Before obtaining access to terminal, all supply
circuits must be disconnected.
3-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R407C
Do not use the existing refrigerant piping.
The old refrigerant and lubricant in the existing piping
contains a large amount of chlorine which may cause the
lubricant deterioration of the new unit.
Use “low residual oil piping”
If there is a large amount of residual oil (hydraulic oil, etc.)
inside the piping and joints, deterioration of the lubricant
will result.
Store the piping to be used during installation
indoors with keep both ends sealed until just
before brazing.
(Store elbows and other joints in a plastic bag.)
If dust, dirt, or water enters the refrigerant cycle,
deterioration of the oil and compressor trouble may result.
Use ESTER , ETHER or HAB as the lubricant to
coat flares and flange connection parts.
If large amount of mineral oil enter, that can cause
deterioration of refrigerant oil etc.
Use liquid refrigerant to seal the system.
If gas refrigerant is used to seal the system, the composition
of the refrigerant in the cylinder will change and performance
may drop.
Do not use a refrigerant other than R407C.
If another refrigerant (R22, etc.) is used, the chlorine in the
refrigerant may cause the lubricant deterioration.
Use a vacuum pump with a reverse flow check valve.
The vacuum pump oil may flow back into the refrigerant
cycle and cause the lubricant deterioration.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
3
Page 4
[1] Cautions for service
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
[2] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it.
(By liquid refrigerant)
Unit
Gravimeter
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.Tool nameSpecifications
·Only for R407C.
Gauge manifold
1
Charge hose
2
Electronic scale
3
Gas leak detector·Use the detector for R134a or R407C.
4
Adapter for reverse flow check.·Attach on vacuum pump.
5
Refrigerant charge base.
6
Refrigerant cylinder.
7
Refrigerant recovery equipment.
8
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
·Only for R407C.
·Use pressure performance of 5.10MPa·G or over.
·For R407C ·Top of cylinder (Brown)
·Cylinder with syphon
4
Page 5
CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R410A
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with
the followings.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
Store the piping to be used during installation
indoors and keep both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
[1] Cautions for service
(1) Perform service after collecting the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
5
Page 6
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.Tool nameSpecifications
·Only for R410A
1
Gauge manifold
2
Charge hose
3
Electronic scale
4
Gas leak detector·Use the detector for R134a, R407C or R410A.
5
Adaptor for reverse flow check·Attach on vacuum pump.
6
Refrigerant charge base
7
Refrigerant cylinder
8
Refrigerant recovery equipment
·Use the existing fitting
·Use high-tension side pressure of 5.3MPa·G or over.
·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
·Only for R410A ·Top of cylinder (Pink)
·Cylinder with syphon
specifications
. (UNF1/2)
6
Page 7
4PART NAMES AND FUNCTIONS
Indoor Unit
Air intake
Guide vane
Filter
Air outlet
Air intake grille
Auto vane
77
Page 8
Wirelessremote controller
When cover is open.
CHECK
TEST RUN
display
CHECK&TEST RUN display indicates that
the unit is being checked or test-run.
MODEL SELECT
Blinks when model is selected.
display
display
Lights up while transmission to the indoor
unit is mode using switches.
display
SET TEMP. display indicates desired
temperature set.
display
OPERATION MODE display
Operation mode display indicates which
operation mode is in effect.
display
The vertical direction of air flow is indicated.
display
FAN SPEED display indicates which fan
speed has been selected.
ON/OFF button
The unit is turned ON and OFF alternately
each time the button is pressed.
FAN SPEED SELECT button
Used to change the fan speed.
MODE SELECT button
Used to switch the operation mode between
cooling, drying, heating and auto mode.
+ In case the outdoor unit is cool only type,
the heating and auto mode not available.
CHECK-TEST RUN button
Only press this button to perform an
inspection check or test operation.
Do not use it for normal operation.
CHECK
TEST RUN
MODEL SELECT
NOT AVAILABLE
ON/OFF TEMP
FAN
MODE
CHECK
VAN E
LOUVER
TEST RUN
RESETSETCLOCK
°C
AMPM
AMPM
AUTO STOP
AUTO START
h
min
CLOCK display
Displays the current time.
TIMER display
Displays when in timer operation or when
setting timer.
“” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
button
SET TEMPERATURE button sets any desired
room temperature.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch
is set, the air conditioner will be
automatically stopped at the preset time.
AUTO START (ON timer): when this switch is
set, the air conditioner will be automatically
started at the preset time.
h and min buttons
Buttons used to set the “hour and minute” of
the current time and timer settings.
LOUVER button
Changes left/right airflow direction.
(Not available for this model.)
VANE CONTROL button
Used to change the air flow direction.
CLOCK button
RESET button
SET buttonCLOCK button
8
Page 9
5
SPECIFICATIONS
Service Ref.
Mode
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
INDOOR UNIT
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe O.D.
Dimensions
Weight
Service Ref.
Mode
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
INDOOR UNIT
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe O.D.
Dimensions
Weight
Airflow(Low-Medium2-Medium1-High)
W
D
H
Airflow(Low-Medium2-Medium1-High)
W
D
H
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
PKA-RP35GAL, PKA-RP35GAL#1
Cooling
Single phase, 50Hz, 230V
0.07
0.33
0.40
Munsell 0.70Y 8.59/0.97
Plate fin coil
Line flow (direct) x 1
0.030
9-10-11-12(320-355-390-425)
0(direct blow)
Wireless remote controller & built-in
36-38-41-43
20(13/16)
990(39)
235(9-1/4)
340(13-3/8)
16(35)
PKA-RP50GAL, PKA-RP50GAL#1
Cooling
Single phase, 50Hz, 230V
0.07
0.33
0.40
Munsell 0.70Y 8.59/0.97
Plate fin coil
Line flow (direct) x 1
0.030
9-10-11-12(320-355-390-425)
0(direct blow)
Wireless remote controller & built-in
36-38-41-43
20(13/16)
990(39)
235(9-1/4)
340(13-3/8)
16(35)
Heating
0.07
0.33
0.40
Heating
0.07
0.33
0.40
99
Page 10
Service Ref.
y
y
Mode
Power supply(phase, cycle,voltage)
Input +1
Running current +1
Starting current +1
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
INDOOR UNIT
Booster heater +1
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe O.D.
Dimensions
Weight
+1 : < > Shows the onl
Airflow(Low-Medium2-Medium1-High)
W
D
H
booster heater rating.
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Cooling
PKH-P35GALH
Single phase, 50Hz, 230V
0.07
0.33
0.40
Munsell 0.70Y8.59/0.97
Plate fin coil
Line flow (direct) x 1
0.030
9-10-11-12(318-353-388-424)
0(direct blow)
<0.73>
Wireless remote controller & built-in
36-38-41-43
20(13/16)
990(39)
235(9-1/4)
340(13-3/8)
17(37)
Heating
0.07<0.73>
0.33<3.17>
0.40<3.17>
Service Ref.
Mode
Power supply(phase, cycle,voltage)
Input +1
Running current +1
Starting current +1
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
External static pressure
INDOOR UNIT
Booster heater +1
Operation control & Thermostat
Noise level(Low-Medium2-Medium1-High)
Unit drain pipe O.D.
Dimensions
Weight
+1 : < > Shows the onl
Airflow(Low-Medium2-Medium1-High)
W
D
H
booster heater rating.
kW
A
A
kW
*/min(CFM)
Pa(mmAq)
kW
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Cooling
PKH-P50GALH
Single phase, 50Hz, 230V
0.07
0.33
0.40
Munsell 0.70Y 8.59/0.97
Plate fin coil
Line flow (direct) x 1
0.030
9-10-11-12(318-353-388-424)
0(direct blow)
<0.73>
Wireless remote controller & built-in
36-38-41-43
20(13/16)
990(39)
235(9-1/4)
340(13-3/8)
17(37)
Heating
0.07<0.73>
0.33<3.17>
0.40<3.17>
10
Page 11
6NOISE CRITERION CURVES
PKA-RP35/50GAL
PKA-RP35/50GAL#1
PKH-P35/50GALH
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 μbar)
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
631252505001000200040008000
BAND CENTER FREQUENCIES, Hz
NOTCH
High
Medium1
Medium2
Low
SPL(dB)
43
41
38
36
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
UNIT
1m
1m
MICROPHONE
WALL
1111
Page 12
7
OUTLINES AND DIMENSIONS
INDOOR UNIT
PKH-P35GALH PKA-RP35GAL PKA-RP35GAL#1
PKH-P50GALH PKA-RP50GAL PKA-RP50GAL#1
1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1, S2, S3).
3. Make sure that the main power supply of the booster heater is independent.
4. Symbols used in wiring diagram above are, : Connector, : Terminal (block).
+1. When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig 1.
+2. For power supply system of this unit, refer to the caution label located near this diagram.
Refrigerant flow in cooling
Refrigerant flow in heating
14
Page 15
10TROUBLESHOOTING
10-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.
Actions to be taken for service and the trouble reoccurrence at field are summarized in the table below. Check the contents
below before investigating details.
Unit conditions at service
The trouble is reoccurring.
The problem is not reoccurring.
Error code
Displayed
Not displayed
Logged
Not logged
Actions to be taken for service (summary)
Judge what is wrong and take a corrective action
according to “SELF-DIAGNOSIS ACTION TABLE” (10-3).
Conduct troubleshooting and ascertain the cause of the
trouble according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (10-4).
Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
trouble occurred, matters related to wiring and etc.
Reset error code logs and restart the unit after finishing
service.
There is no abnormality in electrical component,
controller board, remote controller and etc.
Re-check the abnormal symptom.
Conduct troubleshooting and ascertain the cause of the
trouble according to “TROUBLESHOOTING
BY INFERIOR PHENOMENA ” (10-4).
Continue to operate unit for the time being if the cause
is not ascertained.
There is no abnormality concering of parts such as
electrical component, controller board, remote controller
and etc.
15
Page 16
10-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<Malfunction-diagnosis method at maintenance service>
[Procedure]
CHECK
display
ON/OFF
button
CHECK
button
ON/OFF
MODE
CHECK
TEST RUN
SET
CHECK
FAN
VAN E
LOUVER
RESET
TEMP
AUTO STOP
AUTO START
CLOCK
h
min
Refrigerant
address
display
Temperature
button
HOUR
button
1. Press the CHECK button twice.
2. Press the temperature
buttons.
3. Point the remote controller at the
sensor on the indoor unit and
press the HOUR button.
• "CHECK" lights, and refrigerant
address "00" flashes.
• Check that the remote controller's
display has stopped before continuing.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermit tent buzzer sound, the operation light
flashes, and the error code is
output.
(It takes 3 seconds at most for error
code to appear.)
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
• The check mode is cancelled.
16
To be continued to the next page.
Page 17
• Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds
OPERATION
INDICATOR
lamp flash
pattern
Beep
Self-check
starts
(Start signal
received)
Beep Beep BeepBeepBeep Beep
1st2nd3
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
rd
0.5 sec.
n
On
th
[Output pattern B]
Beeper sounds
OPERATION
INDICATOR
lamp flash
pattern
BeepBeep Beep BeepBeepBeep Beep
1st2nd3
Off
Self-check
starts
(Start signal
received)
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “U2”)
Forced compressor stop(due to water leakage abnormality)
6P6Freezing/Overheating protection operation
7EECommunication error between indoor and outdoor units
8P8Pipe temperature error
9E4, E5Remote controller signal receiving error
10
11
–
–
–
–
12FbIndoor unit control system error (memory error, etc.)
–
E0, E3
Remote controller transmission error
–E1, E2Remote controller control board error
nd
1st2
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
Number of flashes/beeps in pattern indicates
the check code in the following table
rd
th
n
On
0.5 sec.
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
SymptomRemark
··· Repeated
nd
1st2
Number of flashes/beeps in pattern indicates
the check code in the following table
· · · Repeated
[Output pattern B]
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes Check code
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote controller
SymptomRemark
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
E9
UP
U3,U4
UF
U2
U1,Ud
U5
U8
U6
U7
U9,UH
–
–
Others
*1 If the beeper does not sound again after the initial
the OPERATION INDICATOR lamp does not come on,
Indoor/outdoor unit communication error
(Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49C worked/
insufficient refrigerant
Abnormal high pressure (63H worked)/Overheating
protection operation
Abnormal temperature of heat sink
Outdoor unit fan protection stop
Compressor overcurrent interruption/Abnormal of power module
Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and
abnormal synchronous signal to main circuit/Current sensor error
–
–
Other errors (Refer to the technical manual for the outdoor unit.)
2 beeps to confirm the self-check start signal was received and
there are no error records.
For details, check
the LED display
of the outdoor
controller board.
As for outdoor
unit, refer to
outdoor unit's
service manual.
*2 If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
17
Page 18
• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller
Check code displayed in the LCD.
If the unit cannot be operated properly after test run, refer to the following table to find the cause.
•
Symptom
Wired remote controllerLED 1, 2 (PCB in outdoor unit)
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not
appear even when operation
switch is turned ON (operation
lamp does not light up).
On the wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller can be received.
• Operation lamp is blinking.
• The buzzer makes a short ping sound.
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer)Indicates whether control power is supplied. Make sure that this LED is
LED2 (power for remote controller)
LED3 (communication between indoor and
outdoor units)
For about 2
minutes after
power-on
Subsequent to
about 2 minutes
after power-on
After LED 1, 2 are lighted, LED 2 is
turned off, then only LED 1 is
lighted.
(Correct operation)
Only LED 1 is lighted. →
Only LED 1 is lighted.
always lit.
Indicates whether power is supplied to the remote controller.
This LED lights only in the case of the indoor unit which is connected to the
outdoor unit refrigerant addresses “0”.
Indicates state of communication between the indoor and outdoor units.
Make sure that this LED is always blinking.
LED 1, 2 blink.
→
LED 1 blinks twice,
LED 2 blinks once.
•For about 2 minutes following power-on,operation of the remote controller is not possible
due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection
device is not connected.
•Reverse or open phase wiring for the outdoor
unit’s power terminal block (L1, L2, L3)
•Incorrect wiring between indoor and outdoor
units (incorrect polarity of S1, S2, S3)
•Remote controller wire short
Cause
18
Page 19
10-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
P2
Abnormal point and detection method
Room temperature thermistor (TH1)
1 The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 minutes. (The unit returns to normal operation, if it has been reset normally.)
2 Constantly detected during cooling,
drying, and heating operation.
Short: -90: or more
Open: -40: or less
Pipe temperature thermistor/Liquid
(TH2)
1
The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 minutes. (The unit returns to normal operation, if it has been reset normally.)
2 Constantly detected during cooling,
drying, and heating (except defrosting)
operation
Short: 90: or more
Open: -40: or less
1 Defective thermistor
characteristics
2 Contact failure of connector
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective indoor controller
1 Defective thermistor
characteristics
2 Contact failure of connector
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective refrigerant circuit is
5 Defective indoor controller
Note: Refer to the manual of outdoor unit for the details of display
such as F, U, and other E.
Cause
(CN20) on the indoor controller
board (Insert failure)
board
(CN44) on the indoor controller board (Insert failure)
causing thermistor temperature of 90: or more or -40:
or less.
board
Countermeasure
1–3 Check resistance value of thermistor.
If you put force on (draw or bend) the lead wire
with measuring resistance value of thermistor, breaking of wire or contact failure can be
detected.
2 Check contact failure of connector (CN20) on
4 Check room temperature display on remote
Replace indoor controller board if there is
temperature.
Turn the power off, and on again to operate
after check.
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN44) on
4 Check pipe <liquid> temperature with remote
5 Check pipe <liquid> temperature with
....
0:
15.0k"
....
10:
9.6k"
....
20:
6.3k"
....
30:
4.3k"
....
40:
3.0k"
the indoor controller board. Refer to 10-7-1.
Turn the power on again and check restart
after inserting connector again.
controller.
abnormal difference with actual room
the indoor controller board. Refer to 10-7-1.
Turn the power on and check restart after
inserting connector again.
controller in test run mode. If pipe <liquid>
temperature is extremely low (in cooling
mode) or high (in heating mode), refrigerant
circuit may have defective.
remote controller in test run mode. If there is
extremely difference with actual pipe <liquid>
temperature, replace indoor controller board.
P4
P5
Drain sensor (DS)
1 Suspensive abnormality, if short/open
of thermistor is detected for 30 seconds
continuously.Compressor and indoor fan
will be turned off
2 Short/open is detected for 30 seconds
continuously during suspensive
abnormality.
(The unit returns to normal operation,
if it has normally reset.)
3 Detect the following condition.
• During cooling and drying operation.
• In case that pipe <liquid> temperature room temperature <-10deg
(Except defrosting)
• When pipe <liquid> temperature or
room temperature is short/open
temperature.
• During drain pomp operation.
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor is let heat itself and
temperature rises slightly. Compressor
and indoor fan will be turned off.
2 Drain pump is abnormal if the condition
above is detected during suspensive
abnormality.
3 Constantly detected during drain pump
operation.
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN31) on the indoor controller
board. (Insert failure).
3 Breaking of wire or contact
failure of drain sensor wiring.
4 Defective indoor controller board.
1 Malfunction of drain pump
2 Defective drain
Clogged drain pump
Clogged drain pipe
3 Attached drop of water at the
drain sensor
• Drops of drain trickles from
lead wire.
• Clogged filter is causing
wave of drain.
4 Defective indoor controller board.
Turn the power off, and on again to operate
after check.
1–3 Check resistance value of thermistor.
....
0:
6.0k"
....
10:
3.9k"
....
20:
2.6k"
....
30:
1.8k"
....
40:
1.3k"
2 Check contact failure of connector (CN31) on
the indoor controller board. Refer to 10-7-1.
Turn the power on again and check restart
after inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited,
and abnormality reappears.
Turn the power off, and on again to operate
after check.
1 Check if drain-up machine works.
2 Check drain function.
3 Check the setting of lead wire of drain sensor
and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited
and abnormality reappears.
Refer to 10-7-1.
Turn the power off, and on again to operate
after check.
19
Page 20
Error Code
Abnormal point and detection method
Freezing/overheating protection is working
1 Freezing protection (Cooling mode)
The unit is in 6-minute resume prevention mode if pipe <liquid or condenser/
evaporator> temperature stays under
-15: for 3 minutes, 3 minutes after the
compressor started. Abnormal if it stays
under -15: for 3 minutes again within
16 minutes after 6-minute resume prevention mode.
Cause
(Cooling or drying mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Low-load (low temperature)
operation out of the tolerance
range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defective.
Countermeasure
(Cooling or drying mode)
1 Check clogs of the filter.
Remove shields.
2
4 Refer to 10-7-1.
P6
P8
2 Overheating protection (Heating mode)
The units is in 6 minute resume
prevention mode if pipe <condenser /
evaporator> temperature is detected as
over 70: after the compressor started.
Abnormal if the temperature of over
70: is detected again within 30 minutes
after 6 minute resume prevention mode.
Pipe temperature
<Cooling mode>
Detected as abnormal when the pipe temperature is not in the cooling range 3 minutes after compressor start and 6 minutes
after the liquid or condenser/evaporator
pipe is out of cooling range.
Note 1) It takes at least 9 minutes to
detect.
Note 2) Abnormality P8 is not detected in
drying mode.
Cooling range : -3 °C ] (TH-TH1)
TH: Lower temperature between: liquid
pipe temperature (TH2) and condenser/evaporator temperature (TH5)
TH1: Intake temperature
<Heating mode>
When 10 seconds have passed after the
compressor starts operation and the hot
adjustment mode has finished, the unit is
detected as abnormal when condenser/
evaporator pipe temperature is not in heating range within 20 minutes.
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
(clogs)
(Heating mode)
1 Clogged filter (reduced airflow)
2 Short cycle of air path
3 Over-load (high temperature)
operation out of the tolerance
range
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is defective.
5 Defective outdoor fan control
6 Overcharge of refrigerant
7 Defective refrigerant circuit
(clogs)
8 Bypass circuit of outdoor unit
is defective.
1 Slight temperature difference
between indoor room
temperature and pipe <liquid
or condenser / evaporator>
temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
<liquid or condenser /
evaporator> thermistor
• Defective refrigerant circuit
2 Converse connection of
extension pipe (on plural units
connection)
3 Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
4 Defective detection of indoor
room temperature and pipe
<condenser / evaporator>
temperature thermistor
5 Stop valve is not opened
completely.
5 Check outdoor fan motor.
67 Check operating condition of refrigerant
circuit.
(Heating mode)
1 Check clogs of the filter.
2 Remove shields.
4 Refer to 10-7-1.
5 Check outdoor fan motor.
6~8Check operating condition of refrigerant
circuit.
1~4 Check pipe <liquid or condenser / evapo-
rator> temperature with room temperature display on remote controller and
outdoor controller circuit board.
Pipe <liquid or condenser / evaporator>
temperature display is indicated by setting SW2 of outdoor controller circuit
board as follows.
Conduct temperature check with outdoor
controller circuit board after connecting
(
‘A-Control Service Tool(PAC-SK52ST)’.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
)
Note 3) It takes at least 27 minutes to
detect abnormality.
Note 4) It excludes the period of defrosting.
(Detection restarts when defrosting
mode is over.)
Heating range : 3 °C [ (TH5-TH1)
20
Page 21
Error Code
P9
Abnormal point and detection method
Pipe temperature thermistor /
Condenser-Evaporator (TH5)
1 The unit is in 3-minute resume protec-
tion mode if short/open of thermistor is
detected. Abnormal if the unit does not
get back to normal within 3 minutes. (The
unit returns to normal operation, if it has
been reset normally.)
2 Constantly detected during cooling,
drying, and heating operation (except
defrosting)
Short: 90: or more
Open: -40: or less
Cause
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN29) on the indoor controller
board (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Temperature of thermistor is
90: or more or -40: or less
caused by defective refrigerant
circuit.
5 Defective indoor controller
board
Countermeasure
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN29)
on the indoor controller board.
Refer to 10-7-1.
Turn the power on and check restart after
inserting connector again.
4 Operate in test run mode and check pipe
<condenser / evaporator> temperature with
outdoor controller circuit board. If pipe
<condenser / evaporator> temperature is
extremely low (in cooling mode) or high (in
heating mode), refrigerant circuit may have
defect.
5 Operate in test run mode and check pipe
<condenser / evaporator> temperature with
outdoor control circuit board. If there is
extreme difference with actual pipe
<condenser / evaporator> temperature,
replace indoor controller board.
There is no abnormality if none of above
comes within the unit.
Turn the power off and on again to operate.
In case of checking pipe temperature
with outdoor controller circuit board,
be sure to connect A-control service
data at the same time and compares the
received and transmitted data. Abnormal
if these data are judged to be different
30 continuous times. (Error code: E3)
mitted data at the same time and compares the received and transmitted data.
Abnormal if these data are judged to
be different 30 continuous times. (Error
code: E5)
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as “sub” remote controller.
In this case, E0 is displayed
on remote controller, and E4
is displayed at LED (LED1,
LED2) on the outdoor controller
circuit board.
3 Miswiring of remote controller
4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board
of refrigerant addresses “0”.
6 Noise has entered into the
transmission wire of remote
controller.
1 2 remote controllers are set as
“main.”
(In case of 2 remote con trollers)
2 Remote controller is connected
with 2 indoor units or more.
3 Repetition of refrigerant
address
4 Defective transmitting receiving
circuit of remote controller
5 Defective transmitting receiving
circuit of indoor controller board
6 Noise has entered into trans-
mission wire of remote control-
ler.
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main”
if there is no problem with the action above.
3 Check wiring of remote controller.
• Total wiring length: max. 500m
(Do not use cable x 3 or more.)
• The number of connecting indoor units:
max. 16 units
• The number of connecting remote controller: max. 2 units
When it is not the above-mentioned problem of
1~3
4 Diagnose remote controllers.
a) When “RC OK” is displayed,
Remote controllers have no problem.
Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
b) When “RC NG” is displayed,
Replace remote controller.
c)When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormality.
* If the unit is not normal after replacing
indoor controller board in group control,
indoor controller board of address “0” may
be abnormal.
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting.
4~6 Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem.
Turn the power off,and on again to check.
When becoming abnormal again, replace
indoor controller board.
b)When “RC NG” is displayed, replace
remote controller.
c)When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormal-
ity.
21
Page 22
Error Code
E6
Abnornal point and detection method
Indoor/outdoor unit communication
error (Signal receiving error)
1 Abnormal if indoor controller board
cannot receive any signal normally for 6
minutes after turning the power on.
2 Abnormal if indoor controller board
cannot receive any signal normally for 3
minutes.
3 Consider the unit abnormal under the fol-
lowing condition: When 2 or more indoor
units are connected to an
outdoor unit, indoor controller board
cannot receive a signal for 3 minutes
from outdoor controller circuit board, a
signal which allows outdoor controller
circuit board to transmit signals.
Cause
1 Contact failure, short circuit or,
miswiring (converse wiring) of
indoor/outdoor unit connecting
wire
2 Defective transmitting receiving
circuit of indoor controller board
3 Defective transmitting receiving
circuit of indoor controller board
4 Noise has entered into indoor/
outdoor unit connecting wire.
Countermeasure
* Check LED display on the outdoor control
circuit board. (Connect A-control service
tool, PAC-SK52ST.)
Refer to outdoor unit service manual.
1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or
outdoor unit.
Check all the units in case of twin triple
indoor unit system.
2-4 Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board or outdoor
controller circuit board.
* Other indoor controller board may have
defect in case of twin triple indoor unit
system.
E7
Fb
E1
E2
PA
Indoor/outdoor unit communication
error (Transmitting error)
Abnormal if “1” receiving is detected 30
times continuously though indoor controller
board has transmitted “0”.
Indoor controller board
Abnormal if data cannot be read normally
from the nonvolatile memory of the indoor
controller board.
Remote controller control board
1 Abnormal if data cannot be read nor-
mally from the nonvolatile memory of the
remote controller control board.
(Error code: E1)
or
2 Abnormal if the clock function of remote
controller cannot be operated normally.
(Error code: E2)
Forced compressor stop
(due to water leakage abnormality)
1 When the intake temperature subtracted
with liquid pipe temperature is less than
-10:, drain sensor is detected whether
it is soaked in the water or not at the interval
of 90 seconds. (Drain pump will start operating
when the drain sensor is detected to be
soaked in the water.)
2 The unit has a water leakage abnormality
when the following conditions, a and b, are
satisfied while the above-mentioned detection
is performed.
a) The drain sensor is detected to be
soaked in the water 10 times in a row.
b) The intake temperature subtracted with
liquid pipe temperature is detected to be
less than -10: for a total of 30 minutes.
(When the drain sensor is detected to
be NOT soaked in the water, the detection
record of a and b will be cleared.)
3 The drain sensor detection is performed
in operations other than cooling. (When
the unit stops operating, during heating
or fan operation, when the unit stops
because of some abnormality)
*Once the water leakage abnormality is
detected, abnormality state will not be
released until the main power is reset.
6 Extension piping connection
difference at twin, triple,
quadruple system.
7 Mis-wiring of indoor/ outdoor
connecting at twin, triple,
quadruple system.
8 Room temperature thermistor /
liquid pipe temperature thermis tor detection is defective.
1-3 Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
1 Replace indoor controller board.
1 Check the drain pump.
2 Please confirm whether water can be
drained.
3 Confirm the resistance of the drain sensor.
4 Check the connector contact failure.
5 Check the drain sensor leadwire mounted.
Check the filter clogging
6 Check the piping connection.
7 Check the indoor/ outdoor connecting wires.
8 Check the room temperature display of
remote controller.
Check the indoor liquid pipe temperature
display of outdoor controller board.
22
Page 23
10-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Phenomena
(1)LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is also off.
1 Power supply of rated voltage is not supplied to out-
door unit.
2 Defective outdoor controller circuit board.
3 Power supply of 220~240V is not supplied to indoor
unit.
4 Defective indoor power board.
5 Defective indoor controller board.
(For the separate indoor/outdoor unit power sup-
ply system)
1 Power supply of 220~240V AC is not supplied to
indoor unit.
2 The connectors of the optional replacement kit are
not used.
3 Defective indoor controller board.
4 Defective indoor power board.
• When LED1 on indoor controller board is lit.
1 Mis-setting of refrigerant address for outdoor unit
(There is no unit corresponding to refrigerant
address “0”.)
Cause
Countermeasure
1 Check the voltage of outdoor power
supply terminal block (L, N) or (L
• When AC 220~240V is not detected.
Check the power wiring to outdoor unit
and the breaker.
• When AC 220~240V is detected.
—Check 2 (below).
2 Check the voltage between outdoor
terminal block S1 and S2.
• When AC 220~240V is not detected.
Check the fuse on outdoor controller
circuit board.
Check the wiring connection.
• When AC 220~240V is detected.
—Check 3 (below).
3 Check the voltage between indoor terminal
block S1 and S2.
• When AC 220~240V is not detected.
Check indoor/outdoor unit connecting
wire for mis-wiring.
• When AC 220~240V is detected.
—Check 4 (below).
4 Check voltage output from CN2S on indoor
power board (DC13.1V). Refer to 10-7-2.
• When no voltage is output.
Check the wiring connection.
• When output voltage is between
DC12.5V and DC13.7V.
—Check 5 (below).
5 Check the wiring connection between
indoor controller board and indoor power
board. Check the fuse on indoor controller
board. If no problems are found, indoor
controller board is defective.
1 Check the voltage of indoor power supply
terminal block (L,N).
• When AC220~240V is not detected.
Check the power supply wiring.
• When AC220~240V is detected.
-Check 2 (below).
2 Check that there is no problem in the
method of connecting the connectors.
• When there are problems in the method
of connecting the connectors.
Connect the connector correctly refer-
ring to installation manual of an optional
kit.
• When there is no problem in the meth-
od of connecting the connectors.
-Check 3 (below).
3 Check voltage output from CNDK on
indoor controller board.
• When AC220~240V is not detected.
Check the fuse on indoor controller
board.
Check the wiring connection between
indoor power supply terminal block and
CND on indoor controller board.
• When AC220~240V is detected.
-Check 4 (below).
4 Check voltage output from CN2S on
indoor power board.
• When no voltage output.
Check the wiring connection between
CNDK on indoor controller board and
CNSK on indoor power board.
If no problem are found,indoor power
board is defective.
• When DC12.5~13.7V is detected.
Check the wiring connection between
CN2S on indoor power board and
CN2D on indoor power board.
If no problem are found,indoor controller
board is defective.
1 Reconfirm the setting of refrigerant
address for outdoor unit
Set the refrigerant address to “0”.
(For grouping control system under
which 2 or more outdoor units are
connected, set one of the units to “0”.)
Set refrigerant address using SW1 (3-6)
on outdoor controller circuit board.
3, N).
23
Page 24
Phenomena
(2)LED2 on indoor controller board
is blinking.
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Cause
• When LED1 on indoor controller board is also blinking.
Connection failure of indoor/outdoor unit connecting
wire
• When LED1 is lit.
1 Mis-wiring of remote controller wires
Under twin triple indoor unit system, 2 or more indoor
units are wired together.
2 Refrigerant address for outdoor unit is wrong or not
set.
Under grouping control system, there are some units
whose refrigerant address is 0.
3 Short-cut of remote controller wires
4 Defective remote controller
Countermeasure
Check indoor/outdoor unit connecting wire
for connection failure.
1 Check the connection of remote con troller wires in case of twin triple indoor
unit system. When 2 or more indoor units
are wired in one refrigerant system,
connect remote controller wires to one of
those units.
2 Check the setting of refrigerant address
in case of grouping control system.
If there are some units whose refrigerant
addresses are 0 in one group, set one of
the units to 0 using SW1 (3-6) on outdoor
controller circuit board.
34 Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the shortcut of remote controller wires.
• When LED2 is lit, connect remote
controller wires again and:
if LED2 is blinking, remote controller
is defective; if LED2 is lit, connection
failure of remote controller terminal
block etc. has returned to normal.
(3)Upward/downward vane
performance failure
(4)Receiver for wireless remote
controller
1 The vane is not downward during defrosting and heat
preparation and when the thermostat is OFF in HEAT
mode. (Working of COOL protection function)
2 Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
• Up/down vane setting is “No vanes”.
3 Upward/downward vane does not work.
• The vane is set to fixed position.
1 Weak batteries of wireless remote controller.
2 Contact failure of connector (CNB) on wireless
remote controller board.
(Insert failure)
3 Contact failure of connector (CN90) on indoor con-
troller board.(Insert failure)
4 Contact failure of connector between wireless remote
controller board and indoor controller board.
1 Normal operation (The vane is set to
horizontal regardless of remote control.)
2 Check 2 (left).
• Check the vane motor. (Refer to “How
to check the parts”.)
• Check for breaking of wire or connection failure of connector.
• Check “Up/down vane setting”. (Unit
function selection by remote controller).
3 Normal operation (Each connector on
vane motor side is disconnected.)
1 Replace batteries of wireless remote con-
troller.
2~4
Check contact failure of each connector. If no problems are found of connector,
replace indoor controller board.
When the same trouble occurs even if
indoor controller board is replaced,
replace wireless remote controller
board.
24
Page 25
10-5. EMERGENCY OPERATION
10-5-1. When wireless remote controller troubles or its battery is exhausted
1. Emergency operation is available in such a case using emergency operation switch equipped next to the receiver of indoor
unit.
2. To start operation
• Cooling Operation·······Press (Cooling) switch.
• Heating Operation·······Press (Heating) switch.
wWhen the unit starts operating, the power lamp is lit.
Emergency switch(Cool)
Emergency switch(Heat)
COOL
STAND
HEAT
BY
ON
O F F
Receiving
section
Defrosting • Initial heating lamp
Power lamp
+Emergency operation will be performed as follows.
Mode
Set temperature
Fan speed
Airflow direction
Cooling
24
High
Horizontal (30deg)
Heating
24
High
Downward (70deg)
3. To stop operation
• Press either emergency operation switch (cooling/heating).
10-5-2. When wired remote controller or indoor unit micro computer troubles
1. If there is not any other wrong when trouble occures, emergency operation starts as the indoor controller board switch (SWE)
is set to ON.
During the emergency operation the indoor unit is as follows;
(1) Indoor fan high speed operation
2. When emergency operating for COOL or HEAT, setting of the switch (SWE) in the indoor controller board and outdoor unit
emergency operation are necessary.
3. Check items and notices as the emergency operation
(1) Emergency operation cannot be used as follows;
• When the outdoor unit is something wrong.
• When the indoor fan is something wrong.
• When drain over flow protected operation is detected during self-diagnosis. (Error code : P5)
(2) Emergency operation will be serial operation by the power supply ON/OFF.
ON/OFF or temperature, etc. adjustment is not operated by the remote controller.
(3) Do not operate for a long time as cold air is blown when the outdoor unit starts defrosting operation during heat emer-
gency operation.
(4) Cool emergency operation must be within 10 hours at most. It may cause heat exchanger frosting in the indoor unit.
(5) After completing the emergency operation, return the switch setting, etc. in former state.
(6) Since vane does not work at emergency operation, position the vane manually and slowly.
CN22
Connect to the terminal
block(TB5)
(Remote controller connecting
wire)
(10.4~14.6V DC)
CN20
Room temperature
thermistor (TH1)
CN21
Pipe temperature
thermistor/Liquid (TH2)
CN29
Condenser/evaporator
temperature thermistor (TH5)
CN31
Drain sensor (DS)
CN90
Connect to the wireless
remote controller board
(CNB)
CN6V
Vane motor output
(MV)
CN41
Connector (HA terminal-A)
SWE
Emergency operation
FAN
Fan motor output
Jumper wire J41, J42
Pair number setting with
wireless remote controller
27
SW2
Capacity setting
CN51
Centrally control
CN24
Heater output
(12V DC)
CN2L
Connector
(LOSSNAY)
SW1
Model setting
Page 28
10-7-2. Indoor power board
PKA-RP35GAL PKA-RP35GAL#1 PKH-P35GALH
PKA-RP50GAL PKA-RP50GAL#1 PKH-P50GALH
CN2S
Connect to the indoor controller board (CN2D)
Between 1 to 3 12.6-13.7V DC (Pin1 (+))
CNSK
Connect to the indoor controller board
(CNDK)
Between 1 to 3 220-240V AC
28
Page 29
10-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control P.C. board.
SW1 and SW2 are equipped only for service parts.
Model setting and capacity setting are memorized in the nonvolatile memory of the control P.C. board of
the unit.
(Marks in the table below) Jumper wire ( : Short : Open)
Jumper wire
SW1
SW2
J41
J42
JP1
Functions
Model
settings
Capacity
settings
Pair number
setting with
wireless
remote
controller
Unit type
setting
Setting by the dip switch and jumper wire
For service board
12345
Models
PKA-RP35GAL
PKH-P35GALH
PKA-RP50GAL
PKH-P50GALH
Wireless remote
controller setting
0
1
2
3 ~ 9
Model
Without TH5
With TH5
ON
OFF
Service board
12345
12345
Control PCB setting
J41J42
JP1
OFF
OFF
ON
ON
Remarks
<Initial setting>
Wireless remote controller: 0
Control PCB: (for both J41 and J42)
Four pair number settings are supported.
The pair number settings of the wireless remote
controller and indoor control PCB (J41/J42) are
given in the table on the left.
(' ' in the table indicates the jumper line is disconnected.)
There is no jumper (JP1) because these models
have the cond./eva. temperature thermistor (TH5).
For PKA-RP35GAL#1, PKA-RP50GAL#1
11-1-1. Operation
(1) Rotation function (and Back-up function)
• Outline of functions
· Main and sub unit operate alternately according to the interval of rotation setting.
w Main and sub unit should be set by refrigerant address.(Outdoor Dip switch setting)
Refrigerant address"00" Main unit
Refrigerant address"01" Sub unit
· When error occurrs to one unit, another unit will start operation.(Back-up function)
• System constraint
· This function is available only by the grouping control system(INDOOR UNIT : OUTDOOR UNIT=1:1) of 2 refrigerant
groups.(Refer to Fig. 1)
· Main indoor unit should be connected for wired remote controller and the transmission line(TB5) for main and sub unit
should also be connected. (Refer to Fig. 1)
(This function cannot be set by wireless remote controller.)
· Set refrigerant address of each unit.(Dip switch on the outdoor unit···Refrigerant address 00/01)
Operation pattern
[Back-up function only]··· Request code number "312"
Start operation
Main
unit
IC-1
Sub
unit
IC-2
[Rotation function] & [Back-up function]··· Request code number "313~318"
Start operation
Main
unit
IC-1
Sub
unit
IC-2
(Ex:When the request code number is "313", each unit operates alternately in daily cycle.)
Run
Stop
Main SubSub Main Main Sub
Run
Stop
1~28 days1~28 days
Error occurs on main unit.
Main Sub
Abnormal condition
Run
Stop
Run
Run
StopRun
Error occurs on main unit.
Abnormal condition
Main
unit
2
Refrigerant address
"00"
OC-1
3(2)
IC-1
2
RC
Fig. 1
OC : Outdoor unit
IC : Indoor unit
RC : Wired remote controller
Refrigerant address
"01"
OC-2
Sub
3(2)
unit
IC-2
Note:
· When the uint is restarted to operate after turning off the power or OFF operation, the unit which was operating will start
operation.
· To operate the main unit, refer to the 11-1-2. and set the requet code No. which is not the same as the current one, and set
again the former request code No.
(2) 2nd stage cut-in function
Outline of functions
· Number of operating units is determined according to the room temperature and set point.
· When room temperature becomes higher than set point, standby unit starts.(2 units operation)
· When room temperature falls below set point -4:, standby unit stops.(1 unit operation)
System constraint
· This function is available only in rotation operation and back-up function in
cooling mode.
[2nd stage cut-in function]··· Request code number "322~324"
Start operationSub unit start operation
Main
unit
IC-1
Room temp. Set point
Run
Room temp. < Set point -4
Sub unit stop
Sub
unit
IC-2
StopStopRun
30
Page 31
11-1-2. How to set rotation function(Back-up function, 2nd stage cut-in function)
You can set these functions by wired remote controller.(Maintenance monitor)
NOTICE
Both main and sub unit should be set in same setting.
Every time replacing indoor controller board for servicing, the function should be set again.
(1) Request Code List
Rotation setting
Setting No.
(Request code)
No.1
(310)
No.2
(311)
No.3
(312)
No.4
(313)
No.5
(314)
No.6
(315)
No.7
(316)
No.8
(317)
No.9
(318)
Setting contents
Monitoring the request code of current setting.
Rotation and Back-up OFF (Normal group control operation)
Back-up function only
Rotation ON (Alternating interval = 1day) and back up function
Rotation ON (Alternating interval = 3day) and back up function
Rotation ON (Alternating interval = 5day) and back up function
Rotation ON (Alternating interval = 7day) and back up function
Rotation ON (Alternating interval = 14day) and back up function
Rotation ON (Alternating interval = 28day) and back up function
Initial
setting
nd stage cut-in setting
2
Setting No.
(Request code)
No.1
(320)
No.2
(321)
No.3
(322)
No.4
(323)
No.5
(324)
Setting contents
Monitoring the request code of current setting.
Cut-in function OFF
Cut-in Function ON(Set point = Set temp.+ 4°C(7.2°F))
Cut-in Function ON(Set point = Set temp.+ 6°C(10.8°F))
Cut-in Function ON(Set point = Set temp.+ 8°C(14.4°F))
Initial
setting
3131
Page 32
(2) Setting method of each function by wired remote controller
1. Stop operation().
2. Press the button () for 3 seconds so that [Maintenance mode] appears on the screen ().After a while, [00] appears in the refrigerant address number display area.(at )
3. Press the button () for 3 seconds to switch to [Maintenance monitor].
Note) It is not possible to switch to [Maintenance monitor] during data request in maintenance mode
[----] appears on the screen () when [Maintenance monitor] is activated.
(The display () now allows you to set a request code No.)
TEST
CHECK
(i.e., while “----” is blinking) since no buttons are operative.
B: Refrigerant address
C: Data display area
D: Request code display area
4. Press the [TEMP ( and )] buttons () to select the desired refrigerant address.
[ScreenB]
5. Press the [CLOCK ( and )] buttons () to set the desired request code No.(“311~318”, “321~324”)
6. Press the button () to perform function setting.If above setting operations are done correctly, "Request code number" will appear in data display area.()[Example: When the "311" of "Request code number" is set, [311] appears on the screen.()]
[Refererence]
You can check current "request code number" setting by setting the "request code number"(“310” or “320”) and
pressing the button.()
[Example: When the current setting is "Setting No.2(Request code 311)", [311] appears on the screen.()]
7. To return to normal mode, press the button ().
1. REMOVE THE LOWER SIDE OF THE INDOOR UNIT FROM
THE INSTALLATION PLATE.
(1) Remove the left / right corner box of the indoor unit.
(2) Hold and pull down the lower and both ends of the indoor
unit, and remove the ▼ section from the square hole.
(Refer to the figure 2.1)
Or remove the front panel and push the ▼ section down
by using hexagonal wrench ,etc. from the front side.
(Refer to the figure 2.2).
(3) Unhook the top of the indoor unit from the back plate catch.
(Figure 2.2)
Square hole
2. REMOVING THE FRONT PANEL.
(1) Open the front grille.
(2) Remove the terminal block cover with a screw.
(3) Remove the screw 3caps then remove the set 3screws.
(4) After removing the lower side of the front panel a little,
remove it as pulling toward upper.
Up
Down
PHOTOS & ILLUSTRATION
(Figure 1)
(Figure2.1)
(Figure 3)
Hook
Hook
Square hole
Terminal block cover
3. REMOVING THE INDOOR CONTROLLER BOARD.
(1) Remove the terminal block cover.
(2) Remove the front panel. (see the photo 1)
(3) Remove the electrical parts box(2screws).
(4) Remove the electrical parts box cover(1screw).
(5) Disconnect the connector on the controller board and
remove the controller board by Pulling up the hook of the
controller case.
w To smooth works, hang the side hooks of the electrical
parts box on the hook of the motor cover.
(see the photo 3)
(Photo 1)
Front
panel
(Photo 2)
Motor cover
Electrical parts
box hook w
(Photo 3)
Front grille
Set screw
Set screw
Electrical parts
box
Set screw
Control board
3333
Hook
Controller case
Electrical parts box
Page 34
OPERATION PROCEDURE
PHOTOS & ILLUSTRATION
4. REMOVING THE POWER BOARD
(1) Remove the front panel.(see the photo 1)
(2) Remove the electrical parts box(2screws).(see the photo 2)
(3) Disconnect the whole connector in the control board.
(4) After lifting the controller case with pressing it’s convex
section, remove the controller case and the control board
simultaneously.(see the photo 3)
(5) Disconnect the connector in the power board.
(6) Remove the power board.
5. REMOVING THE VANE MOTOR
(1) Disconnect the connector CN6V on the indoor controller
board.
(2) Remove the 2screws of the vane motor, disconnect the
lead wire and remove the vane motor from the shaft.
6. REMOVING THE THERMISTOR
(1) Removing the room temperature thermistor TH1.
1Disconnect the connector CN20<red> on the indoor
controller board.
2Remove the room temperature thermistor from the holder.
(2) Removing the pipe temperature thermistor TH2.
1Disconnect the connector CN21<white> on the controller
board.
2Remove the pipe temperature thermistor with set to the pipe.
(3) Removing the indoor coil temperature thermistor TH5.
1Disconnect the connector CN29<black> on the indoor con-
troller board.
2Remove the gas pipe thermistor with set to the pipe.
(Photo 4)
(Photo 5)
Nozzle
assemble
Van motor
(Photo 6)
Pipe
temperature
thermistor
(TH2)
Room
temperature
thermistor
(TH1)
Power board
Electrical parts
box
Set screws
Lead wire
Condenser
/evaporator
temperature
thermistor
(TH5)
Electrical
parts box
7. REMOVING THE NOZZLE ASSEMBLE
(1) Disconnect the connector CN6V on the controller board.
(2) Disconnect the lead wire of the vane motor.
(3) Remove the corner cover.
(4) Pull the drain hose out from the nozzle assemble.
(5) Unhook the hook of the lower nozzle assemble and
pull the nozzle assemble toward you,then remove the
nozzle assemble by sliding it down.
8. REMOVING THE ELECTRICAL PARTS BOX
(1) Remove the terminal block cover.
(2) Disconnect the connector <yellow> of the wireless remote
controller board.
(3) Remove the front panel.(see the photo 1)
(4) Disconnect the vane motor connector.
(5) Disconnect the fan motor connector from the fan motor.
(6) Disconnect the connector <yellow> of the heater. (only PKH).
(7) Remove the liquid(TH2) / gas(TH5) pipe thermistors.(see the
photo 6)
(8) Remove the electrical parts box (2screws).
(Photo 7)
Nozzle assemble
(Photo 8)
Pipe
temperature
thermistor
Hook
Fan motor connector
Drain hose
Corner cover
Vane motor
connector
Electrical
parts box
34
Page 35
OPERATION PROCEDUREPHOTOS & ILLUSTRATION
9. REMOVING THE FAN MOTOR.
(1) Remove the terminal block cover.
(2) Disconnect the connector <yellow> of the wireless remote
controller board.
(3) Remove the front panel.(see the photo 1)
(4) Remove the electrical parts box.(see the photo 8)
(5) Remove the nozzle assemble.(see the photo 7)
(6) Remove the fan motor leg fixing 3screws.
(7) Unscrew the set screws using by alankey and remove it by
sliding the fan motor to right.
(8) Remove the 4screws and remove the motor cover from the
fan motor leg.
10. REMOVING THE LINE FLOW FAN
(1) Remove the terminal block cover.
(2) Remove the front panel.(see the photo 1)
(3) Remove the electrical parts box.(see the photo 8)
(4) Remove the nozzle assembly.(see the photo 7)
(5) Remove the fan motor.(see the photo 9)
(6) Remove the pipe fixture with 2screws.(see the photo12)
(7) Remove the left / right screws of the heat exchanger and
pull the left-hand side up.
(8) Remove the 2screws by sliding it toward you remove the
fixture(fixing bearing).
w The fan motor is removable first , when the fan removing is hard.
w When resetting the fan to the fan motor. Locate and fix the shaft after installing the fan.
(Photo 9)
Set
screw
(Photo 10)
Motor cover
Fan motor
(Photo11)
Heat exchanger
Set screws
Fixture(fixing bearing)
Motor cover
Fan motor
screws
motor leg
11. REMOVING THE HEAT EXCHANGER
(1) Remove the terminal block cover.
(2) Disconnect the connector <yellow> of the wireless remote
controller board.
(3) Remove the front panel.(see the photo 1)
(4) Remove the electrical parts box.(see the photo 8)
(5) Remove the corner box.
(6) Remove the nozzle assemble.(see the photo 7)
(7) Remove the 2screws and the pipe fixture.
(8) Remove the 2screws and heat exchanger.
(1) Remove the terminal block cover.
(2) Disconnect the connector <yellow> for the wireless remote
controller.
(3) Remove the front panel.(see the photo 1)
(4) Remove the electrical parts box.(see the photo 8)
(5) Remove the nozzle assembly.(see the photo 7)
(6) Remove the heat exchanger.(see the photo 12)
(7) Remove the 2screws and electrical heater.
(Photo 12)
Set screw
(Photo 13)
Pipe fixture
Set screws
Electrical heater
Heat exchanger
Set screws
35
Page 36
OPERATION PROCEDURE
PHOTOS & ILLUSTRATION
13. REMOVING the SIGNAL RECEIVING P.C. BOARD
(1) Remove the terminal block cover.
(2) Disconnect the connector <yellow> for the wireless remote
controller.
(3) Remove the front panel.(see the photo 1)
(4) Remove the 2screws and signal receiving p.c. board cover.
(5) Remove the signal receiving p.c. board.
(Photo 14)
Set screws
(Photo 15)
Front
panel
Signal receiving p.c. board cover
Front
panel
Signal receiving p.c. board
36
Page 37
13PARTS LIST (non-RoHS compliant)
STRUCTURAL PARTS
PKH-P35GALH, PKA-RP35GAL
PKH-P50GALH, PKA-RP50GAL
2
4
5
6
1
3
12
11
No.
Parts No.
R01 07Y 808
1
R01 09Y 658
2
R01 07Y 623
3
R01 89Y 651
4
R01 07Y 096
5
R01 07Y 092
6
R01 07Y 691
7
R01 A16 500
8
R01 07Y 002
9
R01 24K 658
10
R01 07Y 658
11
R01 09Y 635
12
R01 07Y 635
T7W E06 714
13
R01 E01 049
14
R01 E00 075
15
7
8
Parts Name
BACK PLATE
CORNER COVER
UNDER COVER
FRONT PANEL
SCREW CAP
VANE SLEEVE
FRONT GRILLE
AIR FILTER
AUTO VANE
RECEIVING UNIT
CORNER COVER
BOX ASSEMBLY
BOX ASSEMBLY
WIRELESS REMOTE CONTROLLER
WIRELESS REMOTE CONTROLLER DOOR
WIRELESS REMOTE CONTROLLER HOLDER
Specifications
9
10
PKH-
P35 / P50
GALH
1
1
1
1
3
1
1
2
1
1
1
1
1
1
1
13
PKA-
RP35 / RP50
GAL
1
1
1
1
3
1
1
2
1
1
1
1
1
1
1
1415
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
RU
Recommended
Q'ty
3737
Page 38
ELECTRICAL PARTS
PKH-P35GALH, PKA-RP35GAL
PKH-P50GALH, PKA-RP50GAL
1
37
36
4
3
2
35
5
34
6
32
27
33
9
7
8
17
1
31
29
30
28
26
25
24
10
11
23
16
12
10
13
14
15
18
19
20
21
22
No.
Parts No.Parts Name
R01 E48 480
1
T7W E56 480
R01 09Y 114
2
R01 07Y 114
3
R01 07Y 102
4
R01 005 103
5
R01 07Y 106
6
T7W A00 675
7
R01 07Y 524
8
R01 07Y 527
9
R01 07Y 530
10
R01 09Y 038
11
R01 07Y 038
R01 07Y 059
12
R01 E04 223
13
R01 E03 317
14
R01 07Y 135
15
R01 07Y 105
16
T7W A01 762
17
HEAT EXCHANGER
HEAT EXCHANGER
LINE FLOW FAN
LINE FLOW FAN
BEARING MOUNT
SLEEVE BEARING
BEARING SUPPORT
FAN GUARD
DRAIN PLUG
DRAIN HOSE
NOZZLE
GUIDE VANE
GUIDE VANE
ARM
VANE MOTOR
WIRELESS ADAPTER CONTROLLER BOARD
MOTOR COVER
RUBBER MOUNT
FAN MOTOR
Specifications
PM4V30-K
PKH-PKA-
P35 / P50
GALH
1
1
1
1
1
1
1
1
1
4
10
2
1
1
1
2
1
RP35 / RP50
GAL
1
1
1
1
1
1
1
1
1
4
10
2
1
1
1
2
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbo
l
MV
W.B
MF
Recommended
Q'ty
38
To be continued on the next page.
Page 39
From the preceding page.
Part numbers that is circled is not shown in the figure.
No.
Parts No.Parts Name
18
T7W A14 716
19
T7W E23 716
20
R01 588 255
21
T7W E40 310
22
23
24
R01 E02 313
25
R01 E02 239
26
27
R01 71G 215
28
29
R01 E58 202
30
T7W E05 202
31
R01 E02 202
32
R01 07Y 130
33
R01 64K 700
34
T7W E13 300
35
R01 986 706
36
R01 208 706
37
R01 20J 303
38
—
—
—
—
—
TERMINAL COVER
TERMINAL BLOCK
TERMINAL BLOCK
CAPACITOR
INDOOR CONTROLLER BOARD
CONTROLLER COVER
CONTROLLER CASE
POWER BOARD
FUSE
ELECTRICAL PARTS COVER
HEATER CONTACTOR
SENSOR HOLDER
CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR
ROOM TEMPERATURE THERMISTOR
PIPE TEMPERATUER THERMISTOR
MOTOR SUPPORT
HEATER THERMAL SWITCH
HEATER ELEMENT
THERMAL FUSE
THERMAL FUSE
INSULATOR
Specifications
3P(L, N, )
3P(S1, S2, S3)
2.0 ×440V
250V 6.3A
60C OFF 40C ON
800W
104C 10A
84C 10A
PKH-
P35 / P50
GALH
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
PKA-
RP35 / RP50
GAL
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
(BG02V195H10)
(BG02V194G01)
(BG25B573H06)
(BG00V196G41)
(RG25C546H06)
Diagram
Symbo
FUSE
Wiring
TB2
TB4
C
I.B
P. B
88H
TH5
TH1
TH2
26H
H1
FS1
FS2
Recommended
Q'ty
l
39
Page 40
14RoHS PARTS LIST
ELECTRICAL PARTS
PKH-P35GALH, PKA-RP35GAL, PKA-RP35GAL#1
PKH-P50GALH, PKA-RP50GAL, PKA-RP50GAL#1
1
37
36
4
3
2
35
5
34
6
32
27
33
9
7
8
17
1
31
29
30
28
26
25
24
10
11
23
16
12
10
13
14
15
18
19
20
21
22
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Parts No.Parts Name
RoHS
R01 E70 480
G
T7W H36 480
G
R01 E21 114
G
R01 E22 114
G
R01 08Y 102
G
R01 E04 103
G
R01 08Y 106
G
T7W A01 675
G
R01 08Y 524
G
R01 08Y 527
G
R01 08Y 530
G
R01 10Y 038
G
R01 08Y 038
G
R01 08Y 059
G
R01 E14 223
G
R01 E06 317
G
R01 08Y 135
G
R01 08Y 105
G
T7W A02 762
G
HEAT EXCHANGER
HEAT EXCHANGER
LINE FLOW FAN
LINE FLOW FAN
BEARING MOUNT
SLEEVE BEARING
BEARING SUPPORT
FAN GUARD
DRAIN PLUG
DRAIN HOSE
NOZZLE
GUIDE VANE
GUIDE VANE
ARM
VANE MOTOR
WIRELESS ADAPTER CONTROLLER BOARD
MOTOR COVER
RUBBER MOUNT
FAN MOTOR
Specifications
PM4V30-K
PKH-
P35 / P50
GALH
1
1
1
1
1
1
1
1
1
4
10
2
1
1
1
2
1
PKA-
RP35 / RP50
GAL(#1)
1
1
1
1
1
1
1
1
1
4
10
2
1
1
1
2
1
To be continued on the next page.
Remarks
(Drawing No.)
Wiring
Diagram
Symbo
l
MV
W.B
MF
Recom-
mended
Q'ty
40
Page 41
From the preceding page.
Part number that is circled is not shown in the figure.
PKH-PKA-
No.
18 G—TERMINAL COVER111
19 G T7W E23 716 TERMINAL BLOCK3P(L, N,
20 G R01 E20 246 TERMINAL BLOCK
21 G R01 E13 255 CAPACITOR2.0+×440V111C
22
23 G—CONTROLLER COVER111
24 G—CONTROLLER CASE111
25 G R01 E38 313 POWER BOARD111P.B
26 G R01 E06 239 FUSE250V 6.3A111FUSE
27 G—
28 G R01 E03 215 HEATER CONTACTOR188H
29 G—SENSOR HOLDER111
30 G R01 H05 202
31 G R01 H08 202
32 G R01 H11 202
33 G R01 08Y 130 MOTOR SUPPORT111
34 G R01 E11 700
35 G T7W E18 300 HEATER ELEMENT800W1H1
36 G R01 E00 706 THERMAL FUSE104°C 10A1FS1
37 G R01 E01 706 THERMAL FUSE84°C 10A1FS2
38 GR01 31J 303 INSULATOR1
Parts No.Parts Name
RoHS
G T7W E50 310
G T7W E73 310
INDOOR CONTROLLER BOARD
INDOOR CONTROLLER BOARD
ELECTRICAL PARTS COVER
CONDENSER/EVAPORATOR TEMPERATURE THERMISTOR
ROOM TEMPERATURE THERMISTOR
PIPE TEMPERATURE THERMISTOR
HEATER THERMAL SWITCH
Specifi cations
3P(S1, S2,S3)
60°C OFF 40°C ON
;
P35/P50
GALH
1TB2
)
111TB4
11I.B
111
111TH5
111TH1
111TH2
126H
RP35/RP50
GAL
RP35/RP50
GAL#1
Remarks
(Drawing No.)
(BG02V195H10)
1I.B
(BG02V194G01)
(BG25B573H06)
(BG00V196G53)
(RG25C546G01)
Wiring
Diagram
Symbol
Recommended
Q'ty
4141
Page 42
STRUCTURAL PARTS
PKH-P35GALH, PKA-RP35GAL, PKA-RP35GAL#1
PKH-P50GALH, PKA-RP50GAL, PKA-RP50GAL#1
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in May 2008 No.OC330 REVISED EDITION-B PDF 7
Distributed in Jun. 2006 No.OC330 REVISED EDITION-A PDF 8
Distributed in Apr. 2005 No.OC330 PDF 9
Made in Japan.
New publication, effective May 2008
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.