TECHNICAL & SERVICE MANUAL
Air-Conditioners For Building Application
<Indoor unit>
2014
Models
PFFY-P06NRMU-E,PFFY-P08NRMU-E
PFFY-P12NRMU-E,PFFY-P15NRMU-E
PFFY-P18NRMU-E,PFFY-P24NRMU-E
PFFY-P06NEMU-E,PFFY-P08NEMU-E
PFFY-P12NEMU-E,PFFY-P15NEMU-E
PFFY-P18NEMU-E,PFFY-P24NEMU-E
CONTENTS
SAFETY PRECAUTIONS ·························1
1. FEATURES ···········································3
2. PART NAMES AND FUNCTIONS········4
3. SPECIFICATION ···································6
4. OUTLINES AND DIMENSIONS············8
5. WIRING DIAGRAM ·····························10
6.
REFRIGERANT SYSTEM DIAGRAM
····11
7. TROUBLE SHOOTING ·······················12
8. DISASSEMBLY PROCEDURE···········
17
Floor Standing Type
Series PFFY
For use with the R410A & R22
Exposed type
Concealed type
![](/html/ff/ff79/ff79f3bed7b1951e1136a04bb9c860cf3c8b9258541f719e71c3467cad6ee139/bg2.png)
1. Before installation and electric work
• Keep the electric parts away from water (washing water etc.).
- It might result in electric shock, catching fire or smoke.
• To dispose of this product, consult your dealer.
• Do not use a leak detection additive.
s Before installing the unit, make sure you read all the
“Safety precautions”.
s The “Safety precautions” provide very important
points regarding safety. Make sure you follow them.
s This equipment may cause the adverse effect on the
same supply system.
s Please report to or take consent by the supply au-
thority before connection to the system.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger
of injury or death to the user.
•Never repair the unit. If the air conditioner must be repaired,
consult the dealer.
- If the unit is repaired improperly, water leakage, electric shock, or
fire may result.
• Do not touch the heat exchanger fins.
- Improper handling may result in injury.
• If refrigerant gas leaks during installation work, ventilate the
room.
- If the refrigerant gas comes into contact with a flame, poisonous
gases will be released.
• Install the air conditioner according to this manual.
- If the unit is installed improperly, water leakage, electric shock, or
fire may result.
•Have all electric work done by a licensed electrician according
to “Electric Facility Engineering Standard” and “Interior Wire
Regulations”and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is per-
formed improperly, electric shock and fire may result.
Caution:
Describes precautions that should be observed to prevent damage
to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided.
: Indicates that impor tant instructions must be followed.
: Indicates a part which must be grounded.
: Indicates that caution should be taken with rotating parts. (This
symbol is displayed on the main unit label.) <Color: Yellow>
:Beware of electric shock (This symbol is displayed on the main
unit label.) <Color: Yellow>
Warning:
Carefully read the labels affixed to the main unit.
Warning:
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage, elec-
tric shock, or fire.
• Install the air unit at a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down, resulting in
injuries.
• Use the specified cables for wiring. Make the connections securely so that the outside force of the cable is not applied to the
terminals.
- Inadequate connection and fastening may generate heat and cause
a fire.
• Prepare for typhoons and other strong winds and earthquakes
and install the unit at the specified place.
- Improper installation may cause the unit to topple and result in
injury.
•Always use an air cleaner, humidifier, electric heater, and other
accessories specified by Mitsubishi Electric.
- Ask an authorized technician to install the accessories. Improper
installation by the user may result in water leakage, electric shock,
or fire.
• Securely install the cover of control box and the panel.
- If the cover and panel are not installed properly,dust or water may
enter the outdoor unit and fire or electric shock may result.
• When installing and moving the air conditioner to another site,
do not charge the it with a refrigerant different from the refrigerant specified on the unit.
- If a different refrigerant or air is mixed with the original refrigerant,
the refrigerant cycle may malfunction and the unit may be damaged.
• If the air conditioner is installed in a small room, measures
must be taken to prevent the refrigerant concentration from
exceeding the safety limit even if the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to pre-
vent the safety limit from being exceeded. Should the refrigerant
leak and cause the safety limit to be exceeded, hazards due to
lack of oxygen in the room could result.
• When moving and reinstalling the air conditioner, consult the
dealer or an authorized technician.
- If the air conditioner is installed improperly, water leakage, elec-
tric shock, or fire may result.
• After completing installation work, make sure that refrigerant
gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove,
oven, or other heat source, it may generate noxious gases.
• Do not reconstruct or change the settings of the protection
devices.
- If the pressure switch, thermal switch, or other protection device
is shorted and operated forcibly, or parts other than those specified
by Mitsubishi Electric are used, fire or explosion may result.
![](/html/ff/ff79/ff79f3bed7b1951e1136a04bb9c860cf3c8b9258541f719e71c3467cad6ee139/bg3.png)
2. Precautions for devices that use
Caution:
• Do not use the existing refrigerant piping.
- The old refrigerant and refrigerator oil in the existing piping contains a large amount of chlorine which may cause the refrigerator
oil of the new unit to deteriorate.
• Use refrigerant piping made of C1220 (Cu-DHP) phosphorus
deoxidized copper as specified in the *JIS H3300 “Copper and
copper alloy seamless pipes and tubes”. In addition, be sure
that the inner and outer surfaces of the pipes are clean and
free of hazardous sulphur, oxides, dust/dirt, shaving particles,
oils, moisture, or any other contaminant.
- Contaminants on the inside of the refrigerant piping may cause
the refrigerant residual oil to deteriorate.
*JIS: Japanese Industrial Standard
• Store the piping to be used during installation indoors and keep
both ends of the piping sealed until just before brazing. (Store
elbows and other joints in a plastic bag.)
- If dust, dirt, or water enters the refrigerant cycle, deterioration of
the oil and compressor trouble may result.
• Use ester oil, ether oil or alkylbenzene (small amount) as the
refrigerator oil to coat flares and flange connections.
- The refrigerator oil will degrade if it is mixed with a large amount of
mineral oil.
• Use liquid refrigerant to fill the system.
- If gas refrigerant is used to seal the system, the composition of
the refrigerant in the cylinder will change and performance may
drop.
• Do not use a refrig
- If another refrigerant (R22, etc.) is used, the chlorine in the refrig-
erant may cause the refrigerator oil to deteriorate.
• Use a vacuum pump with a reverse flow check valve.
- The vacuum pump oil may flow back into the refrigerant cycle and
cause the refrigerator oil to deteriorate.
• Do not use the following tools that are used with conventional
refrigerants.
(Gauge manifold, charge hose, gas leak detector, reverse flow
check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment)
- If the conventional refrigerant and refrigerator oil are mixed in the
• Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.
• Be especially careful when managing the tools.
- If dust, dirt, or water gets in the refrigerant cycle, the refrigerant
may deteriorate.
R410A refrigerant
erant other than R410A.
R410A , the refrigerant may deteriorated.
- If deteriorate.water is mixed in the R410A , the refrigerator oil may
-Since R410A does not contain any chlorine, gas leak detectors
for conventional refrigerants will not react to it.
Warning:
Note the following when building a heater in the air
conditioning system.
- Leave enough space between units for proper ventilation so that
the indoor unit temperature does not exceed 40˚C when
windless.
- Keep the heater clean, and take appropriate measures so that
the indoor unit does not suck in the dust particles that
accumulate on the heater.
- Use the optional heater cable (PAC-YU24HT) to perform an
interlocked operation with indoor units.
- Do not build a heater inside the indoor unit.
•
Recommended circuit
FS1
FS2
FS1
FS2
R
S
R
S
CN24
H2
88H
H1
88H
26H
88H
Wiring diagram
1-phase power
supply
208V, 230V/60Hz
Control board
FS1, 2 ----- Thermal fuse
H1, H2 ----- Heater
26H --------- Overheat protection
thermostat
88H --------- Electromagnetic contactor
![](/html/ff/ff79/ff79f3bed7b1951e1136a04bb9c860cf3c8b9258541f719e71c3467cad6ee139/bg7.png)
PFFY-P-NEMU-E
PFFY-P-NRMU-E
Notes: *1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor: 26.7
˚C [80 ˚F] DB/19.4 ˚C [67 ˚F] WB Outdoor: 35 ˚C [95 ˚ F] DB
Heating: Indoor: 21.1
˚C [70 ˚F] DB Outdoor: 8.3 ˚C [47 ˚F] DB/6.1 ˚C [43 ˚F] WB
*2 The operating noise is the data that was obtained in an anechoic room.
Model
Item
PFFY-
P06NEMU-E
PFFY-
P08NEMU-E
PFFY-
P12NEMU-E
PFFY-
P15NEMU-E
PFFY-
P18NEMU-E
PFFY-
P24NEMU-E
Power sourse 208/230V, 60Hz
Capacity
*1
Cooling
kW 1.8
BTU/h 6000 8000 12000 15000 18000 24000
Heating
kW 2.
2.3
2.6
3.5
4.0
4.4
5.0
5.3
5.9
7.0
7.90
BTU/h 6700 9000 13500 17000 20000 27000
Dimension
Height
mm 630
in 24-13/16
Width
mm 1050 1170 1410
in 41-11/32 46-3/32 55-17/32
Depth
mm 220
in 8-11/16
Net weight
kg 23 23 25 26 30 32
lb 51 51 56 58 67 71
FAN
Airflow rate
(Low-High)
m
3
/min 5.5-6.5 5.5-6.5 7.0-9.0 8.5-11.0 10.0-13.0 10.0-14.0
cfm 194-229 194-229 247-317 300-388 353-459 353-494
External static
pressure
Pa
208V - - - - - -
230V - - - - - Noise level
(Low-High) *2
dB(A)
208V 36-41 36-41 37-41 38-43 38-43 40-46
230V 36-41 36-41 37-41 38-43 38-43 40-46
Filter Standard filter
Model
Item
PFFY-
P06NRMU-E
PFFY-
P08NRMU-E
PFFY-
P12NRMU-E
PFFY-
P15NRMU-E
PFFY-
P18NRMU-E
PFFY-
P24NRMU-E
Power sourse 208/230V, 60Hz
Capacity
*1
Cooling
kW 1.8
BTU/h 6000 8000 12000 15000 18000 24000
Heating
kW 2.
2.3
2.6
3.5
4.0
4.4
5.0
5.3
5.9
7.0
7.90
BTU/h 6700 9000 13500 17000 20000 27000
Dimension
Height
mm 639
in 25-3/16
Width
mm 886 10061246
in 34-29/32 39-5/8 49-1/16
Depth
mm 220
in 8-11/16
Net weight
kg 19 19 20 21 25 27
lb 41 41 45 47 56 60
FAN
Airflow rate
(Low-High)
m
3
/min 5.5-6.5 5.5-6.5 7.0-9.0 8.5-11.0 10.0-13.0 10.0-14.0
cfm 194-229 194-229 247-317 300-388 353-459 353-494
External static
pressure
Pa
208V - - - - - -
230V - - - - - Noise level
(Low-High) *2
dB(A)
208V 36-41 36-41 37-41 38-43 38-43 40-46
230V 36-41 36-41 37-41 38-43 38-43 40-46
Filter Standard filter
SPECIFICATION3
3-1. Specification
![](/html/ff/ff79/ff79f3bed7b1951e1136a04bb9c860cf3c8b9258541f719e71c3467cad6ee139/bg8.png)
LEV
C1
1.5µF X 440V
2.5µF
X
440V
2.0µF
X
440V
MF1,2
PFFY-P06
NEMU-E
NRMU-E
Model
Parts
name
Tr anrsformer T (Primary) 60Hz 208-230V (Secondary) (23.5V 0.9A)
TH21
Resistance 0˚C[32˚F]/15kΩ,10˚C[50˚F]/9.6kΩ,20˚C[68˚F]/6.3kΩ,25˚C[77˚F]/5.4kΩ,
30˚C[86˚F]/4.3kΩ,40˚C[104˚F]/3.0kΩ
Resistance 0˚C[32˚F]/15kΩ,10˚C[50˚F]/9.6kΩ,20˚C[68˚F]/6.3kΩ,25˚C[77˚F]/5.4kΩ,
30˚C[86˚F]/4.3kΩ,40˚C[104˚F]/3.0kΩ
Resistance 0˚C[32˚F]/15kΩ,10˚C[50˚F]/9.6kΩ,20˚C[68˚F]/6.3kΩ,25˚C[77˚F]/5.4kΩ,
30˚C[86˚F]/4.3kΩ,40˚C[104˚F]/3.0kΩ
TH22
Gas pipe
thermistor
FUSE 250V 6.3A
TB2 (L1, L2, G) 330V 30A
TB5
TB15
(1,2),(M1,M2,S) 300V 10A
Fuse
(Indoor con-
troller board)
Power supply
terminal bed
Tr ansmission
terminal bed
OFF 130˚C±5˚C
ON 90˚C±20˚C
Room
temperature
thermistor
Fan motor
(with Inner-
thermostat)
4-pole
OUTPUT 15W
CU-0206B-A
4-pole
OUTPUT 15W
CU-0206B-A
4-pole
OUTPUT 18W
CU-0207B-A
4-pole
OUTPUT 30W
CU-0303B-A
4-pole
OUTPUT 35W
CRC4415AB
4-pole
OUTPUT 50W
CU-0507B-A
Symbol
DC12V Stepping motor drive port
dimension
ø3.2 (0~2000pulse)
TH23
Innerthermostat/
thermal fuse
(Fan motor)
Liquid pipe
thermistor
Fan motor
capacitor
Linear
expansion valve
PFFY-P08
NEMU-E
NRMU-E
PFFY-P12
NEMU-E
NRMU-E
PFFY-P15
NEMU-E
NRMU-E
PFFY-P18
NEMU-E
NRMU-E
PFFY-P24
NEMU-E
NRMU-E
152˚C ˚C
+5
0
[306˚F ˚F]
+41
+32
[306˚F ˚F]
+41
+32
FUSE
CUT OFF
[266˚F±41˚F]
[194˚F±68˚F]
3-2. Electrical parts specification