Mitsubishi PEHD-3EKA3.UK, PEHD-4EKSA3.UK, PEHD-5EKSA3.UK, PEHD-6EKSA.UK, PEHD-3EKHA3.UK Service Manual

...
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
ADVANCE AND EVER ADVANCING
TECHNICAL & SERVICE MANUAL
<indoor unit> Service ref.
Models
PEHD-3EKA3.UK PEHD-3EKHA
PEHD-4EKSA
PEHD-4EKHSA
PEHD-5EKSA
PEHD-5EKHSA
PEHD-6EKSA.UK PEHD-6EKHSA.UK
The Slim Line. From Mitsubishi Electric
TM
1. FEATURES ················································ 1
2. PART NAMES AND FUNCTIONS ············· 2
3. SPECIFICATIONS······································ 5
4. DATA··························································· 9
5. REFRIGERANT SYSTEM DIAGRAM ·······14
6. OUTLINES AND DIMENSIONS ················15
7. WIRING DIAGRAM ···································16
8. DISASSEMBLY INSTRUCTIONS ············ 17
9. PARTS LIST·············································· 20 10
. OPTIONAL PARTS··································· 24
CONTENTS
INDOOR UNIT
REMOTE CONTROLLER
This manual does not cover the following outdoor units. When servicing them, please refer to the service manual No.OC150A and this manual as a set.
PUH-3YKA
2.UK
PUH-3VKA
2.UK
PUH-4YKSA
2.UK
PUH-4VKSA
2.UK
PUH-5YKSA
2.UK
PUH-6YKSA
2.UK
1
1
FEATURES
1. NEXT GENERATION AIR-CONDITIONING VENTILATION INTERLOCKING SYSTEM "Mr.SLIM"+ "LOSSNAY"
Proper ventilation is important to improve the quality of indoor environments. It eliminates unclean air, which is not only unpleasant, but unhealthy. This "Mr.SLIM" + "LOSSNAY" ventilation interlocking system achieves high air quality with minimum energy consumption. LOSSNAY's unique total heat exchanger reduces heating and cooling expenses by about 25 percent annually(in comparison with our existing models). In addition, its mechanism of simultaneous forced air supply and exhaust enables it to deliver high quality air. Together, "Mr.SLIM" + "LOSSNAY" system makes next-generation air conditioning possible. This system is both people and environment friendly.
2. TOTALLY INVISIBLE INDOOR UNIT BEHIND THE CEILING
The totally hidden indoor unit that lies above the ceiling surface enables you to utilize full floor space while allowing for flexible interior design. This new feature is recommended for stores and offices where the user's own imagination is allowed to be incorporated.
3. MOST SUITABLE FOR SIMULTANEOUS TWO ROOM AIR CONDITIONING
Using air ducts for cooling/heating airflow that matches the structure and purpose of the room enables you to provide two air outlets for simultaneous cooling/heating of two rooms.
4. HIGH EXTERNAL STATIC PRESSURE(OPTION MOTOR)
The exceptional external static pressure of 130Pa allows long ducts to be used more extensively to achieve convenient location of indoor units.(STD:70Pa)
5. DRAIN WATER LIFT-UP MECHANISM(OPTION KIT)
This allows more versatility when selecting drain piping layouts.
air outlet air outlet
Air outlet duct
Air intake duct
air intake
lndoor unit
Remote controller
Models Cooling capacity / Heating capacity
Btu/h W
PEHD-3EK(H)A3 PEHD-4EK(H)SA
3
PEHD-5EK(H)SA
3
PEHD-6EK(H)SA
26,300/30,700(37,900) 33,100/35,500(43,700) 42,300/47,400(57,700) 50,000/54,500(64,700)
7,700/9,000(11,100)
9,700/10,400(12,800) 12,400/13,900(16,900) 14,650/16,000(19,000)
2
2
PART NAMES AND FUNCTIONS
6. ADVANCED MICROPROCESSOR
(1) Easy to use microprocessor
1) Ultra-thin remote controller
The streamlined, square controller is designed to blend well with any interior. Also, the sophisticated micro­processor allows you to easily carry out a wide range of operations.
2) Attractive liquid crystal display (LCD)
The unit's operation mode, set temperature, room temperature, timer setting, and fan speed are displayed on the remote controller's easy-to-read Liquid Crystal Display (LCD)
3) Convenient 24-hour ON-OFF timer
The timer switches Mr.SLIM on and off automatically at the time you set. Once the timer is set, the remaining time is shown on the LCD.
4) Self-diagnostic feature indicates faults instantly
If a problem occurs, the unit will stop operating and the set temperature indicator will change to a self-diagnostic indicator, which shows the location of the trouble. If the check switch is pressed twice, the unit stops operating and the check mode is initiated. The location of the most recent problem that was stored in the memory is displayed on the LCD. This is extremely useful for maintenance purposes.
5) Useful memory feature for storing instructions
The previous set value is memorized so that constant temperature control can be achieved. For example, if a power failure occurs, the temperature will not have to be re adjusted afterwards.
(2) Non-polar two-wire remote controller cable
The slim, non-polar, two-wire remote controller cable makes installation simple and trouble free. Also, the remote controller wire can be extended up to 500m.
(3) Automatic cooling/heating changeover operation
An automatic cooling and heating changeover operation system allows you to easily control comfortable year-round air conditioning. Once the desired temperature is set, unit operation switches automatically between cooling and heating, in accordance with the room temperature. In addition, the use of an outdoor unit fan speed controller allows cooling even when outdoor temperatures are as low as - 5˚C.
7. INNOVATIVE MICROPROCESSOR CONTROL SYSTEM
The most significant feature of PEHD-EK series is the advanced microprocessor control. The development of this system is due to the recent world-wide trend in the air conditioning of larger buildings. They are moving away from centralized duct systems to using individual split type units instead. There are a number of reasons for this change. First of all, the duct's costly and troublesome installation is eliminated. Second, the overall air conditioning balance is excellent in split type units. Lastly, the operation costs are low due to the flexible control of each unit. This system was developed exclusively by Mitsubishi Electric because of high demand. The microprocessor control makes individual control, group control, control using two remote controllers, and remote on/off and individual control possible without troublesome equipment modifications.
Indoor Unit
Air intake (sucks the air inside the room into the unit)
Air outlet
3
Remote controller
Once the operation of the unit is set, subsequent
operations can be performed only by pressing the ON/OFF button repeatedly.
Operation buttons
This switches between continu­ous operation and the timer operation.
Press this button to switch the cool, electronic dry (dehumidify) automatic and heat modes.
This sets the room tempera­ture. The temperature setting can be performed in 1˚C units. Setting range : Cool 19˚C to 30˚C Heat 17˚C to 28˚C
The model name of the remote controller is indicated.
This switches the horizontal fan motion ON and OFF.
(This button does not operate in this model)
Only press this button to per­form an inspection check or test operation. Do not use it for normal operation.
This resets the filter service indication display.
(This button dose not operate in this model.)
This adjusts the vertical angle of the ventilation.
(This button dose not operate in this model)
This switches between the operation and stop modes each time it is pressed. The lamp on this button lights dur­ing operation.
This sets / switches the current
time, start time and stop time.
This sets the ventilation fan speed.
button
button
TEMP button
button
CHECK-TEST RUN
button
FILTER button
button
ON/OFF button
button
button
4
Display
This indicates when the unit is controlled by optinal fea­tures such as central control type remote controller.
The current time, start time and stop time can be dis­played in tencecond intervals by pressing the time switch button. The start time or stop time is always displayed during the timer operation.
The selected fan speed is dis­played.
This indicates when the con­tinuous operation and time operation modes are set. It also displays the time for the timer operation at the same time as when it is set.
This indicates the operation mode.
This indicates when the stand by mode is set from the time the sleep operation starts until the heating air discharges.
This indicates when the de­frost operation is performed.
This indicates when a malfun­ction has occurred in the unit which should be checked.
This displays the selected set­ting temperature.
The temperature of the suc­tion air is displayed during operation. The display range is 8˚C to 39˚C. The display flashes 8˚C when the actual tempera­ture is less then 8˚C and flashes 39˚C when the actual temperature is greater then 39˚C.
This lamp lights during opera­tion, goes off when the unit stops and flashes when a mal­function occurs.
This display lights in the check mode or when a test operation is perfomed.
This lamp lights when electric­ity is supplied to the unit.
Caution
• Only the display lights whe the unit is stopped and power is supplied to the unit.
• When power is turned ON for the first time, the (CENTRAL CTRL) display appears to go off momentarily but this is not a malfunction.
• When the central control remote control unit, which is sold separately, is used the ON - OFF button,
button and TEMP button do not operate.
• "NOT AVAILABLE" is displayed when the button and button are pressed. This indicates that this room unit is not equipped with the fan direction adjustment function and the louver function.
CENTRALLY CONTROLLED display
display
OPERATION MODE
display
STANDBY display
DEFROST display
CHECK display
Display
display
display
display
Operation lamp
CHECK MODE TEST RUN
˚C
display
˚C
display
CLOCK
ON OFF
5
3
SPECIFICATION
Item Function
Capacity Total input
INDOOR UNIT
Model name Power supply
Starting current
Running current
Input
External finish Heat exchanger Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure Booster heater Operation control & Thermostat Noise level(Low-High) Cond.drain conn.O.D.
Dimensions
Weight
dB(A) mm,(in) mm,(in) mm,(in) mm,(in)
W
D H
kg,(lbs)
Model name Power supply Input Running current Starting current External finish Refrigerant control Compressor Model Motor output
kW
Protection devices
Stater type
Heat exchanger Fan(drive) x No. Fan motor output
kW
Airflow
CMM,(CFM) Defrost method Noise level
dB(A)
Dimensions
W
D H
mm,(in) mm,(in) mm,(in) kg,(lbs)
Weight Refrigerant
kg,(lbs)
Charge Pipe size O.D.
Connection method Between the indoor
& outdoor unit
Liquid mm,(in) Gas mm,(in)
Indoor side
Outdoor side
Height difference
Piping length
REFRIGERANT
PIPING
OUTDOOR UNIT
kW
A A
Btu/h
W
kW
kW
A A
kW
kW
CMM,(CFM)
Pa(mmAq)
Model
4 4
✻✻
✻ ✻ ✻
5
1
2
3
1. External static pressure at 130Pa
2. Ex-works at 70Pa(OPTION MOTOR: 130Pa)
3. External static pressure at 70Pa
4. Rating conditions <JIS B 8615, 8616> (INDOOR) Cooling: 27˚CDB, 19˚CWB Heating: 20˚CDB (OUTDOOR) Cooling: 35˚CDB Heating: 7˚CDB, 6˚CWB
5. Noise level: Sound pressure level
PEHD-3EK(H)A3.UK
Cooling
26,300
7,700
3.55
Cooling
26,300
7,700
3.55
Heating
PEHD-3EK(H)A
3.UK
~/N,50Hz, 220-240V
0.40
1.70
1.90
0.40 (2.50)
1.70 (10.41)
1.90 (10.65)
0.40
1.70
1.90
0.40 (2.50)
1.70 (10.41)
1.90 (10.65)
3N~, 380/220-415/240V, 50Hz~/N, 220-240V ,50Hz
Galvanized sheets
Plate fin coil
Centrifugal (direct)x2
0.15
20-25 (700-800)
70(7)/130(13) at Hi-notch
2.1
Remote control & Built-in
37-41
32 (1-1/4)
1,175 (46-1/8)
740 (29-1/8)
325 (12-13/16)
44 (97) [46 (101)]
PUH-3YKA
2PUH-3VKA2
3.15
13.82 58
2.94
12.89 58
3.15
5.16 37
2.94
4.81 37
Munsell 5Y7/1 Capillary tube
Hermetic
NH52VND NH52YDA
2.2 2.4 Line start
Plate fin coil
Propeller (direct)x2
0.085
50 (1764)
Reverse cycle
52
870 (34-1/4)
295+24 (11-5/8 add 1)
850 (33-7/16)
75 (165)
R-22
3.2 (7.1)
9.52 (3/8)
15.88 (5/8) Flared Flared
Max.50m Max.50m
Heating
30,700 (37,900)
9,000 (11,100)
3.34 (5.44)
30,700 (37,900)
9,000 (11,100)
3.34 (5.44)
V: Inner thermostat,HP switch Y: Reversed-phase protector, Thermal relay, Thermal switch, HP switch
6
Item Function
Capacity Total input
Model name Power supply Input Running current Starting current External finish Heat exchanger Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure Booster heater
INDOOR UNIT
Operation control & Thermostat Noise level(Low-High) Cond.drain conn.O.D.
Dimensions
Weight Model name Power supply Input Running current Starting current External finish Refrigerant control Compressor Model Motor output Stater type
Protection devices Heat exchanger
Fan(drive) x No.
OUTDOOR UNIT
Fan motor output Airflow Defrost method Noise level
Dimensions
Weight Refrigerant Charge
Pipe size O.D.
PIPING
Connection method
REFRIGERANT
Between the indoor & outdoor unit
Model
Cooling
✻ ✻
W
kW
4
Btu/h
4
kW
A A
kW
33,100
9,700
4.14
0.62
2.64
3.20
1
CMM,(CFM)
Pa(mmAq)
2
kW
✻✻
dB(A)
5
3
mm,(in)
W
D H
mm,(in) mm,(in) mm,(in) kg,(lbs)
~/N, 220-240V, 50Hz
kW
A A
3.52
16.30 79
kW
V: Inner thermostat, HP switch Y: Reversed-phase protector, Thermal relay, Thermal switch, HP switch
kW
CMM,(CFM)
dB(A)
W
D H
mm,(in) mm,(in) mm,(in) kg,(lbs)
kg,(lbs) Liquid mm,(in) Gas mm,(in)
Indoor side
Outdoor side
Height difference
Piping length
PEHD-4EK(H)SA3.UK
Heating
35,500 (43,700)
10,400 (12,800)
4.14 (6.54) PEHD-4EK(H)SA
Cooling
33,100
9,700
3.82
3.UK
~/N, 50Hz, 220-240V
0.62 (3.02)
2.64 (12.58)
3.20 (13.2)
0.62
2.64
3.20
Galvanized sheets
Plate fin coil
Centrifugal (direct)x2
0.27
27-34 (950-1200)
70(7) / 130(13) at Hi-notch
2.4
Remote control & Built-in
41-46
32 (1-1/4)
1,415 (55-11/16)
740 (29-1/8)
325 (12-13/16)
62 (137) [65(143)]
PUH-4VKSA2
3N~, 380/220-415/240V, 50Hz
3.52
16.30
3.20
5.24
79
Munsell 5Y7/1 Capillary tube
Hermetic
NH56VNDT
2.7 .7 Line start
Plate fin coil
Propeller (direct) x2
0.065+0.065 95 (3350)
Reverse cycle
54
870 (34-1/4)
295+24 (11-5/8 and 1)
1258 (49-1/2)
94 (207)
R-22
4.2 (9.2)
9.52 (3/8)
19.05 (3/4) Flared Flared
Max.50m Max.50m
PUH-4YKSA
40
NH56YDA
Heating
35,500 (43,700) 10,400 (12,800)
3.81 (6.21)
0.62 (3.02)
2.64 (12.58)
3.20 (13.2)
2
3.19
5.22 40
1. External static pressure at 130Pa
2. Ex-works at 70Pa(OPTION MOTOR: 130Pa)
✻ ✻
3. External static pressure at 70Pa
4. Rating conditions <JIS B 8615, 8616>
(INDOOR) Cooling: 27˚CDB, 19˚CWB Heating: 20˚CDB (OUTDOOR) Cooling: 35˚CDB Heating: 7˚CDB, 6˚CWB
5. Noise level: Sound pressure level
7
Item Function
Capacity Total input
Model name Power supply Input Running current Starting current External finish Heat exchanger Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure Booster heater
INDOOR UNIT
Operation control & Thermostat Noise level(Low-High) Cond.drain conn.O.D.
Dimensions
Weight Model name Power supply Input Running current Starting current External finish Refrigerant control Compressor Model Motor output Stater type Protection devices Heat exchanger Fan(drive) x No.
OUTDOOR UNIT
Fan motor output Airflow Defrost method Noise level
Dimensions
Weight Refrigerant Charge
Pipe size O.D.
PIPING
Connection method
REFRIGERANT
Between the indoor & outdoor unit
Model
✽ ✽
Btu/h
4 4
W
kW
kW
A A
kW
CMM,(CFM)
Pa(mmAq)
kW
dB(A)
5
mm,(in)
W
D H
mm,(in) mm,(in) mm,(in)
kg,(lbs)
kW
A A
kW
kW
CMM,(CFM)
dB(A)
W
D H
mm,(in) mm,(in) mm,(in)
kg,(lbs)
kg,(lbs) Liquid mm,(in) Gas mm,(in)
Indoor side
Outdoor side
Height difference
Piping length
PEHD-5EK(H)SA3.UK
Cooling
42,300 12,400
4.85 PEHD-5EK(H)SA
3.UK
Heating
47,400 (57,700) 13,900 (16,900)
4.80 (7.80)
~/N, 50Hz, 220-240V
0.64
2.72
6.00
0.64 (3.64)
2.72 (15.17)
6.00 (18.50)
Galvanized sheets
Plate fin coil
Centrifugal (direct)x2
1
0.30
33.5-42 (1180-1480)
2
70(7) /130(13) at Hi-notch
3.0
Remote control & Built-in
3
44-50
32 (1-1/4)
1,415 (55-11/16)
740 (29-1/8)
325 (12-13/16)
65(143) [68(150)]
PUH-5YKSA
2
3N~, 380/220-415/240V, 50Hz
4.21
6.89
53
4.16
6.81 53
Munsell 5Y7/1 Capillary tube
Hermetic
ZR-61K3-TFD
3.5
Line start
Internal thermostat, Anti-phase protector, Thermal switch, HP switch
Plate fin coil
Propeller(direct)x2
0.085+0.085 95 (3350)
Reverse cycle
55
970 (38-3/16)
345+24 (13-9/16 add 1)
1258 (49-1/2)
114 (251)
R-22
5.4 (11.9)
9.52 (3/8)
19.05 (3/4) Flared Flared
Max.50m Max.50m
1. External static pressure at 130Pa
2. Ex-works at 70Pa(OPTION MOTOR: 130Pa)
3. External static pressure at 70Pa
4. Rating conditions < JIS B 8615, 8616> (INDOOR) Cooling: 27˚CDB, 19˚CWB Heating: 20˚CDB (OUTDOOR) Cooling: 35˚CDB Heating: 7˚CDB, 6˚CWB
5. Noise level: Sound pressure level
8
Item Function
Capacity Total input
Model name Power supply Input Running current Starting current External finish Heat exchanger Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure Booster heater
INDOOR UNIT
Operation control & Thermostat Noise level(Low-High) Cond.drain conn.O.D.
Dimensions
Weight Model name Power supply Input Running current Starting current External finish Refrigerant control Compressor Model Motor output Stater type Protection devices Heat exchanger Fan(drive) x No.
OUTDOOR UNIT
Fan motor output Airflow Defrost method Noise level
Dimensions
Weight Refrigerant Charge
Pipe size O.D.
PIPING
Connection method
REFRIGERANT
Between the indoor & outdoor unit
Model
44
Btu/h
W
kW
kW
A A
kW
CMM,(CFM)
Pa(mmAq)
kW
5
dB(A)
mm,(in)
W
D H
mm,(in) mm,(in) mm,(in) kg,(lbs)
kW
A A
kW
kW
CMM,(CFM)
dB(A)
W
D H
mm,(in) mm,(in) mm,(in) kg,(lbs)
kg,(lbs) Liquid mm,(in) Gas mm,(in)
Indoor side
Outdoor side
Height difference
Piping length
PEHD-6EK(H)SA.UK
Cooling
50,000 14,650
5.39
Heating 54,500 (64,700) 16,000 (19,000)
5.24 (8.24)
PEHD-6EK(H)SA.UK
~ /N,50Hz,220-240V
0.66
2.79
6.25
0.66 (3.66)
2.79 (15.24)
6.25 (18.75)
Galvanized sheets
Plate fin coil
Centrifugal (direct)x2
1
0.30
36.5-46 (1,280-1,620)
2
70(7) / 130(13) at Hi-notch
3.0
Remote control & Built-in
3
46-51
32 (1-1/4)
1,715 (67-1/2)
740 (29-1/8)
325 (12-13/16)
70(154) [ 73(161)]
PUH-6YKSA
2.UK
3N~ , 380/220-415/240V, 50Hz
4.73
7.74 74
4.58
7.50 74
Munsell 5Y7/1 Capillary tube
Hermetic
ZR68KC-TFD
4.0
Line start
Internal thermostat, Anti-phase protector, Thermal switch, HP switch
Plate fin coil
Propeller(direct)x 2
0.10+ 0.10 100 (3530)
Reverse cycle
56
970 (38-3/16)
345+ 24 (13-9/16 and 1)
1,258 (49-1/2)
117 (258)
R-22
5.0 (11.0)
9.52 (3/8)
19.05 (3/4)
Flared
Flared Max.50m Max.50m
1. External static pressure at 130Pa2. Ex-works at 70Pa(OPTION MOTOR: 130Pa)3. External static pressure at 70Pa
4. Rating conditions < JIS B 8615, 8616>
(INDOOR) Cooling: 27˚CDB, 19˚CWB Heating: 20˚CDB (OUTDOOR) Cooling: 35˚CDB Heating: 7˚CDB, 6˚CWB
5. Noise level: Sound pressure level
9
4
DA T A
Service Ref.
Indoor
intake air
WB˚C
20 25 30 35 40 45
CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
14,782 4.32 14,372 4.50 13,844 4.86 13,273 5.20 12,731 5.55 12,116 5.90 15,734 4.40 15,324 4.60 14,767 4.96 14,177 5.33 13,581 5.69 12,951 6.05 16,701 4.49 16,305 4.68 15,734 5.07 15,119 5.45 14,489 5.84 13,844 6.24 17,683 4.58 17,346 4.78 16,745 5.17 16,115 5.58 15,456 6.00 14,782 6.44
16 18 20 22
1. PERFORMANCE DATA
1) COOLING CAPACITY
Note C A: Capacity(W)
P.C.: Power consumption(kW)
PEHD-6EK(H)SA.UK
Service Ref.
PEHD-6EK(H)SA.UK
Refrigerant piping length(one way)
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
1.00 0.975 0.955 0.935 0.918 0.900 0.884 0.869 0.855 0.840
Cooling capacity correction factors
Service Ref. -10 -5 0 5 10 15
10,957 3.58 12,557 3.95 14,313 4.35 16,220 4.78 18,277 5.22 20,480 5.69 10,492 3.85 12,064 4.26 13,773 4.69 15,616 5.14 17,590 5.63 19,695 6.13 10,083 4.09 11,574 4.54 13,227 5.01 15,037 5.51 17,006 6.03 19,131 6.58
15 20 25
2) HEATING CAPACITY
Indoor
intake air
WB˚C
Outdoor intake air DB˚C
PEHD-6EK(H)SA.UK
CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
Note C A : Capacity(W)
P.C.: Power consumption(kW)
Service Ref.
PEHD-6EK(H)SA.UK
Refrigerant piping length(one way)
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
1.00 1.00 1.00 1.00 1.00 1.00 0.998 0.995 0.993 0.990
Heating capacity correction factors
PEHD-3EK(H)A3.UK
PEHD-4EK(H)SA
3.UK
PEHD-5EK(H)SA
3.UK
7,839 2.87 7,623 3.00 7,315 3.21 6,984 3.43 6,637 3.64 6,283 2.9016 8,339 2.94 8,124 3.06 7,792 3.29 7,454 3.51 7,099 3.74 6,738 3.1018 8,847 2.98 8,639 3.11 8,301
8,832 9,215
3.35 7,946 3.60 7,585 3.83 7,215 3.3320 9,363 3.04 9,186 3.18 3.43 8,470 3.68 8,100 3.94 7,715 3.5622 9,875 3.09 9,603 3.23 3.46 8,798 3.69 8,361 3.92 7,915 3.1116 10,505 3.16 10,234 3.29 9,816 3.54 9,390 3.78 8,943 4.02 8,488 3.3418 11,145 3.20 10,883 3.34 10,457 3.61 10,010 3.87 9,555 4.12 9,089 3.5820 11,795 3.26 11,572 3.41 11,126 3.69 10,670 3.96 10,204 4.24 9,719 3.8322 12,623 3.92 12,276 4.10 11,780 4.39 11,247 4.68 10,689 4.98 10,118 3.9616 13,429 4.01 13,083 4.18 12,549 4.49 12,003 4.80 11,433 5.11 10,851 4.2518 14,247 4.07 13,913 4.25 13,367 4.58 12,797 4.91 12,215 5.24 11,619 4.5420 15,078 4.15 14,793 4.34 14,223 4.68 13,640 5.03 13,045 5.38 12,425 4.8622
PEHD-3EK(H)A3.UK PEHD-4EK(H)SA
3.UK
PEHD-5EK(H)SA
3.UK
PEHD-3EK(H)A
3.UK
PEHD-4EK(H)SA
3.UK
PEHD-5EK(H)SA
3.UK
1.00 0.981 0.968 0.952 0.940 0.925 0.913 0.900 0.886 0.874
1.00 0.989 0.980 0.970 0.960 0.950 0.940 0.930 0.920 0.910
1.00 0.981 0.968 0.952 0.940 0.925 0.913 0.900 0.886 0.874
6,245 2.35 7,128 2.59 8,091 2.84 9,136 3.10 10,251 3.38 11,439 4.3715 5,975 2.53 6,849 2.78 7,786 3.05 8,793 3.34 9,865 3.64 11,007 4.2020 5,751 2.69 6,570 2.97 7,479 3.27 8,469 3.57 9,540 3.90 10,683 4.0925 7,217 2.60 8,237 2.86 9,350 3.14 10,557 3.43 11,846 3.74 13,218 4.8415 6,905 2.81 7,914 3.08 8,997 3.38 10,161 3.70 11,399 4.03 12,719 4.6620 6,646 2.98 7,592 3.29 8,642 3.62 9,786 3.96 11,024 4.32 12,345 4.5225 9,646 3.28 11,009 3.60 12,497 3.96 14,110 4.32 15,833 4.72 17,666 6.1015 9,229 3.53 10,577 3.88 12,025 4.26 13,581 4.66 15,235 5.08 16,999 5.8720 8,883 3.76 10,147 4.15 11,550 4.56 13,079 4.99 14,734 5.44 16,500 5.7025
PEHD-3EK(H)A3.UK PEHD-4EK(H)SA
3.UK
PEHD-5EK(H)SA
3.UK
1.00 1.00 1.00 1.00 1.00 1.00 0.998 0.995 0.993 0.990
1.00 1.00 1.00 1.00 1.00 1.00 0.998 0.995 0.993 0.990
1.00 1.00 1.00 1.00 1.00 1.00 0.998 0.995 0.993 0.990
10
2. PERFORMANCE CURVE PEHD-3EK(H)A
3.UK
PEHD-4EK(H)SA
3.UK
PEHD-5EK(H)SA
3.UK
PEHD-6EK(H)SA.UK
Cooling
1.4
1.2
1
0.8
0.6
1.4
1.2
1
0.8
0.6
0.4
1.4
1.2
1
0.8
0.6
1.4
1.2
1
0.8
0.6
0.4
22 20 18 16
22 20 18 16
INDOOR WB
(˚C)
INDOOR WB
(˚C)
INDOOR DB
(˚C)
INDOOR DB
(˚C)
CAPACITY(RATIO)
CAPACITY(RATIO)
TOTAL INPUT(RATIO)
TOTAL INPUT(RATIO)
OUTDOOR DB
(˚C)
OUTDOOR WB
(˚C)
-12 -10 -5 0 5 10 15
-5 5 15 25 35 46
Heating
15 20 25
25 20 15
3. FAN PERFORMANCE AND CORRECTED AIR FLOW
11
PEHD-3EK(H)A3.UK
Fan performance <130pa>
Recommended range
200 180 160 140 120 100
=
80
(1Pa 0.1mmAg)
60
Extemal static pressure (Pa)
40 20
12 16 20 24 28 32
Air flow
Corrected Air Flow
Cooling
1.1
Lo
Hi
(CMM)
Capacity Input
1.3
1.2
Fan performance <70pa>
Recommended range
180 160
140 120 100 80
=
60
(1Pa 0.1mmAg)
40 20
Extemal static pressure (Pa)
12 16 20 24 28 32
Air flow
Heating
Lo
Hi
(CMM)
1.0
0.9
Correction factor
0.8
12 16 20 24 28 32
Air flow (CMM)
PEHD-4EK(H)SA3.UK
Fan performance <130pa>
Recommended range
200 180 160 140 120 100
=
80
(1Pa 0.1mmAg)
60
Extemal static pressure (Pa)
40 20
Corrected Air Flow
Lo
26 28 30 32 34 36 38 40
Air flow
Cooling
1.1
Hi
(CMM)
Correction factor
Capacity Input
1.1
1.0
0.9
0.8 12 16 20 24 28 32
Air flow (CMM)
Fan performance <70pa>
Recommended range
220 200 180 160
140 120 100
=
80
(1Pa 0.1mmAg)
60
Extemal static pressure (Pa)
40 20
24 26 28 30 32 34 36 38
1.2
1.1
Lo
Air flow
Heating
Hi
(CMM)
1.0
0.9
Correction factor
0.8 24 26 28 30 32 34 36 38 40
Air flow (CMM)
1.0
0.9
Correction factor
0.8 24 26 28 30 32 34 36 38 40
Air flow (CMM)
12
PEHD-5EK(H)A3.UK
Fan performance <130pa>
= (1Pa 0.1mmAg)
Extemal static pressure (Pa)
Recommended range
220 200 180 160
140 120 100 80 60 40 20
Lo
Hi
Fan performance <70pa>
Recommended range
220 200 180 160
140 120 100
=
80
(1Pa 0.1mmAg)
60
Extemal static pressure (Pa)
40 20
Lo
Hi
32 34 36 38 40 42 44 46 48
Air flow
Corrected Air Flow
Cooling
1.1
1.0
0.9
Correction factor
0.8 32 34 36 38 40 42 44 46 48
PEHD-6EK(H)SA.UK
Fan performance <130pa>
=
(1Pa 0.1mmAg)
Extemal static pressure (Pa)
Recommended range
220
200 180
160 140 120 100 80 60 40 20
Lo
38 40 42 44 46 48 50
36
Air flow
(CMM)
Air flow (CMM)
(CMM)
Hi
52
Capacity Input
32 34 36 38 40 42 44 46
Air flow
Heating
1.2
1.1
1.0
0.9
Correction factor
0.8 32 34 36 38 40 42 44 46 48
(CMM)
Fan performance <70pa>
Recommended range
200 180
160 140 120 100
=
80
(1Pa 0.1mmAg)
60 40
Extemal static pressure (Pa)
20
Lo
36
38 40 42 44 46 48
Air flow
Air flow (CMM)
Hi
50
(CMM)
Corrected Air Flow Capacity
Cooling
1.1
1.0
0.9
Correction factor
0.8 36 38 40 42 44 46
Air flow (CMM)
Input
48 50
52
Heating
1.2
1.1
1.0
0.9
Correction factor
0.8 36 38 40 42 44 46
Air flow (CMM)
48
50 52
13
4. ELECTRICAL DATA
Models
Indoor
Outdoor Mode Capacity(W) Total input(kW)
Input(kW) Current(A) Starting current(A) Input(kW) Current(A) Starting current(A)
IndoorOutdoor
PUH-6YKSA
PEHD-6EK(H)SA.UK
Cool
14,300
5.20
0.56
2.59
5.75
4.64
8.10 68
Heat
15,800
(18,300)
5.12
(7.62)
0.56
(3.06)
2.59
(13.91)
5.75
(17.11)
4.56
7.96 68
Indoor ······220V 50Hz 1phase Outdoor ···220/380V 50Hz 1/3phases
Models
Indoor
Outdoor Mode Capacity(W) Total input(kW)
Input(kW) Current(A) Starting current(A) Input(kW) Current(A) Starting current(A)
IndoorOutdoor
PUH-6YKSA
PEHD-6EK(H)SA.UK
Cool
14,500
5.30
0.61
2.69
6.00
4.69
7.87 71
Heat
15,900
(18,600)
5.18
(7.88)
0.61
(3.31)
2.69
(14.37)
6.00
(17.74)
4.57
7.67 71
Indoor ······230V 50Hz 1phase Outdoor···230/400V 50Hz 1/3phases
Models
Indoor
Outdoor Mode Capacity(W) Total input(kW)
Input(kW) Current(A) Starting current(A) Input(kW) Current(A) Starting current(A)
IndoorOutdoor
PUH-6YKSA
PEHD-6EK(H)SA.UK
Cool
14650
5.39
0.66
2.79
6.25
4.73
7.74 74
Heat
16000
(19000)
5.24
(8.24)
0.66
(3.66)
2.79
(15.24)
6.25
(18.75)
4.58
7.50 74
Indoor·······240V 50Hz 1phase Outdoor···240/415V 50Hz 1/3phases
PEHD-4EK(H)SA3.UKPEHD-3EK(H)A3.UK PEHD-5EK(H)SA3.UK
PUH-4YKSAPUH-4VKSAPUH-3YKA
PUH-5YKSA
PUH-3VKA
Cool
12,200
4.73
0.54
2.50
5.50
4.19
7.32 49
Heat
13,700
(16,200)
4.67
(7.17)
0.54
(3.04)
2.50
(13.82)
5.50
(16.86)
4.13
7.21 49
Cool HeatCool
9,500
3.87
0.52
2.41
2.93
3.35
16.90 79
Heat
10,200
(12,200)
3.87
(5.87)
0.52
(2.52)
2.41
(11.45)
2.93
(12.02)
3.35
16.90 79
9,500
3.69
0.52
2.41
2.93
3.17
5.29 37
10,200
(12,200)
3.68
(5.68)
0.52
(2.52)
2.41
(11.45)
2.93
(12.02)
3.16
5.28 37
Cool
7,500
3.43
0.30
1.39
1.74
3.13
14.67 54
Heat
8,900
(10,700)
3.22
(5.02)
0.30
(2.10)
1.39
(9.55)
1.74
(9.92)
2.92
13.68 54
Cool
7,500
3.43
0.30
1.39
1.74
3.13
5.23 34
Heat
8,900
(10,700)
3.22
(5.02)
0.30
(2.10)
1.39
(9.55)
1.74
(9.92)
2.92
4.88 34
PEHD-4EK(H)SA3.UKPEHD-3EK(H)A3.UK PEHD-5EK(H)SA3.UK
PUH-4YKSAPUH-4VKSAPUH-3YKA
PUH-5YKSA
PUH-3VKA
Cool
12,300
4.79
0.59
2.62
5.75
4.20
7.05 51
Heat
13,800
(16,500)
4.74
(7.44)
0.59
(3.29)
2.62
(14.30)
5.75
(17.49)
4.15
6.97 51
Cool
9,600
4.01
0.57
2.53
3.07
3.44
16.60 79
Heat
10,300
(12,500)
4.01
(6.21)
0.57
(2.77)
2.53
(12.64)
3.07
(12.64)
3.44
16.60 79
Cool
9,600
3.76
0.57
2.53
3.07
3.19
5.23 39
Heat
10,300
(12,500)
3.75
(5.95)
0.57
(2.77)
2.53
(12.64)
3.07
(12.64)
3.18
5.22 39
Cool
7,600
3.49
0.35
1.55
1.82
3.14
14.22 56
Heat
8,950
(10,850)
3.28
(5.18)
0.35
(2.25)
1.55
(9.78)
1.82
(10.08)
2.93
13.27 56
Cool
7,500
3.49
0.35
1.55
1.82
3.14
5.21 36
Heat
8,950
(10,850)
3.28
(5.18)
0.35
(2.25)
1.55
(9.78)
1.82
(10.08)
2.93
4.86 36
PEHD-4EK(H)SA3.UKPEHD-3EK(H)A3.UK PEHD-5EK(H)SA3.UK
PUH-4YKSAPUH-4VKSAPUH-3YKA
PUH-5YKSA
PUH-3VKA
Cool
12,400
4.85
0.64
2.72
6.00
4.21
6.89 53
Heat
13,900
(16,900)
4.80
(7.80)
0.64
(3.64)
2.72
(15.17)
6.00
(18.50)
4.16
6.81 53
Cool
9,700
4.14
0.62
2.64
3.20
3.52
16.30 79
Heat
10,400
(12,800)
4.14
(6.54)
0.62
(3.02)
2.64
(12.58)
3.20
(13.20)
3.52
16.30 79
Cool
9,700
3.82
0.62
2.64
3.20
3.20
5.24 40
Heat
10,400
(12,800)
3.81
(6.21)
0.62
(3.02)
2.64
(12.58)
3.20
(13.20)
3.19
5.22 40
Cool
7,700
3.55
0.40
1.70
1.90
3.15
13.82 58
Heat
9,000
(11,100)
3.34
(5.44)
0.40
(2.50)
1.70
(10.41)
1.90
(10.65)
2.94
12.89 58
Cool
7,700
3.55
0.40
1.70
1.90
3.15
5.16 37
Heat
9,000
(11,100)
3.34
(5.44)
0.40
(2.50)
1.70
(10.41)
1.90
(10.65)
2.94
4.81 37
14
5. STANDARD OPERATION DATA
5
REFRIGERANT SYSTEM DIAGRAM
Indoor unit
Indoor heat exchanger
Strainer
Restrictor valve
Thermistor TH2
Distributor with strainer
Capillary tube
PEHD-3(OD4.0xID2.0xL400) PEHD-4(OD4.0xID2.4xL550) PEHD-5(OD4.0xID2.4xL350) PEHD-6(OD4.0xID2.4xL300)
Refrigerant flow in cooling R.V.coil Refrigerant flow in heating Heating : ON Cooling : OFF
Unit : mm
PEHD-3EK(H)A3.UK PEHD-4EK(H)SA
3.UK
PEHD-5EK(H)SA
3.UK
PEHD-6EK(H)SA.UK
Models
Mode
TotalElectrical circuitRefrigerant circuit
Indoor side
Outdoor
side
SHF
BF
Capacity Input Indoor unit model Phase . Hz Volts Amperes Outdoor unit-model Phase,Hz Volts Amperes
W
kW
Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref.Pipe length
Intake air temperature
Intake air temperature
Discharge air temperature
MPa MPa
˚C ˚C ˚C
m
DB˚C
WB˚C
DB˚C DB˚C
WB˚C
PEHD-6EK(H)SA.UK
Cooling Heating
14,400 16,000
5.39 5.24
PEHD-6EK(H)SA
1 . 50
240
2.79 2.79 PUH-6YKSA
3.50 415
7.74 7.50
2.00 1.74
0.47 0.36
84.5 71.6
52.7
-
5.6 -2.3 55
27 20 19 15
14.2 40.1 35 7 24 6
0.77
-
0.11
-
Cooling Heating 12,400 13,900
4.85 4.80
PEHD-5EK(H)SA
1 . 50
240
2.72 2.72 PUH-5YKSA
3.50 415
6.89 6.81
1.88 1.70
0.51 0.37
75.8 74.3
48.8
-
6.8 55
27 20 19 15
15.1 37.0 35 7 24 6
0.85
-
0.13
-
Cooling Heating
7,700 9,000
3.55 3.34
PEHD-3EK(H)A
1 . 50
240
1.70 1.70
PUH-3YKA
3.50 415
5.16 4.81
2.00 1.84
0.45 0.34
86.3 81.7
52.1
-
4.8 -2.8 55
27 20 19 15
15.2 37.8 35 7 24 6
0.78
-
0.20
-
Cooling Heating
7,700 9,000
3.55 3.34
PEHD-3EK(H)A
1 . 50
240
1.70 1.70 PUH-3VKA
1.50 240
13.82 12.89
2.04 1.86
0.47 0.34
89.6 83.9
53.1
-
4.2 -3.8 55
27 20 19 15
15.3 37.8 35 7 24 6
0.78
-
0.21
-
Cooling Heating
9,700 10,400
3.82 3.81
PEHD-4EK(H)SA
1 . 50
240
2.64 2.64
PUH-4YKSA
3.50 415
5.24 5.22
1.86 1.70
0.53 0.38
77.7 74.3
49.2
-
7.6 -1.3 -1.7 55
27 20 19 15
15.8 36.1 35 7 24 6
0.80
-
0.22
-
Cooling Heating
9,700 10,400
4.14 4.14
PEHD-4EK(H)SA
1 . 50
240
2.64 2.64
PUH-4VKSA
1.50 240
16.30 16.30
1.88 1.71
0.49 0.36
83.3 80.1
51.5
-
7.5 -1.5 55
27 20 19 15
15.8 36.3 35 7 24 6
0.80
-
0.22
-
PEHD-4EK(H)SA3.UKPEHD-3EK(H)A3.UK PEHD-5EK(H)SA3.UK
15
6
OUTLINES & DIMENSIONS
1. INDOOR UNIT(PEHD-6)
210
12-ø3
450
450
140
282
680
3 3
30
319
261
181 40
30
A
C B 81
10
375
10
80
C B 81 A E 13
30
D
20
35
30
1053 169
307
113
122
12-ø3
(14x22)
Lifting bolt hole
45
163
323
308
44 75
7
6
5
13
Keep duct-work length 850mm or more. Be sure to apply the air filter (field supply) near the air inlet grille.
Service space:500 or more
81
365~465
197
81
50~150
55
Access door
Air outlet
Air inlet
3
1
2
4
Refrigerant piping flare connection (liquid ø9.52 copper tube) : HP Refrigerant piping flare connection (gas øF copper tube) : LP Drain 25A (male screw) Electrical parts box Electric Heater ··· Only PEHD-EKH(S)A Type Drain Pump (Option)
Drain Pipe (Option) ··· Use VP25 (O.D.ø32 PVC TUBE) )
Set
1 2 3 4 5 6 7
Model PEHD-3 PEHD-4·5 PEHD-6
A 1012 1252 1552
B 280 360 460
C 290 370 470
D 1070 1310 1610
E 1044 1284 1584
F
15.88
19.05
19.05
2. REMOTE CONTROLLER
Unit:mm (inch)
Rear side wiring arangement opening
46
83.5
130
18
120
PEHD-3EK(H)A3.UK PEHD-4EK(H)SA3.UK PEHD-5EK(H)SA
3.UK
PEHD-6EK(H)SA.UK
16
7
WIRING DIAGRAM
MODELS:PEHD-3EK(H)A3, PEHD-4EK(H)SA3, PEHD-5EK(H)SA3, PEHD-6EK(H)SA WIRING DIAGRAM
SW3SW5
OFF ON
WHT
YLW
BRN
AC10.8V
T
RED
BRN
WHT
2
1
DP
2
35
RED
ORN
MF
External static pressure 130Pa pressure 70Pa
BRN
41
C
X3X2X1 X6X5X4
M3
BLK
GRN/YLW
2
53
6
BLK
External static
TH2
65
CN2L LOSSNAY
CN21 PIPE
SW2
TH1
CN20 INTAKE
SW6
CN50 DRAIN
1122
2
4135
BLU
BLK
BLK
GRY
GRY
1
32
4
DS
RED
YLW
91043 1287564312431243 124321
CN4T TRANS
RED
AC14.5V
ORN
SW1
BRN
#········ Option parts
C CN1<R.B> CN2<R.B> CN2L<R.B> CN51<R.B> F<I.B> FS1,FS2
H
I.B LCD MF R.B SW1(I.B) SW2(I.B) SW3(I.B) SW5(I.B) SW6(I.B)
Capacitor (fan motor) Connector (program timer) Connector (remote switch) Connector (lossnay) Connector (centrally control) Fuse < 6.3 A > Thermal fuse(FS1:16A FS2:15A) Electric heater Indoor controller board Liquid crystal display Fan motor(with inner thermostat) Remote controller board Switch(mode selector) Switch(address selector) Switch(emergency operation) Switch(model selector)
Switch(model selector)
NOTES
1.Since the indoor transfomer(T) is connected with 240V power; if 220,230V power is used. Change the wiring connection
shown in fig: *1
When power supply is
fig: *1
230V 220V
240 YELLOW 230 ORANGE 220 RED
2. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
3. Indoor and outdoor connecting wires are made with palarities ensure wires match terminals.
4. Symbols used in circuit diagram above are, :Terminal block,
:connector, :PC board insertion tab.
5. Emergency operation If trouble occurs with either the remote controller or the indoor microcomputer and no other trouble exists,emer­gency operation for cooling or heating can be performed by changing the setting of dip switch(SW3<I.B>)on the indoor controller board (emergency dry operation is not possible).
SW1 (R.B) SW3 (R.B) SW4 (R.B) SW5 (R.B) SW6 (R.B) SW7 (R.B) SW8 (R.B) SW9 (R.B) SW10(R.B) SW14(R.B) SW15(R.B) SW17(R.B) T TB2
I.B CN24
HEATER
CN22
TO REMOCON
YLW
BLU
RED
8
88H1
8
88H2
3 3
88H2
88H1
7
7
5 5
PRP PRP
BRN ORN YLW
RED BLU
GRN/YLW
YLWYLW
M2
PNK
M1
M0
WHT
14
GRN/YLW
6
WHITE
ZNR
BLU
F
S
RED
CN30 OUTDOOR
R
CN51 CENTRALLY CONTROL
CN40 REMOCON POWER
4321321
MF
C
········ Only models PEHD-EKH(S)A
Switch (ON/OFF) Switch(cooling/drying operation mode) Switch(automatic operation mode) Switch(heating operation mode) Switch(lowers set temperature) Switch(raises set temperature) Switch(timer time) Switch(timer.continuous and ON/OFF) Switch(fan speed high/low selector) Switch(test run) Switch(inspection) Switch(address selector)
Transformer Terminal block (power)
[ Check items]
(1) Make sure that no other trouble exists with the outdoor unit.
Trouble with the outdoor unit prevents emergency operation.
(If any trouble exists with the outdoor unit,the trouble
location will be displayed on the remote controller and the trouble position will be shown on the outdoor contro­ller board LED.See electric circuit diagram of the outdoor unit for details.)
(2) Make sure that there is no trouble with the indoor fan.
Emergency operation will be a continuous run with operation by the power ON/OFF. (ON/OFFwith the remote controller is not possible).
[Emergency operation procedure ]
(1) Set the dip switch(SW3<I.B>)on the indoor controller board
to 1 · 2 · 3 on and 4 off for cooling, and 2 · 3 · 4
on and 1 off for heeting. (2)Turn on the outdoor unit side circuit breaker. (3) During emergency operation indoor fan runs at High speed. (4)Thermostat will not function.Cold air blows out for defrosting
during heating thus do not operate defrosting for a long time. (5) Emergency cooling should be limited to 10 hours maximum
(the indoor unit heat exchanger may freeze).
TB4 TB5,TB6 TH1 TH2 X1(I.B) X4(I.B) X5(I.B) X6(I.B) ZNR 26H
88H1
88H1
CN50 DP
#
DS
#
BLU
2 1
3 2 1
RED
TB5
TB4
TB2
L N
4 3 2 1
TRANSMISSION WIRES DC 12V
TO OUTDOOR UNIT CONNECTING WIRES DC 12V(polar)
BREAKER
POWER SUPPLY ~ (1phase) 220~ 240V 50Hz
PE
TO DUCT
CN2
213
LCD
CN1 SW17
546312
FS1
SW5
43 12567890
FS2
OFF ON
R.B TB6
26H
H
SW1
SW4
SW3
SW7
SW6
SW9
SW8
SW10
SW15 SW14
Terminal block (indoor/outdoor connecting line) Terminal block (remote controller transmission line)
Thermistor (room temperature sensor 0˚C/15k.25˚C/5.4k) Thermistor (pipe temperature sensor 0˚C/15k.25˚C/5.4k)
Auxiliary relay (drain pump) Auxiliary relay (fan motor) Auxiliary relay (fan motor) Auxiliary relay (fan motor) Varistor Thermal switch(over heat prevention) Contactor (electric heater) Contactor (electric heater) Drain sensor connector Drain pump Drain sensor
17
8
DISASSEMBLY INSTRUCTIONS
Disconnect the fan motor connecter (and the booster heater connector)
Drain pan catches (Hidden)
Drain pan catches (Hidden)
Filter
Bottom plate
Drain pan
Heat exchanger
Bottom plate assembly
1
2
A
Figure1.
11
. Removing the fan motor
1. Removing the 9 screws that fix the bottom plate A, and remove it.
2. Removing the drain pan as follows: (1) Remove the screw that fixes the drain pan. (2) Slide the drain pan in the direction 1, Figure1 and
unhook the drain pan catch near the drain pipe.
(3) Slide the drain pan in the direction 2, Figure1 and
unhook the 2 catches on the other side of the drain pipe.
3. Remove the 8 screws that fix the bottom plate assembly, and remove it.
4. Disconnect the fan motor connector from the controller box. (For the models with booster heater, disconnect the booster heater connector as well.)
5. Remove the fan plate as follow:
Figure2.
(1)Remove the 4 screws1 (2)Slide down the fan plate to remove.
6. Remove the sirocco fan setting screw and the motor fixture setting screw to remove the motor fixture. Remove the other motor fixture as well, and then remove the fan motor.
1
1
Fan base
18
Figure3.
Booster heater
Fan base
Sirocco fan
Sirocco fan
Housing assembly
Housing assembly
Piece
Piece
Leg
Bush
Bush
Motor
Motor base (Only PEHD-3)
22
. Removing the booster heater
1. Remove the bottom plate, drain pan, and bottom plate assembly. (Refer
1-1~3.)
2. Disconnect the booster heater connector from the controller box.
3. Remove the 2 lower screws on the both sides of the booster heater.
4. Loosen the 2 upper screws on the both sides of the booster heater.
5. Removing the booster heater.
Figure4.
Booster heater
Screw holes
19
Pump cover
33
. Removing the drain water lift-up pump
1. Remove the drain pan. (Refer 1- 2.)
2. Disconnect the drain pump connector and drain sensor connector from the controller box.
3. Remove the two screws of the pump cover assembly.
4. Remove the drain hose from drain socket.
5. Remove the three screws of the drain pump assembly.
6. Remove the earth screw and four nuts of the drain pump assembly.
7. Remove the drain pump from drain pump assembly.
Drain socket
assembly
Drain pump assembly
Drain hose
Rubber plug
Drain pan cover
1
2
Drain pan
20
9
PARTS LIST
14.15.16
1.2.3
11.12.13
4.5.6
7.8.9.10
No.
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
Part No. Part Name Drawing No.
Qt'y/set
Spec.
1
1
1
1
1
1
1111
11
1
1
1
1
W631101Z04
W631188G02
W264218G02
W631186G01
W630129G01
PEHD-
PEHD-
5EKHSA3
PEHD-
5EKSA
3
PEHD-
4EKHSA3
PEHD-
4EKSA
3
PEHD-
3EKHA
3
PEHD-
3EKA
3
6EKSA
PEHD-
6EKHSA
Bottom plate 1
Bottom plate 2 ass'y
W634030G01Bottom plate 2 ass'y
W634052G01Bottom plate 2 ass'y
W634028Z01Bottom plate 1
W634050Z01Bottom plate 1
H.EX.General ass'y
W258255G10H.EX.General ass'y
W258255G09H.EX.General ass'y
W258952G08H.EX.General ass'y
Drain pan ass'y
W634034G01Drain pan ass'y
W634056G01Drain pan ass'y
Filter
W611960G04
Filter
W611960G05
Filter
1111
11
1111
11
1111
11
11
11
11
PEHD-3EKA3.UK, PEHD-3EKHA3.UK PEHD-4EKSA
3.UK, PEHD-4EKHSA3.UK
PEHD-5EKSA
3.UK, PEHD-5EKHSA3.UK
PEHD-6EKSA.UK, PEHD-6EKHSA.UK EXTERNAL PARTS
21
PEHD-3EKA3.UK, PEHD-3EKHA3.UK PEHD-4EKSA
3.UK, PEHD-4EKHSA3.UK
PEHD-5EKSA
3.UK, PEHD-5EKHSA3.UK
PEHD-6EKSA.UK, PEHD-6EKHSA.UK BLOWER PARTS
3.4.5
8
15.16.17
18.19
9
2
10.11.12
21
13.14
6.7
6.7
1
2
8
1.20 9
No.
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20
21
Part No. Part Name Drawing No.
R60 508 131 R60 508 132
R61 766 104 R61 Y01 104
R61 Y20 221 R61 Y21 221 R61 Y17 221 R61 652 130
R61 Y04 262 R61 Y05 262 R61 Y06 262
R61 652 131
Piece
Piece
Fan base ass'y
Bush Sirocco fan Housing ass'y
Motor Motor support Leg
Heater ass'y 5
Capacitor 16 Attachment Motor base
R02K338H02 2 R02K338G82 W634058G01Fan base ass'y W634036G01Fan base ass'y W631187G01 W491760H02Bush W860050H02 W631126G01 W631120G01 P714661X01Motor P714659X01Motor P714614X01 W241060H03 W631122Z04 W258903G07Heater ass'y 3 W258903G08Heater ass'y 4 W258903G09 P412172X01Capacitor 6 P412223X01 W353715H01 W634069Z01
PEHD-
PEHD-
3EKHA
3EKA
3
11
22
22 22 11
11
1
22 11
PEHD-
4EKSA
4EKHSA3
3
3
11
22
11
11
11
Qt'y/set
PEHD-
1
PEHD-
PEHD-
5EKSA
3
5EKHSA3
2222
11
2222 2222 22
11
11
22
1
PEHD­6EKSA
2
1
2 2 2
1
1
2
PEHD-
6EKHSA
22222
with a nut
2
1
2
20-25L
2 2
<MF>150W,1Phase 220~ 240V <MF>240W,1Phase 220~ 240V <MF>250W,1Phase 220~ 240V
1
1
1
<C> <C>
2
: Not illustrated
22
PEHD-3EKA3.UK, PEHD-3EKHA3.UK PEHD-4EKSA
3.UK, PEHD-4EKHSA3.UK
PEHD-5EKSA
3.UK, PEHD-5EKHSA3.UK
PEHD-6EKSA.UK, PEHD-6EKHSA.UK CONTROL BOX PARTS
4
10
5
8
6
7
No.
Part No. Part Name Drawing No.
1
R61978247 Terminalbed R61979247
2
R61435246
3 4 5 6 7 8 9
R61274215
10
Terminalbed Terminalbed Controller Transformer work DWG. Thermistor S Thermistor H Ferrite core Ferrite core Start relay
P436109X01 P436110X01 BA73S950H02 RG00C006G02 W855468G05 BG71V163H03 BG71V164H08 P419114X01 P419115X01 P421221X01
PEHD-
3EKA
3
PEHD-
3EKHA
PEHD-
4EKSA
3
PEHD-
4EKHSA3
3
Qt'y/set
PEHD­5EKSA
111111 111111 111111 111111 111111 111111 111111 111111
PEHD-
3
5EKHSA3
222
PEHD-
6EKSA
11111111 1 1 1 1
1 1 1 1
PEHD-
6EKHSA
< TB4 > < TB2 >
1
< TB5 >
1
< I.B >
1
<T>
1
< RT1 >
1
< RT2 >
1 1 1
LY1F< 88H1,2 >
2
2
1
9
3
Spec.
23
PEHD-3EKA3.UK, PEHD-3EKHA3.UK PEHD-4EKSA
3.UK, PEHD-4EKHSA3.UK
PEHD-5EKSA
3.UK, PEHD-5EKHSA3.UK
PEHD-6EKSA.UK, PEHD-6EKHSA.UK DRAIN WATER LIFT-UP PUMP PARTS
3
4
1.2
5
No.
Part No. Part Name Drawing No.
1 2 3 4 5
R61 E96 558
Drain pump-94 Cushion Drain socket ass'y Drain sensor ass'y Rubber plug
Qt'y/set
PEHD-
PEHD-
PEHD-
PEHD-
PEHD-
4EKHSA3
5EKSA
111111 444444 111111 111111 111111
3
3EKA
3
BG56J144G13 1 DB26F111H03 BB00P145G17 DE00H343G21 P312040X01
3
3
4EKSA
3EKHA
PEHD-
5EKHSA3
PEHD-
6EKSA
4 1 1 1
PEHD-
6EKHSA
1 4 1 1 1
Spec.
24
Part No. PAC-SC51PI-E PAC-SC52PI-E PAC-SC53PI-E PAC-SC54PI-E
5m 7m 10m 15mPipe length Pipe size OD Connection method
Liquid:/ø9.52 Gas:/ø19.05
Indoor unit:Flared Outdoor unit:Flared
1. REFRIGERANT PIPES
For model:PEHD-4EK(H)SA3.UK, PEHD-5EK(H)SA3.UK, PEHD-6EK(H)SA.UK
Note 1.How to connect refrigerant pipes.
Factory supplied optional piping contains refrigerant at above atmospheric pressure. As long as the connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow. If piping length exceeds 5m, an additional charge of refrigerant is needed.
Note 2.The following main parts are contained in the optional refrigerant piping kit.
Heat insulating cover, vinyl tapes, nipples, sleeve and flange(for wall hole), connecting cables,
Part No.
Model Name
PAC-SC32PTA
Program timer
2. TIMER
Part name Part No.
Program timer PAC-SC32PTA
Exterior dimensions(mm)
5-4/32X4-23/32X23/32(130X120X18mm) Installation Wall mount Type of clock Quartz Clock accuracy
±
50second/month at 25 ˚C
Display-Time Liquid crystal display
Liquid crystal display
Liquid crystal display Program cycle
-Timer setting unit
-Week
24 hours Timer setting unit 30 minutes No. of set points 48/day
2-1 Program timer specifications
Power rating
5V DC ± 5%(Supplied by Remote Controller)
2-2 Feature of program timer
(1) Daily timer function
Daily timer can be set in 30 minute units for up to 24 hours. Each unit can be set for unit ON, unit OFF, or setback operation.
(2) Setback operation(PAC-SK65PT)
Set back operation is useful for reducing running costs. e.g.AT a hotel with a 24-hour system
8:00~23:00 Cooling operation with set temperature at 26 ˚C
23:00~8:00 Setback operation with 2 degrees of setback As shown in the chart on the right, the set temperature rises 2 degrees automatically during the setback operation. When the setback operation ends, normal operation will begin.
(3) Weekly timer function
Daily timer function can apply to each day of the week.
10
OPTIONAL PARTS
28˚C
26˚C
8:00
Normai operation
8:00
Normai operation
23:00
Setback operation
Part No. PAC-05FFS-E PAC-07FFS-E PAC-10FFS-E PAC-15FFS-E
5m 7m 10m 15mPipe length Pipe size OD Connection method
Liquid:/ø9.52 Gas:/ø15.88
Indoor unit:Flared Outdoor unit:Flared
For model:PEHD-3EK(H)A3.UK
25
2-3 HOW to connect program timer
(1) Install the program timer next to the remote controller the same way as the remote is controller installed. (2) Connect the program timer and the remote controller with a 6-wire cable as shown in the figure below.
NOTE: While the program timer is connected to the remote controller, the 24
hour ON/OFF timer on the remote controller will not operate.
How to connect program timer(For PKH-2FKA
2
, 2.5/3/4FK(S)A1) (1) Install the program timer next to the remote controller the same way as the remote controller is installed. (2) Connect the program timer and the remote controller with a 5-wire cable as shown in the figure below.
NOTE: While the program timer is connected to the remote controller, the 24
hour ON/OFF timer on the remote controller will not operate.
2-4 Names and functions
<PAC-SC32PTA>
To Indoor unit
2.wire cable
Remote controller
Program timer
Connector CN 1Connector CN 1
6-wire cable
2.wire cable
Connector CN 1Connector CN 1
5-wire cable
To Indoor unit
1 2
3
ORN BRN
RED
3. TIMER ADAPTER
This adapter is needed for system control and for operation via external contacts. Adapter connection is described on page 25.
Part No. PAC-SA89TA-E
Used for selection of it. The day operation pattern set by PATTERN SETTING is to be applied in weekly day unit setting.
When SET is displayed, clock adjustment, change of weekly day, daily and weekly timer setting can be performed. When MONITOR is displayed, all switches except SET/MONITOR SW are invalidat-ed. This is normal status.
Used for week day setting.
Using this switch, select "MONITOR" or "SET" Mode.
"MONITOR" : Indicates the current
timer setting. All switches expect MODE SELECTOR SW are invalidated then. This is the normal status.
"SET" : Set to "SET" mode for clock
adjustment, charge or week day, daily and weekly timer setting.
During MONITOR status, current time is displayed. During Daily timer setting, time desired for timer set­ting is displayed.
Indicates the setting set back range.
24 hours is divided indo 48 blocks and each block represents 30 minutes. The block display consists of patterns.
Used for set back setting.
Set back can be done in the range of 1, 2, 4, 6, and 8˚C.
Used to specify the setting pattern.
Used for timer in 30 minute units.
Used for setting timer in day or week unit.
Pushing SW moves the week day light display in order of SMTW··· enabling the week day.
Used for adjustment of the current time. Push SW to advance the time. Each time the but-
ton is pushed the time advances by 1 minute, push­ing continuously advances by 1 minute at 0.5 sec­ond interval, and when the lower digit of minutes becomes 0, indication advances in 10 minute units. SW is used for reversing the time. Each time the button is pushed the time reverses by 1 min-ute, pushing continuously reverses the time by 1 minute at 0.5 second interval, and when the lower digit of minute becomes 0 indication reverses in 10 minute units.
WEEKLY TIMER SETTING DISPLAY CURRENT TIME DISPLAY
SET/MONITOR DISPLAY
WEEK DAY SETTING SW
MODE SELECTOR SW CLOCK ADJUSTMENT SW WEEKLY TIMER SW
DAILY TIMER SW
ON/SET BACK/ OFF SW
SET BACK SETTING SW
DAILY TIMER SETTING DISPLAY
SET BACK DISPLAY
26
5. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units.When using the PAC-805RC, the program timer adapter(PAC­825AD) is also needed.
5-1 Dimensions Unit:mm
4. MULTIPLE REMOTE CONTROLLER ADAPTER
This adapter is needed for remote indication(operation/check.)
Part No. PAC-SA88HA-E
117
117
12
113
113
56.5
23.5 11
8
Part No. PAC-805RC
5-2 Functions
"ENGAGED" indicator When this indicator is lit, transmisson is in progress and all swiches are inoperative.
switch This change-over switch governs the opera­tion of the accessory remote controller.
"DUAL" Instructions from both the accessory remote controller and the centralized remote controller are valid. (Priority given to the last instruction received.)
"CENTRAL" ON / OFF switching by the accessory remote controller is invalidate. Operation is controlled by the centralized remote con­troller only. Inital setting is "DUAL"
LCD Matrix display This display indicates the operational sta­tus of all connected units either by steady lighting or by flashing.
switch Operation ON / OFF switch.
buttons These buttons are used to designate the attached unit (s). (They designate the unit to be centrally controlled.)
•When group "00" is designated ; collec­tive ON/OFF instruction is sent to all units.
•When group "01" - "16" is designated; ON/OFF instruction is sent only to
the designated units.
switch This change-over switch is for the pro­gram timer. Use "ACTIVE" when a program timer is connected. Use "BYPASS" when a program timer is not connected.
Independent "DUAL / CENTRAL" and "ACTIVE / BYPASS" setting of all the groups is prossible. When the power supply to the centralized remote controller is cut due to power failure, all settings will return to the original "DUAL" and "BYPASS".
DUAL/CENTRAL
POWER ON/OFF
BACK AHEAD
ACTIVE/BYPASS
1 2 3 4 5
BRN RED ORN YLW GRN
non-polarity
27
5-3 Connection method
(1) Connection in the power supply cord.
1. Connect the power supply cord to the power supply terminal-block and fix in-place with a tie-wrap. Connect a single phase 200V AC(220, 230, 240V)to
AN
.
As Eis the GND terminal,be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap. Use a ø1.6 (AWG14)or above two-wire cable for the transmission line. CAUTION: Never connect the power supply cord to the transmission terminal-block.
TERMINAL-BLOCK FOR TRANSMISSION
TERMINAL-BLOCK OF POWER SUPPLY
Fuse(5A)
TRANSFORMER
Tie-wrap
Tie-wrap
Transmission
POWER SUPPLY
Wiring has to be changed when a 200,230 or 240V power is used.
(2) Connection method of centralized remote controller and power supply board.
1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable.
TO adaptor's terminal-block
TO adaptor's terminal-block
Non-polar two-wire cable
Power supply board box
Centralized remote controller
Power supply board
Dip swirch SW17
2. Wiring diagram
3. Be sure to set the maximum address number with the dipswitch SW17 on the centralized remote controller.
28
6. PROGRAM TIMER ADAPTER
This adapter is needed when a program timer(PAC-SK65PT)or a centralised remote controller(PAC-805RC)is used.
6-1 Parts included
6-2 Connection method
Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out the work.
Part No. PAC-825AD
1 ADAPTER ···································x1 2 3-core cable ·································· x1 2 3-core cable ·································· x1
2 4-core cable ·································· x1 2 5-core cable ·································· x1
Length:2m(6' 7")
Length:2m(6' 7")
Length:2m(6' 7" )
Length:2m(6' 7")
Fig. 1
TERMINAL-BLOCK FOR TRANSMISSION
Dip switch
SW 1
Transmission cord
TRANSFORMER
Fuse(5A)
TERMINAL-BLOCK FOR POWER SUPPLY
POWER SUPPLY CORD
Terminal block for transmission to program timer or centralized remote controller
Wiring has to be changed when 200V power supply is used.
POWER SUPPLY
Fig. 2
(1) Connections in the adapter box
1. Connect the power supply cord to the terminal-block and fix in-place with a tie-wrap. Connect a single phase 200V AC(220, 230, 240V) to AN
.
As E is the GND terminal, be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap(when a centralized
remote controller is being used).
CAUTION: Never connect the power supply cord to the transmission terminal-block.
(2) When the centralised remote controller is used, set the address number with the dipswitch SW1 of the program timer
adapter.
29
(3)Connections from adapter 6-3 Dimensions (Unit:mm)
Fig. 3
To program timer or centralized remote controller
Adaptor
200-240V AC
CN30 CN50
CN51
5-core cable3-core cable
Remote controller Indoor unit
Maximum length of each cable is 10m.
Fig. 4
40
80
40 27
4 Fixing screw holes
5.5
95
200
22
22
35
86 70
230
15 15
18
15
27
35
65
3
holes
hole
7. OPTIONAL REMOTE CONTROLLER
This is for the control using two remote controllers.
Part No. PAC-JH050KA
Applied model
PEHD-3EK(H)A.UK
4/5/6 EK(H)SA
Rear side wiring arangement opening.
130
18
120
46
83.5
30
8. OPTIONAL MOTOR
The external static pressure of 130Pa allows long ducts to be used more extensively to enable the most convenient positioning of indoor units.
9. DRAIN WATER LIFT-UP MECHANISM
This allows more versatility when selecting drain piping layouts.
Part No. PAC-SK005MT-F
PAC-SK004MT-F
PAC-SK003MT-F
PEHD-3EK(H)A
3
.UK
PEHD-4EK(H)SA
3
.UK
PEHD-5EK(H)SA
3
.UK, PEHD-6EK(H)SA.UK
Applied model
Part No. PAC-SK002DM-F
PEHD-3EK(H)A
3
.UK, PEHD-4EK(H)SA3.UK, PEHD-5EK(H)SA3.UK, PEHD-6EK(H)SA.UK
Applied model
HEAD OFFICE MITSUBISHI DENKI BLDG. MARUNOUCHI TOKYO100 TELEX J24532 CABLE MELCO TOKYO
MEE 99K002 Issued in June. 1999 Printed in Japan
New publication, effective June. 1999 Specifications subject to change without notice.
TM
Loading...