The streamelined, square controller is designed to blend with any interior. Also, the sophisticated microprocessor allows you to easily carry
out a wide range of operations.
(2) Attractive LED display
Every operation condition is indicated on the LED display.
(3) Simultaneous display of set temperature and room temperature
The set temperature is indicated by continuous light and the room temperature is indicated by a flashing light. In this way, accurate temperature conditions are always available at a glance and fine temperature
regulation is possible.
(4) Convenient 12-hour ON-OFF timer
The timer switches on and off automatically at the times you set. Once
the timer is set, the remaining time is shown on the LED display.
If a problem occurs, the unit will stop operating and the temperature
display will change to a self-diagnosis indicator, which shows the location of the trouble.
(6) Useful memory feature for storing instructions
The previous set value is memorized so that constant temperature control can be achived. For example, if a power failure occurs, the temperature will not have to be readjusted afterwards.
(7) Cables between remote controller and indoor unit
The polar, 12-core type remote controller cables makes installation simple and troublefree. Also, the cables can be
extended up to 50m. (optional)
2
Page 3
1. AIR OUTLET
New PC series models have 1 air outlet (auto vane switching of horizontal air flow / down flow by switched by auto vane)
instead of 2 (horizontal, and down flows).
2. EASY TO CLEAN ; FLOCKLESS VANE
With our original air current control mechanism, a flockless vane is
newly adapted.
The flockless vane prevents the condensation on the vane.
By changing the vane to the flockless type, the unit can be cleaned
much easier with mild household detergent.
B
Flockless vane
A
Air outlet
Protruding portion A
Unifies the air speed
with the vane.
Protruding portion B
Sending the air to the upper
area of the vane
Prevents the air comes from
outside the unit
+
=
3. NEW MATERIALS FOR BETTER OIL RESISTANCE
We have changed the materials of grill, filer, fan and fan casing from ABS to P.P. (polypropylene) for better oil resistance. As
a result, oil crazing is cut in half.
4. SIMPLIFIED INSTALLATION WORK (DIRECT SUSPENDING METHOD)
Simplified the installation work by changing the suspending method to the direct suspending method (suspending the unit
directly from the suspension fixture).
In this way, the unit can be attached to the suspension fixture without removing the installation parts off (Only the side cover
is removed). This method is much simpler than the ¨One-time installation method¨.
5. IMPROVING EFFICIENCY OF PIPING WORK
New PC series models have 1 air outlet (auto vane switching of horizontal air flow / down flow by switched by auto vane)
instead of 2 (horizontal, and down flows).
1 Removed the knockout work by separating the piping space
from the air outlet for efficiency of the piping work.
Side panel
L
G
G
D
Open
L : Liquid pipe
G: Gas pipe
D: Drain pipe
U-cut
Back panel
L
D
Open
w Knockout work is needed for the top part. When optional
drain-up machine is installed, the refrigerant pipe exits out
from the top.
2 Improved the flexibility by making it possible for drainage
pipe to exit not only from the right side back but also from
the left side back.
Rubber plug
Insulation cover
(attached)
Drain pipe
(purchased locally)
Joint coupliy
(attached)
Drain pan
Insulation
cover
Band
(attached)
w Please move the rubber plug for the unit to the right joint
when drainage pipe exits from the left side.
3
Page 4
Air outlet
Intake grille
Air intake
Left/right guide vanes
Change the direction of airflow
from the horizontal blower.
Long-life filter
Removes dust and foreigh matter from air coming in
through the grille (Recommended cleaning interval :
Approx, every 2,500 operating hours)
Up/down guide vanes
Change the direction of airflow from the
vartical blower.
6. QUITENESS ; 43dB : PC-3GJA1(HIGH NOTCH)
Auto vane
Swing
Quiteness of the New PC series product is significant. It is because we have adapted the new shape air outlet and changed
the air coures.
7. EASY MAINTENANCE ; NO MAINTENANCE NECESSARY FOR 2500 HOURS
The new long-life air filter can be used continuously 2500 hours without maintenance (at general office situation).
8. CHOICE OF FILTER
High performance filter can be purchased optionally for the special needs.
LocationsAppropriate filterCapabilityFilterMaintenanceHow to attach to the unit
Busy
shops etc···
Regular
office, shops
High performance
filter
Standard longlife
filter
Weighing
method 70%
Weighing
method 30%
2500 hours
2500 hours
The filter can be used
again after cleaning.
The filter can be used
again after cleaning.
Remove the standard long life filter
before attach this optional parts.
It is already attached to
the unit
2
PART NAMES AND FUNCTION
● Indoor (Main) Unit
4
Page 5
● Remote controller
MITSUBISHI ELECTRIC
12
11
10
9
8
7
6
5
4
3
2
1
29
28
27
26
25
24
23
22
21
20
19
18
TIMERTEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER
MODE
DRY
FAN
HIGH
LOW
ON
AUTO
STOP
START
TIMER / TEMP.
This button is used to change
between display of room temperatue and display of remaining timer time durining “AUTO
STOP” operation. Green lamps
light in selected display mode.
Settings remain in effect until changed. Air
conditioner can be operated by simply pushing
ON/OFF button once settings have been
made.
Display PanelOperating panel
ON / OFF button
Pushing button starts
operation. Pushing again
stops operation. Green
lamp remains lit during
operation.
MODE SELECT button
This button is used to
change between cooling.
ventilation and DRY(or heating)operation modes.One of
three green lamps light to
indicate mode in effect.
Lamps display remaining
timer time or room temperature.
Remaining timer time display
Lamps indicate time remaining
until timer stops timed operation.
Green lamps corresponding to
remaining number of hours light.
Room Temperature display
Lamps display temperatue setings and actual room temperatues.
Temperatue settings.
Green lamps light.
Temperatue in room.
Green lamps flash.
(Example display readings are
for explanations only; actual display readings will differ.)
Attention:
Pushing UP and DOWN buttons together for more than two seconds will initate “trial run” or “inspection” mode. Avoid
pushing these buttons simultaneously during normal operation. Push ON / OFF button to cancel trial run or inspection
mode if initiated by accident.
All green lamps turn off when air conditioner is stopped.
Avoid operation of buttons with fingernails or other sharp object. Sharp object may scratch operating panel.
*Heating operation mode is only available for models with built-in electric heater.
UP and DOWN buttons
Temperature control (While ”TEMP” green lamp is
lit.)
Use UP and DOWN buttons to set desired temperature between 18 and 29
o
C.
Timed operation (While green “TIMER” lamp is lit.)
Use UP and DOWN buttons to set timed operation
between one and twelve hours.
FAN SPEED button
This button is used to
change between low and
high fan speeds. One of
two green lamps lights to
indicade fan speed in
effect.
Swing Louver Button
Used to automatically
disperse airflow vertically.
Air is blown in one
direction when louver is
not turning. Lamp lights
effect.
TIMER MODE button
Used for selecting timed
starting or stopping.Green
lamp light to indicate
timer mode selected.
5
Page 6
3
Service Ref.
External finish
Fan motor output
Airflow Lo-Hi
External static pressure
Operation control & Thermostat
Noise level Low-High
Cond. drain connector
Dimensions
Weight
Service Ref.
External finish
Refrigerant (R-22) control
Crankcase Heater w3
Compressor output
Protection devices
Fan motor output
Airflow
Air speed
Coverage
range
Airflow
Air speed
Coverage
range
m
3
/min
m/sec.
m
ft
m
3
/min
m/sec.
m
ft
Configuration
50Hz
Frequency
60Hz
Service Ref.
PC-4GJSA
1
25
4.1
12.6
41.6
25
4.1
12.6
41.6
PC-5GJSA
1
34
4.38
15.2
50.0
34
4.38
15.2
50.0
PC-6GJSA
1
34
4.38
15.2
50.0
34
4.38
15.2
50.0
PC-3GJA
1
18
3.8
10.4
34.5
18
3.8
10.4
34.5
PC-2.5GJA
1
18
3.8
10.4
34.5
18
3.8
10.4
34.5
Ceiling suspended
PC-2GJA
1
13
3.7
8.8
29
13
3.7
8.8
29
The unit of pressure has been changed to MPa based on SI(International System of unit) in accordance with I.S.O.(International
Organization for Standardization).
The conversion factor is : 1(MPa•G)=10.2(kgf / FF•G)
3. OUTLET AIR SPEED AND COVERAGE RANGE
The air coverage range is the value up to the position
where the air speed is 0.25 m/sec. when air is blown out
horizontally from the unit at Hi notch position.
The coverage range should be used as a general guideline since it varies according to the size of the room and
furniture inside the room.
11
Page 12
5
180
210
157
15
85
182 (3/8F) liquid
201 (5/8F) gas
241 (Drainage)
Air intake
918
254
680
Electrical box
226
70
525
928
352
263
171
138
86
46 1751
131
38
3879
161
32
179
42
6-7
Celling
Electrical box
[FRONT VIEW]
When electrical
box is pulled
down
3
2
8
5
1
4
6
2
1
17
150
140
70
320
80
933 (suspension bolt pitch)
983
1000
Air outlet
81
904
76
Gap to ceiling
OUTLINES AND DIMENSIONS
1. INDOOR UNIT
PC-2GJA1
NOTES:
refrigerant pipe will be only upper drain pipe arrangement.
1. Use M10 or W3/8 screws for anchor bolt.
2. Please be sure when installing the drain-up machine (option parts).
NAME
RUN INDICATOR LED
COOLING INDICATOR LED
FAN MODE INDICATOR LED
FAN HIGH INDICATOR LED
LOUVER RUN INDICATOR LED
INDICATOR MODE TEMPERATURE LED
INDICATOR MODE TIMER LED
DRY INDICATOR LED
FAN LOW INDICATOR LED
OFF TIMER INDICATOR LED
ON TIMER INDICATOR LED
TEMPERATURE / TIMER REMAINING TIME INDICATOR LED
FAN MOTOR
VANE MOTOR
HIGH CELING TYPE SWITCH
FUNCTION SELECTOR
JUMPER RESISTORS
NAME
OPTION SWITCH
FUNCTION SWITCH
UNIT SWITCH
EMERGENCY OPERATION SWITCH
ON / OFF SWITCH
OPERATION MODE SWITCH
FAN HIGH/LOW SWITCH
LOUVER ON / OFF SWITCH
INDICATOR SWITCH
TEMPERATURE / TIMER
SETTING UP SWITCH
TEMPERATURE / TIMER
SETTING DOWN SWITCH
TIMER CONTINUOUS ON / OFF SWITCH
REMOTE CONTROLLER BOARD
TRANSFOMER
POWER SUPPLY TERMINAL BLOCK
SYMBOL
TB4
RT1
RT2
X1<I.B>
X4<I.B>
ZNR
DP
DS
W/B
CNB(W.B)
LED1(W.B)
SW2(W.B)
RU(W.B)
NAME
INDOOR / OUTDOOR CONNECTING WIRE TERMINAL BLOCK
ROOM TEMPERATURE THERMISTOR
(0 /15k ,25 /5.4k DETECT)
INDOOR COIL THERMISTOR
(0 /15k ,25 /5.4k DETECT)
DRAIN-UP MACHINE RELAY
FAN MOTOR RELAY
VARISTOR
OPTION DRAIN-UP MACHINE
OPTION DRAIN SENSOR
OPTION WIRELESS REMOTE
CONTROLLER BOARD
INDOOR BOARD CONNECTOR
RUN INDICATOR LED
COOL OPERATION SWITCH
BEAM RECIEVE UNIT
[Emergemcy operation procedure]
(2) Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker in this order.
(3) During emergency operation, indoor fan runs at high speed but automatic vane remains stop.
(4) If vane closed, open the vane by hand slowly.
(5) Thermostat will not function.
(6) Emergency cooling should be limited to 10 hours maximum (The Indoor unit heat exchanger may freeze).
(7) If the ,microcomputer doctor detects the abnomality of the drain-up machine during cool mode. do not execute emergency operation (It causes drain overflow).
NOTES :
1. Since the indoor fan motor (MF) is connected with 220V power, using 230, 240V power will require a setting change of the dip switch (SW1<I.B>) on the indoor controller board
as shown in fig : w1.
fig : w1
Indoor fan motor (MF) for 230, 240V.
2. Since the indoor transformer (T) is connected with 220V power, if 230, 240V power used. Change the wiring connection showing fig : W2.
fig : w2
When power supply is
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4. Symbols used in wiring diagram above are. : Connector , : Terminal block
5. Emergency operation
If remote controller or microcomputer fails but there is no other trouble,. emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board.
[Check items]
(1)Compressor and fan.
(2)Check the abnomality using self diagnostic function. When the result of self diagnosis indicates protective device such as freeze protection, emergency operation is not possible
unless the cause is removed.
(3)Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with remote controller is not possible).
[Emergency operation procedure]
(1)Set the dip switch(SW3<I.B>) on the indoor controller board to
w1Refer to page 26 for timer mode details.
w2The unit starts operation by pressing the ON / OFF switch when unit is OFF.
w3The factors which cause "abnormal operation mode" are as follows.
●Outdoor unit abnormal operation.
●Fault of room temperature thermistor (RT1).
●Fault of indoor coil thermistor (RT2).
●Indoor coil frost protection mode.
●Drain water overflow prevention mode.
Refer to page 28 for abnormal operation mode details.
w4The compressor will not start for 3 minutes after the stop.
20
Page 21
COOLING OPERATION
COOL operation
NO
NO
NO
Vane setting notch
Initial
COOLING
w8
Downward discharge
Vane horizontal
w9
Vane initial
setting
Fan speed
LOW
1 hour
airflow
Compressor
thermostat
ON
Allowance
cancel
NO
YES
YES
YES
NO
NO
YES
YES
NO
w10
w11
YES
3-minute
time delay
NO
6-minute
time delay
NO
3-minute
compressor
operation
YES
Coil frost
prevention
Cooling area
NO
YES
NO
Allowance
period
NO
6 minute
time delay
Allowance set
YES
Coil frost protection
NO
Allowance cancel
NO
temperature is
Compressor ON
compressor
operation
YES
Coil frost
protection
NO
16-minute
compressor
operation
YES
Indoor pipe
1°C or lower
NO
1
YES
YES
Coil frost
prevention
Compressor OFF
Indoor coil
tempreature is
10°C or higher
YES
3-minute
time delay
Coil frost
prevention release
NO
NO
1 min continue
FAN speed
FAN speed
LOW 5 min
elapse
LOW
YES
NO
YES
Outdoor unit
trouble
YES
10-minute
w8 When operation stops or changes to cooling or dry mode, the auto vane turns to a horizontal angle. If operation changes
during auto vane SWING, the auto vane will continue to swing.
w9 When operating TEST RUN, the thermostat will be continuously ON.
w10 After 3 minute compressor operation, if the indoor coil thermistor reads -15°C or below for 3 minutes, the compressor will
stop for 6 minutes.
w11 Cooling area : Indoor coil temperature is more than 5 degrees above the room temperature.
FAN area: Indoor coil temperature is within 5 degrees either way of the room temperature.
21
Page 22
DRY OPERATION
DRY
operation
Vane
setting notch
NO
YES
NO
Initial dry
operation
YES
Vane initial setting
Room tempereature is
18°C or lower
NO
During
compressor ON
YES
3-minute
compressor
operation
YES
Compressor &
thermostat ON
w8
w12
w9
YES
NO
NO
YES
3-minute
time delay
NO
Compressor &
thermostat
ON
NO
YES
w9
Compressor ON
time completes
YES
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
1
w8—9 Refer to page 24~25.
w12When room temperature is 18°C or below, the compressor cannot operate.
When room temperature rises over 18°C, the compressor starts after a 3-minute time delay.
w13Compressor ON time is decided by room temperature. Refer to page 24~25.
w14In dry operation, compressor ON makes the fan speed LOW and compressor OFF stops the fan.
It is not possible to set the fan speed with the remote controller
22
NO
w14
10-minute
compressor
OFF
YES
Compressor ON
time set
Compressor ON
Fan speed LOW
NO
w13
w14
Page 23
MICROPROCESSOR CONTROL9
MITSUBISHI ELECTRIC
12
11
10
9
8
7
6
5
4
3
2
1
29
28
27
26
25
24
23
22
21
20
19
18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER
MODE
DRY
FAN
HIGH
LOW
ON
AUTO
STOP
START
1.OUTLINE OF MICROPROCESSOR CONTROL
INPUT to remote controller
● OFF-ON switching.
● COOL/DRY-FAN selector switching.
● Thermostat setting.
● HIGH-LOW fan speed switching.
● Swing louvers SWING-FIXED switching.
● TIMER mode selector switching.
● Timer setting.
● Self diagnostic troubleshooting.
● Test run switching.
Indoor unit
REMOTE CONTROLLER
● Transmits and receives orders.
12VDC12VDC
OUTPUT to remote controller
● Indication LED lights.
Polar, twelve (12) - core cable
Maximum length 50m (164ft)
INPUT from indoor unit
● Room temperature thermistor.
● Indoor coil thermistor.
OUTPUT to indoor unit
● Fan : ON - OFF.
● Fan speed : HIGH - LOW
● Swing louver : ON-OFF
● Emergency stop.
INPUT from outdoor unit
● Compressor protection device working
INDOOR CONTROLLER BOARD
● Receives orders from remote controller and temperature data from
indoor unit.
● Processes orders and data.
● Transmits the power of indication LED to remote controller
● Controls indoor and outdoor operation.
● Self diagnostic function.
w System control operation.<Optional>
w Emergency operation.
Non - polar, two (2) - core cable
Outdoor unit
OUTDOOR UNIT
● Receives order from indoor
controller.
● Emergency stop.
OUTPUT to outdoor unit
● Compressor motor and outdoor fan motor :
ON - OFF
23
Page 24
2. INDOOR UNIT CONTROL
TIMER
MITSUBISHI ELECTRIC
12
11
10
9
8
7
6
5
4
3
2
1
29
28
27
26
25
24
23
22
21
20
19
18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER
MODE
DRY
FAN
HIGH
LOW
ON
AUTO
STOP
START
2-1COOL operation
<COOL operation time chart>
Operation starts by
POWER button
ON.
ON
Thermostat
OFF
<How to operate>
1 Press POWER ON/OFF button.
2 Press MODE SELECT button to set operation mode to COOL.
3 Check lamp is ON and set desired temperature with UP
TEMP.
or DOWN button.
NOTES : 1. When lamp is ON, press TIMER/TEMP button
to change the display to temperature mode.
2. Set temperature changes by 1°C in the range 18 ~ 29°C
each time UP or DOWN button is pressed.
3. The lighting lamp shows the set temperature, and the
flashing lamp shows the room temperature.
When the room temperature is equal to the set temperature, the lamp keeps lighting, 0.5 seconds brightly and
0.5 seconds faintly.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
Operation stops by
POWER button
OFF.
ON
LOW or HIGHLOW or HIGH
Indoor fan
Louver
OFF
ON
OFF
Depends on remote controller setting
ON
Compressor
OFF
MIN. 3 minutes w1
w1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period has ended.
(1) Compressor control
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when room temperature is higher than set temperature.
The compressor stops when room temperature is equal to or lower than the set temperature.
3 The compressor stops in check mode or during protective functions.
4 Coil frost prevention
To prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 1°C or below after the
compressor has been continuously operated for at least 16 minutes or more. The coil frost prevention is released under any
of the following conditions.
● The indoor coil thermistor rises to 10°C or above.
● The room temperature becomes equal to or lower than the set temperature.
● COOL mode is stopped or changed to another mode.
NOTE : By cutting the jumper wire JRO2 on the indoor controller board, the temperature to start coil frost prevention
changes from 1°C to -3°C.
5 Coil frost protectiony
24
When indoor coil temperatuer becomes -15°C or below, coil frost protection will proceed as follows.
<Start condition>
After the compressor has been continuously operated for 3 minutes or more, and the indoor coil temperature has been -15°C
or below for 3 minutes, the coil frost protection will start.
<Coil frost protection>
Compressor stops for 6 minutes, and then restarts.
If the start condition is satisfied again during the first 10 minutes of compressor operation, both the indoor and outdoor units
stop, displaying a check code of ¨P6¨ on the remote controller.
Page 25
<Termination conditions>
MITSUBISHI ELECTRIC
12
11
10
9
8
7
6
5
4
3
2
1
29
28
27
26
25
24
23
22
21
20
19
18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER
MODE
DRY
FAN
HIGH
LOW
ON
AUTO
STOP
START
TIMER
Coil frost protection is released when the start condition is not satisfied again during the allowance, or when the COOL mode
stops or changes to another mode.
(2) Indoor fan control
Indoor fan speed LOW/HIGH depends on the remote controller setting.
However, if an outdoor unit abnormality is detected, the indoor fan speed will be LOW, regardless of the remote controller
setting.
(3) Louver control
Louver operation (SWING LOUVER ON / OFF) depends on the remote controller setting.
w Louver comes to the holizontal position automatically after 1 hour operation in law mode.
(4) Detecting abnormalities in the outdoor unit
After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperature
and room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the difference is still out of RANGE C,the outdoor unit is functioning abnormally. Thus, the compressor will stops and the remote
controller still display this occurrence.
RANGE A: Indoor coil temperature is more than 5 degrees above room temperature.
RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature.
RANGE C : Indoor coil temperature is more than 5 degrees below room tempetature.
(5) Drain pump control
The drain pump works in COOL or DRY operation. When COOL or DRY operation stops or changes to another mode, the
drain pump continues to operate for 3 more minutes.
<Drain sensor>
When both the drain pump and unit are operating, the drain sensor detects the temperature. This temperature tells
whether the drain water level is above or under the drain sensor. If the drain water level rises above the drain sensor due
to a drain pump malfunction, the unit will enter the check mode. The operation will stop and only the drain pump will continu to operate for 3 more minutes. When either of the following conditions are satisfied, the drain sensor is deamed to be
under water.
● Though the drain sensor has been heated by the drain sensor heater for more than 40 seconds, its temperature rise is
less than 20 degrees.
● The drain sensor temperature is below 63°C.
2-2 DRY operation
2-3 FAN operation
TIMER TEMP
12
11
10
9
8
7
6
5
4
3
2
1
29
28
27
26
25
24
23
22
21
20
19
18
TIMER/TEMP.
UP
DOWN
POWER
ON/OFF
COOL
MODE
DRY
SELECT
FAN
HIGH
FAN
SPEED
LOW
ON
LOUVER
AUTO
STOP
TIMER
MODE
START
MITSUBISHI ELECTRIC
<How to operate>
1 Press POWER ON/OFF button.
2 Press MODE SELECT button to set operation mode to DRY.
3 Check lamp is ON and set desired temperature with UP or DOWN button.
TEMP.
NOTES : 1. When lamp is ON, press TIMER/TEMP button to change the display
to temperature mode.
2. Set temperature changes by 1°C in the range 18 ~ 29°C each time UP or
DOWN button is pressed.
3. The lighting lamp shows the set temperature, and the flashing lamp shows the
room temperature.
When the room temperature is equal to the set temperature, the lamp keeps
lighting, 0.5 seconds brightly and 0.5 seconds faintly.
<How to operate>
1 Press POWER ON/OFF button.
2 Press MODE SELECT button to set operation mode to FAN.
NOTES : Temperature can not be set in FAN operation.
! Indoor fan control
The indoor fan speed LOW/HIGH depends on the remote controller setting.
@ Louver control
The louver operation ON/OFF depends on the remote controller setting.
# Drain pump control
The drain pump does not work in FAN operation. As an exception, when COOL mode
changes to FAN mode, the drain pump continues to operate for the first 3 minutes in FAN
operation.
25
Page 26
TIMER
START w I
AUTO
TIMER
2-4 TIMER operation
MITSUBISHI ELECTRIC
12
11
10
9
8
7
6
5
4
3
2
1
29
28
27
26
25
24
23
22
21
20
19
18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER
MODE
DRY
FAN
HIGH
LOW
ON
AUTO
STOP
START
<Timer function>
AUTO STOP ·········The air conditioner stops after the set time lapses.
AUTO START ········The air conditioner starts after the set time lapses.
<How to operate AUTO STOP timer>
1 While ● POWER lamp is lighting, press TIMER MODE button.
AUTO
STOP w
and lamps turn ON.
2 Set the time for the AUTO STOP timer with the UP or DOWN button.
NOTE : The time setting is in 1 hour units up to 12 hours.
3 With the lapse of time, the timer lamps turn OFF one by one, showing
the remaining time.
4 To cancel the AUTO STOP timer and continue operation, press the
TIMER MODE button.
To cancel the AUTO STOP timer and stop operation, press the
POWER ON/OFF button.
<How to operate AUTO START timer>
1 While ● POWER lamp is OFF, press TIMER MODE button.
and lamps turn ON.
2 Set the time for the AUTO START timer with the UP or DOWN button.
NOTE : The time setting is in 1 hour units up to 12 hours.
3 With the lapse of time, the timer lamps turn OFF one by one, showing
the remaining time.
4 To cancel the AUTO START timer and keep the unit OFF, press the
TIMER MODE button.
To cancel the AUTO START timer and start operation, press the
POWER ON/OFF button.
<Remaining time display>
The green lamps show the remaining time until the time is up. When the time is up, the green lamps are all off.
TIMER
Green
lamps
TEMP
w
12
29
11
28
10
27
9
26
8
25
7
24
6
23
5
22
4
21
3
20
2
19
1
18
Remaining time:2 hour
59 minutes to 2 hour
NOTE : When AUTO STOP timer is active, the remaining time display can be changed to the temperature display by pressing
DISPLAY SELECT button.
TIMER
TEMP
w
12
29
11
28
10
27
9
26
8
25
7
24
6
23
5
22
4
21
3
20
2
19
1
18
1 hour 59 minutes
to 1 hour
TIMER
TEMP
w
12
29
11
28
10
27
9
26
8
25
7
24
6
23
5
22
4
21
3
20
2
19
1
18
59 minutes to 0
TIMER
TEMP
w
12
29
11
28
10
27
9
26
8
25
7
24
6
23
5
22
4
21
3
20
2
19
1
18
Time counting
is completed.
26
Page 27
2-5 Test run
The unit starts the test run by pressing both the UP and DOWN buttons simultaneously for more than two seconds during
TIMER
▲
lamp ON or the unit OFF.
w
● The test run automatically stops in 2 hours.
● Set temperature is not displayed during test run.
● To cancel the test run, press the POWER ON/OFF button.
<Initial setting>
The units are set as follows by the factory.
1) Initial operation mode: FAN 3) Swing louver: OFF
2) Fan speed: LOW4) Set temperature: 28°C
2-6 Emergency operation
When the remote controller or microprocessor malfunctions and no other trouble exists, emergency operation
is available by setting the dipswitch on the indoor controller board.
[Check items]
! Make sure the compressor and the fans are running
normally.
@ Locate the trouble with the self-doagnostic function. If
the self-diagonostic function indicates that the protection device (such as coil frost protection)is functioning, the sources must be removed before attempting
emergency operation.
Emergency operation ON/OFF is activated not with
the remote controller but with the circuit breaker.
SW3
INDOOR CONTROLLER BOARD
[Emergency operation procedure]
! Cooling operation is available by setting the dipswitch
SW3 1 and 2 ON and 3 OFF on the indoor controller board.
@ To start emergency operation, turn the outdoor sidecircuit breakerON first, and then the indoor side circuit breaker ON.
# During emergency operation, the indoor fan runs on HIGH speed, the compressor runs continuously, and the louver
stops.
When the drain pump is attached, it works in emergency operation.
$ Thermostat will not function.
% Do not use emergency cooling operation for more than 10 hours, as the indoor coil may freeze.
w If the self-diagnostic function shows a drain pump malfunction, do not attempt emergency operation, as the drain may
overflow.
2-7 Auto Restart function
Unit can be start / stop by turning the breaker ON / OFF.
! Cutting the JR06 on the indoor board.
Unit can be start / stop using a remote controller. Only If the unit was already being operated before power off, the unit
restarts automatically as soon as power is back.
JR06Auto restart
AvailableNot effective
Not availableEffective
@ Short all the CN2 on the indoor board.
Unit can not be start/ stop using remote controller.
Unit will restart automatically whether the unit is
operated or stopped when the power is cut off.
1
2CN2
3
ORN
BRN
RED
Optional timer adapter
PAC-SA89TA-E
I.B.
27
Page 28
2-8 Function of jumper wire and dipswitch on indoor controller board
1. Jumper wire
...
1 JR1
Jumper wire for the auto vanes.
Cut JR01 for the unit WITHOUT auto vanes.
...
2 JR2
Jumper wire for the temperature to start coil frost prevention
Cutting JR02 changes the temperature from +1°C to -3°C.
...
3 JR3
Jumper wire for set temperature adjustment in HEAT mode.
In HEAT operation, heated air stagnates in the upper part of the room. The indoor unit installed in the upper part of the
room will detect the air temperature higher than the actual temperature in the living space. This difference is about 4
degrees. Therefore, the temperature detected by the room temperature thermistor should be corrected 4 degrees down.
The unit with JR04 attached will make this adjustment.
...
4 JR4
Jumper wire for the indoor fan speed during thermostat OFF in HEAT mode
Cutting JR04 changes the speed from Extra-Low to Low.
...
5 JR5
Jumper wire for detecting abnormalities in the outdoor unit
Cutting JR05 makes this detection unavailable. (Occurrence of abnormality can not be detected. )
...
6 JR6
Jumper wire for auto restart function
Cutting JR06 makes the auto restart function available.
2. Dipswitch
1 SW1 (Function switch)
ON
OFF
1 2 3 4 5 6 7 8
SW1-1) Switch for power supply
ON : 220VOFF : 230V, 240V
SW1-2) Switch for single or twin control
ON : Twin controlOFF : Single control
SW1-3) Switch for unit number in twin control
(This switch is valid when SW1-2 is ON. )
ON : Unit No. 2OFF : Unit No. 1
SW1-4, SW1-5,SW1-6) Switch for capacity of each model
PC-2GJA1PC-2.5GJA1PC-3GJA1
ON
OFF
4 5 6
ON
OFF
4 5 6
ON
OFF
4 5 6
SW1-7, SW1-8)Pair number of the wiress remote controller
ON
OFF
7 8
0
ON
OFF
1
7 8
ON
OFF
7 8
2
2 SW2 (Unit switch)
SW2-1) Switch for air conditioner with or without electric heater
ON : Unit with electric heater
OFF : Unit without slectric heater (PC-GJ(S)A)
ON
OFF
1 2 3 4 5
SW2-2) Switch for air conditioner with or without heat pump
(Keep this switch OFF for PC-GJ(S)A)
ON : Unit with heat pumpOFF : Unit without heat pump
SW2-3) Switch for function code (Keep this switch OFF for PC-GJ(S)A)
ON : 1OFF : 0
SW2-4) Switch for function code (Keep this switch OFF for PC-GJ(S)A)
ON : 1OFF : 0
SW2-5) Switch for function code (Keep this switch ON for PC-GJ(S)A)
ON : 1OFF : 0
3 SW3 (Emergency operation switch)
Normal operationFor emergency cooling
ON
OFF
1 2 3
1 2 3
ON
OFF
ON
OFF
PC-4GJSA1
ON
OFF
7 8
3
4 5 6
PC-5GJSA1
ON
OFF
4 5 6
PC-6GJSA1
ON
OFF
4 5 6
4 SWA : for ceiling height
...
3
High ceiling
...
2
Standard
...
1
Low ceiling
28
5 SWC : optional filter element
...
STD
Without filter element
...
OP
With filter element
For ceiling height
High ceiling3.5m
Standard2.8m
Low ceiling2.3m
Page 29
10
TROUBLESHOOTING
1. self-diagnostic function
! When trouble occurs during operation, the unit stops and enters the self-diagnostic mode, and displays the trouble loca-
tion with the timer lamps on the remote controller. All the other lamps are OFF.
@ To activate the self-diagnostic function for service, press the UP and DOWN buttons simultaneously for more than two
TIMER
seconds during operation with lamp ON.
# The timer lamps show the latest trouble. Trouble data is memorized until the next trouble occurs, even when the breaker
turns OFF. To clear the memory, press the UP and DOWN buttons simultaneously for more than two seconds during the
test run.
$ All buttons except the POWER ON/OFF button are unavailable during the self-diagnostic mode.
% To release the self-diagnostic mode, press the POWER ON/OFF button.
TIMER
12
TEMP.
▲
w
▲
i
29
▲
w
Unit
Trouble location
Transmission error
in twin control
Outdoor unit
Cause
●Wrong wiring between No. 1
and No. 2 units
●Poor connector contact
●Wrong wiring between
indoor/outdoor units
●Outdoor unit abnormality
detection
●Malfunction of outdoor coil
thermistor
●Reversed phase detected
Measures
●Check dipswitch setting
●Check wiring
●Check wiring
●Check outdoor unit
●Check outdoor coil thermistor
11
10
9
8
7
6
5
4
3
2
1
28
27
26
25
24
23
22
21
20
19
18
Unit
No.1
Unit
No.2
Unit
No.1
Unit
No.2
Unit
No.1
Unit
No.2
Unit
No.1
Unit
No.2
Unit
No.1
Unit
No.2
Room
temperature
thermistor
(RT1)
Indoor coil
thermistor
(RT2)
Drain sensor
(DS)
Drain
overflow
protection
Coil frost
or overheat
prevention
●Poor connector contact
●Thermistor malfunction
●Poor connector contact
●Thermistor malfunction
●Poor connector contact
●Thermistor malfunction
●Drain pump malfunction
●Drain sensor improperly
mounted
●Air passage short cycle
●Air filter clogged
●Indoor fan malfunction
●Check connector
●Check thermistor
➔ No trouble ➔ replace indoor
controller
board.
●Check connector
●Check thermistor
➔ No trouble ➔ replace indoor
controller
board.
●Check connector
●Check thermistor
➔ No trouble ➔ replace indoor
controller
board.
●Check drain pump
●Check drain sensor
➔ No trouble ➔ replace indoor
controller
board.
●Remove blockage
●Check air filter
●Check indoor fan
(Indicates that the unit is in self-diagnostic mode)
29
Page 30
11
slide
intake grill
intake grill
holding knobs
Hinges
Pull out the intake grill
electrical cover
screw(electrical cover)
screw(electrical box)
Slide to the left
beam
clamp
DISASSEMBLY PROCEDURE
PC-3GJA1
OPERATING PROCEDUREPHOTOS&ILLUSTRATIONS
1. Removing the air intake grill
(1) Slide the intake grill holding knobs (at two locations) back-
ward to open the intake grill.
(2) When the intake grill left open, push the stoppers on the
rear hinges (at two locations) to pull out the intake grill.
2. Removing the electrical box
(1) Remove the air intake grill.
(2) Remove the screw from the beam and remove the beam.
(3) Remove the screws from the electrical cover, and remove
the electrical cover.
(4) Disconnectors including CN6V and CN21.
(5) Remove the screws from the electrical box and pull out
the electrical box.
Figure 1
Figure 2
30
<Electrical parts in the electrical box>
Terminal block (for power supply)
Terminal block (for in/outdoor connecting wire)
Operation condenser
Indoor control board
Power Trans
Photo 1
Operation
condenser
Power
trans
Indoor
control
board
Terminal
terminal
block
(in / out conncting)
block
(power supply)
Terminal
block
(remote control)
Page 31
screw
side panel
sliding the panel
to the front
OPERATING PROCEDUREPHOTOS&ILLUSTRATIONS
3. Removing the fan motor
(1) Remove the intake grill.
(2) Disconnect the fan motor connector.
(3) Unscrew screws for removing the motor guard.
(4) Unscrew screws for removing the fan guard.
(5) Remove the screw for removing the motor support at both
left and right side.
(6) Loosen the set screws at the fan motor side of the con-
necting joint.
(7) Slide the fan motor to the left side and pull it out.
4. Removing the sirocco fan
(1) Remove the air intake grill.
(2) Remove 1 beam.
(3) Unscrew screws for removing the motor guard.
(4) Unscrew screws for removing the fan guard.
(5) Remove the lower casing while pressing the stoppers at
upper side of the casing.
(6) Loosen the set screws at the connecting joint.
(7) Remove the sirocco fan and shaft together by sliding the
shaft to the left.
Photo 2
Photo 3
Screws
Motor support
Motor guard
Motor gurd
Motor
Set screws
Connecting joint
Fan guard
(Note)
Make sure that the upper side casing is snaped to the fan
plate securely with catch.
5. Removing the side panel
(1) Remove the air intake grill.
(2) Remove the screw from the side panel, and remove the
side panel by sliding the panel to the front.
Figure 2
Motor
Sirocco fan
Connecting joint
Casing
Bearing
31
Page 32
OPERATING PROCEDUREPHOTOS&ILLUSTRATIONS
6. Removing the vane motor
(1) Remove the air intake.
(2) Remove the left side panel.
(3) Remove the relay connector of vane motor.
(4) Remove the electrical box.
(5) Remove the screws of vane motor, then remove vane
motor.
(Note)
Connect the lead wires and connectors properly and place
them in the proper position so that the wires are not pinched
by other parts.
7. Removing the indoor coil thermistor
(1) Remove the air intake grill.
(2) Remove the right side panel.
(3) Remove the relay connector of the indoor coil thermistor.
(4) Remove the screw, and remove the check panel.
(5) Extract the indoor coil thermistor from the holder.
<Caution for the installation>
There is a possibility for the short circuit when connector gets
wet by water through the thermistor lead wire.
Therefore, lead wire of the indoor coil thermistor should be
traped as shown in the picture.
Photo 4
Relay connector of
the vane motor
Photo 5
Left side
panel
Screw
Check
panel
Screw
Vane motor
Relay connector of
the pipe thermistor
8. Removing the under panel
(1) Remove the air intake grill.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Unscrew the screws of the under panel, then remove the
lower panel.
wWeight of the lower panel : app. 2kg.
Photo 6
Holdindoor coil thermistorTrap
Photo 7
Screw
32
Under panel
Page 33
OPERATING PROCEDUREPHOTOS&ILLUSTRATIONS
9. Removing the drain pan
(1) Remove the air intake grill.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Remove the under panel. Remove the screws of the right
and left side drain pan.
(5) Remove the insiation in center of the drain pan, and after
removing the screw, remove the drain pan.
(Note)
Please aware that there might be drain left in the drain pan
when you remove the drain pan.
10. Removing the guide vane
(1) Remove the intake grill.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Remove the under panel.
(5) Remove the drain pan.
(6) Remove the screw from the guide vane, then remove the
guide vane.
Photo 8
Screw
Photo 9
Drain pan
Screw
(Insulation)
Screw
11. Removing the Auto vane
(1) Remove the intake grill.
(2) Remove the left side panel.
(3) Remove the left side box.
(4) Remove the under panel.
(5) Remove the screw from the auto vane.
(6) Slide the auto vane to the right side and pull the auto vane
out.
Drain pan
Photo 10
Guide vane
Auto vane
Screw
Screw
33
Page 34
OPERATING PROCEDUREPHOTOS&ILLUSTRATIONS
12. Removing the heat exchanger
(1) Remove the air intake grill.
(2) Remove the beam.
(3) Remove the side panel. (right and left)
(4) Disconnect the relay connector.
(5) Remove the under panel.
(6) Remove the drain pan.
(7) Unscrew the screw of the pipe cover, and remove the pipe
cover.
(8) Unscrew the screw of the pipe support, and remove the
pipe support.
(9) Unscrew the screw of the heat exchange, and remove the
heat exchanger.
Remove the heat exchange with care, since this is quite
heavy. Removing work should be done with more than 2
people.
w Weight of heat exchanger : ApR.5.3kg.
Photo 11
Pipe
support
Screws
Pipe cover
Screws
Heat
exchanger
34
Page 35
No.
Part No.Part NameSpecification
PC-2
GJA, GJA
1
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Amount
Q'ty / setPrice
Part numbers that are circled not shown in the figure.
1
2
3
4
5
6
7
8
9
10
11
12
13
FAN MOTOR
MOTOR LEG
PIECE (MOTOR)
CASING
SIROCCO FAN
INDOOR COIL THERMISTOR
DRAIN PAN ASSY
ROOM TEMPERATURE THERMISTOR
HEAT EXCHANGER
DRAIN PLUG
FAN GUARD
FAN GUARD
FAN GUARD
Part numbers that are circled not shown in the figure.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
FAN MOTOR
FAN JOINT
SHAFT (FAN)
SLEEVE BEARING
MOTOR LEG
SIROCCO FAN
SIROCCO FAN
CASING
INDOOR COIL THERMISTOR
ROOM TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
DRAIN PAN ASSY
DRAIN PLUG
BEARING SUPPORT
FAN GUARD
FAN GUARD
FAN GUARD
PIECE (MOTOR)
FAN MOTOR
FAN JOINT
SHAFT
SLEEVE BEARING
MOTOR LEG
SIROCCO FAN
SIROCCO FAN
CASING
INDOOR COIL THERMISTOR
ROOM TEMPERATURE THERMISTOR
HEAT EXCHANGER
DRAIN PAN ASSY
DRAIN PLUG
BEARING SUPPORT
FAN GUARD
FAN GUARD
FAN GUARD
PIECE (MOTOR)
4 • 14
8
17
Q'ty / setPrice
PC-4
GJSA, GJSA
D10B4P90MS1
6
12
Wiring
Remarks
(Drawing No.)
1
Diagram
Symbol
Recommended
Q'ty
Unit
Amount
MF
1
1
1
1
2
1
3
1
1
RT2
RT1
1
1
1
1
1
2
1
1
37
Page 38
No.
Part No.Part NameSpecification
PC-5
GJSA,
GJSA
1
Wiring
Diagram
Symbol
Recommended
Q'ty
Unit
Amount
Q'ty / setPrice
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
FAN MOTOR
FAN JOINT
SHAFT
SLEEVE BEARING
MOTOR LEG
SIROCCO FAN
SIROCCO FAN
SIROCCO FAN
CASING
INDOOR COIL THERMISTOR
ROOM TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
DRAIN PAN ASSY
DRAIN PLUG
BEARING SUPPORT
FAN GUARD
FAN GUARD
FAN GUARD
FAN GUARD
PIECE (MOTOR)
Part numbers that are circled not shown in the figure.
No.
Part No.Part Name
1
R01 17J 661
2
R01 17J 662
3
R01 17J 669
4
R01 17J 676
5
R01 17J 500
6
R01 18J 500
7
R01 17J 691
8
R01 18J 691
9
R01 17J 054
10
R01 17J 651
11
R01 17J 085
12
R01 18J 086
13
R01 29J 223
14
R01 17J 067
15
R01 17J 068
16
R01 17J 002
17
R01 17J 061
18
R01 17J 808
19
R01 17J 809
20
R01 17J 070
21
R01 17J 523
22
R01 17J 072
23
R01 18J 665
24
R01 18J 666
25
R01 17J 668
26
27
28
—
—
—
RIGHT SIDE PANEL
LEFT SIDE PANEL
UNDER PANEL
REAR PANEL
L.L. FILTER
L.L. FILTER
GRILLE ASSY
GRILLE ASSY
GRILLE CATCH
FRONT PANEL
GUIDE VANE ASSY-6R.
GUIDE VANE ASSY-6L.
VANE MOTOR
RIGHT SIDE BOX
LEFT SIDE BOX
AUTO VANE
GRILLE HINGE
RIGHT LEG
LEFT LEG
WIRELESS BOARD CASE
JOINT SOCKET
DRAIN HOSE COVER
SIDE PLATE-R.
SIDE PLATE-L.
SERVICE PANEL
BEAM(GA)
REAR SUPPORT
VANE SUPPORT
Specification
Q'ty / setPrice
PC-2
GJA, GJA
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
1
1
1
1
1
1
1
1
4
1
1
1
1
MV
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
(BG17H464H08)
(BG02H454H04)
(BG02R321G06)
Amount
41
Page 42
STRUCTURAL PARTS
PC-2.5GJA / PC-3GJA
PC-4GJSA
PC-2.5GJA1 / PC-3GJA1
PC-4GJSA1
2
18
1116
1413
12
27
23
4
8
9
6
3
719
26
25
22
15
5
10
24
17
1
42
Page 43
Part numbers that are circled not shown in the figure.
No.
Part No.Part Name
R01 17J 661
1
R01 35J 661
R01 17J 662
2
R01 35J 662
3
R01 17J 500
R01 29J 676
4
R01 35J 676
R01 29J 651
5
R01 36J 651
6
R01 17J 691
7
R01 29J 669
8
R01 17J 061
9
R01 17J 054
R01 17J 067
10
R01 35J 067
R01 17J 068
11
R01 35J 068
12
R01 17J 085
13
R01 18J 086
14
R01 29J 087
R01 29J 002
15
R01 35J 002
R01 29J 223
16
R01 35J 223
17
R01 17J 808
18
R01 17J 809
19
R01 17J 070
20
R01 17J 523
21
R01 17J 072
R01 18J 665
22
R01 35J 665
R01 18J 666
23
R01 35J 666
24
R01 17J 668
25
26
27
—
—
—
—
RIGHT SIDE PANEL
RIGHT SIDE PANEL
LEFT SIDE PANEL
LEFT SIDE PANEL
L.L. FILTER
REAR PANEL
REAR PANEL
FRONT PANEL
FRONT PANEL
GRILLE ASSY
UNDER PANEL
GRILLE HINGE
GRILLE CATCH
RIGHT SIDE BOX
RIGHT SIDE BOX
LEFT SIDE BOX
LEFT SIDE BOX
GUIDE VANE ASSY-6R.
GUIDE VANE ASSY-6L.
GUIDE VANE ASSY-6C.
AUTO VANE
AUTO VANE
VANE MOTOR
VANE MOTOR
RIGHT LEG
LEFT LEG
WIRELESS BOARD CASE
JOINT SOCKET
DRAIN HOSE COVER
SIDE PLATE-R.
SIDE PLATE-R.
SIDE PLATE-L.
SIDE PLATE-L.
SERVICE PANEL
BEAM(GA)
REAR SUPPORT
VANE SUPPORT
VANE SUPPORT
Specification
Q'ty / setPrice
PC-2.5/3
GJA,GJA1
PC-4
GJSA,GJSA1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
1
1
1
1
2
2
1
1
1
1
2
1
4
4
2
1
4
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MV
MV
1
1
1
1
1
2
1
2
1
2
(BG17H464H08)
1
(BG02H454H04)
(BG02R321G06)
2
(BG02R805G04)
Unit
Amount
43
Page 44
STRUCTURAL PARTS
PC-5GJSA/PC-6GJSA
PC-5GJSA1/PC-6GJSA1
18
20
2
25
4
6
8
14
16
12
11
29
17
13
10
24
15
26
19
27
1
28
5
9
7
3
21
44
Page 45
Part numbers that are circled not shown in the figure.
No.
Part No.Part Name
1
R01 35J 661
2
R01 35J 662
3
R01 41J 669
4
R01 41J 676
5
R01 17J 500
6
R01 18J 500
7
R01 17J 691
8
R01 18J 691
9
R01 17J 054
10
R01 41J 651
11
R01 41J 085
12
R01 42J 086
13
R01 43J 087
14
R01 35J 223
15
R01 35J 067
16
R01 35J 068
17
R01 41J 002
18
R01 17J 061
19
R01 17J 808
20
R01 17J 809
21
R01 17J 070
22
R01 17J 523
23
R01 17J 072
24
R01 35J 665
25
R01 35J 666
26
R01 17J 668
27
28
29
—
—
—
RIGHT SIDE PANEL
LEFT SIDE PANEL
UNDER PANEL
REAR PANEL
L.L.FILTER
L.L.FILTER
GRILLE ASSY
GRILLE ASSY
GRILLE CATCH
FRONT PANEL
GUIDE VANE ASSY-5R.
GUIDE VANE ASSY-5L.
GUIDE VANE ASSY-5C.
VANE MOTOR
RIGHT SIDE BOX
LEFT SIDE BOX
AUTO VANE
GRILLE HINGE
RIGHT LEG
LEFT LEG
WIRELESS BOARD CASE
JOINT SOCKET
DRAIN HOSE COVER
SIDE PLATE-R.
SIDE PLATE-L.
SERVICE PANEL
BEAM(GA)
REAR SUPPORT
VANE SUPPORT
Specification
Q'ty / setPrice
PC-5/6
GJSA,GJSA1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recommended
Q'ty
Unit
1
1
1
1
2
1
2
1
6
1
1
1
2
1
MV
1
1
1
6
1
1
1
1
1
1
1
1
3
1
3
(BG17H464H08)
(BG02H454H04)
(BG02R805G04)
Amount
45
Page 46
13
OPTIONAL PARTS
1. REFRIGERANT PIPES
Service Ref. : PC-2GJA1 / PC-2.5GJA1 / PC-3GJA1
Part No.
Pipe length
Pipe size O.D.
Connection method
PAC-15FFS-EPAC-10FFS-EPAC-07FFS-EPAC-05FFS-E
15m10m7m5m
Liquid:{9.52 Gas:{15.88
Indoor unit:Flared Outdoor unit:Flared
Service Ref. : PC-4GJSA
Part No.
Pipe length
Pipe size O.D.
Connection method
Note 1. How to connect refrigerant pipes.
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging.
Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor
units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow.
If piping length exceeds 5m, an additional charge of refrigerant in needed.
Note 2. The following main parts are contained in the optional refrigerant piping kit.
When installing the remote controller at a distance from the air conditioner, use the designated extension cable with
connector.
Part No.
Length
PAC-919ECPAC-918ECPAC-906ECPAC-905EC
15m10m7m5m
50m30m20m12m
46
Page 47
3. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units.
Part No.PAC-805RC
3-1. Dimensions
12
113
23.5
56.3
11
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
117
POWER
ON/OFF
AHEAD
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
MITSUBISHI ELECTRIC
117
3-2. Names and Functions
"ENGAGED" indicator
When this indicator is lit, transmission is in
progress and all switches are inoperative.
DUAL/CENTRAL switch
This change-over switch governs the oper-
ation of the accessory remote controller.
"DUAL"
Instructions from both the accessory
remote controller and the centralized
remote controller are valid. (Priority is
given to the last instruction received.)
"CENTRAL"
ON/OFF switching by the accessory
remote controller is invalidated. Operation
is controlled by the centralized remote controller only.
Initial setting is "DUAL".
LCD Matrix Display
This display indicates the operational sta-
tus of all connected units either by steady
lighting or by flashing.
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
POWER
ON/OFF
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
MITSUBISHI ELECTRIC
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER
ON/OFF
AHEAD
AHEAD
8
113
POWER ON/OFF switch
Operation ON/OFF switch.
▲BACK ▼AHEAD buttons
These buttons are used to designate
the attached unit(s). (They designate
the unit to be centrally controlled.)
●When group “00” is designated; collective ON/OFF instruction is sent to all
units.
●When group “01”-“16“ is designated;
ON/OFF instruction is sent to the designated units.
ACTIVE/BYPASS switch
This change-over switch for the program timer.
Use “ACTIVE” when a program timer is
connected.
Use “BYPASS” when a program timer
is not connected.
Independent “DUAL / CENTRAL” and “ACTIVE / BYPASS” setting of all the groups is possible. When the power supply to the
centralized remote controller is cut, due to power failure, all settings will return to original “DUAL” and “BYPASS”.
47
Page 48
A N E
T
(Y)
(W)(R) (O)
(BR)
5A
A
POWER
SUPPLY
N
E
Fuse(5A)
Tie-lap
Wiring has to be changed when
a 200,230 or 240V power is used.
Tie-lap
TRANSFORMER
Transmission
TERMINAL-BLOCK
FOR TRANSMISSION
TERMINAL-BLOCK
OF POWER SUPPLY
200
220
230
240
BACK
ACTIVE
BYPASS
POWER
ON/OFF
DUAL
CENTRAL
AHEAD
ENGAGED
GROUP
ACTIVE BYPASS
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
DUAL CENTRAL
12345678910
10 9 8 7 6 5 4 3 2 1
To adaptor's
terminal-block
Centralized remote
controller
Non-polar,
two-wire cable
To adaptor's
terminal-block
Power supply board box
BACK
ACTIVE
BYPASS
POWER
ON/OFF
DUAL
CENTRAL
AHEAD
ENGAGED
GROUP
ACTIVE BYPASS
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
DUAL CENTRAL
12345678910
10 9 8 7 6 5 4 3 2 1
Dip switch
SW17
Centralized
remote controller
Power supply
board
3-3 Connection method
(1) Connections in the power supply cord.
1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-lap.
Connect a single phase 200V AV (220, 230, 240V) to .
As is the GND terminal, be sure to ground the earth wire.
E
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-lap.
Use a Ω1.6 (AWG 14) or above two-wire cable for the transmission line.CAUTION : Never connect the power supply cord to the transmission terminal-block.
A N
(2) Connection method of centralized remote controller and power supply board.
1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable.
2. Wiring diagram3. Set the maximum address number with the dipswitch
SW17 on the centralized remote controller.
48
Page 49
Adaptor
200~240V AC
3-core cable 5-core cable
52
To program timer or
centralized remote
controller
Fig.3
CN30 CN50
CN51
Remote controller Indoor unit
Max. length of each calbe is 10m.
65
230
22
1515
8670
35
27
3holes
15
hole
408040 27
18
4Fixing screw holes
5.5
95
220
22
35
120
12
30
200
2 2holes 2.9
74
7
8
Fig. 4
(Unit : mm)
10
ORN1
2
3
BRN
RED
4. Set the address number (from SW1-1 to SW1-6) in
the dipswitch when a centralized remote controller is
being used.
The address is the control number of each unit in the
centralized control system.
As the address serves as a time-delay device as
well, sequential starts (all units are triggered collectively by one single ON instruction)must be set with
different address numbers (greater than 0) for each
9 8 7 6 5 4 3 2 1
ON
SW1
Levers No. 1-6 can set the following addresses respectively
with binary notations.
Toggle32No.6 ON16No.5 ON8No.4 ON4No.3 ON2No.2 ON1No.1 ON
Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out the work.
(1) Connections in the adapter box
1. Connect the power supply cord to the terminal-block and fix it in-place with a tie-lap.
Connect a single phase 200V (220, 230, 240V) AV to .
As is the GND terminal, be sure to ground the earth wire.
E
A N
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-lap (when a
centralized remote controller is being used.
CAUTION : Never connect the power supply cord to the transmission terminal-block
Fig-1Fig-2
TERMINAL-BLOCK
FOR
TRANSMISSION
Tie-lap
Transmission cord
CN22
Dip switch
TRANS
CN1 CN21 CN51 CN30 CN42 CN50CN40
Fuse(5A)
TRANSFORMER
(AG)
SW1
A N E
POWER SUPPLY CORD
TERMINAL-BLOCK
FOR POWER
SUPPLY
Tie-lap
Wiring has to be changed when 200V power supply is used.
Transmission
(W)
CN22
TRANS
(B)
200
SW1
T
(Y)
240
220
5A
A
POWER
SUPPLY
N
E
50
Page 51
6.REMOTE INDICATION ADAPTER
Motor
Casing
(Inverted corn shape)
Drain water
Suction port
Flow of drain water
Rotating blabe
(Inverted triangle plate)
This adapter is used for remote indication (operation / check).
Part No.PAC-559AD
BRN
RED
7.DRAIN PUMP
Applied Service Ref.
Part No.
<Wiring>
CN51
connector (5P)
BRN
RED
ORN
YLW
GRN
JST
XHP-3
5
1
Optional multiple display
adapter
The maximum distance between
indoor board and relay is 10m.
GREEN
YELLOW
ORANGE
RED
BROWN
X1
X2
Electrical insulation is needed.
Wiring at the actual place
PC-2/2.5/3GJA1
PAC-SE85DM-E
ORN
YLW
5
5
2
X1
X2
GRN
RL
GL
Power
supply
PC-4/5/6GJSA(1)
PAC-SE86DM-E
8.HIGH PERFORMANCE FILTER
9.WIRELESS KIT
Part No.PAC-SE80KF-E
Applicable Service Ref.PC-2GJA
Part No.PAC-SW93J-E
PAC-SE80KF-E
1
PC-2.5/3/4GJ(S)A
1
PAC-SE82KF-E
PC-5 / 6GJSA
51
Page 52
HEAD OFFICE : MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI,CHIYODA-KU TOKYO 100-8310, JAPAN
cCopyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Reprinted in Sep. 2003 No.OC134 REVISED EDITION-A 20
Reprinted in Apr. 2003 No.OC134 REVISED EDITION-A 100
Reprinted in May 2001 No.OC134 REVISED EDITION-A 5
Issued in Nov. 1999 No.OC134 REVISED EDITION-A 300
Issued in Mar. 1999 No.OC134 REVISED EDITION-A 50
Issued in Sep. 1998 No.OC134 REVISED EDITION-A 200
Issued in Sep. 1998 No.OC134 REVISED EDITION-A 50
Issued in Sep. 1997 No.OC134 REVISED EDITION-A 2420
Issued in Jun. 1997 No.OC134 2420
Made in Japan
New publication, effective Nov. 1999
Specifications subject to change without notice
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.