Air-Conditioners For Building Application
INDOOR UNIT
PEFY-P-VMH-A
GB
D
F
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
MANUEL D’INSTALLATION
Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d’une utilisation correcte.
MANUAL DE INSTALA CIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il condizionatore d’aria.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert.
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado.
Для осторожного и правильного использования прибора необходимо тщательно ознакомиться с данным руководством по
установке до выполнения установки кондиционера.
E
I
NL
P
GR
RU
TR
MONTAJ ELK‹TABI
Emniyetli ve do¤ru biçimde nas›l kullan›laca¤›n› ö¤renmek için lütfen klima cihaz›n› monte etmeden önce bu elkitab›n› dikkatle okuyunuz.
C Nuts (field supply)
D Washers
E M10 Hanging bolt (field supply)
C
E
A Bottom of indoor unit
A
A
6
V
U
V
U
I
T
S
20
20
20
20
6.2
[Fig. 6.2.1]
A
[Fig. 6.3.1]
Type 40 - 140
A
E
A Thermal insulation tubing 1
B Caution:
Pull out the thermal insulation on the refrigerant piping at the site, insert the flare
nut to flare the end, and replace the insulation in its original position.
Take care to ensure that condensation does not form on exposed copper piping.
C Liquid end of refrigerant piping
D Gas end of refrigerant piping
E Site refrigerant piping
F Main body
G Marked “GAS”
H Marked “OUTSIDE”
I Flared insulation (supplied) 2
J Marked “INSIDE”
B
C
D
77130
F
30
E
Type 40 - 140
92200
343
Type 200 · 250
A Air inletB Refrigerant piping (liquid)
C Refrigerant piping (gas)D Control box
E Drain outletF Air outlet
6.3
B
K
C
D
F
K
J
G
H
I
N
M
L
P
O
E
QR
M
I
F
O
O
K Thermal insulation
L Pull
M Flare nut
N Return to original position
O Ensure that there is no gap here
P Plate on main body
Q Outside
R Inside
S Remove tape
T Thermal insulation tubing (small) (supplied) 1
U Tie (large) (supplied) 4
V Ensure that there is no gap here. Place join upwards.
[Fig. 6.3.2]
Type 200 · 250
A
B
C
E
D
G
M
N
O
R
P
Q
F
I
J
K
20
20
K
H
E
L
20
J
20
O
S
T
A Thermal insulation tubing 1
B Caution:
Pull out the thermal insulation on the refrigerant piping
at the site, braze the piping, and replace the insulation
in its original position.
Tak e care to ensure that condensation does not f orm on
exposed copper piping.
C Refrigerant piping (liquid)
D Refrigerant piping (gas)
E Main body
F Thermal insulation tubing 2
G Site refrigerant piping
H Ensure that there are no gaps between the insulation
and the main body.
I Thermal insulation tubing (small) (supplied) 1
J Ties (large) (supplied) 4
K Ensure that there is no gap here. Place join upwards.
L Thermal insulation tubing (medium) (supplied) 2
M Cut
N Release gas before removing the brazing.
O Thermal insulation
P Pull
Q Flared pipe end
R Wrap with damp cloth
S Return to original position
T Ensure that there is no gap here.
3
7
CCC
[Fig. 7.2.1]
A
B1
7.2
E
D2
A Downward slope 1/100 or more
B Drain hose (Accessory)
C Indoor unit
D Collective piping
E Maximize this length to approx. 10 cm
8
[Fig. 8.0.1]
A Air inletB Air filter (supplied at site)
C DuctD Canvas duct
E Access doorF Ceiling
G Ensure sufficient length to prevent short cycling
H Air outletI Keep duct-work length 850 or more
9.3
[Fig. 9.3.1]
B
A Screws
B Terminal box cover
C Control box cover
D Control box
B
AD
C
[Fig. 9.3.2]
C
BAE
A
D
9
9.1
[Fig. 9.1.1]
AB
DE
CCCCCCC
A Switch 16 AB Overcurrent protection 16 A
C Indoor unitD Total operating current be less than 16 A
E Pull box
9.2
[Fig. 9.2.1]
[Fig. 9.2.2]
L
B
M1M221
TB3
B
M1M2
TB3
1
B
N
DC10~13V
AB
12
E
AA
SM1M2SM1M2
TB5TB15 TB5TB15
C
AA
SM1M2SM1M2
TB5TB5
A Terminal block for
indoor transmission
cable
B Terminal block for
outdoor transmission cable
C
C
C Remote controller
[Fig. 9.2.4][Fig. 9.2.3]
2
A
C
D
M1
DC24~30V
N
L
12
(A, B)
A Non-polarized
B Upper level (TB15)
C Remote Controller
D Lower level (TB5)
21
C
M2
A
C
A To pre v ent external tensile force from applying to the wiring connection sec-
tion of power source terminal block use buffer bushing like PG connection
or the like.
B Power source wiring
C Tensile force
D Use ordinary bushing
E Transmission wiring
5. Installing the unit ......................................................................................... 7
5.1. Hanging the unit body ............................................................... 7
5.2. Confirming the unit’s position and fixing hanging bolts ............. 7
6. Refrigerant pipe and drain pipe specifications ............................................ 8
1. Safety precautions
1.1. Before installation and electric work
s Before installing the unit, make sure you read all the “Safety
precautions”.
s The “Safety precautions” provide very important points re-
garding safety. Make sure you follow them.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury
or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the
unit.
Symbols used in the illustrations
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
: Indicates that caution should be taken with rotating parts. (This symbol is
displayed on the main unit label.) <Color: yellow>
: Beware of electric shock (This symbol is displayed on the main unit label.)
<Color: yellow>
Warning:
Carefully read the labels affixed to the main unit.
6.1. Refrigerant pipe and drain pipe specifications .......................... 8
6.2. Refrigerant pipe, drain pipe and filling port................................ 8
6.3. Request for refrigerant piping connection ................................. 8
7. Connecting refrigerant pipes and drain pipes ............................................. 8
7.1. Refrigerant piping work ............................................................. 8
9.6. Sensing room temperature with the built-in sensor in
a remote controller .................................................................. 10
• Have all electric work done by a licensed electrician according to “Electric Facility Engineering Standard” and “Interior Wire Regulations”and
the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is performed im-
properly, electric shock and fire may result.
• Securely install the outdoor unit terminal cover (panel).
- If the terminal cover (panel) is not installed properly , dust or water may enter
the outdoor unit and fire or electric shock may result.
• When installing and moving the air conditioner to another site, do not
charge the it with a refrigerant different from the refrigerant (R407C or
R22) specified on the unit.
- If a different refrigerant or air is mixed with the original refrigerant, the refrig-
erant cycle may malfunction and the unit may be damaged.
• If the air conditioner is installed in a small room, measures must be taken
to prevent the refrigerant concentration from exceeding the safety limit
even if the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to prevent the safety
limit from being exceeded. Should the refrigerant leak and cause the safety
limit to be exceeded, hazards due to lack of oxygen in the room could result.
• When moving and reinstalling the air conditioner, consult the dealer or
an authorized technician.
- If the air conditioner is installed improperly , water leakage , electric shock, or
fire may result.
• After completing installation work, make sure that refrigerant gas is not
leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or
other heat source, it may generate noxious gases.
• Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted
and operated forcibly, or parts other than those specified by Mitsubishi Electric are used, fire or explosion may result.
• To dispose of this product, consult your dealer.
GB
D
F
E
INL
Warning:
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage , electric shock,
or fire.
• Install the air unit at a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down, resulting in injuries.
• Use the specified cables for wiring. Make the connections securely so
that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
• Prepare for typhoons and other strong winds and earthquakes and install the unit at the specified place.
- Improper installation may cause the unit to topple and result in injury.
• Always use an air c leaner, humidifier , electric heater, and other accessories specified by Mitsubishi Electric.
- Ask an authorized technician to install the accessories. Improper installation
by the user may result in water leakage, electric shock, or fire.
• Never repair the unit. If the air conditioner must be repaired, consult the
dealer.
- If the unit is repaired improperly, water leakage, electric shock, or fire may
result.
• Do not touch the heat exchanger fins.
- Improper handling may result in injury.
• If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a flame, poisonous gases will
be released.
• Install the air conditioner according to this Installation Manual.
- If the unit is installed improperly, water leakage, electric shock, or fire may
result.
1.2. Precautions for devices that use R407C
refrigerant
Caution:
• Do not use the existing refrigerant piping.
- The old refrigerant and refrigerator oil in the existing piping contains a large
amount of chlorine which may cause the refrigerator oil of the new unit to
deteriorate.
• Use refrigerant piping made of C1220 (CU-DHP) phosphorus deoxidized
copper as specified in the JIS H3300 “Copper and copper allo y seamless
pipes and tubes”. In addition, be sure that the inner and outer surfaces of
the pipes are clean and free of hazardous sulphur , o xides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
- Contaminants on the inside of the refrigerant piping may cause the refriger-
ant residual oil to deteriorate.
• Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing. (Store elbows and
other joints in a plastic bag.)
- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and
compressor trouble may result.
• Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator
oil to coat flares and flange connections.
- The refrigerator oil will degrade if it is mixed with a large amount of mineral
oil.
• Use liquid refrigerant to fill the system.
- If gas refrigerant is used to seal the system, the composition of the refriger-
ant in the cylinder will change and performance may drop.
5
PGRRUTR
• Do not use a refrigerant other than R407C.
- If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may
cause the refrigerator oil to deteriorate.
• Use a vacuum pump with a reverse flow check valve.
- The vacuum pump oil may flow back into the refrigerant cycle and cause the
refrigerator oil to deteriorate.
• Do not use the following tools that are used with conventional refrigerants.
(Gauge manifold, charge hose, gas leak detector , reverse flow chec k valve,
refrigerant charge base, vacuum gauge, refrigerant recovery equipment.)
- If the conventional refrigerant and refrigerator oil are mixed in the R407C,
the refrigerant may deteriorated.
- If water is mixed in the R407C, the refrigerator oil may deteriorate.
- Since R407C does not contain any chlorine, gas leak detectors for conven-
tional refrigerants will not react to it.
• Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.
• Be especially careful when managing the tools.
- If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deterio-
rate.
1.3. Before getting installed
Caution:
• Do not install the unit where combustible gas may leak.
GB
- If the gas leaks and accumulates around the unit, an explosion may result.
• Do not use the air conditioner where food, pets, plants, precision instruments, or artwork are kept.
- The quality of the food, etc. may deteriorate.
• Do not use the air conditioner in special environments.
D
- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of
the air conditioner or damage its parts.
• When installing the unit in a hospital, communication station, or similar
place, provide sufficient protection against noise.
- The inverter equipment, private power generator, high-frequency medical
F
E
equipment, or radio communication equipment may cause the air conditioner
to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical
treatment or image broadcasting.
• Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80 % or when the drain pipe is clogged,
condensation may drip from the indoor unit. P erform collective drainage w ork
together with the outdoor unit, as required.
• The indoor models should be installed the ceiling over than 2.5 m from
floor.
INL
1.4. Before getting installed (moved) - elec-
trical work
Caution:
• Ground the unit.
- Do not connect the ground wire to gas or water pipes, lightning rods, or
telephone ground lines. Improper grounding may result in electric shock.
• Install the power cable so that tension is not applied to the cable.
- Tension may cause the cable to break and generate heat and cause a fire.
• Install an leak circuit breaker, as required.
- If an leak circuit breaker is not installed, electric shock may result.
• Use power line cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
• Use only a circuit breaker and fuse of the specified capacity.
- A fuse or circuit breaker of a larger capacity or a steel or copper wire may
result in a general unit failure or fire.
• Do not wash the air conditioner units.
- Washing them may cause an electric shock.
• Be careful that the installation base is not damaged by long use.
- If the damage is left uncorrected, the unit may fall and cause personal injury
or property damage.
• Install the drain piping according to this Installation Manual to ensure
proper drainage. Wrap thermal insulation around the pipes to prevent
condensation.
- Improper drain piping may cause water leakage and damage to furniture
and other possessions.
• Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than 20 kg.
- Some products use PP bands for packaging. Do not use an y PP bands f or a
means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspend it at the specified positions on
the unit base. Also support the outdoor unit at four points so that it cannot
slip sideways.
• Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts, may cause
stabs or other injuries.
- Tear apart and throw away plastic packaging bags so that children will not
play with them. If children play with a plastic bag which was not torn apart,
they face the risk of suffocation.
1.5. Before starting the test run
Caution:
• Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the main power switch can
result in severe damage to internal parts. Keep the power switch turned on
during the operational season.
• Do not touch the switches with wet fingers.
- Touching a switch with wet fingers can cause electric shock.
• Do not touch the refrigerant pipes during and immediately after operation.
- During and immediately after operation, the refrigerant pipes are may be hot
and may be cold, depending on the condition of the refrigerant flowing through
the refrigerant piping, compressor, and other refrigerant cycle parts. Your
hands may suffer burns or frostbite if you touch the refrigerant pipes.
• Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
• Do not turn off the power immediately after stopping operation.
- Always wait at least five minutes before turning off the power. Otherwise,
water leakage and trouble may occur.
PGRRUTR
2. Indoor unit accessories
The unit is provided with the following accessories:
Type 40 - 140Type 200 · 250