Mitsubishi PFFY-P-VLRMM-E Installation Manual

Page 1
Air-Conditioners For Building Application INDOOR UNIT
PFFY-P-VLRMM-E
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d’une utilisation correcte.
GB
D
F
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il condizionatore d’aria.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert.
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado.
E°XEIPI¢IO O¢H°IøN E°KATA™TA™H™
°И· ·ЫК¿ПВИ· О·И ЫˆЫЩ‹ ¯Ъ‹ЫЛ, ·Ъ·О·ПВ›ЫЩВ ‰И·‚¿ЫВЩВ ЪФЫВ¯ЩИО¿ ·˘Щfi ЩФ ВБ¯ВИЪ›‰ИФ ВБО·Щ¿ЫЩ·ЫЛ˜ ЪИУ ·Ъ¯›ЫВЩВ ЩЛУ ВБО·Щ¿ЫЩ·ЫЛ ЩЛ˜ МФУ¿‰·˜ ОПИМ·ЩИЫМФ‡.
РУКОВОДСТВО ПО УСТАНОВКЕ
Для осторожного и правильного использования прибора необходимо тщательно ознакомиться с данным руководством по установке до выполнения установки кондиционера.
MONTAJ ELK‹TABI
Emniyetli ve do¤ru biçimde nas›l kullan›laca¤›n› ö¤renmek için lütfen klima cihaz›n› monte etmeden önce bu elkitab›n› dikkatle okuyunuz.
E
I
NL
P
GR
RU
TR
CZ
SV
HG
PO
SL
Page 2
3
630
(F) 205
(E)
170 300
3.1
[Fig. 3.1.1]
<Upward blowing type>
B
For PFFY-P-VLRMM-E (mm)
(C) (D)
(D) (C) (D)
A
639
Model name
20 · 25 660 More than 240 32 · 40 780 More than 240 50 · 63 1030 More than 240
A Floor B Ceiling C Piping space D Electrical part service space
CD
4
[Fig. 4.1.1]
B
A
C
A Floor hole for fixing B Level adjusting screws (supplied) C Screw plate (supplied)
[Fig. 4.1.2]
4.1
For fixing on the floor
<Viewed from bottom of the unit>
(F) 205
(E)
Model name
20 · 25 1050 640 32 · 40 1170 760 50 · 63 1410 1000
[Fig. 4.1.3]
220
114
(E) (F)
For fixing on the wall
<Viewed from front of the unit>
4.2
PFFY-VLRMM-E
L
2
Z
A
XW
A Floor hole for fixing
Page 3
5
[Fig. 5.1.1]
5.1
A B
C
D
E
F
6
[Fig. 6.1.1] [Fig. 6.1.3]
A Cut here B Remove brazed cap
G
6.1
[Fig. 6.1.2]
A
A Cool by a wet cloth
A Refrigerant pipe brazing (for gas): LP B Refrigerant pipe brazing (for liquid): HP C Main drain pan D Sub drain pan E Hose (accessory) (External diameter ø 27 (end ø 20)) F Air filter G Electrical part box
C
A A
B
A Thermal insulation B Pull out insulation C Wrap with damp cloth D Return to original position E Ensure that there is no gap here F Wrap with insulating tape
E
D
F
6.2
[Fig. 6.2.1]
7
[Fig. 7.1.1]
AB
CCCCCCC
A
B
C
D
E
A Indoor unit B Strainer (accessory) C Sub drain pan D Hose band (accessory) E Drain hose (accessory)
7.1
DE
A Switch 16 A B Overcurrent protection 16 A C Indoor unit D Total operating current be less than 16 A E Pull box
3
Page 4
7
N
L
LN
S
M2
M1
2
1
M1 M2
C
G
F
A
B
E
D
D
A
S
M2
M1
B
1
2
L
N
DC24~30V
(A, B)
12
C
[Fig. 7.2.1]
B
M1M2 21 21
TB3
SM1M2 SM1M2
TB5 TB15 TB5 TB15
AA
7.2
[Fig. 7.2.2]
A Terminal block for indoor trans-
B Terminal block for outdoor
CC
C Remote controller
[Fig. 7.2.3] [Fig. 7.2.4]
B
D
M2
M1
N
L
1
S
2
A
DC10~13V
C
AB 12
[Fig. 7.2.5]
*1
G
H
III
L1
L2
JJ
II
K
L3
J
JJ
G Outdoor unit
*2
H Earth
L4
I Indoor unit
R
J Remote controller K Non-polarized 2-wire
mission cable
transmission cable
TB3
M1M2
B
SM1M2 SM1M2
TB5 TB5
A Non-polarized B TB15 C Remote Controller D TB5
AA
CC
[Fig. 7.3.1] [Fig. 7.3.2]
C
B
A
C
D
E
A Control box B Cover C Screw D Knockout hole E Remove
[Fig. 7.3.4]
M2 SM1
B
4
C
A
D
E
A Terminal block B Round terminal C Shield wire D The earth wire from two cables are connected to-
E Insulation tape (To keep the earth wire of the
7.3
A
C
B
D
E
A Use PG bushing to keep the weight of the
cable and external force from being ap­plied to the power supply terminal connec­tor. Use a cable tie to secure the cable.
B Power source wiring C Tensile force D Use ordinary bushing E Transmission wiring
gether to the S terminal. (Dead-end connection)
shielded cable from coming in contact with the transmission terminal)
[Fig. 7.3.3]
A Power source terminal block B Terminal block for indoor transmission C Terminal block for remote controller D To 1-phase power source E Transmission line DC 30 V F Terminal block for outdoor transmission line (TB3) G Transmission line to the remote controller, terminal block
for indoor unit and BC controller
7.4
[Fig. 7.4.1]
<Address board>
SW1
ON
CN828161
W254613G03
FP-AD-R
MADE IN JAPAN
1
JP1
3
2
1
SWCSWA
10
SW12
0
240V 220V
SW14
SW5
SW11
0
0
JP2
N0
10
1
N0
CN62
JP3
JP4
Page 5
Contents
1. Safety precautions ...................................................................................... 5
1.1. Before installation and electric work .......................................... 5
1.2. Precautions for devices that use R410A refrigerant .................. 5
1.3. Before getting installed .............................................................. 6
1.4. Before getting installed (moved) - electrical work ...................... 6
1.5. Before starting the test run ........................................................ 6
2. Indoor unit accessories ............................................................................... 6
3. Selecting an installation site ....................................................................... 6
3.1. Securing installation and service space .................................... 7
3.2. Combining indoor units with outdoor units ................................ 7
4.Installing the unit ............................................................................................ 7
4.1. Assembling the unit ................................................................... 7
4.2. Center of gravity and product weight ......................................... 7
1. Safety precautions
1.1. Before installation and electric work
s Before installing the unit, make sure you read all the “Safety
precautions”.
s The “Safety precautions” provide very important points re-
garding safety. Make sure you follow them.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
: Indicates that caution should be taken with rotating parts. (This symbol is
displayed on the main unit label.) <Color: yellow>
: Beware of electric shock (This symbol is displayed on the main unit label.)
<Color: yellow>
Warning:
Carefully read the labels affixed to the main unit.
Warning:
Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage, electric shock, or fire.
Install the air unit at a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down, resulting in injuries.
Use the specified cables for wiring. Make the connections securely so that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
Prepare for typhoons and other strong winds and earthquakes and in­stall the unit at the specified place.
- Improper installation may cause the unit to topple and result in injury.
Always use an air cleaner, humidifier, electric heater, and other accesso­ries specified by Mitsubishi Electric.
- Ask an authorized technician to install the accessories. Improper installation
by the user may result in water leakage, electric shock, or fire.
Never repair the unit. If the air conditioner must be repaired, consult the dealer.
- If the unit is repaired improperly, water leakage, electric shock, or fire may
result.
Do not touch the heat exchanger fins.
- Improper handling may result in injury.
When handling this product, always wear protective equipment. EG: Gloves, full arm protection namely boiler suit, and safety glasses.
- Improper handling may result in injury.
If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a flame, poisonous gases will
be released.
Install the air conditioner according to this Installation Manual.
- If the unit is installed improperly, water leakage, electric shock, or fire may
result.
5.Refrigerant pipe and drain pipe specifications ............................................... 7
5.1. Refrigerant pipe and drain pipe size .......................................... 7
6.Connecting refrigerant pipes and drain pipes ................................................ 8
6.1. Refrigerant piping work ............................................................. 8
6.2. Drain piping work ....................................................................... 8
7. Electrical wiring ........................................................................................... 8
7.1. Power supply wiring................................................................... 9
7.2. Connecting remote controller, indoor and outdoor transmission
cables ........................................................................................ 9
7.3. Connecting electrical wires ....................................................... 9
7.4. Selecting the external static pressure ..................................... 10
7.5. Setting addresses .................................................................... 10
7.6. Sensing room temperature with the built-in sensor in a remote
controller .................................................................................. 10
Have all electric work done by a licensed electrician according to “Elec­tric Facility Engineering Standard” and “Interior Wire Regulations”and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is performed im-
properly, electric shock and fire may result.
Keep the electric parts away from water (washing water etc.).
- It might result in electric shock, catching fire or smoke.
Securely install the outdoor unit terminal cover (panel).
- If the terminal cover (panel) is not installed properly, dust or water may enter
the outdoor unit and fire or electric shock may result.
When installing and moving the air conditioner to another site, do not charge the it with a refrigerant different from the refrigerant specified on the unit.
- If a different refrigerant or air is mixed with the original refrigerant, the refrig-
erant cycle may malfunction and the unit may be damaged.
If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to prevent the safety
limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
- If the air conditioner is installed improperly, water leakage, electric shock, or
fire may result.
After completing installation work, make sure that refrigerant gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or
other heat source, it may generate noxious gases.
Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted
and operated forcibly, or par ts other than those specified by Mitsubishi Elec­tric are used, fire or explosion may result.
To dispose of this product, consult your dealer.
Do not use a leak detection additive.
1.2. Precautions for devices that use R410A
refrigerant
Caution:
Do not use the existing refrigerant piping.
- The old refrigerant and refrigerator oil in the existing piping contains a large
amount of chlorine which may cause the refrigerator oil of the new unit to deteriorate.
Use refrigerant piping made of C1220 (Cu-DHP) phosphorus deoxidized copper as specified in the JIS H3300 “Copper and copper alloy seamless pipes and tubes”. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shav­ing particles, oils, moisture, or any other contaminant.
- Contaminants on the inside of the refrigerant piping may cause the refriger-
ant residual oil to deteriorate.
Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
- If dust, dir t, or water enters the refrigerant cycle, deterioration of the oil and
compressor trouble may result.
Use liquid refrigerant to fill the system.
- If gas refrigerant is used to seal the system, the composition of the refriger-
ant in the cylinder will change and performance may drop.
Do not use a refrigerant other than R410A.
- If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may
cause the refrigerator oil to deteriorate.
GB
D
F
E
INL
PGRRUTR
5
Page 6
Use a vacuum pump with a reverse flow check valve.
- The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate.
Do not use the following tools that are used with conventional refriger­ants. (Gauge manifold, charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment)
- If the conventional refrigerant and refrigerator oil are mixed in the R410A,
the refrigerant may deteriorated.
- If water is mixed in the R410A, the refrigerator oil may deteriorate.
- Since R410A does not contain any chlorine, gas leak detectors for conven-
tional refrigerants will not react to it.
Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.
Be especially careful when managing the tools.
- If dust, dir t, or water gets in the refrigerant cycle, the refrigerant may deterio-
rate.
1.3. Before getting installed
Caution:
GB
Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
Do not use the air conditioner where food, pets, plants, precision instru­ments, or artwork are kept.
- The quality of the food, etc. may deteriorate.
Do not use the air conditioner in special environments.
- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of
the air conditioner or damage its parts.
When installing the unit in a hospital, communication station, or similar
D
place, provide sufficient protection against noise.
- The inverter equipment, private power generator, high-frequency medical
equipment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air condi-
F
E
tioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80 % or when the drain pipe is clogged,
condensation may drip from the indoor unit. Perform collective drainage work together with the outdoor unit, as required.
The indoor models should be installed the ceiling over than 2.5 m from floor.
1.4. Before getting installed (moved) - elec-
INL
trical work
Caution:
Ground the unit.
- Do not connect the ground wire to gas or water pipes, lightning rods, or
telephone ground lines. Improper grounding may result in electric shock.
Install the power cable so that tension is not applied to the cable.
- Tension may cause the cable to break and generate heat and cause a fire.
Install an leak circuit breaker, as required.
- If an leak circuit breaker is not installed, electric shock may result.
Use power line cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
Use only a circuit breaker and fuse of the specified capacity.
- A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit failure or fire.
Do not wash the air conditioner units.
- Washing them may cause an electric shock.
Be careful that the installation base is not damaged by long use.
- If the damage is left uncorrected, the unit may fall and cause personal injury or property damage.
Install the drain piping according to this Installation Manual to ensure proper drainage. Wrap thermal insulation around the pipes to prevent condensation.
- Improper drain piping may cause water leakage and damage to furniture
and other possessions.
Be very careful about product transportation.
- Only one person should not carr y the product if it weighs more than 20 kg.
- Some products use PP bands for packaging. Do not use any PP bands for a
means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transpor ting the outdoor unit, suspend it at the specified positions on
the unit base. Also support the outdoor unit at four points so that it cannot slip sideways.
Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts, may cause
stabs or other injuries.
- Tear apart and throw away plastic packaging bags so that children will not
play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
1.5. Before starting the test run
Caution:
Turn on the power at least 12 hours before starting operation.
- Star ting operation immediately after turning on the main power switch can
result in severe damage to internal parts. Keep the power switch turned on during the operational season.
Do not touch the switches with wet fingers.
- Touching a switch with wet fingers can cause electric shock.
Do not touch the refrigerant pipes during and immediately after opera­tion.
- During and immediately after operation, the refrigerant pipes are may be hot
and may be cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes.
Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
Do not turn off the power immediately after stopping operation.
- Always wait at least five minutes before turning off the power. Otherwise,
water leakage and trouble may occur.
2. Indoor unit accessories
PGRRUTR
The unit is provided with the following accessories:
Part No. Accessories Qty Place to set
1 Screw plate 4 2 Level adjusting screw 4 3 Strainer 1 4 Drain hose 1 5 Hose band 1
Set inside the packaging material
3. Selecting an installation site
Select a location so that air can be blown into all corners of the room.
Avoid locations exposed to outside air.
Select a location free of obstructions to the airflow in and out of the unit.
Avoid locations exposed to steam or oil vapour.
Avoid locations where combustible gas may leak, settle or be generated.
Avoid installation near machines emitting high-frequency waves (high-frequency
welders, etc.).
Avoid locations where the airflow is directed at a fire alarm sensor. (Hot air could trigger the alarm during the heating operation.)
Avoid places where acidic solutions are frequently handled.
Avoid places where sulphur-based or other sprays are frequently used.
6
If the unit is run for long hours at high temperature/high humidity (due point above 23 °C), due condensation may be produced in the indoor unit. When operating the units in this condition, add insulation material (10-20 mm) to the entire surface of the indoor unit to avoid due condensation.
Warning:
Ensure that the unit is installed in a place strong enough to sustain its weight. If there is a lack of strength, it may cause the unit to fall down, resulting in an injury.
Page 7
3.1. Securing installation and service space
For PFFY-P-VLRMM-E (mm)
Model name (C) (D)
20 · 25 660 More than 240 32 · 40 780 More than 240 50 · 63 1030 More than 240
[Fig. 3.1.1] (P.2)
<Upward blowing type>
A Floor B Ceiling C Piping space D Electrical part service space
4. Installing the unit
3.2. Combining indoor units with outdoor
units
For combining indoor units with outdoor units, refer to the outdoor unit installation manual.
4.1. Assembling the unit
1 Install the unit frame in parallel with the floor securely when installing. If the
floor is not flat, be sure to use the supplied level adjusting screws to maintain the unit body at level.
[Fig. 4.1.1] (P.2)
A Floor hole for fixing B Level adjusting screws (supplied) C Screw plate (supplied)
Note: There are two level adjusting screws on both sides each, a total of four.
There are the following two methods of fixing the unit for purposes of preventing the unit from falling down. Where fixing is necessary, screw the unit at the specified position given below.
For fixing on the floor [Fig. 4.1.2] (P.2)
<Viewed from bottom of the unit>
For fixing on the wall [Fig. 4.1.3] (P.2)
<Viewed from front of the unit>
Model name (E) (F)
20 · 25 1050 640 32 · 40 1170 760 50 · 63 1410 1000
Note: When fixing on the wall, fix the unit with the electrical parts removed from the unit.
4.2. Center of gravity and product weight
[Fig. 4.2.1] (P.2)
A Floor hole for fixing
For PFFY-P-VLRMM-E
Model name
PFFY-P20VLRMM-E PFFY-P25VLRMM-E PFFY-P32VLRMM-E PFFY-P40VLRMM-E PFFY-P50VLRMM-E PFFY-P63VLRMM-E
W
640 640 760
760 1000 1000
100 100 100 100 100 100
X
L
17 17 17 17 17 17
Product Weight (kg)
Z
335 335 335 335 335 335
18.5
18.5 20 21 25 27
GB
D
F
E
INL
5. Refrigerant pipe and drain pipe specifications
To avoid dew drops, provide sufficient antisweating and insulating work to the re­frigerant and drain pipes. When using commercially available refrigerant pipes, be sure to wind commer­cially available insulating material (with a heat-resisting temperature of more than 100°C and thickness given below) onto both liquid and gas pipes. Be also sure to wind commercially available insulating material (with a form polyethylene’s specific gravity of 0.03 and thickness given below) onto all pipes which pass through rooms.
1 Select the thickness of insulating material by pipe size.
Pipe size Insulating material’s thickness
6.4 mm to 25.4 mm More than 10 mm
28.6 mm to 38.1 mm More than 15 mm
2 If the unit is used on the highest story of a building and under conditions of
high temperature and humidity, it is necessary to use pipe size and insulating material’s thickness more than those given in the table above.
3 If there are customer’s specifications, simply follow them.
5.1. Refrigerant pipe and drain pipe size
A Refrigerant pipe sizes
Model name
P20/25/32/40/50 P63
[Fig. 5.1.1] (P.3)
Liquid pipe
ø 6.35 ø 9.52
A Refrigerant pipe brazing (for gas): LP B Refrigerant pipe brazing (for liquid): HP C Main drain pan D Sub drain pan E Hose (accessory) (External diameter ø 27 (end ø 20)) F Air filter G Electrical part box
Gas pipe
ø 12.7 ø 15.88
PGRRUTR
7
Page 8
6. Connecting refrigerant pipes and drain pipes
6.1. Refrigerant piping work
This piping work must be done in accordance with the installation manuals for both outdoor unit and BC controller (simultaneous cooling and heating series R2).
Series R2 is designed to operate in a system that the refrigerant pipe from an outdoor unit is received by BC controller and branches at the BC controller to connect between indoor units.
For constraints on pipe length and allowable difference of elevation, refer to the outdoor unit manual.
The method of pipe connection is brazing connection.
Caution:
Install the refrigerant piping for the indoor unit in accordance with the following.
1. Cut the tip of the indoor unit piping, remove the gas, and then remove the brazed cap.
[Fig. 6.1.1] (P.3)
GB
D
F
E
INL
A Cut here B Remove brazed cap
2. Pull out the thermal insulation on the site refrigerant piping, braze the unit piping, and replace the insulation in its original position. Wrap the piping with insulating tape.
Note:
When blazing the refrigerant pipes, be sure to blaze, after covering a wet cloth to the pipes of the units in order to prevent it from burning and shrinking by heat.
[Fig. 6.1.2] (P.3)
A Cool by a wet cloth
Pay strict attention when wrapping the copper piping since wrapping the piping may cause condensation instead of preventing it.
[Fig. 6.1.3] (P.3)
A Thermal insulation B Pull out insulation C Wrap with damp cloth D Return to original position E Ensure that there is no gap here F Wrap with insulating tape
Cautions On Refrigerant Piping
ss
s Be sure to use non-oxidative brazing for brazing to ensure that no for-
ss
eign matter or moisture enter into the pipe.
ss
s Be sure to apply refrigerating machine oil over the flare connection seat-
ss
ing surface and tighten the connection using a double spanner.
ss
s Provide a metal brace to support the refrigerant pipe so that no load is
ss
imparted to the indoor unit end pipe. This metal brace should be pro­vided 50 cm away from the indoor unit’s flare connection.
Warning:
When installing and moving the unit, do not charge it with refrigerant other than the refrigerant specified on the unit.
- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal­function and result in severe damage.
Caution:
Use refrigerant piping made of C1220 (Cu-DHP) phosphorus deoxidized
copper as specified in the JIS H3300 “Copper and copper alloy seamless pipes and tubes”. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shav­ing particles, oils, moisture, or any other contaminant.
Never use existing refrigerant piping.
- The large amount of chlorine in conventional refrigerant and refrigerator oil in the existing piping will cause the new refrigerant to deteriorate.
Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing.
- If dust, dir t, or water gets into the refrigerant cycle, the oil will deteriorate and
the compressor may fail.
The refrigerant used in the unit is highly hygroscopic and mixes with water and will degrade the refrigerator oil.
6.2. Drain piping work
1. Ensure that the drain piping is downward (pitch of more than 1/100) to the outdoor (discharge) side. Do not provide any trap or irregularity on the way.
2. Ensure that any cross-wise drain piping is less than 20 m (excluding the differ­ence of elevation). If the drain piping is long, provide metal braces to prevent it from waving. Never provide any air vent pipe. Otherwise drain may be ejected.
3. Put the supplied strainer at the bottom of the sub drain pan on the side of the body frame, and connect the supplied drain hose to the end connection. Tighten this end connection using the supplied hose hand.
4. Use a VP30 pipe or equivalent for collecting pipe if it is needed, and pipe it giving a downward pitch of more than 1/100.
5. Provide sufficient insulation just as for refrigerant piping.
[Fig. 6.2.1] (P.3)
A Indoor unit B Strainer (accessory) C Sub drain pan D Hose band (accessory) E Drain hose (accessory)
Caution:
Pipe the drain piping to ensure that it discharges drain, and insulate it to prevent dew condensation. A failure to the piping work may cause water leakage and so wet your property.
7. Electrical wiring
Precautions on electrical wiring
PGRRUTR
Warning:
Electrical work should be done by qualified electrical engineers in accord­ance with “Engineering Standards For Electrical Installation” and supplied installation manuals. Special circuits should also be used. If the power cir­cuit lacks capacity or has an installation failure, it may cause a risk of elec­tric shock or fire.
1. Be sure to take power from the special branch circuit.
2. Be sure to install an earth leakage breaker to the power.
3. Install the unit to prevent that any of the control circuit cables (remote control­ler, transmission cables) is brought in direct contact with the power cable out­side the unit.
4. Ensure that there is no slack on all wire connections.
5. Some cables (power, remote controller, transmission cables) above the ceiling may be bitten by mouses. Use as many metal pipes as possible to insert the cables into them for protection.
6. Never connect the power cable to leads for the transmission cables. Otherwise the cables would be broken.
7. Be sure to connect control cables to the indoor unit, remote controller, and the outdoor unit.
8. Put the unit to the ground on the outdoor unit side.
9. Select control cables from the conditions given in page
9
.
Caution:
Be sure to put the unit to the ground on the outdoor unit side. Do not con­nect the earth cable to any gas pipe, water pipe, lightening rod, or telephone earth cable. Incomplete grounding may cause a risk of electric shock.
Types of control cables
1. Wiring transmission cables
Types of transmission cables
Design wiring in accordance with the following table <Table 1>.
Cable diameter
More than 1.25 mm
2
8
Page 9
<Table 1>
System configuration For a single-refrigerant system For a multi-refrigerant system
Transmission cable length Less than 120 m More than 120 m Regardless of length
Building, clinic, hospital or communications station without noise supposedly generated
Facility example
(for noise judgment)
Types of transmission
cables
Length Less than 120 m Less than 200 m
2. Remote controller cables
Types of cables Cable diameter
Length
Sheathed 2-core cable (unshielded) CVV
0.3 to 1.25 mm
Less than 200 m
Residence or independent store without noise
VCTF, VCTFK, CVV, CVS, VVR, VVF, VCT or shielding wire CVVS or CPEVS
MA remote controller
2
from inverter equipment, private power gen­erator, high-frequency medical equipment, radio-used communications equipment and so on
Shielding wire CVVS or CPEVS
Sheathed 2-core cable (unshielded) CVV
0.3 to 1.25 mm Add any portion in excess of 10 m to within the longest allowable trans-
mission cable length 200 m (Shielding portion is more than 1.25 mm
All facilities
M-NET remote controller
2
2
)
GB
7.1. Power supply wiring
Power supply cords of appliances shall not be lighter than design 245 IEC 57 or 227 IEC 57.
A switch with at least 3 mm contact separation in each pole shall be provided by the Air conditioner installation.
Power cable size: more than 1.5 mm
[Fig. 7.1.1] (P.3)
A Switch 16 A B Overcurrent protection 16 A C Indoor unit D Total operating current be less than 16 A E Pull box
[Selecting non-fuse breaker (NF) or earth leakage breaker (NV)]
To select NF or NV instead of a combination of Class B fuse with switch, use the following:
In the case of Class B fuse rated 15 A or 20 A,
NF model name (MITSUBISHI): NF30-CS (15 A) (20 A) NV model name (MITSUBISHI): NV30-CA (15 A) (20 A)
Use an earth leakage breaker with a sensitivity of less than 30 mA 0.1 s.
2
Caution:
Do not use anything other than the correct capacity breaker and fuse. Using fuse, wire or copper wire with too large capacity may cause a risk of mal­function or fire.
7.2. Connecting remote controller, indoor
and outdoor transmission cables
(Remote controller is optionally available.)
Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)
The “S” on indoor unit TB5 is a shielding wire connection. For specifications about the connecting cables, refer to the outdoor unit installation manual.
Install a remote controller following the manual supplied with the remote con­troller.
Connect the “1” and “2” on indoor unit TB15 to a MA remote controller. (Non­polarized 2-wire)
Connect the “M1” and “M2” on indoor unit TB5 to a M-NET remote controller. (Non-polarized 2-wire)
Connect the remote controller’s transmission cable within 10 m using a 0.75 mm core cable. If the distance is more than 10 m, use a 1.25 mm2 junction cable.
[Fig. 7.2.1] (P.4) MA Remote controller [Fig. 7.2.2] (P.4) M-NET Remote controller
A Terminal block for indoor transmission cable B Terminal block for outdoor transmission cable C Remote controller
DC 9 to 13 V between 1 and 2 (MA remote controller)
DC 24 to 30 V between M1 and M2 (M-NET remote controller)
[Fig. 7.2.3] (P.4) MA Remote controller [Fig. 7.2.4] (P.4) M-NET Remote controller
A Non-polarized B TB15 C Remote Controller D TB5
The MA remote controller and the M-NET remote controller cannot be used at the same time or interchangeably.
Note: Ensure that the wiring is not pinched when fitting the terminal box cover. Pinching the wiring may cut it.
Caution:
Install wiring so that it is not tight and under tension. Wiring under tension may break, or overheat and burn.
Fix power source wiring to control box by using buffer bushing for tensile force. (PG connection or the like.) Connect transmission wiring to transmission ter­minal block through the knockout hole of control box using ordinary bushing.
After wiring is complete, make sure again that there is no slack on the connec­tions, and attach the cover onto the control box in the reverse order removal.
Caution:
Wire the power supply so that no tension is imparted. Otherwise disconnec­tion, heating or fire result.
Note: Put the transmission cable earth via the outdoor unit’s earth terminal the ground.
[Constraints on transmission cable]
[Fig. 7.2.5] (P.4)
G Outdoor unit H Ear th I Indoor unit J Remote controller K Non-polarized 2-wire
7.3. Connecting electrical wires
(Ensure that there is no slack on terminal screws.) Make sure that the model name in the operation manual attached to the control box cover is the same as that on the rating plate.
1. Remove the screw (2pcs) holding the cover to dismount the cover.
2. Open knockout holes. (Recommend to use a screwdriver or the like for this work.)
[Fig. 7.3.1] (P.4)
A Control box B Cover C Screw D Knockout hole E Remove
3. Fix power source wiring to control box by using buffer bushing for tensile force. (PG connection or the like.) Connect transmission wiring to transmission ter-
2
minal block through the knockout hole of control box using ordinary bushing.
[Fig. 7.3.2] (P.4)
A Use PG bushing to keep the weight of the cable and external force from being
applied to the power supply terminal connector. Use a cable tie to secure the cable.
B Power source wiring C Tensile force D Use ordinary bushing E Transmission wiring
4. Connect the power source, Earth, transmission and remote controller wiring.
[Fig. 7.3.3] (P.4)
A Power source terminal block B Terminal block for indoor transmission C Terminal block for remote controller D To 1-phase power source E Transmission line DC 30 V F Terminal block for outdoor transmission line (TB3) G Transmission line to the remote controller, terminal block for indoor unit and BC
controller
D
FINL EPGRRUTR
to
9
Page 10
[Shield wire connection]
[Fig. 7.3.4] (P.4)
A Terminal block B Round terminal C Shield wire D The earth wire from two cables are connected together to the S terminal. (Dead-
end connection)
E Insulation tape (To keep the earth wire of the shielded cable from coming in con-
tact with the transmission terminal)
5. After wiring is complete, make sure again that there is no slack on the connec­tions, and attach the cover onto the terminal block box in the reverse order of removal.
Notes:
Do not pinch the cables or wires when attaching the terminal block box cover. Doing so may cause a risk of disconnection.
When accommodating the terminal block box, make sure that the con­nectors on the box side are not removed. If removed, it cannot operate normally.
Caution:
Fix the electrical wires at site using clamps.
GB
Caution:
Wire the power supply so that no tension is imparted. Otherwise disconnec­tion, heating or fire may result.
7.4. Selecting the external static pressure
As the factory setting is for use under an external static pressure of 20 Pa, no switch operation is needed when using under the standard condition.
D
F
External static pressure Switch operation
20 Pa
3 2 1
SWA
2
1
SWC
E
INL
40 Pa
60 Pa
[Fig. 7.4.1] (P.4)
<Address board>
3 2 1
SWA
3 2 1
SWA
2
1
SWC
2
1
SWC
7.5. Setting addresses
(Be sure to operate with the main power turned OFF.)
[Fig. 7.4.1] (P.4)
<Address board>
There are two types of rotary switch setting available: setting addresses 1 to 9 and over 10, and setting branch numbers. 1 How to set addresses
PGRRUTR
Example: If Address is “3”, remain SW12 (for over 10) at “0”, and match SW11(for 1 to 9) with “3”.
2 How to set branch numbers SW14 (Series R2 only)
The branch number assigned to each indoor unit is the port number of the BC controller to which the indoor unit is connected. Leave it to “0” on the non-R2 series of units.
The rotary switches are all set to “0” when shipped from the factory. These switches can be used to set unit addresses and branch numbers at will.
The determination of indoor unit addresses varies with the system at site. Set them referring to the Data Book.
7.6. Sensing room temperature with the
built-in sensor in a remote controller
If you want to sense room temperature with the built-in sensor in a remote control­ler, set SW1-1 on the control board to “ON”. The setting of SW1-7 and SW1-8 as necessary also makes it possible to adjust the air flow at a time when the heating thermometer is OFF.
10
Page 11
This product is designed and intended for use in the residential, commer-
cial and light-industrial environment.
The product at hand is based on the following EU regulations:
Low Voltage Directive 73/23/EEC
Electromagnetic Compatibility Directive 89/
336/EEC
WT05228X01
Please be sure to put the contact address/telephone number on
this manual before handing it to the customer.
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN