Mitsubishi PC-2GJA1, PC-2.5GJA1, PC-3GJA1, PC-4GJSA1, PC-5GJSA1 Service Manual

...
Page 1
SPLIT-TYPE, COOLING AIR CONDITIONERS
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER
MODE
DRY FAN
HIGH LOW
ON AUTO
STOP START
TECHNICAL & SERVICE MANUAL
No. OC134
REVISED EDITION-A
Series PC
Indoor unit [
Model names]
PC-2GJA PC-2.5GJA PC-3GJA PC-4GJSA PC-5GJSA PC-6GJSA
INDOOR UNIT
Ceiling Suspended
[Service Ref.]
PC-2GJA1 PC-2.5GJA1 PC-3GJA1 PC-4GJSA1 PC-5GJSA1 PC-6GJSA1
This manual does not cover the following outdoor units. When serving them, please refer to the service manual No.OC127(REVISED EDITION-A) .
[Service Ref.] PU-2VJA2 PU-2NJA1 PU-2.5VJA2 PU-2.5NJA1
PU-5YJSA PU-5TJSA PU-6YJSA
PU-6TJSA
PU-3NJA1 PU-3YJA3 PU-3VJA2 PU-4TJSA2 PU-4VLJSA2 PU-4YJSA3
CONTENTS
1. FEATURES ···········································2
2. PART NAMES AND FUNCTIONS········4
3. SPECIFICATIONS ·································6
4. DATA·····················································9
5. OUTLINES AND DIMENSIONS··········12
6. WIRING DIAGRAM ·····························17
REFRIGERANT SYSTEM DIAGRAM
8. OPERATION FLOW-CHART··············20
9. MICROPROCESSOR CONTROL·······23
10. TROUBLE SHOOTING·······················29
11. DISASSEMBLY PROCEDURE···········30
12. PARTS LIST········································35
13. OPTIONAL PARTS ·····························46
······18
Revision:
PC-5GJSA1,PC-6GJSA1
are added.
The first edition has been par-
tially modified.
Please destroy OC134.
REMOTE CONTROLLER
Page 2
1
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
ON AUTO
STOP START
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
ON AUTO
STOP START
FEATURES
Series PC
Ceiling Suspended
Indoor unit
Service Ref. PC-2GJA
1 5,600/5,400 19,100/18,400
Cooling Capacity (50 / 60Hz)
W Btu/h
PC-2.5GJA1 6,500/7,000 22,200/23,900 PC-3GJA1 7,200/7,800 24,600/26,600 PC-4GJSA1 9,800/10,800 33,400/36,800 PC-5GJSA1 12,400/13,500 42,300/46,100 PC-6GJSA1 14,600/15,200 49,800/51,900
Note: Rating condition
Indoor : 27°C D.B., 19°C W.B. Outdoor : 35°C D.B., 24°C W.B.
Remote controller
1. ADVANCED REMOTE CONTROLLER
(1) Ultra-thin 12mm (1/2”) remote controller
The streamelined, square controller is designed to blend with any inte­rior. Also, the sophisticated microprocessor allows you to easily carry out a wide range of operations.
(2) Attractive LED display
Every operation condition is indicated on the LED display.
(3) Simultaneous display of set temperature and room temperature
The set temperature is indicated by continuous light and the room tem­perature is indicated by a flashing light. In this way, accurate tempera­ture conditions are always available at a glance and fine temperature regulation is possible.
(4) Convenient 12-hour ON-OFF timer
The timer switches on and off automatically at the times you set. Once the timer is set, the remaining time is shown on the LED display.
(5) Self-diagnostic feature indicates faults instantly
If a problem occurs, the unit will stop operating and the temperature display will change to a self-diagnosis indicator, which shows the loca­tion of the trouble.
(6) Useful memory feature for storing instructions
The previous set value is memorized so that constant temperature control can be achived. For example, if a power fail­ure occurs, the temperature will not have to be readjusted afterwards.
(7) Cables between remote controller and indoor unit
The polar, 12-core type remote controller cables makes installation simple and troublefree. Also, the cables can be extended up to 50m. (optional)
2
Page 3
1. AIR OUTLET
New PC series models have 1 air outlet (auto vane switching of horizontal air flow / down flow by switched by auto vane) instead of 2 (horizontal, and down flows).
2. EASY TO CLEAN ; FLOCKLESS VANE
With our original air current control mechanism, a flockless vane is newly adapted. The flockless vane prevents the condensation on the vane. By changing the vane to the flockless type, the unit can be cleaned much easier with mild household detergent.
B
Flockless vane
A
Air outlet
Protruding portion A
Unifies the air speed with the vane.
Protruding portion B
Sending the air to the upper area of the vane
Prevents the air comes from outside the unit
+
=
3. NEW MATERIALS FOR BETTER OIL RESISTANCE
We have changed the materials of grill, filer, fan and fan casing from ABS to P.P. (polypropylene) for better oil resistance. As a result, oil crazing is cut in half.
4. SIMPLIFIED INSTALLATION WORK (DIRECT SUSPENDING METHOD)
Simplified the installation work by changing the suspending method to the direct suspending method (suspending the unit directly from the suspension fixture). In this way, the unit can be attached to the suspension fixture without removing the installation parts off (Only the side cover is removed). This method is much simpler than the ¨One-time installation method¨.
5. IMPROVING EFFICIENCY OF PIPING WORK
New PC series models have 1 air outlet (auto vane switching of horizontal air flow / down flow by switched by auto vane) instead of 2 (horizontal, and down flows).
1 Removed the knockout work by separating the piping space
from the air outlet for efficiency of the piping work.
Side panel
L
G
G D
Open
L : Liquid pipe G: Gas pipe D: Drain pipe
U-cut
Back panel
L
D
Open
w Knockout work is needed for the top part. When optional
drain-up machine is installed, the refrigerant pipe exits out from the top.
2 Improved the flexibility by making it possible for drainage
pipe to exit not only from the right side back but also from the left side back.
Rubber plug
Insulation cover (attached)
Drain pipe (purchased locally)
Joint coupliy (attached)
Drain pan
Insulation cover
Band (attached)
w Please move the rubber plug for the unit to the right joint
when drainage pipe exits from the left side.
3
Page 4
Air outlet
Intake grille
Air intake
Left/right guide vanes
Change the direction of airflow from the horizontal blower.
Long-life filter
Removes dust and foreigh matter from air coming in through the grille (Recommended cleaning interval : Approx, every 2,500 operating hours)
Up/down guide vanes
Change the direction of airflow from the vartical blower.
6. QUITENESS ; 43dB : PC-3GJA1(HIGH NOTCH)
Auto vane
Swing
Quiteness of the New PC series product is significant. It is because we have adapted the new shape air outlet and changed the air coures.
7. EASY MAINTENANCE ; NO MAINTENANCE NECESSARY FOR 2500 HOURS
The new long-life air filter can be used continuously 2500 hours without maintenance (at general office situation).
8. CHOICE OF FILTER
High performance filter can be purchased optionally for the special needs.
Locations Appropriate filter Capability Filter Maintenance How to attach to the unit
Busy shops etc···
Regular office, shops
High performance filter
Standard longlife filter
Weighing
method 70%
Weighing
method 30%
2500 hours
2500 hours
The filter can be used again after cleaning.
The filter can be used again after cleaning.
Remove the standard long life filter before attach this optional parts.
It is already attached to the unit
2
PART NAMES AND FUNCTION
Indoor (Main) Unit
4
Page 5
Remote controller
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
ON AUTO
STOP START
TIMER / TEMP.
This button is used to change between display of room tem­peratue and display of remain­ing timer time durining “AUTO STOP” operation. Green lamps light in selected display mode.
Settings remain in effect until changed. Air conditioner can be operated by simply pushing ON/OFF button once settings have been made.
Display Panel Operating panel
ON / OFF button
Pushing button starts operation. Pushing again stops operation. Green lamp remains lit during operation.
MODE SELECT button
This button is used to change between cooling. ventilation and DRY(or heat­ing)operation modes.One of three green lamps light to indicate mode in effect.
Lamps display remaining timer time or room temper­ature.
Remaining timer time display
Lamps indicate time remaining until timer stops timed operation. Green lamps corresponding to remaining number of hours light.
Room Temperature display
Lamps display temperatue set­ings and actual room tempe­ratues.
Temperatue settings.
Green lamps light.
Temperatue in room.
Green lamps flash.
(Example display readings are for explanations only; actual dis­play readings will differ.)
Attention:
Pushing UP and DOWN buttons together for more than two seconds will initate “trial run” or “inspection” mode. Avoid pushing these buttons simultaneously during normal operation. Push ON / OFF button to cancel trial run or inspection mode if initiated by accident. All green lamps turn off when air conditioner is stopped. Avoid operation of buttons with fingernails or other sharp object. Sharp object may scratch operating panel.
*Heating operation mode is only available for models with built-in electric heater.
UP and DOWN buttons
Temperature control (While ”TEMP” green lamp is lit.) Use UP and DOWN buttons to set desired temper­ature between 18 and 29
o
C. Timed operation (While green “TIMER” lamp is lit.) Use UP and DOWN buttons to set timed operation between one and twelve hours.
FAN SPEED button
This button is used to change between low and high fan speeds. One of two green lamps lights to indicade fan speed in effect.
Swing Louver Button
Used to automatically disperse airflow vertically. Air is blown in one direction when louver is not turning. Lamp lights effect.
TIMER MODE button
Used for selecting timed starting or stopping.Green lamp light to indicate timer mode selected.
5
Page 6
3
Service Ref.
External finish Fan motor output
Airflow Lo-Hi
External static pressure Operation control & Thermostat
Noise level Low-High Cond. drain connector
Dimensions
Weight
Service Ref.
External finish Refrigerant (R-22) control Crankcase Heater w3 Compressor output Protection devices Fan motor output
Airflow Noise level
Dimensions
Weight
W
Btu/h
W
Btu/h
W
Btu/h
m/min
CFM
m/min
CFM
Pa(mmAq)
dB(A)
dB(A) mm(in.) mm(in.) mm(in.) mm(in.) kg(lbs.)
W
kW
kW
K/min(CFM) K/min(CFM)
dB(A) mm(in.) mm(in.) mm(in.) kg(lbs.)
50Hz
60Hz
60Hz
50Hz
60Hz
50Hz 60Hz
O.D.
W
D H
50/60Hz 50/60Hz
50Hz 60Hz
50/60Hz
W
D H
Munsell 0.70Y 8.59/0.97
0 (Direct blow)
Remote control & Built-in
Munsell 5Y 7/1
Capillary tube
295+24 (11-5/8 add 1)
9,800 33,400 10,800 36,800
9,300 31,700
3.49/4.47
PC-4GJSA
1
0.09
20-25
706-883
20-25
706-883
40-45
40-45
26 (1)
1310 (51-9/16)
680 (26-3/4) 270 (10-5/8)
37 (82)
w10 PU-4JSA-type
32/38
2.7/2.7
w7(V)/w6(Y,T)
0.065+0.065 95 (3352) 95 (3352)
54/55
870 (34-1/4)
1258 (49-1/2)
94 (207)
Cooling capacity w1
Cooling capacity w4 Total input (50/60Hz) w2
Item
Service Ref.
PC-4GJSA
1
7,200
24,600
7,800
26,600
6,500
22,200
3.30/3.60
PC-3GJA
1
0.07
14-18
494-635
14-18
494-635
37-43 37-43 26 (1)
1310 (51-9/16)
680 (26-3/4)
210 (8-1/4)
34 (75)
w9 PU-3JA-type
32/38
2.2/2.2 w5
0.085 50 (1765) 50 (1765)
52/53
870 (34-1/4)
850 (33-7/16)
73 (161)
PC-3GJA
1
6,500
22,200
7,000
23,900
6,200
21,200
2.58/3.07
PC-2.5GJA
1
0.07
14-18
494-635
14-18
494-635
37-43 37-43 26 (1)
1310 (51-9/16)
680 (26-3/4)
210 (8-1/4)
34 (75)
PU-2.5VJA2,PU-2.5NJA1
32/-
2.0/1.7 w5
0.085 50 (1765) 50 (1765)
52/53
870 (34-1/4)
850 (33-7/16)
71 (157)
PC-2.5GJA
1
5,600
19,100
5,400
18,400
4,300
14,700
2.54/2.60
PC-2GJA
1
0.054
10-13
353-459
10-13
353-459
37-42 37-42 26 (1)
1000 (39-3/8)
680 (26-3/4)
210 (8-1/4)
27 (60)
PU-2VJA2,PU-2NJA1
32/-
2.0/1.5 w5
0.065 45 (1588) 45 (1588)
49/50
870 (34-1/4)
650 (25-5/8)
60 (132)
PC-2GJA
1
Indoor unitOutdoor unit
SPECIFICATIONS
1. STANDARD SPECIFICATIONS
Notes : w1. Rating condition (JISB8616)
Indoor : 27
Models PC-2,2.5,3 PC-4,5,6
50Hz 1ph220V / 1ph220V 1ph220V / 3ph380V 60Hz 1ph220V / 1ph220V
Outdoor : 35OC (95OF) D.B., 24OC (75OF) W.B. Refrigerant piping length (one way) : 5m (16ft)
w2. Total input based indicated voltage (In/Out)
Rating conditions (JISB8616)
w3. The capacity of crankcase heater (W)
O
C (80OF) D.B., 19OC (66OF) W.B.
1ph220V / 3ph220V
6
w4. Rating condition (SSA385, 386)
w5. Inner thermostart, HP switch, LP switch w6. Thermal switch, Reversed-phase protector, HP switch, LP
w7. Thermal switch, HP switch, LP switch, w8. Thermal switch, HP switch,Inner thermostat
w9. PU-3JA w10. PU-4JSA-type···PU-4VLJSA2, PU-4YJSA3, PU-4TJSA2
Indoor : 29OC (84OF) D.B., 19OC (66OF) W.B. Outdoor : 46OC (115OF) D.B., 24OC (75OF) W.B. Refrigerant piping lenght (one way ) : 5m (16ft)
switch Thermal relay
Inner thermostat
-type···PU-3VJA2, PU-3YJA3, PU-3NJA1,
Page 7
Item
220,230,240V 380/220, 400/230, 415/240V 220V 220V
1ph. 3ph. 1ph. 3ph.
50Hz
60Hz
Power supply
Outdoor unit Service Ref.
PC-4GJSA1
PU-4VLJSA2
PU-4YJSA3
PU-4TJSA
2
PC-5GJSA1
PU-5YJSA
PU-5TJSA
PC-6GJSA
1
PU-6YJSA
PU-6TJSA
PC-3GJA
1
PU-3VJA2 PU-3YJA3 PU-3NJA1
PC-2.5GJA
1
PU-2.5VJA2
PU-2.5NJA
1
PC-2GJA
1
PU-2VJA2
PU-2NJA
1
Indoor unit Service Ref.
Cooling capacity w1
Cooling capacity w4 Total input (50/60Hz) w2
Service Ref.
External finish Fan motor output
Airflow Lo-Hi
External static pressure Operation control & Thermostat
Indoor unitOutdoor unit
Noise level Low-High Cond. drain connector
Dimensions
Weight
Service Ref.
External finish Refrigerant (R-22) control Crankcase Heater w3 Compressor output Protection devices Fan motor output
Airflow Noise level
Dimensions
Weight
Service Ref.
50Hz
60Hz
60Hz
50Hz
60Hz
50Hz 60Hz
O.D.
W
D H
50/60Hz 50/60Hz
50Hz 60Hz
50/60Hz
W
D H
W
Btu/h
W
Btu/h
W
Btu/h
K/min
CFM
K/min
CFM
Pa(mmAq)
dB(A)
dB(A) mm(in.) mm(in.) mm(in.) mm(in.) kg(lbs.)
W
kW
kW
K/min(CFM) K/min(CFM)
dB(A) mm(in.) mm(in.) mm(in.) kg(lbs.)
PC-5GJSA
1
12,400 42,300 13,500 46,100 11,600 39,600
4.76/5.89
PC-5GJSA
1
Munsell 0.70Y 8.59/0.97
0.15
27-34
953-1,200
27-34
953-1,200
Remote control & Built-in 41-46 41-46
26(1)
1,620(63-3/4)
680(26-3/4) 270(10-5/8)
43(95)
PU-5YJSA,PU-5TJSA
3.5 w8
0.10+0.10 100(3530) 100(3530)
55
970(38-3/16)
345+24(13-9/16+1)
1,258(49-1/2)
114
0 (Direct blow)
Munsell 5Y 7/1
Capillary tube
PC-6GJSA
1
14,600 49,800 15,200 51,900 13,400 45,700
5.31/6.41
PC-6GJSA
1
0.15
27-34
953-1,200
27-34
953-1,200
42-48 42-48
26(1)
1,620(63-3/4)
680(26-3/4) 270(10-5/8)
45(99)
PU-6YJSA,PU-6TJSA
4.2/4.0 w8
0.10+0.10 100(3530) 100(3530)
56
970(38-3/16)
345+24(13-9/16+1)
1,258(49-1/2)
117
2. POWER SUPPLY & MODEL NAMES
Notes : 1. Power supply key N : 1ph, 220V/60Hz T : 3ph, 220V/60Hz
V(L) : 1ph, 220, 230, 240V/50Hz Y : 3ph, 380/220, 400/230, 415/240V, 50Hz, 4wires
2. Primary power supplies for all indoor units are single-phase.
7
Page 8
3. ELECTRICAL SPECIFICATIONS
A
kW
A
V : 220V , 50Hz
PC-4GJSA1
0.68
0.14
1.36
PU-4
Power supply (1 Phase)
Service Ref.
Current Input Starting current Outdoor unit to be connected
PC-3GJA
1
0.51
0.12
1.17
PU-3
PC-2.5GJA1
0.51
0.12
1.17
PU-2.5
PC-2GJA
1
0.38
0.10
1.10
PU-2
PC-6GJSA1
0.96
0.20
2.00
PU-6
PC-5GJSA1
0.96
0.20
2.00
PU-5
A
kW
A
V : 230V , 50Hz
PC-4GJSA1
0.69
0.15
1.42
PU-4
Power supply (1 Phase)
Service Ref.
Current Input Starting current Outdoor unit to be connected
PC-3GJA
1
0.53
0.13
1.22
PU-3
PC-2.5GJA1
0.53
0.13
1.22
PU-2.5
PC-2GJA
1
0.41
0.12
1.15
PU-2
PC-6GJSA1
1.01
0.22
2.10
PU-6
PC-5GJSA1
1.01
0.22
2.10
PU-5
A
kW
A
V : 240V , 50Hz
PC-4GJSA1
0.70
0.16
1.48
PU-4
Power supply (1 Phase)
Service Ref.
Current Input Starting current Outdoor unit to be connected
PC-3GJA
1
0.55
0.15
1.27
PU-3
PC-2.5GJA1
0.55
0.15
1.27
PU-2.5
PC-2GJA
1
0.43
0.14
1.20
PU-2
PC-6GJSA1
1.06
0.25
2.20
PU-6
PC-5GJSA1
1.06
0.25
2.20
PU-5
A
kW
A
N : 220V , 60Hz
PC-4GJSA1
0.95
0.20
1.27
PU-4
Power supply (1 Phase)
Service Ref.
Current Input Starting current Outdoor unit to be connected
PC-3GJA
1
0.70
0.16
1.11
PU-3
PC-2.5GJA1
0.70
0.16
1.11
PU-2.5
PC-2GJA
1
0.61
0.15
1.03
PU-2
PC-6GJSA1
1.20
0.26
1.91
PU-6
PC-5GJSA1
1.20
0.26
1.91
PU-5
A
kW
A
N : 220V , 60Hz
PC-4GJSA1
0.95
0.20
1.27
PU-4
PC-5GJSA1
1.20
0.26
1.91
PU-5
PC-6GJSA1
1.20
0.26
1.91
PU-6
Power supply (1 Phase)
Service Ref.
Current Input Starting current Outdoor unit to be connected
PC-3GJA
1
0.70
0.16
1.11
PU-3
PC-2.5GJA1
0.70
0.16
1.11
PU-2.5
PC-2GJA
1
0.61
0.15
1.03
PU-2
Rating conditions — JIS B8616 Indoor : 27°C (80°F) D.B., 19°C (66°F) W.B.
Outdoor : 35°C (95°F) D.B., 24°C(75°F) W.B.
Serises PC Indoor unit (Single phase)
Rating conditions — SSA385, 386
8
Indoor : 29°C (84°F) D.B., 19°C (66°F) W.B. Outdoor : 46°C (115°F) D.B., 24°C(75°F) W.B.
Page 9
4
0.84
0.85
0.86
0.86
0.87
0.89
0.96
0.99
1.00
1.00
1.01
1.04
1.04
1.06
1.08
1.08
1.09
1.12
1.11
1.14
1.15
1.16
1.17
1.21
1.19
1.22
1.24
1.25
1.26
1.31
0.90
0.92
0.93
0.93
0.94
0.96
0.81
0.82
0.83
0.83
0.84
0.86
0.93
0.95
0.96
0.97
0.97
0.99
1.03
1.06
1.07
1.08
1.08
1.11
1.10
1.12
1.14
1.15
1.16
1.20
1.16
1.19
1.21
1.22
1.23
1.28
C.F. (T.I.)
Service Ref.
Temperature
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
PC-2GJA1
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
5.5
5.9
6.0
6.1
6.2
6.6
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
5.1
5.4
5.6
5.7
5.8
6.2
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
4.8
5.2
5.3
5.4
5.5
5.9
4.6
4.9
5.1
5.1
5.2
5.6
4.3
4.6
4.7
4.8
4.9
5.3
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
5.3
5.6
5.8
5.9
6.0
6.4
21°C
(69.8°F)
25°C
(77°F)
30°C
(86°F)
32.2°C (90°F)
35°C
(95°F)
40°C
(104°F)
40.6°C
(105°F)
45°C
(113°F)
46°C
(115°F)
50°C
(69.8°F)
52°C
(125.5°F)
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
5.6
6.0
6.2
6.2
6.4
6.7
5.2
5.5
5.7
5.8
5.9
6.3
4.9
5.2
5.4
5.4
5.5
5.9
4.6
4.9
5.1
5.2
5.3
5.7
4.4
4.7
4.9
4.9
5.0
5.4
Indoor W.B.Outdoor D.B.
T.C.
0.84
0.85
0.86
0.86
0.87
0.89
0.96
0.99
1.00
1.00
1.01
1.04
1.04
1.06
1.08
1.08
1.09
1.12
1.11
1.14
1.15
1.16
1.17
1.21
1.19
1.22
1.24
1.25
1.26
1.31
0.90
0.92
0.93
0.93
0.94
0.96
0.81
0.82
0.83
0.83
0.84
0.86
0.93
0.95
0.96
0.97
0.97
0.99
1.03
1.06
1.07
1.08
1.08
1.11
1.10
1.12
1.14
1.15
1.16
1.20
1.16
1.19
1.21
1.22
1.23
1.28
C.F.
(T.I.)
PC-2.5GJA
1
6.4
6.8
7.0
7.1
7.2
7.7
5.9
6.3
6.5
6.6
6.7
7.2
5.6
6.0
6.2
6.3
6.4
6.8
5.3
5.7
5.9
6.0
6.1
6.5
4.9
5.3
5.5
5.6
5.7
6.1
6.1
6.6
6.8
6.9
7.0
7.4
6.5
6.9
7.2
7.3
7.4
7.8
6.0
6.4
6.6
6.7
6.9
7.3
5.6
6.0
6.2
6.3
6.4
6.9
5.4
5.7
5.9
6.0
6.1
6.6
5.1
5.4
5.6
5.7
5.8
6.3
T.C.
0.84
0.85
0.86
0.86
0.87
0.89
0.96
0.99
1.00
1.00
1.01
1.04
1.04
1.06
1.08
1.08
1.09
1.12
1.11
1.14
1.15
1.16
1.17
1.21
1.19
1.22
1.24
1.25
1.26
1.31
0.90
0.92
0.93
0.93
0.94
0.96
0.81
0.82
0.83
0.83
0.84
0.86
0.93
0.95
0.96
0.97
0.97
0.99
1.03
1.06
1.07
1.08
1.08
1.11
1.10
1.12
1.14
1.15
1.16
1.20
1.16
1.19
1.21
1.22
1.23
1.28
C.F.
(T.I.)
PC-3GJA
1
7.1
7.5
7.8
7.9
8.0
8.5
6.5
7.0
7.2
7.3
7.4
7.9
6.2
6.6
6.9
6.9
7.1
7.6
5.9
6.3
6.5
6.6
6.7
7.2
5.5
5.9
6.1
6.2
6.3
6.8
6.8
7.3
7.5
7.6
7.7
8.2
7.2
7.7
7.9
8.0
8.2
8.7
6.7
7.1
7.4
7.5
7.6
8.1
6.2
6.7
6.9
7.0
7.1
7.6
5.9
6.4
6.6
6.7
6.8
7.3
5.6
6.0
6.2
6.3
6.5
6.9
T.C.
0.84
0.85
0.86
0.86
0.87
0.89
0.96
0.99
1.00
1.00
1.01
1.04
1.04
1.06
1.08
1.08
1.09
1.12
1.11
1.14
1.15
1.16
1.17
1.21
1.19
1.22
1.24
1.25
1.26
1.31
0.90
0.92
0.93
0.93
0.94
0.96
0.81
0.82
0.83
0.83
0.84
0.86
0.93
0.95
0.96
0.97
0.97
0.99
1.03
1.06
1.07
1.08
1.08
1.11
1.10
1.12
1.14
1.15
1.16
1.20
1.16
1.19
1.21
1.22
1.23
1.28
C.F. (T.I.)
PC-4GJSA
1 PC-5GJSA1 PC-6GJSA1
9.6
10.2
10.6
10.7
10.9
11.6
8.9
9.5
9.8
9.9
10.1
10.8
8.4
9.0
9.3
9.5
9.6
10.3
8.0
8.6
8.9
9.0
9.2
9.8
7.4
8.0
8.3
8.4
8.6
9.2
9.3
9.9
10.2
10.3
10.5
11.2
9.8
10.5
10.8
10.9
11.1
11.8
9.1
9.7
10.0
10.2
10.3
11.0
8.5
9.1
9.4
9.5
9.7
10.3
8.1
8.6
8.9
9.1
9.3
9.9
7.6
8.2
8.5
8.6
8.8
9.4
T.C.
0.84
0.85
0.86
0.86
0.87
0.89
0.96
0.99
1.00
1.00
1.01
1.04
1.04
1.06
1.08
1.08
1.09
1.12
1.11
1.14
1.15
1.16
1.17
1.21
1.19
1.22
1.24
1.25
1.26
1.31
0.90
0.92
0.93
0.93
0.94
0.96
0.81
0.82
0.83
0.83
0.84
0.86
0.93
0.95
0.96
0.97
0.97
0.99
1.03
1.06
1.07
1.08
1.08
1.11
1.10
1.12
1.14
1.15
1.16
1.20
1.16
1.19
1.21
1.22
1.23
1.28
C.F. (T.I.)
12.2
13.0
13.4
13.6
13.8
14.7
11.2
12.0
12.4
12.6
12.8
13.6
10.7
11.4
11.8
12.0
12.2
13.0
10.1
10.8
11.2
11.3
11.5
12.4
8.1
8.7
9.0
9.1
9.3
9.7
11.7
12.5
12.9
13.1
13.3
14.2
12.4
13.3
13.7
13.8
14.1
14.9
11.5
12.3
12.7
12.8
13.1
13.9
10.7
11.5
11.9
12.0
12.3
13.1
10.2
10.9
11.3
11.5
11.7
12.5
9.1
9.8
10.2
10.3
10.5
10.9
T.C.
0.84
0.85
0.86
0.86
0.87
0.89
0.96
0.99
1.00
1.00
1.01
1.04
1.04
1.06
1.08
1.08
1.09
1.12
1.11
1.14
1.15
1.16
1.17
1.21
1.19
1.22
1.24
1.25
1.26
1.31
0.90
0.92
0.93
0.93
0.94
0.96
0.81
0.82
0.83
0.83
0.84
0.86
0.93
0.95
0.96
0.97
0.97
0.99
1.03
1.06
1.07
1.08
1.08
1.11
1.10
1.12
1.14
1.15
1.16
1.20
1.16
1.19
1.21
1.22
1.23
1.28
C.F.
(T.I.)
14.3
15.3
15.8
16.0
16.3
17.3
13.2
14.1
14.6
14.8
15.1
16.1
12.6
13.4
13.9
14.1
14.4
15.3
11.9
12.7
13.1
13.3
13.5
14.6
9.5
10.2
10.6
10.7
11.0
11.4
13.8
14.7
15.2
15.4
15.7
16.7
14.7
15.6
16.1
16.3
16.6
17.6
13.6
14.5
14.9
15.1
15.4
16.4
12.6
13.5
14.0
14.2
14.4
15.4
12.0
12.9
13.3
13.5
13.8
14.7
10.7
11.5
12.0
12.1
12.4
12.8
T.C.
DATA
1. PERFORMANCE DATA Cooling capacity
Cooling Capacity Correction Factors
Service Ref.
PC-2GJA PC-2.5GJA PC-3GJA PC-4GJSA PC-5GJSA
PC-6GJSA
5m(16ft) 10m(33ft) 15m(49ft) 20m(66ft) 25m(82ft) 30m(98ft)
1
1
1.0 0.985 0.975 0.964 0.954 0.944
1.0
1
1.0 0.978 0.962 0.948 0.934 0.921
1.0 0.984 0.974 0.964 0.954 0.944
1
1.0
1
1.0
1
50Hz
0.983 0.972 0.961 0.951 0.940
0.978
0.970
0.962
0.950
50Hz
Refrigerant piping length (one way)
0.948
0.931
0.934
0.912
0.921
0.896
35m(115ft)
— —
0.935 0.926
0.908
0.880
40m(131ft)
0.896
0.864
45m(148ft)
0.884
0.850
— —
— —
50m(164ft)
— — — —
0.875
0.840
9
Page 10
Cooling capacity
Service Ref.
Temperature
Indoor W.B.Outdoor D.B.
16°C (60.8°F
21°C
(69.8°F)
25°C
(77°F)
30°C
(86°F)
32.2°C (90°F)
35°C
(95°F)
40°C
(104°F)
40.6°C
(105°F)
45°C
(113°F)
46°C
(115°F)
50°C
(69.8°F)
52°C
(125.5°F)
Notes:1.T.C. : Total capacity (xkW)
C.F. (T.I.) : Correction factors of Total input + Outdoor unit input)
2.(oF)=32+9/5(oC)
3.Guaranteed operating range (cooling):
18°C (64.4°F 19°C (66.2°F
19.4°C (67°F 20°C (68°F 22°C (71.6°F 16°C (60.8°F 18°C (64.4°F 19°C (66.2°F
19.4°C (67°F 20°C (68°F 22°C (71.6°F 16°C (60.8°F 18°C (64.4°F
19°C (66.2°F
19.4°C (67°F 20°C (68°F 22°C (71.6°F 16°C (60.8°F 18°C (64.4°F 19°C (66.2°F
19.4°C (67°F 20°C (68°F 22°C (71.6°F
16°C (60.8°F 18°C (64.4°F 19°C (66.2°F
19.4°C (67°F 20°C (68°F
22°C (71.6°F 16°C (60.8°F 18°C (64.4°F 19°C (66.2°F
19.4°C (67°F 20°C (68°F 22°C (71.6°F
16°C (60.8°F
18°C (64.4°F
19°C (66.2°F
19.4°C (67°F
20°C (68°F
22°C (71.6°F 16°C (60.8°F 18°C (64.4°F 19°C (66.2°F
19.4°C (67°F 20°C (68°F 22°C (71.6°F
16°C (60.8°F
18°C (64.4°F
19°C (66.2°F
19.4°C (67°F
20°C (68°F
22°C (71.6°F 16°C (60.8°F 18°C (64.4°F 19°C (66.2°F
19.4°C (67°F 20°C (68°F 22°C (71.6°F
16°C (60.8°F
18°C (64.4°F
19°C (66.2°F
19.4°C (67°F
20°C (68°F
22°C (71.6°F
60Hz
PC-2GJA1
T.C.
)
5.4
)
5.8
)
6.0
)
6.0
)
6.1
)
6.5
)
5.3
)
5.6
)
5.8
)
5.9
)
6.0
)
6.4
)
5.1
)
5.4
)
5.6
)
5.7
)
5.8
)
6.2
)
5.0
)
5.3
)
5.5
)
5.6
)
5.7
)
6.1
)
4.9
)
5.2
)
5.4
)
5.5
)
5.6
)
5.9
)
4.7
)
5.0
)
5.2
)
5.2
)
5.3
)
5.7
)
4.7
)
5.0
)
5.1
)
5.2
)
5.3
)
5.7
)
4.4
)
4.8
)
4.9
)
5.0
)
5.1
)
5.5
)
4.4
)
4.7
)
4.9
)
4.9
)
5.0
)
5.4
)
4.2
)
4.5
)
4.7
)
4.7
)
4.8
)
5.2
)
4.1
)
4.4
)
4.6
)
4.6
)
4.7
)
5.1
...
Btu/h=(W)x0.86
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
Lower limit
{ }
Upper limit
PC-2.5GJA
T.C.
7.0
7.5
7.7
7.8
7.9
8.4
6.9
7.3
7.6
7.7
7.8
8.3
6.6
7.1
7.3
7.4
7.5
8.0
6.5
6.9
7.2
7.3
7.4
7.9
6.3
6.8
7.0
7.1
7.2
7.7
6.1
6.5
6.7
6.8
6.9
7.4
6.0
6.4
6.7
6.8
6.9
7.4
5.8
6.2
6.4
6.5
6.6
7.1
5.7
6.1
6.3
6.4
6.5
7.0
5.5
5.9
6.1
6.2
6.3
6.7
5.3
5.7
5.9
6.0
6.1
6.6
...
Indoor 21oC(70oF) D.B.,15.5oC(60oF) W.B., Outodoor 21oC(70oF) D.B.
...
Indoor 35oC(95oF) D.B.,22.5oC(72.5oF) W.B.,Outodoor 52oC(125.5oF) D.B.
Cooling Capacity Correction Factors
Service Ref.
PC-2GJA PC-2.5GJA PC-3GJA PC-4GJSA PC-5GJSA PC-6GJSA
5m(16ft) 10m(33ft) 15m(49ft) 20m(66ft) 25m(82ft) 30m(98ft) 35m(115ft) 40m(131ft)
1
1
1.0 0.985 0.975 0.964 0.954 0.944
1.0 0.978 0.963 0.948 0.934 0.921
1
1.0 0.971 0.950 0.931 0.913 0.896
1.0 0.980 0.966 0.952 0.939 0.826 0.914 0.902
1
1.0
1
1.0
1
0.971
0.960
0.950
0.933
0.931
0.908
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
1
PC-3GJA
T.C.
7.8
8.3
8.6
8.7
8.9
9.4
7.7
8.2
8.4
8.5
8.7
9.2
7.4
7.9
8.1
8.2
8.4
8.9
7.2
7.7
8.0
8.1
8.2
8.8
7.1
7.5
7.8
7.9
8.1
8.6
6.8
7.2
7.5
7.6
7.7
8.2
6.7
7.2
7.4
7.5
7.7
8.2
6.4
6.9
7.1
7.2
7.4
7.9
6.4
6.8
7.1
7.1
7.3
7.8
6.1
6.5
6.8
6.9
7.0
7.5
5.9
6.4
6.6
6.7
6.9
7.3
1
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
PC-4GJSA
T.C.
10.8
11.5
11.9
12.0
12.3
13.0
10.6
11.3
11.7
11.8
12.0
12.8
10.2
10.9
11.2
11.4
11.6
12.3
10.0
10.7
11.0
11.2
11.4
12.1
9.8
10.5
10.8
10.9
11.1
11.9
9.4
10.0
10.3
10.5
10.7
11.4
9.3
9.9
10.3
10.4
10.6
11.3
8.9
9.5
9.9
10.0
10.2
10.9
8.8
9.4
9.8
9.9
10.1
10.8
8.4
9.0
9.4
9.5
9.7
10.4
8.2
8.8
9.2
9.3
9.5
10.2
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
60Hz
Refrigerant piping length (one way)
0.913
0.885
0.896
0.864
0.880
0.845
1 PC-5GJSA1 PC-6GJSA1
T.C.
13.6
14.4
14.9
15.1
15.3
16.2
13.2
14.1
14.6
14.8
15.0
16.0
12.8
13.6
14.0
14.2
14.5
15.4
12.5
13.4
13.8
14.0
14.3
15.2
12.2
13.1
13.5
13.7
13.9
14.9
11.7
12.5
12.9
13.1
13.4
14.3
11.6
12.4
12.9
13.0
13.3
14.2
11.1
11.9
12.3
12.5
12.7
13.6
11.0
11.8
12.1
12.3
12.5
13.5
10.7
11.1
11.2
11.4
11.8
10.1
10.5
9.9
8.8
9.4
9.8
9.9
C.F. (T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
T.C.
15.3
16.2
16.8
17.0
17.3
18.3
14.9
15.9
16.4
16.6
16.9
18.0
14.4
15.3
15.8
16.0
16.3
17.4
14.1
15.1
15.5
15.7
16.0
17.1
13.8
14.7
15.2
15.4
15.7
16.7
13.2
14.1
14.6
14.7
15.0
16.0
13.1
14.0
14.5
14.7
15.0
16.0
12.5
13.4
13.9
14.1
14.4
15.3
12.4
13.3
13.7
13.8
14.1
15.2
11.2
12.0
12.4
12.6
12.9
13.3
9.9
10.6
11.0
11.2
11.4
11.8
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
45m(148ft) 50m(164ft)
— — —
— — —
0.864
0.828
0.850 0.840
0.812 0.800
C.F.
1.11
1.11
10
Page 11
2. STANDARD OPERATION DATA
Capacity Input Indoor unit Service Ref. phase, Hz Volts Amperes
Outdoor unit Service Ref.
phase, Hz Volts Amperes Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
W
kW
V A
V A
MPa.G
(kgf/F•G)
MPa.G
(kgf/F•G)
°C °C °C
m
D.B.°C
W.B.°C
D.B.°C D.B.°C
W.B.°C
Service Ref.
Electrical circuit TotalRefrigerant circuit
Indoor side
Outdoor
side
MODE
PC-4GJSA1 PC-5GJSA1 PC-6GJSA1
PC-4GJSA1 PC-5GJSA1 PC-6GJSA1PC-3GJA1PC-2.5GJA1PC-2GJA1
Cooling
9,300
5.17
1,60
220
0.95
PU-
4TJSA2
3,60
220
14.0
2.40
(24.4)
0.51 (5.2)
88.4
54.5
6.0 5
29 19
11.7 46 24
Cooling
12,400
4.76
1,50
220
0.96
PU-
5YJSA
3,50
380
8.15
1.83
(18.7)
0.46
(4.7)
72.9
48.8
3.1 5
27 19
13.7 35 24
Cooling
11,600
6.94
1,60
220
1.20
PU-
5TJSA
3,60
220
19.61
2.41
(24.6)
0.43
(4.4)
94.8
60.1
1.7 5
29 19
14.9 46 24
Cooling
14,600
5.31
1,50
220
0.96
PU-
6YJSA
3,50
380
8.63
1.96
(20.0)
0.41
(4.2)
75.4
51.1
2.3 5
27 19
12.2 35 24
Cooling
13,400
7.54
1,60
220
1.20
PU-
6TJSA
3,60
220
21.45
2.41
(24.6)
0.42 (4.3)
94.8
60.3
1.6 5
29 19
12.6 46 24
Cooling
9,800
3.43
1,50
220
0.68
PU-
4YJSA3
3,50
380
5.7
1.80
(18.3)
0.51 (5.2)
67.5
48.3
7.3 5
27 19
10.5 35 24
Cooling 6,500
4.25
1,60
220
0.70
PU-
3NJA
1
1,60
220
20.9
2.54
(25.9)
0.44
(4.5)
82.0
61.6
3.6 5
29 19
12.8 46 24
PC-3GJA
1
Cooling
7,200
3.30
1,50
220
0.51
PU-
3VJA
2
1,50
220
15.1
1.96
(20.0)
0.44
(4.5)
63.9
52.3
3.7 5
27 19
10.7 35 24
Cooling
6,200
3.60
1,60
220
0.70
PU-
2.5NJA1
1,60
220
15.8
2.68
(27.3)
0.52
(5.3)
94.3
57.6
10.2 5
29 19
15.3
46 24
PC-2.5GJA
1
Cooling 6,500
2.58
1,50
220
0.51
PU-
2.5VJA2
1,50
220
11.4
1.96
(20.0)
0.5
(5.1)
72.3
52.4
8.6 5
27 19
12.0 35 24
Cooling
4,300
3.12
1,60
220
0.61
PU-
2NJA
1
1,60
220
13.6
2.49
(25.4)
0.53
(5.4)
77.7
60.5
8.3 5
29 19
13.8 46 24
PC-2GJA
1
Cooling
5,600
2.54
1,50
220
0.38
PU-
2VJA
2
1,50
220
11.3
1.93
(19.7)
0.44
(4.5)
68.6
51.6
3.3 5
27 19
9.7
35 24
Airflow Air speed Coverage range Airflow Air speed Coverage range
m
3
/min
m/sec.
m
ft
m
3
/min
m/sec.
m
ft
Configuration
50Hz
Frequency
60Hz
Service Ref.
PC-4GJSA
1
25
4.1
12.6
41.6 25
4.1
12.6
41.6
PC-5GJSA
1
34
4.38
15.2
50.0 34
4.38
15.2
50.0
PC-6GJSA
1
34
4.38
15.2
50.0 34
4.38
15.2
50.0
PC-3GJA
1
18
3.8
10.4
34.5 18
3.8
10.4
34.5
PC-2.5GJA
1
18
3.8
10.4
34.5 18
3.8
10.4
34.5
Ceiling suspended
PC-2GJA
1
13
3.7
8.8 29 13
3.7
8.8 29
The unit of pressure has been changed to MPa based on SI(International System of unit) in accordance with I.S.O.(International Organization for Standardization).
The conversion factor is : 1(MPa•G)=10.2(kgf / FF•G)
3. OUTLET AIR SPEED AND COVERAGE RANGE
The air coverage range is the value up to the position where the air speed is 0.25 m/sec. when air is blown out horizontally from the unit at Hi notch position. The coverage range should be used as a general guide­line since it varies according to the size of the room and furniture inside the room.
11
Page 12
5
180
210
157
15
85
182 (3/8F) liquid
201 (5/8F) gas
241 (Drainage)
Air intake
918
254
680
Electrical box
226
70
525
928
352
263
171
138
86
46 175 1
131
38
3879
161
32
179
42
6-7
Celling
Electrical box
[FRONT VIEW]
When electrical
box is pulled
down
3
2
8
5
1
4
6
2
1
17
150
140
70
320
80
933 (suspension bolt pitch)
983
1000
Air outlet
81
904
76
Gap to ceiling
OUTLINES AND DIMENSIONS
1. INDOOR UNIT PC-2GJA1
NOTES:
refrigerant pipe will be only upper drain pipe arrangement.
1. Use M10 or W3/8 screws for anchor bolt.
2. Please be sure when installing the drain-up machine (option parts).
1 Drainage pipe connection (26mm I.D.) 5 Refrigerant-pipe connection (liquid pipe side/flared connection)
2 Drainage pipe connection (for the left arrangement) 6 Knock out hole for upper drain pipe arrangement
3 Knock out hole for left drain-piping arrangement 7 Knock out hole for left drain pipe arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knock out hole for wiring arrangement
12
Page 13
1240 (suspension bolt pitch)
140
150
320 80
17
70
6
1290
1214
210 180
81 76
1310
Air outlet
1228
680
254
Air intake
85
182
201
241
15
157
(3/8F liquid)
(5/8F gas)
(Drainage)
3
2
8
5
1
4
Electrical box
When electrical
box is pulled
down
[ FRONT VIEW ]
Celling
32
179
161
38
3879
42
6~7
525
1235
416
263
171
138
86
131
175 1
46
1
2
Electrical box
70
226
Gap to ceiling
PC-2.5GJA1 PC-3GJA1
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
refrigerant pipe will be only upper drain pipe arrangement.
2. Please be sure when installing the drain-up machine (option parts).
2 Drainage pipe connection (for the left arrangement) 6 Knock out hole for upper drain pipe arrangement
3 Knock out hole for left drain-piping arrangement 7 Knock out hole for left drain pipe arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knock out hole for wiring arrangement
1 Drainage pipe connection (26mm I.D.) 5 Refrigerant-pipe connection (liquid pipe side/flared connection)
13
Page 14
1228
680
254
Air intake
1214
270
207
81 96
1310
Air outlet
1240 (suspension bolt pitch)
140
150
320 80
17
70
6
87
182
198
245
16
217
(3/8F liquid)
(5/8F gas)
(Drainage)
3
2
8
5
1
4
Electrical box
When electrical
box is pulled
down
[ FRONT VIEW ]
Celling
93
160
38
38 140
42 239
6~7
525
1235
687
263
171
138
86
192
236
1
45
1
2
Electrical box
70
229
Gap to ceiling
PC-4GJSA1
refrigerant pipe will be only upper drain pipe arrangement.
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. Please be sure when installing the drain-up machine (option parts).
3 Knock out hole for left drain-piping arrangement 7 Knock out hole for left drain pipe arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knock out hole for wiring arrangement
2 Drainage pipe connection (for the left arrangement) 6 Knock out hole for upper drain pipe arrangement
1 Drainage pipe connection (26mm I.D.) 5 Refrigerant-pipe connection (liquid pipe side/flared connection)
14
Page 15
PC-5GJSA1 PC-6GJSA1
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
87
6
16
320 80
70
140
150
18
217
270
refrigerant pipe will be only upper drain pipe arrangement.
2. Please be sure when installing the drain-up machine (option parts).
207
81 96
(3/8F liquid)
(3/4F gas)
182
198
245
(Drainage)
680
254
Gap to ceiling
1
4
1
5
8
Celling
[ FRONT VIEW ]
93
Electrical box
236
192
38 140
160
1535
1620
1524
1547(suspension bolt pitch)
45
86
138
171
687
263
38
Air outlet
Air intake
2
229
1
6~7
525
1545
70
Electrical box
2
1 Drainage pipe connection (26mm I.D.) 5 Refrigerant-pipe connection (liquid pipe side/flared connection)
2 Drainage pipe connection (for the left arrangement) 6 Knock out hole for upper drain pipe arrangement
3 Knock out hole for left drain-piping arrangement 7 Knock out hole for left drain pipe arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knock out hole for wiring arrangement
3
42 239
When electrical
box is pulled
down
15
Page 16
2.REMOTE CONTROLLER
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
ON AUTO
STOP START
75
69
108(4-1/4)
117(4-5/8)
108(4-1/4)
96.5
12(15/32)
90.5
11.6
3.6
33
117(4-5/8)
33
Rear side wiring arrangememt opening
Upper side wiring arrangement opening
Fixing hole
83.5(3-9/32)
12(15/32)
8 6
4.6
46
9.2
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
ON
AUTO
STOP START
Exposed remote controller cable
Cable connection is only from the top. (right, left and bottom not possible)
Note:The cable for the remote controller is 5m (16ft)and 12-core with connection O.D. 5.8.
Remote controller cable installation
For exposed remote controller cable installation ●For recessed remote controller cable installation
Remote controller cable
Conduit tube (local arrangement)
Switch box (local arrangement)
Set screw (match with switch box), local arrangement.
16
Page 17
6
SWC
SWA
OP
STD
1
2
3
CNP
D.U.M
31
X1
X1
CN120
LD9
LD6
SW4
LD24
SW8
LD23
LD22
LD21
LD20
LD19
LD18
LD17
LD16
LD15
LD14
LD13
LD12
LD11
LD10
LD5
LD4
LD3
LD1
LD7
SW7
SW6
SW5
SW3
LD8
SW2
SW1
12
fig:*3
Remote control transmissing wire 12VDC with 12 core connector
112
MV
66
CN2
TIMER
CN70
WIRELESS
SW1
SW1
Service Ref.
Service Ref. 3GJA
12.5GJA12GJA1
ON
OFF
ON
OFF
1 23 456781 2 34 5678 12 3 4 56 7 8
ON
OFF
ON
OFF
SW2
12345
TWIN-1
CN2A
TWIN-2
CN2B
OFF
ON
SW3
123
L N
INDOOR UNIT
TB2
REMOTE CONTROLLER
OUTDOOR UNIT
12
BLK
BLK
RT2
ORN
POWER SUPPLY (1 PHASE) AC220-240V 50Hz AC220V 60Hz
R.B
2
TO OUTDOOR UNIT CONNECTING WIRES DC12V
1
TB4
YLW
RT1
12345678
14.7VAC
11.8VAC
1 3
TRANS
CNT
YLW
WHT
220V 230V 240V
RED
T
YLW
ORN
VANE
6
CN6V
1
5
12
GRN/YLW
X4
MF
CN120
TO.RC OUTDOOR
CN30
123
L.TEST
CN28
CN20
PIPE
CN21
12
CN51
MULTIPLE
1234
DRAIN
CN50
INTAKE
SW1
1 2 3 64 5
JR
X4
1 3 5
C
WHT
BLK
RED
I.B
FAN1
ZNR
F2 F1
4 3 21 13
POWER TRANS
CND CN4T
BRN
BRN
RED
RED
BLU
RED
4GJSA1
ON
OFF
1 2 34 5678
5GJSA1
ON
OFF
1 2 34 5678
6GJSA1
ON
OFF
1 2 34 5678
SYMBOL C CN120<I.B>
CN2<I.B> CN2A<I.B>
CN2B<I.B>
CNP<I.B> CN28<I.B> CN50<I.B> CN51<I.B> CN120<R.B>
F1,2<I.B> CN70<I.B>
I.B
NAME FAN MOTOR CAPACITOR REMOTE CONTROLLER TRANS­MISSION WIRE CONNECTOR TIMER ADAPTOR CONNECTOR TRANSMISSION WIRE No.1 CONNECTOR TRANSMISSION WIRE No.2 CONNECTOR DRAIN-UP MACHINE CONNECTOR TIME SHORTENING CONNECTOR DRAIN SENSOR CONNECTOR MULTIPLE CONNECTOR REMOTE CONTROLLER TRANS­MISSION WIRE CONNECTOR FUSE (6.3A 250V) WIRELESS REMOTE CONT­ROLLER CONNECTOR INDOOR CONTROLLER BOARD
SYMBOL LD1<R.B> LD3<R.B> LD4<R.B> LD5<R.B> LD6<R.B> LD7<R.B> LD8<R.B> LD9<R.B> LD10<R.B> LD11<R.B> LD12<R.B> LD13-24<R.B>
MF MV SWA<I.B> JR<I.B>
NAME RUN INDICATOR LED COOLING INDICATOR LED FAN MODE INDICATOR LED FAN HIGH INDICATOR LED LOUVER RUN INDICATOR LED INDICATOR MODE TEMPERATURE LED INDICATOR MODE TIMER LED DRY INDICATOR LED FAN LOW INDICATOR LED OFF TIMER INDICATOR LED ON TIMER INDICATOR LED TEMPERATURE / TIMER RE­MAINING TIME INDICATOR LED FAN MOTOR VANE MOTOR HIGH CELING TYPE SWITCH FUNCTION SELECTOR JUMPER RESISTORS
SYMBOL SWC<I.B> SW1<I.B> SW2<I.B> SW3<I.B> SW1<R.B> SW2<R.B> SW3<R.B> SW4<R.B> SW5<R.B> SW6<R.B>
SW7<R.B>
SW8<R.B> R.B T TB2
NAME OPTION SWITCH FUNCTION SWITCH UNIT SWITCH EMERGENCY OPERATION SWITCH ON / OFF SWITCH OPERATION MODE SWITCH FAN HIGH/LOW SWITCH LOUVER ON / OFF SWITCH INDICATOR SWITCH TEMPERATURE / TIMER SETTING UP SWITCH TEMPERATURE / TIMER SETTING DOWN SWITCH TIMER CONTINUOUS ON / OFF SWITCH REMOTE CONTROLLER BOARD TRANSFOMER POWER SUPPLY TERMINAL BLOCK
SYMBOL TB4
RT1
RT2
X1<I.B> X4<I.B> ZNR DP DS W/B
CNB(W.B) LED1(W.B) SW2(W.B) RU(W.B)
NAME INDOOR / OUTDOOR CONNECT­ING WIRE TERMINAL BLOCK ROOM TEMPERATURE THERMISTOR (0 /15k ,25 /5.4k DETECT) INDOOR COIL THERMISTOR (0 /15k ,25 /5.4k DETECT) DRAIN-UP MACHINE RELAY FAN MOTOR RELAY VARISTOR OPTION DRAIN-UP MACHINE OPTION DRAIN SENSOR OPTION WIRELESS REMOTE CONTROLLER BOARD INDOOR BOARD CONNECTOR RUN INDICATOR LED COOL OPERATION SWITCH BEAM RECIEVE UNIT
WIRING DIAGRAM
PC-2GJA1 / PC-2.5GJA1 / PC-3GJA1 / PC-4GJSA1 / PC-5GJSA1 / PC-6GJSA1
[Emergemcy operation procedure] (2) Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker in this order. (3) During emergency operation, indoor fan runs at high speed but automatic vane remains stop. (4) If vane closed, open the vane by hand slowly. (5) Thermostat will not function. (6) Emergency cooling should be limited to 10 hours maximum (The Indoor unit heat exchanger may freeze). (7) If the ,microcomputer doctor detects the abnomality of the drain-up machine during cool mode. do not execute emergency operation (It causes drain overflow).
NOTES :
1. Since the indoor fan motor (MF) is connected with 220V power, using 230, 240V power will require a setting change of the dip switch (SW1<I.B>) on the indoor controller board as shown in fig : w1.
fig : w1
Indoor fan motor (MF) for 230, 240V.
2. Since the indoor transformer (T) is connected with 220V power, if 230, 240V power used. Change the wiring connection showing fig : W2.
fig : w2
When power supply is
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4. Symbols used in wiring diagram above are. : Connector , : Terminal block
5. Emergency operation If remote controller or microcomputer fails but there is no other trouble,. emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board.
[Check items] (1)Compressor and fan. (2)Check the abnomality using self diagnostic function. When the result of self diagnosis indicates protective device such as freeze protection, emergency operation is not possible
unless the cause is removed.
(3)Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with remote controller is not possible). [Emergency operation procedure]
(1)Set the dip switch(SW3<I.B>) on the indoor controller board to
SW1
240V 230V
1 2 onand 3 off for cooling.
12345678
ON OFF
240 YELLOW 230 ORANGE 220 RED
12345678
ON OFF
17
Page 18
7 REFRIGERANT SYSTEM DIAGRAM
Indoor heat exchanger
Indoor coil thermistor RT2
Distributor with strainer
Outdoor heat exchanger
Ball valve (with service port)
Flared connection
Flexible tube
Compressor
flow of refrigerant
Capillary tube size
Capillary tube
Capillary tube for injection
Flared connection
Low pressure switch
High pressure switch
Thermal switch (Only PU-4VLJSA)
Refrigerant pipe
15.88 (5/8)
(With insulator) option
Refrigerant pipe
9.52 (3/8)
Strainer
PC-2.5/3GJA
PC-4GJA
Refrigerant pipe
19.05 (3/4)
Ball valve
Check plug
Charge plug
Accumulator
Only PU-2.5 PU-3 PU-4YJSA, 4TJSA
PU-2.5 (O.D.3.2 I.D.1.6 –R760) 2pcs PU-3 (O.D.3.2 I.D.1.8 –R800) 2pcs PU-4YJSA, 4VLJSA, 4TJSA (O.D.3.2 I.D.2.0 –R840) 2pcs
w
w
Indoor heat exchanger
Distributor with strainer
Outdoor heat exchanger
(With insulator) option
Ball valve (with service port)
Flared connection
Flexible tube
Compressor
flow of refrigerant
Capillary tube for injection
Flared connection
Low pressure switch
High pressure switch
Refrigerant pipe
15.88 (5/8)
(With insulator) option
Refrigerant pipe
9.52 (3/8)
Strainer
Ball valve
Check plug
Charge plug
Accumulator
O.D.4 I.D.2 –R430
PC-2GJA1 / PU-2NJA1, PU-2VJA2
PC-2.5GJA1, PC-3GJA1, PC-4GJSA1 / PU-2.5NJA1, PU-2.5VJA2, PU-3NJA1,PU-3VJA2,
PU-3YJA3,PU-4TJSA2, PU-4VLJSA2, PU-4YJSA3
18
Page 19
PC-5GJSA1, 6GJSA1 / PU-5YJSA, PU-5TJSA
PU-6YJSA, PU-6TJSA
INDOOR UNIT
Indoor heat exchanger
Distributor with strainer
Refrigerant pipe
(With insulator) option
Flexible tube
Flared connection
Refrigerant pipe
9.52 (3/8F)
(With insulator) option
19.05 (3/4F)
Flared connection
Thermal switch
Charge plug
Ball valve
Accumulator
Capillary tube PU-5Y·TJSA (O.D. 4.0 oI.D. 2.4 –R840)o2pcs PU-6YJSA (O.D. 4.0 oI.D. 2.4 –R1200)o2pcs PU-6TJSA (O.D. 4.0 oI.D. 2.4 –R740)o2pcs
Check plug
High pressure switch
Compressor
Ball valve (with service port)
Capillary tube PU-5Y·TJSA (O.D. 4.0 oI.D. 2.4 –R400) PU-6Y·TJSA (O.D. 4.0 oI.D. 2.4 –R200)
OUTDOOR UNIT
Outdoor heat exchanger
Strainer
DPR
: flow of refrigerant
19
Page 20
8 OPERATION FLOW-CHART
1
Start
POWER SUPPLY
Live
ON/OFF
button ON
TIMER MODE
button ON
During
operation
AUTO STOP lamp ON AUTO START lamp ON
Auto start timer 1 12Hr up/ press 12 1Hr down/ press
Abnormal
operation mode
MODE SELECT
button
EMERGENCY
ALL STOP
STOP
STOP
Self-diagnostic function
Indicate & Memory
Protection device
Self hold
Protection device
Self hold reset
COOL OPERATION
DRY OPERATION
POWER lamp ON
NO
NO
NO
NO
NO
NO
NO
DRY
COOL
YES
YES
YES YES
YES
YES
YES
<w1>
<w3>
<w2>
<w5>
<w4>
Auto stop timer 1 12Hr up/ press 12 1Hr down/ press
Set time ­Elapsed time=0
Set time ­Elapsed time=0
Models : PC-GJA
1. Main operation
w1 Refer to page 26 for timer mode details. w2 The unit starts operation by pressing the ON / OFF switch when unit is OFF. w3 The factors which cause "abnormal operation mode" are as follows.
Outdoor unit abnormal operation.
Fault of room temperature thermistor (RT1).
Fault of indoor coil thermistor (RT2).
Indoor coil frost protection mode.
Drain water overflow prevention mode.
Refer to page 28 for abnormal operation mode details.
w4 The compressor will not start for 3 minutes after the stop.
20
Page 21
COOLING OPERATION
COOL operation
NO
NO
NO
Vane setting notch
Initial
COOLING
w8
Downward discharge
Vane horizontal
w9
Vane initial
setting
Fan speed
LOW
1 hour
airflow
Compressor
thermostat
ON
Allowance
cancel
NO
YES
YES
YES
NO
NO
YES
YES
NO
w10
w11
YES
3-minute
time delay
NO
6-minute
time delay
NO
3-minute
compressor
operation
YES
Coil frost
prevention
Cooling area
NO
YES
NO
Allowance
period
NO
6 minute
time delay
Allowance set
YES
Coil frost protection
NO
Allowance cancel
NO
temperature is
Compressor ON
compressor
operation
YES
Coil frost protection
NO
16-minute
compressor
operation
YES
Indoor pipe
1°C or lower
NO
1
YES
YES
Coil frost
prevention
Compressor OFF
Indoor coil
tempreature is
10°C or higher
YES
3-minute
time delay
Coil frost
prevention release
NO
NO
1 min continue
FAN speed
FAN speed
LOW 5 min
elapse
LOW
YES
NO
YES
Outdoor unit
trouble
YES
10-minute
w8 When operation stops or changes to cooling or dry mode, the auto vane turns to a horizontal angle. If operation changes
during auto vane SWING, the auto vane will continue to swing.
w9 When operating TEST RUN, the thermostat will be continuously ON.
w10 After 3 minute compressor operation, if the indoor coil thermistor reads -15°C or below for 3 minutes, the compressor will
stop for 6 minutes.
w11 Cooling area : Indoor coil temperature is more than 5 degrees above the room temperature.
FAN area : Indoor coil temperature is within 5 degrees either way of the room temperature.
21
Page 22
DRY OPERATION
DRY
operation
Vane
setting notch
NO
YES
NO
Initial dry
operation
YES
Vane initial setting
Room tempereature is
18°C or lower
NO
During
compressor ON
YES
3-minute
compressor
operation
YES
Compressor &
thermostat ON
w8
w12
w9
YES
NO
NO
YES
3-minute
time delay
NO
Compressor &
thermostat
ON
NO
YES
w9
Compressor ON
time completes
YES
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
1
w8—9 Refer to page 24~25. w12 When room temperature is 18°C or below, the compressor cannot operate.
When room temperature rises over 18°C, the compressor starts after a 3-minute time delay.
w13 Compressor ON time is decided by room temperature. Refer to page 24~25. w14 In dry operation, compressor ON makes the fan speed LOW and compressor OFF stops the fan.
It is not possible to set the fan speed with the remote controller
22
NO
w14
10-minute
compressor
OFF
YES
Compressor ON
time set
Compressor ON
Fan speed LOW
NO
w13
w14
Page 23
MICROPROCESSOR CONTROL9
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
ON AUTO
STOP START
1.OUTLINE OF MICROPROCESSOR CONTROL
INPUT to remote controller
OFF-ON switching.
COOL/DRY-FAN selector switching.
Thermostat setting.
HIGH-LOW fan speed switching.
Swing louvers SWING-FIXED switching.
TIMER mode selector switching.
Timer setting.
Self diagnostic troubleshooting.
Test run switching.
Indoor unit
REMOTE CONTROLLER
Transmits and receives orders.
12VDC12VDC
OUTPUT to remote controller
Indication LED lights.
Polar, twelve (12) - core cable Maximum length 50m (164ft)
INPUT from indoor unit
Room temperature thermistor.
Indoor coil thermistor.
OUTPUT to indoor unit
Fan : ON - OFF.
Fan speed : HIGH - LOW
Swing louver : ON-OFF
Emergency stop.
INPUT from outdoor unit
Compressor protection device working
INDOOR CONTROLLER BOARD
Receives orders from remote controller and temperature data from indoor unit.
Processes orders and data.
Transmits the power of indication LED to remote controller
Controls indoor and outdoor operation.
Self diagnostic function.
w System control operation.<Optional> w Emergency operation.
Non - polar, two (2) - core cable
Outdoor unit
OUTDOOR UNIT
Receives order from indoor controller.
Emergency stop.
OUTPUT to outdoor unit
Compressor motor and outdoor fan motor : ON - OFF
23
Page 24
2. INDOOR UNIT CONTROL
TIMER
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER
MODE
DRY FAN
HIGH LOW
ON AUTO
STOP START
2-1COOL operation
<COOL operation time chart>
Operation starts by POWER button ON.
ON
Thermostat
OFF
<How to operate>
1 Press POWER ON/OFF button. 2 Press MODE SELECT button to set operation mode to COOL.
3 Check lamp is ON and set desired temperature with UP
TEMP.
or DOWN button.
NOTES : 1. When lamp is ON, press TIMER/TEMP button
to change the display to temperature mode.
2. Set temperature changes by 1°C in the range 18 ~ 29°C each time UP or DOWN button is pressed.
3. The lighting lamp shows the set temperature, and the flashing lamp shows the room temperature. When the room temperature is equal to the set tempera­ture, the lamp keeps lighting, 0.5 seconds brightly and
0.5 seconds faintly.
Room temperature becomes equal to set temperature.
Room temperature rises above set temperature.
Operation stops by POWER button OFF.
ON
LOW or HIGHLOW or HIGH
Indoor fan
Louver
OFF
ON
OFF
Depends on remote controller setting
ON
Compressor
OFF
MIN. 3 minutes w1
w1 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period has ended.
(1) Compressor control
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when room temperature is higher than set temperature.
The compressor stops when room temperature is equal to or lower than the set temperature.
3 The compressor stops in check mode or during protective functions. 4 Coil frost prevention
To prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 1°C or below after the compressor has been continuously operated for at least 16 minutes or more. The coil frost prevention is released under any of the following conditions.
The indoor coil thermistor rises to 10°C or above.
The room temperature becomes equal to or lower than the set temperature.
COOL mode is stopped or changed to another mode.
NOTE : By cutting the jumper wire JRO2 on the indoor controller board, the temperature to start coil frost prevention
changes from 1°C to -3°C.
5 Coil frost protectiony
24
When indoor coil temperatuer becomes -15°C or below, coil frost protection will proceed as follows. <Start condition> After the compressor has been continuously operated for 3 minutes or more, and the indoor coil temperature has been -15°C or below for 3 minutes, the coil frost protection will start. <Coil frost protection> Compressor stops for 6 minutes, and then restarts. If the start condition is satisfied again during the first 10 minutes of compressor operation, both the indoor and outdoor units stop, displaying a check code of ¨P6¨ on the remote controller.
Page 25
<Termination conditions>
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER
MODE
DRY FAN
HIGH LOW
ON AUTO
STOP START
TIMER
Coil frost protection is released when the start condition is not satisfied again during the allowance, or when the COOL mode stops or changes to another mode.
(2) Indoor fan control
Indoor fan speed LOW/HIGH depends on the remote controller setting. However, if an outdoor unit abnormality is detected, the indoor fan speed will be LOW, regardless of the remote controller setting.
(3) Louver control
Louver operation (SWING LOUVER ON / OFF) depends on the remote controller setting. w Louver comes to the holizontal position automatically after 1 hour operation in law mode.
(4) Detecting abnormalities in the outdoor unit
After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperature and room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the dif­ference is still out of RANGE C,the outdoor unit is functioning abnormally. Thus, the compressor will stops and the remote controller still display this occurrence. RANGE A: Indoor coil temperature is more than 5 degrees above room temperature. RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature. RANGE C : Indoor coil temperature is more than 5 degrees below room tempetature.
(5) Drain pump control
The drain pump works in COOL or DRY operation. When COOL or DRY operation stops or changes to another mode, the drain pump continues to operate for 3 more minutes.
<Drain sensor>
When both the drain pump and unit are operating, the drain sensor detects the temperature. This temperature tells whether the drain water level is above or under the drain sensor. If the drain water level rises above the drain sensor due to a drain pump malfunction, the unit will enter the check mode. The operation will stop and only the drain pump will con­tinu to operate for 3 more minutes. When either of the following conditions are satisfied, the drain sensor is deamed to be under water.
Though the drain sensor has been heated by the drain sensor heater for more than 40 seconds, its temperature rise is less than 20 degrees.
The drain sensor temperature is below 63°C.
2-2 DRY operation
2-3 FAN operation
TIMER TEMP
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER/TEMP.
UP
DOWN
POWER
ON/OFF
COOL
MODE
DRY
SELECT
FAN HIGH
FAN
SPEED
LOW
ON
LOUVER
AUTO STOP
TIMER
MODE
START
MITSUBISHI ELECTRIC
<How to operate>
1 Press POWER ON/OFF button. 2 Press MODE SELECT button to set operation mode to DRY.
3 Check lamp is ON and set desired temperature with UP or DOWN button.
TEMP.
NOTES : 1. When lamp is ON, press TIMER/TEMP button to change the display
to temperature mode.
2. Set temperature changes by 1°C in the range 18 ~ 29°C each time UP or DOWN button is pressed.
3. The lighting lamp shows the set temperature, and the flashing lamp shows the room temperature. When the room temperature is equal to the set temperature, the lamp keeps lighting, 0.5 seconds brightly and 0.5 seconds faintly.
<How to operate>
1 Press POWER ON/OFF button. 2 Press MODE SELECT button to set operation mode to FAN.
NOTES : Temperature can not be set in FAN operation.
! Indoor fan control
The indoor fan speed LOW/HIGH depends on the remote controller setting.
@ Louver control
The louver operation ON/OFF depends on the remote controller setting.
# Drain pump control
The drain pump does not work in FAN operation. As an exception, when COOL mode changes to FAN mode, the drain pump continues to operate for the first 3 minutes in FAN operation.
25
Page 26
TIMER
START w I
AUTO
TIMER
2-4 TIMER operation
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
ON AUTO
STOP START
<Timer function>
AUTO STOP ·········The air conditioner stops after the set time lapses. AUTO START ········The air conditioner starts after the set time lapses.
<How to operate AUTO STOP timer>
1 While POWER lamp is lighting, press TIMER MODE button.
AUTO
STOP w
and lamps turn ON.
2 Set the time for the AUTO STOP timer with the UP or DOWN button.
NOTE : The time setting is in 1 hour units up to 12 hours.
3 With the lapse of time, the timer lamps turn OFF one by one, showing
the remaining time.
4 To cancel the AUTO STOP timer and continue operation, press the
TIMER MODE button. To cancel the AUTO STOP timer and stop operation, press the POWER ON/OFF button.
<How to operate AUTO START timer>
1 While POWER lamp is OFF, press TIMER MODE button.
and lamps turn ON.
2 Set the time for the AUTO START timer with the UP or DOWN button.
NOTE : The time setting is in 1 hour units up to 12 hours.
3 With the lapse of time, the timer lamps turn OFF one by one, showing
the remaining time.
4 To cancel the AUTO START timer and keep the unit OFF, press the
TIMER MODE button. To cancel the AUTO START timer and start operation, press the POWER ON/OFF button.
<Remaining time display>
The green lamps show the remaining time until the time is up. When the time is up, the green lamps are all off.
TIMER
Green
lamps
TEMP
w
12
29
11
28
10
27
9
26
8
25
7
24
6
23
5
22
4
21
3
20
2
19
1
18
Remaining time:2 hour 59 minutes to 2 hour
NOTE : When AUTO STOP timer is active, the remaining time display can be changed to the temperature display by pressing
DISPLAY SELECT button.
TIMER
TEMP
w
12
29
11
28
10
27
9
26
8
25
7
24
6
23
5
22
4
21
3
20
2
19
1
18
1 hour 59 minutes to 1 hour
TIMER
TEMP
w
12
29
11
28
10
27
9
26
8
25
7
24
6
23
5
22
4
21
3
20
2
19
1
18
59 minutes to 0
TIMER
TEMP
w
12
29
11
28
10
27
9
26
8
25
7
24
6
23
5
22
4
21
3
20
2
19
1
18
Time counting is completed.
26
Page 27
2-5 Test run
The unit starts the test run by pressing both the UP and DOWN buttons simultaneously for more than two seconds during
TIMER
lamp ON or the unit OFF.
w
The test run automatically stops in 2 hours.
Set temperature is not displayed during test run.
To cancel the test run, press the POWER ON/OFF button.
<Initial setting>
The units are set as follows by the factory.
1) Initial operation mode: FAN 3) Swing louver : OFF
2) Fan speed : LOW 4) Set temperature: 28°C
2-6 Emergency operation
When the remote controller or microprocessor malfunc­tions and no other trouble exists, emergency operation is available by setting the dipswitch on the indoor con­troller board.
[Check items] ! Make sure the compressor and the fans are running
normally.
@ Locate the trouble with the self-doagnostic function. If
the self-diagonostic function indicates that the protec­tion device (such as coil frost protection)is function­ing, the sources must be removed before attempting emergency operation. Emergency operation ON/OFF is activated not with the remote controller but with the circuit breaker.
SW3
INDOOR CONTROLLER BOARD [Emergency operation procedure] ! Cooling operation is available by setting the dipswitch
SW3 1 and 2 ON and 3 OFF on the indoor con­troller board.
@ To start emergency operation, turn the outdoor sidecircuit breakerON first, and then the indoor side circuit breaker ON. # During emergency operation, the indoor fan runs on HIGH speed, the compressor runs continuously, and the louver
stops. When the drain pump is attached, it works in emergency operation.
$ Thermostat will not function. % Do not use emergency cooling operation for more than 10 hours, as the indoor coil may freeze.
w If the self-diagnostic function shows a drain pump malfunction, do not attempt emergency operation, as the drain may overflow.
2-7 Auto Restart function
Unit can be start / stop by turning the breaker ON / OFF. ! Cutting the JR06 on the indoor board.
Unit can be start / stop using a remote controller. Only If the unit was already being operated before power off, the unit restarts automatically as soon as power is back.
JR06 Auto restart
Available Not effective
Not available Effective
@ Short all the CN2 on the indoor board.
Unit can not be start/ stop using remote controller. Unit will restart automatically whether the unit is operated or stopped when the power is cut off.
1 2CN2 3
ORN BRN RED
Optional timer adapter PAC-SA89TA-E
I.B.
27
Page 28
2-8 Function of jumper wire and dipswitch on indoor controller board
1. Jumper wire
...
1 JR1
Jumper wire for the auto vanes.
Cut JR01 for the unit WITHOUT auto vanes.
...
2 JR2
Jumper wire for the temperature to start coil frost prevention
Cutting JR02 changes the temperature from +1°C to -3°C.
...
3 JR3
Jumper wire for set temperature adjustment in HEAT mode. In HEAT operation, heated air stagnates in the upper part of the room. The indoor unit installed in the upper part of the room will detect the air temperature higher than the actual temperature in the living space. This difference is about 4 degrees. Therefore, the temperature detected by the room temperature thermistor should be corrected 4 degrees down. The unit with JR04 attached will make this adjustment.
...
4 JR4
Jumper wire for the indoor fan speed during thermostat OFF in HEAT mode Cutting JR04 changes the speed from Extra-Low to Low.
...
5 JR5
Jumper wire for detecting abnormalities in the outdoor unit Cutting JR05 makes this detection unavailable. (Occurrence of abnormality can not be detected. )
...
6 JR6
Jumper wire for auto restart function Cutting JR06 makes the auto restart function available.
2. Dipswitch
1 SW1 (Function switch)
ON OFF
1 2 3 4 5 6 7 8
SW1-1) Switch for power supply
ON : 220V OFF : 230V, 240V
SW1-2) Switch for single or twin control
ON : Twin control OFF : Single control
SW1-3) Switch for unit number in twin control
(This switch is valid when SW1-2 is ON. ) ON : Unit No. 2 OFF : Unit No. 1
SW1-4, SW1-5,SW1-6) Switch for capacity of each model
PC-2GJA1 PC-2.5GJA1 PC-3GJA1
ON OFF
4 5 6
ON OFF
4 5 6
ON OFF
4 5 6
SW1-7, SW1-8) Pair number of the wiress remote controller
ON OFF
7 8
0
ON OFF
1
7 8
ON OFF
7 8
2
2 SW2 (Unit switch)
SW2-1) Switch for air conditioner with or without electric heater
ON : Unit with electric heater OFF : Unit without slectric heater (PC-GJ(S)A)
ON OFF
1 2 3 4 5
SW2-2) Switch for air conditioner with or without heat pump
(Keep this switch OFF for PC-GJ(S)A) ON : Unit with heat pump OFF : Unit without heat pump
SW2-3) Switch for function code (Keep this switch OFF for PC-GJ(S)A)
ON : 1 OFF : 0
SW2-4) Switch for function code (Keep this switch OFF for PC-GJ(S)A)
ON : 1 OFF : 0
SW2-5) Switch for function code (Keep this switch ON for PC-GJ(S)A)
ON : 1 OFF : 0
3 SW3 (Emergency operation switch)
Normal operation For emergency cooling
ON OFF
1 2 3
1 2 3
ON OFF
ON OFF
PC-4GJSA1
ON OFF
7 8
3
4 5 6
PC-5GJSA1
ON OFF
4 5 6
PC-6GJSA1
ON OFF
4 5 6
4 SWA : for ceiling height
...
3
High ceiling
...
2
Standard
...
1
Low ceiling
28
5 SWC : optional filter element
...
STD
Without filter element
...
OP
With filter element
For ceiling height High ceiling 3.5m Standard 2.8m Low ceiling 2.3m
Page 29
10
TROUBLESHOOTING
1. self-diagnostic function
! When trouble occurs during operation, the unit stops and enters the self-diagnostic mode, and displays the trouble loca-
tion with the timer lamps on the remote controller. All the other lamps are OFF.
@ To activate the self-diagnostic function for service, press the UP and DOWN buttons simultaneously for more than two
TIMER
seconds during operation with lamp ON.
# The timer lamps show the latest trouble. Trouble data is memorized until the next trouble occurs, even when the breaker
turns OFF. To clear the memory, press the UP and DOWN buttons simultaneously for more than two seconds during the test run.
$ All buttons except the POWER ON/OFF button are unavailable during the self-diagnostic mode. % To release the self-diagnostic mode, press the POWER ON/OFF button.
TIMER
12
TEMP.
w
i
29
w
Unit
Trouble location
Transmission error
in twin control
Outdoor unit
Cause
Wrong wiring between No. 1 and No. 2 units
Poor connector contact
Wrong wiring between
indoor/outdoor units
Outdoor unit abnormality detection
Malfunction of outdoor coil thermistor
Reversed phase detected
Measures
Check dipswitch setting
Check wiring
Check wiring
Check outdoor unit
Check outdoor coil thermistor
11 10
9 8 7 6 5 4 3 2 1
28 27
26 25
24 23 22 21 20 19 18
Unit
No.1
Unit
No.2
Unit
No.1
Unit
No.2
Unit
No.1
Unit
No.2
Unit
No.1
Unit
No.2
Unit
No.1
Unit
No.2
Room
temperature
thermistor
(RT1)
Indoor coil
thermistor
(RT2)
Drain sensor
(DS)
Drain
overflow
protection
Coil frost
or overheat
prevention
Poor connector contact
Thermistor malfunction
Poor connector contact
Thermistor malfunction
Poor connector contact
Thermistor malfunction
Drain pump malfunction
Drain sensor improperly
mounted
Air passage short cycle
Air filter clogged
Indoor fan malfunction
Check connector
Check thermistorNo trouble ➔ replace indoor
controller board.
Check connector
Check thermistorNo trouble ➔ replace indoor
controller board.
Check connector
Check thermistorNo trouble ➔ replace indoor
controller board.
Check drain pump
Check drain sensorNo trouble ➔ replace indoor
controller board.
Remove blockage
Check air filter
Check indoor fan
(Indicates that the unit is in self-diagnostic mode)
29
Page 30
11
slide
intake grill
intake grill holding knobs
Hinges
Pull out the intake grill
electrical cover
screw(electrical cover)
screw(electrical box)
Slide to the left
beam
clamp
DISASSEMBLY PROCEDURE
PC-3GJA1
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
1. Removing the air intake grill
(1) Slide the intake grill holding knobs (at two locations) back-
ward to open the intake grill.
(2) When the intake grill left open, push the stoppers on the
rear hinges (at two locations) to pull out the intake grill.
2. Removing the electrical box
(1) Remove the air intake grill. (2) Remove the screw from the beam and remove the beam. (3) Remove the screws from the electrical cover, and remove
the electrical cover. (4) Disconnectors including CN6V and CN21. (5) Remove the screws from the electrical box and pull out
the electrical box.
Figure 1
Figure 2
30
<Electrical parts in the electrical box> Terminal block (for power supply) Terminal block (for in/outdoor connecting wire) Operation condenser Indoor control board Power Trans
Photo 1
Operation condenser
Power trans
Indoor control board
Terminal
terminal block (in / out conncting)
block (power supply)
Terminal block (remote control)
Page 31
screw
side panel
sliding the panel to the front
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
3. Removing the fan motor
(1) Remove the intake grill. (2) Disconnect the fan motor connector. (3) Unscrew screws for removing the motor guard. (4) Unscrew screws for removing the fan guard. (5) Remove the screw for removing the motor support at both
left and right side.
(6) Loosen the set screws at the fan motor side of the con-
necting joint.
(7) Slide the fan motor to the left side and pull it out.
4. Removing the sirocco fan
(1) Remove the air intake grill. (2) Remove 1 beam. (3) Unscrew screws for removing the motor guard. (4) Unscrew screws for removing the fan guard. (5) Remove the lower casing while pressing the stoppers at
upper side of the casing. (6) Loosen the set screws at the connecting joint. (7) Remove the sirocco fan and shaft together by sliding the
shaft to the left.
Photo 2
Photo 3
Screws
Motor support
Motor guard
Motor gurd
Motor
Set screws
Connecting joint
Fan guard
(Note)
Make sure that the upper side casing is snaped to the fan plate securely with catch.
5. Removing the side panel
(1) Remove the air intake grill. (2) Remove the screw from the side panel, and remove the
side panel by sliding the panel to the front.
Figure 2
Motor
Sirocco fan
Connecting joint
Casing
Bearing
31
Page 32
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
6. Removing the vane motor
(1) Remove the air intake. (2) Remove the left side panel. (3) Remove the relay connector of vane motor. (4) Remove the electrical box. (5) Remove the screws of vane motor, then remove vane
motor.
(Note)
Connect the lead wires and connectors properly and place them in the proper position so that the wires are not pinched by other parts.
7. Removing the indoor coil thermistor
(1) Remove the air intake grill. (2) Remove the right side panel. (3) Remove the relay connector of the indoor coil thermistor. (4) Remove the screw, and remove the check panel. (5) Extract the indoor coil thermistor from the holder. <Caution for the installation>
There is a possibility for the short circuit when connector gets wet by water through the thermistor lead wire. Therefore, lead wire of the indoor coil thermistor should be traped as shown in the picture.
Photo 4
Relay connector of the vane motor
Photo 5
Left side panel
Screw
Check panel
Screw
Vane motor
Relay connector of the pipe thermistor
8. Removing the under panel
(1) Remove the air intake grill. (2) Remove the beam. (3) Remove the side panel (right and left). (4) Unscrew the screws of the under panel, then remove the
lower panel.
wWeight of the lower panel : app. 2kg.
Photo 6
Hold indoor coil thermistor Trap
Photo 7
Screw
32
Under panel
Page 33
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
9. Removing the drain pan
(1) Remove the air intake grill. (2) Remove the beam. (3) Remove the side panel (right and left). (4) Remove the under panel. Remove the screws of the right
and left side drain pan. (5) Remove the insiation in center of the drain pan, and after
removing the screw, remove the drain pan. (Note)
Please aware that there might be drain left in the drain pan when you remove the drain pan.
10. Removing the guide vane
(1) Remove the intake grill. (2) Remove the beam. (3) Remove the side panel (right and left). (4) Remove the under panel. (5) Remove the drain pan. (6) Remove the screw from the guide vane, then remove the
guide vane.
Photo 8
Screw
Photo 9
Drain pan
Screw
(Insulation)
Screw
11. Removing the Auto vane
(1) Remove the intake grill. (2) Remove the left side panel. (3) Remove the left side box. (4) Remove the under panel. (5) Remove the screw from the auto vane. (6) Slide the auto vane to the right side and pull the auto vane
out.
Drain pan
Photo 10
Guide vane
Auto vane
Screw
Screw
33
Page 34
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
12. Removing the heat exchanger
(1) Remove the air intake grill. (2) Remove the beam. (3) Remove the side panel. (right and left) (4) Disconnect the relay connector. (5) Remove the under panel. (6) Remove the drain pan. (7) Unscrew the screw of the pipe cover, and remove the pipe
cover.
(8) Unscrew the screw of the pipe support, and remove the
pipe support.
(9) Unscrew the screw of the heat exchange, and remove the
heat exchanger. Remove the heat exchange with care, since this is quite heavy. Removing work should be done with more than 2 people.
w Weight of heat exchanger : ApR.5.3kg.
Photo 11
Pipe support
Screws
Pipe cover
Screws
Heat
exchanger
34
Page 35
No.
Part No. Part Name Specification
PC-2
GJA, GJA
1
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Amount
Q'ty / set Price
Part numbers that are circled not shown in the figure.
1 2 3 4 5 6 7 8
9 10 11 12 13
FAN MOTOR MOTOR LEG PIECE (MOTOR) CASING SIROCCO FAN INDOOR COIL THERMISTOR DRAIN PAN ASSY ROOM TEMPERATURE THERMISTOR HEAT EXCHANGER DRAIN PLUG FAN GUARD FAN GUARD FAN GUARD
D09B4P54MS 1
1 1 2 2 1 1 1 1 1 1 1 1
MF
RT2
RT1
Remarks
(Drawing No.)
T7W 23J 762 R01 17J 130 R01 43E 126 R01 17J 110 R01 17J 114 R01 17J 202 R01 17J 529 R01 18J 202 T7W 26J 480 R01 17J 524 T7W 17J 675 T7W 18J 675 T7W 19J 675
12
PARTS LIST
FAN PARTS PC-2GJA PC-2GJA1
9
6
4
10
5
13
8
1
11
2
4
3
5
12
7
35
Page 36
No.
Part No. Part Name Specification
PC-2.5
GJA,GJA1 GJA,GJA1
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
Amount
Q'ty / set Price
Part numbers that are circled not shown in the figure.
1
2
3
4
5
6
7
8
9
10
11
12 13 14 15 16 17 18
FAN MOTOR FAN JOINT SHAFT (FAN) SLEEVE BEARING MOTOR LEG SIROCCO FAN SIROCCO FAN CASING
INDOOR COIL THERMISTOR ROOM TEMPERATURE THERMISTOR HEAT EXCHANGER HEAT EXCHANGER DRAIN PAN ASSY DRAIN PLUG BEARING SUPPORT FAN GUARD FAN GUARD FAN GUARD PIECE (MOTOR)
DC9C4P70MS 1
1 1 1 1 2 1 3 1 1 1
1 1 1 1 2 1 1
Remarks
(Drawing No.)
T7W 30J 762 R01 29J 116 R01 29J 100 R01 705 103 R01 29J 130 R01 29J 114 R01 33J 114 R01 17J 110 R01 17J 202 R01 18J 202 T7W 29J 480 T7W 33J 480 R01 29J 529 R01 17J 524 R01 29J 145 T7W 20J 675 T7W 21J 675 T7W 18J 675 R01 43E 126
PC-3
1 1 1 1 1 2 1 3 1 1
1 1 1 1 1 2 1 1
MF
RT2 RT1
FAN PARTS PC-2.5GJA, PC-2.5GJA1 PC-3GJA, PC-3GJA1
5
1
2
11
18
9
10
13
7
15
3
16
36
4•14
6
8
17
12
Page 37
FAN PARTS PC-4GJSA PC-4GJSA1
11
18
5
9
1
2
10
13
7
15
3
16
No.
Part No. Part Name Specification
1
T7W 39J 762
2
R01 29J 116
3
R01 29J 100
4
R01 705 103
5
R01 35J 130
6
R01 35J 114
7
R01 39J 114
8
R01 35J 110
9
R01 17J 202
10
R01 18J 202
11
T7W 37J 480
12
R01 35J 529
13
R01 17J 524
14
R01 35J 145
15
T7W 22J 675
16
T7W 23J 675
17
T7W 24J 675
18
R01 43E 126
FAN MOTOR FAN JOINT SHAFT SLEEVE BEARING MOTOR LEG SIROCCO FAN SIROCCO FAN CASING INDOOR COIL THERMISTOR ROOM TEMPERATURE THERMISTOR HEAT EXCHANGER DRAIN PAN ASSY DRAIN PLUG BEARING SUPPORT FAN GUARD FAN GUARD FAN GUARD PIECE (MOTOR)
4 • 14
8
17
Q'ty / set Price
PC-4
GJSA, GJSA
D10B4P90MS 1
6
12
Wiring
Remarks
(Drawing No.)
1
Diagram
Symbol
Recom­mended
Q'ty
Unit
Amount
MF 1 1 1 1 2 1 3 1 1
RT2
RT1 1 1 1 1 1 2 1 1
37
Page 38
No.
Part No. Part Name Specification
PC-5
GJSA, GJSA
1
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
Amount
Q'ty / set Price
1 2 3 4 5 6 7 8
9 10 11
12
13 14 15 16 17 18 19 20
FAN MOTOR FAN JOINT SHAFT SLEEVE BEARING MOTOR LEG SIROCCO FAN SIROCCO FAN SIROCCO FAN CASING INDOOR COIL THERMISTOR ROOM TEMPERATURE THERMISTOR HEAT EXCHANGER HEAT EXCHANGER DRAIN PAN ASSY DRAIN PLUG BEARING SUPPORT FAN GUARD FAN GUARD FAN GUARD FAN GUARD PIECE (MOTOR)
1 1 1 1 1 1 1 2 4 1 1 1
1 1 1 1 2 1 1 1
Remarks
(Drawing No.)
T7W
43J 762 R01 29J 116 R01 29J 100 R01 705 103 R01 41J 130 R01 41J 114 R01 39J 114 R01 35J 114 T7W
B07 110 R01 17J 202 R01 14N 202 T7W
41J 480 T7W
45J 480 R01 41J 529 R01 17J 524 R01 35J 145 T7W
25J 675 T7W
23J 675 T7W
24J 675 T7W
26J 675 R01 43E 126
PC-6
1 1 1 1 1 1 1 2 4 1 1
1 1 1 1 1 2 1 1 1
MF
RT2 RT1
GJSA, GJSA
1
D10B4P150MS
FAN PARTS PC-5GJSA,PC-6GJSA PC-5GJSA1,PC-6GJSA1
12
20
11
19
16
14
13
17
10
4·15
18
38
Page 39
No.
Part No. Part Name
Specification
PC-2
GJA
GJA
1
PC-2.5/3
GJA
GJA
1
PC-4
GJSA
GJSA
1
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
Amount
Q'ty / set Price
1 2 3 4
5
6 7
8
9
10
CONTROLLER BOARD FUSE TRANSFORMER CONTROL BOX CAPACITOR CAPACITOR CAPACITOR TERMINAL BLOCK TERMINAL BLOCK
BOX COVER
REMOTE CONTROLLER
REMOTE CONTROLLER CORD
1 1 1 1
1
1 1
1 1 1
1 1 1 1 1
1 1 1
1 1
1 1 1 1
1
1 1
1
1 1
PC-5/6
GJSA
GJSA
1
1 1 1 1
1 1 1
1 1 1
(BG00N015G12)
(BG02A804G12) (BG02A804G14) (BG02A804G13)
I.B
F1,2<I.B>
T
C C
C TB2 TB5
R.B
250V 6.3A
3+ 400V
3P(L,N,;) 2P(1,2)
12m
Remarks
(Drawing No.)
T7W 27K 310 T7W 520 239 T7W 23J 260
— R01 30L 255 T7W 39J 255 T7W 43J 255 T7W 521 716 T7W 512 716
— T7W 20K 200 T7W 139 305
ELECTRICAL PARTS PC-2GJA, PC-2GJA1 PC-2.5GJA, PC-2.5GJA1 PC-3GJA, PC-3GJA1 PC-4GJSA, PC-4GJSA1 PC-5GJSA, PC-5GJSA1 PC-6GJSA, PC-6GJSA1
3
5
4
2
1
6
7
8
10
9
39
Page 40
STRUCTURAL PARTS PC-2GJA PC-2GJA1
2 19 13 15 4 12 16
28
24
17
10 11
5
23 14
7
8
26
18
1
40
25
9 6 27 3 20
Page 41
Part numbers that are circled not shown in the figure.
No.
Part No. Part Name
1
R01 17J 661
2
R01 17J 662
3
R01 17J 669
4
R01 17J 676
5
R01 17J 500
6
R01 18J 500
7
R01 17J 691
8
R01 18J 691
9
R01 17J 054
10
R01 17J 651
11
R01 17J 085
12
R01 18J 086
13
R01 29J 223
14
R01 17J 067
15
R01 17J 068
16
R01 17J 002
17
R01 17J 061
18
R01 17J 808
19
R01 17J 809
20
R01 17J 070
21
R01 17J 523
22
R01 17J 072
23
R01 18J 665
24
R01 18J 666
25
R01 17J 668 26 27 28
— — —
RIGHT SIDE PANEL LEFT SIDE PANEL UNDER PANEL REAR PANEL L.L. FILTER L.L. FILTER GRILLE ASSY GRILLE ASSY GRILLE CATCH FRONT PANEL GUIDE VANE ASSY-6R. GUIDE VANE ASSY-6L. VANE MOTOR RIGHT SIDE BOX LEFT SIDE BOX AUTO VANE GRILLE HINGE RIGHT LEG LEFT LEG WIRELESS BOARD CASE JOINT SOCKET DRAIN HOSE COVER SIDE PLATE-R. SIDE PLATE-L. SERVICE PANEL BEAM(GA) REAR SUPPORT VANE SUPPORT
Specification
Q'ty / set Price
PC-2
GJA, GJA
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
1 1 1 1 1 1 1 1 4 1 1 1 1
MV 1 1 1 2 1 1 1 1 1 1 1 1 2 1 1
(BG17H464H08) (BG02H454H04)
(BG02R321G06)
Amount
41
Page 42
STRUCTURAL PARTS PC-2.5GJA / PC-3GJA PC-4GJSA PC-2.5GJA1 / PC-3GJA1 PC-4GJSA1
2
18
1116
1413
12
27
23
4
8
9
6
3
7 19
26
25
22
15
5
10
24
17
1
42
Page 43
Part numbers that are circled not shown in the figure.
No.
Part No. Part Name
R01 17J 661
1
R01 35J 661 R01 17J 662
2
R01 35J 662
3
R01 17J 500 R01 29J 676
4
R01 35J 676 R01 29J 651
5
R01 36J 651
6
R01 17J 691
7
R01 29J 669
8
R01 17J 061
9
R01 17J 054 R01 17J 067
10
R01 35J 067 R01 17J 068
11
R01 35J 068
12
R01 17J 085
13
R01 18J 086
14
R01 29J 087 R01 29J 002
15
R01 35J 002 R01 29J 223
16
R01 35J 223
17
R01 17J 808
18
R01 17J 809
19
R01 17J 070
20
R01 17J 523
21
R01 17J 072 R01 18J 665
22
R01 35J 665 R01 18J 666
23
R01 35J 666
24
R01 17J 668 25 26
27
— — — —
RIGHT SIDE PANEL RIGHT SIDE PANEL LEFT SIDE PANEL LEFT SIDE PANEL L.L. FILTER REAR PANEL REAR PANEL FRONT PANEL FRONT PANEL GRILLE ASSY UNDER PANEL GRILLE HINGE GRILLE CATCH RIGHT SIDE BOX RIGHT SIDE BOX LEFT SIDE BOX LEFT SIDE BOX GUIDE VANE ASSY-6R. GUIDE VANE ASSY-6L. GUIDE VANE ASSY-6C. AUTO VANE AUTO VANE VANE MOTOR VANE MOTOR RIGHT LEG LEFT LEG WIRELESS BOARD CASE JOINT SOCKET DRAIN HOSE COVER SIDE PLATE-R. SIDE PLATE-R. SIDE PLATE-L. SIDE PLATE-L. SERVICE PANEL BEAM(GA) REAR SUPPORT VANE SUPPORT VANE SUPPORT
Specification
Q'ty / set Price
PC-2.5/3
GJA,GJA1
PC-4
GJSA,GJSA1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
1
1
1
1
2
2
1
1
1
1 2 1 4 4
2
1
4
4 1
1 1
1 1 1 1
1
1
1 1
1 1
1 1 1 1 1 1
1
1
1
1
1
MV MV
1
1 1
1 1 2 1 2
1
2
(BG17H464H08)
1
(BG02H454H04) (BG02R321G06)
2
(BG02R805G04)
Unit
Amount
43
Page 44
STRUCTURAL PARTS PC-5GJSA/PC-6GJSA PC-5GJSA1/PC-6GJSA1
18
20
2
25
4
6
8
14
16
12
11
29
17
13
10
24
15
26
19
27
1
28
5
9
7
3
21
44
Page 45
Part numbers that are circled not shown in the figure.
No.
Part No. Part Name
1
R01 35J 661
2
R01 35J 662
3
R01 41J 669
4
R01 41J 676
5
R01 17J 500
6
R01 18J 500
7
R01 17J 691
8
R01 18J 691
9
R01 17J 054
10
R01 41J 651
11
R01 41J 085
12
R01 42J 086
13
R01 43J 087
14
R01 35J 223
15
R01 35J 067
16
R01 35J 068
17
R01 41J 002
18
R01 17J 061
19
R01 17J 808
20
R01 17J 809
21
R01 17J 070
22
R01 17J 523
23
R01 17J 072
24
R01 35J 665
25
R01 35J 666
26
R01 17J 668 27 28 29
— — —
RIGHT SIDE PANEL LEFT SIDE PANEL UNDER PANEL REAR PANEL L.L.FILTER L.L.FILTER GRILLE ASSY GRILLE ASSY GRILLE CATCH FRONT PANEL GUIDE VANE ASSY-5R. GUIDE VANE ASSY-5L. GUIDE VANE ASSY-5C. VANE MOTOR RIGHT SIDE BOX LEFT SIDE BOX AUTO VANE GRILLE HINGE RIGHT LEG LEFT LEG WIRELESS BOARD CASE JOINT SOCKET DRAIN HOSE COVER SIDE PLATE-R. SIDE PLATE-L. SERVICE PANEL BEAM(GA) REAR SUPPORT VANE SUPPORT
Specification
Q'ty / set Price
PC-5/6
GJSA,GJSA1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
1 1 1 1 2 1 2 1 6 1 1 1 2 1
MV 1 1 1 6 1 1 1 1 1 1 1 1 3 1 3
(BG17H464H08) (BG02H454H04) (BG02R805G04)
Amount
45
Page 46
13
OPTIONAL PARTS
1. REFRIGERANT PIPES
Service Ref. : PC-2GJA1 / PC-2.5GJA1 / PC-3GJA1
Part No. Pipe length Pipe size O.D. Connection method
PAC-15FFS-EPAC-10FFS-EPAC-07FFS-EPAC-05FFS-E
15m10m7m5m
Liquid:{9.52 Gas:{15.88
Indoor unit:Flared Outdoor unit:Flared
Service Ref. : PC-4GJSA
Part No. Pipe length Pipe size O.D. Connection method
Note 1. How to connect refrigerant pipes.
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as con­nection takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow. If piping length exceeds 5m, an additional charge of refrigerant in needed.
Note 2. The following main parts are contained in the optional refrigerant piping kit.
Heat insulating cover, vinyl tapes, nipples, sleeve and flange (for wall hole), connecting cables.
1/PC-5GJSA1/PC-6GJSA1
PAC-SC54PI-EPAC-SC53PI-EPAC-SC52PI-EPAC-SC51PI-E
Liquid:{9.52 Gas:{19.05
Indoor unit:Flared Outdoor unit:Flared
2. REMOTE CONTROLLER EXTENSION CABLE
When installing the remote controller at a distance from the air conditioner, use the designated extension cable with connector.
Part No. Length
PAC-919ECPAC-918ECPAC-906ECPAC-905EC
15m10m7m5m
50m30m20m12m
46
Page 47
3. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units.
Part No. PAC-805RC
3-1. Dimensions
12
113
23.5
56.3 11
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
117
POWER ON/OFF
AHEAD
BACK
ACTIVE BYPASS
DUAL
CENTRAL
MITSUBISHI ELECTRIC
117
3-2. Names and Functions
"ENGAGED" indicator When this indicator is lit, transmission is in
progress and all switches are inoperative.
DUAL/CENTRAL switch This change-over switch governs the oper-
ation of the accessory remote controller.
"DUAL" Instructions from both the accessory
remote controller and the centralized remote controller are valid. (Priority is given to the last instruction received.)
"CENTRAL" ON/OFF switching by the accessory
remote controller is invalidated. Operation is controlled by the centralized remote con­troller only.
Initial setting is "DUAL".
LCD Matrix Display This display indicates the operational sta-
tus of all connected units either by steady lighting or by flashing.
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
POWER ON/OFF
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
BACK
ACTIVE BYPASS
DUAL
CENTRAL
MITSUBISHI ELECTRIC
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER ON/OFF
AHEAD
AHEAD
8
113
POWER ON/OFF switch Operation ON/OFF switch.
BACK AHEAD buttons These buttons are used to designate the attached unit(s). (They designate the unit to be centrally controlled.)
When group “00” is designated; col­lective ON/OFF instruction is sent to all units.
When group “01”-“16“ is designated; ON/OFF instruction is sent to the des­ignated units.
ACTIVE/BYPASS switch This change-over switch for the pro­gram timer. Use “ACTIVE” when a program timer is connected. Use “BYPASS” when a program timer is not connected.
Independent “DUAL / CENTRAL” and “ACTIVE / BYPASS” setting of all the groups is possible. When the power supply to the
centralized remote controller is cut, due to power failure, all settings will return to original “DUAL” and “BYPASS”.
47
Page 48
A N E
T
(Y)
(W) (R) (O)
(BR)
5A
A
POWER SUPPLY
N
E
Fuse(5A)
Tie-lap
Wiring has to be changed when a 200,230 or 240V power is used.
Tie-lap
TRANSFORMER
Transmission
TERMINAL-BLOCK FOR TRANSMISSION
TERMINAL-BLOCK OF POWER SUPPLY
200
220
230
240
BACK
ACTIVE
BYPASS
POWER ON/OFF
DUAL
CENTRAL
AHEAD
ENGAGED
GROUP
ACTIVE BYPASS
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
DUAL CENTRAL
12345678910
10 9 8 7 6 5 4 3 2 1
To adaptor's terminal-block
Centralized remote controller
Non-polar, two-wire cable
To adaptor's terminal-block
Power supply board box
BACK
ACTIVE
BYPASS
POWER ON/OFF
DUAL
CENTRAL
AHEAD
ENGAGED
GROUP
ACTIVE BYPASS
GROUP SELECTION
PROGRAM TIMER
CONTROLLER OPERATION
DUAL CENTRAL
12345678910
10 9 8 7 6 5 4 3 2 1
Dip switch SW17
Centralized remote controller
Power supply board
3-3 Connection method
(1) Connections in the power supply cord.
1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-lap. Connect a single phase 200V AV (220, 230, 240V) to .
As is the GND terminal, be sure to ground the earth wire.
E
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-lap. Use a Ω1.6 (AWG 14) or above two-wire cable for the transmission line. CAUTION : Never connect the power supply cord to the transmission terminal-block.
A N
(2) Connection method of centralized remote controller and power supply board.
1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable.
2. Wiring diagram 3. Set the maximum address number with the dipswitch
SW17 on the centralized remote controller.
48
Page 49
Adaptor
200~240V AC
3-core cable 5-core cable
52
To program timer or centralized remote controller
Fig.3
CN30 CN50
CN51
Remote controller Indoor unit
Max. length of each calbe is 10m.
65
230
22
15 15
86 70
35
27
3holes
15
hole
40 80 40 27
18
4Fixing screw holes
5.5
95
220
22
35
120
12
30
200
2 2holes 2.9
74 7
8
Fig. 4
(Unit : mm)
10
ORN 1
2 3
BRN RED
4. Set the address number (from SW1-1 to SW1-6) in the dipswitch when a centralized remote controller is being used. The address is the control number of each unit in the centralized control system. As the address serves as a time-delay device as well, sequential starts (all units are triggered collec­tively by one single ON instruction)must be set with different address numbers (greater than 0) for each
9 8 7 6 5 4 3 2 1
ON
SW1
Levers No. 1-6 can set the following addresses respectively with binary notations.
Toggle32No.6 ON16No.5 ON8No.4 ON4No.3 ON2No.2 ON1No.1 ON
Address
adapter.
(Ex.1) 3 = 2 + 1 (Ex.2) 9 = 8 + 1 (Ex.3) 15 = 8 + 4 + 2 + 1
10
9 8 7 6 5 4 3 2 1
10
9 8 7 6 5 4 3 2 1
10
9 8 7 6 5 4 3 2 1
ON
5. Dimensions
(3) Connection from adaptor
ON
ON
4.TIMER ADAPTER
This adapter is needed for system control and for operation via external contacts.
Part No. PAC-SA89TA-E
49
Page 50
5. PROGRAM TIMER ADAPTER
This adapter is needed when a program timer(PAC-815PT)or a centralized remote controller(PAC-805RC)is used.
Part No. PAC-825AD
5-1 Parts included
1 ADAPTER ·························1P 2 3-core cable···························1P
Length : 2m (6' 7") Length : 2m (6' 7")
4 4-core cable···························1P
Length : 2m (6' 7") Length : 2m (6' 7")
3 3-core cable···························1P
5 5-core cable···························1P
5-2 Connection method
Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out the work.
(1) Connections in the adapter box
1. Connect the power supply cord to the terminal-block and fix it in-place with a tie-lap. Connect a single phase 200V (220, 230, 240V) AV to . As is the GND terminal, be sure to ground the earth wire.
E
A N
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-lap (when a centralized remote controller is being used.
CAUTION : Never connect the power supply cord to the transmission terminal-block
Fig-1 Fig-2
TERMINAL-BLOCK FOR TRANSMISSION
Tie-lap
Transmission cord
CN22
Dip switch
TRANS
CN1 CN21 CN51 CN30 CN42 CN50CN40
Fuse(5A)
TRANSFORMER
(AG)
SW1
A N E
POWER SUPPLY CORD
TERMINAL-BLOCK FOR POWER SUPPLY
Tie-lap
Wiring has to be changed when 200V power supply is used.
Transmission
(W)
CN22
TRANS
(B)
200
SW1
T
(Y)
240
220
5A
A
POWER SUPPLY
N E
50
Page 51
6.REMOTE INDICATION ADAPTER
Motor
Casing (Inverted corn shape)
Drain water
Suction port
Flow of drain water
Rotating blabe (Inverted triangle plate)
This adapter is used for remote indication (operation / check).
Part No. PAC-559AD
BRN
RED
7.DRAIN PUMP
Applied Service Ref.
Part No.
<Wiring>
CN51
connector (5P)
BRN RED
ORN YLW
GRN
JST XHP-3
5
1
Optional multiple display adapter
The maximum distance between indoor board and relay is 10m.
GREEN YELLOW
ORANGE
RED
BROWN
X1
X2
Electrical insulation is needed.
Wiring at the actual place
PC-2/2.5/3GJA1
PAC-SE85DM-E
ORN YLW
5
5
2
X1
X2
GRN
RL
GL
Power supply
PC-4/5/6GJSA(1) PAC-SE86DM-E
8.HIGH PERFORMANCE FILTER
9.WIRELESS KIT
Part No. PAC-SE80KF-E
Applicable Service Ref. PC-2GJA
Part No. PAC-SW93J-E
PAC-SE80KF-E
1
PC-2.5/3/4GJ(S)A
1
PAC-SE82KF-E
PC-5 / 6GJSA
51
Page 52
HEAD OFFICE : MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI,CHIYODA-KU TOKYO 100-8310, JAPAN
cCopyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Reprinted in Sep. 2003 No.OC134 REVISED EDITION-A 20 Reprinted in Apr. 2003 No.OC134 REVISED EDITION-A 100 Reprinted in May 2001 No.OC134 REVISED EDITION-A 5 Issued in Nov. 1999 No.OC134 REVISED EDITION-A 300 Issued in Mar. 1999 No.OC134 REVISED EDITION-A 50 Issued in Sep. 1998 No.OC134 REVISED EDITION-A 200 Issued in Sep. 1998 No.OC134 REVISED EDITION-A 50 Issued in Sep. 1997 No.OC134 REVISED EDITION-A 2420 Issued in Jun. 1997 No.OC134 2420 Made in Japan
New publication, effective Nov. 1999 Specifications subject to change without notice
Loading...