Mitsubishi PK-1.6FLA3, PK-2FLA3, PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA4 Service Manual

...
Page 1
SPLIT-TYPE,AIR CONDITIONERS
TEMP
ON / OFF
NOT AVAILABLE
AM PM
AM PM
˚C
TECHNICAL & SERVICE MANUAL
1997
No. OC129
REVISED EDITION-A
Series PK
Indoor unit [ Model names ] [ Service Ref. ]
Wall Mounted
1997, 1999, 2001 1997 1999 2001
PK-1.6FLA
PK-2FLA
PK-2.5FLA
PK-3FLA
PK-4FLSA
Indoor unit
PK-1.6FLA PK-2FLA PK-2.5FLA PK-3FLA PK-4FLSA
• PK-2.5FLA3, PK-2.5FLA4, PK-3FLA3, PK-3FLA4, PK-3FLA5, PK-4FLA
• Please void OC129 and OC200.
• This manual does not cover outdoor units. When servicing them, please refer to the service manual No.OC127 REVISED EDITION-A, OC187, OC217 REVISED EDITION-A and this manual in a set.
3
and PK-4FLA4are added in REVISED EDITION-A.
3
3
2/3
2/3/4
2/3
REMOTE CONTROLLER
PK-1.6FLA PK-2FLA PK-2.5FLA
PK-3FLA PK-4FLSA
PK-2.5FLA PK-3FLA PK-4FLSA
4
5
4
3
3
2
2
PK-3FLA
2
3
CONTENTS
1. TECHNICAL CHANGES·······························3
2. COMBINATION OF INDOOR AND OUTDOOR UNITS··············3
3. PART NAMES AND FUNCTIONS················3
4. SPECIFICATIONS·········································6
6. OUTLINES AND DIMENSIONS ··················16
7. WIRING DIAGRAM·····································20
8.
REFRIGERANT SYSTEM DIAGRAM
9. OPERATION FLOW-CHART······················24
10. MICROPROCESSOR CONTROL···············27
11. TROUBLESHOOTING·································36
12. DISASSEMBLY PROCEDURE ···················39
13. PARTS LIST················································42
14. OPTIONAL PARTS ·····································54
PK-2.5FLA
PK-2.5FLA PK-3FLA PK-3FLA PK-4FLSA PK-4FLSA
···············22
3
4 4 5
3 4
Page 2
Page 3
1
Air intake
Room air is suctioned in here.
(Removes dust and dirt from the intake air.)
Disperses airflow up and down as well as adjusts the angle of air flow direction.
Filter Air intake grille
Air outletAir outlet
Swing louvers
Air flow can be changed to horizontally by moving the Guide vane to the left or right.
Guide vane
Outdoor unit
(OC187)
Outdoor unit
(OC127 REVISED EDITION-A)
PU-1.6
VLJSA
2
VJA2 NJA1 VJA2 NJA1 VJA2 YJA2 YJA3 NJA1
VLJSA2YJSA2YJSA3TJSA2VJC YJC
PU-2 PU-2.5 PU-3 PU-4 PU-3
(OC217 REVISED EDITION-A)
Outdoor unit
VJB YJB
PU-3
PK-1.6FLA
3
PK-2FLA
3
PK-3FLA
2
PK-2.5FLA
2
PK-2.5FLA
3
PK-2.5FLA
4
PK-4FLSA
2
PK-4FLSA
3
PK-4FLSA
4
PK-3FLA
3
PK-3FLA
4
PK-3FLA
5
Indoor unit
TEMP
ON / OFF
NOT AVAILABLE
AM PM
AM PM
˚C
TECHNICAL CHANGES
PK-3FLA2 PK-3FLA3
Outdoor units has changed.
PK-2.5FLA2 ➔ PK-2.5FLA3 PK-3FLA3 PK-3FLA4 PK-4FLSA2 PK-4FLSA3
NOSE has changed by changing its shape.
UNDER PLATE has changed.
BOX ASSEMBLY has changed by changing its shape.
DRAIN PAN has changed by changing its shape.
2
COMBINATION OF INDOOR AND OUTDOOR UNITS
PK-2.5FLA3 ➔ PK-2.5FLA4 PK-3FLA4 PK-3FLA5 PK-4FLSA3 PK-4FLSA4
The parts No. of REMOTE CONTROLLER has changed. (The following parts numbers are interchangeable.)
[ T7W 570 200 ] [ T7W E06 714 ]
3
PART NAMES AND FUNCTIONS
Indoor Unit
3
Page 4
TEMP
ON / OFF
NOT AVAILABLE
AM PM
AM PM
˚C
MODE
FAN
VANE STOP
START
CLOCK
HR MIN.
ON / OFF
Remote controller
When cover is closed.
display
PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2, PK-2.5FLA3 PK-3FLA2, PK-3FLA3, PK-3FLA4 PK-4FLSA2, PK-4FLSA3
Part No. [ T7W 570 200 ]
display
OPERATION MODE display Operation mode display indicates which opera­tion mode is in effect.
• • display CHECK&TEST RUN display indicates that the unit is being checked or test-run.
TEST RUNCHECK
display
Displays when batteries are dead.
display
Displays when setting timer.
Lights when signal is sent from the remote controller to the indoor unit.
display
display
The vertical direction of airflow is indicated in
marks.
display
FAN SPEED display indicates which fan speed has been selected.
SET TEMP. display indicates desired tempera­ture set.
CLOCK display
DIsplays the current time.
“ ”display
Flashes when the current time is displayed.
TIMER display
Displays when in timer operation or when set­ting timer.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
“ ” “ ” display
Displays when the current time and the timer
time can be changed.
button
SET TEMPERATURE button sets any desired room temperature.
When cover is open.
MODE SELECT button
MODE SELECT button is used to change cooling. dry (dehumidify) and fan (ventilation) operation modes.
FAN SPEED SELECT button
FAN SPEED SELECT button selects low or high fan speed.
VANE CONTROL button
VANE CONTROLbutton regulates the vertical distribution of airflow.
button
Push to start operation. Push again to stop operation.
SET CLOCK button
Button used to set the current time.
TIMER CONTROL buttons
STOP (OFF timer): when this switch is set, the air conditioner will be automatically stopped at the preset time. START(ON timer): when this switch is set, the air conditioner will be automatically started at the preset time.
HR. and MIN.buttons
Buttons used to set the “hour and minute” of the current time and timer time.
4
Page 5
Wireless remote controller
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
NOT AVAILABLE
CHECK
TEST RUN
˚C
AMPM
AMPM
VANE CONTROL button
Used to change the air flow direction.
CLOCK button
RESET button
SET button
ON/OFF button
The unit is turned ON and OFF alternately each time the button is pressed.
LOUVER button
This switch the horizontal fan motion ON and OFF.
(Not available for this model.)
MODE SELECT button
Used to switch the operation mode between cooling, drying, fan.
CHECK-TEST RUN button
Only press this button to perform an inspec­tion check or test operation. Do not use it for normal operation.
FAN SPEED SELECT button
Used to change the fan speed.
TIMER display
Displays when in timer operation or when setting timer.
button
SET TEMPERATURE button sets any desired room temperature.
CLOCK display
Displays the current time.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
Buttons used to set the “hour and minute” of the current time and timer settings.
h and min buttons
display
SET TEMP. display indicates desired temper­ature set.
display
FAN SPEED display indicates which fan speed has been selected.
display
The vertical direction of air flow is indicated.
display
Blinks when model is selected.
display
Lights up while transmission to the indoor unit is mode using switches.
display
CHECK&TEST RUN display indicates that the unit is being checked or test-run.
display
OPERATION MODE display Operation mode display indicates which op­eration mode is in effect.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch is set, the air conditioner will be au­tomatically stopped at the preset time. AUTO START (ON timer): when this switch is set, the air conditioner will be automatical­ly started at the preset time.
MODEL SELECT
CHECK
TEST RUN
When cover is open.
PK-2.5FLA4 PK-3FLA5 PK-4FLSA4
Part No. [ T7W E06 714 ]
5
Page 6
4 SPECIFICATIONS
Item
Service Ref.
PK-1.6FLA
3 PK-2FLA3
PK-2FLA3
PU-2VJA2
Single, 50Hz, 220/240V
2.44 / 2.48
11.3 / 10.8(98/96) 48 / 52
PU-2NJA
1
Single, 60Hz, 220V
2.45
11.4(98) 54
2.97
13.6(99) 54
Munsell 5Y 7/1
Capillary tube
Hermetic
Line start
Inner thermostat, HP/LP switch
Plate fin coil
Propeller (direct) o 1
0.065
45 (1588)
870 (34-1/4) 295 (11-5/8) 650 (25-5/8)
60 (132)
9.52 (3/8)
15.88 (5/8) Flared Flared
w3 Max. 20m w3 Max. 30m
49 50
32 / 38
R-22 1.78 (3.9)
R-22 1.9 (4.2)
NHJ41VMD
2.0
NHJ33NBD
1.5
Single, 50Hz, 220/240V
0.08
0.37(98/90)
0.4
Munsell 3.4Y 7.7/0.8(White)
Plate fin coil
Line flow (direct) o 1
0.030
10-14 (353-459)
0 (direct blow)
Wireless remote controller & Built-in
38 - 45
20 (13/16)
1,250 (49-3/16)
200 (7-7/8)
300 (11-13/16)
17 (37)
Single, 60Hz, 220V
0.09
0.42(97)
0.5 0.5
w6 w7
16,000
4,600
3.06
19,000
5,450
2.54
27/19.0°C, 35/24°C
Cooling (JIS B8616)
19,100
5,600
2.52/2.56
27/19.0°C, 35/24°C
Cooling (JIS B8616)
13,300
3,900
1.49/1.59
PK-1.6FLA
3
Single, 50Hz, 220/240V
0.07
0.32(99/91)
0.4
Munsell 3.4Y 7.7/0.8(White)
Plate fin coil
Line flow (direct) o 1
0.030
10-13 (353-459)
0 (direct blow)
Wireless remote controller & Built-in
36 - 43
20 (13/16)
1,250 (49-3/16)
200 (7-7/8)
300 (11-13/16)
17 (37)
PU-1.6VLJA
2
Single, 50Hz, 220/240V
1.42 / 1.52
6.7 / 6.9 (97/92) 30 /33
Munsell 5Y 7/1
Capillary tube
Hermetic
RH247VFC
1.2
Line start
w4
Plate fin coil
Propeller (direct ) o 1
0.065
45 (1588)
49 870 (34-1/4) 295 (11-5/8) 650 (25-5/8)
45 (99)
R-22 1.3 (2.9)
9.52 (3/8)
15.88 (5/8) Flared Flared
w3 Max. 15m w3 Max. 20m
Condition Capacity w1 Total input w1
Service Ref. Power supply(phase, cycle,voltage)
Input
Running current (Power factor)
Starting current External finish Heat exchanger
Fan(drive) o No.
Fan motor output
Airflow (Low-High)
External static pressure Booster heater Operation control & Thermostat Noise level (Low-High) w2 Cond. drain conn. O.D.
Dimensions
Weight Service Ref. Power supply (phase, cycle, voltage)
Input Running current (Power factor)
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Heat exchanger
Fan(drive) o No.
Fan motor output
Airflow Defrost method Noise level w2
Dimensions
Weight Crankcase heater Refrigerant Charge
Pipe size O.D.
Connection method Between the indoor &
outdoor units
Btu/h
W
kW
kW
A (%)
A
kW
m
3
/min(CFM)
Pa(mmAq)
kW
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
kW
A(%)
A
kW
kW
m
3
/min(CFM)
dB mm(in.) mm(in.) mm(in.)
kg(lbs)
W
kg(lbs) mm(in.) mm(in.)
Indoor, Outdoor D.B./W.B.°C
Liquid
Gas
W
D H
W
D H
REFRIGERANT PIPING
OUTDOOR UNIT
Indoor side Outdoor side Height difference Piping length
INDOOR UNIT
1. STANDARD SPECIFICATION
w1 Refrigerant piping length (one way) : 5m (16ft) w2 Noise level is measured in an unacoustic room based on JIS conditions. w3 Up to 20m it is unnecessary to charge additional refrigerant. w4 Inner thermostat, HP/LP switch. w5 Motor protector, Thermal switch, HP/LP switch. w6 Indoor, Outdoor D.B./W.B. : 29/19°C, 46/24°C w7 Cooling SSA385, 386
6
Page 7
Item
Service Ref.
PK-2.5FLA
Indoor, Outdoor D.B./W.B.°C
Condition Capacity w1 Total input w1
Service Ref. Power supply(phase, cycle,voltage)
Input
Running current (Power factor)
Starting current
External finish
Btu/h
W
kW
Single, 50Hz, 220/240V
kW
A(%)
A
23,900
7,000
2.56 / 2.62
PK-2.5FLA2 PK-2.5FLA3 PK-2.5FLA4
0.095 / 0.095
0.44 / 0.44 (98/90)
0.7 / 0.8 Munsell 3.4Y 7.7/0.8(White)
Heat exchanger
Fan(drive) o No. Fan motor output Airflow (Low-High) External static pressure
Booster heater
INDOOR UNIT
Operation control & Thermostat Noise level (Low-High) w2 Cond. drain conn. O.D.
Dimensions
W
D
H Weight Service Ref. Power supply (phase, cycle, voltage)
Input
Running current (Power factor)
Starting current
kW
3
/min(CFM)
m
Pa(mmAq)
kW
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
kW
A(%)
A
Wireless remote controller & Built-in
PU-2.5VJA
2
Single, 50Hz, 220/240V
2.46 / 2.52
11.4 / 10.7 (98/98) 45 / 49
External finish Refrigerant control Compressor
Model Motor output
kW
NHJ41VMD
2.0 Starter type Protection devices
Inner thermostat, HP/LP switch
Heat exchanger
OUTDOOR UNIT
Fan(drive) o No. Fan motor output Airflow
kW
3
/min(CFM)
m Defrost method Noise level w2
Dimensions
Weight Crankcase heater Refrigerant Charge
Pipe size O.D.
Connection method Between the indoor &
REFRIGERANT PIPING
outdoor units
W
D H
mm(in.) mm(in.) mm(in.)
kg(lbs)
kg(lbs)
Liquid
Gas
mm(in.)
mm(in.) Indoor side Outdoor side Height difference Piping length
dB
W
52 53
295 (+24) (11-5/8 (add 1))
32 / 38
R-22 2.4 (5.3)
w1 Refrigerant piping length (one way) : 5m (16ft) w2 Noise level is measured in an unacoustic room based on JIS conditions. w3 Up to 20m it is unnecessary to charge additional refrigerant. w4 Indoor, Outdoor D.B./W.B. : 29/19°C, 46/24°C. w5 Cooling SSA385, 386
2 PK-2.5FLA3 PK-2.5FLA4
27/19.0°C, 35/24°C
Cooling (JIS B8616)
24,400
Single, 60Hz, 220V
Plate fin coil
Line flow (direct) o 2
0.04
15 - 20(530-706)
0 (direct blow)
39 - 45
20 (13/16)
1,400 (55-1/8)
235 (9-1/4)
340 (13-3/8)
24 (53)
Single, 60Hz, 220V
13.4 (99)
Munsell 5Y 7/1
Capillary tube
Hermetic
Line start
Plate fin coil
Propeller (direct) o 1
0.085
50 (1765)
870 (34-1/4)
850 (33-7/16)
71 (157)
9.52 (3/8)
15.88 (5/8) Flared Flared
w3 Max. 20m w3 Max. 30m
7,150
3.01
0.095
0.44 (98)
0.7
PU-2.5NJA
2.91
58
NHJ38NBD
1.7
R-22 2.4 (5.3)
w4 w5
22,700
6,650
3.54
1
3.44
15.8(99) 58
7
Page 8
Item
Service Ref.
PK-3FLA
2
PK-3FLA2
27/19.0°C, 35/24°C
Cooling (JIS B8616)
Munsell 3.4Y 7.7/0.8(White)
Plate fin coil
Line flow (direct) o 2
0.04
15 - 20 (530-706)
0 (direct blow)
Wireless remote controller & Built-in
39 - 45
20 (13/16)
1,400 (55-1/8)
235 (9-1/4)
340 (13-3/8)
24 (53)
24,600
7,200
3.28 / 3.30 3.28 / 3.30
27,300
8,000
3.54
Single, 50Hz, 220/240V
0.095 / 0.095
0.44 / 0.44 (98/90)
0.7 / 0.8
Single, 60Hz, 220V
0.095
0.44 (98)
0.7
w4 w5
23,500
6,900
4.19
4.09
20.9(89) 80
PU-3VJA
2
Single, 50Hz, 220/240V
3.18 / 3.20
15.1/13.9(96/96) 68 / 68
Three, 50Hz, 380/415V
3.18 / 3.20
5.7/5.3(85/84) 36 / 36
NHJ52VND
2.2 2.2
NHJ52YDA NHJ52YDE
3.44
17.6(89) 80
PU-3NJA
1
Single, 60Hz, 220V
NHJ47NAD
2.2
w6 w7
53 53
w6
32 / 38
R-22 3.08 (6.8)
32 / 38
R-22 2.88 (6.3)
38
R-22 3.5 (7.7)
Munsell 5Y 7/1
Capillary tube
Hermetic
Line start
Plate fin coil
Propeller (direct) o 1
0.085
50 (1765)
870 (34-1/4)
295 (+24) (11-5/8 (add 1))
850 (33-7/16)
73 (161)
9.52 (3/8)
15.88 (5/8) Flared Flared
w3 Max. 20m w3 Max. 30m
Condition Capacity w1 Total input w1
Service Ref. Power supply(phase, cycle,voltage)
Input
Running current (Power factor)
Starting current External finish Heat exchanger
Fan(drive) o No.
Fan motor output
Airflow (Low-High)
External static pressure Booster heater Operation control & Thermostat Noise level (Low-High) w2 Cond. drain conn. O.D.
Dimensions
Weight Service Ref. Power supply (phase, cycle, voltage)
Input Running current (Power factor)
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Heat exchanger
Fan(drive) o No.
Fan motor output
Airflow Defrost method Noise level w2
Dimensions
Weight Crankcase heater Refrigerant Charge
Pipe size O.D.
Connection method Between the indoor &
outdoor units
Btu/h
W
kW
kW
A(%)
A
kW
m
3
/min(CFM)
Pa(mmAq)
kW
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
kW
A(%)
A
kW
kW
m
3
/min(CFM)
dB mm(in.) mm(in.) mm(in.)
kg(lbs)
W
kg(lbs) mm(in.) mm(in.)
Indoor, Outdoor D.B./W.B.°C
Liquid
Gas
W
D H
W
D H
REFRIGERANT PIPING
OUTDOOR UNIT
Indoor side Outdoor side Height difference Piping length
INDOOR UNIT
PU-3YJA2 PU-3YJA3
w1 Refrigerant piping length (one way) : 5m (16ft) w2 Noise level is measured in an unacoustic room based on JIS conditions. w3 Up to 20m it is unnecessary to charge additional refrigerant. w4 Indoor, Outdoor D.B./W.B. : 29/19°C, 46/24°C w5 Cooling SSA385, 386 w6 Inner thermostat, HP switch, LP switch. w7 Thermal switch, Reversed-phase protector, HP switch, LP switch, Thermal relay.
8
Page 9
Item
Indoor, Outdoor D.B./W.B.°C
Condition Capacity w1 Total input w1
Service Ref. Power supply(phase, cycle,voltage)
Input
Running current (Power factor)
Starting current External finish Heat exchanger
Fan(drive) o No.
Fan motor output
Airflow (Low-High)
External static pressure Booster heater
INDOOR UNIT
Operation control & Thermostat Noise level (Low-High) w2 Unit drain pipe O.D.
Dimensions
Weight Service Ref. Power supply (phase, cycle, voltage)
Input Running current (Power factor)
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Heat exchanger
OUTDOOR UNIT
Defrost method Noise level w2
Dimensions
Weight Crankcase heater Refrigerant Charge
Pipe size O.D.
Connection method Between the indoor &
REFRIGERANT PIPING
outdoor units
Fan(drive) o No.
Fan motor output
Airflow
Indoor side Outdoor side Height difference Piping length
W
D H
W
D H
Liquid
Gas
Service Ref.
Btu/h
W
kW
kW
A(%)
A
kW
3
/min(CFM)
m
Pa,mmAq
kW
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
kW
A(%)
A
kW
kW
3
/min(CFM)
m
dB mm(in.) mm(in.) mm(in.)
kg(lbs)
W
kg(lbs) mm(in.) mm(in.)
3.28 / 3.30 3.28 / 3.30
Single, 50Hz, 220/240V
0.095 / 0.095
0.44 / 0.44 (98/90)
PU-3VJC
Single, 50Hz, 220/240V
3.18 / 3.20
15.1/13.9(96/96) 54 / 58
NH52VND
2.2
w6 w7
32 / 38 32 / 38 38
R-22 2.8(6.2)
PK-3FLA
27,000
7,900
PK-3FLA3 PK-3FLA4 PK-3FLA5
0.7 / 0.8
Wireless remote controller & Built-in
Three, 50Hz, 380/415V
5.7/5.3(85/84)
52 53
3 PK-3FLA4 PK-3FLA5
27/19°C , 35/24°C
Cooling (JIS B8616)
Munsell 3.4Y 7.7/0.8(White)
Plate fin coil
Line flow (direct) o 2
15 - 20 (530-706)
0 (direct blow)
20 (13/16)
1,400 (55-1/8)
235 (9-1/4)
340 (13-3/8)
PU-3YJC
3.18 / 3.20
34 / 37
Munsell 5Y 7/1
Capillary tube
Hermetic
NH52YDE
2.4 Line start
Plate fin coil
Propeller (direct) o 1
50 (1765)
870 (34-1/4)
295 (+24) (11-5/8 (add 1))
850 (33-7/16)
9.52 (3/8)
15.88 (5/8)
w3 Max. 20m w3 Max. 30m
w1 Refrigerant piping length (one way) : 5m (16ft) w2 Noise level is measured in an unacoustic room based on JIS conditions. w3 Up to 20m it is unnecessary to charge additional refrigerant. w4 Indoor, Outdoor D.B./W.B. : 29/19°C, 46/24°C w5 Cooling SSA385, 386 w6 Inner thermostat, HP switch, LP switch. w7 Thermal switch, Reversed-phase protector, HP switch, LP switch, Thermal relay.
0.04
39 - 45
24 (53)
0.085
73 (161)
Flared Flared
27,300
8,000
3.54
Single, 60Hz, 220V
0.095
0.44 (98)
0.7
PU-3NJA
Single, 60Hz, 220V
3.44
17.6(89) 80
NHJ47NAD
R-22 3.5 (7.7)
1
2.2
w6
w4 w5
23,500
6,900
4.19
4.09
20.9(89) 80
9
Page 10
Item
Service Ref.
PK-3FLA
2 PK-3FLA3 PK-3FLA4 PK-3FLA5
PK-3FLA2 PK-3FLA3 PK-3FLA4 PK-3FLA5
27/19°C , 35/24°C
Cooling (JIS B8616)
Munsell 3.4Y 7.7/0.8(White)
Plate fin coil
Line flow (direct) o 2
0.04
15 - 20 (530-706)
0 (direct blow)
Wireless remote controller & Built-in
39 - 45
20 (13/16)
1,400 (55-1/8)
235 (9-1/4)
340 (13-3/8)
24 (53)
25,600
7,500
2.75
Single, 50Hz, 220V
0.095
0.44 (98)
0.7
PU-3VJB
Single, 50Hz, 220V
2.65
12.4(97) 54
PU-3YJB
Three, 50Hz, 380V
2.65
4.2(97) 34
NH47VNHT
2.2
NH47YDNT
2.2
w6 w7
52
32 32
Munsell 5Y 7/1
Capillary tube
Hermetic
Line start
Plate fin coil
Propeller (direct) o 1
0.085
50 (1765)
870 (34-1/4)
295 (+24) (11-5/8 (add 1))
850 (33-7/16)
73 (161)
9.52 (3/8)
15.88 (5/8) Flared Flared
w3 Max. 20m w3 Max. 30m
Condition Capacity w1 Total input w1
Service Ref. Power supply(phase, cycle,voltage)
Input
Running current (Power factor)
Starting current External finish Heat exchanger
Fan(drive) o No.
Fan motor output
Airflow (Low-High)
External static pressure Booster heater Operation control & Thermostat Noise level (Low-High) w2 Unit drain pipe O.D.
Dimensions
Weight Service Ref. Power supply (phase, cycle, voltage)
Input Running current /Power factor
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Heat exchanger
Fan(drive) o No.
Fan motor output
Airflow Defrost method Noise level w2
Dimensions
Weight Crankcase heater Refrigerant Charge
Pipe size O.D.
Connection method Between the indoor &
outdoor units
Btu/h
W
kW
kW
A(%)
A
kW
m
3
/min(CFM)
Pa,mmAq
kW
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
kW
A(%)
A
kW
kW
m
3
/min(CFM)
dB mm(in.) mm(in.) mm(in.)
kg(lbs)
W
kg(lbs) mm(in.) mm(in.)
Indoor, Outdoor D.B./W.B.°C
Liquid
Gas
W
D H
W
D H
REFRIGERANT PIPING
OUTDOOR UNIT
Indoor side Outdoor side Height difference Piping length
INDOOR UNIT
R-22 3.0(6.6)
w1 Refrigerant piping length (one way) : 5m (16ft) w2 Noise level is measured in an unacoustic room based on JIS conditions. w3 Up to 20m it is unnecessary to charge additional refrigerant. w4 Indoor, Outdoor D.B./W.B. : 29/19°C, 46/24°C w5 Cooling SSA385, 386 w6 Inner thermostat, HP switch, LP switch. w7 Thermal switch, Reversed-phase protector, HP switch, LP switch, Thermal relay.
10
Page 11
Item
Service Ref.
PK-4FLSA
Indoor, Outdoor DB/WB°C
Condition Capacity w1 Total input w1
Service Ref. Power supply(phase, cycle,voltage)
Input
Running current (Power factor)
Starting current
External finish
Btu/h
W
kW
kW
A(%)
A
3.46 / 3.63 3.40 / 3.47
33,400
9,800
PK-4FLSA
Single, 50Hz, 220/240V
0.114 / 0.114
0.53 / 0.53 (98/90)
0.8 / 0.9 Munsell 3.4Y 7.7/0.8(White)
Heat exchanger
Fan(drive) o No. Fan motor output Airflow (Low-High) External static pressure
Booster heater
INDOOR UNIT
Operation control & Thermostat Noise level (Low-High) w2 Cond. drain conn. O.D.
Dimensions
W
D
H Weight Service Ref. Power supply (phase, cycle, voltage)
Input
Running current (Power factor)
Starting current
kW
3
/min(CFM)
m
Pa(mmAq)
kW
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
kW
A(%)
A
Wireless remote controller & Built-in
2
PU-4VLJSA
Single, 50Hz, 220/240V
PU-4YJSA2 PU-4YJSA3
Three, 50Hz, 380/415V
3.35 / 3.52
16.9 / 16.3 (90/90)
5.7 / 5.5 (87/85)
79 / 79
3.29 / 3.36
38 / 38 External finish Refrigerant control Compressor
Model Motor output
kW
NH56VND
2.7 2.7
NHJ56YDA NHJ56YDE
Starter type Protection devices
w6 w7 w7
Heat exchanger
OUTDOOR UNIT
Fan(drive) o No. Fan motor output Airflow
kW
3
/min(CFM)
m Defrost method Noise level w2
Dimensions
Weight Crankcase heater Refrigerant Charge
Pipe size O.D.
Connection method Between the indoor &
REFRIGERANT PIPING
outdoor units
W
D H
mm(in.) mm(in.) mm(in.)
kg(lbs)
kg(lbs)
Liquid
Gas
mm(in.)
mm(in.) Indoor side Outdoor side Height difference Piping length
dB
W
54 55 55
295 (+24) (11-5/8 (add 1))
32 / 38
R-22 3.8 (8.4)
32 / 38
R-22 4.6 (10.1)
w1 Refrigerant piping length (one way) : 5m (16ft) w2 Noise level is measured in an unacoustic room based on JIS conditions. w3 Up to 20m it is unnecessary to charge additional refrigerant. w4 Indoor, Outdoor D.B./W.B. : 29/19°C, 46/24°C w5 Cooling SSA385, 386 w6 Inner thermostat, HP switch, LP switch. w7 Thermal switch, Reversed-phase protector, HP switch, LP switch, Thermal relay.
2 PK-4FLSA3 PK-4FLSA4
27/19.0°C, 35/24°C
Cooling (JIS B8616)
2 PK-4FLSA3 PK-4FLSA4
Plate fin coil
Line flow (direct) o 2
0.07
22 - 28 (777 - 989)
0 (direct blow)
41 - 46
20 (13/16)
1,680 (66-1/8)
235 (9-1/4)
340 (13-3/8)
28 (62)
Munsell 5Y 7/1
Capillary tube
Hermetic
Line start
Plate fin coil
Propeller (direct) o 2
0.065 + 0.065 95 (3352)
870 (34-1/4)
1258 (49-1/2)
94 (207)
9.52 (3/8)
19.05 (4/3) Flared Flared
w3 Max. 30m w3 Max. 40m
37,500 11,000
4.38
Single, 60Hz, 220V
0.114
0.53 (98)
0.8
PU-4TJSA
2
3, 60Hz, 220V
4.27
12.2 (92) 69
NHJ56TKA
2.7
38
R-22 4.6 (10.1)
w4 w5
33,800
9,900
5.08
4.97
14.0(93) 69
11
Page 12
2. POWER SUPPLY & MODEL NAMES
Service Ref. (Indoor unit)Power supply
1ph
3ph 1ph
3ph
220,230,240V
380/220,400/230,415/240V 220V
220V
PU-1.6VLJA2
— —
PU-2VJA
2
PU-2NJA
1
PU-2.5VJA
2
PU-2.5NJA
1
PU-3VJA
2
PU-3VJB PU-3YJA
3
PU-3YJB PU-3NJA
1
PU-3VJC PU-3VJB PU-3YJC PU-3YJB PU-3NJA
1
PU-4VLJSA2
PU-4YJSA3
PU-4TJSA
2
50Hz
60Hz
Service Ref. (Outdoor unit)
PK-4FLSA
2
PK-4FLSA3 PK-4FLSA4
PK-3FLA3 PK-3FLA4 PK-3FLA5
PK-3FLA2 PK-2.5FLA2 PK-2.5FLA3 PK-2.5FLA4
PK-2FLA3 PK-1.6FLA3
Power supply (1 Phase) Service Ref.
Current Input Starting current Outdoor unit
A
kW
A
0.32
0.07
0.4
PU-1.6
0.37
0.08
0.4
PU-2
0.44
0.095
0.7
PU-2.5
0.44
0.095
0.7
PU-3
0.44
0.095
0.7
PU-3
0.53
0.114
0.8
PU-4
0.32
0.07
0.4
PU-1.6
0.37
0.08
0.4
PU-2
0.44
0.095
0.8
PU-2.5
0.44
0.095
0.8
PU-3
0.44
0.095
0.8
PU-3
0.53
0.114
0.8
PU-4
V : 220V 50Hz V : 230V 50Hz
PK-4FLSA2 PK-4FLSA3 PK-4FLSA4
PK-3FLA3 PK-3FLA4 PK-3FLA5
PK-3FLA2
PK-2.5FLA2 PK-2.5FLA3 PK-2.5FLA4
PK-2FLA3
PK-1.6FLA3
PK-4FLSA2 PK-4FLSA3 PK-4FLSA4
PK-3FLA3 PK-3FLA4 PK-3FLA5
PK-3FLA2
PK-2.5FLA2 PK-2.5FLA3 PK-2.5FLA4
PK-2FLA3
PK-1.6FLA3
Power supply (1 Phase) Service Ref.
Current Input Starting current Outdoor unit
A
kW
A
0.32
0.07
0.4
PU-1.6
0.37
0.08
0.4
PU-2
0.44
0.095
0.8
PU-2.5
0.44
0.095
0.8
PU-3
0.44
0.095
0.8
PU-3
0.53
0.114
0.8
PU-4
0.43
0.09
0.5
PU-2
0.44
0.095
0.7
PU-2.5
0.44
0.095
0.7
PU-3
0.44
0.095
0.7
PU-3
0.53
0.114
0.8
PU-4
V : 240V 50Hz N : 220V 50Hz
PK-4FLSA2 PK-4FLSA3 PK-4FLSA4
PK-3FLA3 PK-3FLA4 PK-3FLA5
PK-3FLA2
PK-2.5FLA2 PK-2.5FLA3 PK-2.5FLA4
PK-2FLA3
PK-1.6FLA3
PK-4FLSA2 PK-4FLSA3 PK-4FLSA4
PK-3FLA3 PK-3FLA4 PK-3FLA5
PK-3FLA2
PK-2.5FLA2 PK-2.5FLA3 PK-2.5FLA4
PK-2FLA3
Notes : 1. Power supply key N
……
1ph, 220V, 60Hz Y…3ph, 380/220, 400/230,
V(L) …1ph, 220, 230 240V, 50Hz 415/240V, 50Hz, 4 wires
……
T
3ph, 220V, 60Hz
2. Primary power supplies for all indoor units are single-phase.
3. ELECTRICAL SPECIFICATION
(1) Rating conditions
Series PK Indoor Unit (Single Phase)
JIS B8615, 8616
Indoor : D.B. 27°C (80°F), W.B. 19°C(66°F) Outdoor : D.B. 35°C (95°F)
12
Page 13
5
DATA
1. PERFORMANS DATA
(67˚ F) (68˚ F)
(67˚ F) (68˚ F)
(67˚ F) (68˚ F)
(67˚ F) (68˚ F)
(67˚ F) (68˚ F)
(67˚ F) (68˚ F)
(67˚ F) (68˚ F)
(67˚ F) (68˚ F)
(67˚ F) (68˚ F)
(67˚ F) (68˚ F)
(67˚ F) (68˚ F)
50Hz
PK-1.6FLA
T.C.
3.9
4.2
4.3
4.4
4.4
4.7
3.8
4.1
4.2
4.3
4.3
4.6
3.7
3.9
4.1
4.1
4.2
4.5
3.6
3.9
4.0
4.0
4.1
4.4
3.5
3.8
3.9
4.0
4.0
4.3
3.4
3.6
3.7
3.8
3.9
4.1
3.4
3.6
3.7
3.8
3.8
4.1
3.2
3.4
3.6
3.6
3.7
3.9
3.2
3.4
3.5
3.6
3.6
3.9
13
0.18
0.81
3 PK-2FLA3 PK-2.5FLA3/4 PK-3FLA2 PK-3FLA3/4/5 PK-3FLA2/3/4/5 W PK-4FLSA2/3/4
C.F.
T.C. C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
Lower limit … Indoor : D.B. 21°C(70°F), W.B. 15.5°C(60°F), Outdoor : D.B. 21°C(70°F).
{
Upper limit … Indoor : D.B. 35°C(95°F), W.B. 22.5°C(72.5°F), Outdoor : D.B. 46°C(115°F)…VLJ, VJB, YJB. W
5.6
6.0
6.2
6.2
6.4
6.7
5.5
5.9
6.0
6.1
6.2
6.6
5.3
5.6
5.8
5.9
6.0
6.4
5.2
5.5
5.7
5.8
5.9
6.3
5.1
5.4
5.6
5.7
5.8
6.2
4.9
5.2
5.4
5.4
5.5
5.9
4.8
5.2
5.3
5.4
5.5
5.9
4.6
4.9
5.1
5.2
5.3
5.7
4.6
4.9
5.1
5.1
5.2
5.6
4.4
4.7
4.9
4.9
5.0
5.4
4.3
4.6
4.7
4.8
4.9
5.3
(T.I.)
14
0.16
0.73
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
T.C. C.F.
7.0
7.5
7.7
7.8
7.9
8.4
6.9
7.3
7.6
7.7
7.8
8.3
6.6
7.1
7.3
7.4
7.5
8.0
6.5
6.9
7.2
7.3
7.4
7.9
6.3
6.8
7.0
7.1
7.2
7.7
6.1
6.5
6.7
6.8
6.9
7.4
6.0
6.4
6.7
6.8
6.9
7.4
5.8
6.2
6.4
6.5
6.6
7.1
5.7
6.1
6.3
6.4
6.5
7.0
5.5
5.9
6.1
6.2
6.3
6.7
5.3
5.7
5.9
6.0
6.1
6.6
COOLING CAPACITY
Service Ref. Temperature Outdoor D.B. Indoor W.B.
21˚C (69.8˚ F)
25˚C (77˚ F)
30˚C (86˚ F)
32.2˚C (90˚ F)
35˚C (95˚ F)
40˚C (104˚ F)
40.6˚C (105˚ F)
45˚C (113˚ F)
46˚C (115˚ F)
50˚C (69.8˚ F)
52˚C (125.5˚ F)
Evaporator airflow (CMM) Bypass factors S.H.F. at rating conditions
Notes: 1. T.C.: Total capacity (kW) …(kcal/h)=(kW)x860, (Btu/h)=4x(kW)x860
16˚C
(60.8˚ F)
18˚C
(64.4˚ F)
19˚C
(66.2˚ F)
19.4˚C 20˚C 22˚C
(71.6˚ F)
16˚C
(60.8˚ F)
18˚C
(64.4˚ F)
19˚C
(66.2˚ F)
19.4˚C 20˚C 22˚C
(71.6˚ F)
16˚C
(60.8˚ F)
18˚C
(64.4˚ F)
19˚C
(66.2˚ F)
19.4˚C 20˚C 22˚C
(71.6˚ F)
16˚C
(60.8˚ F)
18˚C
(64.4˚ F)
19˚C
(66.2˚ F)
19.4˚C 20˚C 22˚C
(71.6˚ F)
16˚C
(60.8˚ F)
18˚C
(64.4˚ F)
19˚C
(66.2˚ F)
19.4˚C 20˚C 22˚C
(71.6˚ F)
16˚C
(60.8˚ F)
18˚C
(64.4˚ F)
19˚C
(66.2˚ F)
19.4˚C 20˚C 22˚C
(71.6˚ F)
16˚C
(60.8˚ F)
18˚C
(64.4˚ F)
19˚C
(66.2˚ F)
19.4˚C 20˚C 22˚C
(71.6˚ F)
16˚C
(60.8˚ F)
18˚C
(64.4˚ F)
19˚C
(66.2˚ F)
19.4˚C 20˚C 22˚C
(71.6˚ F)
16˚C
(60.8˚ F)
18˚C
(64.4˚ F)
19˚C
(66.2˚ F)
19.4˚C 20˚C 22˚C
(71.6˚ F)
16˚C
(60.8˚ F)
18˚C
(64.4˚ F)
19˚C
(66.2˚ F)
19.4˚C 20˚C 22˚C
(71.6˚ F)
16˚C
(60.8˚ F)
18˚C
(64.4˚ F)
19˚C
(66.2˚ F)
19.4˚C 20˚C 22˚C
(71.6˚ F)
C.F.(T.I.) : Correction factors of Total input(Indoor unit input + Outdoor unit input)
2. (°F)=32+9/5(°C)
3. Guaranteed operating range(cooling)
20
0.11
0.81
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
T.C. C.F.
(T.I.)
7.2
0.81
7.7
0.82
7.9
0.83
8.0
0.83
8.2
0.84
8.7
0.86
7.1
0.84
7.5
0.85
7.8
0.86
7.9
0.86
8.0
0.87
8.5
0.89
6.8
0.90
7.3
0.92
7.5
0.93
7.6
0.93
7.7
0.94
8.2
0.96
6.7
0.93
7.1
0.95
7.4
0.96
7.5
0.97
7.6
0.97
8.1
0.99
6.5
0.96
7.0
0.99
7.2
1.00
7.3
1.00
7.4
1.01
7.9
1.04
6.2
1.03
6.7
1.06
6.9
1.07
7.0
1.08
7.1
1.08
7.6
1.11
6.2
1.04
6.6
1.06
6.9
1.08
6.9
1.08
7.1
1.09
7.6
1.12
5.9
1.10
6.4
1.12
6.6
1.14
6.7
1.15
6.8
1.16
7.3
1.20
5.9
1.11
6.3
1.14
6.5
1.15
6.6
1.16
6.7
1.17
7.2
1.21
5.6
1.16
6.0
1.19
6.2
1.21
6.3
1.22
6.5
1.23
6.9
1.28
5.5
1.19
5.9
1.22
6.1
1.24
6.2
1.25
6.3
1.26
6.8
1.31
20
0.12
0.76
W Outdoor unit
PU-3JB
T.C. C.F.
7.9
8.4
8.7
8.8
9.0
9.5
7.8
8.3
8.5
8.6
8.8
9.4
7.5
8.0
8.2
8.3
8.5
9.0
7.3
7.8
8.1
8.2
8.3
8.9
7.2
7.6
7.9
8.0
8.2
8.7
6.8
7.3
7.6
7.7
7.8
8.3
6.8
7.3
7.5
7.6
7.8
8.3
6.5
7.0
7.2
7.3
7.5
8.0
6.4
6.9
7.1
7.2
7.4
7.9
6.2
6.6
6.9
6.9
7.1
7.6
6.0
6.5
6.7
6.8
6.9
7.4 20
0.12
0.73
W Outdoor : D.B. 52°C(125.5°F)…VJA, YJA.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
T.C. C.F.
(T.I.)
0.81
7.5
0.82
8.0
0.83
8.3
0.83
8.4
0.84
8.5
0.86
9.0
0.84
7.4
0.85
7.8
0.86
8.1
0.86
8.2
0.87
8.4
0.89
8.9
0.90
7.1
0.92
7.6
0.93
7.8
0.93
7.9
0.94
8.1
0.96
8.6
0.93
7.0
0.95
7.4
0.96
7.7
0.97
7.8
0.97
7.9
0.99
8.4
0.96
6.8
0.99
7.3
1.00
7.5
1.00
7.6
1.01
7.7
1.04
8.3
1.03
6.5
1.06
6.9
1.07
7.2
1.08
7.3
1.08
7.4
1.11
7.9
1.04
6.5
1.06
6.9
1.08
7.1
1.08
7.2
1.09
7.4
1.12
7.9
1.10
6.2
1.12
6.6
1.14
6.8
1.15
6.9
1.16
7.1
1.20
7.6
1.11
6.1
1.14
6.5
1.15
6.8
1.16
6.9
1.17
7.0
1.21
7.5
20
0.12
0.75
T.C. C.F.
9.8
10.5
10.8
10.9
11.1
11.8
9.6
10.2
10.6
10.7
10.9
11.6
9.3
9.9
10.2
10.3
10.5
11.2
9.1
9.7
10.0
10.2
10.3
11.0
8.9
9.5
9.8
9.9
10.1
10.8
8.5
9.1
9.4
9.5
9.7
10.3
8.4
9.0
9.3
9.5
9.6
10.3
8.1
8.6
8.9
9.1
9.3
9.9
8.0
8.6
8.9
9.0
9.2
9.8
7.6
8.2
8.5
8.6
8.8
9.4
7.4
8.0
8.3
8.4
8.6
9.2
0.12
0.73
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
28
COOLING CAPACITY correction factors
Service Ref.
PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2/3/4 PK-3FLA2/3/4/5 PK-4FLSA2/3/4
5m (16ft)
1.0
1.0
1.0
1.0
1.0
10m (33ft)
0.992
0.985
0.983
0.978
0.984
50Hz
15m (49ft)
0.987
0.975
0.972
0.962
0.974
Refrigerant piping length (one way)
20m (66ft)
0.982
0.964
0.961
0.948
0.964
25m (82ft)
0.954
0.951
0.934
0.954
13
30m (98ft)
0.944
0.940
0.921
0.944
35m (115ft)
— — — —
0.914
40m (13ft)
— — — —
0.902
Page 14
COOLING CAPACITY
Service Ref. Temperature
Evaporator airflow (CMM) Bypass factors S.H.F. at rating conditions
14
0.16
0.73
20
0.12
0.78
20
0.13
0.78
28
0.14
0.73
PK-2FLA
3 PK-2.5FLA3/4 PK-3FLA2/3/4/5 PK-4FLSA2/3/4
T.C. C.F.
(T.I.)
T.C. C.F.
(T.I.)
T.C. C.F.
(T.I.)
T.C. C.F.
(T.I.)
Outdoor D.B.
21˚C (69.8˚ F)
16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚ F) (64.4˚ F) (66.2˚ F)
(67˚ F) (68˚ F)
(71.6˚ F) 16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚ F)
(64.4˚ F)
(66.2˚ F)
(67˚ F) (68˚ F)
(71.6˚ F) 16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚ F)
(64.4˚ F)
(66.2˚ F)
(67˚ F) (68˚ F)
(71.6˚ F) 16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚ F)
(64.4˚ F)
(66.2˚ F)
(67˚ F) (68˚ F)
(71.6˚ F) 16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚ F)
(64.4˚ F)
(66.2˚ F)
(67˚ F) (68˚ F)
(71.6˚ F) 16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚ F)
(64.4˚ F)
(66.2˚ F)
(67˚ F) (68˚ F)
(71.6˚ F) 16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚ F)
(64.4˚ F)
(66.2˚ F)
(67˚ F) (68˚ F)
(71.6˚ F) 16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚ F)
(64.4˚ F)
(66.2˚ F)
(67˚ F) (68˚ F)
(71.6˚ F) 16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚ F)
(64.4˚ F)
(66.2˚ F)
(67˚ F) (68˚ F)
(71.6˚ F) 16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚ F)
(64.4˚ F)
(66.2˚ F)
(67˚ F) (68˚ F)
(71.6˚ F) 16˚C 18˚C 19˚C
19.4˚C 20˚C 22˚C
(60.8˚ F)
(64.4˚ F)
(66.2˚ F)
(67˚ F) (68˚ F)
(71.6˚ F)
25˚C (77˚ F)
30˚C (86˚ F)
32.2˚C (90˚ F)
35˚C (95˚ F)
40˚C (104˚ F)
40.6˚C (105˚ F)
45˚C (113˚ F)
46˚C (115˚ F)
50˚C (69.8˚ F)
52˚C (125.5˚ F)
Indoor W.B.
5.5
5.8
6.0
6.1
6.2
6.6
5.3
5.7
5.9
6.0
6.1
6.5
5.2
5.5
5.7
5.7
5.9
6.2
5.1
5.4
5.6
5.6
5.8
6.1
4.9
5.3
5.5
5.5
5.6
6.0
4.7
5.0
5.2
5.3
5.4
5.8
4.7
5.0
5.2
5.3
5.4
5.7
4.5
4.8
5.0
5.0
5.1
5.5
4.4
4.8
4.9
5.0
5.1
5.5
4.2
4.6
4.7
4.8
4.9
5.2
4.1
4.5
4.6
4.7
4.8
5.1
7.2
7.6
7.9
8.0
8.1
8.6
7.0
7.5
7.7
7.8
8.0
8.5
6.8
7.2
7.4
7.5
7.7
8.2
6.6
7.1
7.3
7.4
7.5
8.0
6.5
6.9
7.2
7.2
7.4
7.9
6.2
6.6
6.8
6.9
7.1
7.5
6.2
6.6
6.8
6.9
7.0
7.5
5.9
6.3
6.5
6.6
6.8
7.2
5.8
6.2
6.5
6.6
6.7
7.2
5.6
6.0
6.2
6.3
6.4
6.9
5.4
5.8
6.1
6.2
6.3
6.7
8.0
8.6
8.8
8.9
9.1
9.6
7.8
8.4
8.6
8.7
8.9
9.5
7.6
8.1
8.3
8.4
8.6
9.1
7.4
7.9
8.2
8.3
8.4
9.0
7.3
7.7
8.0
8.1
8.3
8.8
6.9
7.4
7.7
7.8
7.9
8.4
6.9
7.4
7.6
7.7
7.9
8.4
6.6
7.1
7.3
7.4
7.6
8.1
6.5
7.0
7.2
7.3
7.5
8.0
6.2
6.7
6.9
7.0
7.2
7.7
6.1
6.5
6.8
6.9
7.0
7.5
11.0
11.8
12.1
12.3
12.5
13.2
10.8
11.5
11.9
12.0
12.2
13.0
10.4
11.1
11.4
11.6
11.8
12.6
10.2
10.9
11.3
11.4
11.6
12.4
10.0
10.6
11.0
11.1
11.4
12.1
9.5
10.2
10.5
10.7
10.9
11.6
9.5
10.1
10.5
10.6
10.8
11.6
9.1
9.7
10.0
10.2
10.4
11.1
9.0
9.6
9.9
10.1
10.3
11.0
8.6
9.2
9.5
9.7
9.9
10.6
8.4
9.0
9.3
9.5
9.7
10.4
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
60Hz
Notes: 1. T.C.: Total capacity (kW) …(kcal/h)=(kW)x860, (Btu/h)=4x(kW)x860
COOLING CAPACITY correction factors
PK-2FLA PK-2.5FLA2/3/4 PK-3FLA2/3/4/5 PK-4FLSA2/3/4
C.F.(T.I.) : Correction factors of Total input(Indoor unit input + Outdoor unit input)
2. (°F)=32+9/5(°C)
3. Guaranteed operating range(cooling)
Service Ref.
3
5m (16ft)
1.0
1.0
1.0
1.0
Lower limit … Indoor : D.B. 21°C(70°F), W.B. 15.5°C(60°F), Outdoor : D.B. 21°C(70°F).
{
Upper limit … Indoor : D.B. 35°C(95°F), W.B. 22.5°C(72.5°F), Outdoor : D.B. 52°C(125.5°F).
10m (33ft)
0.985
0.978
0.971
0.980
60Hz
15m (49ft)
0.975
0.963
0.950
0.966
Refrigerant piping length (one way)
20m (66ft)
0.964
0.948
0.931
0.952
14
25m (82ft)
0.954
0.934
0.913
0.939
30m (98ft)
0.944
0.921
0.896
0.926
35m (115ft)
— — —
0.941
40m (131ft)
— — —
0.902
Page 15
Service Ref.
MODE
W
kW
Mpa
(o/f)
Mpa
(o/f)
˚C ˚C ˚C m
D.B.˚C W.B.˚C D.B.˚C
D.B.˚C W.B.˚C
CoolingCoolingCoolingCoolingCoolingCoolingCoolingCoolingCooling
PK-3FLA
3
PK-3FLA
4
PK-3FLA
5
PK-3FLA
3
PK-3FLA
4
PK-3FLA
5
PK-2.5FLA
2
PK-2.5FLA
3
PK-2.5FLA
4
PK-2.5FLA
2
PK-2.5FLA
3
PK-2.5FLA
4
PK-2FLA
3
PK-2FLA
3
PK-1.6 FLA
3
PK-1.6 FLA
3
PK-3FLA
2
PK-3FLA
2
Electrical circuitRefrigerant circuit
Indoor
side
Outdoor
side
Capacity Input
Indoor unit Service Ref.
Phase , Hz Volts Amperes
Outdoor unit Service Ref.
Phase , Hz Volts Amperes Discharge pressure
Suction pressure
Discharge temperature Condensing temperature Suction temperature Refrigerant pipe length Intake air temperature Discharge air temperature Intake air temperature
Total
7900
3.28
1 , 50
220
0.44
PU-3
VJC
1 , 50
220
15.1
1.99
(20.3)
0.47
(4.79)
86 51
6
5 27 19
13.0 35 24
Cooling
PK-3FLA
2
PK-3FLA3 PK-3FLA
4
PK-3FLA
5
PK-3FLA
2
PK-3FLA3 PK-3FLA
4
PK-3FLA
5
7500
3.28
1 , 50
220
0.44
PU-3
VJB
1 , 50
220
12.4
1.94
(19.8)
0.48
(4.85)
76
51.4 5 5
27 19
13.4
35 24
6900
4.19
1 , 60
220
0.44
PU-3
NJA
1
1 , 60
220
20.9
2.07
(21.1)
0.44
(4.49)
70 53
4
5 29 19
13.2 46 24
7200
3.28
1 , 50
220
0.44
PU-3 VJA
2
1 , 50
220
15.1
1.99
(20.3)
0.47
(4.79)
62 51
6
5 27 19
13.7 35 24
6900
4.19
1 , 60
220
0.44
PU-3 NJA
1
1 , 60
220
20.9
2.07
(21.1)
0.44
(4.49)
70 53
4
5 29 19
13.2 46 24
7000
2.56
1 , 50
220
0.44
PU-2.5
VJA
2
1 , 50
220
11.4
2.05
(20.9)
0.47
(4.79)
74.3 52
10.3
5 27 19
14.1 35 24
6650
3.54
1 , 60
220
0.44
PU-2.5
NJA
1
1 , 60
220
15.8
2.13
(21.7)
0.44
(4.49)
87 54 10
5 29 19
14.1 46 24
5600
2.52
1 , 50
220
0.37
PU-2
VJA
2
1 , 50
220
11.3
1.98
(20.2)
0.46
(4.69)
66 52
3
5 27 19
13.4 35 24
3900
1.49
1 , 50
220
0.32
PU-1.6
VLJA
2
1 , 50
220
6.7
1.89
(19.3)
0.5
(5.1)
84 50
9
5 27 19
15.4 35 24
4600
2.60
1 , 60
220
0.42
PU-2
NJA
1
1 , 60
220
13.6
1.96
(20.0)
0.47
(4.79)
66 52
5
5 29 19
13.5 46 24
CoolingCooling
PK-4FLSA
2
PK-4FLSA
3
PK-4FLSA
4
PK-4FLSA
2
PK-4FLSA
3
PK-4FLSA
4
9800
3.46
1 , 50
220
0.53
PU-4
YJSA
3
3 , 50
220
5.7
1.80
(18.4)
0.48
(4.89)
65 49
6
5 27 19
13.9 35 24
9900
5.08
1 , 60
220
0.53
PU-4
TJSA
3
3 , 60
220
14.0
1.93
(19.7)
0.45
(4.59)
74 52
5
5 29 19
13.2 46 24
2. STANDARD OPERATION DATA
Total Electrical circuit Refrigerant circuit Indoor side Outdoor side
The unit of pressure has been changed to Mpa on the international system of unit(SI unit system). The converted score against the traditional unit system can be gotten according to the formula below.
1(Mpa)=10.2(O/F·G)
3. ADDITIONAL REFRIGERANT CHARGE (R-22…kg(lbs))
Service Ref.
PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2/3/4 PK-3FLA2 PK-3FLA3/4/5 PK-4FLSA2/3/4
4. OUTLET AIR SPEED AND COVERAGE RANGE
Frequency
Airflow Air speed Coverage range Airflow Air speed
60Hz 50Hz
Coverage rangew
w The air coverage range is the value up to the position where the air speed is 0.25m/sec. when air is blown out horizontally
from the unit at the Hi notch position/ The coverage range should be used only as a general guideline since it varies according to the size of the room and furni­ture inside the room.
Outdoor unit precharged (kg)
VL---1.3, V---1.79, N---1.9 V---2.4, N---2.4 V---3.08, Y---2.88, N---3.5 V---2.8, Y---2.8, N---3.5 VL---3.8, Y---4.6, T---4.6
Configuration Wall mounted
Model PK-1.6FLA
w
(up to 20m)
m3/min m/sec.
m(ft)
3
m
/min
m/sec.
m(ft)
13
4.0
9.1(30) — — —
20m (66ft)
0 0 0 0 0 0
PK-2FLA
14
4.3
9.8(32) 14
4.3
9.8(32)
15
Refrigerant piping length (one way)
25m (82ft)
0.06(0.13)
0.06(0.13)
0.06(0.13)
0.06(0.13)
0.15(0.33)
PK-2.5FLA
20
4.9
12.4(41) 20
4.9
12.4(41)
30m (98ft)
0.12(0.26)
0.12(0.26)
0.12(0.26)
0.12(0.26)
0.30(0.66)
PK-3FLA
20
4.9
12.4(41) 20
4.9
12.4(41)
35m (115ft)
— — — — —
0.45(0.99)
PK-4FLSA
15.3(50)
15.3(50)
28
5.4
28
5.4
40m (131ft)
— — — — —
0.6(1.32)
Page 16
6
TEMP
ON / OFF
NOT AVAILABLE
AM PM
AM PM
˚C
153
57 18 3
55
58
162
19
ON/OFF TEMP
MODEL SELECT
NOT AVAILABLE
CHECK
TEST RUN
˚C
AMPM
AMPM
OUTLINES AND DIMENSIONS
1. REMOTE CONTROLLER
Unit : mm
PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2, PK-2.5FLA3 PK-3FLA2, PK-3FLA3, PK-3FLA4 PK-4FLSA2, PK-4FLSA3
PK-2.5FLA4 PK-3FLA5 PK-4FLSA4
16
Page 17
Pipe position
Left side
Lequid pipe
Gas pipe
Service space required
around indoor unit
(100 for left-hand
side piping)
Right side
130 or less
2 tapping screws
for installation plate
(Necessary clearance for
Unit installation)
Drain pipe
Front
50 or more
2-unit hangers
Unit cennter
Liquid pipe position
Gas pipe position
(Width of unit)
Knock out hole for
left-rear piping
Knock out hole for
left-rear piping
Rear piping hole
2 X5 - 2.9 hole
for tapping screw
Details of installation plate
1 Sleeves are available on
the market.
2 This size shows the lower
end of through hole.
Sleeve
90 90~ 100
Through hole
150 or more
Knock out hole for
left-hand side piping
Ref.pipes & drain pipe
215
168
2134
8
20
70
300
47
30 or more
180 or more
80
25
35
60
Left side
Air intake
Front
1250
449 Air intake
Auto vanes
Service panel for
power supply connection
449 Air intake
968 Air intake
48
236
227
Right side
Terminal block
Right side
Knock out hole for right piping
(2:1)
Knock-out hole for
night-hand side piping
Knock out hole
for piping
8
60
Knock out hole for piping
Terminal block for control
Terminal block & pipe position
Drainage
Drainage(Flexible hole: length 1200)
Liquid pipe
Bass pipe
Lower side
Terminal block for
power supply
Knock out hole for under-piping
15 or less
bolt
Installation bolt position
200
B
B
A
A
8
8
60
91
65
20
70
(2:1)
70
Lower side
976
16 -louvers
(manual)
500
479 Air outlet479 Air outlet
26
173
223
222
143
553
635
685
170
190
200
1100
50
1
Knock out hole
for piping
1
2
2
3/8F
5/8F
0355380130
177
227
(178)
(375)
447
190
13- 14
hole
60
1250
330
80
0
53
68- 5
hole
277
Tapping screw
300
491
476
450
405
323
276
229
179
150
70
24
0
70
150
174
224
271
318
374
9
73
405
450
476
486
625
(Height ut unit)
85
45
286X
2
R52.5R52.5
R52.5R52.5
w
w
2. INDOOR UNIT
3
3
PK-1.6FLA PK-2FLA
Unit : mm
17
Page 18
235 45
235 45
235 45
235
62.5
13
58 42
340
197
Top
Front
Right side
Left side
1400
1090
Air intake
235
C
Knock out hole for right piping
Refrigerant pipe. Drain pipe
Knock out hole for
left piping
Drain hose for
left-hand side piping
Drain hose
Lower side
Auto vane
(Gas pipe)
Drain hose
Bolt
Gas pipe
15
Terminal block for power supply
Terminal block for control
(Liquid pipe)
Liquid pipe 9.52(3/8F)
Gas pipe 15.88(5/8F)
Liquid pipe
A
30
32
39
98
37
74
439
100
30
37
74
4
2980
280
3030
18430
60
10
39
37
65
100
AB C
Knock out hole for piping
25
1110
183
240
B
1120
552
55
120
107
111
Air outlet
552
Air outlet
Change vane (manual)
Under panel
Removable at left-hand
side piping
Knock out hole for under-piping
Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping opening
12-ø6 hole for
tapping screw
66-ø6 hole for
tapping screw
Wall fixture
Unit center
32-ø12 hole for bolt
225
18
18
91
900
990
455
285
245
19
240 280 314
610
90
Drainage range
on left-hand side
Drainage range
on right-hand side
10 91=(910)
180
PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA
4
PK-3FLA2, PK-3FLA3, PK-3FLA4, PK-3FLA
Unit : mm
5
18
Page 19
235 45
235 45
235 45
235 45
235
62.5
13
58 42
340
197
Top
Front
Right side
Left side
1680
1370
Air intake
235
C
Knock out hole for right piping
Knock out hole for left piping
Drain hose for left-hand side piping
Drain hose
Drain hose
Lower side
Auto vane
(Gas pipe)
Bolt
Gas pipe
15
Terminal block for power supply
Terminal block for control
(Liquid pipe)
Gas pipe 19.05(3/4F)
Liquid pipe 9.52(3/8F)
Liquid pipe
A
30
32
39
98
37
74
439
100
30
37
74
4
2980
280
3030
18430
60
10
39
37
65
100
AB C
Knock out hole for wiring
25
1110
183
240
B
1400
55
120
102
111
694
Air outlet
694
Air outlet
Change vane (manual)
Under panel
(Removable at left-hand side piping)
Knock out hole for under-piping
Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping openingRange for left rear piping opening
12-ø6 hole for tapping screw
84-ø6 hole for
tapping screw
Wall fixture
Unit out line
Unit center
41-ø12 hole for bolt
295 225
18
18
91
900
1270
595
285
245
19
240 280 314
750
90
Drainage range
on right-hand side
13 91=(1183)
180
Drainage range
on left-hand side
PK-4FLSA2, PK-4FLSA3, PK-4FLSA
4
Unit : mm
19
Page 20
7
PK-2FLA3PK-1.6FLA3
SW1
OFF
ON
SW1
OFF
12345678
ON
MF
135
12
LS
MV
CN23
VANE
31
CNV
VANE
REMORT CONTROLLER
65432
RT2
2
SW1
1
JR
N
GRN/YLW
L
I.B
TO OUTDOOR UNIT CONNECTING WIRES DC12V
1
T
X4
ZNR
F2 F1
C
X4
CNB
LD1
Ru
SW1
1
7
1
1
4
3
2
3
5
3
2
11
1
33
FAN
POWER
OUTDOOR
TIMER
WIRELESS
TRANS
L.TEST
CN2A
TWIN.1
CN2B
TWIN.2
TRANS
CND
CN30
CN2
CN70
CN4T
CN28
CNT
INTAKE
CN20
PIPE
CN21
CN51
MULTIPLE
1122
SW2
SW3
ON
ON
OFF
OFF
123
12345678 12345
RT1
7
RED
WHT
BRN
RED
BLK
BLK
W.R
TB4
W.B
TB2
ORN YLW
BRN
RED
240V
14.5VAC
10.6VAC
230V
220V
BLU
YLW
WHT
RED
BLK
WHT
RED
POWER SUPPLY ~(1 PHASE) AC220-240V 50Hz AC220V 60Hz
YLW
ORN
RED
7
12345678
WIRING DIAGRAM
PK-1.6FLA PK-2FLA
3
3
SYMBOL
C
CN2<I.B> CN2A<I.B> CN2B<I.B> CN23<I.B> CN28<I.B> CN51<I.B>
F1,2<I.B>
NOTES:
1. Since the indoor fan motor (MF) is connected with 220V power, using 230, 240V power will require a setting change of the dip switch (SW1<I.B>) on the
2. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
3. Since the indoor transformer (T) is connected with 220V power, if 230,240V power is used. Change the wiring connection showing fig * : 2.
4. Symbols used in wiring diagram above are, : Connector, : Terminal block.
5. Emergency operation
[Check items]
[Emergency operation procedure]
FAN MOTOR CAPACITOR TIMER ADAPTOR CONNECTOR TRANSMISSION WIRES No.1 CONNECTOR TRANSMISSION WIRES No.2 CONNECTOR VANE POSITION CONNECTOR TIME SHORTENING CONNECTOR MULTIPLE CONNECTOR FUSE(6.3A 250V)
I.B
INDOOR CONTROLLER BOARD FUNCTION SELECTOR JUMPER RESISTORS
JR
indoor controller board as shown is fig:
fig w1
fig w2
If remote controller of microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor con­troller board.
(1) Compressor and fan. (2) Check the trouble position using self diagnostic function. If the result of self diagnosis indicates protective device such as freeze protection is functioning
(1) Set the dip switch (SW3<I.B>) on the indoor controller board to on and off for cooling. (2) Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker in this order. (3) During emergency operation indoor fan runs at high speed but automatic vane remains stop.
(4) Thermostat will not function. (5) Emergency cooling should be limited to 10 hours maximum.
Indoor fan motor (MF) for 230,240V.
When power supply is
emergency operation is not possible unless the cause is removed. Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with remote controller is not possible).
If vane is closed open the vane by hands/
(The indoor unit heat exchanger may freeze).
NAME
w
1.
230V 220V
SYMBOL LD1<W.B>
Ru<W.B> SW1<I.B> SW2<I.B>
RUN INDICATOR LED
MF
FAN MOTOR
MV
VANE MOTOR ROOM TEMPERATURE THERMISTOR
RT1
(0%/15k",25°C/5.4k" DETECT) PIPE TEMPERATURE THERMISTOR
RT2
(0%/15k". 25°C/5.4k" DETECT RECEIVING UNIT FUNCTION SWITCH UNIT SELECTOR SWITCH
SW1 SW1
ON OFF
2 3 4 5 6 7 8
1
220V
YELLOW
230V
ORANGE
240V
RED
NAME
SYMBOL SW3<I.B>
SW1<W.B>
X4<I.B>
ZNR
EMERGENCY OPERATION SWITCH ON/OFF SWITCH
T
TRANSFORMER
TB2
POWER SUPPLYTERMINAL BLOCK INDOOR/OUTDOOR CONNECTING WIRE
TB4
TERMINAL BLOCK FAN MOTOR RELAY VARISTOR WIRELESS REMOTE CONTROLLER BOARD
W.B
WIRELESS REMOTE CONTROLLER
W.R
NAME
ON OFF
2 3 4 5 6 7 8
21
3
1
20
Page 21
PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA
X4
SW1
OFF
ON
12345678
OFF
ON
12345678
PK-4FLSA
PK-2.5FLA PK-3FLA
MODELS
REMOTE CONTROLLER
65432
RT2
2
SW1
CN27
D.U.M
1
JR
N
GRN/YLW
L
I.B
TO OUTDOOR UNIT CONNECTING WIRES DC12V
1
T
X4
ZNR
F2 F1
C
MF
MV
CNB
LD1
Ru
SW1
54321
1
1
6
7
1
1
43
2
35
3
211 133
FAN1
POWER
OUTDOOR
TIMER
WIRELESS
TRANS
VANE
L.TEST
CN2A
TWIN-1
CN2B
TWIN-2
TRANS
CND
CN30
CN2
CN70
CN6V
CN4T
CN28
CNT
DRAIN
CN50
INTAKE
CN20
PIPE
CN21
CN51
MULTIPLE
1122
SW2
SW3
ON
ON
OFF
OFF
123
1234567812345
RT1
7
W.R
TB4
6
W.B
TB2
ORN
YLW
BRN
BRN
RED
RED
240V
14.5VAC
10.6VAC
230V
220V
BLU
YLW
WHT
RED
BLK
WHT
RED
POWER SUPPLY ~(1 PHASE) AC220-240V 50Hz AC220V 60Hz
YLW
ORN
RED
7
4
PK-3FLA2, PK-3FLA3, PK-3FLA4, PK-3FLA PK-4FLSA2, PK-4FLSA3, PK-4FLSA
4
5
SYMBOL
C
CN2<I.B> CN2A<I.B> CN2B<I.B> CN23<I.B> CN27<I.B> CN28<I.B> CN51<I.B>
F1,2<I.B>
FAN MOTOR CAPACITOR TIMER ADAPTOR CONNECTOR TRANSMISSION WIRES No.1 CONNECTOR TRANSMISSION WIRES No.2 CONNECTOR DRAIN LEFT-UP MECHANISM VANE POSITION CONNECTOR TIME SHORTENING CONNECTOR MULTIPLE CONNECTOR FUSE(6.3A 250V)
I.B
INDOOR CONTROLLER BOARD FUNCTION SELECTOR JUMPER RESISTORS
JR
NOTES:
1. Since the indoor fan motor (MF) is connected with 220V power, using 230, 240V power will require a setting change of the dip switch (SW1<I.B>) on the indoor controller board as shown is fig:
2. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
3. Since the indoor transformer (T) is connected with 220V power, if 230,240V power is used. Change the wiring connection showing fig * : 2.
4. Symbols used in wiring diagram above are, : Connector, : Terminal block.
5. Emergency operation
[Check items]
[Emergency operation procedure]
fig w1
Indoor fan motor (MF) for 230,240V.
fig w2
When power supply is
If remote controller of microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor con­troller board.
(1) Compressor and fan. (2) Check the trouble position using self diagnostic function. If the result of self diagnosis indicates protective device such as freeze protection is functioning
emergency operation is not possible unless the cause is removed. Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with remote controller is not possible).
(1) Set the dip switch (SW3<I.B>) on the indoor controller board to on and off for cooling. (2) Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker in this order. (3) During emergency operation indoor fan runs at high speed but automatic vane remains stop. (4) Thermostat will not function. (5) Emergency cooling should be limited to 10 hours maximum.
(The indoor unit heat exchanger may freeze).
NAME
230V 220V
w
1.
SYMBOL
MF MV
RT1 RT2
Ru<W.B> SW1<I.B> SW2<I.B> SW3<I.B>
T
ON OFF
1
220V
230V
240V
FAN MOTOR VANE MOTOR ROOM TEMPERATURE THERMISTOR (0%/15k",25°C/5.4k" DETECT) PIPE TEMPERATURE THERMISTOR (0%/15k". 25%/5.4k" DETECT RECEIVING UNIT FUNCTION SWITCH UNIT SELECTOR SWITCH EMERGENCY OPERATION SWITCH TRANSFORMER
SW1 SW1
2
3 4 5 6 7 8
YELLOW ORANGE RED
NAME
21
3
ON OFF
2
3 4 5 6 7 8
1
SYMBOL
X4<I.B>
SW1<W.B>
LD1<W.B>
TB2
POWER SUPPLYTERMINAL BLOCK INDOOR/OUTDOOR CONNECTING WIRE
TB4
TERMINAL BLOCK FAN MOTOR RELAY VARISTOR
ZNR
ON/OFF SWITCH RUN INDICATOR LED WIRELESS REMOTE CONTROLLER BOARD
W.B
WIRELESS REMOTE CONTROLLER
W.R
NAME
21
Page 22
8
INDOOR UNIT PK-2.5 PK-3 PK-4
OUTDOOR UNIT PU-2.5/3J series PU-4J series
Indoor heat exchanger
Distributor
Flexible tube
Flared connection
Flared connection
PK-2.5
/ PK-3 Refrigerant pipe [15.88(5/8)
(with insulator) option PK-4 Refrigerant pipe [19.05(3/4) (with insulator) option
Refrigerant pipe [ 9.52(3/8) (with insulator) option
Ball valve
Low pressure switch
Charge pIug
Check pIug
High pressure switch
Outdoor heat exchanger
Strainer
Capillary tube for injection Only PU-2.5NJA
1 PU-3YJA2
PU-2.5VJA2 PU-3YJA3 PU-3NJA1 PU-4YJSA2 PU-3VJA2 PU-4YJSA3 PU-4TJSA2
Capillary tube
Compressor
Accumulator
Ball valve (with service port)
flow of refrigerant
PU-2.5 (O.D.3.2 I.D.1.6 L760) 2pcs PU-3 (O.D.3.2 I.D.1.8 L800) 2pcs PU-4 (O.D.3.2 I.D.2.0 L840) 2pcs
Capillary tube size
Indoor coil thermistor RT2
INDOOR UNIT PK-1.6 PK-2
OUTDOOR UNIT PU-1.6/2J series
Indoor heat exchanger
Flexible tube
Flared connection
Flared connection
Refrigerant pipe [15.88(5/8) (with insulator) option
Refrigerant pipe [9.52(3/8) (with insulator) option
Ball valve
Low pressure switch
Charge pIug
Check plug
High pressure switch
Outdoor heat exchanger
Strainer
Capillary tube for injection (Only PU-2VJA2) PU-2NJA1
Capillary tube
Compressor
Accumulator
Ball valve (with service port)
flow of refrigerant
PU-1.6 (O.D.3.2 I.D.1.8 L900) PU-2 (O.D.4.0 I.D.2.0 L430)
Distributor
Indoor coil thermistor RT2
REFRIGERANT SYSTEM DIAGRAM
PK-1.6FLA3/ PU-1.6VLJA
2
PK-2FLA3/ PU-2VJA2, PU-2NJA
1
PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA4, / PU-2.5VJA2, PU-2.5NJA PK-3FLA2/ PU-3VJA2, PU-3YJA3, PU-3NJA PK-3FLA3, PK-3FLA4, PK-3FLA5/ PU-3NJA
1
1
1
PK-4FLSA2, PK-4FLSA3, PK-4FLSA4, / PU-4VLJSA2, PU-4YJSA3, PU-4TJSA
22
2
Page 23
PK-3FLA3, PK-3FLA4, PK-3FLA5/ PU-3VJC , PU-3YJC
Indoor heat exchanger
Distributor with strainer
Flexible tube
Flared connection
Flared connection
Refrigerant pipe [15.88(5/8") (with insulator) option
Refrigerant pipe [ 9.52(3/8") (with heat insulator) option
Ball valve
Low pressure switch
Charge pIug
Check pIug
High pressure switch
Outdoor heat exchanger
Capillary tube
Compressor
Accumulator
Ball valve (with service port)
flow of refrigerant
(O.D.3.2 oI.D.1.8 oL800) o2pcs
strainer
Indoor coil thermistor RT2
strainer
strainer
Refrigerant pipe [15.88(5/8")
Indoor heat exchanger
(with insulator) option
Flexible tube
strainer
Ball valve
Low pressure switch
Charge pIug
Check pIug
High pressure switch
Outdoor heat exchanger
strainer
Indoor coil thermistor RT2
Distributor with strainer
Flared connection
Refrigerant pipe [ 9.52(3/8") (with heat insulator) option
Flared connection
Accumulator
Ball valve (with service port)
PK-3FLA3, PK-3FLA4, PK-3FLA5/ PU-3VJB , PU-3YJB
strainer
Compressor
Capillary tube
(O.D.3.2 o I.D.1.8 o L800) o2pcs
D.P.R. (Discharge pressure regulator)
flow of refrigerant
23
Page 24
9 OPERATION FLOW-CHART
START
STOP
EMERGENCY
ALL STOP
COOL OPERATION
DRY OPERATION
POWER SUPPLY
Live
ON/OFF
button ON
Abnormal
operation mode
MODE SELECT
button
POWER lamp ON
Protection device
Self hold reset
Protection device
Self hold
Self-diagnostic function
Indicate & Memory
NO
NO
YES
<Note 4> <Note 5>
NO
1
NO
YES
YES
COOL
DRY
1. Main operation
Note1. The unit starts operation by pressing the ON/OFF switch when unit is OFF.
During operation, the unit stops operation by pressing the ON/OFF switch. In addition, operation can be turned ON/OFF with the centralized remote controller or the remote switch.
Note2. The factors which cause “abnormal operation mode” are as follows.
Outdoor unit abnormal operation.
Fault of room temperature thermistor(RT1).
Fault of indoor coil thermistor(RT2).
Indoor coil frost protection mode.
Fault of drain sensor(DS).
Drain water overflow prevention mode.
Note3. The indoor fan runs on the low speed for 1 minute to eliminate remaining heat.
Refer to page 30 for abnormal operation, mode details.
Note4. The compressor will not start for 3 minutes after the stop. Note5. The thermostat is continuously ON during the test run. Note6. Refer to page 31 for coil frost protection. Note7. Range A: Indoor coil temperature is more than 5 degrees above room temperature.
Range B : Indoor coil temperature is within 5 degrees either way of room temperature. Range C : Indoor coil temperature is more than 5 degrees below room temperature.
24
Page 25
2. COOL operation
COOL operation
YES
YES
NO
<Note 7>
<Note 8>
NO
3 min. delay
NO
6-minute
time delay
NO
Compressor start 3 minutes elapse
Coil frost
protection
NO
Range C
Compressor
start 10 minutes
elapse
Allowance release
Coil frost
prevention
YES
NO
Allowance
YES
NO
6-minute time delay
Allowance set
Indoor coil
temperature
10°C or bellow
NO NO
YES YES
Continue
1 minute
Coil frost
protection
check mode
<Note 6>
Compressor
themostat ON
NO
Allowance release
YES
NO
Compressor ON
Compressor ON
NO
Compressor
start 16 minutes
elapse
YES
Indoor coil
temperature
1°C or below
NO
1
3-minute time delay
Coil frost
prevention release
Coil frost
prevention set
Compressor OFF
Fan speed LOW
NO
Fan speed LOW
5 minutes elapse
YES
Outdoor unit abnormality
check mode
25
Page 26
3. DRY operation
Dry operation
Room temperature
18°C or below
Compressor ON
Compressor ON
3 min. elapse
Compressor
thermostat ON
Compressor ON
time completed
Compressor OFF
10-minute timer start
Compressor OFF
Fan stop
Compressor ON
3 min. delay
YES
YES
YES
YES
YES
YES
YES
YES
<Note 10> <Note 10>
<Note 6>
<Note 6>
<Note 9>
<Note 8>
YES
NO
NO
NO
NO
NO
NO
NO
Compressor
thermostat ON
Compressor OFF
10 minutes completed
Compressor ON
time set
Compressor ON
Fan speed LOW
1
Note8. When room temperature is 18°C or below, the compressor can not turn ON. When the room temperature rises to 18°C or
above, the compressor will start operation after a 3-minute time delay. Note9. Refer to page 30 for the compressor operation time. Note10. In DRY operation, the indoor fan runs on the low speed during the compressor ON and stops during the compressor OFF.
26
Page 27
MICROPROCESSOR CONTROL10
TEMP
ON / OFF
NOT AVAILABLE
AM PM
AM PM
˚C
1. OUTLINE OF MICROPROCESSOR CONTROL
INPUT to remote controller OUTPUT to remote controller
OFF-ON switching.
COOL • DRY • FAN selector switching.
HIGH-LOW fan speed switching.
TIMER mode selector-switching
Timer setting.
Self diagnostic troubleshooting.
TEST RUN switching.
CHECK mode switching.
AUTO Vane setting.
Indoor unit
Processes and transmits orders.
Indication LCD lights.
PK-1.6FLA PK-2FLA3 PK-2.5FLA2/3 PK-3FLA2/3/4 PK-4FLSA2/3
3
PK-2.5FLA4 PK-3FLA5 PK-4FLSA4
REMOTE CONTROLLER
INPUT from indoor unit
Room temperature thermistor.
Indoor coil thermistor.
OUTPUT to indoor unit
Fan: ON-OFF.
Fan speed: HIGH-LOW.
AUTO vane’s angle setting.
Emergency stop.
Independent Control of Outdoor Unit
INPUT from outdoor unit
INDOOR CONTROLLER BOARD
Receives orders from remote controller and temperature data from indoor unit.
Processes orders and data.
Controls indoor and outdoor operation.
Self diagnostic function
w System control operation.<Optional> w Emergency operation
Non-polar, two (2) - core cable
Outdoor unit
12VDC
OUTPUT UNIT
Compressor protection device working.
OUTPUT from outdoor unit
Compressor motor and outdoor fan motor : ON-OFF.
Receives orders from
indoor controller.
Emergency stop.
27
Page 28
2. INDOOR UNIT CONTROL
Thermostat
Operation starts by POWER button ON.
ON
OFF
Indoor fan
ON
OFF
Auto vane
ON
OFF
Compressor
ON
OFF
w1 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this period has ended.
LOW or HIGH
CLOSE CLOSE
LOW or HIGH
Depends on remote controller setting
MIN. 3 minutes w1
Room temperature becomes equal to set temperature.
Room temperature rises above set temperature.
Operation stops by POWER button OFF.
TEMP
ON / OFF
NOT AVAILABLE
AM PM
AM PM
˚C
/
/
/
/
2-1COOL operation
<How to operate>
1 Press
[ ON/OFF button.
2 Press MODE button to set operation mode to COOL . 3 Set desired temperature with or button.
button.
NOTE: 1. Set temperature changes by 1 °C in the range 19-30 °C
each TEMP or button is pressed.
2. Set temperature is displayed on the LCD.
PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2/3
PK-2.5FLA4 PK-3FLA5
PK-4FLSA4 PK-3FLA2/3/4 PK-4FLSA2/3
<COOL operation time chart>
(1)Compressor control
1 3-minute time delay
2 The compressor runs when the room temperature is higher than the set temperature.
To prevent overload, the compressor will not start within 3 minutes after stop.
The compressor stops when the room temperature is equal to or lower than the set temperature.
3 The compressor stops in check mode or during protective functions. 4 Coil frost prevention
To prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 1°C or below after the compressor has been continuously operated for 16 minutes or more. The coil frost prevention is released under any of the following conditions.
The indoor coil thermistor rises to 10°C or above.
The room temperature becomes equal to or lower than the set temperature.
COOL mode is stopped or changed to another mode.
NOTE : By cutting the jumper wire JR02 on the indoor controller board, the temperature to start coil frost prevention
changes from 1°C to - 3°C
28
Page 29
5 Coil frost protection
Automatic swing (PK-2.5/3/4)
10°
30°
60° (PK-2.5/3/4) 50° (PK-1.6/2)
70° (PK-2.5/3/4) 60° (PK-1.6/2)
When the indoor coil temperature becomes - 15°C or below, coil frost protection will proceed as follows.
<Start condition>
After the compressor has been continuously operated for 3 minutes or more, and the indoor coil temperature has been ­15°C or below for 3 minutes, the coil frost protection will start.
<Coil frost protection>
Compressor stops for 6 minutes, and then restarts. If the start condition is satisfied again during the first 10 minutes of compressor operation, both the indoor and outdoor units stop, and the remote controller displays this occurrence.
<Termination conditions>
Coil frost protection released when the start condition is not satisfied again during the allowance, or when the COOL mode stops changes another mode.
(2)Indoor fan control
Indoor fan speed depends on the remote controller setting. However, if an outdoor unit abnormality is detected, the indoor fan speed will be LOW, regardless of the remote controller setting.
(3)Auto vane control
Auto vane position depends on the remote controller setting.
(4)Detecting abnormalities in the outdoor unit
After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperature and the room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the difference is still out of RANGE C, the outdoor unit is functioning abnormally. Thus, the compressor will stop and the remote controller will display this occurrence. RANGE A : Indoor coil temperature is more than 5 degrees above room temperature. RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature. RANGE C : Indoor coil temperature is more than 5 degrees below room temperature.
(5)AUTO VANE CONTROL
11
Frequency judgement
When the unit operates for the first time after the circuit breaker turned to ON, the frequency, 50Hz or 60Hz, is judged by the horizontality sensing switch. If The frequency cannot be judged immediately for some reason, the sensing operation continues for 3 minutes with the vane motor at ON. If the frequency cannot be judged yet after 3-minute sensing, the vane motor turns to OFF. But the AIR DISCHARGE DIRECTION display continues to be indicated.
22
During cooling operation
When the cooling operation starts, the vane is automatically set to the horizontal However, the desired direction among four below-listed can be selected with the vane button on the remote controller.
a) 10° b) 30° downward c) 60° downward (PK-2.5, 3, 4FL(S)A) / 50° downward (PK-1.6, 2FLA) d) 70° downward (PK-2.5, 3, 4FL(S)A) / 60° downward (PK-1.6, 2FLA) e) Automatic swing (only PK-2.5, 3, 4FL(S)A)
NOTE : 30° is available only when the fan speed is HIGH. <AUTO RETURN> When discharge 50°, 60° or 70° continues for 1 hour with the fan speed at LOW, the discharge direction turns to the horizontal discharge automatically. NOTE1 : After that, 50°, 60° or 70° is available by setting with the remote controller, and it continues for 1 hour. NOTE2 : If the discharge direction changes from 50°, 60° or 70° , the direction returns to the horizontal discharge when 1 hour has passed since the discharge 60° started. NOTE3 : If the discharge direction changes from 50° or 60° (or 70° ) to the horizontal discharge, the 1-hour timer to return the horizontal discharge is cancelled.
33
During the operation OFF, the auto vane is in the airflow shut-off position.
44
When the vane motor is out of order or the connector is badly connected, the
remote controller display of the remote controller does not change.
29
Page 30
2-2 DRY operation
Thermostat
Operation starts by POWER button ON.
ON
OFF
Indoor fan
ON
OFF
Auto vane
ON
OFF
Compressor
ON
OFF
w2 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this period has ended.
LOW speed
CLOSE CLOSE
LOW speed
Depends on remote controller setting
MIN. 3 minutes w2
Room temperature becomes equal to set temperature.
Room temperature rises above set temperature.
Operation stops by POWER button OFF.
/
/
/
/
TEMP
ON / OFF
NOT AVAILABLE
AM PM
AM PM
˚C
<How to operate>
1 Press [ ON/OFF button. 2 Press MODE button to set operation mode to DRY .
3 Set desired temperature with or button.
NOTE: 1. Set temperature changes by 1 °C in the range 19-30 °C
each TEMP or button is pressed.
2. Set temperature is displayed on the LCD.
PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2/3 PK-3FLA2/3/4
PK-2.5FLA4 PK-3FLA5 PK-4FLSA4
PK-4FLSA2/3
(1)Compressor control
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when the room temperature is higher than the set temperature.
The compressor stops when the room temperature is equal to or lower than the set temperature.
3 The compressor stops in check mode or during protective functions. 4 The compressor will not start when the room temperature is below 18 °C. The compressor starts intermittent operation
when the power is turned ON with room temperature above 18 °C. The compressor ON/OFF time depends on the thermo­stat ON/OFF and the room temperature as follows. After 3-minute compressor operation,
If the room temperature thermistor reads above 28 °C with thermostat ON, the compressor will operate will operate for 6 more minutes and then stop for 3 minutes.
If the room temperature thermistor reads 26 °C ~ 28 °C with thermostat 0N, the compressor will operate for 4 more min­utes and then stop for 3 minutes.
If the room temperature thermistor reads 24 °C ~ 26 °C with thermostat ON, the compressor will operate for 2 more min­utes and then stop for 3 minutes.
If the room temperature thermistor reads below 24 °C with thermostat ON, the compressor will stop for 3 minutes.
If the thermostat is OFF, regardless of room temperature, the compressor will stop for 10 minutes.
5 Coil frost protection
Coil frost protection in DRY operation is the same as in COOL operation.
6 Coil frost prevention
Coil frost prevention does not operate in DRY operation.
30
Page 31
(2) Indoor fan control
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
NOT AVAILABLE
CHECK
TEST RUN
˚C
AMPM
AMPM
ON / OFF
NOT AVAILABLE
AM PM
AM PM
˚C
MODE
FAN
VANE STOP
START
CLOCK
HR MIN.
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
NOT AVAILABLE
CHECK
TEST RUN
˚C
AMPM
AMPM
ON / OFF
NOT AVAILABLE
AM PM
AM PM
˚C
MODE
FAN
VANE STOP
START
CLOCK
HR MIN.
h
HR
/
min
MIN.
/
STOP
/
AUTO STOP
/
START
AUTO START
The indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote con­troller. Also, the indoor fan does not run during compressor OFF.
(3)Auto vane control
Same as in COOL operation.
(4)Detecting abnormalities in the outdoor unit
An abnormality in the outdoor unit can not be detected in DRY operation.
2-3 FAN operation
<How to operate>
1 Press POWER ON/OFF button. 2 Press MODE button to set operation mode to Fan .
(1) Indoor fan control
The indoor fan speed depends on the remote controller setting.
(2) Auto vane control
The auto vane position depends on the remote controller set­ting.
PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2/3 PK-3FLA2/3/4 PK-4FLSA2/3
2-4 TIMER operation
PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2/3 PK-3FLA2/3/4 PK-4FLSA2/3
PK-2.5FLA4 PK-3FLA5 PK-4FLSA4
PK-2.5FLA4 PK-3FLA5 PK-4FLSA4
<How to operate>
1 Push POWER ON/OFF button. 2 Check if or not the current time is correct. 3 Push the or button and select the desired
time.
4 Set the timer time using and buttons.
31
Page 32
ON / OFF
0
9
8
7
6
5
4
3
2
1
Nrm Set
Reset
After refiling batteries. Press the reset button.
Display will start flashingTurn the adjusting switch to "SET"
ON / OFF
NOT AVAILABLE
AM PM
AM PM
˚C
MODE
FAN
VANE STOP
START
CLOCK
HR MIN.
2-5 Test run
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
TEST RUN
RESET
SET
CLOCK
6
4
A
5
2
3
MODE
COOL
TEST RUN
FAN
VANE TEST RUN
PK-1.6FLA3, PK-2FLA3 PK-2.5FLA2/3, PK-3FLA2/3/4 PK-4FLSA2/3
Measure an impedance between the power supply terminal block and ground with a 500V Megger and check that it is equal to or greater than 1.0M".
(1) Turn on the main power of unit. (2) Turn the adjusting switch on the back of the
wireless remote controller to “SET” CHECK and TEST RUN will start flashing.
Wireless remote controller with backside battery cover removed Display will start finishing.
(3) Push the MIN button TEST RUN and
the operating mode will be displayed (Refer to the illustrated sample display at left)
(4) Push the MODE button, change the
mode to “FAN” and make sure that there will be blowout of air.
(5) Push the MODE button, change the mode
to COOLand make sure that there will be blowout of cool air.
PK-2.5FLA4 PK-3FLA5 PK-4FLSA4
(6) Push the FAN button and make sure that
there will be strong (or weak) blowout of air.
For operations marked "", point the transmitter to the wireless receiver, and make sure that you will hear a short beep from the receiver.
(7) Push the VANE button and verify the
operation of the auto vane.
(8) Push the POWER ON/OFF button and
cancel the test run.
(9) After completing a test run, be sure to
turn the adjusting switch back to “Nrm”.
The test run automatically stops in 2 hours.
Set temperature is not displayed during test run.
Test run
Measure an impedance between the power supply terminal block and ground with a 500V Megger and check that it is equal to or greater than 1.0M".
1 Turn on the main power to the unit. 2 Press the button twice continuously.
(Start this operation from the status of remote controller display turned off.)
A and current operation mode are displayed.
3 Press the ( ) button to activate mode, then check
whether cool air is blown out from the unit.
4 Press the button and check whether strong air is blown out from the
unit.
5 Press the button and check whether the auto vane operates properly. 6 Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver while fol­lowing steps 22to 66.
• It is not possible to run the in FAN, DRY mode.
32
Page 33
2-6 Emergency operation
When the remote controller or microprocessor malfunctions and no other trouble exists, emergency operation is available by setting the dip switch on the controller board.
[Check items] (1) Make sure the compressor and the fans are running normally. (2) Locate the trouble with the self-diagnostic function.
If the self-diagnostic function indicates that the protection device (such as coil frost protection) is functioning, the sources must be removed before attempting emergency operation. Emergency operation ON/OFF is activated not with the remote controller but with the circuit breaker.
[Emergency operation produce] (1)Cooling operation is available by setting the dip switch SW3
1and 2 ON and 3 OFF on the indoor controller board.
(2)To start emergency operation, turn the outdoor side circuit
breaker ON first, and then the indoor side circuit breaker ON.
(3)During emergency operation, the indooor fan runs on HIGH
speed, the compressor runs continuously, and the louver
ON
OFF
COOLING
SW3
123
SW3 INDOOR CONTROLLER BOARD
stops. (4)Thermostat will not function. (5)Do not use emergency cooling operation for more than 10
hours, as the indoor coil may freeze.
2-7 Function of jumper wire and dip switch on indoor controller board
1. Jumper wire
1 JR01:Jumper wire for the auto vanes
Cut JR01 for the unit WITHOUT auto vanes.
2 JR02:Jumper wire for the temperature to start coil frost prevention
Cutting JR02 changes the temperature from +1°C to -3°C.
3 JR03:Jumper wire for set temperature adjustment in HEAT mode
In HEAT operation, heated air stagnates in the upper part of the room. The indoor unit installed in the upper part of the room will detect the air temperature higher than the actual temperature in the living space. This difference is about 4 degrees. Therefore, the temperature detected by the room temperature thermistor should be corrected 4 degrees down. The unit with JR04 attached will make this adjustment.
4 JR04:Jumper wire for the indoor fan speed during thermostat OFF in HEAT mode
Cutting JR04 Changes the speed from Extra-Low to Low.
5 JR05:Jumper wire for detecting abnormalities in the outdoor unit
Cutting JR05 makes this detection unavailable. (Occurrence of abnormality can not be detected.)
6 JR06:Jumper wire for auto restart function
Cutting JR06 makes the auto restart function available.
2.Dip switch
1 SW1 (Function switch)
ON OFF
123
4567 8
SW1-1) Switch for power supply
ON:220V OFF:230V, 240V
SW1-2) Switch for single or twin control
ON:Twin control OFF:Single control
SW1-3) Switch for unit number in twin control (This switch is valid when SW1-2 is ON.)
ON:Unit No.2 OFF:Unit No.1
33
Page 34
SW1-4 ~ SW1-6) Switch for capacity of each model
PK-1.6 PK-2.5 PK-3
ON OFF
456
SW1-7 ~ SW1-8) Switch for the pair number of wireless remote controller
0
ON OFF
78
The pair number setting of the wireless remote controller is needed. (Refer to the next page for the details.)
2 SW2 (Unit switch)
ON OFF
12345
SW2-1) Switch for air conditioner with or without electric heater
ON:Unit with electric heater OFF:Unit without electric heater
SW2-2) Switch for air conditioner with or without heat pump
ON:Unit with heat pump OFF:Unit without heat pump
SW2-3, SW2-4, SW2-5) Switch for function code
ON:Unit with electric heater OFF:Unit without electric heater
PK-2 PK-4
ON OFF
456
1
ON OFF
78
ON OFF
456
2
ON OFF
78
3
ON OFF
78
PK-1.6 PK-2
ON OFF
345
3 SW3 (Emergency operation switch)
Normal operation For emergency cooling
3
12 ON OFF
12 ON OFF
PK-2.5 PK-3 PK-4
ON OFF
345
3
34
Page 35
2-8 Wireless remote controller pair number setting operation
Pair Number
0
1
2
3
Pair NumberSW1 SW1
123456
ON
OFF
78
123456
ON
OFF
78
123456
ON
OFF
78
123456
ON
OFF
78
0
9
8
7
6
5
4
3
2
1
Nrm Set
Reset
After refiling batteries. Press the reset button.
A
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
MODEL SELECT
4
A
Model No.
5
1,4
MODEL SELECT
min
A Pair No. of wireless remote controller
Indoor PC board
< SW1 >
0
1
2
3~9
123456
ON
OFF
78
123456
ON
OFF
78
123456
ON
OFF
78
123456
ON
OFF
78
PK-1.6FLA3, PK-2FLA3 PK-2.5FLA2/3, PK-3FLA2/3/4 PK-4FLSA2/3
Switches are located on the indoor unit PC board and inside the remote controller as shown.
• Setting the SW1 (PC board inside indoor unit) Sub-switches 7 or 8 of SW1 can be used as follows to assign a pair No.
• The pair No. SW of the remote controller has been set to ‹‹0›› at the time of
ship-ment.
Note:
Make sure that the pair No. AAof the remote controller matches that of the indoor unit PC board.
PK-2.5FLA4 PK-3FLA5 PK-4FLSA4
1 Turn on the main power to the unit. 2 Press the SET button with the point of a ball-point pen or the like.
Start this operation from the status of remote controller display turned off.
blinks and Model No. is lighted.
3 Press the button twice continuously. A Pair No. “0” blinks. 4 Press the temp button to set the pair number you want to set. 5 Press the SET button with the point of a ball-point pen or the like.
Set pair number is lighted for three seconds then turned off.
35
Page 36
11
TROUBLESHOOTING
1. Self-diagnostic function [for PK-1.6FLA3, PK-2FLA3, PK-2.5FLD2/3, PK-3FLD2/3/4, PK-4FLSD2/3 ]
(1) Turn on the main power of the unit. (2) Set the adjusting switch on the back of
the wireless remote controller to “Set” CHECK and TEST RUN will start light­ing.
(3) Push the HR button, CHECK will start
blinking.
(4) Send the signal from the remote controller
to the unit with pressing HR button. If the buzzer sound is heard and the ON/OFF lamp (unit display) blinks, refer to following table.
The number of
Buzzer sound
ON/OFF lamp
(Unit display) blinking
1 second
(0.5 second interval)
Beep
This corresponds
to the number of
buzzer sound
The number of
ON/OFF lamp
(Unit display) blinking
Irregular point
and buzzer sound
1 2 4 5 6 8 9
Irregular intake sensor Irregular piping sensor Irregular drain sensor Irregular drain pump Freezing protected Irregular outdoor unit NO irregular
(Refer to next page in detail)
(5) Push the POWER ON/OFF button and
cancel the test run.
(6) After completing a test run, be sure to
turn the adjusting switch back to “Nrm”.
NOT AVAILABLE
ON / OFF
MODE
FAN
VANE STOP
HR MIN.
Remove the battery cover on the back side of the wireless remote controller, display will start flashing when the “Set” switch is turned on. For operations marked “”, point the transmitter to the wireless receiver, and make sure that you will hear a short beep from the receiver.
Turn the adjusting switch to "SET"
˚C
AM PM
AM PM
CLOCK
START
After refiling batteries. Press the reset button.
Nrm Set
Display will start flashing
ON / OFF
Reset
3
2
4
1
5
0
6
9
7
8
For operations marked "", point the transmitter to the wireless receiver, and make sure that you will hear a short beep from the receiver.
36
Page 37
1. Self-diagnostic function
CHECK
h
ON/OFF
Check Code
1 2 3 4 5
6
7 8
9
Suction sensor alarm Plpe sensor alarm Transmission alarm Drain sensor alarm Drain pump alarm Anti-freezing on Anti-overheat on System error Outdoor unit alarm
No alarm (no error)
Single beep 1 Single beep 2 Single beep 3 Single beep 4 Single beep 5 Single beep 6 Single beep 6 Single beep 7 Single beep 8 Receiving signal only
(no error alarm)
Alarm Buzzer sound
[for PK-2.5FLA4, PK-3FLA5, PK-4FLSA4]
1 Turn on the main power to the unit. 2 Press the button twice continuously.
• begins to light and refrigerant address display “00” begins to blink.
• Start this operation from the status of remote controller display turned off
3 While pointing the remote controller toward the unit’s receiver, press the
button
• If the buzzer sound is heard and the ON/OFF lamp (unit display) blinks, refer to following table.
4 While pointing the remote controller toward the unit’s receiver, press the
ON/OFF button.
• Self-check mode is cancelled.
4
ON/OFF
TEMP
FAN
AUTO STOP
2. OTHER TROUBLES AND CAUSES
Auto vanes do not work.
Auto vane motor does not work. Connector is poorly connected. Auto vane motor is poorly assembled. Indoor controller board is damaged.
VANE
LOUVER
RESET
CLOCK
AUTO START
2
MODE
CHECK
TEST RUN
SET
Auto vane motor is damaged. Auto vane motor relay is damaged.
h
3
min
Power ON/OFF button
is not available.
Indoor/outdoor connecting wire is connected incorrectly. Indoor/outdoor connecting wire shorts. Compressor protector is damaged. Outdoor controller board is defective. Remote controller is damaged. Transmission wire is poorly connected
Transmission wire is damaged. Connector is poorly connected.
37
Page 38
3. How to check the parts
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
< Thermistor for lower temperature >
Temperature (:)
Resistance (K")
PK-1.6FLA3, PK-2FLA3, PK-2.5FLA
2/3/4
, PK-3FLA
Parts name Check points
Room temperature thermistor (RT1) Pipe temperature thermistor (RT2)
Disconnect the connector, then measure the resistance using a tester. (Surrounding temperature 10°C~30°C)
Normal
4.3k'~9.6k'
Abnormal
Open or short
2/3/4/5
, PK-4FLSA
2/3/4
Transformer
CNT T CN4T
WHT
1 2 3
YLW
BRN
RED
Fan motor
Relay connector
1
White
3
5
Protector
Vane motor
Orange
4
Red
5
Pink
2
Yellow
Connector
3 6 1
Red
Black
1 2 3 4
M
Blue
Brown
Disconnect the connector and measure the resistance using a tester.
CNT(1)-(3) CN4T(1)-(2) CN4T(3)-(4)
Normal
WHT. Approx. 135'
BRN. Approx. 0.5~2.0' RED. Approx. 1.0~2.0'
Abnormal
Open or short
Measure the resistance between the terminals using a tester.
Motor terminal
Relay connector
1 3 5
Red-White
White-Black
Thermal protector
or
1.6FLA3, 2FLA3
114.5'i10%
118.2'i10%
OFF : 125i5˚C
ON : 125i5˚C
Normal
PK-
2.5FLD
2/3/4
99.5'i10%
103.5'i10%
, 3FLD
2/3/4/5
OFF : 130i5˚C
ON : 80i20˚C
4FLSA2/3/4
62.6'i10%
74.0'i10%
Abnormal
Open or short
Measure the resistance between the terminals using a tester. (Surrounding temperature 20°C~30°C)
Normal
PK­PK-
1.6FLA3 2FLA3
PK-2.5FLD PK-
4FLSA2/3/4
2/3/4
, PK-3FLD
2/3/4/5
,
Abnormal
Brown-Yellow
Brown-Blue
Red-Orange
15k'
186~214'
Open or short
Red-Pink
<Thermistor Characteristic graph>
Thermistor for lower temperature
Thermistor R0=15k' ±3%
Room temperature thermistor(RT1) Pipe temperature thermistor(RT2)
Fixed number of B=3480k' ±2% Rt=15exp { 3480( ) }
1
273+t
0: 15k' 10: 9.6k' 20: 6.3k' 25: 5.4k' 30: 4.3k' 40: 3.0k'
1
273
38
Page 39
12
Metal fixture
Screws
Hanger of indoor unit
Catch of installation plate
Terminal cover
Electrical parts box cover
Connector
Connector
Indoor controller board
Right side panel
DISASSEMBLY PROCEDURE
PK-1.6FLA3, PK-2FLA3, PK-2.5FLA
2/3/4
, PK-3FLA
OPERATING PROCEDURE PHOTOS&ILLUSTRATION
1. Removing the lower side of the indoor unit from the instal­lation plate
(1) Remove the 2 screws.
Hang the indoor unit hangers to the catches on the instal­lation plate.
2. Removing the right side panel
(1) Remove the 2 screws of the right side panel:one on the
bottom and the other on the upper right-hand side. (2) Disconnect the connector from the adapter case. (3) Sliding the right side panel to the right, pull it out toward
you.
2/3/4/5
, PK-4FLSA
Figure 1
Figure 2
2/3/4
3. Removing the indoor controller board
(1) Remove the right side panel. (2) Remove the screw of the electrical parts box cover, and
remove the cover. (3) Disconnect the connectors on the indoor controller board. (4) To unhook the catches on the right-hand side of the indoor
controller board, pull the left-hand side toward you and lift
up the cover to the right. Then the indoor controller board
can be removed.
4. Removing the electrical parts box
(1) Remove the right side panel. (2) Remove the screw of the electrical parts box cover, and
remove the cover. (3) Remove the room temperature thermistor and the indoor
coil thermistor. (4) Disconnect the vane motor connector on the indoor con-
troller board. (5) Remove the 2 screws of the electrical parts box. (6) Disconnect the connector of the heater lead wire connec-
tor. (7) Disconnect the connector of the fan motor lead wire. (8) Remove the electrical parts box.
Photo 1
Photo 2
Indoor controller board
Room temperature thermistor
Indoor coil thermistor
Electrical parts box cover
Catches
Screws
Electrical parts
box
39
Page 40
OPERATING PROCEDURE PHOTOS&ILLUSTRATION
Catch on the left side panel
Catch on the unit
(9) Remove the screws of the indoor controller board case,
and pull out the indoor controller board case. Then the transformer and the capacitor and relay can be serviced.
5. Removing the vane motor
(1) Remove the right side panel. (2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Remove the 2 screws of the vane motor, and remove the
motor from the shaft.
(4) Disconnect the vane motor connector on the indoor con-
troller board.
Photo 3
Capacitor
Indoor controller board case
Photo 4
Relay
Transformer
Electrical parts box
Screws
6 Removing the intake grills
(1) Remove the right side panel. (2) To remove the left side panel, remove the screw on the
bottom and the screw on the upper left-hand side. (See Figure 3.)
1. Press up this side of the left side panel to unhook the catch on the panel from the catch on the unit.
2. Slide the left side panel to the left to remove the panel.
Note: Fix the unit to the metal fixture securely (3) Remove the air filters. (4) Hold and press the centre cover to remove. (5) Remove the screws of the grills. (6) Pull the lower side of the grill toward you and slide the
upper to the right to remove the grills.
7. Removing the drain pan
(1) Remove the left and right side panels. (2) Remove the grills. (3) Remove the electrical parts box cover. (4) Loosen the drain hose band to remove. (5) Remove the 3 screws of the drain pan, and slide the drain
pan toward you to remove.
Vane motor
Figure 3
Photo 5
Left side panel
Photo 6
Indoor controller board
Slide to the right
Screws for grills
Drain pan
Screws
Grills
Drain hose band
Drain hose
40
Page 41
OPERATING PROCEDURE PHOTOS
8. Removing the lineflow fan and the fan motor
(1) Remove the left and right side panels. (2) Remove the grills. (3) Remove the electrical parts box. (4) Remove the drain pan. (5) Loosen the screw that fixes the lineflow fan to the fan
motor. (See Photo 7. )
(6) Remove the 4 screws of the motor fixture, and remove the
fan motor and the motor fixture at a time (See Photo 8.)
(7) Remove the screws of the left and right motor supports,
and remove the motor supports and the fan motor. (See Photo 9.)
(8) Remove the screw of the centre support, and remove the
support. (See Photo 10. )
(9) Remove the 2 screws on the left and right sides of the heat
exchanger, and pull the bearing support toward you. (See Photo 11.)
(10) Pull the left-hand side of the heat exchanger toward you,
and remove the lineflow fan.
Photo 7
Photo 8
Lineflow fan
Screw
Fan motor
Screw Fan motor
Motor fixture
Heat exchanger
Bearing support
Lineflow fan
Photo 9Photo 11
Screw
Motor support
Photo 10
Centre support
Fan motor
Lineflow fan
Screw
Screw
Motor support
41
Page 42
13
No.
Part No.
Part name
Specification
Unit
Amount
Remarks.
(Drawing No.)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty/set
PK-1.6,PK-2
Price
1
2 3 4
5
6 7 8
9 10 11 12
FRONT PANEL FRONT PANEL SCREW CAP CATCH HOLDER FILTER CATCH AIR FILTER AIR FILTER SERVICE PANEL WIRELESS ADAPTER PANEL CATCH UNDER COVER CORNER COVER BOX ASSEMBLY BACK PLATE
(BG25R572H06)
(BG25G057H07)
FLA1 FLA2 FLA3
FLA
W.B
1
4 2 2 2
1 1 2 1 1 1 1
1 4 2 2
2 1 1 2 1 1 1 1
R01 KV5 651 R01 47J 651 R01 KV5 096
— R01 A20 054 R01 KV5 500 R01 47J 500 T7W 570 058 T7W 570 317
— R01 KV5 623 R01 KV5 658 R01 KV5 635 R01 KV5 808
PARTS LIST
STRUCTURAL PARTS
1
PK-1.6FLA, PK-1.6FLA
, PK-1.6FLA2, PK-1.6FLA
PK-2FLA, PK-2FLA1, PK-2FLA2, PK-2FLA
3
3
42
Page 43
STRUCTURAL PARTS PK-2.5FLA, PK-2.5FLA
1
, PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA
4
10
1
2
3
9
8
12
7
6
4
Part number that is circled is not shown in the figure.
No.
Part No.
1
R01 12G 662 R01 12G 812
2
R01 E01 812 R01 12G 811
3
R01 E00 811
4
R01 A17 500
5
T7W 570 317
6
R01 12G 661
7
R01 12G 691
8
R01 12G 808
9
R01 E01 641
10
11
R01 12G 523
12
R01 24K 658
— —
Part name
LEFT SIDE PANEL UNDER PLATE UNDER PLATE NOSE NOSE AIR FILTER WIRELESS ADAPTER RIGHT SIDE PANEL INTAKE GRILLE BACK PLATE TOP PLATE BOX ASSEMBLY BOX ASSEMBLY DRAIN SOCKET RECEIVER
Specification
Q'ty/set
PK-2.5
FLA FLA1 FLA2
1 1
1
4 1 1 2 1 1 1
1 1
PK-2.5
FLA3 FLA4
1
1
1 4 1 1 2 1 1
1 1 1
5
Remarks.
(Drawing No.)
(BG00A593G89) (RG00A734G61)
Wiring
Diagram
Symbol
W.B
Recom-
mended
Q'ty
Unit
Price
Amount
43
Page 44
No.
Part No.
Part name
Specification
Unit
Amount
Remarks.
(Drawing No.)
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Q'ty/set
Price
1
2
3
4 5 6 7 8 9
10
11 12
LEFT SIDE PANEL UNDER PLATE UNDER PLATE NOSE NOSE AIR FILTER WIRELESS ADAPTER RIGHT SIDE PANEL INTAKE GRILLE BACK PLATE TOP PLATE BOX ASSEMBLY BOX ASSEMBLY DRAIN SOCKET RECEIVER
(BG00A593G89) (RG00A734G61)
PK-3
FLA3FLA FLA1 FLA2
PK-3
W.B
1 1
1
4 1 1 2 1 1 1
1 1
1 1
1
4 1 1 2 1 1 1
1 1
FLA4 FLA5
PK-3
1
1
1 4 1 1 2 1 1
1 1 1
R01 12G 662 R01 12G 812 R01 E01 812 R01 12G 811 R01 E00 811 R01 A17 500 T7W 570 317 R01 12G 661 R01 12G 691 R01 12G 808 R01 E01 641
— R01 12G 523 R01 24K 658
STRUCTURAL PARTS
1
PK-3FLA, PK-3FLA
, PK-3FLA2, PK-3FLA3, PK-3FLA4, PK-3FLA
1
5
910
8
2
3
4
Part number that is circled is not shown in the figure.
5
7
12
6
44
Page 45
STRUCTURAL PARTS PK-4FLSA, PK-4FLSA
1
1
, PK-4FLSA2, PK-4FLSA3, PK-4FLSA
910
4
8
2
3
4
Part number that is circled is not shown in the figure.
No.
Part No.
1
R01 12G 662 R01 16G 812
2
R01 E00 812 R01 16G 811
3
R01 E01 811
4
R01 A17 500
5
T7W 570 317
6
R01 12G 661
7
R01 12G 691
8
R01 16G 808
9
R01 E00 641
10
11
R01 12G 523
12
R01 24K 658
13
R01 16G 692
— —
Part name
LEFT SIDE PANEL UNDER PLATE UNDER PLATE NOSE NOSE AIR FILTER WIRELESS ADAPTER RIGHT SIDE PANEL INTAKE GRILLE BACK PLATE TOP PLATE BOX ASSEMBLY BOX ASSEMBLY DRAIN SOCKET RECEIVER INTAKE GRILLE
Specification
Q'ty/set
PK-4
FLSA FLSA1 FLSA2
1 1
1
5 1 1 2 1 1 1
1 1 1
PK-4
FLSA3 FLSA4
1
1
1 5 1 1 2 1 1
1 1 1 1
7
5
Remarks.
(Drawing No.)
(BG00A593G89) (RG00A734G62)
Wiring
Diagram
Symbol
W.B
12
Recom-
mended
Q'ty
Unit
6
Price
Amount
45
Page 46
ELECTRICAL PARTS
1
PK-1.6FLA, PK-1.6FLA
, PK-1.6FLA2, PK-1.6FLA
PK-2FLA, PK-2FLA1, PK-2FLA2, PK-2FLA
3
3
3
4
5
6
8
9
11
12
1
2
27
7
31
32
10
15
30
16
29
17
28
19 20 21
26
22
25
24
23
13
33
14
34
35
18
36
46
Page 47
No.
Part No.
Part name
Specification
Unit
Amount
Remarks.
(Drawing No.)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty/set
PK-1.6 PK-2
Price
1
2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18
19
20 21 22 23
24
25 26
27
28 29 30 31 32 33
34
35 36 37
HEAT EXCHANGER HEAT EXCHANGER LINEFLOW FAN BEARING SUPPORT SLEEVE BEARING BEARING MOUNT FAN GUARD FAN GUARD VANE MOTOR NOZZLE ASSEMBLY GUIDE VANE LEFT ROTARY VANE CENTER SUPPORT VANE SLEEVE DRAIN HOSE ARM RIGHT ROTARY VANE CONTROL BOX COVER TERMINAL COVER CONTROLLER BOARD CONTROLLER BOARD CONTROLLER CASE FUSE TERMINAL BLOCK TERMINAL BLOCK TRANSFORMER TRANSFORMER RUN CAPACITOR INDOOR COIL THERMISTOR ROOM TEMPERATURE THERMISTOR ROOM TEMPERATURE THERMISTOR WATER SHIELD MOTOR SUPPORT FAN MOTOR RUBBER MOUNT MOTOR COVER REMOTE CONTROLLER DOOR REMOTE CONTROLLER REMOTE CONTROLLER BATTERY COVER REMOTE CONTROLLER HOLDER DRAIN SOCKET
(BG25M017H06)
(BG02A326G06) (BG02B718H05)
(BG25B573H05)
(BG25B846H11)
FLA
FLA1
FLA2 FLA3
FLA
FLA1
FLA2 FLA3
MV
I.B I.B
F1,2<I.B> TB2 TB5 T T C1 RT2 RT1 RT1
MF
W.R W.R
250V 6.3A 3P(L,N,;) 2P(1/2)
2.0+ 440V
PK4V30-KA
1
1 1 1 1
1 1
16
1 1 1 1 2 1 1 1 1
1 2 1 1 1
1 1 1
1 1 1 1 1 1 1
1 1 1
1
1 1 1 1
1 1
16
1 1 1 1 2 1 1 1 1
1 2 1 1 1
1 1
1 1 1 1 1 1 1 1
1 1 1
1
1 1 1 1 1 1 1 1
16
1 1 1 1 2 1 1 1
1 1 2 1 1
1 1 1
1 1 1 1 1 1 1
1 1 1 1
1 1 1 1 1
1 1
16
1 1 1 1 2 1 1 1 1
1 2 1 1 1
1 1 1
1 1 1 1 1 1 1
1 1 1
1 1 1 1 1
1 1
16
1 1 1 1 2 1 1 1 1
1 2 1 1 1
1 1
1 1 1 1 1 1 1 1
1 1 1
1 1 1 1 1 1 1 1 1
16
1 1 1 1 2 1 1 1
1 1 2 1 1
1 1 1
1 1 1 1 1 1 1
1 1 1 1
T7W 570 480 R01 21A 480 R01 KV5 114 R01 KV5 106 R01 566 103 R01 KV5 102 T7W 52J 675 T7W 51J 675 R01 KV5 223 R01 KV5 530 R01 KV5 038 R01 KW1 002 R01 KV5 048
— R01 71G 527 R01 KV5 059 R01 KW2 002
— T7W 520 310 T7W 27K 310
— R01 520 239 T7W 514 716 T7W 512 716 T7W 552 799 T7W 52J 799 R01 588 255 R01 KN7 202 R01 J07 202 R01 06A 202
— R01 KV5 130 T7W 570 762 R01 KV5 105 R01 KV5 135 R01 58A 049 T7W 570 200 T7W 56J 200 R01 58A 050 R01 18G 075 R01 12G 523
Parts number that is circled is not shown in the figure.
47
Page 48
No.
Part No.
Part name
Specification
Unit
Amount
Remarks.
(Drawing No.)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty/set
PK-2.5
Price
1 2 3 4
5
6 7 8
SLEEVE BEARING BEARING MOUNT LEFT LINEFLOW FAN HEAT EXCHANGER DRAIN PAN DRAIN PAN ARM JOINT SHAFT CENTER COVER
FLA
1
FLA2
FLA FLA3 FLA4
1 1 1 1 1
3 1 1
1 1 1 1 1
3 1 1
1 1 1 1
1 3 1 1
1 1 1 1
1 3 1 1
R01 005 103 R01 Z61 102 R01 13G 114 T7W 572 480 R01 12G 529 T7W E13 529
— R01 12G 063 R01 12G 621
(BG25H301H02)
ELECTRICAL PARTS PK-2.5FLA, PK-2.5FLA
1
, PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA
4
37
1
2
32
35
36
38
PK-2.5FLA PK-2.5FLA PK-2.5FLA PK-2.5FLA
1 2 3
34
3
33
4
31
32
PK-2.5FLA
4
26
5
30
29
25
28
27
24
6
22
8
7
23
21
9
10
11
12
13
1514
48
16
17
18
20
19
Page 49
No.
Part No.
Part name
Specification
Q'ty/set
PK-2.5
FLA FLA2
1
FLA FLA3 FLA4
Remarks.
(Drawing No.)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Price
Amount
R01 12G 002
9
R01 KV5 527
10
11
R01 12G 223
12
R01 06A 202
13
R01 KL5 202
14 15
R01 588 255
16
T7W 560 310
17
T7W 27K 310 T7W 520 239
18 19 20
T7W 552 799
21
T7W 51J 799 T7W 512 716
22
T7W 509 716
23 24
R01 12G 220
25 26
R01 12G 105
27 28
R01 13G 115
29 30 31
T7W 53J 675
32
R01 12G 103
33
R01 KV5 102
34
R01 58A 049
35
R01 E01 049 T7W 570 200
36
T7W E06 714 R01 58A 050
37
R01 18G 075
38
R01 E00 075
— —
— —
— —
AUTO VANE DRAIN HOSE GUIDE VANE GUIDE VANE (WITH HANDLE) VANE MOTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR TERMINAL COVER RUN CAPACITOR CONTROLLER BOARD CONTROLLER BOARD FUSE CONTROLLER COVER CONTROLLER CASE TRANSFORMER TRANSFORMER TERMINAL BLOCK TERMINAL BLOCK MOTOR BAND FAN MOTOR MOTOR LEG RUBBER MOUNT MOTOR BAND RIGHT LINEFLOW FAN CENTER SUPPORT BEARING BAND FAN GUARD SLEEVE BEARING BEARING MOUNT REMOTE CONTROLLER DOOR REMOTE CONTROLLER DOOR REMOTE CONTROLLER REMOTE CONTROLLER BATTERY COVER REMOTE CONTROLLER HOLDER REMOTE CONTROLLER HOLDER
2.0+ 440V
250V 6.3A
2P(1/2) 3P(L,N,;)
20
2
2
2
2
1
1
1
1
20
20
20
4
4
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 1
1
1
2
2
2
1
1
1
1
1
1 1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
(BG25J821H01)
4
(BG25J821H02) 1 1 1 1
(BG02J608H07) 1
1 2 1
(BG02A648G02) 1
(BG25B573H06)
1 1 1 1
(BG02H065H01) 1 1
(BG02A534H16) 2 1
(BG02H178H01) 1 1
(BG00R259G07) 1
(BG02L462H02) 2 1 1
1
1
1
MV RT1 RT2
C I.B I.B F1,2<I.B>
T T TB4 TB2
MF
W.R W.R
49
Page 50
No.
Part No.
Part name
Specification
Unit
Amount
Remarks.
(Drawing No.)
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Q'ty/set
PK-3
Price
1 2 3 4
5
6 7 8
SLEEVE BEARING BEARING MOUNT LEFT LINEFLOW FAN HEAT EXCHANGER DRAIN PAN DRAIN PAN ARM JOINT SHAFT CENTER COVER
FLA
1
FLA2 FLA3
FLA FLA4 FLA5
1 1 1 1 1
3 1 1
1 1 1 1 1
3 1 1
1 1 1 1
1 3 1 1
1 1 1 1
1 3 1 1
R01 005 103 R01 Z61 102 R01 13G 114 T7W 573 480 R01 12G 529 T7W E13 529
— R01 12G 063 R01 12G 621
(BG25H301H02)
ELECTRICAL PARTS PK-3FLA, PK-3FLA
1
, PK-3FLA2, PK-3FLA3, PK-3FLA4, PK-3FLA
5
37
1
2
32
35
36
38
PK-3FLA PK-3FLA PK-3FLA PK-3FLA PK-3FLA
1 2 3 4
34
3
33
4
31
32
PK-3FLA
5
26
5
30
29
25
28
27
24
6
22
8
7
23
21
9
10
11
12
13
50
1514
16
17
18
20
19
Page 51
No.
Part No.
R01 12G 002
9
R01 KV5 527
10
11
R01 12G 223
12
R01 06A 202
13
R01 KL5 202
14 15
R01 588 255
16
T7W 560 310
17
T7W 27K 310 T7W 520 239
18 19 20
T7W 552 799
21
T7W 51J 799 T7W 512 716
22
T7W 509 716
23 24
R01 12G 220
25 26
R01 12G 105
27 28
R01 13G 115
29 30 31
T7W 53J 675
32
R01 12G 103
33
R01 KV5 102
34
R01 58A 049
35
R01 E01 049 T7W 570 200
36
T7W E06 714 R01 58A 050
37
R01 18G 075
38
R01 E00 075
— —
— —
— —
Part name
AUTO VANE DRAIN HOSE GUIDE VANE GUIDE VANE (WITH HANDLE) VANE MOTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR TERMINAL COVER RUN CAPACITOR CONTROLLER BOARD CONTROLLER BOARD FUSE CONTROLLER COVER CONTROLLER CASE TRANSFORMER TRANSFORMER TERMINAL BLOCK TERMINAL BLOCK MOTOR BAND FAN MOTOR MOTOR LEG RUBBER MOUNT MOTOR BAND RIGHT LINEFLOW FAN CENTER SUPPORT BEARING BAND FAN GUARD SLEEVE BEARING BEARING MOUNT REMOTE CONTROLLER DOOR REMOTE CONTROLLER DOOR REMOTE CONTROLLER REMOTE CONTROLLER BATTERY COVER REMOTE CONTROLLER HOLDER REMOTE CONTROLLER HOLDER
Specification
2.0+ 440V
250V 6.3A
2P(1/2) 3P(L,N,;)
Q'ty/set
PK-3
FLA
1
FLA2
FLA FLA4 FLA5
FLA3
2
2
2
2
1
1
1
1
20
20
20
20
4
4
4
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 1
1
1
1
2
2
2
2
1
1
1
1
1
1
1
1 1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks.
(Drawing No.)
(BG25J821H01) (BG25J821H02)
(BG02J608H07)
(BG02A648G02) (BG25B573H06)
(BG02H065H01)
(BG02A534H16)
(BG02H178H01)
(BG00R259G07) (BG02L462H02)
Wiring
Diagram
Symbol
MV RT1 RT2
C I.B I.B F1,2<I.B>
T T TB4 TB2
MF
W.R W.R
Recom­mended
Q'ty
Unit
Price
Amount
51
Page 52
No.
Part No.
Part name
Specification
Unit
Amount
Remarks.
(Drawing No.)
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Q'ty/set
PK-4
Price
1 2 3
4
5
6 7 8
SLEEVE BEARING BEARING MOUNT LEFT LINEFLOW FAN HEAT EXCHANGER HEAT EXCHANGER DRAIN PAN DRAIN PAN ARM JOINT SHAFT CENTER COVER
FLSA1 FLSA2
FLSA
FLSA3FLSA4
1 1 1 1
1
4 1 1
1 1 1
1 1
4 1 1
1 1 1
1
1 4 1 1
1 1 1
1
1 4 1 1
R01 005 103 R01 Z61 102 R01 17G 114 T7W 574 480 R01 46G 480 R01 16G 529 T7W E14 529
R01 12G 063 R01 12G 621
(BG25H301H02)
ELECTRICAL PARTS PK-4FLSA, PK-4FLSA
1
, PK-4FLSA2, PK-4FLSA3, PK-4FLSA
4
37
1
2
32
35
36
38
PK-4FLSA PK-4FLSA PK-4FLSA PK-4FLSA
1 2 3
34
3
33
4
31
32
PK-4FLSA
4
26
5
30
29
25
28
27
24
6
22
8
7
23
21
9
10
11
12
13
52
1514
16
17
18
20
19
Page 53
No.
Part No.
Part name
Specification
FLSA
Q'ty/set
PK-4
FLSA1 FLSA2
FLSA3FLSA4
Remarks.
(Drawing No.)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Price
Amount
R01 16G 002
9
R01 KV5 527
10
11
R01 12G 223
12
R01 06A 202
13
R01 KL5 202
14 15
R01 576 255
16
T7W 560 310
17
T7W 27K 310 T7W 520 239
18 19 20
T7W 552 799
21
T7W 51J 799 T7W 512 716
22
T7W 509 716
23 24
T7W 571 762
25 26
R01 16G 105
27 28
R01 17G 115
29 30 31
T7W 71J 675
32
R01 12G 103
33
R01 KV5 102
34
R01 58A 049
35
R01 E01 049 T7W 570 200
36
T7W E06 714 R01 58A 050
37
R01 18G 075
38
R01 E00 075
— —
— —
— —
AUTO VANE DRAIN HOSE GUIDE VANE GUIDE VANE (WITH HANDLE) VANE MOTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR TERMINAL COVER RUN CAPACITOR CONTROLLER BOARD CONTROLLER BOARD FUSE CONTROLLER COVER CONTROLLER CASE TRANSFORMER TRANSFORMER TERMINAL BLOCK TERMINAL BLOCK MOTOR BAND FAN MOTOR MOTOR LEG RUBBER MOUNT MOTOR BAND RIGHT LINEFLOW FAN CENTER SUPPORT BEARING BAND FAN GUARD SLEEVE BEARING BEARING MOUNT REMOTE CONTROLLER DOOR REMOTE CONTROLLER DOOR REMOTE CONTROLLER REMOTE CONTROLLER BATTERY COVER REMOTE CONTROLLER HOLDER REMOTE CONTROLLER HOLDER
3.0+ 440V
250V 6.3A
2P(1/2) 3P(L,N,;)
26
2
2
2
2
1
1
1
1
26
26
26
4
4
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 1
1
1
2
2
2
1
1
1
1
1
1 1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
(BG25J821H01)
4
(BG25J821H02) 1 1 1 1
(BG02J608H07) 1
1 2 1
(BG02A648G02) 1
(BG25B573H06)
1 1 1 1
(BG02H065H01) 1 1
(BG02A534H17) 2 1
(BG02H178H01) 1 1
(BG00R259G07) 1
(BG02L462H02) 2 1 1
1
1
1
MV RT1 RT2
C I.B I.B F1,2<I.B>
T T TB4 TB2
MF
W.R W.R
53
Page 54
14
ORN 1
2 3
BRN RED
1 2 3 4 5
BRN RED ORN YLW GRN
Part No. Pipe lenght Pipe size O.D. Pipe size O.D.
PAC-05FFS-E
5m
Liquid:{9.52
Indoor unit:Flared
Gas:{15.88 Outdoor unit:Flared
PAC-07FFS-E
7m
PAC-10FFS-E
10m
PAC-15FFS-E
15m
Part No. Pipe lenght Pipe size O.D. Connection methed
PAC-SC51PI-E
5m
Liquid:{9.52
Indoor unit:Flared
Gas:{19.05 Outdoor unit:Flared
PAC-SC52PI-E
7m
PAC-SC53PI-E
10m
PAC-SC54PI-E
15m
OPTIONAL PARTS
1. REFRIGERANT PIPES
Service Ref. : PK-1.6FLA3,
PK-2FLA3, PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA4, PK-3FLA2, PK-3FLA3, PK-3FLA4, PK-3FLA5,
Service Ref. : PK-4FLSA2, PK-4FLSA3, PK-4FLSA
Note 1. How to connect refrigerant pipes.
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as the connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow. If piping length exceeds 5m,an additional charge of refrigerant is needed.
Note 2. The following main parts are contained in the optional refrigerant piping kit.
Heat insulating cover, vinyl tapes, nipples, sleeve and flange (for wall hole),connecting cables.
4
2. TIMER ADAPTER
This adapter is needed for system control and for operation via external contacts.
Part No. PAC-SA89TA-E
3. MULTIPLE REMOTE CONTROLLER ADAPTER
This adapter is needed for remote indication (operation/check).
Part No. PAC-SA88HA-E
54
Page 55
4. CENTRALIZED REMOTE CONTROLLER
BACK
ACTIVE BYPASS
POWER ON/OFF
DUAL
CENTRAL
AHEAD
ENGAGED
GROUP
ACTIVE BYPASS
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
DUAL CENTRAL
12345678910
113
113
10 9 8 7 6 5 4 3 2 1
56.3 11
23.5
8
Allows individual or combined control of up to 16 units.
Part No.
4-1. Dimensions
ENGAGED
GROUP
12345678910
GROUP SELECTION
PROGRAM
ACTIVE BYPASS
TIMER CONTROLLER
DUAL CENTRAL
OPERATION
117
4-2. Names and Functions
POWER ON/OFF
AHEAD
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
MITSUBISHI ELECTRIC
PAC-805RC
Unit : mm
12
117
"ENGAGED" indicator When this indicator is lit, transmission is in
progress and all switches are inoperative.
DUAL/CENTRAL switch This change-over switch governs the oper-
ation of the accessory remote controller.
"DUAL" Instructions from both the accessory
remote controller and the centralized remote controller are valid. (Priority given to the last instruction received.)
"CENTRAL" ON/OFF switching by the accessory
remote controller is invalidated. Operation is controlled by the centralized remote con­troller only.
Initial setting is "DUAL".
LCD Matrix Display This display indicates the operational sta-
tus of all connected units either by steady lighting or by flashing.
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
POWER ON/OFF
AHEAD
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
MITSUBISHI ELECTRIC
POWER ON/OFF switch Operation ON/OFF switch.
BACK AHEAD buttons These buttons are used to designate the attached unit(s). (They designate the unit to be centrally controlled.)
When group “00” is designated; col­lective ON/OFF instruction is sent to all units.
When group “01”-“16“ is designated; ON/OFF instruction is sent only to the designated units.
ACTIVE/BYPASS switch This is a change-over switch for the program timer. Use “BYPASS” when a program timer is not connected.
Independent “DUAL / CENTRAL” and “ACTIVE / BYPASS” setting of all the groups is possible. When the power supply to the
centralized remote controller is cut due to power failure, all settings will return to original “DUAL” and “BYPASS”.
55
Page 56
ANE
T
(Y)
(W) (R) (O)
(BR)
5A
A
POWER SUPPLY
N E
Fuse(5A)
Tie-wrap
Wiring has to be changed when a 200,230 or 240V power is used.
Tie-wrap
TRANSFORMER
Transmission
TERMINAL-BLOCK FOR TRANSMISSION
TERMINAL-BLOCK OF POWER SUPPLY
200
220
230
240
BACK
ACTIVE BYPASS
POWER ON/OFF
DUAL
CENTRAL
AHEAD
ENGAGED
GROUP
ACTIVE BYPASS
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
DUAL CENTRAL
12345678910
10 9 8 7 6 5 4 3 2 1
To adaptor's terminal-block
Centralized remote controller
Non-polar, two-wire cable
To adaptor's terminal-block
Power supply board box
BACK
ACTIVE
BYPASS
POWER ON/OFF
DUAL
CENTRAL
AHEAD
ENGAGED
GROUP
ACTIVE BYPASS
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
DUAL CENTRAL
12345678910
10 9 8 7 6 5 4 3 2 1
Dip switch SW17
Centralized remote controller
Power supply board
4-3 Connection method
(1) Connections in the power supply cord.
1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-wrap. Connect a sin­gle phase 200V AV (220, 230, 240V) to . As is the GND terminal, be sure to ground the earth wire.
E
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap. Use a Ω1.6 (AWG 14) or above two-wire cable for the transmission line. CAUTION : Never connect the power supply cord to the transmission terminal-block.
A N
(2) Connection method of centralized remote controller and power supply board.
1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable.
2. Wiring diagram
3. Be sure to set the maximum address number with the dip switch SW17 on the centralized remote controller.
56
Page 57
5. PROGRAM TIMER ADAPTER
Length : 2m(6' 7")
Length : 2m(6' 7")
Length : 2m(6' 7")
This adapter is needed when a program timer(PAC-815PT)or a centralized remote controller(PAC-805RC)is used.
Part No
5-1 Parts included
PAC-825AD
1 ADAPTER··························1P 2 3-core cable···························1P
3 3-core cable···························1P
Length : 2m(6' 7")
4 4-core cable···························1P
5 5-core cable···························1P
5-2 Connection method Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out the work.
(1) Connections in the adapter box
1. Connect the power supply cord to the terminal-block and fix it in-place with a tie-wrap. Connect a single phase 200V (220, 230, 240V) AV to .
E
As is the GND terminal, be sure to ground the earth wire.
A N
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap (when a centralized remote controller is being used). CAUTION : Never connect the power supply cord to the transmission terminal-block
Fig-1 Fig-2
TERMINAL-BLOCK FOR TRANSMISSION
Tie-wrap
Transmission cord
CN22
Dip switch
TRANS
CN1 CN21 CN51CN30CN42 CN50CN40
Fuse(5A)
TRANSFORMER
(AG)
SW1
ANE
POWER SUPPLY CORD
TERMINAL-BLOCK FOR POWER SUPPLY
Tie-wrap
CN22
TRANS
(B)
(W)
Transmission
Wiring has to be changed when 200V power supply is used.
200
SW1
T
(Y)
240
220
5A
A N E
POWER SUPPLY
57
Page 58
Fig.4
Fig.3
To program timer or centralized remote controller
Adaptor
200 240V AC
CN30
CN2 CN51
CN50
Indoor unit
Max. Length of each cable is 10m.
3-core cable ¡ 5-core cable ƒ
65
230
22
15
15
86 70
35
27
15
hole
40 80 40 27 18
Fixing screw hole
4- 5.5
95
220
22
35
120
12
30
200
2 2- 2.9
74 7
8
2. Set the address number (from SW1-1 to SW1-6) in the dip switch when a centralized remote controller is being used. The address is the control number of each unit in the centralized control system. As the address serves as a time-delay device as well, sequential starts (all units are trig­gered collectively by one single ON instruc­tion) must be set with different address num­bers (greater than O) for each adapter.
SW1
10 9 8 7 6 5 4 3 2 1
ON
Levers No. 1-6 can set the following address respectively with binary notations
Toggle
No.6ON32No.5ON16No.4ON8No.3ON4No.2ON2No.1ON
Address
1
(Ex. 1) 3=2+1
10 9 8 7 6 5 4 3 2 1
(2) Connection from adaptor
(Ex. 2) 9=8+1
10 9 8 7 6 5 4 3 2 1
ON
ON
(Ex. 3) 15=8+4+2+1
10 9 8 7 6 5 4 3 2 1
ON
58
Page 59
28˚C
26
˚C
8:00
Normal
operation
23:00
Setback
operation
8:00
Normal
operation
6. TIMER
Model Name
Product Name
(The PAC-SK65PT can only be used together with the PAC-825AD)
6-1 Program timer specifications
Product name Model name. Mounting method Clock system Clock accuracy
Display Program cycle
Timer setting unit Number. of set point
Time
Week
Program Timer PAC-SK65PT Wall mount Quarts clock
+ Liquid crystal display
Liquid crystal display 24 hours 30 minutes
48/day Minimum ON/OFF interval Power failure safeguard Rated power supply Set back function
6-2 Feature of program timer
(1) Daily timer function
Daily timer can be set in 30 minutes units for up to 24 hours. Each unit can be set for unit ON, unit OFF, or setback operation.
(2) Setback operation (PAC-SK65PT)
Set back operation is useful for reducing running costs e.g. At a hotel with a 24-hour system
8:00~23:00 Cooling operation with set temperature at 26°C
23:00~8:00 Setback operation with 2 degrees of setback As shown in the chart on the night, the set temperature rises 2 degrees automatically during the setback operation. When the setback operation ends, normal operation will begin.
(3) Weekly timer function
Daily timer function can apply to each day of the week.
5V DC Not provided
PAC-SK65PT
Program timer
50 second/month
— —
6-3. How to connect program timer (PAC-SK65PT)
(1) Install the program timer next to the remote controller the same way as the remote controller is installed. (2) Connect the program timer and the remote controller with a 6-wire cable as shown in the figure below
NOTE:While the program timer is connected to the remote controller, the 24hour
ON/OFF timer on the remote controller will not work.
2-wire cable
Centraized
Remote
controller
Connector CN1 Connector CN1
To indoor unit
6-wire cable
Program
timer
59
Page 60
SET/MOTOR
BACK AHEAD
BACK
AHEAD
ON OFF
ON SETBACK OFF
SMTWTF S
MITSUBISHI ELECTRIC
SET MONITOR
TODAY
CLOCK
WEEKLY TIMER
DAILY TIMER
Mode display
Current time
display
Current day display
Weekly timer
display
Day timer display
NOTE : Display above is only an example.
6-4. Name and functions
(PAC-SK65PT)
MODE selector button : Used to select \MONITOR" or "SET" mode.
"MONITOR" : Indicates the current timer setting. All buttons except
SET/MONITOR will not work.This is the normal status.
"SET" : "SET" is used to set the time, change the day of the week, and
program the daily and weekly timer.
Clock adjustment button : Used to adjust the current time.Press
AHEAD button to advance the time. Each time the button is pressed the time advances by 1 minute. Pressing contin­uously advances 1 minute in a 0.5 sec­ond interval. When the lower digit of minute becomes 0 the indication advances in 10 minutes unit. BACK button is used for reversing the time. Each time the button is pressed the time reverses by 1 minute. Pressing continu­ously reverses the time by 1 minute in a
0.5 second interval. When the lower digit of minute becomes 0 the indication reverses in 10 minutes unit.
Weekday setting button : Used to set the day of week.
Pressing button changes the day.
Weekly timer button : Used to set the weekly timer.
Daily timer button : Used to set the timer settings in units of 30 minutes.
7. Drain pump (for PK-2.5FLA, PK-3FLA, PK-4FLSA)
Model Name PAC-SE89DM-E
HEAD OFFICE : MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI,CHIYODA-KU TOKYO 100-8310, JAPAN
© Copyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD. Distributed in Sep.2001. No. OC129 REVISED EDITION-A 870 Reprinted in May.2001. No. OC129 5 Issued in Nov.1999. No. OC129 300 Issued in Aug.1999. No. OC129 50 Issued in Mar.1999. No. OC129 50 Issued in Jun.1997. No. OC129 2420 Made in Japan
New publication, effective Sep. 2001 Specifications subject to change without notice
Loading...