• Combination of outdoor units (PU3/4VAKR type) has been added in
REVISED EDITION-B.
•
Some descriptions have been modified.
• Please void OC382 REVISED
EDITION-A.
Note:
• This manual does not cover the outdoor units. When serving outdoor
units, please refer to the service manual No.OC152, OC206, OC353,
OCH/OCB414, OCH/OCB431 and
this manual in a set.
• RoHS compliant products have <G>
mark on the spec name plate.
• For servicing RoHS compliant products, refer to the RoHS Parts List.
11. PARTS LIST········································65
12. RoHS PARTS LIST·····························73
13. OPTIONAL PARTS·····························81
······22
REMOTE CONTROLLER
Page 2
1
Air outlet
Intake grille
Air intake
Left/right guide vanes
Change the direction of airflow
from the horizontal blower.
Long-life filter
Removes dust and foreign matter from air coming in
through the grille (Recommended cleaning interval :
Approx, every 2,500 operating hours).
Up/down guide vanes
Change the direction of airflow from the
vertical blower.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
ON/OFF
Temperature setting buttons
Down
Up
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button
(Set Day button)
Opening the
lid
ON/OFF button
Fan Speed button
Filter button
(<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button
(
Operation button)
To return operation
number
Ventilation button
(
Operation button)
To go to next operation
number
PART NAMES AND FUNCTIONS
● Indoor Unit
● Wired remote controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
2
Page 3
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
●
●
Display Section
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc.
*Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the
remote controller has been prohibited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, the time to be
switched off is shown.
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
To be displayed on when it is time to
clean the filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Up/Down Air Direction indicator
The indicator shows the direction of the outcoming airflow.
“One Hour Only” indicator
Room Temperature display
Shows the room temperature. The room
temperature display range is 8–39:.
The display blinks if the temperature
is less than 8: or 39: or more.
Louver display
Indicates the action of the swing louver.
Does not appear if the louver is not
running.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Note:
“PLEASE WAIT” message
This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power
failure.
“NOT AVAILABLE” message
This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have).
If a single remote controller is used to simultaneously operate multiple indoor units that are different types, this message will not be displayed as
far as any of the indoor units is equipped with the function.
Displayed if the airflow is set to
Low or downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off in 1 hour,
when the airflow direction also
changes.
3
Page 4
2
Service Ref.
External finish
Fan motor output
Airflow Low-High
External static pressure
Operation control & Thermostat
Noise level Low-High
Cond. drain connector
Dimensions
Weight
Service Ref.
External finish
Refrigerant (R-22) control
Crankcase Heater w3
Compressor output
Protection devices
Fan motor output
Capacity
Input
Indoor unitModel
Phase, Hz
Voltage
Current
Outdoor unitModel
Phase, Hz
Voltage
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
W
kW
V
A
V
A
°C
°C
°C
m
°C
°C
°C
°C
°C
D.B.
W.B.
D.B.
D.B.
W.B.
Models
Electrical circuitTotalRefrigerant circuit
Indoor side
Outdoor
side
MODE
PC-4GAKD PC-5GAKDPC-6GAKD
PC-4GAKDPC-5GAKD PC-6GAKDPC-3AKD
PC-2.5GAKD
PC-2GAKD
9,300
5.17
1, 60
220
0.95
PU-
4TJSA
3, 60
220
14.0
2.40
(24.4)
0.51
(5.2)
88.4
54.5
6.0
5
29
19
11.7
46
24
13,300
4.76
1, 50
220
0.96
PU-
5YJSA
3, 50
380
8.15
1.83
(18.7)
0.46
(4.7)
72.9
48.8
3.1
5
27
19
12.8
35
24
11,600
6.94
1, 60
220
1.20
PU-
5TJSA
3, 60
220
19.61
2.41
(24.6)
0.43
(4.4)
94.8
60.1
1.7
5
29
19
14.9
46
24
14,600
5.31
1, 50
220
0.96
PU-
6YJSA
3, 50
380
8.63
1.96
(20.0)
0.41
(4.2)
75.4
51.1
2.3
5
27
19
11.4
35
24
13,400
7.54
1, 60
220
1.20
PU-
6TJSA
3, 60
220
21.45
2.41
(24.6)
0.42
(4.3)
94.8
60.3
1.6
5
29
19
12.6
46
24
10,300
3.43
1, 50
220
0.68
PU-
4YJSA
3, 50
380
5.7
1.80
(18.3)
0.51
(5.2)
67.5
48.3
7.3
5
27
19
10.5
35
24
6,500
4.25
1, 60
220
0.70
PU-
3NJA
1, 60
220
20.9
2.54
(25.9)
0.44
(4.5)
82.0
61.6
3.6
5
29
19
12.8
46
24
PC-3GAKD
7,600
3.30
1, 50
220
0.51
PU-
3VJC
1, 50
220
15.1
1.96
(20.0)
0.44
(4.5)
87.9
52.3
3.7
5
27
19
12.2
35
24
6,200
3.60
1, 60
220
0.70
PU-
2.5NJA
1, 60
220
15.8
2.68
(27.3)
0.52
(5.3)
94.3
57.6
10.2
5
29
19
15.3
46
24
PC-2.5GAKD
6,500
2.58
1, 50
220
0.51
PU-
2.5VJA
1, 50
220
11.4
1.96
(20.0)
0.5
(5.1)
72.3
52.4
8.6
5
27
19
12.0
35
24
4,300
3.12
1, 60
220
0.61
PU-
2NJA
1, 60
220
13.6
2.49
(25.4)
0.53
(5.4)
77.7
60.5
8.3
5
29
19
13.8
46
24
PC-2GAKD
5,600
2.54
1, 50
220
0.38
PU-
2VJA
1, 50
220
11.3
1.93
(19.7)
0.44
(4.5)
68.6
51.6
3.3
5
27
19
9.7
35
24
MPa
(kgf/F)
MPa
(kgf/F)
Cooling
The unit of pressure has been changed to MPa based on SI(International System of unit) in accordance with I.S.O.(International
Organization for Standardization).
The conversion factor is : 1(MPa)=10.2(kgf / FF)
14
Page 15
Airflow
Air speed
Coverage range
Airflow
Air speed
Coverage range
m3/min
m/sec.
m
ft
m
3
/min
m/sec.
m
ft
Configuration
50Hz
Frequency
60Hz
Model
PC-4GAKD
25
4.1
12.6
41.6
25
4.1
12.6
41.6
PC-5GAKD
34
4.38
15.2
50.0
34
4.38
15.2
50.0
PC-6GAKD
34
4.38
15.2
50.0
34
4.38
15.2
50.0
PC-3GAKD
18
3.8
10.4
34.5
18
3.8
10.4
34.5
PC-2.5GAKD
18
3.8
10.4
34.5
18
3.8
10.4
34.5
Ceiling suspended
PC-2GAKD
13
3.7
8.8
29
13
3.7
8.8
29
The unit of pressure has been changed to MPa based on SI(International System of unit) in accordance with I.S.O.(International
Capacity
Input
Indoor unitModel
Phase, Hz
Voltage
Current
Outdoor unitModel
Phase, Hz
Voltage
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
w The air coverage range is the distance to which the 0.25 m/sec. air can reach when air is blown out horizontally from the unit
at the High notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room.
15
Page 16
4
180
210
157
15
85
182 (3/8) liquid
201 (5/8) gas
241 (Drainage)
Air intake
918
254
680
Electrical box
226
70
525
928
352
263
171
138
86
46
1751
131
38
38 79
161
32
179
42
6-7
Celling
Electrical box
When electrical
box is pulled
down
3
2
8
5
1
4
6
2
1
17
150
140
70
320
80
933 (suspension bolt pitch)
983
1000
Air outlet
81
904
76
Gap to ceiling
OUTLINES AND DIMENSIONS
4-1. INDOOR UNIT
PC-2GAKD
1 Drainage pipe connection (Unit side: 26mm I.D.)5
2 Drainage pipe connection (for the left arrangement)6 Knockout hole for upper pipe arrangement
3 Knockout hole for left drain-piping arrangement7 Knockout hole for left drain pipe arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection)8 Knockout hole for wiring arrangement
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When installing the drain-up machine (option parts),
please be sure that refrigerant pipe will be only upper pipe arrangement.
Please set the voltage
using the remote controller.
For the setting method,
please refer to the indoor
unit Installation Manual
SW6
SWE
ON
OFF
ON
OFF
1 2
SW2 SW5SW1
Refer to tables 1, 2, 3 .
WHT
(
D.SENSOR
)
CN31
WHT
(
D.SENSOR
)
CN31
DS
WHT
(
WIRELESS
)
CN90
1 21 23
RED
(INTAKE)
CN20
1 2
WHT
(PIPE)
CN21
BLU
(
REMOCON
)
CN22
BLK
(
INDOOR/OUTDOOR
COMUNICATION
)
CN30
1 21 2
TH1TH2
6
R.B
CN41 CN2L
CN51 CN32
W.B
(OPTION)
CNB
RECEIVER
RU
LED1
LED1
LED2
LED2 SW2 SW1
X4X1
I.B
P.B
CNSK
(RED)
DC13.1V
CN2S
(WHT)
TO OUTDOOR UNIT
POWER SUPPLY
~(1 PHASE)
220-240V 50Hz
220V 60Hz
TB4
TB2
1
2
3
L
N
GRN/YLW
Table 2
SW2
1 2 3 4 5
ON
OFF
MODELS
PC-2GAKD
1 2 3 4 5
ON
OFF
PC-2.5GAKD
1 2 3 4 5
ON
OFF
MODELS
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
PC-3GAKD
PC-4GAKD
PC-5GAKD
PC-6GAKD
1 2 3 4 5
ON
OFF
ZNR
WHT
(FAN)
FAN
RED
(PUMP)
CN27
GRN
(VANE)
CN6V
BLU
(D.U.M)
CNP
X1
FUSE
RED
(D.HEATER)
CNC
(OPTION)
ORN
(POWER)
CND
RED
(POWER
BOARD)
CNDK
WHT
(POWER
BOARD)
CN2D
1 31 3 1 31 31 3
1 2
1 2
3
1
2
5
1 3 5
BLK
WHT WHT
RED
RED
YLW
ORN
BLU
BLU
RED
BLK
WHT
WHT
BLU
MF
MV
DP
BCR
X4
9
1 2 3
1 2 3
2
1
TB5
TRANSMISSION WIRES DC12V
TB6
12
BZ
w
When installing optional
drain-up machine, disconnect
the CN31 jumper connector
and replace it with the
drain sensor (DS).
When installing drain-up
machine (Optional part)
SW1
Table 1
1 2 3 4 5
ON
OFF
SW5
Table 3
1 2 3 4 5 6 7 8
ON
OFF
SW2
[Servicing]
Fasten terminal of the terminal board "TB4" that equips lock system.
To remove the fastened terminal, pull it while pressing the protruding
portion (locking lever) of the terminal. The fastened terminal protruding
portion should face upward.
Check code
Symptom
Fb
Abnormality of indoor controller board
FFFF
No corresponding unit
No trouble generated in the past
P4
Abnormality of drain sensor(DS)
P5
Malfunction of drain-up machine
P6
Freezing / overheating protection is working.
P8
Abnormality in outdoor unit
Refer to outdoor unit wiring diagram.
P2
Abnormality of pipe temperature thermistor / Liquid(TH2)
P1
Abnormality of room temperature thermistor(TH1)
E0–E5
Abnormality of the signal transmission between remote
controller and indoor unit
1. Since the outdoor side electric wiring may change, be sure to
check the outdoor unit electric wiring diagram for servicing.
2. Indoor and outdoor connecting wires have poIarities, make
sure to match terminal numbers (1, 2, 3) for correct wirings.
3. SymboIs used in wiring diagram above are,
: Connector, : Terminal (block).
[Self-diagnosis]
1. For details on how to operate self-diagnosis with the wireless
remote control, refer to the technical manuals etc.
2. For the wired remote control : When you quickly press twice the
CHECK switch on the remote control, the unit begins self-diagnosis,
and Check Codes generated in the past appear on the display.
For Check Codes and Symptoms refer to the table.
[Emergency operation procedure]
1.When the indoor unit microcomputer has failed, but all other components
work properly, if you set the switch(SWE,SW6) on the indoor control
board, the indoor unit will begin Emergency Operation.
2.When you activate emergency operation of the cooling, you have to set
the switch(SWE) and switch(SW6) on indoor controller.
SWE:ON ·Indoor fan is running at high speed.
·Drain-up machine(optional) is working.
SW6-1:ON ·Emergency operation of cooling mode
3.Before you activate emergency operation, check the following points:
(1) Emergency operation cannot be activated when:
· The outdoor unit malfunctions. · The indoor fan malfunctions.
(2) Emergency operation becomes continuous only by switching the power
source on / off. ON / OFF on the remote control or temperature control
etc. does not function.
(3) Emergency cooling should be limited to 10 hours maximum
(The indoor unit heat exchanger may freeze).
(4) After emergency operation has been deactivated, set the switches etc.
to their original positions.
(5) Movement of the vanes does not work in emergency operation, therefore
you have to slowly set them manually to the appropriate position.
Judge what is wrong and take a corrective action
according to “SELF-DIAGNOSIS ACTION TABLE” (7-3).
Identify the cause of the trouble and take a corrective
action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (7-4).
The trouble is not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
trouble occurred, and wiring related.
2Reset error code logs and restart the unit after finishing
service.
3There is no abnormality in electrical components,
controller boards, and remote controller.
1Recheck the abnormal symptom.
2Identify the cause of the trouble and take a corrective
action according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (7-4).
3Continue to operate unit for the time being if the cause
is not ascertained.
4There is no abnormality in electrical components,
controller boards, remote controller etc.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
1 Turn on the power.
2 Press the [CHECK] button twice.
3 Set address with [TEMP] button if system control is used.
4 Press the [ON/OFF] button to stop the self-check.
A CHECK button
B Address
C TEMP. button
D IC : Indoor unit
OC: Outdoor unit
E Check code
F Unit No.
G Timer ON/OFF button
A
F
C
BBEED
G
<To cancel check code>
1 Display the error code at the self-check result display screen.
2 The address for self-check will blink when the
G ON/OFF
button is pressed twice within 3 seconds.
– – – – : No trouble generated in the past
F F F F : No corresponding unit
7-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.
Actions to be taken for service, which depends on whether or not the trouble is reoccurring at service, are summarized in the
table below. Check the contents below before investigating details.
7-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
■ Wired remote controller
27
Page 28
Symptom
Cause
Wired remote controller
On the wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller can be received.
• Operation lamp is blinking.
• The buzzer makes a short ping sound.
PLEASE WAIT
PLEASE WAIT → Error code
No messages appear even
when operation switch is
turned ON (operation lamp
does not light up).
For about 2
minutes after
power-on
Subsequent to
about 2 minutes
after power-on
• For about 2 minutes after power-on,operation of the remote controller is not possible
due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection
device is not connected.
•Reverse or open phase wiring for the outdoor
unit’s power terminal block
•Incorrect wiring between indoor and outdoor
units
•Remote controller wire short
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer)Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for wired remote controller)
Indicates whether power is supplied to the wired remote controller.
This LED lights only in the case of the main indoor unit.
•
If the unit cannot be operated properly after the test run, refer to the following table to find out the cause.
• On wired remote controller
1Check code displayed in the LCD.
1 Check code
SymptomRemark
Wired remote controller
P1
Intake sensor error
P2Pipe (TH2) sensor error
P4Drain sensor error
P5
PA
Drain pump error
Forced compressor stop
P6Freezing/ Overheating protection operation
P8Pipe temperature error / Outdoor unit error
E4, E5Remote controller signal receiving error
–
–
–
–
FbIndoor unit control system error (memory error, etc.)
E0, E3
E1, E2Remote controller control board error
Remote controller transmission error
28
Page 29
7-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
P2
Abnormal point and detection method
Room temperature thermistor (TH1)
1 The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 minutes. (The unit returns to normal operation, if it has been normally reset.)
2 Constantly detected during cooling,
drying, and heating operation.
Short: 90: or more
Open: -40: or less
Pipe temperature thermistor/Liquid (TH2)
1 The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 minutes. (The unit returns to normal operation, if it has been normally reset.)
2 Constantly detected during cooling,
drying, and heating (except defrosting)
operation.
Short: 90: or more
Open: -40: or less
Note: Refer to the manual of outdoor unit for the details of display
such as F, U, and other E.
Cause
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN20) on the indoor controller
board (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective indoor controller
board
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN21) on the indoor controller
board (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective refrigerant circuit is
causing thermistor temperature
of 90: or more or -40: or
less.
5 Defective indoor controller board
Countermeasure
1–3 Check resistance value of thermistor.
0:15.0k"
10:9.6k"
20:6.3k"
30:4.3k"
40:3.0k"
If you put force on (draw or bend) the lead
wire with measuring resistance value of thermistor, breaking of wire or contact failure can
be detected.
2 Check contact failure of connector (CN20)
on the indoor controller board. Refer to 7-7.
Turn the power back on and check restart
after inserting connector again.
4 Check room temperature display on remote
controller.
Replace indoor controller board if there is
abnormal difference with actual room
temperature.
Turn the power off, and on again to operate
after check.
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN21)
on the indoor controller board. Refer to 7-7.
Turn the power on and check restart after
inserting connector again.
4 Check pipe <liquid> temperature with
remote controller in test run mode. If pipe
<liquid> temperature is extremely low (in
cooling mode) or high (in heating mode),
refrigerant circuit may have defective.
5 Check pipe <liquid> temperature with remote
controller in test run mode. If there is extreme
difference with actual pipe <liquid> temperature, replace indoor controller board.
P4
P5
Drain sensor (DS)
1 Suspensive abnormality, if short/open of
thermistor is detected for 30 seconds
continuously.
Turn off compressor and indoor fan.
2 Short/open is detected for 30 seconds
continuously during suspensive
abnormality.
(The unit returns to normal operation,
if it has been normally reset.)
3 Detect the following condition.
• During cooling and drying operation
• In case that pipe <liquid> temperature
- room temperature <-10deg
(Except defrosting)
• When pipe <liquid> temperature or
room temperature is short/open
temperature.
• During drain pump operation
Drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor heats itself and
temperature rises slightly. Turn off
compressor and indoor fan.
2 Drain pump is abnormal if the condition
above is detected during suspensive
abnormality.
3 Constantly detected during drain pump
operation
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN31) on the indoor controller
board (Insert failure)
3 Breaking of wire or contact
failure of drain sensor wiring
4 Defective indoor controller board
1 Malfunction of drain pump
2 Defective drain
Clogged drain pump
Clogged drain pipe
3 Attached drop of water at the
drain sensor
• Drops of drain trickles from
lead wire.
• Clogged filter is causing
wave of drain.
4 Defective indoor controller board
Turn the power off, and on again to operate
after check.
1–3 Check resistance value of thermistor.
0:6.0k"
10:3.9k"
20:2.6k"
30:1.8k"
40:1.3k"
2 Check contact failure of connector (CN31)
on the indoor controller board. Refer to 7-7.
Turn the power back on and check restart
after inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited,
and abnormality reappears.
Turn the power off, and on again to operate
after check.
1 Check if drain-up machine works.
2 Check drain function.
3 Check the setting of lead wire of drain sen-
sor and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited
and abnormality reappears.
Refer to 7-7.
Turn the power off, and on again to operate
after check.
29
Page 30
Error Code
P6
Abnormal point and detection method
Freezing/overheating protection is
working
1 Freezing protection (Cooling mode)
The unit is in 6-minute resume prevention
mode if pipe temperature stays under
-15: for 3 minutes, 3 minutes after the
compressor started. Abnormal if it stays
under -15: for 3 minutes again within
16 minutes after 6-minute resume prevention mode.
<Frost prevention mode>
If pipe temperature is 1: or below
when 16 minutes has passed after compressor starts operating, unit will start
operating in frost prevention mode which
stops compressor operation. After that,
when pipe temperature stays 10: or
more for 3 minutes, frost prevention
mode will be released and compressor
will restart its operation.
Cause
(Cooling or drying mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Low-load (low temperature)
operation out of the tolerance
range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
defective.
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
(clogs)
Countermeasure
(Cooling or drying mode)
1 Check clogs of the filter.
2 Remove shields.
4 Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector
(FAN) on the indoor controller board.
WThe indoor controller board should be
normal when voltage of AC 220~240V is
detected while fan motor is connected.
Refer to 7-7.
5 Check outdoor fan motor.
67 Check operating condition of refrigerant
circuit.
Pipe temperature
<Cooling mode>
Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes after compressor start and 6 minutes
after the liquid pipe is out of cooling range.
Note 1) It takes at least 9 minutes to
detect.
Note 2) Abnormality P8 is not detected in
P8
E0
or
E4
drying mode.
Cooling range : -5 deg ] (TH2-TH1)
TH2: Liquid pipe temperature
TH1: Intake temperature
troller cannot receive any transmission
normally from indoor unit of refrigerant
address “0” for 3 minutes.
(Error code : E0)
2 Abnormal if sub remote controller could
not receive for any signal for 2 minutes.
(Error code: E0)
1 Abnormal if indoor controller board can
not receive any data normally from
remote controller board or from other
indoor controller board for 3 minutes.
(Error code: E4)
2 Indoor controller board cannot receive
any signal from remote controller for 2
minutes. (Error code: E4)
1 Slight temperature difference
between indoor room
temperature and pipe temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
thermistor
• Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units
connection)
3 Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
4 Defective detection of indoor
room temperature and pipe
temperature thermistor
5 Stop valve is not opened
completely.
1 Wrong wiring of indoor/outdoor
connecting wire
2 Reversed phase
3 Protection device is working.
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as “sub” remote controller. In
this case, E0 is displayed on
remote controller, and E4 is
displayed at LED (LED1, LED2)
on the outdoor controller circuit
board.
3 Miswiring of remote controller
4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board
of refrigerant address “0”
6 Noise has entered into the
transmission wire of remote
controller.
1~4Check pipe temperature with room
temperature display on remote controller.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
1 Check the indoor/outdoor connecting wire.
2 Change the connection of electric wiring.
3 Check the protection device.
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main”,
if there is no problem with the action above.
3 Check wiring of remote controller.
• Total wiring length: max. 500m
(Do not use cable x 3 or more.)
• The number of connecting indoor units:
max. 16 units
• The number of connecting remote controller: max. 2 units
When it is not the above-mentioned problem of
1~3
4 Diagnose remote controllers.
a) When “RC OK” is displayed,
remote controllers have no problem.
Turn the power off, and on again to
check. If abnormality generates again,
replace indoor controller board.
b) When “RC NG” is displayed,
replace remote controller.
c)When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormality.
∗ If the unit is not normal after replacing
indoor controller board in group control,
indoor controller board of address “0”
may be abnormal.
find blank of transmission path for 6 seconds and could not transmit.
(Error code: E3)
2 Remote controller receives transmitted
data at the same time and compares the
received and transmitted data. Abnormal
if these data are judged to be different
30 continuous times. (Error code: E3)
1 Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2 Indoor controller board receives trans-
mitted data at the same time and compares the received and transmitted data.
Abnormal if these data are judged to be
different 30 continuous times. (Error
code: E5)
Cause
1 Two remote controller are set
as “main.”
(In case of 2 remote controllers)
2 Remote controller is connected
with 2 indoor units or more.
3 Repetition of refrigerant
address
4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller
board
6 Noise has entered into trans-
mission wire of remote controller.
Countermeasure
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting.
4~6 Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem.
Turn the power off, and on again to check.
When becoming abnormal again, replace
indoor controller board.
b)When “RC NG” is displayed, replace
remote controller.
c)When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormali-
ty.
Indoor controller board
Abnormal if data cannot be read normally
Fb
from the nonvolatile memory of the indoor
controller board.
Remote controller control board
1 Abnormal if data cannot be read normal-
ly from the nonvolatile memory of the
E1
or
E2
PA
remote controller control board.
(Error code: E1)
1 Abnormal if the clock function of remote
controller cannot be normally operated.
(Error code: E2)
Forced compressor stop
(due to water leakage abnormality)
Forced compressor stop
(due to water leakage abnormality)
1 When the liquid pipe temperature sub-
tracted with the intake temperature is
less than -10:, drain sensor is detected
whether it is soaked in the water or not
at the interval of 90 seconds. (Drain
pump will start operating when the drain
sensor is detected to be soaked in the
water.)
2 The unit has a water leakage abnormali-
ty when the following conditions, a) and
b), are satisfied while the above-mentioned detection is performed.
a) The drain sensor is detected to be
soaked in the water 10 times in a row.
b) The liquid pipe temperature subtract-
ed with the intake temperature is
detected to be less than -10: for a
total of 30 minutes. (When the drain
sensor is detected to be NOT soaked
in the water, the detection record of a
and b will be cleared.)
3 The drain sensor detection is performed
in operations other than cooling. (When
the unit stops operating, during heating
or fan operation, when the unit stops
because of some abnormality)
*Once the water leakage abnormality is
detected, abnormality state will not be
released until the main power is reset.
3 Open circuit of drain sensor
4 Contact failure of drain sensor
connector
5 Dew condensation on drain
sensor
· Drain water descends along
lead wire.
· Drain water waving due to filter
clogging
6 Extension piping connection
difference at twin system
7 Miswiring of indoor/ outdoor
connecting at twin system
8 Room temperature thermistor /
liquid pipe temperature thermistor detection is defective.
1 Replace indoor controller board.
1Check the drain pump operation.
2Check whether water can be drained.
3Check the resistance of the drain sensor.
4Check the connector contact failure.
5Check the drain sensor lead wire mounted.
Check the filter clogging.
6Check the piping connection.
7Check the indoor/ outdoor connecting wires.
8Check the room temperature display of
remote controller.
31
Page 32
7-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
Phenomena
(1)LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is also off.
1 Power supply of 220~240V AC is not supplied to
indoor unit.
2 Defective indoor controller board
3 Defective indoor power board
Cause
Countermeasure
1 Check the voltage of indoor power supply
terminal block (L,N).
• When AC220~240V is not detected,
check the power supply wiring.
• When AC220~240V is detected,
check 2 (below).
2 Check voltage output from CNDK on
indoor controller board.
• When AC220~240V is not detected,
check the fuse on indoor controller
board.
Check the wiring connection between
indoor power supply terminal block, and
CND on indoor controller board.
• When AC220~240V is detected,
check 3 (below).
3 Check voltage output from CN2S on
indoor power board.
• When no voltage output.
check the wiring connection between
CNDK on indoor controller board and
CNSK on indoor power board.
If no problem are found, indoor power
board is defective.
• When DC12.5~13.7V is detected,
check the wiring connection between
CN2S on indoor power board and
CN2D on indoor power board.
If no problem are found, indoor controller board is defective.
(2)LED2 on indoor controller board
is blinking.
• When LED1 on indoor controller board is lit.
1 Mis-setting of main/sub for indoor unit
(There is no unit corresponding to main unit.)
• When LED1 on indoor controller board is also blinking.
Connection failure of indoor/outdoor unit connecting
wire
• When LED1 is lit.
1 Miswiring of remote controller wires
When 2 indoor units are wired in one refrigerant
system, each indoor unit sets as main unit. (SW5-3)
2 Short-cut of indoor/outdoor unit connecting wire
3 Short-cut of remote controller wires
4 Defective remote controller
1 Check the setting of main/sub for indoor
unit.
Set the main unit.
Set main/sub using SW5-3 on indoor
controller board.
Check indoor/outdoor unit connecting wire
for connection failure.
1 Check the connection of remote con-
troller wires in case of twin triple indoor
unit system. When 2 or more indoor units
are wired in one refrigerant system,
connect remote controller wires to one of
those units.
2 Remove indoor/outdoor connecting wires
and check LED2 on indoor controller
board.
• When LED2 is blinking, check the shortcut of indoor/outdoor connecting wires.
• When LED2 is lit, connect indoor/outdoor
connecting wires again, and; if LED2 is
blinking, outdoor unit’s controller board is
defective; if LED2 is lit, connection failure
of indoor/outdoor terminal block etc. has
returned to normal.
34 Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the
short-cut of remote controller wires.
• When LED2 is lit, connect remote
controller wires again and:
if LED2 is blinking, remote controller
is defective; if LED2 is lit, connection
failure of remote controller terminal
block etc. has returned to normal.
32
Page 33
Phenomena
After completing installation and the wiring and piping of the indoor and outdoor units, check for refrigerant leakage,
looseness in the power supply or control wiring, wrong polarity, and no disconnection of 1 phase in the supply.
Use a 500-volt megohmmeter to check that the resistance between the power supply terminals and ground is at
least 1.0M".
Do not carry out this test on the control wiring (low voltage circuit) terminals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0M".
▲▲▲
B
EF
C
H
G
JM
A
D
ûC
ûC
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
ON/OFF
TEST RUN
COOL, HEAT
I
A ON/OFF button
B Test run display
C Liquid pipe(Indoor unit)
temperature display
D ON/OFF lamp
E Power display
F Error code display
Test run remaining time display
G Set temperature button
H Mode selection button
I Fan speed button
J Air direction button
M TEST button
1 Turn on the power at least 12 hours before the test run.
2 Press the [TEST] button twice. ➜ "TEST RUN" liquid crystal display
3 Press the [Mode selection] button. Make sure that air is blown out.
4 Press the [Mode selection] button and switch to the cooling mode.
➜ Make sure that cool air is blown out.
5 Press the [Fan speed] button. ➜ Make sure that the fan speed is switched.
6 Press the [Air direction button]. ➜Check operation of the vane.
7 Check operation of the outdoor unit fan.
8 Release test run by pressing the [ON/OFF] button. ➜ Stop
9 Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error
occurs can be registered in the remote controller. The telephone number will be
displayed when an error occurs. For registration procedures, refer to the operation
manual for the indoor unit.
(3)Upward/downward vane
performance failure
(4)Receiver for wireless remote
controller
1 Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
• Up/down vane setting is “No vanes”.
2 Upward/downward vane does not work.
• The vane is set to fixed position.
1 Weak batteries of wireless remote controller
2 Contact failure of connector (CNB) on wireless
remote controller board (Insert failure)
3 Contact failure of connector (CN90) on indoor con-
troller board(Insert failure)
4 Contact failure of connector between wireless
remote controller board and indoor controller board
Cause
7-5. TEST RUN AND EMERGENCY OPERATION
7-5-1. Before test run
Countermeasure
1 Check 1 (left).
• Check the vane motor. (Refer to “How
to check the parts”.)
• Check for breaking of wire or connection failure of connector.
• Check “Up/down vane setting”. (Unit
function selection by remote controller).
2 Normal operation (Each connector on
vane motor side is disconnected.)
1 Replace batteries of wireless remote con-
troller.
2~4
Check contact failure of each connector.
If no problems are found of connector,
replace indoor controller board. When
the same trouble occurs even if indoor
controller board is replaced, replace wireless remote controller board.
7-5-2. Test run (Using wired remote controller)
33
Page 34
7-5-3. When wired remote controller or indoor unit micro computer troubles
1.When the wired remote control or the indoor unit microcomputer has failed, but all other components work if you set the
switch (SWE, SW6) on the indoor control board, the indoor unit will begin properly
Emergency Operation.
wNote on the wireless remote control: When the remote control does not function, it is possible to activate Emergency
Operation by using the indoor unit emergency operation switch (SW1,SW2 of the wireless signal receiver board). However,
if the indoor unit microcomputer has failed, it is necessary to proceed with points 2 and 3 below as in the case of the
wired remote controller.
2.When you activate emergency operation of the cooling, you have to set the switch (SWE) and switch (SW6) on the indoor
controller.
SWE : ON • Indoor fan is running at high speed. • Drain-up machine is working.
SW6-1 : ON • Emergency operation of cooling mode
3.Before you activate emergency operation, check the following points:
(1) Emergency operation cannot be activated when:
• the outdoor unit malfunctions. • the indoor fan malfunctions.
• when it has detected the malfunction of drain-up machine during self-diagnosing.
(2) Emergency operation becomes continuous only by switching the power source on/off. ON/OFF on the remote control or
temperature control etc,dose not function.
(3) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze).
(4) After emergency operation has been deactivated, set the switches etc.to their original positions.
(5) Movement of the vanes does not work in emergency operation, therefore you have to slowly set them manually to the
appropriate position.
34
Page 35
7-6. HOW TO CHECK THE PARTS
1
1
2
2
3
3
Red
White
Black
Relay connector
Protector
1
3
Gray
Gray
4
5
2
361
Orange
Red
Pink
Yellow Brown Blue
M
4
2
5
31
Pink
Orange
Red
Yellow Blue
M
OFF:130i 5:
ON : 80i 20:
Parts nameCheck points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 10:~30:)
(Refer to the next page for a detail.)
Room temperature
thermistor (TH1)
Pipe temperature
thermistor (TH2)
Normal
4.3k"~9.6k"
Abnormal
Open or short
Measure the resistance between the terminals with a tester.
(Winding temperature 20:)
Measure the resistance between the terminals with a tester.
(Winding temperature 20:)
CNDK
Connect to the indoor
power board (CNSK)
(220~240V AC)
SW6
Emergency operation
FUSE
(6.3 A 250 V)
CND
Power supply input
(220~240V AC)
CNP
Drain-pump output
(DP)
(220~240V AC)
CN2D
Connect to the indoor
power board (CN2S)
(12.5~13.7V DC)
LED1
Power supply (I.B)
LED2
Power supply (R.B)
CN22
Connect to the terminal
block(TB5)
(Remote controller connecting
wire)
(10.4~14.6V DC)
CN30
Transmission
(Indoor/outdoor)
CN20
Room temperature
thermistor (TH1)
CN21
Pipe temperature
thermistor/Liquid (TH2)
CN31
Drain sensor (DS)
CN90
Connect to the wireless
remote controller board
(CNB)
CN6V
Vane motor output
(MV)
CN41
Connector (HA terminal-A)
CN105 / CN92
(RED)
CN51
Centrally control
SWE
Emergency operation
FAN
Fan motor output
Jumper wire J41, J42
Pair number setting with
wireless remote controller
38
SW2
Capacity setting
SW1
Model setting
CN24
Heater output
(12V DC)
CN32
Remote switch
CN2L
Connector
(LOSSNAY)
SW5
System setting
Page 39
7-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control P.C. board.
(Marks in the table below) Jumper wire ( : Short : Open)
Jumper wire
SW1
SW2
SW5
Functions
Model
settings
Capacity
settings
System
settings
Setting by the dip switch and jumper wire
SW1
1 2 3 4 5
MODELS
PC-2GAKD
PC-2.5GAK
D
PC-3GAKD
PC-4GAKD
PC-5GAKD
PC-6GAKD
ON
OFF
SW2
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
SW5
1 2 3 4 5 6 7 8
ON
OFF
Remarks
SW5-3 Main/Sub setting
OFF : Main ON : Sub
SW5-4 Rotation operation setting
OFF : Not available ON : available
J41
J42
Pair number
setting with
wireless
remote
controller
Wireless remote
controller setting
0
1
2
3 ~ 9
Control PCB setting
J41J42
<Initial setting>
Wireless remote controller: 0
Control PCB: (for both J41 and J42)
4 pair number settings are supported.
The pair number settings of the wireless remote
controller and indoor control PCB (J41/J42) are
given in the table on the left.
(' ' in the table indicates the jumper wire is disconnected.)
39
Page 40
8
Function
Settings
Mode No.
Setting No.
: Initial setting
(when sent from the factory)
Remarks
Power failure
automatic recovery
Indoor temperature
detecting
LOSSNAY
connectivity
Power supply
voltage
Frost prevention
temperature
Humidifier control
Rotation
OFF
ON
Indoor unit's (Main) internal sensor
Remote controller's internal sensor W1
Not supported
Supported
(Indoor unit does not intake outdoor air through LOSSNAY
)
Supported
(Indoor unit intakes outdoor air through LOSSNAY)
240V
220V,230V
1: (Normal)
-3:
When the compressor operates, the humidifier also operates.
When the fan operates, the humidifier also operates.
24h cycle
168 cycle
Backup function
1
2
1
2
3
1
2
3
1
2
1
2
1
2
1
2
3
01
02
03
04
15
16
20
The setting is
applied to all
the units in the
same
refrigerant
system.
FunctionSettings
No.
Mode
No.
Setting
: Initial setting (Factory setting
)
- : Not available
4-Way cassette
Ceiling
concealed
Ceiling
suspended
Wall
mounted
Floor
standing
PL-AAK
PE-EAK
PC-GAK
PK-GAKL
PS-GAK
PK-FAKL
Filter sign
100Hr
1
2500Hr
072
No filter sign indicator
3
Airflow
QuietStandard
1---
(
Fan speed
)
Standard
High ceiling1
082---
High ceiling
High ceiling2
3---
No.of air outlets4 directions1----
3 directions092---2 directions
3-----
Optional high efficiency
Not supported
10
1
---
filter
Supported
2
---
Vane setting
No vanes (Vane No.3 setting:PL-AAKonly
)
1---
Vane No.1 setting
112---
Vane No.2 setting
3---
Energy saving airflowDisabled
12
1
---
(
Heating mode
)
Enabled
2
---
Optional humidifier
Not supported
13
1
----
(
PLH-AAK(H) only
)
Supported
2
----
Vane differential setting
No.1 setting (TH2: 24-28:
)
1- -
in heating mode
No.2 setting (Standard, TH2:28-32:
)
142--
(
cold wind prevention
)
No.3 setting (TH2: 32-38:
)
3- -
Swing
Not available
23
1
--
Available
2
24
1
2
--
Quiet operation mode
Disabled (Standard
)
26
1
----
of PL-AAK(Fan speed
)
Enabled (Quiet operation mode
)
2
----
Fan speed when the
Set fan speed
27
1
cooling thermostat is OFF
Stop
2
Detection of abnormality ofAvailable
28
1
the pipe temperature (P8
)
Not available
2
}
PL-AAK
PL-KAK
-
-
-
-
Fan speed when theExtra low1
heating thermostat is OFF
Stop
252
Set fan speed
3
Set temperature in heatingAvailable
mode (4 deg up
)
Not available
FUNCTION SETTING
8-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be
done by the remote controller. Select function available from the table 1.
(1) Functions available when setting the unit number to 00 (Select 00 referring to 4 Set the indoor unit number.)
W1 The functions below are available only when the wired remote controller is used. The functions are not available for
floor standing models.
<Table 1> Function selections
(2) Functions available when setting the unit number to 01-02
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to 4 Set the
indoor unit number.
• When setting functions for a simultaneous twin indoor unit system, set the unit number to 01 to 02 for each indoor
unit in case of selecting different functions for each unit referring to 4 Set the indoor unit number.
40
Page 41
8-1-1. Selecting functions using the wired remote controller
First, try to familiarize yourself with the flow of the function selection procedure. In this section, an example of setting the
room temperature detection position is given.
For actual operations, refer to steps 1 to 0 .
Setting number
AddressUnit number
Mode number
F
E
G
C
D
J
B
A
I
Modes 01 to 14 can be activated
by pressing buttons
A
and
B
simultaneously, and modes 15 to
28 by pressing buttons
B
and J.
Example of units operationFig. 1
(Setting No. = 01 or 02)
Main Unit is abnormal.
Operation starts Main➝SubSub➝Main
(Setting No. = 02
• • •
168hours cycle)
Outdoor
unit
(Setting No. = 03)
Main Unit is abnormal.
Indoor
Operation startsMain➝Sub
unit
Remote
Controller
Main➝Sub
ON
OFF
OFF
ON
OFF
ON
ON
OFF
Rotation setting (Function setting mode No.20
)
This function is available when only 2 indoor units are connected to each outdoor unit as Fig.1.
Function setting
FeaturesIndoor controller board
Mode No.
Setting No.
SW5-3 settingSW5-4 setting
2001
(
24hours cycle
)
02ON
OFF : Main
ON : Sub
(
168hours cycle
)
03
(
Back up function
)
When abnormality occurs while operating
,
it
changes as a backup unit
,
and operating continues.
Each system operates alternately for 24hours.
Each system operates alternately for 168hours.
Main
indoor
unit
Sub
indoor
unit
Main
indoor
unit
Sub
indoor
unit
24h24h
Main
Sub
41
Page 42
Selecting functions using the wired remote controller
The above procedure must be carried out only if changes are necessary.
1 : 1 systemSimultaneous twin systemRotation system
Indoor unit
address = 00
unit No. = 01
Main indoor unit
address = 00
unit No. = 01
Sub indoor unit
address = 01
unit No. = 02
Outdoor unit
Indoor unit
Remote controller
Outdoor unitOutdoor unitOutdoor unit
Main
indoor unit
Sub
indoor unit
Remote controller
Main indoor unit
address = 00
unit No. = 01
Sub indoor unit
address = 01
unit No. = 01
Main
indoor unit
Sub
indoor unit
Remote controller
1
Check the function selection setting.
2
Switch to function setting mode.
(Press
A
and B at the same time
For modes 15 and higher,
press
with the remote controller stopped.)
3
Specify address.
(Use
C
4
Specify unit No.
and D.)
Refer to address and unit No. to the figure
below.
J
and B at the same time.
5
Enter the setting.
(Press
E
.)
(Specified indoor unit:
FAN operation)
NO
6
Select mode No. 02
(room temperature detection position).
7
Select setting No. 03 (remote controller fixed).
(Use
F
and G.)
8
Enter the setting.
E
(Press
.)
Finished
Example:
Selecting room temperature
detection position
NO
YES
0
Ending of function display
(Press
A
and B at the same time.)
YES
Change address
and unit No.
9
42
Page 43
[Operating Procedure]
1 Check the setting items provided by function selection.
If settings for a mode are changed by function selection, the functions of that mode will be changed accordingly. Check all the current settings according to steps 2
to 7 , fill in the "Check" column in Table 1, and then change them as necessary. For initial settings, refer to the indoor unit's installation manual.
2 Switch off the remote controller.
A Hold down the
buttons
and then the remote controller's display content will change as shown below.
* If the unit stops after
Check to see if there are any sources of noise or interference near the transmission path.
Note :
If you have made operational mistakes during this procedure, exit function selection (see step 0 ), and then restart from step 2 .
4 Set the indoor unit number.
D Press the
area.
FILTER
simultaneously for at least 2 seconds.
Address
display section
FUNCTION
flashed for 2 seconds or "88" flashes in the room temperature display area for 2 seconds, a transmission error may have occurred.
SELECTION
ON/OFF
button so that " - -" flashes in the unit number display
Unit number
display section
FUNCTION
SELECTION
B and ( mode 15 or more)
TEST
will start to flash,
3 Set the outdoor address.
C Press the [ CLOCK] buttons ( and ) to select the desired
address. The address changes from "00" to "15".
C Press the [
of the indoor unit for which you want to perform function selection. The unit
number changes to "00", "01", "02","03",04" and "AL" each time a button is
pressed.
CLOCK] buttons ( and ) to select the unit number
* To set modes 01 to 06 or 15 to 22, select unit number "00".
* To set modes 07 to 14 or 23 to 28, carry out as follows:
• To set each indoor unit individually, select "01" to "04".
• To set all the indoor units collectively, select "AL".
5 Check the address and unit number.
E Press the
number.
After a while, "- - " will start to flash in the mode number display area.
Mode number
display section
*"88" will flash in the room temperature display area if the selected address
does not exist in the system.
Furthermore, if
address display area also flashes, there are no units that correspond to the
selected unit number. In this case, the address and unit number may be incorrect,
so repeat steps 2 and 3 to set the correct ones.
6 Select the mode number.
F Press the [TEMP] buttons ( and ) to set the desired mode
number.
(Only the selectable mode numbers can be selected.)
7 Select the setting content for the selected mode.
G Press the
flash, so check the currently set content.
8 Register the settings you have made in steps 3 to 7 .
E Press the
to flash and registration starts.
MODE
button to confirm the address and unit
MODE
"F"
appears and flashes in the unit number display area and the
button. The currently selected setting number will
MENU
Setting number display section
button. The mode number and setting number will start
Setting number 1 = Indoor unit's internal sensor
E When the address and unit number are confirmed by pressing the
button, the corresponding indoor unit will start fan operation. This
MODE
helps you find the location of the indoor unit for which you want to perform function
selection. However, if "00" or "AL" is selected as the unit number, all the indoor
units corresponding to the specified address will start fan operation.
Example) When the address is set to 01 and the unit number is 02.
00 address
Outdoor unit
Indoor unit
Designate operation
* When grouping different systems, if an indoor unit other than the
one to which the address has been set to perform fan operation,
there may be another address that is the same as the specified one.
In this case, check the DIP switch of the outdoor unit to see
whether such a address exists.
Mode number
display section
F Press the [
number.
The mode number and setting number will stop flashing and remain lit, indicating the
end of registration.
TEMP] buttons ( and ) to select the desired setting
MainSub
Remote controller
Mode number 02 = Indoor temperature detection
Setting number 3 = Remote controller's internal sensor
Fan draft
* If " - - - " is displayed for both the mode number and setting number and "
Check to see if there are any sources of noise or interference near the transmission path.
9 If you wish to continue to select other functions, repeat steps 3 to 8 .
0 Complete function selection.
A Hold down the
buttons simultaneously for at least
After a while, the function selection screen will disappear and the air conditioner OFF screen will reappear.
Note : If a function of an indoor unit is changed by function selection after installation is complete, make sure that a " " mark, etc., is given in the "Check"
column of Table 1 to indicate the change.
FILTERTEST
and ( mode 15 or more)
2 seconds.
" flashes in the room temperature display area, a transmission error may have occurred.
* Do not operate the remote controller for at least 30 seconds after completing
function selection. (No operations will be accepted even if they are made.)
43
Page 44
8-2. FUNCTION SELECTION OF REMOTE CONTROLLER
The setting of the following remote controller functions can be changed using the remote controller function selection mode.
Change the setting when needed.
Item 1
1.Change Language
("CHANGE LANGUAGE")
2.Function limit
("FUNCTION SELECTION")
3.Mode selection
("MODE SELECTION")
4.Display change
("DISP MODE SETTING")
Item 3 (Setting content)
• Display in multiple languages is possible.
• Setting the range of operation limit (operation lock)
• Setting the use or non-use of "automatic" operation mode
• Setting the temperature adjustable range (maximum, minimum)
• Selecting main or sub remote controller
* When 2 remote controllers are connected to 1 group, 1 controller must be set to sub.
• Setting the use or non-use of clock function
• Setting the timer type
• Contact number display in case of error
• Setting the telephone number
• Setting the temperature unit (: or °F) to display
• Setting the use or non-use of the display of indoor (suction) air temperature
• Setting the use or non-use of the display of "Cooling" or "Heating" display during
operation with automatic mode
Item 2
Language setting to display
(1)
Operation function limit setting (operation lock) ("LOCKING FUNCTION")
(2)
Use of automatic mode setting ("SELECT AUTO MODE")
(3)
Temperature range limit setting ("LIMIT TEMP FUNCTION")
[Function selection flowchart] Refer to next page.
[1] Stop the air conditioner to start remote controller function selection mode. [2] Select from item1. [3] Select from item2. [4] Make the setting.
(Details are specified in item3) [5] Setting completed. [6] Change the display to the normal one. (End)
➔➔➔
➔➔
[Detailed setting]
[4] -1. CHANGE LANGUAGE setting
The language that appears on the dot display can be selected.
• Press the [
MENU] button to change the language.
1 Japanese (JP), 2 English (GB), 3 German (D), 4 Spanish (E),
5 Russian (RU), 6Italian (I), 7 Chinese (CH), 8 French (F)
[4] -2. Function limit
(1) Operation function limit setting (operation lock)
• To switch the setting, press the [ ON/OFF] button.
1 no1 : Operation lock setting is made on all buttons other than
the [
ON/OFF] button.
2 no2: Operation lock setting is made on all buttons.
3 OFF (Initial setting value) : Operation lock setting is not made
* To make the operation lock setting valid on the normal screen, it is
necessary to press buttons (Press and hold down the [FILTER]
and [ ON/OFF] buttons at the same time for 2 seconds.) on
the normal screen after the above setting is made..
(2) Use of automatic mode setting
When the remote controller is connected to the unit that has automatic operation mode, the following settings can be made.
• To switch the setting, press the [ ON/OFF] button.
1 ON (Initial setting value) : The automatic mode is displayed when
• To switch the setting, press the [ ON/OFF] button.
1 Main : The controller will be the main controller.
2 Sub : The controller will be the sub controller.
(2) Use of clock setting
• To switch the setting, press the [ ON/OFF] button.
1 ON :The clock function can be used.
2 OFF: The clock function cannot be used.
(3) Timer function setting
• To switch the setting, press the [ ON/OFF] button (Choose one of
the followings.).
1 WEEKLY TIMER (initial setting):
The weekly timer can be used.
2 AUTO OFF TIMER: The auto off timer can be used.
SIMPLE TIMER:
The simple timer can be used.
4
3
TIMER MODE OFF: The timer mode cannot be used.
* When the use of clock setting is OFF , the "WEEKLY TIMER" cannot be
used.
(4) Contact number setting for error situation
• To switch the setting, press the [ ON/OFF] button.
1 CALL OFF:
The set contact numbers are not displayed in case of error.
2 CALL **** *** **** : The set contact numbers are displayed in case
of error.
(3) Temperature range limit setting
After this setting is made, the temperature can be changed within the set range.
• To switch the setting, press the [ ON/OFF] button.
1 LIMIT TEMP COOL MODE :
The temperature range can be changed on cooling/dry mode.
2 LIMIT TEMP HEAT MODE :
The temperature range can be changed on heating mode.
3 LIMIT TEMP AUTO MODE :
The temperature range can be changed on automatic mode.
4 OFF (initial setting) : The temperature range limit is not active.
*
When the setting, other than OFF, is made, the temperature range limit setting
on cooling, heating and automatic mode is made at the same time. However
the range cannot be limited when the set temperature range has not changed.
•
To increase or decrease the temperature, press the [ TEMP ( ) or ( )] button.
•
To switch the upper limit setting and the lower limit setting, press the
[ ]
button. The selected setting will flash and the temperature can be set.
Use of 2 controllers enables
operation of the air
conditioner both
from a distance
and nearby.
C.Group control
operation
Use of 1 remote
controller to control multiple air
conditioners with
the same settings
simultaneously
D.
Remote/local
combined control
operation
Allows start/stop
of the air conditioner from a distance, and prohibits/permits start/
stop from remote
controllers.
E.Operation by
external signal
F.
Control and remote
display by external
signal (extraction
of monitor signal)
Enables you to
display the operation state and
control start/stop
from a distance.
• There are 2 types of remote controllers: wired type
and wireless type.
• Simultaneous twin indoor units are started or stopped
simultaneously.
• Up to 2 remote controllers can be connected to
one group.
• Simultaneous twin units are counted as each unit.
• Operation control by the latest command (last entered priority)
• Wired and wireless remote controllers can be combined as a pair.
• One group can consist of up to 16 indoor units, and
they can be started sequentially by connecting the
remote controller to them and assigning an address
to each interface.
• Simultaneous twin units are counted as one unit.
• All the units belonging to the same group are operated in the same mode, but thermostats can be
turned ON/OFF individually for each indoor unit.
• Up to 2 remote controllers can be connected.
• All the air conditioners can be turned ON/OFF collectively
from a distance.
• Operation can be switched between the remote operating panel and handheld controller.
• Operations (e.g., temperature adjustment, airflow, airflow direction) except for start/stop operations can be
performed even if the remote controller is being operated.
• In the case of simultaneous twin units, connect the
controller to 1 indoor unit only. If connected to 2
or more indoor units, an error (operation stop) may
occur.
• Control by an external timer is possible by connecting it.
• Use of optional "remote operation adapter" enables
remote control via relay. (Level signal)
Extraction of non-voltage contact output
• Use of optional "remote operation adapter" and
"remote display panel"(Part to be provided at your
site) provides non-voltage contact outputs of signals
(operation, error) and operation/stop input function.
Extraction of DC12 V contact output
• Use of optional "remote display adapter" and "remote display panel" (Part to be provided at your site)
provides DC12 V contact outputs of signals
(operation, error) and operation/stop input function.
* One of the wired remote con-
trollers must be set as a sub
remote controller.
Wired remote controller (additional)
(PAR-21MAA)
Interface MAC-397IF-E
Remote ON/OFF adapter
(PAC-SE55RA-E)
Relay box
(Part to be provided at your site)
Remote operating panel
(Part to be provided at your site)
Remote ON/OFF adapter
(PAC–SE55RA-E)
Remote operation adapter
(PAC-SF40RM-E)
Remote display panel
(Part to be provided at your site)
Remote display adapter
(PAC-SA88HA)
Remote display panel
(Part to be provided at your site)
9-1. VARIETY OF SYSTEM CONTROL FUNCTIONS
Indoor unit
Remote
Controller
Relay box
Indoor unit
Remote Controller
Remote operating panel
Remote
Outdoor
Controller
unit
Indoor
unit
Remote
Controller
Interface
Indoor
unit
Outdoor
unit
Remote
display kit
Indoor unit
Remote Controller
Remote display (operation, error)
46
Page 47
System NameSystem DiagramFeatures
• Weekly timer:
In addition to ON/OFF, up to 8 temperature
patterns can be set for each day of the week.
*
G. Timer operation
Enables control
of start and stop.
* For control by
external timer,
refer to Remote/
local combined
control operation".
Only one timer can be selected; the auto off, simple
and weekly timers cannot be combined.
•
Simple timer: Start and stop operations can each be
performed once within 72 hours (can
be set in 1-hour increments).
• Auto off timer:
Operation is stopped when the preset
time elapses following the start of
operation.
The time can be set from 30 minutes
to 4 hours in 30-minute increments.
*
Only one timer can be selected; the simple and auto
off timers cannot be combined.
Enables control of
Mitsubishi Lossnay
ventilator by remote
controller.
I.Rotation
Lossnay
ventilator
Remote
Controller
SubMain
Indoor unit
Remote
Controller
Indoor
unit
Outdoor
unit
• Connecting a Lossnay ventilator and an indoor unit
enables control of interlock/solo ventilation operation and airflow.
(Only the microcomputer type Lossnay ventilator
can be used.)
•
When abnormality occurs while operating, it
changes into operating the backup unit, and
operating is continued.
(Unit function Mode No. 20 setting No.3 , Indoor
controller board SW-5-4 ON)
Main / Sub setting
Main : Indoor controller board
SW5-3 : OFF
Sub : Indoor controller board
SW5-3 : ON
•
Each system operates alternately for 24 hours or
168 hours.
(Unit function Mode No. 20 setting No.1: 24 hours/.
No.2 : 168 hours, Indoor controller board SW 5-4
ON)
Main / Sub setting
Main : Indoor controller board
SW5-3 : OFF
Sub : Indoor controller board
SW5-3 : ON
This function is available when
only 2 indoor units are connected
to each outdoor unit.
47
Page 48
9-2. 1 REMOTE CONTROLLER (STANDARD) OPERATION
Slim Air Conditioners System
System diagram
(Wired remote
controller)
Outdoor unit
OC
Indoor unit
IC
Wired
remote
controller R
Indoor/Outdoor
connection
cable
Remote
controller
cable
OC
IC-1
R
IC-2
2
2
OC
IC-1
R
2
2
Standard 1:1Simultaneous TwinIndoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
OCIC
1
2
LN
Power source wiring
1
2
1
2
1
2
R
(No polarity)
Outdoor unitIndoor unitRemote controller
Power
source
wiring
(Polarity)
Slim Air Conditioners System
System diagram
(Wireless remote
controller receiver)
Outdoor unit
OC
Indoor unit
IC
Wireless
remote controller
receiver section R'
Indoor/Outdoor
connection
cable
OC
IC-1
R'
IC-2
2
2
9
OC
IC-1
R'
2
9
Standard 1:1Simultaneous Twin
Wireless remote
controller cable
Wireless remote
controller cable
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
CN90
Controller board
Indoor unit IC
9
CNB
12
Wireless remote controller
receiver R’
Remote controller
cable terminal block
(1) 1 Wired Remote Controller
(OC: Outdoor unit IC: Indoor unit R: Remote controller (for wireless type: receiver)
(Reference)
1 If simultaneous twin, connect the remote controller to an indoor unit. All functions of the indoor unit can control even if
• Remote controller cable terminal block
1,2 (No polarity)
(2) Wireless remote controller
(Reference)
1 If simultaneous twin, connect the remote controller to an indoor unit. All functions of the indoor unit can control even if
different models (different types) are mixed.
2 Electrical wiring diagram
48
Page 49
9-3. 2-REMOTE CONTROLLER OPERATION
(1) 2 Wired Remote Controllers
Slim Air Conditioner System
Outdoor unit
OC
Indoor unit IC
System
diagram
(wired
remote
controller)
Wired remote
controller R
Outdoor unit
OC
Indoor unit IC
Wired remote
controller R
[Reference]
1 In the case of free component multi type systems consisting of simultaneous twin units, connect the remote controllers to each indoor unit.
All the functions of the connected indoor units can be controlled even if the system consists of different models.
2 In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring.
3 Set one of the remote controllers as the main controller (initial setting) and the other as the sub controller using the remote controller's function
selection.
(2) 2 Wireless Remote Controllers
Slim Air Conditioner System
Outdoor unit
System
diagram
(wireless
remote
controller
receiver)
OC
Indoor unit IC
Wireless remote
controller receiver section R'
Standard 1:1Simultaneous Twin
Remote
controller
cable
OC
IC
R-1
OC
2
IC
2
2
R-1
2
2
R-2
2
R-2
(R': Wireless remote controller receiver)
Indoor/outdoor
connection cable
Standard 1:1Simultaneous Twin
—
(R: Wired remote controller)
OC
2
IC-1
R-1
OC
IC-1
R-1
Indoor/outdoor
connection cable
Receiver
connection
cable
IC-2
2
2
2
R-2
2
IC-2
2
2
Remote controller cable
R-2
OC
2
IC-1
99
R'-1
2
2
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
Indoor controller board switch setting
SW5-3
OFF
IC-2
ON
R'-2
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
[Reference]
1 In the case of free component multi type systems consisting of simultaneous twin units, connect two wireless remote controller receivers
(one each) to any two of the indoor units. All the functions of the connected indoor units can be controlled even if the system consists of
different models.
2
In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring
In the case of "standard 1:1" connection, it is not possible to connect 2 remote controller receivers to the indoor units. However, with
3
systems consisting of simultaneous twin units, it is possible to connect a remote controller receiver to two indoor units. In this case, all the
pair numbers will be "0" (initial setting, no change necessary), and all the units will be turned ON/OFF simultaneously.
4 When using two or more wireless remote controllers, the display contents on the remote controllers may differ from the actual settings, since
the last operation made by any of the remote controllers will be effective.
In the case of free component multi type systems consisting of simultaneous twin units, connect both the wired remote controller and wireless
1
remote controller receiver to any one of the indoor units. All the functions of the connected indoor units can be controlled even if the system
consists of different models.
In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring.
2
When using 2 or more wireless remote controllers, the display contents on the remote controllers may differ from the actual settings, since the
3
last operation made by any of the wireless remote controllers will be effective.
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
.
49
Page 50
2.Connecting the remote control interface with each system
(For details on each system, see the relevant instruction manual.)
• Replace the interface unit mounting cord clamp with a supplied mounting cord clamp based on the thickness of the
connecting cable used for each system.
• The cables connected to the Indoor unit should be mounted on or near the indoor unit.
If the connecting cable is not securely mounted, the connector may detach, break, or malfunction.
• Set the interface dip switch (SW500–502) settings before turning on the power.
• If the interface dip switch (SW500–502) settings are not set correctly, the system will not function properly.
9-4. GROUP CONTROL OPERATION
(COLLECTIVE OPERATION AND CONTROL OF MULTIPLE REFRIGERANT SYSTEMS (2 to 16))
●
●
●
●
Group control can be operated by using MAC-397IF-E.
The setting of wired remote controller is subject to variation according to the function of the indoor unit.
(for mode operation, setting temperature, fan step, air direction)
The display of remote controller and operation of the indoor unit might be different.
Neither the test run nor the function setting can be done by MA remote controller connected with MAC-397IF-E.
1.Connecting the MA& CONTACT TERMINAL Interface to the Indoor Unit
• Connect the interface unit and the indoor control board using the connecting cable that came with the interface.
• Extending or shortening the connecting cable that comes out of the interface may cause it to malfunction. Also,
keep the connecting cable as far as possible from the electrical wires and ground wire. Do not bundle them together.
Indoor control board
INDOOR
CN105
CN92
or
Connect the connecting cable that comes with the
interface unit to the connector
CN105 or CN92 on the indoor control board.
Mounting screws (black) 3.5 o 12
Interface unit mounting cord clamp or mounting
cord clamps
Connecting cable for each system
Mounting cord clamp
Electrical wire mounting
bracket
Mounting screws 4 o 16
Mounting screws 4 o 10
Mounting cord clamp
50
Page 51
Use as a Wired Remote Control (Using the MA Remote Controller)
Note:
1. Be sure the Auto Heating/Cooling Display Setting on the MA remote controller is set to OFF before use.
• For information on how to set the Auto/Heating Cooling Display Setting, see the MA remote controller
instruction manual.
• The actual operating status of the unit may differ from what is shown on the remote controller display
2. A test run cannot be initiated using the test run switch on the MA remote controller.
3. The horizontal vanes on the unit cannot be operated using the louver switch.
4. The range of room temperature indication is between 10: and 38:.
CN560
TB580
2
1
2
A
B
Indoor unit
Remote control cord that came with
the MA remote controller (Non polarity)
Dip switch settings
SW500 does not have to be set.
SW501:
SW501- No. 1-4: Refrigerant address
• Set this switch when multiple indoor units (and remote control interfaces) are connected to a single MA remote controller.
• Always start the refrigerant address at "0".
1
Even when connecting multiple outdoor units, set a different refrigerant address for each indoor unit.
ON
1
234
ON
1
234
ON
1
234
ON
1
234
1Outdoor unit
2Outdoor unit
3Indoor unit
4Interface
5MA remote controller
Refrigerant
address
0
1
2
15
SW501- No. 5–6
ON
5
6
In case of connecting MAC-397IF-E to this model,
No. 5 should be set to OFF and No.6 should be set to ON.
Interface unit
Refrigerant
address "0"
Refrigerant
address "1"
Refrigerant
address "2"
MA remote controller
(PAR-21MAA)
* PAR-20MAA cannot be used
with this interface.
112
3333
4
5
44
51
Page 52
SW501: Settings to accommodate MA remote controller and settings to accommodate outdoor units
SW No.
No. 1
No. 2
No. 3
No. 4
ON
1
2 3 4 56
ON
1
2 3 4 56
ON
1
2 3 4 56
ON
1
2 3 4 56
ON
1
2 3 4 56
ON
1
2 3 4 56
ON
1
2 3 4 56
ON
1
2 3 4 56
ON
1
2 3 4 56
ON
1
2 3 4 56
ON
1
2 3 4 56
ON
1
2 3 4 56
ON
1
2 3 4 56
ON
1
2 3 4 56
ON
1
2 3 4 56
ON
1
2 3 4 56
FunctionsOFFONComments
Only specify these settings when
Refrigerant address 0
connecting an MA remote controller
.
Refrigerant address 0
Refrigerant address 0
Refrigerant address 0
Refrigerant address 0
Refrigerant address 0
Refrigerant address 0
Refrigerant address 0
Refrigerant address 0
Refrigerant address 0
Refrigerant address 0
Refrigerant address 0
Refrigerant address 0
Refrigerant address 0
Refrigerant address 0
Refrigerant address 0
SW No.
No. 5
No. 6
Room temperature detector
The model of Mr. SLIM exists in
Functions
the same group.
OFF
Indoor unit
Not mixed
ON
Remote control
Mixed
52
Comments
This should be set to OFF.
This should be set to ON.
Page 53
* Fan speed 2 step model : An actual fan speed is 2 step though the display of remote controller becomes 4 step or 3 step.
3. Test Run (Check Operations)
Interface status monitor
You can check the status of the interface by the LED lamp on the interface unit board.
LED lamp no.
LED521
LED522
LED523
Lamp off
DC 12 V is not being supplied from the
air conditioner.
Device is not communicating properly
with the air conditioner.
Device is not communicating properly
with the MA remote controller.
Lamp on
DC 12 V is being supplied from the air
conditioner.
–
–
Blinking
–
Blinking at approx. 1 second intervals: Device is
communicating normally with the air conditioner.
Blinking at approx. 8 second intervals: Device is communicating normally with the MA remote controller.
* Use the table above to check the device operations.
SW502 : Air Conditioner Function Settings
SW No.
No. 1
No. 2
No. 3
No. 4
No. 5
No. 6
No. 7
No. 8
Functions
Cooling only type/ Heat pump type
Auto mode
Fan speed
Vane
Swing
Not in use
Fan mode
OFF
Heat pump type
Not available
(setting No.3 disabled)
Available
(unit)
Available
Available
–
Not available
ON
Cooling only type
Available
(setting No.3 enabled)
Available
(remote controller)
Not available
Not available
–
Available
Comments
Set to OFF.
Permanently set to OFF.
4 speeds
3 speeds (2-speed
model set ON)
When operating a 2-speed model with the 3-speed
setting (ON), the MA remote controller display will
indicate 3 fan speeds.
The table below shows the displays and the actual
outputs at that time.
DisplayMeaningIndoor unit output
Low speedLow speed
Medium speedHigh speed
High speed
Set the mode in accordance with the operation
manual for the indoor unit.
Heat pump type : Set to ON.
Cooling only type : Set to OFF.
The vane function of either of indoor unit :
When the function is provided, it is available (OFF).
When the function is not provided, it is not available (ON).
The swing function of either of indoor unit :
When the function is provided, it is available (OFF).
When the function is not provided, it is not available (ON).
Set to ON.
High speed
4. Mounting the Remote Control Interface Unit
The interface unit should be placed in a location where the connecting cable from the interface can reach an indoor unit.
The device will not function properly if the connecting cable is extended so the connecting cable should not be extended.
Mount the interface unit securely to a pillar or wall using 2 or more screws.
■
When Using Wall Mounting Brackets
1
Attach the wall mounting brackets to the interface unit
using 2 mounting screws.
2
Mount the unit to a pillar or wall using 2 mounting screws.
Interface unit
Wall mounting
brackets
Mounting screws
Mounting screws
53
Cord clamp for
wiring
Mounting screws
Page 54
■ When Mounting Directly to a Wall
Mount the interface unit case to the wall using the mounting
screws.
Interface case
mounting screws
Mounting
screws
* When mounting the interface unit using a cushioning
material, be sure to mount it in a location where it will not
fall.
Interface unit
Cushioning material
When mounting the interface unit inside a ceiling
or wall, install an access door to facilitate maintenance.
When the interface unit is mounted
above an indoor unit, it should be
positioned 40 mm or more away from the
unit to ensure that ceiling grills can be
removed.
40 mm or more
Attach the interface unit connecting cable here.
Store extra connecting cable in the ductwork space
behind the indoor unit.
* If there is any slack in the connecting cable, use a
fastener to keep it in place.
54
Page 55
9-5. POWER OUTAGE AUTOMATIC RECOVERY OPERATION
Indoor unitIndoor unitIndoor unit
Remote controller
Control roomroom 1room 2room 3
Indoor unit
Relay boxRelay boxRelay box
Indoor unit
Control circuit
power supply
Indoor unitIndoor unit
Remote
controller
Remote/Local
selection switch
Control room W
room 1room 2room 3
Remote
controller
Remote
controller
Remote
controller
• Whenever a power outage or switching of the power supply causes the power supply of an operating air conditioner to go
from OFF to ON, this function will automatically restore the operation of the air conditioner to its previous operating mode.
w If the power is turned from OFF to ON when the air conditioner is not in operation, the air conditioner will not automatically
be turned on. However, the timer operation will be cancelled if the air conditioner is in timer operation (including when the
unit is waiting for its start time). Setting for timer operation must be performed once again.
• If there is a momentary power outage of less than 1 second while the air conditioner is in operation, there may not be a clear
determination of whether or not there was a power failure. When it has been determined that there has been a power failure,
recovery will take approximately 4 minutes after the power is restored. So please wait. (Once "PLEASE WAIT" has
appeared on the display, a protection system will operate to prevent the unit from restarting for 3 minutes.)
When it has been determined that there has been no power failure, operation will continue as is.
• Settings can be made by function selections from the remote controller.
• When there is group control, selection of all refrigerants is required.
9-6. INDIVIDUAL CONTROL OPERATION FROM A SEPARATE ROOM
• By simply centralizing the remote controllers installed in each room in a separate control room, individual control or centralized monitoring of the air conditioners in each room can be attained.
• Air conditioner control can be performed up to a total of 500 meters away by connecting the indoor units and remote controllers with 0.3 to 1.25 mm22-core cable.
• If a remote controller is installed in a room and control room, refer to the section on operating with 2 remote controllers.
9-7. COMBINED REMOTE/LOCAL CONTROL
• Operation/remote controller prohibit/ stop can be controlled from a remote location by routing the remote stop/start adapter
(PAC-SE55RA-E optional parts) through the relay box installed on site. When this remote control is cancelled, the local
remote controller can be used for operating and stopping the air conditioner.
1. Basic system wiring
• Use the remote start/stop adapter (PAC-SE55RA-E) and connect the "Start/Stop Circuit From Remote Location" that comes
from the relay box and remote/local selection switch and connect it to the CN32 connector on the printed circuit board for
the indoor unit.
<Points of precaution>
1 Match the rated power supply voltage of the remote/local selection switch and relay (X2) with the power supply for the con-
troller.
2 When performing group control of multiple outdoor unit using a timer, be sure to arrange the timer so that all units do not start
at the same time. If this is not performed, all of the units will start at one time creating an overcurrent that will cause the circuit
breaker to operate.
3 An on-delay system is one that includes specifications for operating a limited time when an ON signal is received and has a
temporary off timer for recovery operations.
4 Use a connecting relay when the wiring length exceeds 10 meters, such as when performing remote wiring. If this is not pro-
vided, abnormal operation will occur.
(1) System diagram
W The AC for the control room is usually disconnected from the remote/local control system.
55
Page 56
Control circuit
power supply
Dedicated short
circuit prevention
device
Remote/Local
selection switch
No.1 unit
relay box
No.2 unit
relay box
3 Relay box
2
Adapter for
remote start/stop
1
Remote/Local
selection switch
T Timer
(On delay system)
X Relay
Model
PAC-SE55RA-E
(optional parts)
(Example)
Single polarity
single-throw switch
(125V rating)
To
next
unit
T
Brown
Red
X
2X2
T
One method of easily
distinguishing the on/off
status of SW1 and SW2
is to use together with a
"illuminated switch R" or
pilot lamp.
T
X
2
SW1
SW2
T
X
2
OrangeOrange
Brown
Red
•
Starting/stopping
with remote
controller disabled.
• Starting/stopping by
remote operation
enabled.
•
Starting/stopping
with remote
controller disabled.
• AC is in operation.
• Starting/stopping by
remote operation
enabled.
•
Starting/stopping
with remote
controller disabled.
• Starting/stopping by
remote operation
enabled.
•
Starting/stopping
with remote
controller disabled.
• AC is in operation.
• Starting/stopping by
remote operation
enabled.
Remote
control
OFFON
Description of
functions
OFFON
SW1
SW2
OFFON
Remote/Local
selection switch
(2) Basic wiring diagram
Indoor unit
circuit board
CN32
Orange
Red
Brown
On site wiringOn site wiring
On site wiring
Timer
Timer
For remote operation
On site wiring
On site wiring
This is not used.
Protect exposed wire by
wrapping with insulating tape
On site wiring
SW1
Indoor unit
circuit board
CN32
Orange
Red
Brown
SW1
SW2
Indoor unit
circuit board
CN32
Orange
Red
Brown
SW2
Indoor unit
circuit board
CN32
Orange
Red
Brown
SW2
Indoor unit
circuit board
CN32
Orange
Red
Brown
Indoor unit
circuit board
CN32
Orange
Red
Brown
SW2
For remote operation
For timer operation
(3) Part specifications
Note: When using group address, connect to refrigerant
address "0" on the inside.
2. Examples of system applications
In any of the following examples, there is 5 to 6 seconds delay from the time the operating command is issued until the operation begins.
1 This is when starting and stopping is performed by remote operation or external timer and when starting and stopping by
the remote controller is to be prohibited.
2 This is when starting and stopping are performed by remote operation or external timer and when starting and stopping by
the remote controller is to be separated.
3 This is when starting and stopping are performed by remote operation and then allowing starting or stopping by remote
control at any time.
4 This is when permitting or prohibiting operation by remote controller is performed by external circuit.
Use momentary switch for SW2. (Manual operation/automatic recover switch on
time is more than 1 second.)
Press SW2 (on time is more than 1 second) and operation starts. After this has
been done, stopping or restarting can be done by remote controller.
If SW2 is on, operation by remote controller cannot be
performed.
If SW2 is off, operation by remote controller is permitted.
56
Page 57
9-8. OBTAINING REMOTE DISPLAY
CN90CN1
CN41
Wireless
3
TB3
External input
TB2
Error
TB1
Operation
2
Indoor control circuit boardRemote operation adapter
5
External input
Error output
(No voltage momentary "a" contact)
Operating output
(No voltage momentary "a" contact)
No voltage
(Momentary "a" contact)
HA
Power supply for controller
Timer control
panel (on-site)
Remote controller
Indoor unit
Remote controller
Indoor unit
Remote controller
Indoor unit
The model of a wireless type cannot correspond.
Use the remote operation adapter (PAC-SF40RM-E) to provide operation/error non-voltage contact output and on/off input
function.
(1) Wiring method
..
Caution
TB3 is a dedicated terminal for contact point input. Never input voltage. It will damage
the indoor control circuit board.
<Connections on the indoor unit side>
1 When using external output function
Insert the 9-pole connector (3-core) of the attached cable to CN90 on the indoor control circuit board.
2 When using the external input function
Insert the 4-pole connector (2-core) of the attached cable to CN41 on the indoor control circuit board.
W The connector is direction-sensitive. Take care not to make an error when inserting.
Never force the connectors. This will result in damage.
(2) Locally procured parts
ItemNameModel and specifications
External output functionExternal output signal wireUse sheathed vinyl coated cord or cable.
Wire type:CV, CVS or equivalent
Wire size:Stranded wire 0.5mm
2
to 1.25mm
2
Single wire: {0.65mm to 1.25mm
Display lamp, etc.No voltage “a” contact AC200V (DC30V), 1Aor less
External input functionExternal input signal wireUse sheathed vinyl coated cord or cable.
Wire type:CV, CVS or equivalent
Wire size:Stranded wire 0.5mm2to 1.25mm
2
Single wire: {0.65mm to 1.2mm
SwitchNo voltage “a” contact
(Start and stop operation is switched by inputting a
pulse of 200ms or more.)
9-9. TIMER OPERATION
● Timer operation can be performed by setting the wired or wireless remote controller timer. Start and stop times can be set in
10-minute increments within a 24-hour period.
● When used in combination with the central control remote controller of the M-NET control system for the outdoor unit, one
program timer can be used for individual timer settings for each group of the central control system. (Each timer setting can
be stored in data memory so timer settings for up to 50 groups can be set individually.)
W Please refer to the MELANS catalog or technical information for details about the central control remote controller.
Operating with on-site timer
(1) Summary of system
If the “Remote ON/OFF adapter” (PACSE55RA-E) (optional parts) is used, the
on-site timer can be operated to turn each
unit on and off.
57
Page 58
(2) Basic pattern for timer control
Orange
As selected by remote controller operation switch.
From indoor unit
Red
Brown
T
SW ON
SW OFF
Timer control
Remote controller control
SW
Orange
From indoor unit
Red
Brown
T
Wiring diagram
Control circuit board
Slim indoor unit
Lossnay
Lossnay linkage
(PAC-SB81VS)
External control
input terminal
block
1
2
3
Connector
(CN2L)
Basic wiring
X: Relay
(DC12V) CN25 (Indoor unit circuit board)
System example
Remote controller
Indoor unit
Relay box
(On-site installation)
Relay box
(On-site installation)
Remote controller
Humidifier unit
Humidifier
unit
Use a no-voltage contact point output timer (one that has separate circuits for the load side and timer power supply).
a) Timer-independent controlb) Combined control by timer and remote controller
(3) Basic system
Refer to 9-7. COMBINED REMOTE/LOCAL CONTROL.
9-10. LINKED OPERATION WITH PERIPHERAL AIR CONDITIONERS EQUIPMENT
■ Lossnay operation
● Linked operation with a Lossnay unit can be obtained by connecting Lossnay linkage cable (Model PAC-SB81VS - option-
al parts) to the CN2L (Remote kit) on the circuit board of the indoor unit. This function must be selected from the remote
controller.
1 Summary of wiring
● Connect the Lossnay linkage cable (Model PACSB81VS) connector to CN2L on the indoor unit on the
circuit board of the indoor unit.
● Connect the lead wire of the Lossnay linkage cable to
the Lossnay external control input terminal blocks (1)
and (2) (At this time, the input terminal blocks (1) and
(2) have no polarity).
2 Precautions when wiring
● The Lossnay linkage cable can be extended up to a maximum of 500 meters.
When extending the Lossnay linkage cable, be sure to connect securely and take proper steps to ensure insulation.
(Extension cable specifications: Sheathed vinyl cord or cable 0.5 to 0.75mm
● Arrange wiring so that there is no contact between the Lossnay linkage cable and the power supply cable. Contact may
cause malfunction. (Separate by 5cm or more.)
9-11. OBTAINING HUMIDIFIER SIGNAL
● The humidifier signal that is linked to the AC heating operation (indoor unit ventilator) can be obtained by connecting the
adapter for the humidifier signal to connector CN25 on the printed circuit for the indoor unit and wiring it to the humidifier
unit via the on-site relay box. There is no output when the thermostat is off during heating preparation and during defrosting.
9-12. EXTERNAL MOUNTING OF TEMPERATURE SENSOR
● Temperature control from an alternative external location can be performed by connecting the temperature sensor (Model
PAC-SE41TS-E - optional parts) to the CN20 connector on the circuit board for the indoor unit.
● The wired remote controller also has an internal temperature sensor. Function selection from the remote controller is
required.
Refer to “FUNCTION SETTING” for information of installation manual about selecting functions with the remote controller.
58
2
)
Page 59
Be sure to secure insulation
material by tape, etc.
5
Green
Yellow
Orange
Connector (5P)
Indoor unit side
Multiple remote
controller adapter
PAC-SA88HA-E
Be sure to secure insulation
material by tape, etc.
Installation at site
CN51
on
indoor
controller
board
Red
Brown
1
~
MB
9-13. MULTIPLE REMOTE CONTROL DISPLAY
CN51
connector(5P)
GREEN
Power
supply
Electrical insulation is needed.
Wiring at the actual place
Optional multiple display
adapter
The maximum distance between
indoor board and relay is 10m.
YELLOW
ORANGE
RED
BROWN
5
X2
X2
GL
RL
X1
X1
1
<Wiring >
Power
supply
Remote
controller
cable
Relay box
(Field supply)
Remote
controller
Remote
controller
Remote
controller
3wires
3wires
3wires
2wires
No.1 unitNo.2 unitNo.3 unit
Muitiple remote control
ON-OFF display
(Field supply)
(Operation check)
<System>
Power
supply
RL-1
GL-1
Multiple Remote Control Display
Multiple remote
controller adapter
connect to
the connector CN51
Relay box
5
X1-1
X2-1
1
<Wiring diagram>
RL-2
GL-2
RL-3
No.1 unit
GL-3
X1-1
X2-1
X1-2
X1-3
X2-3
X2-2
5
1
No.2 unit
5
1
No.3 unit
X1-2
X2-2
X1-3
X2-3
Indoor controller board
CN51
You can control several units with a multiple remote control display, by wiring an optional multiple display adapter (PACSA88HA-E) with relays and lamps on the market.
How to wire
(1) Connect the multiple display adapter to the connector CN51 on the indoor controller board.
(2) Wire 3 of the 5 wires from the multiple display adapter as shown in the figure below.
[Notes on Signs]
X1:Relay (for operation lamp)
X2:Relay (for check lamp)
RL:Operation Lamp
GL:Check Lamp
[Field supplied parts]
Relays:12V DC with rated coil power
consumption below 0.9W.
Lamps:Matching to power supply voltage.
9-14. OPERATION IN CONJUNCTION WITH DUCT FAN (Booster fan)
●Whenever the indoor unit is operating,
the duct fan operates.
(1)Connect the optional multiple remote
controller adapter(PAC-SA88HA-E) to
the connector CN51 on the indoor
controller board.
(2)Drive the relay after connecting the
12V DC relay between the Yellow and
Orange connector lines.
(2) When the intake grille left open, push the stoppers on the
rear hinges (at 2 locations) to pull out the intake grille.
2. Removing the electrical box
(1) Remove the air intake grille.
(2) Remove the screw from the beam and remove the beam.
(3) Remove the screws from the electrical cover, and
remove the electrical cover.
(4) Disconnectors including CN6V and CN21.
(5) Remove the screws from the electrical box and pull out
the electrical box.
Figure 1
Figure 2
<Electrical parts in the electrical box>
Terminal block (for power supply)
Terminal block (for in/outdoor connecting wire)
Terminal block (for remote controller)
Fan motor capacitor
Indoor control board
Indoor power board
60
Photo 1
Power board
Fan motor
capacitor
Indoor
control
board
Relay (PCH only)
Terminal
block
(Electric heater)
Terminal
block
(Indoor / outdoor
connecting line)
Terminal
block
(remote control)
Page 61
Screw
Side panel
Sliding the panel
to the front
OPERATING PROCEDUREPHOTOS & ILLUSTRATIONS
3. Removing the fan motor
(1) Remove the intake grill.
(2) Disconnect the fan motor connector.
(3) Remove the screw for removing the motor support at both
left and right side.
(4) Loosen the set screws at the fan motor side of the con-
necting joint.
(5) Slide the fan motor to the left side and pull it out.
4. Removing the sirocco fan
(1) Remove the air intake grill.
(2) Remove 1 beam.
(3) Remove the lower casing while pressing the stoppers at
upper side of the casing.
(4) Loosen the set screws at the connecting joint.
(5) Remove the sirocco fan and shaft together by sliding the
shaft to the left.
Photo 2
Screws
Photo 3
Motor
Motor support
Set screw
MotorSet screws
Connecting joint
Catch
Casing
(Note)
Make sure that the upper side casing is snapped to the fan
plate securely with catch.
5. Removing the side panel
(1) Remove the air intake grill.
(2) Remove the screws from the side panel, and remove the
side panel by sliding the panel to the front.
Connecting joint
Figure 3
Sirocco fan
Shaft
Bearing
Screws
61
Page 62
OPERATING PROCEDUREPHOTOS & ILLUSTRATIONS
6. Removing the vane motor
(1) Remove the air intake.
(2) Remove the left side panel.
(3) Remove the relay connector of vane motor.
(4) Remove the electrical box.
(5) Remove the screws of vane motor, then remove vane
motor.
(Note)
Connect the lead wires and connectors properly and place
them in the proper position so that the wires are not pinched
by other parts.
7. Removing the indoor coil thermistor
(1) Remove the air intake grill.
(2) Remove the right side panel.
(3) Remove the relay connector of the indoor coil thermistor.
(4) Remove the screw, and remove the check panel.
(5) Extract the indoor coil thermistor from the holder.
<Caution for the installation>
There is a possibility for the short circuit when connector gets
wet by water through the thermistor lead wire.
Therefore, lead wire of the indoor coil thermistor should be
traped as shown in the picture.
Photo 4
Relay connector of
the vane motor
Photo 5
Left side
panel
Screw
Check
panel
Screw
Vane motor
Relay connector of
the pipe thermistor
8. Removing the under panel
(1) Remove the air intake grill.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Unscrew the screws of the under panel, then remove the
lower panel.
wWeight of the lower panel : approx. 2kg
Photo 6
HoldIndoor coil thermistorTrap
Photo 7
Screws
Under panel
62
Page 63
OPERATING PROCEDUREPHOTOS & ILLUSTRATIONS
9. Removing the drain pan
(1) Remove the air intake grill.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Remove the under panel. Remove the screws of the right
and left side drain pan.
(5) Remove the insulation in center of the drain pan, and
after removing the screw, remove the drain pan.
(Note)
Please aware that there might be drain left in the drain pan
when you remove the drain pan.
10. Removing the guide vane
(1) Remove the intake grill.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Remove the under panel.
(5) Remove the drain pan.
(6) Remove the screw from the guide vane, then remove the
guide vane.
Photo 8
Screw
Photo 9
Drain pan
Screw
(Insulation)
Screw
11. Removing the Auto vane
(1) Remove the intake grill.
(2) Remove the left side panel.
(3) Remove the left side box.
(4) Remove the under panel.
(5) Remove the screw from the auto vane.
(6) Slide the auto vane to the right side and pull the auto vane
out.
63
Drain pan
Photo 10
Guide vane
Auto vane
Screw
Screw
Page 64
OPERATING PROCEDUREPHOTOS & ILLUSTRATIONS
12. Removing the heat exchanger
(1) Remove the air intake grille.
(2) Remove the beam.
(3) Remove the side panel. (right and left)
(4) Disconnect the relay connector.
(5) Remove the under panel.
(6) Remove the drain pan.
(7) Unscrew the screws of the pipe cover, and remove the pipe
cover.
(8) Unscrew the screws of the pipe support, and remove the
pipe support.
(9) Unscrew the screw of the heat exchanger, and remove the
heat exchanger.
Remove the heat exchange with care, since this is quite
heavy. Removing work should be done with more than 2
people.
w Weight of heat exchanger : approx. 5.3kg
Photo 11
Pipe
support
Screws
Pipe cover
Screws
Heat
exchanger
64
Page 65
11
No.Parts No.Parts NameSpecifications
Wiring
Diagram
Symbol
Recommended
Q'ty
Q'ty / set
1
2
3
4
5
6
7
8
9
10
MOTOR LEG
CASING
SIROCCO FAN
ROOM TEMPERATURE THERMISTOR
PIECE (MOTOR)
FAN MOTOR
DRAIN PLUG
DRAIN PAN ASSY
PIPE TEMPERATURE THERMISTOR
HEAT EXCHANGER
MOTOR LEG
FAN MOTOR
SHAFT JOINT
PIECE (MOTOR)
SIROCCO FAN
ROOM TEMPERATURE THERMISTOR
SHAFT (FAN)
SLEEVE BEARING
BEARING SUPPORT
DRAIN PLUG
DRAIN PAN ASSY
CASING
SIROCCO FAN
PIPE TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
PIECE (MOTOR)
MOTOR LEG
FAN MOTOR
SHAFT JOINT
SIROCCO FAN
ROOM TEMPERATURE THERMISTOR
SHAFT
SLEEVE BEARING
BEARING SUPPORT
DRAIN PLUG
DRAIN PAN ASSY
CASING
SIROCCO FAN
PIPE TEMPERATURE THERMISTOR
HEAT EXCHANGER
D10B4P90MS
12
11
10
Q'ty / set
PC-4GAKD
1
1
1
1
2
1
1
1
1
1
1
3
1
1
1
13
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
MF
TH1
TH2
14
Recom-
mended
Q'ty
67
Page 68
No.Parts No.Parts NameSpecifications
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty / set
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
SHAFT
MOTOR LEG
FAN MOTOR
PIECE (MOTOR)
SIROCCO FAN
ROOM TEMPERATURE THERMISTOR
SIROCCO FAN
SHAFT JOINT
DRAIN PAN ASSY
SIROCCO FAN
DRAIN PLUG
CASING
SLEEVE BEARING
BEARING SUPPORT
PIPE TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
S.PLATE-L
L.L FILTER
GRILLE HINGE
GRILLE ASSY
GRILLE ASSY
GRILLE CATCH
L.L FILTER
REAR SUPPORT
UNDER PANEL
BEAM(GA)
W.BOARD CASE
S.PLATE-R
RIGHT LEG (R)
SERVICE PANEL
RIGHT SIDE PANEL
RIGHT SIDE BOX
G.V ASSY-6R
VANE SUPPORT
FRONT PANEL
AUTO VANE
G.V ASSY-6L
REAR PANEL
LEFT SIDE BOX
VANE MOTOR
LEFT LEG (L)
LEFT SIDE PANEL
JOINT SOCKET
DRAIN HOSE COVER
LEFT SIDE PANEL
LEFT SIDE PANEL
LEFT LEG
S.PLATE-L
S.PLATE-L
REAR PANEL
REAR PANEL
GRILLE HINGE
GRILLE CATCH
GRILLE ASSY
L.L FILTER
UNDER PANEL
W.BOARD CASE
REAR SUPPORT
BEAM (GA)
S.PLATE-R
S.PLATE-R
RIGHT SIDE PANEL
RIGHT SIDE PANEL
RIGHT LEG
SERVICE PANEL
SERVICE PANEL
RIGHT SIDE BOX
RIGHT SIDE BOX
FRONT PANEL
FRONT PANEL
AUTO VANE
AUTO VANE
VANE SUPPORT
VANE SUPPORT
G.V ASSY-6R
G.V ASSY-6C
G.V ASSY-6L
LEFT SIDE BOX
LEFT SIDE BOX
VANE MOTOR
VANE MOTOR
JOINT SOCKET
DRAIN HOSE COVER
Q'ty/set
PC-·GAKD
2.5/3
4
PC-2.5GAKD
PC-3GAKD
PC-4GAKD
Part numbers that are circled are not show in the figure.
LEFT SIDE PANEL
S.PLATE-L
REAR PANEL
L.L FILTER
GRILLE HINGE
GRILLE ASSY
GRILLE CATCH
GRILLE ASSY
L.L FILTER
UNDER PANEL
W.BOARD CASE
REAR SUPPORT
BEAM(GA)
RIGHT SIDE PANEL
RIGHT LEG
SERVICE PANEL
RIGHT SIDE BOX
S.PLATE-R
FRONT PANEL
AUTO VANE
G.V ASSY-5R
G.V ASSY-5C
VANE SUPPORT
G.V ASSY-5L
LEFT SIDE BOX
VANE MOTOR
LEFT LEG
JOINT SOCKET
DRAIN HOSE COVER
PC-5 / 6GAKD
Q'ty/set
STRUCTURAL PART
PC-5GAKD
PC-6GAKD
1
27
26 2524
23
22
21
2
3
4
5
6
7
Part numbers that are circled are not shown in the figure.
8
9
71
10
11
12
20
19
18
17
16
15
14
13
Page 72
No.Parts No.Parts NameSpecifications
Wiring
Diagram
Symbol
Recommended
Q'ty
(BG00N015G40)
Q'ty / set
1
2
3
4
5
6
7
8
9
10
11
CAPACITOR
CAPACITOR
CAPACITOR
FUSE
INDOOR CONTROLLER BOARD
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
CONTROL BOX
POWER BOARD
CONTROL COVER
CONTROL COVER
CONTROL COVER
REMOTE CONTROLLER CORD
REMOTE CONTROLLER
MOTOR LEG
FAN MOTOR
SHAFT JOINT
PIECE (MOTOR)
SIROCCO FAN
ROOM TEMPERATURE THERMISTOR
SHAFT (FAN)
SLEEVE BEARING
BEARING SUPPORT
DRAIN PLUG
DRAIN PAN ASSY
CASING
SIROCCO FAN
PIPE TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
PIECE (MOTOR)
MOTOR LEG
FAN MOTOR
SHAFT JOINT
SIROCCO FAN
ROOM TEMPERATURE THERMISTOR
SHAFT
SLEEVE BEARING
BEARING SUPPORT
DRAIN PLUG
DRAIN PAN ASSY
CASING
SIROCCO FAN
PIPE TEMPERATURE THERMISTOR
HEAT EXCHANGER
D10B4P90MS
12
11
10
Q'ty / set
PC-4GAKD
1
1
1
1
2
1
1
1
1
1
1
3
1
1
1
13
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
MF
TH1
TH2
14
Recom-
mended
Q'ty
75
Page 76
No.Parts No.Parts NameSpecifications
Wiring
Diagram
Symbol
Recommended
Q'ty
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
RoHS
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
SHAFT
MOTOR LEG
FAN MOTOR
PIECE (MOTOR)
SIROCCO FAN
ROOM TEMPERATURE THERMISTOR
SIROCCO FAN
SHAFT JOINT
DRAIN PAN ASSY
SIROCCO FAN
DRAIN PLUG
CASING
SLEEVE BEARING
BEARING SUPPORT
PIPE TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
S.PLATE-L
L.L FILTER
GRILLE HINGE
GRILLE ASSY
GRILLE ASSY
GRILLE CATCH
L.L FILTER
REAR SUPPORT
UNDER PANEL
BEAM(GA)
W.BOARD CASE
S.PLATE-R
RIGHT LEG (R)
SERVICE PANEL
RIGHT SIDE PANEL
RIGHT SIDE BOX
G.V ASSY-6R
VANE SUPPORT
FRONT PANEL
AUTO VANE
G.V ASSY-6L
REAR PANEL
LEFT SIDE BOX
VANE MOTOR
LEFT LEG (L)
LEFT SIDE PANEL
JOINT SOCKET
DRAIN HOSE COVER
LEFT SIDE PANEL
LEFT SIDE PANEL
LEFT LEG
S.PLATE-L
S.PLATE-L
REAR PANEL
REAR PANEL
GRILLE HINGE
GRILLE CATCH
GRILLE ASSY
L.L FILTER
UNDER PANEL
W.BOARD CASE
REAR SUPPORT
BEAM (GA)
S.PLATE-R
S.PLATE-R
RIGHT SIDE PANEL
RIGHT SIDE PANEL
RIGHT LEG
SERVICE PANEL
SERVICE PANEL
RIGHT SIDE BOX
RIGHT SIDE BOX
FRONT PANEL
FRONT PANEL
AUTO VANE
AUTO VANE
VANE SUPPORT
VANE SUPPORT
G.V ASSY-6R
G.V ASSY-6C
G.V ASSY-6L
LEFT SIDE BOX
LEFT SIDE BOX
VANE MOTOR
VANE MOTOR
JOINT SOCKET
DRAIN HOSE COVER
Q'ty/set
PC-·GAKD
2.5/3
4
PC-2.5GAKD
PC-3GAKD
PC-4GAKD
Part numbers that are circled are not show in the figure.
LEFT SIDE PANEL
S.PLATE-L
REAR PANEL
L.L FILTER
GRILLE HINGE
GRILLE ASSY
GRILLE CATCH
GRILLE ASSY
L.L FILTER
UNDER PANEL
W.BOARD CASE
REAR SUPPORT
BEAM(GA)
RIGHT SIDE PANEL
RIGHT LEG
SERVICE PANEL
RIGHT SIDE BOX
S.PLATE-R
FRONT PANEL
AUTO VANE
G.V ASSY-5R
G.V ASSY-5C
VANE SUPPORT
G.V ASSY-5L
LEFT SIDE BOX
VANE MOTOR
LEFT LEG
JOINT SOCKET
DRAIN HOSE COVER
PC-5 / 6GAKD
Q'ty/set
STRUCTURAL PART
PC-5GAKD
PC-6GAKD
1
27
26 2524
23
22
21
2
3
4
5
6
7
Part numbers that are circled are not shown in the figure.
8
9
79
10
11
12
20
19
18
17
16
15
14
13
Page 80
No.Parts No.Parts NameSpecifications
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
(BG00N015G40)
Q'ty / set
1
2
3
4
5
6
7
8
9
10
11
RoHS
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
CAPACITOR
CAPACITOR
CAPACITOR
FUSE
INDOOR CONTROLLER BOARD
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
CONTROL BOX
POWER BOARD
CONTROL COVER
CONTROL COVER
CONTROL COVER
REMOTE CONTROLLER CORD
REMOTE CONTROLLER
Part No.
Pipe length
Pipe size O.D.
Connection method
Service Ref. : PC-4GAKD / PC-5GAKD / PC-6GAKD
Part No.
Pipe length
Pipe size O.D.
Connection method
Note 1. How to connect refrigerant pipes
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging.
Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor
units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow.
If piping length exceeds 20m, an additional charge of refrigerant is needed.
Note 2. The following main parts are contained in the optional refrigerant piping kit.
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU TOKYO 100-8310, JAPAN
cCopyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Feb. 2008 No.OC382 REVISED EDITION-B PDF 8
Distributed in May 2007 No.OC382 REVISED EDITION-A PDF 8
Distributed in Mar. 2006 No.OC382 PDF 9
Made in Japan
New publication, effective Feb. 2008
Specifications subject to change without notice
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.