK” appears, and the unit
address and the check code are displayed alternately at one-second
intervals. (Check mode)
Example
CHECK mode
Check
code
(2) When one remote controller controls several units in the group control,
the LCD shows the unit address and check code of the first malfunctioning unit.
(3) To cancel the check mode, press the ON/OFF button. In remote
ON/OFF control, press the remote ON/OFF switch. In centralized
control, turn OFF the ON/OFF button of centralized controller.
NOTE: The latest check code is memorized, even if the check mode is cancelled by the way mentioned above. It takes
60 seconds maximum to display the memorized check code.
2-2 How to use the self diagnostic function for service
A. For normal control with one unit and one remote controller
(1) Pressing the CHECK button on the remote controller twice starts the self diagnostic function.
(2) During the self diagnostic function, “CHECK MODE” appears at two positions on the remote controller display. Then, at
least 10 seconds later, the unit address and the check code is alternately displayed at one-second intervals.
(3) Check and repair the unit according to the check code. (Refer to the next page.)
B. For group control using one remote controller
(1) Pressing the CHECK button on the remote controller twice starts the self diagnostic function.
(2) Press the TEMP. button or TEMP. button on the remote controller to advance or go back to the unit address.
Each time TEMP. button is pressed, the unit address advances by one. Each time TEMP. button is pressed,
the unit address goes back by one.
The check code and the unit address, appear alternately.
(3) The check code “U8” means no malfunction has occurred since installation.
The check code “EO” means the following conditions:
● The unit address displayed on the remote controller does not apply to any unit.
● power is not supplied to the unit.
● Signal transmitting/receiving circuit is abnormal.
(4) Check and repair the unit according to the check code. (Refer to the next page.)
Unit
address
Check button
49
Page 50
Check
code
EO
Diagnosis of malfunctionCauseCheck points
Signal transmitting/receiving
error
(Indoor controller does not
respond to remote controller
signal.)
During individual unit control
1) Bad contact of transmission
wire
2) Signal transmitting/receiving circuit is abnormal.
1) Check the transmission wire.
2) Check with another remote controller. If “EO” is
still indicated, replace the indoor controller
board.
If other check code appears. replace the original remote controller.
Abnormality of room temper-
P1
ature thermistor (RT1)
Abnormality of indoor coil
P2
thermistor (RT2)
Signal transmission error
P3
(Remote controller does not
respond to indoor controller
signal.)
Abnormality of drain sensor1) Bad contact of transmission
P4
1) Bad contact of thermistor
2) Damaged thermistor
1) Bad contact of transmission
wire
2) Signal transmitting/receiving circuit is abnormal.
3) Wrong operation due to noise
wave emitted by other appliances
wire
2) Damaged thermistor
1) Check the thermistor.
2) Measure the resistance of the thermistor.
Normal resistance should be as follows.
0°C···15kΩ30°C ····4.3kΩ
10°C·····9.6kΩ 40°C·····3.0kΩ
20°C·····6.3kΩ
If the resistance is normal, replace the indoor
controller board.
1) Check the transmission wire.
2) Check with another remote controller.
If “P3” is still indicated, replace the indoor
board.
If other check code appears, replace the original remote controller.
3) Short-circuit between ① and ➁ of CN40 and
attach CN40 to the following units.
● Second unit in twin control
● Second and third units in triple control
● Sub units in group control
1) Check the connector.
2) Measure the resistance of the thermistor ➃ - ➄.
As for the normal resistance, refer to the case
of P1.
If the resistance is normal, replace the indoor controller board.
Malfunction of drain pump1) Malfunction of drain pump
P5
Coil frost protection is work-
P6
ing.
System error1) Wrong address-setting
P7
Abnormality in outdoor unit1) Wrong wiring of indoor/outdoor
P8
2) Damaged drain sensor
1) Short cycle of air cycle
2) Dirty air filter
3) Damaged fan
4) Abnormal refrigerant
2) Signal transmitting/receiving circuit of remote controller is
abnormal.
3) Wrong SW6-setting
connecting wire
2) Reversed phase
3) Protection device is working
4) Damaged outdoor coil thermistor
1) Check the drain pump.
2) ● Check the drain sensor.
● Check the drain sensor heater. Normal resistance should be 82Ω.
If the resistance is normal, replace the indoor controller board.
1) Clear obstructions from the air cycle.
2) Clean the air filter
3) Check the fan.
4) Check the refrigerant temperature.
1) Check the address-setting.
2) Check with another remote controller. If check
code other than “P7” appears, replace the original remote controller.
3) Check SW6 setting.
1) Check the indoor/outdoor connecting wire.
2) Change the connection of electric wiring.
3) Check the protection device.
4) Measure the resistance of the outdoor coil thermistor. If the resistance is normal, replace the
outdoor controller board.
50
Page 51
3. SERVICE DATA INDICATION BY SWITCHES ON OUTDOOR CONTROLLER BOARD
SW3-1
SW3-2
LED
Check code
OFF
OFF
Outdoor coil thermistor is
abnormal
Input circuit on controller
board is abnormal
Open phase
63H2 function
51C function
26C function
Overheat protection
Reversed phase
Blinking
Output state
OFF
OFF
OFF
Outdoor coil
temperature
(bit)
ON
1
2
4
8
16
32
64
128
1
2
4
8
16
32
64
128
256
512
1024
2048
4096
8192
16384
32768
ON
Fan output
step
(bit)
OFF
ON
Total time of
compressor
operation(Hr)
ON
Compressor ON command
from indoor controller
Heating operation command
from indoor controller
During 63H1 function
Compressor ON
Outdoor fan ON
4-way valve ON
Bypass valve ON
Crankcase heater ON
Lighting
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
Setting dip switches SW2 and SW3 on the outdoor controller board enables LED to show the output state and check code.
Output state is shown by LED lighting, and check code by blinking.
SW1 : Turning SW1 ON clears the check code. If SW1 is turned ON while the check code is blinking , the indication changes
to output state indication.
NOTE : SW1 is usually available independent of SW3 setting. As an exception, when the check code shows a
reversed phase or an open phase during the power-on-reset state, SW1 is not available.
SW2 : SW2 is turned ON by pressing, and OFF by releasing.
When SW3-1 and SW3-2 are OFF, pressing SW2 changes indication between output state and check code alternately.
When SW2 is turned On with SW3-1 OFF and SW3-2 ON, the compulsory defrosting starts.
SW3 : Output state indication items depend on the combination of SW3-1 ON/OFF and SW3-2 ON/OFF.
Changed alternately by pressing SW2.
51
Page 52
3-1 Outdoor coil temperature
50
Fan output step (bit)
Fan rotational frequency (rpm)
100150200250
800
600
400
200
0
50
Fan output step (bit)
Type
Fan rotational frequency (rpm)
100150200250
800
600
400
200
0
Type
To obtain data on the outdoor coil temperature, add the number of bits of lighting LEDs, and see the graph below to find
the temperature.
Short
Temperature
Open
Number of bits
3-2 Fan output step
To obtain data on the fan output step, add the number of bits of lighting LEDs, and see the graph below to find the fan
rotational frequency.
1PUH-1.6/2KA
PUH-4KSA
<50HZ>
2PUH-2.5VKA
PUH-2.5/3KA
<50HZ>
3-3 Total time of compressor operation
Compressor operation time is indicated in 256 hour units. To obtain the compressor operation time, add the hours of lighting LEDs. During the compressor operation time indication, SW2 is not available.
3-4 Check code indication
● When a protection function works for the first time during operation, the operation stops and restarts after the 3-minutes
time delay mode. When the protection function works again, the operation stops. (Check mode) When both SW3-1 and
SW3-2 are OFF, the check code is indicated.
● If the outdoor controller board receives the compressor ON command from the indoor controller board during check
mode the indication changes to output state indication.
● By pressing SW2 during normal operation. operation will continue.
● The latest check code is indicated.
52
Page 53
4. TROUBLESHOOTING ACCORDING TO CHECK CODE
Blinking
LED
LD1
LD2
LD3
LD4
LD5
LD6
Diagnosis of malfunctionCauseCheck point
Reversed phasePhases L1, L2, and L3are con-
Open phase● Phase L2is open.
Outdoor coil thermistor is
abnormal. (Open circuit or short
circuit)
High pressure switch (63H2)
function
Thermal relay (51C) function● 51C was connected incor-
Thermal switch (26C) function. ● 26C was connected incor-
nected improperly.
● Contact of protector, such as
thermal switch, opened when
power was turned on.
● Outdoor coil thermistor is
broken.
● Thermistor was connected
incorrectly.
● 62H2 was badly connected.
● 63H2 was working.
rectly.
● 51C was working.
rectly.
● 26C is working.
Check the power supply connection.
● Check the power supply.
● Check each protector.
● Measure the resistance of the thermistor.
● Check the thermistor. If normal, replace the out-
● Check 63H2 and the outdoor fan motor.
● Check if refrigerant supply is low.
● Check if air cycle is short-cycled.
● Check 51C, the compressor, and power supply.
● Check 26C.
● Check if refrigerant supply is low.
● Check if the capillary tube is clogged.
door controller board.
LD7
Over heat protection ● The thermistor is broken.
LD8
Input circuit of outdoor controller board is abnormal.
● Coil temperature is over
67°C.
● Pulse input is abnormal.● Replace the outdoor controller board.
5.WHEN OUTDOOR UNIT DOES NOT WORK
Cause
1) Indoor/outdoor connecting wires are poorly connected.
(Refer to next page.)
2) Power supply is poorly connected.
3) Connector or transformer is broken.
4) Fuse (6A) in the outdoor controller board is blown.
● Measure the resistance of the thermistor.
● Check the outdoor fan motor.
● Check if air cycle is short-cycled.
Check points
1) Check the connecting wires.
2) Check the power supply.
3) Check connectors and transformers.
4) Check the fuse.
53
Page 54
6. WRONG WIRING ON SITE
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
6-1 Between remote controller and indoor unit
If the wire is disconnected between the remote controller and the indoor unit, nothing is displayed on the remote controller
when the POWER button is pressed. The beep sound will also not be heard.
6-2 Phenomenon due to wrong wiring between indoor and outdoor units
Cooling operation. Several minutes later,check code “P8” appears
on remote controller display.
ONNormal operation.
OFFOutdoor unit stops.
Operation stops. 9 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops.
Operation stops. 27 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOutdoor unit stops.
Operation stops. 9 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops.
Operation stops. 27 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOutdoor unit stops.
Operation stops. 9 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops.
Operation stops, 27 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOutdoor unit stops.
Operation stops. 9 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops.
Operation stops. 27 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops.
Operation stops. 9 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops. 4-way valve turns OFF.
27 minutes later, check code “P8” appears on remote controller
ON
display.
Disconnection between 3 and 3.
COOL
HEAT
Normal operation.
–
OFFOperation stops. 4-way valve turns ON.
Operation stops. 27 minutes later, check code “P8” appears on
ON
remote controller display.
54
Page 55
7. OTHER TROUBLES AND CAUSES
Vanes do not work.
Unit stops after 5 to
20 seconds operation
Airflow display is OFF
and button does
not operate.
In this case, remote
controller is normal.
Power ON/OFF button
is not available.
t
t
t
Vane motor does not work.
Limit switch does not work.
Connector is poorly connected.
Vane motor is poorly assembled.
Indoor controller board is damaged.
Protection function is working.
Indoor controller board
deems the auto vanes
are not attached to the
unit.
Horizontal angle can
not be detected.
Beep sound is heard,
but display is turned
OFF.
Beep sound is not
heard, and display
remains OFF.
t
t
t
t
“CENTRALLY CONTROLLED” is displayed.
t
Indoor controller is
damaged.
Dip switch setting is
wrong.
Indoor controller is
damaged.
Vane motor is damaged.
Vane motor limit switch
is poorly connected.
Auto vane is wired after
power is turned to ON.
Indoor/outdoor connecting wire is connected
incorrectly.
Indoor/outdoor connecting wire shorts.
Compressor protector
is damaged.
Outdoor controller
board is detective.
Remote controller is
damaged.
Transmission wire is
poorly connected
Vane motor is damaged.
t
t
Refer to check code on remote controller display.
See page 50.
Vane motor relay is damaged.
Limit switch is damaged.
The size of the cam is wrong.
t
t
t
Vane motor limit switch
is damaged.
Vane motor is damaged.
Poorly connected
Disconnected
Transmission wire is
damaged.
Connector is poorly
connected.
Indoor terminal block is
poorly connected.
Remote controller ter-
minal block is poorly
connected.
55
Page 56
8. MR. SLIM/LOSSNAY INTERLOCK OPERATION
<Symptoms that are not malfunctions>
If any of the following symptoms occur, they are not malfunctions.
Symptom
LOSSNAY control switch can not work during interlock opera-
LOSSNAY control switch does not work.
LOSSNAY air speed can not be controlled in interlock operation.
For LOSSNAY, troubleshooting refer to the LOSSNAY technical & service manual.
tion.
LOSSNAY control switch is effective only while Mr. SLIM is not
operating.
LOSSNAY fan speed is fixed to HIGH during interlock operation.
LOSSNAY fan speed LOW/HIGH can be switched only during
LOSSNAY individual operation with the LOSSNAY control
switch.
Cause
56
Page 57
1
1
2
2
3
3
Red
White
Black
Relay connector
Protector
Parts nameCheck points
Measure the resistance between the terminals using a tester.
(Winding temperature 20:)
Fan motor (MF)
107"
Measure the resistance between the terminals using a tester.
Contactor (88H)
[for heater]
Abnormal
Open or short
61
88H
Normal
1.6
/ 2 /
2.5
/ 3 /
4
Abnormal
Open or short
Red–Black
White–Black
Motor terminal
or
Relay connector
1.6 / 2
154.3"
162.0"
2.5 / 3
99.5"
103.9"
4
62.6"
74.0"
Normal
Open or short
Abnormal
Brown–Yellow
Brown–Blue
Red–Orange
Red–Pink
Connector
Normal
2.5 / 3 / 4
186~214"
Normal
1.6 / 2
15k"
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:~30:)
Vane motor (MV)
Measure the resistance of each heater element by using a tester.
Heater (H)
Normal
Abnormal
1.6 / 2
14.3"
700W 120V
2.5 / 3
18.9"
700W 240V
4
16.5"
800W 240V
Open or short
Room temperature
thermistor (RT1)
Pipe temperature
thermistor (RT2)
Disconnect the connector then measure the resistance using a tester.
(Surrounding temperature 10:~30:)
(Refer to the next page for a detail.)
Normal
4.3k"~9.6k"
Abnormal
Open or short
Thermal protector
OFF : 120i5:
ON : OFF–15:
OFF:130i5:
ON :80i20:
9. How to check the parts
PKH-1.6FKHA3, PKH-2FKHA3, PKH-2.5FKHA2, PKH-3FKHA2, PKH-4FKHSA2,
PKH-2.5FKHA3, PKH-3FKHA3, PKH-4FKHSA3
57
Page 58
0
10
20
30
40
50
-20 -1001020304050
< Thermistor for lower temperature >
Temperature (:)
Resistance (K")
<Thermistor Characteristic graph>
Thermistor for
lower temperature
Thermistor R0=15k' ± 3%
Fixed number of B=3480k' ± 2%
Room temperature thermistor(RT1)
Pipe temperature thermistor(RT2)
1
273+t
1
273
58
Page 59
11SYSTEM CONTROL
Unit
Remote
controller
UnitUnit
Optional
adapter
Remote
ON/OFF
switch
Remote
controller
Relay box
Unit
Unit
Remote
controller
UnitUnit
Unit
Remote controll
display board
Remote
controller
UnitUnit
Circuit breaker
Remote
controller
1. VARIETY OF SYSTEM CONTROL FUNCTIONS
1 Group control with
a single remote
controller
(See page 60.)
Many units, installed at different locations, can be started
and controlled with a single remote controller. The remote
controller can be mounted in a different location using a
non-polar two-wire cable, which can be extended up to
500m. Amaximum of 50 units can be controlled with a
single remote controller. All units operate in the same
mode.
2 Both remote
ON/OFF and individual controls
(See page 61.)
w Timer adapter
(PAC-SA89TA-E)
is needed.
3 Individual control
by grouping
remote controllers
(See page 62.)
4 Multiple remote
control display
(See page 63.)
w Multiple display
adapter
(PAC-SA88HA-E)
is needed.
5 Auto restart func-
tion
(See page 63.)
All units can be turned on or off simultaneously using a
remote ON-OFF switch. Also, each unit can be controlled
individually by each remote controller. Dunning remote
ON-OFF control, a message of “CENTRALLY CONTROLLED” is displayed on the LCD of the remote controller.
This is available for both one unit control and several units
control.
By grouping the remote controllers in one place, several
units installed at different locations can be controlled individually, and operation conditions of all units are visible
without a special control board. The control method is the
same as that of the single unit with a single remote controller.
Several units can be controlled with a remote control display board. Operation conditions of all the units are visible with the remote control display board.
Individual control by each remote controller is also possible.
A unit can be started or stopped with the circuit breaker
on or off.
Remote controller is also available.
With this function, when the power is restored after power
failure, the unit will restart automatically. (However, when
the remote controller POWER ON/OFF button is OFF, the
unit will not start.)
59
Page 60
2. GROUP CONTROL WITH A SINGLE REMOTE CONTROLLER
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
To remote
controller
To next
unit
To next unit
The last unit
dose not have
this wire.
Next unit
electrical box
Master unit
electrical box
123ANE
123ANE
Master
unit
No.1 unitNo.2 unitLast unit
2-wire cable
A maximum of 50 units can be started in order according to the dip switch settings
2-1 How to wire
(1) Connect the remote controller to the double terminal block
on the indoor controller board of the master unit (No.0 unit).
(See Figure 1.)
(2) Connect the double terminal block of the master unit to the
double terminal block of No.1 unit.
(3) Connect the double terminal block of No.1 unit to the double
terminal block of No.2 unit.
(4) Continue the process until all the units are connected with
two-wire cables. (See Figure 2.)
(5) Remove the connector CN40 from the indoor controller
board of each unit except the master unit. (See Figure 3.)
(6) Set the unit-address of each unit with SW2 on the indoor
controller board following the instructions below.
2-2 How to set unit-address
The unit-address also serves as a successive-start timer which
starts each unit at intervals of 1 second. If two or more units
have the same unit-address in a group control, operation stops
due to system error. Be sure to set SW2 correctly following the
instructions below.
(1) Each lever of SW2 shows the number as follows.
(2) Total number of levers turned to ON shows the address of
the unit.
For example, to set No.3 unit, turn ON SW2-1 and SW2-2.
(3) In this way, set from the. master unit to the last unit.
Do not forget to set the master (No. 0) unit.
Figure 1
Figure 2
Figure 3
Indoor controller board ▼
Should be removed from
all units other than unit
No.0:(Master Unit)
Setting examples
Unit address & start
delay in seconds.
2-3 Unit control
The remote controller can control all units ON/OFF, temperature,air flow, and swing louver. However, the thermostat in
each unit turns ON or OFF individually to adjust to the room temperature.
Master (No. 0) unit
ALL OFF
No. 1 unit
1 ON
SW2
0
1
No. 2 unit
2 ON
2
No. 4 unit
60
3 ON
4
No. 8 unit
4 ON
8
No. 16 unit
5 ON
16
No. 32 unit
6 ON
32
Page 61
3. REMOTE ON-OFF AND INDIVIDUAL REMOTE CONTROLS
Remote
controller
power supply of
control circuit
Remote
ON/OFF
switch
2-wire
remote
controller
cable
Figure 6
Relay box
Timer adapter cables
Timer adapter
PAC-SA89TA-E
Power
supply
Remote
ON/OFF
switch
No.1 unit
relay box
No.2 unit
relay box
Next unit
T
X2X2
T
Glow switch or pilot lamp can be
combined to easily identify the
on-off mode of SW1 and SW2.
To
No.1
unit
To
No.2
unit
Timer adapter cables
Remote controller
T
X2
SW
1
SW2
T
X2
This method is available to control one unit or any number of units.
The following operations are available by connecting a relay, a timer adapter (PAC-SA89TA-E), and a remote ON/OFF switch
to the system. Timer adapter is an optional part. Other parts are available on the market.
(A) To start all units in order by remote ON-OFF switch
(B) To stop all units simultaneously by remote ON-OFF switch
(C) To switch between the remote ON-OFF control and the individual remote control
3-1 System
Figure 6 shows the case of three units.The same is the case with any number of units.
NOTE1 : Install the relay box where you can be serviced it easily.
NOTE2 : For control circuit wiring, use a wire of No. 14 AWG or a control cable according to the power supply of control
circuit.
NOTE3 : When the power supply of the control circuit is 220/240V AC,
● Do not connect the control circuit wire to the remote controller cable directly.
● Do not place the control circuit wire and the remote controller cable into the same conduit tube.
3-2 Basic wiring
Caution : Before starting all units simultaneously by the remote ON-OFF switch, be sure to connect a sequence-start timer
into the remote ON-OFF circuit. Otherwise, a rush of starting current may damage the power supply.
61
Page 62
3-3 Switch function of remote ON-OFF switch
Remote
controller cable (2-core)
Remote controller
SW2
(Switches between remote ON-OFF and individual control)
ON
(Remote ON-OFF control)
ON
SW1
(Switches between
remote ON and OFF.)
w1 After all units start together, if SW2 is turned OFF, each unit can be individually stopped by each remote controller.
w2 After all units stop together, if SW2 is turned OFF, each unit can be individually started by each remote controller.
(Start)
OFF
(Stop)
All units start together.
Individual control is not available.
All units stop together.
Individual control is not available.
w1
w2
Each unit can be controlled by each
remote controller.
Remote ON-OFF switch is not available.
OFF
(Individual control)
4. INDIVIDUAL CONTROL BY GROUPING THE REMOTE CONTROLLERS
Grouping the remote controllers allows individual control and centralized monitoring of units installed in different places without a special
control board.
Remote control cables are extendible up to 500m. When the cable
length exceeds 12m, use the double-insulated two-care cable such as
Belden 9407. Also, the cable thickness must be No. 22 AWG or above.
When gathering the power ON/OFF switches of air conditioners near
the remote controllers, you should also install the power ON/OFF
switch near each unit to prevent electric trouble during servicing.
62
Page 63
5. MULTIPLE REMOTE CONTROL DISPLAY
CN51
connector(5P)
GREEN
Power
supply
Electrical insulation is needed.
Wiring at the actual place
Optional multiple display
adapter
The maximumdistance between
indoor board and relay is 10m.
YELLOW
ORANGE
RED
BROWN
5
X1
X1
RL
GL
X2
X2
1
<Wiring >
Power
supply
Remote
controller
cable
Relay box
(Field supply)
Remote
controller
Remote
controller
Remote
controller
3wires
3wires
3wires
2wires
No.1 unitNo.2 unitNo.3 unit
Muitiple remote control
ON-OFF display
(Field supply)
(Operation check)
<System>
Power
supply
RL-1
GL-1
Multiple Remote Control Display
Multiple remote
controller adapter
connect to
the connector CN51
Relay box
5
X1-1
X2-1
1
<Wiring diagram>
RL-2
GL-2
RL-3
No.1 unit
GL-3
X1
X2
5
1
No.2 unit
X1
X2
5
1
No.3 unit
X1
X2
X1-2
X2-2
X1-3
X2-3
Remote controller
A
B
Brown
Red
Orange
Remote controller
A
B
Brown
Red
Orange
You can control several units with a multiple remote control display,by
wiring an optional multiple display adapter (PAC-SA88HA-E) with relays
and lamps on the market.
5-1 How to wire
(1) Connect the multiple display adapter to the connector CN51 on the
indoor controller board.
(2) Wire three of the five wires from the multiple display adapter as shown
in the figure below.
Indoor controller board
[Notes on Signs]
X1:Relay (for check lamp)
X2:Relay (for operation lamp)
RL:Check Lamp
GL:Operation Lamp
[Field supplied parts]
Relays:12V DC with rated coil power con-
sumption below 0.9W.
Lamps:Matching to power supply voltage.
By setting the distich SW1-10 to ON (PKH-1.6/2FKHA), J1-10 Cut (PKH-2.5/3/4FKH(S)A), the air conditioner can be started/stopped by power supply ON/OFF.
If the air conditioner is OFF before the power failure, it will not start operation by power restore.
<Wiring>
For remote control, connect the optional timer adapter (PAC-SA89TA-E)
6. AUTO RESTART FUNCTION
63
A : An optional timer adapter
B : Asingle-throw switch
Page 64
12DISASSEMBLY PROCEDURE
Metal fixture
Screws
Hanger of indoor unit
Catch of installation plate
Terminal cover
Electrical parts box cover
Connector
Connector
Indoor controller
board
Right side panel
PKH-3FKHA2 ,PKH-3FKHA3
OPERATING PROCEDUREPHOTOS&ILLUSTRATION
1. Removing the lower side of the indoor unit from the installation plate
(1) Remove the 2 screws.
Hang the indoor unit hangers to the catches on the installation plate.
Figure 1
2. Removing the right side panel
(1) Remove the 2 screws of the right side panel:one on the
bottom and the other on the upper right-hand side.
(2) Disconnect the connector from the adapter case.
(3) Sliding the right side panel to the right, pull it out toward
you.
3. Removing the indoor controller board
(1) Remove the right side panel.
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Disconnect the connectors on the indoor controller board.
(4) To unhook the catches on the right-hand side of the indoor
controller board, pull the left-hand side toward you and lift
up the cover to the right. Then the indoor controller board
can be removed.
Figure 2
Photo 1
Indoor controller
board
Electrical parts
box cover
Catches
4. Removing the electrical parts box
(1) Remove the right side panel.
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Remove the room temperature thermistor and the pipe
temperature thermistor.
(4) Disconnect the vane motor connector on the indoor con-
troller board.
(5) Remove the 2 screws of the electrical parts box.
(6) Disconnect the connector of the heater lead wire connec-
tor.
(7) Disconnect the connector of the fan motor lead wire.
(8) Remove the electrical parts box.
64
Photo 2
Room temperature thermistor
Pipe temperature thermistor
Screws
Electrical parts
box
Page 65
OPERATING PROCEDUREPHOTOS&ILLUSTRATION
Catch on the left side panel
Catch on
the unit
(9) Remove the screws of the indoor controller board case,
and pull out the indoor controller board case.
Then the transformer and the capacitor and heater contactor
can be serviced.
5. Removing the vane motor
(1) Remove the right side panel.
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Remove the 2 screws of the vane motor, and remove the
motor from the shaft.
(4) Disconnect the vane motor connector on the indoor
controller board.
Photo 3
Capacitor
Indoor controller
board case
Photo 4
Heater contactor
Transformer
Electrical parts box
Screws
6. Removing the intake grilles
(1) Remove the right side panel.
(2) To remove the left side panel, remove the screw on the
bottom and the screw on the upper left-hand side. (See
Figure 3.)
1. Press up this side of the left side panel to unhook the
catch on the panel from the catch on the unit.
2. Slide the left side panel to the left to remove the panel.
Note: Fix the unit to the metal fixture securely
(3) Remove the air filters.
(4) Hold and press the center cover to remove.
(5) Remove the screws of the grilles.
(6) Pull the lower side of the grille toward you and slide the
upper to the right to remove the grills.
7. Removing the drain pan
(1) Remove the left and right side panels.
(2) Remove the grilles.
(3) Remove the electrical parts box cover.
(4) Loosen the drain hose band to remove.
(5) Remove the 3 screws of the drain pan, and slide the drain
pan toward you to remove.
Vane motor
Figure 3
Photo 5
Left side panel
Photo 6
Slide to the
right
Screws for grills
Drain pan
Indoor controller board
Grilles
Drain hose
band
Screws
Drain hose
65
Page 66
OPERATING PROCEDUREPHOTOS
8. Removing the lineflow fan and the fan motor
(1) Remove the left and right side panels.
(2) Remove the grilles.
(3) Remove the electrical parts box.
(4) Remove the drain pan.
(5) Loosen the screw that fixes the lineflow fan to the fan
motor. (See Photo 7. )
(6) Remove the 4 screws of the motor fixture, and remove the
fan motor and the motor fixture at a time (See Photo 8.)
(7) Remove the screws of the left and right motor supports,
and remove the motor supports and the fan motor. (See
Photo 9.)
(8) Remove the 2 screws on the left and right sides of the heat
exchanger, and pull the bearing support toward you. (See
Photo 11.)
(9) Remove the screw of the center support, and remove the
support. (See Photo 10. )
(10)
Pull the left-hand side of the heat exchanger toward you,
and remove the lineflow fan.
Photo 7
Photo 8
Lineflow fan
Screw
Fan motor
Screw
Fan motor
Motor fixture
Heat exchanger
Bearing support
Lineflow fan
9. Removing the electrical heater.
(1) Remove the left and right side panels.
(2) Remove the grilles.
(3) Remove the drain pan.
(4) Loosen the screw that fixes the lineflow fan to the fan
motor.(See Photo 7.)
(5) Remove the screw of the center support, and remove the
support. (See Photo 10.)
(6) Remove the 2 screws on the left and right sides of the heat
exchanger, and pull the bearing support toward you. (See
Photo 11.)
(7) Pull the left-hard side of the heat exchanger toward you,
and remove the lineflow fan.
(8) Remove the heater fixing screws (1 screw each on right
and left sides), and slide the heater element to the left to
remove the heater.
Photo 9Photo 11
Screw
Motor support
Photo 10
Photo 12
Heat exchanger
Fan motor
Lineflow fan
Heater element
Screw
Motor
support
ScrewCenter support
Heater fixing screws
66
Page 67
13PARTS LIST
Part No.Specification
No.
Wiring
Diagram
Symbol
Recom-
mended
Q,ty
Price
Unit
Amount
Remarks
(
Drawing No.
)
Q,ty/set
PKH-1.6/2
FKHA
FKHA
1
FKHA
2
FKHA
3
1
2
3
4
5
6
7
8
9
10
11
Part Name
1
4
2
2
2
1
2
1
1
1
1
1
4
2
2
2
1
2
1
1
1
1
R01 KV5 651
R01 47J 651
R01 KV5 096
—
—
R01 A20 054
R01 KV5 500
R01 47J 500
T7W 580 058
—
R01 KV5 623
R01 KV5 658
R01 KV5 635
R01 KV5 808
FRONT PANEL
FRONT PANEL
SCREW CAP
CATCH HOLDER
CATCH HOLDER
FILTER CATCH
AIR FILTER
AIR FILTER
SERVICE PANEL
PANEL CATCH
UNDER COVER
CORNER COVER
BOX ASSEMBLY
BACK PLATE
(BC25R572H03)
(BC25R572H06)
(BC25G057H07)
STRUCTURAL PARTS
PKH-1.6FKHA, PKH-1.6FKHA1
PKH-1.6FKHA2, PKH-1.6FKHA3
PKH-2FKHA,PKH-2FKHA1
PKH-2FKHA2,PKH-2FKHA3
SLEEVE BEARING
BEARING SUPPORT
BEALING MOUNT
FAN GUARD
FAN GUARD
VANE MOTOR
NOZZLE ASSEMBLY
GUIDE VANE
LEFT ROTARY VANE
CENTER SUPPORT
VANE SLEEVE
DRAIN HOSE
ARM
RIGHT ROTARY VANE
FILTER
CHECK MODE
TEST RUN
241
ELECTRICAL PARTS
PKH-1.6FKHA, PKH-1.6FKHA1 , PKH-1.6FKHA2,PKH-1.6FKHA3
PKH-2FKHA,PKH-2FKHA1,PKH-2FKHA2 ,PKH-2FKHA3
2P(1/2)
MOTOR BAND
FAN MOTOR
MOTOR LEG
MOTOR LEG
RUBBER MOUNT
MOTOR BAND
RIGHT LINEFLOW FAN
CENTER SUPPORT
BEARING BAND
SLEEVE BEARING
BEARING MOUNT
FAN GUARD
THERMAL FUSE
HEATER ELEMENT
LEFT SIDE PANEL
UNDER PLATE
UNDER PLATE
NOSE
NOSE
AIR FILTER
RIGHT SIDE PANEL
INTAKE GRILLE
BACK PLATE
TOP PLATE
BOX ASSEMBLY
BOX ASSEMBLY
DRAIN SOKET
INTAKE GRILLE
STRUCTURAL PARTS
PKH-4FKHSA, PKH-4FKHSA1, PKH-4FKHSA2, PKH-4FKHSA3
9
8
1
7
2
3
6
4
Part number that is circled is not shown in the figure.
5
75
Page 76
14OPTIONAL PARTS
Part No
Pipe length
Pipe size O.D.
Connection method
PAC-05FFS-EPAC-07FFS-EPAC-10FFS-EPAC-15FFS-E
5C7C15C10C
Liquid:{9.52 Gas:{15.88
Indoor unit:Flared Outdoor unit:Flared
Part No
Pipe length
Pipe size O.D.
Connection method
Service Ref. : PKH-1.6FKHA3, PKH-2FKHA3, PKH-2.5FKHA2, PKH-3FKHA2
PKH-2.5FKHA3, PKH-3FKHA3
Service Ref. : PKH-4FKHSA2, PKH-4FKHSA3
Note 1. How to connect refrigerant pipes.
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as the
connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind
caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made,
open the stop valve on the outdoor unit to allow refrigerant gas to flow.
If piping length exceeds 5m,an additional charge of refrigerant is needed.
Note 2. The following main parts are contained in the optional refrigerant piping kit.
When using a program timer, PAC-SK65PT, a program timer adapter (PAC-825AD) is also needed.
2-1 Program timer specifications
2-2 Feature of program timer
(1) Daily timer function
Daily timer can be set in 30 minutes units for up to 24 hours.
Each unit can be set for unit ON, unit OFF, or setback operation.
(2) Setback operation (PAC-SK65PT)
Set back operation is useful for reducing running costs
e.g. At a hotel with a 24-hour system
(3) Weekly timer function
8:00~23:00 Cooling operation with set temperature at 26°C
23:00~8:00 Setback operation with 2 degrees of setback
As shown in the chart on the right, the set temperature rises 2 degrees
automatically during the setback operation. When the setback operation
ends, normal operation will begin.
Daily timer function can apply to each day of the week.
76
Page 77
2-3. How to connect program timer
ORN1
2
3
BRN
RED
SET/MONITOR
SET
S M T W T F S
MONITOR
PROERAN TIMER
PAC-SC32PTA
TODAY
ON
WEEKLY
SETTING
OFF
ON
SET BACK
OFF
CLOCKDAILY TIMER
SET BACK
SET BACK
DAILY
SETTING
12 15 18 21 24
0 3 6 12 15
SET/MONITOR
SET
S M T W T F S
MONITOR
PROERAN TIMER
PAC-SC32PTA
TODAY
ON
WEEKLY
SETTING
OFF
ON
SET BACK
OFF
CLOCKDAILY TIMER
SET BACK
SET BACK
DAILY
SETTING
12 15 18 21 24
0 3 6 12 15
FILTER
CHECK MODE
TEST RUN
4
2-wire cable
5-wire cable
To indoor unit
Connector CN1Connector CN1
(1) Install the program timer next to the remote controller the same way as the remote controller is installed.
(2) Connect the program timer and the remote controller with a 6-wire cable as shown in the figure below
NOTE:While the program timer is connected to the remote controller, the 24hour
ON/OFF timer on the remote controller will not operate.
2-4 Names and functions
<PAC-SC32PTA>
WEEKLY TIMER SETTING DISPLAY
Used for selection of if or not the day operation pattern set by PATTERN SETTING is to
be applied in weekly day unit, setting.
SET/MONITOR DISPLAY
During SET is display, clock adjustment,
change of weekly day, daily and weekly timer
setting can be performed.
During MONITOR is display, all switches
except SET/MONITOR SW are invalidated.
This is normal status.
WEEK DAY SETTING SW
Used for week day setting.
MODE SELECTOR SW
CURRENT TIME DISPLAY
During MONITOR status,current
time is display.
During Daily timer setting, a
time desire for timer setting is
displayed.
CROCK ADJUSTMENT SW
SET BACK DISPLAY
Indicates the setting set
back range.
DAILY TIMER SETTING DISPLAY
24 hours is divided into 48 blocks and each
block express 30 minutes.
The block display consists of 3 pattern.
Set back can be done in the range of 1,2,4,6
and 8°C.
SET BACK SETTING SW
Used for set back setting.
ON/SET BACK/OFF SW
Used to specify the time setting pattern.
DAILY TIMER SW
Used for timer setting in 30 minutes unit.
WEEKLY TIMER SW
Using this switch select “MONITOR” or “SET”
Mode.
“MONITOR” :Indicates the current timer set-
ting. All switch expect MODE
SELECTOR SW are invalidated
then.This is the normal status.
“SET”: Set to “SET” mode for clock adjust-
ment, charge of week day, daily and
weekly timer setting.
3. TIMER ADAPTER
This adapter is needed for system control and for operation via external contacts. Adapter connection is described on page 61.
Part No.PAC-SA89TA-E
Used for adjustment of the current time.
Push SW to advance the time. Each time the button is
pushed the time advance by 1 minute, pushing continuously
advances by 1 minute at 0.5 second interval, and when the
lower digit of minute decomes 0 indication advances in 10 minutes unit.
SW is used for reversing the time. Each time the button is
pushed the time reverses by 1 minute, pushing continuously
reverses the time by 1 minute at 0.5 second interval, and when
the lower digit of minute decomes 0 indication reverses in 10
minutes unit.
77
Used for setting timer in day of week unit.
Pushing SW moves the week day light
display in order of
S → M → T → W
…
enabling to set the week day.
Page 78
4. MULTIPLE REMOTE CONTROLLER ADAPTER
BACK
ACTIVE
BYPASS
POWER
ON/OFF
DUAL
CENTRAL
AHEAD
MITSUBISHI ELECTRIC
ENGAGED
GROUP
ACTIVE BYPASS
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
DUAL CENTRAL
12345678910
117
117
BACK
ACTIVE
BYPASS
POWER
ON/OFF
DUAL
CENTRAL
AHEAD
ENGAGED
GROUP
ACTIVE BYPASS
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
DUAL CENTRAL
12345678910
113
113
12
10 9 8 7 6 5 4 3 2 1
56.3
11
23.5
8
This adapter is needed for remote indication (operation/check). Adapter connection is described on page 63.
Part No.PAC-SA88HA-E
1
2
3
4
5
BRN
RED
ORN
YLW
GRN
5. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units. When using the PAC-805RC, the program timer adapter (PAC825AD)is also needed. See page ##.
Part No.PAC-805RC
5-1. DimensionsUnit : mm
5-2. Functions
"ENGAGED" indicator
When this indicator is lit, transmission is in
progress and all switches are inoperative.
POWER ON/OFF switch
Operation ON/OFF switch.
▲BACK ▼AHEAD buttons
These buttons are used to designate
DUAL/CENTRAL switch
This change-over switch governing the
operation of the accessory remote controller.
"DUAL"
Instructions from both the accessory
remote controller and the centralized
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
POWER
ON/OFF
AHEAD
remote controller are valid. (Priority given
to the last instruction received.)
"CENTRAL"
MITSUBISHI ELECTRIC
ON/OFF switching by the accessory
remote controller is invalidated. Control is
by the centralized remote controller only.
Initial setting is "DUAL".
LCD Matrix Display
This display indicates the operational sta-
tus of all connected units either by steady
lighting or by flashing.
Independent “DUAL / CENTRAL” and “ACTIVE / BYPASS” setting of all the groups is possible. When the power supply to the
the attached unit(s). (They designate
the unit that is centrally controlled.)
●When group “00” is designated; collective ON/OFF instruction is sent to all
units.
●When group “01”-“16“ is designated;
ON/OFF instruction is sent to the designated units only.
ACTIVE/BYPASS switch
This is a change-over switch for the
program timer.
(It selects timer operation on the pro-
gram timer.)
Use “BYPASS” when a program timer
is not connected.
“ACTIVE”
The switch tums ON/OFF operational
instructions from the program timer
automatically.
“BYPASS”
ON/OFF Operation is by the central-
ized remote controller only.
Initial setting is “BYPASS”.
centralized remote controller is cut due to power failure, all settings will return to original “DUAL” and “BYPASS”.
78
Page 79
5-3 Connection method
A N E
T
(Y)
(W)(R) (O)
(BR)
5A
A
POWER
SUPPLY
N
E
Fuse(5A)
Tie-wrap
Wiring has to be changed when
a 200,230 or 240V power is used.
Tie-wrap
TRANSFORMER
Transmission
TERMINAL-BLOCK
FOR TRANSMISSION
TERMINAL-BLOCK
OF POWER SUPPLY
200
220
230
240
BACK
ACTIVE
BYPASS
POWER
ON/OFF
DUAL
CENTRAL
AHEAD
ENGAGED
GROUP
ACTIVE BYPASS
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
DUAL CENTRAL
12345678910
10 9 8 7 6 5 4 3 2 1
To adaptor's
terminal-block
Centralized remote
controller
Non-polar,
two-wire cable
To adaptor's
terminal-block
Power supply board box
(1) Connections in the power supply cord.
1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-wrap.
Connect a single phase 200V AV (220, 230, 240V) to
As E is the GND terminal, be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap. Use a Ø1.6
(AWG 14) or above two-wire cable for the transmission line.
CAUTION : Never connect the power supply cord to the transmission terminal-block.
A N.
(2) Connection method of centralized remote controller and power supply board.
1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable.
2. Wiring diagram
Centralized
remote controller
Power supply
board
3. Be sure to set the maximum address number with the
dip switch SW17 on the centralized remote controller.
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER
ON/OFF
AHEAD
Dip switch
SW17
ENGAGED
GROUP
12345678910
GROUP
SELECTION
PROGRAM
ACTIVE BYPASS
TIMER
CONTROLLER
DUAL CENTRAL
OPERATION
79
Page 80
6. PROGRAM TIMER ADAPTER
Length : 2m (6' 7")
Length : 2m (6' 7")
Length : 2m (6' 7")
Length : 2m (6' 7")
This adapter is needed when a program timer(PAC-SK65PT)or a centralized remote controller(PAC-805RC)is used.
6-2 Connection method
Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out the work.
(1) Connections in the adapter box
1. Connect the power supply cord to the terminal-block and fix it in-place with a tie-wrap.
Connect a single phase 200V (220, 230, 240V) AV to A N.
As E is the GND terminal, be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap (when a
centralized remote controller is being used).
CAUTION : Never connect the power supply cord to the transmission terminal-block
Fig-1Fig-2
TERMINAL-BLOCK
FOR
TRANSMISSION
Tie-wrap
Transmission cord
CN22
Dip switch
TRANS
CN1 CN21CN51CN30CN42 CN50 CN40
Fuse(5A)
TRANSFORMER
(AG)
SW1
A N E
POWER SUPPLY CORD
TERMINAL-BLOCK
FOR POWER
SUPPLY
Tie-wrap
Terminal block for
transmission to
program timer or
centralized remote
controller
Wiring has to be changed when 200V power supply is used.
(W)
CN22
TRANS
(B)
200
SW1
T
(Y)
240
220
5A
A
N
E
POWER
SUPPLY
(2) When the centralized remote controller is used, set the address number with the dip switch SW1 of the pro-
HEAD OFFICE : MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODE-KU, TOKYO100-8310, JAPAN
cCopyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD
Distributed in Oct. 2001 No.OC130 REVISED EDITION-A 620
Issued in Jun. 1997. No.OC130 560
Made in Japan
New publication, effective Oct. 2001
Specifications subject to change without notice
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.