Mitsubishi Electric PLA-SM100EA, SUZ-SA71VA3, SUZ-SA100VA2, PEAD-SM71JA(L), PLA-SM71EA Service Manual

...
TECHNICAL & SERVICE MANUAL
No.TCH030
R410A
Outdoor unit [Model Name]
SUZ-SA71VA3 SUZ-SA71VA3.TH SUZ-SA100VA2 SUZ-SA100VA2.TH
CONTENTS
1.
COMBINATION OF INDOOR AND OUTDOOR UNITS
.....
2
2. TECHNICAL CHANGES
...................................
3
3. PARTS NAMES AND FUNCTIONS
..................
6
4. SPECIFICATION
................................................
7
5. NOISE CRITERIA CURVES
..............................
9
6. OUTLINES AND DIMENSIONS
......................
10
7. WIRING DIAGRAM
...........................................
11
8. REFRIGERANT SYSTEM DIAGRAM
.............
13
9. ACTUATOR CONTROL
...................................
14
10. SERVICE FUNCTIONS
....................................
15
11. TROUBLESHOOTING
.....................................
15
12. DISASSEMBLY INSTRUCTIONS
....................
31
Indication of model name
Note:
This service manual describes technical data of the outdoor units only.
HFC
utilized
R410A
January 2018
PARTS CATALOG (TCB030)
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
2
TCH030 TCH030
1
COMBINATION OF INDOOR AND OUTDOOR UNITS
Note: Please refer to the service manual of indoor unit or the technical data book for the combination data.
INDOOR UNIT SERVICE MANUAL
Model Name Service Ref. Service Manual No.
PLA-SM71/100EA PLA-SM71/100EA.UK
OCH683 OCB683
PEAD-SM71/100JA(L) PEAD-SM71/100JA(L) .UK
HWE17010
BWE017160
3
2
TECHNICAL CHANGES
Refrigerant
oil
Refrigerant
New refrigerant
R410A
HFC-32: HFC-125 (50%:50%)
Pseudo-azeotropic refrigerant
Not included
A1/A1
72.6
51.4
1.557 64
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
None None
Previous refrigerant
R22
R22 (100%)
Single refrigerant
Included
A1
86.5
40.8
0.94
44.4
Non combustible
0.055 1700
Gas phase
Possible
Compatible oil
Light yellow
None
Refrigerant Composition (Ratio) Refrigerant handling Chlorine Safety group (ASHRAE) Molecular weight Boiling point (°C) Steam pressure [25°C](Mpa) Saturated steam density [25°C](Kg/K) Combustibility ODP *1 GWP *2 Refrigerant charge method Additional charge on leakage Kind Color Smell
*1: Ozone Depletion Potential : based on CFC-11 *2: Global Warming Potential : based on CO
2
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
• This room air conditioner adopts an HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 conditioners. As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/materi-
als are required. Refer to the table below.
Take sufficient care not to allow water and other contaminations to enter the R410A refrigerant during storage and installa-
tion, since it is more susceptible to contaminations than R22.
For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant
piping.)
Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
NOTE : The unit of pressure has been changed to MPa on the international system of units (SI unit system).
The conversion factor is: 1 (MPa [Gauge]) =10.2 (kgf/cm
2
[Gauge])
New Specification Current Specification
The incompatible refrigerant oil easily separates from refrigerant and is in the upper layer inside the suction muffler. Raising position of the oil back hole enables to back the refrigerant oil of the upper layer to flow back to the compressor.
Since refrigerant and refrigerant oil are compatible with each other, refrigerant oil backs to the compressor through the lower position oil back hole.
Compressor
Suction muffler
Oil back hole
Refrigerant oil
Refrigerant
Compressor
Suction muffler
Oil back hole
Refrigerant oil /Refrigerant
Compressor
4
TCH030 TCH030
R410A tools Can R22 tools be used?
Gas leak detector
R410A has high pressures beyond the measurement range of existing gauges. Port diameters have been changed to prevent any other refrigerant from being charged into the unit.
Hose material and cap size have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant.
6.35 mm and 9.52 mm
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool.
Provided for flaring work (to be used with R22 flare tool). Provided to prevent the back flow of oil. This adapter enables you to use
vacuum pumps. It is difficult to measure R410A with a charging cylinder because the
refrigerant bubbles due to high pressure and high-speed vaporization
No
No
No
Yes
Yes
New
New
New
Gauge manifold
Charge hose
Torque wrench
Flare tool
Flare gauge Vacuum pump
adapter
Electronic scale for refrigerant charging
No: Not substitutable for R410A Yes: Substitutable for R410A
No 12.7 mm and 15.88 mm
1. Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools. The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
30 20 10 0 10 20
30
40 50 60
0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
(MPa [Gauge])
R410A
R22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
(:)
NOTE: The unit of pressure has been changed to MPa on the
international system of units (SI unit system).
The conversion factor is: 1 (MPa [Gauge]) =10.2 (kgf/cm
2
[Gauge])
5
Electronic scale for refrigerant charging
Outdoor unit
Refrigerant gas cylinder operating valve
Refrigerant gas cylinder for R410A with siphon
Refrigerant (liquid)
Service port
Gauge manifold valve (for R410A)
Union
Liquid pipe
Gas pipe
Stop valve
Indoor unit
Charge hose (for R410A)
R410A
Pipe diameter (mm)
6.35
9.52
12.7
15.88
17 22 26 29
Dimension of flare nut (mm)
R22
17 22 24 27
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm. Never use any pipe with a thickness less than 0.8 mm, as the pressure resistance is insufficient.
Flaring work and flare nut
Flaring work for R410A pipe differs from that for R22 pipe. For details of flaring work, refer to Installation manual “FLARING WORK”.
3. Refrigerant oil
Apply the special refrigerant oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4. Air purge
Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant circuit.
Use the vacuum pump for air purging for the purpose of environmental protection.
5. Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and
the outdoor unit. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
2. Refrigerant piping
Specifications
Use the refrigerant pipes that meet the following specifications.
Wall thicknessOutside diameter
Pipe
mm mm
For liquid
For gas
6.35
9.52
9.52
12.7
15.88
0.8
0.8
0.8
0.8
1.0
Heat resisting foam plastic Specific gravity 0.045 Thickness 8 mm
Insulation material
TCH030 TCH030
6
TCH030 TCH030
3
PARTS NAMES AND FUNCTIONS
SUZ-SA71VA3.TH SUZ-SA100VA2.TH
Model SUZ-SA·VA2(3)
Drain socket 1
Piping
Air outlet
Drain outlet
Air inlet
(back and side)
Drain hose
Piping
Air outlet
Drain outlet
Air inlet
(back and side)
Drain hose
6. Pumping Down
When relocating or disposing of the air conditioner, pump down the system by following the procedure below so that no refrigerant is released into the atmosphere.
1 Turn off the power supply (circuit breaker). 2 Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit. 3 Fully close the stop valve on the liquid pipe side of the outdoor unit. 4 Supply power (circuit breaker). 5 Perform the refrigerant collecting operation (cooling test run).
 •ForthePAR-31MAA,select“Service”→“Testrun”fromthemainmenutostartthetestrun,andthenselectthecooling 
mode.
• For details or for other information about starting the test run when using remote controllers, refer to the installation manual for the indoor unit or the remote controller. 6 Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm²) and quickly stop the air conditioner.
• Push the “ON/OFF” button on the remote controller to stop the air conditioner. Notes:
1. When the extension piping is very long with a large refrigerant amount, it may not be possible to perform a pump down operation. In this case, use refrigerant recovery equipment to collect all of the refrigerant in the system.
2. If the extension piping length for the SUZ-SA100VA is 20 m or longer, it will not be possible to perform a pump-down operation because there is a large amount of refrigerant. In this case, collect the refrigerant in the system.
7 Turn off the power supply (circuit breaker), remove the gauge manifold valve, and then disconnect the refrigerant pipes.
.Warning: When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
• If the refrigerant pipes are disconnected while the compressor is operating and the stop valve (ball valve) is open, the pressure in the refrigeration cycle could become extremely high if air is drawn in, causing the pipes to burst, personal injury, etc.
7
7
SPECIFICATION
4
NOTE: Test conditions are based on ISO 5151 Cooling : Indoor D.B. 27°C W.B. 19°C Outdoor D.B. 35°C Heating : Indoor D.B. 20°C Outdoor D.B. 7°C W.B. 6°C Refrigerant piping length (one way): 5 m *Measured under rated operating frequency.
Outdoor model
SUZ-SA71VA3.TH SUZ-SA100VA2.TH
Power supply Single phase 230V, 50Hz
Compressor
Model SNB140FRKMT SNB220FBGM1T
Output W 1,200 1,500
Current*
Cooling
A
8.30 11. 11
Heating 9.59 12.84
Refrigeration oil (Model)
L 0.4 (FV50S) 0.46 (FV50S)
Fan motor
Model RC0J60-BC RC0J60-BC
Current*
Cooling
A
0.83 0.85
Heating 0.82 0.86
Dimensions W × H × D mm 840 × 880 × 330 840 × 880 × 330
Weight kg 52 56
Special remarks
Air
ow*
Cooling
High
m³/h
3,492 3,426
Med. 3,006 3,234
Low 2,226 2,394
Heating
High 2,952 3,276
Med. 2,952 3,276
Low 2,268 2,472
Sound level*
Cooling
dB(A)
55 55
Heating
55 55
Fan speed
Cooling
High
rpm
950 950
Med. 840 900
Low 620 680
Heating
High 810 910
Med. 810 910
Low 630 700
Fan speed regulator
3 3
Refrigerantllingcapacity
(R410A)
kg 1.80 2.20
TCH030 TCH030
8
TCH030 TCH030
SUZ-SA71VA3.TH SUZ-SA100VA2.TH
Specifications and rating conditions of main electric parts
Model
Item
SUZ-SA71VA3.TH SUZ-SA100VA2.TH
Smoothing capacitor
(C61)
(C62, C63)
(CB1, 2, 3) 560μF450V
Diode module (DB61)
Fuse
(F61)
(F62) T20AL 250 V
(F701, F801, F901)
Intelligent power module
(IPM)
(IC932) 5 A 600 V
IGBT module (IC700) 20 A 600V
Power factor controller
(PFC) 20 A 600 V
(IC820) 20 A 600 V
Expansion valve coil (LEV) 12 V DC
Reactor
(L61)
(L) 340μH20A
Current-Limiting PTC thermistor
(PTC64, PTC65) 33Ω
Terminal block
(TB1, TB2) 3P
(TB)
Relay
(X63)
(X64) 20 A 250 V
(X601) 3 A 250 V
(X602) 3 A 250 V
R.V. coil (21S4) 220–240 V AC
9
9
NOISE CRITERIA CURVES
5
Test conditions Cooling: Dry-bulb temperature 35°C Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C
OUTDOOR UNIT
MICROPHONE
1 m
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
COOLING
FUNCTION
SPL(dB(A)) LINE
High
FAN SPEED
HEATING
55
55
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
NC-10
SUZ-SA71VA3.TH
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
COOLING
FUNCTION
SPL(dB(A)) LINE
High
FAN SPEED
HEATING
55
55
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
NC-10
SUZ-SA100VA2.TH
10
TCH030 TCH030
6
OUTLINES AND DIMENSIONS
Unit: mm
417.5
40
42
Drain hole
175
500
330
50
Air in
Air out
2-Oval holes 10 21
840
109
81
880
452
Service panel
99.5
164.5
195
35
44
Liquid refrigerant pipe joint Refrigerant pipe (flared)
Ø 9.52
Gas refrigerant pipe joint Refrigerant pipe (flared)
Ø 15.88
350 mm or more
100 mm or more
REQUIRED SPACE
Basically, leave this space open. Only if front and both sides are open, leave 500 mm at minimum.
100 mm or more
500 mm or more. Leave any two sides among right, left or rear open.
Air in
Bolt pitch for
installation
360
SUZ-SA71VA3.TH SUZ-SA100VA2.TH
11
7
WIRING DIAGRAM
SUZ-SA71VA3.TH
Loading...
+ 23 hidden pages