(White : 0.98Y 8.99/0.63) (Pure white : 6.4Y 8.9/0.4)
2
SAFETY PRECAUTION
CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R407C
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with
the followings.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
Store the piping to be used indoors during
installation, and both ends sealed until just
before brazing.
(Store elbows and other joints in a plastic bag.)
Use ESTR , ETHER or HAB as the lubricant to
coat flares and flange connection parts.
If large amount of mineral oil enters, that can cause
deterioration of refrigerant oil etc.
Use liquid refrigerant to seal the system.
If gas refrigerant is used to seal the system, the composition
of the refrigerant in the cylinder will change and performance
may drop.
Do not use a refrigerant other than R407C.
If another refrigerant (R22, etc.) is used, the chlorine in the
refrigerant may cause the lubricant deterioration.
Use a vacuum pump with a reverse flow check valve.
The vacuum pump oil may flow back into the refrigerant
cycle and cause the lubricant deterioration.
If dust, dirt, or water enters the refrigerant cycle,
deterioration of the oil and compressor trouble may result.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
2
Page 3
[1] Cautions for service
· After recovering all the refrigerant in the unit, proceed to working.
· Do not release refrigerant in the air.
· After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
[2] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder
· R407C cylinder are available on the market has a syphon pipe.
· Leave the syphon pipe cylinder standing and recharge it.
(By liquid refrigerant)
Unit
Gravimeter
(2) Recharge in refrigerant leakage case
· After recovering the all refrigerant in the unit, proceed to working.
· Do not release the refrigerant in the air.
· After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
[3] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No.Tool nameSpecifications
Gauge manifold· Only for R407C
1
· Use the existing fitting SPECIFICATIONS. (UNF7/16)
· Use high-tension side pressure of 3.43MPa·G or over.
Charge hose· Use the existing fitting SPECIFICATIONS. (UNF7/16)
2
· Use pressure performance of 5.10MPa·G or over.
Electronic scale
3
Gas leak detector· Use the detector for R134a or R407C.
4
Adapter for reverse flow check· Attach on vacuum pump.
5
Refrigerant charge base
6
Refrigerant cylinder· For R407C · Top of cylinder (Brown)
7
· Cylinder with syphon
Refrigerant recovery equipment
8
—
—
—
33
Page 4
Cautions for units utilizing refrigerant R410A
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with
the followings.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
Store the piping to be used indoors during
installation, and both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
If large amount of mineral oil enters, that can cause deterioration of refrigerant oil etc.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
4
Page 5
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.Tool nameSpecifications
Gauge manifold· Only for R410A
1
· Use the existing fitting
· Use high-tension side pressure of 5.3MPa·G or over.
Charge hose· Only for R410A
2
· Use pressure performance of 5.09MPa·G or over.
Electronic scale
3
Gas leak detector· Use the detector for R134a, R407C or R410A.
4
Adapter for reverse flow check· Attach on vacuum pump.
5
Refrigerant charge base
6
Refrigerant cylinder· Only for R410A · Top of cylinder (Pink)
7
· Cylinder with syphon
Refrigerant recovery equipment
8
specifications
—
—
—
. (UNF1/2)
5
Page 6
3
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
ON/OFF
Temperature setting buttons
Down
Up
Timer Menu button
(Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button
(Set Day button)
Opening the
lid
ON/OFF button
Fan Speed button
Filter button
(<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button
( Operation button)
To return operation
number
Ventilation button
( Operation button)
To go to next operation
number
Built-in temperature sensor
PART NAMES AND FUNCTIONS
Indoor Unit
Auto Air Swing Vane
Disperses airflow up and
down and adjusts the angle
of airflow direction.
Horizontal Air Outlet
Filters
Remove dust and pollutants
from return air.
Guide vane
Air flow can be changed to horizontal
by moving the Guide vane to the left or right.
Air intake
Returns air from room.
Wired remote controller
Once the controllers are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
6
Page 7
Wired remote controller
Display Section
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc.
*Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the
remote controller has been prohibited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, the time to be
switched off is shown.
TIME SUN MON TUE WED THU FRI SAT
TIMER
AFTER
ERROR CODE
°F°C
Hr
AFTER
°F°C
ONLY1Hr.
Up/Down Air Direction indicator
The indicator shows the direction
of the outcoming airflow.
“One Hour Only” indicator
Displayed if the airflow is set to
low or downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off in one hour,
when the airflow direction also
changes.
Room Temperature display
Shows the room temperature. The room
temperature display range is 8-39.
The display blinks if the temperature
is less than
Louver display
Indicates the action of the swing louver.
Does not appear if the louver is not
running.
(Power On indicator)
Indicates that the power is on.
ON
OFF
FUNCTION
FILTER
WEEKLY
AUTO OFF
8 or 39
SIMPLE
or more.
“Sensor” indication
Displayed when the remote controller
sensor is used.
“Locked” indicator
Indicates that remote controller buttons have been locked.
“Clean The Filter” indicator
To be displayed on when it is time to
clean the filter.
Timer indicators
The indicator comes on if the corresponding timer is set.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
Note:
●
“PLEASE WAIT” message
This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power failure.
“NOT AVAILABLE” message
●
This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have).
If a single remote controller is used to operate multiple indoor units simultaneously that are different types, this message will not be displayed as
far as any of the indoor units is equipped with the function.
77
Page 8
4
SPECIFICATIONS
4-1. SPECIFICATION
Item
Power
Cooling capacity
Heating capacity
Cooling
Input
Heating
Cooling
Current
Electric characteristic
(munsell symbol)
Dimensions
Heating
Exterior
Height
Width
Depth
Heat exchanger
Fan × No
Air flow 3
External
static pressure
F a n
Fan motor
output
Insulator
Air filter
Pipe
dimensions
Gas
side
Liquid
side
Field drain pipe size
Noise level 3
Product weight
·Hz
V
kW
kW
kW
kW
A
A
—
mm
mm
mm
—
—
G/min
Pa
kW
—
—
:mm(in.)
:mm(in.)
:mm
dB
kg
PMFY-P20VBM-E
PMFY-P20VBM-E
PMFY-P20VBM-E#2
PMFY-P20VBM-ER3
PMFY-P25VBM-E
1
PMFY-P25VBM-E
PMFY-P25VBM-E#2
PMFY-P25VBM-ER3
Single phase 220V-230V-240V 50Hz / 220V 60Hz
2.2
2.5
0.042
0.042
0.20
0.20
2.8
3.2
0.044
0.044
0.21
0.21
Unit : Galvanized sheets · Standard grilles : ABS resin acrylic coating
Munsell <0.98Y 8.99/0.63> (PMFY-P·VBM-E
8.7-8.0-7.2-6.5
Polyethylene sheet
PP honey comb fabric
O.D.26 (PVC pipe VP-20 connectable)
35-33-30-27
PMFY-P32VBM-E
PMFY-P32VBM-E
1
PMFY-P32VBM-E#2
PMFY-P32VBM-ER3
(1)) / <6.4Y 8.9/0.4> (PMFY-P·VBM-E#2/ER3)
230<30>
812<1,000>
395<470>
Cross fin
Line flow fan × 1
9.3-8.6-8.0-7.3
0
0.028
12.7(1/2")
6.35(1/4")
37-36-34-32
14<3.0>
3.6
4.0
0.044
0.044
0.21
0.21
PMFY-P40VBM-E
PMFY-P40VBM-E
1
PMFY-P40VBM-E#2
PMFY-P40VBM-ER3
10.7-9.7-8.7-7.7
39-37-35-33
1
4.5
5.0
0.054
0.054
0.26
0.26
Note 1. Rating conditions (JIS B 8615-1)
Cooling: Indoor: D.B. 27°C W.B. 19°C
outdoor: D.B. 35°C
Heating: Indoor: D.B. 20°C
outdoor: D.B. 7°C W.B. 6°C
Note 2. The number indicated in < > is for the grille.
W 3. Air flow and the noise level are indicated as High – Medium1 – Medium2 – Low.
PMFY-P·VBM-E series enables to take fresh air from outside. When taking fresh air, the duct fan is used.
The air capacity should be 20% or less of the air flow SPEC(Hi).
250288.5
108
90
W
122
100
W
Unit : mm
4-W2.8
Fresh air intake hole
(Knockout)
Service Ref.
Air flow
(Hi)
PMFY-P20VBM-E
PMFY-P20VBM-E
PMFY-P20VBM-E#2
1
8.7m³/min
PMFY-P20VBM-ER3
PMFY-P25VBM-E
PMFY-P25VBM-E
PMFY-P25VBM-E#2
1
9.3m³/min
PMFY-P25VBM-ER3
PMFY-P32VBM-E
PMFY-P32VBM-E
PMFY-P32VBM-E#2
1
9.3m³/min
PMFY-P32VBM-ER3
PMFY-P40VBM-E
PMFY-P40VBM-E
PMFY-P40VBM-E#2
1
10.7m³/min
PMFY-P40VBM-ER3
Operation in conjunction with duct fan (Booster fan)
● Whenever the indoor unit is operating, the duct fun
operates.
(1) Connect the optional multiple remote controller
adapter(PAC-SA88HA-E) to the connector CN51
on the indoor controller board.
(2) Drive the relay after connecting the 12V DC relay
between the Yellow and Orange connector lines.
(w) Use a relay of 1W or smaller.
MB: Electromagnetic switch power relay for duct fan.
X: Auxiliary relay (12V DC LY-1F)
Fresh air intake hole
(Knockout)
Air capacity from outside
Max 1.74m³/min
Max 1.86m³/min
Max 1.86m³/min
Max 2.14m³/min
CN51
on
indoor unit
board
Connector (5P)
Indoor unit side
Green
5
1
Multiple remote
controller adapter
PAC-SA88HA-E
Indoor controller board
Be sure to secure insulation
material by tape, etc.
Yellow
Orange
Red
Brown
~
MB
Installation at site
Be sure to secure insulatio
material by tape, etc.
Distance between indoor
controller board and relay
must be within 10m.
How to read curves
Q
Duct characteristics
at site
A
B
A
EC
AD
Curve in the
right graphs
0
Q
Qa
Q
Multiple remote
controller adapter
PAC-SA88HA-E
Q…Designed amount of fresh air intake
C
A…Static pressure loss of fresh air
intake duct system with air flow
amount Q <Pa>
B…Forced static pressure at air condi-
tioner inlet with air flow amount Q
C…Static pressure of booster fan with
air flow amount Q <Pa>
D…Static pressure loss increase amount
of fresh air intake duct system for air
flow amount Q <Pa>
E…Static pressure of indoor unit with air
flow amount Q <Pa>
Qa…Estimated amount of fresh air
intake without D <m3/min>
<m
3
/min>
<Pa>
50.0
0.0
-50.0
Static pressure (Pa)
-100.0
0.00.51.0
Characteristic diagram of fresh air taken capacity
FAN MOTOR
VANE MOTOR
DRAIN PUMP
DRAIN SENSOR
TERMINAL
BLOCK
THERMISTOR
LINEAR EXPANSION VALVE
POWER SUPPLY
~/N 220-230-240V 50Hz
220V 60Hz
I.B
LED1
FAN
213 654
(WHT)
FUSE
3
1
ZNR
CND
(RED)
POWER
1
3
X1
CNP
(YLW)
D.U. M
0N
0FF
(WHT)
REMOTE
SWITCH
CN32
1
3
4
8
NAME
POWER SUPPLY
TRANSMISSION
MA-REMOTE CONTROLLER
ROOM TEMPERATURE DETECTION
(0/15k, 25/5.4k)
PIPE TEMPERATURE DETECTION/LIQUID
(0/15k, 25/5.4k)
PIPE TEMPERATURE DETECTION/GAS
(0/15k, 25/5.4k)
Meaning
Main power supply
Power supply for
MA-Remote controller
TO OUTDOOR UNIT
BC CONTROLLER
REMOTE CONTROLLER
DC24-30V
TB5
(SHIELD)
CN2M
(BLU)
M-NET
CENTRALLY
M1 M2
BLU
BLU
CN3A
21
(BLU)
REMOCON
LED2
CN41
(WHT)
HA
CN51
(WHT)
CONTROL
CN52
(GRN)
REMOTE
INDICATION
10N2345
(RED)
ADDRESS
CN81CN42
1
4
1
5
1
5
1
0FF
MF
5
T
X1
SW2SW3SW4
65432109876543211
(RED)
ADDRESS
431221 345678
MODELS
P20VBM
P25VBM
P32VBM
P40VBM
Function
Main power supply(Indoor unit:220-240V)
power on Lamp is lit.
Power supply for MA-Remote controller
on Lamp is lit.
TO MA-REMOTE CONTROLLER
DC8.7-13V
2
TB15
ORN
ORN
21
3
CN31
(WHT)
2
DRAIN
1
CN29
2
(BLK)
1
GAS
CN21
2
(WHT)
1
LIQUID
CN20
2
(RED)
1
INTAKE
CN60
(WHT)
LEV
CN6V
(GRN)
VAN E
0N
0FF
0N
0FF
0N
0FF
0N
0FF
123456
SW2
6
5
4
3
2
1
6
5
4
3
2
1
2
1
CN25
2
1
CN27
654321
654321
654321
BLU
BRN
ORN
YLW
RED
WHT
BRN
RED
ORN
YLW
GRN
<1>
SW3
0N
0FF
123456
123456
123456
10987
10987
10987
654321
10987
0N
0FF
0N
0FF
0N
0FF
NOTES:
1. At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2. In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)
3. In case of using M-NET, please connect to TB5.(Transmission wire is non-polar.)
4. Symbol [S] of TB5 is the shield wire connection.
5. Symbols used in wiring diagram above are, : terminal block, : connector.
6. The setting of the SW2 dip switches differs in the capacity. For the detail, refer to the table above.
7. Please set the switch SW5 according to the power supply voltage. Set SW5 to 240V side when the power supply is 230 and 240 volts.
When the power supply is 220 volts, set SW5 to 220V side.
TO OUTDOOR UNIT
BC CONTROLLER
REMOTE CONTROLLER
DC24-30V
TB5
M1 M2
BLU
CN2M
(BLU)
M-NET
1
T
SW3
(RED)
CN42
8
,
25/5.4k
,
25/5.4k
S
(SHIELD)
BLU
CN3A
(BLU)
REMOCON
12
LED2
CENTRALLY
CONTROL
INDICATION
SW2
123456
ADDRESS
)
)
)
TO MA-
REMOTE CONTROLLER
DC8.7-13V
1 2
TB15
ORN
ORN
3
13
CN31
CN51
(WHT)
CN52
(GRN)
REMOTE
ON
OFF
(RED)
CN81
(WHT)
DRAIN
1
CN29
2
(BLK)
1
GAS
CN21
2
(WHT)
1
LIQUID
CN20
2
(RED)
1
INTAKE
6
CN60
(WHT)
LEV
5
1
1
5
1
CN6V
(GRN)
VAN E
6
1
2
CN25
1
2
CN27
1
843111
BRN
RED
BLU
ORN
YLW
WHT
BRN
RED
ORN
YLW
GRN
t°
t°
t°
t°
MODELS
P20VBM
P25VBM
P32VBM
P40VBM
DS
TH23
TH22
TH21
M
LEV
1
M
MV
5
SW2
OFF
OFF
OFF
OFF
ON
ON
ON
ON
123456
123456
123456
123456
OFF
OFF
OFF
OFF
ON
ON
ON
ON
1234567
1234567
123456
12345677
LED on indoor board for service
MarkMeaningFunction
LED1Main power supply
Power supply for
LED2
MA-Remote controller
Main power supply (Indoor unit:220-240V)
Power on Lamp is lit.
Power supply for MA-Remote controller
on Lamp is lit.
NOTES:
1. At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2. In case of using MA-Remote controller, please connect to TB15.
(Remote controllerwire is non-polar.)
3. In case of using M-NET, please connect to TB5. (Transmission wire is non-polar.)
4. Symbol [S] of TB5 is the shield wire connection.
5. Symbols used in wiring diagram above are, :terminal block, :connector.
6. The setting of the SW2 dip switches differs in the capacity. For the detail, refer to
the table above.
7. Please set the switch SW5 according to the power supply voltage. Set SW5 to
240V side when the power supply is 230 and 240 volts. When the power supply is
220 volts, set SW5 to 220V side.
Main power supply (Indoor unit:220-240V)
Power on → Iamp is lit
Power supply for MA-Remote controller
on → Iamp is lit
LN
BLU
RED
864 2
)
CN2M
(
BLU
M-NET
CN3A
(
BLU
)
REMOCON
)
123456
A.B
FUSE
(
15A)
YLW
/
GRN
CND
513
FUSE
DSA
ZNR02
U
1357
)
LED2
4
CN42
(
RED
ADDRESS
1
31
CN32(WHT
REMOTE SWITCH
SW2
12345678910
SW5
SW1
12345678910
SW12
0
9
8
7
6
10ths
DIGIT
BREAKER
(
15A)
(
BLK
)
U
1
2
)
SW3
240V220V
1
2
3
4
5
POWER SUPPLY
~
/ N
220-240V 50Hz
220V 60Hz
ZNR01
CNMF1
(
WHT
)
SWE
ON OFF
)
4
SW11
0
1
9
2
8
3
7
4
6
5
1s
DIGIT
DC311
~
SW4
12345
SWC
339V
(RED)
ADDRESS
CN43
SW14
0
1
F
E
D
C
B
A
8
9
BRANCH
No.
X1
ADDRESS
CN81(RED
4
1
(RED)
ADDRESS
2
CN82
3
4
5
6
7
1
3
CNP
(
YLW
)
D.U.M
CN20
(
RED
INTAKE
CN25
(
4
CN41
(
WHT
)
HA
1
(
WHT
CN51
CENTRALLY
CONTROL
)
81
REMOTE
INDICATION
8
1
)
WHT
5
)
CN52
(
GRN
8
)
CN27
LED1
CN31
2
1
2
1
2
1
(
)
(
WHT
DRAIN
CN60
(
WHT
LEV
RED
)
5
1
I.B
3
)
1
6
)
1
4
1
CN44
(
WHT
LIQUID
/
GAS
1
BLU
BLU
M
1~
DP
DS
t°
BRN
RED
BLU
ORN
YLW
WHT
M
LEV
TH21
t°
t°
TH23
t°
TH22
)
[LEGEND]
SYMBOLNAME
I.BINDOOR CONTROLLER BOARD
CN25
CONNECTOR
SWITCH
(T6.3AL 250V)
FAN MOTOR
VANE MOTOR
DRAIN PUMP
HUMIDIFIER
DAMPER
REMOTE SWITCH
CENTRALLY CONTROL
REMOTE INDICATION
CAPACITY CORD
MODE SELECTION
MODEL SELECTOR
DRAIN UP MACHINE(TEST MODE
DRAIN PUMP
CN27
CN32
CN51
CN52
SW2
SW3
SW4
SWE
ZNR VARISTOR
FUSE FUSE
X1 AUX.RELAY
LED1 POWER SUPPLY (I.B)
LED2 POWER SUPPLY (I.B)
MF
MV
DP
SYMBOLNAME
DS
DRAIN SENSOR
TERMINAL
TB2
TB5
TB15
TH21
TH22
TH23
)
LEVLINEAR EXPANSION VALVE
A.BCIRCUIT BOARD
SW1
SW5
SW11
SW12
SW14BRANCH No.
POWER SUPPLY
TRANSMISSION
BLOCK
MA-REMOTE CONTROLLER
THERMISTOR
ROOM TEMP. DETECTION
(0°C/15kΩ, 25°C/5.4kΩ)
PIPE TEMP. DETECTION / LIQUID
(0°C/15kΩ, 25°C/5.4kΩ)
PIPE TEMP. DETECTION / GAS
(0°C/15kΩ, 25°C/5.4kΩ)
MODE SELECTION
SWITCH
VOLTAGE SELECTION
ADDRESS SETTING 1s DIGIT
ADDRESS SETTING 10ths DIGIT
NOTES:
1.At servicing for outdoor unit,always follow the wiring diagram of outdoor unit.
2.In case of using MA-Remote controller, please connect to TB15.
(Remote controller wire is non-polar.)
3.In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)
4.Symbol [S] of TB5 is the shield wire connection.
5.Symbols used in wiring diagram above are,
: terminal block, :connecter.
6.The setting of the SW2 dip switches differs in the capacity. For the detail, refer to the table below.
7.Please set the switch SW5 according to the power supply voltage.
Set SW5 to 240V side when the power supply is 230 and 240 volts.
When the power supply is 220 volts, set SW5 to 220V side.
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the indoor controller board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the indoor controller board and the linear expansion valve>
Controller board
DC12V
Linear expansion valve
4
M
6
2
5
White
1
Red
3
Orange
Blue
Brown
Yellow
:4
:3
:2
:1
Brown
Red
Blue
Orange
Yellow
White
Connector (CN60)
Note : Since the number of the connector at the controller board side and the relay connector are different, follow the colour of
• When linear expansion valve operation stops, all output phase
become OFF.
• At phase interruption or when phase does not shift in order, motor
does not rotate smoothly and motor will lock and vibrate.
• When the switch is turned on, 2200 pulse closing valve signal will
be send till it goes to A point in order to define the valve position.
D
C
• When the valve move smoothly, there is no sound or vibration occurring from the linear expansion valve : however, when the pulse
number moves from E to A or when the valve is locked, more
sound can be heard than normal situation.
• Sound can be detected by placing the ear against the screw driver
handle while putting the screw driver to the linear expansion valve.
2000 pulse
Opening a valve
all the way
Extra tightning (80~100pulse)
Trouble shooting
3
B
Pulse number
Symptom
Operation circuit
failure of the micro
processor
Linear expansion
valve mechanism is
locked.
Short or breakage
of the motor coil of
the linear expansion
valve
Valve does not close
completely (thermistor leaking).
Wrong connection
of the connector or
contact failure
Check points
Disconnect the connector on the controller board, then connect LED for checking.
Pulse signal will be sent out for 10 seconds as soon as the
main switch is turned on. If there is LED with lights on or
lights off, it means the operation circuit is abnormal.
Motor will idle and make ticking noise when motor is operated
while the linear expansion valve is locked. This ticking sound
is the sign of the abnormality.
Measure the resistance between the each coil (red-white, redorange, brown-yellow, brown-blue) with a tester. It is normal if
the resistance is in the range of 200 " ± 10%.
To check the linear expansion valve, operate the indoor unit
in fan mode and at the same time operate other indoor units
in cooling mode, then check the pipe temperature <liquid
Thermistor
(Liquid pipe)
Linear
expansion
valve
It is not necessary to exchange the linear expansion valve, if
the leakage is small and not making any trouble.
Check the color of lead wire and missing terminal of the connector.
LED1k
pipe temperature> of the indoor unit by the
outdoor multi controller board operation
monitor. During fan operation, linear expansion valve is closed completely and if there
are some leaking, detecting temperature of
the thermistor will go lower. If the detected
temperature is much lower than the temperature indicated in the remote controller,
it means the valve is not closed all the way.
6
5
4
3
2
1
Countermeasures
Exchange the indoor controller board at drive circuit
failure.
Exchange the linear expansion valve.
Exchange the linear expansion valve.
If large amount of refrigerant is leaked, exchange
the linear expansion valve.
Disconnect the connector
at the controller board,
then check the continuity.
19
Page 20
8-2. TROUBLE SHOOTING
Check method of indoor fan motor (fan motor / controller board)
Notes
· High voltage is applied to the connecter (FAN)(CNMF1, 2) for the fan motor. Pay attention to the service.
· Do not pull out the connector (FAN)(CNMF1, 2) for the motor with the power supply on, doing so may result in damage
to the board.
(FAN)
PMFY-P20/25/32/40VBM-E PMFY-P20/25/32/40VBM-E
SW3-9, 10 as trouble
might be caused by
the usage condition.
+6 Second setting
means first setting.
Indoor controller board
10
21
Page 22
SwitchRemarks
Operation by switchPole
Effective
timing
SW11
1s digit
address
setting
SW12
10ths digit
address
setting
SW14
Branch
No.
setting
SW5
Voltage
Selection
SW1210SW11
0
9
8
7
6
5
Rotary switchRotary switch
220V240V
2
1
2
3
4
SW14
0
F
E
D
C
B
A
9
How to set addresses
0
1
9
2
8
7
1
2
3
4
5
6
7
8
Example : If address is “3”, remain SW12
3
4
6
5
(for over 10) at “0”, and match SW11 (for 1 to 9)
with “3”.
1
How to set branch numbers SW14 (Series R2 only)
Match the indoor unit’s refrigerant pipe with
the BC controller’s end connection number.
Remain other than series R2 at “0”.
If the unit is used at the 230V or 240V area,
set the voltage to 240V.
If the unit is used at the 220V, set the voltage
to 220V.
(2) Put your fingers on the both ends of nut of the air intake
grille and put it down after the grille clicked.
Removing the air intake grille
(1) Press the
PUSH
of the air intake grille, and pull down the
both ends of nut with your fingers after the grille clicked.
(See Figure 1)
(2) Pull out the handle of air intake grille strongly toward you.
(See Figure 2)
(3) Draw the string of the air intake grille to prevent the air
intake grille from dropping. (See Figure 3)
Checks before setting the grille in place
(1) Before installing the grille, make sure the indoor unit is
square with the ceiling opening (or parallel to the angle
between the wall and the ceiling).
(2) Check that the 4 points where the grille will be secured are
in contact with the ceiling surface.
(3) Check that the insulation for the refrigerant pipes, drain-
age pipes, etc. is in place and that wiring connections and
arrangements are complete.
Photo 1
Air outlet
grille
Nozzle
Figure 1
Figure 2
Air intake grille
Air filter
PUSH
Figure 4
Figure 5
Ceiling surface
Points for securing the grille
Points for securing the grille
Points for securing
the grille
Drainage
pan
Make sure these
surfaces are fl ush with
each other (0-3 mm).
String for dropping
prevention
Figure 3
26
Page 27
OPERATING PROCEDUREPHOTOS&ILLUSTRATIONS
Removing the grille
Open the intake grille by pressing
(1)
PUSH
of the air intake
grille and remove the air fi lter (× 2). (See Figure 1)
(2) Remove the screw cover in the middle of the air outlet. (See
Figure 7)
(3) Open the upper and lower fl aps on the indoor unit com-
pletely. (See Figure 7)
(4) Remove the securing screws (× 7).
(A: M5 × 0.8 × 16, 6pcs)
(B: 4 × 16, 1pc)
(5) Remove the temporary holding tabs on the grille to the
hooks on the indoor unit.
Attaching the grille
(1) Open the upper and lower fl aps on the indoor unit com-
pletely.
(2) Hook the temporary holding tabs on the front panel to the
hooks on the indoor unit.
(3) Adjust the grille so that it fi ts properly in the angle between
the ceiling and the wall, and install the securing screws A
(supplied with this grille) in their 4 places at left and right,
leaving them slightly loose.
(4) Tighten the securing bolts A and securing screws B in the
centre 3 places. (See Figure 6)
(5)
Tighten the securing bolts A in the 4 places at left and right.
* Make sure there are no gaps between the indoor unit and
the grille, and between the grille and the ceiling surface.
If there are gaps, the wind may come in and it may cause
water to drip. (See Figure 8)
* Tighten the securing bolts A and securing screws B com-
pletely.
PUSH
Replace the air fi lter and screw cover, and press
(6)
of
the intake grille until you hear it snap into place.
Figure 6
Figure 7
Temporary
holding tabs
A
A
Screw cover
Hooks
Temporary holding tabs
B
A
A
Hooks
A
A
Upper and lower fl aps
* Open completely
Temporary
holding tabs
Checks after setting the grille
(1) Check that there are no gaps between the indoor unit and
the grille, between the grille and the ceiling surface. If there
are gaps, the wind may come in and condensation may
result.
(2) Check that the air fi lter is in place.
2727
Figure 8
Ceiling surface
Indoor unit
No gaps between the
indoor unit and the grille
Grille
Page 28
OPERATING PROCEDURE
PHOTOS&ILLUSTRATIONS
2. Removing the electrical parts box
(1) Remove the grille.
(2) Remove the address board cover.
(3) Remove the electrical parts cover.
(4) Disconnect the connectors of
fan motor, vane motor,
drain pump, room temperature thermistor,
pipe temperature thermistor (Liquid, Gas),
and drain sensor on the electrical controller board.
(5) Disconnect the lead wire and earth wire from terminal
block.
(6) Remove the electrical parts box.
3. Removing the nozzle
Note when the nozzle is removed
· The white insulation material which prevents water drop
is mounted to the side of vane motor. Remove the insulation material before removing nozzle.
(See Figure 9)
· After completing the service, re-mount the insulation
material as before as shown in right figure.
· After service, mount the double layer insulation without
fail.
The hard material side should be faced to the nozzle.
(See Figure 9)
(1) Remove the grille.
(2) Remove the room temperature thermistor.
(3) Unhook the claws in the middle of nozzle and remove the
drain pan. (5 screws) (See Photo 2)
(4) Remove the nozzle side of the heat exchanger. (2 screws)
(5) Remove the address board cover. (See Photo 3)
(6) Remove the electrical parts cover. (See Photo 3)
(7) Disconnect the connector of vane motor.
(8) Remove the insulation material (white) on the right side of
nozzle.
(9) Remove the nozzle. (6 screws)
Photo 2
Drain pan
Photo 3
Photo 4
Nozzle
Room temperature thermistor
Figure 9
Hard side of insulation
Nozzle
Vane motor
Claw in middle
of nozzle
Insulation material (whilte)
Nozzle
Heat exchanger
Electrical parts
Electrical parts
cover
Address board
cover
Vane motor
Soft side of insulation
4. Removing the vane motor
(1) Remove the nozzle. Refer to above-mentioned
3. Removing the nozzle.
(2) Remove the vane motor from the nozzle.
Photo 5
Vane motor
28
Page 29
OPERATING PROCEDUREPHOTOS&ILLUSTRATIONS
5. Removing the drain pump
(1) Remove the grille.
(2) Unhook the claw in the middle of nozzle and remove the
drain pan. (See Photo 2)
(3) Remove the address board cover. (See Photo 3)
(4) Remove the electrical parts cover. (See Photo 3)
(5) Disconnect the connector of drain pump.
(6) Remove the drain hose.
(7) Remove the drain pump. (2 screws)
6. Removing the fan motor and line flow fan
(1) Remove the grille.
(2) Unhook the claw in the middle of nozzle and remove the
drain pan. (See Photo 2)
(3) Unscrew 2 screws at the nozzle side of the heat exchanger.
(4) Remove the address board cover. (See Photo 3)
(5) Remove the electrical parts cover. (See Photo 3)
(6) Disconnect the connector of vane motor, fan motor and
drain pump.
(7) Remove the nozzle side of the heat exchanger. (2 screws)
(8) Remove the nozzle.
(9) Remove the drain pump.
(10) Unscrew 2 screws in the motor support.
(11) Remove the fan motor and line flow fan (The fan motor
and line flow fan can be removed without removing the
heat exchanger.)
Photo 6
Photo 7
Drain sensor
Line flow fan
Drain pump
Fan motor
Heat exchanger
Fan motor
7. Removing the thermistor<Intake temperature detector>
(1) Remove the grille.
(2) Remove the address board cover.
(3) Remove the electrical parts cover.
(4) Remove the thermistor <intake temperature detector>.
(5) Disconnect the lead wire from the cord clamp (5 points).
(6) Disconnect the connector (CN20) on the indoor controller
board.
8. Removing the thermistor<Liquid pipe temperature detector>
<Gas pipe temperature detector>
(1) Remove the grille.
(2) Remove the address board cover.
(3) Remove the electrical parts cover.
(4) Remove the drain pan.
(5) Remove the thermistor <Gas pipe temperature detector>
/<Liquid pipe temperature detector>.
(6) Disconnect the lead wire from the cord clamp.
(7) Disconnect the connector (CN21)/(CN29), (CN44) on the
indoor controller board.
Connector (CN21) / Liquid (VBM
(1))
(CN29) / Gas (VBM(1))
(CN44) / Liquid and Gas (VBM#2, VBMR3)
CABINET
ADDRESS BOARD COVER
BEARING MOUNT
SLEEVE BEARING
LINE FLOW FAN
STABILIZER ASSY
VANE MOTOR
VANE SLEEVE
HEAT EXCHANGER
HEAT EXCHANGER
DRAIN PAN
THERMISTOR
GUIDE VANE
THERMISTOR
LINEAR EXPANSION VALVE
THERMISTOR
VANE
CASING
SENSOR HOLDER
DRAIN SENSOR
DRAIN PUMP
MOTOR SUPPORT
FAN MOTOR
MOTOR MOUNT
DRAIN PIPE
CONTROL BOX COVER
SCREW ASSY
ROOM
LIQUID
GAS
Q'ty/set
PMFY-P · VBM-E
20, 2532, 40
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
17
16
15
14
13
12
Remarks
(Drawing No.)
(DT00A478G88)
(RG02L277H02)
(RG00L311G11)
Wiring
Diagram
Symbol
MV
TH21
TH22
LEV
TH23
DS
DP
MF
Recom-
mended
Q'ty
3131
Page 32
ELECTRICAL PARTS
PMFY-P20VBM-E
PMFY-P25VBM-E
PMFY-P32VBM-E
PMFY-P40VBM-E
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
cCopyright 2004 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Oct. 2009 No. OC307 REVISED EDITION-D PDF 7
Distributed in Sep. 2008 No. OC307 REVISED EDITION-C PDF 7
Distributed in Jul. 2007 No. OC307 REVISED EDITION-B PDF 8
Distributed in Jul. 2006 No. OC307 REVISED EDITION-A PDF 8
Distributed in Apr. 2004 No. OC307 PDF 9
Made in Japan
New publication, effective Oct. 2009
Specifications subject to change without notice
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.