Mitsubishi PK-1.6GKL, PK-2GKL Service Manual

Page 1
SPLIT-TYPE, AIR CONDITIONERS
ON/OFF
TECHNICAL & SERVICE MANUAL
2000
No.OC230
Series PK
Indoor unit [Model names]
PK-1.6GKL
PK-2GKL
Wall Mounted
[Service Ref.]
PK-1.6GKL PK-2GKL
Indoor unit
This manual does not cover the following outdoor units. When servicing them, please refer to the service manual No.OC127 Revised Edition-A and this manual in a set. [Service Ref.]
PU-1.6VLJA2 PU-2VJA2
CONTENTS
1. PART NAMES AND FUNCTIONS ·······················2
2. SPECIFICATIONS················································4
3. DATA·····································································6
4. OUTLINES AND DIMENSIONS·························10
5. WIRING DIAGRAM ············································11
6.
7.
OPERATION FLOW-CHART
8.
MICROPROCESSOR CONTROL
9.
TROUBLESHOOTING
10. SYSTEM CONTROL ··········································35
11. DISASSEMBLY PROCEDURE ···························40
12. PARTS LIST ·······················································44
13. OPTIONAL PARTS·············································46
··································13
···········································29
······················12
···························16
Remote controller
Page 2
1 PART NAMES AND FUNCTIONS
Indoor Unit
Air intake
Guide vane
Filter
Air outlet
Air intake grille
Auto vane
2
Page 3
Wireless remote controller
When cover is open.
display
Lights up while transmission to the indoor unit is mode using switches.
display
OPERATION MODE display Operation mode display indicates which oper­ation mode is in effect.
• FUNCTION
Lights up when function are set..
display
TEST RUN CHECK display
CHECK&TEST RUN display indicates that the unit is being checked or test-run.
display
Displays when batteries are dead.
display
The vertical direction of airflow is indicated.
display
FAN SPEED display indicates which fan
speed has been selected.
ADDRESS display
Displays the refrigerant address.
UNIT NO. display
Displays the number of unit..
FUNCTION NO. display
Displays the mode.
SELECTION NO. display
Displays the selection number..
ADDRESS UNIT No. FUNCTION No. SELECTION No.
FUNCTION TEST RUN
CHECK
ON/OFF
MODE FAN
RESET
VANE
AM PM
AM PM
TEMP.
˚C
START
STOP
HR.
MIN.
display
SET TEMP. display indicates desired tempera­ture set.
CLOCK display
DIsplays the current time.
”display
Flashes when the current time is displayed.
TIMER display
Displays when in timer operation or when set­ting timer.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
“ ” “ ” display
Displays when the current time and the timer
time can be changed.
TEMP. button
display
The unit is turned ON and OFF alternately
each time the button is pressed.
When cover is open.
MODE SELECT button
Used to switch the operation mode between cooling , drying , mode.
FAN SPEED SELECT button
Used to change the fan speed.
VANE CONTROL button
Used to change the airflow direction.
ON/OFF
MODE FAN
RESET
VANE
TEMP.
START
STOP
HR.
MIN.
SET TEMPERATURE button sets any desired
room temperature.
TIMER CONTROL buttons
STOP (OFF timer): when this switch is set, the air conditioner will be automatically stopped at the preset time. START(ON timer): when this switch is set, the air conditioner will be automatically started at the preset time.
HR. and MIN.buttons
Buttons used to set the “hour and minute” of the current time and timer settings.
button
RESET button
3
Page 4
2
Guaranteed operating range
Upper limit Lower limit
Indoor D.B. 35˚C, W.B. 22.5˚C D.B. 21˚C, W.B. 15.5˚C
Outdoor
D.B. 52˚C (46˚C)
D.B. 21˚C
Cooling
Item
Service Ref.
PK-1.6GKL PK-2GKL
PK-2GKL
PU-2VJA
2
Single, 50Hz, 220/240V
2.44 / 2.48
11.3 / 10.8(98/96) 48 / 52
Munsell 5Y 7/1
Capillary tube
Hermetic
Inner thermostat, HP/LP switch
Line start
Plate fin coil
Propeller (direct) o 1
0.065
45 (1588)
870 (34-1/4) 295 (11-5/8) 650 (25-5/8)
60 (132)
9.52 (3/8)
15.88 (5/8) Flared Flared
w3 Max. 20m w3 Max. 30m
49
32 / 38
R-22 1.78 (3.9)
NHJ41VMD
2.0
Single, 50Hz, 220/240V
0.07
0.33(96/88)
0.4
Munsell 0.70Y 8.59/0.97
Plate fin coil
Line flow (direct) o 1
0.030
9-12 (318-424)
0 (direct blow)
Wireless remote controller & Built-in
36 - 43
20 (13/16)
990 (39)
235 (9-1/4)
340 (13-3/8)
16 (35)
27/19.0°C, 35/24°C
Cooling (JIS B8616,GB4706.32-96)
19,100
5,600
2.51/2.55
27/19.0°C, 35/24°C
Cooling (JIS B8616,GB4706.32-96)
13,300
3,900
1.49/1.59
PK-1.6GKL
Single, 50Hz, 220/240V
0.07
0.33(96/88)
0.4
Munsell 0.70Y 8.59/0.97
Plate fin coil
Line flow (direct) o 1
0.030
9-12 (318-424)
0 (direct blow)
Wireless remote controller & Built-in
36 - 43
20 (13/16)
990 (39)
235 (9-1/4)
340 (13-3/8)
16 (35)
PU-1.6VLJA
2
Single, 50Hz, 220/240V
1.42 / 1.52
6.7 / 6.9 (97/92) 30 /33
Munsell 5Y 7/1
Capillary tube
Hermetic
RH247VFC
1.2
Line start
Plate fin coil
Propeller (direct ) o 1
0.065
45 (1588)
49 870 (34-1/4) 295 (11-5/8) 650 (25-5/8)
45 (99)
R-22 1.3 (2.9)
9.52 (3/8)
15.88 (5/8) Flared Flared
w3 Max. 15m w3 Max. 20m
Condition Capacity w1 Total input w1
Service Ref. Power supply(phase, cycle,voltage)
Input
Running current (Power factor)
Starting current External finish Heat exchanger
Fan(drive) o No.
Fan motor output
Airflow (Low-High)
External static pressure Booster heater Operation control & Thermostat Noise level (Low-High) w2 Cond. drain conn. I.D.
Dimensions
Weight Service Ref. Power supply (phase, cycle, voltage)
Input
Running current /Power factor
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Heat exchanger
Fan(drive) o No.
Fan motor output
Airflow Defrost method Noise level w2
Dimensions
Weight Crankcase heater Refrigerant Charge
Pipe size O.D.
Connection method Between the indoor &
outdoor units
Btu/h
W
kW
kW
A (%)
A
kW
m
3
/min (CFM)
Pa (mmAq)
kW
dB mm (in.) mm (in.) mm (in.) mm (in.)
kg (lbs)
kW
A (%)
A
kW
kW
m
3
/min(CFM)
dB mm (in.) mm (in.) mm (in.)
kg (lbs)
W
kg (lbs) mm (in.) mm (in.)
Indoor, Outdoor D.B. / W.B.°C
Liquid
Gas
W
D H
W
D H
REFRIGERANT PIPING
OUTDOOR UNIT
Indoor side Outdoor side Height difference Piping length
INDOOR UNIT
Fan
Fan
( ) : PU-1.6VLJA2
SPECIFICATIONS
1. STANDARD SPECIFICATION
w1 Refrigerant piping length (one way) : 5m (16ft) w2 Noise level is measured in an unacoustic room based on JIS Z8731 conditions. w3 Up to 20m it is unnecessary to charge additional refrigerant.
4
Page 5
2. POWER SUPPLY & MODEL NAMES
Power supply Service Ref.(Indoor unit)
Service Ref.(Outdoor unit)
50Hz
1ph. 3ph.
PK-1.6GKL
PU-1.6VLJA
2
PK-2GKL
PU-2VJA
2
220, 230, 240V 380/220, 400/230, 415/240V
V : 220V 50Hz V : 230V 50Hz
Power supply (1 Phase)
Service Ref.
Current Input Starting courrent Outdoor unit
A
KW
A
A
KW
A
PK-1.6GKL
0.33
0.07
0.4
PU-1.6
PK-2GKL
0.33
0.07
0.4
PU-2
PK-1.6GKL
0.33
0.07
0.4
PU-1.6
PK-2GKL
0.33
0.07
0.4
PU-2
V : 240V 50Hz
Power supply (1 Phase)
Service Ref.
Current Input Starting courrent Outdoor unit
PK-1.6GKL
0.33
0.07
0.4
PU-1.6
PK-2GKL
0.33
0.07
0.4
PU-2
Notes : 1. Power supply key V(L) …1ph, 220, 230 240V, 50Hz
2.Primary power supplies for all indoor units are single-phase.
3. ELECTRICAL SPECIFICATION
(1) Rating conditions
Series PK Indoor Unit (Single Phase)
JIS B8616,GB4706.32-96
Indoor : D.B. 27°C (80°F), W.B. 19°C(66°F) Outdoor : D.B. 35°C (95°F)
5
Page 6
3 DATA
Service Ref. PK-2GKLPK-1.6GKL PK-2GKLPK-1.6GKL
Temperature T.C. Outdoor D.B.
21˚C (69.8˚F)
Indoor W.B.
16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚F) (64.4˚F) (66.2˚F)
(67˚F) (68˚F)
(71.6˚F)
3.9
4.2
4.3
4.4
4.4
4.7
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
25˚C (77˚F)
16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚F) (64.4˚F) (66.2˚F)
(67˚F) (68˚F)
(71.6˚F)
3.8
4.1
4.2
4.3
4.3
4.6
0.84
0.85
0.86
0.86
0.87
0.89
30˚C (86˚F)
16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚F) (64.4˚F) (66.2˚F)
(67˚F) (68˚F)
(71.6˚F)
3.7
3.9
4.1
4.1
4.2
4.5
0.90
0.92
0.93
0.93
0.94
0.96
32.2˚C (90˚F)
16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚F) (64.4˚F) (66.2˚F)
(67˚F) (68˚F)
(71.6˚F)
3.6
3.9
4.0
4.0
4.1
4.4
0.93
0.95
0.96
0.97
0.97
0.99
35˚C (95˚F)
16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚F) (64.4˚F) (66.2˚F)
(67˚F) (68˚F)
(71.6˚F)
3.5
3.8
3.9
4.0
4.0
4.3
0.96
0.99
1.00
1.00
1.01
1.04
40˚C (104˚F)
16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚F) (64.4˚F) (66.2˚F)
(67˚F) (68˚F)
(71.6˚F)
3.4
3.6
3.7
3.8
3.9
4.1
1.03
1.06
1.07
1.08
1.08
1.11
T.C.
5.6
6.0
6.2
6.2
6.4
6.7
C.F.
(T.I.)
5.5
5.9
6.0
6.1
6.2
6.6
5.3
5.6
5.8
5.9
6.0
6.4
5.2
5.5
5.7
5.8
5.9
6.3
5.1
5.4
5.6
5.7
5.8
6.2
4.9
5.2
5.4
5.4
5.5
5.9
Service Ref.
Temperature
T.C.
Outdoor D.B.
Indoor W.B.
C.F.
(T.I.)
40.6˚C (105˚F)
16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚F) (64.4˚F) (66.2˚F)
(67˚F) (68˚F)
(71.6˚F)
3.4
3.6
3.7
3.8
3.8
4.1
1.04
1.06
1.08
1.08
1.09
1.12
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
45˚C (113˚F)
16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚F) (64.4˚F) (66.2˚F)
(67˚F) (68˚F)
(71.6˚F)
3.2
3.4
3.6
3.6
3.7
3.9
1.10
1.12
1.14
1.15
1.16
1.20
46˚C (115˚F)
16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚F) (64.4˚F) (66.2˚F)
(67˚F) (68˚F)
(71.6˚F)
3.2
3.4
3.5
3.6
3.6
3.9
1.11
1.14
1.15
1.16
1.17
1.21
50˚F (122˚F)
16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚F) (64.4˚F) (66.2˚F)
(67˚F) (68˚F)
(71.6˚F)
52˚C (125.5˚F)
16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚F) (64.4˚F) (66.2˚F)
(67˚F) (68˚F)
(71.6˚F)
T.C.
C.F.
(T.I.)
4.8
5.2
5.3
5.4
5.5
5.9
4.6
4.9
5.1
5.2
5.3
5.7
4.6
4.9
5.1
5.1
5.2
5.6
4.4
4.7
4.9
4.9
5.0
5.4
4.3
4.6
4.7
4.8
4.9
5.3
Evaporator airflow (CMM)
12
0.10
0.80
0.12
0.69
Bypass factors
S.H.F. at rating conditions
12
Service Ref.
Refrigerant piping length (one way)
PK-1.6GKL PK-2GKL
40m (131ft)
— —
35m (115ft)
— —
30m (98ft)
0.944
25m (82ft)
0.954
20m (66ft)
0.982
0.964
15m (49ft)
0.987
0.975
10m (33ft)
0.992
0.985
5m (16ft)
1.0
1.0
1. PERFORMANCE DATA
Cooling capacity 50Hz
PK-1.6GKL, PK-2GKL
Notes: 1. T.C. : Total capacity (kW) …(kcal/h)=(kW)x860, (Btu/h)=4x(kW)x860
COOLING CAPACITY correction factors
C.F.(T.I.) : Correction factors of Total input(Indoor unit input + Outdoor unit input)
2. (°F)=32+9/5(°C)
3. Guaranteed operating range(cooling)
Lower limit … Indoor : D.B. 21°C(70°F) , W.B. 15.5°C(60°F)
Upper limit … Indoor : D.B. 35°C(95°F) , W.B. 22.5°C(72.5°F)
Outdoor : D.B. 21°C(70°F)
Outdoor : D.B. 46°C(115°F) W Outdoor : D.B. 52°C(125.5°F)…VJ,YJ
50Hz
6
Page 7
2. ELECTRICAL DATA
Input (kW) Current (A) Starting current (A) Input (kW) Current (A) Starting current (A)
Capacity (W) Total Input (kW)
IndoorOutdoor
Service Ref.
Indoor unit
Outdoor unit
3,900
1.49
0.07
0.33
0.40
1.42
6.7 30
5,600
2.51
0.07
0.33
0.40
2.44
11.3 48
PK-1.6GKL
PU-1.6VLJA
2
PK-2GKL
PU-2VJA
2
3,900
1.54
0.07
0.33
0.40
1.47
6.7 32
5,600
2.53
0.07
0.33
0.40
2.45
11.0 50
PK-1.6GKL
PU-1.6VLJA
2
PK-2GKL
PU-2VJA
2
3,900
1.59
0.07
0.33
0.40
1.52
6.9 33
5,600
2.55
0.07
0.33
0.40
2.48
10.8 52
PK-1.6GKL
PU-1.6VLJA
2
PK-2GKL
PU-2VJA
2
Air flow m3/
min
Air speed m/
sec
Coverage range m (ft)
PK-1.6GKL PK-2GKL
12
5.3
10(32.8)
12
5.3
10(32.8)
2-1 Rating conditions (JISB 8616,GB4706.32-96)
Indoor : D.B. 27°C, W.B. 19°C Outdoor : D.B. 35°C, W.B. 24°C Indoor unit …220V / 230V / 240V 50Hz 1phase Outdoor unit…220V / 230V / 240V 50Hz 1phase
3. OUTLET AIR SPEED AND COVERAGE RANGE
The air coverage range is the value up to the position where the air speed is 0.25m/sec. when air is blown out horizontally from the unit at the Hi notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furni­ture inside the room.
7
Page 8
4. STANDARD OPERATION DATA
Service Ref.
Mode Capacity W Input
kW
Indoor unit Service Ref.
Phase, Hz Volts Amperes
Outdoor unit Service Ref.
Phase, Hz Volts Amperes Discharge pressure Suction pressure Discharge temperature Condensing temperature
MPa
(
kg/cm
MPa
(
kg/cm
˚C ˚C
PK-1.6GKL
Cooling
3,900
1.49
PK-1.6GKL
1, 50 V A
220
0.33
PU-1.6VLJA
2
1, 50 V A
2
)
2
)
220
6.7
2.0
(20.6)
0.52
(5.3)
70 52
PK-2GKL
Cooling
5,600
2.51
PK-2GKL
1, 50
220
0.33
PU-2VJA
1, 50
220
11.3
2.0
(20.4)
0.44 (4.5)
72 52
2
Suction temperature Ref. pipe length
Intake air temperature
Discharge air
Indoor side Refrigerant circuit Electrical circuit Total
temperature
Intake air temperature
side
Outdoor
˚C
m
˚CD.B. ˚CW.B. ˚CD.B. ˚CD.B. ˚CW.B.
SHF
BF
7
5 27 19
14.2 35 24
0.80
0.10
3
5 27 19
11.6 35 24
0.69
0.12
The unit of pressure has been changed to Mpa on the international system of unit (SI unit system). The converted score against the traditional unit system can be gotten according to the formula below.
1(Mpa) = 10.2(kg/FF)
8
Page 9
5. NOISE CRITERION CURVES
UNIT
WALL
1m
1m
MICROPHONE
Ambient temperature 27:
Test conditions are based on JIS Z8731
PK-1.6GKL PK-2GKL
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
20
10
APPROXIMATE THRESHOLD OF REARING FOR CONTINUOUS NOISE
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NOTCH
Hi
Lo
SPL(dB)36LINE
43
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
9
Page 10
4
BYOFF
ON STAND
HEATCOOL
OFF BY
ON STAND
COOL HEAT
ÅrÇoÇoÅqÅ@ëOñÅ@ÇeÇqÇnÇmÇs ÅrÇoÇoÅqÅ@ëOñÅ@ÇeÇqÇnÇmÇs
r.SLI
m m
MITSUBISHI ELECTRICMITSUBISHI ELECTRIC
r.SLI
m m
MITSUBISHI ELECTRICMITSUBISHI ELECTRIC
21
Right side
Less than 15
70
245
60
235
Auto vane
Front view
Air intake
Air intake
Air intake
Air intake 198
53
340
715 225
340 80 280 233
990
21
Left side
Knock out hole for left piping Refrigerant pipe. Drain pipe. Wiring hole.
Knock out hole for right piping Refrigerant pipe. Drain pipe. Wiring hole.
60
70
245
(Necessary clearance for Unit installation)
Right side
Allowing clearances Front view
Less than 130
50 or more 150 or more
180 or more 30 or more
for bolts
Left-rear piping hole
left-rear piping
R52.5
R52.5
Installation plate balance point hole
Details of installation plate
49-[5hole for tapping screw
Knock out hole for right-rear piping
Right-rear piping hole
Unit center
14-[14hole
Knock out hole for
425
420
170
190
210
230
0
322 w2
0 35
55 80
130 190
230 272 310
0
3595150
205
260
320
345
495
20
75
135
190
245
300
360
405
495
32
0
w1 Sleeves are available on the market. w2 This size shows the lower end of through hole.
[90~[100[90
Through hole
Sleeve w1
1.6 . 2
Model
R52.5
R52.5
Gas pipe
Liquid pipe
Terminal block for
Terminal block to outdoor unit
Filter grip
Service panel (Power supply access)
5/8F
Gas pipe
Liquid pipe
3/8F1.6 . 2
Model
(Flexible hose total length800)
(Right side piping
installation)
(Left side piping
installation)
Drain pipe (VP-20)
Front view(to open the grille)
700
449
86
581 54
31 280
35
Knock out hole for under piping Refrigerant piping.Drain pipe. Wiring hole
12-Louvers(manual)
Air outlet
Lower side
80
50
395400
190
60
70 35
79
160 40
235
705
power supply
153
OUTLINES AND DIMENSIONS
1.INDOOR UNIT PK-1.6GKL PK-2GKL
Unit : mm
10
Page 11
5
SYMBOL P.B I.B
CN1 CN2 SW17 SW18
RU BZ LED1 SW2
C MF MV TB2~TB6 RT1
RT2
R.B
W.B
CN2L CN51 FC SW1 SW2 SW3 SW5 SW6 SW7 SW8 SW9
INDOOR POWER BOARD INDOOR CONTROLLER BOARD CONNECTOR (LOSSNAY) CONNECTOR (CENTRALLY CONTROL) FAN PHASE CONTROL SWITCH (FUNCTION SELECTOR) SWITCH (ADDRESS SELECTOR) SWITCH (EMERGENCY OPERATION) SWITCH (MODEL SELECTOR) SWITCH (TWIN / TRIPLE SELECTOR) SWITCH (MODEL SELECTOR) SWITCH (OPTION) SWITCH (MODEL SELECTOR)
RELAY (FAN MOTOR) FUSE (6.3V / 250V) VARISTOR LED (DC 12V POWER) LED (DC 5V POWER) CAPACITOR (FAN MOTOR) FAN MOTOR VANE MOTOR TERMINAL BLOCK ROOM TEMPERATURE THERMISTOR (0: / 15k" , 25: / 5.4k" / DETECT) PIPE TEMPERATURE THERMISTOR / LIQUID (0: / 15k" , 25: / 5.4k" / DETECT)
REMOTE CONTROLLER BOARD (OPTION) CONNECTOR (PROGRAM TIMER) CONNECTOR (REMOTE SWITCH) SWITCH (ADDRESS SELECTOR) SWITCH (FUNCTION SELECTOR) WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT BUZZER LED (RUN INDICATOR) SWITCH (COOLING ON / OFF)
NAME SYMBOL
I.B
SYMBOLNAME NAME X4 F1, F2 ZNR LED1 LED2
WIRING DIAGRAM
PK-1.6GKL PK-2GKL
NOTES :
1. Since the indoor fan motor (MF) is connected with 230, 240V power. If 220V power is used, change the dip switch (SW8) on the indoor controller board as shown in fig : w2.
fig w2
Indoor fan motor (MF)for 220V.
ON OFF
1
SW8
2 3 4
56
ON OFF
1
SW8
2 3 4
56
2. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
3. Symbols used in wiring diagram above are, : Connector, : Terminal block.
4. Emergency operation If remote controller or microcomputer fails but there is no other trouble , emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board.
11
Page 12
6
INDOOR UNIT PK-1.6GKL PK-2GKL
OUTDOOR UNIT PU-1.6/2J series
Indoor heat exchanger
Pipe temperature thermistor RT2
Distributor
Flexible tube
Flared connection
Flared connection
Refrigerant pipe [15.88(5/8") (with insulator) option
Refrigerant pipe [9.52(3/8") (with insulator) option
Ball valve
Low pressure switch
Charge pIug
Check plug
High pressure switch
Outdoor heat exchanger
Strainer
Capillary tube for injection (Only PU-2VJA
2)
Capillary tube
Compressor
Accumulator
Ball valve (with service port)
flow of refrigerant
PU-1.6 (O.D.3.2 I.D.1.8 OR900) PU-2 (O.D.4.0 I.D.2.0 OR430)
REFRIGERANT SYSTEM DIAGRAM
PK-1.6GKL / PU-1.6VLJA2 PK-2GKL / PU-2VJA2
Unit : mm
12
Page 13
7
OPERATION FLOW-CHART
MAIN OPERATION
START
YES
NO
NO
NO
YES
NO
NO
w1
YES
YES
YES
Set time
complete
YES
NO
w2
Trouble
Trouble STOP
PROTECTION DEVICE
SELF HOLD
NO
YES
w3
Remote controller
trouble display
Remote controller
operation display
Operating mode
(COOL)
NO
Operating mode
(DRY)
NO
YES
COOL operation
YES
DRY operation
Power circuit
breaker
1
YES
Check SW
ON twice
Operation SW
ON
“OFF” timer
NO
“ON” timer
Set time
complete
STOP
PROTECTION DEVICE
SELF HOLD RELEASE
Remote controller
indicator lamp OFF
w6
Indoor side
FAN operation
w4
Fan STOP
Outdoor side
w5
Compressor OFF
Fan STOP
w1 In addition, the centralized control and remote control can be operated. w2 The modes which indicate the sources of trouble are listed below.
EO-Signal transmitting/receiving error
P1-Room temperature thermistor malfunction
P2-Pipe temperature thermistor malfunction
P4-Drain sensor malfunction
P5-Drain overflow
P6-Coil frost
P7-System error
P8-Outdoor unit trouble
w3 The CHECK switch will indicate if an error has occurred in the past. w4 Fan runs on low speed for 1 minute in order to remove overheat air. w5 The 3-minute time-delay functions after compressor stops. w6 In FAN mode, fan speed and vane operation depend on the remote controller setting. (Compressor is OFF.)
13
Page 14
COOLING OPERATION
COOL operation
NO
NO
NO
Vane setting notch
Initial
COOLING
w8
50 deg downward angle 60 deg downward angle
NO
Vane horizontal
w9
YES
Vane initial
setting
Vane
YES
Fan speed
LOW
YES
Downward discharge
1 hour
YES
airflow
Compressor
thermostat
ON
Allowance
cancel
NO
NO
YES
YES
NO
w11
YES
3-minute
time delay
6-minute time delay
3-minute
compressor
operation
w10
Coil frost protection
Cooling area
NO
NO
YES
NO
YES
NO
Allowance
period
NO
6 minute
time delay
Allowance set
YES
Coil frost protection
YES
10-minute
NO
Allowance cancel
NO
Compressor ON
compressor
operation
YES
Coil frost
prevention
NO
16-minute
compressor
operation
YES
Indoor pipe
temperature is
1°C or lower
NO
1
YES
YES
Coil frost
prevention
Compressor OFF
Pipe
YES
YES
NO
NO
3-minute time delay
temperature is 10°C or higher
Defrosting protection
detection temperature
-1°C or lower
6-minute time delay
Coil frost
prevention release
NO
1 min continue
FAN speed
FAN speed LOW 5 min
LOW
elapse
YES
NO
YES
Outdoor unit
trouble
w8 When operation stops or changes to cooling or dry mode, the auto vane turns to a horizontal angle. If operation changes
during auto vane SWING, the auto vane will continue to swing.
w9 When operating TEST RUN, the thermostat will be continuously ON. w10After 3 minute compressor operation, if the pipe temperature thermistor reads -15°C or below for 3 minutes, the compres-
sor will stop for 6 minutes.
w11Heating area : Pipe temperature is more than 5 degrees above the room temperature.
Cooling area : Pipe temperature is more than 5 degrees below the room temperature. FAN area : Pipe temperature is within 5 degrees either way of the room temperature.
14
Page 15
DRY OPERATION
DRY
operation
Vane
setting notch
NO
YES
NO
Initial dry
operation
YES
Vane initial setting
w12
Room temperature is
18°C or lower
NO
During
compressor ON
YES
3-minute
compressor
operation
YES
Compressor & thermostat ON
YES
w8
w9
NO
NO
YES
3-minute
time delay
NO
Compressor &
thermostat
ON
NO
YES
w9
Compressor ON
time completes
YES
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
1
w8~9 Refer to page 20~21. w12 When room temperature is 18°C or below, the compressor cannot operate.
When room temperature rises over 18°C, the compressor starts after a 3-minute time delay.
w13 Compressor ON time is decided by room temperature. Refer to page 20~21.
w14 In dry operation, compressor ON makes the fan speed LOW. Also, when the compressor OFF and the pipe temperature
is 26°C or less, the fan stops, or when the compressor OFF and the pipe temperature is below 6°C, the fan speed changes to LOW mode. It is not possible to set the fan speed with the remote controller.
NO
w14
10-minute
compressor
OFF
YES
Compressor ON
time set
Compressor ON
Fan speed LOW
NO
w13
w14
15
Page 16
8
FILTER CHECK MODE TEST RUN
ON/OFF
CHECK
ADDRESS UNIT No. FUNCTION No. SELECTION No.
AM PM
AM PM
TEST RUN
FUNCTION
˚C
TEMP.
MICROPROCESSOR CONTROL
1. OUTLINE OF MICROPROCESSOR CONTROL
INPUT to remote controller
OFF-ON switching.
COOL/DRY-FAN selector switching.
Thermostat setting.
TIMER mode selector-switching and Timer
setting.
HIGH-LOW fan speed switching.
AUTO Vane selector (AIR DISCHARGE)
switching.
TEST RUN switching.
CHECK mode switching.
(Self diagnostic trouble shooting)
Indoor unit
Remote controller board
Processes and transmits orders.
Non-polar, two-wire cable maximum length 500 meters (WIRED only)
Signal
12VDC
OUTPUT to remote controller
Remote controller
LCD indicator
WIRED REMOTE
CONTROLLER (OPTION)
INPUT from indoor unit
Room temperature thermistor (RT1)
Pipe temperature thermistor (RT2)
OUTPUT to indoor unit
Auto vane’s angle setting.
Emergency stop.
Independent Control of Outdoor Unit
Compressor protection device working
Crankcase heater control ON-OFF.
Indoor controller board
Receives orders from remote controller and temperature data from indoor unit.
Processes orders and data.
Controls indoor and outdoor operation.
Self diagnostic function.
w System control operation. w Emergency operation. w Set by dip switch on indoor controller board.
Transmits the power to remote controller.
12
Non-polar two-wire cable
Outdoor unit
12VDC
1 2
WIRELESS
REMOTE
CONTROLLER
Compressor and outdoor fan : ON­OFF.
OUTPUT to outdoor unit
16
Page 17
2. INDOOR UNIT CONTROL
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Compressor
ON
ON
LOW or HIGH LOW or HIGH
OFF
OFF
ON
OFF
OFF
Operation starts by POWER button ON.
Operation stops by POWER button OFF.
Room temperature becomes equal to set temperature.
Room temperature rises above set temperature.
FILTER
CHECK MODE
TEST RUN
ON/OFF
CHECK
ADDRESS UNIT No. FUNCTION No. SELECTION No.
AM PM
AM PM
TEST RUN
FUNCTION
˚C
TEMP.
2-1 COOL operation
WIRED REMOTE
CONTROLLER (OPTION)
<COOL operation time chart>
WIRELESS REMOTE
<How to operate>
1 Press POWER ON/OFF button. 2 Press the MODE button to display
3 Press the TEMP. button to set the desired temperature.
NOTE: Set temperature changes 1°C when the or
button is pressed one time. Cooling 19 to 30°C
CONTROLLER
w1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this
period has ended.
(1) Compressor control
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when room temperature is higher than set temperature.
The compressor stops when room temperature is equal to or lower than the set temperature. The compressor maintains the previous state when the discharge temperature minus the set temperature is 0°C or more, or lower than 1°C.
3 The compressor stops in check mode or during protective functions. 4 Coil frost prevention
To prevent indoor coil frost, the compressor will stop when the pipe temperature thermistor (RT2) reads 1°C or below after the compressor has been continuously operated for at least 16 minutes or more. When the pipe temperature rises to 10°C or above, the compressor will start in a 3-minute(w2) time delay. w2 When the pipe temperature is -1°C or less, the compressor starts in 6 minutes.
NOTE : By turning OFF the dip switch SW1-3 on indoor controller board, the start temperature of coil frost prevention changes
from 1°C to -3°C.
17
Page 18
5 Coil frost protection
10 50 60
10
30
50
60
AUTO RETURN
When indoor coil temperature becomes -15°C or below,coil frost protection will proceed as follows.
<Start condition>
After the compressor has been continuously operated for 3 minutes or more,and the indoor coil temperature has been
-15°C or below for 3 minutes,the coil frost protection will start.
<Coil frost protection>
Compressor stops for 6 minutes,and then restarts. lf the start condition is satisfied again during the first 10 minutes of compressor operation,both the indoor and outdoor units stop, displaying a check code of “P6” on the remote controller.
<Termination conditions>
Coil frost protection is released when the start condition is not satisfied again during the allowance, or when the COOL mode stops or changes to another mode.
(2) Indoor fan control
Indoor fan speed LOW/HIGH depends on the remote controller setting. However, if an outdoor unit abnormality is detected, the indoor fan speed will be LOW, regardless of the remote controller setting.
(i ) Fan speed LOW/HIGH depends on the remote controller setting regardless of the thermostat ON/OFF. (ii) Fan speed will remain on LOW if an abnormality in outdoor unit is detected. (5 minutes)
NOTE : Fan stops immediately if the unit stops or the check mode is started.
(3) Auto vane control
Auto vane position is set to 10 degrees airflow at the start-up of COOL operation. (a) Vane position set mode & swing mode. ( i ) Every time VANE button is pressed, setting will be changed . (ii) Airflow direction can be changed with VANE button.
1 Fan speed : LOW
10°
50°
60°
SWING
2 Fan speed : HIGH
10°
30°
50°
60°
SWING
<VANE POSITION>
1 Fan speed : LOW
2 Fan speed : HIGH
As for the unit opreted with only wired remote controller, When 50 degrees or 60 degrees airflow is selected with the LOW fan speed in COOL operation, “1Hr” will appear right side of the air direction display. One hour later, the airflow direction returns to 10 degrees automatically and “1Hr” will disap­pear. If the airflow direction is set to 10 degrees during “1Hr” indication, the time counting for AUTO RETURN is cancelled.
18
Page 19
(4) Detecting abnormalities in the outdoor unit
After the compressor has been continuously operated for 3 minutes, if the difference between the pipe temperature and room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the differ­ence is still out of RANGE C,the outdoor unit is functioning abnormally. Thus, the compressor stops and check code “P8” appears on remote controller. RANGE A: Pipe temperature is more than 5 degrees above room temperature. RANGE B : Pipe temperature is within 5 degrees either way of room temperature. RANGE C : Pipe temperature is more than 5 degrees below room temperature.
Pipe temperature minus room temperature
(degree)
+5
0
-5
RANGE A
RANGE B
RANGE C
19
Page 20
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Compressor
ON
ON
DRY MODE
DRY MODE
OFF
OFF
ON
OFF
OFF
Operation starts by POWER button ON.
Operation stops by POWER button OFF.
Room temperature becomes equal to set temperature.
Room temperature rises above set temperature.
2-2 DRY operation
FILTER
CHECK MODE
TEST RUN
ON/OFF
CHECK
ADDRESS UNIT No. FUNCTION No. SELECTION No.
AM PM
AM PM
TEST RUN
FUNCTION
˚C
TEMP.
WIRED REMOTE
CONTROLLER (OPTION)
<DRY operation time chart>
<How to operate>
1 Press POWER ON/OFF button. 2 Press the MODE button to display “ ” 3 Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is pressed one time. Dry 19 to 30°C
WIRELESS REMOTE
CONTROLLER
w1 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this
period has ended.
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2The compressor stops in check mode or during protective functions.
20
Page 21
4The compressor will not start when the room temperature is below 18°C.
Compressor OFF
6°C or more
Below 6°C
STOP
Pipe temp. Fan
LOW
All LOW
Compressor ON
The compressor starts intermittent operation when the power is turned ON with room temperature above 18°C. The com­pressor ON/OFF time depends on the thermostat ON/OFF and the following room temperatures.After 3-minute compres­sor operation,
If the room temperature thermistor reads above 28°C with thermostat ON, the compressor will operate for 6 more min­utes and then stop for 3 minutes.
If the room temperature thermistor reads above 26°C~28°C with thermostat ON, the compressor will operate for 4 more minutes and then stop for 3 minutes.
If the room temperature thermistor reads 24°C~26°C with thermostat ON, the compressor will operate for 2 more min­utes and then stop for 3 minutes.
If the room temperature thermistor reads below 24°C with thermostat ON, the compressor will stop for 3 minutes.
If the thermostat is OFF regardless of room temperature, the compressor will stop for 10 minutes.
5Coil frost protection
Coil frost protection in DRY operation is the same as in COOL operation.
6Coil frost prevention
Coil frost prevention does not operate in DRY operation.
(2) Indoor fan control
The indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote con­troller. Also, the fan runs on LOW speed when the pipe temperature is 6°C or more, or the compressor is OFF and the pipe temperature is below 6°C.
(a)During compressor OFF
When the pipe temperature is 6°C or above, the indoor fan will stop.
When the pipe temperature is below 6°C, the indoor fan will run on LOW speed.
(b)During compressor ON
The indoor fan runs on LOW speed. <Dry mode>
The fan notch is controlled by the pipe temperature every 30 seconds.
Fan control in DRY operation.
(3) Auto vane
Same as in COOL operation
(4) Detecting abnormalities in the outdoor unit
An abnormality in the outdoor unit can not be detected in DRY operation.
21
Page 22
10°
1
30° downward
2
50° downward
3
60° downward
4
swing
5
2-3 Auto vane control
FILTER
CHECK MODE
TEST RUN
ON/OFF
CHECK
ADDRESS UNIT No. FUNCTION No. SELECTION No.
AM PM
AM PM
TEST RUN
FUNCTION
˚C
TEMP.
<How to operate>
To change the air flow direction, press VANE button.
WIRED REMOTE
CONTROLLER (OPTION)
WIRELESS REMOTE
CONTROLLER
1
10°
2
30°
3
50°
4
60°
Available in COOL operation with fan speed on HIGH . Unavailable in DRY operation. If fan speed changes from HIGH to LOW during 30° downward airflow in COOL mode, the direction automat­ically changes to 10°.
Changes by pressing the VANE button.
(1) COOL/DRY operation
At the start-up of COOL or DRY operation, the airflow direction in automatically set to 10°. After, it can be changed to another direction with VANE button on the remote controller.
<Auto return>
When 50° or 60° airflow is set with fan speed in LOW, “1Hr” appears right side of the air direction. One hour later the direction changes to 10 degrees, automatically and “1Hr” disappears. (Only wired remote controller)
22
Page 23
2-4 TIMER operation
OFF
ON/OFF
CHECK
ADDRESS UNIT No. FUNCTION No. SELECTION No.
AM PM
RESET
AM PM
TEST RUN
FUNCTION
˚C
MODE FAN
VANE
TEMP.
START
STOP
HR.
MIN.
(1) WIRED REMOTE CONTROLLER (OPTION)
FILTER
CHECK MODE
TEST RUN
<Timer setting example>
This setting will stop the air conditioner in 8 hours. With the lapse of time, time display changes in 1 hour units, showing remaining time.
<Timer function>
AUTO STOP ·········The air conditioner stops after the set time lapses. AUTO START ········The air conditioner starts after the set time lapses. AUTO OFF ············Timer is not active.
<How to operate>
1. Press POWER ON/OFF button.
2. Press “ ” button to select AUTO STOP or AUTO START.
3. Press “ ” button to set desired time. Time setting is in 1 hour units for up to 24 hours. Each time HOURS button is pressed, set time increases by 1 hour. When HOURS button is pressed and held, the set time increases by 1 hour every 0.5 seconds.
4. To cancel the timer operation, press POWER ON/OFF button.
(2) WIRELESS REMOTE CONTROLLER
B
A
1
24
3
<How to operate>
1 Press the ON/OFF button to turn it ON. 2 Press the STOP or START button (TIMER SET).
·Time can be set while the following symbol is displayed.
OFF timer : A , B is displayed. ON timer : A , B is displayed.
3 Use the HR. and MIN. buttons to set the desired time. 4 Cancelling the timer.
To cancel the OFF timer, press the STOP button. To cancel the ON timer, press the START button.
·It is possible to combine both OFF and ON timers.
·Pressing the ON/OFF button of the remote controller during
timer mode to stop the unit will cancel the timers.
23
Page 24
TEST RUN
2-5 Test run
ON/OFF
CHECK
ADDRESS UNIT No. FUNCTION No. SELECTION No.
AM PM
RESET
AM PM
TEST RUN
FUNCTION
˚C
MODE FAN
VANE
TEMP.
START
STOP
HR.
MIN.
(1) WIRED REMOTE CONTROLLER (OPTION) <Before test run>
After installing, wiring, and piping the indoor and outdoor units, check for refrigerant leakage, looseness in power supply or control wiring, and mistaken polarity.
Use a 500-volt megger to check the resistance between the power supply terminal block and ground to make sure that it is at least 1.0MΩ.
Attention: Do not use the air conditioner if resistance is less than 1.0MΩ.
Remote controller
Turn on main switch.12 hours before proceeding to step 2 to allow
1
for crankcase heater operation. Push the TEST RUN button twice and indication of TEST RUN will
2
be shown on the liquid crystal display. Press the button, COOL/DRY to confirm that cool air is
3
blown out. Push button LOW/HIGH to check that the fan speed changes
4
properly. Check the operation of outdoor unit fans.This unit controls the rota-
tion speed and performance capacity of fans. ln some cases,it may rotate at low speed as the condition of outside air requires and the speed will be kept unless the performance has become deficient.
TEST RUN button
5
Therefore,when the condition of outside air demands,there may be such cases as the fan stops or rotates reversely.
TEST RUN
Indoor coil temperature code
Display
Display
Please note that these symptoms are not malfunction. After the check is finished leave the test run mode, push the power
ON/OFF button.
6
It can also be stopped by pushing the timer MODE button.
*The above figure shows the state of TEST
RUN at cooling operation.
When a TEST RUN is started,the timer shall be set to 2 hours. The unit will automatically turn off after 2 hours.
(2) WIRELESS REMOTE CONTROLLER
82
BA
7
5 4 6
3
<Before test run> Measure an impedance between the power supply terminal block on the outdoor unit and the ground with a 500 V Megger and check that it is equal or greater than 1.0M"".
1 Turn on the main power to the unit.. 2 Set the Nrm/Set selector switch (on the back of the controller)to <Set>.
AThe FUNCTION , TEST RUN and CHECK begin to blink.
3 Press the MIN. button.
B TEST RUN and current operation mode are displayed.
4 Press the MODE button to activate COOL mode, then check
whether cool air in blown out from the unit.
5 Press the
FAN button and check whether strong air is blown
out from the unit.
5 Press the
VANE button and check whether the auto vane
operates properly.
7 Press the ON/OFF button to stop the test run.
8
After trial run is complete, set the Nrm/Set selector switch to <Nrm.>
Note :
·Point the remote controller toward the inside unit’s receiver
while steps
33
though 77.
·It is not possible to run the unit in FAN or DRY mode.
24
Page 25
(1) Pipe temperature code
1 ON
1
2
12 OFF
SW3
1
2
Code
Pipe temperature
Code
Pipe temperature
1
-40~2(1)°C 9
~45°C
2
3(2)~10°C
10
~50°C
3
~15°C
11
~55°C
4
~20°C
12
~60°C
5
~25°C
13
~70°C
6
~30°C
14
~90°C
7
~35°C
15
Thermistor abnormality
8
~40°C
During the test run, the pipe temperature code from 1 to 15 is displayed on the remote controller instead of room tem­perature. The code should fall with the lapse of time in normal COOL operation.
(2) Trouble during test run
If the unit malfunctions during the test run, refer to section 10 in this manual entitled “TROUBLESHOOTING.”
When the optional program timer is connected to the conditioner, refer to its operating instructions.
2-6 Emergency operation
When the remote controller or microprocessor malfunctions but all other parts are normal, emergency operation is started by setting the dip switch SW3 on the indoor controller board.
<Before emergency operation>
1. Make sure the compressor and the indoor fan are operating normally.
2. Locate the defect with the self-diagnostic function. When the self-diagnostic function indicates “protective function is working”, release the protective function before starting the emergency operation. CAUTION: When the self-diagnostic function indicates a check code of “P5” (drain pump malfunction), DO NOT start
the emergency operation because the drain may overflow.
<How to operate>
1. For emergency cooling, set the dip switch SW3-1 to ON and SW3-2 to OFF.
Emergency cooling
Normal operation
Microcessor board
2. Turn ON the outdoor unit breaker and then ON the indoor unit breaker. Emergency operation will now start.
3. During emergency operation, the indoor fan operates on high speed, the auto vanes do not operate.
4. To stop emergency operation, turn OFF the indoor unit breaker.
5. Movements of the vanes do not work in emergency operation, therefore you have to slowly set them manually to the
appropriate position. NOTE: The remote controller POWER ON/OFF button can not start/stop emergency operations. CAUTION: Do not use emergency cooling for more than 10 hours, as the indoor coil may freeze.
25
Page 26
2-7 Interlock with ventilation system (LOSSNAY)
Relay box
Relay box (PZ-12RB-E)
LOSSNAY
LOSSNAY
LOSSNAY control switch (PZ-05SLB
2-E) LOSSNAY control switch
(PZ-05SLB
2-E)
Mr. SLIM
Mr. SLIM
Remote controller
Remote controller
Remote display adapter (PAC-SA88HA-E)
Power supply
Power supply
Mr. SLIM/LOSSNAY interlock operation is available by using the optional parts listed below.
(1) System organization
(2) LOSSNAY models connectable to Mr. SLIM are: LGH-15RS-E, LGH-50RS-E
LGH-25RS-E, LGH-80RS-E LGH-35RS-E, LGH-100RS-E
(3) Required parts are:
Relay box (PZ-12RB-E)…Contact capacity 10A
Remote display adapter (PAC-SA88HA-E)…An optional part for Mr. SLIM
LOSSNAY control switch (PZ-05SLB2-E)…For LOSSNAY individual operation
(4) Operation
1LOSSNAY turns ON/OFF according to Mr. SLIM ON/OFF 2While Mr. SLIM is OFF, LOSSNAY individual operation is available by using the LOSSNAY control switch.
When Mr. SLIM turns OFF with the LOSSNAY control switch at ON, LOSSNAY will continue to operate.
(5) Wiring.
Mr. SLIM
Indoor controller
N L
DAMPER
2-E)
LOW
board
Connector
CN51
ORN
RED
BRN
Remote controller
Power supply 50Hz 220 240V
10m
Connecting wire
0.13mm or over Connecting wire
solid wire,
1.6 or 2.0 (field supplied)
Circuit breaker (field supplied)
L
N
PL
HIGH
N
LOSSNAY control switch (PZ-05SLB
Insulation is needed
2
Power supply for Mr. SLIM 220 240V AC
GRN
YLW
Relay box
(PZ-12RB-E)
YLW
Junction box (field supplied)
A B L N
HIGH
N
Terminal block
LOW
HIGH
N
DAMPER DAMPER
ORN RED
WHT
RED
WHT
LOSSNAY
ORN RED
WHT RED ORN WHT
8
7
4
6 2
5
3
1
26
2When the LOSSNAY control switch is not used:1When the LOSSNAY control switch is used
Relay box
(PZ-12RB-E)
Terminal block
A B L N HIGH N
Mr.SLIM CN51 12V DC
L
Power supply 220 240V AC
NOTE: For further information, refer to the
LOSSNAY technical & service manual.
Circuit breaker
N
LOSSNAY
Terminal block
ORN
LOW
RED
HIGH
WHT
N
RED
DAMPER
ORN
DAMPER
WHT
Page 27
2-8 Dip switch functions
Each figure shows the initial factory setting.
1. On remote controller board
(1) SW17(Address selector)
1 2 3 4 5 6 7 8
ON OFF
SW17-1~6) For address setting SW17-7) When two remote controllers are used,this switch sets the controller function.
OFF:The remote controller is set as a main controller. ON :The remote controller is set as a sub controller.
SW17-8) Switch for system back-up.
OFF:Without back-up ON :With back-up
(2) SW18(Function selector)
1 2 3 4
ON OFF
SW18-1) Switch for timer
OFF:Single day ON:timer every day
SW18-2) Switch for filter sign
OFF:filter sign absent ON :filter sign present
SW18-3) Switch for filter sign time setting.
OFF:100Hr ON:2500Hr SW18-4) Not for use. SW18-5) OFF:For models with heat pump.
ON :For models with cooling only. SW18-6~8) Not for use.
2. On indoor controller board
(1) SW1 (Mode selector)
1 2 3 4 5 6 7 8 9
ON OFF
SW1-1) Switch that changes between FAN mode and AUTO mode
OFF:AUTO mode for models with heat pump
ON :Fan mode for models with heat pump SW1-2) Not for use. SW1-3) Switch to change the temperature to start coil frost prevention
OFF:1°C
ON :-3°C SW1-4) Not for use. SW1-5) Not for use. SW1-6) Not for use. SW1-7) Switch for detecting abnormalities in the outdoor unit abnormality detection
OFF:When an abnormality occurs,it is detected.
ON :Even if an abnormality occurs,it can not be detected. SW1-8) Switch for auto restart function
OFF:This function does not work
ON :This function works. SW1-9, 10) Not for use.
5678
10
27
Page 28
(2) SW2 (Address selector)
1 2 3 4 5 6
ON OFF
Used in setting the unit-address for group control. For further information,refer to page 36.
(3) SW3 (Emergency operation switch)
Normal operation
1 2
ON OFF
For emergency cooling
1 2
ON OFF
(4) SW5 (Model selector)
1 2 3 4
ON OFF
SW5-1) Not for use. SW5-2) OFF:For models with heat pump
ON: For models with cooling only SW5-3) Not for use. SW5-4) Not for use.
(5) SW6 (Address selector)
1 2 3 4
ON OFF
SW6-1 OFF ON(Twin NO.1) SW6-2 OFF ON(Twin NO.2) SW6-3 OFF OFF SW6-4 OFF OFF
Single control Twin control
(6) SW7 (Model selector)
Switch to set the output of phase-controlled indoor fan motor. Address setting is available at any time. The initial factory setting by is based on each capacity.
Service Ref.
SW7
PK-1.6GKL
ON OFF
1 2 3
PK-2GKL
ON OFF
1 2 3
(7) SW8
1 2 3 4
56
ON OFF
SW8-1~2) Not for use. SW8-3~4) Not for use. SW8-5) Not for use. SW8-6) OFF:For 240, 230V power supply
ON: For 220V power supply
(8) SW9
1 2 3 4
5
ON OFF
SW9-1~5) Keep this switch.
28
Page 29
9
TROUBLESHOOTING
1. TROUBLES IN TEST RUN
Symptom
The display “CENTRALLY CONTROLLED” on remote controller dose not disap­pear.
When remote controller POWER button is turned ON, the check code “EO”appears.
Cause Check points
1) Wrong address setting of remote con­troller/indoor controller board.
2) Timer adapter is connected to the remote controller.
3) Signal transmission error between indoor unit and remote controller.
1) Signal transmission error between indoor unit and remote controller
1) Check the address setting of remote controller and indoor controller.
2) Make sure the timer adapter is used correctly.
3) 1 Turn another remote controller’s DIP SW17-
7 ON to make it sub controller.
2 Connect the sub controller to the unit, and
turn circuit breaker ON.
If the display “centrally controlled” disap­pears, replace the original remote controller.
If the display remains the same, replace the indoor controller board.
1) 1 Connect a sub remote controller. 2 Turn circuit breaker ON.
If the display “centrally controlled” remains, replace the indoor controller board.
3 If the display disappears, turn the remote
controller POWER button ON and check as follows.
Remote controller
1
Operating Display
2
Operating Display
3
No Display
4
No Display
Sub remote controller EO Display
Operating Display
EO Display
Operating Display
Malfunction of indoor Unit
Malfunction of Remote controller
Malfunction of indoor Unit and Remote Controller
Malfunction of Remote controller
Malfunction
When remote controller POWER button is turned ON, operating display appears, but disappears soon.
Despite turning POWER button ON, the remote controller display does not appear.
1) Short circuit of indoor/outdoor connect­ing wire
2) Short circuit of transmission wire.
3) Wrong operation of remote controller due to noise wave emitted by other appliances.
1) Damaged remote controller.
2) Short circuit of transmission wire.
3) Bad contact of indoor CN40.
4) CN40 is attached to a sub unit.
5) Damaged power board.
6) Bad contact of CN2D.
7) Blown fuse.
8) Circuit breaker OFF.
1), 2) Check the wire
3) Turn the circuit breaker OFF, and then turn ON.
If the remote controller remains abnormal,
despite the above measures, replace the indoor controller board.
1) Measure the voltage between terminals of remote controller. If no voltage, remove the terminals and measure the voltage between wires. If the voltage is between 6VDC and 12V, replace the remote controller.
2) ~ 8) Check each point.
If it is not defective, replace the indoor controller board.
29
Page 30
2. SELF DIAGNOSTIC FUNCTION WITH REMOTE CONTROLLER (WIRED REMOTE CONTROLLER (OPTION))
2-1 When malfunction occurs during operation
When a malfunction occurs, the indoor and outdoor units stop and the malfunction is displayed on the LCD of the remote controller. (1) ON the set temperature display part, “CHECK” appears, and the unit
address and the check code are displayed alternately at one-second intervals. (Check mode)
Example
CHECK mode
Check
code
(2) When one remote controller controls several units in the group con-
trol, the LCD shows the unit address and check code of the first mal­functioning unit.
(3) To cancel the check mode, press the ON/OFF button. In remote
ON/OFF control, press the remote ON/OFF switch. In centralized control, turn OFF the ON/OFF button of centralized controller.
NOTE: The latest check code is memorized, even if the check mode is cancelled by the way mentioned above. It takes
60 seconds maximum to display the memorized check code.
Unit
address
Check button
2-2 How to use the self diagnostic function for service
A. For normal control with one unit and one remote controller
(1) Pressing the CHECK button on the remote controller twice starts the self diagnostic function. (2) During the self diagnostic function, “CHECK MODE” appears at two positions on the remote controller display. Then, at
least 10 seconds later, the unit address and the check code is alternately displayed at one-second intervals.
(3) Check and repair the unit according to the check code. (Refer to page 32.)
B. For group control using one remote controller
(1) Pressing the CHECK button on the remote controller twice starts the self diagnostic function. (2) Press the TEMP. button or TEMP. button on the remote controller to advance or go back to the unit address.
Each time TEMP. button is pressed, the unit address advances by one. Each time TEMP. button is pressed, the unit address goes back by one. The check code and the unit address, appear alternately.
(3) The check code “U8” means no malfunction has occurred since installation.
The check code “EO” means the following conditions:
The unit address displayed on the remote controller does not apply to any unit.
power is not supplied to the unit.
Signal transmitting/receiving circuit is abnormal.
(4) Check and repair the unit according to the check code. (Refer to page 32.)
30
Page 31
(WIRELESS REMOTE CONTROLLER)
(1) Turn on the main power of the unit. (2) Set the adjusting switch on the back of
the wireless remote controller to “Set” then FUNCTION , TEST RUN and CHECK will start lighting.
(3) Press the HR. button then CHECK will
start blinking.
(4) Send the signal from the remote con-
troller to the unit with pressing HR. but­ton. If the buzzer sound is heard are the ON/OFF lamp (Unit display) blinks, refer to the following table.
Buzzer sound
1 second (0.5 sec-
ond interval)
Beep
The number of
ON/OFF lamp
(Unit display)
blinking and
buzzer sound
1(P1) 2(P2) 3(P3) Signal transmission error 4(P4) 5(P5)
6(P6)
The number of ON/OFF
lamp (Unit display) blinking
This corresponds to the
number of buzzer sound
Irregular point
Irregular intake sensor Irregular piping sensor
Irregular drain sensor Irregular drain pump
Freezing protection is
working
ADDRESS UNIT No. FUNCTION No. SELECTION No.
FUNCTION TEST RUN
CHECK
ON/OFF
MODE FAN
RESET
VANE
Remove the battery cover on the back side of the wireless remote controller, display will start flashing when the “Set” switch is turned on. For operations marked “ ”, point the transmitter
to the wireless receiver, and make sure that you will hear a short beep from the receiver.
Turn the adjusting switch to “Set”
˚C
AM PM
AM PM
TEMP.
START
STOP
HR.
MIN.
Display will start blinking
ADDRESS UNIT No. FUNCTION No. SELECTION No.
AM
FUNCTION TEST RUN
CHECK
ON/OFF
PM
AM PM
TEMP.
˚C
7(P7) System error 8(P8)
Irregular outdoor unit
(Refer to the page 32 in detail.) When there is any error, receiving sound
beeps.
(5) Push the POWER ON/OFF button and
cancel the test run.
(6) After completing a test run, be sure to
For operations marked “ ”, point the transmitter to the wireless
receiver, and make sure that you will hear a short beep from the receiver. When the other than main unit is operated by the wireless remote controller, the receiver beeps an ineffectual beep 3-times.
31
Page 32
Check
code
EO Signal transmitting/receiving
Diagnosis of malfunction Cause Check points
error
(Indoor controller does not
respond to remote controller signal.)
During individual unit control
1) Bad contact of transmission wire
2) Signal transmitting/receiving cir­cuit is abnormal.
1) Check the transmission wire.
2) Check with another remote controller. If “EO” is still indicated, replace the indoor controller board. If other check code appears. replace the origi­nal remote controller.
P1P2Abnormality of room temper-
ature thermistor (RT1)
Abnormality of pipe tempera-
ture thermistor (RT2)
P3 Signal transmission error
(Remote controller does not
respond to indoor controller signal.)
P6 Freezing protection
is working.
P7 System error 1) Wrong address-setting
1) Bad contact of thermistor
2) Damaged thermistor
1) Bad contact of transmission wire
2) Signal transmitting/receiving cir­cuit is abnormal.
3) Wrong operation due to noise wave emitted by other appli­ances
1) Short cycle of air cycle
2) Dirty air filter
3) Damaged fan
4) Abnormal refrigerant
2) Signal transmitting/receiving cir­cuit of remote controller is abnormal.
3) Wrong SW6-setting
1) Check the thermistor.
2) Measure the resistance of the thermistor. Normal resistance should be as follows.
0: ···15k 30:·····4.3k 10:······9.6k40: ·····3.0k 20:······6.3k If the resistance is normal, replace the indoor controller board.
1) Check the transmission wire.
2) Check with another remote controller. If “P3” is still indicated, replace the indoor board. If other check code appears, replace the origi­nal remote controller.
3) Short-circuit between attach CN40 to the following units.
Second unit in twin control
Sub units in group control
1) Clear obstructions from the air cycle.
2) Clean the air filter
3) Check the fan.
4) Check the refrigerant temperature.
1) Check the address-setting.
2) Check with another remote controller. If check code other than “P7” appears, replace the origi­nal remote controller.
3) Check SW6 setting.
1 and 2 of CN40 and
P8 Abnormality in outdoor unit 1) Wrong wiring of indoor/outdoor
connecting wire
2) Reversed phase
3) Protection device is working
3. WHEN OUTDOOR UNIT DOES NOT WORK
Cause
1) Indoor/outdoor connecting wires are poorly connected.
2) Power supply is poorly connected.
3) Fuse (5A) in the outdoor controller board is blown.
1) Check the connecting wires.
2) Check the power supply.
3) Check the fuse.
1) Check the indoor/outdoor connecting wire.
2) Change the connection of electric wiring.
3) Check the protection device.
Check points
32
Page 33
4. OTHER TROUBLES AND CAUSES
Vanes do not work.
Unit stops after 5 to 20 seconds operation
Air discharge display is OFF and VANE button does not oper­ate.
In this case, remote controller is normal.
Power ON/OFF button is not available.
Vane motor does not work. Connector is poorly connected. Vane motor is poorly assembled. Indoor controller board is damaged.
Protection function is working.
Indoor controller board
deems the auto vanes are not attached to the unit.
Horizontal angle can
not be detected.
Beep sound is heard, but display is turned
OFF.
Beep sound is not heard,
and display remains OFF.
“CENTRALLY CONTROLLED” is displayed.
Indoor controller is damaged. Dip switch setting is wrong.
Indoor controller is damaged. Vane motor is dam­aged. Auto vane is wired after power is turned to ON.
Indoor/outdoor connect­ing wire is connected incorrectly. Indoor/outdoor connect­ing wire shorts. Compressor protector is damaged. Outdoor controller board is defective.
Remote controller is damaged. Transmission wire is poorly connected
Vane motor is damaged. Vane motor relay is damaged.
Refer to check code on remote controller display. See page 32.
Vane motor is damaged.
Transmission wire is damaged. Connector is poorly connected. Indoor terminal block is poorly connected. Remote controller ter­minal block is poorly connected.
5. MR. SLIM/LOSSNAY INTERLOCK OPERATION
<Symptoms that are not malfunctions>
If any of the following symptoms occur, they are not malfunctions.
Symptom
LOSSNAY control switch can not work during interlock opera-
LOSSNAY control switch does not work.
LOSSNAY air speed can not be controlled in interlock opera­tion.
For LOSSNAY, troubleshooting refer to the LOSSNAY technical & service manual.
tion. LOSSNAY control switch is effective only while Mr. SLIM is not operating.
LOSSNAY fan speed is fixed to HIGH during interlock opera­tion. LOSSNAY fan speed LOW/HIGH can be switched only during LOSSNAY individual operation with the LOSSNAY control switch.
33
Cause
Page 34
6. How to check the parts PK-1.6GKL , PK-2GKL
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
< Thermistor for lower temperature >
Temperature (:)
Resistance (k")
Parts name Check points
Room temperature thermistor
(RT1) Pipe temperatuer thermistor (RT2)
Disconnect the connector, then measure the resistance using a tester. (Surrounding temperature 10°C~30°C)
Normal
4.3k'~9.6k'
Abnormal
Open or short
(Refer to the thermistor)
Fan motor (MF)
Relay connector
3
Red
White
2
C
1
Black
Protector
Vane motor (MV)
Measure the resistance between the terminals using a tester.
Motor terminal
1
Relay connector
3 5
Red-Black
White-Black
Measure the resistance between the terminals using a tester. (Surrounding temperature 20°C~30°C)
Orange
4
Red
5
Pink
2
Connector
M
Brown
Yellow
3 6 1
Blue
Brown-Yellow
Brown-Blue
Red-Orange
Red-Pink
<Thermistor Characteristic graph>
Thermistor for lower temperature
Room temperature thermistor(RT1) Pipe temperature thermistor(RT2)
or
Normal
186~214'
Normal
PK-GKL
1.6, 2
141.2'
131.5'
Abnormal
Open or short
Abnormal
Open or short
Thermistor R0=15k' ±3% Fixed number of B=3480k' ±2%
Rt=15exp { 3480( ) }
1
273+t
0: 15k' 10: 9.6k' 20: 6.3k' 25: 5.2k' 30: 4.3k' 40: 3.0k'
1
273
34
Page 35
10
Unit
Remote controller
Unit Unit
Optional adapter
Remote ON/OFF switch
Remote controller
Relay box
Unit
Unit
Remote controller
Unit Unit
Unit
Remote controll display board
Remote controller
Unit Unit
Circuit breaker
Remote controller
SYSTEM CONTROL
1. VARIETY OF SYSTEM CONTROL FUNCTIONS
1 Group control with
a single remote controller (See page 36.)
3 Both remote
ON/OFF and indi­vidual controls (See page 37.)
w Timer adapter
(PAC-SA89TA-E) is needed.
4 Individual control
by grouping remote controllers (See page 38.)
5 Multiple remote
control display (See page 39.)
w Multiple remote
controller adapter (PAC-SA88HA-E) is needed.
Many units, installed at different locations, can be started
and controlled with a single remote controller. The remote controller can be mounted in a different location using a non-polar two-wire cable, which can be extended up to 500m. Amaximum of 50 units can be controlled with a single remote controller. All units operate in the same mode.
All units can be turned on or off simultaneously using a
remote ON-OFF switch. Also, each unit can be controlled individually by each remote controller. Dunning remote ON-OFF control, a message of “CENTRALLY CON­TROLLED” is displayed on the LCD of the remote con­troller.
This is available for both one unit control and several units
control.
By grouping the remote controllers in one place, several
units installed at different locations can be controlled indi­vidually, and operation conditions of all units are visible without a special control board. The control method is the same as that of the single unit with a single remote con­troller.
Several units can be controlled with a remote control dis-
play board. Operation conditions of all the units are visi­ble with the remote control display board.
Individual control by each remote controller is also possi-
ble.
6 Auto restart
function
(See page 39.)
A unit can be started or stopped with the circuit breaker
on or off. Remote controller is also available. With this function, when the power is restored after power
failure, the unit will restart automatically. (However, when
the remote controller POWER ON/OFF button is OFF, the
unit will not start.)
35
Page 36
2. GROUP CONTROL WITH A SINGLE REMOTE CONTROLLER
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
To remote controller
To next unit
To next unit
The last unit dose not have this wire.
Next unit electrical box
Master unit electrical box
123LN PE
LN
PE
123
Master unit
No.1 unit No.2 unit Last unit
2-wire cable
SW2
CN40
CN40
SW2
Should be removed from all units other than unitNo.0: (Master Unit).
1
2
3
4
5
6
ON
A maximum of 50 units can be started in order according to the dip switch settings
2-1 How to wire
(1) Connect the remote controller to the double terminal block
on the indoor controller board of the master unit (No.0 unit). (See Figure 1.)
(2) Connect the double terminal block of the master unit to the
double terminal block of No.1 unit.
(3) Connect the double terminal block of No.1 unit to the dou-
ble terminal block of No.2 unit.
(4) Continue the process until all the units are connected with
two-wire cables. (See Figure 2.)
(5) Remove the connector CN40 from the indoor controller
board of each unit except the master unit. (See Figure 3.)
(6) Set the unit-address of each unit with SW2 on the indoor
controller board following the instructions below.
2-2 How to set unit-address
The unit-address also serves as a successive-start timer which starts each unit at intervals of 1 second. If two or more units have the same unit-address in a group control, operation stops due to system error. Be sure to set SW2 correctly following the instructions below. (1) Each lever of SW2 shows the number as follows.
SW2-1 : 1 SW2-4 : 8 SW2-2 : 2 SW2-5 : 16 SW2-3 : 4 SW2-6 : 32
(2) Total number of levers turned to ON shows the address of
the unit. For example, to set No.3 unit, turn ON SW2-1 and SW2-2.
(3) In this way, set from the master unit to the last unit.
Do not forget to set the master (No. 0) unit.
Figure 1
Figure 2
Figure 3
Indoor controller board
Setting examples
SW2
Unit address & start delay in seconds.
2-3 Unit control
The remote controller can control all units ON/OFF, temperature, air flow, and swing louver. However, the thermostat in each unit turns ON or OFF individually to adjust to the room temperature.
Master (No. 0) unit
ALL OFF
No. 1 unit
1 ON
0
1
No. 2 unit
2 ON
2
No. 4 unit
3 ON
4
No. 8 unit
4 ON
8
No. 16 unit
5 ON
16
No. 32 unit
6 ON
32
36
Page 37
3. REMOTE ON-OFF AND INDIVIDUAL REMOTE CONTROLS
Remote controller
power supply of control circuit
Remote ON/OFF
switch
2-wire remote controller cable
Figure 6
Relay box
Timer adapter cables
Timer adapter PAC-SA89TA-E
Power supply
Remote ON/OFF switch
No.1 unit relay box
No.2 unit relay box
Next unit
T
X2 X2
T
Glow switch or pilot lamp can be combined to easily identify the on-off mode of SW1 and SW2.
To No.1 unit
To No.2 unit
Timer adapter cables
Remote controller
T
X2
SW
1
SW2
T
X2
This method is available to control one unit or any number of units. The following operations are available by connecting a relay, a timer adapter (PAC-SA89TA-E), and a remote ON/OFF switch to the system. Timer adapter is an optional part. Other parts are available on the market. (A) To start all units in order by remote ON-OFF switch (B) To stop all units simultaneously by remote ON-OFF switch (C) To switch between the remote ON-OFF control and the individual remote control
3-1 System
Figure 6 shows the case of three units. The same is the case with any number of units.
NOTE1 : Install the relay box where you can be serviced it easily. NOTE2 : For control circuit wiring, use a wire of No. 14 AWG or a control cable according to the power supply of control
circuit.
NOTE3 : When the power supply of the control circuit is 220/240V AC,
Do not connect the control circuit wire to the remote controller cable directly.
Do not place the control circuit wire and the remote controller cable into the same conduit tube.
3-2 Basic wiring
Caution : Before starting all units simultaneously by the remote ON-OFF switch, be sure to connect a sequence-start timer
into the remote ON-OFF circuit. Otherwise, a rush of starting current may damage the power supply.
37
Page 38
3-3 Switch function of remote ON-OFF switch
Remote controller cable (2-core)
Remote controller
SW2
(Switches between remote ON-OFF and individual control)
ON
(Remote ON-OFF control)
ON
SW1 (Switches between remote ON and OFF.)
w1 After all units start together, if SW2 is turned OFF, each unit can be individually stopped by each remote controller. w2 After all units stop together, if SW2 is turned OFF, each unit can be individually started by each remote controller.
(Start)
OFF
(Stop)
All units start together. Individual control is not available.
All units stop together. Individual control is not available.
w1 w2
Each unit can be controlled by each remote controller. Remote ON-OFF switch is not available.
OFF
(Individual control)
4. INDIVIDUAL CONTROL BY GROUPING THE REMOTE CONTROLLERS
Grouping the remote controllers allows individual control and cen­tralized monitoring of units installed in different places without a special control board.
Remote control cables are extendible up to 500m. When the cable length exceeds 12m, use the double-insulated two-care cable such as Belden 9407. Also, the cable thickness must be No. 22 AWG or above.
When gathering the power ON/OFF switches of air conditioners near the remote controllers, you should also install the power ON/OFF switch near each unit to prevent electric trouble during servicing.
38
Page 39
5. MULTIPLE REMOTE CONTROL DISPLAY
CN51
connector(5P)
GREEN
Power supply
Electrical insulation is needed.
Wiring at the actual place
Optional multiple display adapter
The maximum distance between indoor board and relay is 10m.
YELLOW ORANGE
RED
BROWN
5
X2
X2
GL
RL
X1
X1
1
<Wiring >
CN51
Indoor controller board
CN51
Power supply
Remote controller cable
Relay box (Field supply)
Remote controller
Remote controller
Remote controller
3wires 3wires 3wires
2wires
No.1 unit No.2 unit No.3 unit
Muitiple remote control ON-OFF display (Field supply)
(Operation check)
<System>
Power supply
RL-1 GL-1
Multiple Remote Control Display
Multiple remote controller adapter
connect to the connector CN51
Relay box
5
X1-1
X2-1
1
<Wiring diagram>
RL-2 GL-2
RL-3
No.1 unit
GL-3
X1-1
X2-1
X1-2
X1-3
X2-3
X2-2
5
1
No.2 unit
5
1
No.3 unit
X1-2
X2-2
X1-3
X2-3
Remote controller
A B
Brown
Red
Orange
Remote controller
A B
Brown
Red
Orange
You can control several units with a multiple remote control display, by wiring an optional multiple remote controller adapter (PAC-SA88HA-E) with relays and lamps on the market.
5-1 How to wire
(1) Connect the multiple display adapter to the connector CN51 on the
indoor controller board.
(2) Wire three of the five wires from the multiple display adapter as shown
in the figure below.
Indoor controller board
[Notes on Signs] X1:Relay (for operation lamp) X2:Relay (for check lamp) RL:Operation Lamp GL:Check Lamp [Field supplied parts] Relays:12V DC with rated coil power
consumption below 0.9W.
Lamps:Matching to power supply voltage.
6. AUTO RESTART FUNCTION
By setting the dip switch SW1-8 to ON, the air conditioner can be started/stopped by power supply ON/OFF. If the air conditioner is OFF before the power failure, it will not start operation by power restore.
•This function is mainly to emergency performance when the power supply stops temporarily. Therefore, since the protec­tion function (for example, clank case heater and prevention from restarting in 3 minutes, etc.) of the device is not operat­ed, this function should not be used mostly.
7. TIMER OPERATION OR THE OPERATION BY AN EXTERNAL SIGNAL
<Wiring>
For remote control, connect the optional timer adapter (PAC-SA89TA-E)
39
A : an optional timer adapter B : a single-throw switch
Page 40
DISASSEMBLY PROCEDURE11
PK-1.6GKL PK-2GKL
OPERATION PROCEDURE
1. REMOVE THE LOWER SIDE OF THE INDOOR UNIT FROM THE INSTALLATION PLATE.
(1) Remove the left / right corner box of the indoor unit. (2) Hold and pull down the lower and both ends of the indoor
unit, and remove the section from the square hole. (Refer to the figure 2.1) Or remove the front panel and push the section down by using hexagonal wrench ,etc. from the front side. (Refer to the figure 2.2).
(3) Unhook the top of the indoor unit from the back plate
catch.
(Figure 2.2)
PHOTOS & ILLUSTRATION
(Figure 1)
(Figure 2.1)
Hook
Hook
Square hole
2. REMOVING THE FRONT PANEL.
(1) Open the front grille. (2) Remove the terminal block cover with a screw. (3) Remove the screw 3 caps then remove the set 3 screws. (4) After removing the lower side of the front panel a little,
remove it as pulling toward upper.
3. REMOVING THE INDOOR CONTROLLER BOARD.
(1) Remove the terminal block cover. (2) Remove the front panel. (see the photo 1) (3) Remove the electrical box(2 screws). (4) Remove the electrical box cover(1 screw). (5) Disconnect the connector on the controller board and
remove the controller board by pulling up the hook of the controller case. w To smooth works, hang the side hooks of the electrical box on the hook of the motor cover. (see the photo 3)
Up
Down
(Figure 3)
(Photo 1)
Front panel
(Photo 2)
Motor cover
Electrical box hook w
Square hole
Terminal block cover
Front grille
Set screws
Set screw
Electrical box
Set screw
40
(Photo 3)
Hook
Control board
Controller case
Electrical box
Page 41
OPERATION PROCEDURE
PHOTOS & ILLUSTRATION
4. REMOVING THE POWER BOARD
(1) Remove the front panel.(see the photo 1) (2) Remove the electrical box(2 screws).(see the photo 2) (3) Disconnect the whole connector in the control board. (4) After lifting the controller case with pressing it’s convex
section, remove the controller case and the control board
simultaneously.(see the photo 3) (5) Disconnect the connector in the power board. (6) Remove the power board.
5. REMOVING THE VANE MOTOR
(1) Disconnect the connector CN6V on the indoor controller
board.
(2) Remove the 2 screws of the vane motor, disconnect the
lead wire and remove the vane motor from the shaft.
6. REMOVING THE THERMISTOR
(1) Removing the room temperature thermistor RT1.
1Disconnect the connector CN20<red> on the indoor
controller board.
2Remove the room temperature thermistor from the holder.
(2) Removing the pipe temperature thermistor RT2.
1Disconnect the connector CN21<white> on the controller
board.
2Remove the pipe temperature thermistor with set to the
pipe.
(Photo 4)
(Photo 5)
Nozzle assembly
Vane motor
(Photo 6)
Pipe temperature thermistor
Room temperature thermistor
Power board
Electrical box
Set screws
Lead wire
7. REMOVING THE NOZZLE ASSEMBLY
(1) Disconnect the connector CN6V on the controller board. (2) Disconnect the lead wire of the vane motor. (3) Remove the corner cover. (4) Pull the drain hose out from the nozzle assembly. (5) Unhook the hook of the lower nozzle assembly and
pull the nozzle assembly toward you, then remove the nozzle assembly by sliding it down.
8. REMOVING THE ELECTRICAL BOX
(1) Remove the terminal block cover. (2) Remove the front panel.(see the photo 1) (3) Disconnect the vane motor connector. (4) Disconnect the fan motor connector from the fan motor. (5) Remove the pipe thermistor and the room temperature
thermistor.(see the photo 6)
(6) Remove the electrical box (2 screws).
(Photo 7)
Nozzle assembly
(Photo 8)
Pipe temperature thermistor
Hooks
Electrical box
Drain hose
Corner cover
Vane motor connector
Electrical box
41
Fan motor connector
Page 42
OPERATION PROCEDURE PHOTOS & ILLUSTRATION
9. REMOVING THE FAN MOTOR.
(1) Remove the terminal block cover. (2) Remove the front panel.(see the photo 1) (3) Remove the electrical box.(see the photo 8) (4) Remove the nozzle assembly.(see the photo 7) (5) Remove the fan motor leg fixing 3 screws. (6) Unscrew the set screws using by alankey and remove it by
sliding the fan motor to right.
(7) Remove the 4 screws and remove the motor cover from the
fan motor leg.
10. REMOVING THE LINE FLOW FAN
(1) Remove the terminal block cover. (2) Remove the front panel.(see the photo 1) (3) Remove the electrical box.(see the photo 8) (4) Remove the nozzle assembly.(see the photo 7) (5) Remove the fan motor.(see the photo 9) (6) Remove the pipe fixture with 2 screws.(see the photo12) (7) Remove the left / right screws of the heat exchanger and
pull the left-hand side up.
(8) Remove the 2 screws by sliding it toward you remove the
fixture(fixing bearing). w The fan motor is removable first , when the fan
removing is hard.
w When resetting the fan to the fan motor.
Locate and fix the shaft after installing the fan.
(Photo 9)
Set
screw
(Photo 10)
Motor cover
Fan motor
(Photo11)
Heat exchanger
Set screws
Fixture(fixing bearing)
Motor cover
Fan motor
screws
motor leg
11. REMOVING THE HEAT EXCHANGER
(1) Remove the terminal block cover. (2) Remove the front panel.(see the photo 1) (3) Remove the electrical box.(see the photo 8) (4) Remove the corner box. (5) Remove the nozzle assembly.(see the photo 7) (6) Remove the 2 screws and the pipe fixture. (7) Remove the 2 screws and heat exchanger.
(Photo 12)
Set screw
Pipe fixture
Heat exchanger
Set screws
42
Page 43
OPERATION PROCEDURE
PHOTOS & ILLUSTRATION
12. REMOVING the SIGNAL RECEIVING P.C. BOARD
(1) Remove the terminal block cover. (2) Disconnect the connector <yellow> for the wireless remote
controller. (3) Remove the front panel.(see the photo 1) (4) Remove the 2 screws and signal receiving p.c. board cover. (5) Remove the signal receiving p.c. board.
(Photo 13)
Set screws
(Photo 14)
Front panel
Signal receiving p.c. board cover
Front panel
Signal receiving p.c. board
43
Page 44
12 PARTS LIST
(BG02V194H05) (BG25B573H05) (BG02V195H10) (BG00V196G20) (RG25C546H06)
T7W A01 762 R01 07Y 114 R01 07Y 105 R01 07Y 106 R01 005 103 R01 07Y 102 R01 07Y 130 T7W E13 530 T7W E06 202 R01 09Y 038 T7W E13 223 R01 07Y 527 T7W E12 310 T7W 520 239 R01 07Y 524 T7W 521 716 R01 588 255 T7W E05 202 T7W E67 480 T7W E02 313 T7W 512 716 R01 07Y 135 R01 07Y 038 R01 07Y 059 T7W A00 675 R01 50J 317
— — — — —
No.
Parts No. Parts Name
Specifications
Remarks
(Drawing No.)
Wiring Diagram Symbo
l
Recom-
mended
Q'ty
Unit
Amount
PKH-
1.6GKL 2GKL
Price
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
FAN MOTOR LINE FLOW FAN RUBBER MOUNT BEARING SUPPORT SLEEVE BEARING BEARING MOUNT MOTOR SUPPORT NOZZLE PIPE TEMPERATUER THERMISTOR GUIDE VANE VANE MOTOR DRAIN HOSE INDOOR CONTROLLER BOARD FUSE DRAIN PLUG TERMINAL BLOCK CAPACITOR ROOM TEMPERATURE THERMISTOR HEAT EXCHANGER POWER BOARD TERMINAL BLOCK MOTOR COVER GUIDE VANE ARM FAN GUARD WIRERLESS ADAPTER CONTROLLER BOARD CONTROLLER COVER CONTROLLER CASE TERMINAL COVER ELECTRICAL PARTS COVER SENSOR HOLDER
MF
RT2
MV
I.B
F1,F2
TB2
C
RT1
P.B
TB4
W.B
1 1 2 1 1 1 1 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1
10
2 1 1 1 1 1 1 1
1 1 2 1 1 1 1 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1
10
2 1 1 1 1 1 1 1
3P(L, N, ;)
2.0= 440V
2P(1, 2)
250V 6.3A
PM4V30-K
PK-1.6GKL PK-2GKL
4
6
5
19
2
25
8
10
23
24
15
10
12
11
1
22
26
44
7
9
30
14
1
18
31
20
28
3
17
29
16
21
13
27
Page 45
STRUCTURAL PARTS
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18
FRONT PANEL AIR FILTER SCREW CAP CORNER COVER CORNER COVER BOX ASSEMBLY BACK PLATE UNDER COVER FRONT GRILLE VANE SLEEVE AUTO VANE WIRELESS REMOTE CONTROLLER WIRELESS REMOTE CONTROLLER DOOR BATTERY COVER WIRELESS REMOTE CONTROLLER HOLDER RECEIVING UNIT REMOTE CONTROLLER REMOTE CONTROLLER COVER
1 2 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
No.
Parts No.
Parts Name
Specifications
1.6 / 2 GKL
PK-
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Amount
Price
R01 89Y 651 R01 A16 500 R01 07Y 096 R01 09Y 658 R01 07Y 658 R01 07Y 635 R01 07Y 808 R01 07Y 623
R01 07Y 691 R01 07Y 092 R01 07Y 002 T7W E04 714 T7W E01 049 R01 07Y 050 R01 07Y 075 R01 24K 658 T7W E04 713 T7W E03 049
RU
PK-1.6GKL PK-2GKL
1
3
10
7
4
8
6
5
2
17
9
18
45
11
16
12
13 14
15
Page 46
13
28˚C
26
˚C
8:00
Normal
operation
23:00
Setback
operation
8:00
Normal
operation
OPTIONAL PARTS
1. REFRIGERANT PIPES
Service Ref. : PK-1.6GKL, PK-2GKL
Part No. PAC-05FFS-E PAC-07FFS-E PAC-10FFS-E PAC-15FFS-E Pipe length 5m 7m 10m 15m Pipe size O.D . Connection method Indoor unit: Flared Outdoor unit: Flared
Note 1. How to connect refrigerant pipes.
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as the connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow. If piping length exceeds 20m, an additional charge of refrigerant is needed.
Note 2. The following main parts are contained in the optional refrigerant piping kit.
Heat insulating cover, vinyl tapes, nipples, sleeve and flange (for wall hole).
Liquid:[9.52 Gas:[15.88
2. TIMER
When using a program timer, PAC-SC32PTA, a program timer adapter (PAC-825AD) are and a wired remote controller (PAR-JA240KAT-E) also needed.
Part No. PAC-SC32PTA(with set back function)
Model Name Program timer
2-1 Program timer specifications
Parts name Program timer Parts No. PAC-SC32PTA Exterior dimensions (inch) 5-4/32x4-23/32x23/32 (130x120x18mm) Installation Wall mount Type of clock Quartz Clock accuracy ±50 second / month at 25°C
Display-Time
-Week
-Timer setting unit
Program cycle 24 hours Timer setting unit 30 minutes No. of set points 48 / day Power rating 5V DC ±5% (Supplied by Remote Controller)
Liquid crystal display Liquid crystal display Liquid crystal display
2-2 Feature of program timer
(1) Daily timer function
Daily timer can be set in 30 minutes units for up to 24 hours. Each unit can be set for unit ON, unit OFF, or setback operation.
(2) Setback operation (PAC-SC32PTA)
Set back operation is useful for reducing running costs e.g. At a hotel with a 24-hour system
8:00~23:00 Cooling operation with set temperature at 26°C
23:00~8:00 Setback operation with 2 degrees of setback As shown in the chart on the night, the set temperature rises 2 degrees automatically during the setback operation. When the setback operation ends, normal operation will begin.
(3) Weekly timer function
Daily timer function can apply to each day of the week.
46
Page 47
SET/MONITOR
SET
SMTWTF S
MONITOR
PROERAN TIMER
PAC-SC32PTA
TODAY
ON
WEEKLY SETTING
OFF
ON
SET BACK
OFF
CLOCK DAILY TIMER
SET BACK
SET BACK
DAILY
SETTING
12 15 18 21 24
0361215
FILTER
CHECK MODE
TEST RUN
Use 5-wire cable
2-wire cable
Connect to CN1 Connect to CN1
4
Connect to indoor unit
2-3 How to connect program timer
SET/MONITOR
SET
SMTWT F S
MONITOR
PROERAN TIMER
PAC-SC32PTA
TODAY
ON
WEEKLY SETTING
OFF
ON
SET BACK
OFF
CLOCK DAILY TIMER
SET BACK
SET BACK
DAILY
SETTING
12 15 18 21 24
0361215
(1) Install the program timer next to the remote controller the same way as the remote controller is installed. (2) Connect the program timer and the remote controller with a 5-wire cable as shown in the figure below
NOTE:While the program timer is connected to the remote controller, the
24hour ON/OFF timer on the remote controller will not operate.
2-4 Names and functions
<PAC-SC32PTA>
WEEKLY TIMER SETTING DISPLAY
CURRENT TIME DISPLAY
SET BACK DISPLAY
DAILY TIMER SETTING DISPLAY
Used for selection of if or not the day opera­tion pattern set by PATTERN SETTING is to be applied in weekly day unit, setting.
During MONITOR status,current time is display. During Daily timer setting, a time desire for timer setting is
Indicates the setting set back range.
24 hours is divided into 48 blocks and each
block express 30 minutes.
The block display consists of 3 pattern.
displayed.
Set back can be done in the range of 1,2,4,6 and 8°C.
SET BACK SETTING SW
SET/MONITOR DISPLAY
During SET is display, clock adjustment, change of weekly day, daily and weekly timer setting can be performed. During MONITOR is display, all switches except SET/MONITOR SW are invalidated. This is normal status.
Used for set back setting.
ON/SET BACK/OFF SW
Used to specify the time setting pattern.
WEEK DAY SETTING SW
DAILY TIMER SW
Used for week day setting.
MODE SELECTOR SW
Using this switch select “MONITOR” or “SET” Mode.
“MONITOR” :Indicates the current timer set-
ting. All switch expect MODE SELECTOR SW are invalidated then.This is the normal status.
“SET”: Set to “SET” mode for clock adjust-
ment, charge of week day, daily and weekly timer setting.
CLOCK ADJUSTMENT SW
Used for adjustment of the current time.
Push SW to advance the time. Each time the button is pushed the time advance by 1 minute, pushing continuously advances by 1 minute at 0.5 second interval, and when the lower digit of minute becomes 0 indication advances in 10 min­utes unit.
SW is used for reversing the time. Each time the button is pushed the time reverses by 1 minute, pushing continuously reverses the time by 1 minute at 0.5 second interval, and when the lower digit of minute becomes 0 indication reverses in 10 minutes unit.
3. TIMER ADAPTER
This adapter is needed for system control and for operation via external contacts. Adapter connection is described on page 37.
Used for timer setting in 30 minutes unit.
WEEKLY TIMER SW
Used for setting timer in day of week unit.
Pushing SW moves the week day light display in order of S → M → T → W enabling to set the week day.
ORN 1 BRN RED
Part No. PAC-SA89TA-E
2 3
47
Page 48
4. MULTIPLE REMOTE CONTROLLER ADAPTER
This adapter is needed for remote indication (operation/check). Adapter connection is described on page 39.
Part No. PAC-SA88HA-E
1 2 3 4 5
BRN RED ORN YLW GRN
5. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units. When using the PAC-805RC, the program timer adapter (PAC­825AD)is also needed.
Part No. PAC-805RC
Unit:mm
5-1 Dimensions
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
117
POWER ON/OFF
AHEAD
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
MITSUBISHI ELECTRIC
117
5-2 Functions
"ENGAGED" indicator When this indicator is lit, transmission is in progress and all switches are inoperative.
113
12
ENGAGED
GROUP
12345678910
GROUP SELECTION
PROGRAM
ACTIVE BYPASS
TIMER CONTROLLER
DUAL CENTRAL
OPERATION
23.5
BACK
ACTIVE BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
56.5 11
POWER ON/OFF
AHEAD
8
113
POWER ON/OFF switch Operation ON/OFF switch.
BACK AHEAD buttons These buttons are used to designate
DUAL/CENTRAL switch This change-over switch governing the
operation of the accessory remote con­troller.
"DUAL" Instructions from both the accessory remote controller and the centralized remote controller are valid. (Priority given to the last instruction received.)
"CENTRAL" ON/OFF switching by the accessory remote controller is invalidated. Control is by the centralized remote controller only. Initial setting is "DUAL".
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
POWER ON/OFF
AHEAD
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
MITSUBISHI ELECTRIC
the attached unit(s). (They designate the unit to be centrally controlled.)
When group “00” is designated; col­lective ON/OFF instruction is sent to all units.
When group “01”-“16“ is designated; ON/OFF instruction is sent to the des­ignated units only.
ACTIVE/BYPASS switch This is a change-over switch for the program timer. (It selects timer operation on the pro­gram timer.) Use “BYPASS” when a program timer is not connected.
LCD Matrix Display This display indicates the operational sta­tus of all connected units either by steady lighting or by flashing.
“ACTIVE” The switch turns ON/OFF operational instructions from the program timer automatically. “BYPASS” ON/OFF Operation is by the central­ized remote controller only. Initial setting is “BYPASS”.
Independent “DUAL / CENTRAL” and “ACTIVE / BYPASS” setting of all the groups is possible. When the power supply to the centralized remote controller is cut due to power failure, all settings will return to original “DUAL” and “BYPASS”.
48
Page 49
5-3 Connection method
(1) Connections in the power supply cord.
1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-wrap. Connect a single phase 200V AC (220, 230, 240V) to .
E
As is the GND terminal, be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap.
Use a Ω1.6 (AWG 14) or above two-wire cable for the transmission line.
CAUTION : Never connect the power supply cord to the transmission terminal-block.
L N
TERMINAL-BLOCK FOR TRANSMISSION
TERMINAL-BLOCK OF POWER SUPPLY
Transmission
Tie-wrap
TRANSFORMER
LNE
Fuse(5A)
Tie-wrap
(W) (R) (O)
(BR)
200
220
230
T
(Y)
240
5A
L
N
E
Wiring has to be changed when a 200,230 or 240V power is used.
(2) Connection method of centralized remote controller and power supply board.
1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable.
To adaptor's terminal-block
Power supply board box
POWER SUPPLY
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER ON/OFF
AHEAD
To adaptor's
Non-polar, two-wire cable
terminal-block
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
Centralized remote controller
2. Wiring diagram 3. Be sure to set the maximum address number with the
dip switch SW17 on the centralized remote controller.
BACK
ACTIVE BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER ON/OFF
AHEAD
Dip switch SW17
Centralized remote controller
Power supply board
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
49
Page 50
6. PROGRAM TIMER ADAPTER
Length : 2m (6' 7")
Length : 2m (6' 7")
Length : 2m (6' 7")
This adapter is needed when a program timer(PAC-SC32PTA)or a centralized remote controller(PAC-805RC)is used.
Part No. PAC-825AD
6-1 Parts included
1 ADAPTER ·························1P 2 3-core cable···························1P
3 3-core cable···························1P
Length : 2m (6' 7")
4 4-core cable···························1P
5 5-core cable···························1P
6-2 Connection method
Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out the work.
(1) Connections in the adapter box.
1. Connect the power supply cord to the terminal-block and fix it in-place with a tie-wrap. Connect a single phase 200V AC (220, 230, 240V) to . As is the GND terminal, be sure to ground the earth wire.
E
L N
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap (when a centralized remote controller is being used). CAUTION : Never connect the power supply cord to the transmission terminal-block
Fig.1 Fig.2
TERMINAL-BLOCK FOR TRANSMISSION
Tie-wrap
Transmission cord
CN22
Dip switch
TRANS
CN1 CN21 CN51 CN30 CN42 CN50 CN40
Fuse(5A)
TRANSFORMER
(AG)
SW1
LNE
POWER SUPPLY CORD
TERMINAL-BLOCK FOR POWER SUPPLY
Tie-wrap
Terminal block for transmission to program timer or centralized remote controller
Wiring has to be changed when 200V power supply is used.
(W)
CN22
TRANS
(B)
200
SW1
T
(Y)
240
220
5A
L N
;
(2) When the centralized remote controller is used, set the address number with the dip switch SW1 of the
program timer adapter.
POWER SUPPLY
50
Page 51
(3) Connections from adaptor
Fig.3
To program timer or centralized remote controller
Adaptor
CN30 CN50
200~240V AC
6-3 Dimensions
Fig. 4
35
3-core cable 5-core cable
CN51
Remote controller Indoor unit
Max. length of each calbe is 10m.
40 80 40 27 18
220
Fixing screw hole
95
4- 5.5
22
12
74 7
8
120
2 2- 2.9
30
200
86 70 22
27
52
(Unit : mm)
65
15
15
hole
35
15
230
7. Wired remote controller and terminl bed for remote controller
Part No. PAR-JA240KAT-E
8. Remote Sensor
Part No. PAC-SE41TS-E
51
Page 52
1 Installation manual
This sheet 1 sheet 1 pc
1 pc 1 pc A 1pc B 1pc C 1pc D 1pc
1 pc 1 pc
5 Pipe cover (Liquid pipe) 6 2-core cable (12m) 7 Joint pipe
2 Gas pipe 3 Liquid pipe 4 Pipe cover (Gas pipe)
10. MULTI DISTRIBUTION PIPE FOR TWIN (50:50)
Tag
ID {15.88
ID {19.05
(indoor unit side)
ID {9.52
ID {9.52
(indoor unit side)
(outdoor unit side)
(outdoor unit side)
Model indication
A
C
B
Indoor unit side
Outdoor unit side
Outdoor unit
Indoor unit
Indoor unit
Distribution pipe (Packed part)
H
h
Part No.
Applicable Service Ref.
10-1 Parts included
• The gas pipe 2 and liquid pipe 3 are specified as shown below. 2 Gas pipe 3 Liquid pipe
SDD-50S-E Indoor unit : PK-1.6GKL, 2GKL Outdoor unit : PU-3,4 type
After cutting the pipe with the pipe cutter, deburr the pipe and clean off dirt and foreign materials.
Combination of indoor/outdoor unit
Distributor pipe model
Outdoor unit
The following items must be obtain locally in addition to the packed parts. a Heat insulating sealing tape.
PU-3 PU-4
b Extension pipe for refrigerant pipe.
10-2 Pipe size and refrigerant pipe limits.
Outdoor unit
Gas side
Outdoor unit side Indoor unit side Outdoor unit side Indoor unit side
PU-3 type PU-4S type
{15.88<5/8> {19.05<3/4>
Note1. The number of bends in the refrigerant pipe is respectively 8 or less in the range of <A+B> <A+C>
Pipe size (mm) Actual piping leng <m>
Liquid side
{15.88<5/8> {9.52<3/8> {9.52<3/8>
Indoor ~
Outdoor A+B= A+C= 30m or less
Indoor ~ Indoor
|B-CI=
8m or less
Indoor ~ Outdoor
H=20m
SDD-50S-E
Indoor unit
1.6 + 1.6 2 + 2
Height deffence <m>
Indoor ~ Indoor
h=1m
or less
(Note 1) No. of bend
or less less than 8
52
Page 53
10-3 Pipe connection
Control cable Prepared by site
0.8mm or more
Enclosed with
optional distribu-
tor pipe. (12m)
DC12V
Not designated
0.3mm
2
or more
Enclosed with
the optional
remote controller.
Control circuit voltage
Cable thickness
Polarity
A6C
(1) Note the following during work:
• Be sure to recheck the combination <Table1> and pipe size <Table2> of the outdoor/indoor units.
• Observe the refrigerant pipe length limits and no of bend limits <Table2>.
• Insert the refrigerant pipe (obtain locally) into the flared end of the distributior pipe (packed) until the former pipe stops. Use oxidization-free solder for connection when possible.
• The installation of the distributor pipe (packed) is not regulated.
• Take care to prevent dirt, foreign materials, etc., from entering the pipe when connecting the pipe.
• After checking remove the tag from the liquid pipe 3.
(2) Piping connection
• When welding the piping, use the exclusive joint 7 as the diame­ters of the pipe on the outdoor unit side and the joint section differ. (Refer to the table on the right.)
10-4 Heat insulating work
Gas pipe Liquid pipe
Do not bend or expend any distributor pipe
(Liquid pipe)
Gas side
•Outdoor unit PU-3type / PU-4type
Joint pipe A / B
ID {15.88 / 19.05
Liquid side
•Outdoor unit PU-3type, PU-4type
ID {9.52
Joint pipe C
• Install the gas pipe 2 while aligning it with the pipe cover
4. Seal the joint area of the pipe cover 4 with heat insulat­ing sealing tape (obtain locally).
Note:
1. Cover the entire refrigerant pipe (obtain locally) with heat insulating material If connercial heat insulating meterial is used, it must be 12mm or thicker.
2. As the pipe covers 4 and 5 will shrink slightly due to the high temperature, allow a lap when installing the heat insulat­ing material.
10-5 Control wiring for indoor unit
• Connect the control cables of the indoor units Nos. 1 and 2 with the enclosed 2-core cable (12m) 6.
• Connect the 2-core cable 6 to the remote controller terminal in the electrical box of each indoor unit and tighten the screws. (The polarity is not designated.)
Specifications of each control cable
Indoor unit No.1
Terminal
Terminal block block for control
12 12 12
for remote
controller
Indoor unit No.2
Terminal block
for remote
controller
A
Remote
controller
c
6
12
Terminal block for control
Outdoor unit
53
• Install the liquid pipe 3 while aligning it with the pipe cover
5. Seal the joint area of the pipe cover 5 with heat insulat­ing sealing tape (obtain locally).
Twin Setting
1 Set DIP switch SW6. 2 Remove the short-circuit connector CN40. (Leave it con-
nected to the No.1 unit.)
No.1 unit
SW6 Twin type
CN40 connector Leave it connected. Disconnect.
OFF
ON
4
321 4
No.2 unit
OFF
ON
321
Note 1: SW6 default settings are all OFF. Note 2: The short-circuit connector CN40 is connected by
factory.
Page 54
Page 55
Page 56
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100-8310 TELEX J24532 CABLE MELCO TOKYO
cCopyright 2000 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Issued in Aug. 2000. NO.OC230 325 Printed in Japan
New publication, effective Aug. 2000 Specifications subject to change without notice
Loading...