Air-Conditioners For Building Application
INDOOR UNIT
PFFY-P-VLEM-A
PFFY-P-VLRM-A
GB
D
F
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
MANUEL D’INSTALLATION
Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d’une utilisation correcte.
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il condizionatore d’aria.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert.
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado.
Для осторожного и правильного использования прибора необходимо тщательно ознакомиться с данным руководством по
установке до выполнения установки кондиционера.
E
I
NL
P
GR
RU
TR
MONTAJ ELK‹TABI
Emniyetli ve do¤ru biçimde nas›l kullan›laca¤›n› ö¤renmek için lütfen klima cihaz›n› monte etmeden önce bu elkitab›n› dikkatle okuyunuz.
3
A
B
C
D
8
220
(F)205
(E)
114
3.1
[Fig. 3.1.1]
BB
(B)(B)(A)
[Fig. 3.1.2]
<Upward blowing type>
B
20
639
A
(D)(C)(D)
CD
C
A
<Forward blowing type>
(D)(C)(D)
CD
D
630
B
A
For PFFY-P-VLEM-A(mm)
(A)(B)
(C)(D)
25660More than 240
A Floor
B Ceiling
C Piping space
D Electrical part service space
50
Model name
251050More than 50
32 · 401170More than 50
50 · 631410More than 50
A Floor
B Wall
C Ceiling
D Secure large enough space to prevent that blowout air is blocked.
For PFFY-P-VLRM-A(mm)
Model name
611
32 · 40780More than 240
50 · 631030More than 240
4
[Fig. 4.1.1]
[Fig. 4.1.2]
4.1
[Fig. 4.1.6]
A
A
[Fig. 4.1.3][Fig. 4.1.4][Fig. 4.1.5]
C
B
C
E
D
F
A Front panelB Control panel cover
C Side casingD Floor hole for fixing
E Level adjusting screws (supplied)F Screw plate (supplied)
4.2
[Fig. 4.2.1][Fig. 4.2.3]
[Fig. 4.2.2]
For fixing on the floor
<Viewed from bottom of the unit>
Model name
251050640
32 · 401170760
50 · 6314101000
(E)(F)
For fixing on the wall
<Viewed from front of the unit>
[Fig. 4.1.7]
(F)205
(E)
630
170300
2
1
C
4
2
E
2
3
A Duct
B Tape
C Blowout hole section
D Insulating material
E Insulating material (10 mm in thickness. Be provided around the
blowout hole section.)
9
5
EF
C
25 ~ 63
A
B
43050
90
10035
5.1
[Fig. 5.1.1]
A
80
G
B
10035
C
43050
D
E
90
6
[Fig. 6.2.1]
A
7
[Fig. 7.1.1][Fig. 7.1.2]
AB
CCCCCCC
DE
F
45
6.2
B
C
D
E
A Indoor unit
B Strainer (accessory)
C Drain pan
D Hose band (accessory)
E Drain hose (accessory)
A Refrigerant pipe flare connection (for gas): LP
B Refrigerant pipe flare connection (for liquid): HP
C Drain pan
D Stainer
E Hose (accessory) (External diameter ø27 (end ø20))
F Air filter
G Electrical part box
7.1
A Switch 16 A
B Overcurrent protection 16 A
C Indoor unit
D Total operating current be less than 16 A
E Pull box
80
C
D
G
E
F
45
E Switch 16 A
F Overcurrent protection 16 A
7.2
[Fig. 7.2.1]
[Fig. 7.2.2]
B
M1M221
TB3
TB3
AA
SM1M2SM1M2
TB5TB15 TB5TB15
C
B
M1M2
AA
SM1M2SM1M2
TB5TB5
21
C
A T erminal block for indoor trans-
mission cable
B Terminal block for outdoor
transmission cable
C Remote controller
C
C
7.3
[Fig. 7.3.1]
D
B
C
A
A Control box
B Cover
1
C Screw
D Hook
[Fig. 7.3.2]
E
H
21
NL
F
[Fig. 7.2.3][Fig. 7.2.4]
2
DC10~13V
C
AB
12
A
1
B
N
L
[Fig. 7.2.5]
*1
G
H
III
L1
II
K
A DC 24 to 30 V
B Network remote controller
C Terminal bed for power supply
D Shielding
E Terminal bed for transmission cable
F To single-phase power supply
G To terminal bed for outdoor transmis-
sion cable
C
* Take shielding earth on the out-
door unit side.
H T o terminal bed for transmission cable,
remote controller, indoor BC controller
D
L2
JJ
L3
JF
[Fig. 7.4.1]
<Address board>
W254613G03
FP-AD-R
MADE IN JAPAN
N
L
A Non-polarized
B Upper level (TB15)
C Remote Controller
D Lower level (TB5)
G Outdoor unit
H Earth
I Indoor unit
J Remote controller
s Before installing the unit, make sure you read all the “Safety
GB
D
F
E
INL
PGRRUTR
precautions”.
s The “Safety precautions” provide very important points re-
garding safety. Make sure you follow them.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury
or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the
unit.
Symbols used in the illustrations
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
: Indicates that caution should be taken with rotating parts. (This symbol is
displayed on the main unit label.) <Color: yellow>
: Beware of electric shock (This symbol is displayed on the main unit label.)
<Color: yellow>
Warning:
Carefully read the labels affixed to the main unit.
Warning:
•Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage , electric shock,
or fire.
•Install the air unit at a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down, resulting in injuries.
•Use the specified cables for wiring. Make the connections securely so
that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
•Prepare for typhoons and other strong winds and earthquakes and install the unit at the specified place.
- Improper installation may cause the unit to topple and result in injury.
•Alwa ys use an air c leaner, humidifier, electric heater, and other accessories specified by Mitsubishi Electric.
- Ask an authorized technician to install the accessories. Improper installation
by the user may result in water leakage, electric shock, or fire.
•Never repair the unit. If the air conditioner must be repaired, consult the
dealer.
- If the unit is repaired improperly, water leakage, electric shock, or fire may
result.
•Do not touch the heat exchanger fins.
- Improper handling may result in injury.
•If refrigerant gas leaks during installation w ork, ventilate the room.
- If the refrigerant gas comes into contact with a flame, poisonous gases will
be released.
•Install the air conditioner according to this Installation Manual.
- If the unit is installed improperly, water leakage, electric shock, or fire may
result.
•Have all electric work done by a licensed electrician according to “Electric Facility Engineering Standard” and “Interior Wire Regulations”and
the instructions given in this manual and always use a special circuit.
5. Refrigerant pipe and drain pipe specifications ............................................ 6
5.1. Refrigerant pipe and drain pipe size.......................................... 6
6. Connecting refrigerant pipes and drain pipes ............................................. 6
6.1. Refrigerant piping work ............................................................. 6
- If the power source capacity is inadequate or electric work is performed improperly, electric shock and fire may result.
•Securely install the outdoor unit terminal cover (panel).
- If the terminal cover (panel) is not installed properly , dust or w ater ma y enter
the outdoor unit and fire or electric shock may result.
•When installing and moving the air conditioner to another site, do not
charge the it with a refrigerant different from the refrigerant (R407C or
R22) specified on the unit.
- If a different refrigerant or air is mixed with the original refrigerant, the refrig-
erant cycle may malfunction and the unit may be damaged.
•If the air conditioner is installed in a small r oom, measures m ust be taken
to prevent the refrigerant concentration from exceeding the safety limit
even if the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to prevent the saf ety
limit from being exceeded. Should the refrigerant leak and cause the safety
limit to be exceeded, hazards due to lack of o xygen in the room could result.
•When moving and reinstalling the air conditioner, consult the dealer or
an authorized technician.
- If the air conditioner is installed improperly , w ater leakage, electric shoc k, or
fire may result.
•After completing installation work, make sure that refrigerant gas is not
leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or
other heat source, it may generate noxious gases.
•Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted
and operated forcibly, or parts other than those specified by Mitsubishi Electric are used, fire or explosion may result.
1.2.Precautions for devices that use R407C
refrigerant
Caution:
•Do not use the existing refrigerant piping.
- The old refrigerant and refrigerator oil in the existing piping contains a large
amount of chlorine which may cause the refrigerator oil of the new unit to
deteriorate.
•Use refrigerant piping made of C1220 (CU-DHP) phosphorus deoxidized
copper as specified in the JIS H3300 “Copper and copper alloy seamless
pipes and tubes”. In addition, be sure that the inner and outer surfaces of
the pipes are clean and free of hazardous sulphur , o xides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
- Contaminants on the inside of the refrigerant piping may cause the refriger-
ant residual oil to deteriorate.
•Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing. (Store elbows and
other joints in a plastic bag.)
- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and
compressor trouble may result.
•Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator
oil to coat flares and flange connections.
- The refrigerator oil will degrade if it is mixed with a large amount of mineral
oil.
•Use liquid refrigerant to fill the system.
- If gas refrigerant is used to seal the system, the composition of the refriger-
ant in the cylinder will change and performance may drop.
•Do not use a refrigerant other than R407C.
- If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may
cause the refrigerator oil to deteriorate.
•Use a vacuum pump with a reverse flow check valve.
- The vacuum pump oil may flow bac k into the refrigerant cycle and cause the
refrigerator oil to deteriorate.
4
•Do not use the following tools that are used with conventional refrigerants.
(Gauge manifold, charge hose, gas leak detector , reverse flow c heck valve,
refrigerant charge base, vacuum gauge, refrigerant recovery equipment)
- If the conventional refrigerant and refrigerator oil are mixed in the R407C,
the refrigerant may deteriorated.
- If water is mixed in the R407C, the refrigerator oil may deteriorate.
- Since R407C does not contain any chlorine, gas leak detectors for conven-
tional refrigerants will not react to it.
•Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.
•Be especially careful when managing the tools.
- If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deterio-
rate.
1.3.Before getting installed
Caution:
•Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
•Do not use the air conditioner where f ood, pets, plants, precision instruments, or artwork are kept.
- The quality of the food, etc. may deteriorate.
•Do not use the air conditioner in special environments.
- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of
the air conditioner or damage its parts.
•When installing the unit in a hospital, communication station, or similar
place, provide sufficient protection against noise.
- The inverter equipment, private power generator, high-frequency medical
equipment, or radio communication equipment may cause the air conditioner
to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical
treatment or image broadcasting.
•Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80 % or when the drain pipe is clogged,
condensation may drip from the indoor unit. P erform collective dr ainage work
together with the outdoor unit, as required.
•The indoor models should be installed the ceiling over than 2.5 m from
floor.
1.4.Before getting installed (moved) - elec-
trical work
Caution:
•Ground the unit.
- Do not connect the ground wire to gas or water pipes, lightning rods, or
telephone ground lines. Improper grounding may result in electric shock.
•Install the power cable so that tension is not applied to the cable.
- Tension may cause the cable to break and generate heat and cause a fire.
•Install an leak circuit breaker, as required.
- If an leak circuit breaker is not installed, electric shock may result.
•Use power line cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
•Use only a circuit breaker and fuse of the specified capacity.
- A fuse or circuit breaker of a larger capacity or a steel or copper wire may
result in a general unit failure or fire.
•Do not wash the air conditioner units.
- Washing them may cause an electric shock.
•Be careful that the installation base is not damaged by long use.
- If the damage is left uncorrected, the unit may fall and cause personal injury
or property damage.
•Install the drain piping according to this Installation Manual to ensure
proper drainage. Wrap thermal insulation around the pipes to prevent
condensation.
- Improper drain piping may cause water leakage and damage to furniture
and other possessions.
•Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than 20 kg.
- Some products use PP bands for packaging. Do not use any PP bands for a
means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspend it at the specified positions on
the unit base. Also support the outdoor unit at four points so that it cannot
slip sideways.
•Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts, may cause
stabs or other injuries.
- Tear apart and throw away plastic packaging bags so that children will not
play with them. If children play with a plastic bag which was not torn apart,
they face the risk of suffocation.
1.5.Before starting the test run
Caution:
•Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the main power switch can
result in severe damage to internal parts. Keep the power switch turned on
during the operational season.
•Do not touch the switches with wet fingers.
- Touching a switch with wet fingers can cause electric shock.
•Do not touch the refrigerant pipes during and immediately after operation.
- During and immediately after operation, the refrigerant pipes are may be hot
and may be cold, depending on the condition of the refrigerant flowing through
the refrigerant piping, compressor, and other refrigerant cycle parts. Your
hands may suffer burns or frostbite if you touch the refrigerant pipes.
•Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
•Do not turn off the power immediately after stopping operation.
- Always wait at least five minutes before turning off the power. Otherwise,
water leakage and trouble may occur.
GB
D
F
E
INL
2. Indoor unit accessories
The unit is provided with the following accessories:
•Select a location so that air can be blown into all corners of the room.
•Avoid locations exposed to outside air.
•Select a location free of obstructions to the airflow in and out of the unit.
•Avoid locations exposed to steam or oil vapour.
•Avoid locations where combustible gas may leak, settle or be generated.
•A void installation near machines emitting high-frequency wa ves (high-frequency
welders, etc.).
•Avoid locations where the airflow is directed at a fire alarm sensor. (Hot air
could trigger the alarm during the heating operation.)
•Avoid places where acidic solutions are frequently handled.
•Avoid places where sulphur-based or other sprays are frequently used.
Warning:
Ensure that the unit is installed in a place strong enough to sustain its weight.
If there is a lack of strength, it may cause the unit to fall do wn, resulting in an
injury.
PGRRUTR
3.1.Securing installation and service space
For PFFY-P-VLEM-A(mm)
Model name(A)(B)
251050More than 50
32 · 401170More than 50
50 · 631410More than 50
[Fig. 3.1.1] (P.2)
A FloorB Wall
C Ceiling
D Secure large enough space to prevent that blowout air is blocked.
5