Mitsubishi PEFY-P-VMH-A Installation Manual

Air-Conditioners For Building Application INDOOR UNIT
PEFY-P-VMH-A
GB
D
F
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
MANUEL D’INSTALLATION
MANUAL DE INSTALA CIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il condizionatore d’aria.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert.
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado.
E°XEIPI¢IO O¢H°IøN E°KATA™TA™H™
°И· ·ЫК¿ПВИ· О·И ЫˆЫЩ‹ ¯Ъ‹ЫЛ, ·Ъ·О·ПВ›ЫЩВ ‰И·‚¿ЫВЩВ ЪФЫВ¯ЩИО¿ ·˘Щfi ЩФ ВБ¯ВИЪ›‰ИФ ВБО·Щ¿ЫЩ·ЫЛ˜ ЪИУ ·Ъ¯›ЫВЩВ ЩЛУ ВБО·Щ¿ЫЩ·ЫЛ ЩЛ˜ МФУ¿‰·˜ ОПИМ·ЩИЫМФ‡.
РУКОВОДСТВО ПО УСТАНОВКЕ
Для осторожного и правильного использования прибора необходимо тщательно ознакомиться с данным руководством по установке до выполнения установки кондиционера.
E
I
NL
P
GR
RU
TR
MONTAJ ELK‹TABI
Emniyetli ve do¤ru biçimde nas›l kullan›laca¤›n› ö¤renmek için lütfen klima cihaz›n› monte etmeden önce bu elkitab›n› dikkatle okuyunuz.
3
[Fig. 3.1.1]
3.1
[Fig. 3.1.2]
Type 40~140
Type 40~140
Type 200 · 250
700
70
C
100~200
450
F
G
23
380
JF
B
B
420
150~200
A
250
340
A
B
A Fan and motor removal door B Duct dimension
Type A B C D
B
340
PEFY-P40·50·63VMH-A 680 754 550 600 PEFY-P71·80VMH-A 930 1004 800 850 PEFY-P100·125·140VMH-A 1130 1204 1000 1050 PEFY-P200·250VMH-A 1250 1326 1100 1100
B
D
D
814
E
H
B
C A B
I
844
38 23
K
LL
30±10
Type 200 · 250
800
200~300
450
F
G
B
70
C
D
D
B Duct dimension C Electrical components case D Air inlet E Top of unit
1034
1067
60
23
470
H
B
C A B
I
38 23
K
30±10
F Access door G Servicing space H Air outlet I Hanging bolt spacing J Ceiling K 100 min. L 20 min.
LL
JF
4
4.1
[Fig. 4.1.1] [Fig. 4.1.2]
E
A Ceiling board B Edge beam C Tie beam
E
A
B
C
D
D Square timber for hanging the air
conditioner
E Pitch
F
G
Product Weight (kg)
Model name 40 50 · 63 71 · 80 100 · 125 · 140 200 · 250 PEFY-P-VMH 44 45 50 70 100
5
[Fig. 5.1.1] [Fig. 5.2.1]
[Fig. 5.1.2]
C
D
H
F Insert: 100 to 150 kg (1 piece)
(field supply)
G M10 hanging bolt (field supply) H Reinforcement
5.25.1
2
A Unit body B Lifting machine
A
D
B
C Nuts (field supply) D Washers E M10 Hanging bolt (field supply)
C
E
A Bottom of indoor unit
A
A
6
V
U
V
U
I
T
S
20
20
20
20
6.2
[Fig. 6.2.1]
A
[Fig. 6.3.1]
Type 40 - 140
A
E
A Thermal insulation tubing 1 B Caution:
Pull out the thermal insulation on the refrigerant piping at the site, insert the flare nut to flare the end, and replace the insulation in its original position.
Take care to ensure that condensation does not form on exposed copper piping.
C Liquid end of refrigerant piping D Gas end of refrigerant piping E Site refrigerant piping F Main body G Marked “GAS” H Marked “OUTSIDE” I Flared insulation (supplied) 2 J Marked “INSIDE”
B
C
D
77130
F
30
E
Type 40 - 140
92 200
343
Type 200 · 250
A Air inlet B Refrigerant piping (liquid) C Refrigerant piping (gas) D Control box E Drain outlet F Air outlet
6.3
B
K
C
D
F
K
J
G
H
I
N
M
L
P
O
E
QR
M
I
F
O
O
K Thermal insulation L Pull M Flare nut N Return to original position O Ensure that there is no gap here P Plate on main body Q Outside R Inside S Remove tape T Thermal insulation tubing (small) (supplied) 1 U Tie (large) (supplied) 4 V Ensure that there is no gap here. Place join upwards.
[Fig. 6.3.2]
Type 200 · 250
A
B
C
E
D
G
M
N
O
R
P
Q
F
I
J
K
20
20
K
H
E
L
20
J
20
O
S
T
A Thermal insulation tubing 1 B Caution:
Pull out the thermal insulation on the refrigerant piping at the site, braze the piping, and replace the insulation in its original position.
Tak e care to ensure that condensation does not f orm on exposed copper piping.
C Refrigerant piping (liquid) D Refrigerant piping (gas) E Main body F Thermal insulation tubing 2 G Site refrigerant piping H Ensure that there are no gaps between the insulation
and the main body.
I Thermal insulation tubing (small) (supplied) 1 J Ties (large) (supplied) 4 K Ensure that there is no gap here. Place join upwards. L Thermal insulation tubing (medium) (supplied) 2 M Cut N Release gas before removing the brazing. O Thermal insulation P Pull Q Flared pipe end R Wrap with damp cloth S Return to original position T Ensure that there is no gap here.
3
7
C C C
[Fig. 7.2.1]
A
B 1
7.2
E
D 2
A Downward slope 1/100 or more B Drain hose (Accessory) C Indoor unit D Collective piping E Maximize this length to approx. 10 cm
8
[Fig. 8.0.1]
A Air inlet B Air filter (supplied at site) C Duct D Canvas duct E Access door F Ceiling G Ensure sufficient length to prevent short cycling H Air outlet I Keep duct-work length 850 or more
9.3
[Fig. 9.3.1]
B
A Screws B Terminal box cover C Control box cover D Control box
B
A D
C
[Fig. 9.3.2]
C
BAE
A
D
9
9.1
[Fig. 9.1.1]
AB
DE
CCCCCCC
A Switch 16 A B Overcurrent protection 16 A C Indoor unit D Total operating current be less than 16 A E Pull box
9.2
[Fig. 9.2.1]
[Fig. 9.2.2]
L
B
M1M2 21
TB3
B
M1M2
TB3
1
B
N
DC10~13V
AB 12
E
AA
SM1M2 SM1M2
TB5 TB15 TB5 TB15
C
AA
SM1M2 SM1M2
TB5 TB5
A Terminal block for
indoor transmission cable
B Terminal block for
outdoor transmis­sion cable
C
C
C Remote controller
[Fig. 9.2.4][Fig. 9.2.3]
2
A
C
D
M1
DC24~30V
N
L
12
(A, B)
A Non-polarized B Upper level (TB15) C Remote Controller D Lower level (TB5)
21
C
M2
A
C
A To pre v ent external tensile force from applying to the wiring connection sec-
tion of power source terminal block use buffer bushing like PG connection or the like.
B Power source wiring C Tensile force D Use ordinary bushing E Transmission wiring
4
[Fig. 9.5.1]
ON
W254613G03 FP-AD-R
MADE IN JAPAN
1
JP1
3 2 1
SWCSWA
<Address board>
9.5
240V 220V
SW5
SW14
SW1
10
SW12
0
0
10
N0
N0
CN828161
SW11
1
CN62
0
JP2
JP3
JP4
Contents
1. Safety precautions ...................................................................................... 5
1.1. Before installation and electric work.......................................... 5
1.2. Precautions for devices that use R407C refrigerant.................. 5
1.3. Before getting installed.............................................................. 6
1.4. Before getting installed (moved) - electrical work...................... 6
1.5. Before starting the test run ........................................................ 6
2. Indoor unit accessories ............................................................................... 6
3. Selecting an installation site ....................................................................... 7
3.1. Installation and servicing space ................................................ 7
3.2. Combining indoor units with outdoor units ................................ 7
4. Fixing hanging bolts .................................................................................... 7
4.1. Fixing hanging bolts .................................................................. 7
5. Installing the unit ......................................................................................... 7
5.1. Hanging the unit body ............................................................... 7
5.2. Confirming the unit’s position and fixing hanging bolts ............. 7
6. Refrigerant pipe and drain pipe specifications ............................................ 8
1. Safety precautions
1.1. Before installation and electric work
s Before installing the unit, make sure you read all the “Safety
precautions”.
s The “Safety precautions” provide very important points re-
garding safety. Make sure you follow them.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided. : Indicates that important instructions must be followed. : Indicates a part which must be grounded. : Indicates that caution should be taken with rotating parts. (This symbol is
displayed on the main unit label.) <Color: yellow>
: Beware of electric shock (This symbol is displayed on the main unit label.)
<Color: yellow>
Warning:
Carefully read the labels affixed to the main unit.
6.1. Refrigerant pipe and drain pipe specifications .......................... 8
6.2. Refrigerant pipe, drain pipe and filling port................................ 8
6.3. Request for refrigerant piping connection ................................. 8
7. Connecting refrigerant pipes and drain pipes ............................................. 8
7.1. Refrigerant piping work ............................................................. 8
7.2. Drain piping work....................................................................... 9
8. Duct work .................................................................................................... 9
9. Electrical wiring ........................................................................................... 9
9.1. Power supply wiring ................................................................ 10
9.2. Connecting remote controller, indoor and outdoor
transmission cables................................................................. 10
9.3. Connecting electrical connections........................................... 10
9.4. Selecting the static pressure ................................................... 10
9.5. Setting addresses.................................................................... 10
9.6. Sensing room temperature with the built-in sensor in
a remote controller .................................................................. 10
• Have all electric work done by a licensed electrician according to “Elec­tric Facility Engineering Standard” and “Interior Wire Regulations”and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is performed im-
properly, electric shock and fire may result.
• Securely install the outdoor unit terminal cover (panel).
- If the terminal cover (panel) is not installed properly , dust or water may enter
the outdoor unit and fire or electric shock may result.
• When installing and moving the air conditioner to another site, do not charge the it with a refrigerant different from the refrigerant (R407C or R22) specified on the unit.
- If a different refrigerant or air is mixed with the original refrigerant, the refrig-
erant cycle may malfunction and the unit may be damaged.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to prevent the safety
limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
• When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
- If the air conditioner is installed improperly , water leakage , electric shock, or
fire may result.
• After completing installation work, make sure that refrigerant gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or
other heat source, it may generate noxious gases.
• Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted
and operated forcibly, or parts other than those specified by Mitsubishi Elec­tric are used, fire or explosion may result.
• To dispose of this product, consult your dealer.
GB
D
F
E
INL
Warning:
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage , electric shock, or fire.
• Install the air unit at a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down, resulting in injuries.
• Use the specified cables for wiring. Make the connections securely so that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
• Prepare for typhoons and other strong winds and earthquakes and in­stall the unit at the specified place.
- Improper installation may cause the unit to topple and result in injury.
• Always use an air c leaner, humidifier , electric heater, and other accesso­ries specified by Mitsubishi Electric.
- Ask an authorized technician to install the accessories. Improper installation
by the user may result in water leakage, electric shock, or fire.
• Never repair the unit. If the air conditioner must be repaired, consult the dealer.
- If the unit is repaired improperly, water leakage, electric shock, or fire may
result.
• Do not touch the heat exchanger fins.
- Improper handling may result in injury.
• If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a flame, poisonous gases will
be released.
• Install the air conditioner according to this Installation Manual.
- If the unit is installed improperly, water leakage, electric shock, or fire may
result.
1.2. Precautions for devices that use R407C refrigerant
Caution:
• Do not use the existing refrigerant piping.
- The old refrigerant and refrigerator oil in the existing piping contains a large amount of chlorine which may cause the refrigerator oil of the new unit to deteriorate.
• Use refrigerant piping made of C1220 (CU-DHP) phosphorus deoxidized copper as specified in the JIS H3300 “Copper and copper allo y seamless pipes and tubes”. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur , o xides, dust/dirt, shav­ing particles, oils, moisture, or any other contaminant.
- Contaminants on the inside of the refrigerant piping may cause the refriger-
ant residual oil to deteriorate.
• Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and
compressor trouble may result.
• Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
- The refrigerator oil will degrade if it is mixed with a large amount of mineral
oil.
• Use liquid refrigerant to fill the system.
- If gas refrigerant is used to seal the system, the composition of the refriger-
ant in the cylinder will change and performance may drop.
5
PGRRUTR
• Do not use a refrigerant other than R407C.
- If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerator oil to deteriorate.
• Use a vacuum pump with a reverse flow check valve.
- The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate.
• Do not use the following tools that are used with conventional refriger­ants. (Gauge manifold, charge hose, gas leak detector , reverse flow chec k valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment.)
- If the conventional refrigerant and refrigerator oil are mixed in the R407C,
the refrigerant may deteriorated.
- If water is mixed in the R407C, the refrigerator oil may deteriorate.
- Since R407C does not contain any chlorine, gas leak detectors for conven-
tional refrigerants will not react to it.
• Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.
• Be especially careful when managing the tools.
- If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deterio-
rate.
1.3. Before getting installed
Caution:
• Do not install the unit where combustible gas may leak.
GB
- If the gas leaks and accumulates around the unit, an explosion may result.
• Do not use the air conditioner where food, pets, plants, precision instru­ments, or artwork are kept.
- The quality of the food, etc. may deteriorate.
• Do not use the air conditioner in special environments.
D
- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of
the air conditioner or damage its parts.
• When installing the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
- The inverter equipment, private power generator, high-frequency medical
F
E
equipment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air condi­tioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
• Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80 % or when the drain pipe is clogged,
condensation may drip from the indoor unit. P erform collective drainage w ork together with the outdoor unit, as required.
• The indoor models should be installed the ceiling over than 2.5 m from floor.
INL
1.4. Before getting installed (moved) - elec-
trical work
Caution:
• Ground the unit.
- Do not connect the ground wire to gas or water pipes, lightning rods, or
telephone ground lines. Improper grounding may result in electric shock.
• Install the power cable so that tension is not applied to the cable.
- Tension may cause the cable to break and generate heat and cause a fire.
• Install an leak circuit breaker, as required.
- If an leak circuit breaker is not installed, electric shock may result.
• Use power line cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
• Use only a circuit breaker and fuse of the specified capacity.
- A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit failure or fire.
• Do not wash the air conditioner units.
- Washing them may cause an electric shock.
• Be careful that the installation base is not damaged by long use.
- If the damage is left uncorrected, the unit may fall and cause personal injury or property damage.
• Install the drain piping according to this Installation Manual to ensure proper drainage. Wrap thermal insulation around the pipes to prevent condensation.
- Improper drain piping may cause water leakage and damage to furniture
and other possessions.
• Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than 20 kg.
- Some products use PP bands for packaging. Do not use an y PP bands f or a
means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspend it at the specified positions on
the unit base. Also support the outdoor unit at four points so that it cannot slip sideways.
• Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts, may cause
stabs or other injuries.
- Tear apart and throw away plastic packaging bags so that children will not
play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
1.5. Before starting the test run
Caution:
• Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the main power switch can
result in severe damage to internal parts. Keep the power switch turned on during the operational season.
• Do not touch the switches with wet fingers.
- Touching a switch with wet fingers can cause electric shock.
• Do not touch the refrigerant pipes during and immediately after opera­tion.
- During and immediately after operation, the refrigerant pipes are may be hot
and may be cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes.
• Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
• Do not turn off the power immediately after stopping operation.
- Always wait at least five minutes before turning off the power. Otherwise,
water leakage and trouble may occur.
PGRRUTR
2. Indoor unit accessories
The unit is provided with the following accessories: Type 40 - 140 Type 200 · 250
No. Accessories Quantity
1 Insulation pipe (small) 1 2 Insulation cover 1 3 Tie band (small) 1 4 Tie band (large) 6 5 Drain hose 1 6 Washer 8 7 Insulation pipe (large) 1 8 Hose band 1 9 Attachment connector 2
6
No. Accessories Quantity
1 Insulation pipe (small) 1 2 Insulation pipe (medium) 1 3 Tie band (small) 1 4 Tie band (large) 6 5 Drain hose 1 6 Washer 8 7 Insulation pipe (large) 1 8 Hose band 1
Loading...
+ 12 hidden pages