Mitsubishi PEFY-P08NMSU-E, PEFY-P18NMSU-E, PEFY-P06NMSU-E, PEFY-P12NMSU-E, PEFY-P15NMSU-E Technical & Service Manual

...
Page 1
Air-Conditioners
TECHNICAL & SERVICE MANUAL
Models
PEFY-P06NMSU-E, PEFY-P08NMSU-E PEFY-P12NMSU-E, PEFY-P15NMSU-E PEFY-P18NMSU-E, PEFY-P24NMSU-E
For use with R410A & R22
2008
Page 2
HWE08010 GB
Safety Precautions
Read before installation and performing electrical work
Symbol explanations
Thoroughly read the following safety precautions prior to installation.Observe these safety precautions for your safety.This equipment may have adverse effects on the equipment on the same power supply system.Contact the local power authority before connecting to the system.
WARNING
This symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or death.
CAUTION
This symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or dam-
age to the unit.
Indicates an action that must be avoided.
Indicates important instructions.
Indicates a parts that requires grounding.
Indicates that caution must be taken with rotating parts. (This symbol is on the main unit label.) <Color: Yellow>
Indicates that the parts that are marked with this symbol pose a risk of electric shock. (This symbol is on the main unit label.) <Color: Yellow>
WARNING
Carefully read the labels affixed to the main unit.
WARNING
Ask your dealer or a qualified technician to install the unit.
Improper installation by the user may result in water leak­age, electric shock, or fire.
Properly install the unit on a surface that can withstand its weight.
Unit installed on an unstable surface may fall and cause in­jury.
Only use specified cables. Securely connect each cable so that the terminals do not carry the weight of the cable.
Improperly connected cables may produce heat and start a fire.
Take appropriate safety measures against wind gusts and earthquakes to prevent the unit from toppling over.
Improper installation may cause the unit to topple over and cause injury or damage to the unit.
Only use accessories (i.e., air cleaners, humidifiers, electric heaters) recommended by Mitsubishi Electric.
Do not make any modifications or alterations to the unit. Consult your dealer for repair.
Improper repair may result in water leakage, electric shock, or fire.
Do not touch the heat exchanger fins with bare hands.
The fins are sharp and pose a risk of cuts.
In the event of a refrigerant leak, thoroughly ventilate the room.
If gaseous refrigerant leaks out and comes in contact with an open flame, toxic gases will be generated.
Properly install the unit according to the instructions in the Installation Manual.
Improper installation may result in water leakage, electric shock, or fire.
Have all electrical work performed by an authorized electri­cian according to the local regulations and the instructions in this manual. Use a dedicated circuit.
Insufficient power supply capacity or improper installation of the unit may result in malfunctions of the unit, electric shock, or fire.
Page 3
ii
HWE08010 GB
Precautions for handling units for use with R410A
WARNING
Keep electrical parts away from water.
Wet electrical parts pose a risk of electric shock, smoke, or fire.
Securely attach the control box cover.
If the cover is not installed properly, dust or water may infil­trate and pose a risk of electric shock, smoke, or fire.
Only use the type of refrigerant that is indicated on the unit when installing or relocating the unit.
Infiltration of any other types of refrigerant or air into the unit may adversely affect the refrigerant cycle and may cause the pipes to burst or explode.
When installing the unit in a small space, take appropriate precautions to prevent leaked refrigerant from reaching the limiting concentration.
Leaked refrigerant gas will displace oxygen and may cause oxygen starvation. Consult your dealer before installing the unit.
Consult your dealer or a qualified technician when moving or reinstalling the unit.
Improper installation may result in water leakage, electric shock, or fire.
After completing the service work, check for a refrigerant leak.
If leaked refrigerant is exposed to a heat source, such as a fan heater, stove, or electric grill, toxic gases will be gener­ated.
Do not try to defeat the safety features of the unit.
Forced operation of the pressure switch or the temperature switch by defeating the safety features for these devices, or the use of accessories other than the ones that are recom­mended by Mitsubishi Electric may result in smoke, fire, or explosion.
Consult your dealer for proper disposal method.
Do not use a leak detection additive.
CAUTION
Do not use the existing refrigerant piping.
A large amount of chlorine that may be contained in the re­sidual refrigerant and refrigerator oil in the existing piping may cause the refrigerator oil in the new unit to deteriorate.
Use refrigerant piping materials made of phosphorus deox­idized copper. Keep the inner and outer surfaces of the pipes clean and free of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and moisture.
Contaminants in the refrigerant piping may cause the refrig­erator oil to deteriorate.
Store the piping materials indoors, and keep both ends of the pipes sealed until immediately before brazing. (Keep el­bows and other joints wrapped in plastic.)
Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerator oil to deteriorate or cause the compressor to malfunction.
Use a small amount of ester oil, ether oil, or alkyl benzene to coat flares and flanges.
Infiltration of a large amount of mineral oil may cause the re­frigerator oil to deteriorate.
Charge the system with refrigerant in the liquid phase.
If gaseous refrigerant is drawn out of the cylinder first, the composition of the remaining refrigerant in the cylinder will change and become unsuitable for use.
Only use R410A.
The use of other types of refrigerant that contain chloride may cause the refrigerator oil to deteriorate.
Use a vacuum pump with a check valve.
If a vacuum pump that is not equipped with a check valve is used, the vacuum pump oil may flow into the refrigerant cy­cle and cause the refrigerator oil to deteriorate.
Prepare tools for exclusive use with R 410A. Do not use the following tools if they have been used with the conventional refrigerant: gauge manifold, charging hose, gas leak detec­tor, check valve, refrigerant charge base, vacuum gauge, and refrigerant recovery equipment.
If the refrigerant or the refrigerator oil that may be left on these tools are mixed in with R410A, it may cause the refrigerator oil in the new system to deteriorate. Infiltration of water may cause the refrigerator oil to deteriorate. Leak detectors for conventional refrigerants will not detect an R410A leak because R410A is free of chlorine.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of the refrigerant in the cylinder will change and become unsuitable for use.
Exercise special care when handling tools for use with R410A.
Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerator oil to deteriorate.
Page 4
iiiiii
HWE08010 GB
Precautions for PAC-YU25HT (Optional parts)
WARNING
Stop the operation if any malfunction occurs.
If malfunction occurs (burning smell, etc.) stop the opera­tion and turn off the power supply. Contact your dealer or technical representative. If the controller continues to oper­ate after a malfunction occurs, this may cause damage, electric shock or fire.
Do not turn on the main power until installation has been completed.
Doing so may result in electric shock or fire.
Leave sufficient space between heater and indoor unit to al­low for air movement to prevent the indoor unit from over­heating.
If they are installed too closely and the indoor unit temper­ature exceeds 40°C, malfunctions or fire may result.
Keep the heater clean to keep the indoor unit from sucking in accumulated dust on the heater.
Dust particles that enter the indoor unit may cause fire.
When air conditioner and heater are configured to perform an interlocked operation, do not use any other type of ca­bles except this external heater adapter (PAC-YU25HT).
The use of any other type of cables may result in malfunc­tions or fire.
Do not build a heater into the indoor unit.
Doing so may result in fire.
CAUTION
Do not install in any place exposed to flammable gas leak­age.
Flammable gases accumulated around the body of PAC­YU25HT may cause an explosion.
Do not use in any special environment.
Using in any place exposed to oil (including machine oil), steam and sulfuric gas may deteriorate the performance significantly or give damage to the component parts.
Do not install in any place where acidic or alkaline solution or special spray are often used.
Doing so may cause an electric shock or malfunction.
Do not install in any steamy place such a bathroom or kitch­en.
Avoid any place where moisture is condensed into dew.Do­ing so may cause an electric shock or malfunction.
Do not wash with water.
Doing so may cause an electric shock or malfunction.
Do not install in any place at a temperature of more than 40°C (104°F) or less than 0°C (32°F) or exposed to direct sunlight.
Page 5
iv
HWE08010 GB
Page 6
CONTENTS
HWE08010 GB
I
Features
[1] Features.................................................................................................................................... 1
II
Components and Functions
[1] Components and Functions...................................................................................................... 2
III
Specfications
[1] Specifications............................................................................................................................ 4
1.Specfications .......................................................................................................................... 4
2.Electrical component specifications........................................................................................ 6
IV
Outlines and Dimensions
[1] Outlines and Dimensions.......................................................................................................... 7
V
Wiring Diagram
[1] Wiring Diagram......................................................................................................................... 8
VI
Refrigerant System Diagram
[1] Refrigerant system diagram...................................................................................................... 9
VII
Microprocessor Control
[1] Microprocessor Control........................................................................................................... 10
1.Cool operation ...................................................................................................................... 10
2.Dry operation ........................................................................................................................ 11
3.Fan operation........................................................................................................................ 12
4.Heat operation ...................................................................................................................... 13
5.Auto operation [Automatic cool / heat change over operation] ............................................. 14
6.When unit is stopped control mode ...................................................................................... 15
7.Heater control ....................................................................................................................... 15
VIII
Troubleshooting
[1] Troubleshooting ...................................................................................................................... 19
1.Check methods..................................................................................................................... 19
2.DC fan motor (fan motor/indoor control board)..................................................................... 23
3.Address switch setting .......................................................................................................... 24
4.Voltage test points on the control board ............................................................................... 25
5.Dipswitch setting (Factory setting)........................................................................................ 26
IX
Disassembly Procedure
[1] Disassembly Procedure.......................................................................................................... 29
1.Control box ........................................................................................................................... 29
2.Thermistor (Intake air) .......................................................................................................... 30
3.Drainpan ............................................................................................................................... 31
4.Thermistor (Gas pipe) (Liquid pipe) ...................................................................................... 32
5.Fan and fan motor ................................................................................................................ 33
6.Bearing ................................................................................................................................. 34
7.Heat exchanger .................................................................................................................... 35
Page 7
HWE08010 GB
Page 8
[ I Features ]
- 1 -
HWE08010 GB
IFeat ures
[1] Features
Model Cooling capacity/Heating capacity
BTU/h kW
PEFY-P06NMSU-E 6000/6700 1.8/2.0
PEFY-P08NMSU-E 8000/9000 2.3/2.6
PEFY-P12NMSU-E 12000/13500 3.5/4.0
PEFY-P15NMSU-E 15000/17000 4.4/5.0
PEFY-P18NMSU-E 18000/20000 5.3/5.9
PEFY-P24NMSU-E 24000/27000 7.0/7.9
Page 9
[ II Components and Functions ]
- 2 -
HWE08010 GB
IIComponen ts and Functions
[1] Components and Functions
1. Indoor (Main) Unit
2. Remote Controller [PAR-21MAA]
Once the operation mode is selected, the unit will remain in the selected mode until changed.
(1) Remote Controller Buttons
Keep the remote controller out of direct sunlight to ensure accurate measurement of room temperature.The thermistor at the lower right-hand section of the remote controller must be free from obstructions to ensure accurate mea-
surement of room temperature.
(A) Air
1 [Set Temperature] Button 7 [Vane Control] Button 2 [Timer Menu] Button 8 [Ventilation] Button
[Monitor/Set] Button [Operation] Button
3 [Mode] Button 9 [Check/Clear] Button
[Back] Button 10 [Test Run] Button
4 [Timer On/Off] Button 11 [Filter] Button
[Set Day] Button [ ] Button
5 [Louver] Button 12 [ON/OFF] Button
[Operation] Button 13 Position of built-in room thermistor
6 [Fan Speed] Button 14 [Set Time] Button
(A)
(A)
Page 10
[ II Components and Functions ]
- 3 -
HWE08010 GB
(2) Remote Controller Display
A Current time/Timer time I Louver swing
B Centralized control indicator J Ventilation
C Timer OFF indicator K Filter sign
D Timer mode L Sensor position
E Operation mode display: COOL, DRY, AUTO,
FAN, HEAT
M Room temperature
F Function Lock indicator N Vane setting
G Preset temperature O Fan speed
H Power indicator
Page 11
[ III Specfications ]
- 4 -
HWE08010 GB
III Specfications
[1] Specifications
1. Specfications
Model PEFY-P06NMSU-E PEFY-P08NMSU-E PEFY-P12NMSU-E PEFY-P15NMSU-E
Power source 1-phase 208/230V 60Hz Cooling capacity *1 BTU / h 6,000 8,000 12,000 15,000 (Nominal) *1 kW 1.8 2.3 3.5 4.4
Power input kW 0.05/0.05 0.06/0.06 0.07/0.07 0.07/0.07
Current input A 0.42/0.41 0.51/0.49 0.56/0.53 0.57/0.55 Heating capacity *2 BTU / h 6,700 9,000 13,500 17,000 (Nominal) *2 kW 2.0 2.6 4.0 5.0
Power input kW 0.03/0.03 0.04/0.04 0.05/0.05 0.05/0.05
Current input A 0.32/0.31 0.41/0.39 0.46/0.43 0.47/0.45 External finish Galvanized External dimension H x W x D in. 7-7/8 x 31-1/8 x 27-9/16 7-7/8 x 31-1/8 x 27-9/16 7-7/8 x 31-1/8 x 27-9/16 7-7/8 x 39 x 27-9/16
mm 200 x 790 x 700 200 x 790 x 700 200 x 790 x 700 200 x 990 x 700 Net weight lbs (kg) 42(19) 42(19) 46(20) 54(24) Heat exchanger Cross fin(Aluminium fin and copper tube) FAN Type x Quantity Sirocco fan x 2 Sirocco fan x 2 Sirocco fan x 2 Sirocco fan x 3
External in.WG
0.02-0.06-0.14-0.20 (208V)
0.02-0.06-0.14-0.20 (208V)
0.02-0.06-0.14-0.20 (208V)
0.02-0.06-0.14-0.20 (208V)
static press Pa 5-15-35-50 5-15-35-50 5-15-35-50 5-15-35-50
in.WG
0.02-0.06-0.14-0.20 (230V)
0.02-0.06-0.14-
0.20(230V)
0.02-0.06-0.14-
0.20(230V)
0.02-0.06-0.14-
0.20(230V)
Pa 5-15-35-50 5-15-35-50 5-15-35-50 5-15-35-50 Motor type DC brushless motor Motor output kW 0.096 0.096 0.096 0.096 Driving mechanism Direct-driven Airflow rate cfm 176-212-247 194-247-317 211-282-370 282-335-388 (Low-Mid-High) m3 / min 5-6-7 5.5-7-9 6-8-10.5 8-9.5-11
L / s 83-100-117 91-116-150 100-133-175 133-158-183
Sound pressure level dB <A> 22-24-28 (208V) 23-26-30 (208V) 23-28-35 (208V) 28-30-33 (208V) (Low-Mid-High) dB <A> 22-24-28 (230V) 23-26-30 (230V) 23-28-35 (230V) 28-30-33 (230V) (measured in anechoic room) dB <A> - - - ­Insulation material Polystyrene foam,Polyethylene foam,Urethane foam Air filter PP Honeycomb fabric (washable) Protection device Fuse Refrigerant control device LEV
Connectable outdoor unit *3
R410A,R22 CITY
MULTI
R410A,R22 CITY
MULTI
R410A,R22 CITY
MULTI
Diameter of Liquid (R410A)
in. (mm)
1/4 (6.35) Brazed 1/4 (6.35) Brazed 1/4 (6.35) Brazed 1/4 (6.35) Brazed refrigerant (R22 ) 1/4 (6.35) Brazed 1/4 (6.35) Brazed 1/4 (6.35) Brazed 1/4 (6.35) Brazed pipe Gas (R410A)
in. (mm)
1/2 (12.7) Brazed 1/2 (12.7) Brazed 1/2 (12.7) Brazed 1/2 (12.7) Brazed (O.D.) (R22 ) 1/2 (12.7) Brazed 1/2 (12.7) Brazed 1/2 (12.7) Brazed 1/2 (12.7) Brazed Diameter of drain pipe in. (mm) O.D. 1-1/4(32) O.D. 1-1/4(32) O.D. 1-1/4(32) O.D. 1-1/4(32) Drawing External WKB94L522
Wiring WKB94L523
Refrigerant cycle ­Standard Document Installation Manual, Instruction Book attachment Accessory Drain hose (flexible joint) Optional External heater adaptor PAC-YU25HT PAC-YU25HT PAC-YU25HT PAC-YU25HT parts Remark
Installation Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other
items shall be referred to the Installation Manual.
Note : *1 Nominal cooling conditions *2 Nominal heating conditions Unit convertor
Indoor : 80degF D.B. / 67degF W.B. 70degF D.B. kcal/h = kW x 860
(26.7degC D.B. / 19.4degC W.B.) (21.1degC D.B.) BTU/h = kW x 3,412
Outdoor : 95degF D.B. 47degF D.B. / 43degF W.B. cfm = m3/min x 35.31
(35degC D.B.) (8.3degC D.B. / 6.1degC W.B.) lbs = kg / 0.4536
Pipe length : 25 ft. (7.6 m) 25 ft. (7.6 m)
Level difference : 0 ft. (0 m) 0 ft. (0 m) *Above specification data is *3 PUHY-THMU,PURY-THMU,PUHY-YHMU,PURY-YHMU,PUMY-NHMU subject to rounding variation. *The external static pressure is set to 15 Pa at factory shipment. *Due to continuing improvement, above specification may be subject to change without notice.
Page 12
[ III Specfications ]
- 5 -
HWE08010 GB
Model PEFY-P18NMSU-E PEFY-P24NMSU-E
Power source 1-phase 208/230V 60Hz Cooling capacity *1 BTU / h 18,000 24,000 (Nominal) *1 kW 5.3 7.0
Power input kW 0.09/0.09 0.12/0.12
Current input A 0.74/0.70 0.98/0.93 Heating capacity *2 BTU / h 20,000 27,000 (Nominal) *2 kW 5.9 7.9
Power input kW 0.07/0.07 0.10/0.10
Current input A 0.64/0.60 0.88/0.83 External finish Galvanized External dimension H x W x D in. 7-7/8 x 39 x 27-9/16 7-7/8 x 46-7/8 x 27-9/16
mm 200 x 990 x 700 200 x 1190 x 700 Net weight lbs (kg) 54(24) 62(28) Heat exchanger Cross fin(Aluminium fin and copper tube) FAN Type x Quantity Sirocco fan x 3 Sirocco fan x 4
External in.WG
0.02-0.06-0.14-0.20 (208V)
0.02-0.06-0.14-0.20 (208V)
static press Pa 5-15-35-50 5-15-35-50
in.WG
0.02-0.06-0.14-0.20 (230V)
0.02-0.06-0.14-
0.20(230V)
Pa 5-15-35-50 5-15-35-50 Motor type DC brushless motor Motor output kW 0.096 0.096 Driving mechanism Direct-driven Airflow rate cfm 353-441-529 423-565-706 (Low-Mid-High) m3 / min 10-12.5-15 12-16-20
L / s 167-208-250 200-267-333
Sound pressure level dB <A> 30-34-37 (208V) 30-35-40 (208V) (Low-Mid-High) dB <A> 30-34-37 (230V) 30-35-40 (230V) (measured in anechoic room) dB <A> - ­Insulation material Polystyrene foam,Polyethylene foam,Urethane foam Air filter PP Honeycomb fabric (washable) Protection device Fuse Refrigerant control device LEV
Connectable outdoor unit
R410A,R22 CITY
MULTI
R410A,R22 CITY
MULTI
Diameter of Liquid (R410A)
in. (mm)
1/4 (6.35) Brazed 3/8 (9.52) Brazed refrigerant (R22 ) 3/8 (9.52) Brazed 3/8 (9.52) Brazed pipe Gas (R410A)
in. (mm)
1/2 (12.7) Brazed 5/8 (15.88) Brazed (O.D.) (R22 ) 5/8 (15.88) Brazed 5/8 (15.88) Brazed Diameter of drain pipe in. (mm) O.D. 1-1/4(32) O.D. 1-1/4(32) Drawing External WKB94L522
Wiring WKB94L523
Refrigerant cycle ­Standard Document Installation Manual, Instruction Book attachment Accessory Drain hose (flexible joint) Optional External heater adaptor PAC-YU25HT PAC-YU25HT parts Remark
Installation Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other
items shall be referred to the Installation Manual.
Note : *1 Nominal cooling conditions *2 Nominal heating conditions Unit convertor
Indoor : 80degF D.B. / 67degF W.B. 70degF D.B. kcal/h = kW x 860
(26.7degC D.B. / 19.4degC W.B.) (21.1degC D.B.) BTU/h = kW x 3,412
Outdoor : 95degF D.B. 47degF D.B. / 43degF W.B. cfm = m3/min x 35.31
(35degC D.B.) (8.3degC D.B. / 6.1degC W.B.) lbs = kg / 0.4536
Pipe length : 25 ft. (7.6 m) 25 ft. (7.6 m)
Level difference : 0 ft. (0 m) 0 ft. (0 m) *Above specification data is *The external static pressure is set to 15 Pa at factory shipment. subject to rounding variation. *Due to continuing improvement, above specification may be subject to change without notice.
Page 13
[ III Specfications ]
- 6 -
HWE08010 GB
2. Electrical component specifications
Component Sym-
bol
PEFY-P06NMSU-E PEFY-P08NMSU-E PEFY-P12NMSU-E
Room temperature thermistor
TH21 Resistance 0°C[32°F]/15k , 10°C[50°F]/9.6k , 20°C[68°F]/6.3k , 25°C[77°F]/5.4k ,
30°C[86°F]/4.3k , 40°C[104°F]/3.0k
Liquid pipe thermistor TH22 Resistance 0°C[32°F]/15k , 10°C[50°F]/9.6k , 20°C[68°F]/6.3k , 25°C[77°F]/5.4k ,
30°C[86°F]/4.3k , 40°C[104°F]/3.0k
Gas pipe thermistor TH23 Resistance 0°C[32°F]/15k , 10°C[50°F]/9.6k , 20°C[68°F]/6.3k , 25°C[77°F]/5.4k ,
30°C[86°F]/4.3k , 40°C[104°F]/3.0k
Fuse FUSE 250V 6.3A
Fan motor 8-pole, Output 96W SIC-70CW-D8114-1
Linear expansion valve LEV 12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse)
Power supply terminal block
TB2
(L1, L2, G) 330V 30A
Transmission terminal block
TB5
TB15
(1, 2), (M1, M2, S) 250V 20A
Drain float switch DS Open/short detection
Initial contact resistance 500 m or less
Component Sym-
bol
PEFY-P15NMSU-E PEFY-P18NMSU-E PEFY-P24NMSU-E
Room temperature thermistor
TH21 Resistance 0°C[32°F]/15k , 10°C[50°F]/9.6k , 20°C[68°F]/6.3k , 25°C[77°F]/5.4k ,
30°C[86°F]/4.3k , 40°C[104°F]/3.0k
Liquid pipe thermistor TH22 Resistance 0°C[32°F]/15k , 10°C[50°F]/9.6k , 20°C[68°F]/6.3k , 25°C[77°F]/5.4k ,
30°C[86°F]/4.3k , 40°C[104°F]/3.0k
Gas pipe thermistor TH23 Resistance 0°C[32°F]/15k , 10°C[50°F]/9.6k , 20°C[68°F]/6.3k , 25°C[77°F]/5.4k ,
30°C[86°F]/4.3k , 40°C[104°F]/3.0k
Fuse FUSE 250V 6.3A
Fan motor 8-pole, Output 96W SIC-70CW-D896-2
Linear expansion valve LEV 12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse)
Power supply terminal block
TB2
(L1, L2, G) 330V 30A
Transmission terminal block
TB5
TB15
(1, 2), (M1, M2, S) 250V 20A
Drain float switch DS Open/short detection
Initial contact resistance 500 m or less
Page 14
[ IV Outlines and Dimensions ]
- 7 -
HWE08010 GB
IV Outlines and Dimensions
[1] Outlines and Dimensions
1. PEFY-P06,08,12,15,18,24NMSU-E
mm(in.)
(35-7/16)
(27-9/16)
(19-11/16)
(41-3/4)
(33-7/8)
(26)
(47-1/4)
(39-3/8)
(31-1/2)
(39-3/8)
(31-1/2)
(23-5/8)
(41-3/4)
(33-7/8)
(26)
(47-3/16)
(39-5/16)
(31-7/16)
(45-3/8)
(37-1/2)
(29-5/8)
(43-5/16)
(35-7/16)
(27-9/16)
700
Drain pipe(O.D.ø32(1-1/4))
(Emergency draining)
*2
*1
ø6.35(1/4)ø12.7(1/2)
PEFY-P18NMSU-E
900 952 998
860
9
800 1000 860
7
700
20
24
16
L
900
500
(48-25/32)
(40-29/32)
(33-1/16)
1039
1239
839
(46-7/8)
(39)
(31-1/8)
990
1190
790
KMN
9
5
J
1060
660
H
800600
7
660798752
Knockout hole ø27(1-3/32)
(Transmission wiring)
Knockout hole ø27(1-3/32)
(Power source wiring)
G
1200
F
1000
E
11
D
1060
C
1100
B
1152
PEFY-P06,08,12NMSU-E
PEFY-P15NMSU-E
PEFY-P24NMSU-E
Model A
1198
Gas pipe Liquid pipe
*1
*2
ø12.7(1/2)
ø15.88(5/8)
ø6.35(1/4)
ø9.52(3/8)
ø9.52(3/8)
ø15.88(5/8)
L-ø2.9(1/8)
2x2-ø2.9(1/8)
2xE-ø2.9(1/8)
Control box
Air filter
Suspension bolt hole
4-14x30(9/16x1-3/16) Slot
Terminal bed(Power source)
Refrigerant piping
brazing connection (liquid)
2
Refrigerant piping
brazing connection (gas)
1
Drain pipe(O.D.ø32(1-1/4))
(Spontaneous draining)
Terminal bed(Transmission)
Drain pump
Drain pipe(O.D.ø32(1-1/4))
Air
inlet
Air
outlet
(1-31/32~5-29/32)
159(6-9/32)
345 (13-19/32)
(21-21/32)
(11-13/16)
(30-19/32)
(17-23/32)
(11-13/16)
(17-23/32)
More than 300
(13/16)
(13/32)
(3-9/16)
(5-29/32)
(2-25/32)(4-19/32)
70
10(13/32)
(3-15/16)
(1-15/16) (24-5/8)
450
37(1-15/32)
200(7-7/8)
H20 (13/16)
157.5 (6-7/32)20 (13/16)
100(3-15/16)
37(1-15/32)
12 (1/2)
12 (1/2)
88(3-15/32)
100(3-15/16)xJ=K
100(3-15/16)
88 (3-15/32)
777
50(1-31/32)
50~150
50(1-31/32)
G
450
Less than 550
Less than 300
175
±5(6-29/32±7/32)
10 (13/32)
49
25(1)
More than 20
More than 10
170 (6-23/32)
102 (4-1/32)
48(1-29/32)
270 (10-21/32)
116
150(Duct)
23 (29/32)
100 25 (1)
700 (27-9/16)
677 (26-21/32)23(29/32)
C
M
B (Suspension bolt pitch)23 (29/32)
A
N
90
625 (Suspension bolt pitch)
100(3-15/16)
57(2-1/4)
D (Duct)
30 (1-3/16) 100(3-15/16)x(E-1)=F
100(3-15/16)
20 (13/16)
15 (19/32)
<accessory>
Drain hose (I.D.ø32(1-1/4))
(Actual length)
Note2
Access door
Required space for service and maintenance
Access door
Ceiling surface
Make the access door at the appointed
position properly for service maintenance.
Note 1. Use M10 screw for the Suspension bolt (field supply).
2. Keep the service space for the maintenance at the bottom.
3. This chart indicates for PEFY-P15·18NMSU-E models,which
has 3 fans.
PEFY-P06~12NMSU-E models have 2 fans.
PEFY-P24NMSU-E model have 4 fans.
4. In case of the inlet duct is used,remove the air filter(supply with
the unit), then install the filter(field supply) at suction side.
*1:R410A outdoor unit
*2:R22 outdoor unit
12
Unit : mm(in)
Page 15
[ V Wiring Diagram ]
- 8 -
HWE08010 GB
VWiring Diagram
[1] Wiring Diagram
1. PEFY-P06,08,12,15,18,24NMSU-E
8765432
1
432
1
1~
M
M
4231
M
1324 12 14567
6
5
3
1
432
1
1351213248132 4567
13
PARTS LOCATION
CONTROL BOX
I.B.
TB2TB15TB5A.B.
INSIDE SECTION OF CONTROL BOX
SW5
SW14
(Connection No.)
SWBSWA
SWC
SW12
(2nd digit)
SW11
(1st digit)
SW1
A.B.
I.B.
0
1
2
3
4
5
6
7 8 9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
Switch (for mode selection)
ConnectorCN4Y
Switch (for model selection)
Connector (emergency operation)
Switch (for mode selection)
Switch (2nd digit address set)
Switch (connection No.set)
Switch (for static pressure selection)
Switch (for model selection)
Switch (for static pressure selection)
Switch (for mode selection)
Switch (for capacity code)
Thermistor (piping temp.detection/gas)
Thermistor (piping temp.detection/liquid)
Connector (Heater)CN24
Drainpump
Connector (Wireless)
X1 Aux. relay
ArresterDSA
VaristorZNR01,02
Fuse AC250V 6.3AFUSE
LEV
Fan motor
Float switchFS
Connector (Remote indication)
Connector (Centrally control)
CN90
Connector (Remote switch)
Connector (Damper)
CN32
CN52
CN51
CN41
Transmission terminal bedTB15
TH21 Thermistor (inlet air temp.detection)
TH23
TH22
NAMESYMBOLSYMBOL
I.B.
A.B.
Indoor controller board
Address board
Switch (1st digit address set)
SW2(I.B.)
SW5(A.B.)
SWB(A.B.)
SWA(A.B.)
SWC(A.B.)
SWE(I.B.)
SW3(I.B.)
SW11(A.B.)
SW12(A.B.)
SW14(A.B.)
SW1(A.B.)
SW4(I.B.)
TB2
TB5 Transmission terminal bed
Power source terminal bed
SYMBOL EXPLANATION
NAME
CN27
Connector (HA terminal-A)
SYMBOL NAME
NOTE: 1.The wirings to TB2,TB5,TB15 shown in dotted line are field work.
2.Mark indicates terminal bed, connector.
3.Use copper supply wire.
CN4Y CN24
(Yellow)
G
CN82
CN43
U
LED1
LED2
DC310~340V
Rectify circuit
ZNR01
POWER SUPPLY
~ 208V/230V 60Hz
TO NEXT INDOOR UNIT
FUSE (16A)
PULL BOX
BREAKER (16A)
FUSE
X1
ZNR02
DSA
U
(Green)
(Blue)
(Red)
(Red)
(Red)
(Red)
(Blue)
(Blue)
(Black)
TB5
L2
L1
TB15
12
S(SHIELD)
M2
TB2
M1
FSTH22 TH23 TH21
CN60
CN3A
CNMF
CNP
CND
CN2M
SW2SW4SW3
CN90
CN42CN81CN32
CN27
CN20CN4FCN44CN41CN52 CN51
SWE
ON
OFF
TO MA REMOTE
CONTROLLER
TO OUTDOOR UNIT
BC CONTROLLER
REMOTE CONTROLLER
Page 16
[ VI Refrigerant System Diagram ]
- 9 -
HWE08010 GB
VI Refrigerant System Diagram
[1] Refrigerant system diagram
(A) Gas pipe thermistor TH23
(B) Gas pipe
(C) Liquid pipe
(D) Brazed connections
(E) Strainer (#100 mesh)
(F) Linear expansion valve
(G) Liquid pipe thermistor TH22
(H) Heat exchanger
(I) Room temperature thermistor TH21
(H)
(I)
(F)
(E)(E)
(C)
(G)
(A)
(D)
(B)
mm[in.]
Capacity PEFY-P06,08,12,15NMSU-E PEFY-P18NMSU-E PEFY-P24NMSU-E
Gas pipe ø12.7 [1/2] R410A: ø12.7 [1/2]
R22: ø15.88 [5/8]
ø15.88 [5/8]
Liquid pipe ø6.35 [1/4] R410A: ø6.35 [1/4]
R22: ø9.52 [3/8]
ø9.52 [3/8]
Page 17
[ VII Microprocessor Control ]
- 10 -
HWE08010 GB
VII Microprocessor Control
[1] Microprocessor Control
1. Cool operation
1. Termoregulating function (1) Thermoregulating function (Function to prevent restarting for 3 minutes)
Room temperature desired temperature + 2°F ···Thermo ONRoom temperature desired temperature ···Thermo OFF
(2) Anti-freezing control
Detected condition :
When the liquid pipe temp. (TH22) is 32°F or less in 16 minutes from compressors start up, anti-freezing control starts and the thermo OFF.
Released condition :
The timer which prevents reactivating is set for 3 minutes, and anti-freezing control is cancelled when any one of the following conditions is satisfied.
1) Liquid pipe temp. (TH22) turns 50°F or above.
2) The condition of the thermo OFF has become complete by thermoregulating, etc.
3) The operation modes became mode other than COOL.
4) The operation stopped.
2. Fan (1) By the remote controller setting (switch of 3 speeds+Auto)
When [Auto] is set, fan speed is changed depending on the value of: Room temperature - Desired temperature
3. Drain pump (1) Drain pump control
Always drain pump ON during the COOL and DRY mode operation. (Regardless of the thermo ON/ OFF)When the operation mode has changed from the COOL or DRY to the others (including Stop), OFF the control after the drain
pump ON for 3 minutes.
(2) Float switch control
Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF.
In the water : Detected that the float switch is ON for 15 seconds.
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display COOL.
3. Press the [Set Temperature] button to set the desired tempera­ture.
The set temperature changes 2°F when the [Set Temperature] button is pressed one time. Cooling 67 to 87°F
Type Fan speed notch
3 speeds + Auto type [Low], [Med], [High], [Auto]
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON OFFHrAFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Page 18
[ VII Microprocessor Control ]
- 11 -
HWE08010 GB
In the air : Detected that the float switch is OFF for 15 seconds.
2. Dry operation
1. Termoregulating function (1) Thermo regulating function (Function to prevent restarting for 3 minutes)
Setting the Dry thermo by the thermo regulating signal and the room temperature (TH21).
Dry thermo ON Room temperature desired temperature + 2°F Dry thermo OFF Room temperature desired temperature
(2) Frozen prevention control
No control function
2. Fan (1) Indoor fan operation controlled depends on the compressor conditions.
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display DRY.
3. Press the [Set Temperature] button to set the desired tempera­ture.
The set temperature changes 2°F when the [Set Temperature] button is pressed one time. Dry 67 to 87°F
Room temperature
3 min. passed since starting operation
Dry thermo
ON time (min)
Dry thermo
OFF time (min)
Thermo regulating signal Room temperature (T1)
Over 64°F
ON
T1 83°F 9 3
83°F > T1 79°F 7 3
79°F > T1 75°F 5 3
75°F > T1 3 3
OFF Unconditional 3 10
Less than 64°F Dry thermo OFF
Dry thermo Fan speed notch
ON [Low]
OFF
Excluding the following Stop
Room temp. < 64°F [Low]
ON
OFF
15sec. 15sec. 15sec. 1min.30sec. 1min.30sec.
Float SW
In the water In the air In the water Error
postponement
Drain pump
abnormal
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON OFFHrAFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Page 19
[ VII Microprocessor Control ]
- 12 -
HWE08010 GB
Remote controller setting is not acceptable.
3. Drain pump (1) Same control as COOL operation
3. Fan operation
1. Fan (1) Set by remote controller.
When [Auto] is set, fan speed becomes [Low].
2. Drain pump (1) Drain pump control
The drain pump turns ON for the specified amount of time when any of the following conditions is met:
1) ON for 3 minutes after the operation mode is switched from COOL or DRY to another operation mode (FAN).
2) ON for 6 minutes after the float switch is submerged in the water when the float switch control judges the sensor is in the water.
(2) Float switch control
Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF.
In the water : Detected that the float switch is ON for 15 seconds. In the air : Detected that the float switch is OFF for 15 seconds.
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display FAN.
Type Fan speed notch
3 speeds + Auto type [Low], [Med], [High], [Auto]
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON OFFHrAFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
ON
OFF
15sec. 15sec. 15sec. 1min.30sec. 1min.30sec.
Float SW
In the water In the air In the water Error
postponement
Drain pump
abnormal
Page 20
[ VII Microprocessor Control ]
- 13 -
HWE08010 GB
4. Heat operation
1. Termoregulating function (1) Thermoregulating function (Function to prevent restarting for 3 minutes)
Room temperature desired temperature -2°F ···Thermo ONRoom temperature desired temperature ···Thermo OFF
2. Fan (1) By the remote controller setting (switch of 3 speeds+Auto)
When [Auto] is set, fan speed is changed depending on the value of:
Desired temperature - Room temperature Give priority to under-mentioned controlled mode
1) Hot adjust mode
2) Preheating exclusion mode
3) Thermo OFF mode (When the compressor off by the thermoregulating)
4) Cool air prevention mode (Defrosting mode)
5) Capacity increasing mode
(2) Hot adjust mode
The fan controller becomes the hot adjuster mode for the following conditions.
1) When starting the HEAT operation
2) When the thermoregulating function changes from OFF to ON.
3) When release the HEAT defrosting operation
A: Hot adjust mode starts. B: 5 minutes have passed since the condition A or the indoor liquid pipe temperature turned 95°F or more. C: 2 minutes have passed since the condition A. (Terminating the hot adjust mode)
*1 "STAND BY" will be displayed during the hot adjust mode.
(3) Preheating exclusion mode
When the condition changes the auxiliary heater ON to OFF (thermoregulating or operation stop, etc.), the indoor fan operates
in [Low] mode for 1 minute.
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display HEAT.
3. Press the [Set Temperature] button to set the desired tempera­ture.
The set temperature changes 2°F when the [Set Temperature] button is pressed one time. Heating 63 to 83°F.
<Display in HEAT operation>
[DEFROST] The [DEFROST] symbol is only displayed during the defrost op­eration. [STANDBY] The [STANDBY] symbol is only displayed during the hot adjust mode.
Type Fan speed notch
3 speeds + Auto type [Low], [Med], [High], [Auto]
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON OFFHrAFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
CAB
[Extra Low]
[Low]
Set fan speed by the remote controller
Hot adjust mode *1
Page 21
[ VII Microprocessor Control ]
- 14 -
HWE08010 GB
This control is same for the model without auxiliary heater.
(4) Thermo OFF mode
When the thermoregulating function changes to OFF, the indoor fan operates in [Extra low].
(5) Heat defrosting mode
The indoor fan stops.
3. Drain pump (1) Drain pump control
The drain pump turns ON for the specified amount of time when any of the following conditions is met:
1) ON for 3 minutes after the operation mode is switched from COOL or DRY to another operation mode (FAN).
2) ON for 6 minutes after the float switch is submerged in the water when the float swich control judges the sensor is in the water.
(2) Float switch control
Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF.
In the water : Detected that the float switch is ON for 15 seconds. In the air : Detected that the float switch is OFF for 15 seconds.
5. Auto operation [Automatic cool / heat change over operation]
1. Initial value of operation mode (1) HEAT mode for room temperature < Desired temperature (2) COOL mode for room temperature Desired temperature
2. Mode change (1) HEAT mode -> COOL mode
Room temperature Desired temperature + 3°F. or 3 min. has passed
(2) COOL mode -> HEAT mode
Room temperature Desired temperature - 3°F. or 3 min. has passed
3. COOL mode (1) Same control as cool operation
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display AUTO.
3. Press the [Set Temperature] button to set the desired tempera­ture.
The set temperature changes 2°F when the [Set Temperature] button is pressed one time. Automatic 67 to 83°F
ON
OFF
15sec. 15sec. 15sec. 1min.30sec. 1min.30sec.
Float SW
In the water In the air In the water Error
postponement
Drain pump
abnormal
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON OFFHrAFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Page 22
[ VII Microprocessor Control ]
- 15 -
HWE08010 GB
4. HEAT mode (1) Same control as heat operation
The value "3°F" is modifiable from 1.8°F to 9°F by maintenance tool.
6. When unit is stopped control mode
1. Drain pump (1) Drain pump control
The drain pump turns ON for the specified amount of time when any of the following conditions is met:
1) ON for 3 minutes after the operation mode is switched from COOL or DRY to another operation mode (FAN).
2) ON for 6 minutes after the float switch is submerged in the water when the float switch control judges the sensor is in the water.
(2) Float switch control
Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF.
In the water : Detected that the float switch is ON for 15 seconds. In the air : Detected that the float switch is OFF for 15 seconds.
7. Heater control
1. Control specifications and DIP S/W setting Table 1 shows how the field-installed heater is controlled. Select the desired pattern in the table below, and set the DIP S/W
on the outdoor and indoor units as shown in Table 1. See section 3 "Installation" for details. The table below shows Heater Control patterns #A and B.
ON
OFF
15sec. 15sec. 15sec. 1min.30sec. 1min.30sec.
Float SW
In the water In the air In the water Error
postponement
Drain pump
abnormal
Table.1
Outdoor unit
setting
Condition of outdoor unit
Duct unit PE/PD/PF-NR(NL)
Î
(PEFY-P06,08,12,15,18,24
NMSU-E)
NON duct unit
(PL/PK/PC)
DIP S/W OFF In the case of: <TGMU> S/W5-2 OFF <THMU> S/W5-10 OFF <PUMY> S/W4-4 OFF
N / A
DIP S/W3-4
OFF
(Indoor unit)
Heater control #A
(defrost/error:
Heater OFF)
Heater control #A
(defrost/error:
Heater ON)
DIP S/W3-4
ON
(Indoor unit)
Heater control #A
(defrost/error:
Heater ON)
DIP S/W ON In the case of: <TGMU> S/W5-2 ON <THMU> S/W5-10 ON <PUMY> S/W4-4 ON
Normal drive Heater OFF Heater OFF
Defrost drive
H/P drive
H/P stop
DIP S/W3-4
OFF
(Indoor unit)
Heater control #A
(defrost/error:
Heater OFF)
Heater control #B
(defrost/error:
Heater ON)
DIP S/W3-4
ON
(Indoor unit)
Heater control #B
(defrost/error:
Heater ON)
Norm al drive
Defrost drive
H/P drive
H/P stop
Condition of O/U
㪧㪸㫉㪸㫄 㪼㫋㪼㫉㫊㩷a/b/c/d are set by maintenance tool.
a b cd
Outdoor temp.
Page 23
[ VII Microprocessor Control ]
- 16 -
HWE08010 GB
(1) On the ducted model units (except the Fresh air intake type), turning on the heater with the fan setting set to OFF requires that
the DIP S/W and connectors on the indoor units*1 are set on site. (in case of PEFY-P06,08,12,15,18,24NMSU-E)
*1: DIP SW 3-4, CN24, and CN4Y (2) On the Fresh air intake type units, the heater cannot be turned on with the fan setting set to OFF. (3) Non-ducted models do not require the settings described in Section (1) above. (4) Back-up heating will not be performed when the heater turns on while demand control is performed (not a request item). (5) This is applicable only to the R410 series. Make the settings for the following dip switches on the outdoor unit control board
before switching on the power.
2. Fan control
By using the optional parts PAC-YU25HT, fan speed can be controlled.
*depend on SW1-7/1-8
Table.2
Heater control #A
Heater OFF Inlet air temp. set temp. Heater ON Inlet air temp. < set temp.-4°F
Heater control #B Heater OFF
Inlet air temp. set temp. Heater ON Inlet air temp. < set temp.-1.8°F
<For heater> The value "4°F" is modifiable from 1.8°F to 9°F by maintenance tool.
Pattern Duct unit PE/PD/PF-NR(NL)
Î
(PEFY-P06,08,12,15,18,24NMSU-E)
CN4Y for FAN control (YU25) DIP S/W3-4 (Indoor unit) Fan in defrost
1
Disabled
OFF Stop (Heater OFF)
2 ON L / LL / Set * (Heater ON)
3
Enabled
OFF Stop (Heater OFF)
4 ON Stop (Heater ON)
SW3-1 SW1-7 SW1-8 Fan speed *1
OFF OFF OFF Very low
OFF ON OFF Low
OFF OFF ON Remote controller setting
OFF ON ON
Stop
(Remote controller setting *2)
ON ON ON
Stop
(Remote controller setting *2)
*1 The fan operates at the same speed settings as shown in this table during the Heating Thermo-OFF mode. *2 If Pattern 2 in the table above is selected for the fan control pattern, the fan will follow the setting of the remote controller.
Set temp. Set temp.-1.8°F
Set tem p.-4°F
Inlet air tem p .
Heater ou tput
OFF
ON
Set temp. Set temp.-1.8°F
Inlet air temp.
Heater output
OFF
ON
Page 24
[ VII Microprocessor Control ]
- 17 -
HWE08010 GB
Reference (not applicable to the ducted models)
This is applicable only to the R410A series. Make the settings for the following dip switches on the indoor unit control board
before switching on the power.
3. PAC-YU25HT (Optional Parts) installation
The following section describes installation of the External Heater Adapter that connects to CITY MULTI air conditioner R410A
series indoor unit. This products is the special wiring parts to drive an electric heater with the air conditioner.
(1) Parts list
Check that the following parts are included in the package.
1) External output cable (with a yellow connector).............................2 in total
Two types of cables with different connectors are included.
2) Panel heater connector.................................................................. 3 in total
White: 1
Green: 2 (2 types)
(2) Connection to the indoor unit
Use the cables that fit the connectors on the indoor unit control board. The items listed in this parts list cannot be used with
the following models.
PMFY-BM
PMFY-AM
1) External output cable (with a yellow connector)
This cable is used to connect a relay circuit for an interlocked operation with either an electric or a panel heater. Connect the
cable to CN24 on the indoor unit control board.
2) Panel heater connector (with a green connector)
This connector is used to perform an interlocked operation with a panel heater. Depending on the indoor unit control board
specification, connect the cable either to CN4Y or CN22 as appropriate.
(3) Locally procured wiring
A basic connection method is shown below.
1) PEFY-P-NMSU-E and other models
Pattern NON duct unit (PL/PK/PC)
CN4Y for FAN control (YU25) *3 DIP S/W (Indoor unit) Fan in defrost
1 N/A N/A Stop (Heater ON)
*3 Refer to Section 5 "Dipswitch Setting" for further information about each switch.
CN4Y for FAN control (PAC-YU25HT)
<Image>
CN24
CN22
X
X
Remote control board Relay circuit
Adapter
Indoor unit control board
Outdoor unit control board
retaeHcirtcelE
ecruosrewop
Electric Heater or panel heater
Red 1
White 2
• PUHY, PURY-P­TGMU type Dip switch SW5-2 “ON”
• PUHY, PURY-P­YHMU type Dip switch SW5-10 “ON”
• PUMY series Dip switch SW4-4 “ON”
Preparations in the field
Maximum cable length is 10 m (32ft)
wo lleYetihW
White 1
Dip switch SW3-2 “ON”
(applicable only when a panel heater is connected)
3
CN4Y
Page 25
[ VII Microprocessor Control ]
- 18 -
HWE08010 GB
2) PEFY-P-NMHU-E, PDFY-P-NMU-E and other models
For relay X use the specifications given below Operation coil
Rated voltage: 12VDC Power consumption: 0.9W or less * Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.
The length of the electrical wiring for the PAC-YU25HT is 2 meters (6-1/2 ft.)To extend this length, use sheathed 2-core cable.
Control cable type: CVV, CVS, CPEV or equivalent. Cable size: 0.5 mm
2
~ 1.25 mm2 (16 to 22 AWG)
Don't extend the cable more than 10 meters (32ft)
(4) Wiring restrictions
Keep the length of the cable connecting to the circuit board of the indoor unit shorter than 10 meters (32ft).Longer than 10 meters (32ft) could cause improper operation.Use a transit relay when extending wiring such as remote wiring.
CN24
CN22
X
X
Remote control board Relay circuit
Adapter
Indoor unit control board
Outdoor unit control board
retaeHcirtcelE
ecruosrewop
Red 1
White 2
• PUHY, PURY-P­TGMU type Dip switch SW5-2 “ON”
• PUHY, PURY-P­YHMU type Dip switch SW5-10 “ON”
• PUMY series Dip switch SW4-4 “ON”
Preparations in the field
Maximum cable length is 10 m (32ft)
wo lleYneerG
White 1
Dip switch SW3-2 “ON”
(applicable only when a panel heater is connected)
2
Electric Heater or panel heater
Recommended circuit
Wiring diagram
1-phase power supply
208V, 230V/60Hz
Control board
FS1, 2 ----- Thermal fuse
H1, H2 ----- Heater
26H --------- Overheat protection
thermostat
88H --------- Electromagnetic contactor
FS1
FS2 FS1
FS2
R
S
R
S
CN24
H2
88H
H1
88H
26H
88H
Page 26
[ VIII Troubleshooting ]
- 19 -
HWE08010 GB
VIII Troubleshooting
[1] Troubleshooting
1. Check methods
1. Component and check points (1) Thermistor
Room temperature thermistor (TH21)Liquid pipe thermistor (TH22)Gas pipe thermistor (TH23)
Disconnect the connector and measure the resistance between terminals with a tester. (Ambient temperature 10°C - 30°C[50°F-86°F])
1) Thermistor characteristic graph
(2) Fan motor (CNMF)
Refer to the page on "DC fan motor (fan motor/indoor control board)."
(3) Linear expansion valve
Disconnect the connector, and measure the resistance between terminals with a tester. Refer to the next page for details.
Normal Abnormal
4.3k - 9.6k Open or short
(Refer to the thermistor characteristic graph below.)
Low-temperature thermistor
Room temperature thermistor (TH21)Liquid pipe thermistor (TH22)Gas pipe thermistor (TH23)Drain sensor (DS)
Thermistor R
0
= 15 k 3%
Multiplier of B = 3480 k 2%
0°C 32°F 15k 10°C 50°F 9.6k 20°C 68°F 6.3k 25°C 77°F 5.2k 30°C 86°F 4.3k 40°C 104°F 3.0k
(A) Temperature (°C)[°F]
(B) Resistance (k )
Normal Abnormal
1-5 2-6 3-5 4-6 Open or short
White-Red Yellow-Brown Orange-Red Blue-Brown
200 k 10%
(A) Brown (D) Orange
(B) Red (E) Yellow
(C) Blue (F) White
Rt = 15 exp { 3480( ) }
1
273+t
1
273
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
-4 14 32 50 68 86 104 122
(A)
(B)
1 2 3 4 5 6
LEV
M
(A)
(B)
(C)
(D)
(E)
(F)
CN60
Page 27
[ VIII Troubleshooting ]
- 20 -
HWE08010 GB
1) Summary of linear expansion valve (LEV) operation
The LEV is operated by a stepping motor, which operates by receiving a pulse signal from the indoor control board.The LEV position changes in response to the pulse signal.
Indoor control board and LEV connection
Pulse signal output and valve operation
The output pulse changes in the following order: When the valve closes 1 -> 2 -> 3 -> 4 -> 1
When the valve opens 4 -> 3 -> 2 -> 1 -> 4
When the valve position remains the same, all output signals will be OFF.If any output signal is missing or if the signal remains ON, the motor vibrates and makes clicking noise.
(A) Brown (F) White
(B) Red (G) Control board
(C) Blue (H) Connection (CN60)
(D) Orange (I) Drive circuit
(E) Yellow (J) Linear expansion valve
Phase
number
Output pulse
1234 ø1 ON OFF OFF ON ø2 ON ON OFF OFF ø3 OFF ON ON OFF ø4 OFF OFF ON ON
4
3
6
5
2
1
(G)
(H)
(I)
(J)
(A)
(A)
(B)
(B)
(C)
(C)
(D)
(D)
(E)
(E)
(F)
(F)
12VDC
M
4
6
2 3
5
1
Page 28
[ VIII Troubleshooting ]
- 21 -
HWE08010 GB
2) LEV operation
When the power is turned on, a pulse signal of 2200 pulses is output (valve closure signal), to bring the valve to position A.When the valve is operating normally, it is free of vibration noise. If the valve locks or when it goes from point E to A in the
figure, it makes louder noise than would be heard when there is an open phase.
Check for abnormal sound/vibration by placing the metal tip of a screwdriver against the valve and the handle side against
your ear.
3) Troubleshooting
(a) Close
(b) Open
(c) Fully open valve (2000 pulses)
(d) No. of pulses
(e) Extra tightning (80 - 100 pulse)
(f) Valve opening degree
(f)
(a)
(b)
(e)
(d)
(c)
Symptom Checking Criteria Remedy
Circuit failure on the microcomputer
Disconnect the connectors on the control board, and connect LEDs to test the cir­cuit as shown below.
Pulse signals are output for 10 seconds when the main power is turned on. If there are LEDs that do not light up at all or remain lit after the pulses are turned off, there is a problem with the driving circuit.
Replace the in­door control board if driving circuit failure is detected.
Locked LEV The motor will idle and make small clicking noise if it is run while the LEV is locked.
If this clicking noise is heard both when the valve is fully closed and while it is being opened, it indicates a problem.
Replace the LEV.
Disconnected or shorted LEV motor coils
easure the resistance between the coils with a tester (red-white, red-orange, brown-yellow, brown-blue). The normal range of resistance is 150 10%
Replace the LEV.
6 5 4 3 2 1
1 k
LED
Page 29
[ VIII Troubleshooting ]
- 22 -
HWE08010 GB
(4) Drain-up mechanism
Measure the resistance between the terminals with a tester. (coil temperature 20°C[68°F])
(5) Drain float switch (CN4F)
Disconnect the connector, and measure the resistance between terminals with a tester.
Valve closure fail­ure (leaky valve)
To check the LEV on the indoor unit, check the indoor unit liquid pipe temperature that appears on the operation monitor on the outdoor unit's multi control board while operating the indoor unit in question in the FAN mode and the other indoor units in the cooling mode.
Replace the LEV if the amount of leakage is great.
(A) Termistor (TH22)
Normally, the LEV is fully closed while the unit is in the FAN mode. If the valve is leaky, liquid pipe thermistor reading will be lower than normal. If it is significantly lower than the inlet temperature on the remote controller, valve closure failure is suspected. If the amount of leakage is insignificant, replacement of LEV is unnec­essary unless it is causing a problem.
Misconnections of connectors or con­tact failure
Perform a visual check for disconnected connectors. Perform a visual check of lead wire color.
Disconnect the connectors on the control board and perform a continuity test.
Symptom Checking Criteria Remedy
(A)
LEV
Normal Abnormal
340 Open or short
(A) Moving part
(B) Switch
(C) Magnet
Position of the moving part Normal Abnormal
Up Short (any position but short)
Down Open (any position but open)
1
3
1 2 3 4
(A)
(A)
(B)
(C)
Page 30
[ VIII Troubleshooting ]
- 23 -
HWE08010 GB
2. DC fan motor (fan motor/indoor control board)
1. CAUTION
A high voltage is applied to the connector for connection to the fan motor (CNMF). Do not unplug the connector CNMF with the unit energized to avoid damage to the indoor control board and fan motor.
2. Troubleshooting Symptom: Indoor unit fan does not run.
Check fan motor connector contact (CNMF).
Replace the indoor control board.
Replace the indoor control board.
Fix the connection.
Yes
No
Yes
No
Yes
No
Check the fan motor position thermistor signal. Get the motor to make a full rotation or more, and measure the voltage at the test point V
FG.
(same with the voltage between fan connector 7 (+) and 4(-))
Is the fan motor connector (CNMF) fully inserted?
Is the voltage within the normal range?
Replace the motor.
Are 0VDC and 15VDC displayed alternately?
Check the power supply.
Measure the voltage at the indoor control board.
294 - 340VDC (same with the voltage between fan connector 1 (+) and 4(-))
15VDC (same with the voltage between fan connector 5 (+) and 4(-))
1 - 6.5VDC (same with the voltage between fan connector 6 (+) and 4(-))
[Values for Vsp are the values that are measured with the fan motor in operation. Vsp is 0V when the fan motor is stopped.]
V
DC
Power supply voltage
Power supply voltage V
DC
208VAC
294VDC
220VAC
311VDC
230VAC
325VDC
240VAC
340VDC
Page 31
[ VIII Troubleshooting ]
- 24 -
HWE08010 GB
3. Address switch setting
Make sure that power to the unit is turned off.
1. When using an ME remote controller, set the address with the rotary switches (SW11, SW12). Address setting is not required when the unit remote controller is used.
On-site address setting is required for the indoor units to run.
2. Address settings vary in different systems.
Refer to the section on address setting in the outdoor unit installation manual.
3. Address is set with a combination of SW12 (10's digit) and SW11 (1's digit).
To set the address to "3," set SW12 to "0" and SW11 to "3." To set the address to "25," set SW 12 to "2" and SW 11 to "5."
(A) Indoor unit control board
(B) Factory setting (all models)
ON
OFF
ON
OFF
(A)
(B)
1
2
Page 32
[ VIII Troubleshooting ]
- 25 -
HWE08010 GB
4. Voltage test points on the control board
1. PEFY-P06,08,12,15,18,24NMSU-E
Fuse Fuse(AC 250V 6.3A)
CND Power supply voltage (208 -
230VAC)
CN2M For M-NET transmission cable
connection (24 - 30VDC)
SWE Emergency operation
SW2 Capacity setting
SW4 Function setting
CN42 For address board connection
SW3 Function setting
CN81 For address board connection
CN32 Remote start/stop adapter
CN3A For MA remote controller cable
connection (10 - 13 VDC (Between 1 and 3.))
CN4Y For fan control
CN52 Remote display
CN51 Centralized control
CN41 JAMA standard HA terminal A
CN44 Thermistor (liquid/gas tempera-
ture)
CN4F Float thermistor
CN24 For heater control
CN20 Thermistor (Inlet temperature)
CN3C Indoor-outdoor transmission
(0 - 24VDC)
CNMF Fan motor output
1 - 4: 310 - 340 VDC 5 - 4: 15 VDC 6 - 4: 0 - 6.5 VDC 7 - 4: Stop 0 or 15 VDC
Run 7.5 VDC (0 - 15 pulse)
CNP Drain-up mechanism output
(200VAC)
(*1)
V
FG
Voltage on the (-) side of PC941 and C25 (Same with the voltage between 7 (+) and 4 (-) of CNMF)
V
CC
Voltage between the C25 pins 15 VDC (Same with the voltage between 5 (+) and 4 (-) of CNMF)
Vsp Voltage between the C951 pins
0VDC (with the fan stopped) 1 - 6.5VDC (with the fan in opera­tion) (Same with the voltage between 6 (+) and 4 (-) of CNMF)
Fuse
CND
С25(*1)
CN2M
SWE
SW2
SW4
CN42
SW3
CN81
CN32
LED2 CN3A CN60 CN4Y
CN52
CN51
CN41
CN44
CN4F
CN20
CN24
CN3C
LED1
PC941(*1)
C951(*1)
CNMF
CNP
Page 33
[ VIII Troubleshooting ]
- 26 -
HWE08010 GB
5. Dipswitch setting (Factory setting)
1. Function setting
(1) SW1
1) Adress board
(2) SW3
*1 Please don't use SW3-9,10 as trouble might be caused by the usage condition.
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Switch position Function Switch setting
ON OFF
1 Active Thermistor (Intake air ther-
mistor)
Built-in thermistor on the remote controller
Indoor unit
2 Filter clogging detection Available Unavailable 3 Filter life 2500 hr 100 hr 4 Outdoor air intake Enabled Disabled 5 Remote display Thermo-ON signal Fan output 6 Humidifier operation During heating mode During heating operation 7 Fan speed Low Very low 8 Fan speed at heating Thermo-OFF Preset fan speed Follows the setting of SW1-7 9 Auto restart after power failure Enabled Disabled
10 Power start/stop Enabled Disabled
Factory setting
Switch position Function Switch setting
ON OFF 1 Unit type Cooling only Heat pump 2- - ­3- - ­4 Heater backup Enabled Disabled 5- - ­6- - ­7- - ­8 Sensible temprature correction Disabled Enabled 9 Superheat setting tempurature*1 - -
10 Sub cool setting tempurature*1 - -
Factory setting
PEFY-P06NMSU-E
PEFY-P15NMSU-E
PEFY-P08NMSU-E
PEFY-P18NMSU-E
PEFY-P12NMSU-E
PEFY-P24NMSU-E
Page 34
[ VIII Troubleshooting ]
- 27 -
HWE08010 GB
2. Capacity code setting (1) SW2
1) Indoor control board Dipswitch settings must be made while the unit is stopped.
Factory setting The switches are set to correspond to the unit capacity.
3. Model setting
(1) SW4
1) Indoor control board Dipswitch settings must be made while the unit is stopped.
Note: Changes made to the dipswitches SW1, SW2, and SW3 will become effective when the unit comes to a stop (remote controller off). There is no need to power cycle the unit.
4. External static pressure
(1) SWA, SWC
1) Address board
Note: Changes that are made to the dipswitches SWA and SWC immediately become effective regardless of the unit's operation status (RUN/STOP) or the remote controller status (ON/OFF).
5. 1's and 10's digits
(1) SW11, SW12 (Rotary switch)
The use of a network remote controller (PAR-F27MEA) requires address setting.
1) Address board Address settings must be made while the unit is stopped.
Factory setting
All models Factory
setting
(A) Option (B) Standard
Factory setting
PEFY-P08NMSU-EPEFY-P06NMSU-E PEFY-P12NMSU-E
PEFY-P15NMSU-E PEFY-P18NMSU-E PEFY-P24NMSU-E
1
2
3
SWA SWC
1
2
3
SWA SWC
1
2
3
SWA SWC
1
2
3
SWA SWC
1
2
1
2
1
2
1
2
5[0.02] 15[0.06] 35[0.14] 50[0.20]
Pa[in.WG]
1
2
3
(B)
(A)
SWA SWC
1
2
Page 35
[ VIII Troubleshooting ]
- 28 -
HWE08010 GB
6. Connection No. setting
(1) SW14 (Rotary switch)
This switch is used when the unit connected to an R2 series of outdoor unit.
1) Address board
Note: Changes to the dipswitches SW11, SW12, SW14, and SW15 must be made while the unit is stopped and the remote controller is OFF.
Factory setting
Page 36
[ IX Disassembly Procedure ]
- 29 -
HWE08010 GB
IX Disassembly Procedure
[1] Disassembly Procedure
1. Control box
Exercise caution when removing heavy parts.
1. Removing the control box cover (1) Remove the two fixing screws on the cover (A) to remove
it.
Fig.1
Fig.2
(A)
Page 37
[ IX Disassembly Procedure ]
- 30 -
HWE08010 GB
2. Thermistor (Intake air)
Exercise caution when removing heavy parts.
1. Remove the control box cover according to the procedure in section [1].
2. Remove the thermistor.
(1) Remove the two fixing screws on the metal base (B) to re-
move it.
Fig.3
(2) Pull out the thermistor holder (C) and thermistor (D) on
the control box.
Fig.4
(B)
(C), (D)
Page 38
[ IX Disassembly Procedure ]
- 31 -
HWE08010 GB
3. Drainpan
Exercise caution when removing heavy parts.
1. Removing the filter and the bottom plate
(1) Push down the tab on the filter, and pull out the filter in
the direction of the arrow 1.
(2) Remove the fixing screws on the bottom plate (D), (E) to
remove it.
Fig.5
2. Removing the drainpan
(1) Pull out the drain pan in the direction of the arrow 1.
Fig.6
Note
Drain the water out of the drain pan before removing
it.
To avoid dew condensation, use insulated screws in
the places marked with circles in Figure 7.
Fig.7
(a) Insulation material
(D)
(a)
(a)
(a)
(a)
(E)
(a)
(E)
Page 39
[ IX Disassembly Procedure ]
- 32 -
HWE08010 GB
4. Thermistor (Gas pipe) (Liquid pipe)
Exercise caution when removing heavy parts.
1. Remove the drain pan according to the procedure in sec­tion [1].
2. Removing the Heat exchanger cover
(1) Remove the four fixing screws on the heat exchanger cov-
er (F) to remove it.
Fig.8
3. Removing the thermistor
(1) Remove the thermistor (G) from the thermistor holder (H)
on the copper tube.
Thermistor size Liquid pipe: ø8mm Gas pipe: ø6mm
Fig.9
HEX
(F)
(G), (H)
Page 40
[ IX Disassembly Procedure ]
- 33 -
HWE08010 GB
5. Fan and fan motor
Exercise caution when removing heavy parts.
1. Removing the filter and the bottom plate
(1) Push down the tab on the filter, and pull out the filter in the
direction of the arrow 1.
(2) Remove the fixing screws on the bottom plate (J) to re-
move it.
Fig.10
(a) Tab
2. Removing the punching metal
(1) Remove the two fixing screws on the punching metal (K)
to remove it.
Fig.11
3. Removing the fan casing (bottom half)
(1) Squeeze the tabs on the fan casing to remove it in the di-
rection of arrow 2.
4. Removing the motor cable
(1) Remove the motor cable threw the rubber bush.
5. Removing the fan motor and the Sirocco fan
(1) Remove the two motor fixing screws to remove the motor
and the Sirocco fan in the direction of arrow 3.
Fig.12
(2) Remove the four fan case fixing screws to take the top
half of the fan casing off.
Fig.13
(J)
(a)
(a)
(a)
(a)
(K)
(a)
Page 41
[ IX Disassembly Procedure ]
- 34 -
HWE08010 GB
6. Bearing
P15, P18, P24 models only. Exercise caution when removing heavy parts.
1. Removeing the bearing
(1) Remove the two fixing screws on the bearing cover (M)
to remove it.
Fig.14
(2) Remove the two bearing retainer screws to remove the
bearing.
Fig.15
(M)
Page 42
[ IX Disassembly Procedure ]
- 35 -
HWE08010 GB
7. Heat exchanger
Exercise caution when removing heavy parts.
1. Remove the drain pan according to the procedure in section [1].
2. Remove the heat exchanger cover according to the proce­dure in section [4] 2.
3. Removing the cover
(1) Remove the two fixing screws on the cover (T) to remove it.
Fig.16
(T) Pipe support plate
4. Removing the Heat exchanger
(1) Remove the fixing screws on the heat exchanger (S) to re-
move it.
Fig.17
(T)
(S)
Page 43
Jul. 2008 HWE08010 Printed in Japan
New publication, effective Jul. 2008 Specifications subject to change without notice
Loading...