Mitsubishi OB322 Service Manual

Page 1
SERVICE MANUAL
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
Wireless type Models
No. OB322
MUH-A18WV ­MUH-A24WV ­MUH-A30WV -
Indication of model name
MUH-A18WV -
E1
E1
E1
E1
CONTENTS
1. TECHNICAL CHANGES ····································3
2. PART NAMES AND FUNCTIONS······················6
3. SPECIFICATION·················································7
4. NOISE CRITERIA CURVES·······························8
5. OUTLINES AND DIMENSIONS·························9
6. WIRING DIAGRAM ··········································10
7. REFRIGERANT SYSTEM DIAGRAM··············12
8. PERFORMANCE CURVES······························15
9. MICROPROCESSOR CONTROL ····················25
11. TROUBLESHOOTING ······································29
13. PARTS LIST······················································43
NOTE:
•This service manual describes technical data of outdoor unit. As for indoor unit MSH-A18WV- , MSH-A24WV- and MSH-A30V- , refer to the service manual OB321.
E1E1E1
Page 2
Page 3
1
Refrigerating
oil
Refrigerant
New refrigerant
R410A
HFC-32: HFC-125 (50%:50%)
Pseudo-azeotropic refrigerant
Not included
A1/A1
72.6
-51.4
1.557 64
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
Non Non
Previous refrigerant
R22
R22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055 1700
Gas phase
Possible
Compatible oil
Light yellow
Non
Refrigerant Composition (Ratio) Refrigerant handling Chlorine Safety group (ASHRAE) Molecular weight Boiling point (:) Steam pressure [25:](Mpa) Saturated steam density [25:](Kg/K) Combustibility ODP w1 GWP w2 Refrigerant charge method Additional charge on leakage Kind Color Smell
w1:Ozone Destruction Parameter : based on CFC-11 w2 :Global Warmth Parameter : based on CO
2
TECHNICAL CHANGES
MUH-18RV - MUH-A18WV -
1. Refrigerant has changed. (R22➔R410A)
2. Refrigerant system diagram has changed.
• Compressor, stop valve and 4-way valve have changed.
• Diameter of stop valve has changed. (Gas: [15.88[12.7)
• Accumulator has removed and high pressure receiver has been added.
3. Oil separator has been added.
MUH-24RV - MUH-A24WV -
1. Dimension of outdoor unit has changed.
2. Refrigerant has changed. (R22➔R410A)
3. Refrigerant system diagram has changed.
• Diameter of stop valve has changed. (Liquid: [9.52[6.35)
• Accumulator has removed and high pressure receiver has been added.
MUH-30RV - MUH-A30WV -
1. Dimension of outdoor unit has changed.
2. Refrigerant has changed. (R22➔R410A)
3. Refrigerant system diagram has changed.
• Accumulator has removed and high pressure receiver has been added.
E1E2
E1E1
E1E1
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
• This room air conditioner adopts an HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 conditioners. 1 As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/
materials are required. Refer to the table below.
2 Take sufficient care not to allow water and other contaminations to enter the R410Arefrigerant during storage and
installation, since it is more susceptible to contaminations than R22.
3 For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant
piping.)
4 Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
3
Page 4
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
New Specification Current Specification
The incompatible refrigerating oil easily separates from refrigerant and is in the upper layer inside the suction muffler. Raising position of the oil back hole enables to back the refrigerating oil of the upper layer to flow back to the compressor.
Since refrigerant and refrigerating oil are compatible each, refrigerating oil backs to the compressor through the lower position oil back hole.
Compressor
Suction muffler
Oil back hole
Refrigerating oil
Refrigerant
Compressor
Suction muffler
Oil back hole
Refrigerating oil /Refrigerant
Compressor
-30 -20 -10 0 10 20
30
40 50 60
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
(MPa [Gauge])
R410A R22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
(:)
R410A tools Can R22 tools be used?
Gas leak detector
R410A has high pressures beyond the measurement range of existing gauges. Port diameters have been changed to prevent any other refrigerant from being charged into the unit.
Hose material and cap size have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant.
6.35 mm and 9.52 mm
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool. Provided for flaring work (to be used with R22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use vacuum pumps.
It is difficult to measure R410A with a charging cylinder because the refrigerant bubbles due to high pressure and high-speed vaporization
No
No
No
Yes
Yes
New
New
New
Gauge manifold
Charge hose
Torque wrench
Flare tool Flare gauge
Vacuum pump adapter
Electronic scale for refrigerant charging
No : Not Substitutable for R410A Yes : Substitutable for R410A
No 12.7 mm and 15.88 mm
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
NOTE : The unit of pressure has been changed to MPa on the
international system of units(SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
1.Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools. The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
4
Page 5
2.Refrigerant piping
Wall thickness
Outside diameter
Pipe
mm
For liquid
For gas
6.35
9.52
12.7
15.88
0.8 mm
0.8 mm
0.8 mm
1.0 mm
Heat resisting foam plastic Specific gravity 0.045 Thickness 8 mm
Insulation material
1 Specifications
Use the refrigerant pipes that meet the following specifications.
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm (6.35, 9.52, 12.7), 1.0 mm (15.88). Never use any pipe with a thickness less than 0.8 mm (6.35, 9.52, 12.7), 1.0 mm (15.88), as the pressure resistance is insufficient.
2 Flaring work and flare nut
Flaring work for R410A pipe differs from that for R22 pipe. For details of flaring work, refer to Installation manual “FLARING WORK”.
Pipe diameter
mm
6.35
9.52
12.7
15.88
Dimension of flare nut
R410A
17 22 26 29
R22
17 22 24 27
3.Refrigerant oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4.Air purge
• Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant
circuit.
• Use the vacuum pump for air purging for the purpose of environmental protection.
5.Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
Union
Stop valve
Indoor unit
Refrigerant gas cylinder operating valve
Liquid pipe Gas pipe
Service port
Outdoor unit
Gauge manifold valve (for R410A)
Charge hose (for R410A)
Refrigerant gas cylinder for R410A with siphon
Refrigerant (liquid)
Electronic scale for refrigerant charging
5
Page 6
2
Drainage hose
Piping
Air inlet
Air inlet
Air outlet
Drain outlet
(back and side)
Air outlet
(back and side)
1
2
Drain socket Drain cap {33 Drain cap {16
1 2
1 2 1
MUH-A18WV-
E1
MUH-A24WV­MUH-A30WV-
E1 E1
PART NAMES AND FUNCTIONS
OUTDOOR UNIT
MUH-A18WV -
ACCESSORIES
Outdoor unit
E1
MUH-A24WV ­MUH-A30WV -
E1 E1
6
Page 7
3
Outdoor model
Function
Power supply
Capacity Dehumidification Air flow(High/Low ) Starting current Compressor motor current Fan motor current
Model Output Winding resistance(at20:) Model Winding resistance(at20:) Dimensions WOHOD Weight Sound level(High) Fan speed(High/Low ) Fan speed regulator Refrigerant filling capacity(R410A) Refrigerating oil (Model) Thermistor RT61(at0:) Thermistor RT62(at25:) Thermistor RT63(at0:)
kW
R/h
K /h
A A A
W
"
"
mm
kg
dB
rpm
kg cc
k" k" k"
MUH-A30WV -
E1
Single phase
230V, 50Hz
90
0.57
NN37VAAHT
2,500 C-R 0.64 C-S 1.63
RA6V75-AB
WHT-BLK 62.8 BLK-YLW 55.9
YLW-RED 26.0
840o850o330
77 55
805/435
2
2.30
1,300 (NEO 22)
33.18
231.44
33.18
Cooling
8.5
4.6
2,940/1,470
13.85
2.52-2.40
Heating
9.4 —
2,940/1,470
14.62
2.73-2.70
Electrical
data
Compressor
Fan
motor
Special
remarks
Coefficient of performance(C.O.P)
Capacity
www
w
w
Outdoor model
Function
Power supply
Capacity Dehumidification Air flow(High) Starting current Compressor motor current Fan motor current
Model Output Winding resistance(at20:) Model Winding resistance(at20:) Dimensions WOHOD Weight Sound level(High) Fan speed(High) Fan speed regulator Refrigerant filling capacity(R410A) Refrigerating oil (Model) Thermistor RT61(at0:)
kW
r/h
K /h
A A A
W
"
"
mm
kg
dB
rpm
kg cc
k"
MUH-A18WV -
E1
Single phase
230V, 50Hz
2,196
37
0.39
RN196VHSHT
1,300 C-R 1.80 C-S 3.00
RA6V50-OG
WHT-BLK 116
BLK-RED 111 850o605o290
47 52
828
1
1.75
520 (NEO22)
33.18
Cooling
5.0
2.5
7.54
2.81
Heating
5.2 —
6.84
3.23
MUH-A24WV -
E1
Single phase
230V, 50Hz
2,760
74
0.58
NN29VBAHT
1,900 C-R 0.80 C-S 1.64
RA6V85-AB
WHT-BLK 63 BLK-YLW 30
YLW-RED 63
840o850o330
74 53
730
1
2.15
1,200 (NEO22)
33.18
Cooling
6.3
3.2
9.81
2.61
Heating
7.2 —
10.12
2.90
Electrical
data
Compressor
Fan
motor
Special
remarks
Coefficient of performance(C.O.P)
Capacity
SPECIFICATION
NOTE: Test conditions are based on JIS C 9612.
w Reference value
Cooling : Indoor DB27°C WB19°C Heating : Indoor DB20°C WB 15.5°C
Outdoor DB35°C WB(24°C) Outdoor DB 7°C WB 6°C
Indoor-Outdoor piping length 5m
7
Page 8
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
52
SPL(dB(A)) LINE
High
FAN SPEED
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
53
SPL(dB(A)) LINE
High
FAN SPEED
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
NOISE CRITERIA CURVES
MUH-A18WV-
E1
MUH-A24WV-
E1
MUH-A30WV-
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
90
80
E1
FAN SPEED
SPL(dB(A)) LINE
High
55
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
OUTDOORUNIT
1m
MICROPHONE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
8
Page 9
5
OUTLINES AND DIMENSIONS
MUH-A18WV-
E1
OUTDOOR UNIT
Drainage hole [16.2
35
90
248
Air in
Drainage 3holes [33
605
292
20
355
350
Air in
Air out
183
500 850
20
50
74
157
290
30
100
310
345
100mm or more
161
500mm or more
Service panel
Liquid refrigerant pipe joint
Refregerant pipe (flared) [6.35
35-
30-
Gas refregerant pipe joint
Refregerant pipe (flared) [12.7
100mm or more
100mm or more
Unit: mm
350mm or more
MUH-A24WV- MUH-A30WV-
OUTDOOR UNIT
515
299
66
51
34
330
500 840
121
850
430
40
E1E1
Open as a rule 500mm or more if the front and both sides are open
100mm or more 200mm or more if
100mm or more
there are obstacles to both sides
360
Open as a rule 500mm or more if the back, both sides and top are open
80
350mm or more
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared) [6.35 (MUH-A24WV)
[9.52 (MUH-A30WV)
30-
35-
155
90
Gas refrigerant pipe joint
198
Refrigerant pipe (flared) [15.88
9
Page 10
6
WIRING DIAGRAM
MUH-A18WV -
OUTDOOR UNIT
TO INDOOR UNIT CONNECTING 12V
POWER SUPPLY
~ /N
50Hz
230V
SYMBOL
C1
C65
DSAR
F61
MC
NOTES:
COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE (2A) COMPRESOR (INNER PROTECTOR)
1.About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate. : Terminal block
E1
MODEL WIRING DIAGRAM
TB2
3
RED
N
BLK
TB1
CIRCUIT BREAKER
BRN
L
BRN
N
BLU
PE
GRN/YLW
NAME
: Connector
SYMBOL
MF NR61 RT61
SR61,SR62
T61
RT61
21S4
1 2 3
CN661
CN730
CN721
SR62
SR61
CN711
1 2 3
DSAR
BLU
OUTDOOR FAN MOTOR (INNER PROTECTOR) VARISTOR DEFROST THERMISTOR SOLID STATE RELAY TRANSFORMER
F61
TAB20
NAME
T61
52C
4
NR61
3
DEICER P.C.BOARD
C1
WHT
RED
BLK
SYMBOL TB1,TB2
21S4
52C
C65
C
MC
S
TERMINAL BLOCK R.V. COIL COMPRESSOR CONTACTOR
WHT
BLK RED
R
MF
WHT
BLK
RED
ORN
1
4
23
NAME
VG79B553H01
MUH-A24WV -
OUTDOOR UNIT
CIRCUIT BREAKER
~ /N 230V 50Hz
POWER SUPPLY
12V
TO INDOOR UNIT CONNECTING
TB1
L N
PE
TB2
3
N
NOTES:
E1
MODEL WIRING DIAGRAM
RT61
BRN
DSAR
CN661
X52X62
GRN/YLW
BLU
BLU
1.Use copper conductors only (For field wiring).
2.Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers (3,N).
3.Symbols below indicate. : Terminal block, : Connector
BLU
BRN
DEICER P.C. BOARD
BRN
3
52C
4
SR61
T61
A1 A2
WHT
52C
YLW
YLW
123
NR61
MF
BLK
BLK
C1
WHT
3456
WHT
CN711
X62
X52
ORN
RED
21
COM
COM
CN730
F61
RED
BLK
RED
ORN
C2
CN721
NO
TAB52
NO
MC
S
SYMBOL
C1 C2
DSAR
1 2
21S4
3
F61
MC MF
7 5 3 1
NR61 RT61 SR61
TB1 TB2
C
R
T61 X52 X62
BLU
RED
BLU
21S4
52C
COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE (3.15A) COMPRESSOR (INNER PROTECTOR) OUTDOOR FAN MOTOR (INNER PROTECTOR) VARISTOR DEFROST THERMISTOR SOLID STATE RELAY TERMINAL BLOCK TERMINAL BLOCK TRANSFORMER CONTACTOR R. V. COIL RELAY R. V. COIL COMPRESSOR CONTACTOR
NAME
SG79J883H01
10
Page 11
MUH-A30WV -
OUTDOOR UNIT
E1
MODEL WIRING DIAGRAM
BRN
CIRCUIT BREAKER
TB1
L
DSAR
N
PE
~ /N 230V 50Hz
POWER SUPPLY
GRN/YLW
BLU
TB2
3
BRN
N
BLU
12V
TO INDOOR UNIT CONNECTING
BLU
RT61
CN661
DEICER PC BOARD
BRN
1
52C
CZ
RT62RT63
CN662
X52X62
2
WHTWHT
LEV
6
CN724
SR62 SR61
T61
NR61
WHT
A1 A2
52C
MF
YLW
BLK
WHT
ORN
RED
21
3456
RED
ORN
CN721
NO
TAB52
NO
CN730
F61
C2
1 2 3
7 5 3 1
21S4
YLW
BLK
WHT
3
1
2
CN711
X62
COM
X52
COM
C
C1
RED
BLK
MC
S
R
BLU
RED
BLU
SYMBOL
CZ C1 C2
DSAR
F61
LEV
MC
NOTE 1. Use copper conductors only (For field wiring).
CZ SURGE ABSRBER COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE(3.15A) EXPANSION VALVE COIL COMPRESSOR (INNER PROTECTOR)
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers (3,N).
3. Symbols below indicate.
/: Terminal block, : Connector
NAME
SYMBOL
MF
NR61
RT61 RT62
RT63 SR61 SR62
OUTDOOR FAN MOTOR (INNER PROTECTOR) VARISTOR DEFROST THERMISTOR DISCHARGE TEMPERATURE THERMIST OR AMBIENT TEMPERA TURE THERMIST OR SOLID STATE RELAY SOLID STATE RELAY
NAME NAME
SYMBOL
TB1 TB2 T61 X52 X62
21S4
52C
TERMINAL BLOCK TERMINAL BLOCK TRANSFORMER CONTACTOR R.V. COIL RELAY R.V. COIL COMPRESSOR CONTACTOR
SG79J882H01
11
Page 12
7
REFRIGERANT SYSTEM DIAGRAM
MUH-A18WV -
OUTDOOR UNIT
E1
Refrigerant pipe [12.7 (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe[6.35 (with heat insulator)
Stop valve (with service port)
Capillary tube
[2.5o[0.6o1,000
Receiver
Stop valve
Strainer
4- way valve
Capillary tube
[3.0o[1.6o450
#100
Compressor
Check valve
Oil separator #100
Defrost thermistor RT61
Capillary tube
[3.0o[1.6o300 Refrigerant flow in cooling Refrigerant flow in heating
Outdoor heat exchanger
Capillary tube
[3.0o[1.6o750
(2 pcs)
R.V. coil Heating ON Cooling OFF
Unit:mm
MUH-A24WV -
OUTDOOR UNIT
E1
Refrigerant pipe [15.88 (with heat insulator)
Flared connection
Flared connection
Stop valve
Refrigerant pipe [6.35 (with heat insulator)
Stop valve (with service port)
Muffler
Receiver
Strainer
#100
4- way valve
Capillary tube
[3.0X[2.0X550
Check valve
Muffler
#100
Compressor
Capillary tube [3.0X[2.0X650
Refrigerant flow in cooling Refrigerant flow in heating
Outdoor heat exchanger
Defrost thermistor RT61
R.V. coil Heating ON Cooling OFF
12
Page 13
MUH-A30WV -
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube [3.6[2.450
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe [15.88 (with heat insulator)
Refrigerant pipe [9.52 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Muffler
#100
Strainer
#100
Receiver
Muffler
Ambient temperature thermistor RT63
Strainer
#100
Indoor unit
wMax. Height
difference: 10m(MSH-A18/A24WV)/ 15m(MSH-A30WV)
A
Refrigerant Piping Max. Length
w Height difference should be within 10m(MSH-A18/A24WV)/ 15m(MSH-A30WV) regardless of which unit, indoor or outdoor position is high.
Outdoor unit
Model
Piping size O.D : mm Length of connecting pipe : m
Refrigerant piping
Max. length : m
A
25
30
Indoor unit
Gas 0.43
Liquid 0.5
Gas
12.7
15.88
Liquid
6.35
9.52
MUH-A18WV - E1
MUH-A24WV - E1 MUH-A30WV - E1
Outdoor unit
Gas 0
Liquid 0
OUTDOOR UNIT
E1
Unit:mm
MAX. REFRIGERANT PIPING LENGTH
MAX. HEIGHT DIFFERENCE
13
Page 14
Model
MUH-A18WV -
E1
Refrigerant piping length (one way)
Outdoor unit precharged
1,750
15m
160
20m
260
25m
360
7m
0
10m
60
ADDITIONAL REFRIGERANT CHARGE(R410A : g)
Model
MUH-A24WV -
E1
Refrigerant piping length (one way)
Outdoor unit precharged
2,150
15m
160
20m
260
25m
360
7m
0
10m
60
Outdoor unit
precharged
0 165 440 715 990 1,2652,300
Refrigerant piping length (one way)
15m10m7m
Model
MUH-A30WV -
E1
20m
25m 30m
Calculation : Xg=20g/m (Refrigerant piping length (m)–7)
Calculation : Xg=20g/m (Refrigerant piping length (m)–7)
Calculation : Xg=55g/mo(Refrigerant piping length(m)-7)
14
Page 15
8
11.6
10.5
7.5
8.5
9.5
12.8
15.6
9.8
12.6
11.2
14.1
17.2
17.4
13.9
12.4
10.8
15.6
19.2
MUH-A18WV - E1
MSH-A24WV - E1
MSH-A18WV - E1
MUH-A24WV - E1
MSH-A30WV - E1
MUH-A30WV - E1
Wet-and dry-bulb thermometers
Wet-and dry-bulb thermometers
PERFORMANCE CURVES
}
}
E1E1E1
Cooling
Heating
MUH-A18WV - MUH-A24WV - MUH-A30WV -
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions, since operating conditions vary according to the areas where these units are installed. The following information has been pro­vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264V, 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : °CWB (2) Indoor outlet air wet-bulb temperature : °CWB (3) Outdoor intake air dry-bulb temperature : °CDB (4) Total input: W (5) Indoor intake air dry-bulb temperature : °CDB (6) Outdoor intake air wet-bulb temperature : °CWB (7) Total input : W
Indoor air wet/dry-bulb temperature difference on the left side of the chart on this page and next page shows the differ­ence between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL(HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
OUTDOOR UNIT
15
Page 16
26.6
24.5
22.5
20.4
18.4
16.3
14.3
12.3
36.8
34.0
31.1
28.3
25.5
22.6
19.8
17.0
38.4
35.5
32.5
29.6
26.6
23.6
20.7
17.7
MUH-A18WV - E1
MSH-A24WV - E1
MSH-A18WV - E1
MUH-A24WV - E1
MSH-A30WV - E1
MUH-A30WV - E1
NOTE:The above curves are for the heating operation without any frost.
18
32
70(%)
230V
15 20
50
25 60
30 35
0.7
0.8
0.9
1.0
1.1
1.2
1.3
7
8
9
10
11
12
13
(:)
15 20
50
25 60
30 70(%)
35(:)
5
6
8
7
18 32
230V
18
32
70(%)
230V
15 20
50
25 60
30 35
0.6
0.7
0.8
0.9
1.0
1.1
(:)
6
7
8
9
10
11
10
11
8
9
230V
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation
11
Both indoor and outdoor unit are under the same temperature/humidity condition.
Dry-bulb temperature
20 25
Relative humidity(%)
50 60
30 70
22
Air flow should be set at MAX.
33
The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is : 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
(kgf/F[Gauge])(MPa[Gauge])
Outdoor low pressure
Ambient temperature(˚C) Ambient humidity(%)
MUH-A18WV -
E1
MUH-A18WV -
Outdoor unit current (A)
Ambient temperature(˚C) Ambient humidity(%)
E1
(kgf/F[Gauge])(MPa[Gauge])
Outdoor low pressure
MUH-A24WV -
Ambient temperature(˚C) Ambient humidity(%)
E1
MUH-A24WV -
E1
Outdoor unit current (A)
Ambient temperature(˚C) Ambient humidity(%)
16
Page 17
14
13
12
11
230V
18
32
70(%)
230V
15 20
50
25 60
30 35
5
6
7
8
9
10
11
(:)
5
6
7
8
9
18
32
70(%)
230V
15 20
50
25 60
30 35
10
11
12
13
14
15
16
(:)
(kgf/F[Gauge])(MPa[Gauge])
7
21
230V
(:)
5 10152025
16
17
18
19
20
MUH-A30WV -
E1
MUH-A30WV -
E1
Outdoor low pressure
HEAT operation
Condition indoor:Dry bulb temperature 20.0°C
Outdoor:Dry bulb temperature 7,15,20°C
MUH-A18WV -
10
9
8
Ambient temperature(˚C) Ambient humidity(%)
Wet bulb temperature 14.5°C
Wet bulb temperature 6,12,14.5°C
E1
230V
Outdoor unit current(A)
Ambient temperature(˚C) Ambient humidity(%)
MUH-A24WV -
E1
Outdoor unit current (A)
7
5 10152025
7
Ambient temperature(˚C)
MUH-A30WV -
Outdoor unit current(A)
Ambient temperature(˚C)
21
Outdoor unit current (A)
(:)
Ambient temperature(˚C)
E1
17
Page 18
PERFORMANCE DATA COOL operation
MSH-A18WV - : MUH-A18WV - (230V)
CAPACITY : 5.0(KW) SHF : 0.65 INPUT : 1780(W)
INDOOR
DB(:)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
INDOOR
WB(:)
21 18 5.88 2.76 0.47 1424 5.63 2.64 0.47 1495 5.40 2.54 0.47 1566 5.20 2.44 0.47 1638 21 20 6.13 2.14 0.35 1495 5.88 2.06 0.35 1584 5.70 2.00 0.35 1620 5.50 1.93 0.35 1691 22 18 5.88 3.00 0.51 1424 5.63 2.87 0.51 1495 5.40 2.75 0.51 1566 5.20 2.65 0.51 1638 22 20 6.13 2.39 0.39 1495 5.88 2.29 0.39 1584 5.70 2.22 0.39 1620 5.50 2.15 0.39 1691 22 22 6.38 1.72 0.27 1549 6.15 1.66 0.27 1647 6.00 1.62 0.27 1691 5.75 1.55 0.27 1762 23 18 5.88 3.23 0.55 1424 5.63 3.09 0.55 1495 5.40 2.97 0.55 1566 5.20 2.86 0.55 1638 23 20 6.13 2.63 0.43 1495 5.88 2.53 0.43 1584 5.70 2.45 0.43 1620 5.50 2.37 0.43 1691 23 22 6.38 1.98 0.31 1549 6.15 1.91 0.31 1647 6.00 1.86 0.31 1691 5.75 1.78 0.31 1762 24 18 5.88 3.47 0.59 1424 5.63 3.32 0.59 1495 5.40 3.19 0.59 1566 5.20 3.07 0.59 1638 24 20 6.13 2.88 0.47 1495 5.88 2.76 0.47 1584 5.70 2.68 0.47 1620 5.50 2.59 0.47 1691 24 22 6.38 2.23 0.35 1549 6.15 2.15 0.35 1647 6.00 2.10 0.35 1691 5.75 2.01 0.35 1762 24 24 6.70 1.54 0.23 1620 6.45 1.48 0.23 1709 6.30 1.45 0.23 1762 6.10 1.40 0.23 1851 25 18 5.88 3.70 0.63 1424 5.63 3.54 0.63 1495 5.40 3.40 0.63 1566 5.20 3.28 0.63 1638 25 20 6.13 3.12 0.51 1495 5.88 3.00 0.51 1584 5.70 2.91 0.51 1620 5.50 2.81 0.51 1691 25 22 6.38 2.49 0.39 1549 6.15 2.40 0.39 1647 6.00 2.34 0.39 1691 5.75 2.24 0.39 1762 25 24 6.70 1.81 0.27 1620 6.45 1.74 0.27 1709 6.30 1.70 0.27 1762 6.10 1.65 0.27 1851 26 18 5.88 3.94 0.67 1424 5.63 3.77 0.67 1495 5.40 3.62 0.67 1566 5.20 3.48 0.67 1638 26 20 6.13 3.37 0.55 1495 5.88 3.23 0.55 1584 5.70 3.14 0.55 1620 5.50 3.03 0.55 1691 26 22 6.38 2.74 0.43 1549 6.15 2.64 0.43 1647 6.00 2.58 0.43 1691 5.75 2.47 0.43 1762 26 24 6.70 2.08 0.31 1620 6.45 2.00 0.31 1709 6.30 1.95 0.31 1762 6.10 1.89 0.31 1851 26 26 6.90 1.31 0.19 1709 6.70 1.27 0.19 1798 6.60 1.25 0.19 1851 6.40 1.22 0.19 1905 27 18 5.88 4.17 0.71 1424 5.63 3.99 0.71 1495 5.40 3.83 0.71 1566 5.20 3.69 0.71 1638 27 20 6.13 3.61 0.59 1495 5.88 3.47 0.59 1584 5.70 3.36 0.59 1620 5.50 3.25 0.59 1691 27 22 6.38 3.00 0.47 1549 6.15 2.89 0.47 1647 6.00 2.82 0.47 1691 5.75 2.70 0.47 1762 27 24 6.70 2.35 0.35 1620 6.45 2.26 0.35 1709 6.30 2.21 0.35 1762 6.10 2.14 0.35 1851 27 26 6.90 1.59 0.23 1709 6.70 1.54 0.23 1798 6.60 1.52 0.23 1851 6.40 1.47 0.23 1905 28 18 5.88 4.41 0.75 1424 5.63 4.22 0.75 1495 5.40 4.05 0.75 1566 5.20 3.90 0.75 1638 28 20 6.13 3.86 0.63 1495 5.88 3.70 0.63 1584 5.70 3.59 0.63 1620 5.50 3.47 0.63 1691 28 22 6.38 3.25 0.51 1549 6.15 3.14 0.51 1647 6.00 3.06 0.51 1691 5.75 2.93 0.51 1762 28 24 6.70 2.61 0.39 1620 6.45 2.52 0.39 1709 6.30 2.46 0.39 1762 6.10 2.38 0.39 1851 28 26 6.90 1.86 0.27 1709 6.70 1.81 0.27 1798 6.60 1.78 0.27 1851 6.40 1.73 0.27 1905 29 18 5.88 4.64 0.79 1424 5.63 4.44 0.79 1495 5.40 4.27 0.79 1566 5.20 4.11 0.79 1638 29 20 6.13 4.10 0.67 1495 5.88 3.94 0.67 1584 5.70 3.82 0.67 1620 5.50 3.69 0.67 1691 29 22 6.38 3.51 0.55 1549 6.15 3.38 0.55 1647 6.00 3.30 0.55 1691 5.75 3.16 0.55 1762 29 24 6.70 2.88 0.43 1620 6.45 2.77 0.43 1709 6.30 2.71 0.43 1762 6.10 2.62 0.43 1851 29 26 6.90 2.14 0.31 1709 6.70 2.08 0.31 1798 6.60 2.05 0.31 1851 6.40 1.98 0.31 1905 30 18 5.88 4.88 0.83 1424 5.63 4.67 0.83 1495 5.40 4.48 0.83 1566 5.20 4.32 0.83 1638 30 20 6.13 4.35 0.71 1495 5.88 4.17 0.71 1584 5.70 4.05 0.71 1620 5.50 3.91 0.71 1691 30 22 6.38 3.76 0.59 1549 6.15 3.63 0.59 1647 6.00 3.54 0.59 1691 5.75 3.39 0.59 1762 30 24 6.70 3.15 0.47 1620 6.45 3.03 0.47 1709 6.30 2.96 0.47 1762 6.10 2.87 0.47 1851 30 26 6.90 2.42 0.35 1709 6.70 2.35 0.35 1798 6.60 2.31 0.35 1851 6.40 2.24 0.35 1905 31 18 5.88 5.11 0.87 1424 5.63 4.89 0.87 1495 5.40 4.70 0.87 1566 5.20 4.52 0.87 1638 31 20 6.13 4.59 0.75 1495 5.88 4.41 0.75 1584 5.70 4.28 0.75 1620 5.50 4.13 0.75 1691 31 22 6.38 4.02 0.63 1549 6.15 3.87 0.63 1647 6.00 3.78 0.63 1691 5.75 3.62 0.63 1762 31 24 6.70 3.42 0.51 1620 6.45 3.29 0.51 1709 6.30 3.21 0.51 1762 6.10 3.11 0.51 1851 31 26 6.90 2.69 0.39 1709 6.70 2.61 0.39 1798 6.60 2.57 0.39 1851 6.40 2.50 0.39 1905 32 18 5.88 5.35 0.91 1424 5.63 5.12 0.91 1495 5.40 4.91 0.91 1566 5.20 4.73 0.91 1638 32 20 6.13 4.84 0.79 1495 5.88 4.64 0.79 1584 5.70 4.50 0.79 1620 5.50 4.35 0.79 1691 32 22 6.38 4.27 0.67 1549 6.15 4.12 0.67 1647 6.00 4.02 0.67 1691 5.75 3.85 0.67 1762 32 24 6.70 3.69 0.55 1620 6.45 3.55 0.55 1709 6.30 3.47 0.55 1762 6.10 3.36 0.55 1851 32 26 6.90 2.97 0.43 1709 6.70 2.88 0.43 1798 6.60 2.84 0.43 1851 6.40 2.75 0.43 1905
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 2725 30
E1E1
OUTDOOR DB(:)
18
Page 19
PERFORMANCE DATA COOL operation
MSH-A18WV - : MUH-A18WV - (230V)
CAPACITY : 5.0(KW) SHF : 0.65 INPUT : 1780(W)
INDOOR
DB(:)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
INDOOR
WB(:)
21 18 4.90 2.30 0.47 1744 4.50 2.12 0.47 1851 4.33 2.03 0.47 1887 21 20 5.15 1.80 0.35 1816 4.80 1.68 0.35 1905 4.63 1.62 0.35 1958 22 18 4.90 2.50 0.51 1744 4.50 2.30 0.51 1851 4.33 2.21 0.51 1887 22 20 5.15 2.01 0.39 1816 4.80 1.87 0.39 1905 4.63 1.80 0.39 1958 22 22 5.45 1.47 0.27 1887 5.10 1.38 0.27 1994 4.93 1.33 0.27 2029 23 18 4.90 2.70 0.55 1744 4.50 2.48 0.55 1851 4.33 2.38 0.55 1887 23 20 5.15 2.21 0.43 1816 4.80 2.06 0.43 1905 4.63 1.99 0.43 1958 23 22 5.45 1.69 0.31 1887 5.10 1.58 0.31 1994 4.93 1.53 0.31 2029 24 18 4.90 2.89 0.59 1744 4.50 2.66 0.59 1851 4.33 2.55 0.59 1887 24 20 5.15 2.42 0.47 1816 4.80 2.26 0.47 1905 4.63 2.17 0.47 1958 24 22 5.45 1.91 0.35 1887 5.10 1.79 0.35 1994 4.93 1.72 0.35 2029 24 24 5.75 1.32 0.23 1958 5.40 1.24 0.23 2047 5.25 1.21 0.23 2092 25 18 4.90 3.09 0.63 1744 4.50 2.84 0.63 1851 4.33 2.72 0.63 1887 25 20 5.15 2.63 0.51 1816 4.80 2.45 0.51 1905 4.63 2.36 0.51 1958 25 22 5.45 2.13 0.39 1887 5.10 1.99 0.39 1994 4.93 1.92 0.39 2029 25 24 5.75 1.55 0.27 1958 5.40 1.46 0.27 2047 5.25 1.42 0.27 2092 26 18 4.90 3.28 0.67 1744 4.50 3.02 0.67 1851 4.33 2.90 0.67 1887 26 20 5.15 2.83 0.55 1816 4.80 2.64 0.55 1905 4.63 2.54 0.55 1958 26 22 5.45 2.34 0.43 1887 5.10 2.19 0.43 1994 4.93 2.12 0.43 2029 26 24 5.75 1.78 0.31 1958 5.40 1.67 0.31 2047 5.25 1.63 0.31 2092 26 26 6.05 1.15 0.19 2029 5.70 1.08 0.19 2118 5.53 1.05 0.19 2163 27 18 4.90 3.48 0.71 1744 4.50 3.20 0.71 1851 4.33 3.07 0.71 1887 27 20 5.15 3.04 0.59 1816 4.80 2.83 0.59 1905 4.63 2.73 0.59 1958 27 22 5.45 2.56 0.47 1887 5.10 2.40 0.47 1994 4.93 2.31 0.47 2029 27 24 5.75 2.01 0.35 1958 5.40 1.89 0.35 2047 5.25 1.84 0.35 2092 27 26 6.05 1.39 0.23 2029 5.70 1.31 0.23 2118 5.53 1.27 0.23 2163 28 18 4.90 3.68 0.75 1744 4.50 3.38 0.75 1851 4.33 3.24 0.75 1887 28 20 5.15 3.24 0.63 1816 4.80 3.02 0.63 1905 4.63 2.91 0.63 1958 28 22 5.45 2.78 0.51 1887 5.10 2.60 0.51 1994 4.93 2.51 0.51 2029 28 24 5.75 2.24 0.39 1958 5.40 2.11 0.39 2047 5.25 2.05 0.39 2092 28 26 6.05 1.63 0.27 2029 5.70 1.54 0.27 2118 5.53 1.49 0.27 2163 29 18 4.90 3.87 0.79 1744 4.50 3.56 0.79 1851 4.33 3.42 0.79 1887 29 20 5.15 3.45 0.67 1816 4.80 3.22 0.67 1905 4.63 3.10 0.67 1958 29 22 5.45 3.00 0.55 1887 5.10 2.81 0.55 1994 4.93 2.71 0.55 2029 29 24 5.75 2.47 0.43 1958 5.40 2.32 0.43 2047 5.25 2.26 0.43 2092 29 26 6.05 1.88 0.31 2029 5.70 1.77 0.31 2118 5.53 1.71 0.31 2163 30 18 4.90 4.07 0.83 1744 4.50 3.74 0.83 1851 4.33 3.59 0.83 1887 30 20 5.15 3.66 0.71 1816 4.80 3.41 0.71 1905 4.63 3.28 0.71 1958 30 22 5.45 3.22 0.59 1887 5.10 3.01 0.59 1994 4.93 2.91 0.59 2029 30 24 5.75 2.70 0.47 1958 5.40 2.54 0.47 2047 5.25 2.47 0.47 2092 30 26 6.05 2.12 0.35 2029 5.70 2.00 0.35 2118 5.53 1.93 0.35 2163 31 18 4.90 4.26 0.87 1744 4.50 3.92 0.87 1851 4.33 3.76 0.87 1887 31 20 5.15 3.86 0.75 1816 4.80 3.60 0.75 1905 4.63 3.47 0.75 1958 31 22 5.45 3.43 0.63 1887 5.10 3.21 0.63 1994 4.93 3.10 0.63 2029 31 24 5.75 2.93 0.51 1958 5.40 2.75 0.51 2047 5.25 2.68 0.51 2092 31 26 6.05 2.36 0.39 2029 5.70 2.22 0.39 2118 5.53 2.15 0.39 2163 32 18 4.90 4.46 0.91 1744 4.50 4.10 0.91 1851 4.33 3.94 0.91 1887 32 20 5.15 4.07 0.79 1816 4.80 3.79 0.79 1905 4.63 3.65 0.79 1958 32 22 5.45 3.65 0.67 1887 5.10 3.42 0.67 1994 4.93 3.30 0.67 2029 32 24 5.75 3.16 0.55 1958 5.40 2.97 0.55 2047 5.25 2.89 0.55 2092 32 26 6.05 2.60 0.43 2029 5.70 2.45 0.43 2118 5.53 2.38 0.43 2163
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
35 4340
E1E1
OUTDOOR DB(:)
19
Page 20
PERFORMANCE DATA COOL operation
MSH-A24WV - : MUH-A24WV - (230V)
CAPACITY : 6.3(KW) SHF : 0.64 INPUT : 2410(W)
INDOOR
DB(:)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
INDOOR
WB(:)
21 18 7.40 3.41 0.46 1928 7.09 3.26 0.46 2024 6.80 3.13 0.46 2121 6.55 3.01 0.46 2217 21 20 7.72 2.62 0.34 2024 7.40 2.52 0.34 2145 7.18 2.44 0.34 2193 6.93 2.36 0.34 2290 22 18 7.40 3.70 0.50 1928 7.09 3.54 0.50 2024 6.80 3.40 0.50 2121 6.55 3.28 0.50 2217 22 20 7.72 2.93 0.38 2024 7.40 2.81 0.38 2145 7.18 2.73 0.38 2193 6.93 2.63 0.38 2290 22 22 8.03 2.09 0.26 2097 7.75 2.01 0.26 2229 7.56 1.97 0.26 2290 7.25 1.88 0.26 2386 23 18 7.40 4.00 0.54 1928 7.09 3.83 0.54 2024 6.80 3.67 0.54 2121 6.55 3.54 0.54 2217 23 20 7.72 3.24 0.42 2024 7.40 3.11 0.42 2145 7.18 3.02 0.42 2193 6.93 2.91 0.42 2290 23 22 8.03 2.41 0.30 2097 7.75 2.32 0.30 2229 7.56 2.27 0.30 2290 7.25 2.17 0.30 2386 24 18 7.40 4.29 0.58 1928 7.09 4.11 0.58 2024 6.80 3.95 0.58 2121 6.55 3.80 0.58 2217 24 20 7.72 3.55 0.46 2024 7.40 3.41 0.46 2145 7.18 3.30 0.46 2193 6.93 3.19 0.46 2290 24 22 8.03 2.73 0.34 2097 7.75 2.63 0.34 2229 7.56 2.57 0.34 2290 7.25 2.46 0.34 2386 24 24 8.44 1.86 0.22 2193 8.13 1.79 0.22 2314 7.94 1.75 0.22 2386 7.69 1.69 0.22 2506 25 18 7.40 4.59 0.62 1928 7.09 4.39 0.62 2024 6.80 4.22 0.62 2121 6.55 4.06 0.62 2217 25 20 7.72 3.86 0.50 2024 7.40 3.70 0.50 2145 7.18 3.59 0.50 2193 6.93 3.47 0.50 2290 25 22 8.03 3.05 0.38 2097 7.75 2.94 0.38 2229 7.56 2.87 0.38 2290 7.25 2.75 0.38 2386 25 24 8.44 2.19 0.26 2193 8.13 2.11 0.26 2314 7.94 2.06 0.26 2386 7.69 2.00 0.26 2506 26 18 7.40 4.89 0.66 1928 7.09 4.68 0.66 2024 6.80 4.49 0.66 2121 6.55 4.32 0.66 2217 26 20 7.72 4.17 0.54 2024 7.40 4.00 0.54 2145 7.18 3.88 0.54 2193 6.93 3.74 0.54 2290 26 22 8.03 3.37 0.42 2097 7.75 3.25 0.42 2229 7.56 3.18 0.42 2290 7.25 3.04 0.42 2386 26 24 8.44 2.53 0.30 2193 8.13 2.44 0.30 2314 7.94 2.38 0.30 2386 7.69 2.31 0.30 2506 26 26 8.69 1.56 0.18 2314 8.44 1.52 0.18 2434 8.32 1.50 0.18 2506 8.06 1.45 0.18 2579 27 18 7.40 5.18 0.70 1928 7.09 4.96 0.70 2024 6.80 4.76 0.70 2121 6.55 4.59 0.70 2217 27 20 7.72 4.48 0.58 2024 7.40 4.29 0.58 2145 7.18 4.17 0.58 2193 6.93 4.02 0.58 2290 27 22 8.03 3.69 0.46 2097 7.75 3.56 0.46 2229 7.56 3.48 0.46 2290 7.25 3.33 0.46 2386 27 24 8.44 2.87 0.34 2193 8.13 2.76 0.34 2314 7.94 2.70 0.34 2386 7.69 2.61 0.34 2506 27 26 8.69 1.91 0.22 2314 8.44 1.86 0.22 2434 8.32 1.83 0.22 2506 8.06 1.77 0.22 2579 28 18 7.40 5.48 0.74 1928 7.09 5.24 0.74 2024 6.80 5.03 0.74 2121 6.55 4.85 0.74 2217 28 20 7.72 4.78 0.62 2024 7.40 4.59 0.62 2145 7.18 4.45 0.62 2193 6.93 4.30 0.62 2290 28 22 8.03 4.02 0.50 2097 7.75 3.87 0.50 2229 7.56 3.78 0.50 2290 7.25 3.62 0.50 2386 28 24 8.44 3.21 0.38 2193 8.13 3.09 0.38 2314 7.94 3.02 0.38 2386 7.69 2.92 0.38 2506 28 26 8.69 2.26 0.26 2314 8.44 2.19 0.26 2434 8.32 2.16 0.26 2506 8.06 2.10 0.26 2579 29 18 7.40 5.77 0.78 1928 7.09 5.53 0.78 2024 6.80 5.31 0.78 2121 6.55 5.11 0.78 2217 29 20 7.72 5.09 0.66 2024 7.40 4.89 0.66 2145 7.18 4.74 0.66 2193 6.93 4.57 0.66 2290 29 22 8.03 4.34 0.54 2097 7.75 4.18 0.54 2229 7.56 4.08 0.54 2290 7.25 3.91 0.54 2386 29 24 8.44 3.55 0.42 2193 8.13 3.41 0.42 2314 7.94 3.33 0.42 2386 7.69 3.23 0.42 2506 29 26 8.69 2.61 0.30 2314 8.44 2.53 0.30 2434 8.32 2.49 0.30 2506 8.06 2.42 0.30 2579 30 18 7.40 6.07 0.82 1928 7.09 5.81 0.82 2024 6.80 5.58 0.82 2121 6.55 5.37 0.82 2217 30 20 7.72 5.40 0.70 2024 7.40 5.18 0.70 2145 7.18 5.03 0.70 2193 6.93 4.85 0.70 2290 30 22 8.03 4.66 0.58 2097 7.75 4.49 0.58 2229 7.56 4.38 0.58 2290 7.25 4.20 0.58 2386 30 24 8.44 3.88 0.46 2193 8.13 3.74 0.46 2314 7.94 3.65 0.46 2386 7.69 3.54 0.46 2506 30 26 8.69 2.96 0.34 2314 8.44 2.87 0.34 2434 8.32 2.83 0.34 2506 8.06 2.74 0.34 2579 31 18 7.40 6.37 0.86 1928 7.09 6.10 0.86 2024 6.80 5.85 0.86 2121 6.55 5.63 0.86 2217 31 20 7.72 5.71 0.74 2024 7.40 5.48 0.74 2145 7.18 5.31 0.74 2193 6.93 5.13 0.74 2290 31 22 8.03 4.98 0.62 2097 7.75 4.80 0.62 2229 7.56 4.69 0.62 2290 7.25 4.49 0.62 2386 31 24 8.44 4.22 0.50 2193 8.13 4.06 0.50 2314 7.94 3.97 0.50 2386 7.69 3.84 0.50 2506 31 26 8.69 3.30 0.38 2314 8.44 3.21 0.38 2434 8.32 3.16 0.38 2506 8.06 3.06 0.38 2579 32 18 7.40 6.66 0.90 1928 7.09 6.38 0.90 2024 6.80 6.12 0.90 2121 6.55 5.90 0.90 2217 32 20 7.72 6.02 0.78 2024 7.40 5.77 0.78 2145 7.18 5.60 0.78 2193 6.93 5.41 0.78 2290 32 22 8.03 5.30 0.66 2097 7.75 5.11 0.66 2229 7.56 4.99 0.66 2290 7.25 4.78 0.66 2386 32 24 8.44 4.56 0.54 2193 8.13 4.39 0.54 2314 7.94 4.29 0.54 2386 7.69 4.15 0.54 2506 32 26 8.69 3.65 0.42 2314 8.44 3.55 0.42 2434 8.32 3.49 0.42 2506 8.06 3.39 0.42 2579
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 2725 30
E1E1
OUTDOOR DB(:)
20
Page 21
PERFORMANCE DATA COOL operation
MSH-A24WV - : MUH-A24WV - (230V)
CAPACITY : 6.3(KW) SHF : 0.64 INPUT : 2410(W)
INDOOR
DB(:)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
INDOOR
WB(:)
21 18 6.17 2.84 0.46 2362 5.67 2.61 0.46 2506 5.45 2.51 0.46 2555 21 20 6.49 2.21 0.34 2458 6.05 2.06 0.34 2579 5.83 1.98 0.34 2651 22 18 6.17 3.09 0.50 2362 5.67 2.84 0.50 2506 5.45 2.72 0.50 2555 22 20 6.49 2.47 0.38 2458 6.05 2.30 0.38 2579 5.83 2.21 0.38 2651 22 22 6.87 1.79 0.26 2555 6.43 1.67 0.26 2699 6.21 1.61 0.26 2747 23 18 6.17 3.33 0.54 2362 5.67 3.06 0.54 2506 5.45 2.94 0.54 2555 23 20 6.49 2.73 0.42 2458 6.05 2.54 0.42 2579 5.83 2.45 0.42 2651 23 22 6.87 2.06 0.30 2555 6.43 1.93 0.30 2699 6.21 1.86 0.30 2747 24 18 6.17 3.58 0.58 2362 5.67 3.29 0.58 2506 5.45 3.16 0.58 2555 24 20 6.49 2.98 0.46 2458 6.05 2.78 0.46 2579 5.83 2.68 0.46 2651 24 22 6.87 2.33 0.34 2555 6.43 2.18 0.34 2699 6.21 2.11 0.34 2747 24 24 7.25 1.59 0.22 2651 6.80 1.50 0.22 2772 6.62 1.46 0.22 2832 25 18 6.17 3.83 0.62 2362 5.67 3.52 0.62 2506 5.45 3.38 0.62 2555 25 20 6.49 3.24 0.50 2458 6.05 3.02 0.50 2579 5.83 2.91 0.50 2651 25 22 6.87 2.61 0.38 2555 6.43 2.44 0.38 2699 6.21 2.36 0.38 2747 25 24 7.25 1.88 0.26 2651 6.80 1.77 0.26 2772 6.62 1.72 0.26 2832 26 18 6.17 4.07 0.66 2362 5.67 3.74 0.66 2506 5.45 3.60 0.66 2555 26 20 6.49 3.50 0.54 2458 6.05 3.27 0.54 2579 5.83 3.15 0.54 2651 26 22 6.87 2.88 0.42 2555 6.43 2.70 0.42 2699 6.21 2.61 0.42 2747 26 24 7.25 2.17 0.30 2651 6.80 2.04 0.30 2772 6.62 1.98 0.30 2832 26 26 7.62 1.37 0.18 2747 7.18 1.29 0.18 2868 6.96 1.25 0.18 2928 27 18 6.17 4.32 0.70 2362 5.67 3.97 0.70 2506 5.45 3.81 0.70 2555 27 20 6.49 3.76 0.58 2458 6.05 3.51 0.58 2579 5.83 3.38 0.58 2651 27 22 6.87 3.16 0.46 2555 6.43 2.96 0.46 2699 6.21 2.85 0.46 2747 27 24 7.25 2.46 0.34 2651 6.80 2.31 0.34 2772 6.62 2.25 0.34 2832 27 26 7.62 1.68 0.22 2747 7.18 1.58 0.22 2868 6.96 1.53 0.22 2928 28 18 6.17 4.57 0.74 2362 5.67 4.20 0.74 2506 5.45 4.03 0.74 2555 28 20 6.49 4.02 0.62 2458 6.05 3.75 0.62 2579 5.83 3.61 0.62 2651 28 22 6.87 3.43 0.50 2555 6.43 3.21 0.50 2699 6.21 3.10 0.50 2747 28 24 7.25 2.75 0.38 2651 6.80 2.59 0.38 2772 6.62 2.51 0.38 2832 28 26 7.62 1.98 0.26 2747 7.18 1.87 0.26 2868 6.96 1.81 0.26 2928 29 18 6.17 4.82 0.78 2362 5.67 4.42 0.78 2506 5.45 4.25 0.78 2555 29 20 6.49 4.28 0.66 2458 6.05 3.99 0.66 2579 5.83 3.85 0.66 2651 29 22 6.87 3.71 0.54 2555 6.43 3.47 0.54 2699 6.21 3.35 0.54 2747 29 24 7.25 3.04 0.42 2651 6.80 2.86 0.42 2772 6.62 2.78 0.42 2832 29 26 7.62 2.29 0.30 2747 7.18 2.15 0.30 2868 6.96 2.09 0.30 2928 30 18 6.17 5.06 0.82 2362 5.67 4.65 0.82 2506 5.45 4.47 0.82 2555 30 20 6.49 4.54 0.70 2458 6.05 4.23 0.70 2579 5.83 4.08 0.70 2651 30 22 6.87 3.98 0.58 2555 6.43 3.73 0.58 2699 6.21 3.60 0.58 2747 30 24 7.25 3.33 0.46 2651 6.80 3.13 0.46 2772 6.62 3.04 0.46 2832 30 26 7.62 2.59 0.34 2747 7.18 2.44 0.34 2868 6.96 2.37 0.34 2928 31 18 6.17 5.31 0.86 2362 5.67 4.88 0.86 2506 5.45 4.69 0.86 2555 31 20 6.49 4.80 0.74 2458 6.05 4.48 0.74 2579 5.83 4.31 0.74 2651 31 22 6.87 4.26 0.62 2555 6.43 3.98 0.62 2699 6.21 3.85 0.62 2747 31 24 7.25 3.62 0.50 2651 6.80 3.40 0.50 2772 6.62 3.31 0.50 2832 31 26 7.62 2.90 0.38 2747 7.18 2.73 0.38 2868 6.96 2.65 0.38 2928 32 18 6.17 5.56 0.90 2362 5.67 5.10 0.90 2506 5.45 4.90 0.90 2555 32 20 6.49 5.06 0.78 2458 6.05 4.72 0.78 2579 5.83 4.55 0.78 2651 32 22 6.87 4.53 0.66 2555 6.43 4.24 0.66 2699 6.21 4.10 0.66 2747 32 24 7.25 3.91 0.54 2651 6.80 3.67 0.54 2772 6.62 3.57 0.54 2832 32 26 7.62 3.20 0.42 2747 7.18 3.02 0.42 2868 6.96 2.92 0.42 2928
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
35 4340
E1E1
OUTDOOR DB(:)
21
Page 22
21 18 9.99 4.39 0.44 2608 9.56 4.21 0.44 2738 9.18 4.04 0.44 2869 8.84 3.89 0.44 2999 21 20 10.41 3.33 0.32 2738 9.99 3.20 0.32 2901 9.69 3.10 0.32 2967 9.35 2.99 0.32 3097 22 18 9.99 4.79 0.48 2608 9.56 4.59 0.48 2738 9.18 4.41 0.48 2869 8.84 4.24 0.48 2999 22 20 10.41 3.75 0.36 2738 9.99 3.60 0.36 2901 9.69 3.49 0.36 2967 9.35 3.37 0.36 3097 22 22 10.84 2.60 0.24 2836 10.46 2.51 0.24 3016 10.20 2.45 0.24 3097 9.78 2.35 0.24 3227 23 18 9.99 5.19 0.52 2608 9.56 4.97 0.52 2738 9.18 4.77 0.52 2869 8.84 4.60 0.52 2999 23 20 10.41 4.17 0.40 2738 9.99 4.00 0.40 2901 9.69 3.88 0.40 2967 9.35 3.74 0.40 3097 23 22 10.84 3.03 0.28 2836 10.46 2.93 0.28 3016 10.20 2.86 0.28 3097 9.78 2.74 0.28 3227 24 18 9.99 5.59 0.56 2608 9.56 5.36 0.56 2738 9.18 5.14 0.56 2869 8.84 4.95 0.56 2999 24 20 10.41 4.58 0.44 2738 9.99 4.39 0.44 2901 9.69 4.26 0.44 2967 9.35 4.11 0.44 3097 24 22 10.84 3.47 0.32 2836 10.46 3.35 0.32 3016 10.20 3.26 0.32 3097 9.78 3.13 0.32 3227 24 24 11.39 2.28 0.20 2967 10.97 2.19 0.20 3130 10.71 2.14 0.20 3227 10.37 2.07 0.20 3390 25 18 9.99 5.99 0.60 2608 9.56 5.74 0.60 2738 9.18 5.51 0.60 2869 8.84 5.30 0.60 2999 25 20 10.41 5.00 0.48 2738 9.99 4.79 0.48 2901 9.69 4.65 0.48 2967 9.35 4.49 0.48 3097 25 22 10.84 3.90 0.36 2836 10.46 3.76 0.36 3016 10.20 3.67 0.36 3097 9.78 3.52 0.36 3227 25 24 11.39 2.73 0.24 2967 10.97 2.63 0.24 3130 10.71 2.57 0.24 3227 10.37 2.49 0.24 3390 26 18 9.99 6.39 0.64 2608 9.56 6.12 0.64 2738 9.18 5.88 0.64 2869 8.84 5.66 0.64 2999 26 20 10.41 5.41 0.52 2738 9.99 5.19 0.52 2901 9.69 5.04 0.52 2967 9.35 4.86 0.52 3097 26 22 10.84 4.34 0.40 2836 10.46 4.18 0.40 3016 10.20 4.08 0.40 3097 9.78 3.91 0.40 3227 26 24 11.39 3.19 0.28 2967 10.97 3.07 0.28 3130 10.71 3.00 0.28 3227 10.37 2.90 0.28 3390 26 26 11.73 1.88 0.16 3130 11.39 1.82 0.16 3293 11.22 1.80 0.16 3390 10.88 1.74 0.16 3488 27 18 9.99 6.79 0.68 2608 9.56 6.50 0.68 2738 9.18 6.24 0.68 2869 8.84 6.01 0.68 2999 27 20 10.41 5.83 0.56 2738 9.99 5.59 0.56 2901 9.69 5.43 0.56 2967 9.35 5.24 0.56 3097 27 22 10.84 4.77 0.44 2836 10.46 4.60 0.44 3016 10.20 4.49 0.44 3097 9.78 4.30 0.44 3227 27 24 11.39 3.64 0.32 2967 10.97 3.51 0.32 3130 10.71 3.43 0.32 3227 10.37 3.32 0.32 3390 27 26 11.73 2.35 0.20 3130 11.39 2.28 0.20 3293 11.22 2.24 0.20 3390 10.88 2.18 0.20 3488 28 18 9.99 7.19 0.72 2608 9.56 6.89 0.72 2738 9.18 6.61 0.72 2869 8.84 6.36 0.72 2999 28 20 10.41 6.25 0.60 2738 9.99 5.99 0.60 2901 9.69 5.81 0.60 2967 9.35 5.61 0.60 3097 28 22 10.84 5.20 0.48 2836 10.46 5.02 0.48 3016 10.20 4.90 0.48 3097 9.78 4.69 0.48 3227 28 24 11.39 4.10 0.36 2967 10.97 3.95 0.36 3130 10.71 3.86 0.36 3227 10.37 3.73 0.36 3390 28 26 11.73 2.82 0.24 3130 11.39 2.73 0.24 3293 11.22 2.69 0.24 3390 10.88 2.61 0.24 3488 29 18 9.99 7.59 0.76 2608 9.56 7.27 0.76 2738 9.18 6.98 0.76 2869 8.84 6.72 0.76 2999 29 20 10.41 6.66 0.64 2738 9.99 6.39 0.64 2901 9.69 6.20 0.64 2967 9.35 5.98 0.64 3097 29 22 10.84 5.64 0.52 2836 10.46 5.44 0.52 3016 10.20 5.30 0.52 3097 9.78 5.08 0.52 3227 29 24 11.39 4.56 0.40 2967 10.97 4.39 0.40 3130 10.71 4.28 0.40 3227 10.37 4.15 0.40 3390 29 26 11.73 3.28 0.28 3130 11.39 3.19 0.28 3293 11.22 3.14 0.28 3390 10.88 3.05 0.28 3488 30 18 9.99 7.99 0.80 2608 9.56 7.65 0.80 2738 9.18 7.34 0.80 2869 8.84 7.07 0.80 2999 30 20 10.41 7.08 0.68 2738 9.99 6.79 0.68 2901 9.69 6.59 0.68 2967 9.35 6.36 0.68 3097 30 22 10.84 6.07 0.56 2836 10.46 5.85 0.56 3016 10.20 5.71 0.56 3097 9.78 5.47 0.56 3227 30 24 11.39 5.01 0.44 2967 10.97 4.82 0.44 3130 10.71 4.71 0.44 3227 10.37 4.56 0.44 3390 30 26 11.73 3.75 0.32 3130 11.39 3.64 0.32 3293 11.22 3.59 0.32 3390 10.88 3.48 0.32 3488 31 18 9.99 8.39 0.84 2608 9.56 8.03 0.84 2738 9.18 7.71 0.84 2869 8.84 7.43 0.84 2999 31 20 10.41 7.50 0.72 2738 9.99 7.19 0.72 2901 9.69 6.98 0.72 2967 9.35 6.73 0.72 3097 31 22 10.84 6.50 0.60 2836 10.46 6.27 0.60 3016 10.20 6.12 0.60 3097 9.78 5.87 0.60 3227 31 24 11.39 5.47 0.48 2967 10.97 5.26 0.48 3130 10.71 5.14 0.48 3227 10.37 4.98 0.48 3390 31 26 11.73 4.22 0.36 3130 11.39 4.10 0.36 3293 11.22 4.04 0.36 3390 10.88 3.92 0.36 3488 32 18 9.99 8.79 0.88 2608 9.56 8.42 0.88 2738 9.18 8.08 0.88 2869 8.84 7.78 0.88 2999 32 20 10.41 7.91 0.76 2738 9.99 7.59 0.76 2901 9.69 7.36 0.76 2967 9.35 7.11 0.76 3097 32 22 10.84 6.94 0.64 2836 10.46 6.69 0.64 3016 10.20 6.53 0.64 3097 9.78 6.26 0.64 3227 32 24 11.39 5.92 0.52 2967 10.97 5.70 0.52 3130 10.71 5.57 0.52 3227 10.37 5.39 0.52 3390 32 26 11.73 4.69 0.40 3130 11.39 4.56 0.40 3293 11.22 4.49 0.40 3390 10.88 4.35 0.40 3488
INDOOR
DB(:)
INDOOR
WB(:)
OUTDOOR DB(:)
21 2725 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
CAPACITY : 8.5(KW) SHF : 0.62 INPUT : 3260(W)
PERFORMANCE DATA COOL operation
MSH-A30WV - : MUH-A30WV - (230V)
E1E1
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
22
Page 23
PERFORMANCE DATA COOL operation
MSH-A30WV - : MUH-A30WV - (230V)
CAPACITY : 8.5(KW) SHF : 0.62 INPUT : 3260(W)
INDOOR
DB(:)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
INDOOR
WB(:)
21 18 8.33 3.67 0.44 3195 7.65 3.37 0.44 3390 7.35 3.24 0.44 3456 21 20 8.76 2.80 0.32 3325 8.16 2.61 0.32 3488 7.86 2.52 0.32 3586 22 18 8.33 4.00 0.48 3195 7.65 3.67 0.48 3390 7.35 3.53 0.48 3456 22 20 8.76 3.15 0.36 3325 8.16 2.94 0.36 3488 7.86 2.83 0.36 3586 22 22 9.27 2.22 0.24 3456 8.67 2.08 0.24 3651 8.37 2.01 0.24 3716 23 18 8.33 4.33 0.52 3195 7.65 3.98 0.52 3390 7.35 3.82 0.52 3456 23 20 8.76 3.50 0.40 3325 8.16 3.26 0.40 3488 7.86 3.15 0.40 3586 23 22 9.27 2.59 0.28 3456 8.67 2.43 0.28 3651 8.37 2.34 0.28 3716 24 18 8.33 4.66 0.56 3195 7.65 4.28 0.56 3390 7.35 4.12 0.56 3456 24 20 8.76 3.85 0.44 3325 8.16 3.59 0.44 3488 7.86 3.46 0.44 3586 24 22 9.27 2.96 0.32 3456 8.67 2.77 0.32 3651 8.37 2.68 0.32 3716 24 24 9.78 1.96 0.20 3586 9.18 1.84 0.20 3749 8.93 1.79 0.20 3831 25 18 8.33 5.00 0.60 3195 7.65 4.59 0.60 3390 7.35 4.41 0.60 3456 25 20 8.76 4.20 0.48 3325 8.16 3.92 0.48 3488 7.86 3.77 0.48 3586 25 22 9.27 3.34 0.36 3456 8.67 3.12 0.36 3651 8.37 3.01 0.36 3716 25 24 9.78 2.35 0.24 3586 9.18 2.20 0.24 3749 8.93 2.14 0.24 3831 26 18 8.33 5.33 0.64 3195 7.65 4.90 0.64 3390 7.35 4.71 0.64 3456 26 20 8.76 4.55 0.52 3325 8.16 4.24 0.52 3488 7.86 4.09 0.52 3586 26 22 9.27 3.71 0.40 3456 8.67 3.47 0.40 3651 8.37 3.35 0.40 3716 26 24 9.78 2.74 0.28 3586 9.18 2.57 0.28 3749 8.93 2.50 0.28 3831 26 26 10.29 1.65 0.16 3716 9.69 1.55 0.16 3879 9.39 1.50 0.16 3961 27 18 8.33 5.66 0.68 3195 7.65 5.20 0.68 3390 7.35 5.00 0.68 3456 27 20 8.76 4.90 0.56 3325 8.16 4.57 0.56 3488 7.86 4.40 0.56 3586 27 22 9.27 4.08 0.44 3456 8.67 3.81 0.44 3651 8.37 3.68 0.44 3716 27 24 9.78 3.13 0.32 3586 9.18 2.94 0.32 3749 8.93 2.86 0.32 3831 27 26 10.29 2.06 0.20 3716 9.69 1.94 0.20 3879 9.39 1.88 0.20 3961 28 18 8.33 6.00 0.72 3195 7.65 5.51 0.72 3390 7.35 5.29 0.72 3456 28 20 8.76 5.25 0.60 3325 8.16 4.90 0.60 3488 7.86 4.72 0.60 3586 28 22 9.27 4.45 0.48 3456 8.67 4.16 0.48 3651 8.37 4.02 0.48 3716 28 24 9.78 3.52 0.36 3586 9.18 3.30 0.36 3749 8.93 3.21 0.36 3831 28 26 10.29 2.47 0.24 3716 9.69 2.33 0.24 3879 9.39 2.25 0.24 3961 29 18 8.33 6.33 0.76 3195 7.65 5.81 0.76 3390 7.35 5.59 0.76 3456 29 20 8.76 5.60 0.64 3325 8.16 5.22 0.64 3488 7.86 5.03 0.64 3586 29 22 9.27 4.82 0.52 3456 8.67 4.51 0.52 3651 8.37 4.35 0.52 3716 29 24 9.78 3.91 0.40 3586 9.18 3.67 0.40 3749 8.93 3.57 0.40 3831 29 26 10.29 2.88 0.28 3716 9.69 2.71 0.28 3879 9.39 2.63 0.28 3961 30 18 8.33 6.66 0.80 3195 7.65 6.12 0.80 3390 7.35 5.88 0.80 3456 30 20 8.76 5.95 0.68 3325 8.16 5.55 0.68 3488 7.86 5.35 0.68 3586 30 22 9.27 5.19 0.56 3456 8.67 4.86 0.56 3651 8.37 4.69 0.56 3716 30 24 9.78 4.30 0.44 3586 9.18 4.04 0.44 3749 8.93 3.93 0.44 3831 30 26 10.29 3.29 0.32 3716 9.69 3.10 0.32 3879 9.39 3.01 0.32 3961 31 18 8.33 7.00 0.84 3195 7.65 6.43 0.84 3390 7.35 6.18 0.84 3456 31 20 8.76 6.30 0.72 3325 8.16 5.88 0.72 3488 7.86 5.66 0.72 3586 31 22 9.27 5.56 0.60 3456 8.67 5.20 0.60 3651 8.37 5.02 0.60 3716 31 24 9.78 4.69 0.48 3586 9.18 4.41 0.48 3749 8.93 4.28 0.48 3831 31 26 10.29 3.70 0.36 3716 9.69 3.49 0.36 3879 9.39 3.38 0.36 3961 32 18 8.33 7.33 0.88 3195 7.65 6.73 0.88 3390 7.35 6.47 0.88 3456 32 20 8.76 6.65 0.76 3325 8.16 6.20 0.76 3488 7.86 5.98 0.76 3586 32 22 9.27 5.93 0.64 3456 8.67 5.55 0.64 3651 8.37 5.36 0.64 3716 32 24 9.78 5.08 0.52 3586 9.18 4.77 0.52 3749 8.93 4.64 0.52 3831 32 26 10.29 4.11 0.40 3716 9.69 3.88 0.40 3879 9.39 3.76 0.40 3961
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
35 4340
E1E1
OUTDOOR DB(:)
23
Page 24
OUTDOOR WB(:)
INDOOR
-10 -5 0 5 10 15 20
DB(:)
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
CAPACITY : 5.2(KW)
INPUT : 1610(W)
15 21 26
3.28
3.12
2.81
1047 1127 1208
3.95
3.74
3.48
1256 1336 1417
4.63
4.42
4.11
1417 1481 1562
5.30
5.04
4.78
1530 1594 1674
5.98
5.72
5.46
1626 1674 1755
6.60
6.34
6.08
1674 1723 1803
7.28
6.99
6.76
1707 1787 1852
PERFORMANCE DATA HEAT operation
OUTDOOR WB(:)
INDOOR
-10 -5 0 5 10 15 20
DB(:)
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
CAPACITY : 7.2(KW)
INPUT : 2480(W)
15 21 26
4.54
4.32
3.89
1612 1736 1860
5.47
5.18
4.82
1934 2058 2182
6.41
6.12
5.69
2182 2282 2406
7.34
6.98
6.62
2356 2455 2579
8.28
7.92
7.56
2505 2579 2703
9.14
8.78
8.42
2579 2654 2778
10.08
9.68
9.36
2629 2753 2852
OUTDOOR WB(:)
INDOOR
-10 -5
0 5 10 15 20
DB(:)
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
CAPACITY : 9.4(KW)
INPUT : 3430(W)
15 21 26
5.92
5.64
5.08
2230 2401 2573
7.14
6.77
6.30
2675 2847 3018
8.37
7.99
7.43
3018 3156 3327
9.59
9.12
8.65
3259 3396 3567
10.81
10.34
9.87
3464 3567 3739
11.94
11.47
11.00
3567 3670 3842
13.16
12.64
12.22
3636 3807 3945
MSH-A18WV - : MUH-A18WV - (230V)
NOTE Q :Total capacity (kW) INPUT:Total power input (W) DB : Dry-bulb temperature
E1E1
MSH-A24WV - : MUH-A24WV - (230V)
NOTE Q :Total capacity (kW) INPUT:Total power input (W) DB : Dry-bulb temperature
MSH-A30WV - : MUH-A30WV - (230V)
NOTE Q :Total capacity (kW) INPUT:Total power input (W) DB : Dry-bulb temperature
E1E1
E1E1
24
Page 25
9
Outdoor fan speed
20: 22:
High
Ambient temperature thermistor RT63 temperature
Low
High pressure protection
Released
48: 52:
ON
Outdoor fan
OFF
55:
(MUH-A18WV) (MUH-A24WV) 58:
Outdoor fan speed
13: 18:
High
Ambient temperature thermistor RT63 temperature
Low
MICROPROCESSOR CONTROL
MUH-A18WV - MUH-A24WV - MUH-A30WV -
E1E1E1
9-1. “I FEEL CONTROL” ( ) OPERATION 9-1-1. COOL mode of “I FEEL CONTROL”
1. Outdoor fan speed control <MUH-A30WV>
Outdoor fan speed is controlled according to the temperature of ambient temperature thermistor RT63. Outdoor fan Low operation : When the outside temperature decreases to 20°C or less.
Until the outside temperature goes to 22°C.
Outdoor fan High operation : Until the outside temperature decreases to 20°C or less.
When the outside temperature goes to 22°C.
NOTE1. : If the temperature of RT63 reads from 20: to 22: at the air conditioner starting outdoor fan speed is High. NOTE2. : When indoor fan speed is Low except HEAT operation mode and the outside temperature is 30: or less, the
outdoor fan operates at Low.
Outdoor fan Low operation is cancelled according to the following conditions(1 or 2):
1 When the operation is not changed and the outside temperature goes to 33: or more. 2 When the operation is changed. (Change to HEAT operation mode / Change of the indoor fan speed)
2. Discharge temperature protection <MUH-A30WV>
The compressor is controlled by the temperature of discharge temperature thermistor RT62 for excess rise protection of compressor discharge pressure.
• Compressor When the temperature of discharge temperature thermistor RT62 goes to 120: or more, the compressor is turned OFF.
After 3 minutes since the compressor has been turned OFF, if the temperature of discharge temperature thermistor RT62 becomes 100: or less, the compressor is turned ON.
9-1-2. DRY mode of “I FEEL CONTROL”
1. Outdoor fan speed control <MUH-A30WV>
Outdoor fan speed control is as same as one of COOL mode of “I FEEL CONTROL”.
9-1-3. HEAT mode of “I FEEL CONTROL”
1. Outdoor fan speed control <MUH-A30WV>
Outdoor fan speed is controlled according to the temperature of ambient temperature thermistor RT63. Outdoor fan Low operation : Until the outside temperature decreases to 13°C.
When the outside temperature goes to 18°C or more.
Outdoor fan High operation :When the outside temperature decreases to 13°C or less.
Until the outside temperature goes to 18°C.
2. High pressure protection <MUH-A18/A24WV>
During heating operation, the outdoor fan motor is controlled by the temperature of indoor coil thermistor RT12 for excess rise protection of compressor discharge pressure. (MUH-A18WV)Outdoor fan OFF : 52°C
Outdoor fan ON : 48°C
(MUH-A24WV)Outdoor fan OFF : 58°C
Outdoor fan ON : 55°C
High pressure protection chart Example
Indoor coil thermistor
RT12 temperature
(MUH-A18WV) 52˚C (MUH-A24WV) 58˚C
(MUH-A18WV) 48˚C (MUH-A24WV) 55˚C
Outdoor fan motor turn OFF
Outdoor fan motor turn ON
Outdoor fan motor
ON
OFF
ON
OFF
25
Page 26
NOTE : During high pressure protection and for 4 minutes and 15 seconds after high pressure protection, defrosting of
outdoor heat exchanger is not detected by the defrost thermistor RT61.
<MUH-A30WV>
During heating operation, the outdoor fan and the compressor are controlled by the temperature of indoor coil thermistor RT12 for excess rise protection of compressor discharge pressure.
• Outdoor fan When the temperature of indoor coil thermistor RT12 goes to 55: or more, the outdoor fan is turned OFF. When the temperature of indoor coil thermistor RT12 becomes to 52: or less, the outdoor fan is turned ON.
• Compressor When the temperature of indoor coil thermistor RT12 goes to 75: or more, the compressor is turned OFF. 3 minutes after the compressor is turned OFF and if the temperature of indoor coil thermistor RT12 becomes 75: or less,
the compressor is turned ON.
NOTE : During the high pressure protection and for 10 seconds after high pressure protection, defrosting of outdoor heat
exchanger is not detected by the defrost thermistor RT61.
3. Discharge temperature protection <MUH-A30WV>
Discharge temperature protection is as same as during COOL mode of “I FEEL CONTROL”.
4. Defrosting
Defrosting of outdoor heat exchanger is controlled by deicer P.C. board, with detection by the defrost thermistor RT61.
(1) Starting conditions of defrost
When all conditions of a) ~ c) are satisfied, the defrosting operation starts.
a) Under the heat operation, the compressor cumulative operation time exceeds 40 minutes without the defrosting opera-
tion working. b) The defrost thermistor RT61 reads -3°C or less. c) After releasing the high pressure protection 4 minutes and 15 seconds(MUH-18/24WV)/ 10 seconds(MUH-30WV) have
elapsed.
(2) Releasing conditions of defrost
When the condition d) or e) is satisfied, the defrosting operation stops.
d) The defrost thermistor RT61 reads 3°C(MUH-18/24WV)/ 13°C(MUH-30WV) or more. e) The defrosting time exceeds 10 minutes.
(3) Defrosting time chart Defrost thermistor RT61
13: or more
3: or more
-3: or less Outdoor 52C
contactor(Compressor)
X62 (R.V. coil)
SR61 Outdoor fan
Defrost counter
Indoor fan
Indoor vane
(MUH-A30WV)
(MUH-A18/A24WV)
ON OFF
ON OFF
ON OFF
ON OFF
ON Very Low OFF
Horizontal
Set position
30 sec.
NOTE
15 sec.
30 sec.
5 sec.
Max 10 min.
NOTE: • When the indoor coil thermistor RT12 reads above 18°C, indoor fan operates at Very Low for 30 seconds.
• When the indoor coil thermistor RT12 reads 18°C or less, the indoor fan stops. 26
Page 27
5. R.V. coil control
Controlled range
Basic specification
Minimum : 54 pulse, Maximum : 500 pulse
Drive speed
30 ~ 90 pulse / second
Opening set
The setting is always in opening direction. (To close the LEV, it is closed to the pulse smaller than the one which is set finally. Then the LEV is opened to the final setting pulse.)
Stop of indoor unit
Opening in stop : 150 pulse LEV opening is set to becomes 500 pulse after 3 minutes passed.
Remote controller ON
LEV positioning (LEV is closed completely at once)
Power ON (Breaker ON)
LEV is positioned. However, afterwards, LEV is not positioned at the first remote controller ON.
Approximate for 2 minutes since compressor has started.
Opening is set by the initial opening. (Initial opening is set according to each operation modes and outer temperature conditions.)
From approximate 2 minutes to approximate 13 minutes (for 11 minutes) since compressor has started.
Opening is set by standard opening. (Standard opening is set according to each operation modes and outer temperature conditions.)
After 13 minutes passed since compressor has started.
LEV opening is corrected to be once every 2 minutes so that discharge temperature becomes the target discharge temperature. (When the discharge temperature is lower than target one : LEV is corrected in closed direction, when the discharge temperature is higher than target one : LEV is corrected in opening direction.)
At thermostat OFF
Opening in stop : 150 pulse LEV is set to the initial opening after about 3 minutes passed.
At thermostat ON
Same as the starting of compressor operation
At remote controller OFF
Opening in stop : 150 pulse LEV is set so that the opening is opened completely at the speed of 4 pulse every 5 seconds in opening after about 3 minutes passed.
General operation
Heating · · · · · ON Cooling · · · · · OFF Dry · · · · · · · · OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
(COOL / DRY)
5 sec.
Compressor
ON OFF
R.V. coil
ON OFF
ON
Outdoor fan
OFF
9-2. LEV control <MUH-A30WV>
LEV (Expansion valve) is controlled by “Thermostat ON” commands given from the unit.
(HEAT)
5 sec.
ON OFF
ON OFF
ON OFF
27
Page 28
Ta (:)
more than Tb+10 Tb+5 to Tb+10 Tb+2 to Tb+5 Tb-2 to Tb+2 Tb-5 to Tb-2 Tb-10 to Tb-5 less than Tb-10
less than 2:
20 10
2 0
-2
-5
-10
NOTE : Discharge temperature : Ta, Target discharge temperature : Tb
3: or more
60 20
2 0
-2
-5
-10
RT
2: or more and less than 3:
60 20
2 0
-2
-5
-10
Tb (:) HEAT COOL (Normal) COOL ( RT is less than 2:, or RT is 2:or more and less than 3:.) COOL ( RT is 3 :or more.)
NOTE : Target discharge temperature : Tb
85 80 70 65
Operation mode
(1) LEV opening correction by discharge temperature
Rank
Ta (:) more than Tb+10 Tb+5 to Tb+10 Tb+2 to Tb+5 Tb-2 to Tb+2 Tb-5 to Tb-2 Tb-10 to Tb-5 less than Tb-10
100 pulse or less
Cooling / Heating
5 2 1 0
-1
-2
-5
NOTE : Discharge temperature : Ta, Target discharge temperature : Tb
100 pulse or more
Cooling / Heating
20 10
2 0
-2
-5
-10
Opening immediately before having stopped last time
The LEV opening is corrected according to the temperature difference between target discharge temperature (Tb) and actual discharge temperature (Ta).
1 The LEV correction is used properly for two kinds according to the LEV opening status at operation off.
2 When the temperature difference RT between indoor coil thermistor (main) RT12 and indoor coil thermistor (sub)
RT13 in the indoor unit is 2: or more for a fixed time at cool or dry operation, the target discharge temperature is changed. After the temperature is changed, when temperature difference RT is 3: or more, the target temperature
is changed again. The LEV opening is controlled based on the changed target discharge temperature and the temper­ature difference RT.
The target discharge temperature (Tb) is set according to the operation mode or the unit status as follows.
NOTE : When the discharge temperature (Ta) is 50: or less on the cool operation, or is 49: or less on heat operation,
LEV opening is set in 54 pulse. When this state continues for 20 minutes, the compressor is stopped and restarts in 3 minutes. When the compressor is stopped, the indoor unit indicates the abnormality of refrigerant system and stops. (OPERATION INDICATOR lamp is 10-time flashing on and off.)
28
Page 29
(2) LEV time chart
E1
Jumper wire
JRF
JRG
Model Change point
Defrost interval time changes from 40 minutes to 15 minutes. Defrost start temperature changes from -3: to 0:. (MUH-A18WV)
Defrost start temperature does not change.(-3.0:)(MUH-A24/A30WV) Defrost finish temperature changes from 3: to 10:.(MUH-A18WV)
Defrost finish temperature changes from 3: to 15:.(MUH-A24WV) Defrost finish temperature changes from 13: to 15:.(MUH-A30WV)
E1
E1
MUH-A18WV ­MUH-A24WV ­MUH-A30WV -
Lead wiring
Housing point
Power ON
Open
LEV opening
Close
Opening completely
Initial opening
Positioning
Remote controller ON
Standard opening
Operation
Thermostat OFF
Opening in stop
Standard opening
Thermostat ON
Initial opening
Operation
Remote controller OFF
Opening completely
Opening in stop
Remote
controller ON
Positioning
Operation
Standard opening
Initial opening
NOTE : Opening increases and decreases to be in the target discharge temperature during operation.
10
MUH-A18WV - MUH-A24WV - MUH-A30WV -
SERVICE FUNCTIONS
E1E1E1
10-1. COMPULSORY DEFROSTING MODE FOR SERVICE
By short circuit of the connector JPDS and JPSG(MUH-A18WV)/ JPG1 and R871(MUH-A24/A30WV) on the outdoor deicer
P.C. board, defrosting mode can be accomplished regardless of the defrost interval restriction. (Refer to page 37 or 38.)
Defrost thermistor RT61 must read below -3°C.
10-2. CHANGE IN DEFROST SETTING
<JRF> When the JRF wire of the deicer P.C. board is cut, the defrost interval time will be changed. <JRG> When the JRG wire of the deicer P.C. board is cut, the defrost temperature will be changed.
(Refer to page 37 or 38.)
Time
11
MUH-A18WV - MUH-A24WV - MUH-A30WV -
11-1. Cautions on troubleshooting
TROUBLESHOOTING
E1E1E1
1. Before troubleshooting, check the following:
(1) Check the power supply voltage. (2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
(1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then after
confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
(2) Be sure to turn OFF the power supply before removing the front panel, the
cabinet, the top panel, and the electronic control P.C. board.
(3) When removing the electronic control P.C. board, hold the edge of the
board with care NOT to apply stress on the components.
(4) When connecting or disconnecting the connectors, hold the housing of the
connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
(1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work. (2) Before servicing check that the connector and terminal are connected properly. (3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discolouration. (4) When troubleshooting, refer to the flow chart on page 30.
29
Page 30
Start
Indoor unit operates. Outdoor unit doesn't operate.
Indoor unit doesn't receive the signal from remote controller.
Indoor unit operates. Outdoor unit doesn't operate normally.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Outdoor unit operates in only Test Run operation.
Outdoor unit doesn't operate even in Test Run operation.
Indoor unit operates, when the EMERGENCY OPERATION switch is pressed.
Indoor unit doesn't operate, when the EMERGENCY OPERATION switch is pressed.
Check room temperature thermistor. Refer to "Test point diagram and voltage".
Refer to A "Check of outdoor unit" on page 32 or
33.
Refer to "Check of remote controller and receiver P.C. board".
Flash on and off at 0.5­second intervals Cause: Indoor/ Outdoor unit
• Mis-wiring
Refer to D "How to check mis-wiring (When outdoor unit doesn't work)" on page 35.
2-time flash Cause: Indoor unit
• Trouble of room temp­ erature/ indoor coil thermistor
3-time flash Cause: Indoor unit
• Trouble of indoor fan motor
Check room temperature thermistor and indoor coil thermis­tor. Refer to "Test point diagram and voltage".
Refer to "Check of indoor fan motor".
4-time flash Cause: Indoor unit
• Trouble of indoor unit control system
Replace the indoor electronic control P.C. board.
1. Check indoor / outdoor connecting wire.
2. Refer to "Check of indoor electronic control P.C. board".
Outdoor unit doesn't stop even if indoor unit stops.
Unit doesn't operate normal operation in COOL or HEAT mode.
Refer to B "Check of outdoor unit" on page 34.
Refer to C "Check of R.V. coil" on page 34 or 35.
As for indoor unit, refer to service manual OB321.
6-time flash Cause: Outdoor unit
• Trouble of thermistor in outdoor unit
7-time flash Cause: Outdoor unit
• Trouble of outdoor control system
Refer to F "Check of outdoor thermistor"
on page 36.
Replace the deicer P.C. board.
10-time flash Cause: Outdoor unit
MUH-A30WV
• Trouble of low discharge temperature protection
MUH-A30WV
Refer to E "Check of LEV" on page 36.
30
Page 31
11-2. Trouble criterion of main parts
Part name FigureCheck method and criterion
Measure the resistance between the terminals with a tester. (Part temperature –10˚C ~ 40˚C)
Compressor (MC) INNER PROTECTOR 160i 5: OPEN 90i10: CLOSE
Normal
MUH-A18WV
Terminal
C – R
C – S
1.59 " ~ 1.95 "
2.65 " ~ 3.24 "
MUH-A24WV
0.71 " ~ 0.87 "
1.45 " ~ 1.77 "
MUH-A30WV
0.56 " ~ 0.71 "
1.43 " ~ 1.76 "
Abnormal
Open or
short-circuit
R.V. coil(21S4)
LEV(Expansion valve)
MUH-A30WV
Measure the resistance between the terminals with a tester. (Part temperature –10˚C ~ 40˚C)
Normal
2.673 k" ~ 3.268 k"
Abnormal
Open or short-circuit
Color of lead wire
WHT – RED RED – ORN
YLW – BRN BRN – BLU
Abnormal
Open or
short-circuit
Normal
30.3 " ~ 37.0 "
Measure the resistance with a tester. (Part temperature : –10˚C ~ 40˚C)
Measure the resistance with a tester. (Part temperature –10˚C ~ 40˚C)
Discharge temperature thermistor(RT62)
MUH-A30WV
Ambient temperature thermistor(RT63)
MUH-A30WV
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up. (Part temperature 0˚C ~ 40˚C)
Normal
120 k" ~ 800k"
Abnormal
Open or short-circuit
Normal
5 k" ~ 60 k"
Abnormal
Open or short-circuit
Measure the resistance with a tester. (Part temperature –10˚C ~ 40˚C)
Normal
5 k" ~ 60 k"
Abnormal
Open or short-circuit
Defrost thermistor (RT61)
w Reference value
MUH-A18WV MUH-A24WV MUH-A30WV
Measure the resistance between the terminals with a tester. (Part temperature –10˚C ~ 40˚C)
Color of
lead wire WHT – BLK BLK – RED BLK – YLW
YLW – RED
Open or
short-circuit
102 " ~ 126 "
97 " ~ 120 "
– –
55 " ~ 68 "
– 26 " ~ 33 " 55 " ~ 68 "
55.4 " ~ 67.7 " –
49.3 " ~ 60.3 "
22.9 " ~ 28.0 "
Normal
Abnormal
Outdoor fan motor(MF)
MUH-A18/A24WV
INNER PROTECTOR 145i 8: OPEN ( 88i15: CLOSE
w
)
MUH-A30WV
INNER PROTECTOR 135i 5: OPEN ( 83i15: CLOSE
w
)
REDORN WHT
YLW
BLK
MAIN
AUX.1AUX.2
C
P
P
~
BLK
R
MAIN
AUX
RED
S
C
WHT
MAIN
AUX
BLK
MUH-A18WV
MUH-A24WV
MUH-A30WV
RED
WHTORN
P
P
C
RED
ORN WHT
YLW
BLK
MAIN
AUX.1 AUX.2
LEV
WHT
6
RED1 ORN4
YLW5
BRN2
BLU3
:INNER PROTECTOR
P
MUH-A18WV - MUH-A24WV - MUH-A30WV -
E1E1E1
31
Page 32
Compressor and/or outdoor fan motor doesn’t operate.
Yes
Compressor doesn't operate.
Yes
Yes
Is there 230V AC between 3 on the compressor contactor (52C) and N on the outdoor terminal block (TB1)?
Operate the unit in COOL or HEAT mode by pressing the EMERGENCY OPERATION switch. 3-minute time delay works. Test run operation operates for 30 minutes.
Outdoor fan motor doesn't operate.
No
Rectify the indoor and outdoor connecting wire.
Rectify the connecting wire.
Check the compressor and compressor capacitor. Refer to page 31.
Yes
Is there 230V AC between 4 on the compressor contactor (52C) and TAB20 on the deicer P.C. board?
Is there 230V AC between LN on the outdoor terminal block (TB1)?
Replace the deicer P.C. board.
Replace the deicer P.C. board.
No
No
Yes
Yes
No
Check the outdoor fan motor. Refer to page 31.
Is there 230V AC between 4 on the compressor contactor (52C) and TAB 20 on the deicer P.C. board?
Replace the deicer P.C. board.
No
Yes
Rectify the indoor and outdoor connecting wire.
Rectify the connecting wire.
Is there 230V AC between LN on the outdoor terminal block (TB1)?
No
No
+
Is there 5V DC between J205 –J101 on the deicer P.C. board?
+
Is there 5V DC between J205 –J101 on the deicer P.C. board?
w Refer to page 37.
w
w
w
w
AA
Check of outdoor unit
MUH-A18WV
32
Page 33
Is there 230V AC to between
L-N on the
outdoor terminal block
?
No
Check the outdoor power supply and connection of wiring.
Yes
Compressor does not operate.
Yes
3minutes after the power supply turns ON, is there 230V AC between A1-A2 on the compressor contactor (52C)?
Operate the unit in COOL or HEAT mode by pressing the EMERGENCY OPERATION switch.
Outdoor fan motor does not operate.
No
Rectify the connecting wire.
Rectify the connecting wire.
Rectify the connecting wire.
Check the compressor. Refer to page 31.
Replace the compressor contactor(52C).
Turn ON the power supply.
Yes
Is there 230V AC between 2/T1 on the compressor contactor(52C) and N on the outdoor terminal block?
Yes
Replace the deicer P.C. board.
Replace the deicer P.C. board.
No
Yes
No
Is there 230V AC between 1/L1 on the compressor contactor(52C) and N on the outdoor terminal block?
No
No
Yes
Yes
Yes
Is there 230V AC between CN711 2-3 (MUH-A24WV)/ CN711 1-3 or 2-3 (MUH-A30WV) on the deicer P.C. board? w
Operate the unit in COOL or HEAT mode by pressing the EMERGENCY OPERATION switch.
No
Check the outdoor fan motor. Refer to page 31.
Yes
Is there 230V AC CN730 1-3 on the deicer P.C. board? w
Replace the deicer P.C. board.
Replace the deicer P.C. board.
No
No
Is there 5V DC between J101 - J401 on the deicer P.C. board? w
Is there 230V AC between CN730 1-3 on the deicer P.C. board? w
+
Is there 5V DC between J101 - J401 on the deicer P.C. board? w
+
w Refer to page 38.
MUH-A24WV MUH-A30WV
33
Page 34
Compressor and/or outdoor fan motor doesn’t stop.
BB
Check of outdoor unit
MUH-A18WV
Turn OFF the power supply. After 1 minute, turn ON power supply again.
Is there 230V AC between 3 on the
Does compressor stop?
Yes
OK
No
compressor contactor (52C) and N on the outdoor terminal block (TB1)?
Replace the deicer P.C. board.
Yes
No
Rectify the connecting wire.
Does outdoor fan motor stop?
Yes
OK
No
MUH-A24WV MUH-A30WV
1 Turn OFF the power supply. 2 After 30 seconds, turn ON the power supply again. 3 Operate the unit in COOL or HEAT mode by
pressing the EMERGENCY OPERATION switch. 4 Operate the unit for 1 minute or more and stop it by pressing the EMERGENCY OPERATION switch again.
After 30 seconds, does compressor stop?
Yes
Ok
After 30 seconds, does outdoor fan motor stop?
Yes
Ok
Replace the deicer P.C. board.
Is there 230V AC between
No
A1-A2 on the compressor contactor (52C)?
Replace the deicer P.C. board.
No
Replace the deicer P.C. board.
Yes
Is there 230V AC between
No
2/T1 on the compressor contactor (52C) and N on the
outdoor terminal block?
Replace the compressor contactor(52C).
Yes
No
Rectify the connecting wire.
Unit operates COOL mode even if it is set to HEAT mode.
Check of R.V. coil
C
w First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
Disconnect the TAB52 on the deicer P.C. board. Turn ON the power supply and operate the indoor unit in HEAT mode by pressing the EMERGENCY OPERATION switch.
After 3 minutes, is there 230V AC between CN721 1-3 on the deicer P.C. board?
Yes
Replace the R.V. coil.
No
Replace the deicer P.C. board.
34
Page 35
Unit operates HEAT mode even if it is set to COOL mode.
After 3 minutes, is there 230V AC between CN721 1-3 on the deicer P.C. board?
Replace the deicer P.C. board.
Yes
No
Replace the R.V. coil.
Disconnect the TAB52 on the deicer P.C. board. Turn ON the power supply and operate the indoor unit in COOL mode by pressing the EMERGENCY OPERATION switch.
Check of R.V. coil
C
w First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second. Outdoor unit doesn’t operate.
How to check mis-wiring
D
Start
• Turn ON the power supply. (indoor/ outdoor unit)
• Press once EMERGENCY OPERATION switch.
w Short circuit of JPG and JPS on the indoor electronic control P.C. board enables self -check to be displayed in 3 seconds.
After 3 minutes, mis-wiring is indicated (0.5-second ON, 0.5-second OFF) on OPERATION INDICATOR lamp on indoor unit.w
Make them sure.
1. Turn OFF the power supply (indoor/ outdoor unit) and disconnect indoor/outdoor connecting wire on indoor side.
2. Short-circuit terminal block N-3 by lead wire.
Turn ON the power supply (indoor unit) and press once EMERGENCY OPERATION switch.
3.
Yes
Is this mis-wiring, poor contact, or wire disconnection?
Is there 20V DC between both ends of R132 on the indoor electronic control P.C. board ? ( By tester, the stylus is between 0 ~ 20V. )
• Turn OFF the power supply. (indoor unit)
• Connect ON indoor/outdoor connecting wire.
Turn ON the power supply. (outdoor unit)
Is there 230V AC between L-N on the outdoor terminal block?
Is there 5V DC between J205 + -J101 ­(MUH-A18WV)/J101 + -J401 - (MUH-A24/A30 WV) on the deicer P.C. board?(Refer to page 37 or 38.)
During EMERGENCY OPERATION, is there 10V DC between both ends of R601on the deicer P.C. board? (Refer to page 37or 38.) (By tester, the stylus is between 5 ~10V)
Replace the deicer P.C. board.
No
Yes
Yes
Yes
Yes
35
No
Replace the indoor electronic control P.C. board.
No
Check the outdoor power supply and connection of wiring.
No
Replace the deicer P.C. board.
Make the wiring between CN730
No
on the deicer P.C. board and outdoor terminal block correct. (Refer to page 37 or 38.)
As for indoor unit, refer to service manual OB321.
Page 36
Replace the LEV coil.
With remote controller set toward the indoor unit, press OPERATE/ STOP(ON/ OFF) button and confirm one beep tone.
LEV operates in full-opening direction.
Is LEV coil properly fixed to the body?
Ok
Do you hear LEV "click, click·······"? Do you touch LEV and feel it vibrate?
Does the resistance of LEV coil have the characterictics?
No
Yes
Yes
Yes
No
LEV (CN724)
WHT–RED
RED–ORN YLW–BRN BRN–BLU
Resistance
30.3 " ~ 37.0 "
Characteristics of LEV coil
No
Properly fix LEV coil to the body.
Replace the deicer P.C. board.
NOTE : After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply of the unit and turn ON again.
2. Press the RESET button on the remote controller.
1 During pressing OPERATION SELECT button
on remote controller, press RESET button.
2 First, release RESET button.
(Confirm all displays of remote controller.)
3 Then release OPERATION SELECT button.
1 During pressing OPERATION SELECT
button on remote controller, press
RESET button.
2 First, release RESET button.
(Confirm all displays of remote controller.) 3 Then release OPERATION SELECT button.
AMPM
CLOCK
˚C
AMPM
When OPERATION INDICATOR lamp flashes 10-time. Heating/ Cooling doesn't operate.
Check of LEV (Expansion valve)
E
MUH-A30WV
When OPERATION INDICATOR lamp flashes 6-time. Thermistors in the outdoor unit are abnormal.
F
Check of outdoor thermistor
w Disconnect the connectors CN661 and/ or CN662 from the deicer P.C. board.
(Check the characteristics of each thermistor.)
Defrost thermistor(RT61)
Measure resistance between CN 661 1 and 2.
<MUH-A30WV>
Discharge temperature thermistor(RT62)
Turn OFF the power supply.
Measure resistance between CN 662 1 and 2.
<MUH-A30WV>
Ambient temperature thermistor(RT63)
Measure resistance between CN 662 3 and 4.
Does the resistancs of thermistor have the characteristics on page 37 or 38?
No
Replace the thermistor.
36
Yes
Connect CN661 and CN662. Turn ON the power supply and press the EMERGENCY OPERATION switch.
W It is thought defective contact of the connector.
Replace the deicer P.C.
board.
No
Does the unit operate 10 minutes or more?
Yes
Ok W.
Page 37
MUH-A18WV -
E1
Outdoor deicer P.C. board
CN711 Outdoor fan motor
230V AC
}
CN721 R.V. coil
230V AC
}
5V DC J205 J101
+
--
(Refer to page 32 or 35.)
Power supply input
230V AC
}
NR61 Varistor
F61 Fuse
2A/250V
R601
+
5~10V DC
}
--
Defrost interval time short pin (JPDS, JPSG) (Refer to page 29.)
Jumper wire for
}
change in defrost setting (JRF,JRG)
}
CN661 1-2 Defrost thermistor RT61 (Refer to page 36.)
(Refer to page 29.)
12V DC J204
+
J101
--
37
Page 38
MUH-A24WV -
Temperature(:)
Discharge temperature thermistor(RT62)
Resistance(k")
0 102030405060708090100110120
0
100
200
300
400
500
600
700
800
900
Defrost thermistor (RT61)
Ambient temperature thermistor (RT63)
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature(:)
Resistance(k")
MUH-A30WV -
E1
E1
Outdoor deicer P.C. board
CN661 1-2 Defrost ther­mistor (RT61) (Refer to page 36.)
Defrost
interval time short pin(JPG1, R871)
(Refer to
page 29.)
(Refer to page 33
or 35.)
+
J101
}
5V
DC
J401
<MUH-A30WV> CN662 1-2
Discharge temper­ature thermistor (RT62) (Refer to page 36.)
Jumper wire for change in defrost setting (JRF, JRG) (Refer to page 29.)
CN662 3-4 <MUH-A30WV> Ambient temperature thermistor (RT63) (Refer to page 36.)
38
<MUH-A30WV> LEV connector (CN724)
R601 10V DC (Refer to page 35.)
Fan motor connector (CN711)
+
}
Varistor (NR62)
R.V. coil
}
(CN721)
+
12V DC
}
Fuse
3.15A / 250V Varistor
(NR61)
CN7301-3
}
230V AC
(Refer to page 33 or
35.)
Page 39
12
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector is a terminal
with lock mechanism
1Slide the sleeve. 2Pull the terminal while
pushing the locking lever.
1Hold the sleeve, and pull out the terminal slowly.
In case of terminal with lock mechanism, detach the terminal as shown below. There are two types ( Refer to (1) and (2)) of the terminal with lock mechanism. The terminal with no lock mechanism can be removed by pulling it out. Check the shape of the terminal and work.
<"Terminal with lock mechanism" Detaching points>
Connector
Sleeve
Locking lever
DISASSEMBLY INSTRUCTIONS
12-1. MUH-A18WV -
E1
OUTDOOR UNIT
OPERATING PROCEDURE
1. Removing the cabinet
(1) Remove the screws of the cabinet. (2) Hold the down of the cabinet on the both side and remove
the cabinet.
Photo 2
Screws of
the cabinet
PHOTOS
Photo 1
Screws of the cabinet
Service panel
2. Removing the deicer P.C. board
(1) Remove the service panel and the cabinet. (2) Disconnect all the connectors and the terminals on the
deicer P.C. board.
(3) Remove the deicer P.C. board.
Photo 3
Screw of the relay panel
Deicer P.C. board
39
Relay panel
Terminal blocks
Screw of the relay panel
Page 40
OPERATING PROCEDURE
3. Removing the propeller and the outdoor fan motor
(1) Remove the cabinet. (Refer to 1.) (2) Remove the propeller nut and the propeller.
NOTE : Loose the propeller in the rotating direction for
removal.
When attaching the propeller, align the mark on the propeller and the motor shaft cut section. Set the propeller fan in position by using the cut on the shaft and the mark on the propeller.
(3) Remove the clamp of outdoor fan motor lead wire and
disconnect the outdoor fan motor connector. (4) Remove the screws fixing the outdoor fan motor. (5) Remove the outdoor fan motor.
Photo 4
Propeller
PHOTOS
Set screws of the outdoor fan motor
Lead clamps
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1.) (2) Remove the relay panel. (3) Remove the soundproof felt. (4) Remove the terminal cover on the compressor. (5) Disconnect lead wires from the compressor. (6) Recover gas from the refrigerant circuit. (7) Disconnect the welded part of the discharge pipe. (8) Disconnect the welded part of the suction pipe. (9) Remove nuts fixing the compressor.
)
(
Remove the compressor.
10
NOTE
Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm
Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat.
2
(0 MPa).
Propeller nut
Photo 5
Compressor
Set screws of the outdoor fan motor
Discharge pipe
Terminal cover
Outdoor fan motor
Suction pipe
40
Compressor set nuts
Page 41
12-2. MUH-A24WV - MUH-A30WV -
OUTDOOR UNIT
E1E1
NOTE : These photos are MUH-A30WV.
MUH-A24WV is almost the same as MUH-A30WV.
OPERATING PROCEDURE
1.Removing the cabinet
(1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover. (7) Remove the screws of the front panel. (8) Remove the front panel. (9) Remove the screws of the back panel.
(10)
Remove the back panel.
Photo 3
Screw of the motor support
Photo 1
Screws of the cabinet
Photo 2
PHOTOS
Screw of the top panel
Screws of the cabinet
Screw of the service panel
Screws of the back panel
Set screws of the back panel
2. Removing the deicer P.C. board
(1) Remove the service panel and the cabinet. (2) Disconnect all the connectors and the terminals on the
deicer P.C. board.
(3) Remove the deicer P.C. board.
Screws of the front panel
Photo 4
Deicer P.C. board
Screws of the top panel
Screw of the valve cover
Terminal
blocks
41
Screws of the relay panel
Screws of the relay panel
Page 42
OPERATING PROCEDURE
PHOTOS
3. Removing the propeller and the outdoor fan motor
(1) Remove the cabinet. (Refer to 1.) (2) Remove the propeller nut and the propeller.
NOTE : Loose the propeller in the rotating direction for
removal.
When attaching the propeller, align the mark on the propeller and the motor shaft cut section. Set the propeller fan in position by using the cut on the shaft and the mark on the propeller.
(3) Remove the clamp of outdoor fan motor lead wire and
disconnect the outdoor fan motor connector. (4) Remove the screws fixing the outdoor fan motor. (5) Remove the outdoor fan motor.
Photo 5
Set screws of the outdoor fan motor
Propeller
nut
Propeller
Set screws of the outdoor fan motor
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1.) (2) Remove the relay panel. (3) Remove the soundproof felt. (4) Remove the terminal cover on the compressor. (5) Disconnect lead wires from the compressor. (6) Recover gas from the refrigerant circuit. (7) Disconnect the welded part of the discharge pipe. (8) Disconnect the welded part of the suction pipe. (9) Remove nuts fixing the compressor.
)
(
Remove the compressor.
10
NOTE
Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm
Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat.
2
(0 MPa).
Photo 6
Discharge pipe
Suction pipe
Terminal cover
Compressor set nuts
42
Page 43
13
Symbol
in Wiring
Diagram
Q'ty/unit
MUH-A18WV-
Remarks
Part No. Part Name
E1
E02 817 233 E02 817 232 E02 817 521 E02 643 630 E02 141 501 E02 139 515 E02 075 506 E02 817 900 E02 817 290 E02 817 661 E02 820 662 E02 817 245 E02 679 961 E02 817 353 E02 144 301 E02 466 383 E02 820 451 E02 817 374 E02 821 374 E02 820 310 E02 817 009 E02 139 936 E02 340 936 E02 414 936 E02 820 936 E02 095 382 E02 821 490 E02 154 642 E02 820 385
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21
22
23 24 25 26
BACK PANEL CABINET GRILLE OUTDOOR HEAT EXCHANGER PROPELLER MOTOR SUPPORT COMPRESSOR RUBBER SET COMPRESSOR BASE STOP VALVE(GAS) STOP VALVE(LIQUID) SERVICE PANEL 4-WAY VALVE COMPRESSOR CAPACITOR OUTDOOR FAN MOTOR SURGE ABSORBER DEICER P.C. BOARD TERMINAL BLOCK TERMINAL BLOCK DEFROST THERMISTOR HANDLE CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE FUSE R.V. COIL CHECK VALVE VARISTOR
MC
C1
MF
DSAR
TB1 TB2
RT61
F61
21S4
NR61
3RUBBERS/SET RN196VHSHT
{12.7 { 6.35
40+/440V AC RA6V50 -
3P 2P
{3.0{1.6750 {3.0{1.6450 {3.0{1.6300 {2.5{0.61000
250V / 2A
NO.
1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1
PARTS LIST
MUH-A18WV -
E1
13-1. OUTDOOR UNIT STRUCTURAL PARTS,
ELECTRICAL PARTS AND FUNCTIONAL PARTS
21
1
2
DEFROST THERMISTOR
20
15
14
19
18
17
16
13
12
11
Part numbers that are circled are not shown in the illustration.
4
653
43
7
10
8
9
Page 44
MUH-A24WV -
E1
13-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS
AND FUNCTIONAL PARTS
24252627
1
2
3 4
5
6
7
8
23
22
21
20 19
18
17
9
10
11
12
16
1513 14
44
Page 45
MUH-A24WV -
E1
13-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS
AND FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.
Q'ty/unit
MUH-A24WV -
1 1 1 1 1 1 1 1 1 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NO.
Part No.
E02 819 297
1
E02 821 630
2
E02 821 301
3
E02 214 501
4
E02 821 290
5
E02 819 232
6
E02 819 009
7
E02 819 521
8
E02 679 961
9
E02 821 490
10
E02 821 310
11
E02 527 506
12
E02 821 900
13
E02 819 661
14
E02 821 662
15
E02 819 650
16
E02 819 245
17
E02 128 383
18
E02 821 374
19
E02 817 374
20
E02 138 351
21
E02 821 451
22
E07 012 340
23
E02 818 353
24
E02 819 233
25
E02 817 009
26
E02 726 515
27
E02 127 382
28
E02 336 385
29
E02 154 642
30
E02 625 936
31
E02 010 936
Part Name
TOP PANEL OUTDOOR HEAT EXCHANGER OUTDOOR FAN MOTOR PROPELLER BASE CABINET HANDLE FAN GUARD 4-WAY VALVE R.V. COIL DEFROST THERMISTOR COMPRESSOR RUBBER SET COMPRESSOR STOP VALVE(GAS) STOP VALVE(LIQUID) VALVE COVER SERVICE PANEL SURGE ABSORBER TERMINAL BLOCK TERMINAL BLOCK OUTDOOR FAN CAPACITOR DEICER P.C. BOARD COMPRESSOR CONTACTOR COMPRESSOR CAPACITOR BACK PANEL(OUT) HANDLE MOTOR SUPPORT FUSE VARISTOR CHECK VALVE CAPILLARY TUBE CAPILLARY TUBE
Symbol
in Wiring
Diagram
MF
21S4
RT61
MC
DSAR
TB2 TB1
C2
52C
C1
F61
NR61
E1
Remarks
RA6V85-
4RUBBERS/SET NN29VBAHT
{15.88 {6.35
2P 3P
3.0+/440V AC
55+/440V AC
250V/3.15A
{3.0x{2.0x550 {3.0x{2.0x650
45
Page 46
MUH-A30WV -
E1
13-3. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS
AND FUNCTIONAL PARTS
25262728
1
2 3 4 5
6
7
8 9
24
23
22
21 20
19
2
18
10
11
12
13
17
1614 15
46
Page 47
MUH-A30WV -
E1
13-3. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS
AND FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.
Q'ty/unit
MUH-A30WV -
1 1 1 1 1 1 1 1 1 1 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NO.
Part No.
E02 819 297
1
E02 819 309
2
E02 822 630
3
E02 819 301
4
E02 214 501
5
E02 819 290
6
E02 819 232
7
E02 819 009
8
E02 819 521
9
E02 679 961
10
E02 821 490
11
E02 821 310
12
E02 527 506
13
E02 819 900
14
E02 819 661
15
E02 822 662
16
E02 819 650
17
E02 819 245
18
E02 128 383
19
E02 821 374
20
E02 817 374
21
E02 064 351
22
E02 822 451
23
E02 819 340
24
E02 819 353
25
E02 819 233
26
E02 817 009
27
E02 726 515
28
E02 819 640
29
E02 819 493
30
E02 127 382
31
E02 336 385
32
E02 214 386
33
E02 822 936
34
Part Name
TOP PANEL THERMISTOR OUTDOOR HEAT EXCHANGER OUTDOOR FAN MOTOR PROPELLER BASE CABINET HANDLE FAN GUARD 4-WAY VALVE R.V. COIL DEFROST THERMISTOR COMPRESSOR RUBBER SET COMPRESSOR STOP VALVE(GAS) STOP VALVE(LIQUID) VALVE COVER SERVICE PANEL SURGE ABSORBER TERMINAL BLOCK TERMINAL BLOCK OUTDOOR FAN CAPACITOR DEICER P.C. BOARD COMPRESSOR CONTACTOR COMPRESSOR CAPACITOR BACK PANEL(OUT) HANDLE MOTOR SUPPORT EXPANSION VALVE EXPANSION VALVE COIL FUSE VARISTOR CZ SURGE ABSORBER CAPILLARY TUBE(TAPER PIPE)
Symbol
in Wiring
Diagram
RT62, RT63
MF
21S4
RT61
MC
DSAR
TB2 TB1
C2
52C
C1
LEV F61
NR61
CZ
E1
Remarks
DISCHARGE, AMBIENT
RA6V75-
4RUBBERS/SET NN37VAAHT
{15.88 {9.52
2P 3P
4.0+/440V AC
60+/440V AC
250V/3.15A
{3.6x{2.4x50
47
Page 48
MUH-A18WV ­MUH-A24WV ­MUH-A30WV -
E1
E1
E1
13-4. ACCESSORY
1
2
NO.
Part No.
1
E02 817 704 E02 444 705
2
E02 444 706
Part Name
DRAIN SOCKET DRAIN CAP DRAIN CAP
Symbol
in Wiring
Diagram
Q'ty/unit
MUH-A18WV-E1MUH-A24WV-E1MUH-A30WV-
E1
1 2
1 2
1 2
1
Remarks
[33 [16
HEAD OFFICE: MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
CC
Copyright 2003 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Nov. 2003. No.OB322 6 Made in Japan
New publication, effective Nov. 2003 Specifications subject to change without notice.
Loading...