SPECIFI C ATION
Model Name Indoor
Outdoor
System capacity kW
System Power input kW
System current A
Power source
Power input kW
Current A
Fan Type x Quantity
Airflow rate m
3
/ min
External static pressure Pa
Motor output kW
Refrigerant
External finish
External dimension mm
Protection devices Fan
Refrigerant piping diameter
Liquid pipe mm
Gas pipe mm
Refrigerant piping allowable length m
Sound pressure level dB(A)
Heat exchanger
Air filter
Net weight kg
Operating temperature range
S TA ND ARD mod el P FAV - P 2 5 0 V M - E P FAV - P 5 0 0 V M - E PFA V-P75 0 V M - E
PFAV-P250VM-E
PUHY-P250YHM-A
Cooling Heating
25.0 (Maximum28.0) 28.0 (Maximum 31.5)
7.46 / 7.53 8.27 / 8.34
14.5-13.8-13.3 / 13.4-12.8-12.3 15.8-15.0-14.4 / 14.7-14.0-13.4
3-phase 4-wire 380-400-415V (50Hz / 60Hz)
0.82 / 0.89
3.4-3.2-3.1 / 2.3-2.2-2.1
Sirocco fan x 2
90
30 / 90
2.2
R410A
Galvanized steel plate (with polyester coating)
MUNSEL 5Y 8 / 1 or similar
1748(H) x 1200(W) x 485(D)
Over current protection
9.52 Brazed (12.7 for over 90m)
22.2 Brazed
165
55
Cross fin (aluminum plate fin and copper tube)
Synthetic fiber unwoven cloth filter
156
Cooling Heating
Indoor: 10 to 25 °CWB Indoor: 15 to 28 °CDB
(Outdoor: -5 to 43 °CDB) (Outdoor: -20 to 15.5 °CWB)
PFAV-P500VM-E
PUHY-P500YSHM-A (PUHY-P250YHM-A x2, CMY-Y100VBK2)
Cooling Heating
50.0 (Maximum56.0) 56.0 (Maximum 63.0)
17.85 / 18.84 17.00 / 17.99
32.3-30.7-29.6 / 32.6-31.0-29.9 30.8-29.3-28.2 / 31.1-29.6-28.5
3-phase 4-wire 380-400-415V (50Hz / 60Hz)
2.37 / 3.36
6.2-5.9-5.7 / 6.5-6.2-6.0
Sirocco fan x 1
180
30 / 130
5.5
R410A
Galvanized steel plate (with polyester coating)
MUNSEL 5Y 8 / 1 or similar
1899(H) x 1420(W) x 635(D)
Over current protection
15.88 Brazed
28.58 Brazed
165
59 / 62
Cross fin (aluminum plate fin and copper tube)
Synthetic fiber unwoven cloth filter
265
Cooling Heating
Indoor: 10 to 25 °CWB Indoor: 15 to 28 °CDB
(Outdoor: -5 to 43 °CDB) (Outdoor: -20 to 15.5 °CWB)
PFAV-P750VM-E
PUHY-P750YSHM-A (PUHY-P350YHM-A + PUHY-P400YHM-A, CMY-Y200VBK2)
Cooling Heating
71.0 (Maximum 80.0) 80.0 (Maximum 90.0)
26.33 / 27.40 23.93 / 25.00
48.1-45.7-44.1 / 47.5-45.1-43.5 43.4-41.2-39.8 / 42.8-40.6-39.2
3-phase 4-wire 380-400-415V (50Hz / 60Hz)
4.30 / 5.37
10.9-10.4-10.0 / 10.3-9.8-9.4
Sirocco fan x 1
260
100 / 310
7.5
R410A
Galvanized steel plate (with polyester coating)
MUNSEL 5Y 8 / 1 or similar
1860(H) x 1750(W) x 1064(D)
Over current protection
19.05 Brazed
34.93 Brazed
165
65
Cross fin (aluminum plate fin and copper tube)
PP Honeycomb fabric filter
459
Cooling Heating
Indoor: 10 to 25 °CWB Indoor: 15 to 28 °CDB
(Outdoor: -5 to 43 °CDB) (Outdoor: -20 to 15.5 °CWB)
Works not included: Installation / foundation work, electric connection work, duct work, insulation work, the power source switch and other items are not specified in the specifications.
1. Cooling / Heating capacity indicates the value at operation under the following conditions.
(Cooling) Indoor: 27°CDB / 19°CWB, Outdoor: 35°CDB
(Heating) Indoor: 20°CDB, Outdoor: 7°CDB / 6°CWB
Pipe length: 7.5m, Height difference: 0m
2. The noise level is measured in an anechoic room.
3. Long period operation in a high temperature and humidity atmosphere(dew point of 23°C or
more) may cause condensation to form in the indoor unit.
Model Name Indoor
Outdoor
System capacity kW
System Power input kW
System current A
Power source
Power input kW
Current A
Fan Type x Quantity
Airflow rate m
3
/ min
External static pressure Pa
Motor output kW
Refrigerant
External finish
External dimension mm
Protection devices Fan
Refrigerant piping diameter
Liquid pipe mm
Gas pipe mm
Refrigerant piping allowable length m
Sound pressure level dB(A)
Heat exchanger
Air filter
Net weight kg
Operating temperature range
F R E SH AI R I NTA K E mode l P F AV - P 3 0 0 VM -E-F P FAV - P 6 0 0 V M - E - F P FAV- P9 00VM - E - F
PFAV-P300VM-E-F
PUHY-P250YHM-A
Cooling Heating
28.0 (Maximum 33.5) 26.5 (Maximum 28.0)
6.73 / 6.72 7.57 / 7.56
12.6-11.9-11.5 / 12.2-11.5-11.1 14.0-13.3-12.8 / 13.6-12.9-12.4
3-phase 4-wire 380-400-415V (50Hz / 60Hz)
0.37 / 0.36
1.9-1.8-1.7 / 1.5-1.4-1.3
Sirocco fan x 2
45
80
1.5
R410A
Galvanized steel plate (with polyester coating)
MUNSEL 5Y 8 / 1 or similar
1748(H) x 1200(W) x 485(D)
Over current protection
9.52 Brazed (12.7 for over 90m)
22.2 Brazed
165
48.5
Cross fin (aluminum plate fin and copper tube)
Synthetic fiber unwoven cloth filter
151
Cooling Heating
Indoor: 15 to 35 °CWB Indoor: 0 to 20 °CDB
(Outdoor: 20 to 43 °CDB) (Outdoor: -4 to 15.5 °CWB)
PFAV-P600VM-E-F
PUHY-P500YSHM-A (PUHY-P250YHM-A x2, CMY-Y100VBK2)
Cooling Heating
56.0 (Maximum 67.0) 50.0 (Maximum 56.0)
14.69 / 15.05 15.43 / 15.79
26.1-24.9-24.0 / 26.2-25.0-24.0 27.4-26.1-25.1 / 27.5-26.2-25.1
3-phase 4-wire 380-400-415V (50Hz / 60Hz)
0.90 / 1.26
2.9-2.8-2.8 / 3.0-2.9-2.8
Sirocco fan x 1
90
110 / 170
2.2
R410A
Galvanized steel plate (with polyester coating)
MUNSEL 5Y 8 / 1 or similar
1899(H) x 1420(W) x 635(D)
Over current protection
15.88 Brazed
28.58 Brazed
165
50 / 53
Cross fin (aluminum plate fin and copper tube)
Synthetic fiber unwoven cloth filter
248
Cooling Heating
Indoor: 15 to 35 °CWB Indoor: 0 to 20 °CDB
(Outdoor: 20 to 43 °CDB) (Outdoor: -4 to 15.5 °CWB)
PFAV-P900VM-E-F
PUHY-P750YSHM-A (PUHY-P350YHM-A + PUHY-P400YHM-A, CMY-Y200VBK2)
Cooling Heating
80.0 (Maximum 100.0) 71.0 (Maximum 80.0)
22.54 / 22.74 21.43 / 21.63
40.5-38.5-37.1 / 39.6-37.6-36.2 38.7-36.8-35.5 / 37.8-35.9-34.6
3-phase 4-wire 380-400-415V (50Hz / 60Hz)
1.77 / 1.97
5.6-5.3-5.1 / 4.7-4.4-4.2
Sirocco fan x 1
120
210 / 330
3.7
R410A
Galvanized steel plate (with polyester coating)
MUNSEL 5Y 8 / 1 or similar
1860(H) x 1750(W) x 1064(D)
Over current protection
19.05 Brazed
34.93 Brazed
165
57
Cross fin (aluminum plate fin and copper tube)
PP Honeycomb fabric filter
437
Cooling Heating
Indoor: 15 to 35 °CWB Indoor: 0 to 20 °CDB
(Outdoor: 20 to 43 °CDB) (Outdoor: -4 to 15.5 °CWB)
1. Cooling / Heating capacity indicates the value at operation under the following conditions.
(Cooling) Indoor,Outdoor: 33°CDB / 28°CWB
(Heating) Indoor,Outdoor: 7°CDB / 3°CWB
Pipe length: 7.5m, Height difference: 0m
2. The noise level is measured in an anechoic room.
3. The indoor intake air temperature should be kept higher than 0 °C.
4. At factory setting, the fan temporary stops in defrosting. Change DIP SW for fan to operate in
defrosting.
5. Indoor temperature and humidity cannnot be controlled with Fresh air intake type.
Plenum chamber
Twinning kit
PAC-CC83PL-E
PAC-CC85PL-E
PAC-CC87PL-E
CMY-Y100VBK2
CMY-Y200VBK2
PFAV-P250VM-E
PFAV-P500VM-E
PFAV-P750VM-E
PUHY-P500YSHM-A
PUHY-P750YSHM-A
D e s cri ptio n M o d el A ppli cabl e c apac ity
I n d oor uni t
O u t doo r un it
O p t ion al p arts