Mitsubishi PE-8GAK(T), PE-10GAK(T), PE-12GAK(T), PE-16GAK(T), PE-20GAK(T) Service Manual

Page 1
TECHNICAL & SERVICE MANUAL
CONTENTS
1.
TYPES OF CONNECTED OUTDOOR UNITS
·····2
2.SAFETY FOR USE··································3
3.PART NAMES AND FUNCTIONS ···········7
5.DATA······················································13
6.OUTLINES AND DIMENSIONS·············21
7.WIRING DIAGRAM································25
8.REFRIGERANT SYSTEM DIAGRAM···27
9.TROUBLESHOOTING···························28
10.FUNCTION SETTING····························41
11.SYSTEM CONTROL······························45
12.SERVICE DATE PART NANES·············53
13.OPTIONAL PARTS································57
Indoor unit [Model names]
PE-8GAK(T) PE-10GAK(T) PE-12GAK(T) PE-16GAK(T) PE-20GAK(T)
Indoor unit
Ceiling Concealed
Series PE
Remote controller
NOTE:
• This service manual describes technical data of indoor units.
• RoHS compliant products have <G> mark on the spec name plate.
SPLIT-TYPE, AIR CONDITIONERS
2007
Page 2
2
1
TYPES OF CONNECTED OUTDOOR UNITS
Outdoor unit
Service manual No.
HWE07070 HWE07070 HWE07070 HWE07070 HWE07070
Model name
Indoor unit
Standard Model
High static pressure motor
Steel fan
Types of connected outdoor units
Outdoor Unit List
PE - 8GAK(T) PE - 10GAK(T) PE - 12GAK(T) PE - 16GAK(T) PE - 20GAK(T)
PU - 8YAKD PU - 10YAKD PU - 12YAKD PU - 8YAKD X 2 PU - 10YAKD X 2
PE - 8GAK PE - 10GAK PE - 12GAK PE - 16GAK PE - 20GAK
PE-8GAK.TH PE-10GAK.TH PE-12GAK.TH PE-16GAK.TH PE-20GAK.TH
PE-8GAK.TH-SP
PE-10GAK.TH-SP
-
-
-
PE-8GAK.TH-MF PE-10GAK.TH-MF PE-12GAK.TH-MF
-
-
High static pressure motor
/steel fan
PE-8GAK.TH-SPMF
PE-10GAK.TH-SPMF
-
-
-
PE - 8GAKT PE - 10GAKT PE - 12GAKT PE - 16GAKT PE - 20GAKT
Standard Model
High static pressure motor
PE-8GAKT.TH PE-10GAKT.TH PE-12GAKT.TH PE-16GAKT.TH PE-20GAKT.TH
PE-8GAKT.TH-SP
PE-10GAKT.TH-SP
-
-
-
Model name
Specification
Model name
Specification
Page 3
Before conducting installation work, please read this ''SAFETY FOR USE'' carefully
for
correct installation.
Since the caution items shown here contain important description relative to safety, please
observe them without fail.
After reading, please keep it with you together the Instruction Manual, and read it again at the
movement of the unit.
The unit should not be installed by the user.
If the unit is installed improperly, explosion, water leakage, electric shock or fire may be result. Consult your dealer or specialist subcontractor for repair and movement.
For installation, conduct the work correctly by following the Installation Manual.
Improper installation may cause a fire, electrical shock or water leakage.
Install the unit on a spot sufficiently durable against the unit weight.
Insufficient durability can cause an injury by the falling down of unit.
All electric work must be performed by licensed technician, according to local regulations and the instructions given in this manual.
The units should be powered by dedicated power lines. Power lines with insufficient capacity or improper electrical work may result in electric shock or fire.
Use only the specified cables for wiring. The connections must be made secured without tension the terminals.
Improper connection or fastening can cause a fire or electrical shock.
The unit should be installed according to the instructions in order to minimize the risk of damage from earthquakes, typhoons or strong winds.
Improper installation work can cause an injury by the falling down of the unit.
The outdoor unit must be installed on stable, level surface, in a place where there is no accumulation of snow , leaves or rubbish. The outdoor unit should be installed in a location where air and noise emitted by the unit will not disturb the neighbors. The indoor unit should be securely installed.
When installing or relocating the unit, make sure that no substance other than the specified refrigerant enters the refrigerant circuit. Any presence of foreign substance such as air can cause abnormal pressure rise or explosion.
If the unit is loosely mounted, it may fall, and cause injury.
Never repair the unit, remodel or transfer it to another site by yourself.
If they are performed improperly, water leakage, electric shock or fire may result. If you need to have the unit repaired or moved, consult your dealer.
Use only the specified refrigerant (R-22) to charge the refrigerant circuit. Do not mix it with any other refrigerant and do not allow air to remain in the circuit.
Air enclosed in the circuit can cause high pressure resulting in a rupture and other hazards.
Ventilate the room if refrigerant leaks during Installation.
The refrigerant heated generates poisonous gas by decomposition which can cause poisoning.
After completing installation work, make sure that refrigerant gas has not leaked.
If refrigerant gas has leaked and exposed to fan heater, stove, oven and so on, it may generate noxious gases.
Take a proper measure to suppress the critical concentration of refrigerant if leaked when installing the unit in a small room.
The limit density is made not to be exceeded even if the refrigerant leaks by any chance. You are necessary to ventilation measures to prevent the accident. If the refrigerant leaks, hypoxia accident may caused. For the countermeasure to be taken, consult your dealer.
The terminal block cover of unit must be firmly attached to prevent entry of dust and moisture.
Improper mounting of the cover cause electric shock or fire.
Use only optional parts authorised by Mitsubishi Electric.
If the accessories are installed improperly, water leakage, electric shock or fire may result. Ask your dealer or an authorised company to install them.
Erroneous handling gives a high possibility to induce serious results such as
death or heavy injury.
Erroneous handling may induce serious injury depending on the situation.
Warning
Warning
Caution
2.1 SAFETY FOR USE
3
2
SAFETY FOR USE
Page 4
4
Never install on the place where a combustible gas might leak.
The gas may ignite or explode when the gas leaks and collects in surrounding of the unit.
When the unit is installed at telecommunication centers or hospitals, take a proper provision against noise.
The erroneous operation of air conditioner may be induced by inverter equipment, independent power device, medical equipment or communication equipment. While the erroneous operation of medical equipment or communication equipment may caused by the air conditioner.
For special use as for foods, animals/plants, precision equipment or art objects, the applicability should be confirmed beforehand.
As the use for the applications other than that designed originally may result in the deterioration of the quality. Consult your dealer in this regard.
Do not use the unit under a special atmosphere.
Installing the unit at the following places may cause a trouble, a place where much machine oil, salt sonnet, humidity or dust, spa district, a place full of sulfur gas, volatile gas, or corrosive gas, a place near high frequency processing machine.
Thermal insulation of the drain pipes is necessary prevent dew condensation.
If the drain pipes are not properly insulated, condensation will result and drip on ceiling, floor or other possessions.
The drain piping must process by surely,and insulate the drain piping not to be dewy.
When the room humidity exceeds 80% or when the drain pipe is clogged, water may drip from the indoor unit. The outdoor unit produces condensation during the heating operation. Make sure to provide drainage around the outdoor unit if such condensation is likely to cause damage.
Install drain piping according to this Installation Manual to ensure proper drainage. Place thermal insulation on the pipes to prevent condensation.
Improper drain piping may cause water leakage and damage to furniture or other possessions.
The unit must be properly earth connected.
Do not connect the earth wire to gas pipe, city water pipe, lightning rod or telephone earth wire. Improper earth connection may cause electrical shock.
When installing at a watery place, provide an electric leak breaker.
Failure to mount the electric leak breaker may cause electrical shock.
Make sure that there is a main power switch.
Use breaker or fuse with proper capacity.
Using a wire or a copper wire instead of proper capacity of fuse can cause fire or trouble. Other appliances connected to the same line could cause an overload.
For the power lines, use standard cables of sufficient current capacity.
Otherwise, current leakage, overheating or fire may occur.
When installing the power lines, do not apply tension to the cables.
The tighten or loosen the connections may cause generate heat and cause fire.
Arrange the configuration of wiring not to bring up the panel and terminal cover, and fasten the panel and terminal cover securely.
The poor mounting of the panel or terminal cover may cause the heat generation of the terminal connection, a fire or electrical shock.
Do not wash the unit with water.
If washed with water, electrical shock may be caused.
Do not handle the switch with wet hands.
Otherwise electrical shock can be resulted.
Be very careful on handling the unit.
When carrying in outdoor unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make outdoor unit unstable, resulting in a fall of it. The unit should not be carried by only one person if it is more than 20kg. Some units use PP bands for packing. Do not use any PP band for delivery purpose. Do not touch the heat exchanger fins with your bear hands. Doing so may cut your hands. Be sure to safely dispose the packaging materials. Packaging materials, such as catches and other metal or wooden parts, may cause stabs or other injuries. Tear off and discard plastic packing bags so that children will not play any of them. If children play with a plastic bag which was not torn off, it may cause a risk of suffocation.
Do not leave the mounting base being damaged.
The damaged base may cause the falling down of the unit which may give injury.
Turn on the main power switch more than 6 hours before starting operation.
Do not turn the main power switch OFF during seasons of heavy use, doing so can result in failure.
Do not touch the compressor or refrigerant piping without wearing glove on your hands.
Touching directly such part can cause a burn or frostbite as it becomes high or low temperature according to the refrigerant state.
Do not touch the metal edges inside the unit without wearing glove on your hands.
Touching directly it may injure your hands.
Do not remove the panel or the fan guard from the outdoor unit when it is running.
You could be injured if you touch rotating, hot or high­voltage parts.
Do not operate the air conditioner without the air filter set place.
Dust may accumulate, and cause a failure.
At emergency (if you smell something burning), stop operation and turn the power source switch off.
Continuing the operation without eliminating the emergency state may cause a machine trouble, fire, or electrical shock.
After stopping operation, be sure to wait for five minutes before turning off the main power switch.
Otherwise, water leakage or unit failure may occur.
Remote controller is not pushed with the thing sharpening ahead.
It occasionally causes the electric shock and the breakdown.
Do not connect the unit in the reverse phase sequence.
If connected in the reverse phase sequence, the indoor unit will not be able to provide sufficient cooling air. The fan on the outdoor unit that is connected in the reverse phase sequence will turn in the wrong direction and makes the compressor rattle, and it will result in compressor damage.
Remote controller is not installed for the place where direct sunshine strikes.
Caution
Page 5
5
2-2 SAFETY PRECAUTIONS
2-2-1 Before installation and electric work
s Before installing the unit, make sure y ou read all the “Safety
precautions.
s The Safety precautions” provide very important points re-
garding safety. Make sure you follow them.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided. : Indicates that important instructions must be followed. : Indicates a part which must be grounded. : Beware of electric shock. <Color: yellow>
Warning:
Carefully read the labels affixed to the unit.
Warning:
Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user ma y result in water leakage , electric shock, or fire.
Install the unit at a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down, resulting in injuries.
Use the specified cables for wiring. Make the connections securely so that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
Prepare for strong winds and earthquakes and install the unit at the speci­fied place.
- Improper installation may cause the unit to topple and result in injury.
Always use an filter and other accessories specified by Mitsubishi Elec­tric.
- Ask an authorized technician to install the accessories. Improper installation
by the user may result in water leakage, electric shock, or fire.
Never repair the unit. If the air conditioner must be repaired, consult the dealer.
- If the unit is repaired improperly, water leakage, electric shock, or fire may
result.
Do not touch the heat exchanger fins and metal edges.
- Improper handling may result in injury.
If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a flame, poisonous gases will
be released.
Install the air conditioner according to this Installation Manual.
- If the unit is installed improperly, water leakage, electric shock, or fire may
result.
Have all electric work done by a licensed electrician according to “Elec- tric Facility Engineering Standard” and “Interior Wire Regulations”and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is performed im-
properly, electric shock and fire may result.
Securely install the terminal cover (panel).
- If the terminal cover (panel) is not installed properly , dust or water may enter
the outdoor unit and fire or electric shock may result.
When installing and moving the air conditioner to another site, do not charge the it with a refrigerant different from the refrigerant (R22) speci­fied on the unit.
- If a different refrigerant or air is mix ed with the original refrigerant, the refrig-
erant cycle may malfunction and the unit may be damaged.
If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to prevent the saf ety
limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
- If the air conditioner is installed improperly, water leakage, electric shock, or
fire may result.
After completing installation work, make sure that refrigerant gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or
other heat source, it may generate noxious gases.
Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted
and operated forcibly, or parts other than those specified by Mitsubishi Elec­tric are used, fire or explosion may result.
To dispose of this product, consult your dealer.
The installer and system specialist shall secure safety against leakage
according to local regulation or standards.
- Following standards may be applicable if local regulation are not available.
Pay a special attention to the place, such as a basement, etc. where re­frigeration gas can stay, since refrigeration is heavier than the air.
The appliance is not intended for use by young children or infirm per­sons without supervision.
Young children should be supervised to ensure that they do not play with the appliance.
Never operate in open phase condition. Control box may be broken.
2-2-2 Before Installation
Caution:
Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
Do not use the air conditioner where food, pets, plants, precision instru­ments, or artwork are kept.
- The quality of the food, etc. may deteriorate.
Do not use the air conditioner in special environments.
- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of
the air conditioner or damage its parts.
When installing the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
- The inverter equipment, private power generator, high-frequency medical
equipment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air condi­tioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80 % or when the drain pipe is clogged,
condensation may drip from the indoor unit. P erform collectiv e drainage work together with the outdoor unit, as required.
2-2-3
Before Installation (moved) - electrical work
Caution:
Ground the unit.
- Do not connect the ground wire to gas or water pipes, lightning rods, or
telephone ground lines. Improper grounding may result in electric shock.
The reverse phase of L lines (L but the reverse phase of L lines and N line can be not be detected.
- Some electric parts should be damaged when power is supplied under the
miss wiring.
Install the power cable so that tension is not applied to the cable.
- Tension may cause the cable to break and generate heat and cause a fire.
Install an leak circuit breaker, as required.
- If an leak circuit breaker is not installed, electric shock may result.
Use power line cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
Use only a circuit breaker and fuse of the specified capacity.
- A fuse or circuit breaker of a larger capacity or a steel or copper wire may
result in a general unit failure or fire.
Do not wash the air conditioner units.
- Washing them may cause an electric shock.
Be careful that the installation base is not damaged by long use.
- If the damage is left uncorrected, the unit may f all and cause personal injury
or property damage.
Install the drain piping according to this Installation Manual to ensure proper drainage. Wrap thermal insulation around the pipes to prevent condensation.
- Improper drain piping may cause water leakage and damage to furniture
and other possessions.
1, L2, L3) can be detected (Error cord: 4103),
Page 6
6
Remote controller is not allowed to install for the place where direct sunshine strikes.
2-2-4 Before starting the test run
Caution:
Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the main power switch can
result in severe damage to internal parts. Keep the power switch turned on during the operational season.
Do not touch the switches with wet fingers.
- Touching a switch with wet fingers can cause electric shock.
Do not touch the refrigerant pipes during and immediately after opera­tion.
- During and immediately after operation, the refrigerant pipes are may be
hot and may be cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes.
Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
Do not turn off the power immediately after stopping operation.
- Always wait at least five minutes before turning off the power. Otherwise,
water leakage and trouble may occur.
Do not operate the air conditioner without the air filter set place.
- Dust may accumulate, and cause a failure.
At emergency (if you smell something burning), stop operation and turn the power source switch off.
- Continuing the operation without eliminating the emergency state may cause
a machine trouble, fire, or electric shock.
Remote controller should be pushed with finger.
- It occasionally causes the electric shock and the breakdown.
Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than 20 kg.
- Some products use PP bands for pac kaging. Do not use an y PP bands f or a
means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspend it at the specified positions on
the unit base. Also support the outdoor unit at four points so that it cannot slip sideways.
Safely dispose of the packing materials.
- Pac king materials, such as nails and other metal or wooden parts, may cause
stabs or other injuries.
- Tear apart and throw away plastic packaging bags so that children will not
play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
Page 7
Operation buttons
7
3
PART NAMES AND FUNCTIONS
Indoor (Main) Unit
Air intake duct flange
Air outlet duct flange
Air outlet
Air intake (sucks the air inside the room into the unit)
Remote controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
Set Temperature buttons
Down
Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button (Set Day button)
Opening the door.
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button (
Operation button)
To preceding operation number.
Ventilation button (
Operation button)
To next operation number.
Page 8
8
Display
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
ûFûC
ûFûC
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON OFF
Hr AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Identifies the current operation
Shows the operating mode, etc. * Multilanguage display is sup-
ported.
ÒCentrally ControlledÓ indicator
Indicates that operation of the re- mote controller has been prohib- ited by a master controller.
ÒTimer Is OffÓ indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, shows the time remaining.
ÒSensorÓ indication
Displayed when the remote controller sensor is used.
ÒLockedÓ indicator
Indicates that remote controller but- tons have been locked.
ÒClean The FilterÓ indicator
Comes on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre- sponding timer is set.
Up/Down Air Direction indica- tor
The indicator shows the direc- tion of the outcoming airflow.
ÒOne Hour OnlyÓ indicator
Displayed if the airflow is set to weak and downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off after one hour, at which time the airflow di- rection also changes.
Room Temperature display
Shows the room temperature.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is stationary.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
Caution
Only the Power on indicator lights when the unit is stopped and power supplied to the unit.
If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the Not Available
message. If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not present at the parent unit.
When power is turned ON for the first time, it is normal that “PLEASE WAIT is displayed on the room temperature indica- tion (For max. 2minutes). Please wait until this PLEASE WAIT indication disappear then start the operation.
Page 9
9
4 SPECIFICATIONS
Hi Lo
Lo
Hi
W D
H
W D
H
Liquid Gas Indoor side Outdoor side Height difference Piping length
PE-8GAK(T) PE-10GAK(T)
INDOOR UNIT
Model name
Item
Btu/h
kW
kcal/h
kW
kcal/h.W
W/W
kW
A A
kW
CMM
L/s
CMM
L/s
Pa
mmAq
dB(A)
mm mm mm
kg
lbs
kW
A A
kW
kW
m
3
/min
L/s
dB(A)
mm mm mm
kg
lbs
kg
lbs mm mm
Capacity 1 Total input
EER COP
Model name
Power supply(phase,cycle,voltage)
Input Running current
Starting current External finish Heat exchanger
Fan(drive) X No.
Fan motor output
Operation control & Thermostat Noise level ✻2 Cond. Drain connection O.D.
Dimensions
Weight
Fan
OUTDOOR UNIT
REFRIGERANT PIPING
Model name
Power supply(phase,cycle,voltage)
Input
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Heat exchanger
Fan(drive) X No.
Fan motor output
Airflow Noise level 2
Dimensions
Weigh
Fan
Refrigerant
Charge Pipe size O.D. Connection method
Between the indoor & outdoor unit
PE-8GAK(T)
3PH 4W 50Hz 380-415V
1.00
1.8
5.0
Galvanized steel
Cross fin coil
Centrifugal (direct) X 2
0.75 65
1,083
52
867 100
10
Remote control & built in
49 45
R1
400
1400
634
70
154
PU-8YAKD
3PH 4W 50Hz 380-415V
6.43
12.4 95
Munsell 3Y 7.8/1.1
Capillary tube
Hermetic
ZR94KC-TFD
5.6
Line start
Thermal relay, Thermal switch
HP switch, LP switch
Cross fin coil
Propeller(direct) X 2
0.15 X 2 160
2,667
66 1480 1047
547 197 433
R-22
6.0
13.2
15.88
25.4
Blazed
Flared/Flanged
Max. 30m Max. 50m
Gross
80,000
23.4
20,100
2.7
3.14
Net
76,000
22.4
19,200
2.58
3.01
7.43
PE-10GAK(T)
3PH 4W 50Hz 380-415V
1.10
1.9
5.0
Galvanized steel
Cross fin coil
Centrifugal (direct) X 2
0.75 80
1,333
64
1,067
100
10
Remote control & built in
50 46
R1
400
1600
634
77
169
PU-10YAKD
3PH 4W 50Hz 380-415V
9.00
16.0
125
Munsell 3Y 7.8/1.1
Capillary tube
Hermetic
ZR125KC-TFD
7.5
Line start
Thermal relay, Thermal switch
HP switch, LP switch
Cross fin coil
Propeller(direct) X 2
0.15 X 2 160
2,667
66 1480 1047
547 206 453
R-22
6.5
14.3
15.88
28.6
Blazed
Flared/Flanged
Max. 30m Max. 50m
Gross
100,000
29.3
25,100
2.48
2.9
Net
96,000
28.2
24,200
2.39
2.79
10.10
External static pressure
Airflow
NOTE : 1 Rating condition
Cooling : Indoor unit D.B.27°C, W.B.19°C
Outdoor unit D.B.35°C
Refrigerant piping length (one way) : 7.5m (in case of others)
NOTE :
2 Noise level is measured in an unacoustic room based on JIS conditions.
NOTE :
3 Guaranteed operating range is ; Outdoor D.B.20-52°C Indoor W.B.15-24°C
4-1 STANDARD SPECIFICATIONS
Page 10
10
Hi Lo
Lo
Hi
W D
H
W D
H
Liquid Gas Indoor side Outdoor side Height difference Piping length
PE-12GAK(T)
INDOOR UNIT
Model name
Item
Btu/h
kW
kcal/h
kW
kcal/h.W
W/W
kW
A A
kW
CMM
L/s
CMM
L/s Pa
mmAq
dB(A)
mm mm mm
kg
lbs
kW
A A
kW
kW
m
3
/min
L/s
dB(A)
mm mm mm
kg
lbs
kg
lbs mm mm
Capacity 1 Total input
EER COP
Model name
Power supply(phase,cycle,voltage)
Input Running current
Starting current External finish Heat exchanger
Fan(drive) X No.
Fan motor output
Operation control & Thermostat Noise level
✻2
Cond. Drain connection O.D. Dimensions
Weight
Fan
OUTDOOR UNIT
REFRIGERANT PIPING
Model name
Power supply(phase,cycle,voltage)
Input
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Heat exchanger
Fan(drive) X No.
Fan motor output
Airflow Noise level 2
Dimensions
Weigh
Fan
Refrigerant
Charge Pipe size O.D. Connection method
Between the indoor & outdoor unit
PE-12GAK(T)
3PH 4W 50Hz 380-415V
1.17
2.2
6.4
Galvanized steel
Cross fin coil
Centrifugal (direct) X 2
0.77 90
1,500
72
1,200
100
10
Remote control & built in
51 48
R1
400
1600
634
77
169
PU-12YAKD
3PH 4W 50Hz 380-415V
10.32
17.9
118
Munsell 3Y 7.8/1.1
Capillary tube
Hermetic
ZR144KC-TFD
8.6
Line start
Thermal relay, Thermal switch
HP switch, LP switch
Cross fin coil
Propeller(direct) X 2
0.15 X 2 160
2,667
66 1480 1047
547 208 458
R-22
7.0
15.4
15.88
28.6
Blazed
Flared/Flanged
Max. 30m Max. 50m
114,500
33.5
28,800
2.50
2.91
110,000
32.3
27,700
2.41
2.81
11.49
PE-16GAK(T) PE-20GAK(T)
PE-16GAK(T)
3PH 4W 50Hz 380-415V
1.55
3.8
8.5
Galvanized steel
Cross fin coil
Centrifugal (direct) X 2
1.3
120
2,000
-
-
150
15
Remote control & built in
52
-
R1
595
1947
764 130 286
PU-8YAKD X 2
3PH 4W 50Hz 380-415V
6.43 X 2
12.4 X 2
107.4
Munsell 3Y 7.8/1.1
Capillary tube
Hermetic
ZR94KC-TFD X 2
5.6 X 2
Line start
Thermal relay, Thermal switch
HP switch, LP switch
Cross fin coil
Propeller(direct) X 2
(0.15 X 2) X 2
160 / unit
2,667 / unit
66 / unit 1480 / unit 1047 / unit
547 / unit 197 / unit 433 / unit
R-22
6.0 / unit
13.2 / unit
15.88
25.4
Blazed
Flared/Flanged
Max. 30m Max. 50m
PE-20GAK(T)
3PH 4W 50Hz 380-415V
2.84
5.4 10
Galvanized steel
Cross fin coil
Centrifugal (direct) X 2
1.8
160
2,667
-
-
150
15
Remote control & built in
53
-
R1
595
1947
764 133 293
PU-10YAKD X 2
3PH 4W 50Hz 380-415V
9.00 X 2
16.0 X 2 141
Munsell 3Y 7.8/1.1
Capillary tube
Hermetic
ZR125KC-TFD X 2
7.5 X 2
Line start
Thermal relay, Thermal switch
HP switch, LP switch
Cross fin coil
Propeller(direct) X 2
(0.15 X 2) X 2
160 / unit
2,667 / unit
66 / unit 1480 / unit 1047 / unit
547 / unit 206 / unit 453 / unit
R-22
6.5 / unit
14.3 / unit
15.88
28.6
Blazed
Flared/Flanged
Max. 30m Max. 50m
Gross Net
160,000
46.8
40,200
2.78
3.24
154,000
45.3
38,900
2.69
3.14
Gross Net
14.41
200,000
58.6
50,300
2.41
2.81
190,000
55.8
47,900
2.29
2.67
Gross Net
20.84
External static pressure
Airflow
NOTE : 1 Rating condition
Cooling : Indoor unit D.B.27°C, W.B.19°C
Outdoor unit D.B.35°C
Refrigerant piping length (one way) : 7.5m (in case of others)
NOTE :
2 Noise level is measured in an unacoustic room based on JIS conditions.
NOTE :
3 Guaranteed operating range is ; Outdoor D.B.20-52°C Indoor W.B.15-24°C
Page 11
11
Item
NOTE : 1 Rating condition
Cooling : Indoor unit D.B.27°C, W.B.19°C
Outdoor unit D.B.35°C
Refrigerant piping length (one way) : 7.5m (in case of others)
NOTE :
2 Noise level is measured in an unacoustic room based on JIS conditions.
NOTE :
3 Guaranteed operating range is ; Outdoor D.B.20-52°C Indoor W.B.15-24°C
Capacity 1 Total input
EER COP
Model name
Power supply(phase,cycle,voltage)
Input Running current
Starting current External finish Heat exchanger
Fan(drive) X No.
Fan motor output
Fan
Fan
INDOOR UNIT
Airflow
External static
pressure Operation control & Thermostat
Noise level ✻2 Cond. Drain connection O.D.
Dimensions
Weight
Model name
Power supply(phase,cycle,voltage)
Input
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Heat exchanger
OUTDOOR UNIT
Fan
Fan
Fan(drive) X No.
Fan motor output
Airflow Noise level 2
Dimensions
Weigh
Refrigerant
Charge Pipe size O.D. Connection method
Between the indoor &
REFRIGERANT PIPING
outdoor unit
Liquid Gas Indoor side Outdoor side Height difference Piping length
Model name
Btu/h
kW
kcal/h
kW
kcal/h.W
W/W
kW
kW
Hi Lo
CMM
L/s
CMM
L/s
mmAq
Hi
dB(A)
Lo H
W D
mm mm mm
lbs
kW
kW
kW
3
m
L/s
dB(A) H W D
mm mm mm
lbs
lbs mm mm
A A
Pa
kg
A A
/min
kg
kg
Gross
23.4
PE-8GAK(T)
Net
76,000
22.4
19,200
(With a high static pressure motor)
80,000 20,100
7.43
2.7
3.14
2.58
3.01
PE-8GA(T)
3PH 4W 50Hz 380-415V
1.00
1.8
6.4
Galvanized steel
Cross fin coil
Centrifugal (direct) X 2
0.77 65
1,083
52
867 150
15
Remote control & built in
51 48
R1
400
1400
634
70
154
PU-8YAKD
3PH 4W 50Hz 380-415V
6.43
12.4 95
Munsell 3Y 7.8/1.1
Capillary tube
Hermetic
ZR94KC-TFD
5.6
Line start
Thermal relay, Thermal switch
HP switch, LP switch
Cross fin coil
Propeller(direct) X 2
0.15 X 2 160
2,667
66 1480 1047
547 197 433
R-22
6.0
13.2
15.88
25.4
Blazed
Flared/Flanged
Max. 30m Max. 50m
Gross
100,000
29.3
25,100
PE-10GAK(T)
Net
96,000
28.2
24,200
(With a high static pressure motor)
10.10
2.48
2.9
2.39
2.79
PE-10GA(T)
3PH 4W 50Hz 380-415V
1.10
2.1
6.4
Galvanized steel
Cross fin coil
Centrifugal (direct) X 2
0.77 80
1,333
64
1,067
150
15
Remote control & built in
52 49
R1
400
1600
634
77
169
PU-10YAKD
3PH 4W 50Hz 380-415V
9.00
16.0
125
Munsell 3Y 7.8/1.1
Capillary tube
Hermetic
ZR125KC-TFD
7.5
Line start
Thermal relay, Thermal switch
HP switch, LP switch
Cross fin coil
Propeller(direct) X 2
0.15 X 2 160
2,667
66 1480 1047
547 206 453
R-22
6.5
14.3
15.88
28.6
Blazed
Flared/Flanged
Max. 30m Max. 50m
Page 12
12
4-2. ELECTRICAL SPECIFICATIONS
Rating conditions
JIS B 8616
Indoor : D.B. 27°C (80°F), W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F), W.B. 24°C (75°F)
Input Current Starting current Outdoor unit
PE-8GAK(T)
1.00
1.8
5.0
PU-8YAKD
PE-10GAK(T)
1.10
1.9
5.0
PU-10YAKD
PE-12GAK(T)
1.17
2.2
6.4
PU-12YAKD
PE-16GAK(T)
1.55
3.8
8.5
PU-8YAKD X 2
PE-20GAK(T)
2.84
5.4
10.0
PU-10YAKD X 2
PE-8GAK(T)
(With a high static pressure motor)
1.00
1.8
6.4
PU-8YAKD
PE-10GAK(T)
(With a high static pressure motor)
1.10
2.1
6.4
PU-10YAKD
kW
A A
Indoor unit
Input Current Starting current Outdoor unit
kW
A A
Indoor unit
Page 13
13
DATA
5
5-1. PERFORMANCE DATA
Cooling capacity
Outdoor intake air D.B.¡C
20 25 30 35
Model name
PE-8GAK
PE-10GAK
PE-12GAK
PE-16GAK
PE-20GAK
Indoor Intake air W.B.¡C
CA 23,480 24,917 26,834 28,431 29,400 31,200 33,600 35,600 33,614 35,672 38,416 40,703 46,960 49,835 53,668 56,863 58,800 62,400 67,200 71,200
16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
P.C.
5.93
6.13
6.27
6.41
8.06
8.34
8.52
8.71
9.17
9.49
9.70
9.91
11.50
11.90
12.16
12.42
16.63
17.20
17.59
17.97
CA 22,921 24,358 26,275 27,872 28,700 30,500 32,900 34,900 32,814 34,872 37,616 39,903 45,842 48,717 52,550 55,745 57,400 61,000 65,800 69,800
P.C.
6.27
6.41
6.54
6.68
8.52
8.71
8.89
9.08
9.70
9.91
10.12
10.33
12.16
12.42
12.69
12.95
17.59
17.97
18.35
18.73
CA 22,042 23,400 25,237 27,074 27,600 29,300 31,600 33,900 31,556 33,500 36,130 38,759 44,085 46,800 50,474 54,147 55,200 58,600 63,200 67,800
P.C.
6.68
6.82
7.09
7.16
9.08
9.27
9.64
9.73
10.33
10.54
10.96
11.07
12.95
13.22
13.75
13.88
18.73
19.12
19.88
20.07
CA 21,004 22,442 24,358 26,275 26,300 28,100 30,500 32,900 30,070 32,128 34,872 37,616 42,008 44,883 48,717 52,550 52,600 56,200 61,000 65,800
P.C.
7.16
7.29
7.57
8.11
9.73
9.91
10.29
11.03
11.07
11.28
11.70
12.55
13.88
14.15
14.67
15.73
20.07
20.46
21.22
22.75
Outdoor intake air D.B.¡C
40 45 50 52
Model name
PE-8GAK
PE-10GAK
PE-12GAK
PE-16GAK
PE-20GAK
Indoor Intake air W.B.¡C
CA 19,886 21,483 23,320 25,157 24,900 26,900 29,200 31,500 28,469 30,756 33,386 36,015 39,772 42,967 46,640 50,314 49,800 53,800 58,400 63,000
P.C.
7.77
7.91
8.11
8.25
10.56
10.75
11.03
11.21
12.02
12.23
12.55
12.76
15.07
15.34
15.73
16.00
21.80
22.18
22.75
23.14
CA 18,528 20,126 22,042 23,879 23,200 25,200 27,600 29,900 26,526 28,812 31,556 34,186 37,057 40,251 44,085 47,758 46,400 50,400 55,200 59,800
P.C.
8.39
8.59
8.73
8.93
11.40
11.68
11.86
12.14
12.97
13.28
13.49
13.81
16.26
16.66
16.92
17.32
23.52
24.09
24.48
25.05
CA 17,236 18,722 20,505 22,213 21,581 23,442 25,674 27,814 24,675 26,802 29,355 31,801 34,471 37,443 41,009 44,427 43,163 46,884 51,349 55,628
P.C.
9.06
9.29
9.43
9.65
12.32
12.62
12.82
13.12
14.02
14.36
14.59
14.93
17.58
18.01
18.29
18.72
25.42
26.04
26.46
27.08
CA 15,522 16,860 18,466 20,005 19,436
21,111 23,122 25,049 22,222 24,138 26,437 28,640 31,044 33,721 36,932 40,010 38,872 42,223 46,244 50,098
P.C.
9.35
9.58
9.73
9.96
12.72
13.03
13.23
13.54
14.47
14.82
15.05
15.41
18.14
18.58
18.88
19.32
26.24
26.88
27.30
27.94
Page 14
14
Cooling capacity correction factors
Model
7.5m
Refrigerant piping length (one way)
PE-8
PE-10
PE-12
PE-16
PE-20
1.000
1.000
1.000
1.000
1.000
10m
0.993
0.995
0.993
0.993
0.995
15m
0.978
0.985
0.978
0.978
0.985
20m
0.964
0.974
0.964
0.964
0.974
25m
0.949
0.964
0.949
0.949
0.964
30m
0.935
0.953
0.935
0.935
0.953
35m
0.920
0.943
0.920
0.920
0.943
40m
0.906
0.932
0.906
0.906
0.932
45m
0.891
0.922
0.891
0.891
0.922
50m
0.877
0.911
0.877
0.877
0.911
Page 15
15
5-2. STANDARD OPERATION DATA
V
A
V
A
Capacity
(GROSS)
Capacity (NET)
Input
Indoor unit
Phase, Hz
Volts
Amperes
Outdoor unit
Phase, Hz
Volts
Amperes
Discharge temp.
Suction temp.
Ref. pipelength
SHF
BF
Model name PE-8GAK(T) PE-10GAK(T) PE-12GAK(T)
Mode
kW
kW
kW
MPa
kgf/
F
MPa
kgf/
F
:
:
m
:
:
:
:
Cooling
23.4
22.4
7.43
PE-8GAK(T)
3, 50
380/400/415
1.8
PU-8YAKD
3, 50
380/400/415
12.4
1.84
18.8
0.45
4.6
79
5
7.5
27
19
35
24
0.74
0.18
Cooling
29.3
28.4
10.10
PE-10GAK(T)
3, 50
380/400/415
1.9
PU-10YAKD
3, 50
380/400/415
16.0
2.03
20.7
0.43
4.4
89
3
7.5
27
19
35
24
0.75
0.15
Cooling
33.5
32.3
11.49
PE-12GAK(T)
3, 50
380/400/415
2.2
PU-12YAKD
3, 50
380/400/415
17.9
2.04
20.8
0.41
4.2
97
12
7.5
27
19
35
24
0.74
0.16
TotalElectrical circuitRefrigerant circuit
Indoor intake air temp.
Outdoor intake air temp.
D.B.
W.B.
D.B.
W.B.
Discharge Pressure.
Suction pressure.
Page 16
16
V A
V A
Capacity
(GROSS) Capacity (NET) Input
Indoor unit
Phase, Hz Volts Amperes
Outdoor unit
Phase, Hz Volts Amperes
Discharge temp. Suction temp. Ref. pipe length
SHF BF
Model name
Mode
kW kW kW
MPa
kgf/F
MPa
kgf/F
:
:
m
:
:
:
:
Cooling
46.8
45.3
14.41
PE-16GAK(T)
3, 50
380/400/415
3.8
PU-8YAKD
27 19
0.69
0.24
3, 50
380/400/415
12.4
1.84
18.8
0.45
4.6 79
5
7.5
35
24
3, 50
380/400/415
12.4
1.84
18.8
0.45
4.6 79
5
7.5
35
24
Cooling
58.6
55.8
20.84
PE-20GAK(T)
3, 50
380/400/415
5.4
PU-10YAKD
27 19
0.69
0.30
3, 50
380/400/415
16.0
2.03
20.7
0.43
4.4 89
3
7.5
35
24
3, 50
380/400/415
16.0
2.03
20.7
0.43
4.4 89
3
7.5
35
24
TotalElectrical circuitRefrigerant circuit
Indoor intake air temp.
Outdoor intake air temp.
D.B. W.B. D.B. W.B.
Discharge Pressure.
Suction pressure.
PE-16GAK(T) PE-20GAK(T)
Page 17
17
Model name
PE-8GAK(T)
(With a high static pressure motor)
PE-10GAK(T)
(With a high static pressure motor)
Mode
Capacity
Capacity (NET)
TotalElectrical circuitRefrigerant circuit
Input
Indoor unit
Phase, Hz
Volts
Amperes
Outdoor unit
Phase, Hz
Volts
Amperes
Discharge Pressure.
Suction pressure.
(GROSS)
kW
kW
kW
V
A
V
A
MPa
kgf/
MPa
kgf/
F
F
Cooling
23.4
22.4
7.43
PE-8GAK(T)
(With a high static pressure motor)
3, 50
380/400/415
1.8
PU-8YAKD
3, 50
380/400/415
12.4
1.84
18.8
0.45
4.6
Cooling
29.3
28.2
10.10
PE-10GAK(T)
(With a high static pressure motor)
3, 50
380/400/415
2.1
PU-10YAKD
3, 50
380/400/415
16.0
2.03
20.7
0.43
4.4
Discharge temp.
Suction temp.
Ref. pipelength
Indoor intake air temp.
Outdoor intake air temp.
SHF
BF
D.B.
W.B.
D.B.
W.B.
:
:
m
:
:
:
:
79
5
7.5
27
19
35
24
0.74
0.18
89
3
7.5
27
19
35
24
0.75
0.15
Page 18
18
5-3. FAN PERFORMANCE AND CORRECTED AIRFLOW
PE-8GAK(T) Fan Performance
PE-10GAK(T) Fan Performance
PE-12GAK(T) Fan Performance
PE-16GAK(T) Fan Performance
(Pa)
0
50
100
150
200
300
250
65 70 75 80 85 90 95 100
0.9
1.0
1.1
Hi
Lo
0
50
100
150
200
250
65.0 70.0 75.0 80.0 85.0 90.0 95.0 100.0
(CMM)
80.0 100.0 110.0 120.0 130.090.0
50.0 60.0 70.0
(Pa)
External static pressure
Airflow
Airflow
0
50
100
150
200
250
Hi
Lo
(CMM)
(CMM)
60.0 70.0 80.0 90.0
(Pa)
External static pressure
Airflow
(CMM)
(CMM)
(CMM)
(CMM)
0
50
100
150
200
250
Hi
Lo
External static pressure
External static pressure
Airflow
(CMM)
Corrected Airflow
Input
Capacity
Input
Capacity
0.9
1.0
1.1
45 50 55 60 65 70
Airflow
Capacity / input factor
Corrected Airflow
0.9
1.0
1.1
60 65 70 75 80 85 90
Airflow
Capacity / input factor
Corrected Airflow
Airflow
Correction coefficient
Corrected Airflow
Airflow
Capacity / input factor
0.9
1.0
1.1
80 85 90 95 100 105 110 115 120 125 130 135 140
Input
Capacity
Input
Capacity
Page 19
19
PE-20GAK(T) Fan Performance
(Pa)
350
300
250
200
150
100
External static pressure
50
0
120.0 130.0 140.0 150.0 160.0 170.0
Airflow
Corrected Airflow
1.1
1.0
Capacity
Input
Capacity / input factor
0.9 120 130 140 150 160 170 180
Airflow
PE-8GAK(T) (With a high static pressure motor) Fan Performance
300
250
200
150
100
External static pressure
50
Hi
Lo
(CMM)
(CMM)
PE-10GAK(T) (With a high static pressure motor) Fan Performance
250
200
150
100
External static pressure
50
Lo
Hi
0
45.0 50.0 55.0 60.0 65.0 70.0
Corrected Airflow
1.1
1.0
Capacity
Input
Capacity / input factor
0.9 45 50 55 60 65 70
Airflow
(CMM)
(CMM)
0
60.0 65.0 70.0 75.0 80.0 85.0 90.0
AirflowAirflow
Corrected Airflow
1.1
1.0
Capacity
Input
Capacity / input factor
0.9 60 65 70 75 80 85 90
Airflow
(CMM)
(CMM)
Page 20
20
5-4. SOUND DATA
Indoor units
Indoor unit
Position measurement
Measurement point
Inlet
Outlet
1.5m
2m
1m
PE-8,10,12: Upper High/Lower Low
SPL
dB(A) 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz
49 52 51 50 45 45 42 34 26 45 46 45 45 41 41 36 28 19 50 51 50 51 46 45 41 34 26 46 47 46 46 43 42 37 28 19
52 53 51 52 50 46 44 39 30
53 55 54 51 50 48 44 40 31
52 56 55 52 50 48 44 34 28 49 51 51 48 47 45 41 30 22
1) Sound Levels
51 55 54 51 49 47 43 33 27 48 50 50 47 46 44 40 29 21
51 55 54 51 49 47 43 33 27 48 50 50 47 46 44 40 29 21
PE-8
PE-8
PE-10
PE-10
PE-16
PE-20
PE-12
(With a high static pressure motor)
(With a high static pressure motor)
Model
OCTAVE BAND FREQ.Hz
Page 21
21
OUTLINES AND DIMENSIONS
6
6-1. INDOOR UNIT
PE-8GAK(T)
Unit : mm
25 100 100 25
376
10
54
10
73262
634
35
130
130
35
89
145
330 22
39 565
1400
1340
40126040
1051000155
400
1284
144
462
20
40
100
199
20
1300
8x130(=1040)
10
200
1102
3131
45
45
130
130
10
7x130(=910)
11 250 95
50
530
131
34124
42
70 1295575
Front view
Supply air
Left side view
Return air
Accessory
Pipe cover
(For dew condensation prevention of
local piping and unit connection.)
Remote controller
Refrigerant pipe
25.4 (1 braze)
Refrigerant pipe
15.88 (5/8 braze)
3 Holes24-
3.1 Holes22-
For hanging bolt M10
[Field supply]
Supply air
duct flange
Return air
duct flange
Control box
Top view
Drain R1
12 Holes4-
A
Rubber bush
Power supply
wiring
Rubber bush
Outdoor unit
connection wiring
Rubber bush
controller wiring
A
Return air
sensor
2pcs.
1pc.
Remote
Page 22
22
Refrigerant pipe
28.6 (1-1/8 braze)
Refrigerant pipe
15.88 (5/8 braze)
Accessory
Pipe cover
(For dew condensation prevention of
local piping and unit connection.)
Remote controller
Return air
sensor
Front view
Return air
Supply air
Left side view
26-
Supply air
duct flange
Return air
duct flange
For hanging bolt M10
[Field supply]
22-
Control box
Top view
Drain R1
12 Holes4-
A
A
Rubber bush
Power supply
wiring
Rubber bush
Outdoor unit
connection wiring
Rubber bush
controller wiring
2pcs.
1pc.
Remote
3 Holes
3.1 Holes
35
130
22330
144
145
89
130 35
634
54
56539
400
262 73
1600
1000
376
205255
40 1460 40
1540
1010
2510010025
10
9X130(=1170)66
462
1500
40
199
20
100
20
200
45
45
130
7x130(=910)
1484
1302
66
10
11 250 95
130
34
53050
131
124
42
129705575
PE-10,12GAK(T)
Unit : mm
Page 23
23
PE-16,20GAK(T)
39
700
59 425
20
141 320 203
10
42.5 8X130(=1040)
130
42.5
100
45
1618149
29 12X130(=1560) 29
33
10
4013013040
570
1947
22 188340
395 1125 280
764
50
1824
595
22.5 4X120(=480)
120
22.5
102 117 156 117 81
22525
66450
1880
180040 40
60
61
60 60
40
10
184020
10
Accessory
Pipe cover 4pcs.
(For dew condensation prevention of
local piping and unit connection.)
Remote controller 1pc.
A
Rubber bush
<Outdoor unit
connection wiring>
Rubber bush
<Power supply
wiring>
Rubber bush
<Remote controller
wiring>
A
Supply air
duct flange
Control box
Return air
duct flange
[Field supply]
4 15 HOLES
Supply air
Return air
Top view
Front view
Left side view
36- 3 HOLES
24 - 3.1 HOLES
Drain R1
Return air
sensor
(2 places)
Refrigerant pipe
PE-16GAK(T)
: 25.4 (1 braze)
PE-20GAK(T)
: 28.6 (1-1/8 braze)
[2 places (*1 part)]
Refrigerant pipe
15.88 (5/8 braze)
[2 places (*2 part)]
*1
*2
*1
*2
For hanging bolt M12
Unit : mm
Page 24
24
6-2. REMOTE CONTROLLER
130
120
19
Unit : mm
Page 25
25
WIRING DIAGRAM
7
PE-8,10,12GAK(T)
ZNR5~7
CR2CR1
Caution,
1.To protect fan motor from abnormal current,over current
relays is installed.
Therefore, do not change factory set value of over current
relays.
51F
SNB BOARD 1
POWER BOARD
INDOOR
CONTROLLER BOARD
INDOOR
REMOTE
CONTROLLER
BOARD
CONNECTOR (DRAIN SENSOR)CN31
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
CONNECTOR (WIRELESS REMOTE CONTROLLER)
CN2L
CN32
CN41
CN51
CN90
FERRITE CORE
SURGE KILLER
FB
CR1,2
OVER CURRENT RELAY (INDOOR FAN MOTOR)51F
INDOOR
CONTROLLER
BOARD
NAME
X1 AUXILIARY RELAY
MAGNETIC CONTACTOR (INDOOR FAN MOTOR<LOW SPEED>)52FLo
MF1
49F
TB2,4,5
TH1
TH2
FAN MOTOR (INDOOR)
INTERNAL THERMOSTAT (INDOOR FAN MOTOR)
TERMINAL BLOCK
THERMISTOR
REMOTE CONTROLLER
FUSE FUSE (T6.3AL250V)
ZNR VARISTOR
AUXILIARY RELAYX4-6
SW5
SW6
SWITCH (MODEL SELECTION)SW1
SWITCH (SYSTEM SELECTION)
SWITCH (EMERGENCY OPERATION)
MAGNETIC CONTACTOR (INDOOR FAN MOTOR<HIGH SPEED>)52FHi
SYMBOL
ROOM TEMP
LIQUID PIPE TEMP
TB6 TERMINAL BLOCK
SYMBOL NAME
INDOOR UNIT
ARRESTERDSA,DSR
VARISTORZNR5~7
SNB
BOARD 1
SWE CONNECTOR (EMERGENCY OPERATION)
LED1
LED2
LED (POWER SUPPLY)
LED (POWER SUPPLY <REMOTE CONTROLLER>)
CN31
OFF
ON
SW6
12
SW5
8764123
OFF
ON
512345
SW1
OFF
ON
SWE
OFF
ON
FB
51F
(3P)
(Hi)
C02
(6P)
(Lo)
MF1
321
52F
C01
123
Lo
Hi
52F
PE
L1L2L3
TB2
RED
WHITE
BLACK
N
DSA
DSR
RED
WHITE BLACK
RED
CIRCUIT BREAKER
(FIELD SUPPLY)
PE-8,10,12GAK(T):15A
POWER SUPPLY
3N~PE
380/400/415V
50Hz
CNSK
CN2S
1
2
1
3
DC
13.1V
ZNR
X6 X5 X4
5
X1
52F 52F
Hi Lo
FUSE
CND
CNDK
FAN
X5X6 X4
1357
13
13
49F
X1
X1
CN41 CN2L
CN51 CN32
TH1
TH2
LCD
REMOTE CONTROLLER
TB6
TB5
TB4
1
2
2
1
132
1
2
CN30
CN22
LED2
LED1
DC13.1V
CN2D
12
212
1
CN21
CN20
BLUE
4
C01
CN90
OUTDOOR UNIT
TAB1
INDOOR UNIT
GREEN/YELLOW
TO OUTDOOR UNIT
CONNECTING WIRES
(POLAR)
Note:1. The dotted lines show field wiring.
2.Color of earth wire is yellow and green twisting.
3.Specification subject to change without notice.
4.Indoor and outdoor connecting wires are made with
polarities,make sure matching wiring and terminal.
5.Emergency operation
If a trouble occurs with either the remote controller or
the indoor microcomputer and no other trouble exists,
emergency operation for cooling or heating can be
performed by changing the setting of connector (SWE)
and switch (SW6) on the indoor controller board.
SWE :ON / Indoor fan is running high speed.
SW6-1:ON / Emargency operation of cooling mode.
6. mark is connector. mark is terminal.
Page 26
26
PE-16,20GAK(T)
ZNR5~7
CR
Caution,
1. To protect fan motor from abnormal current,over current relays is installed.
Therefore, do not change factory set value of over current relays.
51F
REMOTE
CONTROLLER
BOARD
INDOOR
CONTROLLER BOARD
INDOOR POWER BOARD(No.1)
SNB BOARD 1
INDOOR
CONTROLLER BOARD
INDOOR POWER BOARD(No.2)
(No.1)
(No.2)
Note:1. The dotted lines show field wiring.
2. Color of earth wire is yellow and green twisting.
3. Specification subject to change without notice.
4. Indoor and outdoor connecting wires are made with polarities,
make surematching wiring and terminal.
5. Emergency operation
If a trouble occurs with either the remote controller or the indoor
microcomputer and no other trouble exists, emergency operation
for cooling or heating can be performed by changing the setting
of connector (SWE) and switch (SW6) on the indoor controller board.
SWE :ON / Indoor fan is running high speed.
SW6-1:ON / Emargency operation of cooling mode.
6. mark is connector. mark is terminal.
CONNECTOR (DRAIN SENSOR)CN31
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
CONNECTOR (WIRELESS REMOTE CONTROLLER)
CN2L
CN32
CN41
CN51
CN90
SURGE KILLERCR
FERRITE COREFB11,FB12
FB21,FB22
OVER CURRENT RELAY (INDOOR FAN MOTOR)51F
LED (POWER SUPPLY <REMOTE CONTROLLER>)
LED (POWER SUPPLY)
LED2
LED1
CONNECTOR (EMERGENCY OPERATION)SWE
SNB
BOARD 1
ZNR5~7 VARISTOR
DSA,DSR
ARRESTER
INDOOR UNIT
NAMESYMBOL
LIQUID PIPE TEMP
ROOM TEMP
SWITCH (EMERGENCY OPERATION)
SWITCH (SYSTEM SELECTION)
SW1 SWITCH (MODEL SELECTION)
SW6
SW5
X4-6 AUXILIARY RELAY
VARISTORZNR
FUSE (T6.3AL250V)FUSE
THERMISTOR
TERMINAL BLOCK
INTERNAL THERMOSTAT (INDOOR FAN MOTOR)
FAN MOTOR (INDOOR)
TH2-1,2-2
TH1-1,1-2
TB2,4-1,4-2,5
49F
MF1
52F MAGNETIC CONTACTOR (INDOOR FAN MOTOR)
BOARD
CONTROLLER
INDOOR
X1,2 AUXILIARY RELAY
NAME
REMOTE CONTROLLER
SYMBOL
TB6 TERMINAL BLOCK
CN31
CN31
OFF
ON
SW6
12
12345
SW1
OFF
ON
SWE
OFF
ON
SW5
8764123
OFF
ON
5
OFF
ON
SW6
12
12345
SW1
OFF
ON
SWE
OFF
ON
SW5
8764123
OFF
ON
5
FB22
FB12
FB21
FB11
51F
TAB1
OUTDOOR UNIT
(No.1)
CN90
BLUE
CN20
CN21
121
2
21
CN2D
DC13.1V
LED1
LED2
CN22
CN30
2
1
231
1
2
2
1
TB4-1
TB5
TB6
REMOTE CONTROLLER
LCD
TH2-1
TH1-1
CN32CN51
CN2LCN41
31
31
7531
X4X6 X5
FAN
CNDK
CND
FUSE
X1
X4X5X6
ZNR
DC
13.1V
3
1
2
1
CN2S
CNSK
POWER SUPPLY
3N~PE
380/400/415V
50Hz
CIRCUIT BREAKER
(FIELD SUPPLY)
PE-16,20GAK(T):15A
BLACK
WHITE
RED
DSR
DSA
N
BLACK
WHITE
RED
TB2
L3
L2
L1
PE
52F
C01 C02
123
MF1
123
X2
7531
X4X6 X5
FAN
X4X5X6
CN90
CN20
CN21
121
2
21
CN2D
DC13.1V
LED1
LED2
CN22
CN30
2
1
231
1
2
TH2-2
TH1-2
CN32CN51
CN2LCN41
31
31
CNDK
CND
FUSE
ZNR
CN2S
CNSK
TAB1
DC
13.1V
3
1
2
1
OUTDOOR UNIT
(No.2)
52F
C01
5
4
X01
X02
TB4-2
49F
GREEN/YELLOW
INDOOR UNIT
TO OUTDOOR UNIT
CONNECTING WIRES
(POLAR)
TO OUTDOOR UNIT
CONNECTING WIRES
(POLAR)
Page 27
27
REFRIGERANT SYSTEM DIAGRAM
8
Unit : mm
PE-8GAK(T)/PU-8YAKD PE-10GAK(T)/PU-10YAKD
Indoor heat
exchanger
Outdoor heat
exchanger Indoor coil thermistor TH2
Brazing
Flared connection
Flared connection
Refrigerant pipe ø15.88 (With heat insulator)
Flow of refrigerant
Flow of refrigerant
Compressor
Accumulator
Ball Valve
Low pressure switch
High pressure switch
Ball Valve
Capillary tube 8HP : O.D. 6.0 X I.D. 4.0X L1000
10HP : O.D. 6.0 X I.D. 7.0 X L700
Strainer
Refrigerant pipe 8HP: ø25.4 10HP:ø28.6 (With heat insulator)
Serviceport
(With service port and strainer)
Serviceport
( )
Indoor heat
exchanger
Outdoor heat
exchanger
Indoor coil thermistor TH2
Brazing
Refrigerant pipe ø15.88 (With heat insulator)
Compressor
Accumulator
Ball Valve
Low pressure switch
High pressure switch
Ball Valve
Capillary tube
Capillary tube
(O.D. 6.0 X I.D. 7.0 X L700)
(O.D. 6.0 X I.D. 4.0 X L800)
Capillary tube (O.D. 6.0 X I.D. 4.0 X L700)
Strainer
Refrigerant pipe ø28.6 (With heat insulator)
Serviceport Serviceport
(With service port and strainer)
Unit : mm
PE-12GAK(T)/PU-12YAKD
Page 28
28
9
TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit. Actions to be taken for service,which depends on whether or not the the inferior phenomenon is reoccurring at service, are summarized in the table below. Check the contents below before investigating details.
9-1. TROUBLESHOOTING
Unit conditions at service
Error code
Actions to be taken for service (summary)
The inferior phenomenon is reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according to SELF-DIAGNOSIS ACTION TABLE (7-3).
Identify the cause of the inferior phenomenon and take a corrective action according to TROUBLESHOOTING BY INFERIOR PHENOMENA (7-4).
The inferior phenomenon is not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise and etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the inferior phenomenon occurred, and wiring related. 2Reset error code logs and restart the unit after finishing service. 3There is no abnormality in electrical components, controller boards, and remote controller.
1Recheck the abnormal symptom. 2Identify the cause of the inferior phenomenon and take
a corrective action according to TROUBLESHOOTING BY INFERIOR PHENOMENA (7-4). 3Continue to operate unit for the time being if the cause is not ascertained. 4There is no abnormality in electrical components, controller boards, remote controller etc.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
1 Turn on the power. 2 Press the [CHECK] button twice. 3 Set address with [TEMP] button if system control is used. 4 Press the [ON/OFF] button to stop the self-check.
A CHECK button B Address C TEMP. button D IC : Indoor unit
OC: Outdoor unit E Check code
F Unit No. G Timer ON/OFF button
A
F
C
BBEED
G
<To delete check code>
1 Display the error code at the self-check result display screen. 2 The address for self-check will blink when the
G ON/OFF
button is pressed twice within three seconds.
– – – – : No trouble generated in the past. F F F F : No corresponding unit.
9-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop.
Wired remote controller
Page 29
29
Errors detected by indoor unit
Wired remote controller
1 Check code
Symptom Remark
P1
Intake sensor error
P2 Pipe (TH2) sensor error P4 Drain sensor error P5 PA
Drain pump error
Forced compressor stop P6 Freezing/ Overheating safeguard operation P8 Pipe temperature error / Outdoor unit error E4, E5 Remote controller signal receiving error
– –
– –
Fb Indoor unit control system error (memory error, etc.) E0, E3
Remote controller transmission error E1, E2 Remote controller control board error
On wired remote controller
1Check code displayed in the LCD.
If the unit cannot be operated properly after test run has been performed, refer to the following table to remove the cause.
Wired remote controller
PLEASE WAIT
Symptom
For about 2 minutes follow­ing power-on
For about 2 minutes following power-on,op­eration of the remote controller is not possible due to system start-up. (Correct operation)
Cause
Connector for the outdoor units protection
PLEASE WAIT → Error code
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).
After about 2 minutes has expired follow­ing power-on
device is not connected.
Reverse or open phase wiring for the outdoor units power terminal block
Incorrect wiring between indoor and outdoor units
Remote controller wire short
Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for wired remote controller)
Indicates whether power is supplied to the wired remote controller. This LED lights only in the case of the main indoor unit.
Page 30
30
9-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
Meaning of error code and detection method
Cause
Countermeasure
P1
Abnormality of room temperature thermistor (TH1)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating operation. Short: 90
: or more
Open: -40
: or less
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN20) on the indoor controller board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective indoor controller
board.
13 Check resistance value of thermistor.
0
: ····15.0k" 10: ······9.6k" 20: ······6.3k" 30: ······4.3k" 40: ······3.0k" If you put force on (draw or bend) the lead wire with measuring resistance value of thermistor breaking of wire or contact failure can be detected. 2 Check contact failure of connector (CN20)
on the indoor controller board. Refer to 9-7. Turn the power on again and check restart after inserting connector again.
4 Check room temperature display on remote
controller. Replace indoor controller board if there is abnormal difference with actual room temperature.
Turn the power off, and on again to operate after check.
P2
Abnormality of pipe temperature thermistor/Liquid (TH2)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating (except defrosting) operation. Short: 90
: or more
Open: -40
: or less
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN21) on the indoor controller board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective refrigerant circuit is
causing thermistor temperature of 90
: or more or -40: or
less.
5 Defective indoor controller board.
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above. 2 Check contact failure of connector (CN21)
on the indoor controller board. Refer to 9-7. Turn the power on and check restart after inserting connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid> temperature is exclusively low (in cooling mode) or high (in heating mode), refrigerant circuit may have defective.
5 Check pipe <liquid> temperature with remote
controller in test run mode. If there is exclusive difference with actual pipe <liquid> temperature, replace indoor controller board.
Turn the power off, and on again to operate after check.
P4
Abnormality of drain sensor (DS)
1 Suspensive abnormality, if short/open of
thermistor is detected for 30 seconds continuously. Turn off compressor and indoor fan.
2 Short/open is detected for 30 seconds
continuously during suspensive abnormality. (The unit returns to normal operation,
if it has normally reset.)
3 Detect the following condition.
During cooling and drying operation.
In case that pipe <liquid> temperature
- room temperature <-10deg
(Except defrosting)
When pipe <liquid> temperature or room temperature is short/open temperature.
During drain pump operation.
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN31) on the indoor controller board. (Insert failure).
3 Breaking of wire or contact
failure of drain sensor wiring.
4 Defective indoor controller board.
1–3 Check resistance value of thermistor.
0
: ······6.0k" 10: ····3.9k" 20: ····2.6k" 30: ····1.8k" 40: ····1.3k" 2 Check contact failure of connector (CN31)
on the indoor controller board. Refer to 9-7. Turn the power on again and check restart after inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor connector CN31-
1 and 2 is short-circuited,
and abnormality reappears.
Turn the power off, and on again to operate after check.
P5
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor is let heat itself and temperature rises slightly. Turn off compressor and indoor fan.
2 Drain pump is abnormal if the condition
above is detected during suspensive abnormality.
3 Constantly detected during drain pump
operation.
1 Malfunction of drain pump 2 Defective drain
Clogged drain pump Clogged drain pipe
3 Attached drop of water at the
drain sensor
Drops of drain trickles from lead wire.
Clogged filter is causing wave of drain.
4 Defective indoor controller board.
1 Check if drain-up machine works. 2 Check drain function. 3 Check the setting of lead wire of drain
sensor and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor connector CN31-1 and 2 is short-circuited and abnormality reappears. Refer to 9-7.
Turn the power off, and on again to operate after check.
Page 31
31
Error Code
Meaning of error code and detection method
Cause
Countermeasure
P6
Freezing/overheating protection is working
1 Freezing protection (Cooling mode)
The unit is in six-minute resume prevention mode if pipe temperature stays under
-15: for three minutes, three minutes after the compressor started. Abnormal if it stays under -15: for three minutes again within 16 minutes after six-minute resume prevention mode.
<Frost prevention mode>
If pipe temperature is 1: or below when 16 minutes has passed after com­pressor starts operating, unit will start operating in frost prevention mode which stops compressor operation. After that, when pipe temperature stays 10: or more for 3 minutes, frost prevention mode will be released and compressor will restart its operation.
P8
1 Slight temperature difference
between indoor room temperature and pipe tempera­ture thermistor
Shortage of refrigerant
Disconnected holder of pipe
thermistor
Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units connection)
3 Converse wiring of indoor/
outdoor unit connecting wire (on plural units connection)
4 Defective detection of indoor
room temperature and pipe temperature thermistor
5 Stop valve is not opened
completely.
(Cooling or drying mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Low-load (low temperature)
operation beyond the tolerance range
4 Defective indoor fan motor
Fan motor is defective.
Indoor controller board is
defective.
5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit
(clogs)
(Cooling or drying mode)
1 Check clogs of the filter. 2 Remove shields.
4 Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector (FAN) on the indoor controller board. Relay for the indoor controller board should
be normal when voltage of AC 220~240V
is detected while fan motor is connected. Refer to 9-7.
5 Check outdoor fan motor. 67 Check operating condition of refrigerant
circuit.
Abnormality of pipe temperature
<Cooling mode> Detected as abnormal when the pipe tem­perature is not in the cooling range 3 min­utes later of compressor start and 6 min­utes later of the liquid pipe is out of cooling range. Note 1) It takes at least 9 min. to detect. Note 2) Abnormality P8 is not detected in
drying mode. Cooling range : -5 deg ] (TH2-TH1) TH2: Liquid pipe temperature TH1: Intake temperature
1~4 Check pipe temperature with room
temperature display on remote controller.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor unit connecting wire.
1 Wrong wiring of indoor/outdoor
connecting wire
2 Reversed phase 3 Protection device is working 4 Damaged outdoor coil thermis-
tor
Abnormality in outdoor unit
1 Check the indoor/outdoor connecting wire. 2 Change the connection of electric wiring. 3 Check the protection device. 4 Measure the resistance of the outdoor coil
thermistor. If the resistance is normal, replace the outdoor controller board.
Page 32
32
Error Code
Meaning of error code and detection method
Cause
Countermeasure
E0
or
E4
Remote controller transmission error(E0)/signal receiving error(E4)
1 Abnormal if main or sub remote con-
troller can not receive normally any transmission from indoor unit of refriger­ant address “0” for three minutes. (Error code : E0)
2 Abnormal if sub remote controller could
not receive for any signal for two min­utes. (Error code: E0)
1 Abnormal if indoor controller board can
not receive normally any data from remote controller board or from other indoor controller board for three minutes. (Error code: E4)
2 Indoor controller board cannot receive
any signal from remote controller for two minutes. (Error code: E4)
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main.
If there is no problem with the action above.
3 Check wiring of remote controller.
Total wiring length: max.500m (Do not use cable x 3 or more)
The number of connecting indoor units: max.16units
The number of connecting remote con­troller: max.2units
When it is not the above-mentioned problem of
1~3 4 Diagnose remote controllers.
a) When RC OK is displayed,
Remote controllers have no problem. Put the power off, and on again to check. If abnormality generates again, replace indoor controller board.
b) When RC NG is displayed,
Replace remote controller. c) When RC E3 is displayed, d) When ERC 00-06 is displayed, [ c),d)Noise may be causing abnormality. ]
If the unit is not normal after replacing
indoor controller board in group control, indoor controller board of address “0” may be abnormal.
E3
or
E5
Remote controller transmission error(E3)/signal receiving error(E5)
1 Abnormal if remote controller could not
find blank of transmission path for six seconds and could not transmit. (Error code: E3)
2 Remote controller receives transmitted
data at the same time, compares the data, and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E3)
1 Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2 Indoor controller board receives trans-
mitted data at the same time, compares the data,and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E5)
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting. 4~6 Diagnose remote controller.
a) When RC OKis displayed, remote con-
trollers have no problem.
Put the power off,and on again to check. When becoming abnormal again, replace
indoor controller board. b)When RC NGis displayed, replace
remote controller. c)When RC E3or ERC 00-66is displayed,
noise may be causing abnormality.
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as sub remote controller. In this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED1, LED2) on the outdoor controller circuit board.
3 Mis-wiring of remote controller. 4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board of refrigerant address “0”.
6 Noise has entered into the
transmission wire of remote controller.
1 Two remote controller are set
as main. (In case of 2 remote con-
trollers)
2 Remote controller is connected
with two indoor units or more.
3 Repetition of refrigerant
address.
4 Defective transmitting receiving
circuit of remote controller.
5 Defective transmitting receiving
circuit of indoor controller board.
6 Noise has entered into trans-
mission wire of remote con­troller.
Page 33
33
Error Code
Meaning of error code and detection method
Cause
Countermeasure
Fb
Abnormality of indoor controller board
Abnormal if data cannot be normally read from the nonvolatile memory of the indoor controller board.
1 Defective indoor controller
board.
1 Replace indoor controller board.
E1
or
E2
Abnormality of remote controller con­trol board
1 Abnormal if data cannot be normally
read from the nonvolatile memory of the remote controller control board.
(Error code: E1)
2 Abnormal if the clock function of remote
controller cannot be normally operated.
(Error code: E2)
1 Defective remote controller. 1 Replace remote controller.
PA (2502) (2500)
Forced compressor stop (due to water leakage abnormality)
1 When the intake temperature subtracted
with liquid pipe temperature is less than
-10
:, drain sensor is detected whether it is soaked in the water or not at the interval of 90 seconds. (Drain pump will start operating when the drain sensor is detected to be soaked in the water.)
2 The unit has a water leakage abnormality
when the following conditions, a and b, are satisfied while the above-mentioned detection is performed. a) The drain sensor is detected to be
soaked in the water 10 times in a row.
b) The intake temperature subtracted with
liquid pipe temperature is detected to be
less than -10
: for a total of 30 minutes.
(When the drain sensor is detected to
be NOT soaked in the water, the detection
record of a and b will be cleared.)
3 The drain sensor detection is performed
in operations other than cooling. (When the unit stops operating, during heating or fan operation, when the unit stops because of some abnormality)
*Once the water leakage abnormality is
detected, abnormality state will not be released until the main power is reset.
1 Drain pump trouble 2 Drain defective
· Drain pump clogging
· Drain pipe clogging
3 Open circuit of drain sensor
side heater
4 Contact failure of drain sensor
connector
5 Dew condensation on drain
sensor
· Drain water descends along lead wire.
· Drain water waving due to filter clogging.
6 Extension piping connection
difference at twin, triple, quadruple system.
7 Mis-wiring of indoor/ outdoor
connecting at twin, triple, quadruple system.
8 Room temperature thermistor /
liquid pipe temperature thermis­tor detection is defective.
1Check the drain pump.
Performance 2Please confirm whether water can be drained.
3Confirm the resistance of the drain sensor
side heater.
4Check the connector contact failure.
5 Check the drain sensor leadwire mounted.
Check the filter clogging
6Check the piping connection.
7Check the indoor/ outdoor connecting wires.
8Check the room temperature display of
remote controller.
Check the indoor liquid pipe temperature
display of outdoor controller board.
Page 34
34
When LED1 on indoor controller board is also off.
1 Power supply of 220~240V AC is not supplied to
indoor unit.
2 Defective indoor controller board.
3 Defective indoor power board.
9-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
Phenomena
Cause
Countermeasure
(1)LED2 on indoor controller board
is off.
When LED1 on indoor controller board is lit.
1 Mis-setting of main/sub for indoor unit
(There is no unit corresponding to main unit.)
1 Reconfirm the setting of main/sub for
indoor unit
Set the main unit. Set main/sub using SW5-3 on indoor controller board.
1 Check the voltage of indoor power supply
terminal block.
2 Check voltage output from CNDK on
indoor controller board.
When AC220~240V is not detected. Check the fuse on indoor controller board. Check the wiring connection between indoor power supply terminal block and CND on indoor controller board.
When AC220~240V is detected.
-Check 3 (below).
3 Check voltage output from CN2S on
indoor power board.
When no voltage output. Check the wiring connection between CNDK on indoor controller board and CNSK on indoor power board. If no problem are found,indoor power board is defective.
When DC12.5~13.7V is detected. Check the wiring connection between CN2S on indoor power board and CN2D on indoor power board. If no problem are found,indoor con­troller board is defective.
(2)LED2 on indoor controller board
is blinking.
When LED1 on indoor controller board is also blinking. Connection failure of indoor/outdoor unit connecting wire
When LED1 is lit.
1 Mis-wiring of remote controller wires
When 2 indoor units are wired in one refrigerant system, each indoor unit sets main unit. (SW5-3)
2 Short-cut of indoor/outdoor unit connecting wire.
3 Short-cut of remote controller wires 4 Defective remote controller
Check indoor/outdoor unit connecting wire for connection failure.
1 Check the connection of remote con-
troller wires in case of twin triple indoor unit system. When 2 or more indoor units are wired in one refrigerant system, connect remote controller wires to one of those units.
2 Remove indoor/outdoor connecting wires
and check LED2 on indoor controller board.
When LED2 is blinking, check the short­cut of indoor/outdoor connecting wires.
When LED2 is lit, connect indoor/outdoor connecting wires again, and; if LED2 is blinking, outdoor units controller board is defective; if LED2 is lit, connection failure of indoor/outdoor terminal block etc. has returned to normal.
34 Remove remote controller wires and
check LED2 on indoor controller board.
When LED2 is blinking, check the
short-cut of remote controller wires.
When LED2 is lit, connect remote
controller wires again and: if LED2 is blinking, remote controller is defective; if LED2 is lit, connection failure of remote controller terminal block etc. has returned to normal.
Page 35
35
(3)Upward/downward vane
performance failure
1 The vane is not downward during defrosting and
heat preparation and when the thermostat is OFF in HEAT mode. (Working of COOL protection function)
2 Vane motor does not rotate.
Defective vane motor
Breaking of wire or connection failure of connector
Up/down vane setting is No vanes”.
3 Upward/downward vane does not work.
The vane is set to fixed position.
1 Normal operation (The vane is set to hor-
izontal regardless of remote control.)
2 Check 2 (left).
Check the vane motor. (Refer to How to check the parts.)
Check for breaking of wire or connec­tion failure of connector.
Check Up/down vane setting. (Unit function selection by remote controller).
3 Normal operation (Each connector on
vane motor side is disconnected.)
Phenomena
Cause
Countermeasure
9-6. TEST RUN AND EMERGENCY OPERATION
9-6-1. Before test run
9-5. Error countermeasures for PE-16,20GAK(T)
Daisy-chains between indoor and outdoor units in No.1 system.
A
Outdoor unit No.1
C2
C1
Remote controller
No.1
Indoor unit
Outdoor unit No.2
BA
No.2
:
Daisy-chains between indoor and outdoor units in No.2 system.
B
:
C
Remote controller cable
:
Wiring Errors
Refrigerant system related errors
Cable A breakage, reversed connection
Cable B breakage, reversed connection
Cable C breakage
No.1 system error
No.2 system error
Startup at power on
Symptom Remedy Symptom Remedy Symptom Remedy
Normal completion of startup N/A
Normal completion of startup N/A
Power is not supplied to the remote controller, and the controller is inoperable. Error status can be checked with the LED2 on the indoor unit.
Normal completion of startup N/A Normal stoppage N/A
Normal completion of startup N/A Normal stoppage N/A
Repair cable C.
During stoppage (with the power being supplied)
Normal stoppage P8 error during operation Repair
Normal stoppage N/A
Power is not supplied to the remote controller, and the controller is inoperable. Error status can be checked with the LED2 on the indoor unit.
N/A
Repair cable C.
P8 error during operation Repair
Power is not supplied to the remote controller, and the controller is inoperable. Error status can be checked with the LED2 on the indoor unit.
Outdoor unit No. 1 does not operate when all of the units in the system are turned on, and abnormal pipe temperature error P8 appears.
Outdoor unit No. 2 does not operate when all of the units in the system are turned on, and abnormal pipe temperature error P8 appears.
During operation
cable A.
cable B.
Repair cable C.
Correct the error.
Correct the error.
After completing installation and the wiring and piping of the indoor and outdoor units, check for refrigerant leakage, looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply.
To avoid damage to the compressor, make certain that all three phases of the power supply voltage are in the proper phase sequence.
If connected in the reverse phase sequence, the indoor unit will not be able t o provide sufficient cooling air. The fan on the outdoor unit that is connected in the reverse phase sequence will tarn in the wrong direction
and makes the compressor rattle.
If the outdoor unit is connected to the power supply voltage in the wrong phase sequence, P8 error occurs, or the built-in thermostat triggers the compressor to stop and results in P8 error. Once the built-in thermostat is triggered, it will take a long time until it returns to its pre-set temperature. Until then, the compressor cannot be started, even after the phase sequence is corrected.
Use a 500-volt megohmmeter to check that the resistance between the power supply terminals and ground is
at least 1.0M".
Do not carry out this test on the control wiring (low voltage circuit) terminals.
Warning: Do not use the air conditioner if the insulation resistance is less than 1.0M".
Page 36
36
9-6-2. Test run (Using wired remote controller)
B
EF
C
H
G
IM
A
D
ûC
ûC
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
TEST RUN COOL, HEAT
A ON/OFF button B Test run display C Indoor temperature liquid line
temperature display
D ON/OFF lamp E Power display
F Error code display
Test run remaining time display
G Set temperature button H Mode selection button I Fan speed button M TEST button
1 Turn on the power at least 12 hours before the test run. 2 Press the [TEST] button twice. "TEST RUN" liquid crystal display 3 Press the [Mode selection] button. Make sure that wind is blown out. 4 Press the [Mode selection] button and switch to the cooling mode.
Make sure that cold wind is blown out.
5 Press the [Fan speed] button. Make sure that the wind speed is switched. 6 Check operation of the outdoor unit fan. 7 Release test run by pressing the [ON/OFF] button. Stop 8 Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error occurs can be registered in the remote controller. The telephone number will be displayed when an error occurs. For registration procedures, refer to the operation manual for the indoor unit.
1.When the wired remote control or the indoor unit microcomputer has failed,but all other components work if you set the switch(SWE,SW6) on the indoor control board,the indoor unit will begin properly Emergency Operation.
2.When you activate emergency operation of the cooling, you have to set the connector(SWE) and switch(SW6)on the indoor controller.
SWE:ON Indoor fan is running high speed. SW6-1:ON Emergency operation of cooling mode.
3.Before you activate emergency operation,check the following points: (1)Emergency operation cannot be activated when:
the outdoor unit malfunctions.
the indoor fan malfunctions.
(2)Emergency operation becomes continuous only by switching the power source on/off. ON/OFF on the remote
control or temperature control etc. does not function.
(3)Emergency cooling should be limited to 10 hours maximum
(The indoor unit heat exchanger may freeze).
(4)After emergency operation has been deactivated,set the switches etc. to their original positions.
9-6-3. When wired remote controller or indoor unit micro computer troubles
Page 37
37
9-7. HOW TO CHECK THE PARTS
PE-8GAK(T) PE-10GAK(T) PE-12GAK(T) PE-16GAK(T) PE-20GAK(T)
Room temperature thermistor
(TH1)
Indoor coil thermistor
(TH2)
Fan motor
Disconnect the connector, then measure the resistance using a tester. (Surrounding temperature 10°C~30°C)
(Refer to the thermistor)
Normal
4.3k'~9.6k'
Abnormal
Open or short
Parts name Check points
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
< Thermistor for lower temperature >
Temperature (:)
Resistance (K")
<Thermistor Characteristic graph>
Room temperature thermistor(TH1) Indoor coil thermistor(TH2)
Thermistor R
0=15k' ±3%
Fixed number of B=3480 ± 2% Rt=15exp { 3480( ) }
0
: 15k' 10: 9.6k' 20: 6.3k' 25: 5.2k' 30: 4.3k' 40: 3.0k'
Thermistor for lower temperature
1
273+t
1
273
Normal
26.0W
37.8W
PE-8,10
Red-White / White-Blue / Red-Blue Red-White / White-Blue / Red-Blue Red-White / White-Blue / Red-Blue
Red-White / White-Blue / Red-Blue Red-White / White-Blue / Red-Blue
Red-White / White-Blue / Red-Blue
Abnormal
Open
or
short
Hi Lo
19.9W
25.1W
PE-8,10
(High static pressure motor)
Hi Lo
34.2W
PE-16
25.2W
PE-20
Measure the resistance value across the terminals with a multimeter.
Thermal protector trip temperature 135 ±5˚C : open 86 ±15˚C : close
PE-8,10
Thermal protector trip temperature 150 ±5˚C : open 96 ±15˚C : close
PE-16,20
THERMO
W
ZY
ab
U
X
V
THERMO
Thermal protector
17AM034E5-4
(LO)
(HI)
(HI)
(LO)
P
U2
U1
V1
V1
W1
W2
(LO)
(HI)
Operating temperature135˚C
Black marking
Black marking
Black marking
(Winding temperature 20 ˚C)
Red
White
Blue
YELLOW
YELLOW
Blue
White
Red
Page 38
38
9-8. TEST POINT DIAGRAM
9-8-1. Power board PE-8GAK(T) PE-10GAK(T) PE-12GAK(T) PE-16GAK(T) PE-20GAK(T)
CNSK Connect to the indoor controller board (CNDK) Between
1 to 3 220-240V AC
CN2S Connect to the indoor controller board (CN2D) Between
1 to 3 12.6-13.7V DC (Pin1 (+))
Page 39
39
9-8-2. Indoor controller board PE-8GAK(T) PE-10GAK(T) PE-12GAK(T) PE-16GAK(T) PE-20GAK(T)
FAN Fan motor output
CNP Drain-pump output (DP) (220~240V AC)
CNC Dew prevention heater (H2) (220~240V AC)
CNDK Connect to the indoor power board (CNSK) (220~240V AC)
FUSE (6.3A 250V)
CND Power supply input (220~240V AC)
SWE Emergency operation
SW1 Model setting
CN2L Connector (LOSSNAY)
CN51 Centrally control
CN6V Vane motor output (MV)
CN90 Connect to the wire­less remote con­troller board (CNB)
CN31 Drain sensor (DS)
CN21 Pipe temperature thermistor/Liquid (TH2)
CN20 Room temperature thermistor (TH1)
CN22 Remote controller connecting wire (10.4~14.6V DC)
LED2 Power supply (R.B)
LED1 Power supply (I.B)
CN2D Connector to the indoor power board (CN2S) (12.5~13.7V DC)
}
}
+
+
SW5 System Setting
CN32 Remote Switch
CN41 Connector (HA terminal-A)
CN105/ CN92 (RED)
SW6 Emergency operation
CN30 Transmission (indoor/outdoor)
Page 40
40
SW1
Setting by the dip switch and jumper wireFunctions
PE-16,20GAK(T)
No.2No.1
PE-8,10,12GAK(T)
PE-16,20GAK(T)
No.2No.1
PE-8,10,12GAK(T)
Jumper
wire
Model settings
SW5
System settings
Remarks
(Marks in the table below) Jumper wire ( : Short : Open)
SW5-3 Main/Sub setting OFF : Main ON : Sub SW5-4 Rotaion operation setting OFF : Not avairable ON : avairable
SW5-7 COMP ON signal output switch OFF : COMP ON signal output is turned off. ON : COMP ON signal output is turned on.
8761
SW5
OFF
ON
5432
8761
SW5
OFF
ON
54328761
SW5
OFF
ON
5432
1
SW1
OFF
ON
5432
1
SW1
OFF
ON
54321
SW1
OFF
ON
5432
9-9. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control p.c. board.
Page 41
41
FUNCTION SETTING10
Function Settings
No.
Mode
No.
Setting
Initial setting (Factory setting
)
- : Not available PE-GAK(T)
Filter sign 100Hr 1
2500Hr 07 2
No filter sign indicator
3
Air flow Quiet 1 ­(
Fan speed
)
Standard 08 2 ­High ceiling 3 -
No.of air outlets 4 directions 1 -
3 directions 09 2 ­2 directions
3-
Optional high efficiency
Not supported
10
1
-
filter Supported
2
-
Vane setting
No vanes
1-
Vane No.1 setting
11 2 -
Vane No.2 setting
3-
Energy saving air Disabled
12
1
-
flow (Heating mode
)
Enabled
2
-
Vane differential setting No.1 setting (TH2: 24-28:
)
1-
in heating mode No.2 setting (Standard, TH2:28-32:)14 2 ­(
cold wind prevention
)
No.3 setting (TH2: 32-38:
)
3-
Swing
Not available
23
1
-
Available
2
-
Fan speed when the
Set fan speed
27
1
cooling thermostat is OFF Stop
2
Detection of abnormality of Available
28
1
the pipe temperature (P8
)
Not available
2
Function
Settings
Mode No.
Setting No.
Initial setting
(when sent from the factory)
Remarks
Power failure automatic recovery Indoor temperature detecting
LOSSNAY connectivity
Power supply voltage Frost prevention temperature Humidifier control
Rotation
OFF ON Indoor unit's (Main) internal sensor
Remote controller's internal sensor w1 Not supported Supported (indoor unit not equipped with outdoor air intake) Supported (indoor unit equipped with outdoor air intake) 240V 220V,230V 1: (Normal)
-3: When the compressor operates, the humidifier also operates. When the fan operates, the humidifier also operates. 24h cycle 168h cycle Back up function
1 2 1 2 3 1 2 3 1 2 1 2 1 2 1 2 3
01
02
03
04 15 16
20
The setting is applied to all the units in the same refrigerant system.
10-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be done by the remote controller. Select function available from the table 1. (1) Functions available when setting the unit number to 00 (Select 00 referring to
4 setting the indoor unit number.)
1 The functions below are available only when the wired remote controller is used.The functions are not available for floor
standing models.
<Table 1> Function selections
(2) Functions available when setting the unit number to 01-02 or AL (07 in case of wireless remote controller)
When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to
4 setting the
indoor unit number.
When setting functions for a simultaneous Twin-indoor unit system, set the unit number to 01 to 02 for each indoor unit in case of selecting different functions for each unit referring to
4 setting the indoor unit number.
When setting the same functions for an entire simultaneous Twin-indoor unit system, set refrigerant address to AL (07 in case of wireless remote controller) referring to
4 setting the indoor unit number.
Page 42
42
[Operating Procedure]
1 Check the setting items provided by function selection.
If settings for a mode are changed by function selection, the functions of that mode will be changed accordingly. Check all the current settings according to steps 2 to 7 , fill in the "Check" column in Table 1, and then change them as necessary. For factory settings, refer to the indoor unit's installation manual.
2 Switch off the remote controller.
A Hold down the
buttons and then the remote controller's display content will change as shown below.
* If the unit stops after
Check to see if there are any sources of noise or interference near the transmission path. Note
If you have made operational mistakes during this procedure, exit function selection (see step 0), and then restart from step 2 .
4 Set the indoor unit number.
D Press the
area.
FILTER
simultaneously for at least two seconds.
Address display section
FUNCTION
flashed for two seconds or "88" flashes in the room temperature display area for two seconds, a transmission error may have occurred.
SELECTION
ON/OFF
button so that " - -" flashes in the unit number display
Unit number display section
FUNCTION SELECTION
B ( mode 15 or more) and
TEST
will start to flash,
3 Set the outdoor address.
C Press the [
address. The address changes from "00" to "15".
C Press the [
of the indoor unit for which you want to perform function selection. The unit number changes to "00", "01", "02","03",04" and "AL" each time a button is pressed.
CLOCK] buttons ( and ) to select the desired
CLOCK] buttons ( and ) to select the unit number
* To set modes 01 to 06 or 15 to 22 select unit number "00". * To set modes 07 to 14 or 23 to 28 carry out as follows:
To set each indoor unit individually, select "01" to "04".
To set all the indoor units collectively, select "AL".
5 Confirm the address and unit number.
E Press the
number. After a while, "- - " will start to flash in the mode number display area.
Mode number display section
* "88" will flash in the room temperature display area if the selected address
does not exist in the system. Furthermore, if address display area also flashes, there are no units that correspond to the selected unit number. In this case, the address and unit number may be incorrect, so repeat steps 2 and 3 to set the correct ones.
6 Select the mode number.
F Press the [
number. (Only the selectable mode numbers can be selected.)
7 Select the setting content for the selected mode.
G Press the
flash, so check the currently set content.
8 Register the settings you have made in steps 3 to 7 .
E Press the
to flash and registration starts.
MODE
button to confirm the address and unit
MODE
"F"
appears and flashes in the unit number display area and the
TEMP] buttons ( and ) to set the desired mode
button. The currently selected setting number will
MENU
Setting number display section
button. The mode number and setting number will start
Setting number 1 = Indoor unit operating average
E When the address and unit number are confirmed by pressing the
button, the corresponding indoor unit will start fan operation. This
MODE
helps you find the location of the indoor unit for which you want to perform function selection. However, if "00" or "AL" is selected as the unit number, all the indoor units corresponding to the specified address will start fan operation.
Example) When the address is set to 01 and the unit number is 02.
00 address Outdoor unit
Indoor unit
Designate operation
* When grouping different systems, if an indoor unit other than the
one to which the address has been set performs fan operation, there may be another address that is the same as the specified one. In this case, check the DIP switch of the outdoor unit to see whether such a address exists.
Mode number display section
F Press the [
number.
The mode number and setting number will stop flashing and remain lit, indicating the end of registration.
TEMP] buttons ( and ) to select the desired setting
Main Sub
Remote controller
Mode number 02 = Indoor temperature detection
Setting number 3 = Remote controller built-in sensor
Fan draft
* If " - - - " is displayed for both the mode number and setting number and "
Check to see if there are any sources of noise or interference near the transmission path. 9 If you wish to continue to select other functions, repeat steps 3 to 8 . 0 Complete function selection.
A Hold down the
buttons simultaneously for at least two seconds.
After a while, the function selection screen will disappear and the air condi­tioner OFF screen will reappear.
Note If a function of an indoor unit is changed by function selection after installation is complete, make sure that a " " mark, etc., is given in the "Check" column of Table 1 to indicate the change.
( mode 15 or more) and
FILTER TEST
" flashes in the room temperature display area, a transmission error may have occurred.
* Do not operate the remote controller for at least 30 seconds after completing
function selection. (No operations will be accepted even if they are made.)
Page 43
43
10-2. FUNCTION SELECTION OF REMOTE CONTROLLER
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when needed.
Item 1
1.Change Language ("CHANGE LANGUAGE")
2.Function limit ("FUNCTION SELECTION")
3.Mode selection ("MODE SELECTION")
4.Display change ("DISP MODE SETTING")
Item 3 (Setting content)
Display in multiple languages is possible.
Setting the range of operation limit (operation lock)
Setting the use or non-use of "automatic" operation mode
Setting the temperature adjustable range (maximum, minimum)
Selecting main or sub remote controller
*
When two remote controllers are connected to one group, one controller must be set to sub.
Setting the use or non-use of clock function
Setting the timer type
Contact number display in case of error
Setting the telephone number
Setting the temperature unit (: or °F) to display
Setting the use or non-use of the display of indoor (suction) air temperature
Setting the use or non-use of the display of "Cooling" or "Heating" display during
operation with automatic mode
Item 2
Language setting to display
(1)
Operation function limit setting (operation lock) ("LOCKING FUNCTION")
(2)
Use of automatic mode setting ("SELECT AUTO MODE")
(3)
Temperature range limit setting ("LIMIT TEMP FUNCTION")
(1)
Remote controller main/sub setting ("CONTROLLER MAIN/SUB")
(2) Use of clock setting ("CLOCK") (3) Timer function setting ("WEEKLY TIMER") (4) Contact number setting for error situation ("CALL.")
(1) Temperature display :/°F setting ("TEMP MODE :/°F") (2)
Suction air temperature display setting ("ROOM TEMP DISP SELECT")
(3)
Automatic cooling/heating display setting ("AUTO MODE DISP C/H")
[Function selection flowchart] Refer to next page. [1] Stop the air conditioner to start remote controller function selection mode. [2] Select from item1. [3] Select from item2. [4] Make the setting. (Details are specified in item3) [5] Setting completed. [6] Change the display to the normal one. (End)
➔➔
[Detailed setting] [4] -1. CHANGE LANGUAGE setting
The language that appears on the dot display can be selected.
Press the [
MENU] button to change the language.
1 Japanese (JP), 2 English (GB), 3 German (D), 4 Spanish (E), 5 Russian (RU), 6 Italian (I), 7 Chinese (CH), 8 French (F)
[4] -2. Function limit (1) Operation function limit setting (operation lock)
To switch the setting, press the [ ON/OFF] button. 1 no1 : Operation lock setting is made on all buttons other than
the [
ON/OFF] button.
2 no2: Operation lock setting is made on all buttons. 3 OFF (Initial setting value) : Operation lock setting is not made
* To make the operation lock setting valid on the normal screen, it is
necessary to press buttons (Press and hold down the [FILTER] and [ ON/OFF] buttons at the same time for two seconds.) on the normal screen after the above setting is made..
(2) Use of automatic mode setting When the remote controller is connected to the unit that has auto­matic operation mode, the following settings can be made.
To switch the setting, press the [ ON/OFF] button. 1 ON (Initial setting value) : The automatic mode is displayed when
the operation mode is selected.
2 OFF : The automatic mode is not display
when the operation mode is selected.
[4] -3. Mode selection setting (1) Remote controller main/sub setting
To switch the setting, press the [ ON/OFF] button.
1 Main : The controller will be the main controller. 2 Sub : The controller will be the sub controller.
(2) Use of clock setting
To switch the setting, press the [ ON/OFF] button.
1 ON :The clock function can be used. 2 OFF: The clock function cannot be used.
(3) Timer function setting
To switch the setting, press the [ ON/OFF] button (Choose one of the followings.).
1 WEEKLY TIMER (initial setting on MA deluxe):
The weekly timer can be used.
2 AUTO OFF TIMER: The auto off timer can be used.
SIMPLE TIMER (Default setting on MA smooth):
The simple timer can be used.
4
3
TIMER MODE OFF: The timer mode cannot be used.
* When the use of clock setting is OFF, the "WEEKLY TIMER" cannot be
used.
(4) Contact number setting for error situation
To switch the setting, press the [ ON/OFF] button.
1 CALL OFF:
The set contact numbers are not displayed in case of error.
2 CALL **** *** **** : The set contact numbers are displayed in case
of error.
(3) Temperature range limit setting After this setting is made, the temperature can be changed within the set range.
To switch the setting, press the [ ON/OFF] button. 1 LIMIT TEMP COOL MODE :
The temperature range can be changed on cooling/dry mode.
2 LIMIT TEMP HEAT MODE :
The temperature range can be changed on heating mode.
3 LIMIT TEMP AUTO MODE :
The temperature range can be changed on automatic mode. 4 OFF (initial setting) : The temperature range limit is not active. *
When the setting, other than OFF, is made, the temperature range limit setting on cooling, heating and automatic mode is made at the same time. However the range cannot be limited when the set temperature range has not changed.
To increase or decrease the temperature, press the [ TEMP ( ) or ( )] button.
To switch the upper limit setting and the lower limit setting, press the
[ ]
button. The selected setting will flash and the temperature can be set.
Settable range
Cooling/Dry mode : Lower limit: 19 : ~ 30: Upper limit: 30 : ~ 19: Heating mode : Lower limit: 17 : ~ 28: Upper limit: 28 : ~ 17: Automatic mode : Lower limit: 19 : ~ 28: Upper limit: 28 : ~ 19:
CALL_ : The contact number can be set when the display is as
shown on the left.
Setting the contact numbers To set the contact numbers, follow the following procedures. Move the flashing cursor to set numbers. Press the [
TEMP. ( ) and ( )] button to move the cursor to the right (left). Press the [ CLOCK (
) and ( )] button to set the numbers.
[4] -4. Display change setting (1) Temperature display :/ F setting
To switch the setting, press the [ ON/OFF] button.
1 : : The temperature unit : is used. 2 F: The temperature unit
°
°°
F is used.
(2) Suction air temperature display setting
To switch the setting, press the [ ON/OFF] button.
1 ON :The suction air temperature is displayed. 2 OFF: The suction air temperature is not displayed.
(3) Automatic cooling/heating display setting
To switch the setting, press the [ ON/OFF] button. 1 ON :One of "Automatic cooling" and "A utomatic heating" is displayed
under the automatic mode is running.
2 OFF: Only "Automatic" is displayed under the automatic mode.
Page 44
44
Flowchart of Function Setting
Setting language (English)
Item1 Item2
Change Language
Normal display (Display when the air condition is not running)
Hold down the E button and press the D button for 2 seconds.
Remote controller function selection mode
E
Hold down the E button and press the D button for 2 seconds.
E Press the operation mode button. G Press the TIMER MENU button. D Press the TIMER ON/OFF button.
G
EN
Dot display
GE
ES
RU
G
IT
ZH
FR
F
TEMP.
MENU
E
PAR-21MAA
G
MONITOR/SET
BACK DAY
CLOCK
ON/OFF
OPERATION
ON/OFF
FILTER
CHECK
CLEAR
I A
TEST
B
H
D
C
Function selection
Mode selection
JA
G
G
E
G
G
E
G
G
E
G
G
G
D
D
D
D
D
D
Item3
D
D
D
D
D
D
OFF
on1
on2
ON
OFF
OFF
Operation lock setting is not used. (Initial setting value)
D
Operation lock setting is except On/Off buttons.
Operation lock setting is All buttons.
The automatic mode is displayed when the operation mode is selected. (Initial setting value)
D
The automatic mode is not displayed when the operation mode is selected.
The temperature range limit is not active. (Initial setting value)
D
The temperature range can be changed on cooling/dry mode.
The temperature range can be changed on heating mode.
The temperature range can be changed on automatic mode.
The remote controller will be the main controller. (Initial setting value)
D
The remote controller will be the sub controller.
ON
OFF
The clock function can be used. (Initial setting value)
D
The clock function can not be used.
Weekly timer can be used. (Initial setting value)
D
Auto off timer can be used.
Simple timer can be used.
Display mode setting
Timer mode can not be used.
D
OFF
D
CALL-
G
G
G
G
D
:
°F
D
D
ON
OFF
D
D
ON
OFF
D
The set contact numbers are not displayed in case of error. (Initial setting value)
D
The set contact numbers are displayed in case of error.
:
The temperature unit
D
The temperature unit °F is used.
Room air temperature is displayed. (Initial setting value)
is used. (Initial setting value)
D
Room air temperature is not displayed.
One of "Automatic cooling" and "Automatic heating" is displayed under the automatic mode is running. (Initial setting value)
D
Only "Automatic" is displayed under the automatic mode.
Page 45
45
11
SYSTEM CONTROL
11-1. VARIETY OF SYSTEM CONTROL FUNCTIONS
System Name System Diagram Features
Parts Required in Addition to Standard System
Components (Indoor/Outdoor Units, Remote Controller)
A.Remote control-
ler operation
Use of two con­trollers enables operation of the air conditioner both from a distance and nearby.
B.Group control
operation
Use of one remote controller to con­trol multiple air conditioners with the same settings simultaneously.
Up to two remote controllers can be connected to one group.
Operation control by the latest command (last en­tered priority) Wired remote controllers can be combined as a pair.
One group can consist of up to 16 indoor units, and they can be started sequentially by connecting the remote controller to them and assigning an address to each inter face.
All the units belonging to the same group are oper­ated in the same mode, but thermostats can be turned ON/OFF individually for each indoor unit.
Up to two remote controllers can be connected.
* One of the wired remote con-
trollers must be set as a sub remote controller.
Wired remote controller (addi­tional) (PAR-21MAA)
Inter face MAC-397IF-E
C. Timer operation
Enables control of start and stop.
* For control by
external timer, refer to Remote/ handheld com­bined control op­eration".
Weekly timer: In addition to ON/OFF, up to eight temperature patterns can be set for each day of the week.
* Only one timer can be selected; the auto off, simple
and weekly timers cannot be combined.
Simple timer: Start and stop operations can each be
performed once within 72 hours (can be set in 1-hour increments).
Auto off timer: Operation is stopped when the preset
time elapses following the start of operation. The time can be set from 30 minutes to 4 hours in 30-minute increments.
* Only one timer can be selected; the simple and auto
off timers cannot be combined.
MA Remote controller (PAR-21MAA)
Indoor unit
Remote Controller
Remote Controller
Inter face Indoor
unit Outdoor unit
Page 46
46
11-3. TWO-REMOTE CONTROLLER OPERATION
(1) Two Wired Remote Controllers
(R: Wired remote controller)
Slim Air Conditioner System
Standard 1:1
[Reference]
Set one of the remote controllers as the main controller (factory setting) and the other as the sub controller using the remote controller's function selection.
Remote controller connection circuit (Controller cable)
Outdoor unit OC
Indoor unit IC
Wired remote controller R
Outdoor unit OC
Indoor unit IC
Wired remote controller R
2
OC
2
IC
R-1
R-2
2
11-2. ONE REMOTE CONTROLLER (STANDARD) OPERATION
(1) One Wired Remote Controller
(OC: Outdoor unit IC: Indoor unit R: Remote controller (for wireless type: optical receiver adapter)
Slim Air Conditioners System
Remote controller connection circuit (Controller cable)
Outdoor unit OC
Indoor unit IC
Wired remote controller R
Indoor/Outdoor connection cable
Remote controller cable
OC
IC-1
R
2
2
Standard 1:1
(Reference)
Electrical wiring diagram
OC IC
1 2
LN
Power source wiring
1 2
1 2
1 2
R
(No polarity)
Outdoor unit Indoor unit Remote controller
Power source wiring
(Polarity)
Power supply terminal block L, N
Indoor/outdoor connection cable terminal
block 1,2 (Polarity)
Remote controller cable terminal block 1,2 (No polarity)
Remote controller cable
OC
R-1
2
IC
2
2
R-2
Indoor/outdoor connection cable
Page 47
47
Indoor control board
CN105
or
CN92
2.Connecting the remote control interface with each system
(For details on each system, see the relevant instruction manual.)
Replace the interface unit mounting cord clamp with a supplied mounting cord clamp based on the thickness of the connecting cable used for each system.
The cables connected to the Indoor unit should be mounted on or near the Indoor unit. If the connecting cable is not securely mounted, the connector may detach, break, or malfunction.
Set the interface dip switch (SW500502) settings before turning on the power.
If the interface dip switch (SW500502) settings are not set correctly, the system will not function properly.
Connecting cable for each system
Mounting screws 4 o 16
Electrical wire mounting bracket
Mounting cord clamp
Mounting screws 4 o 10
Mounting cord clamp
Connect the connecting cable that comes with the interface unit to the connector CN105 or CN92 on the indoor control board.
INDOOR
Mounting screws (black) 3.5 o 12
Interface unit mounting cord clamp or mounting cord clamps
11-4. GROUP CONTROL OPERATION
(COLLECTIVE OPERATION AND CONTROL OF MULTIPLE REFRIGERANT SYSTEMS (2 to 16))
Group control can be operated by using MAC-397IF-E. The setting of wired remote controller is subjected to variation according to the function of the indoor unit. (for mode operation, setting temperature, fan step, air direction) The display of remote controller and operating the indoor unit might be different. Neither the test run nor the function setting can be done by MA remote controller connected with MAC-397IF-E.
1.Connecting the MA& CONTACT TERMINAL Interface to the Indoor Unit
Connect the interface unit and the indoor control board using the connecting cable that came with the interface.
Extending or shortening the connecting cable that comes out of the interface may cause it to malfunction. Also,
keep the connecting cable as far as possible away from the electrical wires and ground wire. Do not bundle them together.
Page 48
48
Use as a Wired Remote Control (Using the MA Remote Controller)
Note:
1.Be sure the Auto Heating/Cooling Display Setting on the MA remote controller is set to OFF before use.
•For information on how to set the Auto/Heating Cooling Display Setting, see the MA remote controller instruction manual.
•The actual operating status of the unit may differ from what is shown on the remote controller display
2.A test run cannot be initiated using the test run switch on the MA remote controller..
3.The horizontal vanes on the unit cannot be operated using the louver switch.
4.The range of room temperature indication is between 10: and 38:.
CN560
TB580
2
1 2 A B
Indoor unit
Remote control cord that came with the MA remote controller (Non polarity)
Dip switch settings
SW500 does not have to be set. SW501:
SW501- No. 1-4: Refrigerant address
Set this switch when multiple indoor units (and remote control interfaces) are connected to a single MA remote controller. Always start the refrigerant address at "0".
1
Even when connecting multiple outdoor units, set a different refrigerant address for each indoor unit.
ON
1
2 3 4
ON
1
2 3 4
ON
1
2 3 4
ON
1
2 3 4
1Outdoor unit 2Outdoor unit 3Indoor unit 4Interface 5MA remote controller
Refrigerant address
0
1
2
15
SW501- No. 5–6
ON
5
6
When the model of Mr. SLIM exists in the same group, it sets it to turning ON.
Set them to ON only when using the room temperature sensor installed in the MA remote controller. * This can be switched when an accurate room temperature cannot be detected by the air conditioner unit. PE-GAK(T) series do not have a room temperature sensor on their MA remote controllers.
No. 5 should normally be set to OFF. Under the following conditions, No.6 should normally be set to ON.
Interface unit
Refrigerant address "0"
Refrigerant address "1"
Refrigerant address "2"
MA remote controller (PAR-21MAA) * PAR-20MAA cannot be used
with this interface.
112
333
4
5
44
Page 49
49
SW501: Settings to accommodate MA remote controller and settings to accommodate outdoor units
SW No.
No. 1 No. 2 No. 3 No. 4
Functions OFF ON Comments
Only specify these settings when connecting an MA remote controller.
Functions Room temperature detector The model of Mr. SLIM exists in the
same group.
This should normally be set to ON.
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1 2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1 2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1
2 3 4 5 6
ON
1 2 3 4 5 6
ON
1
2 3 4 5 6
Refrigerant address 0
Refrigerant address 1
Refrigerant address 2
Refrigerant address 3
Refrigerant address 4
Refrigerant address 5
Refrigerant address 6
Refrigerant address 7
Refrigerant address 8
Refrigerant address 9
Refrigerant address 10
Refrigerant address 11
Refrigerant address 12
Refrigerant address 13
Refrigerant address 14
Refrigerant address 15
OFF Indoor unit Not mixed
ON Remote control Mixed
Comments
This should normally be set to OFF.
SW No.
No. 5 No. 6
Page 50
50
* Fan speed 2 step model : An actual fan speed is 2 step though the display of remote controller becomes 4 step or 3 step.
3. Test Run (Check Operations)
Interface status monitor
You can check the status of the interface by the LED lamp on the interface unit board.
LED lamp no.
LED521
LED522
LED523
Lamp off
DC 12 V is not being supplied from the air conditioner.
Device is not communicating properly with the air conditioner.
Device is not communicating properly with the MA remote controller.
Lamp on
DC 12 V is being supplied from the air conditioner.
Blinking
Blinking at approx. 1 second intervals: Device is communicating normally with the air conditioner.
Blinking at approx. 8 second intervals: Device is com­municating normally with the MA remote controller.
* Use the table above to check the device operations.
SW502 : Air Conditioner Function Settings
SW No.
No. 1
No. 2
No. 3
No. 4
No. 5
No. 6
No. 7 No. 8
Functions
Cooling only type/ Heat pump type
Auto mode
Fan speed
Vane
Swing
Not in use Fan mode
OFF
Heat pump type
Not available
(setting No.3 disabled)
Available
(unit)
Available
Available
Not available
ON
Cooling only type
Available
(setting No.3 enabled)
Available
(remote controller)
Not available
Not available
Available
Comments
Set to OFF.
Permanently set to OFF.
4 speeds
3 speeds
(1-speed,2-speed
model set ON)
When operating 1-speed,2-speed models with the 3-speed setting (ON), the MA remote controller display will indicate 3 fan speeds. The table below shows the displays and the actual outputs at that time.
The 1-speed fan always operates at high speed when turned on.
Display Meaning Indoor unit output
Low speedLow speed
Medium speed High speed
High speed
Set the mode in accordance with the operation manual for the indoor unit.
Heat pump type : Set to ON. Cooling only type : Set to OFF.
The Vane function of either of indoor unit : When the function is provided, it is Available (OFF). When the function is not provided, it is Not available (ON).
The Swing function of either of indoor unit : When the function is provided, it is Available (OFF). When the function is not provided, it is Not available (ON).
Set to ON.
High speed
4. Mounting the Remote Control Interface Unit
The Interface unit should be placed in a location where the connecting cable from the interface can reach an indoor unit. The device will not function properly if the connecting cable is extended so the connecting cable should not be extended. Mount the interface unit securely to a pillar or wall using 2 or more screws.
When Using Wall Mounting Brackets
1
Attach the wall mounting brackets to the interface unit using 2 mounting screws.
2
Mount the unit to a pillar or wall using 2 mounting screws.
Interface unit
Wall mounting brackets
Mounting screws
Mounting screws
Mounting screws
Cord clamp for wiring
Page 51
51
When Mounting Directly to a Wall
Mount the interface unit case to the wall using the mounting screws.
Interface case mounting screws
Mounting screws
When mounting the interface unit inside a ceiling or wall, install an access door to facilitate mainte­nance.
When the interface unit is mounted above an indoor unit, it should be positioned 40 mm or more away from the unit to ensure that ceiling grills can be removed.
40 mm or more
Attach the interface unit connecting cable here. Store extra connecting cable in the ductwork space behind the indoor unit.
* If there is any slack in the connecting cable, use a
fastener to keep it in place.
* When mounting the interface unit using a cushioning
material , be sure to mount it in a location where it will not fall.
Interface unit
Cushioning material
Page 52
52
11-7. TIMER OPERATION
Timer operation can be performed by setting the wired timer. Start and stop times can be set in 10-minute increments within a 24-hour period.
When used in combination with the central control remote controller of the M-NET control system for the outdoor unit, one program timer can be used for individual timer settings for each group of the central control system. (Each timer setting can be stored in data memory so timer settings for up to 50 groups can be set individually.)
Please refer to the MELANS catalog or technical information for details about the central control remote controller.
11-5. POWER OUTAGE AUTOMATIC RECOVERY OPERATION
Whenever a power outage or switching of the power supply causes the power supply of an operating air conditioner to go
from OFF to ON, this function will automatically restore the operation of the air conditioner to its previous operating mode.
w If the power is turned from OFF to ON when the air conditioner is not in operation, the air conditioner will not automatically
be turned on. However, the timer operation will be cancelled if the air conditioner is in timer operation (including when the unit is waiting for its start time). Setting for timer operation must be performed once again.
If there is a momentary power outage of less than one second while the air conditioner is in operation, there may not be a
clear determination of whether or not there was a power failure. When it has been determined that there has been a power failure, recovery will take approximately four minutes after the power is restored. Please wait. (Once "PLEASE WAIT" has appeared on the display, a protection system will operate to prevent the unit from restarting for three minutes.)
When it has been determined that there has been no power failure, operation will continue as is.
Settings can be made by function selections from the remote controller.
When there is group control, selection of all refrigerants is required.
11-6. INDIVIDUAL CONTROL OPERATION FROM A SEPARATE ROOM
By simply centralizing the remote controllers installed in each room in a separate control room, individual control or central-
ized monitoring of the air conditioners in each room can be attained.
Air conditioner control can be performed up to a total of 500 meters away by connecting the indoor units and remote con-
trollers with 0.3 to 1.25 mm
2
2-core cable.
If a remote controller is installed in a room and control room, refer to the section on operating with two remote controllers.
Indoor unit Indoor unit Indoor unit
Remote controller
Control room room 1 room 2 room 3
Page 53
Control box
Drain pan
Drain pipe connection (R1)
Fan motor
Sirocco fan
Suspension bracket
Special washer
Heat exchanger
Liquid pipe
Gas pipe
Inlet thermistor (TH1)
Liquid pipe thermistor (TH2)
Strainer
Drain pan
53
SERVICE DATA PART NAMES12
PE-8,10,12GAK(T)
In case of PE-8,10,12GAK(T)
Page 54
54
PE-16,20,GAK(T)
Drain pan
Drain pipe connection (R1)
Fan motor
Sirocco fan
Suspension bracket
Control box
Special washer
Heat exchanger
No.2 Strainer
No.1 Strainer
2-phase pipe thermistor (TH5-1)
2-phase pipe thermistor (TH5-2)
No.1 Liquid pipe
No.1 Gas pipe
No.2 Liquid pipe
No.2 Gas pipe
No.1 Inlet thermistor (TH1)
No.2 Inlet thermistor (TH2)
Page 55
55
PE-8,10,12GAK(T)
A
Ferrite core
Power supply board
Control board
I/D POWER BOARD
I/D CONTROLLER BOARD
Lo
52F
Hi
52F
51F
X1
FB
view A
L2 NL3L1
TB2
TB4TB5
12 12
Relay
SNB board
Magnetic contactor (Fan motor Lo speed)
Magnetic contactor (Fan motor Hi speed)
Terminal block for remote controller
Terminal block for outdoor/indoor control wiring connection
Power supply terminal block
Page 56
56
PE-16,20GAK(T)
(NO.2)
I/D POWER BOARD
(NO.1)
I/D POWER BOARD
A
view A
I/D CONTROLLER BOARD
(NO.2)
CONTROLLER BOARD
(NO.1)
I/D
FB12
FB22
FB11
FB21
52F
TB2
TB4-1 TB5TB4-2
X1
X2
51F
12 12
Ferrite core Ferrite core
Control board (No.2 unit)
Control board (No.1 unit)
Relay
Power supply terminal block
Terminal block for outdoor/indoor control wiring connection (No.1 unit)
Terminal block for outdoor/indoor control wiring connection (No.2 unit)
Terminal block for remote controller
Magnetic contactor
Control board (No.1 unit)
Control board (No.2 unit)
SNB board
Page 57
57
OPTIONAL PARTS13
Item Individual order number Applicable model
MAC-397IF-E MAC-399IF-E PAC-KE208AF PAC-KE210AF PAC-KE220AF
All models All models PE-8GAK(T) PE-10,12GAK(T) PE-16,20GAK(T)
Group control operation
M-NET operation
Air filter
1 2 3
Page 58
New publication, effective July 2007.
Specifications subject to change without notice.
HWE07060 Printed in Japan
Loading...