Mitsubishi Electronics pha-a-kal, pka-a-ka User Manual

Air-Conditioners
PKA-A·KA PKA-A·KAL
INSTALLATION MANUAL
For safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing the air-conditioner unit.
Avant d’installer le climatiseur, lire attentivement ce manuel, ainsi que le manuel d’installation de l’appareil extérieur pour une utilisation sûre et correct.
MANUAL DE INSTALACIÓN
Para un uso correcto y seguro, lea detalladamente este manual y el manual de instalación de la unidad exterior antes de instalar la unidad de aire acondicionado.
FOR INSTALLER
POUR L’INSTALLATEUR
PARA EL INSTALADOR
English
Français
Español
Contents
1. Safety precautions .............................................................................................2
2. Installation location ............................................................................................3
3. Installing the indoor unit ....................................................................................3
4. Installing the refrigerant piping ..........................................................................7
1. Safety precautions
X Before installing the unit, make sure you read all the “Safety
precautions”.
X Please report to your supply authority or obtain their consent before
connecting this equipment to the power supply system.
Warning: Describes precautions that must be observed to prevent danger of injury or death to the user.
Caution: Describes precautions that must be observed to prevent damage to the unit.
Warning:
• Ask a dealer or an authorized technician to install the unit.
• For installation work, follow the instructions in the Installation Manual and
use tools and pipe components specifically made for use with refrigerant
specified in the outdoor unit installation manual.
• The unit must be installed according to the instructions in order to
minimize the risk of damage from earthquakes, typhoons, or strong winds.
An incorrectly installed unit may fall down and cause damage or injuries.
• The unit must be securely installed on a structure that can sustain its
weight.
• If the air conditioner is installed in a small room, measures must be taken
to prevent the refrigerant concentration in the room from exceeding the
safety limit in the event of refrigerant leakage. Should the refrigerant leak
and cause the concentration limit to be exceeded, hazards due to lack of
oxygen in the room may result.
5. Drainage piping work .........................................................................................8
6. Electrical work ...................................................................................................9
7. Test run ............................................................................................................12
8. Easy maintenance function [This function only for A-control] ..........................15
After installation work has been completed, explain the “Safety precautions,” use, and maintenance of the unit to the customer according to the information in the Operation Manual and perform the test run to ensure normal operation. Both the Installation Manual and Operation Manual must be given to the user for keeping. These manuals must be passed on to subsequent users.
: Indicates a part which must be grounded.
Warning:
Carefully read the labels affixed to the main unit.
• Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
• All electric work must be performed by a qualified technician according to local regulations and the instructions given in this manual.
• Use only specified cables for wiring.
• The terminal block cover panel of the unit must be firmly attached.
• Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them.
• The user should never attempt to repair the unit or transfer it to another location.
• After installation has been completed, check for refrigerant leaks. If refrigerant leaks into the room and comes into contact with the flame of a heater or portable cooking range, poisonous gases will be released.
1.1. Before installation (Environment)
Caution:
• Do not use the unit in an unusual environment. If the air conditioner is installed in areas exposed to steam, volatile oil (including machine oil), or sulfuric gas, areas exposed to high salt content such as the seaside, the performance can be significantly reduced and the internal parts can be damaged.
• Do not install the unit where combustible gases may leak, be produced, flow, or accumulate. If combustible gas accumulates around the unit, fire or explosion may result.
• Do not keep food, plants, caged pets, artwork, or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water.
1.2. Before installation or relocation
Caution:
• Be extremely careful when transporting the units. Two or more persons are needed to handle the unit as it weighs 20 kg, 44lbs or more. Do not grasp the packaging bands. Wear protective gloves as you can injure your hands on the fins or other parts.
• Be sure to safely dispose of the packaging materials. Packaging materials, such as nails and other metal or wooden parts may cause stabs or other injuries.
1.3. Before electric work
Caution:
• Be sure to install molded case circuit brakers. If not installed, electric shock may result.
• For the power lines, use standard cables of sufficient capacity. Otherwise, a short circuit, overheating, or fire may result.
• When installing the power lines, do not apply tension to the cables.
• When the room humidity exceeds 80% or when the drainpipe is clogged, water may drip from the indoor unit. Do not install the indoor unit where such dripping can cause damage.
• When installing the unit in a hospital or communications office, be prepared for noise and electronic interference. Inverters, home appliances, high-frequency medical equipment, and radio communications equipment can cause the air conditioner to malfunction or breakdown. The air conditioner may also affect medical equipment, disturbing medical care, and communications equipment, harming the screen display quality.
• Thermal insulation of the refrigerant pipe is necessary to prevent condensation. If the refrigerant pipe is not properly insulated, condensation will be formed.
• Place thermal insulation on the pipes to prevent condensation. If the drainpipe is installed incorrectly, water leakage and damage to the ceiling, floor, furniture, or other possessions may result.
• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all flare nuts to specification using a torque wrench. If tightened too much, the flare nut can break after an extended period.
• Be sure to ground the unit. If the unit is not properly grounded, electric shock may result.
• Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and molded case circuit breaker) with the specified capacity. If the circuit breaker capacity is larger than the specified capacity, breakdown or fire may result.
1.4. Before starting the test run
Caution:
• Turn on the main power switch more than 12 hours before starting operation. Starting operation just after turning on the power switch can severely damage the internal parts.
• Before starting operation, check that all panels, guards and other protective parts are correctly installed. Rotating, hot, or high voltage parts can cause injuries.
2
• Do not operate the air conditioner without the air filter set in place. If the air filter is not installed, dust may accumulate and breakdown may result.
• Do not touch any switch with wet hands. Electric shock may result.
• Do not touch the refrigerant pipes with bare hands during operation.
• After stopping operation, be sure to wait at least five minutes before turning off the main power switch. Otherwise, water leakage or breakdown may result.
2. Installation location
G
PKA-A·KA(L)
117 0
B
L
F
46-1/16
E
Fig. 2-1
3. Installing the indoor unit
1
4 5 6
7 8 9
0
TEMP.
ON/OFF
2 3
a b
Fig. 3-1
A
295
11-39/64
*
C
365
D
H
K
14-3/8
(mm) (inch)
2.1. Outline dimensions (Indoor unit) (Fig. 2-1)
Select a proper position allowing the following clearances for installation and maintenance.
PKA-A·KA(L)
(mm, inch)
ABCDE
Min. 100.5 Min. 22.4 Min. 48 Min. 250 Min. 220
Min. 3-61/64 Min. 7/8 Min. 1-52/64 Min. 9-27/32 Min. 8-21/32
F Air outlet: Do not place an obstacle within 1500 mm, 59-1/16 inch of the air outlet. G Floor surface
J
I
H Furnishing I When the projection dimension of a curtain rail or the like from the wall exceeds 60 mm,
2/23/64 inch extra distance should be taken because the fan air current may create a short cycle.
J 1800 mm,70-7/8 inch or greater from the floor surface (for high location mounting) K 108 mm, 4-1/4 inch or greater with left or rear left piping. L Minimum 7 mm, 9/32 inch.
3.1. Check the indoor unit accessories (Fig. 3-1)
The indoor unit should be supplied with the following accessories.
PART
NUMBER
1 2 3 4 5 6 7 8 9
0 a
b
ACCESSORY
Mount board 1 1 Tapping screw 4 × 25 Felt tape 2 2 L-shaped connection pipe 1 1 Charge nut 1 1 Wireless remote controller 1 Remocon holder 1 Alkali batteries (size AAA) 2 Tapping screw 3.5 × 16 2 Wired remote controller 1 Remote controller cable 1
Spacer 1 1
QUANTITY
PKA-A·KAL PKA-A·KA
77
LOCATION OF
SETTING
Fix at the back of the unit
Make use of packaging material
PKA-A·KA(L)
20-3/8
23-1/32
D
5/8
0
31/32 1-31/32 2-15/16
3-15/16
4-19/32 4-29/32
5-19/32
7-9/16
9-17/32
11
11-1/2
C
20-7/8
A
C
F
17-7/8
D
17-9/32
16-3/32
17-9/32
16-15/16
14-11/32
15-1/8
15-1/8
12-3/8
13-11/32
3.2. Installing the wall mounting fixture
3.2.1. Setting the wall mounting fixture and piping positions (Fig. 3-2)
X Using the wall mounting fixture, determine the unit’s installation position
B
1-1/4 1/2
and the locations of the piping holes to be drilled.
Warning:
Before drilling a hole in the wall, you must consult the building contractor.
PKA-A·KA(L)
A Mount board 1 B Indoor unit C Bottom left rear pipe hole (ø75-ø80 mm, 2-61/64~3-35/64 inch) D Bottom right rear pipe hole (ø75-ø80 mm, 2-61/64~3-35/64 inch) E Knockout hole for left rear hole (75 × 480) F Bolt hole (4-ø9 mm, 23/64 inch hole) G Center measurement hole (ø2.5 mm, 3/32 inch hole) H Tapping hole (75-ø5.1 mm, 13/64 inch hole)
7-7/16
A
4-11/32
E
2-3/8
0
13/32
0
3-15/16
13/32
2-1/8
2-3/8
4-11/32
G
(inch)
1/8
A
8-17/32
R1-15/32
12-3/8
13-11/32
15-1/8
14-11/32
13-3/4
15-1/8
16-3/32
17-7/8
17-9/32
17-9/32
17-11/16
18-5/16
23-1/32
D
2-1/8 31/32
0 1/2 1-15/32 2-15/32 3-7/16 4-1/8 5-3/32
6-9/16
8-17/32 9-1/32 10-13/32 11-1/2
12-5/32 12-1/4
I Hole centre J Align the scale with the line.
K
K Insert scale.
3.2.2. Drilling the piping hole (Fig. 3-3)
I
J
Fig. 3-2
B
E
A Sleeve B Hole C (Indoors) D Wall E (Outdoors)
X Use a core drill to make a hole of 75-80 mm, 2-61/64~3-5/32 inch diameter
in the wall in the piping direction, at the position shown in the diagram to the left.
X The hole should incline so that the outside opening is lower than the
inside opening.
X Insert a sleeve (with a 75 mm, 2-61/64 inch diameter and purchased
locally) through the hole.
Note: The purpose of the hole’s inclination is to promote drain flow.
Fig. 3-3
3
3. Installing the indoor unit
H
AA
D
D
PKA-A·KA(L)
F
A
D
C
C
E
I
Fig. 3-4
Fig. 3-5
B
Fig. 3-8
B
3.2.3. Installing the wall mounting fixture
X Since the indoor unit weighs near 21 kg, 46.3lbs, selection of the mounting
location requires thorough consideration. If the wall does not seem to be strong enough, reinforce it with boards or beams before installation.
X The mounting fixture must be secured at both ends and at the centre, if
possible. Never fix it at a single spot or in any nonsymetrical way.
(If possible, secure the fixture at all the positions marked with a bold arrow.)
Warning:
If possible, secure the fixture at all positions indicated with a bold arrow.
Caution:
• The unit body must be mounted horizontally.
• Fasten at the holes marked with S as shown by the arrows.
PKA-A·KA(L) (Fig. 3-4)
A Min. 90 mm, 3-35/64 inch B Min. 200 mm, 7-7/8 inch C Min. 70 mm, 2-3/4 inch
C
B
D Fixing screws (4 × 25) 2 E Level F Fasten a thread to the hole. G
Place the level against the horizontal reference line of the mount board and mount so that it is level. Hang a weight from the thread and align with
H Weight I Mount board 1
V
EPK of the mount board to permit leveling.
3.3. When embedding pipes into the wall (Fig. 3-5)
G
A
• The pipes are on the bottom left.
• When the cooling pipe, drain pipes internal/external connection lines etc are to be embedded into the wall in advance, the extruding pipes etc, may have to be bent and have their length modified to suit the unit.
• Use marking on the mount board as a reference when adjusting the length of the embedded cooling pipe.
• During construction, give the length of the extruding pipes etc some leeway.
A Mount board 1 B Reference marking for flare connection C Through hole D On-site piping
3.4. Preparing the indoor unit
* Check beforehand because the preparatory work will differ depending on the
exiting direction of the piping.
* When bending the piping, bend gradually while maintaining the base of the
piping exiting portion. (Abrupt bending will cause misshaping of the piping.)
PKA-A·KA(L) Attachment of L-shaped connection pipe 4 Right, left and rear piping (Fig. 3-6)
1. Remove the flare nut and cap of the indoor unit. (Gas pipe only)
2. Apply refrigerating machine oil to the flare sheet surface. (Preparation on
location)
3. Facing the direction in which the L-shaped connection pipe 4 will be removed,
make a quick connection to the indoor unit flare connection opening.
4. Tighten the flare nut using a double open-end wrench. (Fig. 3-9)
Tightening force: 68~82 N•m, 49~59ft lbs
5. Attach the charge nut 5 to the liquid pipe side joint portion, and check for
leakage of the L-shaped connection pipe 4 connection portion.
Remove the charge nut 5 after completion of the work. Tightening force: 34~42 N•m, 25~30ft lbs
6. Cover the flare connection portion with the pipe cover of the L-shaped
Fig. 3-7Fig. 3-6
A
E
Fig. 3-10Fig. 3-9
connection pipe 4 so that it is not exposed. (Fig. 3-10)
A L-shaped connection pipe 4 B Cut-off position (Straight pipe portion) C Tightening direction D Cover with pipe cover E Cover the flare nut connection portion with the pipe cover.
Lower piping (Fig. 3-7)
1. Cut L-shaped connection pipe 4 at the position indicated in (Fig. 3-8).
2. Insert the flare nut that was removed earlier onto the straight pipe side of the cut
L-shaped connection pipe 4 and then flare the end of the pipe.
3. Remove the flare nut and cap of the indoor unit. (Gas pipe only)
4. Apply refrigerating machine oil to the flare sheet surface. (Preparation on
location)
5. Quickly connect the L-shaped connection pipe 4 that has been processed as
described in part 2) to the indoor unit flare connection opening.
6. Tighten the flare nut using a double open-end wrench. (Fig. 3-9)
Tightening force: 68~82 N•m, 49~59ft lbs
7. Attach the charge nut 5 to the liquid pipe side joint portion, and check for
leakage of the L-shaped connection pipe 4 connection portion.
Remove the charge nut 5 after completion of the work. Tightening force: 34~42 N•m, 25~30ft lbs
8. Cover the flare connection portion with the pipe cover of the L-shaped
connection pipe 4 so that it is not exposed. (Fig. 3-10)
4
3. Installing the indoor unit
E
A
Leakage check of the L-shaped connection pipe connection portion
1. Attach the charge nut 5 to the liquid pipe side joint portion. Tightening force: 34~42 N•m, 25~30ft lbs
2. Pressurize by filling with nitrogen gas from the charge nut. Do not pressurize to the current constant pressure all at once. Pressurize
gradually.
1) Pressurize to 0.5MPa, 73PSIB wait five minutes, and make sure the pressure does not decrease.
2) Pressurize to 1.5MPa, 218PSIB wait five minutes, and make sure the pressure does not decrease.
3) Pressurize to 4.15MPa, 606PSIB and measure the surrounding temperature and refrigerant pressure.
3. If the specified pressure holds for about one day and does not decrease, the pipes have passed the test and there are no leaks.
• If the surrounding temperature changes by 33.8°F, the pressure will change by
about 0.01MPa, 1.5PSIB. Make the necessary corrections.
4. If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the source of the gas leak.
C
D
A
B
Fig. 3-11
)
1
)
2
Extraction and processing of the piping and wiring (Fig. 3-11)
1. Connection of indoor/outdoor wiring See page. 9.
2. Wrap the felt tape 3 in the range of the refrigerant piping and drain hose which will be housed within the piping space of the indoor unit.
• Wrap the felt tape 3 securely from the base for each of the refrigerant piping
and the drain hose.
• Overlap the felt tape 3 at one-half of the tape width.
• Fasten the end portion of the wrapping with vinyl tape.
A Liquid pipe B Gas pipe C Indoor/outdoor connection cable D Drain hose E Felt tape 3
3. Be careful that the drain hose is not raised, and that contact is not made with the indoor unit box body. Do not pull the drain hose forcefully because it might come out.
Rear, right and lower piping (Fig. 3-12)
1) Be careful that the drain hose is not raised, and that contact is not made with
the indoor unit box body. Arrange the drain hose at the underside of the piping and wrap it with felt
B
Fig. 3-12
tape 3.
2) Securely wrap the felt tape 3 starting from the base. (Overlap the felt tape at
one-half of the tape width.)
A Cut off for right piping. B Cut off for lower piping.
Left and left rear piping (Fig. 3-13)
4. Drain hose replacement See 5. Drainage piping work
Be sure to replace the drain hose and the drain cap for the left and rear left
piping. Dripping may occur if you forget to install or fail to replace these parts.
C Drain cap
1) Be careful that the drain hose is not raised, and that contact is not made with
the indoor unit box body.
2) Securely wrap the felt tape 3 starting from the base. (Overlap the felt tape at
C
one-half of the tape width.)
3) Fasten the end portion of the felt tape 3 with vinyl tape.
D Cut off for left piping.
)
1
)
2
D
)
3
Fig. 3-13
5
D
3. Installing the indoor unit
B
B
PKA-A·KA(L)
C
C
3.5. Mounting the indoor unit
1. Affix the mount board 1 to the wall.
2. Hang the indoor unit on the hook positioned on the upper part of the mount board.
Rear, right and lower piping (Fig. 3-14)
3. While inserting the refrigerant piping and drain hose into the wall penetration
A
Fig. 3-14
C
D
A
Fig. 3-15
B
A
hole (penetration sleeve), hang the top of the indoor unit to the mount board 1.
4. Move the indoor unit to the left and right, and verify that the indoor unit is hung securely.
5. Fasten by pushing the bottom part of the indoor unit onto the mount board 1. (Fig. 3-15)
* Check that the knobs on the bottom of the indoor unit are securely hooked into
the mount board 1.
6. After installation, be sure to check that the indoor unit is installed level.
A Mount board 1 B Indoor unit C Hook D square hole
Left and left rear piping (Fig. 3-16)
3. While inserting the drain hose into the wall penetration hole (penetration sleeve), hang the top of the indoor unit to the mount board 1.
Giving consideration to the piping storage, move the unit all the way to the left
side, then cut part of the packaging carton and wrap into a cylindrical form as illustrated in the diagram. Hook this to the rear surface rib as a spacer, and raise the indoor unit.
4. Connect the refrigerant piping with the site-side refrigerant piping.
5. Fasten by pushing the bottom part of the indoor unit onto the mount board 1.
* Check that the knobs on the bottom of the indoor unit are securely hooked into
the mount board 1.
6. After installation, be sure to check that the indoor unit is installed level.
A Indoor unit B Packaging carton C Cut off D Wrap into a cylindrical form E Fasten with tape
E
Fig. 3-16
6
4. Installing the refrigerant piping
A
45±2°
B
(inch)
C
øA
90°±0.5°
R1-64~R1/32
D
Fig. 4-1
4.1. Precautions
4.1.1. For devices that use R410A refrigerant
• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil applied to the flared sections.
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses specified in the table to the below. Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sulfuric compounds, oxidants, debris, or dust.
Warning: When installing or moving the air conditioner, use only the specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it with any other refrigerant and do not allow air to remain in the lines. Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards.
Liquid pipe ø9.52 mm, 3/8 inch thickness 0.8 mm, 1/32 inch
Gas pipe ø15.88 mm, 5/8 inch thickness 1.0 mm, 3/64 inch
• Do not use pipes thinner than those specified above.
A24, A30, A36
4.2. Connecting pipes (Fig. 4-1)
• When commercially available copper pipes are used, wrap liquid and gas pipes with commercially available insulation materials (heat-resistant to 100 °C, 212 °F or more, thickness of 12 mm, 1/2 inch or more). The indoor parts of the drain pipe should be wrapped with polyethylene foam
• insulation materials (specific gravity of 0.03, thickness of 9 mm, 23/64 inch or more).
• Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut.
• Use two wrenches to tighten piping connections.
• Use refrigerant piping insulation provided to insulate indoor unit connections. Insulate carefully.
A Flare cutting dimensions
Copper pipe O.D.
(mm, inch) ø9.52, 3/8” 12.8 - 13.2, 1/2-33/64
ø15.88, 5/8” 19.3 - 19.7, 49/64-25/32
Flare dimensions
øA dimensions (mm, inch)
B Flare nut tightening torque
Copper pipe O.D.
(mm, inch)
ø9.52, 3/8” 22, 7/8 34 - 42, 25-30
ø15.88, 5/8” 29, 1-9/64 68 - 82, 49-59
Flare nut O.D.
(mm, inch)
Tightening torque
(N·m, ft·lbs)
C Apply refrigerating machine oil over the entire flare seat surface. D Use correct flare nuts meeting the pipe size of the outdoor unit.
4.3. Positioning refrigerant and drain piping (Fig. 4-2)
PKA-A·KA(L)
A Gas pipe * Indicates the condition with accessories mounted. B Liquid pipe C Drain hose D Left-side piping knockout hole E Right-side piping knockout hole F Lower piping knockout hole G Mount board 1
PKA-A·KA(L)
2-5/8
3-1/325/16
2-9/16
PKA-A·KA(L)
(inch)
14-3/8
D
2-9/16
3-1/32
3-7/16
46-1/16
17-15/32 (A)* 4-27/32
18-31/32 (B)
23-1/32 (C)
45-15/32
FF
3-1/32
3-7/16 2-51/6413/32
6-1/16 5-9/32
2-9/16
11-5/8 3/16
2-5/8
2-9/16
G
3-1/32
5/16
E
Fig. 4-2
A
B
Fig. 4-3
C
B
A
D
4.4. Refrigerant piping (Fig. 4-3)
Indoor unit
1. Remove the flare nut and cap of the indoor unit.
2. Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil
(available from your local supplier) to the flare sheet surface.
3. Quickly connect the on site cooling pipes to the unit.
4. Wrap the pipe cover that is attached to the gas pipe and make sure that the
connection join is not visible.
5. Wrap the pipe cover of the unit’s liquid pipe and make sure that it covers the
insulation material of the on site liquid pipe.
6. The portion where the insulation material is joined is sealed by taping.
A Site-side refrigerant piping B Unit side refrigerant piping
4.4.1. Storing in the piping space of the unit (Fig. 4-4)
1. Wrap the supplied felt tape in the range of the refrigerant piping which will be
housed within the piping space of the unit to prevent dripping.
2. Overlap the felt tape at one-half of the tape width.
3. Fasten the end portion of the wrapping with vinyl tape, etc.
A Gas pipe B Liquid pipe C Indoor/outdoor connection cable D Felt tape 3
Fig. 4-4
7
5. Drainage piping work
A
E
A
C
G
C
H
Fig. 5-1
1
3
A
I
B
2
4
5.1. Drainage piping work (Fig. 5-1)
• Drain pipes should have an inclination of 1/100 or more.
• For extension of the drain pipe, use a soft hose (inner dia. 15 mm, 19/32 inch)
D
E
C
F
J
K
a
b
B
available on the market or hard vinyl chloride pipe (VP-16 mm, 5/8 inch/O.D. ø22 mm, ø55/64 inch PVC TUBE). Make sure that there is no water leakage from the connections.
• Do not put the drain piping directly in a drainage ditch where sulphuric gas may be generated.
• When piping has been completed, check that water flows from the end of the drain pipe.
Caution: The drain pipe should be installed according to this Installation Manual to ensure correct drainage. Thermal insulation of the drain pipes is necessary to prevent condensation. If the drain pipes are not properly installed and insulated, condensation may drip on the ceiling, floor or other possessions.
A Inclined downwards
B Must be lower than outlet point
C Water leakage
D Trapped drainage
E Air
F Wavy
G The end of drain pipe is under water.
H Drainage ditch
I 5 cm or less between the end of drain pipe and the ground.
J Drain hose
K Soft PVC hose (Inside diameter ø15 mm, 19/32 inch)
or Hard PVC pipe (VP-16 mm, 5/8 inch) * Bond with PVC type adhesive
Preparing left and left rear piping (Fig. 5-2)
1 Remove the drain cap.
A
Fig. 5-2
D
C
B
A
Fig. 5-3
• Remove the drain cap by holding the bit that sticks out at the end of the pipe and
pulling.
A Drain cap
2 Remove the drain hose.
• Remove the drain hose by holding on to the base of the hose a (shown by
arrow) and pulling towards yourself b.
3 Insert the drain cap.
• Insert a screwdriver etc into the hole at the end of the pipe and be sure to push
to the base of the drain cap.
4 Insert the drain hose.
• Push the drain hose until it is at the base of the drain box connection outlet.
• Please make sure the drain hose hook is fastened properly over the extruding
drain box connection outlet.
B Hooks
¡ Storing in the piping space of the indoor unit (Fig. 5-3)
* When the drain hose will be routed indoors, be sure to wrap it with commercially
available insulation.
* Gather the drain hose and the refrigerant piping together and wrap them with the
supplied felt tape 3.
* Overlap the felt tape 3 at one-half of the tape width. * Fasten the end portion of the wrapping with vinyl tape, etc.
A Gas pipe
B Liquid pipe
C Drain hose
D Indoor/outdoor connection wiring
E Felt tape 3
¡ Check of drainage (Fig. 5-4)
1. Open the front grille and remove the filter.
2. Facing the fins of the heat exchanger, slowly fill with water.
3. After the drainage check, attach the filter and close the grille.
Fig. 5-4
8
6. Electrical work
PKA-A·KA(L)
J
2-11/64 inch
15/32 inch
6.1. Indoor unit
PKA-A·KA(L) (Fig. 6-1)
Connection can be made without removing the front panel.
1. Open the front grille, remove the screw (1 piece), and remove the electrical parts cover.
2. Securely connect each wire to the terminal board.
B
* In consideration of servicing, provide extra length for each of the wires. * Take care when using strand wires, because beards may cause the wiring to
short out.
3. Install the parts that were removed back to their original condition.
A Electrical box cover B Fixing screw D Ground wire connection portion E Remote control terminal board: (only for PKA-A·KA) 1 and 2, do not have polarity F Indoor/outdoor connection terminal board: S1, S2, and S3, have polarity G Lead H Terminal screw I Ground wire: Connect the ground wire in the direction illustrated in the diagram. J Remote control cord K Indoor/outdoor connection cord L Conduit plate M Bush (purchased locally) N Lock nut (purchased locally) O Connector (purchased locally) P Conduit (purchased locally)
15/32 inch
2-11/64 inch
K
D
A
F
E
K
E
I
J
G
H
M
N
H
L
F
D
O
P
Fig. 6-1
6.1.1. Indoor unit power supplied from outdoor unit (A-control application)
The following connection patterns are available. The outdoor unit power supply patterns vary on models.
1:1 System
C
L1
AB
L2
GR
S1
S2
S3
D
G
* Affix a label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Simultaneous twin system
C
L1
AB
L2
GR
S1
S2
S3
D
E
F
S1
S2
S3
1 2
FF
S1
S1
S2
S2
S3
S3
A Outdoor unit power supply B Wiring circuit breaker or isolating switch C Outdoor unit D Indoor unit/outdoor unit connecting cords E Wired remote controller (Only for PKA-A·KA) F Indoor unit G Indoor unit earth
A Outdoor unit power supply B Wiring circuit breaker or isolating switch C Outdoor unit D Indoor unit/outdoor unit connecting cords E Wired remote controller (Only for PKA-A·KA) F Indoor unit G Indoor unit earth
1
E
1
2
2
* Affix a label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.
GG
9
6. Electrical work
D
Indoor unit model PKA-A·KA(L) Minimum circuit ampacity 1A Maximum rating of overcurrent protective device 15A
Indoor unit-Outdoor unit *1 3 × AWG16 (Polar) Indoor unit earth 1 × Min. AWG16
Wiring
× size
Wire No.
Remote controller-Indoor unit *2 2 × AWG22 (Non-polar) Indoor unit-Outdoor unit S1-S2 *3 AC 208/230 V Indoor unit-Outdoor unit S2-S3 *3 DC24 V
rating
Circuit
Remote controller-Indoor unit *3 DC12 V
*1. Max. 50 m, 165 ft *2. The 3 m, 10 ft wire is attached in the remote controller accessory. Max. 500 m, 1640 ft <Only for PKA-A·KA> *3. The figures are NOT always against the ground. S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulataed by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Use copper supply wires.
3. Use wires rated 300V or more for the power supply cords and the indoor unit/outdoor unit connecting cords.
4. Install an earth longer than other cords.
A
1-3/16
3-9/32
B
1-37/64
1-3/16
1-3/16
D
A
C
E
6.2. Remote controller
6.2.1. For wired remote controller
(inch)
1) Installing procedures
(1) Select an installing position for the remote controller. (Fig. 6-2) The temperature sensors are located on both remote controller and indoor unit.
X Procure the following parts locally:
Two piece switch box Thin copper conduit tube Lock nuts and bushings
F
C
4-23/32
H
I
G
A Remote controller profile B Required clearances surrounding the remote controller C Installation pitch
(2) Seal the service entrance for the remote controller cord with putty to prevent
possible invasion of dew drops, water, cockroaches or worms. (Fig. 6-3)
Fig. 6-2
B-1. B-2.
B
H
I
A
I
Fig. 6-3
H
J
A For installation in the switch box: B For direct installation on the wall select one of the following:
• Prepare a hole through the wall to pass the remote controller cord (in order to run the remote controller cord from the back), then seal the hole with putty.
• Run the remote controller cord through the cut-out upper case, then seal the cut­out notch with putty similarly as above.
B-1. To lead the remote controller cord from the back of the controller: B-2. To run the remote controller cord through the upper portion:
(3) For direct installation on the wall
C Wall D Conduit E Lock nut F Bushing G Switch box H Remote controller cord I Seal with putty J Wood screw
2) Connecting procedures (Fig. 6-4)
1 Connect the remote controller cord to the terminal block.
A To TB5 on the indoor unit B TB6 (No polarity)
3) Two remote controllers setting
If two remote controllers are connected, set one to “Main” and the other to “Sub”. For setting procedures, refer to “Function selection of remote controller” in the operation manual for the indoor unit.
Fig. 6-4
AB TB6
B
6.2.2. For wireless remote controller
1) Installation area
• Area in which the remote controller is not exposed to direct sunshine.
• Area in which there is no nearby heating source.
• Area in which the remote controller is not exposed to cold (or hot) winds.
• Area in which the remote controller can be operated easily.
A
• Area in which the remote controller is beyond the reach of children.
2) Installation method (Fig. 6-5)
1 Attach the remote controller holder to the desired location using two tapping
3
screws.
2 Place the lower end of the controller into the holder.
A Remote controller B Wall C Display panel D Receiver
• The signal can travel up to approximately 7 meters, 23 ft (in a straight line) within 45 degrees to both right and left of the center line of the receiver.
B
2
A
1
C
2,4
ON/OFF TEMP
FAN
VANE
MODE
LOUVER
CHECK
TEST RUN
RESETSET CLOCK
AUTO STOP
AUTO START
h
min
3) Setting (Fig. 6-6)
1 Insert batteries.
Fig. 6-6
Fig. 6-5
2 Press the SET button with something sharp at the end.
blinks and Model No. is lighted.
3 Press the temp
button to set the Model No.
4 Press the SET button with something sharp at the end.
and Model No. are lighted for three seconds, then turned off.
PKA (A24, A30, A36)
heat pump models 002
cooling only models 034
10
6. Electrical work
1,4
F E
G
TEMP.
MENU
BACK DAY
MONITOR/SET
PAR-21MAA
CLOCK
ON/OFF
OPERATION
DC
ON/OFF TEMP
FAN
VANE
MODE
LOUVER
CHECK
TEST RUN
RESETSET CLOCK
Fig. 6-7
ON/OFF
FILTER
CHECK
TEST
CLEAR
Fig. 6-8
A B
AUTO STOP
AUTO START
h
min
A
3
2
Mode number Setting number Refrigerant address Unit number
4) Assigning a remote controller to each unit (Fig. 6-7)
Each unit can be operated only by the assigned remote controller. Make sure each pair of an indoor unit PC board and a remote controller is assigned to the same pair No.
5) Wireless remote controller pair number setting operation
1 Press the SET button with something sharp at the end. Start this operation from the status of remote controller display turned off.
blinks and Model No. is lighted.
2 Press the
min
button twice continuously.
Pair No. “0” blinks. 3 Press the temp
button to set the pair number you want to set.
4 Press the SET button with something sharp at the end. Set pair number is lighted for three seconds then turned off.
Pair No. of wireless remote controller
A
Indoor PC board
0 Factory setting 1 Cut J41 2 Cut J42
3-9 Cut J41, J42
6.3. Function settings
6.3.1 Function setting on the unit (Selecting the unit functions)
1) For wired remote controller (Fig. 6-8)
Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used. 1 Go to the function setting mode.
Switch OFF the remote controller. Press the A and B buttons simultaneously and hold them for at least 2
seconds. FUNCTION will start to flash.
2 Use the C button to set the refrigerant address (3) to 00. 3 Press D and [--] will start to flash in the unit number (4) display. 4 Use the C button to set the unit number (4) to 00. 5 Press the E MODE button to designate the refrigerant address/unit number. [--]
will flash in the mode number (1) display momentarily.
6 Press the F buttons to set the mode number (1) to 04. 7 Press the G button and the current set setting number (2) will flash.
Use the F button to switch the setting number in response to the power supply
voltage to be used. Power supply voltage 230 V : setting number = 1 208 V : setting number = 2 8 Press the MODE button E and mode and the setting number (1) and (2) will
change to being on constantly and the contents of the setting can be confirmed. 9 Press the FILTER A and TEST RUN B buttons simultaneously for at least two
seconds. The function selection screen will disappear momentarily and the air
conditioner OFF display will appear.
E
F
CHECK
ON/OFF TEMP
FAN
VANE
MODE
LOUVER
CHECK
TEST RUN
RESETSET CLOCK
AUTO STOP
AUTO START
h
min
C,D
A B
1
3
Fig. 6-9
CHECK
2
CHECKCHECK
4
CHECK
Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used. 1 Go to the function select mode
Press the
CHECK
button F twice continuously.
(Start this operation from the status of remote controller display turned off.)
CHECK
is lighted and “00” blinks. Press the temp toward the receiver of the indoor unit and press the
button C once to set “50”. Direct the wireless remote controller
h
button A.
2 Setting the unit number Press the temp wireless remote controller toward the receiver of the indoor unit and press the
button C and D to set the unit number “00”. Direct the
min
button B. 3 Selecting a mode Enter 04 to change the power voltage setting using the Direct the wireless remote controller toward the receiver of the indoor unit and
press the
h
button A.
C and D buttons.
Current setting number: 1 = 1 beep (one second) 2 = 2 beeps (one second each) 3 = 3 beeps (one second each) 4 Selecting the setting number
Use the (230 V). Direct the wireless remote controller toward the sensor of the indoor unit
and press the
C and D buttons to change the power voltage setting to 01
h
button A. 5 To select multiple functions continuously Repeat steps 3 and 4 to change multiple function settings continuously. 6 Complete function selection Direct the wireless remote controller toward the sensor of the indoor unit and press
button E.
the
Note: Whenever changes are made to the function settings after installation or maintenance, be sure to record the changes with a mark in the “Setting” column of the Function table.
2) For wireless remote controller (Fig. 6-9)
6.3.2 Function setting on the remote controller
Refer to the indoor unit operation manual.
11
6. Electrical work
Function table
Select unit number 00
Mode Settings Mode no. Setting no. Initial setting setting Power failure automatic recovery Not available
Available *1
01
Indoor temperature detecting Indoor unit operating average
Set by indoor unit’s remote controller 2
02
Remote controller’s internal sensor 3
LOSSNAY connectivity Not Supported
Supported (indoor unit is not equipped with outdoor-air intake) 2
03
Supported (indoor unit is equipped with outdoor-air intake) 3
Power voltage 230 V
208 V 2
04
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode Settings Mode no. Setting no. Initial setting setting Filter sign 100Hr
2500Hr 2
07
No filter sign indicator 3
Fan speed Silent
Standard
08
High ceiling 3
*1 When the power supply returns, the air conditioner will start 3 minutes later.
1 2 1
1
1
1
1
2
7. Test run
7.1. Before test run
X After completing installation and the wiring and piping of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply.
X Use a 500-volt megohmmeter to check that the resistance between the
power supply terminals and ground is at least 1.0 MΩ.
FCEDB
TEST RUN COOL, HEAT
BACK DAY
MONITOR/SET
PAR-21MAA
°F
°F
TEMP.
MENU
ON/OFF
CLOCK
OPERATION
SIMPLE
ON/OFF
FILTER
CHECK
CLEAR
TEST
A
A ON/OFF button B Test run display C Indoor temperature liquid
line temperature display
D ON/OFF lamp E Power display F Error code display
Test run remaining time
display
G Set temperature button H Mode selection button I Fan speed button M TEST button
MIHG
Fig. 7-1
A
ON/OFF TEMP
7
FAN
AUTO STOP
3,4
2
MODE
CHECK
TEST RUN
VANE
LOUVER
RESETSET CLOCK
AUTO START
h
min
5 6
Fig. 7-2
X Do not carry out this test on the control wiring (low voltage circuit)
terminals.
Warning: Do not use the air conditioner if the insulation resistance is less than 1.0 MΩ. Insulation resistance.
7.2. Test run
The following 3 methods are available.
7.2.1. Using wired remote controller (Fig. 7-1)
1 Turn on the power at least 12 hours before the test run. 2 Press the [TEST] button twice. “TEST RUN” liquid crystal display 3 Press the [Mode selection] button. Make sure that wind is blown out. 4 Press the [Mode selection] button and switch to the cooling (or heating) mode.
Make sure that cold (or warm) wind is blown out.
5 Press the [Fan speed] button. Make sure that the wind speed is switched. 6 Check operation of the outdoor unit fan. 7 Release test run by pressing the [ON/OFF] button. Stop 8 Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an
error occurs can be registered in the remote controller. The telephone number
will be displayed when an error occurs. For registration procedures, refer to the
operation manual for the indoor unit.
7.2.2. Using wireless remote controller (Fig. 7-2)
1 Turn on the power to the unit at least 12 hours before the test run. 2 Press the
(Start this operation from the status of remote controller display turned off.)
A and current operation mode are displayed.
3 Press the
cool air is blown out from the unit. 4 Press the
warm air is blown out from the unit.
5 Press the 6 Press the
7 Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver while following
steps 2 to 7.
• It is not possible to run the in FAN, DRY or AUTO mode.
TEST RUN
button twice continuously.
MODE
button to activate
MODE
button to activate
FAN
button and check whether fan speed changes.
VAN E
button and check whether the auto vane operates properly.
COOL
mode, then check whether
HEAT
mode, then check whether
12
7. Test run
F
B
ED
ERROR CODE
C
TEMP.
MENU
MONITOR/SET
BACK DAY
PAR-21MAA
CLOCK
B
ON/OFF
ERROR CODE
ERROR CODE
OPERATION
ON/OFF
FILTER
CHECK
TEST
CLEAR
A
4
MODE
CHECK
2
TEST RUN
E
Fig. 7-3
• Refer to the following tables for details on the check codes. (Wireless remote controller) [Output pattern A]
Beeper sounds
OPERATION INDICATOR lamp flash pattern
[Output pattern B]
Beeper sounds
OPERATION INDICATOR lamp flash pattern
Beep
Self-check starts (Start signal received)
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Beep Beep Beep Beep Beep Beep
1st2nd3
Number of flashes/beeps in pattern indicates the check code in the following table (i.e., n=5 for “P5”)
rd
Beep Beep Beep Beep Beep Beep Beep
Off
Self-check starts (Start signal received)
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates the check code in the following table (i.e., n=5 for “U2”)
A
CHECK
ON/OFF TEMP
FAN
VANE
LOUVER
RESETSET CLOCK
Fig. 7-4
1st2
B
AUTO STOP
AUTO START
h
3
min
th
n
On
0.5 sec.
nd3rd
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
7.2.3. Using SW4 in outdoor unit
Refer to the outdoor unit installation manual.
7.3. Self-check
7.3.1. Wired remote controller (Fig. 7-3)
1 Turn on the power. 2 Press the [CHECK] button twice. 3 Set refrigerant address with [TEMP] button if system control is used. 4 Press the [ON/OFF] button to stop the self-check.
A CHECK button B Refrigerant address C TEMP. button D IC: Indoor unit
OC: Outdoor unit
E Check code F Unit address
7.3.2. Wireless remote controller (Fig. 7-4)
1 Turn on the power. 2 Press the
(Start this operation from the status of remote controller display turned off.)
A B “00” begins to blink.
3 While pointing the remote controller toward the unit’s receiver, press the h
button. The check code will be indicated by the number of times that the buzzer sounds from the receiver section and the number of blinks of the operation lamp.
4 Press the ON/OFF button to stop the self-check.
0.5 sec.
CHECK
button twice.
begins to light.
CHECK
nd
1st2
Number of flashes/beeps in pattern indicates the check code in the following table
th
n
On
· · · Repeated
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates the check code in the following table
1st2
nd
· · · Repeated
[Output pattern A] Errors detected by indoor unit
Wireless remote controller
Wired remote
controller
Beeper sounds/OPERATION
INDICATOR lamp flashes
Check code
Check code (Number of times)
1 P1 Intake sensor error 2 P2, P9 Pipe (Liquid or 2-phase pipe) sensor error 3 E6, E7 Indoor/outdoor unit communication error 4 P4 Float switch connector CN4F open.
5
P5 Drain pump error
PA Forced compressor error 6 P6 Freezing/Overheating safeguard operation 7 EE Communication error between indoor and outdoor units 8 P8 Pipe temperature error 9 E4 Remote controller signal receiving error
10 – 11 – 12 Fb Indoor unit control system error (memory error, etc.)
No sound – – – – No corresponding
Symptom Remark
13
7. Test run
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes
(Number of times)
1 E9 Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit) 2 UP Compressor overcurrent interruption 3 U3, U4 Open/short of outdoor unit thermistors 4 UF Compressor overcurrent interruption (When compressor locked) 5 U2 Abnormal high discharging temperature/49C worked/insufficient refrigerant 6 U1, Ud Abnormal high pressure (63H worked)/Overheating safeguard operation 7 U5 Abnormal temperature of heat sink 8 U8 Outdoor unit fan safeguard stop 9 U6 Compressor overcurrent interruption/Abnormal of power module
10 U7 Abnormality of super heat due to low discharge temperature
11 U9, UH Abnormality such as overvoltage or voltage shortage and abnormal
12 – 13 – 14 Others Other errors (Refer to the technical manual for the outdoor unit.)
*1 If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not come
on, there are no error records.
*2 If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm the self-check start signal was received, the
specified refrigerant address is incorrect.
• On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit. Blink of operation lamp
• On wired remote controller Check code displayed in the LCD.
• If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
Wired remote controller LED 1, 2 (PCB in outdoor unit)
PLEASE WAIT
PLEASE WAIT Error code
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).
On the wireless remote controller with condition above, following phenomena takes place.
• No signals from the remote controller are accepted.
• OPE lamp is blinking.
• The buzzer makes a short pipng sound.
Wired remote
controller
Check code
For about 2 minutes following power-on
After about 2 minutes has expired following power-on
Symptom Remark
synchronous signal to main circuit/Current sensor error
Symptom
After LED 1, 2 are lighted, LED 2 is turned off, then only LED 1 is lighted. (Correct operation)
Only LED 1 is lighted. LED 1, 2 blink.
Only LED 1 is lighted. LED 1 blinks twice, LED 2 blinks once.
For details, check the LED display of the outdoor controller board.
Cause
• For about 2 minutes following power-on, operation of the remote controller is not possible due to system start-up. (Correct operation)
• Connector for the outdoor unit’s protection device is not connected.
• Reverse or open phase wiring for the outdoor unit’s power terminal block (L1, L2, GR)
• Incorrect wiring between indoor and outdoor units (incorrect polarity of S1, S2, S3)
• Remote controller wire short
Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED 1, 2, 3) provided on the indoor controller, refer to the following table.
LED 1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED is always lit. LED 2 (power for remote controller) Indicates whether power is supplied to the remote controller. This LED lights only in the case
LED 3 (communication between indoor and outdoor units only A-control) Indicates state of communication between the indoor and outdoor units. Make sure that this
of the indoor unit which is connected to the outdoor unit refrigerant address “0”.
LED is always blinking.
14