Mitsubishi OB378C Service Manual

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
INDOOR UNIT
SERVICE MANUAL
Wireless type Models
Revision C:
• 3.SPECIFICATION has been corrected.
Please void OB378 REVISED EDITION-B.
No. OB378
REVISED EDITION-C
MSZ-GA22VA ­MSZ-GA22VA ­MSZ-GA22VA ­MSZ-GA25VA ­MSZ-GA25VA ­MSZ-GA25VA ­MSZ-GA35VA ­MSZ-GA35VA ­MSZ-GA35VA -
E1
E2
E3
E1
E2
E3
E1
E2
E3
Outdoor unit service manual
MUZ-GA·VA Series (OB379) MXZ-A·VA Series (OB377) MXZ-8A140VA1 (OC316)
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································5
4. NOISE CRITERIA CURVES·······························6
5. OUTLINES AND DIMENSIONS·························7
6. WIRING DIAGRAM ············································8
7. REFRIGERANT SYSTEM DIAGRAM················8
10. DISASSEMBLY INSTRUCTIONS·····················24
11. PARTS LIST······················································27
12. RoHS PARTS LIST···········································31
13. OPTIONAL PARTS ···········································34
NOTE:
RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS Parts List.
Revision A:
• MSZ-GA·VA- has been added. Color of BOX and CORNER BOX has been changed to white.
E2
Revision B:
E3
model has been added.
• Failure mode recall function(9-2.) has been changed.
• RoHS PARTS LIST has been added.
Revision C:
• 3.SPECIFICATION has been corrected. Air flow of indoor units connecting to MXZ-8A140VA
1 has been corrected.
1
MSZ-A09YV - MSZ-GA22VA ­MSZ-A09YV - MSZ-GA25VA ­MSZ-A12YV - MSZ-GA35VA -
1. Indication of capacity has been changed.(BTU base kW base)
2. Control method between indoor and outdoor has been changed.
3. Power supply method has been changed (change to supply from outdoor unit).
4. Power supply cord has been removed.
5. Indoor electronic control P.C. board has been changed.
6. Position of terminal block has been changed.
7. Indoor fan motor has been changed. ( AC ➔ DC)
8. Indoor heat exchanger has been changed.
9. The horizontal vane motor unit has been changed. An external gear is added to the generalized stepping motor. The unit is structured so that the driving torque and stopping torque would increase.
10. Air cleaning filer has been removed (available as an optional part).
11. Signal of remote controller has been changed. ( It is not available for the conventional models.)
12. Symbol on terminal block has been changed (to S1/S2/S3).
TECHNICAL CHANGES
E1E1 E1E1 E1E1
NOTE:
Do not remove the vane motor from the motor unit. Do not disassemble the horizontal vane motor unit.
Generalized stepping motor
MSZ-GA22VA- MSZ-GA22VA­MSZ-GA25VA- MSZ-GA25VA­MSZ-GA35VA- MSZ-GA35VA-
1. Color of BOX and CORNER BOX has been changed to white.
MSZ-GA22VA- MSZ-GA22VA­MSZ-GA25VA- MSZ-GA25VA­MSZ-GA35VA- MSZ-GA35VA-
1. The operation of thermo-off-unit has been changed. (When 2 or more indoor units are connected with a multi type outdoor unit, and operated in heat mode.)
E2E1
< , > Indoor fan operates with very Low speed or stops.
E3
< > Indoor fan operates intermittently with very Low speed or stops.
MSZ-GA25VA- MSZ-GA25VA-
1. Indoor fan speed has been changed.
E2E1 E2E1 E2E1
E3E2 E3E2 E3E2
E3E2
2
2
Line flow fan
Air outlet Vertical vane
Air inlet
Display section
Front panel
Panel
Heat exchanger
Horizontal vane
Operation section
(When the front panel is opened)
Remote controller
Remote control receiving section
Catechin air filter
Air cleaning filter (Optional parts,Anti­Allergy Enzyme Filter, Blue bellows type)
Emergency operation switch
Fan guard
Operation Indicator lamp
PART NAMES AND FUNCTIONS
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
3
1 2 3 4 5 6 7
Installation plate Installation plate fixing screw 4 o 25 mm Remote controller holder Fixing screw for 3 3.5 o 1.6 mm (Black) Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping)
1 5 1 2 2 1 1
MSZ-GA22VA
ON-TIMER button
CLOCK SET button
TIME SET buttons FORWARD button BACKWARD button
OFF-TIMER button
(This diagram shows an overall view.)
Open the front lid.
RESET button
VANE CONTROL button
Signal transmitting section
Operation display section
Temperature buttons
OPERATE/STOP (ON/OFF) button
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
Indication of remote controller model is on back
MSZ-GA25VA MSZ-GA35VA
ACCESSORIES
REMOTE CONTROLLER
4
3
T3.15AL 250V
MSBPC20M16 12V DC 250" (at 25˚C)
ERZV14D471
3P
INDOOR UNIT
Item Fuse Horizontal vane motor Varistor Terminal block
(F11)
(MV)
(NR11)
(TB)
MSZ-GA25VA MSZ-GA22VA MSZ-GA35VA
Indoor model
Function
Power supply
1
Single phase
230V,50Hz
630/504 384/258
10
0.25 33 57
0.25
RC0J30-CC
780O298O210
9 4
43
36/29/21
1,250/1,040
830/620
4
KM05B
Single phase
230V,50Hz
10
0.25 33 57
0.25
RC0J30-CC
780O298O210
9 4
43
36/29/21
4
KM05B
43
36/29/21
1,100
43
36/29/22
Cooling
600/480 366/234
1,200/1,000
800/580
2
486/408 336/258
1,010/880
750/620
Cooling
600/480 366/234
1,200/1,000
800/580
Heating
630/504 384/258
1,250/1,040
830/620
Single phase
230V,50Hz
10
0.25 33 57
0.25
RC0J30-CC
780O298O210
9 4
43
36/29/22
4
KM05B
Cooling
600/480 366/246
1,200/1,000
800/600
Heating
630/504 384/270
1,250/1,040
830/640
Air flow(Super High/High) Air flow(Med./Low) Power outlet Running current 1 Power input 1 Power factor 1 Fan motor current 1 Model Dimensions WOHOD Weight Air direction Sound level(Super High) Sound level(High/Med./Low)
Fan speed(Super High/High)
Fan speed(Med./Low) Fan speed regulator
Remote controller model
K /h
A
A W %
A
mm
kg
dB(A) dB(A)
rpm
Electrical
data
Fan motor
Special
remarks
Capacity
MSZ-GA25VA MSZ-GA22VA MSZ-GA35VA
Indoor model
Function
Cooling
528
432/336/234
930/760/580
Heating
540
420/366/258
900/800/620
Cooling
528
432/336/234
930/760/580
Heating
540
420/366/258
900/800/620
Cooling
582
468/354/246
1,200
1,000/800/600
Heating
618
504/390/270
1,230
1,040/850/640
Air flow(Super High) Air flow(High/Med./Low) Sound level(Super High) Sound level(High/Med./Low) Fan speed(Super High) Fan speed(High/Med./Low)
K /h K /h
dB(A) dB(A)
rpm rpm
Special
remarks
Capacity
43
36/29/21
1,100
Heating
1 :
E1 , E2 (serial number : ~ 6024700)
2 :
E2 (serial number : 6024701 ~) , E3
SPECIFICATION
When outdoor unit is MXZ-8A140VA
NOTE : Test conditions are based on ISO 5151
Specifications and rating conditions of main electric parts
Cooling : Indoor Dry-bulb temperature 27:Wet-bulb temperature 19: Heating : Indoor Dry-bulb temperature 20:Wet-bulb temperature 15: Refrigerant piping length (one way): 5m
1 Measured under rated operating frequency.
Outdoor Dry-bulb temperature 35:Wet-bulb temperature 24: Outdoor Dry-bulb temperature 7:Wet-bulb temperature 6:
1.
5
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
43 43
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
INDOOR UNIT
WALL
MICROPHONE
0.8m
1m
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
43 43
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
NOISE CRITERIA CURVES
MSZ-GA22VA MSZ-GA25VA
MSZ-GA35VA
6
5
155 155
335 320
41.5 215
42.5
214
3
287.5
7055
5555 225 225
or more7
100
90
106
298
102624.5
780
210 5
53.5 19
159
58
14273.5
234
Air in
Air out
Wall hole [65
Indoor unit
Installation plate
Installation plate
11X20 Oblong hole
11X26 Oblong hole
10 or more
75 or more
66 or more
W
75 or more
W
In case of left, left back, or
left under piping (using spacer),
115 or more
Insulation [28
Drain hose [16 (Connected part O.D)
Liquid line [6.35-0.5m Gas line [9.52-0.43m Insulation [35 O.D [19 I.D
{
Required space (Indoor unit)
OUTLINES AND DIMENSIONS
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
Unit : mm
7
6
Indoor heat exchanger
Flared connection
Room temperature thermistor RT11
Indoor coil thermistor RT13(sub)
Flared connection
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant pipe [9.52 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
Indoor coil thermistor RT12(main)
SYMBOL
DB111
F11
MF MV
NR11
SYMBOL
RT11 RT12 RT13
T111
TB
NAME DIODE STACK FUSE (T3.15AL250V) INDOOR FAN MOTOR VANE MOTOR (HORIZONTAL) VARISTOR
NAME ROOM TEMPERATURE THERMIST OR INDOOR COIL THERMISTOR (MAIN) INDOOR COIL THERMISTOR (SUB) TRANSFORMER TERMINAL BLOCK
4 3 2 1
S2
POWER MONITOR RECEIVER P.C.BOARD
2
6
230V~
BLU
INDOOR ELECTRONIC CONTROL P.C. BOARD
SW P.C. BOARD
INTERLOCK SWITCH(FAN)
5
MV
TO OUTDOOR UNIT CONNECTING
BLK
RED
S3
TB
TAB3
DB111
NR11
F11
5
6
4
2
2
LD
105(T)
LD
101(A)
12-24V
RT13
1R1
CN
GRN
LD104
CN201
2 1
151
CN
T111
RED
WHT
111
CN
CN
112
CN211
BLU
YLW
BLK
MF
RT11
RT12
1 3 5
S1
WIRING DIAGRAM
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
7
REFRIGERANT SYSTEM DIAGRAM
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
8
Unit : mm
8
No. 1 unit No. 2 unit No. 3 unit No. 4 unit
1 unit operation No modification
– – –
2 units operation
Same as at left
Solder J1
– –
3 units operation
Same as at left Same as at left
Solder J2
4 units operation
Same as at left Same as at left Same as at left
Solder both J1 and J2
SERVICE FUNCTIONS
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
8-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board. The time will be shortened as follows. (Refer to 9-7.) Set time : 1-minute 1-second Set time : 3-minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
NOTE : For modification, take out
the batteries and press the OPERATE/STOP(ON/OFF) button twice or 3 times at first. After finish modification, put back the batteries then press the RESET button.
J1
The P.C. board has the print J1 and J2. Solder J1 and J2 according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
J2
Table 1
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit will only accept the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored.
9
Housing point
JR07
CN151 CN211CN112 CN1R1
BZ
8-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The AUTO RESTART FUNCTION sets to work the moment power has restored after power failure. Then, the unit will restart automatically.
Operation
1
If the main power has been cut, the operation settings remain.
2 After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
How to release AUTO RESTART FUNCTION
1
Turn OFF the main power for the unit.
2Solder the Jumper wire to JR07 on the indoor electronic control P.C. board. (Refer to 9-7.)
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the
remote controller.
If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliance not to turn ON at the
same time.
When some air conditioners are connected to the same supply system, if they are operated before power failure,
the starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.
9
TROUBLESHOOTING
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
9-1. Cautions on troubleshooting
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
10
3. Troubleshooting procedure
RESET button
Insert the negative pole of the batteries first. Check if the polarity of the batteries is correct.
OPERATION INDICATOR
Not lighted
Blinking
Lighted
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing, check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) When troubleshooting, refer to 9-2., 9-3. and 9-4.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally.
1 Remove the front lid and insert batteries.
Then reattach the front lid.
2 Press RESET button with tip end of ball point pen
or the like, and then use the remote controller.
NOTE : 1. If RESET button is not pressed, the remote controller may not operate correctly.
2. This remote controller has a circuit to automatically reset the microcomputer when batteries are replaced. This function is equipped to prevent the microcomputer from malfunctioning due to the voltage drop caused by
the battery replacement.
5. How to install the horizontal vane
If horizontal vane is not installed correctly, all of the operation indicator lamps will blink. In this case, install the horizontal vane correctly by following the procedures 1 to 2.
NOTE: Before installation of the horizontal vane, turn OFF the power supply.
Stopper
21
Left
In procedure stoppers until they click into place.
Lock.
Insert this end first.
INFORMATION FOR MULTI SYSTEM AIR CONDITIONER
OUTDOOR UNIT : MXZ series
Multi system air conditioner can connect two or more indoor units with one outdoor unit.
Unit wont operate in case the total capacity of indoor units exceeds the capacity of outdoor units. Do not connect indoor units beyond the outdoor unit capacity. Operation indicator lamp flashes as shown in the figure below.
When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the other for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units cannot operate, indicating as shown in the figure below. In this case, please set all the indoor units to the same operation mode.
22
lock the
When indoor units starts the operation while the defrosting of outdoor unit is being done, it takes a few minutes (max. 10 minutes) to blow out the warm air.
In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant flowing may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
11