Read before installation and performing electrical work
Thoroughly read the following safety precautions prior to installation.
Observe these safety precautions for your safety.
This equipment may have adverse effects on the equipment on the same power supply system.
Contact the local power authority before connecting to the system.
Symbol explanations
WARNING
This symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or death.
CAUTION
This symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or dam-
age to the unit.
Indicates an action that must be avoided.
Indicates important instructions.
Indicates a parts that requires grounding.
Indicates that caution must be taken with rotating parts. (This symbol is on the main unit label.) <Color: Yellow>
Indicates that the parts that are marked with this symbol pose a risk of electric shock. (This symbol is on the main
unit label.) <Color: Yellow>
WARNING
Carefully read the labels affixed to the main unit.
WARNING
Ask your dealer or a qualified technician to install the unit.
Improper installation by the user may result in water leakage, electric shock, or fire.
Properly install the unit on a surface that can withstand its
weight.
Unit installed on an unstable surface may fall and cause injury.
Only use specified cables. Securely connect each cable so
that the terminals do not carry the weight of the cable.
Improperly connected cables may produce heat and start a
fire.
Take appropriate safety measures against wind gusts and
earthquakes to prevent the unit from toppling over.
Improper installation may cause the unit to topple over and
cause injury or damage to the unit.
Only use accessories (i.e., air cleaners, humidifiers, electric
heaters) recommended by Mitsubishi Electric.
Do not make any modifications or alterations to the unit.
Consult your dealer for repair.
Improper repair may result in water leakage, electric shock,
or fire.
Do not touch the heat exchanger fins with bare hands.
The fins are sharp and pose a risk of cuts.
In the event of a refrigerant leak, thoroughly ventilate the
room.
If gaseous refrigerant leaks out and comes in contact with
an open flame, toxic gases will be generated.
Properly install the unit according to the instructions in the
Installation Manual.
Improper installation may result in water leakage, electric
shock, or fire.
Have all electrical work performed by an authorized electrician according to the local regulations and the instructions
in this manual. Use a dedicated circuit.
Insufficient power supply capacity or improper installation
of the unit may result in malfunctions of the unit, electric
shock, or fire.
HWE09040GB
ii
Page 3
WARNING
Keep electrical parts away from water.
Wet electrical parts pose a risk of electric shock, smoke, or
fire.
Securely attach the control box cover.
If the cover is not installed properly, dust or water may infiltrate and pose a risk of electric shock, smoke, or fire.
Only use the type of refrigerant that is indicated on the unit
when installing or relocating the unit.
Infiltration of any other types of refrigerant or air into the unit
may adversely affect the refrigerant cycle and may cause
the pipes to burst or explode.
When installing the unit in a small space, take appropriate
precautions to prevent leaked refrigerant from reaching the
limiting concentration.
Leaked refrigerant gas will displace oxygen and may cause
oxygen starvation. Consult your dealer before installing the
unit.
Consult your dealer or a qualified technician when moving
or reinstalling the unit.
Improper installation may result in water leakage, electric
shock, or fire.
After completing the service work, check for a refrigerant
leak.
If leaked refrigerant is exposed to a heat source, such as a
fan heater, stove, or electric grill, toxic gases will be generated.
Do not try to defeat the safety features of the unit.
Forced operation of the pressure switch or the temperature
switch by defeating the safety features for these devices, or
the use of accessories other than the ones that are recommended by Mitsubishi Electric may result in smoke, fire, or
explosion.
Consult your dealer for proper disposal method.
Do not use a leak detection additive.
Precautions for handling units for use with R410A
CAUTION
Do not use the existing refrigerant piping.
A large amount of chlorine that may be contained in the residual refrigerant and refrigerator oil in the existing piping
may cause the refrigerator oil in the new unit to deteriorate.
Use refrigerant piping materials made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the
pipes clean and free of such contaminants as sulfur, oxides,
dust, dirt, shaving particles, oil, and moisture.
Contaminants in the refrigerant piping may cause the refrigerator oil to deteriorate.
Store the piping materials indoors, and keep both ends of
the pipes sealed until immediately before brazing. (Keep elbows and other joints wrapped in plastic.)
Infiltration of dust, dirt, or water into the refrigerant system
may cause the refrigerator oil to deteriorate or cause the
compressor to malfunction.
Use a small amount of ester oil, ether oil, or alkyl benzene
to coat flares and flanges.
Infiltration of a large amount of mineral oil may cause the refrigerator oil to deteriorate.
Charge the system with refrigerant in the liquid phase.
If gaseous refrigerant is drawn out of the cylinder first, the
composition of the remaining refrigerant in the cylinder will
change and become unsuitable for use.
Only use R410A.
The use of other types of refrigerant that contain chloride
may cause the refrigerator oil to deteriorate.
Use a vacuum pump with a check valve.
If a vacuum pump that is not equipped with a check valve is
used, the vacuum pump oil may flow into the refrigerant cycle and cause the refrigerator oil to deteriorate.
Prepare tools for exclusive use with R 410A. Do not use the
following tools if they have been used with the conventional
refrigerant: gauge manifold, charging hose, gas leak detector, check valve, refrigerant charge base, vacuum gauge,
and refrigerant recovery equipment.
If the refrigerant or the refrigerator oil that may be left on these
tools are mixed in with R410A, it may cause the refrigerator oil
in the new system to deteriorate.
Infiltration of water may cause the refrigerator oil to deteriorate.
Leak detectors for conventional refrigerants will not detect an
R410A leak because R410A is free of chlorine.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of the refrigerant
in the cylinder will change and become unsuitable for use.
Exercise special care when handling tools for use with R410A.
Infiltration of dust, dirt, or water into the refrigerant system
may cause the refrigerator oil to deteriorate.
[Operation] Button13Position of built-in room thermistor
6[Fan Speed] Button14[Set Time] Button
Keep the remote controller out of direct sunlight to ensure accurate measurement of room temperature.
The thermistor at the lower right-hand section of the remote controller must be free from obstructions to ensure accurate mea-
Power source1-phase 208/230V 60Hz
Cooling capacity*1 BTU / h 6,0008,00012,00015,000
(Nominal)*1 kW 1.82.33.54.4
Power inputkW 0.060.060.090.09
Current inputA 0.560.560.660.67
Heating capacity*2 BTU / h 6,7009,00013,50017,000
(Nominal)*2 kW 2.02.64.05.0
Power inputkW 0.040.040.070.07
Current inputA 0.450.450.550.56
External finishGalvanized
External dimension H x W x Din.9-13/16x27-9/16x28-7/8 9-13/16x27-9/16x28-7/8 9-13/16x27-9/16x28-7/8 9-13/16x35-7/16x28-7/8
mm250 x 700 x 732250 x 700 x 732250 x 700 x 732250 x 700 x 732
Net weightlbs (kg)51(23)51(23)51(23)58(26)
Heat exchangerCross fin(Aluminium fin and copper tube)
FANType x QuantitySirocco fan x 1Sirocco fan x 1Sirocco fan x 1Sirocco fan x 1
Externalin.WG0.14-0.20-0.28-0.40-0.60
static press.Pa35-50-70-100-150
Motor typeDC brushless motor
Motor outputkW 0.085 0.085 0.085 0.085
Driving mechanismDirect-driven by motor
Airflow ratecfm212-265-300212-265-300265-318-371353-424-494
(Low-Mid-High)m3 / min6.0-7.5-8.56.0-7.5-8.57.5-9.0-10.510.0-12.0-14.0
L / s100-125-142100-125-142125-150-175167-200-233
Sound pressure level
(Low-Mid-High)
(measured in anechoic room)
Insulation materialEPS, Polyethylene foam,Urethane foam
Air filter PP Honeycomb fabric
Protection device Fuse
Refrigerant control device LEV
Connectable outdoor unit R410A,R22 CITY MULTI
Refrigerant cycle StandardDocument Installation Manual, Instruction Book
attachmentAccessory Insulation pipe for refrigerant pipe, Washer, Drain hose, Tie band
Optional External heater adaptorPAC-YU25HT
partsFilter boxPAC-KE91TB-EPAC-KE91TB-EPAC-KE91TB-EPAC-KE92TB-E
RemarkInstallationDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other
Level difference : 0 ft. (0 m)0 ft. (0 m)*Above specification data is
*The external static pressure is set to 0.20in. WG(50Pa) at factory shipment.subject to rounding variation.
*Due to continuing improvement, above specification may be subject to change without notice.
dB <A>26-28-2926-28-2928-30-3428-30-34
in. (mm)
in. (mm)
(26.7degC D.B. / 19.4degC W.B.)(21.1degC D.B.)BTU/h = kW x 3,412
(35degC D.B.)(8.3degC D.B. / 6.1degC W.B.)lbs = kg / 0.4536
items shall be referred to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
HWE09040GB
- 4 -
Page 10
[ III Specifications ]
ModelPEFY-P18NMAU-EPEFY-P24NMAU-EPEFY-P27NMAU-EPEFY-P30NMAU-E
Power source1-phase 208/230V 60Hz
Cooling capacity*1 BTU / h 18,00024,00027,00030,000
(Nominal)*1 kW 5.37.07.98.8
Power inputkW 0.110.120.140.14
Current inputA 0.771.041.181.18
Heating capacity*2 BTU / h 20,00027,00030,00034,000
(Nominal)*2 kW 5.97.98.810.0
Power inputkW 0.090.100.120.12
Current inputA 0.660.931.071.07
External finishGalvanized
External dimension H x W x Din.9-13/16x35-7/16x28-7/8 9-13/16x43-5/16x28-7/8 9-13/16x43-5/16x28-7/8 9-13/16x43-5/16x28-7/8
mm250 x 900 x 732250 x 1100 x 732250 x 1100 x 732250 x 1100 x 732
Net weightlbs (kg)58(26)71(32)71(32)71(32)
Heat exchangerCross fin(Aluminium fin and copper tube)
FANType x QuantitySirocco fan x 1Sirocco fan x 2Sirocco fan x 2Sirocco fan x 2
Externalin.WG0.14-0.20-0.28-0.40-0.60
static press.Pa35-50-70-100-150
Motor typeDC brushless motor
Motor outputkW 0.085 0.121 0.1210.121
Driving mechanismDirect-driven by motor
Airflow ratecfm424-512-600477-565-671512-636-742512-636-742
(Low-Mid-High)m3 / min12.0-14.5-17.013.5-16.0-19.014.5-18.0-21.014.5-18.0-21.0
L / s200-242-283225-267-317242-300-350242-300-350
Sound pressure level
(Low-Mid-High)
(measured in anechoic room)
Insulation materialEPS, Polyethylene foam,Urethane foam
Air filter PP Honeycomb fabric
Protection device Fuse
Refrigerant control device LEV
Connectable outdoor unit R410A,R22 CITY MULTI
Refrigerant cycle StandardDocument Installation Manual, Instruction Book
attachmentAccessory Insulation pipe for refrigerant pipe, Washer, Drain hose, Tie band
Optional External heater adaptorPAC-YU25HT
partsFilter boxPAC-KE92TB-EPAC-KE93TB-EPAC-KE93TB-EPAC-KE93TB-E
RemarkInstallationDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other
Level difference : 0 ft. (0 m)0 ft. (0 m)*Above specification data is
*The external static pressure is set to 0.20in. WG(50Pa) at factory shipment.subject to rounding variation.
*Due to continuing improvement, above specification may be subject to change without notice.
dB <A>28-32-3529-32-3630-34-3830-34-38
in. (mm)
in. (mm)
(26.7degC D.B. / 19.4degC W.B.)(21.1degC D.B.)BTU/h = kW x 3,412
(35degC D.B.)(8.3degC D.B. / 6.1degC W.B.)lbs = kg / 0.4536
items shall be referred to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
HWE09040GB
- 5 -
Page 11
[ III Specifications ]
ModelPEFY-P36NMAU-EPEFY-P48NMAU-EPEFY-P54NMAU-E
Power source1-phase 208/230V 60Hz
Cooling capacity*1 BTU / h 36,00048,00054,000
(Nominal)*1 kW 10.614.115.8
Power inputkW 0.24 0.340.36
Current inputA 1.502.082.24
Heating capacity*2 BTU / h 40,00054,00060,000
(Nominal)*2 kW 11.715.817.6
Power inputkW 0.220.320.34
Current inputA 1.391.972.13
External finishGalvanized
External dimension H x W x Din.9-13/16x55-1/8x28-7/89-13/16x55-1/8x28-7/89-13/16x63x28-7/8
mm250 x 1400 x 732250 x 1400 x 732250 x 1600 x 732
Net weightlbs (kg)93(42)93(42)102(46)
Heat exchangerCross fin(Aluminium fin and copper tube)
FANType x QuantitySirocco fan x 2Sirocco fan x 2Sirocco fan x 2
Externalin.WG0.14-0.20-0.28-0.40-0.60
static press.Pa35-50-70-100-150
Motor typeDC brushless motor
Motor outputkW 0.2440.2440.244
Driving mechanismDirect-driven by motor
Airflow ratecfm812-989-1165989-1201-14121042-1254-1483
(Low-Mid-High)m3 / min23.0-28.0-33.028.0-34.0-40.029.5-35.5-42.0
L / s383-467-550467-567-667492-592-700
Sound pressure level
(Low-Mid-High)
(measured in anechoic room)
Insulation materialEPS, Polyethylene foam,Urethane foam
Air filter PP Honeycomb fabric
Protection device Fuse
Refrigerant control device LEV
Connectable outdoor unit R410A,R22 CITY MULTI
Refrigerant cycle StandardDocument Installation Manual, Instruction Book
attachmentAccessory Insulation pipe for refrigerant pipe, Washer, Drain hose, Tie band
Optional External heater adaptorPAC-YU25HT
partsFilter boxPAC-KE94TB-EPAC-KE94TB-EPAC-KE95TB-E
RemarkInstallationDetails on foundation work, duct work, insulation work, electrical wiring, power source switch, and other
Level difference : 0 ft. (0 m)0 ft. (0 m)*Above specification data is
*The external static pressure is set to 0.20in. WG(50Pa) at factory shipment.subject to rounding variation.
*Due to continuing improvement, above specification may be subject to change without notice.
dB <A>32-37-4135-40-4436-41-45
in. (mm)
in. (mm)
(26.7degC D.B. / 19.4degC W.B.)(21.1degC D.B.)BTU/h = kW x 3,412
(35degC D.B.)(8.3degC D.B. / 6.1degC W.B.)lbs = kg / 0.4536
(A)Space required for service and maintenance.
(B)Provide an access door for maintenance at the bottom.
Note1 Use M10 suspension bolts. (not supplied)
2 Provide an access door for maintenance at the bottom.
3 The dimensions in the table are those of the PEFY-P24, 27, 30, 36, 48, 54NMAU-E models, which have 2
fans. The PEFY-P06, 08, 12, 15, 18NMAU-E model have 1 fans.
4 To connect an intake duct, uninstall the air filter on the unit, and install a locally procured air filter on the intake
duct on the intake side.
5 Heat air to 0°C(32°F) or higher when taking fresh air with a fresh air intake.
F01Fuse AC 250V 6.3ACN105Connector (IT terminal)SW11
ZNR01,02VaristorCN2AConnector (0-10V Analog in-
put)
DSAArresterFSFloat switchSW14
X01Aux. relayTH21Thermistor (inlet air temp.de-
tection)
X10Aux. relayTH22Thermistor (piping temp.de-
tection / liguid)
ACLAC reactor (Power factor im-
provement)
CN27Connector (Damper)SW1
TH23Thermistor (piping temp. de-
tection / gas)
Switch (for mode selection)
(I.B.)
BOL
(I.B.)
(I.B.)
(I.B.)
SW5
(I.B.)
(I.B.)
(I.B.)
SW12
(I.B.)
(I.B.)
SWA
(I.B.)
SWC
(I.B.)
NAME
Switch (for capacity code)
Switch (for mode selection)
Switch (for model selection)
Switch (for mode selection)
Connector (emergency operation)
Switch (1s digit address set)
Switch (10ths digit address
set)
Switch (BRANCH No.)
Switch (for static pressure selection)
Switch (for static pressure selection)
Note1 Wiring to TB2, TB5, and TB15 indicated by the double-dashed lines is on-site work.
2 terminal block, connector.
3 Use copper supply wire.
HWE09040GB
- 10 -
Page 16
[ VI Refrigerant System Diagram ]
VI Refrigerant System Diagram
[1] Refrigerant system diagram
(A)
(B)
(G)
(D)
(H)
(F)
(I)
(A)Gas pipe thermistor TH23
(B)Gas pipe
(C)Liquid pipe
(D)Brazed connections
(E)Strainer (#100 mesh)
(F)Linear expansion valve
(G)Liquid pipe thermistor TH22
(H)Heat exchanger
(I)Room temperature thermistor TH21
CapacityPEFY-
P06, 08, 12, 15NMAU-E
Gas pipeø12.7 [1/2]R410A: ø12.7 [1/2]
Liquid pipeø6.35 [1/4]R410A: ø6.35 [1/4]
PEFY-
P18NMAU-E
R22: ø15.88 [5/8]
R22: ø9.52 [3/8]
(C)
(E)(E)
PEFY-
P24, 27, 30NMAU-E
ø15.88 [5/8]R410A: ø15.88 [5/8]
ø9.52 [3/8]ø9.52 [3/8]
PEFY-
P36, 48, 54NMAU-E
R22: ø19.02 [3/4]
HWE09040GB
- 11 -
Page 17
[ VII Microprocessor Control ]
VII Microprocessor Control
[1] Microprocessor Control
1. Cool operation
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display COOL.
3. Press the [Set Temperature] button to set the desired tempera-
TIME SUN MON TUE WED THU FRI SAT
˚F˚C
TEMP.
MENU
MONITOR/SET
BACKDAY
PAR-21MAA
CLOCK
TIMER
AFTER
ONLY1Hr.
ON/OFF
ERROR CODE
˚F˚C
OPERATION
ON
OFFHrAFTER
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
ON/OFF
FILTER
CHECK
CLEAR
TEST
1. Termoregulating function
(1) Thermoregulating function (Function to prevent restarting for 3 minutes)
Room temperature desired temperature + 2°F ···Thermo ON
Room temperature desired temperature ···Thermo OFF
ture.
The set temperature changes 2°F when the [Set Temperature]
button is pressed one time. Cooling 67 to 87°F
(2) Anti-freezing control
Detected condition :
When the liquid pipe temp. (TH22) is 32°F or less in 16 minutes from compressors start up, anti-freezing control starts and
the thermo OFF.
Released condition :
The timer which prevents reactivating is set for 3 minutes, and anti-freezing control is cancelled when any one of the following
conditions is satisfied.
1) Liquid pipe temp. (TH22) turns 50°F or above.
2) The condition of the thermo OFF has become complete by thermoregulating, etc.
3) The operation modes became mode other than COOL.
4) The operation stopped.
2. Fan
(1) By the remote controller setting (switch of 3 speeds+Auto)
TypeFan speed notch
3 speeds + Auto type[Low], [Med], [High], [Auto]
When [Auto] is set, fan speed is changed depending on the value of: Room temperature - Desired temperature
3. Drain pump
(1) Drain pump control
Always drain pump ON during the COOL and DRY mode operation. (Regardless of the thermo ON/ OFF)
When the operation mode has changed from the COOL or DRY to the others (including Stop), OFF the control after the drain
pump ON for 3 minutes.
(2) Float switch control
Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF.
In the water : Detected that the float switch is ON for 15 seconds.
HWE09040GB
- 12 -
Page 18
[ VII Microprocessor Control ]
In the air : Detected that the float switch is OFF for 15 seconds.
Float SW
ON
OFF
15sec.15sec.15sec. 1min.30sec.1min.30sec.
In the waterIn the airIn the waterError
postponement
2. Dry operation
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display DRY.
3. Press the [Set Temperature] button to set the desired tempera-
TIME SUN MON TUE WED THU FRI SAT
˚F˚C
TEMP.
MENU
MONITOR/SET
BACKDAY
PAR-21MAA
CLOCK
TIMER
AFTER
ONLY1Hr.
ON/OFF
ERROR CODE
˚F˚C
OPERATION
ON
OFFHrAFTER
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
ON/OFF
FILTER
CHECK
CLEAR
TEST
1. Termoregulating function
(1) Thermo regulating function (Function to prevent restarting for 3 minutes)
Setting the Dry thermo by the thermo regulating signal and the room temperature (TH21).
Dry thermo ON Room temperature desired temperature + 2°F
Dry thermo OFF Room temperature desired temperature
ture.
The set temperature changes 2°F when the [Set Temperature]
button is pressed one time. Dry 67 to 87°F
Drain pump
abnormal
Room temperature
3 min. passed since starting operation
Thermo regulating signalRoom temperature (T1)
83°F > T1 79°F73
ON
Over 64°F
79°F > T1 75°F53
75°F > T133
OFFUnconditional310
Less than 64°FDry thermo OFF
(2) Frozen prevention control
No control function
2. Fan
(1) Indoor fan operation controlled depends on the compressor conditions.
Dry thermoFan speed notch
ON[Low]
Excluding the followingStop
OFF
Room temp. < 64°F[Low]
Dry thermo
ON time (min)
Dry thermo
OFF time (min)
T1 83°F93
HWE09040GB
- 13 -
Page 19
[ VII Microprocessor Control ]
Remote controller setting is not acceptable.
3. Drain pump
(1) Same control as COOL operation
3. Fan operation
TIME SUN MON TUE WED THU FRI SAT
TIMER
AFTER
ERROR CODE
˚F˚C
TEMP.
MENU
MONITOR/SET
BACKDAY
PAR-21MAA
CLOCK
˚F˚C
ONLY1Hr.
ON/OFF
OPERATION
ON
OFFHrAFTER
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
ON/OFF
FILTER
CHECK
CLEAR
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display FAN.
TEST
1. Fan
(1) Set by remote controller.
TypeFan speed notch
3 speeds + Auto type[Low], [Med], [High], [Auto]
When [Auto] is set, fan speed becomes [Low].
2. Drain pump
(1) Drain pump control
The drain pump turns ON for the specified amount of time when any of the following conditions is met:
1) ON for 3 minutes after the operation mode is switched from COOL or DRY to another operation mode (FAN).
2) ON for 6 minutes after the float switch is submerged in the water when the float switch control judges the sensor is in the water.
(2) Float switch control
Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF.
In the water : Detected that the float switch is ON for 15 seconds.
In the air : Detected that the float switch is OFF for 15 seconds.
Float SW
ON
OFF
15sec.15sec.15sec. 1min.30sec.1min.30sec.
In the waterIn the airIn the waterError
postponement
Drain pump
abnormal
HWE09040GB
- 14 -
Page 20
[ VII Microprocessor Control ]
4. Heat operation
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display HEAT.
3. Press the [Set Temperature] button to set the desired tempera-
TIME SUN MON TUE WED THU FRI SAT
˚F˚C
TEMP.
MENU
MONITOR/SET
BACKDAY
PAR-21MAA
CLOCK
TIMER
AFTER
ONLY1Hr.
ON/OFF
ERROR CODE
˚F˚C
OPERATION
ON
OFFHrAFTER
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
ON/OFF
FILTER
CHECK
CLEAR
TEST
1. Termoregulating function
(1) Thermoregulating function (Function to prevent restarting for 3 minutes)
Room temperature desired temperature -2°F ···Thermo ON
Room temperature desired temperature ···Thermo OFF
ture.
The set temperature changes 2°F when the [Set Temperature]
button is pressed one time. Heating 63 to 83°F.
<Display in HEAT operation>
[DEFROST]
The [DEFROST] symbol is only displayed during the defrost operation.
[STANDBY]
The [STANDBY] symbol is only displayed during the hot adjust
mode.
2. Fan
(1) By the remote controller setting (switch of 3 speeds+Auto)
TypeFan speed notch
3 speeds + Auto type[Low], [Med], [High], [Auto]
When [Auto] is set, fan speed is changed depending on the value of:
Desired temperature - Room temperature
Give priority to under-mentioned controlled mode
1) Hot adjust mode
2) Preheating exclusion mode
3) Thermo OFF mode (When the compressor off by the thermoregulating)
4) Cool air prevention mode (Defrosting mode)
5) Capacity increasing mode
(2) Hot adjust mode
The fan controller becomes the hot adjuster mode for the following conditions.
1) When starting the HEAT operation
2) When the thermoregulating function changes from OFF to ON.
3) When release the HEAT defrosting operation
Hot adjust mode *1
Set fan speed by the remote controller
[Low]
[Extra Low]
A: Hot adjust mode starts.
B: 5 minutes have passed since the condition A or the indoor liquid pipe temperature turned 95°F or more.
C: 2 minutes have passed since the condition A. (Terminating the hot adjust mode)
*1 "STAND BY" will be displayed during the hot adjust mode.
(3) Preheating exclusion mode
When the condition changes the auxiliary heater ON to OFF (thermoregulating or operation stop, etc.), the indoor fan operates
in [Low] mode for 1 minute.
HWE09040GB
CAB
- 15 -
Page 21
[ VII Microprocessor Control ]
This control is same for the model without auxiliary heater.
(4) Thermo OFF mode
When the thermoregulating function changes to OFF, the indoor fan operates in [Extra low].
(5) Heat defrosting mode
The indoor fan stops.
3. Drain pump
(1) Drain pump control
The drain pump turns ON for the specified amount of time when any of the following conditions is met:
1) ON for 3 minutes after the operation mode is switched from COOL or DRY to another operation mode (FAN).
2) ON for 6 minutes after the float switch is submerged in the water when the float swich control judges the sensor is in the water.
(2) Float switch control
Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF.
In the water : Detected that the float switch is ON for 15 seconds.
In the air : Detected that the float switch is OFF for 15 seconds.
Float SW
ON
OFF
15sec.15sec.15sec. 1min.30sec.1min.30sec.
In the waterIn the airIn the waterError
postponement
5. Auto operation [Automatic cool / heat change over operation]
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display AUTO.
3. Press the [Set Temperature] button to set the desired tempera-
TIME SUN MON TUE WED THU FRI SAT
˚F˚C
TEMP.
MENU
MONITOR/SET
BACKDAY
PAR-21MAA
CLOCK
TIMER
AFTER
ONLY1Hr.
ON/OFF
ERROR CODE
˚F˚C
OPERATION
ON
OFFHrAFTER
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
ON/OFF
FILTER
CHECK
CLEAR
TEST
1. Initial value of operation mode
(1) HEAT mode for room temperature < Desired temperature
(2) COOL mode for room temperature Desired temperature
ture.
The set temperature changes 2°F when the [Set Temperature]
button is pressed one time. Automatic 67 to 83°F
Drain pump
abnormal
2. Mode change
(1) HEAT mode -> COOL mode
Room temperature Desired temperature + 3°F. or 3 min. has passed
(2) COOL mode -> HEAT mode
Room temperature Desired temperature - 3°F. or 3 min. has passed
3. COOL mode
(1) Same control as cool operation
HWE09040GB
- 16 -
Page 22
[ VII Microprocessor Control ]
4. HEAT mode
(1) Same control as heat operation
The value "3°F" is modifiable from 1.8°F to 9°F by maintenance tool.
6. When unit is stopped control mode
1. Drain pump
(1) Drain pump control
The drain pump turns ON for the specified amount of time when any of the following conditions is met:
1) ON for 3 minutes after the operation mode is switched from COOL or DRY to another operation mode (FAN).
2) ON for 6 minutes after the float switch is submerged in the water when the float switch control judges the sensor is in the water.
(2) Float switch control
Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF.
In the water : Detected that the float switch is ON for 15 seconds.
In the air : Detected that the float switch is OFF for 15 seconds.
Float SW
ON
OFF
15sec.15sec.15sec. 1min.30sec.1min.30sec.
In the waterIn the airIn the waterError
postponement
Drain pump
abnormal
7. Heater control
1. Control specifications and DIP S/W setting
Table 1 shows how the field-installed heater is controlled. Select the desired pattern in the table below, and set the DIP S/W
on the outdoor and indoor units as shown in Table 1. See section 3 "Installation" for details. The table below shows Heater
Control patterns #A and B.
Table.2
Outdoor unit
setting
DIP S/W OFF
In the case of:
<TGMU>
S/W5-2 OFF
<THMU>
S/W5-10 OFF
<PUMY>
S/W4-4 OFF
DIP S/W ON
In the case of:
<TGMU>
S/W5-2 ON
<THMU>
S/W5-10 ON
<PUMY>
S/W4-4 ON
Condition of outdoor unit
N / A
Norm al drive
Defrost drive
Condition of O/U
a b cd
Outdoor temp.
㪧㪸㫉㪸㫄 㪼㫋㪼㫉㫊㩷a/b/c/d are set by㩷
maintenance tool.
H/P drive
H/P stop
Duct unit PE/PD/PF-NR(NL)
P06,08,12,15,18,24,27,30,36,48,
DIP S/W3-4
OFF
(Indoor unit)
DIP S/W3-4
ON
(Indoor unit)
Normal driveHeater OFFHeater OFF
DIP S/W3-4
OFF
(Indoor unit)
Defrost drive
H/P drive
H/P stop
DIP S/W3-4
ON
(Indoor unit)
Î
(PEFY-
54NMAU-E)
Heater control #A
(defrost/error:
Heater OFF)
Heater control #A
(defrost/error:
Heater ON)
Heater control #A
(defrost/error:
Heater OFF)
Heater control #B
(defrost/error:
Heater ON)
NON duct unit
(PL/PK/PC)
Heater control #A
(defrost/error:
Heater ON)
Heater control #B
(defrost/error:
Heater ON)
HWE09040GB
- 17 -
Page 23
[ VII Microprocessor Control ]
Table.3
Heater OFF
Heater control #A
Inlet air temp. set temp.
Heater ON
Inlet air temp. < set temp.-4°F
Heater control #B Heater OFF
Inlet air temp. set temp.
Heater ON
Inlet air temp. < set temp.-1.8°F
Inlet air tem p.
Set temp.
Set temp.-1.8°F
Inlet air temp.
Set temp.
Set temp.-1.8°F
Set tem p.-4°F
Heater output
ON
OFF
Heater output
ON
OFF
<For heater>
The value "4°F" is modifiable from 1.8°F to 9°F by maintenance tool.
(1) On the ducted model units (except the Fresh air intake type), turning on the heater with the fan setting set to OFF requires that
the DIP S/W and connectors on the indoor units*1 are set on site.
*1: DIP SW 3-4, CN24, and CN4Y (or CN22)
Fan control
PatternDuct unit PE/PD/PF-NR(NL)
Î
(PEFY-NMSU-E, PEFY-NMAU-E)
CN4Y or CN22 for FAN control
(YU25)
1
Disabled
2ONL / LL / Set
3
DIP S/W3-4 (Indoor unit)Fan in defrost
OFFStop (Heater OFF)
*1
(Heater ON)
OFFStop (Heater OFF)
Enabled
4ONStop (Heater ON)
*1. depend on SW1-7/1-8
SW3-1SW1-7SW1-8Fan speed
*1
OFFOFFOFFVery low
OFFONOFFLow
OFFOFFONRemote controller setting
OFFONON
ONONON
(Remote controller setting
(Remote controller setting*2)
Stop
Stop
*2
)
*1. The fan operates at the same speed settings as shown in this table during
the Heating Thermo-OFF mode.
*2. If Pattern 2 in the table above is selected for the fan control pattern, the
fan will follow the setting of the remote controller.
<Image>
CN4Y or CN22 for FAN control
(PAC-YU25HT)
Indoor unit Control board
HWE09040GB
- 18 -
Page 24
[ VII Microprocessor Control ]
(2) On the Fresh air intake type units, the heater cannot be turned on with the fan setting set to OFF.
(3) Non-ducted models do not require the settings described in Section (1) above.
Reference (not applicable to the ducted models)
PatternNON duct unit (PL/PK/PC)
CN4Y or CN22 for FAN control
*1
(YU25)
DIP S/W (Indoor unit)Fan in defrost
1N/AN/AStop (Heater ON)
*1. Refer to Section 5 "Dipswitch Setting" for further information about each switch.
(4) Back-up heating will not be performed when the heater turns on while demand control is performed (not a request item).
(5) This is applicable only to the R410 series. Make the settings for the following dip switches on the outdoor unit control board
before switching on the power.
This is applicable only to the R410A series. Make the settings for the following dip switches on the indoor unit control board
before switching on the power.
2. PAC-YU25HT (Optional Parts) installation
The following section describes installation of the External Heater Adapter that connects to CITY MULTI air conditioner R410A
series indoor unit. This products is the special wiring parts to drive an electric heater with the air conditioner.
(1) Parts list
Check that the following parts are included in the package.
1) External output cable (with a yellow connector).............................2 in total
Two types of cables with different connectors are included.
2) Panel heater connector.................................................................. 3 in total
White: 1
Green: 2 (2 types)
(2) Connection to the indoor unit
Use the cables that fit the connectors on the indoor unit control board. The items listed in this parts list cannot be used with
the following models.
PMFY-BM
PMFY-AM
1) External output cable (with a yellow connector)
This cable is used to connect a relay circuit for an interlocked operation with either an electric or a panel heater. Connect the
cable to CN24 on the indoor unit control board.
2) Panel heater connector (with a green connector)
This connector is used to perform an interlocked operation with a panel heater. Depending on the indoor unit control board
specification, connect the cable either to CN4Y or CN22 as appropriate.
(3) Locally procured wiring
A basic connection method is shown below.
1) PEFY-P-NMSU-E and other models
Remote control boardRelay circuit
retaeHcirtcelE
ecruosrewop
X
Electric Heater
or panel
heater
Preparations in the field
Indoor unit
Adapter
Red1
X
White 2
White 1
(applicable only when a panel
heater is connected)
Maximum cable length
is 10 m (32ft)
3
control board
wo
lleYe
tihW
CN24
CN22
CN4Y
Outdoor unit
control board
• PUHY, PURY-PTGMU type Dip
switch SW5-2
“ON”
• PUHY, PURY-PYHMU type Dip
switch SW5-10
“ON”
• PUMY series Dip
switch SW4-4
“ON”
HWE09040GB
- 19 -
Page 25
[ VII Microprocessor Control ]
2) PEFY-P-NMAU-E, PEFY-P-NMHU-E, PDFY-P-NMU-E and other models
Remote control boardRelay circuit
retaeHcirtcelE
ecruosrewop
X
Electric Heater
or panel
heater
Preparations in the field
Adapter
Red1
X
White 2
White 1
(applicable only when a panel
heater is connected)
Maximum cable length
is 10 m (32ft)
2
Indoor unit
control board
wolle
Ynee
r
G
CN24
CN22
For relay X use the specifications given below Operation coil
Rated voltage: 12VDC
Power consumption: 0.9W or less
* Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.
The length of the electrical wiring for the PAC-YU25HT is 2 meters (6-1/2 ft.)
To extend this length, use sheathed 2-core cable.
Control cable type: CVV, CVS, CPEV or equivalent.
Cable size: 0.5 mm
2
~ 1.25 mm2 (16 to 22 AWG)
Don't extend the cable more than 10 meters (32ft)
Outdoor unit
control board
• PUHY, PURY-PTGMU type Dip
switch SW5-2
“ON”
• PUHY, PURY-PYHMU type Dip
switch SW5-10
“ON”
• PUMY series Dip
switch SW4-4
“ON”
Recommended circuit
Wiring diagram
1-phase power
supply
208V, 230V/60Hz
R
S
R
S
Control board
88H
88H
CN24
88H
FS1
FS2
FS1
FS2
26H
H1
H2
FS1, 2 ----- Thermal fuse
H1, H2 ----- Heater
26H --------- Overheat protection
88H --------- Electromagnetic contactor
thermostat
(4) Wiring restrictions
Keep the length of the cable connecting to the circuit board of the indoor unit shorter than 10 meters (32ft).
Longer than 10 meters (32ft) could cause improper operation.
Use a transit relay when extending wiring such as remote wiring.
Refer to the page on "DC fan motor (fan motor/indoor control board)."
(3) Linear expansion valve
Disconnect the connector, and measure the resistance between terminals with a tester.
Refer to the next page for details.
NormalAbnormal
200 k10%
M
LEV
CN60
(F)
1
(E)
2
(D)
3
(C)
4
(B)
5
(A)
6
1-52-63-54-6Open or short
White-RedYellow-BrownOrange-RedBlue-Brown
(A)Brown(D)Orange
(B)Red(E)Yellow
(C)Blue(F)White
HWE09040GB
- 21 -
Page 27
[ VIII Troubleshooting ]
1) Summary of linear expansion valve (LEV) operation
The LEV is operated by a stepping motor, which operates by receiving a pulse signal from the indoor control board.
The LEV position changes in response to the pulse signal.
The output pulse changes in the following order:
When the valve closes 1 -> 2 -> 3 -> 4 -> 1
When the valve opens 4 -> 3 -> 2 -> 1 -> 4
When the valve position remains the same, all output signals will be OFF.
If any output signal is missing or if the signal remains ON, the motor vibrates and makes clicking noise.
(I)
HWE09040GB
- 22 -
Page 28
[ VIII Troubleshooting ]
2) LEV operation
(a)Close
(b)Open
(c)Fully open valve (2000 pulses)
(d)No. of pulses
(a)
(f)
(b)
(c)
(d)
(e)
(e)Extra tightning (80 - 100 pulse)
(f)Valve opening degree
When the power is turned on, a pulse signal of 2200 pulses is output (valve closure signal), to bring the valve to position A.
When the valve is operating normally, it is free of vibration noise. If the valve locks or when it goes from point E to A in the
figure, it makes louder noise than would be heard when there is an open phase.
Check for abnormal sound/vibration by placing the metal tip of a screwdriver against the valve and the handle side against
your ear.
3) Troubleshooting
SymptomChecking CriteriaRemedy
Circuit failure on
the microcomputer
Disconnect the connectors on the control board, and connect LEDs to test the circuit as shown below.
6
5
4
3
2
1 k
LED
1
Pulse signals are output for 10 seconds when the main power is turned on. If there
are LEDs that do not light up at all or remain lit after the pulses are turned off, there
is a problem with the driving circuit.
Locked LEVThe motor will idle and make small clicking noise if it is run while the LEV is locked.
If this clicking noise is heard both when the valve is fully closed and while it is being
opened, it indicates a problem.
Disconnected or
shorted LEV motor
easure the resistance between the coils with a tester (red-white, red-orange,
brown-yellow, brown-blue). The normal range of resistance is 150 10%
coils
Replace the indoor control
board if driving
circuit failure is
detected.
Replace the LEV.
Replace the LEV.
HWE09040GB
- 23 -
Page 29
[ VIII Troubleshooting ]
SymptomChecking CriteriaRemedy
Valve closure failure (leaky valve)
Misconnections of
connectors or contact failure
To check the LEV on the indoor unit, check the indoor unit liquid pipe temperature
that appears on the operation monitor on the outdoor unit's multi control board while
operating the indoor unit in question in the FAN mode and the other indoor units in
the cooling mode.
(A)Termistor (TH22)
(A)
LEV
Normally, the LEV is fully closed while the unit is in the FAN mode. If the valve is
leaky, liquid pipe thermistor reading will be lower than normal. If it is significantly
lower than the inlet temperature on the remote controller, valve closure failure is
suspected. If the amount of leakage is insignificant, replacement of LEV is unnecessary unless it is causing a problem.
Perform a visual check for disconnected connectors.
Perform a visual check of lead wire color.
Replace the LEV
if the amount of
leakage is great.
Disconnect the
connectors on
the control board
and perform a
continuity test.
(4) Drain-up mechanism
Measure the resistance between the terminals with a tester.
(coil temperature 20°C[68°F])
NormalAbnormal
1
3
340 Open or short
(5) Drain float switch (CN4F)
Disconnect the connector, and measure the resistance between terminals with a tester.
(A)Moving part
(A)
1
(B)
(C)
(B)Switch
(C)Magnet
2
3
4
(A)
Position of the moving partNormalAbnormal
UpShort(any position but short)
DownOpen(any position but open)
HWE09040GB
- 24 -
Page 30
[ VIII Troubleshooting ]
2. DC fan motor (fan motor/indoor control board)
1. CAUTION
A high voltage is applied to the connector for connection to the fan motor (CNMF).
Do not unplug the connector CNMF with the unit energized to avoid damage to the indoor control board and fan motor.
2. Troubleshooting
Symptom: Indoor unit fan does not run.
Check fan motor connector contact
(CNMF).
Is the fan motor connector
No
Fix the connection.
(CNMF) fully inserted?
V
Yes
Power supply voltage
DC
Check the power supply.
Measure the voltage at the indoor control board.
294 - 340VDC (same with the voltage between fan connector 1 (+) and 4(-))
Power supply voltageV
208VAC
220VAC
230VAC
240VAC
DC
294VDC
311VDC
325VDC
340VDC
15VDC (same with the voltage between fan connector 5 (+) and 4(-))
1 - 6.5VDC (same with the voltage between fan connector 6 (+) and 4(-))
[Values for Vsp are the values that are measured with the fan motor in operation.
Vsp is 0V when the fan motor is stopped.]
Is the voltage within the
No
Replace the indoor control board.
normal range?
Yes
Check the fan motor position thermistor signal.
Get the motor to make a full rotation or more, and measure the voltage at the test point
V
FG.
(same with the voltage between fan connector 7 (+) and 4(-))
Are 0VDC and 15VDC
displayed alternately?
Yes
Replace the indoor control board.
HWE09040GB
No
Replace the motor.
- 25 -
Page 31
[ VIII Troubleshooting ]
3. Address switch setting
Make sure that power to the unit is turned off.
(A)
(B)
ON
OFF
(A)Indoor unit control board
(B)Factory setting (all models)
1. When using an ME remote controller, set the address with the rotary switches (SW11, SW12).
Address setting is not required when the unit remote controller is used.
On-site address setting is required for the indoor units to run.
2. Address settings vary in different systems.
Refer to the section on address setting in the outdoor unit installation manual.
3. Address is set with a combination of SW12 (10's digit) and SW11 (1's digit).
To set the address to "3," set SW12 to "0" and SW11 to "3."
To set the address to "25," set SW 12 to "2" and SW 11 to "5."
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Factory setting
Note:
Changes made to the dipswitches SW1, SW2, and SW3 will become effective when the unit comes to a stop (remote controller
off). There is no need to power cycle the unit.
4. Power voltage setting
(1) SW5
1) Indoor control board
Dipswitch settings must be operated with the main power turned OFF.
Factory settingSet SW5 to 240V side when the power supply is 230 volts.
220V
(208V)
240V
(230V)
When the power supply is 208 volts, set SW5 to 220V side.
HWE09040GB
- 29 -
Page 35
[ VIII Troubleshooting ]
5. External static pressure
(1) SWA, SWC
1) Indoor control board
All modelsFactory
35Pa(0.14in.WG)
2
3
2
1
1
SWA SWC
50Pa(0.20in.WG)
2
3
2
1
1
SWA SWC
70Pa(0.28in.WG)
2
3
2
1
1
SWA SWC
100Pa(0.40in.WG)
2
3
2
1
1
SWA SWC
150Pa(0.60in.WG)
2
3
2
1
1
SWA SWC
setting
3
2
1
2
1
SWA SWC
Note:
Changes that are made to the dipswitches SWA and SWC immediately become effective regardless of the unit's operation
status (RUN/STOP) or the remote controller status (ON/OFF).
6. 1s and 10ths digits
(1) SW11, SW12 (Rotary switch)
The use of a network remote controller (PAR-F27MEA) requires address setting.
1) Indoor control board
Address settings must be made while the unit is stopped.
Factory setting
7. Connection No. setting
(1) SW14 (Rotary switch)
This switch is used when the unit connected to an R2 series of outdoor unit.
1) Indoor control board
Factory setting
Note:
Changes to the dipswitches SW11, SW12, SW14, and SW15 must be made while the unit is stopped and the remote controller
is OFF.
HWE09040GB
- 30 -
Page 36
[ IX Disassembly Procedure ]
IX Disassembly Procedure
[1] Disassembly Procedure
1. Control box
Exercise caution when removing heavy parts.
1. Removing the control box cover
(1) Remove the three fixing screws on the cover (A) to re-
move it.
(A)
Fig.1
Fig.2
HWE09040GB
- 31 -
Page 37
[ IX Disassembly Procedure ]
2. Thermistor (Intake air)
Exercise caution when removing heavy parts.
1. Remove the control box cover according to the procedure
in section [1].
2. Remove the thermistor.
(1) Pull out the thermistor holder (B) and thermistor (C) on
the control box.
(B), (C)
Fig.3
HWE09040GB
- 32 -
Page 38
[ IX Disassembly Procedure ]
3. Drainpan
Exercise caution when removing heavy parts.
1. Removing the filter and the bottom plate
(1) Push down the tab on the filter, and pull out the filter in
the direction of the arrow 1.
(2) Remove the fixing screws on the bottom plate (D), (E) to
remove it.
2. Removing the drainpan
(1) Pull out the drain pan in the direction of the arrow 2.
Note
Drain the water out of the drain pan before removing
it.
Fig.4
Fig.5
(D)
(E)
HWE09040GB
- 33 -
Page 39
[ IX Disassembly Procedure ]
4. Thermistor (Gas pipe) (Liquid pipe)
Exercise caution when removing heavy parts.
1. Remove the drain pan according to the procedure in section [1].
2. Removing the Heat exchanger cover
(1) Remove the four fixing screws on the heat exchanger cov-
er (F) to remove it.
3. Removing the thermistor
(1) Remove the thermistor (G) from the thermistor holder (H)
on the copper tube.
HEX
(F)
Fig.6
Thermistor size
Liquid pipe: ø8mm
Gas pipe: ø6mm
(G), (H)
Fig.7
HWE09040GB
- 34 -
Page 40
[ IX Disassembly Procedure ]
5. Fan and fan motor
Exercise caution when removing heavy parts.
1. Removing the filter and the bottom plate
(1) Push down the tab on the filter, and pull out the filter in the
direction of the arrow 1.
(2) Remove the fixing screws on the bottom plate (J) to re-
move it.
2. Removing the fan casing (bottom half)
(1) Squeeze the tabs on the fan casing to remove it in the di-
rection of arrow 2.
(J)
Fig.8
(a)Tab
(a)
3. Removing the motor cable
(1) Remove the motor cable threw the rubber bush.
4. Removing the fan motor and the Sirocco fan
(1) Remove the two motor fixing screws to remove the motor
and the Sirocco fan in the direction of arrow 3.
(2) Remove the four fan case fixing screws to take the top
half of the fan casing off.
Fig.9
Fig.10
HWE09040GB
Fig.11
- 35 -
Page 41
[ IX Disassembly Procedure ]
6. Heat exchanger
Exercise caution when removing heavy parts.
1. Remove the drain pan according to the procedure in section
[1].
2. Remove the heat exchanger cover according to the procedure in section [4] 2.
3. Removing the cover
(1) Remove the five fixing screws on the cover (K) to remove it.
4. Removing the Heat exchanger
(1) Remove the fixing screws on the heat exchanger (M) to re-