Mitsubishi OB379D Service Manual

Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
HFC
utilized
R410A
OUTDOOR UNIT
SERVICE MANUAL
Wireless type Models
Revision D:
•PARTS LIST and RoHS PARTS LIST have been changed.
Please void OB379 REVISED EDITION-C.
No. OB379
REVISED EDITION-D
MUZ-GA25VA ­MUZ-GA25VA ­MUZ-GA25VA ­MUZ-GA25VA ­MUZ-GA35VA ­MUZ-GA35VA -
E1
E2
E3
E4
E1
E2
MUZ-GA25VAH ­MUZ-GA25VAH -
MUZ-GA25VAH ­MUZ-GA25VAH -
MUZ-GA35VAH ­MUZ-GA35VAH -
E1
E2 E3 E4
E1
E2
Indoor unit service manual
MSZ-GAVA Series (OB378) MSZ-CBVA Series (OB441)
CONTENTS
1. TECHNICAL CHANGES ····································3
2. PART NAMES AND FUNCTIONS······················7
3. SPECIFICATION·················································8
4. NOISE CRITERIA CURVES·····························10
5. OUTLINES AND DIMENSIONS························11
6. WIRING DIAGRAM ··········································12
8. PERFORMANCE CURVES······························23
9. ACTUA TOR CONTROL····································31
10. SERVICE FUNCTIONS·····································32
11. TROUBLESHOOTING ······································32
12. DISASSEMBLY INSTRUCTIONS·····················53
13. PARTS LIST······················································56
14. RoHS PARTS LIST···········································60
NOTE:
RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS Parts List.
Page 2
Revision A:
Model 6. Wiring diagram
11-6.N Check of inverter P.C.board
Change Change
MUZ-GA25VA MUZ-GA25VAH MUZ-GA35VA MUZ-GA35VAH
No change No change
•Alternative inverter P.C.board has been added(Refer to 11-7.1. Inverter P.C.board (Alternative)). FUSE F901 has been
equipped to MUZ-GA35.
E2
model has been added.
Quick clean kit has been removed.
Revision B:
MUZ-GA25VA(H)- has been added.
11-2. Failure mode recall function has been changed.
RoHS PARTS LIST has been added.
E3
Revision C:
MUZ-GA25VA(H)- has been added.
Solenoid valve coil has been removed.
(MUZ-GA25VA- :Serial No. 6021351T~ , MUZ-GA25VAH- :Serial No. 7000001T~)
E4
E3E3
Revision D:
PARTS LIST and RoHS PARTS LIST have been changed.
2
Page 3
1
TECHNICAL CHANGES
MUZ-A09YV - MUZ-GA25VA ­MUZ-A09YVH - MUZ-GA25VAH -
1.Indication of capacity has been changed.(BTU base kW base)
2.Control method between indoor and outdoor unit has been changed.
3.Power supply method has been changed (change to supply from outdoor unit).
4.Terminal block for power supply has been added.
5.Power P.C. board has been changed.
6.Inverter P.C. board has been changed.
7.Refrigerant circuit has been changed.
Compressor has been changed.(KNB073FBVHKNB065FDTH)
LEV has been removed and capillary tube has been added.
Bypass circuit for low outside temperature operation has been added.
Specification and position of muffler have been changed.
Path of outdoor heat exchanger has been changed.
4-way valve and R.V. coil have been changed.
Stop valve has been changed.
8.Fan motor has been changed. (AC)
9.Shape of grille has been changed.
10.Shape of service panel has been changed.
11.Shape of propeller has been changed.
12.Quick Clean Kit has been added.
13.Symbol on terminal block has been changed (to S1/S2/S3).
MUZ-A12YV - MUZ-GA35VA ­MUZ-A12YVH - MUZ-GA35VAH -
E1E1
E1E1
E1E1
E1E1
1.Indication of capacity has been changed.(BTU base kW base)
2.Control method between indoor and outdoor unit has been changed.
3.Power supply method has been changed (change to supply from outdoor unit).
4.Terminal block for power supply has been added.
5.Power P.C. board has been changed.
6.Inverter P.C. board has been changed.
7.Refrigerant circuit has been changed.
Compressor has been changed.(KNB092FAAHKNB073FDVH)
Specification and position of muffler have been changed.
Path of outdoor heat exchanger has been changed.
4-way valve and R.V. coil have been changed.
Stop valve has been changed.
8.Fan motor has been changed.(AC➔DC)
9.Shape of grille has been changed.
10.Shape of service panel has been changed.
11.Shape of propeller has been changed.
12.Quick Clean Kit has been added.
13.Symbol on terminal block has been changed (to S1/S2/S3).
MUZ-GA25VA - MUZ-GA25VA ­MUZ-GA25VAH - MUZ-GA25VAH ­MUZ-GA35VA - MUZ-GA35VA ­MUZ-GA35VAH - MUZ-GA35VAH -
1.Quick clean kit has been removed.
MUZ-GA25VA - MUZ-GA25VA ­MUZ-GA25VAH - MUZ-GA25VAH -
1.Capillary tube for heating has been added.
2.Solenoid valve coil has been removed.(GA25VA- :Serial No. 6021351T~ , GA25VAH- :Serial No. 7000001T~)
E2E1
E2E1
E2E1
E2E1
E3E2
E3E2
E3E3
MUZ-GA25VA - MUZ-GA25VA ­MUZ-GA25VAH - MUZ-GA25VAH -
1.Refrigerant circuit has been changed.
2.Solenoid valve coil has been removed.
E4E3
E4E3
3
Page 4
Refrigeration
oil
Refrigerant
New refrigerant
R410A
HFC-32: HFC-125 (50%:50%)
Pseudo-azeotropic refrigerant
Not included
A1/A1
72.6
-51.4
1.557 64
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
Non Non
Previous refrigerant
R22
R22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055 1700
Gas phase
Possible
Compatible oil
Light yellow
Non
Refrigerant Composition (Ratio) Refrigerant handling Chlorine Safety group (ASHRAE) Molecular weight Boiling point (:) Steam pressure [25:](Mpa) Saturated steam density [25:](Kg/K) Combustibility ODP w1 GWP w2 Refrigerant charge method Additional charge on leakage Kind Color Smell
w1:Ozone Depletion Potential : based on CFC-11 w2 :Global Warming Potential : based on CO
2
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
New Specification Current Specification
The incompatible refrigeration oil easily separates from refrigerant and is in the upper layer inside the suction muffler. Raising position of the oil back hole enables to back the refrigeration oil of the upper layer to flow back to the compressor.
Since refrigerant and refrigeration oil are compatible, refrigeration oil goes back to the compressor through the lower position oil back hole.
Compressor
Suction muffler
Oil back hole
Refrigeration oil
Refrigerant
Compressor
Suction muffler
Oil back hole
Refrigeration oil /Refrigerant
Compressor
This room air conditioner adopts HFC refrigerant (R410A) which never destroys the ozone layer.
Pay particular attention to the following points, though the basic installation procedure is same as that for R22 air
conditioners.
1 As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/
materials are required. Refer to the table below.
2 Take sufficient care not to allow water and other contaminations to enter the R410Arefrigerant during storage and
installation, since it is more susceptible to contaminations than R22.
3 For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant
piping.)
4 Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
4
Page 5
Conversion chart of refrigerant temperature and pressure
R410A tools
Can R22 tools be used?
Gas leak detector
R410A has high pressures beyond the measurement range of existing gauges. Port diameters have been changed to prevent any other refrigerant from being charged into the unit.
Hose material and cap size have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant.
6.35 mm and 9.52 mm
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool. Provided for flaring work (to be used with R22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use vacuum pumps.
It is difficult to measure R410A with a charging cylinder because the refrigerant bubbles due to high pressure and high-speed vaporization
No
No
No
Yes
Yes
New
New
New
Gauge manifold
Charge hose
Torque wrench
Flare tool Flare gauge
Vacuum pump adapter
Electronic scale for refrigerant charging
No : Not Substitutable for R410A Yes : Substitutable for R410A
No 12.7 mm
Wall thickness
Outside diameter
Pipe
mm
For liquid For gas
6.35
9.52
12.7
0.8 mm
0.8 mm
0.8 mm
Heat resisting foam plastic Specific gravity 0.045 Thickness 8 mm
Insulation material
(MPa [Gauge])
4.0
3.5
3.0
2.5
2.0
1.5
R410A R22
NOTE : The unit of pressure has been changed to MPa on the
international system of units(SI unit system).
1.0
0.5
Saturated liquid pressure
0.0
-0.5
-30 -20 -10 0 10 20
30
40 50 60
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
(:)
1.Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools. The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
2.Refrigerant piping
1 Specifications
Use the refrigerant pipes that meet the following specifications.
Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm. Never use any pipe with a thickness less than 0.8mm, as the pressure resistance is insufficient.
5
Page 6
Electronic scale for refrigerant charging
Outdoor unit
Refrigerant gas cylinder operating valve
Refrigerant gas cylinder for R410A with siphon
Refrigerant (liquid)
Service port
Gauge manifold valve (for R410A)
Union
Liquid pipe Gas pipe
Stop valve
Indoor unit
Charge hose (for R410A)
R410A
Pipe diameter
mm
6.35
9.52
12.7
17 22 26
Dimension of flare nut
R22
17 22 24
2 Flaring work and flare nut
Flaring work for R410A pipe differs from that for R22 pipe. For details of flaring work, refer to Installation manual FLARING WORK”.
3.Refrigeration oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4.Air purge
Do not discharge the refrigerant into the atmosphere. Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant
circuit.
Use the vacuum pump for air purging for the purpose of environmental protection.
5.Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, capacity of the refrigeration cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
6
Page 7
2
PART NAMES AND FUNCTIONS
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
ACCESSORIES
Drain socket
1
Quick clean kit
2
MUZ-GA25VA ­MUZ-GA35VA -
1 1
E1
MUZ-GA25VAH -
E1
MUZ-GA35VAH -
MUZ-GA25VA -
E1
MUZ-GA25VA -
E1
MUZ-GA25VA ­MUZ-GA35VA -
1
1
––
E2
MUZ-GA25VAH -
E3
MUZ-GA25VAH -
E4
MUZ-GA25VAH -
E2
MUZ-GA35VAH -
E2 E3 E4 E2
7
Page 8
3
SPECIFICATION
Outdoor model
Function
Power supply
A
A W %
A
A
A
W
"
"
kg
kg cc
2.5 (0.9-3.0)
U-V 1.88
Capacity Rated frequency(Min.-Max.) Dehumidification Air flow 1
Capacity
Power outlet Running current 1 Power input 1 Power factor 1 Starting current 1
Electrical
data
Compressor motor current ✽1 Fan motor current 1
Coefficient of performance(C.O.P)
Model Output Winding resistance(at 20:)
Compressor
Model Winding
Fan
motor
resistance(at 20:) Dimensions WOHOD
Weight Sound level 1 Fan speed(High/Low, High/Med./Low) Fan speed regulator Refrigerant filling
Special
remarks
capacity(R410A) Refrigeration oil (Model)
NOTE : Test conditions are based on ISO 5151
Cooling : Indoor Dry-bulb temperature 27:Wet-bulb temperature 19:
Outdoor Dry-bulb temperature 35:Wet-bulb temperature(24:)
Heating : Indoor Dry-bulb temperature 20:Wet-bulb temperature 15:
Outdoor Dry-bulb temperature 7: Wet-bulb temperature 6: Refrigerant piping length (one way): 5m 1 Measured under rated operating frequency
kW
r/h
K /h
1
mm
dB(A)
rpm
MUZ-GA25VA MUZ-GA25VAH
Cooling
Single phase
230V,50Hz
1.4 1,890
10
2.95 607
89
3.6
2.71
0.24
3.91
KNB065FDTH
500
V-W 1.88
RA6V21-AB
WHT-BLK 347 BLK-RED 281
800o550o285
31 46
810
1
0.85
320 (NEO22)
Heating
3.2 (0.9-4.5)
3.35 727
94
3.11
4.21
U-W 1.88
MUZ-GA35VA MUZ-GA35VAH
Cooling
Single phase
230V,50Hz
3.5 (1.0-3.9)
2.0
2,058
4.75
1,047
96
4.44
0.31
3.24 KNB073FDVH
U-V 1.53
V-W 1.53
RC0J50-AL
WHT-BLK 37.5
BLK-RED 37.5
RED-WHT 37.5
800o550o285
47
810/750
2
320 (NEO22)
Heating
4.0 (0.9-5.0)
2,178
10
4.55
1,022
5.0
4.20
0.35
3.79
550
U-W 1.53
33
880/810/650
0.90
98
48
3
8
Page 9
Specifications and rating conditions of main electric parts
Item
Model
Current transformer Current transformer Smoothing capacitor Diode module
(CT761, CT781) (
C63A, C63B, C63C
(DB61, DB65) Fuse Fuse Fuse
(CT)
(F61)
(F71, F801)
( F901 w1) Defrost heater Intelligent power module Expansion valve coil Reactor Current-detecting resistor Current-detecting resistor Current-limiting resistor
( Terminal block Relay Relay Relay Relay R.V. coil Solid state relay Solenoid valve coil Heater protector
(IPM)
(LEV)
(L61)
(R61)
(R831)
R64A, R64B
(TB1,TB2)
(X63) (X64) (X66) (X69)
(21S4) (SR61) (21R1)
(26H)
)
(H)
)
MUZ-GA25VA
G5NB-1a(for
FQ-208-RK (for
Outdoor fan motor thermal fuse
w1 Refer to Revision A. w2 MUZ-GA25VA- (Serial No. ~6021350T)
MUZ-GA25VAH- (Serial No. ~7000000T)
E3
E3
MUZ-GA25VAH
230V 130W
E1 / E2 / E3 )
SHF-4-10W5
G3MC-202PL
E1 / E2 / E3 w2)
Open 152:
ETA19Z59BZ
ETQ19Z71AY
620+ 420V
D25XB60 250V 20A
250V 3.15A
PS21244-A-203
10A 23.0mH
45m" 5W (1 element)
25m" 5W
10" 5W
G5NB-1a
G4A-1A-PS
G5NB-1a
Open 45:
MUZ-GA35VA
3P
MUZ-GA35VAH
250V 3.15A
230V 130W
CAM-MD12ME 12VDC
G5NB-1a
STF-01AJ503
— —
Open 45:
9
Page 10
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:)
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
46 46
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
SPL(dB(A))
LINE
FAN SPEED
HEATING
47 48
Test conditions Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:)
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
OUTDOORUNIT
MICROPHONE
1m
High Med.
NOISE CRITERIA CURVES
MUZ-GA25VA MUZ-GA25VAH
MUZ-GA35VA MUZ-GA35VAH
10
Page 11
5
10
69
800
302.5 500 Bolt pitch for installation
150
22.3
Handle
550
280
164.5
99.5
170.5
23
Service panel
Service port
285
344.5
44
400
Air in
Air out
Air in
17.5
Bolt pitch for
installation
304~325
40
Liquid refrigerant pipe joint Refrigerant pipe (flared) [6.35
Gas refrigerant pipe joint Refrigerant pipe (flared) [9.52
43-
35-
2 holes 10X21
Drain hole [33 (MUZ-GA25/GA35VAH)
REQUIRED SPACE
Basically open 100mm or more without any obstruction in front and on both sides of the unit.
350mm or more
200mm or more
100mm or more
100mm or more
Open two sides of left, right, or rear side.
Drain hole [42 (MUZ-GA25/GA35VA)
OUTLINES AND DIMENSIONS
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
Unit: mm
11
Page 12
6
SYMBOL
CT,CT761,CT781
C63A,C63B,C63C
C65
DB61,DB65
DSA61
F61
F71,F801
IC801
IPM
SYMBOL
L61
L62,L63MCMF
NR63,NR64
RT61
RT62
RT64
RT65
SYMBOL
R61,R831
R64A,R64B
SR61
TB1,TB2
TR821
T801
X63,X64,X69
21S4
21R1
NAME
CURRENT TRANSFORMER
SMOOTHING CAPACITOR
OUTDOOR FAN CAPACITOR
DIODE MODULE
SURGE ABSORBER
FUSE (T20AL250V)
FUSE (T3.15AL250V)
INTELLIGENT POWER DEVICE
INTELLIGENT POWER MODULE
NAME
REACTOR
CMC COIL
COMPRESSOR
OUTDOOR FAN MOTOR(INNER FUSE)
VARISTOR
DEFROST THERMISTOR
DISCHARGE TEMPERATURE THERMIST OR
FIN TEMPERATURE THERMIST OR
AMBIENT TEMPERA TURE THERMIST OR
NAME
CURRENT-DETECTING RESISTOR
CURRENT-LIMITING RESISTOR
SOLID STATE RELAY
TERMINAL BLOCK
SWITCHING POWER TRANSISTOR
TRANSFORMER
RELAY
R.V. COIL
SOLENOID VALVE COIL
WIRING DIAGRAM
MUZ-GA25VA­MUZ-GA25VA­MUZ-GA25VA- (Serial No. ~6021350T)
E1
E2
E3
U
BLK
1
BLK
LD-U
CT761
U
P
+++
W
REDRED
2
WHT
LD-V
V
F801
MC
3
N
C63C
C63B
C63A
CN61
LD-W
W
R61
V
WHT
CT781
IPM
T801
IC801
CN642
2134
CN641
2121
CN643
INVERTER P.C. BOARD
R831
LDY
54321
CN601
TR821
RT64
RT62RT61
RT65
GRN
the indoor unit electric wiring diagram for
servicing.
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
NOTE:1. About the indoor side electric wiring refer to
BLK
L61
BLK
TAB63
TAB61
L63
L62
WHT
F61
DB61
R64A
R64B
LD70
X64
TAB62
BLK
BLU
3 4
CT
LD69
CN721
X63
F71
NR63NR64
TB800
21S4
2
1
DSA61
MF
CN771
C65
SR61
LDE
GRN
DB65
21R1
2
1
321
2
1
CN923
CN726 CN725
X69
64
CN727
POWER P.C. BOARD
WHITE
BLU
RED
WHT
BLU
230V~
RED
S2S1S3
V 12-24
TB2
L
GRN/YLW
N
~/N
230V 50Hz
TB1
CONNECTING TO INDOOR UNIT
CIRCUIT BREAKER
PE
POWER
SUPPLY
12
Page 13
MUZ-GA25VA- (Serial No. 6021351T~) MUZ-GA25VA-
E3
E4
13
Page 14
SYMBOL
CT,CT761,CT781
C63A,C63B,C63C
C65
DB61,DB65
DSA61
F61
F71,F801HIC801
IPM
SYMBOL
L61
L62,L63MCMF
NR63,NR64
RT61
RT62
RT64
RT65
R61,R831
SYMBOL
R64A,R64B
SR61
TB1,TB2
TR821
T801
X63,X64,X66,X69
21S4
21R1
26H
NAME
CURRENT TRANSFORMER
SMOOTHING CAPACITOR
OUTDOOR FAN CAPACITOR
DIODE MODULE
SURGE ABSORBER
FUSE (T20AL250V)
FUSE (T3.15AL250V)
DEFROST HEATER
INTELLIGENT POWER DEVICE
INTELLIGENT POWER MODULE
NAME
REACTOR
CMC COIL
COMPRESSOR
OUTDOOR FAN MOTOR(INNER FUSE)
VARISTOR
DEFROST THERMISTOR
DISCHARGE TEMPERATURE THERMIST OR
FIN TEMPERATURE THERMIST OR
AMBIENT TEMPERA TURE THERMIST OR
CURRENT-DETECTING RESISTOR
NAME
CURRENT-LIMITING RESISTOR
SOLID STATE RELAY
TERMINAL BLOCK
SWITCHING POWER TRANSISTOR
TRANSFORMER
RELAY
R.V. COIL
SOLENOID VALVE COIL
HEATER PROTECTOR
MUZ-GA25VAH- MUZ-GA25VAH- (Serial No. ~7000000T) MUZ-GA25VAH-
E2
U
E3E1
V
BLK
L61
BLK
TAB63
BLK
DB61
1
BLK
LD-U
U
P
R64A
R64B
MC
W
2
3
WHT
RED RED
LD-V
CT761
V
N
F801
C63C
C63B
+++
C63A
LD70
X64
CN61
LD-W
CT781
W
R61
BLK
BLU
3 4
CT
WHT
IPM
T801
LD69
1
CN721
X63
F71
IC801
TR821
TB800
21S4
2
CN771
CN642
431212
CN641
21
CN643
INVERTER P.C. BOARD
LDY
21R1
2
2
1
1
45 231
CN601
CN725CN727 CN726
46
R831
DB65
MF
312
CN923
X69
C65
SR61
RT65 RT64RT62RT61
GRN
the indoor unit electric wiring diagram for
servicing.
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
NOTE:1. About the indoor side electric wiring refer to
L63
L62
TAB61
WHT
F61
BLU
WHT
TB2
S1
S2
230V~
TAB62
NR64 NR63
RED
S3
V 12-24
CONNECTING TO INDOOR UNIT
DSA61
LDE
POWER P.C. BOARD
GRN
GRN/YLW
N
~/N
230V 50Hz
PE
POWER
SUPPLY
TB1
L
CIRCUIT BREAKER
14
X66
CN722
RED
1
2
BLKBLK
BLK BLK
312
YLW
26H
BLK
H
BLK
1
BLK
WHITE
BLU
RED
2
Page 15
MUZ-GA25VAH- (Serial No. 7000001T~) MUZ-GA25VAH-
E3
E4
15
Page 16
SYMBOL
CT,CT761,CT781
C63A,C63B,C63C
DB61,DB65
DSA61
F61
F71,F801
IC801
IPM
LEV
SYMBOL
L61
L62,L63MCMF
NR63,NR64
RT61
RT62
RT64
RT65
SYMBOL
R61,R831
R64A,R64B
TB1,TB2
TR821
T801
X63,X64
21S4
NAME
CURRENT TRANSFORMER
SMOOTHING CAPACITOR
DIODE MODULE
SURGE ABSORBER
FUSE (T20AL250V)
FUSE (T3.15AL250V)
INTELLIGENT POWER DEVICE
INTELLIGENT POWER MODULE
EXPANSION VALVE COIL
NAME
REACTOR
CMC COIL
COMPRESSOR
OUTDOOR FAN MOTOR
VARISTOR
DEFROST THERMISTOR
DISCHARGE TEMPERATURE THERMIST OR
FIN TEMPERATURE THERMIST OR
AMBIENT TEMPERA TURE THERMIST OR
NAME
CURRENT-DETECTING RESISTOR
CURRENT-LIMITING RESISTOR
TERMINAL BLOCK
SWITCHING POWER TRANSISTOR
TRANSFORMER
RELAY
R.V. COIL
MUZ-GA35VA
~/N
230V~
230V 50Hz
CIRCUIT BREAKER
PE
RED
BLU
WHITE
GRN/YLW
TB1
POWER
SUPPLY
L
N
R64A
TB2
S3
S1
TO INDOOR UNIT
CONNECTING
S2
RED
BLU
WHT
R64B
WHT
+++
NR63
LDE
GRN
4
6
21
231
CN601
45
31 24
5
3
2
1
24
51 3
CN931 CN932
431212
TB800
RT65 RT64RT62RT61
POWER P.C. BOARD
CN643
CN641
INVERTER P.C. BOARD
CN642
21S4
MF
X63
CN721
1
2
IC801
F801
C63C
LD-V
LD-W
LD-U
3
1
WHT
BLK
RED RED
V
BLK
WHT
W
U
MC
CN61
IPM
CT781
CT761
2
CN724
LEV
6
R61
N
U
V
W
P
L61
BLK
R831
TAB63
3
LD69
DB65
DB61
LD70
TR821
C63B
C63A
BLK
T801
L63
NR64
DSA61
F61
CT
LDY
TAB61
L62
X64
4
F71
TAB62
GRN
BLK
BLU
CN727CN72
6
CN725
12-24
V
the indoor unit electric wiring diagram for
servicing.
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
NOTE:1. About the indoor side electric wiring refer to
16
Page 17
MUZ-GA35VAH
SYMBOL
CT,CT761,CT781
C63A,C63B,C63C
DB61,DB65
DSA61
F61
F71,F801HIC801
IPM
LEV
SYMBOL
L61
L62,L63MCMF
NR63,NR64
RT61
RT62
RT64
RT65
R61,R831
SYMBOL
R64A,R64B
TB1,TB2
TR821
T801
X63,X64,X66
21S4
26H
NAME
CURRENT TRANSFORMER
SMOOTHING CAPACITOR
DIODE MODULE
SURGE ABSORBER
FUSE (T20AL250V)
FUSE (T3.15AL250V)
DEFROST HEATER
INTELLIGENT POWER DEVICE
INTELLIGENT POWER MODULE
EXPANSION VALVE COIL
NAME
REACTOR
CMC COIL
COMPRESSOR
OUTDOOR FAN MOTOR
VARISTOR
DEFROST THERMISTOR
DISCHARGE TEMPERATURE THERMIST OR
FIN TEMPERATURE THERMIST OR
AMBIENT TEMPERA TURE THERMIST OR
CURRENT-DETECTING RESISTOR
NAME
CURRENT-LIMITING RESISTOR
TERMINAL BLOCK
SWITCHING POWER TRANSISTOR
TRANSFORMER
RELAY
R.V. COIL
HEATER PROTECTOR
BLK
L61
BLK
U
BLK
BLK
LD-U
U
P
DB61
TAB63
R64A
R64B
W
2
1
WHT
RED RED
LD-V
CT761
V
F801
+++
MC
3
LD-W
W
N
C63C
C63B
C63A
LD70
X64
CN61
CT781
R61
BLK
BLU
3 4
V
WHT
IPM
T801
6
CN724
LD69
X63
LEV
IC801
TR821
TB800
21S4
1
2
CN642
431212
CN641
21
CN643
3 2 1
INVERTER P.C. BOARD
5 3
24
CN931 CN932
1
R831
LDY
CN725
4
23145
CN601
6
DB65
6
CN727CN72
CN721
5 31
24
GRN
RT65 RT64RT62RT61
MF
the indoor unit electric wiring diagram for
servicing.
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
NOTE:1. About the indoor side electric wiring refer to
L63
L62
TAB61
WHT
F61
WHT
TB2
S1
230V~
BLU
S2
TAB62
RED
S3
V 12-24
CT
F71
DSA61
LDE
NR64 NR63
GRN
GRN/YLW
TB1
L
N
CONNECTING TO INDOOR UNIT
CIRCUIT BREAKER
~/N
230V 50Hz
X66
WHITE
BLU
312
CN722
POWER P.C. BOARD
BLK
RED
YLW
1
2
1
2
BLKBLK
BLK
BLK
BLK BLK
H
PE
POWER
26H
SUPPLY
17
RED
Page 18
SYMBOL
CT,CT761,CT781
C63A,C63B,C63C
DB61,DB65
DSA61
F61
F71,F801,F901
IC801
IPM,IC932
LEV
SYMBOL
L61
L62,L63MCMF
NR63,NR64
RT61
RT62
RT64
RT65
SYMBOL
R61,R831
R64A,R64B
TB1,TB2
TR821
T801
X63,X64
21S4
NAME
CURRENT TRANSFORMER
SMOOTHING CAPACITOR
DIODE MODULE
SURGE ABSORBER
FUSE (T20AL250V)
FUSE (T3.15AL250V)
INTELLIGENT POWER DEVICE
INTELLIGENT POWER MODULE
EXPANSION VALVE COIL
NAME
REACTOR
CMC COIL
COMPRESSOR
OUTDOOR FAN MOTOR
VARISTOR
DEFROST THERMISTOR
DISCHARGE TEMPERATURE THERMIST OR
FIN TEMPERATURE THERMIST OR
AMBIENT TEMPERA TURE THERMIST OR
NAME
CURRENT-DETECTING RESISTOR
CURRENT-LIMITING RESISTOR
TERMINAL BLOCK
SWITCHING POWER TRANSISTOR
TRANSFORMER
RELAY
R.V. COIL
MUZ-GA35VA
ww
Alternative inverter P.C. board
U
MC
BLK
W
RED
1
2
3
CN61
WHT
BLK
RED
LD-W
LD-U
LD-V
CT761
U
V
W
P
N
R61
V
WHT
CT781
IPM
LEV
6
724
C
N
CN931
IC932
F901
CN932
3 2 1
5 42 3
1
MF
5 42 3
1
the indoor unit electric wiring diagram for
servicing.
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
NOTE:1. About the indoor side electric wiring refer to
L61
DB61
BLK
BLK
TAB63
L63
L62
TAB61
WHT
F61
+++
R64A
R64B
F801
C63C
C63B
C63A
LD70
X64
TAB62
BLK
3
4
CT
T801
BLU
NR63
NR64
LD69
X63
F71
IC801
TR821
TB800
21S4
1
2
DSA61
GRN
DB65
6
C
CN721
LDE
CN642
21213412
CN641
INVERTER P.C. BOARD
CN643
R831
LDY
CN601
725
C
N
4
726
727
C
N
N
RT61 RT62 RT64RT65
GRN
45 231
POWER P.C. BOARD
WHITE
BLU
RED
WHT
TB2
S1
~ 230V
BLU
S2
RED
S3
12-24V
TB1
L
N
CONNECTING TO INDOOR UNIT
CIRCUIT BREAKER
~/N
230V 50Hz
GRN/YLW
PE
POWER
SUPPLY
18
Page 19
MUZ-GA35VAH
SYMBOL
CT,CT761,CT781
C63A,C63B,C63C
DB61,DB65
DSA61
F61
F71,F801,F901
H
IC801
IPM,IC932
LEV
SYMBOL
L61
L62,L63MCMF
NR63,NR64
RT61
RT62
RT64
RT65
R61,R831
SYMBOL
R64A,R64B
TB1,TB2
TR821
T801
X63,X64,X66
21S4
26H
NAME
CURRENT TRANSFORMER
SMOOTHING CAPACITOR
DIODE MODULE
SURGE ABSORBER
FUSE (T20AL250V)
FUSE (T3.15AL250V)
DEFROST HEATER
INTELLIGENT POWER DEVICE
INTELLIGENT POWER MODULE
EXPANSION VALVE COIL
NAME
REACTOR
CMC COIL
COMPRESSOR
OUTDOOR FAN MOTOR
VARISTOR
DEFROST THERMISTOR
DISCHARGE TEMPERATURE THERMIST OR
FIN TEMPERATURE THERMIST OR
AMBIENT TEMPERA TURE THERMIST OR
CURRENT-DETECTING RESISTOR
NAME
CURRENT-LIMITING RESISTOR
TERMINAL BLOCK
SWITCHING POWER TRANSISTOR
TRANSFORMER
RELAY
R.V. COIL
HEATER PROTECTOR
ww
Alternative inverter P.C. board
BLK
U
1
BLK
LD-U
U
P
MC
W
2
3
WHT
RED RED
LD-V
CT761
V
N
CN61
LD-W
W
R61
V
WHT
CT781
IPM
LEV
6
CN932
3 2 1
5 3
24 1
MF
5 31
24
the indoor unit electric wiring diagram for
servicing.
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
NOTE:1. About the indoor side electric wiring refer to
724
C
N
IC932
CN931
F901
BLK
L61
BLK
TAB63
TAB61
TB2
DB61
L63
L62
WHT
F61
WHT
S1
230V~
F801
+++
R64A
R64B
BLU
S2
T801
C63C
C63B
C63A
LD70
BLK
BLU
3
X64
4
CT
TAB62
NR64 NR63
RED
S3
V 12-24
CONNECTING TO INDOOR UNIT
CIRCUIT BREAKER
LD69
X63
F71
TB1
L
IC801
TR821
TB800
21S4
1
2
DSA61
GRN
N
~/N
CN642
431212
CN641
INVERTER P.C. BOARD
21
CN643
R831
LDY
CN725
4
23145
CN601
6
DB65
6
CN727CN72
CN721
X66
LDE
POWER P.C. BOARD
GRN/YLW
PE
POWER
SUPPLY
230V 50Hz
CN722
RED
1
2
BLKBLK
BLK BLK
312
YLW
26H
BLK
H
1
BLK
2
BLK
RT65 RT64RT62RT61
GRN
WHITE
BLU
RED
19
Page 20
7
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainer)
Stop valve (with service port)
Refrigerant flow in cooling
Compressor
Muffler
Muffler
4-way valve
Refrigerant flow in heating
Refrigerant pipe [9.52 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
Capillary tube [3.0[1.4800
Check valve
Capillary tube [3.0[1.4500
Solenoid valve
Ambient temperature thermistor RT65
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainer)
Stop valve (with service port)
Refrigerant flow in cooling
Compressor
Muffler
Muffler
4-way valve
Refrigerant flow in heating
Refrigerant pipe [9.52 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
Capillary tube [3.0[1.4800
Check valve
Capillary tube [3.0[1.4500
Solenoid
valve
Ambient temperature thermistor RT65
Capillary tube [3.0[1.4400
Check valve
REFRIGERANT SYSTEM DIAGRAM
MUZ-GA25VA - MUZ-GA25VA ­MUZ-GA25VAH - MUZ-GA25VAH -
E2E1
E2E1
Unit:mm
MUZ-GA25VA ­MUZ-GA25VAH -
E3
E3
20
Unit:mm
Page 21
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainer)
Stop valve (with service port)
Refrigerant flow in cooling
Compressor
Muffler
Muffler
4-way valve
Refrigerant flow in heating
Refrigerant pipe [9.52 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
Capillary tube [3.0[1.4800
Ambient temperature thermistor RT65
Capillary tube [3.0[1.4400
Check valve
MUZ-GA25VA -
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainer)
Stop valve (with service port)
Capillary tube [3.0[2.0240
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe [9.52 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Strainer #100
Muffler
Ambient temperature thermistor RT65
Muffler
Muffler
MUZ-GA25VAH -
E4
E4
Unit:mm
MUZ-GA35VA MUZ-GA35VAH
21
Unit:mm
Page 22
Outdoor unit
precharged
14m
270
7m
0
6m
0
5m
0
11m
180
Model
Refrigerant piping length (one way)
8m
90
9m
120
10m
150
12m
210
13m
240
15m
300
20m
450
850
900
MUZ-GA25VA MUZ-GA25VAH
MUZ-GA35VA MUZ-GA35VAH
Max. length A
Max. Height
difference
B
Indoor unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Max. length
A
20
Max. Height difference
B
12
Model
Gas
9.52
Liquid
6.35
Piping size O.D : mm
Refrigerant piping : m
MUZ-GA25VA MUZ-GA25VAH MUZ-GA35VA MUZ-GA35VAH
ADDITIONAL REFRIGERANT CHARGE (R410A:g)
Calculation : Xg=30g/m (Refrigerant piping length (m)–5)
NOTE: Refrigerant piping exceeding 7m requires additional refrigerant charge according to the calculation.
22
Page 23
PERFORMANCE CURVES8
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions. Since operating conditions vary according to the areas where these units are installed, the following information has been pro­vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264V, 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : °C WB (2) Indoor outlet air wet-bulb temperature : °C WB (3) Outdoor intake air dry-bulb temperature : °C DB (4) Total input: W (5) Indoor intake air dry-bulb temperature : °C DB (6) Outdoor intake air wet-bulb temperature : °C WB (7) Total input : W Indoor air wet/dry-bulb temperature difference on the left side of the following chart shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb / dry-bulb temperature difference
1. Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
}
}
Cooling
Heating
INDOOR UNIT
Wet and dry-bulb thermometers
8-1. Capacity and input curves
6.4
5.8
5.3
4.9
4.4
difference (degree)
3.9
Indoor air Wet-bulb temperature
9.1
8.3
7.6
6.8
6.1
5.5
OUTDOOR UNIT
Indoor intake air Wet-bulb temperature (
Wet and dry-bulb thermometers
:)
Indoor intake air W
et-bulb tem
perature (
)
:
MUZ-GA25VAH
MUZ-GA25VA
MUZ-GA35VA
Rated frequency 65Hz
Outdoor intake air Dry-bulb temperature (:)
MUZ-GA35VAH
Rated frequency 88Hz
Outdoor intake air Dry-bulb temperature (:)
23
Page 24
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
Correction of Heating total input
The operational frequency of compressor
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
Correction of Heating total input
Input correction factors
The operational frequency of compressor
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
Input correction factors
MUZ-GA25VA MUZ-GA25VAH
MUZ-GA25VA MUZ-GA25VAH
MUZ-GA25VA MUZ-GA25VAH
MUZ-GA25VA MUZ-GA25VAH
MUZ-GA35VA MUZ-GA35VAH
MUZ-GA35VA MUZ-GA35VAH
MUZ-GA35VA MUZ-GA35VAH
MUZ-GA35VA MUZ-GA35VAH
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
2.0
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
2.0
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
2.0
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
2.0
19.7
18.2
16.7
15.2
13.7
12.1
10.6
9.1
24.7
22.8
20.9
19.0
17.1
15.2
13.3
11.4
Indoor air Dry-bulb temperature
difference (degree)
Indoor intake air Dry-bulb tem
perature (
:
)
Outdoor intake air Wet-bulb temperature (:)
Outdoor intake air Wet-bulb temperature (:)
Indoor intake air Dry-bulb temperature (
:)
Rated frequency 85Hz
Rated frequency 96Hz
MUZ-GA35VA
MUZ-GA35VAH
MUZ-GA25VA
MUZ-GA25VAH
NOTE:The above broken lines are for the heating operation without any frost and
defrost operation.
8-2. Capacity and input correction by operational frequency of compressor
8-3. Test run operation (How to operate fixed-frequency operation)
1. Press EMERGENCY OPERATION switch to COOL or HEAT mode (COOL : Press once, HEAT : Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (Operation frequency of compressor
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on
varies). remote controller.
24
Page 25
8-4. Outdoor low pressure and outdoor unit current
Dry bulb temperature (°C)
Indoor
20.0
14.521
Outdoor 7 6
151220.0
14.5
Wet bulb temperature (°C)
COOL operation
1 Both indoor and outdoor unit are under the
same temperature/humidity condition.
2 Operation : TEST RUN OPERATION (refer to 8-3.)
MUZ-GA25VA MUZ-GA25VAH
(kgf/F [Gauge]) (MPa [Gauge])
1.4
14
1.2
12
1.0
10
0.8
8
0.6
6
Outdoor low pressure
0.4
4 2
0.2 15 2050256030
18 32
Ambient temperature(˚C) Ambient humidity(%)
MUZ-GA25VA MUZ-GA25VAH
4
3.5
70 (%)
(kgf/F [Gauge]) (MPa [Gauge])
14
65Hz
35(˚C)
12 10
8 6
Outdoor low pressure
4 2
Ambient temperature(˚C) Ambient humidity(%)
Dry-bulb temperature(:)
MUZ-GA35VA MUZ-GA35VAH
1.4
1.2
1.0
0.8
0.6
0.4
0.2 15 2050256030
18 32
MUZ-GA35VA MUZ-GA35VAH
6
5
20 25 30 70
88Hz
35(˚C)
70 (%)
88Hz
Relative humidity(%)
50 60
3
65Hz
2.5
Outdoor unit current(A)
2
15 2050256030
18
Ambient temperature(˚C) Ambient humidity(%)
35(˚C)
32
70 (%)
HEAT operation
1 Condition :
2 Operation : Test run operation (refer to 8-3.)
MUZ-GA25VA MUZ-GA25VAH
3.0
2.5
2.0
1.5
1.0
0.5
Outdoor unit current (A)
0.0 2
5 10 15 20 25(:)
Ambient temperature(˚C)
58Hz
4
3
Outdoor unit current(A)
2
15 205025
18
Ambient temperature(˚C) Ambient humidity(%)
60
30
35(˚C)
32
70 (%)
MUZ-GA35VA MUZ-GA35VAH
4.0
3.5
3.0
2.5
2.0
1.5
Outdoor unit current (A)
1.0 2
5 10 15 20 25(:)
Ambient temperature(˚C)
58Hz
25
Page 26
21 18 2.94 1.79 0.61 512 2.81 1.72 0.61 538 2.70 1.65 0.61 563 2.60 1.59 0.61 589 21 20 3.06 1.50 0.49 538 2.94 1.44 0.49 570 2.85 1.40 0.49 582 2.75 1.35 0.49 608 22 18 2.94 1.91 0.65 512 2.81 1.83 0.65 538 2.70 1.76 0.65 563 2.60 1.69 0.65 589 22 20 3.06 1.62 0.53 538 2.94 1.56 0.53 570 2.85 1.51 0.53 582 2.75 1.46 0.53 608 22 22 3.19 1.31 0.41 557 3.08 1.26 0.41 592 3.00 1.23 0.41 608 2.88 1.18 0.41 634 23 18 2.94 2.03 0.69 512 2.81 1.94 0.69 538 2.70 1.86 0.69 563 2.60 1.79 0.69 589 23 20 3.06 1.75 0.57 538 2.94 1.67 0.57 570 2.85 1.62 0.57 582 2.75 1.57 0.57 608 23 22 3.19 1.43 0.45 557 3.08 1.38 0.45 592 3.00 1.35 0.45 608 2.88 1.29 0.45 634 24 18 2.94 2.14 0.73 512 2.81 2.05 0.73 538 2.70 1.97 0.73 563 2.60 1.90 0.73 589 24 20 3.06 1.87 0.61 538 2.94 1.79 0.61 570 2.85 1.74 0.61 582 2.75 1.68 0.61 608 24 22 3.19 1.56 0.49 557 3.08 1.51 0.49 592 3.00 1.47 0.49 608 2.88 1.41 0.49 634 24 24 3.35 1.24 0.37 582 3.23 1.19 0.37 614 3.15 1.17 0.37 634 3.05 1.13 0.37 666 25 18 2.94 2.26 0.77 512 2.81 2.17 0.77 538 2.70 2.08 0.77 563 2.60 2.00 0.77 589 25 20 3.06 1.99 0.65 538 2.94 1.91 0.65 570 2.85 1.85 0.65 582 2.75 1.79 0.65 608 25 22 3.19 1.69 0.53 557 3.08 1.63 0.53 592 3.00 1.59 0.53 608 2.88 1.52 0.53 634 25 24 3.35 1.37 0.41 582 3.23 1.32 0.41 614 3.15 1.29 0.41 634 3.05 1.25 0.41 666 26 18 2.94 2.38 0.81 512 2.81 2.28 0.81 538 2.70 2.19 0.81 563 2.60 2.11 0.81 589 26 20 3.06 2.11 0.69 538 2.94 2.03 0.69 570 2.85 1.97 0.69 582 2.75 1.90 0.69 608 26 22 3.19 1.82 0.57 557 3.08 1.75 0.57 592 3.00 1.71 0.57 608 2.88 1.64 0.57 634 26 24 3.35 1.51 0.45 582 3.23 1.45 0.45 614 3.15 1.42 0.45 634 3.05 1.37 0.45 666 26 26 3.45 1.14 0.33 614 3.35 1.11 0.33 646 3.30 1.09 0.33 666 3.20 1.06 0.33 685 27 18 2.94 2.50 0.85 512 2.81 2.39 0.85 538 2.70 2.30 0.85 563 2.60 2.21 0.85 589 27 20 3.06 2.24 0.73 538 2.94 2.14 0.73 570 2.85 2.08 0.73 582 2.75 2.01 0.73 608 27 22 3.19 1.94 0.61 557 3.08 1.88 0.61 592 3.00 1.83 0.61 608 2.88 1.75 0.61 634 27 24 3.35 1.64 0.49 582 3.23 1.58 0.49 614 3.15 1.54 0.49 634 3.05 1.49 0.49 666 27 26 3.45 1.28 0.37 614 3.35 1.24 0.37 646 3.30 1.22 0.37 666 3.20 1.18 0.37 685 28 18 2.94 2.61 0.89 512 2.81 2.50 0.89 538 2.70 2.40 0.89 563 2.60 2.31 0.89 589 28 20 3.06 2.36 0.77 538 2.94 2.26 0.77 570 2.85 2.19 0.77 582 2.75 2.12 0.77 608 28 22 3.19 2.07 0.65 557 3.08 2.00 0.65 592 3.00 1.95 0.65 608 2.88 1.87 0.65 634 28 24 3.35 1.78 0.53 582 3.23 1.71 0.53 614 3.15 1.67 0.53 634 3.05 1.62 0.53 666 28 26 3.45 1.41 0.41 614 3.35 1.37 0.41 646 3.30 1.35 0.41 666 3.20 1.31 0.41 685 29 18 2.94 2.73 0.93 512 2.81 2.62 0.93 538 2.70 2.51 0.93 563 2.60 2.42 0.93 589 29 20 3.06 2.48 0.81 538 2.94 2.38 0.81 570 2.85 2.31 0.81 582 2.75 2.23 0.81 608 29 22 3.19 2.20 0.69 557 3.08 2.12 0.69 592 3.00 2.07 0.69 608 2.88 1.98 0.69 634 29 24 3.35 1.91 0.57 582 3.23 1.84 0.57 614 3.15 1.80 0.57 634 3.05 1.74 0.57 666 29 26 3.45 1.55 0.45 614 3.35 1.51 0.45 646 3.30 1.49 0.45 666 3.20 1.44 0.45 685 30 18 2.94 2.85 0.97 512 2.81 2.73 0.97 538 2.70 2.62 0.97 563 2.60 2.52 0.97 589 30 20 3.06 2.60 0.85 538 2.94 2.50 0.85 570 2.85 2.42 0.85 582 2.75 2.34 0.85 608 30 22 3.19 2.33 0.73 557 3.08 2.24 0.73 592 3.00 2.19 0.73 608 2.88 2.10 0.73 634 30 24 3.35 2.04 0.61 582 3.23 1.97 0.61 614 3.15 1.92 0.61 634 3.05 1.86 0.61 666 30 26 3.45 1.69 0.49 614 3.35 1.64 0.49 646 3.30 1.62 0.49 666 3.20 1.57 0.49 685 31 18 2.94 2.97 1.01 512 2.81 2.84 1.01 538 2.70 2.73 1.01 563 2.60 2.63 1.01 589 31 20 3.06 2.73 0.89 538 2.94 2.61 0.89 570 2.85 2.54 0.89 582 2.75 2.45 0.89 608 31 22 3.19 2.45 0.77 557 3.08 2.37 0.77 592 3.00 2.31 0.77 608 2.88 2.21 0.77 634 31 24 3.35 2.18 0.65 582 3.23 2.10 0.65 614 3.15 2.05 0.65 634 3.05 1.98 0.65 666 31 26 3.45 1.83 0.53 614 3.35 1.78 0.53 646 3.30 1.75 0.53 666 3.20 1.70 0.53 685 32 18 2.94 3.08 1.05 512 2.81 2.95 1.05 538 2.70 2.84 1.05 563 2.60 2.73 1.05 589 32 20 3.06 2.85 0.93 538 2.94 2.73 0.93 570 2.85 2.65 0.93 582 2.75 2.56 0.93 608 32 22 3.19 2.58 0.81 557 3.08 2.49 0.81 592 3.00 2.43 0.81 608 2.88 2.33 0.81 634 32 24 3.35 2.31 0.69 582 3.23 2.23 0.69 614 3.15 2.17 0.69 634 3.05 2.10 0.69 666 32 26 3.45 1.97 0.57 614 3.35 1.91 0.57 646 3.30 1.88 0.57 666 3.20 1.82 0.57 685
INDOOR INDOOR
CAPACITY:2.5(kW)
INPUT:640(W)SHF:0.79
21
OUTDOOR DB(:)
25 27 30
WB(:)
Q SHC SHF Q SHC SHF Q SHC SHF Q SHC SHFINPUT INPUT INPUT INPUT
DB(:)
PERFORMANCE DATA COOL operation Rated frequency 65Hz
MUZ-GA25VA MUZ-GA25VAH
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
26
Page 27
PERFORMANCE DATA COOL operation Rated frequency 65Hz
MUZ-GA25VA MUZ-GA25VAH
CAPACITY:2.5(kW)
INDOOR INDOOR
DB (:) WB (:)
21 18 2.45 1.49 0.61 627 2.25 1.37 0.61 666 2.08 1.27 0.61 691 21 20 2.58 1.26 0.49 653 2.40 1.18 0.49 685 2.23 1.09 0.49 723 22 18 2.45 1.59 0.65 627 2.25 1.46 0.65 666 2.08 1.35 0.65 691 22 20 2.58 1.36 0.53 653 2.40 1.27 0.53 685 2.23 1.18 0.53 723 22 22 2.73 1.12 0.41 678 2.55 1.05 0.41 717 2.38 0.97 0.41 742 23 18 2.45 1.69 0.69 627 2.25 1.55 0.69 666 2.08 1.43 0.69 691 23 20 2.58 1.47 0.57 653 2.40 1.37 0.57 685 2.23 1.27 0.57 723 23 22 2.73 1.23 0.45 678 2.55 1.15 0.45 717 2.38 1.07 0.45 742 24 18 2.45 1.79 0.73 627 2.25 1.64 0.73 666 2.08 1.51 0.73 691 24 20 2.58 1.57 0.61 653 2.40 1.46 0.61 685 2.23 1.36 0.61 723 24 22 2.73 1.34 0.49 678 2.55 1.25 0.49 717 2.38 1.16 0.49 742 24 24 2.88 1.06 0.37 704 2.70 1.00 0.37 736 2.55 0.94 0.37 768 25 18 2.45 1.89 0.77 627 2.25 1.73 0.77 666 2.08 1.60 0.77 691 25 20 2.58 1.67 0.65 653 2.40 1.56 0.65 685 2.23 1.45 0.65 723 25 22 2.73 1.44 0.53 678 2.55 1.35 0.53 717 2.38 1.26 0.53 742 25 24 2.88 1.18 0.41 704 2.70 1.11 0.41 736 2.55 1.05 0.41 768 26 18 2.45 1.98 0.81 627 2.25 1.82 0.81 666 2.08 1.68 0.81 691 26 20 2.58 1.78 0.69 653 2.40 1.66 0.69 685 2.23 1.54 0.69 723 26 22 2.73 1.55 0.57 678 2.55 1.45 0.57 717 2.38 1.35 0.57 742 26 24 2.88 1.29 0.45 704 2.70 1.22 0.45 736 2.55 1.15 0.45 768 26 26 3.03 1.00 0.33 730 2.85 0.94 0.33 762 2.68 0.88 0.33 794 27 18 2.45 2.08 0.85 627 2.25 1.91 0.85 666 2.08 1.76 0.85 691 27 20 2.58 1.88 0.73 653 2.40 1.75 0.73 685 2.23 1.62 0.73 723 27 22 2.73 1.66 0.61 678 2.55 1.56 0.61 717 2.38 1.45 0.61 742 27 24 2.88 1.41 0.49 704 2.70 1.32 0.49 736 2.55 1.25 0.49 768 27 26 3.03 1.12 0.37 730 2.85 1.05 0.37 762 2.68 0.99 0.37 794 28 18 2.45 2.18 0.89 627 2.25 2.00 0.89 666 2.08 1.85 0.89 691 28 20 2.58 1.98 0.77 653 2.40 1.85 0.77 685 2.23 1.71 0.77 723 28 22 2.73 1.77 0.65 678 2.55 1.66 0.65 717 2.38 1.54 0.65 742 28 24 2.88 1.52 0.53 704 2.70 1.43 0.53 736 2.55 1.35 0.53 768 28 26 3.03 1.24 0.41 730 2.85 1.17 0.41 762 2.68 1.10 0.41 794 29 18 2.45 2.28 0.93 627 2.25 2.09 0.93 666 2.08 1.93 0.93 691 29 20 2.58 2.09 0.81 653 2.40 1.94 0.81 685 2.23 1.80 0.81 723 29 22 2.73 1.88 0.69 678 2.55 1.76 0.69 717 2.38 1.64 0.69 742 29 24 2.88 1.64 0.57 704 2.70 1.54 0.57 736 2.55 1.45 0.57 768 29 26 3.03 1.36 0.45 730 2.85 1.28 0.45 762 2.68 1.20 0.45 794 30 18 2.45 2.38 0.97 627 2.25 2.18 0.97 666 2.08 2.01 0.97 691 30 20 2.58 2.19 0.85 653 2.40 2.04 0.85 685 2.23 1.89 0.85 723 30 22 2.73 1.99 0.73 678 2.55 1.86 0.73 717 2.38 1.73 0.73 742 30 24 2.88 1.75 0.61 704 2.70 1.65 0.61 736 2.55 1.56 0.61 768 30 26 3.03 1.48 0.49 730 2.85 1.40 0.49 762 2.68 1.31 0.49 794 31 18 2.45 2.47 1.01 627 2.25 2.27 1.01 666 2.08 2.10 1.01 691 31 20 2.58 2.29 0.89 653 2.40 2.14 0.89 685 2.23 1.98 0.89 723 31 22 2.73 2.10 0.77 678 2.55 1.96 0.77 717 2.38 1.83 0.77 742 31 24 2.88 1.87 0.65 704 2.70 1.76 0.65 736 2.55 1.66 0.65 768 31 26 3.03 1.60 0.53 730 2.85 1.51 0.53 762 2.68 1.42 0.53 794 32 18 2.45 2.57 1.05 627 2.25 2.36 1.05 666 2.08 2.18 1.05 691 32 20 2.58 2.39 0.93 653 2.40 2.23 0.93 685 2.23 2.07 0.93 723 32 22 2.73 2.21 0.81 678 2.55 2.07 0.81 717 2.38 1.92 0.81 742 32 24 2.88 1.98 0.69 704 2.70 1.86 0.69 736 2.55 1.76 0.69 768 32 26 3.03 1.72 0.57 730 2.85 1.62 0.57 762 2.68 1.52 0.57 794
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
INPUT:640(W)SHF:0.79
OUTDOOR DB(:)
35 40 46
27
Page 28
21 18 4.11 2.39 0.58 864 3.94 2.28 0.58 907 3.78 2.19 0.58 950 3.64 2.11 0.58 994 21 20 4.29 1.97 0.46 907 4.11 1.89 0.46 961 3.99 1.84 0.46 983 3.85 1.77 0.46 1026 22 18 4.11 2.55 0.62 864 3.94 2.44 0.62 907 3.78 2.34 0.62 950 3.64 2.26 0.62 994 22 20 4.29 2.14 0.50 907 4.11 2.06 0.50 961 3.99 2.00 0.50 983 3.85 1.93 0.50 1026 22 22 4.46 1.70 0.38 940 4.31 1.64 0.38 999 4.20 1.60 0.38 1026 4.03 1.53 0.38 1069 23 18 4.11 2.71 0.66 864 3.94 2.60 0.66 907 3.78 2.49 0.66 950 3.64 2.40 0.66 994 23 20 4.29 2.32 0.54 907 4.11 2.22 0.54 961 3.99 2.15 0.54 983 3.85 2.08 0.54 1026 23 22 4.46 1.87 0.42 940 4.31 1.81 0.42 999 4.20 1.76 0.42 1026 4.03 1.69 0.42 1069 24 18 4.11 2.88 0.70 864 3.94 2.76 0.70 907 3.78 2.65 0.70 950 3.64 2.55 0.70 994 24 20 4.29 2.49 0.58 907 4.11 2.39 0.58 961 3.99 2.31 0.58 983 3.85 2.23 0.58 1026 24 22 4.46 2.05 0.46 940 4.31 1.98 0.46 999 4.20 1.93 0.46 1026 4.03 1.85 0.46 1069 24 24 4.69 1.59 0.34 983 4.52 1.54 0.34 1037 4.41 1.50 0.34 1069 4.27 1.45 0.34 1123 25 18 4.11 3.04 0.74 864 3.94 2.91 0.74 907 3.78 2.80 0.74 950 3.64 2.69 0.74 994 25 20 4.29 2.66 0.62 907 4.11 2.55 0.62 961 3.99 2.47 0.62 983 3.85 2.39 0.62 1026 25 22 4.46 2.23 0.50 940 4.31 2.15 0.50 999 4.20 2.10 0.50 1026 4.03 2.01 0.50 1069 25 24 4.69 1.78 0.38 983 4.52 1.72 0.38 1037 4.41 1.68 0.38 1069 4.27 1.62 0.38 1123 26 18 4.11 3.21 0.78 864 3.94 3.07 0.78 907 3.78 2.95 0.78 950 3.64 2.84 0.78 994 26 20 4.29 2.83 0.66 907 4.11 2.71 0.66 961 3.99 2.63 0.66 983 3.85 2.54 0.66 1026 26 22 4.46 2.41 0.54 940 4.31 2.32 0.54 999 4.20 2.27 0.54 1026 4.03 2.17 0.54 1069 26 24 4.69 1.97 0.42 983 4.52 1.90 0.42 1037 4.41 1.85 0.42 1069 4.27 1.79 0.42 1123 26 26 4.83 1.45 0.30 1037 4.69 1.41 0.30 1091 4.62 1.39 0.30 1123 4.48 1.34 0.30 1156 27 18 4.11 3.37 0.82 864 3.94 3.23 0.82 907 3.78 3.10 0.82 950 3.64 2.98 0.82 994 27 20 4.29 3.00 0.70 907 4.11 2.88 0.70 961 3.99 2.79 0.70 983 3.85 2.70 0.70 1026 27 22 4.46 2.59 0.58 940 4.31 2.50 0.58 999 4.20 2.44 0.58 1026 4.03 2.33 0.58 1069 27 24 4.69 2.16 0.46 983 4.52 2.08 0.46 1037 4.41 2.03 0.46 1069 4.27 1.96 0.46 1123 27 26 4.83 1.64 0.34 1037 4.69 1.59 0.34 1091 4.62 1.57 0.34 1123 4.48 1.52 0.34 1156 28 18 4.11 3.54 0.86 864 3.94 3.39 0.86 907 3.78 3.25 0.86 950 3.64 3.13 0.86 994 28 20 4.29 3.17 0.74 907 4.11 3.04 0.74 961 3.99 2.95 0.74 983 3.85 2.85 0.74 1026 28 22 4.46 2.77 0.62 940 4.31 2.67 0.62 999 4.20 2.60 0.62 1026 4.03 2.50 0.62 1069 28 24 4.69 2.35 0.50 983 4.52 2.26 0.50 1037 4.41 2.21 0.50 1069 4.27 2.14 0.50 1123 28 26 4.83 1.84 0.38 1037 4.69 1.78 0.38 1091 4.62 1.76 0.38 1123 4.48 1.70 0.38 1156 29 18 4.11 3.70 0.90 864 3.94 3.54 0.90 907 3.78 3.40 0.90 950 3.64 3.28 0.90 994 29 20 4.29 3.34 0.78 907 4.11 3.21 0.78 961 3.99 3.11 0.78 983 3.85 3.00 0.78 1026 29 22 4.46 2.95 0.66 940 4.31 2.84 0.66 999 4.20 2.77 0.66 1026 4.03 2.66 0.66 1069 29 24 4.69 2.53 0.54 983 4.52 2.44 0.54 1037 4.41 2.38 0.54 1069 4.27 2.31 0.54 1123 29 26 4.83 2.03 0.42 1037 4.69 1.97 0.42 1091 4.62 1.94 0.42 1123 4.48 1.88 0.42 1156 30 18 4.11 3.87 0.94 864 3.94 3.70 0.94 907 3.78 3.55 0.94 950 3.64 3.42 0.94 994 30 20 4.29 3.52 0.82 907 4.11 3.37 0.82 961 3.99 3.27 0.82 983 3.85 3.16 0.82 1026 30 22 4.46 3.12 0.70 940 4.31 3.01 0.70 999 4.20 2.94 0.70 1026 4.03 2.82 0.70 1069 30 24 4.69 2.72 0.58 983 4.52 2.62 0.58 1037 4.41 2.56 0.58 1069 4.27 2.48 0.58 1123 30 26 4.83 2.22 0.46 1037 4.69 2.16 0.46 1091 4.62 2.13 0.46 1123 4.48 2.06 0.46 1156 31 18 4.11 4.03 0.98 864 3.94 3.86 0.98 907 3.78 3.70 0.98 950 3.64 3.57 0.98 994 31 20 4.29 3.69 0.86 907 4.11 3.54 0.86 961 3.99 3.43 0.86 983 3.85 3.31 0.86 1026 31 22 4.46 3.30 0.74 940 4.31 3.19 0.74 999 4.20 3.11 0.74 1026 4.03 2.98 0.74 1069 31 24 4.69 2.91 0.62 983 4.52 2.80 0.62 1037 4.41 2.73 0.62 1069 4.27 2.65 0.62 1123 31 26 4.83 2.42 0.50 1037 4.69 2.35 0.50 1091 4.62 2.31 0.50 1123 4.48 2.24 0.50 1156 32 18 4.11 4.19 1.02 864 3.94 4.02 1.02 907 3.78 3.86 1.02 950 3.64 3.71 1.02 994 32 20 4.29 3.86 0.90 907 4.11 3.70 0.90 961 3.99 3.59 0.90 983 3.85 3.47 0.90 1026 32 22 4.46 3.48 0.78 940 4.31 3.36 0.78 999 4.20 3.28 0.78 1026 4.03 3.14 0.78 1069 32 24 4.69 3.10 0.66 983 4.52 2.98 0.66 1037 4.41 2.91 0.66 1069 4.27 2.82 0.66 1123 32 26 4.83 2.61 0.54 1037 4.69 2.53 0.54 1091 4.62 2.49 0.54 1123 4.48 2.42 0.54 1156
INDOOR INDOOR
CAPACITY:3.5(kW)
INPUT:1080(W)SHF:0.76
21
OUTDOOR DB(:)
25 27 30
WB(:)
Q SHC SHF Q SHC SHF Q SHC SHF Q SHC SHFINPUT INPUT INPUT INPUT
DB(:)
PERFORMANCE DATA COOL operation Rated frequency 88Hz
MUZ-GA35VA MUZ-GA35VAH
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
28
Page 29
PERFORMANCE DATA COOL operation Rated frequency 88Hz
MUZ-GA35VA MUZ-GA35VAH
CAPACITY:3.5(kW)
INDOOR INDOOR
DB (:) WB (:)
21 18 3.43 1.99 0.58 1058 3.15 1.83 0.58 1123 2.91 1.68 0.58 1166 21 20 3.61 1.66 0.46 1102 3.36 1.55 0.46 1156 3.12 1.43 0.46 1220 22 18 3.43 2.13 0.62 1058 3.15 1.95 0.62 1123 2.91 1.80 0.62 1166 22 20 3.61 1.80 0.50 1102 3.36 1.68 0.50 1156 3.12 1.56 0.50 1220 22 22 3.82 1.45 0.38 1145 3.57 1.36 0.38 1210 3.33 1.26 0.38 1253 23 18 3.43 2.26 0.66 1058 3.15 2.08 0.66 1123 2.91 1.92 0.66 1166 23 20 3.61 1.95 0.54 1102 3.36 1.81 0.54 1156 3.12 1.68 0.54 1220 23 22 3.82 1.60 0.42 1145 3.57 1.50 0.42 1210 3.33 1.40 0.42 1253 24 18 3.43 2.40 0.70 1058 3.15 2.21 0.70 1123 2.91 2.03 0.70 1166 24 20 3.61 2.09 0.58 1102 3.36 1.95 0.58 1156 3.12 1.81 0.58 1220 24 22 3.82 1.75 0.46 1145 3.57 1.64 0.46 1210 3.33 1.53 0.46 1253 24 24 4.03 1.37 0.34 1188 3.78 1.29 0.34 1242 3.57 1.21 0.34 1296 25 18 3.43 2.54 0.74 1058 3.15 2.33 0.74 1123 2.91 2.15 0.74 1166 25 20 3.61 2.24 0.62 1102 3.36 2.08 0.62 1156 3.12 1.93 0.62 1220 25 22 3.82 1.91 0.50 1145 3.57 1.79 0.50 1210 3.33 1.66 0.50 1253 25 24 4.03 1.53 0.38 1188 3.78 1.44 0.38 1242 3.57 1.36 0.38 1296 26 18 3.43 2.68 0.78 1058 3.15 2.46 0.78 1123 2.91 2.27 0.78 1166 26 20 3.61 2.38 0.66 1102 3.36 2.22 0.66 1156 3.12 2.06 0.66 1220 26 22 3.82 2.06 0.54 1145 3.57 1.93 0.54 1210 3.33 1.80 0.54 1253 26 24 4.03 1.69 0.42 1188 3.78 1.59 0.42 1242 3.57 1.50 0.42 1296 26 26 4.24 1.27 0.30 1231 3.99 1.20 0.30 1285 3.75 1.12 0.30 1339 27 18 3.43 2.81 0.82 1058 3.15 2.58 0.82 1123 2.91 2.38 0.82 1166 27 20 3.61 2.52 0.70 1102 3.36 2.35 0.70 1156 3.12 2.18 0.70 1220 27 22 3.82 2.21 0.58 1145 3.57 2.07 0.58 1210 3.33 1.93 0.58 1253 27 24 4.03 1.85 0.46 1188 3.78 1.74 0.46 1242 3.57 1.64 0.46 1296 27 26 4.24 1.44 0.34 1231 3.99 1.36 0.34 1285 3.75 1.27 0.34 1339 28 18 3.43 2.95 0.86 1058 3.15 2.71 0.86 1123 2.91 2.50 0.86 1166 28 20 3.61 2.67 0.74 1102 3.36 2.49 0.74 1156 3.12 2.31 0.74 1220 28 22 3.82 2.37 0.62 1145 3.57 2.21 0.62 1210 3.33 2.06 0.62 1253 28 24 4.03 2.01 0.50 1188 3.78 1.89 0.50 1242 3.57 1.79 0.50 1296 28 26 4.24 1.61 0.38 1231 3.99 1.52 0.38 1285 3.75 1.42 0.38 1339 29 18 3.43 3.09 0.90 1058 3.15 2.84 0.90 1123 2.91 2.61 0.90 1166 29 20 3.61 2.81 0.78 1102 3.36 2.62 0.78 1156 3.12 2.43 0.78 1220 29 22 3.82 2.52 0.66 1145 3.57 2.36 0.66 1210 3.33 2.19 0.66 1253 29 24 4.03 2.17 0.54 1188 3.78 2.04 0.54 1242 3.57 1.93 0.54 1296 29 26 4.24 1.78 0.42 1231 3.99 1.68 0.42 1285 3.75 1.57 0.42 1339 30 18 3.43 3.22 0.94 1058 3.15 2.96 0.94 1123 2.91 2.73 0.94 1166 30 20 3.61 2.96 0.82 1102 3.36 2.76 0.82 1156 3.12 2.55 0.82 1220 30 22 3.82 2.67 0.70 1145 3.57 2.50 0.70 1210 3.33 2.33 0.70 1253 30 24 4.03 2.33 0.58 1188 3.78 2.19 0.58 1242 3.57 2.07 0.58 1296 30 26 4.24 1.95 0.46 1231 3.99 1.84 0.46 1285 3.75 1.72 0.46 1339 31 18 3.43 3.36 0.98 1058 3.15 3.09 0.98 1123 2.91 2.85 0.98 1166 31 20 3.61 3.10 0.86 1102 3.36 2.89 0.86 1156 3.12 2.68 0.86 1220 31 22 3.82 2.82 0.74 1145 3.57 2.64 0.74 1210 3.33 2.46 0.74 1253 31 24 4.03 2.50 0.62 1188 3.78 2.34 0.62 1242 3.57 2.21 0.62 1296 31 26 4.24 2.12 0.50 1231 3.99 2.00 0.50 1285 3.75 1.87 0.50 1339 32 18 3.43 3.50 1.02 1058 3.15 3.21 1.02 1123 2.91 2.96 1.02 1166 32 20 3.61 3.24 0.90 1102 3.36 3.02 0.90 1156 3.12 2.80 0.90 1220 32 22 3.82 2.98 0.78 1145 3.57 2.78 0.78 1210 3.33 2.59 0.78 1253 32 24 4.03 2.66 0.66 1188 3.78 2.49 0.66 1242 3.57 2.36 0.66 1296 32 26 4.24 2.29 0.54 1231 3.99 2.15 0.54 1285 3.75 2.02 0.54 1339
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
INPUT:1080(W)SHF:0.76
OUTDOOR DB(:)
35 40 46
29
Page 30
PERFORMANCE DATA HEAT operation
CAPACITY:3.2(kW)
INPUT:760(W)
OUTDOOR WB(:)
INDOOR
-10 -5 0 5 10 15 20
DB(:)
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 2.02 494 2.43 593 2.85 669 3.26 722 3.68 768 4.06 790 4.48 806 21 1.92 532 2.30 631 2.72 699 3.10 752 3.52 790 3.90 813 4.30 844 26 1.73 570 2.14 669 2.53 737 2.94 790 3.36 828 3.74 851 4.16 874
CAPACITY:4.0(kW)
INPUT:1055(W)
OUTDOOR WB(:)
INDOOR
-10 -5 0 5 10 15 20
DB(:)
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 2.52 686 3.04 823 3.56 928 4.08 1002 4.60 1066 5.08 1097 5.60 1118 21 2.40 739 2.88 876 3.40 971 3.88 1044 4.40 1097 4.88 1129 5.38 1171 26 2.16 791 2.68 928 3.16 1023 3.68 1097 4.20 1150 4.68 1182 5.20 1213
MUZ-GA25VA MUZ-GA25VAH Rated frequency 85Hz
MUZ-GA35VA MUZ-GA35VAH Rated frequency 96Hz
NOTE Q:Total capacity (kW) INPUT:Total power input (W) DB : Dry-bulb temperature WB : Wet-bulb temperature
30
Page 31
9
Discharge temperature thermistor Indoor coil temperature thermistor
Defrost thermistor
Fin temperature thermistor Ambient temperature thermistor
Purpose
Protection Cooling : Coil frost prevention Heating : High pressure protection Cooling : High pressure protection Heating : Defrosting
Protection Cooling : Low ambient temperature operation Heating : Defrosting (Heater)
Compressor
LEV
Outdoor
fan motor
Indoor
fan motor
Defrost
heater
Solenoid
valve
R.V. coil
Sensor
Actuator
w1
w1 w1 w1
w1
w2
w1
w1 MUZ-GA35VA
MUZ-GA35VAH
w2 MUZ-GA25VA-
E1 / E2
/
E3 (Serial No. ~6021350T)
MUZ-GA25VAH-
E1 / E2
/
E3 (Serial No. ~7000000T)
ON
OFF
ON
OFF
Outdoor fan motor
Compressor
5 seconds 15 seconds
ON OFF
Compressor
Outdoor fan motor
R.V.coil
ON OFF
ON OFF
<COOL>
5 seconds
<HEAT>
5 seconds
ON or OFF
ON or OFF
ACTUATOR CONTROL
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
9-1. Outdoor fan motor control
The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
9-2. R.V. coil control
Heating
Cooling
Dry
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
ON OFF OFF
9-3. Relation between main sensor and actuator
31
Page 32
10
Jumper wire
Defrost finish temperature
JS
none
(cut)
soldered
(Initial setting)
MUZ-GA35VA
8:
5:
MUZ-GA25VAH MUZ-GA35VAH
MUZ-GA25VA
15:
8:
8:
5:
15:
8:
Housing point
SERVICE FUNCTIONS
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
CHANGE IN DEFROST SETTING
Changing defrost finish temperature
<JS> When the JS wire of the outdoor Inverter P.C. board is cut/ soldered, the defrost finish temperature is changed.
(Refer to 11-7-1.)
11
TROUBLESHOOTING
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
11-1. Cautions on troubleshooting
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.
4) When troubleshooting, refer to 11-2., 11-3. and 11-4.
32
Page 33
11-2. Failure mode recall function
Operational procedure
Yes
(Blinks)
No
(OFF)
Yes
No
Releasing the failure mode recall function
Note1.Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2.If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2. Blinking pattern when the indoor unit is abnormal:
W3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle Repeated cycle
ON
OFF
No beep Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Repeated cycle
Beeps
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the left lamp of OPERATION INDICATOR lamp. W2
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Before blinking, does the left lamp of OPERATION INDICATOR lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the indoor unit failure mode table (Refer to indoor unit service manual.) Make sure to check at least two consecutive blinking cycles. W2
Turn ON the power supply. <
Preparation of the remote controller
>
1 While pressing both OPERATION SELECT
button and TOO COOL button on the remote controller at the same time, press RESET button.
2 First, release RESET button.
And release the other two buttons after all LCD except the set temperature in operation display section of the remote controller is displayed after 3 seconds.
Deleting the memorized abnormal condition
1After repairing the unit, recall the failure mode again according to
"Setting up the failure mode recall function" mentioned above.
2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. 4Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Repair the defective parts.
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Judgment of indoor/outdoor abnormality
Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. W1
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnormalities that can't be recalled with this way. Confirm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function.(Refer to 11-2.2)
The outdoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the outdoor unit failure mode table (Refer to 11-2.3). Make sure to check at least two consecutive blinking cycles. W3
W1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (11-4.) disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
33
Page 34
2. Flow chart of the detailed outdoor unit failure mode recall function
Operational procedure
Note1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized. W2.Blinking pattern when outdoor unit is abnormal:
Yes
(Blinks)
No
(OFF)
ON
OFF
No beep
Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5-
second interval
Repeated cycle
W1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
Does left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the left lamp of OPERATION INDICATOR lamp. W2
Deleting the memorized abnormal condition
1After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above. 2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. 4Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Repair the defective parts.
With the remote controller headed towards the indoor unit, press TOO COOL or TOO WARM button to adjust the set temperature to 25:. W1
The outdoor unit is normal.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
The outdoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the outdoor unit failure mode table (Refer to 11-2.3.). Make sure to check at least two consecutive blinking cycles. W2
Release the failure mode recall function according to the left mentioned procedure.
Confirm that the remote controller is in the failure mode recall function.
The outdoor unit might be abnormal. Confirm if outdoor unit is abnormal according to the following procedures.
34
Page 35
OFF
2-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
5-time flash
2.5 seconds OFF
6-time flash
2.5 seconds OFF
7-time flash
2.5 seconds OFF
8-time flash
2.5 seconds OFF
9-time flash
2.5 seconds OFF
10-time flash
2.5 seconds OFF
11-time flash
2.5 seconds OFF
12-time flash
2.5 seconds OFF
14-time flash
2.5 seconds OFF
None (Normal)
Outdoor power system
Discharge temperature thermistor
Defrost thermistor
Fin temperature thermistor
P.C. board temperature thermistor
Ambient temperature thermistor
Overcurrent
Compressor synchronous abnormality
( Compressor start-up failure
protection)
Discharge temperature
High pressure
Fin temperature/ P.C. board
temperature
Outdoor fan motor
Nonvolatile memory data
Discharge temperature
DC voltage
Each phase current of compressor
Overcurrent
Compressor open-phase
Outdoor unit
(Other abnormality)
1-time flash every
2.5 seconds
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
2-time flash
2.5 seconds OFF
11-time flash
2.5 seconds OFF
12-time flash
2.5 seconds OFF
7-time flash
2.5 seconds OFF
5-time flash
2.5 seconds OFF
8-time flash
2.5 seconds OFF
9-time flash
2.5 seconds OFF
10-time flash
2.5 seconds OFF
When it consecutively occurs 3 times that the compressor
stops for overcurrent protection within 1 minute after start-up.
When thermistor shorts or opens during compressor running.
When 14A(MUZ-GA25VA,MUZ-GA25VAH)/ 24A
(MUZ-GA35VA,MUZ-GA35VAH) current flow into intelligent
power module.
When waveform of compressor current is distorted.
When temperature of discharge temperature thermistor
exceeds 116:, compressor stops. Compressor can restart
if discharge temperature thermistor reads 100: or less
3 minutes later.
When temperature of indoor coil thermistor exceeds 70: in
HEAT mode.
When defrost thermistor exceeds 70: in COOL mode.
When temperature of fin temperature thermistor on the
inverter P.C. board exceeds 82 :(MUZ-GA25VA,
MUZ-GA25VAH)/ 83:(MUZ-GA35VA,MUZ-GA35VAH), or
temperature of P.C. board temperature thermistor on the
inverter P.C. board exceeds 81:(MUZ-GA25VA,
MUZ-GA25VAH)/ 85:(MUZ-GA35VA,MUZ-GA35VAH).
When outdoor fan has stopped 3 times in a row within
30 seconds after outdoor fan start-up.
When nonvolatile memory data cannot be read properly.
When temperature of discharge temperature thermistor has
been 50: or less for 20 minutes.
When DC voltage of inverter cannot be detected normally.
When each phase current of compressor cannot
be detected normally.
When 14A(MUZ-GA25VA,MUZ-GA25VAH)/ 24A
(MUZ-GA35VA,MUZ-GA35VAH) current flow into intelligent
power module (IPM).
When the open-phase operation of compressor is detected.
When the interphase short out
occurs in the output of the intelligent power module (IPM).
When the compressor winding shorts out.
When the inverter P.C. board is defective.
•Reconnect connectors.
•Refer to 11-6.A"How to check
inverter/ compressor".
•Check stop valve.
•Refer to 11-6.G"Check of
outdoor thermistors".
Defective outdoor thermistors
can be identified by checking
the blinking pattern of LED.
•Reconnect compressor connector.
•Refer to 11-6.A"How to check
inverter/ compressor".
•Check stop valve.
•Reconnect compressor connector.
•Refer to 11-6.A"How to check
inverter/ compressor".
•Check refrigerant circuit and
refrigerant amount.
•Refer to 11-6.L"Check of LEV".
•Check refrigerant circuit and
refrigerant amount.
•Check stop valve.
•Check around outdoor unit.
•Check outdoor unit air passage.
•Refer to 11-6.I"Check of
outdoor fan motor".
•Refer to 11-6.I"Check of
outdoor fan motor".
Refer to 11-6.N"Check of inverter
P.C. board".
•Replace the inverter P.C. board.
•Refer to 11-6.L"Check of LEV".
•Check refrigerant circuit and
refrigerant amount.
•Refer to 11-6.A"How to check
inverter/ compressor".
•Reconnect compressor connector.
•Refer to 11-6. A"How to check
inverter/ compressor".
•Replace the inverter P.C. board.
The left lamp of
OPERATION
INDICATOR lamp
(Indoor unit)
Abnormal point
(Failure mode / protection)
Condition Correspondence
Indoor/outdoor
unit failure mode
recall function
Outdoor unit
failure mode
recall function
LED indication
(Outdoor P.C. board)
3. Outdoor unit failure mode table NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-4.).
35
Page 36
Start
Indoor unit operates. Outdoor unit doesn't operate.
Indoor unit doesn't receive the signal from remote controller.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Outdoor unit operates only in Test Run operation. (Refer to 8-3.)
Outdoor unit doesn't operate even in Test Run operation. (Refer to 8-3.)
Indoor unit operates, when EMERGENCY OPERATION switch is pressed.
Indoor unit doesn't operate, when EMERGENCY OPERATION switch is pressed.
Check room temperature thermistor. Refer to "Test point diagram and voltage".
Refer to 11-6.A "How to check inverter/ compressor".
Refer to "Check of remote controller and receiver P.C. board".
1. Check indoor / outdoor connecting wire. (Check if the power is supplied to the indoor unit.)
2. Refer to "Check of indoor electronic control P.C. board and indoor fan motor".
Unit doesn't operate normal operation in COOL or HEAT mode.
Refer to 11-6.H "Check of R.V. coil".
Left lamp Flash on and off at
0.5-second intervals Cause: Indoor/ Outdoor unit
Mis-wiring or trouble of serial signal.
Left
lamp 2-time flash Cause: Indoor unit
Trouble of room temp­ erature/ indoor coil thermistor
Left
lamp 3-time flash Cause: Indoor unit
Trouble of indoor fan motor
Left
lamp 5-time flash Cause: Outdoor unit
Outdoor power system abnormality
Left
lamp 6-time flash Cause: Outdoor unit
Trouble of thermistor in outdoor unit
Left
lamp 7-time flash Cause: Outdoor unit
Trouble of outdoor control system
Refer to 11-6.O "How to check of mis-wiring and serial signal error".
(MUZ-GA25/35)
All lamps Flash on and off at 0.5-second intervals Cause: Indoor unit
The horizontal vane is not installed correctly.
Refer to "Check of installation of the horizontal vane".
Check room temperature thermistor and indoor coil thermis­tor. Refer to "Test point diagram and voltage".
Refer to "Check of indoor fan motor".
Refer to 11-6.A "How to check inverter/ compressor".
Refer to 11-6.G "Check of outdoor thermistors".
Replace inverter P.C. board or out­door control electronic control P.C. board.
Left
lamp 14-time flash Cause: Outdoor unit
Other abnormality
Check 11-2.2. "Flow chart of the detailed outdoor unit failure mode recall function."
Left lamp 4-time flash Cause: Indoor unit
Trouble of indoor unit control system
Replace the indoor electronic control P.C. board.
Refer to indoor unit service manual.
Indoor unit operates. Outdoor unit doesn't operate normally.
If blinking of OPERATION INDICATOR lamp cannot be checked, it can be checked with failure mode recall function.
11-3. Instruction of troubleshooting
36
Page 37
Abnormal point/ Condition
When it consecutively occurs 3 times that the compressor stops for overcurrent protection within 1minute after start-up.
When discharge temperature thermistor, fin temperature thermistor, defrost thermistor, P.C. board temperature thermistor or ambient temperature thermistor shorts or opens during compressor running.
When nonvolatile memory data cannot be read properly. (When
the left lamp of OPERATION INDICATOR lamp
of the indoor unit
lights up or flashes 7-time.)
When 14A(MUZ-GA25VA,MUZ-GA25VAH)/ 24A(MUZ-GA35VA, MUZ-GA35VAH) current flows into intelligent power module.
When temperature of discharge temperature thermistor exceeds 116:, compressor stops. Compressor can restart if discharge temperature thermistor reads 100: or less 3 minutes later.
When temperature of fin temperature thermistor on the heat sink exceeds 82:(MUZ-GA25VA,MUZ-GA25VAH)/ 83: (MUZ-GA35VA,MUZ-GA35VAH) or temperature of P.C. board temperature thermistor on the inverter P.C.board exceeds 81:(MUZ-GA25VA,MUZ-GA25VAH)/ 85:(MUZ-GA35VA, MUZ-GA35VAH).
When indoor coil thermistor exceeds 70: in HEAT mode. When the defrost thermistor exceeds 70: in COOL mode.
When current from power outlet exceeds 5.2A(MUZ-GA25VA, MUZ-GA25VAH)/ 6.1A(MUZ-GA35VA,MUZ-GA35VAH), compressor frequency lowers.
When temperature of indoor coil thermistor exceeds 55: in HEAT mode, compressor frequency lowers.
When indoor coil thermistor reads 8: or less in COOL mode, compressor frequency lowers.
When temperature of discharge temperature thermistor exceeds 111:, compressor frequency lowers.
When temperature of discharge temperature thermistor has been 50: or less for 20 minutes.
No.
1
2
3
6
7
8
9
14
15
16
17
18
Symptom
LED indication
Condition
Correspondence
Outdoor unit does not operate
'Outdoor unit stops and restarts 3 minutes later' is repeated
Outdoor unit operates
Outdoor unit operates
1-time flash every
2.5 seconds
2-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
5-time flash
2.5 seconds OFF
1-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
7-time flash
2.5 seconds OFF
Outdoor power system
Outdoor thermistors
Outdoor control system
Overcurrent protection
Discharge temperature overheat protection
Fin temperature /P.C. board temperature thermistor overheat protection
High pressure protection
Frequency drop by current protection
Frequency drop by high pressure protection
Frequency drop by defrosting in COOL mode
Frequency drop by discharge temperature protection
Low discharge temperature protection
· Check stop valve.
·
Reconnect connector of compressor.
· Refer to 11-6.A "How to check inverter/ compressor".
· Refer to 11-6.G "Check of outdoor thermistors".
· Check stop valve.
·
Reconnect connector of compressor.
· Refer to 11-6.A "How to check
inverter/compressor".
Replace inverter P.C. board.
· Check refrigerant circuit and refrigerant amount.
· Refer to 11-6.L "Check of LEV".
· Check around outdoor unit.
· Check outdoor unit air passage.
· Refer to 11-6.I "Check of outdoor
fan motor".
· Check refrigerant circuit and refrigerant amount.
· Check stop valve.
The unit is normal, but check the following.
· Check if indoor filters are clogged.
· Check if refrigerant is short.
· Check if indoor/outdoor unit air
circulation is short cycled.
· Refer to 11-6.L "Check of LEV".
· Check refrigerant circuit and
refrigerant amount.
Inverter P.C. board (Parts side)
LED
Flashing
Refer to 11-6.O "How to check mis­wiring and serial signal error".
When the communication fails between the indoor and outdoor unit for 3 minutes.
Serial signal
8-time flash
2.5 seconds OFF
Compressor synchronous abnormality
When the waveform of compressor current is distorted.
·
Reconnect connector of compressor.
· Refer to 11-6.A "How to check
inverter/compressor".
8-time flash
2.5 seconds OFF
PAM protection PAM:
Pulse Amplitude Modulation
When the overcurrent flows into IGBT(Insulated Gate Bipolar transistor : TR821) or when the bus-bar voltage reaches 320V or more, PAM stops and restarts.
This is not malfunction. PAM protection will be activated in the following cases; 1Instantaneous power voltage drop (Short time power failure) 2When the power supply voltage is high.
9-time flash
2.5 seconds OFF
Inverter check mode
When the connector of compressor is disconnected, inverter check mode starts.
Check if the connector of the compressor is correctly connected. Refer to 11-6.A "How to check inverter/ compressor".
4
10
19
10-time flash
2.5 seconds OFF
Outdoor fan motor
6-time flash
2.5 seconds OFF
When outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up.
· Refer to 11-6.I "Check of outdoor fan motor".
· Refer to 11-6.N "Check of inverter P.C. board".
11
12
13
12-time flash
2.5 seconds OFF
Each phase current of compressor
When each phase current of compressor cannot be detected normally
· Refer to 11-6.A "How to check inverter/compressor".
13-time flash
2.5 seconds OFF
DC voltage
When DC voltage of inverter cannot be detected normally.
· Refer to 11-6.A "How to check inverter/compressor".
· Check refrigerant circuit and refrigerant amount.
· Refer to 11-6.L "Check of LEV".
· Refer to 11-6.G "Check of
outdoor thermistors".
Refer to 11-2.2. Flow chart of the detailed outdoor unit failure mode recall function.
When outdoor unit is defective.
Outdoor unit (Other abnormality)
5
14-time flash
2.5 seconds OFF
11-4. Troubleshooting check table
NOTE 1. The location of LED is illustrated at the right figure. Refer to 11-7.1.
2. LED is lighted during normal operation.
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the flashing frequency is “2”.
ON OFF
2.5-second OFF
0.5-second ON
2.5-second OFF
37
0.5-second ON
Page 38
11-5. Trouble criterion of main parts
Part name FigureCheck method and criterion
Outdoor fan motor(MF) INNER FUSE (Only MUZ-GA25VA/H) 152i : CUT OFF
0 5
R.V. coil(21S4)
Expansion valve coil(LEV)
MUZ-GA35VA MUZ-GA35VAH
Measure the resistance between the terminals with a tester. (Part temperature –20˚C ~ 40˚C)
WHT – BLK
BLK – RED
RED – WHT
Normal
Measure the resistance between the terminals with a tester. (Part temperature –20˚C ~ 40˚C)
Normal
1.26 k" ~ 1.62 k" 1.20 k" ~ 1.55 k"
WHT – RED RED – ORN
YLW – BRN BRN – BLU
Normal
38 " ~ 50 "
Measure the resistance with a tester. (Part temperature : –20˚C ~ 40˚C)
Color of the lead wire
Color of the lead wire
292 " ~ 374 " 236 " ~ 304 "
31 " ~ 41 " 31 " ~ 41 " 31 " ~ 41 "
Measure the resistance between the terminals with a tester. (Part temperature –20˚C ~ 40˚C)
Compressor(MC)
Defrost heater(H)
Measure the resistance with a tester. (Part temperature –20˚C ~ 40˚C)
Normal
333 " ~ 428 "
Normal
1,220 " ~ 1,580 "
Measure the resistance with a tester. (Part temperature –20˚C ~ 40˚C)
MUZ-GA25VA MUZ-GA25VAH
U-V U-W V-W
Normal
1.28 " ~ 1.66 "
1.58 " ~ 2.03"
MUZ-GA35VA MUZ-GA35VAH
MUZ-GA25VA MUZ-GA25VAH
MUZ-GA35VA MUZ-GA35VAH
MUZ-GA25VA MUZ-GA25VAH
MUZ-GA35VA MUZ-GA35VAH
MUZ-GA25VA MUZ-GA25VAH
23
W
U
V
1
WHT
RED BLK
23
W
U
V
1
WHT
RED BLK
WHT
RED
BLK
FUSE
Solenoid valve coil (21R1)
MUZ-GA25VA-
E1 / E2 /
E3
(Serial No. ~6021350T)
MUZ-GA25VAH- E1 / E2 /
E3
(Serial No. ~7000000T)
MUZ-GA35VA MUZ-GA35VAH
Measure the resistance with a tester.
Refer to 11-7. "Test point diagram and voltage", 1. "Inverter P.C. board", the chart of thermistor.
Refer to 11-7. "Test point diagram and voltage", 1. "Inverter P.C. board", the chart of thermistor.
Discharge temperature thermistor (RT62)
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Defrost thermistor (RT61)
Fin temperature thermistor (RT64)
Ambient temperature thermistor (RT65)
LEV
WHT
6
RED1 ORN4
YLW5
BRN2
BLU3
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
38
Page 39
11-6. Troubleshooting flow
When OPERATION INDICATOR lamp flashes 5-time. Outdoor unit does not operate.
A
How to check inverter/ compressor
Disconnect the connector (CN61) between compressor and the intelligent power module (IPM).
Check the voltage between terminals.
Are the voltages
balanced?
Yes
Check the compressor.
B
Check of open phase
With the connector between the compressor and the intelligent power module disconnected, activate the inverter and check if the inverter is normal by measuring the balance of voltage between the terminals.
Output voltage 115V
<< Operation method>> Start cooling or heating operation by pressing EMERGENCY OPERATION
switch on the indoor unit. (Test run operation : refer to 8-3.)
<<Measurement point>>
at 3 points BLK (U)-WHT (V) BLK (U)-RED (W) WHT(V)-RED (W)
See 11-6.B Check of open phase” .
No
Check the resistance of the intelligent
power module.
See 11-6.D Check of compressor” .
w Measure AC voltage between the lead wires at 3 points.
See 11-6.C 'Check of intelligent power module'.
Is the resistance infinite?
No (0~several
Yes
Replace the inverter P.C. board.
")
Replace the inverter P.C. board and compressor.
Inverter P.C. board (Parts side)
LED
Flashing
NOTE 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of inverter P.C. board flashes 9 times.
C
Check of intelligent power module
Measure the resistance between the terminals on the intelligent
power module. <<Measurement point>> at 6 points BLK-WHT, WHT-BLK BLK-RED, RED-BLK WHT-RED, RED-WHT
<<Judgement>> Infinite ["]···········Normal 0~dozens of ······Abnormal (short)
39
9-time flash
ohmmeter indication
"
X1
"
X1
Normal (infinite)
Abnormal (0~dozens of ")
2.5-second OFF
Page 40
D
Check of compressor
Refer to 11-6.E "Check of compressor winding". Is the compressor normal?
Yes
Refer to 11-6.F "Check of compressor operation time".
Does the compressor operate continuously?
Yes
Ok
E
Check of compressor winding
Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance between the compressor terminals.
<<Measurement point>>
at 3 points BLK-WHT BLK-RED WHT-RED
<<Judgement>>
Refer to 11-5. 0["] ···············Abnormal [short] Infinite["] ·······Abnormal [open] NOTE 1. Be sure to zero the ohmmeter before measurement.
2. Winding resistance for each phase at 20:. Refer to 3.SPECIFICATION.
w Measure the resistance between the lead wires at 3 points.
No
No
Is the compressor operation time more than 10 seconds?
Check the refrigerant circuit.
Replace the compressor.
Yes
No
Replace the compressor.
Check of compressor operation time
F
Connect the compressor and activate the inverter. Then measure the time until the inverter stops due to over current.
<<Operation method>>
Start heating or cooling operation by pressing EMERGENCY OPERATION switch on the indoor unit. (Test run operation : Refer to 8-3.)
<<Measurement>> Measure the time from the start of outdoor fan running to the stop of
compressor due to over current.
<<Judgement>>
For reference 0~10 seconds·····················Abnormal (compressor short or poor contact) (compressor lock-out) 10 seconds~5 minutes·······Abnormal (refrigerant circuit defect) more than 5 minutes···········Normal
40
0 second
10 seconds
5 minutes
Outdoor fan starts Abnormal (Compressor winding short or layer short) (Compressor connector poor contact) (Compressor lock-out)
Abnormal (Refrigerant circuit defect, etc.)
Normal
Page 41
When OPERATION INDICATOR lamp flashes 6-time. The thermistors in the outdoor unit are abnormal.
G
Check of outdoor thermistors
Defrost thermistor RT61
Measure the resistance between CN641 1 and 2.
Discharge temperature thermistor RT62
Measure the resistance between CN641 3 and 4.
Fin temperature thermistor RT64
Measure the resistance between CN642 1 and 2.
Ambient temperature thermistor RT65
Measure the resistance between CN643 1 and 2.
Check of R.V. coil
H
Disconnect the connectors CN641, CN642 and CN643 from the inverter P.C. board.
(Check the characteristics of each thermistor.)
Replace the inverter
P.C. board.
No
Does the unit operate 10 minutes or more?
Yes
OK. (Cause is poor contact.)
Is the resistance of thermistor normal? (Refer to 11-7.1.)
No
Replace the thermistor except RT64. In case that RT64 is abnormal, replace the inverter P.C. board, since RT64 is combined with the inverter P.C. board.
Reconnect the connectors CN641, CN642 and CN643. Turn ON the
Yes
power supply and press EMERGENCY OPERATION switch.
w First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-5. w In case CN721 is not connected or R.V. coil is open, voltage is generated between the
terminal pins of the connector although any signal is not being transmitted to R.V. coil. Check if CN721 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector (CN61) between the compressor and intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Is there 230V AC between CN7211 and 2 on the power P.C.board 3 minutes after the power supply is turned ON?
Yes
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector (CN61) between the compressor and the intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
Is there 230V AC between CN7211 and 2 on the power P.C. board 3 minutes after the power supply is turned ON?
No
Replace the 4-way valve.
No
Power P.C. board (Soldered side)
Yes
Replace the power P.C. board.
CN721
Replace the power P.C. board.
41
Page 42
Outdoor fan motor does not operate.
Replace the outdoor fan motor.
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit light up?
Is the resistance of fan motor normal?
3 minutes after, is there voltage 230V AC between CN771 2 and 3 on the power P.C. board?
Disconnect the connector CN771 on the power P.C. board. Disconnect the connector (CN61) between compressor and power transistor module. Turn ON the power supply and press the EMERGENCY OPERATION switch.
Yes
Yes
No
Check the resistance of fan motor. (Refer to 11-5.)
Replace the power P.C. board.
No
Replace the outdoor fan motor.
I
Check of outdoor fan motor
MUZ-GA25VA MUZ-GA25VAH
42
Page 43
Outdoor fan motor does not operate.
Disconnect the connector (CN61) between compressor and intelligent power module. Turn ON power supply and press EMERGENCY OPERATION switch.
Check the electric parts in main circuit.
If light up,ok. If flash, refer to 11-4.
Is there voltage 280V ~ 370V DC between DB61 (+) and DB61 (–) on the inverter P.C. board? (Refer to 11-7.1.)
Dose LED on the inverter P.C. board light up or flash? (Refer to 11-7.1.)
Yes
Yes
Yes
No
No
Replace the indoor
electronic control P.C. board.
No
Yes
No
Replace the inverter P.C. board.
DB61
280V~370V DC
Inverter P.C. board (Solder side)
Is there voltage 230V AC
between the indoor terminal block S1 and S2?
Rectify indoor/ outdoor connecting wire.
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit light up?
Does the voltage between each terminal repeat 5V and 0V DC by turns?
Does the outdoor fan rotate smoothly?
Check the inverter P.C. board. (Refer to 11-6. N)
No
Yes
Yes
( Fixed to either 5V or 0V DC)
Yes
No
Rotate the outdoor fan slowly by hand, and measure the voltage of CN931 (Measurement of feedback output). Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-)
Is the resistance between each terminal of outdoor fan motor normal? (Refer to 11-5.)
Disconnect CN932 from the inverter P.C. board.
Replace the outdoor fan motor.
CN931
CN932
Inverter P.C. board (Solder side)
Turn ON the power supply.
No
I
Check of outdoor fan motor
MUZ-GA35VA MUZ-GA35VAH
Inverter does not operate.
Check of power supply
J
43
Page 44
Outdoor unit does not operate at all, or stops immediately due to overcurrent.
Check other electric parts in the main circuit together in the case that the current-limiting resistor is defective.
Turn ON the power supply and press EMERGENCY OPERATION switch.
Replace the inverter P.C. board or the compressor.
Replace the power P.C. board or the inverter P.C. board.
Does the rush current limiting relay(X64) work properly? (Normally it closes 1 second after outdoor unit power ON.)
No
Yes
No
No
Yes
Yes
Is the resistance of current-limiting resistor (R64A or R64B) on the power P.C. board normal? (Normal resistance : 5' i5%)
Replace the power P.C.board.
Replace the power P.C. board.
Does LED on the inverter P.C. board light up?
Replace the LEV.
Expansion valve operates in full-opening direction.
Is LEV properly fixed to the expansion valve?
Ok
Do you hear the expansion valve "click, click·······"? Do you feel the expansion valve vibrate on touching it ?
Does the resistance of LEV have the characteristics? (Refer to 11-5.)
Measure each voltage between connector pins of CN724 on the inverter P.C. board.
1.Pin3(-) Pin1(+)
2.Pin4(-) Pin1(+)
3.Pin5(-) Pin1(+)
4.Pin6(-) Pin1(+) Is there about 3~5V AC between each? NOTE: Measure the voltage by an analog tester.
No
Yes
Yes
Yes
No
Replace the expansion valve.
Yes
No
No
Properly fix the LEV to the expansion valve.
Replace the inverter P.C. board.
NOTE : After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn ON it again.
2. Press RESET button on the remote controller.
W1. Regardless of normal or abnormal, a short beep is emitted once as the signal is received.
Turn ON the power supply. <
Preparation of the remote controller
> 1 While pressing both OPERATION SELECT button and TOO COOL button on the remote
controller at the same time, press RESET button. 2 First, release RESET button. And release the other two buttons after all LCD
except the set temperature in operation display
section of the remote controller is displayed after
3 seconds.
Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. W1
Check of current-limiting resistor
K
When the current-limiting resistor is open, the rush current limiting relay (X64) may not work properly.
Heating/Cooling does not work sufficiently.
Check of LEV (Expansion valve)
L
44
Page 45
Replace the inverter P.C. board.
Is there 230V AC between CN722 1 and 3 on the power P.C. board? Refer to 11-7.2.
Yes
No
No problem of the power P.C. board.
Is the voltage between CN726 2(+)-3(-) on the power P.C. board 0V DC? Refer to 11-7.2.
Yes
No
Replace the power P.C. board.
NOTE: In case both thermistors are more than the above temperature, cool them with cold water etc...
In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read 5: or less, and let the defrost thermistor continue to read -1: or less.
3 2 1
230V AC
Check the following points before checking electric continuity.
1) Does the resistance of ambient temperature thermistor have the characteristics? Refer to 11-7.1.
2) Is the resistance of defrost heater normal? Refer to 11-5.
3) Does the heater protector remain conducted (not open)?
4) Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors?
26H
CN726
CN722
H
2
1
2
1
23
Outdoor base gets frozen.
Outdoor fan motor does not operate, or stops immediately after starting up.
Replace the inverter P.C. board.
CN931
CN932
Inverter P.C.board (Solder side)
Check the outdoor fan motor. Refer to11-6.I.
Yes (10-time flash)
Check the LED indication on the inverter P.C. board. Does the LED flash 10-time?
No
Check the corresponding parts following LED indication. (Refer to 11-4.)
Operate the outdoor unit by starting
EMERGENCY OPERATION.
Check the connection of the connectors (CN931, CN932) of outdoor fan motor. If the connection is poor, make it correct.
Check of defrost heater
M
Check of inverter P.C. board
N
MUZ-GA35VA
<MUZ-GA25VAH MUZ-GA35VAH>
MUZ-GA35VAH
45
Page 46
Check of inverter P.C. board
Outdoor fan motor does not operate, or stops immediately after starting up.
Yes (10-time flash)
Yes
Check the LED indication on the inverter P.C. board. Does the LED flash 10-time?
No
No
Is the fuse (F901) blown on the inverter P.C. board?
Replace the inverter P.C. board.
CN931
CN932
Inverter P.C.board (Solder side)
Check the corresponding parts following LED indication. (Refer to 11-4.)
Operate the outdoor unit by starting EMERGENCY OPERATION.
Check the connection of the connectors. (CN931, CN932) of outdoor fan motor. If the connection is poor, make it correct.
Check the outdoor fan motor. (Refer to11-6.I.)
N
MUZ-GA35VA MUZ-GA35VAH
ww
Alternative inverter P.C. board
46
Page 47
• When unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch.
Is there rated voltage in the power supply?
Is there any mis-wiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire?
W1. Mis-wiring may damage indoor electronic control P.C. board during the operation. Be sure to confirm the wiring is correct before the operation starts. W3.Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C.board is normal, LED blinks 6 times after 3 minutes.
(Lighted or not lighted)
No
Yes
No
Yes
Yes
No
Yes
No
Yes
W2 Be careful to the residual voltage of smoothing capacitor.
Be sure to release the failure-mode recall function after checking.
No
No
Yes
No
Yes
Yes
Yes
No
Yes
Refer to indoor unit service manual.
Inverter P.C.board (Parts side)
LED
Blinking
Turn OFF the power supply.
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Does the left lamp of OPERATION INDICATOR lamp light up? <Confirmation of the power to the indoor unit>
Press EMERGENCY OPERATION switch once.
Check the power supply.
A
Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not mis-wiring.
Short-circuit outdoor terminal block S2 and S3. W1
B
Turn ON the power supply.
Check the wiring.
Correct them .
Turn OFF the power supply. Remove the short-circuit between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20V DC between outdoor terminal block S2 and S3? <Confirmation of serial signal>
Is there rated voltage between indoor terminal block S1 and S2? <Confirmation of power voltage>
Replace the indoor electronic control P.C. board.
Replace the inverter P.C. board or the outdoor electronic control P.C.board. W2
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
Replace the indoor/outdoor connecting wire.
Replace the indoor/outdoor connecting wire.
Is serial signal error indicated 6 minutes later?
Yes
No
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON again.
· Press EMERGENCY OPERATION switch.
B
· Reinstall either the unit or the light each other away.
· Attach a filter on remote control receiving section of the indoor unit.
A
Is serial signal error indicated 6 minutes later?
No
Does the LED on the inverter P.C. board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"?
W3
Indoor unit does not operate.
• When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second. Outdoor unit doesn’t operate.
How to check mis-wiring and serial signal error (when outdoor unit does not work)
O
47
Page 48
Do you hear the operation sound (click sound) of the solenoid valve every 5 seconds?
Disconnect CN923 and measure the voltage between CN923 1 and 2 using tester.
Replace the solenoid valve coil.
Are the cords between CN726, CN727 on the outdoor power P.C. board and CN725 on the outdoor inverter P.C. board firmly connected without disconnection or loose connection?
Yes
No
Yes
No
Yes
Yes
No
No
Yes
No
No
Yes
Set the failure mode recall function.(Refer to 11-2.)
The solenoid valve is normal.
Check the ambient temperature thermistor (RT65) in the outdoor unit. (Refer to 11-6.G)
Correct the connection.
Replace the solenoid valve.
Trouble of the solenoid valve or solenoid valve coil.
Are the connectors for solenoid valve coil firmly connected without disconnection or loose connection?
Does it repeat to go 0V and 230VAC at 5 second interval?
Correct the connection.
Measure the voltage between CN725 8(+) and 2(GND) on the inverter P.C. board.
Does it repeat to go 0V and 12VDC at 5 second interval?
Measure the resistance of solenoid valve coil. Is the resistance normal ? (Refer to 11-5)
Replace the inverter P.C. board.
Replace the power P.C. board.
When the cool air does not blow out from the indoor unit in Low Outside Temperature Operation, or the condensed water drops from the indoor unit.
Operation check of the solenoid valve.
P
MUZ-GA25VA- //(Serial No. ~6021350T) MUZ-GA25VAH- //(Serial No. ~7000000T)
E3E2E1
E3E2E1
48
Page 49
Q
Replace or repair the antenna. Replace or repair the coaxial cable.
No
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Is the distance between the antennas and the indoor unit within 3m, or is the distance between the antennas and the outdoor unit within 3m?
Is the distance between the TV sets or radios and the indoor unit within 1m, or is the distance between the TV sets or radios and the outdoor unit within 3m?
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the antenna wiring?
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength or the installation condition (combination of specific conditions such as antennas or wiring). Check the followings before asking for service.
1.Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2.Channel, frequency, broadcast station affected by the electromagnetic noise
3.Channel, frequency, broadcast station unaffected by the electromagnetic noise
4.Layout of ; indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver
5.Electric field intensity of the broadcast station affected by the electromagnetic noise
6.Presence or absence of amplifier such as booster
7.Operation condition of air conditioner when the electromagnetic noise enters in
1)Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2)Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3)After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4)Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
Is the unit earthed?
Earth the unit.
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas.
Electromagnetic noise enters into TV sets or radios
49
Page 50
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature(:)
Ambient temperature thermistor(RT65)
Defrost thermistor(RT61)
Temperature(:)
Discharge temperature thermistor(RT62)
0 102030405060708090100110120
0
100
200
300
400
500
600
700
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature(:)
Fin temperature thermistor(RT64)
Resistance(k")
Resistance(k")
Resistance(k")
11-7. Test point diagram and voltage.
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
1. Inverter P.C. board
Back side of unit
Output to drive compressor (LDV,LDW,LDU)
Smoothing capacitor (C63C)
FUSE (F801)
Smoothing capacitor (C63B)
Smoothing capacitor (C63A)
Rotational frequency
feedback signal of outdoor fan motor
(CN931)
MUZ-GA35VA,MUZ-GA35VAH
DB61 280V ~ 370V DC
(+)
(-)
Jumper wire for change in defrost setting (JS)
Front side of unit
Connecting wire with power P.C. board (CN725)
230V AC DB61
LEV connector (CN724)
Defrost thermistor/RT61
(CN641)
Discharge temperature
thermistor/RT62
(CN641)
(CN643)
(CN642)
Ambient temperature
thermistor /RT65
Fin temperature
thermistor/RT64
Output to drive outdoor fan motor (CN932)
MUZ-GA35VA MUZ-GA35VAH
}
1(+) 2(+) 3(+)
45V 5GND
LED monitor lamp
door communication
(CN601)
Connector for indoor/out-
50
Page 51
11-7. Test point diagram and voltage
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
1. Inverter P.C. board (Alternative)
Back side of unit
DB61 280V ~ 370V DC
(+)
(-)
Output to drive compressor (LDW, LDV, LDU)
230V AC DB61
Smoothing capacitor (C63C)
Smoothing capacitor (C63B)
Smoothing capacitor (C63A)
FUSE(F801) 250V 3.15A
FUSE(F901) 250V 3.15A
LED monitor lamp
fan motor CN931)
1(+) 2(+) 3(+) 45V 5GND
MUZ-GA35VA,MUZ-GA35VAH
Rotational frequency
feedback signal of outdoor
Jumper wire for change in defrost setting (JS)
Front side of unit
Fin temperature thermistor(RT64)
200 180 160 140 120
100
80 60
Resistance(k")
40 20
0
0 1020304050607080
Temperature(:)
Connecting wire with power P.C. board (CN725)
Defrost thermistor(RT61) Ambient temperature thermistor(RT65)
100
90 80 70 60 50 40 30
Resistance(k")
20 10
0
-20 -10 0 10 20 30 40
LEV
(CN641)
connector (CN724)
Temperature(:)
Discharge temperature
thermistor/RT62
(CN641)
Defrost thermistor/RT61
(CN643)
700
600
500
400
300
200
Resistance(k")
100
Ambient temperature
thermistor /RT65
Fin temperature
thermistor/RT64
(CN642)
Output to drive outdoor fan motor
(CN932)
}
MUZ-GA35VA MUZ-GA35V AH
Connector for indoor/ outdoor communication (CN601)
Discharge temperature thermistor(RT62)
0
0 102030405060708090100110120
Temperature(:)
51
Page 52
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
2. Power P.C. board
Back side of unit
MUZ-GA25VA- //(Serial No. ~6021350T) MUZ-GA25VAH- //(Serial No. ~7000000T)
Solenoid valve coil (CN923) 230V AC
E3E2E1
E3E2E1
Varistor (NR63)
Varistor (NR62)
Varistor (NR64)
Front side of unit
230V AC
MUZ-GA25VA MUZ-GA25V AH
Output to drive outdoor Fan motor(CN771) 230V AC
R.V.coil(CN721) 230V AC
Connecting wire with inverter P.C.board (CN726)
FUSE(F71) 250V 3.15A
230V AC
Heater connector (CN722)
}
MUZ-GA25VAH MUZ-GA35VAH
52
Page 53
12
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.
Sleeve
1Slide the sleeve. 2Pull the terminal while
Locking lever
pushing the locking lever.
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
OPERATING PROCEDURE
1. Removing the cabinet
(1) Remove the screw fixing the service panel. (See Photo 2.) (2) Pull down the service panel and remove it. (See Photo 2.) (3)
Disconnect the power supply and indoor/outdoor connecting wire. (4) Remove the screws fixing the top panel. (See Photo 1.) (5) Remove the top panel. (See Photo 1.) (6) Remove the screws fixing the cabinet. (See Photo 1, 2.) (7) Remove the cabinet. (8) Remove the screws fixing the back panel. (9) Remove the back panel. (See Photo 1.)
(2) The terminal with this connector has the locking mechanism.
1Hold the sleeve, and pull out the terminal slowly.
Connector
PHOTOS
Photo 1
Screws of the top panel
Screws of the cabinet
Screws of the top panel
Photo 2
Screws of the cabinet
Screw of the
service panel
Direction to remove
Hooks
Screws of the cabinet
Back panel
Service
panel
53
Page 54
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board and power P.C. board
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the power supply and indoor/outdoor
connecting wire and remove the back panel. (Refer to 1.)
(3) Disconnect the ground wires (See Photo 3.), the lead wire
to the reactor and the following connectors; <Power P.C. board> CN721 (4-way valve) CN771 (Fan motor) MUZ-GA25VA/GA25VAH CN722 (Defrost heater) MUZ-GA25/GA35VAH CN923 (Solenoid valve coil)
E3E2E1
MUZ-GA25VA-
MUZ-GA25VAH­<Inverter P.C. board> CN931,CN932 (Fan motor) MUZ-GA35VA/GA35VAH CN641 (Defrost thermistor and discharge temperature
thermistor) CN643 (Ambient temperature thermistor) CN724 (LEV) MUZ-GA35VA/GA35VAH
(4) Remove the compressor connector (CN61). (5) Remove the screws fixing the relay panel. (See Photo 3.) (6) Remove the inverter assembly. (See Photo 4.) (7) Disconnect all connectors and lead wires on the inverter
P.C. board. (See Photo 4.)
(8) Remove the inverter P.C. board from the inverter assembly. (9) Remove the screw fixing the power P.C. board. (See Photo
4.)
(10)
Disconnect all connectors and lead wires on the power P.C.
board.
(11)
Remove the power P.C. board from the inverter assembly.
//(Serial No. ~6021350T)
E3E2E1
//(Serial No. ~7000000T)
Photo 3
Photo 4
Heat sink
Screws of the relay panel
(Inverter assembly)
Inverter P.C. board
Screws of
the ground wires
Power P.C. board
3. Removing R.V. coil
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the power supply and indoor/outdoor
connecting wire and remove the back panel. (Refer to 1.) (3) Remove the inverter assembly. (Refer to 2.) (4) Remove the R.V. coil. (See Photo 5.)
4. Removing the discharge temperature thermistor and defrost thermistor
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the power supply and indoor/outdoor
connecting wire and remove the back panel. (Refer to 1.) (3) Remove the inverter assembly. (Refer to 2.) (4) Pull out the discharge temperature thermistor from its
holder. (See Photo 5.) (5) Pull out the defrost thermistor from its holder. (See Photo 6.)
Photo 5
Screw of the power P.C. board
R.V. coil
54
Discharge temperature thermistor
Page 55
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the power supply and indoor/outdoor
connecting wire and remove the back panel. (Refer to 1.) (3) Disconnect the connectors for outdoor fan motor. (4) Remove the propeller nut. (5) Remove the propeller. (See Photo 7.) (6) Remove the screws fixing the fan motor. (See Photo 7.) (7) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the power supply and indoor/outdoor
connecting wire and remove the back panel. (Refer to 1.) (3) Remove the inverter assembly. (Refer to 2.) (4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm
(5) Detach the welded part of the suction and the discharge
pipe connected with compressor. (6) Remove the nuts of compressor legs. (7) Remove the compressor. (8) Detach the welded part of pipes connected with 4-way
valve. (See Photo 8.)
2
(0 MPa).
Photo 6
Defrost thermistor
Photo 7
Screws of the outdoor fan motor
55
Propeller
Photo 8
Welded parts of 4-way valve
Page 56
13
PARTS LIST (non-RoHS compliant)
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
13-1. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
24
1
20
22
21
18
19 1723
15
13
1416
10
9
11 12
4
3
2
5
6
7
8
56
Page 57
PARTS LIST (non-RoHS compliant)
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
13-1. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.
Part No.
No.
E02 927 232
1
E02 927 521
2
E02 931 501
3
E02 927 501 E02 927 290
4
E02 928 290 E02 928 900
5
E02 927 900 E02 065 506
6
E02 927 661
7
E02 927 662
8
E02 927 245
9
E02 927 233
10
E02 927 640
11
E02 927 493
12
E02 927 961
13
E02 931 961 E02 928 079
14
E02 928 525
15
E02 928 523
16
E02 838 523
17
E02 927 293
18
E02 928 293 E02 899 515
19
E02 927 515 E02 927 297
20
E02 927 630
21
E02 931 301
22
E02 927 301 E02 840 526
23
E02 840 381
24
E02 927 937 E02 096 936
25
E02 156 936 E02 096 642
26
E02 932 490
27
E02 931 492
28
Part Name
CABINET GRILLE PROPELLER PROPELLER BASE BASE COMPRESSOR COMPRESSOR COMPRESSOR RUBBER SET STOP VALVE (GAS) STOP VALVE (LIQUID) SERVICE PANEL BACK PANEL EXPANSION VALVE EXPANSION VALVE COIL 4-WAY VALVE 4-WAY VALVE THERMO HOLDER CONDENSER WIRE NET CONDENSER NET CONDENSER NET SEPARATOR SEPARATOR MOTOR SUPPORT MOTOR SUPPORT TOP PANEL OUTDOOR HEAT EXCHANGER OUTDOOR FAN MOTOR OUTDOOR FAN MOTOR DEFROST HEATER HEATER PROTECTOR CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE CHECK VALVE SOLENOID VALVE COIL SOLENOID VALVE
Symbol
in Wiring
Diagram
MC MC
LEV
MF MF
H
26H
21R1
MUZ-
GA25VA-
E1
1
1
1
1
1
1
1
1
1
1
3
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Q'ty/unit
MUZ-
GA25VAH-
E1
1
1
1
1
1
1
1
1
1
1
3
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MUZ-
GA35VA-
E1
1
1
1
1
1
1
1
1
1
1
3
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MUZ-
GA35VAH-
E1E2 E2E2 E2
1
1
1
1
1
1
1
1
1
1
3
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks
KNB065FDTH KNB073FDVH 3RUBBERS/SET
{9.52 {6.35
RA6V21­RC0J50-
{3.0{2.0240 {3.0{1.4800 {3.0{1.4500
57
Page 58
REACTOR POWER P.C. BOARD POWER P.C. BOARD POWER P.C. BOARD POWER P.C. BOARD R.V. COIL R.V. COIL THERMISTOR SET AMBIENT TEMPERATURE THERMISTOR FUSE HOLDER FUSE TERMINAL BLOCK TERMINAL BLOCK INVERTER P.C. BOARD INVERTER P.C. BOARD INVERTER P.C. BOARD INVERTER P.C. BOARD INVERTER P.C. BOARD FUSE VARISTOR VARISTOR
E02 838 337 E02 927 444 E02 931 444 E02 928 444 E02 932 444 E02 927 490 E02 928 490 E02 927 306 E02 927 308 E02 735 241 E02 735 382 E02 573 375 E02 927 374 E02 928 451 E02 932 451 E02 B40 451 E02 B41 451 E02 A77 451 E02 127 382 E02 661 385 E02 927 385
1
2
3 4
5 6 7 8 9
10
11 12 13
Symbol
in Wiring
Diagram
Q'ty/unit
DEFROST, DISCHARGE
T20AL250V 3P 3P Including heat sink and RT64 Including heat sink and RT64 Including heat sink and RT64 Including heat sink and RT64 Including heat sink and RT64 T3.15AL250V
Remarks
Part No.
No.
Part Name
L61
21S4 21S4
RT61,RT62
RT65
F61 TB1 TB2
F71,F801,F901
NR62,NR63,NR64
1
1
1 1 1 1 1 1 1 1
1 1 1
1
1
1 1 1 1 1 1 1
1
1 1 1
1 1
1
1 1 1 1 1 1
1
1 1 1
1
1
1
1 1 1 1 1 1
1
1 1 1
1
1
1 1 1 1 1 1 1
1 1 1 1
1
1
1 1 1 1 1 1 1
1
1 1 1
1 1
1
1 1 1 1 1 1
1
1 1 1
1
1
1
1 1 1 1 1 1
1
1 1 1
MUZ-
GA25VA-
E1
MUZ-
GA25VAH-
E1
MUZ-
GA35VA-
E1
MUZ-
GA35VAH-
E1E2 E2 E2 E2
PARTS LIST (non-RoHS compliant)
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
13-2. OUTDOOR UNIT ELECTRICAL PARTS
9
10
8
7
6
1 4
Part numbers that are circled are not shown in the illustration.
2
3
58
5
Page 59
Symbol
in Wiring
Diagram
Q'ty/unit
MUZ-
GA25VA-
Remarks
Parts No. Parts Name
E1
MUZ-
GA35VA-
E1
MUZ-
GA25VA-
E2
MUZ-
GA35VA-
E2
E02 838 704
1
DRAIN SOCKET
No.
1111
PARTS LIST (non-RoHS compliant)
MUZ-GA25VA MUZ-GA35VA 13-3. DRAIN SOCKET
1
MUZ-GA25VA - MUZ-GA35VA ­MUZ-GA25VAH - MUZ-GA35VAH -
13-4. QUICK CLEAN KIT
You can clean the surface of the heat exchanger and line flow fan if you attach QUICK CLEAN KIT to your vacuum cleaner.
2
Parts No. Parts Name
No.
2
E02 927 113
3
E02 927 115
4
E02 927 112
BRUSH NOZZLE UNIVERSAL ADAPTER
43
E1E1
E1E1
heat exchanger
Symbol
in Wiring
Diagram
MUZ-
GA25VA-
E1
1 1 1
Q'ty/unit
MUZ-
GA25VAH-
E1
1 1 1
MUZ-
GA35VA-
E1
1 1 1
MUZ-
GA35VAH-
E1
1 1 1
Remarks
NOTE : Quick clean kit has been removed from model.
E2
59
Page 60
14
RoHS PARTS LIST (RoHS compliant)
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
14-1. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
24
1
20
22
21
18
19 1723
15
13
1416
10
9
11 12
4
3
2
5
6
7
8
60
Page 61
RoHS PARTS LIST (RoHS compliant)
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
14-1. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.
No.
1 2
3
4
5 6
7 8
9 10 11 12
13 14
15 16 17
18
19 20
21 22 23
24
25
26 27
28
Part No.
RoHS
G
E12 927 232
G
E12 927 521
G
E12 931 501
G
E12 927 501
G
E12 927 290
G
E12 928 290
G
E12 928 900
G
E12 927 900
G
E12 065 506
G
E12 927 661
G
E12 927 662
G
E12 927 245
G
E12 927 233
G
E12 927 640
G
E12 927 493
G
E12 927 961
G
E12 931 961
G
E12 928 079
G
E12 928 525
G
E12 928 523
G
E12 838 523
G
E12 927 293
G
E12 928 293
G
E12 899 515
G
E12 927 515
G
E12 927 297
G
E12 927 630
G
E12 931 301
G
E12 927 301
G
E12 840 526
G
E12 840 381
G
E12 927 937
G
E12 096 936
G
E12 156 936
G
E12 642 936
G
E12 096 642
G
E12 B45 642 E12 932 490
G G
E12 931 492
Symbol
Part Name
CABINET GRILLE PROPELLER PROPELLER BASE BASE COMPRESSOR COMPRESSOR COMPRESSOR RUBBER SET STOP VALVE (GAS) STOP VALVE (LIQUID) SERVICE PANEL BACK PANEL EXPANSION VALVE EXPANSION VALVE COIL 4-WAY VALVE 4-WAY VALVE THERMO HOLDER CONDENSER WIRE NET CONDENSER NET CONDENSER NET SEPARATOR SEPARATOR MOTOR SUPPORT MOTOR SUPPORT TOP PANEL OUTDOOR HEAT EXCHANGER OUTDOOR FAN MOTOR OUTDOOR FAN MOTOR DEFROST HEATER HEATER PROTECTOR CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE CHECK VALVE CHECK VALVE SOLENOID VALVE COIL SOLENOID VALVE
in Wiring
Diagram
LEV
26H
21R1
MC MC
MF MF
H
MUZ-
GA25VA-
E2
1
1
1
1
1
1
1
1
1
1
3
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 1
1
1 1
1
1
1
1 1 1
1
1
3 1 1 1 1
1
1 1
1
1 1 1
1
1
1
Q'ty/unit
MUZ-
GA25VAH-
E2
1
1
1
1
1
1
1
1
1
1
3
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 1
1
1 1
1
1
1
GA35VA-
1 1 1
1 1
3 1 1 1 1
1 1 1 1
1 1
1 1 1
1 1
1
1
1
MUZ-
E2
1 1
1 1
1 3 1 1 1 1 1 1 1
1 1
1 1 1
1
1
MUZ-
GA35VAH-
E2E3 E4 E3 E4
1 1
1
1
1 3 1 1 1 1 1 1 1
1 1 1
1
1 1 1
1 1 1 1
Remarks
KNB065FDTH KNB073FDVH 3RUBBERS/SET
{9.52 {6.35
RA6V21­RC0J50-
{3.0{2.0240 {3.0{1.4800 {3.0{1.4500 {3.0{1.4400
61
Page 62
REACTOR POWER P.C. BOARD POWER P.C. BOARD POWER P.C. BOARD POWER P.C. BOARD POWER P.C. BOARD POWER P.C. BOARD R.V. COIL R.V. COIL THERMISTOR SET AMBIENT TEMPERATURE THERMISTOR FUSE HOLDER FUSE TERMINAL BLOCK TERMINAL BLOCK INVERTER P.C. BOARD INVERTER P.C. BOARD INVERTER P.C. BOARD INVERTER P.C. BOARD FUSE VARISTOR VARISTOR
E12 838 337 E12 927 444 E12 931 444 E12 928 444 E12 C01 444 E12 932 444 E12 C02 444 E12 927 490 E12 928 490 E12 927 306 E12 927 308 E12 735 241 E12 735 382 E12 573 375 E12 927 374 E12 A77 451 E12 A79 451 E12 B40 451 E12 B41 451 E12 127 382 E12 661 385 E12 927 385
1
2
3 4
5 6 7 8 9
10
11 12 13
G G G G G G G G G G G G G G G G G G G G G G
Symbol
in Wiring
Diagram
Q'ty/unit
DEFROST, DISCHARGE
T20AL250V 3P 3P Including heat sink and RT64 Including heat sink and RT64 Including heat sink and RT64 Including heat sink and RT64 T3.15AL250V
Remarks
Part No.
No.
Part Name
L61
21S4 21S4
RT61,RT62
RT65
F61 TB1 TB2
F71,F801,F901 NR62,NR63,NR64
1
1
1 1 1 1 1 1 1 1
1 1 1
1
1
1 1 1 1 1 1 1
1
1 1 1
1 1
1
1 1 1 1 1 1
1
1 1 1
1
1
1
1 1 1 1 1 1
1 1 1 1
1
1
1 1 1 1 1 1 1 1
1 1 1
1
1
1 1 1 1 1 1 1
1
1 1 1
1
1
1 1 1 1 1 1 1 1
1 1 1
1
1
1 1 1 1 1 1 1
1
1 1 1
MUZ-
GA25VA-
E2
MUZ-
GA25VAH-
E2
MUZ-
GA35VA-
E2
MUZ-
GA35VAH-
E2E3 E3E4 E4
RoHS
RoHS PARTS LIST (RoHS compliant)
MUZ-GA25VA MUZ-GA35VA MUZ-GA25VAH MUZ-GA35VAH
14-2. OUTDOOR UNIT ELECTRICAL PARTS
9
10
8
7
6
1 4
Part numbers that are circled are not shown in the illustration.
2
3
62
5
Page 63
Symbol
in Wiring
Diagram
Q'ty/unit
MUZ-GA25VA-
Remarks
Parts No. Parts Name
E2
MUZ-
GA35VA-
E2E3 E4
E12 838 704
1G
DRAIN SOCKET
No.
111 1
RoHS
RoHS PARTS LIST (RoHS compliant)
MUZ-GA25VA MUZ-GA35VA 14-3. DRAIN SOCKET
1
63
Page 64
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CC
Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in May 2007. No. OB379 REVISED EDITION-D 6 Distributed in Feb. 2007. No. OB379 REVISED EDITION-C 6 Distributed in May 2006. No. OB379 REVISED EDITION-B 6 Distributed in Jan. 2006. No. OB379 REVISED EDITION-A 6 Distributed in Jan. 2005. No. OB379 6 Made in Japan
New publication, effective May 2007 Specifications subject to change without notice.
Loading...