Mitsubishi PEHD-3EKA3.UK, PEHD-4EKSA3.UK, PEHD-5EKSA3.UK, PEHD-6EKSA.UK, PEHD-3EKHA3.UK Service Manual

...
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
ADVANCE AND EVER ADVANCING
TECHNICAL & SERVICE MANUAL
<indoor unit> Service ref.
Models
PEHD-3EKA3.UK PEHD-3EKHA
PEHD-4EKSA
PEHD-4EKHSA
PEHD-5EKSA
PEHD-5EKHSA
PEHD-6EKSA.UK PEHD-6EKHSA.UK
The Slim Line. From Mitsubishi Electric
TM
1. FEATURES ················································ 1
2. PART NAMES AND FUNCTIONS ············· 2
3. SPECIFICATIONS······································ 5
4. DATA··························································· 9
5. REFRIGERANT SYSTEM DIAGRAM ·······14
6. OUTLINES AND DIMENSIONS ················15
7. WIRING DIAGRAM ···································16
8. DISASSEMBLY INSTRUCTIONS ············ 17
9. PARTS LIST·············································· 20 10
. OPTIONAL PARTS··································· 24
CONTENTS
INDOOR UNIT
REMOTE CONTROLLER
This manual does not cover the following outdoor units. When servicing them, please refer to the service manual No.OC150A and this manual as a set.
PUH-3YKA
2.UK
PUH-3VKA
2.UK
PUH-4YKSA
2.UK
PUH-4VKSA
2.UK
PUH-5YKSA
2.UK
PUH-6YKSA
2.UK
1
1
FEATURES
1. NEXT GENERATION AIR-CONDITIONING VENTILATION INTERLOCKING SYSTEM "Mr.SLIM"+ "LOSSNAY"
Proper ventilation is important to improve the quality of indoor environments. It eliminates unclean air, which is not only unpleasant, but unhealthy. This "Mr.SLIM" + "LOSSNAY" ventilation interlocking system achieves high air quality with minimum energy consumption. LOSSNAY's unique total heat exchanger reduces heating and cooling expenses by about 25 percent annually(in comparison with our existing models). In addition, its mechanism of simultaneous forced air supply and exhaust enables it to deliver high quality air. Together, "Mr.SLIM" + "LOSSNAY" system makes next-generation air conditioning possible. This system is both people and environment friendly.
2. TOTALLY INVISIBLE INDOOR UNIT BEHIND THE CEILING
The totally hidden indoor unit that lies above the ceiling surface enables you to utilize full floor space while allowing for flexible interior design. This new feature is recommended for stores and offices where the user's own imagination is allowed to be incorporated.
3. MOST SUITABLE FOR SIMULTANEOUS TWO ROOM AIR CONDITIONING
Using air ducts for cooling/heating airflow that matches the structure and purpose of the room enables you to provide two air outlets for simultaneous cooling/heating of two rooms.
4. HIGH EXTERNAL STATIC PRESSURE(OPTION MOTOR)
The exceptional external static pressure of 130Pa allows long ducts to be used more extensively to achieve convenient location of indoor units.(STD:70Pa)
5. DRAIN WATER LIFT-UP MECHANISM(OPTION KIT)
This allows more versatility when selecting drain piping layouts.
air outlet air outlet
Air outlet duct
Air intake duct
air intake
lndoor unit
Remote controller
Models Cooling capacity / Heating capacity
Btu/h W
PEHD-3EK(H)A3 PEHD-4EK(H)SA
3
PEHD-5EK(H)SA
3
PEHD-6EK(H)SA
26,300/30,700(37,900) 33,100/35,500(43,700) 42,300/47,400(57,700) 50,000/54,500(64,700)
7,700/9,000(11,100)
9,700/10,400(12,800) 12,400/13,900(16,900) 14,650/16,000(19,000)
2
2
PART NAMES AND FUNCTIONS
6. ADVANCED MICROPROCESSOR
(1) Easy to use microprocessor
1) Ultra-thin remote controller
The streamlined, square controller is designed to blend well with any interior. Also, the sophisticated micro­processor allows you to easily carry out a wide range of operations.
2) Attractive liquid crystal display (LCD)
The unit's operation mode, set temperature, room temperature, timer setting, and fan speed are displayed on the remote controller's easy-to-read Liquid Crystal Display (LCD)
3) Convenient 24-hour ON-OFF timer
The timer switches Mr.SLIM on and off automatically at the time you set. Once the timer is set, the remaining time is shown on the LCD.
4) Self-diagnostic feature indicates faults instantly
If a problem occurs, the unit will stop operating and the set temperature indicator will change to a self-diagnostic indicator, which shows the location of the trouble. If the check switch is pressed twice, the unit stops operating and the check mode is initiated. The location of the most recent problem that was stored in the memory is displayed on the LCD. This is extremely useful for maintenance purposes.
5) Useful memory feature for storing instructions
The previous set value is memorized so that constant temperature control can be achieved. For example, if a power failure occurs, the temperature will not have to be re adjusted afterwards.
(2) Non-polar two-wire remote controller cable
The slim, non-polar, two-wire remote controller cable makes installation simple and trouble free. Also, the remote controller wire can be extended up to 500m.
(3) Automatic cooling/heating changeover operation
An automatic cooling and heating changeover operation system allows you to easily control comfortable year-round air conditioning. Once the desired temperature is set, unit operation switches automatically between cooling and heating, in accordance with the room temperature. In addition, the use of an outdoor unit fan speed controller allows cooling even when outdoor temperatures are as low as - 5˚C.
7. INNOVATIVE MICROPROCESSOR CONTROL SYSTEM
The most significant feature of PEHD-EK series is the advanced microprocessor control. The development of this system is due to the recent world-wide trend in the air conditioning of larger buildings. They are moving away from centralized duct systems to using individual split type units instead. There are a number of reasons for this change. First of all, the duct's costly and troublesome installation is eliminated. Second, the overall air conditioning balance is excellent in split type units. Lastly, the operation costs are low due to the flexible control of each unit. This system was developed exclusively by Mitsubishi Electric because of high demand. The microprocessor control makes individual control, group control, control using two remote controllers, and remote on/off and individual control possible without troublesome equipment modifications.
Indoor Unit
Air intake (sucks the air inside the room into the unit)
Air outlet
3
Remote controller
Once the operation of the unit is set, subsequent
operations can be performed only by pressing the ON/OFF button repeatedly.
Operation buttons
This switches between continu­ous operation and the timer operation.
Press this button to switch the cool, electronic dry (dehumidify) automatic and heat modes.
This sets the room tempera­ture. The temperature setting can be performed in 1˚C units. Setting range : Cool 19˚C to 30˚C Heat 17˚C to 28˚C
The model name of the remote controller is indicated.
This switches the horizontal fan motion ON and OFF.
(This button does not operate in this model)
Only press this button to per­form an inspection check or test operation. Do not use it for normal operation.
This resets the filter service indication display.
(This button dose not operate in this model.)
This adjusts the vertical angle of the ventilation.
(This button dose not operate in this model)
This switches between the operation and stop modes each time it is pressed. The lamp on this button lights dur­ing operation.
This sets / switches the current
time, start time and stop time.
This sets the ventilation fan speed.
button
button
TEMP button
button
CHECK-TEST RUN
button
FILTER button
button
ON/OFF button
button
button
4
Display
This indicates when the unit is controlled by optinal fea­tures such as central control type remote controller.
The current time, start time and stop time can be dis­played in tencecond intervals by pressing the time switch button. The start time or stop time is always displayed during the timer operation.
The selected fan speed is dis­played.
This indicates when the con­tinuous operation and time operation modes are set. It also displays the time for the timer operation at the same time as when it is set.
This indicates the operation mode.
This indicates when the stand by mode is set from the time the sleep operation starts until the heating air discharges.
This indicates when the de­frost operation is performed.
This indicates when a malfun­ction has occurred in the unit which should be checked.
This displays the selected set­ting temperature.
The temperature of the suc­tion air is displayed during operation. The display range is 8˚C to 39˚C. The display flashes 8˚C when the actual tempera­ture is less then 8˚C and flashes 39˚C when the actual temperature is greater then 39˚C.
This lamp lights during opera­tion, goes off when the unit stops and flashes when a mal­function occurs.
This display lights in the check mode or when a test operation is perfomed.
This lamp lights when electric­ity is supplied to the unit.
Caution
• Only the display lights whe the unit is stopped and power is supplied to the unit.
• When power is turned ON for the first time, the (CENTRAL CTRL) display appears to go off momentarily but this is not a malfunction.
• When the central control remote control unit, which is sold separately, is used the ON - OFF button,
button and TEMP button do not operate.
• "NOT AVAILABLE" is displayed when the button and button are pressed. This indicates that this room unit is not equipped with the fan direction adjustment function and the louver function.
CENTRALLY CONTROLLED display
display
OPERATION MODE
display
STANDBY display
DEFROST display
CHECK display
Display
display
display
display
Operation lamp
CHECK MODE TEST RUN
˚C
display
˚C
display
CLOCK
ON OFF
5
3
SPECIFICATION
Item Function
Capacity Total input
INDOOR UNIT
Model name Power supply
Starting current
Running current
Input
External finish Heat exchanger Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure Booster heater Operation control & Thermostat Noise level(Low-High) Cond.drain conn.O.D.
Dimensions
Weight
dB(A) mm,(in) mm,(in) mm,(in) mm,(in)
W
D H
kg,(lbs)
Model name Power supply Input Running current Starting current External finish Refrigerant control Compressor Model Motor output
kW
Protection devices
Stater type
Heat exchanger Fan(drive) x No. Fan motor output
kW
Airflow
CMM,(CFM) Defrost method Noise level
dB(A)
Dimensions
W
D H
mm,(in) mm,(in) mm,(in) kg,(lbs)
Weight Refrigerant
kg,(lbs)
Charge Pipe size O.D.
Connection method Between the indoor
& outdoor unit
Liquid mm,(in) Gas mm,(in)
Indoor side
Outdoor side
Height difference
Piping length
REFRIGERANT
PIPING
OUTDOOR UNIT
kW
A A
Btu/h
W
kW
kW
A A
kW
kW
CMM,(CFM)
Pa(mmAq)
Model
4 4
✻✻
✻ ✻ ✻
5
1
2
3
1. External static pressure at 130Pa
2. Ex-works at 70Pa(OPTION MOTOR: 130Pa)
3. External static pressure at 70Pa
4. Rating conditions <JIS B 8615, 8616> (INDOOR) Cooling: 27˚CDB, 19˚CWB Heating: 20˚CDB (OUTDOOR) Cooling: 35˚CDB Heating: 7˚CDB, 6˚CWB
5. Noise level: Sound pressure level
PEHD-3EK(H)A3.UK
Cooling
26,300
7,700
3.55
Cooling
26,300
7,700
3.55
Heating
PEHD-3EK(H)A
3.UK
~/N,50Hz, 220-240V
0.40
1.70
1.90
0.40 (2.50)
1.70 (10.41)
1.90 (10.65)
0.40
1.70
1.90
0.40 (2.50)
1.70 (10.41)
1.90 (10.65)
3N~, 380/220-415/240V, 50Hz~/N, 220-240V ,50Hz
Galvanized sheets
Plate fin coil
Centrifugal (direct)x2
0.15
20-25 (700-800)
70(7)/130(13) at Hi-notch
2.1
Remote control & Built-in
37-41
32 (1-1/4)
1,175 (46-1/8)
740 (29-1/8)
325 (12-13/16)
44 (97) [46 (101)]
PUH-3YKA
2PUH-3VKA2
3.15
13.82 58
2.94
12.89 58
3.15
5.16 37
2.94
4.81 37
Munsell 5Y7/1 Capillary tube
Hermetic
NH52VND NH52YDA
2.2 2.4 Line start
Plate fin coil
Propeller (direct)x2
0.085
50 (1764)
Reverse cycle
52
870 (34-1/4)
295+24 (11-5/8 add 1)
850 (33-7/16)
75 (165)
R-22
3.2 (7.1)
9.52 (3/8)
15.88 (5/8) Flared Flared
Max.50m Max.50m
Heating
30,700 (37,900)
9,000 (11,100)
3.34 (5.44)
30,700 (37,900)
9,000 (11,100)
3.34 (5.44)
V: Inner thermostat,HP switch Y: Reversed-phase protector, Thermal relay, Thermal switch, HP switch
6
Item Function
Capacity Total input
Model name Power supply Input Running current Starting current External finish Heat exchanger Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure Booster heater
INDOOR UNIT
Operation control & Thermostat Noise level(Low-High) Cond.drain conn.O.D.
Dimensions
Weight Model name Power supply Input Running current Starting current External finish Refrigerant control Compressor Model Motor output Stater type
Protection devices Heat exchanger
Fan(drive) x No.
OUTDOOR UNIT
Fan motor output Airflow Defrost method Noise level
Dimensions
Weight Refrigerant Charge
Pipe size O.D.
PIPING
Connection method
REFRIGERANT
Between the indoor & outdoor unit
Model
Cooling
✻ ✻
W
kW
4
Btu/h
4
kW
A A
kW
33,100
9,700
4.14
0.62
2.64
3.20
1
CMM,(CFM)
Pa(mmAq)
2
kW
✻✻
dB(A)
5
3
mm,(in)
W
D H
mm,(in) mm,(in) mm,(in) kg,(lbs)
~/N, 220-240V, 50Hz
kW
A A
3.52
16.30 79
kW
V: Inner thermostat, HP switch Y: Reversed-phase protector, Thermal relay, Thermal switch, HP switch
kW
CMM,(CFM)
dB(A)
W
D H
mm,(in) mm,(in) mm,(in) kg,(lbs)
kg,(lbs) Liquid mm,(in) Gas mm,(in)
Indoor side
Outdoor side
Height difference
Piping length
PEHD-4EK(H)SA3.UK
Heating
35,500 (43,700)
10,400 (12,800)
4.14 (6.54) PEHD-4EK(H)SA
Cooling
33,100
9,700
3.82
3.UK
~/N, 50Hz, 220-240V
0.62 (3.02)
2.64 (12.58)
3.20 (13.2)
0.62
2.64
3.20
Galvanized sheets
Plate fin coil
Centrifugal (direct)x2
0.27
27-34 (950-1200)
70(7) / 130(13) at Hi-notch
2.4
Remote control & Built-in
41-46
32 (1-1/4)
1,415 (55-11/16)
740 (29-1/8)
325 (12-13/16)
62 (137) [65(143)]
PUH-4VKSA2
3N~, 380/220-415/240V, 50Hz
3.52
16.30
3.20
5.24
79
Munsell 5Y7/1 Capillary tube
Hermetic
NH56VNDT
2.7 .7 Line start
Plate fin coil
Propeller (direct) x2
0.065+0.065 95 (3350)
Reverse cycle
54
870 (34-1/4)
295+24 (11-5/8 and 1)
1258 (49-1/2)
94 (207)
R-22
4.2 (9.2)
9.52 (3/8)
19.05 (3/4) Flared Flared
Max.50m Max.50m
PUH-4YKSA
40
NH56YDA
Heating
35,500 (43,700) 10,400 (12,800)
3.81 (6.21)
0.62 (3.02)
2.64 (12.58)
3.20 (13.2)
2
3.19
5.22 40
1. External static pressure at 130Pa
2. Ex-works at 70Pa(OPTION MOTOR: 130Pa)
✻ ✻
3. External static pressure at 70Pa
4. Rating conditions <JIS B 8615, 8616>
(INDOOR) Cooling: 27˚CDB, 19˚CWB Heating: 20˚CDB (OUTDOOR) Cooling: 35˚CDB Heating: 7˚CDB, 6˚CWB
5. Noise level: Sound pressure level
7
Item Function
Capacity Total input
Model name Power supply Input Running current Starting current External finish Heat exchanger Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure Booster heater
INDOOR UNIT
Operation control & Thermostat Noise level(Low-High) Cond.drain conn.O.D.
Dimensions
Weight Model name Power supply Input Running current Starting current External finish Refrigerant control Compressor Model Motor output Stater type Protection devices Heat exchanger Fan(drive) x No.
OUTDOOR UNIT
Fan motor output Airflow Defrost method Noise level
Dimensions
Weight Refrigerant Charge
Pipe size O.D.
PIPING
Connection method
REFRIGERANT
Between the indoor & outdoor unit
Model
✽ ✽
Btu/h
4 4
W
kW
kW
A A
kW
CMM,(CFM)
Pa(mmAq)
kW
dB(A)
5
mm,(in)
W
D H
mm,(in) mm,(in) mm,(in)
kg,(lbs)
kW
A A
kW
kW
CMM,(CFM)
dB(A)
W
D H
mm,(in) mm,(in) mm,(in)
kg,(lbs)
kg,(lbs) Liquid mm,(in) Gas mm,(in)
Indoor side
Outdoor side
Height difference
Piping length
PEHD-5EK(H)SA3.UK
Cooling
42,300 12,400
4.85 PEHD-5EK(H)SA
3.UK
Heating
47,400 (57,700) 13,900 (16,900)
4.80 (7.80)
~/N, 50Hz, 220-240V
0.64
2.72
6.00
0.64 (3.64)
2.72 (15.17)
6.00 (18.50)
Galvanized sheets
Plate fin coil
Centrifugal (direct)x2
1
0.30
33.5-42 (1180-1480)
2
70(7) /130(13) at Hi-notch
3.0
Remote control & Built-in
3
44-50
32 (1-1/4)
1,415 (55-11/16)
740 (29-1/8)
325 (12-13/16)
65(143) [68(150)]
PUH-5YKSA
2
3N~, 380/220-415/240V, 50Hz
4.21
6.89
53
4.16
6.81 53
Munsell 5Y7/1 Capillary tube
Hermetic
ZR-61K3-TFD
3.5
Line start
Internal thermostat, Anti-phase protector, Thermal switch, HP switch
Plate fin coil
Propeller(direct)x2
0.085+0.085 95 (3350)
Reverse cycle
55
970 (38-3/16)
345+24 (13-9/16 add 1)
1258 (49-1/2)
114 (251)
R-22
5.4 (11.9)
9.52 (3/8)
19.05 (3/4) Flared Flared
Max.50m Max.50m
1. External static pressure at 130Pa
2. Ex-works at 70Pa(OPTION MOTOR: 130Pa)
3. External static pressure at 70Pa
4. Rating conditions < JIS B 8615, 8616> (INDOOR) Cooling: 27˚CDB, 19˚CWB Heating: 20˚CDB (OUTDOOR) Cooling: 35˚CDB Heating: 7˚CDB, 6˚CWB
5. Noise level: Sound pressure level
8
Item Function
Capacity Total input
Model name Power supply Input Running current Starting current External finish Heat exchanger Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure Booster heater
INDOOR UNIT
Operation control & Thermostat Noise level(Low-High) Cond.drain conn.O.D.
Dimensions
Weight Model name Power supply Input Running current Starting current External finish Refrigerant control Compressor Model Motor output Stater type Protection devices Heat exchanger Fan(drive) x No.
OUTDOOR UNIT
Fan motor output Airflow Defrost method Noise level
Dimensions
Weight Refrigerant Charge
Pipe size O.D.
PIPING
Connection method
REFRIGERANT
Between the indoor & outdoor unit
Model
44
Btu/h
W
kW
kW
A A
kW
CMM,(CFM)
Pa(mmAq)
kW
5
dB(A)
mm,(in)
W
D H
mm,(in) mm,(in) mm,(in) kg,(lbs)
kW
A A
kW
kW
CMM,(CFM)
dB(A)
W
D H
mm,(in) mm,(in) mm,(in) kg,(lbs)
kg,(lbs) Liquid mm,(in) Gas mm,(in)
Indoor side
Outdoor side
Height difference
Piping length
PEHD-6EK(H)SA.UK
Cooling
50,000 14,650
5.39
Heating 54,500 (64,700) 16,000 (19,000)
5.24 (8.24)
PEHD-6EK(H)SA.UK
~ /N,50Hz,220-240V
0.66
2.79
6.25
0.66 (3.66)
2.79 (15.24)
6.25 (18.75)
Galvanized sheets
Plate fin coil
Centrifugal (direct)x2
1
0.30
36.5-46 (1,280-1,620)
2
70(7) / 130(13) at Hi-notch
3.0
Remote control & Built-in
3
46-51
32 (1-1/4)
1,715 (67-1/2)
740 (29-1/8)
325 (12-13/16)
70(154) [ 73(161)]
PUH-6YKSA
2.UK
3N~ , 380/220-415/240V, 50Hz
4.73
7.74 74
4.58
7.50 74
Munsell 5Y7/1 Capillary tube
Hermetic
ZR68KC-TFD
4.0
Line start
Internal thermostat, Anti-phase protector, Thermal switch, HP switch
Plate fin coil
Propeller(direct)x 2
0.10+ 0.10 100 (3530)
Reverse cycle
56
970 (38-3/16)
345+ 24 (13-9/16 and 1)
1,258 (49-1/2)
117 (258)
R-22
5.0 (11.0)
9.52 (3/8)
19.05 (3/4)
Flared
Flared Max.50m Max.50m
1. External static pressure at 130Pa2. Ex-works at 70Pa(OPTION MOTOR: 130Pa)3. External static pressure at 70Pa
4. Rating conditions < JIS B 8615, 8616>
(INDOOR) Cooling: 27˚CDB, 19˚CWB Heating: 20˚CDB (OUTDOOR) Cooling: 35˚CDB Heating: 7˚CDB, 6˚CWB
5. Noise level: Sound pressure level
9
4
DA T A
Service Ref.
Indoor
intake air
WB˚C
20 25 30 35 40 45
CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
14,782 4.32 14,372 4.50 13,844 4.86 13,273 5.20 12,731 5.55 12,116 5.90 15,734 4.40 15,324 4.60 14,767 4.96 14,177 5.33 13,581 5.69 12,951 6.05 16,701 4.49 16,305 4.68 15,734 5.07 15,119 5.45 14,489 5.84 13,844 6.24 17,683 4.58 17,346 4.78 16,745 5.17 16,115 5.58 15,456 6.00 14,782 6.44
16 18 20 22
1. PERFORMANCE DATA
1) COOLING CAPACITY
Note C A: Capacity(W)
P.C.: Power consumption(kW)
PEHD-6EK(H)SA.UK
Service Ref.
PEHD-6EK(H)SA.UK
Refrigerant piping length(one way)
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
1.00 0.975 0.955 0.935 0.918 0.900 0.884 0.869 0.855 0.840
Cooling capacity correction factors
Service Ref. -10 -5 0 5 10 15
10,957 3.58 12,557 3.95 14,313 4.35 16,220 4.78 18,277 5.22 20,480 5.69 10,492 3.85 12,064 4.26 13,773 4.69 15,616 5.14 17,590 5.63 19,695 6.13 10,083 4.09 11,574 4.54 13,227 5.01 15,037 5.51 17,006 6.03 19,131 6.58
15 20 25
2) HEATING CAPACITY
Indoor
intake air
WB˚C
Outdoor intake air DB˚C
PEHD-6EK(H)SA.UK
CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
Note C A : Capacity(W)
P.C.: Power consumption(kW)
Service Ref.
PEHD-6EK(H)SA.UK
Refrigerant piping length(one way)
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
1.00 1.00 1.00 1.00 1.00 1.00 0.998 0.995 0.993 0.990
Heating capacity correction factors
PEHD-3EK(H)A3.UK
PEHD-4EK(H)SA
3.UK
PEHD-5EK(H)SA
3.UK
7,839 2.87 7,623 3.00 7,315 3.21 6,984 3.43 6,637 3.64 6,283 2.9016 8,339 2.94 8,124 3.06 7,792 3.29 7,454 3.51 7,099 3.74 6,738 3.1018 8,847 2.98 8,639 3.11 8,301
8,832 9,215
3.35 7,946 3.60 7,585 3.83 7,215 3.3320 9,363 3.04 9,186 3.18 3.43 8,470 3.68 8,100 3.94 7,715 3.5622 9,875 3.09 9,603 3.23 3.46 8,798 3.69 8,361 3.92 7,915 3.1116 10,505 3.16 10,234 3.29 9,816 3.54 9,390 3.78 8,943 4.02 8,488 3.3418 11,145 3.20 10,883 3.34 10,457 3.61 10,010 3.87 9,555 4.12 9,089 3.5820 11,795 3.26 11,572 3.41 11,126 3.69 10,670 3.96 10,204 4.24 9,719 3.8322 12,623 3.92 12,276 4.10 11,780 4.39 11,247 4.68 10,689 4.98 10,118 3.9616 13,429 4.01 13,083 4.18 12,549 4.49 12,003 4.80 11,433 5.11 10,851 4.2518 14,247 4.07 13,913 4.25 13,367 4.58 12,797 4.91 12,215 5.24 11,619 4.5420 15,078 4.15 14,793 4.34 14,223 4.68 13,640 5.03 13,045 5.38 12,425 4.8622
PEHD-3EK(H)A3.UK PEHD-4EK(H)SA
3.UK
PEHD-5EK(H)SA
3.UK
PEHD-3EK(H)A
3.UK
PEHD-4EK(H)SA
3.UK
PEHD-5EK(H)SA
3.UK
1.00 0.981 0.968 0.952 0.940 0.925 0.913 0.900 0.886 0.874
1.00 0.989 0.980 0.970 0.960 0.950 0.940 0.930 0.920 0.910
1.00 0.981 0.968 0.952 0.940 0.925 0.913 0.900 0.886 0.874
6,245 2.35 7,128 2.59 8,091 2.84 9,136 3.10 10,251 3.38 11,439 4.3715 5,975 2.53 6,849 2.78 7,786 3.05 8,793 3.34 9,865 3.64 11,007 4.2020 5,751 2.69 6,570 2.97 7,479 3.27 8,469 3.57 9,540 3.90 10,683 4.0925 7,217 2.60 8,237 2.86 9,350 3.14 10,557 3.43 11,846 3.74 13,218 4.8415 6,905 2.81 7,914 3.08 8,997 3.38 10,161 3.70 11,399 4.03 12,719 4.6620 6,646 2.98 7,592 3.29 8,642 3.62 9,786 3.96 11,024 4.32 12,345 4.5225 9,646 3.28 11,009 3.60 12,497 3.96 14,110 4.32 15,833 4.72 17,666 6.1015 9,229 3.53 10,577 3.88 12,025 4.26 13,581 4.66 15,235 5.08 16,999 5.8720 8,883 3.76 10,147 4.15 11,550 4.56 13,079 4.99 14,734 5.44 16,500 5.7025
PEHD-3EK(H)A3.UK PEHD-4EK(H)SA
3.UK
PEHD-5EK(H)SA
3.UK
1.00 1.00 1.00 1.00 1.00 1.00 0.998 0.995 0.993 0.990
1.00 1.00 1.00 1.00 1.00 1.00 0.998 0.995 0.993 0.990
1.00 1.00 1.00 1.00 1.00 1.00 0.998 0.995 0.993 0.990
Loading...
+ 22 hidden pages