Mitsubishi PKH-1.6FKA-E, PKH-2FKA-E, PKH-2.5FKA-E, PKH-3FKA-E, PKH-4FKSA-E Service Manual

Page 1
This manual does not cover the following outdoor units. When servicing them, please refer to the service manual No.OC150 and this manual in a set.
[Service Ref.] PUH-1.6VKA
PUH-2VKA
PUH-2.5VKA
PUH-3VKA
PUH-3YKA
PUH-4YKSA
TECHNICAL & SERVICE MANUAL
SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS
CONTENTS
1. PART NAMES AND FUNCTIONS········2
2. SPECIFICATIONS·································4
3. DATA ·····················································9
4. OUTLINES AND DIMENSIONS··········23
5. WIRING DIAGRAM·····························27
6.
REFRIGERANT SYSTEM DIAGRAM
······29
7. OPERATION FLOW-CHART··············30
8. MICROPROCESSOR CONTROL·······34
9. TROUBLESHOOTING························56
10. SYSTEM CONTROL ···························65
11. DISASSEMBLY PROCEDURE ···········70
12. PARTS LIST········································73
13. OPTIONAL PARTS·····························79
1999
Indoor unit [Model names] [Service Ref.]
PKH-1.6FKA PKH-1.6FKA-E PKH-2FKA PKH-2FKA-E PKH-2.5FKA PKH-2.5FKA-E PKH-3FKA PKH-3FKA-E PKH-4FKSA PKH-4FKSA-E
INDOOR UNIT
Wall MountedSeries PKH
FILTER
CHECK MODE
TEST RUN
REMOTE CONTROLLER
No.OC190
The Slim Line. From Mitsubishi Electric.
Page 2
2
1 PART NAMES AND FUNCTIONS
Indoor Unit
Air intake
room air is suctioned in here.
(Removes dust and dirt from the intake air.)
Disperses airflow up and down as well as adjusts the angle of air flow direction.
Filter Air intake grill
Air outletAir outlet
Swing louvers
Air flow can be changed to horizontally by moving the Guide vane to the left or right.
Guide vane
Remote controller
Once the operation of the unit is set, subsequent operations can only be performed by pressing the ON/OFF button
repeatedly.
w button
This switches between continuous
operation and the timer operation
l button
The sets the ventilation fan speed.
Operation buttons
q button
This sets or switches the current time, start time and stop time.
a button
Press this button to switch the cooler electronic dry (dehumidify), automatic and heater modes.
i TEMP. button
This sets the room temperature. The temperature setting can be performed in 1°C units.
Setting range :
Cooler 19°C to 30°C Heater 17°C to 28°C
CHECK-TEST RUN button
Only press this button to perform an inspection check or test operation. Do not use it for normal operation
FILTER button
This resets the filter service indication display
j button
This adjusts the vertical angle of the
ventilation.
ON/OFF button
This switches between the operation
and stop modes each time it is pressed. The lamp on this button lights during operation.
The model name of the remote controller is indicated. PAR-JH241KA(2.5 ~ 4) PAR-JH150KA(1.6/2)
k button
This switches the horizontal fan motion ON and OFF.
(This button does not operate in this model.)
241
FILTER
CHECK MODE
TEST RUN
Page 3
3
Caution
Only the display lights when the unit is stopped and power supplied to the unit.
When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a
malfunction.
When the central control remote control unit, which is sold separately, is used the ON-OFF button, a button and i TEMP button do not operate.
“NOT AVAILABLE” is displayed when the k button are pressed.This indicates that this room unit is not equipped with the fan direction adjustment function and the louver function.
CENTRALLY CONTROLLED display
This indicates when the unit is
controlled by optional features such as central control type remote controller.
w display
This indicates when the continuous operation and time operation modes are set. It also display the time for the timer operation at the same time as when it is set.
OPERATION MODE display
This indicates the operation mode.
STANDBY display
This indicates when the standby
mode is set from the time the sleep operation starts until the heating air is discharged.
DEFROST display
This indicates when the defrost
operation is performed.
CHECK display
This indicates when a malfunction
has occurred in the unit which should be checked.
display
FILTER
This display lights when the filter need to be cleaned.
88°C display
This displays the selected setting temperature.
r display
The current time , start time and stop
time can be displayed in ten second intervals by pressing the time switch button. The start time or stop time is always displayed during the timer operation.
l display
The selected fan speed is displayed.
j display
This indicates the air direction.
Display
In this display example on the bottom left, a condition where all display lamps light is shown for explanation purposes although this differs from actual operation.
display
This display lights in the check mode or when a test operation is performed.
CHECK MODE
TEST RUN
88°C display
The temperature of the suction air is displayed during operation. The display range is 8° to 39°C. The display flashes 8°C when the actual temperature is less than 8° and flashes 39°C when the actual temperature is greater than 39°C.
Operation lamp
This lamp lights during operation, goes off when the unit stops and flashes when a malfunction occurs.
Display
This lamp lights when electricity is supplied to the unit.
241
FILTER
CHECK MODE
TEST RUN
Page 4
2
SPECIFICATIONS
Item Function
Capacity Total input
Service Ref.
Power supply(phase,cycle,voltage)
Input Running current
Starting current External finish Heat exchanger Fan Fan(drive) No.
Fan motor output
Airflow(Low-High)
External static pressure Booster heater
INDOOR UNITOUTDOOR UNIT
Operation control & Thermostat Noise level(Low-High) Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Input
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Heat exchanger Fan Fan(drive)No.
Fan motor output
Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge
Oil<Model> Pipe size O.D.
Connection method
Between the indoor & outdoor unit
REFRIGERANT PIPING
Note1. Rating Conditions (JIS B 8616)
Cooling : Indoor : 27°C (80°F) DB, 19°C (66°F) WB
Heating : Indoor : 20°C (68°F) DB
Outdoor : 35°C (95°F) DB, 24°C (75°F) WB
Outdoor : 7°C (45°F) DB, 6°C (43°F) WB
Liquid mm(in.) Gas mm(in.) Indoor side Outdoor side Height difference Piping length
W
D H
W
D H
Service Ref.
W
Btu/h
kW
kW
A A
kW
3
/min <CFM>
m
Pa(mmAq)
kW
dB(A) mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
kW
A A
kW
kW
3
/min<CFM>
m
dB(A) mm(in.) mm(in.) mm(in.)
kg(lbs)
kg(lbs)
L
2. Guaranteed operating range
Cooling
Heating
PKH-1.6FKA-E
Cooling
4,500
15,350
1.51
PKH-1.6FKA-E
Single, 50Hz, 220-240V
0.07
0.32
0.40 Munsell 3.4Y 7.7/0.8(White)
Plate fin coil
Line flow(direct) ✕ 1
0.030
10-13(353-459)
0(direct blow)
Remote controller & built-in
36-43
20(13/16)
1,250(49-3/16)
200(7-7/8)
300(11-13/16)
17(37)
PUH-1.6VKA
Single, 50Hz, 220-240V
1.44
6.74
33
Munsell 5Y 7/1
Capillary tube
Hermetic
RH247VFCT
1.2
Line start
Internal thermostat, HP switch
Plate fin coil
Propeller (direct) ✕ 1
0.065
45(1,590)
Reverse cycle
49
870(34-1/4)
295+24(11-5/8 add 1)
650(25-5/8)
53(117)
R-22
2.2(4.9)
0.57<MS-56>
9.52(3/8)
15.88(5/8) Flared Flared
Max. 40m Max. 40m
Indoor Upper limit Lower limit Upper limit Lower limit
35°C DB, 22.5°C WB 21°C DB, 15.5°C WB
27°C DB 20°C DB
3
.UK
Heating
4,650
15,900
1.48
0.07
0.32
0.40
1.41
6.60
Outdoor 46°C DB
-5°C DB
21°C DB, 15.5°C WB
-8.5°C DB, -9.5°C WB
4
Page 5
Item Function
Capacity Total input
Service Ref.
Power supply(phase,cycle,voltage)
Input Running current
Starting current External finish Heat exchanger Fan Fan(drive) No.
Fan motor output
Airflow(Low-High)
External static pressure Booster heater
INDOOR UNITOUTDOOR UNIT
Operation control & Thermostat Noise level (Low-High) Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Input
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Heat exchanger Fan Fan(drive)No.
Fan motor output
Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge
Oil<Model> Pipe size O.D.
Connection method
Between the indoor & outdoor unit
REFRIGERANT PIPING
Note1. Rating Conditions (JIS B 8616)
Cooling : Indoor : 27°C (80°F) DB, 19°C (66°F) WB
Outdoor : 35°C (95°F) DB, 24°C (75°F) WB
Heating : Indoor : 20°C (68°F) DB
Outdoor : 7°C (45°F) DB, 6°C (43°F) WB
Liquid mm(in.) Gas mm(in.) Indoor side Outdoor side Height difference Piping length
W
D H
W
D H
Service Ref.
W
Btu/h
kW
kW
A A
kW
3
/min <CFM>
m
Pa(mmAq)
kW
dB(A) mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
kW
A A
kW
kW
3
/min <CFM>
m
dB(A) mm(in.) mm(in.) mm(in.)
kg(lbs)
kg(lbs)
L
2. Guaranteed operating range
Cooling
Heating
PKH-2FKA-E
Cooling
5,500
18,800
2.27
PKH-2FKA-E
Single, 50Hz, 220-240V
0.07
0.32
0.40 Munsell 3.4Y 7.7/0.8(White)
Plate fin coil
Line flow(direct) ✕ 1
0.030
10-13(353-459)
0(direct blow)
Remote controller & built-in
36-43
20(13/16)
1,250(49-3/16)
200(7-7/8)
300(11-13/16)
17(37)
PUH-2VKA
2
Single, 50Hz, 220-240V
2.20
9.86
45
Munsell 5Y 7/1
Capillary tube
Hermetic
NH38VMDT
1.7
Line start
Internal thermostat, HP switch
Plate fin coil
Propeller (direct) ✕ 1
0.065
45(1,590)
Reverse cycle
49
870(34-1/4)
295+24(11-5/8 add 1)
650(25-5/8)
64(141)
R-22
2.2(4.9)
1.2<MS-32>
9.52(3/8)
15.88(5/8) Flared Flared
Max. 40m Max. 40m
Indoor Upper limit Lower limit Upper limit Lower limit
35°C DB, 22.5°C WB 21°C DB, 15.5°C WB
27°C DB 20°C DB
Heating
6,250
21,300
2.29
0.07
0.32
0.40
.UK
2.22
9.95
Outdoor 46°C DB
-5°C DB
21°C DB, 15.5°C WB
-8.5°C DB, -9.5°C WB
5
Page 6
Item
Function Capacity
Total input
Service Ref.
Power supply(phase,cycle,voltage)
Input Running current
Starting current External finish Heat exchanger Fan Fan(drive) No.
Fan motor output
Airflow(Low-High)
External static pressure Booster heater
INDOOR UNITOUTDOOR UNIT
Operation control & Thermostat Noise level(Low-High) Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Input
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Heat exchanger Fan Fan(drive)No.
Fan motor output
Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge
Oil<Model> Pipe size O.D.
Connection method
Between the indoor & outdoor unit
REFRIGERANT PIPING
Note1. Rating Conditions (JIS B 8616)
Cooling : Indoor : 27°C (80°F) DB, 19°C (66°F) WB
Heating : Indoor : 20°C (68°F) DB
Outdoor : 35°C (95°F) DB, 24°C (75°F) WB
Outdoor : 7°C (45°F) DB, 6°C (43°F) WB
Liquid mm(in.) Gas mm(in.) Indoor side Outdoor side Height difference Piping length
W
D H
W
D H
Service Ref.
W
Btu/h
kW
kW
A A
kW
3
/min <CFM>
m
Pa(mmAq)
kW
dB(A) mm(in.) mm(in.) mm(in.) mm(in.) kg(lbs)
kW
A A
kW
kW
3
/min <CFM>
m
dB(A)
mm(in.) mm(in.) mm(in.) kg(lbs)
kg(lbs)
L
2. Guaranteed operating range
Cooling
Heating
PKH-2.5FKA-E
Cooling
6,500
22,200
2.56
PKH-2.5FKA-E
Single, 50Hz, 220-240V
0.095
0.44
0.80 Munsell 3.4Y 7.7/0.8(White)
Plate fin coil
Line flow(direct) ✕ 2
0.040
15-20(530-706)
0(direct blow)
Remote controller & built-in
39-45
20(13/16)
1,400(55-1/8)
235(9-1/4)
340(13-3/8)
24(53)
PUH-2.5VKA
Single, 50Hz, 220-240V
2.46
10.68 52
Munsell 5Y 7/1
Capillary tube
Hermetic
NH41VMDT
2.0
Line start
Internal thermostat, HP switch
Plate fin coil
Propeller (direct) ✕ 1
0.085
50(1,764)
Reverse cycle
52
870(34-1/4)
295+24(11-5/8 add 1)
850(33-7/16)
64(150)
R-22
2.8(6.2)
1.2<MS-32>
9.52(3/8)
15.88(5/8) Flared Flared
Max. 50m Max. 50m
Indoor Upper limit Lower limit Upper limit Lower limit
35°C DB, 22.5°C WB 21°C DB, 15.5°C WB
27°C DB 20°C DB
2
.UK
Heating
7,200
24,600
2.33
0.095
0.44
0.80
2.23
9.78
Outdoor
46°C DB
-5°C DB
21°C DB, 15.5°C WB
-8.5°C DB, -9.5°C WB
6
Page 7
Item
Function Capacity Total input
Service Ref.
Power supply(phase,cycle,voltage)
Input Running current
Starting current External finish Heat exchanger Fan Fan(drive) No.
Fan motor output
Airflow(Low-High)
External static pressure Booster heater
INDOOR UNITOUTDOOR UNIT
Operation control & Thermostat Noise level(Low-High) Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Input
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Heat exchanger Fan Fan(drive)No.
Fan motor output
Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge
Oil<Model> Pipe size O.D.
Connection method
Between the indoor & outdoor unit
REFRIGERANT PIPING
Note1. Rating Conditions (JIS B 8616)
Cooling : Indoor : 27°C (80°F) DB, 19°C (66°F) WB
Outdoor : 35°C (95°F) DB, 24°C (75°F) WB
Heating : Indoor : 20°C (68°F) DB
Outdoor : 7°C (45°F) DB, 6°C (43°F) WB
Liquid mm(in.) Gas mm(in.) Indoor side Outdoor side Height difference Piping length
W D H
W D H
Service Ref.
W
Btu/h
kW
kW
A A
kW
3
/min <CFM>
m
Pa(mmAq)
kW
dB(A) mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
kW
A A
kW
kW
3
/min <CFM>
m
dB(A) mm(in.) mm(in.) mm(in.)
kg(lbs)
kg(lbs)
L
2. Guaranteed operating range
PKH-3FKA-E
Cooling
7,900
27,000
3.25
Heating
9,100
31,000
3.04
PKH-3FKA-E
Single, 50Hz, 220-240V
0.095
0.44
0.80
0.095
0.44
0.80
Munsell 3.4Y 7.7/0.8(White)
Plate fin coil
Line flow(direct) ✕ 2
0.040
15-20(530-706)
0(direct blow)
Remote controller & built-in
39-45
20(13/16)
1,400(55-1/8)
235(9-1/4)
340(13-3/8)
24(53)
2
PUH-3VKA
.UK / PUH-3YKA2.UK
Single, 50Hz, 220-240V/3, 50Hz, 380-415V(4wires)
3.15/3.15
13.82/5.16
2.94/2.94
12.89/4.81
58/37
Munsell 5Y 7/1
Capillary tube
Hermetic
NH52VNDT/NH52YDAT
2.2/2.4
Line start
Internal thermostat, HP switch/Thermal relay, thermal switch
Plate fin coil
Propeller (direct) ✕ 1
0.085
50(1,764)
Reverse cycle
52
870(34-1/4)
295+24(11-5/8 add 1)
850(33-7/16)
75(165)
R-22
3.2(7.1)
1.6<MS-32>
9.52(3/8)
15.88(5/8) Flared Flared
Max. 50m Max. 50m
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
Indoor 35°C DB, 22.5°C WB 21°C DB, 15.5°C WB
27°C DB 20°C DB
Outdoor
46°C DB
-5°C DB
21°C DB, 15.5°C WB
-8.5°C DB, -9.5°C WB
7
Page 8
Item Function
Capacity Total input
Service Ref.
Power supply(phase,cycle,voltage)
Input Running current
Starting current External finish Heat exchanger Fan Fan(drive) No.
Fan motor output
Airflow(Low-High)
External static pressure Booster heater
INDOOR UNITOUTDOOR UNIT
Operation control & Thermostat Noise level(Low-High) Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Input
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Heat exchanger Fan Fan(drive)No.
Fan motor output
Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge
Oil<Model> Pipe size O.D.
Connection method
Between the indoor & outdoor unit
REFRIGERANT PIPING
Note1. Rating Conditions (JIS B 8616)
Cooling : Indoor : 27°C (80°F) DB, 19°C (66°F) WB
Heating : Indoor : 20°C (68°F) DB
Outdoor : 35°C (95°F) DB, 24°C (75°F) WB
Outdoor : 7°C (45°F) DB, 6°C (43°F) WB
Liquid mm(in.) Gas mm(in.) Indoor side Outdoor side Height difference Piping length
W
D H
W
D H
Service Ref.
W
Btu/h
kW
kW
A A
kW
3
/min <CFM>
m
Pa(mmAq)
kW
dB(A) mm(in.) mm(in.) mm(in.) mm(in.) kg(lbs)
kW
A A
kW
kW
3
/min <CFM>
m
dB(A) mm(in.) mm(in.) mm(in.) kg(lbs)
kg(lbs)
L
2. Guaranteed operating range
PKH-4FKSA-E
Cooling
9,500
32,400
3.31
Heating
10,700 36,500
3.30
PKH-4FKSA-E
Single, 50Hz, 220-240V
0.114
0.53
0.90
0.114
0.53
0.90
Munsell 3.4Y 7.7/0.8(White)
Plate fin coil
Line flow(direct) ✕ 2
0.070
22-28(777-989)
0(direct blow)
Remote controller & built-in
41-46
20(13/16)
1,680(66-1/8)
235(9-1/4)
340(13-3/8)
28(62)
2
PUH-4YKSA
.UK
3, 50Hz, 380-415V(4wires)
3.20
5.24
3.19
5.22
40
Munsell 5Y 7/1
Capillary tube
Hermetic
NH56YDAT
2.7
Line start
Thermal relay, thermal swich, HP switch, anti-phase protector
Plate fin coil
Propeller (direct) ✕ 2
0.065+0.065 95(3,350)
Reverse cycle
54
870(34-1/4)
295+24(11-5/8 add 1)
1,258(49-1/2)
94(207)
R-22
4.2(9.2)
1.6<MS-32>
9.52(3/8)
19.05(3/4) Flared Flared
Max. 50m Max. 50m
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
Indoor 35°C DB, 22.5°C WB 21°C DB, 15.5°C WB
27°C DB 20°C DB
Outdoor 46°C DB
-5°C DB
21°C DB, 15.5°C WB
-8.5°C DB, -9.5°C WB
8
Page 9
9
3
DATA
1. PERFORMANCE DATA
1) COOLING CAPACITY<1> PKH-1.6FKA-E
Outdoor intake air °C DB
20 25 30
Indoor
Intake air
°C DB
Indoor
Intake air
°C WB
20
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
20
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
CA
4540
4834
5131
4540
4834
5131
4540
4834
5131
5431
4540
4834
5131
5431
4540
4834
5131
5431
4540
4834
5131
5431
4540
4834
5131
5431
4540
4834
5131
5431
SHC(W)
3042
2659
2206
3405
3045
2617
3768
3432
3027
2553
4131
3819
3438
2987
4313
4012
3643
3204
4494
4205
3848
3422
4540
4592
4259
3856
4540
4834
4669
4290
SHF
0.67
0.55
0.43
0.75
0.63
0.51
0.83
0.71
0.59
0.47
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
0.99
0.87
0.75
0.63
1.00
0.95
0.83
0.71
1.00
1.00
0.91
0.79
P.C.
1.21
1.23
1.26
1.21
1.23
1.26
1.21
1.23
1.26
1.28
1.21
1.23
1.26
1.28
1.21
1.23
1.26
1.28
1.21
1.23
1.26
1.28
1.21
1.23
1.26
1.28
1.21
1.23
1.26
1.28
CA
4415
4706
5010
4415
4706
5010
4415
4706
5010
5327
4415
4706
5010
5327
4415
4706
5010
5327
4415
4706
5010
5327
4415
4706
5010
5327
4415
4706
5010
5327
SHC(W)
2958
2589
2154
3312
2965
2555
3665
3342
2956
2504
4018
3718
3357
2930
4195
3906
3557
3143
4371
4095
3758
3356
4415
4471
4158
3782
4415
4706
4559
4208
SHF
0.67
0.55
0.43
0.75
0.63
0.51
0.83
0.71
0.59
0.47
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
0.99
0.87
0.75
0.63
1.00
0.95
0.83
0.71
1.00
1.00
0.91
0.79
P.C.
1.26
1.29
1.31
1.26
1.29
1.31
1.26
1.29
1.31
1.34
1.26
1.29
1.31
1.34
1.26
1.29
1.31
1.34
1.26
1.29
1.31
1.34
1.26
1.29
1.31
1.34
1.26
1.29
1.31
1.34
CA
4253
4535
4831
4253
4535
4831
4253
4535
4831
5142
4253
4535
4831
5142
4253
4535
4831
5142
4253
4535
4831
5142
4253
4535
4831
5142
4253
4535
4831
5142
SHC(W)
2850
2494
2077
3190
2857
2464
3530
3220
2851
2417
3870
3583
3237
2828
4041
3764
3430
3034
4211
3945
3624
3240
4253
4308
4010
3651
4253
4535
4397
4062
SHF
0.67
0.55
0.43
0.75
0.63
0.51
0.83
0.71
0.59
0.47
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
0.99
0.87
0.75
0.63
1.00
0.95
0.83
0.71
1.00
1.00
0.91
0.79
P.C.
1.36
1.39
1.42
1.36
1.39
1.42
1.36
1.39
1.42
1.45
1.36
1.39
1.42
1.45
1.36
1.39
1.42
1.45
1.36
1.39
1.42
1.45
1.36
1.39
1.42
1.45
1.36
1.39
1.42
1.45
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
Page 10
10
Outdoor intake air °C DB
35 40 45
Indoor
Intake air
°C DB
Indoor
Intake air
°C WB
20
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
20
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
CA
4081
4355
4645
4081
4355
4645
4081
4355
4645
4950
4081
4355
4645
4950
4081
4355
4645
4950
4081
4355
4645
4950
4081
4355
4645
4950
4081
4355
4645
4950
SHC(W)
2734
2395
1997
3061
2744
2369
3387
3092
2740
2327
3714
3441
3112
2723
3877
3615
3298
3921
4040
3789
3484
3119
4081
4137
3855
3515
4081
4355
4227
3911
SHF
0.67
0.55
0.43
0.75
0.63
0.51
0.83
0.71
0.59
0.47
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
0.99
0.87
0.75
0.63
1.00
0.95
0.83
0.71
1.00
1.00
0.91
0.79
P.C.
1.46
1.49
1.53
1.46
1.49
1.53
1.46
1.49
1.53
1.56
1.46
1.49
1.53
1.56
1.46
1.49
1.53
1.56
1.46
1.49
1.53
1.56
1.46
1.49
1.53
1.56
1.46
1.49
1.53
1.56
CA
3899
4167
4451
3899
4167
4451
3899
4167
4451
4750
3899
4167
4451
4750
3899
4167
4451
4750
3899
4167
4451
4750
3899
4167
4451
4750
3899
4167
4451
4750
SHC(W)
2612
2292
1914
2924
2625
2270
3236
2958
2626
2233
3548
3292
2982
2613
3704
3458
3160
2803
3860
3625
3338
2993
3899
3958
3694
3373
3899
4167
4050
3753
SHF
0.67
0.55
0.43
0.75
0.63
0.51
0.83
0.71
0.59
0.47
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
0.99
0.87
0.75
0.63
1.00
0.95
0.83
0.71
1.00
1.00
0.91
0.79
P.C.
1.55
1.59
1.64
1.55
1.59
1.64
1.55
1.59
1.64
1.68
1.55
1.59
1.64
1.68
1.55
1.59
1.64
1.68
1.55
1.59
1.64
1.68
1.55
1.59
1.64
1.68
1.55
1.59
1.64
1.68
CA
3706
3970
4249
3706
3970
4249
3706
3970
4249
4543
3706
3970
4249
4543
3706
3970
4249
4543
3706
3970
4249
4543
3706
3970
4249
4543
3706
3970
4249
4543
SHC(W)
2483
2183
1827
2780
2501
2167
3076
2819
2507
2135
3373
3136
2847
2499
3521
3295
3017
2680
3669
3454
3187
2862
3706
3771
3527
3225
3706
3970
3866
3589
SHF
0.67
0.55
0.43
0.75
0.63
0.51
0.83
0.71
0.59
0.47
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
0.99
0.87
0.75
0.63
1.00
0.95
0.83
0.71
1.00
1.00
0.91
0.79
P.C.
1.65
1.70
1.75
1.65
1.70
1.75
1.65
1.70
1.75
1.81
1.65
1.70
1.75
1.81
1.65
1.70
1.75
1.81
1.65
1.70
1.75
1.81
1.65
1.70
1.75
1.81
1.65
1.70
1.75
1.81
COOLING CAPACITY<2> PKH-1.6FKA-E
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
Page 11
11
Outdoor intake air °C DB
20 25 30
Indoor
Intake air
°C DB
Indoor
Intake air
°C WB
20
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
20
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
CA
5549
5908
6271
5549
5908
6271
5549
5908
6271
6638
5549
5908
6271
6638
5549
5908
6271
6638
5549
5908
6271
6638
5549
5908
6271
6638
5549
5908
6271
6638
SHC(W)
3385
2895
2320
3829
3367
2822
4272
3840
3324
2722
4716
4313
3825
3253
4938
4549
4076
3518
5160
4785
4327
3784
5549
5258
4829
4315
5549
5731
5330
4846
SHF
0.61
0.49
0.37
0.69
0.57
0.45
0.77
0.65
0.53
0.41
0.85
0.73
0.61
0.49
0.89
0.77
0.65
0.53
0.93
0.81
0.69
0.57
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
P.C.
1.82
1.86
1.89
1.82
1.86
1.89
1.82
1.86
1.89
1.93
1.82
1.86
1.89
1.93
1.82
1.86
1.89
1.93
1.82
1.86
1.89
1.93
1.82
1.86
1.89
1.93
1.82
1.86
1.89
1.93
CA
5397
5752
6124
5397
5752
6124
5397
5752
6124
6511
5397
5752
6124
6511
5397
5752
6124
6511
5397
5752
6124
6511
5397
5752
6124
6511
5397
5752
6124
6511
SHC(W)
3292
2819
2266
3724
3279
2756
4155
3739
3245
2669
4587
4199
3735
3190
4803
4429
3980
3451
5019
4659
4225
3711
5397
5119
4715
4232
5397
5580
5205
4753
SHF
0.61
0.49
0.37
0.69
0.57
0.45
0.77
0.65
0.53
0.41
0.85
0.73
0.61
0.49
0.89
0.77
0.65
0.53
0.93
0.81
0.69
0.57
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
P.C.
1.90
1.94
1.97
1.90
1.94
1.97
1.90
1.94
1.97
2.01
1.90
1.94
1.97
2.01
1.90
1.94
1.97
2.01
1.90
1.94
1.97
2.01
1.90
1.94
1.97
2.01
1.90
1.94
1.97
2.01
CA
5198
5543
5905
5198
5543
5905
5198
5543
5905
6285
5198
5543
5905
6285
5198
5543
5905
6285
5198
5543
5905
6285
5198
5543
5905
6285
5198
5543
5905
6285
SHC(W)
3171
2716
2185
3587
3159
2657
4003
3603
3130
2577
4419
4046
3602
3080
4627
4268
3838
3331
4835
4490
4074
3583
5198
4933
4547
4085
5198
5376
5019
4588
SHF
0.61
0.49
0.37
0.69
0.57
0.45
0.77
0.65
0.53
0.41
0.85
0.73
0.61
0.49
0.89
0.77
0.65
0.53
0.93
0.81
0.69
0.57
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
P.C.
2.04
2.09
2.13
2.04
2.09
2.13
2.04
2.09
2.13
2.18
2.04
2.09
2.13
2.18
2.04
2.09
2.13
2.18
2.04
2.09
2.13
2.18
2.04
2.09
2.13
2.18
2.04
2.09
2.13
2.18
COOLING CAPACITY<3> PKH-2FKA-E
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
Page 12
12
Outdoor intake air °C DB
35 40 45
Indoor
Intake air
°C DB
Indoor
Intake air
°C WB
20
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
20
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
CA
4988
5323
5677
4988
5323
5677
4988
5323
5677
6050
4988
5323
5677
6050
4988
5323
5677
6050
4988
5323
5677
6050
4988
5323
5677
6050
4988
5323
5677
6050
SHC(W)
3043
2608
2101
3442
3034
2555
3841
3460
3009
2481
4240
3886
3463
2965
4439
4099
3690
3207
4639
4312
3917
3449
4988
4737
4371
3933
4988
5163
4826
4417
SHF
0.61
0.49
0.37
0.69
0.57
0.45
0.77
0.65
0.53
0.41
0.85
0.73
0.61
0.49
0.89
0.77
0.65
0.53
0.93
0.81
0.69
0.57
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
P.C.
2.19
2.24
2.30
2.19
2.24
2.30
2.19
2.24
2.30
2.35
2.19
2.24
2.30
2.35
2.19
2.24
2.30
2.35
2.19
2.24
2.30
2.35
2.19
2.24
2.30
2.35
2.19
2.24
2.30
2.35
CA
4765
5093
5440
4765
5093
5440
4765
5093
5440
5806
4765
5093
5440
5806
4765
5093
5440
5806
4765
5093
5440
5806
4765
5093
5440
5806
4765
5093
5440
5806
SHC(W)
2907
2495
2013
3288
2903
2448
3669
3310
2883
2380
4050
3718
3318
2845
4241
3921
3536
3077
4431
4125
3753
3309
4765
4533
4189
3774
4765
4940
4624
4238
SHF
0.61
0.49
0.37
0.69
0.57
0.45
0.77
0.65
0.53
0.41
0.85
0.73
0.61
0.49
0.89
0.77
0.65
0.53
0.93
0.81
0.69
0.57
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
P.C.
2.34
2.40
2.46
2.34
2.40
2.46
2.34
2.40
2.46
2.53
2.34
2.40
2.46
2.53
2.34
2.40
2.46
2.53
2.34
2.40
2.46
2.53
2.34
2.40
2.46
2.53
2.34
2.40
2.46
2.53
CA
4530
4852
5193
4530
4852
5193
4530
4852
5193
5552
4530
4852
5193
5552
4530
4852
5193
5552
4530
4852
5193
5552
4530
4852
5193
5552
4530
4852
5193
5552
SHC(W)
2763
2378
1921
3125
2766
2337
3488
3154
2752
2276
3850
3542
3168
2721
4031
3736
3376
2943
4213
3930
3583
3165
4560
4318
3999
3609
4530
4707
4414
4053
SHF
0.61
0.49
0.37
0.69
0.57
0.45
0.77
0.65
0.53
0.41
0.85
0.73
0.61
0.49
0.89
0.77
0.65
0.53
0.93
0.81
0.69
0.57
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
P.C.
2.49
2.55
2.63
2.49
2.55
2.63
2.49
2.55
2.63
2.71
2.49
2.55
2.63
2.71
2.49
2.55
2.63
2.71
2.49
2.55
2.63
2.71
2.49
2.55
2.63
2.71
2.49
2.55
2.63
2.71
COOLING CAPACITY<4> PKH-2FKA-E
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
Page 13
13
Outdoor intake air °C DB
20 25 30
Indoor
Intake air
°C DB
Indoor
Intake air
°C WB
20
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
20
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
CA
6557
6982
7411
6557
6982
7411
6557
6982
7411
7845
6557
6982
7411
7845
6557
6982
7411
7845
6557
6982
7411
7845
6557
6982
7411
7845
6557
6982
7411
7845
SHC(W)
4787
4259
3631
5312
4818
4224
5836
5376
4817
4158
6361
5936
5412
4785
6557
6214
5707
5099
6557
6493
6003
5413
6557
6982
6596
6040
6557
6982
7189
6668
SHF
0.73
0.61
0.49
0.81
0.69
0.57
0.89
0.77
0.65
0.53
0.97
0.85
0.73
0.61
1.00
0.89
0.77
0.65
1.00
0.93
0.81
0.69
1.00
1.00
0.89
0.77
1.00
1.00
0.97
0.85
P.C.
2.05
2.09
2.13
2.05
2.09
2.13
2.05
2.09
2.13
2.17
2.05
2.09
2.13
2.17
2.05
2.09
2.13
2.17
2.05
20.9
2.13
2.17
2.05
20.9
2.13
2.17
2.05
20.9
2.13
2.17
CA
6378
6798
7237
6378
6798
7237
6378
6798
7237
7694
6378
6798
7237
7694
6378
6798
7237
7694
6378
6798
7237
7694
6378
6798
7237
7694
6378
6798
7237
7694
SHC(W)
4656
4147
3546
5166
4691
4125
5676
5235
4704
4078
6187
5778
5283
4694
6378
6050
5572
5001
6378
6322
5862
5309
6378
6798
6441
5925
6378
6798
7020
6540
SHF
0.73
0.61
0.49
0.81
0.69
0.57
0.89
0.77
0.65
0.53
0.97
0.85
0.73
0.61
1.00
0.89
0.77
0.65
1.00
0.93
0.81
0.69
1.00
1.00
0.89
0.77
1.00
1.00
0.97
0.85
P.C.
2.14
2.18
2.23
2.14
2.18
2.23
2.14
2.18
2.23
2.27
2.14
2.18
2.23
2.27
2.14
2.18
2.23
2.27
2.14
2.18
2.23
2.27
2.14
2.18
2.23
2.27
2.14
2.18
2.23
2.27
CA
6144
6551
6979
6144
6551
6979
6144
6551
6979
7428
6144
6551
6979
7428
6144
6551
6979
7428
6144
6551
6979
7428
6144
6551
6979
7428
6144
6551
6979
7428
SHC(W)
4485
3996
3420
4976
4520
3978
5468
5044
4536
3937
5959
5568
5094
4531
6144
5830
5374
4828
6144
6092
5653
5125
6144
6551
6211
5719
6144
6551
6769
6314
SHF
0.73
0.61
0.49
0.81
0.69
0.57
0.89
0.77
0.65
0.53
0.97
0.85
0.73
0.61
1.00
0.89
0.77
0.65
1.00
0.93
0.81
0.69
1.00
1.00
0.89
0.77
1.00
1.00
0.97
0.85
P.C.
2.30
2.36
2.41
2.30
2.36
2.41
2.30
2.36
2.41
2.46
2.30
2.36
2.41
2.46
2.30
2.36
2.41
2.46
2.30
2.36
2.41
2.46
2.30
2.36
2.41
2.46
2.30
2.36
2.41
2.46
COOLING CAPACITY<5> PKH-2.5FKA-E
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
Page 14
14
Outdoor intake air °C DB
35 40 45
Indoor
Intake air
°C DB
Indoor
Intake air
°C WB
20
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
20
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
CA
5895
6291
6709
5895
6291
6709
5895
6291
6709
7150
5895
6291
6709
7150
5895
6291
6709
7150
5895
6291
6709
7150
5895
6291
6709
7150
5895
6291
6709
7150
SHC(W)
4303
3837
3288
4775
4341
3824
5246
4844
4361
3790
5718
5347
4898
4362
5895
5599
5166
4648
5895
5850
5435
4934
5895
6291
5971
5506
5895
6291
6508
6078
SHF
0.73
0.61
0.49
0.81
0.69
0.57
0.89
0.77
0.65
0.53
0.97
0.85
0.73
0.61
1.00
0.89
0.77
0.65
1.00
0.93
0.81
0.69
1.00
1.00
0.89
0.77
1.00
1.00
0.97
0.85
P.C.
2.47
2.53
2.59
2.47
2.53
2.59
2.47
2.53
2.59
2.65
2.47
2.53
2.59
2.65
2.47
2.53
2.59
2.65
2.47
2.53
2.59
2.65
2.47
2.53
2.59
2.65
2.47
2.53
2.59
2.65
CA
5631
6019
6429
5631
6019
6429
5631
6019
6429
6862
5631
6019
6429
6862
5631
6019
6429
6862
5631
6019
6429
6862
5631
6019
6429
6862
5631
6019
6429
6862
SHC(W)
4111
3671
3150
4561
4153
3664
5012
4634
4179
3637
5462
5116
4693
4186
5631
5357
4950
4460
5631
5597
5207
4735
5631
6019
5722
5283
5631
6019
6236
5832
SHF
0.73
0.61
0.49
0.81
0.69
0.57
0.89
0.77
0.65
0.53
0.97
0.85
0.73
0.61
1.00
0.89
0.77
0.65
1.00
0.93
0.81
0.69
1.00
1.00
0.89
0.77
1.00
1.00
0.97
0.85
P.C.
2.64
2.70
2.78
2.64
2.70
2.78
2.64
2.70
2.78
2.85
2.64
2.70
2.78
2.85
2.64
2.70
2.78
2.85
2.64
2.70
2.78
2.85
2.64
2.70
2.78
2.85
2.64
2.70
2.78
2.85
CA
5353
5734
6137
5353
5734
6137
5353
5734
6137
6562
5353
5734
6137
6562
5353
5734
6137
6562
5353
5734
6137
6562
5353
5734
6137
6562
5353
5734
6137
6562
SHC(W)
3908
3498
3007
4336
3957
3498
4764
4415
3989
3478
5193
4874
4480
4003
5353
5104
4726
4265
5353
5333
4971
4528
5353
5734
5462
5053
5353
5734
5953
5578
SHF
0.73
0.61
0.49
0.81
0.69
0.57
0.89
0.77
0.65
0.53
0.97
0.85
0.73
0.61
1.00
0.89
0.77
0.65
1.00
0.93
0.81
0.69
1.00
1.00
0.89
0.77
1.00
1.00
0.97
0.85
P.C.
2.80
2.88
2.96
2.80
2.88
2.96
2.80
2.88
2.96
3.06
2.80
2.88
2.96
3.06
2.80
2.88
2.96
3.06
2.80
2.88
2.96
3.06
2.80
2.88
2.96
3.06
2.80
2.88
2.96
3.06
COOLING CAPACITY<6> PKH-2.5FKA-E
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
Page 15
15
Outdoor intake air °C DB
20 25 30
Indoor
Intake air
°C DB
Indoor
Intake air
°C WB
20
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
20
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
CA
7970
8486
9007
7970
8486
9007
7970
8486
9007
9534
7970
8486
9007
9534
7970
8486
9007
9534
7970
8486
9007
9534
7970
8486
9007
9534
7970
8486
9007
9534
SHC(W)
5101
4413
3603
5738
5091
4323
6376
5770
5044
4195
7013
6449
5765
4958
7332
6789
6125
5339
7651
7128
6485
5721
7970
7807
7206
6483
7970
8486
7926
7246
SHF
0.64
0.52
0.40
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
P.C.
2.60
2.66
2.71
2.60
2.66
2.71
2.60
2.66
2.71
2.76
2.60
2.66
2.71
2.76
2.60
2.66
2.71
2.76
2.60
2.66
2.71
2.76
2.60
2.66
2.71
2.76
2.60
2.66
2.71
2.76
CA
7752
8262
8796
7752
8262
8796
7752
8262
8796
9352
7752
8262
8796
9352
7752
8262
8796
9352
7752
8262
8796
9352
7752
8262
8796
9352
7752
8262
8796
9352
SHC(W)
4961
4296
3518
5581
4957
4222
6201
5618
4926
4115
6821
6279
5629
4863
7132
6610
5981
5237
7442
6940
6333
5611
7752
7601
7037
6359
7752
8262
7740
7107
SHF
0.64
0.52
0.40
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
P.C.
2.72
2.77
2.83
2.72
2.77
2.83
2.72
2.77
2.83
2.88
2.72
2.77
2.83
2.88
2.72
2.77
2.83
2.88
2.72
2.77
2.83
2.88
2.72
2.77
2.83
2.88
2.72
2.77
2.83
2.88
CA
7467
7961
8482
7467
7961
8482
7467
7961
8482
9028
7467
7961
8482
9028
7467
7961
8482
9028
7467
7961
8482
9028
7467
7961
8482
9028
7467
7961
8482
9028
SHC(W)
4779
4140
3393
5376
4777
4071
5973
5414
4750
3972
6571
6051
5428
4694
6869
6369
5768
5056
7168
6688
6107
5417
7467
7325
6785
6139
7467
7961
7464
6861
SHF
0.64
0.52
0.40
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
P.C.
2.92
2.99
3.06
2.92
2.99
3.06
2.92
2.99
3.06
3.12
2.92
2.99
3.06
3.12
2.92
2.99
3.06
3.12
2.92
2.99
3.06
3.12
2.92
2.99
3.06
3.12
2.92
2.99
3.06
3.12
COOLING CAPACITY<7> PKH-3FKA-E
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
Page 16
16
Outdoor intake air °C DB
35 40 45
Indoor
Intake air
°C DB
Indoor
Intake air
°C WB
20
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
20
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
CA
7164
7646
8154
7164
7646
8154
7164
7646
8154
8690
7164
7646
8154
8690
7164
7646
8154
8690
7164
7646
8154
8690
7164
7646
8154
8690
7164
7646
8154
8690
SHC(W)
4585
3976
3262
5158
4587
3914
5731
5199
4566
3824
6305
5811
5219
4519
6591
6117
5545
4867
6878
6422
5871
5214
7164
7034
6523
5909
7164
7646
7176
6605
SHF
0.64
0.52
0.40
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
P.C.
3.13
3.21
3.29
3.13
3.21
3.29
3.13
3.21
3.29
3.37
3.13
3.21
3.29
3.37
3.13
3.21
3.29
3.37
3.13
3.21
3.29
3.37
3.13
3.21
3.29
3.37
3.13
3.21
3.29
3.37
CA
6844
7315
7813
6844
7315
7813
6844
7315
7813
8339
6844
7315
7813
8339
6844
7315
7813
8339
6844
7315
7813
8339
6844
7315
7813
8339
6844
7315
7813
8339
SHC(W)
4380
3804
3125
4928
4389
3750
5475
4974
4376
3669
6023
5559
5001
4337
6297
5852
5313
4670
6570
6145
5626
5004
6844
6730
6251
5671
6844
7315
6876
6338
SHF
0.64
0.52
0.40
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
P.C.
3.35
3.43
3.52
3.35
3.43
3.52
3.35
3.43
3.52
3.62
3.35
3.43
3.52
3.62
3.35
3.43
3.52
3.62
3.35
3.43
3.52
3.62
3.35
3.43
3.52
3.62
3.35
3.43
3.52
3.62
CA
6506
6970
7459
6506
6970
7459
6506
6970
7459
7975
6506
6970
7459
7975
6506
6970
7459
7975
6506
6970
7459
7975
6506
6970
7459
7975
6506
6970
7459
7975
SHC(W)
4164
3624
2984
4685
4182
3580
5205
4739
4177
3509
5726
5297
4774
4147
5986
5576
5072
4466
6246
5854
5371
4785
6506
6412
5967
5423
6506
6970
6564
6061
SHF
0.64
0.52
0.40
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
P.C.
3.56
3.65
3.76
3.56
3.65
3.76
3.56
3.65
3.76
3.89
3.56
3.65
3.76
3.89
3.56
3.65
3.76
3.89
3.56
3.65
3.76
3.89
3.56
3.65
3.76
3.89
3.56
3.65
3.76
3.89
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
COOLING CAPACITY<8> PKH-3FKA-E
Page 17
17
Outdoor intake air °C DB
20 25 30
Indoor
Intake air
°C DB
Indoor
Intake air
°C WB
20
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
20
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
CA
9584
10204
10832
9584
10204
10832
9584
10204
10832
11465
9584
10204
10832
11465
9584
10204
10832
11465
9584
10204
10832
11465
9584
10204
10832
11465
9584
10204
10832
11465
SHC(W)
6709
5919
4983
7476
6735
5849
8242
7551
6716
5733
9009
8368
7582
6650
9392
8776
8015
7109
9584
9184
8449
7567
9584
10000
9315
8484
9584
10204
10182
9402
SHF
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.50
0.94
0.82
0.70
0.58
0.98
0.86
0.74
0.62
1.00
0.90
0.78
0.66
1.00
0.98
0.86
0.74
1.00
1.00
0.94
0.82
P.C.
2.65
2.71
2.76
2.65
2.71
2.76
2.65
2.71
2.76
2.81
2.65
2.71
2.76
2.81
2.65
2.71
2.76
2.81
2.65
2.71
2.76
2.81
2.65
2.71
2.76
2.81
2.65
2.71
2.76
2.81
CA
9322
9936
10577
9322
9936
10577
9322
9936
10577
11246
9322
9936
10577
11246
9322
9936
10577
11246
9322
9936
10577
11246
9322
9936
10577
11246
9322
9936
10577
11246
SHC(W)
6525
5763
4865
7271
6558
5712
8017
7352
6558
5623
8762
8147
7404
6522
9135
8545
7827
6972
9322
8942
8250
7422
9322
9737
9096
8322
9322
9936
9942
9221
SHF
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.50
0.94
0.82
0.70
0.58
0.98
0.86
0.74
0.62
1.00
0.90
0.78
0.66
1.00
0.98
0.86
0.74
1.00
1.00
0.94
0.82
P.C.
2.77
2.82
2.88
2.77
2.82
2.88
2.77
2.82
2.88
2.94
2.77
2.82
2.88
2.94
2.77
2.82
2.88
2.94
2.77
2.82
2.88
2.94
2.77
2.82
2.88
2.94
2.77
2.82
2.88
2.94
CA
8979
9574
10200
8979
9574
10200
8979
9574
10200
10856
8979
9574
10200
10856
8979
9574
10200
10856
8979
9574
10200
10856
8979
9574
10200
10856
8979
9574
10200
10856
SHC(W)
6285
5553
4692
7004
6319
5508
7722
7085
6324
5428
8440
7851
7140
6297
8800
8234
7548
6731
8979
8616
7959
7165
8979
9382
8772
8034
8979
9574
9588
8902
SHF
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.50
0.94
0.82
0.70
0.58
0.98
0.86
0.74
0.62
1.00
0.90
0.78
0.66
1.00
0.98
0.86
0.74
1.00
1.00
0.94
0.82
P.C.
2.98
3.05
3.11
2.98
3.05
3.11
2.98
3.05
3.11
3.18
2.98
3.05
3.11
3.18
2.98
3.05
3.11
3.18
2.98
3.05
3.11
3.18
2.98
3.05
3.11
3.18
2.98
3.05
3.11
3.18
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
COOLING CAPACITY<9> PKH-4FKSA-E
Page 18
18
Outdoor intake air °C DB
35 40 45
Indoor
Intake air
°C DB
Indoor
Intake air
°C WB
20
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
20
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
CA
8615
9194
9806
8615
9194
9806
8615
9194
9806
10450
8615
9194
9806
10450
8615
9194
9806
10450
8615
9194
9806
10450
8615
9194
9806
10450
8615
9194
9806
10450
SHC(W)
6031
5333
4511
6720
6068
5295
7409
6804
6080
5225
8098
7539
6864
6061
8443
7907
7256
6479
8615
8275
7649
6897
8615
9010
8433
7733
8615
9194
9217
8569
SHF
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.50
0.94
0.82
0.70
0.58
0.98
0.86
0.74
0.62
1.00
0.90
0.78
0.66
1.00
0.98
0.86
0.74
1.00
1.00
0.94
0.82
P.C.
3.19
3.27
3.35
3.19
3.27
3.35
3.19
3.27
3.35
3.43
3.19
3.27
3.35
3.43
3.19
3.27
3.35
3.43
3.19
3.27
3.35
3.43
3.19
3.27
3.35
3.43
3.19
3.27
3.35
3.43
CA
8230
8797
9396
8230
8797
9396
8230
8797
9396
10028
8230
8797
9396
10028
8230
8797
9396
10028
8230
8797
9396
10028
8230
8797
9396
10028
8230
8797
9396
10028
SHC(W)
5761
5102
4322
6420
5806
5074
7078
6509
5825
5014
7736
7213
6577
5817
8066
7565
6953
6218
8230
7917
7329
6619
8230
8621
8081
7421
8230
8797
8832
8223
SHF
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.50
0.94
0.82
0.70
0.58
0.98
0.86
0.74
0.62
1.00
0.90
0.78
0.66
1.00
0.98
0.86
0.74
1.00
1.00
0.94
0.82
P.C.
3.41
3.49
3.59
3.41
3.49
3.59
3.41
3.49
3.59
3.69
3.41
3.49
3.59
3.69
3.41
3.49
3.59
3.69
3.41
3.49
3.59
3.69
3.41
3.49
3.59
3.69
3.41
3.49
3.59
3.69
CA
7824
8381
8970
7824
8381
8970
7824
8381
8970
9590
7824
8381
8970
9590
7824
8381
8970
9590
7824
8381
8970
9590
7824
8381
8970
9590
7824
8381
8970
9590
SHC(W)
5477
4861
4126
6103
5532
4844
6729
6202
5561
4795
7355
6872
6279
5562
7668
7208
6638
5946
7824
7543
6997
6330
7824
8213
7714
7097
7824
8381
8432
7864
SHF
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.50
0.94
0.82
0.70
0.58
0.98
0.86
0.74
0.62
1.00
0.90
0.78
0.66
1.00
0.98
0.86
0.74
1.00
1.00
0.94
0.82
P.C.
3.62
3.72
3.83
3.62
3.72
3.83
3.62
3.72
3.83
3.96
3.62
3.72
3.83
3.96
3.62
3.72
3.83
3.96
3.62
3.72
3.83
3.96
3.62
3.72
3.83
3.96
3.62
3.72
3.83
3.96
Notes CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
COOLING CAPACITY<10> PKH-4FKSA-E
Page 19
19
Service Ref.
PKH-1.6FKA-E
Refrigerant piping length(one way)
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
PKH-2FKA-E
PKH-2.5FKA-E
PKH-3FKA-E
PKH-4FKSA-E
1.00
1.00
1.00
1.00
1.00
0.093
0.992
0.989
0.981
0.989
0.984
0.983
0.980
0.968
0.980
0.978
0.978
0.970
0.952
0.970
0.969
0.966
0.960
0.940
0.960
0.961
0.959
0.950
0.925
0.950
0.956
0.950
0.940
0.913
0.940
0.948
0.945
0.930
0.900
0.930
-
-
0.920
0.886
0.920
-
-
0.910
0.874
0.910
Cooling capacity correction factors
15 20 25 15 20 25 15 20 25 15 20 25 15 20 25
CA 3,184 3,049 2,930 4,280 4,098 3,939 4,931 4,721 4,537 6,232 5,967 5,735 7,328 7,016 6,743
P. C .
1.01
1.09
1.15
1.56
1.68
1.79
1.59
1.71
1.82
2.07
2.23
2.37
2.25
2.43
2.58
CA 3,650 3,506 3,364 4,905 4,713 4,521 5,651 5,429 5,209 7,142 6,862 6,583 8,398 8,068 7,741
P. C .
1.12
1.20
1.28
1.73
1.86
1.98
1.76
1.89
2.02
2.29
2.47
2.63
2.49
2.68
2.86
CA 4,160 4,003 3,844 5,591 5,380 5,167 6,441 6,198 5,952 8,141 7,834 7,523 9,572
9,211
8,845
P.C.
1.23
1.32
1.42
1.90
2.05
2.19
1.93
2.09
2.23
2.52
2.72
2.91
2.74
2.95
3.16
CA 4,714 4,538 4,370 6,336 6,100 5,874 7,229 7,027 6,767 9,225 8,881 8,553
10,847 10,443 10,056
P.C.
1.35
1.45
1.56
2.09
2.25
2.41
2.12
2.29
2.45
2.77
2.99
3.20
3.01
3.24
3.47
CA 5,312 5,112 4,942 7,139 6,871 6,643 8,225 7,916 7,653
10,395 10,004
9,672
12,223 11,763 11,373
P. C .
1.48
1.59
1.70
2.28
2.46
2.64
2.32
2.50
2.68
3.03
3.26
3.50
3.29
3.54
3.80
CA 5,952 5,724 5,560 8,000 7,693 7,473 9,216 8,863 8,609
11,648 11,201 10,881 13,696 13,171 12,794
P. C .
1.61
1.73
1.86
2.49
2.68
2.87
2.53
2.73
2.92
3.30
3.56
3.82
3.59
3.86
4.14
-10 -5 0Service Ref.
Indoor intake
air
˚C DB
PKH-1.6FKA-E
PKH-2FKA-E
PKH-2.5FKA-E
PKH-3FKA-E
PKH-4FKSA-E
5
Outdoor intake air ˚C WB
10 15
Service Ref.
PKH-1.6FKA-E
Refrigerant piping length(one way)
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
PKH-2FKA-E
PKH-2.5FKA-E
PKH-3FKA-E
PKH-4FKSA-E
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.998
0.998
0.998
0.998
0.998
0.995
0.995
0.995
0.995
0.995
-
-
0.993
0.993
0.993
-
-
0.990
0.990
0.990
2) HEATING CAPACITY
Note CA : Capacity (W)
P.C. : Power consumption (kW)
Heating capacity correction factors
Page 20
20
Service Ref.
Indoor unit
Outdoor unit
PKH-1.6FKA-E
PUH-1.6VKA3.UK
Cool
4,400
1.43
0.07
0.32
0.40
1.36
6.79 30
Cool
5,400
2.19
0.07
0.32
0.40
2.12
9.83 43
Heat
4,550
1.39
0.07
0.32
0.40
1.32
6.59 30
Heat
6,150
2.21
0.07
0.32
0.40
2.14
9.93 43
Heat
7,100
2.26
0.095
0.44
0.70
2.16
10.02 52
Heat
9,000
3.02
0.095
0.44
0.70
2.92
13.68 54
Heat
9,000
3.02
0.095
0.44
0.70
2.92
4.88 34
Heat
10,500
3.27
0.114
0.53
0.80
3.16
5.28 37
Cool
6,400
2.51
0.095
0.44
0.70
2.41
11.18 52
Cool
7,800
3.23
0.095
0.44
0.70
3.13
14.67 54
Cool
7,800
3.23
0.095
0.44
0.70
3.13
5.23 34
Cool
9,400
3.28
0.114
0.53
0.80
3.17
5.29 37
PKH-2FKA-E
PUH-2VKA2.UK
PKH-2.5FKA-E
PUH-2.5VKA2.UK
PUH-3VKA2.UK
PKH-3FKA-E
PUH-3YKA2.UK
PKH-4FKSA-E
PUH-4YKSA2.UK
Mode Capacity(W) Total Input(kW)
Input(kW) Current(A) Starting current(A) Input(kW) Current(A) Starting current(A)
Indoor
unit
Outdoor
unit
2. ELECTRICAL DATA
Indoor unit · · · · · 220V 50Hz 1phase Outdoor unit · · · 220V 50Hz 1phase / 380V 50Hz 3phase
Cool
4,450
1.47
0.07
0.32
0.40
1.40
6.76 32
Cool
5,450
2.23
0.07
0.32
0.40
2.16
9.78 44
Heat
4,600
1.43
0.07
0.32
0.40
1.36
6.57 32
Heat
6,200
2.25
0.07
0.32
0.40
2.18
9.87 44
Heat
7,150
2.30
0.095
0.44
0.80
2.20
9.86 52
Heat
9,050
3.03
0.095
0.44
0.80
2.93
13.27 56
Heat
9,050
3.03
0.095
0.44
0.80
2.93
4.86 36
Heat
10,600
3.29
0.114
0.53
0.90
3.18
5.22 39
Cool
6,450
2.54
0.095
0.44
0.80
2.44
10.94 52
Cool
7,850
3.24
0.095
0.44
0.80
3.14
14.22 56
Cool
7,850
3.24
0.095
0.44
0.80
3.14
5.21 36
Cool
9,450
3.30
0.114
0.53
0.90
3.19
5.23 39
Service Ref.
Indoor unit
Outdoor unit
PKH-1.6FKA-E
PUH-1.6VKA3.UK
PKH-2FKA-E
PUH-2VKA2.UK
PKH-2.5FKA-E
PUH-2.5VKA2.UK
PUH-3VKA2.UK
PKH-3FKA-E
PUH-3YKA2.UK
PKH-4FKSA-E
PUH-4YKSA2.UK
Mode Capacity(W) Total Input(kW)
Input(kW) Current(A) Starting current(A) Input(kW) Current(A) Starting current(A)
Indoor
unit
Outdoor
unit
Indoor unit · · · · · 230V 50Hz 1phase Outdoor unit· · · · 230V 50Hz 1phase / 400V 50Hz 3phase
Cool
4,500
1.51
0.07
0.32
0.40
1.44
6.74 33
Cool
5,500
2.27
0.07
0.32
0.40
2.20
9.86 45
Heat
4,650
1.48
0.07
0.32
0.40
1.41
6.60 33
Heat
6,250
2.29
0.07
0.32
0.40
2.22
9.95 45
Heat
7,200
2.33
0.095
0.44
0.80
2.23
9.78 52
Heat
9,100
3.04
0.095
0.44
0.80
2.94
12.89 58
Heat
9,100
3.04
0.095
0.44
0.80
2.94
4.81 37
Heat
10,700
3.30
0.114
0.53
0.90
3.19
5.22 40
Cool
6,500
2.56
0.095
0.44
0.80
2.46
10.68 52
Cool
7,900
3.25
0.095
0.44
0.80
3.15
13.82 58
Cool
7,900
3.25
0.095
0.44
0.80
3.15
5.16 37
Cool
9,500
3.31
0.114
0.53
0.90
3.20
5.24 40
Service Ref.
Indoor unit
Outdoor unit
PKH-1.6FKA-E
PUH-1.6VKA3.UK
PKH-2FKA-E
PUH-2VKA2.UK
PKH-2.5FKA-E
PUH-2.5VKA2.UK
PUH-3VKA2.UK
PKH-3FKA-E
PUH-3YKA2.UK
PKH-4FKSA-E
PUH-4YKSA2.UK
Mode Capacity(W) Total Input(kW)
Input(kW) Current(A) Starting current(A) Input(kW) Current(A) Starting current(A)
Indoor
unit
Outdoor
unit
Indoor unit · · · · · 240V 50Hz 1phase Outdoor unit· · · · 240V 50Hz 1phase / 415V 50Hz 3phase
Page 21
21
Service Ref.
PKH-1.6FKA-E
Cooling Heating
Mode
Capacity W
Input
Indoor unit Service Ref.
Phase,Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase,Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discahrge temperature
Condensing temperature
Suction temperature
Ref.pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
kW
4,500
1.51
4,650
1.48
0.32 0.32
6.74 6.60
1.74
(
17.7
)
1.72
(
17.5
)
1.87
(
19.1
)
1.99
(
20.3
)
2.00
(
20.4
)
1.62
(
16.5
)
2.07
(
21.1
)
1.96
(
20.0
)
2.07
(
21.1
)
1.96
(
20.0
)
1.80
(
18.4
)
1.69
(
17.2
)
0.41
(
4.18
)
0.42
(
4.28
)
0.36
(
3.67
)
0.52
(
5.3
)
0.36
(
3.67
)
0.45
(
4.59
)
0.37
(
3.77
)
0.45
(
4.59
)
0.35
(
3.57
)
0.51
(
5.2
)
0.37
(
3.77
)
0.52
(
5.3
)
77 78
47 47
81
55
27 20
19 15
14.6 38.9
35 7
24 6
0.77
-
0.17
-
1,50
1,50
240
240
PUH-1.6VKA3.UK
Cooling Heating
5,500
2.27
6,250
2.29
0.32 0.32
9.86 9.95
86 90
51 53
2-2
55
27 20
19 15
13.0 44.3
35 7
24 6
0.71
-
0.15
-
1,50
1,50
240
240
PUH-2VKA2.UK
Cooling Heating
6,500
2.56
7,200
2.33
0.44 0.44
10.68 9.78
85 74
53 44
7-3
55
27 20
19 15
14.5 37.9
35 7
24 6
0.83
-
0.11
-
1,50
1,50
240
240
PUH-2.5VKA2.UK
Cooling Heating
7,900
3.25
9,100
3.04
0.44 0.44
13.82 12.89
90 86
53 52
6-2
55
27 20
19 15
13.2 43.4
35 7
24 6
0.74
-
0.12
-
1,50
1,50
240
240
PUH-3VKA2.UK
Cooling Heating
7,900
3.25
9,100
3.04
0.44 0.44
5.16 4.81
90 86
53 52
6-2
55
27 20
19 15
13.2 43.4
35 7
24 6
0.74
-
0.12
-
3,50
415
PUH-3YKA2.UK
Cooling Heating
9,500
3.31
10,700
3.30
0.53 0.53
5.24 5.22
79 76
49 46
8-1
55
27 20
19 15
14.3 40.4
35 7
24 6
0.80
-
0.11
-
1,50
3,50
240
415
PUH-4YKSA2.UK
˚C DB
˚C DB
˚C WB
˚C DB
BF
SHF
˚C WB
˚C
˚C
˚C
m
Mpa
(
kg/cm
2
)
Mpa
(
kg/cm
2
)
PKH-2FKA-E
PKH-2.5FKA-E
PKH-3FKA-E
PKH-4FKSA-E
PKH-1.6FKA-E
PKH-2FKA-E
PKH-2.5FKA-E
PKH-3FKA-E
PKH-4FKSA-E
Outdoor
side
Indoor side Refrigetrant circuit Electrical circuit Total
Air flow m3/
min
Air speed m/
sec
Coverage range m
PKH-1.6FKA-E
13
4.0
9.1
PKH-2FKA-E
13
4.0
9.1
PKH-2.5FKA-E
20
4.9
12.4
PKH-3FKA-E
20
4.9
12.4
PKH-4FKSA-E
28
5.4
15.3
3. STANDARD OPERATION DATA
The unit of pressure has been changed to Mpa on the international system of unit (SI unit system). The converted score against the traditional unit system can be gotten according to the formula below.
1(Mpa) = 10.2(kg/F)
4. OUTLET AIR SPEED AND COVERAGE RANGE
The air coverage range is the value up to the position where the air speed is 0.25m/sec. when air is blown out horizontally from the unit at the Hi notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room.
Page 22
22
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROTIMATE TERESHOLD OF REARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
PKH-1.6FKA PKH-2FKA
Hi
Lo
NOTCH
43
36
SPL(db
(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROTIMATE TERESHOLD OF REARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
PKH-2.5FKA PKH-3FKA
Hi
Lo
NOTCH
45
39
SPL(db
(A)) LINE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROTIMATE TERESHOLD OF REARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
PKH-4FKSA
Hi
Lo
NOTCH
46
41
SPL(db
(A)) LINE
UNIT
WALL
1m
1m
MICROPHONE
5. NOISE CRITERION CURVES
Ambient temperature 27:
Test conditions are based on JIS Z8731
Page 23
23
4
OUTLINES AND DIMENSIONS
Unit : mm
1. INDOOR UNIT PKH-1.6FKA-E PKH-2FKA-E
Pipe position
Left side
Lequid pipe
Gas pipe
Service space required
around indoor unit
(100 for left-hand
side piping)
Right side
130 or less
2 tapping screws
for installation plate
(Necessary clearance for
Unit installation)
Drain pipe O.D. 20
Front
50 or more
2-unit hangers
Unit cennter
Liquid pipe position
Gas pipe position
(Width of unit)
Knock out hole for
left-rear piping
Knock out hole for
left-rear piping
Rear piping hole
2 X5 - 2.9 hole
for tapping screw
Details of installation plate
1 Sleeves are available on
the market.
2 This size shows the lower
end of through hole.
Sleeve
90 90~ 100
Through hole
150 or more
Knock out hole for
left-hand side piping
Ref.pipes & drain pipe
215
168
2134
8
20
70
300
47
30 or more
180 or more
80
25
35
60
Left side
Air intake
Front
1250
449 Air intake
Auto vanes
Service panel for
power supply connection
449 Air intake
968 Air intake
48
236
227
Right side
Terminal block
Right side
Knock out hole for right piping
(2:1)
Knock-out hole for
night-hand side piping
Knock out hole
for piping
8
60
Knock out hole for piping
Terminal block for control
Terminal block & pipe position
Drainage
Drainage(Flexible hole: length 1200)
Liquid pipe
Bass pipe
Lower side
Terminal block for
power supply
Knock out hole for under-piping
15 or less
bolt
Installation bolt position
200
B
B
A
A
8
8
60
91
65
20
70
(2:1)
70
Lower side
976
16 -louvers
(manual)
500
479 Air outlet479 Air outlet
26
173
223
222
143
553
635
685
170
190
200
1100
50
1
Knock out hole
for piping
1
2
2
3/8F
5/8F
0355380130
177
227
(178)
(375)
447
190
13- 14
hole
60
1250
330
80
0
53
68- 5
hole
277
Tapping screw
300
491
476
450
405
323
276
229
179
150
70
24
0
70
150
174
224
271
318
374
9
73
405
450
476
486
625
(Height ut unit)
85
45
286X
2
R
52.5
R52.5R
52.5
R
52.5
R52.5R
52.5
Page 24
24
Unit : mm
PKH-2.5FKA-E PKH-3FKA-E
Gas pipe
Terminal block for power supply
Terminal block for remote controller
Top
62.5
13
235
45
235
45
235
45
235
Knock out hole for right piping
Refrigerant pipe. Drain pipe
235
Right side
Front
1400
Air intake
1090
Left side
C
15
Bolt
197
Terminal block for control
Liquid pipe
Drain hose O.D. 20
107
111
58
(Gas pipe)
55
120
(Liquid pipe)
42
183
Drain hose
1110
Liquid pipe 9.52(3/8F)
Gas pipe 15.88(5/8F)
240
Air outlet
552
Lower side
Auto vane
1120
Air outlet
B
Change vane (manual)
Knock out hole for under-piping
Refrigerant pipe. Drain pipe
552
Under panel
Removable at left-hand
side piping
280
60
18430
Rear piping opening
340
2980
25
3030 10
90
245
285
455
990
10 91=(910)
19
91
Drainage range
on right-hand side
900
Drainage range
on left-hand side
18
18
610
Range for left rear piping opening
180
240 280 314
12-ø6 hole for
tapping screw
225
Drain hose for
Knock out hole for
left piping
A
30
left-hand side piping
4
100
39
37
74
65
37
Unit center
32
98
39
Knock out hole for piping
AB C
30
100
74
37
439
Wall fixture
66-ø6 hole for
tapping screw
32-ø12 hole for bolt
Page 25
25
Unit : mm
PKH-4FKSA-E
235
45
235
45
235
45
235
45
235
62.5
13
58 42
340
197
Top
Front
Right side
Left side
1680
1370
Air intake
235
C
Knock out hole for right piping
Knock out hole for left piping
Drain hose for left-hand side piping
Drain hose
Drain hose
Lower side
Auto vane
(Gas pipe)
Bolt
Gas pipe
15
Terminal block for power supply
Terminal block for control
Terminal block for remote controller
(Liquid pipe)
Gas pipe 19.05(3/4F)
Liquid pipe 9.52(3/8F)
Liquid pipe
A
30
65
39
98
37
74
439
100
30
37
74
4
2980
280
3030
18430
60
10
39
37
65
100
AB C
Knock out hole for wiring
25
1110
183
240
B
1400
55
120
102
111
Drain hose O.D. 20
694
Air outlet
694
Air outlet
Change vane (manual)
Under panel
(Removable at left-hand side piping)
Knock out hole for under-piping
Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping openingRange for left rear piping opening
12-ø6 hole for tapping screw
84-ø6 hole for
tapping screw
Wall fixture
Unit out line
Unit center
41-ø12 hole for bolt
295 225
18
18
91
900
1270
595
285
245
19
240 280 314
750
90
Drainage range
on right-hand side
13 91=(1183)
180
Drainage range
on left-hand side
Page 26
26
Unit : mm
18
130
Rear side wiring arrangement opening.
120
FILTER
CHECK MODE
TEST RUN
FILTER
CHECK MODE
TEST RUN
46
83.5
SW18
SW17
REMOTE CONTROLLER PAR-JH241KA
CAUTION
2. REMOTE CONTROLLER
Page 27
5
WIRING DIAGRAM
PKH-1.6FKA-E / PKH-2FKA-E
SYMBOLSYMBOL C CN1 <R.B> CN2 <R.B> CN2L <I.B> CN51 <I.B> FAN2 F1 <I.B> I.B LED1 <I.B> LED2 <I.B> LS MF MV R.B RT1
GRN/YLW
MF
WHT
LS
MV
C
I.B
WHT
BLK
RED
FAN1
1
CN6V
VANE
X4
X4
ZNR
FAN2
135
SW5
SW2
ON OFF
123456 101234
FAN MOTOR CAPACITOR PROGRAM TIMER CONNECTOR REMOTE SWITCH CONNECTOR LOSSNAY CONNECTOR CENTRALLY CONTROL CONNECTOR EMERGENCY OPERATION CONNECTOR FUSE (6.3A 250V) INDOOR CONTROLLER BOARD DC 12V POWER LED DC 5V POWER LED LIMIT SWITCH FAN MOTOR VANE MOTOR REMOTE CONTROLLER BOARD ROOM TEMPERATURE THERMISTOR (0°C/15k,25°C/5.4k DETECT)
SW6
1234
RED
CND
31
POWER
SW7
123
123456789
NAME
RED
ON OFF
SW1
BLU
SW3
WHT
F1
12
240V 230V 220V
RED
YLW
ORN
YLW
CNT
TRANS
LED1 12V POWER
HEATER
CN24
11.1VAC
14.2VAC
T
LED2 5V POWER
REMOCON
POWER
CENTRALLY
CONTROL
CN51
SYMBOL RT2
SW1 <I.B> SW2 <I.B> SW3 <I.B> SW5.6 <I.B> SW7 <I.B> SW17 <R.B> SW18 <R.B> T TB2 TB4
TB5 TB6 4 <I.B> ZNR
RED
43
CN40
INTAKE
RED
35
4213
CN21
PIPE
CN20
LOSSNAY
BRN
211 133
CN2L
L N
GRN/YLW
POWER SUPPLY ~(1 PHASE) AC220-240V 50Hz AC220V 60Hz
TB2
ON
SW7
BRN
CN4T
TRANS
TO
REMOCON
CN22
12
OUTDOOR
3
CN30
2 1
1122
CN23
VANE
21
INDOOR COIL THERMISTOR (0°C/15k ,25°C/5.4k DETECT) MODE SELECTOR ADDRESS SELECTOR EMERGENCY OPERATION SWITCH MODEL SELECTOR MODEL SELECTOR ADDRESS SELECTOR FUNCTION SELECTOR TRANSFORMER TERMINAL BLOCK (POWER SUPPLY) TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING WIRE) TERMINAL BLOCK (REMOTE CONTROLLER) LINE TRANSMISSION TERMINAL BLOCK FAN MOTOR RELAY VARISTOR
BLU
BLU
BRN ORN
YLW
OFF
TRANSMISSION WIRES DC12V
TB5
2 1
TB4
3
TO OUTDOOR UNIT
2
CONNECTING WIRES
1
DC12V
R.B
RT2
RT1
SW18
4321
SW17
87654321
NAME
ON OFF
OFF ON
OFF ON
2FKA1.6FKAMODELS
1 2 31 2 3
TB6
A01 B02 CN1
45231
CN2
321
NOTES :
1. Since the indoor fan motor (MF) is connected with 230, 240V power, using 220V power will require a setting change of the dip switch (SW7<I.B>) on the indoor controller board as shown in fig :
fig w1
Indoor fan motor (MF) for 220V .
2. Since the indoor transformer (T) is connected with 240V power if 220,230V power is used. Change the wiring connection showing fig :
fig w2
When power supply is
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers.
5. Symbols used in wiring diagram above are, : Connector / : Terminal block.
6. Emergency operation If remote controller or microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board.
[Check items] (1)Make sure that no other trouble exist the outdoor unit. Trouble with the outdoor unit prevents emergency operation.
(If any trouble exists the outdoor unit error code “P8”will be displayed on the remote controller and the trouble position will be shown on the outdoor controller board LED. See electric wiring diagram of the outdoor unit for details.)
(2)Make sure that there is no trouble with the indoor fan.
Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with the remote controller is not possible).
[Emergency operation procedure] (1)Switch the fan connector on the indoor controller board from FAN 1 to FAN 2. (2)Set the dip switch (SW3<I.B>) on the indoor controller board to 1 on and 2 off for cooling and 1 - 2 on for heating. (3)Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker. (4)During emergency operation indoor fan runs at high speed but automatic vane remains stop. (5)Thermostat will mot function. Cold air blows out for defrosting during heating thus do mot operate defrosting for along time. (6)Emergency cooling should be limited to 10 hours maximum.
(The indoor unit heat exchanger may freeze).
(7)After every operation, switch the fan connector to FAN1, and set all dip switches (SW3<I.B>) to OFF.
w1.
230V 220V
SW7
ON OFF
240V
230V
220V
23
1
YELLOW ORANGE RED
ON OFF
23
1
w2.
27
Page 28
PKH-2.5FKA-E / PKH-3FKA-E / PKH-4FKSA-E
SYMBOL C CN1 <R.B> CN2 <R.B> CN2L <I.B> CN27 <I.B> CN51 <I.B> F1.2 <I.B> I.B J1 J5 J9 LED1 <I.B> LED2 <I.B> MF MV R.B
MF
C
I.B
ON OFF
WHT
BLK
RED
FAN1
1
X4
X4
J5
SW2
123456
FAN MOTOR CAPACITOR PROGRAM TIMER CONNECTOR REMOTE SWITCH CONNECTOR LOSSNAY CONNECTOR DRAIN LIFT-UP MECHANISM CONNECTOR CENTRALLY CONTROL CONNECTOR FUSE (6.3A 250V) INDOOR CONTROLLER BOARD MODE SELECTOR JUMPER RESISTORS MODE SELECTOR JUMPER RESISTORS MODE SELECTOR JUMPER RESISTORS DC 12V POWER LED DC 5V POWER LED FAN MOTOR VANE MOTOR REMOTE CONTROLLER BOARD
42
POWER
ZNR
D.U.M
CN27
J9
2
RED
CND
F2 F1
SW7 SW3
1234
SW6
1234
BLU
NAME
ON OFF
12
J1
RED
YLW
ORN
WHT
YLW
CNT
TRANS
LED2 5V POWER
LED1 12V POWER
HEATER
87
109654
240V 230V 220V
CONTROL
CN24
T
6
CN6V
VAN E
CENTRALLY
CN51
CN50
DRAIN
10VAC
14.3VAC
1
REMOCON
POWER
CN40
12345
SYMBOL RT1
RT2
SW2 <I.B> SW3 <I.B> SW6 <I.B> SW7 <I.B> SW17 <R.B> SW18 <R.B> T TB2 TB4 TB5 TB6 4 <I.B> ZNR
RED
43
35
4213
CN21
PIPE
CN20
INTAKE
GRN/YLW
BRN
RED
BRN
CN4T
211 133
TRANS TO
REMOCON
CN22
OUTDOOR
CN30
1122
LOSSNAY
L N
POWER SUPPLY ~(1 PHASE) AC220-240V 50Hz AC220V 60Hz
TB2
4FKSA
ON OFF
1234 1234
SW18
OFF ON
4321
SW17
OFF ON
87654321
NAME
TB6
A01 B02
CN1
45231
CN2
321
BLU BLU
BRN ORN YLW
MODELS
TB5
TB4
6
MV
12
3 2 1
RT2
2.5,3FKA
ON
SW7
OFF
TRANSMISSION WIRES DC12V
2 1
3
TO OUTDOOR UNIT
2
CONNECTING WIRES
1
DC12V
R.B
RT1
CN2L
ROOM TEMPERATURE THERMISTOR (0°C/15k ,25°C/5.4k DETECT) INDOOR COIL THERMISTOR (0°C/15k ,25°C/5.4k DETECT) ADDRESS SELECTOR EMERGENCY OPERATION SWITCH MODEL SELECTOR MODEL SELECTOR ADDRESS SELECTOR FUNCTION SELECTOR TRANSFORMER TERMINAL BLOCK (POWER SUPPLY) TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING WIRE) TERMINAL BLOCK (REMOTE CONTROLLER) LINE TRANSMISSION TERMINAL BLOCK FAN MOTOR RELAY VARISTOR
NOTES:
1. Since the indoor fan motor (MF) is connected with 230, 240V power, using 220V power will require a setting change of the dip switch (SW7<I.B>) on the indoor controller board as shown in fig :
fig w1
SW 7
2. Since the indoor transformer (T) is connected with 240V power, if 220,230V power is used. Change the wiring connection showing fig :
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers.
5. Symbols used in wiring diagram above are, : Connector, / : Terminal block.
6. Emergency operation
[Check items] (1) Make sure that no other trouble exist the outdoor unit. Trouble with the outdoor unit prevents emergency operation.
(2)Make sure that there is no trouble with the indoor fan.
[Emergency operation procedure] (1)Set the dip switch (SW3<I.B>) on the indoor controller board to 1 on and 2 off for cooling and 1 - 2 on for heating. (2)Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker. (3)During emergency operation indoor fan runs at high speed but automatic vane remains stop. (4)Thermostat will not function. Cold air blows out for defrosting during heating thus do not operate defrosting for along time. (5)Emergency cooling should be limited to 10 hours maximum.
(6)After every operation, switch the fan connector to FAN1, and set all dip switches (SW3<I.B>) to OFF.
Indoor fan motor (MF) for 220V.
fig w2
When power supply is
If remote controller of microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board.
(If any trouble exists the outdoor unit error code “P8” will be displayed on the remote controller and the trouble position will be shown on the outdoor controller board LED. See electric wiring diagram of the outdoor unit for details.)
Emergency operation will be continuous operation mode due to power ON/OFF(ON/OFF with the remote controller is not possible).
(The indoor unit heat exchanger may freeze).
w 1.
230V
220V
SW7
ON OFF
240V 230V 220V
234
1
YELLOW ORANGE RED
ON OFF
1
234
w 2.
28
Page 29
29
6
REFRIGERANT SYSTEM DIAGRAM
Indoor heat exchanger
Indoor unit
Refrigerant pipe (option)
15.88mm( 5/8") (with heat insulator)
Refrigerant pipe (option)
9.52mm( 3/8") (with heat insulator)
Flexible tube
Flared connection
Ball valve Strainer
Ball valve (with Service port)
Oil separator
4-way valve
Service port
Service port
High pressure control switch
High pressure protect switch
Accumulator
Compressor
Strainer
Restrictor valve
Outdoor heat exchanger
Outdoor coil thermistor (TH)
Indoor coil thermistor (RT2)
PKH-1.6 (O.D.3.2 I.D.1.6 700) PKH-2 (O.D.3.2 I.D.1.6 300)
PKH-2.5 (O.D.3.2 I.D.1.8 430) PKH-3 (O.D.4.0 I.D.2.0 500)
PUH-1.6 (O.D.3.2 I.D.1.8 400) PUH-2 (O.D.4.0 I.D.2.0 430) PUH-2.5 (O.D.4.0 I.D.2.4 1550) PUH-3 (O.D.4.0 I.D.2.4 1070)
Distributor with strainer
Capillary tube
Capillary tube
Restrictor valve
Strainer
Bypass valve
Outdoor unit
PKH-1.6FKA-E / PUH-1.6VKA3.UK PKH-2FKA-E / PUH-2VKA
2.UK
PKH-2.5FKA-E / PUH-2.5VKA
2.UK
PKH-3FKA-E / PUH-3VKA
2.UK, 3YKA2.UK
Unit : mm
PKH-4FKSA-E / PUH-4YKSA2.UK
Indoor heat exchanger
Indoor unit
Refrigerant pipe (option)
19.05mm( 3/4") (with heat insulator)
Refrigerant pipe (option)
9.52mm( 3/8") (with heat insulator)
Flexible tube
Flared connection
Ball valve Strainer
Ball valve (with Service port)
Oil separator
4-way valve
Service port (check)
Service port
High pressure control switch
High pressure protect switch
Accumulator
Compressor
Strainer
Restrictor valve
Outdoor heat exchanger
Outdoor coil thermistor (TH3)
Indoor coil thermistor (RT1)
Distributor with strainer
Capillary tube
Capillary tube
Restrictor valve
Strainer
Bypass valve
Outdoor unit
PKH-4 (O.D.4.0 I.D.2.0 400)
PUH-4 (O.D.3.2 I.D.2.0 820) 2pcs
Refrigerant flow in cooling Refrigerant flow in heating
R.V. coil Heating:ON Cooling:OFF
Page 30
30
7
OPERATION FLOW-CHART
START
Power circuit
breaker
Check SW
ON twice
Operation SW
ON
“OFF” timer
“ON” timer
STOP
Set time
complete
Set time complete
1
NO
NO
NO NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
w1
w2
w3
w4
w5
w7
w6
PROTECTION DEVICE
SELF HOLD RELEASE
Remote controller indicator lamp OFF
Trouble STOP
Remote controller
operation display
Operating mode
(COOL)
Operating mode
(DRY)
Operating mode
(HEAT)
Operating mode
(FAN)
Auto COOL/HEAT
operation
COOL operation
DRY operation
HEAT operation
FAN operation
Trouble
PROTECTION DEVICE
SELF HOLD
Remote controller
trouble display
Indoor side
Outdoor side
Fan STOP
Compressor OFF
Fan STOP
Four-way valve OFF
MAIN OPERATION
w 1 In addition, the centralized and remote control can be operated. w 2 The modes which indicate the sources of trouble are listed below.
EO=Signal transmitting/receiving error
P1=Room temperature thermistor malfunction
P2=Indoor coil thermistor malfunction
P4=Drain sensor malfunction
P5=Drain over flow
P6=Coil frost/overheat protection
P7=System error
P8=Outdoor unit trouble
w 3 The CHECK switch will show if an error has occurred in the past. w 4 Fan runs on low speed for 1 minute in order to remove overheat air. w 5 The 3-minute (6 minutes … heating mode) time-delay functions after compressor stops. w 6 FAN or AUTO mode is selected by the indoor dip switch setting. w 7 In FAN mode, fan speed and vane operation depend on the remote controller setting. (Compressor is OFF.)
Page 31
COOLING OPERATION
COOL operation
Four-way valve/OFF
NO
NO
NO
NO
Vane setting notch
Initial
COOLING
*8
60 deg downward angle 70 deg downward angle
Downward discharge
YES
Vane initial
setting
Vane
YES
Fan speed
LOW
YES
1 hour
Vane horizontal
airflow
*9
NO
Compressor
thermostat
ON
NO
Allowance
cancel
NO
YES
YES
NO
*11
YES
3-minute
time delay
time delay
3-minute
compressor operation
*10
Coil frost
prevention
Cooling area
NO
6-minute
NO
YES
NO
YES
NO
Allowance
period
NO
6 minute
time delay
Allowance set
YES
Coil frost protection
YES
10-minute
NO
compressor operation
Allowance cancel
Coil frost protection
NO
16-minute
NO
compressor operation
YES
Indoor pipe
temperature is
1°C or lower
NO
Compressor ON
1
YES
YES
Compressor OFF
YES
Coil frost
prevention
Indoor coil
tempreature is 10°C or higher
YES
3-minute
time delay
Coil frost
prevention release
NO
NO
1 min continue
FAN speed
LOW
FAN speed LOW 5 min
elapse
YES
NO
Outdoor unit
YES
trouble
w 8 When operation stops or changes to cooling or dry mode, the auto vane turns to a horizontal angle. IF operation changes
during auto vane SWING, the auto vane will continue to swing.
w 9 When operating TEST RUN, the thermostat will be continuously ON. w10 After 3 minute compressor operation, if the indoor coil thermistor reads -15°C or below for 3 minutes, the compressor will
stop for 6 minutes.
w11 Cooling area : Indoor coil temperature is more than 5 degrees above the room temperature.
Heating area : Indoor coil temperature is more than 5 degrees below the room temperature. FAN area : Indoor coil temperature is within 5 degrees either way of the room temperature.
31
Page 32
HEATING OPERATION
Heat operation
*15
Initial
NO
HEATING
Vane setting notch
*9
NO
YES
Vane initial setting
NO
Defrosting
NO
Four-way valve ON
Hor adjust in process
NO
Compressor ON
NO
Compressor
thermostat ON
Allowance cancel
Indoor piping
-15°C or lower
Outdoor unit
FAN SPEED
Very low airflow
Compressor OFF
2
YES
trouble
1
YES
YES
YES
YES
3 min.restart
prevention
YES
6 min. restart
prevention
NO
Hot adjust start
FAN SPEED very low
Compressor ON
10-minute
NO
compressor
operation
Allowance caccel
*11
Heating
area
FAN STOP
*11
Ariflow area
20 min.elaspe
YES
Airflow area Heating area
*11
Airflow area Cooling area
Defrost operation
START
Four-way valve
OFF
YES
NO
YES
*11
YES
YES
*10
NO
Defrost
A
trouble
YES
NO
NO
YES
1
NO
NO
Heating area
30 min. elapse
Outdoor unit trouble
Outdoor unit
Defrost release
2
B
Indoor piping 55°C or lower
NO
Auxiliary heater
ON
YES
NO
Indoor piping
60°C or higher
YES
Auxiliary heater OFF
Overheat remote
START
Indoor unit
70°C or higher
YES
Allowance
period
YES
Overload protect
YES
NO
Auxiliary heater
thermostat ON
Auxiliary heater ON
NO
6-minute restart
prevention
Allowance set
Compressor OFF
YES
YES
FAN SPEED
Indoor piping
35°C or higher
NO
HOT adjust
6 min. elapse
YES
FAN SPEED
Low
FAN SPEED
Low 2 min.
elapse
YES
setting nitch
Hot adjust
release
A
PKH-FK
Type
3-minute
Auxiliary heater
OFF
Indoor coil
thermstor is 60°C
or higher
FAN speed
Low notti
YES
Airflow 10% up
B
NO
NO
NO
NO
NO
NO
FAN setting notch
Auto COOL/HEAT
operation
YES
>
T1 T0
=
YES
YES
After 15min.
T1<(T0-2)
NO
*16
NO
NO
YES
HEAT operation
NO
Initial mode
*17
COOL mode HEAT mode
COOL mode
NO
T1 < (T0 - 2)
COOL operation
NO
T1>(T0 + 2)
YES
NO
YES
Cool mode
set
1
After 15min.
T1>(T0 + 2)
HEAT operation
1
1
w15 (!) Until Low airflow is set while hot adjustment
(@) While defrosting (FAN STOP) (#) When thermostat is OFF In the case of(!), (@) and (#) above, airflow is horizontal regardless the VANE setting.
w16 When AUTO operation is started, COOL or HEAT mode is selected automatically. w17 T1 : Room temperature.
To : Set temperature
32
Page 33
33
w 8 ~ 9 Refer to page 31. w 12 When room temperature is 18°C or below, the compressor cannot operate.
When room temperature rises over 18°C, the compressor starts after a 3-minute time delay.
w 13 Compressor ON time is decided by room temperature. Refer to page 32. w 14 In dry operation, compressor ON makes the fan speed LOW and compressor OFF stops the fan.
It is not possible to set the fan speed with the remote controller
DRY OPERATION
DRY
operation
Four-way valve / OFF
Initial dry
operation
Room temperature is
18°C or lower
During
compressor ON
Compressor & thermostat ON
Vane initial setting
Vane
setting notch
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
3-minute
time delay
10-minute
compressor
OFF
Compressor ON
time set
Compressor ON
Fan speed LOW
1
Compressor &
thermostat
ON
3-minute
compressor
operation
Compressor ON
time completes
NO
YES
NO
NO
YES
W
14
W
14
w
13
YES
YES
NO
YES
NO
NO
w
9
YES
YES
w
9
NO
NO
w
12
YES
NO
YES
w
8
Page 34
34
8
MICROPROCESSOR CONTROL
Compressor and outdoor fan : ON­OFF
Operation mode change :COOL­HEAT.
1. OUTLINE OF MICROPROCESSOR
OFF-ON switching.
COOL/DRY-AUTO-HEAT selector switching.
Thermostat setting.
TIMER mode selector-switching and Timer
setting.
HIGH-LOW fan speed switching.
AUTO Vane selector (AIR DISCHARGE)
switching.
TEST RUN switching.
CHECK mode switching.
(Self diagnostic trouble shooting)
Room temperature thermistor (RT1)
Indoor coil thermistor (RT2)
Auto vane’s angle setting.
Emergency stop.
Compressor protection
device working
Defrosting START-STOP
Fan speed control.
Crankcase heater control
ON-OFF.
Self diagnostic function
Independent Control of Outdoor Unit
OUTPUT to indoor unit
INPUT from indoor unit
INPUT to remote controller
REMOTE CONTROLLER
Processes and transmits orders.
OUTPUT to remote controller
INDOOR CONTROLLER BOARD
Receives orders from remote controller and temperature data from indoor unit.
Processes orders and data.
Controls indoor and outdoor operation.
Self diagnostic function.
w System control operation. w Emergency operation. w Set by dip switch on indoor controller board.
Transmits the power to remote controller.
OUTPUT to outdoor unit
12VDC
Non-polar, two-wire cable maximum length 500 meters
Signal
Remote controller
LCD indicator
Polar three-wire cable
12VDC
123
1 2 3
Indoor unit
Outdoor unit
FILTER
CHECK MODE
TEST RUN
241
Page 35
35
<How to operate>
1 Press POWER ON/OFF button. 2 Press the a button to display “ f ”.
3 Press the i TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is press one time Cooling 19 to 30°C.
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Compressor
ON
LOW or HIGH
Initially 10 degrees
(Changeable by remote controller setting)
LOW or HIGH
ON
ON
OFF
OFF
CLOSE CLOSE
OFF
OFF
Operation starts by POWER button ON.
Operation stops by POWER button OFF.
Room temperature becomes equal to set temperature.
Room temperature rises above set temperature.
<COOL operation time chart>
W1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period has ended.
FILTER
CHECK MODE
TEST RUN
241
2. INDOOR UNIT CONTROL
2-1 COOL operation
(1) Compressor control
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when room temperature is higher than set temperature.
The compressor stops when room temperature is equal to or lower than the set temperature.
3 The compressor stops in check mode or during protective functions. 4 Coil frost prevention to prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 1°C or
below after the compressor has been continuously operated for at least 16 minutes or more. When the indoor coil temperature rises to 10°C or above, the compressor will start after a 3-minute time delay. NOTE : By turning OFF the dip switch SW1-5, PKH-2.5/3/4 for J1-5 on indoor controller board, the start temperature of coil
frost prevention changes 1°C to -3°C.
5 Coil frost protection
When indoor coil temperature becomes -15°C or below, coil frost protection will proceed as follows.
<Start condition>
After the compressor has been continuously operated for 3 minutes or more,and the indoor coil temperature has been -15°C or below for 3 minutes,the coil frost protection will start.
<Coil frost protection>
Compressor stops for 6 minutes, and then restarts. If the start condition is satisfied again during the first 10 minutes of compressor operation, both the indoor and outdoor units stop, displaying a check code of “P8” on the remote controller.
<Termination conditions>
Coil frost protection is released when the start condition is not satisfied again during the allowance, or when the COOL mode stops or changes to another mode.
Page 36
36
(2) Indoor fan control
Indoor fan speed LOW/HIGH depends on the remote controller setting. However, if an outdoor unit abnormality is detected, the indoor fan speed will be LOW, regardless of the remote controller setting.
When the outdoor unit abnormality detection is released and the fan speed returns to the set speed, the quiet cycle control will work. (a) Normal control
( i ) Fan speed LOW/HIGH depends on the remote controller setting regardless of the thermostat ON/OFF. (ii) Fan speed will remain on LOW if an abnormality in outdoor unit is detected. (5 minutes)
When the abnormality detection is released, the fan speed returns to the set speed.
1 Start-up of outdoor unit abnormality
detection.
2 Release of outdoor unit abnormality
detection.
3 Unit stop due to outdoor unit abnormality
with P8 indication.
NOTE 1 : Fan stops immediately if the unit stops or the check mode is started.
5 minutes
SET
LOW
12 13
5 minutes
SET
LOW
OFF
Page 37
37
(3) Auto vane control
Auto vane position is set to 10 degrees airflow at the start-up of COOL operation. It can then be changed by the remote controller.
(a) Stop mode (fixed operation) ( i ) At start-up of COOL operation, the auto vane is set to 10 degrees airflow direction. ( ii ) Discharge direction can be changed with button.
1 Fan speed : LOW
2 Fan speed : HIGH
(b) SWING mode (Only PKH-2.5FKA-E / PKH-3FKA-E / PKH-4FKSA-E)
( i ) The vane motor turns ON when the SWING mode is selected.The vane motor is continuously ON during SWING mode.
<AUTO RETURN>
1 Fan speed : LOW
2 Fan speed : HIGH
When 60 degrees or 70 degrees airflow is selected with the LOW fan speed in COOL operation, “Auto RETURN” will appear below the temperature display. One hour later, the airflow direction returns to 10 degrees automatically and “AUTO RETURN” will disappear. If the airflow direction is set to 10 degrees during “AUTO RETURN” indication, the time counting for AUTO RETURN is cancelled.
10° 60°
70°
10°
60°
70°
30°
(SWING)
(SWING)
10°
60°
70°
10°
60°
70°
30°
AUTO
RETURN
AUTO
RETURN
Page 38
38
<Auto vane drive> (PKH-1.6FKA-E / PKH-2FKA-E) (a) The auto vane is driven by a 2.5 rpm motor.
(b) Vane motor drive time
(c) Airflow direction is based on the horizontal position detected by the vane motor limit switch. When the horizontal position
can not be determined, the vane motor will remain ON until it is determined.
1
If the horizontal position still can not be detected, despite the 10minute detection, the vane motor will turn OFF Remote controller indication continues.
2
After, if the vane motor receives the “auto vane ON” command again, it will restart detecting the horizontal position.
If the horizontal position still can not be determined, despite the 10-minute detection, the vane motor will turn OFF. <Auto vane drive> (PKH-2.5FKA-E / PKH-3FKA-E / PKH-4FKSA-E) (a) The vane is driven by DC12V motor. (b) Airflow direction is selected depends on the number of pulse were sent. (c) Before start driving the auto vane, detect the standard position first, output the number of pulse to each Airflow. (d) The speed of the auto vane drive for both open and close are set at 200 pulse/sec. (e) Method of driving the auto vane.
1
Detecting the standard position:
Output 1600 pulse to the opening direction.
2
Position setting:Output the number of pulse indicated no below chart to the closing direction.
(4) Detecting abnormalities in the outdoor unit
After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperature and room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the difference is still out of RANGE C,the outdoor unit is functioning abnormally. Thus, the compressor stops and check code “P8” appears on remote controller. RANGE A : Indoor coil temperature is more than 5 degrees above room temperature. RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature. RANGE C : Indoor coil temperature is more than 5 degrees below room temperature.
1
10°
2
30°
3
60°
4
70°
Downward C Horizontal 4→
1
Airflow direction change
Horizontal Downward A1→
2
Downward A Horizontal B 2→
3
Horizontal B Downward C 3→
4
Rise 2.1
50Hz
0.65
6.7
0.65
Close
Horizontal Downward A Downward B
1600
The number of pulse output after detecting the standard position
680 578 283
Downward C 113
Indoor coil temperature minus room temperature
+5
0
-5
RANGE A
RANGE B
RANGE C
(degree)
Page 39
39
(5) Drain pump control (Option : Only PKH-2.5FKA-E / PKH-3FKA-E / PKH-4FKSA-E)
The drain pump works in COOL or DRY operation. When operation stops or changes to HEAT mode, the drain pump continues to operate for 3 more minutes. The drain pump does not work in check mode.
<Drain sensor>
When both the drain pump and unit are operating, the drain sensor detects the temperature. This temperature tells whether the drain water level is above or under the drain sensor. If the drain water level rises above the drain sensor due to a drain pump malfunction, the unit will stop operating in order to prevent drain from overflowing. The check code “P5” on the remote controller will display this occurrence. When both of the following conditions are satisfied, the drain sensor is determined to be under water.
Though the drain sensor has been heated by the drain sensor heater for more than 40 seconds, its temperature rise is less than 20 degrees.
The drain sensor temperature is below 63°C.
2-2 DRY operation
<DRY operation time chart>
w1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period
has ended.
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Compressor
ON
(
PKH-2.5/3/4
)
wRefer to
page 40
for PKH-1.6/2
Initially 10 degrees discharge
(
Changeable by remote controller setting
)
LOW speedLOW speed
ON
ON
OFF
OFF
CLOSE
CLOSE
OFF
OFF
Operation starts by POWER button ON.
Operation stops by POWER button OFF.
Room temperature becomes equal to set temperature.
Room temperature rises above set temperature.
<How to operate>
1 Press POWER ON/OFF button. 2 Press the a button to display “ e ”.
3 Press the i TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is press one time DRY 19 to 30°C.
FILTER
CHECK MODE
TEST RUN
241
Page 40
40
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2The compressor runs when the room temperature is higher than the set temperature.
The compressor stops when the room temperature is equal to or lower than the set temperature.
3The compressor stops in check mode or during protective functions. 4The compressor will not start when the room temperature is below 18°C.
The compressor starts intermittent operation when the power is turned ON with room temperature above 18°C. The compressor ON/OFF time depends on the thermostat ON/OFF and the following room temperatures.After 3-minute compressor operation,
If the room temperature thermistor reads above 28°C with thermostat ON, the compressor will operate for 6 more minutes and then stop for 3 minutes.
If the room temperature thermistor reads 26°C—28°C with thermostat ON, the compressor will operate for 4 more minutes and then stop for 3 minutes.
If the room temperature thermistor reads 24°C—26°C with thermostat ON, the compressor will operate for 2 more minutes and then stop for 3 minutes.
If the room temperature thermistor reads below 24°C with thermostat ON, the compressor will stop for 3 minutes.
If the thermostat is OFF regardless of room temperature, the compressor will stop for 10 minutes.
5Coil frost protection
Coil frost protection in DRY operation is the same as in COOL operation.
6Coil frost prevention
Coil frost prevention does not operate in DRY operation.
(2) Indoor fan control
<PKH-2.5FKA-E / PKH-3FKA-E / PKH-4FKSA-E> The indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote
controller. Also, the indoor fan does not run during compressor OFF. <PKH-1.6FKA-E / PKH-2FKA-E> (a)During compressor OFF
When the indoor coil temperature is 6°C or above, the indoor fan will stop.
When the indoor coil temperature is below 6°C, the indoor fan will run in DRY mode.
(b)During compressor ON
The indoor fan runs on EXTRA-LOW speed for the first 1 minute after the compressor is turned on.
After, the indoor fan runs in DRY mode.
<Dry mode>
The fan notch is controlled by the indoor coil temperature every 30 seconds.
During compressor OFF, when the indoor coil temperature becomes 6°C or above, the indoor fan turns OFF immediately.
(3) Auto vane & drain pump controls
Same as in COOL operation
(4) Detecting abnormalities in the outdoor unit
An abnormality in the outdoor unit can not be detected in DRY operation.
Indoor coil temperature
Below -10°C
-10 to 0°C
Above 0°C
Fan operation LOW speed EXTRA-LOW speed Dry mode
Page 41
2-3 HEAT operation <How to operate>
1 Press POWER ON/OFF button. 2 Press the a button to display “ g ”.
FILTER
CHECK MODE
TEST RUN
3 Press the i TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is press one time Heating 17 to 28°C.
<Display in HEAT operation>
[ DEFROST ]
The [ DEFROST ] symbol is only displayed during the defrost operation.
241
<HEAT operation time chart>
Operation starts by POWER button ON.
Thermostat
Indoor fan
Auto vane
Compressor
Power ON lamp
STAND BY lamp
ON
OFF
ON OFF
ON
OFF
ON OFF
ON
OFF
ON OFF
Room temperature becomes equal to set temperature.
LOW
Depends on remote controller setting
Close
From POWER ON until
warm begins to blow
[ STANDBY ]
The [ STANDBY ] symbol is displayed from the time the heating operation starts until the heated air begins to blow.
Room temperature falls below set tem­perature.
Extra LOW *1Extra LOW *1
LOW or HIGHLOW or HIGH
Depends on remote controller setting
10° Close
Minimum 3 minutes *2
Operation stops by POWER button OFF.
*1 Changeable by indoor dipswitch SW1- 7 and SW1- 8.
(
PKH-2.5/3/4 for
J1-7,J1-8)
w
2 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period has ended.
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3, minutes after stop.
2The compressor runs when the room temperature is lower than the set temperature.
The compressor stops when the room temperature is equal to or higher than the set temperature.
3The compressor stops in check mode or during protective functions. 4Overheat protection
<Start condition>
When the indoor coil thermistor reads 70°C or above, the overheat protection will start.
<Overheat protection>
The compressor stops for 6 minutes, and then restarts. If the start condition is satisfied again within 10 minutes of compressor operation, both the indoor and outdoor units stop, displaying a check code of “P6” on the remote controller.
<Termination conditions>
Overheat protection is terminated when the start condition is not satisfied again during the allowance (10-minute compressor operation), when operation mode changes to other mode, or when thermostat turns OFF.
41
Page 42
(2) Indoor fan control
(a) Normal control
(!)The indoor fan runs on EXTRA-LOW speed during the thermostat OFF.
EXTRA-LOW speed can be changed to LOW or HIGH speed by setting the dip switch SW1-7 and SW1-8,(PKH-
2.5/3/4 for J1-7, J1-8) If the indoor coil temperature becomes more than 5 degrees below the room temperature during the thermostat OFF, the indoor fan will stop. After, when the indoor coil temperature becomes within 5 degrees of room temperature, the indoor fan will run on EXTRA-LOW speed.
(@)Hot adjustment is a warm-up for HEAT operation
<Start conditions> The hot adjustment works under any of the following conditions.
HEAT operation starts.
Defrosting ends.
Thermostat turns ON.[Hot adjustment]
Initially, the indoor fan runs on EXTRA-LOW speed. When 5 minutes have passed or the indoor coil temperature exceeds 35°C, the fan speed changes to LOW. Two minutes later, the hot adjustment ends. Then, the fan speed
depends on the remote controller setting. (#)The indoor fan stops when the indoor coil temperature is within 5 degrees either way of room temperature. ($)To eliminate the remaining heat, the indoor fan runs for the first 1 minute after the booster heater is turned OFF.
(3) Auto vane control
(a) STOP mode (fixed operation)
(!) The airflow direction at the start-up of HEAT operation is the same as that of the previous operation. (@) The airflow direction can be charged by the remote controller setting.
In the following cases, airflow direction becomes 10° regardless of the remote controller setting.
1 During the hot adjustment with fan speed at EXTRA-LOW 2 During defrosting with indoor fan OFF 3 During the thermostat OFF
(b) SWING mode (Only for PKH-2.5FKA-E / PKH-3FKA-E / PKH-4FKSA-E)
(!) The vane motor turns ON when the SWING mode is selected.
The vane motor is continuously ON during SWING mode.
(@) In the following cases, the discharge direction is 10° regardless of the remote controller setting.
1 During the hot adjustment with fan speed at EXTRA-LOW 2 During defrosting with indoor fan OFF 3 During thermostat OFF
42
10°
30° 60°
70°
(SWING)
(Only for PKH-2.5FKA-E / PKH-3FKA-E / PKH-4FKSA-E)
Page 43
(4) Detecting abnormalities in the outdoor unit
When the outdoor unit is determined to be abnormal by the following causes, the compressor will stop and the check code
“ P8 ” will appear on the remote controller display.
1 During compressor ON after hot adjustment
[1]If the difference between the indoor coil temperature and room temperature is in the RANGE B, the indoor fan will
stop. [2]Within 20 minutes after entering RANGE B (except for the first 10 seconds), a) If the temperature difference enters RANGE A, the hot adjustment starts, b) If the temperature difference is still in RANGE B, the outdoor unit is deemed abnormal. c) If the temperature difference enters RANGE C, defrosting starts.
Within 30 minutes after entering RANGE C,
If the temperature difference does not return to RANGE B,the outdoor unit is deemed abnormal.
If the temperature difference returns to RANGE B, the next 20 minutes is an allowance period. If the difference enter
RANGE A during the allowance, defrosting ends and the hot adjustment starts. If the difference does not enter RANGE A during the allowance, the outdoor unit is deemed abnormal.
2 During compressor ON in hot adjustment
After 30 minutes of defrosting in hot adjustment, if the temperature difference is still in RANGE C, the outdoor unit is determined to be abnormal.
3 During compressor OFF
After 20 minutes of thermostat OFF, if the indoor coil thermistor reads -25°C or below, the outdoor unit is determined to be abnormal.
(5) Indoor coil thermistor abnormality detection
An abnormality can be detected during compressor ON, except for the following.
For the first 30 minutes after the temperature difference between the indoor coil temperature and room temperature enters the RANGE C.
When the temperature difference enters the RANGE C until it moves to the RANGE B.
w1 (See the next page.)
(6) Defrosting operation
After the outdoor unit starts the defrosting operation, when the temperature difference between the indoor coil temperature and room temperature gets out of RANGE A and into RANGE B, the indoor unit starts the defrosting mode. After the outdoor unit stops the defrosting operation, when the temperature difference returns to the RANGE A, the indoor unit stops the defrosting mode. While the indoor unit is in the defrosting mode, the indoor fan and the booster heater stop.
w1 RANGE A : Indoor coil temperature is more than 5 degrees above room temperature.
RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature. RANGE C : Indoor coil temperature is more than 5 below room temperature.
Indoor coil temperature minus room temperature
(degree)
+5
0
-5
RANGE A
RANGE B
RANGE C
43
Page 44
44
(1) Initial mode
1 When AUTO operation starts after unit OFF.
If the room temperature is higher than the set temperature, operation starts in COOL mode.
If the room temperature is equal to or lower than the set temperature, operation starts HEAT mode.
2 When AUTO operation starts after COOL or HEAT operation, the previous mode continues.
(2) Mode change
1 HEAT mode changes to cool mode when 15 minutes have passed since the room temperature became 2 degrees above
the set temperature.
2 COOL mode changes to HEAT mode when 15 minutes have passed since the room temperature became 2 degrees
below the set temperature.
(3) Temperature range
AUTO operation is available under the outside air temperatures as follows.
Mode change (HEAT COOL)
When room temperature becomes2degrees above the set temperature,the operation mode can not be changed for 15 minutes.
(degree)
To+2
To:Set temperature (19 28 )
To+1
To
To - 1
To - 2
Compressor
Start
HEAT mode HEAT mode
Mode change
15 minutes
15 minutes
Mininum 3 minutes
COOL mode
(COOL HEAT)
ON OFF
-9 0 1020304046
-8.5
Cooling range
(Outside air temperature)
Heating range
-5
<How to operate>
1 Press POWER ON/OFF button. 2 Press the a button to display “ h ”.
3 Press the i TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is press one time Auto 19 to 28°C.
“AUTOMATIC” works to change by itself the operation mode either to cooling or heating according to the room temperature.
2-4 AUTO operation (Automatic COOL/HEAT change over operation)
FILTER
CHECK MODE
TEST RUN
241
Page 45
45
<How to operate>
To change the airflow direction, press button.
(1) COOL/DRY operation
At the start-up of COOL or DRY operation, the airflow direction in automatically set to 10°. After, it can be changed to another direction with button on the remote controller.
<Auto return>
When 60° or 70° airflow is set with fan speed on LOW, “AUTO RETURN” appears below the room temperature display. One hour later the direction changes to 10°, automatically and “AUTO RETURN” disappears.
(2) HEAT operation
At the start-up of HEAT operation, discharge direction depends on the setting of the last operation. After, it can be changed to another direction with button. The discharge direction shifts to 10° regardless of the remote controller settings under any of the following conditions.
Thermostat OFF
Defrosting
Indoor fan speed EXTRA-LOW in hot adjustment
Available in COOL operation with fan speed on HIGH or in HEAT operation. Unavailable in DRY operation. If fan speed changes from LOW to HIGH during 30° downward airflow in COOL mode, the direction automatically changes to 10°.
10˚
30˚
60˚
70˚
Swing
Changes by pressing the button.
FILTER
CHECK MODE
TEST RUN
241
2-5 Auto vane control
Page 46
46
<Timer function>
AUTO STOP ·········The air conditioner stops after the set time lapses. AUTO START ········The air conditioner starts after the set time lapses. AUTO OFF ············Timer is not active.
<How to operate>
1. Press POWER ON/OFF button.
2. Press w button to select AUTO STOP or AUTO START.
3. Press q button to set desired time. Time setting is in 1 hour units for up to 24 hours. Each time HOURS button is pressed, set time increases by 1 hour. When HOURS button is pressed and held, the set time increases by 1 hour every 0.5 seconds.
4. To cancel the timer operation, press POWER ON/OFF button.
2-7 Test run <Before test run>
After installing, wiring, and piping the indoor and outdoor units, check for refrigerant leakage, looseness in power supply or control wiring, and mistaken polarity.
Use a 500-volt measure to check the resistance between the power supply terminal block and ground to make sure that it is at least 1.0MΩ.
Attention : Do not use the air conditioner if resistance is less than 1.0MΩ.
This setting will stop the air conditioner in 8 hours. With the lapse of time, time display changes in 1 hour units, showing remaining time.
<Timer setting example>
OFF
2-6 TIMER operation
FILTER
CHECK MODE
TEST RUN
241
TEST RUN
241
TEST RUN button
TEST RUN
Display
Remote controller
1
Turn on main switch.12 hours before proceeding to step 2 to allow for crankcase heater operation.
2
Push the TEST RUN button twice and indication of TEST RUN will be shown on the liquid crystal display.
4
Push button LOW/HIGH to check that the fan speed changes properly.
6
After the check is finished leave the test run mode,push the power ON/OFF button. It can also be stopped by pushing the timer MODE button.
5
Check the operation of outdoor unit fans.This unit controls the rotation speed and performance capacity of fans. In some cases,it may rotate at low speed as the condition of outside air requires and the speed will be kept unless the performance has become deficient. Therefore,when the condition of outside air demands,there may be such cases as the fan stops or rotates reversely. Please note that these symptoms are not mulfunction.
3
Press the button to display ,COOL/DRY(or HEAT)to confirm that cool (or warm)air is blown out. (At heating operation,there may be a short delay before warm air begins to blow out.)
*The above figure shows the state of TEST RUN at cooling operation.
When a TEST RUN is started,the timer shall be set to 2 hours. The unit will automatically turn off after 2 hours.
Page 47
47
(1) Indoor coil temperature code
During the test run, the indoor coil temperature code from 1 to 15 is displayed on the remote controller instead of room temperature. The code should fall with the lapse of time in normal COOL operation, and should rise in normal HEAT operation.
(2) Trouble during test run
If the unit malfunctions during the test run, refer to section 10 in this manual entitled “TROUBLESHOOTING.”
When the optional program timer is connected to the conditioner, refer to its operating instructions.
2-8 Emergency operation
When the remote controller or microprocessor malfunctions but all other parts are normal, emergency operation is started by setting the dip switch SW3 on the indoor controller board.
<Before emergency operation>
1. Make sure the compressor and the indoor fan are operating normally.
2. Locate the defect with the self-diagnostic function. When the self-diagnostic function indicates “protective function is working”, release the protective function before starting the emergency operation. CAUTION: When the self-diagnostic function indicates a check code of “P5” (drain pump malfunction), DO NOT start the
emergency operation because the drain may overflow.
<How to operate>
1. For emergency cooling, set the dip switch SW3-1 to ON and SW3-2 to OFF. For emergency heating, set the dip switch SW3-1,2 to ON.
2. Turn ON the outdoor unit breaker and then ON the indoor unit breaker.
Emergency operation will now start.
3. During emergency operation, the indoor fan operates on high speed, but the swing louvers and the auto vanes do not operate.
4. To stop emergency operation, turn OFF the indoor unit breaker.
NOTE: The remote controller POWER ON/OFF button can not start/stop emergency operations.
CAUTION: Do not use emergency cooling for more than 10 hours, as the indoor coil may freeze.
Code
Indoor coil
temperature
Indoor coil
temperature
Thermistor
abnormality
Code
1
-40~1˚C 9
~45˚C
2
~10˚C ~15˚C ~20˚C ~25˚C ~30˚C
~90˚C
~35˚C ~40˚C
10 11 12 13 14 15
~50˚C
3
~55˚C
4
~60˚C
5
~70˚C
678
1 ON
1
2
1.2 ON
1
2
1-2 OFF
1
2
Emergency cooling
Emergency heating
Normal operation
Microprocessor board
Page 48
2-9 Interlock with ventilation system (LOSSNAY)
Mr. SLIM/LOSSNAY interlock operation is available by using the optional parts listed below.
(1) System organization
Relay box (PZ-12RB-E)
Relay box
LOSSNAY
Mr. SLIM
Remote controller
Power supply
LOSSNAY
Mr. SLIM
Remote controller
LOSSNAY control switch (PZ-05SLB
Power supply
2-E) LOSSNAY control switch
(PZ-05SLB
Remote display adapter (PAC-SA88HA-E)
2-E)
(2) LOSSNAY models connectable to Mr. SLIM are : LGH-15RS-E, LGH-50RS-E
LGH-25RS-E, LGH-80RS-E LGH-35RS-E, LGH-100RS-E
(3) Reqired parts are:
Relay box (PZ-12RB-E)…Contact capacity 10A
Remote display adapter (PAC-SA88HA-E)…An optional part for Mr. SLIM
2-E)
LOSSNAY control switch (PZ-05SLB
For LOSSNAY individual operation
(4) Operation
1LOSSNAY turns ON/OFF according to Mr. SLIM ON/OFF 2While Mr. SLIM is OFF, LOSSNAY individual operation is available by using the LOSSNAY control switch.
When Mr. SLIM turns OFF with the LOSSNAY control switch at ON, LOSSNAY will continue to operate.
(5) Wiring.
2When the LOSSNAY control switch is not used:1When the LOSSNAY control switch is used
Remote controller
Power supply 50Hz 220 240V
10m
Connecting wire
0.13mm or over
Connecting wire solid wire,
1.6 or 2.0 (field supplied)
Circuit breaker (field supplied)
L
N
PL
HIGH
N
LOSSNAY control switch (PZ-05SLB
Insulation is needed
2
Indoor controller
N L
LOW
DAMPER
2-E)
Mr. SLIM
board
Connector
CN51
ORN
RED
BRN
GRN
YLW
Junction box (field supplied)
Power supply for Mr. SLIM 220 240V AC
Relay box
(PZ-12RB-E)
YLW
A
ORN
B
RED
L
WHT
N
RED
HIGH
N
WHT
LOSSNAY
Terminal block
ORN
LOW
RED
HIGH
WHT
N
RED
DAMPER
ORN
DAMPER
WHT
Relay box
(PZ-12RB-E)
Terminal block
A B L N HIGH N
Mr.SLIM CN51
8
7
4
6 2
5
3
1
12V DC
L
Power supply 220 240V AC
N
Circuit breaker
NOTE: For further information, refer to the
LOSSNAY technical & service manual.
LOSSNAY
Terminal block
ORN
LOW
RED
HIGH
WHT
N
RED
DAMPER
ORN
DAMPER
WHT
48
Page 49
10
9
49
2-10 Dip switch and jumper connector functions
Each figure shows the initial factory setting.
[1] On remote controller board
(1) SW17(Address selector)
SW17-1 ~ 6) For address setting SW17-7) When two remote controllers are used, this switch sets the controller function.
OFF: The remote controller is set as a main controller. ON: The remote controller is set as a sub controller.
SW17-8) Switch for system back-up
OFF: Without back-up ON: With back-up
(2) SW18 (Function selector)
SW18-1) Switch for timer
OFF: single day ON: timer every day
SW18-2) Switch for filter sign
OFF: filter sign absent ON: filter sign present
SW18-3) Switch for filter sign time setting.
OFF: 100 Hr ON: 2500 Hr
SW18-4) Not yet used
[2] On indoor controller board
For PKH-1.6FKA-E / PKH-2FKA-E (1) SW1 (Mode selector)
SW1-1) Switch that changes between FAN mode and AUTO mode.
OFF: Fan mode for models with heat pump.
ON: AUTO mode for models with heat pump. SW1-2) Not for use SW1-3) Switch for auto vanes.
OFF: Unit without auto vanes.
ON: Unit with auto vanes. SW1-4) Not for use SW1-5) Switch to change the temperature to start coil frost prevention.
OFF: -3°C(For previous special models)
ON: 1°C(For all current models) SW1-6) Switch for set temperature adjustment in HEAT mode.
During HEAT operation, warm air collects near the ceiling. When the indoor unit is installed near the ceiling, the
temperature read by room temperature thermistor differs from the actual living-space temperature by about 4
degrees. Therefore, the room temperature read by room temperature thermistor must be lowered by 4 degrees.
OFF: 4-degree adjustment
ON: No adjustment SW1-7) Switch for fan speed during thermostat OFF in HEAT operation.
OFF: EXTRA LOW
ON: LOW SW1-8) Switch for fan speed during thermostat OFF in HEAT operation.
OFF: EXTRA LOW or LOW (set with SW1-6)
ON: LOW or HIGH (set with remote controller) SW1-9) Switch for detecting abnormalities in the outdoor unit abnormality detection.
OFF: When an abnormality occurs, it is detected.
ON: Even if an abnormality occurs, it can not be detected. SW1-10) Switch for auto restart function.
OFF: This function does not work.
ON: This function works.
8 7 6 5 4 3
2 1
ON
OFF
4 3 2 1
ON
OFF
1 2 3 4 5 6 7 8
OFF
ON
Page 50
50
(2) SW2 (Address selector)
(3) SW3 (Emergency operation switch)
(4) SW5 (Model selector)
(5) SW6 (Model selector)
(6) SW7 (Model selector)
Switch to set the output of phase-controlled indoor fan motor. Address setting is available at any time. The initial factory setting by is based on each capacity.
SW5-1) Power supply
SW5-2) OFF:For models with heat pump.
ON:For models without heat pump. SW5-3) Not for use SW5-4) This switch is unavailable for PKH-FK(S)A-E. Keep this switch at OFF.
Single control Twin control Triple control SW6-1 OFF ON(Twin NO.1) ON(Triple NO.1) SW6-2 OFF ON(Twin NO.2) ON(Triple NO.2) SW6-3 OFF OFF ON(Triple NO.3) SW6-4 OFF OFF ON
Service Ref.
SW7
PKH-1.6FKA-E PKH-2FKA-E
[3] On indoor controller board
For PKH-2.5FKA-E / PKH-3FKA-E / PKH-4FKSA-E
(1) J1 (Mode selector)
J1-1) Switch that changes between FAN mode and AUTO mode.
Provided: Fan mode for models with heat pump. Not provided: AUTO mode for models with heat pump.
J1-4) Switch for drain pump (For optional parts)
Provided: The drain pump works in only COOL operation. Not provided: The drain pump works in both COOL and HEAT operation.
J1-5) Switch to change the temperature to start coil frost prevention.
Provided : 1°C (For all current models) Not provided: -3°C (For previous special models)
ON :230V/240V OFF:220V
)(
Used in setting the unit-address for group control. For further information, refer to page 68.
1456789
10
123456 ON OFF
Normal operation For emergency cooling For emergency heating
12
ON OFF
12
ON OFF
12
ON OFF
12
ON OFF
3
12
ON OFF
34
12
ON OFF
34
12
ON OFF
3
Page 51
51
J1-6) Switch for set temperature adjustment in HEAT mode
During HEAT operation, warm air collects near the ceiling. When the indoor unit is installed near the ceiling, the temperature read by room temperature thermistor differs from the actual living-space temperature by about 4 degrees. Therefore, the room temperature read by room temperature thermistor must be lowered by 4 degrees.
Provided : 4-degree adjustment
Not provided : No adjustment
J1-7) Switch for fan speed during thermostat OFF in HEAT operation.
Provided : EXTRA LOW
Not provided : LOW
J1-8) Switch for fan speed during thermostat OFF in HEAT operation.
Provided : EXTRA LOW or LOW (set with J1-7)
Not provided : Low or HIGH (set with remote controller)
J1-9) Switch for detecting abnormalities in the outdoor unit abnormality detection.
Provided : When an abnormality occurs, it is detected. Not provided : Even if an abnormality occurs, it can not be detected.
J1-10) Switch for auto restart function.
Provided : This function does not work.
Not provided : This function works.
(2) SW2 (Address selector)
Used in setting the unit-address for group control. For further information, refer to page 66.
(3) SW3 (Emergency operation switch)
(4) J5 (Model selector)
J5-2) Provided :For models with heat pump.
Not Provided :For models without heat pump.
J5-4) This jumper is unavailable for PKH-FK(S)A-E.
(5) SW6 (Model selector)
(6) SW7
SW7-2) POWER SUPPLY
(7) J9 (Model selector)
J9-1) Not provided J9-2) Provided
2-11 INDOOR FAN CONTROL
Indoor fan relay output. (a) During fan ON
The indoor fan relay turns ON. One second later, the phase control will start.
(b) During fan OFF
The phase control turns OFF. One second later, the indoor fan relay will turn OFF.
Normal operation For emergency cooling For emergency heating
24
OFF: 220V ON : 240V
)(
SW6-1 SW6-2 SW6-3 SW6-4
OFF
Single control
OFF OFF OFF
ON(Twin No.1)
Twin control
ON(Twin No.2)
OFF OFF
ON(Triple No.1)
Triple control
ON(Triple No.2) ON(Triple No.3)
ON
12
}
PKH-FK(S)A-E
PKH-2.5 / 3
PKH-4
123456 ON OFF
1234 ON OFF
12 ON OFF
12 ON OFF
12 ON OFF
1234 ON OFF
1234 ON OFF
1234 ON OFF
Page 52
52
3. OUTDOOR UNIT CONTROL
3-1 Outdoor fan control
The rotational frequency of outdoor fan is phase-controlled according to the outdoor coil temperature. This control allows the cooling operation even with the low outside-air temperature and the heating operation even with the high outside-air temperature.
3-2 Outdoor unit control
The outdoor unit turns ON/OFF the cooling/heating operation according to orders given from the indoor unit.
3-3 Protective functions
1 If an reversed-phase, an open phase, or an indoor controller abnormality is detected, the outdoor unit will stop operation and
the check mode will start. (For the check mode details, see page 57.)
2 If a protective function works, the compressor will stop running. Three minutes later, the compressor will restart. If the
protective function works again, the compressor will stop running and the check mode will start.
3 The protective function is memorized. 4 The memory is cleared when the POWER ON/OFF button on the remote controller is turned OFF. However, the check mode
display continues until the outdoor unit receives the “operation ON” command from the indoor unit.
3-4 COOL/HEAT operation time chart
10 minutes w1
ON
Thermostat
Outdoor fan
4-way valve (COOL)
4-way valve (HEAT)
Bypass valve
Compressor
Crankcase heater (with jumper wire J3)
Crankcase heater (without jumper wire J3)
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON OFF
60 minutes 60 minutes 60 minutes 60 minutes 60 minutes
3 minutes
10 minutes
3 minutes
Repeats 60-minute ON/OFF
60 minutes
60 minutes
Operation starts by POWER button ON.
Operation stops by POWER button OFF.
Room temperature becomes equal to set temperature.
Room temperature becomes different from set temperature.
w1 If compressor restarts within 10 minutes, 4-way valve remains ON.
Page 53
53
(1) Start conditions
A. When all of the following conditions are satisfied, defrosting will start. However, when the bypass valve turns OFF,
defrosting starts 10 minutes later.
(a) More than seven minutes have passed since the compressor start-up. (b) The outdoor coil thermistor reads -5°C or below. (c) The outdoor fan motor output step is 100% (d) Total time of compressor operation exceeds 30 minutes, and the outdoor coil temperature has fallen by 8 degrees or
more in comparison with that of 10 minutes after the compressor start-up.
NOTE: The outdoor coil temperature of 10 minutes after the compressor start-up is memorized until the defrosting
operation has ended.
B. When all of the following conditions are satisfied, defrosting will start.
(a) ~ (c) The same as above (a) ~ (c) in item A (d) Total time of compressor operation exceeds “defrost interval”.
Further information on the defrost interval is described in (3).
C. After the total time of compressor operation exceeds the defrost interval, the thermostat repeats ON/OFF three times.
Two minutes after the fourth “ON” of the thermostat, if the outdoor coil thermistor reads -5°C or below and the fan output output is 100%, defrosting will start.
NOTE: The count of the thermostat ON/OFF is cleared by the compressor-OFF command or defrosting start-up.
(2) During defrosting
Even if the thermostat turns OFF, defrosting continues.
The 4-way valve, bypass valve, outdoor fan, and indoor fan are OFF.
ON
Outdoor fan
Compressor
4-way valve
Bypass valve
Auto vane
Indoor fan
10 degrees discharge direction.
(Remote controller still displays set direction.)
Outdoor unit
Indoor unit
ON
CLOSE
ON
OFF
OFF
OFF
ON OFF
ON
OFF
ON
OFF
CLOSE
Defrosting starts.
Defrosting stops.
3-5 Defrosting in HEAT mode <Defrosting time chart>
Page 54
54
(3) Defrost interval
The defrost interval time is determined as follows.
Initial defrost interval is 50 minutes.
The defrost interval after defrosting depends on the preceding defrosting time as shown below.
NOTE1:If the unit stops during defrosting , the next defrost interval will be 50 minutes. NOTE2:If a protection function works for the first time during defrosting, the compressor will stop.
After a 3-minute time delay, defrosting will restart. In this case, a 3-minute time delay is included with the defrosting time. If the protection function works for the second time, the unit stops operation and displays the check code. The next defrost interval will be 30 minutes.
NOTE3:When the defrosting has ended, the total time of the compressor operation is cleared off.
(4) Termination conditions
Defrosting finishes when any of the following conditions are satisfied.
1Defrosting has continued for 15 minutes. 2Outdoor coil thermistor reads 22°C or above for the first 75 seconds after defrosting start-up. 3Outdoor coil thermistor reads 8°C or above after the 75-second defrosting. 4Power ON/OFF button is turned OFF during defrosting.
3-6 Actuators (1) Bypass valve control
<Cooling mode> 1When the unit stops due to the coil frost prevention, the bypass valve turns ON. When one hour has passed since the
compressor stopped, the bypass valve returns to OFF.
2When the compressor operates with the bypass valve at ON for more than 30 minutes, the bypass valve turns OFF. 3When the compressor stops with the bypass valve at OFF, the bypass valve turns ON and remains ON for three minutes.
<Heating mode> 1When the unit starts for the first time after the circuit breaker has been turned ON, or when it starts after the compressor
OFF of 30 minutes or more, if the outdoor coil thermistor reads 12°C or more, the bypass valve turns ON.
2When the high pressure switch (63H1) works, the bypass valve turns ON. 3When the bypass has been ON for 30 minutes:
If the high pressure switch has already returned, the bypass valve turns to OFF.
If not, the fan output step keeps 70 for three minutes. Meanwhile, if the high pressure switch returns, the bypass valve
turns OFF. Otherwise the normal fan control starts.
4When the operation mode changes or stops, the bypass valve turns ON and remains ON for three minutes. <Defrosting operation>
1The bypass valve is OFF.
(2) Crankcase heater control
1With jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and then turns ON one hour
after the compressor stops.
2Without jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and repeats 1-hour ON and
1-hour OFF.
Defrosting operation time Next defrost interval 3 minutes or below 120 minutes 3 to 7 minutes 80 minutes 7 to 10 minutes 60 minutes 10 to 15 minutes 40 minutes 15 minutes (Maximum) 30 minutes
Page 55
55
3-7 Service functions (1) Compulsory defrosting
1When all of the following conditions are satisfied, pressing SW2 starts the compulsory defrosting.
During HEAT mode
The compressor is ON.
The outdoor coil temperature is being displayed by LED. (Outdoor controller board dip switch SW3-1 : OFF, SW3-2 :
ON)
The outdoor coil thermistor reads 8°C or below.
2The operation state and the termination conditions of the compulsory defrosting are the same as those of the normal
defrosting. As an exception, the defrost interval after the defrosting completion is 50 minutes.
(2) Fixed fan-output
While the compressor is operating (except during defrosting) and the fan output step is indicated by LED, pressing SW2 fixes the fan output. The fixed fan-output can be released when any of the following conditions are satisfied.
1SW2 is pressed again. 2SW3 setting is changed. 3The compressor stops. 4Defrosting operation starts.
(3) Function of switches on the outdoor controller board
SW1: Clears the check code memory (push-button switch) SW2: Switches the output state indication and the check code display (push-button switch) SW3-1,2: Switches the output state indication items (dip switch) For further information, refer to page 59.
(4) 100% fan output
Fan output is fixed to 100% by shorting the connector CN22. However, the fan stops during compressor OFF or defrosting. Open-circuit of CN22 restarts the normal fan control.
(5) Time shortening
Short circuit of the connector CN21 shortens the time as follows
1Fan control period: 30 seconds 3 seconds 2Three-minutes time delay function : 3 minutes 3 seconds 3Max. time of defrosting : 15 minutes 15 seconds 4Defrost interval : 30 ~ 120 minutes 3 ~ 12 seconds 5Compressor ON/OFF time for bypass valve ON/OFF : 30 minutes 3 seconds 6Compressor ON time to start other functions : x minutes x seconds 7Crankcase heater operation : 1 hour 6 seconds
Page 56
56
9 TROUBLESHOOTING
Symptom Cause Check points
The display “CENTRALLY CONTROLLED” on remote controller dose not disappear.
1) Wrong address setting of remote controller/indoor controller board.
2) Timer adapter is connected to the remote controller.
3) Signal transmission error between indoor unit and remote controller.
1) Check the address setting of remote controller and indoor controller.
2) Make sure the timer adapter is used correctly.
3) 1 Turn another remote controller’s DIP SW17-
7 ON to make it sub controller.
2 Connect the sub controller to the unit, and
turn circuit breaker ON.
If the display “centrally controlled” disappears, replace the original remote controller.
If the display remains the same, replace the
When remote controller POWER button is turned ON, the check code “EO”appears.
1) Signal transmission error between indoor unit and remote controller
1) 1 Connect a sub remote controller. 2 Turn circuit breaker ON.
If the display “centrally controlled” remains, replace the indoor controller board.
3 If the display disappears, turn the remote
controller POWER button ON and check as follows.
When remote controller POWER button is turned ON, operating display appears, but disappears soon.
1) Short circuit of indoor/outdoor connecting wire
2) Short circuit of transmission wire.
3) Short circuit of drain sensor heater circuit.
4) Wrong operation of remote controller due to noise wave emitted by other appliances.
1), 2) Check the wire
3) Measure the resistance of the drain sensor connector CN50 1 - 3. Normal resistance should be 82Ω.
4) Turn the circuit breaker OFF, and then turn ON.
If the remote controller remains abnormal, despite the above measures, replace the indoor controller board.
Despite turning POWER button ON, the remote controller display does not appear.
1) Damaged remote controller.
2) Short circuit of transmission wire.
3) Bad contact of indoor CN40.
4) CN40 is attached to a sub unit.
5) Damaged transformer.
6) Bad contact of CN4T.
7) Blown fuse.
8) Circuit breaker OFF.
1) Measure the voltage between terminals of remote controller. If no voltage, remove the terminals and measure the voltage between wires. If the voltage is between 6VDC and 12VDC, replace the remote controller.
2) ~ 8) Check each point.
If it is not defective, replace the indoor controller board.
1.TROUBLE IN TEST RUN
Remote controller
1
2
3
4
Operating Display
Operating Display
No Display
No Display
Sub remote controller
EO Display
Operating Display
EO Display
Operating Display
Malfunction
Malfunction of indoor Unit
Malfunction of Remote controller
Malfunction of indoor Unit and Remote Controller
Malfunction of Remote controller
Page 57
57
2. SELF DIAGNOSTIC FUNCTION WITH REMOTE CONTROLLER
2-1 When malfunction occurs during operation
When a malfunction occurs, the indoor and outdoor units stop and the malfunction is displayed on the LCD of the remote controller. (A) ON the set temperature display part, “CHECK” appears, and
the unit address and the check code are displayed alternately
at one-second intervals. (Check mode)
2-2 How to use the self diagnostic function for service A. For normal control with one unit and one remote controller
(1) Pressing the CHECK button on the remote controller twice starts the self diagnostic function. (2) During the self diagnostic function, “CHECK” appears at two positions on the remote controller display. Then, at least 10
seconds later, the unit address and the check code is alternately displayed at one-second intervals.
(3) Check and repair the unit according to the check code. (Refer to the next page.)
2-3 For group control using one remote controller
(1) Press the TEMP. button or TEMP. button on the remote controller to advance or go back to the unit
address. Each time TEMP. button is pressed, the unit address advances by one. Each time TEMP. button is pressed, the unit address goes back by one. The check code and the unit address, appear alternately.
(2) The check code “U8” means no malfunction has occurred since installation.
The check code “EO” means the following conditions:
The unit address displayed on the remote controller does not apply to any unit.
Power is not supplied to the unit.
Signal transmitting / receiving circuit is abnormal.
(3) Check and repair the unit according to the check code. (Refer to the next page.)
(2) When one remote controller controls several units in the group control,
the LCD shows the unit address and check code of the first malfunctioning unit.
(3) To cancel the check mode, press the [ON/OFF button. In remote
ON/OFF control, press the remote [ON/OFF switch. In centralized control, turn OFF the [ON/OFF button of centralized controller.
NOTE: The latest check code is memorized, even if the check mode is cancelled by the way mentioned above. It takes
60 seconds maximum to display the memorized check code.
CHECK mode
CHECK button
Example
Check
code
Unit
address
Page 58
58
Check
code
Diagnosis of malfunction Cause Check points
EO
Signal transmitting/receiving
error
(Indoor controller does not
respond to remote controller signal.)
During individual unit control
1) Bad contact of transmission wire
2) Signal transmitting/receiving circuit is abnormal.
1) Check the transmission wire.
2) Check with another remote controller. If “EO” is still indicated, replace the indoor controller board. If other check code appears. replace the original remote controller.
P3
Signal transmission error (Remote controller does not
respond to indoor controller signal.)
1) Bad contact of transmission wire
2) Signal transmitting/receiving circuit is abnormal.
3) Wrong operation due to noise wave emitted by other appliances
1) Check the transmission wire.
2) Check with another remote controller. If “P3” is still indicated, replace the indoor board. If other check code appears, replace the original remote controller.
3) Short-circuit between ① and ➁ of CN40 and
attach CN40 to the following units.
Second unit in twin control
Second and third units in triple control
Sub units in group control
P4
Abnormality of drain sensor 1) Bad contact of transmission
wire
2) Damaged thermistor
1) Check the connector.
2) Measure the resistance of the thermistor - ➄. As for the normal resistance, refer to the case of P1.
If the resistance is normal, replace the indoor controller board.
P5
Malfunction of drain pump 1) Malfunction of drain pump
2) Damaged drain sensor
1) Check the drain pump.
2) Check the drain sensor.
Check the drain sensor heater. Normal
resistance should be 82Ω.
If the resistance is normal, replace the indoor controller board.
P6
Coil frost protection is
working.
1) Short cycle of air cycle
2) Dirty air filter
3) Damaged fan
4) Abnormal refrigerant
1) Clear obstructions from the air cycle.
2) Clean the air filter
3) Check the fan.
4) Check the refrigerant temperature.
P7
System error 1) Wrong address-setting
2) Signal transmitting/receiving circuit of remote controller is abnormal.
3) Wrong SW6-setting
1) Check the address-setting.
2) Check with another remote controller. If check code other than “P7” appears, replace the original remote controller.
3) Check SW6 setting.
P8
Abnormality in outdoor unit 1) Wrong wiring of indoor/outdoor
connecting wire
2) Reversed phase
3) Protection device is working
4) Damaged outdoor coil thermistor
1) Check the indoor/outdoor connecting wire.
2) Change the connection of electric wiring.
3) Check the protection device.
4) Measure the resistance of the outdoor coil thermistor. If the resistance is normal, replace the outdoor controller board.
P1
P2
Abnormality of room
temperature thermistor (RT1)
Abnormality of indoor coil
thermistor (RT2)
1) Bad contact of thermistor
2) Damaged thermistor
1) Check the thermistor.
2) Measure the resistance of the thermistor. Normal resistance should be as follows.
0°C···15k 30°C ····4.3k 10°C ·····9.6k40°C·····3.0k 20°C ·····6.3k If the resistance is normal, replace the indoor controller board.
Page 59
59
3. SERVICE DATA INDICATION BY SWITCHES ON OUTDOOR CONTROLLER BOARD
Setting dip switches SW2 and SW3 on the outdoor controller board enables LED to show the output state and check code. Output state is shown by LED lighting, and check code by blinking. SW1 : Turning SW1 ON clears the check code. If SW1 is turned ON while the check code is blinking , the indication changes
to output state indication. NOTE : SW1 is usually available independent of SW3 setting. As an exception, when the check code shows a
reversed phase or an open phase during the power-on-reset state, SW1 is not available.
SW2 : SW2 is turned ON by pressing, and OFF by releasing.
When SW3-1 and SW3-2 are OFF, pressing SW2 changes indication between output state and check code alternately. When SW2 is turned On with SW3-1 OFF and SW3-2 ON, the compulsory defrosting starts.
SW3 : Output state indication items depend on the combination of SW3-1 ON/OFF and SW3-2 ON/OFF.
Changed alternately by pressing SW2.
SW3-1
SW3-2
LED
Check code
OFF
OFF
Outdoor coil thermistor is abnormal
Input circuit on controller board is abnormal
Open phase
63H2 function
51C function
26C function
Overheat protection
Reversed phase
Blinking
Output state
OFF
OFF
OFF
Outdoor coil temperature
(bit)
ON
1
2
4
8
16
32
64
128
1
2
4
8
16
32
64
128
256
512
1024
2048
4096
8192
16384
32768
ON
Fan output
step (bit)
OFF
ON
Total time of
compressor
operation(Hr)
ON
Compressor ON command from indoor controller
Heating operation command from indoor controller
During 63H1 function
Compressor ON
Outdoor fan ON
4-way valve ON
Bypass valve ON
Crankcase heater ON
Lighting
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
Page 60
60
3-1 Outdoor coil temperature
To obtain data on the outdoor coil temperature, add the number of bits of lighting LED, and see the graph below to find the
temperature.
3-2 Fan output step
To obtain data on the fan output step, add the number of bits of lighting LED, and see the graph below to find the fan
rotational frequency.
1PUH-1.6/2VKA
PUH-4YKSA
<50HZ>
50
Fan output step (bit)
Fan rotational frequency (rpm)
100 150 200 250
800
600
400
200
0
50
Fan output step (bit)
Type
Fan rotational frequency (rpm)
100 150 200 250
800
600
400
200
0
Type
100
C
Temperature
80
60
40
20
0
0
(Open 8 bits)(Open 8 bits)(Open 219 bits)
(Short 238 bits)(Short 238 bits)(Short 38 bits)
Number of bits
50 100 150 200 255
-20
-40
2PUH-2.5VKA
PUH-3VKA/3YKA
<50HZ>
3-3 Total time of compressor operation
Compressor operation time is indicated in 256 hour units. To obtain the compressor operation time, add the hours of lighting LED. During the compressor operation time indication, SW2 is not available.
3-4 Inspection code indication
When the inspection code is displayed twice during the normal operation, the operation changes to INSPECTION mode automatically. (On the first display of the inspection code, the mode changes to Restarting Protection Mode for 3 minutes and the operation restarts after 3 minutes.) W1) When the mode changes to INSPECTION by pressing the SW2 ¨ON¨, the operation will be continued if during
operation.
W2) When pressing except for the SW3-1 OFF and SW3-2 OFF, the mode changes to INSPECTION but the indication
code is not displayed.
W3) During the INSPECTION when the indoor controller operates OFF → ON of the compressor, output is displayed.
3-5 SW1 operation
The inspection code is deleted by operating the SW1 ¨ON¨ and also self-preservation is released, if during self­preservation. Or if while the inspection code is blinking, it changes output display.
Note) SW1 has no connection with the Dip SW3 setting and is available at any time. However, when the inspection code is
displayed initially (anti-phase, phase interruption), SW1 will be unavailable.
Page 61
61
Blinking
LED
Diagnosis of malfunction Cause Check point
LD1
Reversed phase Phases L1, L2, and L3are
connected improperly.
Check the power supply connection.
LD2
Open phase ● Phase L2is open.
Contact of protector, such as thermal switch, opened when power was turned on.
Check the power supply.
Check each protector.
LD3
Outdoor coil thermistor is abnormal. (Open circuit or short circuit)
Outdoor coil thermistor is broken.
Thermistor was connected incorrectly.
Measure the resistance of the thermistor.
Check the thermistor. If normal, replace the
outdoor controller board.
LD4
High pressure switch (63H2) function
62H2 was badly connected.
63H2 was working.
Check 63H2 and the outdoor fan motor.
Check if refrigerant supply is low.
Check if air cycle is short-cycled.
LD5
Thermal relay (51C) function 51C was connected
incorrectly.
51C was working.
Check 51C, the compressor, and power supply.
LD6
Thermal switch (26C) function. 26C was connected
incorrectly.
26C is working.
Check 26C.
Check if refrigerant supply is low.
Check if the capillary tube is clogged.
LD7
Over heat protection The thermistor is broken.
Coil temperature is over 67°C.
Measure the resistance of the thermistor.
Check the outdoor fan motor.
Check if air cycle is short-cycled.
LD8
Input circuit of outdoor controller board is abnormal.
Pulse input is abnormal. Replace the outdoor controller board.
Cause
1) Indoor/outdoor connecting wires are poorly connected. (Refer to next page.)
2) Power supply is poorly connected.
3) Connector or transformer is broken.
4) Fuse (6A) in the outdoor controller board is blown.
Check points
1) Check the connecting wires.
2) Check the power supply.
3) Check connectors and transformers.
4) Check the fuse.
4. TROUBLESHOOTING ACCORDING TO CHECK CODE
5.WHEN OUTDOOR UNIT DOES NOT WORK
Page 62
62
6. WRONG WIRING ON SITE
6-1 Between remote controller and indoor unit
If the wire is disconnected between the remote controller and the indoor unit, nothing is displayed on the remote controller when the POWER button is pressed. The beep sound will also not be heard.
6-2 Phenomenon due to wrong wiring between indoor and outdoor units
Wrong wiring Mode
Thermostat
Phenomenon
OutdoorIndoor
1 2 3
1 2 3
COOL
OFF Operation stops.
ON
4-Way valve turns ON. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF
Cooling operation. Several minutes later, check code “P8” appears on remote controller display.
ON Normal operation.
OutdoorIndoor
1 2 3
1 2 3
COOL
OFF Outdoor unit stops.
ON
Operation stops. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF Operation stops.
ON
Operation stops. 27 minutes later, check code “P8” appears on remote controller display.
OutdoorIndoor
1 2 3
1 2 3
COOL
OFF Outdoor unit stops.
ON
Operation stops. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF Operation stops.
ON
Operation stops. 27 minutes later, check code “P8” appears on remote controller display.
OutdoorIndoor
1 2 3
1 2 3
COOL
OFF Outdoor unit stops.
ON
Operation stops. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF Operation stops.
ON
Operation stops, 27 minutes later, check code “P8” appears on remote controller display.
OutdoorIndoor
1 2 3
1 2 3
COOL
OFF Outdoor unit stops.
ON
Operation stops. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF Operation stops.
ON
Operation stops. 27 minutes later, check code “P8” appears on remote controller display.
Disconnection between 1 and 1 or 2 and 2.
COOL
OFF Operation stops.
ON
Operation stops. 9 minutes later, check code “P8” appears on remote controller display.
HEAT
OFF Operation stops. 4-way valve turns OFF.
ON
27 minutes later, check code “P8” appears on remote controller display.
Disconnection between 3 and 3.
COOL
Normal operation.
HEAT
OFF Operation stops. 4-way valve turns ON.
ON
Operation stops. 27 minutes later, check code “P8” appears on remote controller display.
Page 63
63
Vanes do not work.
Vane motor does not work. Limit switch does not work. Connector is poorly connected. Vane motor is poorly assembled. Indoor controller board is damaged.
Unit stops after 5 to 20 seconds operation
Protection function is working.
Airflow display is OFF and button does not operate.
Indoor controller board deems the auto vanes are not attached to the unit. Horizontal angle can not be detected.
In this case, remote controller is normal.
Power ON/OFF button is not available.
Beep sound is heard, but display is turned OFF.
Beep sound is not heard, and display remains OFF.
Indoor/outdoor connecting wire is connected incorrectly. Indoor/outdoor connecting wire shorts. Compressor protector is damaged. Defroster is broken.
Remote controller is damaged. Transmission wire is poorly connected
Transmission wire is damaged. Connector is poorly connected. Indoor terminal block is poorly connected. Remote controller terminal block is poorly connected.
Vane motor is damaged. Vane motor relay is damaged.
Limit switch is damaged. The size of the cam is wrong.
Refer to check code on remote controller display. See page 58.
Indoor controller is damaged. Dip switch setting is wrong.
Indoor controller is damaged. Vane motor is damaged. Vane motor limit switch is poorly connected. Auto vane is wired after power is turned to ON.
Vane motor limit switch is damaged. Vane motor is damaged.
Poorly connected Disconnected
7. OTHER TROUBLES AND CAUSES
t
t
t
t t
t
t
t
t
t
t
t
t
“CENTRALLY CONTROLLED” is displayed.
Page 64
64
Symptom
LOSSNAY control switch does not work.
LOSSNAY air speed can not be controlled in interlock operation.
LOSSNAY control switch can not work during interlock operation. LOSSNAY control switch is effective only while Mr. SLIM is not operating.
LOSSNAY fan speed is fixed to HIGH during interlock operation. LOSSNAY fan speed LOW/HIGH can be switched only during LOSSNAY individual operation with the LOSSNAY control switch.
Cause
For LOSSNAY, troubleshooting refer to the LOSSNAY technical & service manual.
8.MR. SLIM/LOSSNAY INTERLOCK OPERATION
<Symptoms that are not malfunctions>
If any of the following symptoms occur, they are not malfunctions.
Page 65
65
10 SYSTEM CONTROL
1 Group control with
a single remote controller (See page 66.)
Unit
Remote controller
Unit Unit
Many units, installed at different locations, can be started and controlled with a single remote controller. The remote controller can be mounted in a different location using a non-polar two-wire cable, which can be extended up to 500m. A maximum of 50 units can be controlled with a single remote controller. All units operate in the same mode.
2 Both remote
ON/OFF and individual controls (See page 67.)
w Timer adapter
(PAC-SA89TA-E) is needed.
Optional adapter
Remote ON/OFF switch
Remote controller
Relay box
Unit
All units can be turned on or off simultaneously using a remote ON/OFF switch. Also, each unit can be controlled individually by each remote controller. During remote ON/OFF control, a message of “CENTRALLY CONTROLLED” is displayed on the LCD of the remote controller. This is available for both one unit control and several units control.
3 Individual control
by grouping remote controllers (See page 68.)
Unit
Remote controller
Unit Unit
By grouping the remote controllers in one place, several units installed at different locations can be controlled individually, and operation conditions of all units are visible without a special control board. The control method is the same as that of the single unit with a single remote controller.
4 Multiple remote
control display (See page 69.)
w Multiple display
adapter (PAC-SA88HA-E) is needed.
Unit
Remote controll display board
Remote controller
Unit Unit
Several units can be controlled with a remote control display board. Operation conditions of all the units are visible with the remote control display board. Individual control by each remote controller is also possible.
5 Auto restart
function (See page 69.)
Circuit breaker
Remote controller
A unit can be started or stopped with the circuit breaker on or off. Remote controller is also available. With this function, when the power is restored after power failure, the unit will restart automatically. (However, when the remote controller POWER ON/OFF button is OFF, the unit will not start.)
1. VARIETY OF SYSTEM CONTROL FUNCTIONS
Page 66
66
2. GROUP CONTROL WITH A SINGLE REMOTE CONTROLLER
A maximum of 50 units can be started in order according to the dip switch settings
2-1 How to wire
(1) Connect the remote controller to the double terminal block
on the indoor controller board of the master unit (No.0 unit). (See Figure 1.)
(2) Connect the double terminal block of the master unit to the
double terminal block of No.1 unit.
(3) Connect the double terminal block of No.1 unit to the double
terminal block of No.2 unit.
(4) Continue the process until all the units are connected with
two-wire cables. (See Figure 2.)
(5) Remove the connector CN40 from the indoor controller
board of each unit except the master unit. (See Figure 3.)
(6) Set the unit-address of each unit with SW2 on the indoor
controller board following the instructions below.
2-2 How to set unit-address
The unit-address also serves as a successive-start timer which starts each unit at intervals of 1 second. If two or more units have the same unit-address in a group control, operation stops due to system error. Be sure to set SW2 correctly following the instructions below. (1) Each lever of SW2 shows the number as follows.
SW2-1 : 1 SW2-4 : 8 SW2-2 : 2 SW2-5 : 16 SW2-3 : 4 SW2-6 : 32
(2) Total number of levers turned to ON shows the address of
the unit. For example, to set No.3 unit, turn ON SW2-1 and SW2-2.
(3) In this way, set from the. master unit to the last unit.
Do not forget to set the master (No. 0) unit.
2-3 Unit control
The remote controller can control all units ON/OFF, temperature,air flow, and swing louver. However, the thermostat in each unit turns ON or OFF individually to adjust to the room temperature.
Unit address & start delay in seconds.
SW2
Master (No. 0) unit
0
1
2
3
4
5
6
ALL OFF
No. 1 unit
1
1
2
3
4
5
6
1 ON
No. 2 unit
2
1
2
3
4
5
6
2 ON
No. 4 unit
4
1
2
3
4
5
6
3 ON
No. 8 unit
8
1
2
3
4
5
6
4 ON
No. 16 unit
16
1
2
3
4
5
6
5 ON
No. 32 unit
32
1
2
3
4
5
6
6 ON
Setting examples
To remote controller
To next unit
To next unit
The last unit dose not have this wire.
Next unit electrical box
Master unit electrical box
123LN
123
LN
Master unit
No.1 unit No.2 unit Last unit
2-wire cable
Figure 2
Figure 3
Indoor controller board
Should be removed from all units other than unit No.0:(Master Unit)
Figure 1
1
2
3
4
5
6
SW2
CN40
Page 67
67
3. REMOTE ON-OFF AND INDIVIDUAL REMOTE CONTROLS
This method is available to control one unit or any number of units. The following operations are available by connecting a relay, a timer adapter (PAC-SA89TA-E), and a remote ON/OFF switch to the system. Timer adapter is an optional part. Other parts are available on the market. (A) To start all units in order by remote ON-OFF switch (B) To stop all units simultaneously by remote ON-OFF switch (C) To switch between the remote ON-OFF control and the individual remote control
3-1 System
Figure 6 shows the case of three units.The same is the case with any number of units.
NOTE1 : Install the relay box where you can be serviced it easily. NOTE2 : For control circuit wiring, use a wire of No. 14 AWG or a control cable according to the power supply of control
circuit.
NOTE3 : When the power supply of the control circuit is 220/240V AC,
Do not connect the control circuit wire to the remote controller cable directly.
Do not place the control circuit wire and the remote controller cable into the same conduit tube.
3-2 Basic wiring
Caution : Before starting all units simultaneously by the remote ON-OFF switch, be sure to connect a sequence-start timer
into the remote ON-OFF circuit. Otherwise, a rush of starting current may damage the power supply.
Remote controller
power supply of control circuit
Remote ON/OFF
switch
2-wire remote controller cable
Figure 6
Relay box
Timer adapter cables
Timer adapter PAC-SA89TA-E
Power supply
Remote ON/OFF switch
No.1 unit relay box
No.2 unit relay box
Next unit
T
X2 X2
T
Glow switch or pilot lamp can be combined to easily identify the on-off mode of SW1 and SW2.
To No.1 unit
To No.2 unit
Timer adapter cables
Remote controller
T
X2
SW
1
SW2
T
X2
Page 68
68
w1 After all units start together, if SW2 is turned OFF, each unit can be individually stopped by each remote controller. w2 After all units stop together, if SW2 is turned OFF, each unit can be individually started by each remote controller.
Grouping the remote controllers allows individual control and centralized monitoring of units installed in different places without a special control board.
Remote control cables are extendable up to 500m. When the cable length exceeds 12m, use the double-insulated two-care cable such as Belden 9407. Also, the cable thickness must be No. 22 AWG or above.
When gathering the power ON/OFF switches of air conditioners near the remote controllers, you should also install the power ON/OFF switch near each unit to prevent electric trouble during servicing.
4. INDIVIDUAL CONTROL BY GROUPING THE REMOTE CONTROLLERS
3-3 Switch function of remote ON-OFF switch
SW1 (Switches between remote ON and OFF.)
ON
(Start)
OFF
(Stop)
All units start together. Individual control is not available.
All units stop together. Individual control is not available.
SW2
(Switches between remote ON-OFF and individual control)
ON
(Remote ON-OFF control)
Each unit can be controlled by each remote controller. Remote ON-OFF switch is not available.
OFF
(Individual control)
w1
w2
Remote controller cable (2-core)
Remote controller
Page 69
69
5. MULTIPLE REMOTE CONTROL DISPLAY
You can control several units with a multiple remote control display,by wiring an optional multiple display adapter (PAC-SA88HA-E) with relays and lamps on the market.
5-1 How to wire
(1) Connect the multiple display adapter to the connector CN51 on the
indoor controller board.
(2) Wire three of the five wires from the multiple display adapter as shown
in the figure below.
6. AUTO RESTART FUNCTION
By setting the dip switch SW1-10 to ON, the air conditioner can be started/stopped by power supply ON/OFF. If the air conditioner is OFF before the power failure, it will not start operation by power restore.
[Notes on Signs] X1:Relay (for check lamp) X2:Relay (for operation lamp) RL:Check Lamp GL:Operation Lamp
[Field supplied parts] Relays:12V DC with rated coil power consumption below 0.9W. Lamps:Matching to power supply voltage.
CN51
connector(5P)
GREEN
Power supply
Electrical insulation is needed.
Wiring at the actual place
Optional multiple display adapter
The maximumdistance between indoor board and relay is 10m.
YELLOW ORANGE
RED
BROWN
5
X1
X1
RL
GL
X2
X2
1
<Wiring >
Power supply
Remote controller cable
Relay box (Field supply)
Remote controller
Remote controller
Remote controller
3wires 3wires 3wires
2wires
No.1 unit No.2 unit No.3 unit
Muitiple remote control ON-OFF display (Field supply)
(Operation check)
<System>
Power supply
RL-1 GL-1
Multiple Remote Control Display
Multiple remote controller adapter
connect to the connector CN51
Relay box
5
X1-1
X2-1
1
<Wiring diagram>
RL-2 GL-2
RL-3
No.1 unit
GL-3
X1
X2
5
1
No.2 unit
X1
X2
5
1
No.3 unit
X1
X2
X1-2
X2-2
X1-3
X2-3
Remote controller
A B
Brown
Red
Orange
Remote controller
A B
Brown
Red
Orange
A : An optional timer adapter B : A single-throw switch
For remote control, connect the optional timer adapter (PAC-SA89TA-E)
<Wiring>
Indoor controller board
CN51
Page 70
70
11 DISASSEMBLY PROCEDURE
OPERATING PROCEDURE PHOTOS&ILLUSTRATION
Metal fixture
Screws
1. Removing the lower side of the indoor unit from the installation plate
(1) Remove the 2 screws.
Hang the indoor unit hangers to the catches on the installation plate.
Hanger of indoor unit
Catch of installation plate
2. Removing the right side panel
(1) Remove the 2 screws of the right side panel:one on the
bottom and the other on the upper right-hand side. (2) Disconnect the connector from the adapter case. (3) Sliding the right side panel to the right, pull it out toward
you.
Terminal cover
Electrical parts box cover
Connector
Connector
Indoor controller board
Right side panel
3. Removing the indoor controller board
(1) Remove the right side panel. (2) Remove the screw of the electrical parts box cover, and
remove the cover. (3) Disconnect the connectors on the indoor controller board. (4) To unhook the catches on the right-hand side of the indoor
controller board, pull the left-hand side toward you and lift
up the cover to the right. Then the indoor controller board
can be removed.
4. Removing the electrical parts box
(1) Remove the right side panel. (2) Remove the screw of the electrical parts box cover, and
remove the cover. (3) Remove the room temperature thermistor and the indoor
coil thermistor. (4) Disconnect the vane motor connector on the indoor
controller board. (5) Remove the 2 screws of the electrical parts box. (6) Disconnect the connector of the heater lead wire
connector. (7) Disconnect the connector of the fan motor lead wire. (8) Remove the electrical parts box.
Figure 1
Figure 2
Photo 1
Photo 2
Indoor coil thermistor
Catches
Screws
Room temperature thermistor
Electrical parts
box
Electrical parts
box cover
Indoor controller board
PKH-3FKA-E
Page 71
71
OPERATING PROCEDURE PHOTOS&ILLUSTRATION
(9) Remove the screws of the indoor controller board case,
and pull out the indoor controller board case. Then the transformer and the capacitor and relay can be serviced.
5. Removing the vane motor
(1) Remove the right side panel. (2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Remove the 2 screws of the vane motor, and remove the
motor from the shaft.
(4) Disconnect the vane motor connector on the indoor
controller board.
6. Removing the intake grills
(1) Remove the right side panel. (2) To remove the left side panel, remove the screw on the
bottom and the screw on the upper left-hand side. (See Figure 3.)
1. Press up this side of the left side panel to unhook the catch on the panel from the catch on the unit.
2. Slide the left side panel to the left to remove the panel.
Note: Fix the unit to the metal fixture securely (3) Remove the air filters. (4) Hold and press the centre cover to remove. (5) Remove the screws of the grills. (6) Pull the lower side of the grill toward you and slide the
upper to the right to remove the grills.
7. Removing the drain pan
(1) Remove the left and right side panels. (2) Remove the grills. (3) Remove the electrical parts box cover. (4) Loosen the drain hose band to remove. (5) Remove the 3 screws of the drain pan, and slide the drain
pan toward you to remove.
Screws
Drain pan
Drain hose band
Drain hose
Photo 6
Photo 5
Figure 3
Screws for grills
Slide to the right
Grills
Left side panel
Screws
Vane motor
Indoor controller board
Relay
Photo 4
Photo 3
Transformer
Capacitor
Electrical parts box
Indoor controller board case
Catch on the left side panel
Catch on the unit
Page 72
72
OPERATING PROCEDURE PHOTOS
8. Removing the lineflow fan and the fan motor
(1) Remove the left and right side panels. (2) Remove the grills. (3) Remove the electrical parts box. (4) Remove the drain pan. (5) Loosen the screw that fixes the lineflow fan to the fan
motor. (See Photo 7. )
(6) Remove the 4 screws of the motor fixture, and remove the
fan motor and the motor fixture at a time (See Photo 8.)
(7) Remove the screws of the left and right motor supports,
and remove the motor supports and the fan motor. (See Photo 9.)
(8) Remove the 2 screws on the left and right sides of the heat
exchanger, and pull the bearing support toward you. (See Photo 11.)
(9) Remove the screw of the centre support, and remove the
support. (See Photo 10. )
Pull the left-hand side of the heat exchanger toward you,
and remove the lineflow fan.
Photo 10
ScrewCentre support
Lineflow fan
Photo 9Photo 11
Photo 8
Photo 7
Screw
Motor support
Motor support
Screw
Fan motor
Motor fixture
Fan motor
Screw
Screw
Fan motor
Lineflow fan
Lineflow fan
Bearing support
Heat exchanger
(10)
Page 73
73
12 PARTS LIST
STRUCTURAL PARTS PKH-1.6FKA-E PKH-2FKA-E
1
9
9
3
24
10
5
6
7
8
3
3
Part No.
Specification
No.
Wiring
Diagram
Symbol
Recom-
mended
Q,ty
Price
Unit
Amount
Remarks
(
Drawing No.
)
Q,ty/set
PKH-1.6/2
FKA-E
R01 KV5 651 R01 47J 500 R01 KV5 096 T7W 580 058 R01 KV5 658 R01 KV5 635 R01 KV5 808 R01 KV5 623
— —
Part Name
(
BC25R572H06
)
(
BC25G057H07
)
1 2 4 1 1 1 1 1 2 2
1 2 3 4 5 6 7 8 9
10
FRONT PANEL AIR FILTER SCREW CAP SERVICE PANEL CORNER COVER BOX ASSEMBLY BACK PLATE UNDER COVER CATCH HOLDER PANEL CATCH
Page 74
Part No.
Specification
No.
Wiring
Diagram
Symbol
Recom-
mended
Q,ty
Price
Unit
Amount
Remarks
(
Drawing No.
)
Q,ty/set
PKH-1.6 PKH-2
FKA-E FKA-E T7W 570 762 R01 KV5 114 R01 KV5 105 R01 KV5 106 R01 566 103 R01 KV5 102 R01 KV5 130 R01 93W 530 R01 KW1 002 R01 KW2 002 R01 KV5 223 R01 KV5 527 T7W 70J 310 T7W 520 239 T7W 514 716
Part Name
PK4V30KA
250V 6.3A 3P(L/N/;)
1 1 2 1 1 1 1 1 1 1 1 1 1 1 1
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
1 1 2 1 1 1 1 1 1 1 1 1 1 1 1
MF
MV
I.B
F1<I.B>
TB2
FAN MOTOR LINEFLOW FAN RUBBER MOUNT BEARING SUPPORT SLEEVE BEARING BEALING MOUNT MOTOR SUPPORT NOZZLE ASSEMBLY LEFT ROTARY VANE RIGHT ROTARY VANE VANE MOTOR DRAIN HOSE INDOOR CONTROLLER BOARD FUSE TERMINAL BLOCK
74
ELECTRICAL PARTS PKH-1.6FKA-E PKH-2FKA-E
22
18
20
6
521
19
16 17
33
14 15
30
31
29
1
7
13
12
26
27
10
32
34
35
24
25
3
2
11
9
28
8
4
FILTER
CHECK MODE
TEST RUN
36
38
37
Page 75
75
Part No.
Specification
No.
Price
Remarks
(
Drawing No.
)
Q,ty/set
PKH-1.6 PKH-2
FKA-E FKA-E
T7W 512 716 T7W 517 716 R01 588 255 R01 J07 202 T7W 53J 799 T7W 53J 480 T7W 54J 480 T7W 54J 200 R01 12G 523 R01 KV5 135 R01 KV5 038 R01 KV5 059 R01 KV5 092 R01 KV5 048
— — —
— T7W 556 305 T7W 52J 675 T7W 51J 675 R01 08K 049 R01 07Y 092 T7W E03 202
Part Name
2P(1/2) 3P(1/2/3)
2.0µF 440V
12m
1 1 1 1 1 1
1 1 1
16
2 1 1 1 1 1 1 1 1 1 1 1 1
16 17 18 19 20
21
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38
1 1 1 1 1
1 1 1 1
16
2 1 1 1 1 1 1 1 1 1 1 1 1
TB5 TB4
C
RT2
T
R.B
RT1
(
BG25B573H05
)
(
BG25B846H11
)
(
BG02A326G06
)
(
BG02B718H05
)
Wiring
Diagram
Symbol
Recom-
mended
Q,ty
Unit
Amount
TERMINAL BLOCK TERMINAL BLOCK FAN MOTOR CAPACITOR INDOOR COIL THERMISTOR TRANSFORMER HEAT EXCHANGER HEAT EXCHANGER REMOTE CONTROLLER BOARD DRAIN SOCKET MOTOR COVER GUIDE VANE ARM VANE SLEEVE CENTER SUPPORT CONTROLLER CASE WATER SHIELD CONTROL BOX COVER TERMINAL COVER REMOTE CONTROLLER CABLE FAN GUARD (LEFT) FAN GUARD (RIGHT) REMOTE CONTROLLER COVER VANE SLEEVE ROOM TEMPERTURE THERMISTOR
Part number that is circled is not shown in the figure.
Page 76
76
ELECTRICAL PARTS PKH-2.5FKA-E PKH-3FKA-E PKH-4FKSA-E
5
1
3
31
10
7
21
18
322033
35 28 27
30 23 24
17
15 36
29
6
9
13
8
37·38
16
2
12
11
4
22
14
16
19
25
26
Part No.
Specification
No.
Wiring
Diagram
Symbol
Recom-
mended
Q,ty
Price
Unit
Amount
Remarks
(
Drawing No.
)
Q,ty/set
PKH-2.5
PKH-4PKH-3
FKA-E FKA-E
FKSA-E R01 12G 220 T7W 571 762 R01 12G 105 R01 16G 105
— — —
— R01 13G 115 R01 17G 115 R01 13G 114 R01 17G 114 R01 005 103 R01 12G 103
Part Name
1
2
1 1 1
1
1
1 1
1
2
3 4
5
6
7
8 9
1
2
1 1 1
1
1
1 1
1
2 1 1
1
1
1 1 1
MF MF
(
BG02H065H01
)
(
BG02H178H01
)
(
BG02A534H16
)
(
BG02A534H17
)
D10A4P70MS
FAN MOTOR FAN MOTOR RUBBER MOUNT RUBBER MOUNT MOTOR BAND MOTOR BAND MOTOR LEG MOTOR LEG RIGHT LINEFLOW FAN RIGHT LINEFLOW FAN LEFT LINEFLOW FAN LEFT LINEFLOW FAN SLEEVE BEARING SLEEVE BEARING
34
FILTER
CHECK MODE
TEST RUN
39
Page 77
Part No.
No.
10
R01 Z61 102
11
R01 KV5 102 12 13
R01 12G 529 14
R01 16G 529 15
R01 12G 223
16
17
R01 12G 002 18
R01 16G 002 19
R01 12G 621 20
R01 12G 063 21
R01 KV5 527
T7W 585 480 22
T7W 587 480
T7W 589 480 23
T7W 71J 310 24
T7W 520 239 25 26 27
T7W 509 716 28
T7W 517 716 29
R01 588 255 30
R01 576 255 31
T7W 50J 799 32
R01 06A 202 33
R01 22A 202 34
T7W 53J 200 35
R01 512 716 36
T7W 556 305 37
T7W 53J 675 38
T7W 71J 675 39
R01 08K 049
— —
— — —
— —
Part Name
Specification
BEARING MOUNT BEARING MOUNT BEARING BAND CENTER SUPPORT DRAIN PAN DRAIN PAN VANE MOTOR GUIDE VANE GUIDE VANE(WITH HANDLE) ARM AUTO VANE AUTO VANE CENTER COVER JOINT SHAFT DRAIN HOSE HEAT EXCHANGER HEAT EXCHANGER HEAT EXCHANGER INDOOR CONTROLLER BOARD FUSE
250V 6.3A CONTROLLER CASE CONTROLLER COVER TERMINAL BLOCK TERMINAL BLOCK
3P(L/N/
3P(1/2/3) TERMINAL COVER FAN MOTOR CAPACITOR FAN MOTOR CAPACITOR
2.0µF 440V
3.0µF 440V
TRANSFORMER ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR REMOTE CONTROLLER BOARD TERMINAL BLOCK REMOTE CONTROLLER CABLE
2P(1/2)
12m FAN GUARD FAN GUARD REMOTE CONTROLLER COVER
Q,ty/set
PKH-2.5
PKH-3 PKH-4
FKA-E FKA-E FKSA-E
1 1 1 1 1
1
20
4 3 2
1 1 1
1 1 1 1 1
1
20
4
3 2
1 1 1
1
1
1 2 1 1 1 1 1 1
1 1 1 1 1 1 2
1
Earth
1 2 1 1 1
)
1 1 1
1 1 1 1 1 1 2
1
1 1 1 1
1 1
26
4 4
2 1 1 1
1 1 2 1 1 1 1 1
1 1 1 1 1 1 1
2 1
Remarks
(
Drawing No.
(
BG02L462H02
(
BG25A543H07
(
BG25J821H02
(
BG25J821H02
(
BG25H301H02
(
BG25B573H05
(
BG02A648G01
(
BG02J608H05
)
) )
) )
)
)
)
)
Wiring
Diagram
Symbol
MV
I.B
F1.2<I.B>
TB2 TB4
C C
T RT1 RT2 R.B TB5
Recom­mended
Q,ty
Unit
Price
Amount
77
Page 78
78
Part number that are circled are not shown in the figure.
Part No.
No.
Price
Remarks
(
Drawing No.
)
R01 12G 661 R01 12G 662 R01 12G 691 R01 16G 692 R01 A17 500 R01 12G 811 R01 16G 811 T7W E01 812 T7W E00 812 T7W E00 641 T7W E01 641 R01 12G 523 R01 12G 808 R01 16G 808
— —
Part Name
Specification
Q,ty/set
PKH-2.5 PKH-3 PKH-4
FKA-E FKA-E FKSA-E
1 1 2
4 1
1
1
1 1
1
1 2 3 4 5
6
7
8
9
10
11
1 1 2
4 1
1
1
1 1
1
1 1 2 1 5
1
1
1 1
1
1
(
BG00A593GM3
)
(
BG00A593GM4
)
Wiring
Diagram
Symbol
Recom­mended
Q,ty
Unit
Amount
RIGHT SIDE PANEL LEFT SIDE PANEL INTAKE GRILLE INTAKE GRILLE AIR FILTER NOSE NOSE UNDER PLATE UNDER PLATE TOP PLATE TOP PLATE DRAIN SOKET BACK PLATE BACK PLATE BOX ASSEMBLY BOX ASSEMBLY
STRUCTURAL PARTS PKH-2.5FKA-E PKH-3FKA-E PKH-4FKSA-E
11
1
5
7
6
3
108
2
Page 79
13 OPTIONAL PARTS
1. REFRIGERANT PIPES
Service Ref. : PKH-1.6FKA-E/PKH-2FKA-E/PKH-2.5FKA-E/PKH-3FKA-E
Part No Pipe length Pipe size O.D. Connection method
Service Ref. : PKH-4FKSA-E
Part No Pipe length Pipe size O.D. Connection method
Note 1. How to connect refrigerant pipes.
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as the connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow. If piping length exceeds 5m,an additional charge of refrigerant is needed.
Note 2. The following main parts are contained in the optional refrigerant piping kit.
Heat insulating cover, vinyl tapes, nipples, sleeve and flange (for wall hole).
PAC-05FFS-E PAC-07FFS-E PAC-10FFS-E PAC-15FFS-E
5C 7C 15C10C
Liquid:{9.52 Gas:{15.88
Indoor unit:Flared Outdoor unit:Flared
PAC-SC51PI-E PAC-SC52PI-E PAC-SC53PI-E PAC-SC54PI-E
5C 7C 15C10C
Liquid:{9.52 Gas:{19.05
Indoor unit:Flared Outdoor unit:Flared
2. TIMER
When using a program timer, PAC-SK65PT, a program timer adapter (PAC-825AD) is also needed.
Service Ref.
Part No
Model Name
PKH-1.6/2FKA-E, PKH-2.5/3FKA-E, PKH-4FKSA-E
PAC-SC32PTA(with set back function)
Program timer
2-1 Program timer specifications
Service Ref. Part name Part No. Exterior dimensions (inch) Installation Type of clock Clock accuracy Display-Time
-Week
-Timer setting unit Program cycle Timer setting unit No.of set points Power rating Set back function
2-2 Feature of program timer
(1) Daily timer function
Daily timer can be set in 30 minutes units for up to 24 hours. Each unit can be set for unit ON, unit OFF, or setback operation.
(2) Setback operation (PAC-SK65PT)
Set back operation is useful for reducing running costs e.g. At a hotel with a 24-hour system
8:00~23:00 Cooling operation with set temperature at 26°C
23:00~8:00 Setback operation with 2 degrees of setback As shown in the chart on the right, the set temperature rises 2 degrees automatically during the setback operation. When the setback operation ends, normal operation will begin.
(3) Weekly timer function
Daily timer function can apply to each day of the week.
PKH-1.6/2FKA-E, PKH-2.5/3FKA-E, PKH-4FKSA-E Program timer PAC-SC32PTA 5-4/32 4-23/32 23/32(13012018mm) Wall mount Quartz ±50seconds/month at25°C Liquid crystal display Liquid crystal display Liquid crystal display 24 hours 30minutes 48/day 5V DC ±5%(Supplyed by Remote Controller) Provided
28˚C
˚C
26
8:00
Normal
operation
23:00
Setback
operation
8:00
Normal
operation
79
Page 80
80
2-3. How to connect program timer
(1) Install the program timer next to the remote controller the same way as the remote controller is installed. (2) Connect the program timer and the remote controller with a 6-wire cable as shown in the figure below
2-4 Names and functions <PAC-SC32PTA>
3. TIMER ADAPTER
This adapter is needed for system control and for operation via external contacts. Adapter connection is described on page
59.
NOTE:While the program timer is connected to the remote controller, the 24hour
ON/OFF timer on the remote controller will not operate.
ORN 1
2 3
BRN RED
Part No. PAC-SA89TA-E
SET/MONITOR
SET
SMTWTF S
MONITOR
PROERAN TIMER
PAC-SC32PTA
TODAY
ON
WEEKLY SETTING
OFF
ON
SET BACK
OFF
CLOCK DAILY TIMER
SET BACK
SET BACK
DAILY
SETTING
12 15 18 21 24
0361215
“MONITOR” :Indicates the current timer
setting. All switch expect MODE SELECTOR SW are invalidated then.This is the normal status.
“SET”: Set to “SET” mode for clock
adjustment, charge of week day, daily and weekly timer setting.
Push SW to advance the time. Each time the button is pushed the time advance by 1 minute, pushing continuously advances by 1 minute at 0.5 second interval, and when the lower digit of minute becomes 0 indication advances in 10 minutes unit.
SW is used for reversing the time. Each time the button is pushed the time reverses by 1 minute, pushing continuously reverses the time by 1 minute at 0.5 second interval, and when the lower digit of minute becomes 0 indication reverses in 10 minutes unit.
Pushing SW moves the week day light display in order of S M → T → W
enabling to set the week day.
Set back can be done in the range of 1,2,4,6 and 8°C.
WEEKLY TIMER SW
Used for setting timer in day of week unit.
DAILY TIMER SW
Used for timer setting in 30 minutes unit.
ON/SET BACK/OFF SW
Used to specify the time setting pattern.
SET BACK SETTING SW
Used for set back setting.
DAILY TIMER SETTING DISPLAY
24 hours is divided into 48 blocks and each block express 30 minutes. The block display consists of 3 pattern.
SET BACK DISPLAY
Indicates the setting set back range.
CURRENT TIME DISPLAY
During MONITOR status,current time is display. During Daily timer setting, a time desire for timer setting is displayed.
WEEKLY TIMER SETTING DISPLAY
Used for selection of if or not the day operation pattern set by PATTERN SETTING is to be applied in weekly day unit, setting.
SET/MONITOR DISPLAY
During SET is display, clock adjustment, change of weekly day, daily and weekly timer setting can be performed. During MONITOR is display, all switches except SET/MONITOR SW are invalidated. This is normal status.
WEEK DAY SETTING SW
Used for week day setting.
MODE SELECTOR SW
Using this switch select “MONITOR” or “SET” Mode.
CROCK ADJUSTMENT SW
Used for adjustment of the current time.
SET/MONITOR
SET
SMTWTF S
MONITOR
PROERAN TIMER
PAC-SC32PTA
TODAY
ON
WEEKLY SETTING
OFF
ON
SET BACK
OFF
CLOCK DAILY TIMER
SET BACK
SET BACK
DAILY
SETTING
12 15 18 21 24
0361215
FILTER
CHECK MODE
TEST RUN
4
2-wire cable
5-wire cable
To indoor unit
Connector CN1 Connector CN1
Page 81
81
BACK
ACTIVE BYPASS
POWER ON/OFF
DUAL
CENTRAL
AHEAD
MITSUBISHI ELECTRIC
ENGAGED
GROUP
ACTIVE BYPASS
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
DUAL CENTRAL
12345678910
4. MULTIPLE REMOTE CONTROLLER ADAPTER
This adapter is needed for remote indication (operation/check). Adapter connection is described on page 84.
5. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units. When using the PAC-805RC, the program timer adapter (PAC­825AD)is also needed. See page ##.
5-1. Dimensions Unit : mm
5-2. Functions
Part No. PAC-SA88HA-E
Part No. PAC-805RC
"ENGAGED" indicator When this indicator is lit, transmission is in
progress and all switches are inoperative.
DUAL/CENTRAL switch This change-over switch governing the
operation of the accessory remote controller.
"DUAL" Instructions from both the accessory
remote controller and the centralized remote controller are valid. (Priority given to the last instruction received.)
"CENTRAL" ON/OFF switching by the accessory
remote controller is invalidated. Control is by the centralized remote controller only.
Initial setting is "DUAL".
LCD Matrix Display This display indicates the operational
status of all connected units either by steady lighting or by flashing.
POWER ON/OFF switch Operation ON/OFF switch.
BACK AHEAD buttons These buttons are used to designate the attached unit(s). (They designate the unit that is centrally controlled.)
When group “00” is designated; collective ON/OFF instruction is sent to all units.
When group “01”-“16“ is designated; ON/OFF instruction is sent to the designated units only.
ACTIVE/BYPASS switch This is a change-over switch for the program timer. (It selects timer operation on the program timer.) Use “BYPASS” when a program timer is not connected. “ACTIVE” The switch turns ON/OFF operational instructions from the program timer automatically. “BYPASS” ON/OFF Operation is by the centralized remote controller only. Initial setting is “BYPASS”.
Independent “DUAL / CENTRAL” and “ACTIVE / BYPASS” setting of all the groups is possible. When the power supply to the centralized remote controller is cut due to power failure, all settings will return to original “DUAL” and “BYPASS”.
BACK
ACTIVE
BYPASS
POWER ON/OFF
DUAL
CENTRAL
AHEAD
MITSUBISHI ELECTRIC
ENGAGED
GROUP
ACTIVE BYPASS
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
DUAL CENTRAL
12345678910
117
117
BACK
ACTIVE
BYPASS
POWER ON/OFF
DUAL
CENTRAL
AHEAD
ENGAGED
GROUP
ACTIVE BYPASS
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
DUAL CENTRAL
12345678910
113
113
12
10 9 8 7 6 5 4 3 2 1
56.3
11
23.5
8
1 2 3 4 5
BRN RED ORN YLW GRN
Page 82
82
5-3 Connection method
(1) Connections in the power supply cord.
1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-wrap. Connect a single phase 200V AV (220, 230, 240V) to AN. As E is the GND terminal, be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap. Use a Ø1.6 (AWG 14) or above two-wire cable for the transmission line. CAUTION : Never connect the power supply cord to the transmission terminal-block.
(2) Connection method of centralized remote controller and power supply board.
1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable.
2. Wiring diagram
3. Be sure to set the maximum address number with the dip switch SW17 on the centralized remote controller.
ANE
T
(Y)
(W) (R) (O)
(BR)
5A
A
POWER SUPPLY
N
E
Fuse(5A)
Tie-wrap
Wiring has to be changed when a 200,230 or 240V power is used.
Tie-wrap
TRANSFORMER
Transmission
TERMINAL-BLOCK FOR TRANSMISSION
TERMINAL-BLOCK OF POWER SUPPLY
200
220
230
240
BACK
ACTIVE BYPASS
POWER ON/OFF
DUAL
CENTRAL
AHEAD
ENGAGED
GROUP
ACTIVE BYPASS
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
DUAL CENTRAL
12345678910
10 9 8 7 6 5 4 3 2 1
To adaptor's terminal-block
Centralized remote controller
Non-polar, two-wire cable
To adaptor's terminal-block
Power supply board box
Centralized remote controller
Power supply board
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER ON/OFF
AHEAD
Dip switch SW17
ENGAGED
GROUP
12345678910
GROUP SELECTION
PROGRAM
ACTIVE BYPASS
DUAL CENTRAL
TIMER
CONTROLLER OPERATION
Page 83
83
6. PROGRAM TIMER ADAPTER
This adapter is needed when a program timer(PAC-SC32PTA)or a centralized remote controller(PAC-805RC)is used.
6-1 Parts included
6-2 Connection method Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out the work.
Part No. PAC-825AD
(2) When the centralized remote controller is used, set the address number with the dip switch SW1 of the
program timer adapter.
1 ADAPTER··························1P 2 3-core cable···························1P
Length : 2m (6' 7")
4 4-core cable···························1P
Length : 2m (6' 7")
3 3-core cable···························1P
Length : 2m (6' 7")
5 5-core cable···························1P
Length : 2m (6' 7")
(1) Connections in the adapter box
1. Connect the power supply cord to the terminal-block and fix it in-place with a tie-wrap. Connect a single phase 200V (220, 230, 240V) AV to AN. As E is the GND terminal, be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap (when a centralized remote controller is being used). CAUTION : Never connect the power supply cord to the transmission terminal-block
Fig-1 Fig-2
TERMINAL-BLOCK FOR TRANSMISSION
Tie-wrap
Transmission cord
CN22
Dip switch
TRANS
CN1 CN21 CN51 CN30CN42 CN50 CN40
Fuse(5A)
TRANSFORMER
(AG)
SW1
ANE
POWER SUPPLY CORD
TERMINAL-BLOCK FOR POWER SUPPLY
Tie-wrap
Terminal block for transmission to program timer or centralized remote controller
Wiring has to be changed when 200V power supply is used.
(W)
CN22
TRANS
(B)
200
SW1
T
(Y)
240
220
5A
A N E
POWER SUPPLY
Page 84
7. DRAIN PUMP (Only for PKH-2.5FKA-E / PKH-3FKA-E / PKH-4FKSA-E).
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100-8310 TELEX J24532 CABLE MELCO TOKYO
cCopyright 1999 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Issued in Sep. 1999. NO.OC190 541 Printed in Japan
New publication, effective Sep. 1999.
Specifications subject to change without notice
Part No. PAC-SE89DM-E
Loading...